Tail end >>>> To Source End (Radial System)

Enter Data in White Background Cells

:IDMT Over Current Relay Grad


D 160 Amp 2000 Amp 3000 Amp 100 1 Normal Inverse (NI) 200% 0.100 Sec 7.5% 10.0% 0.05 Sec 0.17 Sec 0.33 Sec 0.58 Sec 0.25 Sec

Trail end Last Bus Bar Load Current (IL) Min Fault Current Max Fault Current CT Ratio (Amp) for Relay-D Curve Selection for Relay-D Plug Setting of Relay-D TMS of Relay-D Relay Error (%) CT Error (%) Over shoot C.B Interrupting Time Safety Total Time Grading: Expected Operaion Time of Relay-D O/L Relay Setting for Section: D Operating Time of Relay D at Max Fault at D Over Load Current : Over Load Current :(In) Required Over Current Relay Plug Setting Actual Plug Setting of Over Current Relay (PMS): (I>) Plug Setting Multiplier (PSM): Time Multiplier Setting: (TMS) Time of Operation of Relay Actual Operaion Time of Relay D: (t>) Time Grading: Required Operaiting Time of Relay D at Max Fault at Bus-D Operating Time of Relay D at Min Fault at D Over Current Setting (PMS): Plug Setting Multiplier (PSM): Time Multiplier Setting Time of Operation of Relay Actual Operaion Time of Relay Operating Time of Downsteam Relay Time Grading: Actual Operaion Time of Relay D at Min Fault at Bus-D

125% 200 2 2 15 0.1 2.52 0.25 0.58 0.83

X IL Amp
2 A X In 2 A X In

Sec Sec Sec Sec

2 10 0.1 2.97 0.30 0.1 0.575 0.8 OK 2 A X In 0.100 0.25 Sec Sec

:Results:
Pick Up Setting of Over Current Relay (I>): Pick Up Setting of Over Current Relay (I>): Time Multiplier Setting: (TMS) Expected Operaion Time of Relay:

DMT Over Current Relay Grading Calculation (50/51):


Bus Bar Location Load Current Min Fault Current Max Fault Current CT Ratio (Amp) for Relay-C Curve Selection for Relay-C Plug Setting of Relay-C TMS of Relay-C Relay Error (%) CT Error (%) Over shoot C.B Interrupting Time Safety Total Time Grading: Expected Operaion Time of Relay-C O/L Relay Setting for Section: C-D Primary Protection for C-D Operating Time of Relay C at Max Fault at D Over Load Current : Over Load Current :(In) Required Over Current Relay Plug Setting Actual Plug Setting of Over Current Relay (PMS): (I>) Plug Setting Multiplier (PSM): Time Multiplier Setting: (TMS) Time of Operation of Relay Actual Operaion Time of Relay C: (t>) Time Grading: Required Operaiting Time of Relay D at Max Fault at Bus-C Backup Protection for DOperation Time of Relay C at Min Fault at D Over Current Setting (PMS): Plug Setting Multiplier (PSM): Time Multiplier Setting Time of Operation of Relay Actual Operaion Time of Relay Operating Time of Downsteam Relay Time Grading: Actual Operaion Time of Relay C at Min Fault at Bus-C C 200 Amp 3500 Amp 4000 Amp 300 1 Normal Inverse (NI) 100% 0.28 Sec 7.5% 10.0% 0.05 Sec 0.10 Sec 0.10 Sec 0.28 0.83 Sec

Jignesh.parmar, www.electricalnote

125% 250 0.83 1 10 0.28 2.97 0.83 0.28 1.10

X IL Amp
0.8 A X In 1 A X In

Sec Sec Sec Sec

1 6.67 0.28 3.62 1.01 0.10 0.28 0.38 OK 1 A X In 0.278 0.83 Sec Sec

:Results:
Pick Up Setting of Over Current Relay (I>): Relay Pick up Setting: (I>) Time Multiplier Setting: (TMS) Expected Operaion Time of Relay:

Jignesh.parmar, www.electricalnotes.wordpress.com, jiguparmar@yahoo.com

Bus Bar Location Load Current Min Fault Current Max Fault Current CT Ratio (Amp) for Relay-B Curve Selection for Relay-B Plug Setting of Relay-B TMS of Relay-B Relay Error (%) CT Error (%) Over shoot C.B Interrupting Time Safety Total Time Grading: Expected Operaion Time of Relay-B O/L Relay Setting for Section: B-C Primary Protection for B-C Operating Time of Relay B at Max Fault at C Over Load Current : Over Load Current :(In) Required Over Current Relay Plug Setting Actual Plug Setting of Over Current Relay (PMS): (I>) Plug Setting Multiplier (PSM): Time Multiplier Setting: (TMS) Time of Operation of Relay Actual Operaion Time of Relay B: (t>) Time Grading: Required Operaiting Time of Relay C at Max Fault at Bus-B Backup Protection for C-D Operation Time of Relay B at Min Fault at C Over Current Setting (PMS): Plug Setting Multiplier (PSM): Time Multiplier Setting Time of Operation of Relay Actual Operaion Time of Relay Operating Time of Downsteam Relay Time Grading: Actual Operaion Time of Relay B at Min Fault at Bus-B

B 200 Amp 3500 Amp 4000 Amp 300 1 Normal Inverse (NI) 100% 0.42 Sec 7.5% 10.0% 0.05 Sec 0.10 Sec 0.10 Sec 0.32 1.10 Sec

125% 250 0.83 1 13 0.418 2.63 1.10 0.32 1.42

X IL Amp
0.8 A X In 1 A X In

Sec Sec Sec Sec

1 11.67 0.42 2.78 1.16 0.28 0.32 0.60 OK 1 A X In 0.418 1.10 Sec Sec

:Results:
Pick Up Setting of Over Current Relay (I>): Relay Pick up Setting: (I>) Time Multiplier Setting: (TMS) Expected Operaion Time of Relay:

Bus Bar Location Load Current Min Fault Current Max Fault Current CT Ratio (Amp) for Relay-A Curve Selection for Relay-A Plug Setting of Relay-A TMS of Relay-A Relay Error (%) CT Error (%) Over shoot C.B Interrupting Time Safety Total Time Grading: Expected Operaion Time of Relay-A O/L Relay Setting for Section: A-B Primary Protection for A-B Operating Time of Relay A at Max Fault at B Over Load Current : Over Load Current :(In) Required Over Current Relay Plug Setting Actual Plug Setting of Over Current Relay (PMS): (I>) Plug Setting Multiplier (PSM): Time Multiplier Setting: (TMS) Time of Operation of Relay Actual Operaion Time of Relay A: (t>) Time Grading: Required Operaiting Time of Relay B at Max Fault at Bus-A Backup Protection for B-C Operation Time of Relay A at Min Fault at B Over Current Setting (PMS): Plug Setting Multiplier (PSM): Time Multiplier Setting Time of Operation of Relay Actual Operaion Time of Relay Operating Time of Downsteam Relay Time Grading: Actual Operaion Time of Relay A at Min Fault at Bus-A

A 200 Amp 3500 Amp 4000 Amp 300 1 Normal Inverse (NI) 100% 0.54 Sec 7.5% 10.0% 0.05 Sec 0.10 Sec 0.10 Sec 0.35 1.42 Sec

125% 250 0.83 1 13 0.540 2.63 1.42 0.35 1.78

X IL Amp
0.8 A X In 1 A X In

Sec Sec Sec Sec

1 11.67 0.54 2.78 1.50 0.42 0.35 0.77 OK 1 A X In 0.540 1.42 Sec Sec

:Results:
Pick Up Setting of Over Current Relay (I>): Relay Pick up Setting: (I>) Time Multiplier Setting: (TMS) Expected Operaion Time of Relay:

Bus Bar Location Load Current Min Fault Current Max Fault Current CT Ratio (Amp) for Relay-E Curve Selection for Relay-E Plug Setting of Relay-E TMS of Relay-E Relay Error (%) CT Error (%) Over shoot C.B Interrupting Time Safety Total Time Grading: Expected Operaion Time of Relay-E O/L Relay Setting for Section: E-A Primary Protection for E-A Operating Time of Relay E at Max Fault at A Over Load Current : Over Load Current :(In) Required Over Current Relay Plug Setting Actual Plug Setting of Over Current Relay (PMS): (I>) Plug Setting Multiplier (PSM): Time Multiplier Setting: (TMS) Time of Operation of Relay Actual Operaion Time of Relay E: (t>) Time Grading: Required Operaiting Time of Relay A at Max Fault at Bus-E Backup Protection for A-B Operation Time of Relay E at Min Fault at A Over Current Setting (PMS): Plug Setting Multiplier (PSM): Time Multiplier Setting Time of Operation of Relay Actual Operaion Time of Relay Operating Time of Downsteam Relay Time Grading: Actual Operaion Time of Relay E at Min Fault at Bus-E

E 200 Amp 3500 Amp 4000 Amp 300 1 Normal Inverse (NI) 100% 0.67 Sec 7.5% 10.0% 0.05 Sec 0.10 Sec 0.10 Sec 0.38 1.78 Sec

125% 250 0.83 1 13 0.674 2.63 1.78 0.38 2.16

X IL Amp
0.8 A X In 1 A X In

Sec Sec Sec Sec

1 11.67 0.67 2.78 1.87 0.54 0.38 0.92 OK 1 A X In 0.674 1.78 Sec Sec

:Results:
Pick Up Setting of Over Current Relay (I>): Relay Pick up Setting: (I>) Time Multiplier Setting: (TMS) Expected Operaion Time of Relay: