Trail end Last Bus Bar Load Current (IL) Min Fault Current Max Fault Current CT Ratio (Amp) for Relay-D Curve Selection for Relay-D Plug Setting of Relay-D TMS of Relay-D Relay Error (%) CT Error (%) Over shoot C.B Interrupting Time Safety Total Time Grading: Expected Operaion Time of Relay-D O/L Relay Setting for Section: D Operating Time of Relay D at Max Fault at D Over Load Current : Over Load Current :(In) Required Over Current Relay Plug Setting Actual Plug Setting of Over Current Relay (PMS): (I>) Plug Setting Multiplier (PSM): Time Multiplier Setting: (TMS) Time of Operation of Relay Actual Operaion Time of Relay D: (t>) Time Grading: Required Operaiting Time of Relay D at Max Fault at Bus-D Operating Time of Relay D at Min Fault at D Over Current Setting (PMS): Plug Setting Multiplier (PSM): Time Multiplier Setting Time of Operation of Relay Actual Operaion Time of Relay Operating Time of Downsteam Relay Time Grading: Actual Operaion Time of Relay D at Min Fault at Bus-D
X IL Amp
2 A X In 2 A X In
2 10 0.1 2.97 0.30 0.1 0.575 0.8 OK 2 A X In 0.100 0.25 Sec Sec
:Results:
Pick Up Setting of Over Current Relay (I>): Pick Up Setting of Over Current Relay (I>): Time Multiplier Setting: (TMS) Expected Operaion Time of Relay:
Jignesh.parmar, www.electricalnote
X IL Amp
0.8 A X In 1 A X In
1 6.67 0.28 3.62 1.01 0.10 0.28 0.38 OK 1 A X In 0.278 0.83 Sec Sec
:Results:
Pick Up Setting of Over Current Relay (I>): Relay Pick up Setting: (I>) Time Multiplier Setting: (TMS) Expected Operaion Time of Relay:
Bus Bar Location Load Current Min Fault Current Max Fault Current CT Ratio (Amp) for Relay-B Curve Selection for Relay-B Plug Setting of Relay-B TMS of Relay-B Relay Error (%) CT Error (%) Over shoot C.B Interrupting Time Safety Total Time Grading: Expected Operaion Time of Relay-B O/L Relay Setting for Section: B-C Primary Protection for B-C Operating Time of Relay B at Max Fault at C Over Load Current : Over Load Current :(In) Required Over Current Relay Plug Setting Actual Plug Setting of Over Current Relay (PMS): (I>) Plug Setting Multiplier (PSM): Time Multiplier Setting: (TMS) Time of Operation of Relay Actual Operaion Time of Relay B: (t>) Time Grading: Required Operaiting Time of Relay C at Max Fault at Bus-B Backup Protection for C-D Operation Time of Relay B at Min Fault at C Over Current Setting (PMS): Plug Setting Multiplier (PSM): Time Multiplier Setting Time of Operation of Relay Actual Operaion Time of Relay Operating Time of Downsteam Relay Time Grading: Actual Operaion Time of Relay B at Min Fault at Bus-B
B 200 Amp 3500 Amp 4000 Amp 300 1 Normal Inverse (NI) 100% 0.42 Sec 7.5% 10.0% 0.05 Sec 0.10 Sec 0.10 Sec 0.32 1.10 Sec
X IL Amp
0.8 A X In 1 A X In
1 11.67 0.42 2.78 1.16 0.28 0.32 0.60 OK 1 A X In 0.418 1.10 Sec Sec
:Results:
Pick Up Setting of Over Current Relay (I>): Relay Pick up Setting: (I>) Time Multiplier Setting: (TMS) Expected Operaion Time of Relay:
Bus Bar Location Load Current Min Fault Current Max Fault Current CT Ratio (Amp) for Relay-A Curve Selection for Relay-A Plug Setting of Relay-A TMS of Relay-A Relay Error (%) CT Error (%) Over shoot C.B Interrupting Time Safety Total Time Grading: Expected Operaion Time of Relay-A O/L Relay Setting for Section: A-B Primary Protection for A-B Operating Time of Relay A at Max Fault at B Over Load Current : Over Load Current :(In) Required Over Current Relay Plug Setting Actual Plug Setting of Over Current Relay (PMS): (I>) Plug Setting Multiplier (PSM): Time Multiplier Setting: (TMS) Time of Operation of Relay Actual Operaion Time of Relay A: (t>) Time Grading: Required Operaiting Time of Relay B at Max Fault at Bus-A Backup Protection for B-C Operation Time of Relay A at Min Fault at B Over Current Setting (PMS): Plug Setting Multiplier (PSM): Time Multiplier Setting Time of Operation of Relay Actual Operaion Time of Relay Operating Time of Downsteam Relay Time Grading: Actual Operaion Time of Relay A at Min Fault at Bus-A
A 200 Amp 3500 Amp 4000 Amp 300 1 Normal Inverse (NI) 100% 0.54 Sec 7.5% 10.0% 0.05 Sec 0.10 Sec 0.10 Sec 0.35 1.42 Sec
X IL Amp
0.8 A X In 1 A X In
1 11.67 0.54 2.78 1.50 0.42 0.35 0.77 OK 1 A X In 0.540 1.42 Sec Sec
:Results:
Pick Up Setting of Over Current Relay (I>): Relay Pick up Setting: (I>) Time Multiplier Setting: (TMS) Expected Operaion Time of Relay:
Bus Bar Location Load Current Min Fault Current Max Fault Current CT Ratio (Amp) for Relay-E Curve Selection for Relay-E Plug Setting of Relay-E TMS of Relay-E Relay Error (%) CT Error (%) Over shoot C.B Interrupting Time Safety Total Time Grading: Expected Operaion Time of Relay-E O/L Relay Setting for Section: E-A Primary Protection for E-A Operating Time of Relay E at Max Fault at A Over Load Current : Over Load Current :(In) Required Over Current Relay Plug Setting Actual Plug Setting of Over Current Relay (PMS): (I>) Plug Setting Multiplier (PSM): Time Multiplier Setting: (TMS) Time of Operation of Relay Actual Operaion Time of Relay E: (t>) Time Grading: Required Operaiting Time of Relay A at Max Fault at Bus-E Backup Protection for A-B Operation Time of Relay E at Min Fault at A Over Current Setting (PMS): Plug Setting Multiplier (PSM): Time Multiplier Setting Time of Operation of Relay Actual Operaion Time of Relay Operating Time of Downsteam Relay Time Grading: Actual Operaion Time of Relay E at Min Fault at Bus-E
E 200 Amp 3500 Amp 4000 Amp 300 1 Normal Inverse (NI) 100% 0.67 Sec 7.5% 10.0% 0.05 Sec 0.10 Sec 0.10 Sec 0.38 1.78 Sec
X IL Amp
0.8 A X In 1 A X In
1 11.67 0.67 2.78 1.87 0.54 0.38 0.92 OK 1 A X In 0.674 1.78 Sec Sec
:Results:
Pick Up Setting of Over Current Relay (I>): Relay Pick up Setting: (I>) Time Multiplier Setting: (TMS) Expected Operaion Time of Relay: