Field Loss Light Illuminated In order to help us provide you with quality support please have the following information available when you call AB Drives Technical Support. Drives Catalog/Bulletin number (Normally found on the inside of the front cover door) Fuses 4F and 5F checked for blown condition Measured field voltage and field current Motor nameplate information: Field Voltage, Field Current, and Field resistance if given. Measured Field resistance of the motor. NOTE: A motor problem is indicated if the measured field resistance is very high or very low. Field Resistance = Field Voltage/ (Field Current X 1.39) Motor field connections (F1, F2, F3 , and F4) series or parallel.

Additional Hints: Terminal 1 on the Main Control Board is the field loss input. The minimum dc voltage at terminal with respect to terminal 24, common, is 0.9 volts dc. If this voltage is not present then either there is no field current flow or Field Loss board is not operating. If the voltage is present but the field loss is still indicated then the Main Control Board should be replaced.

`cdmpc>wms>a_jj
Thyristor Over temperature Light Illuminated In order to help us provide you with quality support please have the following information available when you call AB Drives Technical Support. Drives Catalog/Bulletin number (Normally found on the inside of the front cover door)

Additional Hints: Two thermistors, 1Therm and 2Therm, are mounted on the armature scr heatsink assemblies. The leads from the thermistors are connected to the main control board on terminals 33 and 34 for 1Therm and terminals 35 and 36 for 2Therm. The normal resistance of the thermistors is 50 K ohms at 25o C and decreases to 2603 ohms at 100o C. If the Thyristor Over temperature fault occurs intermittently a simple test would be to replace the two thermistors with 47K ohm, 2 watt resistors across terminals 33-34 and terminals 35-36. If the fault clears and does not reoccur then the thermistors should be replaced. If the problem persists then the Main control board should be replaced.

Part Description Main Control Potentiometer board Potentiometer board Relay board Field Loss Assembly Tach Feedback Board

Old Board Part Number New Board Part Number Kit Number 12M08-0007 102902 111741 12M08-0008 102903 104201 12M08-0005 12M08-00012 12M08-00017 102899 102906 102910 none 116184 116185 116183 102910

Field Bridge Rectifier

5P2-54

101020 101024

Obsolete see below 101024 103042 101665

Fan Control Transformer Fuse 8P01-0050 600 volt, 1 amp, KTK-R Field Fuse, 500V, 10 amp, KLM-10 Fault Relay Fault Relay Retaining Clip Plug in Relays Retaining Clip Capacitor, 4MFD Control Transformer Surge Suppressors 6P1-00090 6P99-00015 6P1-00016 6P99-0004 8P01-146

103042 101665

101751

101751

101184 101472

101184 101472

101215 101474 100778 100840 101063

101215 101474 100778 100840 101063

105 Amp Module Line Fuses Armature SCR 101749 101110

250 Amp Module 101750 163181

345 Amp Module 101756 163182