You are on page 1of 4

RTU560

Data Sheet Binary Input 23BE50






Doc.-No.: 1KGT 150 677 V001 1 1

Binary Input 23BE50


Application

The binary input board 23BE50 is used for the iso-
lated input of 64 process signals in 4 groups with
each up to 16 binary signals. Scanning and process-
ing of the inputs are executed with the high time
resolution of 1 ms.
Allocation of an input to a processing function can be
done according to the rules of configuration. The
board 23BE50 can process the following types of
signals:
64 single indications with time stamp
32 double indications with time stamp
8 step position information each with 8 bit
8/16 bit digital measured value(s)
8/16 bit string Information
64 pulse counters (max. 120Hz)

Characteristics
All inputs are potentially isolated by means of opto-
couplers. If a common return is necessary, it may be
realized by external short circuit connectors, which
are included in the delivery.
The input current of the inputs is typ. 1.5 mA.
The board has 64 light emitting diodes to indicate the
signal-state. The LEDs are organized in two col-
umns. The LEDs follows directly the input.

EAP
EEPROM
RAM
Mikro-
prozessor
ST
X1.1
GND
+24V
GND
TB
TA
X1.2
X1.3
X1.4
X1.5
X1.6
X2.1
X2.2
X2.3
X2.4
X2.5
X2.6
VCC
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
C1
X3.1
X3.2
X3.3
X3.4
X3.5
X3.6
X3.7
X3.8
X3.9
X3.10
X3.11
X3.12
X3.13
X3.14
X3.15
X3.16
X3.17
E12
E11
E10
E9
E8
E7
E6
E5
E4
E3
E2
E1
E13
E14
E13
E14
5V
E

Figure 1: Block diagram 23BE50
RTU560
Data Sheet Binary Input 23BE50



2 Doc.No.: 1KGT 150 677 V001 1
23 BE 50
X3.1
X3.2
X3.3
X3.4
X3.5
X3.6
I1
I2
I3
I4
I5
I6
X3.7
X3.8
X3.9
X3.10
X3.11
X3.12
I7
I8
I9
I10
I11
I12
X3.13
X3.14
X3.15
X3.16
X3.17
X3.18
I13
I14
I15
I17
C1
C2
X3.19
I18
I19
I20
I21
I22
I23
X3.20
X3.21
X3.22
X3.23
X3.24
X3.25
X3.26
X3.27
X3.28
X3.29
X3.30
X3.31
X3.32
X3.33
X3.34
X3.35
I24
I25
I26
I27
I28
I29
I30
I31
I32
I33
X3.36
X3.37
X3.38
X3.39
I34
I35
I36
I37
X3.40
X3.41
X3.42
X3.43
I38
X3.44
I39
I40
I41
I42
I43 X3.45
I44 X3.46
I45 X3.47
I46 X3.48
I47
X3.50
C3
X3.49
I48
X3.51
X3.52
X3.53 I49
X3.54 I50
X3.55 I51
X3.56 I52
X3.57 I53
I16
C4
X3.58
X3.59
X3.60
X3.61
I54
X3.62
I55
I56
I57
I58
X3.63
X3.64
X3.65
X3.66
X3.67
X3.68
I59
I60
I61
I62
I63
I64
+Up
-Up
-Up
+Up
+Up
-Up
-Up
+Up

Figure 2: Input block diagram 23BE50

The binary input board 23BE50 can execute the
following processing functions for the different types
of signals:
Digital filtering to suppress contact bounce
Suppression of technologically caused chat-
tering signals
Intermediate position suppression and mo-
nitoring for double indications
Consistency check for all binary input chan-
nels allocated to digital measured values

The 23BE50 has a buffer which allows the temporary
storage of 247 time-stamped event messages in
chronological order designated for transmission to
the communication unit.
The micro-controller on the board processes all time-
critical tasks of the parameterized processing func-
tions. Moreover it carries out the interactive commu-
nication with the RTU560 system bus. All configura-
tion data and processing parameters are loaded from
the communication unit via the RTU560 bus.
The board is equipped with a serial interface to the
RTU560 system bus.
During initialization and operation the board carries
out a number of tests. If a fault occurs it is reported
to the communication unit. All fault conditions impair-
ing the function of the board are displayed as com-
mon fault signal with a light emitting diode (ST). A
failure of the board is detected by the communication
unit.



















RTU560
Data Sheet Binary Input 23BE50



Doc.-No. 1KGT 150 677 V001 1 3

Technical Data
In addition to the RTU general technical data, the following applies:

Input Channels

Inputs 64, opto-coupler isolated
Input voltage 24V/48V/60V V DC
-20 % +15 %
log. 0: -3 V 9 V
log 1: 18 V 60 V
Input current Typ. 1,5 mA
Maximum Input Voltage
(IEC870-3)
-3V, max 1. Min.
120V, max 1 Min.

Power Supply
Supply 24 V DC 10 %
Current consumption Typ. 42 mA

Mechanical Layout
Housing for EN-Rail mounting
Color Housing green
Color top cover light gray
Dimension 186 x 126 x 61 mm
Weight 370 g without connectors

Connection Type
Process connector 8-pole pluggable screw-
terminal -Anytek
TJ 085153000G
0,34-2,5mm
9-pole pluggable screw-
terminal -Anytek
TJ 095153000G
0,34-2,5mm
(included in delivery)
Power supply and E-line
Serial peripheral bus

6-pole pluggable screw-
terminal -Anytek
TJ 085153000G
0,34-2,5mm
(included in delivery)

Insulation
Transient voltage ac-
cording to EN60255-5,
12/2001, chapter 6.1.3,
respectively EN60870-
2-1, 07/1997, chapter 6,
class VW3
5 kV DC,
1.2s/50s
Withstand voltage ac-
cording to EN60255-5,
12/2001, chapter 6.1.4,
respectively EN60870-
2-1, 07/1997, chapter 6,
class VW3
2,5 kV AC
50 Hz
Insulation resistance
according to EN60255-
5, 12/2001, chapter
6.2.2
>100 M
at 500 V DC

Electromagnetic Compatibility
Electrostatic discharge
immunity test according
EN61000-4-2, 12/2001,
(level 3)
6 kV Conducted
8 kV Air

Performance criteria A
Radiated radio-
frequency electromag-
netic field immunity test
according to
EN61000-4-3, 11/2003,
(level 3)
10 V/m

Performance criteria A
Electrical fast tran-
sient/burst immunity test
according to EN61000-4-
4, 07/2005 (level 3)
4 kV

Performance criteria A
Surge immunity test
according to EN61000-4-
5, 12/2001, (level 3)
2 kV (line to line)
4 kV (line to earth)
Performance criteria A
Immunity to conducted
disturbances, inducted
by radio-frequency fields
according to
EN61000-4-6, 12/2001
(level 3)
10 V

Performance criteria A
Oscillatory wave immu-
nity test according to
EN61000-4-12, 12/2001
(level 3)
2,5 kV (Common Mode)
1 kV (Differential Mode)

Performance criteria A
Test for immunity to
conducted, common
mode disturbances ac-
cording to EN61000-4-
16, 04/2005 (level 4)
0 Hz to 150 kHz
30 / 300 V

Performance criteria A
RTU560
Data Sheet Binary Input 23BE50



4 Doc.-No.: 1KGT 150 677 V001 1
Test for immunity to
voltage dips/short inter-
ruptions according to
EN61000-4-29, 10/2001
-100 %: 50 ms

Performance criteria A

Interference
Electromagnetic distur-
bance characteristics
according to EN55011,
08/2003
0.01 to 30 MHz
66 V

Class A
Electromagnetic distur-
bance characteristics
according to EN55011,
08/2003
30 MHz to 1 GHz
50 V/m

Class A

Safety
Information Technology
Equipment according to
EN60950-1, 03/2003
Over voltage category II,
pollution degree II, rein-
forced insulation

Mechanical Stress
Vibration tests (sinusoi-
dal) according to
IEC60255-21-1, 05/1996,
chapter 4.2, class 1
0.0350 mm
0.5 g at 10 150 Hz
Mechanical influences
(sinusoidal) according to
IEC60870-2-2, 06/1998,
chapter 4.2, class B
10 m/s
2
at 9 200 Hz
15 m/s
2
at 200..500 Hz
Vibration, shock, bump
and seismic tests accord-
ing to IEC60255-21-2,
05/1996, chapter 4.2,
class 1
15 g, 25 g / 11 ms
6 impulse / ordinate
10 g / 16 ms
1000 impulse / ordinate
Seismic test 3.5 mm / 1 g / 19 Hz
935 Hz

Environmental Conditions
Temperature -25 70 C
Relative humidity 5 95 %
(not condensing)

Ordering information
23BE50

1KGT 020 900 R 0001

Accessories
Power supply unit
560PSU40/41
For up to 8 units
Ordering information for
560PSU40
1KGT 011600 R0001
Ordering information for
560PSU41
1KGT 017700 R0001
Fiber optic coupler
560FOC40

Ordering information for
560FOC40
1KGT 011500 R0001






Note:
We reserve the right to make technical changes or modify the
contents of this document without prior notice. With regard to
purchase orders, the agreed particulars shall prevail. ABB AG
does not accept any responsibility whatsoever for potential er-
rors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
to third parties or utilization of its contents - in whole or in parts
- is forbidden without prior written consent of ABB AG.

Copyright2011 ABB
All rights reserved

You might also like