Transducer Test File # 15
Bus coupler Scheme & Alarm Test File # 16
Site Acceptance Test Report - Index
Battery Charge Acceptance Test
File # 6
File # 7
Index
Description Ref
Project & System Details
File # 12
Battery Capacity Test File # 10
Battery Recharge for Charge Acceptance Test
File # 14
Battery Final Recharging Test
Charger Alarm Test
File # 11
File # 13
File # 1
Charger Preliminary Checks
Startup Checks
Functional Checks
Parameter Checks
Battery Preliminary Checks
Battery Charging Test
Capacity Test
VCU Test
File # 2
File # 3
File # 4
File # 5
File # 8
File # 9
1
ADDC
STATRON
48 V 400 A
48 BDT
48 V 100 A
System Rating:
System Model:
System Year of Mfr:
System software version:
VCU Rating:
Client / End User:
AL NABBAGH VILLA COMPLEX
Consultant:
Contractor:
Sub Contractor:
Site Ref.:
Manufacturer:
Battery Charger Details:
DECCAN CONTRACTING
File # 1
Test date:
Site Acceptance Test Report - Project & System Details
Project Details:
System Ref.:
System Sl. No:
Contract Ref. No:
Project Ref.:
2
SAFT
48 V BATTERY #
44 End Volts : 1.05 V Per Cell
48 V Ah
Name Name Name
Organization STATRON Organization 0 Organization ADDC
Date 0 Date 0 Date 0
File # 1
Site Acceptance Test Report - Project & System Details
Battery Details:
Signature
Tested by Witnessed by Approved by
Manufacturer:
Battery Ref.:
Signature Signature
No. of Cells:
Battery Rating:
Battery Model:
Battery Year of Mfr:
3
Checked
(OK / Not OK)
1
2
3
4
5
6
7
8
Checked
(OK / Not OK)
1
2
3
4
5
6
7
8
9
Ensure that the installation is complete in all respects and is
as per Approved layout
Ensure that the system installed is as per Approved Sizing
calculations
Ensure that all the external cables are as per Approved
Sizing calculations
Ensure that the system installed is as per Approved Drawings
Ensure that the system installed is as per Specification
Ensure that the Approved equipment installation layout is
available
Sl No Comments (if any)
Installation Checks:
Ensure that the O&M Manual is available
Description of Check
Ensure that the Approved Sizing calculations of installed
system is available
Site Acceptance Test Report - Preliminary Checks
Sl No Comments (if any)
Documentation Checks:
Description of Check
Ensure that the system is installed in clean, dry and well
ventilated location
Ensure that the system installed in proper level
Ensure that the system installed is properly identified
Ensure that the ventilation canopies are properly fixed
File # 2
Ensure that the Approved Sizing calculations of external
cables is available
Ensure that the Approved Drawings of system is available
Ensure that the Specification of system is available
Ensure that the Factory acceptance test (FAT) is available
Ensure that the Approved Site acceptance test format (SAT)
is available
4
Checked
(OK / Not OK)
1
2
3
4
4
5
6
Checked
(OK / Not OK)
1
2
3
4
5
6
7
8
9
Checked
(OK / Not OK)
1
2
3
Site Acceptance Test Report - Preliminary Checks
Safety Checks:
Visual Checks:
Sl No Comments (if any)
Sl No Comments (if any)
Description of Check
Ensure that all the required safety signs are installed
Ensure that all the cable terminations are tight and secured
Description of Check
Ensure that all the cable glands are earthed
Ensure that all the tools are of insulated type
Ensure that the system is not energized
Ensure that all the Switches / MCBs / Isolators inside the
system are OFF
Electrical Checks:
Ensure that there is no packing material / foreign objects in
the interior of the system
Ensure that all the cables / wires are properly identified
Ensure that all the internal components / parts are properly
identified
Ensure that all the cable glanding and dressing is
satisfactory
Ensure that all the terminals have group markers
Description of Check Sl No Comments (if any)
Ensure that all the external cables are tested for Insulation
resistance (Test report shall be attached)
Ensure all the cable terminations are of correct polarity /
sequence
Ensure that the upstream isolator / breaker is properly rated
at the input
File # 2
Ensure that all the terminals are segregated
Ensure that there are no Scratch marks on the system
external surface (Touch up if necessary)
Ensure that all the Doors and Locks are operational
Ensure that there is no damage to the internal components
Ensure that the system is earthed
5
Name Name Name
Organization STATRON Organization 0 Organization ADDC
Date 0 Date 0 Date 0
Site Acceptance Test Report - Preliminary Checks
Comments (if any)
*** End of test report ***
Tested by Witnessed by Approved by
Signature Signature Signature
File # 2
6
Checked
(OK / Not OK)
1
2
3
Frequency
RY YB BR RE YE BE ( Hz )
Checked
(OK / Not OK)
1
2
3
4
5
6
Make
Name Name Name
Organization STATRON Organization 0 Organization
Date 0 Date 0 Date
Start the system according to start-up instructions
List of Instruments used:
Comments (if any)
*** End of test report ***
Calibration due date
Comments (if any)
Comments (if any)
Site Acceptance Test Report - Startup Checks
Startup checks:
File # 3
Ensure that the input voltage and frequency is as per
nameplate
Ensure that the phase rotation is proper
Verify nameplate data of the system before startup
Ensure that the system operating (ambient) temperature is as
per specification
Record the Mains Voltage and Frequency at Input Terminals
(fill the below furnished table)
Description of Check Sl No
Input Voltage (V AC)
Sl No Description of Check
Signature Signature Signature
Tested by Witnessed by
Check for the Normal operation of the system
Check for the proper operation of fans
Check for the available modes of operation
Instrument Name
Digital Multi Meter
Digital Clamp Meter
Serial number
Approved by
ADDC
0
7
Objective:
Procedure:
Set @ Operating @
1 0
2 0
3 N.A N.A
4 2
Make
0
0
Name Name Name
Organization STATRON Organization 0 Organization
Date 0 Date 0 Date
Tested by Witnessed by
Comments (if any)
*** End of test report ***
Instrument Name
Digital Multi Meter
Digital Clamp Meter
Serial number
0
0
0
Signature Signature Signature
Check Auto transfer from Manual
Boost Mode to Float Mode (Time
control)
Calibration due date
1. Apply dummy load in Battery path and verify the atomatic changeover from Float mode to Boost mode and
vice versa. Record the values in the table furnished below.
2. Put the charger in to Boost mode using push button provided (if any) and verify the atomatic changeover
from Boost mode to Float mode after the time set and record the values in the table furnished below.
Comments (if any)

List of Instruments used:
File # 4
Sl No.

Rectifier Functional Checks
Description of Check
Check Auto transfer from Float Mode
to Boost Mode
Check Auto transfer from Boost Mode
to Float Mode (Current control)
Check Manual transfer from Float
Mode to Boost Mode
Time (Min)/Current (A)
To verify Automatic changeover from Float mode to Boost mode and vice versa using Current control and Time
control
Site Acceptance Test Report - Functional Checks
0
0
Approved by
ADDC
8
Objective:
Procedure:
Sl. No. Settings Units
1 70.4 V dc
2 0 A dc
3 0 A dc
4 Current na
5 720 Min
6 10 Min
7 5 Min
8 480 Min
1 52.8 V dc
2 0 A dc
3 720 Min
720 Min
10 Min
File # 5
Parameter Description
Boost Voltage
Float to Boost Current
Boost to Float Current
Automatic Boost Operation control
Boost Safety Timer
Manual Boost Timer (Time control)
5 Min
Boost Delay after mains fail
Boost post timer (Current control)
Recommended values
480 Min
BOOST CHARGE DATA
1.20 0.01 VPC for SBL / SBLE
0.2 C5 A Max Battery Current Limit
Equalize Safety Timer
1.60 0.01 VPC for SBL / SBLE
0.16 C5 A
0.06 C5 A
Site Acceptance Test Report - Parameter Checks
Parameter Checks
To verify all parameters to suit site and system requirements as per specification
1. Navigate through the menu using keypad provided on the front panel of charger and verify each setting to
suit site and system requirements as per specification. Record the values in the table furnished below.
720 Min
MANUAL CHARGE DATA
Equalize Start Voltage
CURRENT
9
Sl. No. Settings Units
1 62.48 V dc
2 60.28 V dc
3 52.8 V dc
4 48.4 V dc
5 0 A dc
6 63.8 V dc
7 198 Sec
8 59.4 V dc
9 10 %
10 10 Min
1 47.175 Hz
2 50 Hz
3 52.825 Hz
4 460 V ac
5 400 V ac
6 340 V ac Low Voltage
Discharge level-3
Max Battery Current Limit
High Float Voltage
Factory default
Factory default
Factory default
Factory default
INPUT DATA
High Frequency
Nominal Frequency
Low Frequency
High Voltage
Nominal Voltage
Factory default
Factory default
Site Acceptance Test Report - Parameter Checks
BATTERY DATA
Parameter Description Recommended values
10%
10 Minutes
High Float delay
Low Float Voltage
High Float Current
Time High Float Current
1.42 0.01 VPC for SBL / SBLE
1.37 0.01 VPC for SBL / SBLE
1.20 0.01 VPC for SBL / SBLE
1.10 0.01 VPC for SBL / SBLE
0.2 C5 A
Alarm @ 1.45 0.01 VPC for SBL
/ SBLE
198 Sec
Alarm @ 1.35 0.01 VPC for SBL
/ SBLE
Float Voltage
Discharge level-1
Discharge level-2
File # 5
10
Sl. No. Settings Units
1 48 V dc
2 400 A dc
3 440 A dc
4 73.92 V dc
5 46.2 V dc
6 49.4 V dc
7 5 Sec
1 0 Ah
2 n.a
1 n.a
Make
0
0
Name Name Name
Organization STATRON Organization 0 Organization
Date 0 Date 0 Date
Battery Size (Capacity)
Battery Installation Date
Factory default
MM/YY
CLOCK SETTING DD/MM/YY-HH:MM
GENERAL
1.05 0.01 VPC for SBL / SBLE
5 Sec
Nominal voltage +3%
Maximum Output Voltage
Minimum Output Voltage
Emergency level
Maximum Output Voltage time delay
Factory default
Factory default
Factory default
1.68 0.01 VPC for SBL / SBLE
BATTERY INFO
Site Acceptance Test Report - Parameter Checks
OUTPUT DATA
Parameter Description Recommended values
Nominal Voltage
Nominal Current
Maximum Current
Approved by
ADDC
0
*** End of test report ***
Tested by Witnessed by
Signature Signature Signature
File # 5
Comments (if any)
List of Instruments used:
Instrument Name Serial number Calibration due date
Digital Multi Meter 0 0
Digital Clamp Meter 0 0
11
Objective:
Procedure:
Sl No.
1 48 V 100 A
2 50.4 V Maximum & 43.2 V Minimum
3
Stage-1 Stage-2 Stage-3 Comments (if any)
20 A
Stage-1 Stage-2 Stage-3 Total
File # 6
Remote Contacts
Site Acceptance Test Report - VCU Test
VCU Test
To verify the ability of VCU to control its input voltage to maintain output voltage in tolerance specified
1. Apply a minimum load equal to 20% of VCU rating at VCU Output
VCU Input Volts
VCU Output
Volts
2. Increase the input voltage of VCU from Nominal system voltage to battery boost level.
3. Decrease the input voltage of VCU from Battery boost level to nominal system voltage.
4. Record the values in the table furnished below.
. Stages
Check the VCU Rating
Check for the No. Of VCU Stages
Remarks Description of Requirement
Check the VCU Output tolerance limits
Case-1: VCU Input voltage manually increased from Nominal system voltage to Battery boost level
Check for the No. of Diodes used per stage 4
VCU Output
Max/ Min Volts
observed
Voltage Drop
Operation of VCU when loaded to 20% of VCU Rating
12
Case-2: Rectifier output voltage manually decreased from Battery boost level to Nominal system voltage
Stage-1 Stage-2 Stage-3 Total
Name Name Name
Organization Organization Organization ADDC
Date Date Date 0
Signature Signature
Tested by Witnessed by
List of Instruments used:
Comments (if any)
*** End of test report ***
Instrument Name
Digital Multi Meter
Digital Clamp Meter
Serial number
0
Remote Contacts
VCU Output
Volts
VCU Output
Max/ Min Volts
observed
Site Acceptance Test Report - VCU Test
0 0
0
Voltage Drop
0
0
Make Calibration due date
File # 6
VCU Input Volts
Approved by
Signature
STATRON 0
0 0
13
Calculated Measured Calculated Measured Calculated Measured
I I I I I I
(V) (V) (A) (Hz) (V) (A) (A) (mV) max (V) (A) (A) (V) (A) (A)
440 na 330 110
0 na 0 na na
4. Record the values in the table furnished below.
P/E I F
*** End of test report ***
List of Instruments used:
Comments (if any)
Site Acceptance Test Report - Capacity Test
Capacity Test
To verify the capacity of Charger, VCU and DCDB to meet the site requirements while maintaining the specified output voltage in tolerance specified
1. Apply dummy load in both Battery and Load path at different proportions from No load to Full Load. The system under test shall supply rated capacity without
damaging itself. Battery current limit shall be disabled during the test.
Load
Volts
Battery
Volts
0
25
50
75
Name
Organization
Date
Signature
Tested by
Date
0
100
200
300
400
Signature
Name
Organization
0
STATRON
0
75
150
AC I/P
2. Increase dummy load in both Battery and Load path >/= 110% and observe for the functioning of Rectifier total current limit. Further increase in load shall reduce the
rectifier output voltage. The Rectifier shall generate over load alarm in this situation. Battery current limit shall be disabled during the test.
3. Remove the dummy load from load path and with dummy load in Battery path >/= 110% , enable the Battery current limit and observe for the functioning of Battery
current limit. Further increase in load shall reduce the rectifier output voltage.
110
Note: Rectifier Current limit Function with Battery
Current limit Disabled
Note: Battery Current limit Function with Battery
Current limit enabled
300 100
Load % P/P
100
Volts Ripple
225 75
25
0
File # 7
Instrument Name
Digital Multi Meter
Digital Clamp Meter
Serial number
0
0
Make
0
0
Calibration due date
0
0
Objective:
Procedure:
Rectifier
50
Approved by
0
ADDC
Witnessed by
Signature
Name
Organization
Date 0
0
14
Checked
(OK / Not OK)
1
2
3
4
5
6
7
8
Checked
(OK / Not OK)
1
2
3
4
5
6
7
8
9
Ensure that the Battery installed is as per Approved Sizing
calculations
Ensure that all the external cables are as per Approved
Sizing calculations
Ensure that the Battery installed is as per Approved Drawings
Ensure that the Battery installed is as per Specification
Ensure that the Battery is installed in clean, dry and well
ventilated location
Ensure that the Battery installed in proper level
Ensure that the Battery and all individual cells installed is
properly identified
Ensure that the Exhaust fans are fixed in Battery room
Ensure that the installation is complete in all respects and is
as per Approved layout
Ensure that the Approved Drawings of Battery is available
Ensure that the Specification of Battery is available
Ensure that the Factory acceptance test (FAT) is available
Ensure that the Approved Site acceptance test format (SAT)
is available
Ensure that the O&M Manual is available
Installation Checks:
Sl No Description of Check Comments (if any)
Ensure that the Approved Sizing calculations of external
cables is available
File # 8
Site Acceptance Test Report - Battery Preliminary Checks
Documentation Checks:
Sl No Description of Check Comments (if any)
Ensure that the Approved equipment installation layout is
available
Ensure that the Approved Sizing calculations of installed
Battery is available
15
Checked
(OK / Not OK)
1
2
3
4
4
5
6
Checked
(OK / Not OK)
1
2
3
4
5
6
7
8
9
Checked
(OK / Not OK)
1
2
3
4
Ensure that all the external cables are tested for Insulation
resistance (Test report shall be attached)
Ensure all the cable terminations are of correct polarity /
sequence
Ensure that the upstream isolator / breaker is properly rated
at the input
Ensure that the Electrolyte level detector is installed properly
Sl No Description of Check Comments (if any)
Ensure that there are no Scratch marks on the Battery rack
external surface (Touch up if necessary)
Ensure that the Battery fuse box Doors and Locks are
operational
Ensure that there is no damage to cells of battery and
internal components of fuse box
Ensure that there is no packing material / foreign objects in
the Battery fuse box
Ensure that all the cables / wires are properly identified
Ensure that all the internal components / parts in Battery
fuse box are properly identified
Ensure that all the cable glanding and dressing is
satisfactory
Ensure that all the terminals have group markers
Ensure that all the terminals are segregated
Electrical Checks:
Visual Checks:
Sl No Description of Check Comments (if any)
Ensure that all the cable terminations are tight and secured
Safety Checks:
Sl No Description of Check Comments (if any)
Ensure that the Battery is not energized
Ensure that all the Switches / MCBs / Isolators related to
Battery are OFF
Ensure that the Battery Rack is earthed
Ensure that all the cable glands are earthed
Ensure that all the tools are of insulated type
Ensure that all the required safety signs are installed
File # 8
Site Acceptance Test Report - Battery Preliminary Checks
16
Name Name Name
Organization STATRON Organization 0 Organization ADDC
Date 0 Date 0 Date 0
Site Acceptance Test Report - Battery Preliminary Checks
Comments (if any)
*** End of test report ***
Tested by Witnessed by Approved by
Signature Signature Signature
File # 8
17
1
2
3
4
5
6
7
8
9
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
1 13 25 37
2 14 26 38
3 15 27 39
4 16 28 40
5 17 29 41
6 18 30 42
7 19 31 43
8 20 32 44
9 21 33
10 22 34
11 23 35
12 24 36
V
Ensure that the Open Circuit Voltage, specific gravity and electrolyte
temperature of all cells are recorded before charging
Ensure that the Open Circuit Voltage, specific gravity and electrolyte
temperature of all cells are recorded before charging
Ensure that all the cells are cleaned and all the connectors / busbars are
applied with anti corrosion compound
Ensure that the Charging voltage, Current and time set is as per battery
requirement
Ensure that the Open Circuit Voltage, specific gravity and electrolyte
temperature of all cells are recorded before charging
Ensure that all the cells are allowed to soak for minimum 4 hrs and maximum
24 hrs
Total Battery Bank Voltage
Ensure that all the cells are filled upto the middle of Maximum and Minimum
level marks
File # 9
Site Acceptance Test Report - Battery Charging Test
Battery Charging Checks
Description of Check
Checked
(OK / Not OK)
Comments (if any) Sl No
Battery initial readings before Charging:
Ensure that the electrolyte is being distributed among the cells in each block
Test Date
Ensure that all the cells are filled with electrolyte supplied by the
manufacturer only
18
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
11
12
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
21
22
23
24
Cell No. Volt Cell No. Volt
40
41
42
43
44
Cell No. Volt
1
Cell No. Volt
Battery Charging Readings:
13
14
15
16
17
18
Specific gravity
Ambient room
temperature
AM / PM Measurement Time
Charging Current 0
Electrolyte temperature
Parameter
Charging Voltage
Requirement
File # 9
Site Acceptance Test Report - Battery Charging Test
81.4
AM / PM
Parameter
Value Value
Reading Requirement Reading
Charging Started at
5
6
7
8
9
10
Charging Duration
10 Hours at
Constant
Current
1
19
20
2
3
4
19
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
File # 9
Site Acceptance Test Report - Battery Charging Test
Battery Charging Readings:
Charging Started at 0 AM / PM Measurement Time AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Charging Duration
10 Hours at
Constant
Current
2
Ambient room
temperature
Charging Voltage 81.4 Electrolyte temperature
Charging Current 0 Specific gravity
Volt Cell No. Volt
1 13 25 37
2
Cell No. Volt Cell No. Volt Cell No.
14 26 38
3 15 27 39
4 16 28 40
10 22 34
5 17 29 41
6 18 30 42
7 19 31 43
11 23 35
8 20 32 44
12 24 36
9 21 33
20
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
22 34
18 30 42
11 23 35
12 24 36
9 21 33
10
7 19 31 43
8 20 32 44
5 17 29 41
6
4 16 28 40
13 25 37
2 14 26 38
File # 9
Site Acceptance Test Report - Battery Charging Test
Charging Started at 0 AM / PM AM / PM Measurement Time
Battery Charging Readings:
Cell No. Volt
1
3 15 27 39
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
10 Hours at
Constant
Current
3
Ambient room
temperature
Charging Voltage 81.4 Electrolyte temperature
Charging Current 0 Specific gravity
Charging Duration
Cell No. Volt Cell No. Volt Cell No. Volt
21
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
11 23 35
12 24 36
9 21 33
10 22 34
7 19 31 43
8 20 32 44
5 17 29 41
6 18 30 42
4 16 28 40
13 25 37
2 14 26 38
Reading
Value
Cell No. Volt
1
3 15 27 39
File # 9
Site Acceptance Test Report - Battery Charging Test
Battery Charging Readings:
Charging Started at 0 AM / PM Measurement Time AM / PM
Parameter
Requirement Reading
Parameter
Requirement
Value
Charging Duration
10 Hours at
Constant
Current
4
Ambient room
temperature
Charging Voltage 81.4 Electrolyte temperature
Charging Current 0 Specific gravity
Cell No. Volt Cell No. Volt Cell No. Volt
22
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
11 23 35
12 24 36
9 21 33
10 22 34
7 19 31 43
8 20 32 44
5 17 29 41
6 18 30 42
28 40
13 25 37
2 14 26 38
Cell No. Volt
1
3 15 27 39
File # 9
Site Acceptance Test Report - Battery Charging Test
Battery Charging Readings:
Charging Started at 0 AM / PM Measurement Time AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Charging Duration
10 Hours at
Constant
Current
5
Ambient room
temperature
Charging Voltage 81.4 Electrolyte temperature
Charging Current 0 Specific gravity
Cell No. Volt Cell No. Volt Cell No. Volt
4 16
23
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
11 23 35
12 24 36
9 21 33
10 22 34
5 17 29 41
6 18 30 42
2 14 26 38
7 19 31 43
1
3 15 27 39
Charging Duration
10 Hours at
Constant
Current
6
Ambient room
temperature
Charging Voltage 81.4 Electrolyte temperature
Charging Current 0 Specific gravity
File # 9
Site Acceptance Test Report - Battery Charging Test
Battery Charging Readings:
Charging Started at 0 AM / PM Measurement Time AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Cell No.
4 16 28 40
8 20 32 44
Volt Cell No. Volt Cell No. Volt Cell No. Volt
13 25 37
24
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
11 23 35
12 24 36
9 21 33
10 22 34
7 19 31 43
8 20 32 44
5 17 29 41
6 18 30 42
28 40
13 25 37
2 14 26 38
File # 9
Site Acceptance Test Report - Battery Charging Test
Battery Charging Readings:
Charging Started at 0 AM / PM Measurement Time AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Charging Duration
10 Hours at
Constant
Current
7
Ambient room
temperature
3 15 27 39
4
Charging Voltage 81.4 Electrolyte temperature
Charging Current 0 Specific gravity
Cell No. Volt Cell No. Volt Cell No. Volt Cell No. Volt
1
16
25
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
11 23 35
12 24 36
9 21 33
10 22 34
7 19 31 43
8 20 32 44
5 17 29 41
6 18 30 42
3 15 27 39
4 16 28 40
2 14 26 38
Volt Cell No. Volt Cell No. Volt
Battery Charging Readings:
Charging Started at 0 AM / PM Measurement Time AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
0 Specific gravity
Cell No. Volt
1 13 25 37
File # 9
Site Acceptance Test Report - Battery Charging Test
Charging Voltage 81.4 Electrolyte temperature
Charging Current
Charging Duration
10 Hours at
Constant
Current
8
Ambient room
temperature
Cell No.
26
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
10 22 34
11 23 35
8 20 32 44
9 21 33
6 18 30 42
7 19 31 43
4 16 28 40
5 17 29 41
2 14 26 38
3 15 27 39
Cell No. Volt
1 13 25 37
Charging Current 0 Specific gravity
Charging Duration
10 Hours at
Constant
Current
9
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Charging Voltage 81.4 Electrolyte temperature
File # 9
Site Acceptance Test Report - Battery Charging Test
Battery Charging Readings:
Charging Started at 0 AM / PM Measurement Time AM / PM
27
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
10 22 34
11 23 35
8 20 32 44
9 21 33
6 18 30 42
7 19 31 43
4 16 28 40
5 17 29 41
2 14 26 38
3 15 27 39
Cell No. Volt
1 13 25 37
Charging Current 0 Specific gravity
Charging Duration
10 Hours at
Constant
Current
10
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Charging Voltage 81.4 Electrolyte temperature
File # 9
Site Acceptance Test Report - Battery Charging Test
Battery Charging Readings:
Charging Started at 0 AM / PM Measurement Time AM / PM
28
Date 0 Date 0 Date 0
List of Instruments used:
Comments (if any)
*** End of Test Report ***
Name Name Name
Organization STATRON Organization 0 Organization ADDC
Tested by Witnessed by Approved by
Signature Signature Signature
File # 9
Site Acceptance Test Report - Battery Charging Test
Calibration due date
0
0
Instrument Name Serial number Make
Digital Multi Meter 0 0
Digital Clamp Meter 0 0
29
Ah VPC
Hr V
1
2
3
4
5
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
1 13 25 37
2 14 26 38
3 15 27 39
4 16 28 40
5 17 29 41
6 18 30 42
7 19 31 43
8 20 32 44
9 21 33
10 22 34
11 23 35
12 24 36
V
46.2 Specified Duration 5 Specified Battery End voltage
Battery initial readings before Capacity Test:
Procedure:
The battery under test shall supply rated capacity and individual cell voltage at the end of discharge duration
specified, shall not be less than the specified.
Acceptance
Criteria:
0 Specified Capacity Specified End cell voltage 1.05
Test Date
Ensure that all the cells are properly charged
Ensure that the battery discharge current is maintained as per battery
manufacturer data sheet
Total Battery Bank Voltage
File # 10
Site Acceptance Test Report - Battery Capacity Test
Battery Capacity Test:
Sl No Description of Check
Checked
Comments (if any)
(OK / Not OK)
To verify the capacity of Battery rating while maintaining the specified voltage in tolerance specified
1. Apply dummy load in Battery path equal to the current to be maintained as per battery data sheet, as a minimum.
2. Closely monitor the discharge current with a clamp meter and make adjustments if necessary.
3. After completion of specified discharge duration, further extend the discharge until the end cell voltage reaches to
1.00V per cell. Remove the dummy load in Battery path.
4. Record the values in the table furnished below.
Objective:
Ensure that the Specific gravity and electrolyte temperature of pilot cell is
recorded for every hour of discharge
Ensure that the Open Circuit Voltage, specific gravity and electrolyte
temperature of all cells are recorded before capacity test
Ensure that the Voltage of all cells and Ambient temperature is recorded for
every hour of discharge
30
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
44
9 21 33
8 20 32
11 23 35
10 22 34
40
5 17 29 41
4 16 28
42
7 19 31 43
6 18 30
Volt
1 13 25 37
3 15 27 39
2 14 26
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
Discharge Current 0 Specific gravity
38
Cell No.
Discharge Duration 5 1
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 10
Site Acceptance Test Report - Battery Capacity Test
Battery Capacity test Readings:
Discharge Started at AM / PM Measurement Time
31
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
42
7 19 31 43
6 18 30
44
9 21 33
8 20 32
38
3 15 27 39
2 14 26
40
5 17 29 41
4 16 28
Discharge Duration 5 2
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt Cell No. Volt
1 13 25 37
Discharge Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Site Acceptance Test Report - Battery Capacity Test
Battery Capacity test Readings:
Discharge Started at 0 AM / PM Measurement Time
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
File # 10
32
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
44
9 21 33
8 20 32
11 23 35
10 22 34
40
5 17 29 41
4 16 28
42
7 19 31 43
6 18 30
1 13 25 37
Cell No. Volt
3 15 27 39
2 14 26 38
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
Discharge Current 0 Specific gravity
Value
Parameter
Requirement Reading
Parameter
Value
Discharge Duration 5 3
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Requirement
File # 10
Measurement Time AM / PM
Site Acceptance Test Report - Battery Capacity Test
Battery Capacity test Readings:
Discharge Started at 0 AM / PM
Reading
33
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
42
7 19 31 43
6 18 30
44
9 21 33
8 20 32
38
3 15 27 39
2 14 26
40
5 17 29 41
4 16 28
Discharge Duration 5 4
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt Cell No. Volt
1 13 25 37
Discharge Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Site Acceptance Test Report - Battery Capacity Test
Battery Capacity test Readings:
Discharge Started at 0 AM / PM Measurement Time
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
File # 10
34
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
44
9 21 33
8 20 32
11 23 35
10 22 34
40
5 17 29 41
4 16 28
42
7 19 31 43
6 18 30
1 13 25 37
Cell No. Volt
3 15 27 39
2 14 26 38
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
Discharge Current 0 Specific gravity
Value
Parameter
Requirement Reading
Parameter
Value
Discharge Duration 5 5
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Requirement
File # 10
Measurement Time AM / PM
Site Acceptance Test Report - Battery Capacity Test
Battery Capacity test Readings:
Discharge Started at 0 AM / PM
Reading
35
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
n.a
degree
Celsius
(Max)
A A 1.18 n.a n.a n.a
Hour Hour 20
degree
Celsius
(Max)
n.a
degree
Celsius
(Max)
Test Result:
Sl.No
1
2
Description of Requirement/Activity Comments (if any)
Check and record minimum cell voltage after 5 Hours battery capacity test
Result of Battery Capacity Test
12 24 36
44
9 21 33
8 20 32
11 23 35
10 22 34
40
5 17 29 41
4 16 28
42
7 19 31 43
6 18 30
Volt
1 13 25 37
3 15 27 39
2 14 26
Discharge Voltage
(Minimum)
44 Electrolyte temperature
Discharge Current n.a n.a Specific gravity
38
Cell No.
Discharge Duration n.a n.a
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 10
Site Acceptance Test Report - Battery Capacity Test
Battery Extended discharge Readings:
Discharge Started at n.a AM / PM Measurement Time n.a AM / PM
36
Name
*** End of Test Report ***
Date 0 Date 0 Date 0
Name Name
Organization STATRON Organization 0 Organization ADDC
Signature Signature
List of Instruments used:
Instrument Name Serial number Make Calibration due date
File # 10
Site Acceptance Test Report - Battery Capacity Test
0 0 0
Digital Clamp Meter 0 0 0
Digital Multi Meter
Signature
Comments (if any)
Tested by Witnessed by Approved by
37
1
2
3
4
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
1 13 25 37
2 14 26 38
3 15 27 39
4 16 28 40
5 17 29 41
6 18 30 42
7 19 31 43
8 20 32 44
9 21 33
10 22 34
11 23 35
12 24 36
V Total Battery Bank Voltage
Test Date
Battery initial readings before Recharging:
01.01.2012
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Checks
Sl No Description of Check
Checked
Comments (if any)
(OK / Not OK)
Ensure that the Voltage of all cells and Ambient temperature is recorded for
every hour of Re-Charge
Ensure that the Specific gravity and electrolyte temperature of pilot cell is
recorded for every hour of Re-Charge
Ensure that the charger is set in Boost Charge mode to recharge the battery
for Charge Acceptance Test
Ensure that the Open Circuit Voltage, specific gravity and electrolyte
temperature of all cells are recorded before Re-Charging
38
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 1
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at AM / PM Measurement Time
Recharging Voltage 70.4 Electrolyte temperature
39
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 2
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 70.4 Electrolyte temperature
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time
40
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 3
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 70.4 Electrolyte temperature
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time
41
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 4
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 70.4 Electrolyte temperature
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time
42
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 5
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 70.4 Electrolyte temperature
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time
43
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 6
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 70.4 Electrolyte temperature
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time
44
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 7
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 70.4 Electrolyte temperature
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time
45
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 8
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 70.4 Electrolyte temperature
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time
46
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 9
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 70.4 Electrolyte temperature
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time
47
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration 10 10
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 70.4 Electrolyte temperature
Recharging Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time
48
*** End of Test Report ***
Tested by Witnessed by Approved by
Signature Signature Signature
Digital Multi Meter
Date 01.01.2012 Date 01.01.2012 Date 01.01.2012
Organization STATRON Organization 0 Organization ADDC
Name Name Name
Digital Clamp Meter 0 0 0
File # 11
Site Acceptance Test Report - Battery Recharge for Charge Acceptance Test
List of Instruments used:
Instrument Name Serial number Make Calibration due date
Comments (if any)
0 0 0
49
Ah %
Ah VPC
4 Hr 30 Min V
1
2
3
4
5
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
1 13 25 37
2 14 26 38
3 15 27 39
4 16 28 40
5 17 29 41
6 18 30 42
7 19 31 43
8 20 32 44
9 21 33
10 22 34
11 23 35
12 24 36
V
Ensure that the Specific gravity and electrolyte temperature of pilot cell is
recorded for every hour of discharge
Battery initial readings before Capacity Test:
Total Battery Bank Voltage
Ensure that the Open Circuit Voltage, specific gravity and electrolyte
temperature of all cells are recorded before capacity test
Ensure that the Voltage of all cells and Ambient temperature is recorded for
every hour of discharge
Ensure that all the cells are properly charged
Ensure that the battery discharge current is maintained as per battery
manufacturer data sheet
Specified Battery End voltage 46.2
Sl No Description of Check
Checked
Comments (if any)
(OK / Not OK)
Specified Duration
3. After completion of specified discharge duration. Remove the dummy load in Battery path.
4. Record the values in the table furnished below.
Acceptance
Criteria:
The battery under test shall supply 90% of the rated capacity and individual cell voltage at the end of discharge
duration specified, shall not be less than specified.
Specified Capacity 0 Specified End cell voltage 1.05
Rated Capacity 0
Specified Capacity
Accumulation %
90
Battery Charge Acceptance Test:
Objective:
To verify the capacity accumulated in Battery in 10 hours with Boost charge, while maintaining the specified voltage in
Distribution within tolerance specified
Procedure: 1. Apply dummy load in Battery path equal to the current to be maintained as per battery data sheet, as a minimum.
2. Closely monitor the discharge current with a clamp meter and make adjustments if necessary.
File # 12
Site Acceptance Test Report - Battery Charge Acceptance Test
Test Date 01.01.2012
50
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Min Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Discharge Duration 4Hr 30 1
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
Discharge Current 0 Specific gravity
AM / PM
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
File # 12
Site Acceptance Test Report - Battery Charge Acceptance Test
Battery Charge Acceptance test Readings:
Discharge Started at AM / PM Measurement Time
51
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Min Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Discharge Duration 4Hr 30 2
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
Discharge Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Charge Acceptance test Readings:
Discharge Started at 0 AM / PM Measurement Time AM / PM
File # 12
Site Acceptance Test Report - Battery Charge Acceptance Test
52
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Min Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Discharge Duration 4Hr 30 3
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
Discharge Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Charge Acceptance test Readings:
Discharge Started at 0 AM / PM Measurement Time AM / PM
File # 12
Site Acceptance Test Report - Battery Charge Acceptance Test
53
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Min Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Discharge Duration 4Hr 30 4
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
Discharge Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Charge Acceptance test Readings:
Discharge Started at 0 AM / PM Measurement Time AM / PM
File # 12
Site Acceptance Test Report - Battery Charge Acceptance Test
54
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Min Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Discharge Duration 4Hr 30 5
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Discharge Voltage
(Minimum)
46.2 Electrolyte temperature
Discharge Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Charge Acceptance test Readings:
Discharge Started at 0 AM / PM Measurement Time AM / PM
File # 12
Site Acceptance Test Report - Battery Charge Acceptance Test
55
Test Result:
Sl.No
1
2
Name Name Name
Tested by Witnessed by Approved by
Signature Signature Signature
Date 01.01.2012 Date 01.01.2012 Date 01.01.2012
Organization STATRON Organization 0 Organization ADDC
Digital Clamp Meter 0 0 0
Comments (if any)
*** End of Test Report ***
Instrument Name Serial number Make Calibration due date
Digital Multi Meter 0 0 0
Result of Battery Charge acceptance Test
File # 12
Site Acceptance Test Report - Battery Charge Acceptance Test
List of Instruments used:
Description of Requirement/Activity Comments (if any)
Check and record minimum cell voltage after 4 Hour 30 Minutes battery charge acceptance
test
56
1
2
3
4
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
Cell
No.
Volt Sp.G Temp
1 13 25 37
2 14 26 38
3 15 27 39
4 16 28 40
5 17 29 41
6 18 30 42
7 19 31 43
8 20 32 44
9 21 33
10 22 34
11 23 35
12 24 36
V
Battery initial readings before Recharging:
Total Battery Bank Voltage
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
Test Date 01.01.2012
Ensure that the Voltage of all cells and Ambient temperature is recorded for
every hour of Re-Charge
Ensure that the Specific gravity and electrolyte temperature of pilot cell is
recorded for every hour of Re-Charge
Ensure that the Re-Charging voltage, Current and time set is as per battery
requirement
Ensure that the Open Circuit Voltage, specific gravity and electrolyte
temperature of all cells are recorded before Re-Charging
Battery Recharging Checks
Sl No Description of Check
Checked
Comments (if any)
(OK / Not OK)
57
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
1
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
58
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
2
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
59
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
3
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
60
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
4
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
61
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
5
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
62
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
6
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
63
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
7
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
64
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
8
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
65
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
9
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
66
Units Units Value Units Value Units
V V 45
degree
Celsius
(Max)
degree
Celsius
(Max)
A A 1.18 n.a n.a
Hour Hour 20
degree
Celsius
(Max)
degree
Celsius
(Max)
12 24 36
11 23 35
10 22 34
44
9 21 33
8 20 32
42
7 19 31 43
6 18 30
40
5 17 29 41
4 16 28
38
3 15 27 39
2 14 26
Cell No. Volt
1 13 25 37
Recharging Duration
10 Hours at
Constant
Current
10
Ambient room
temperature
Cell No. Volt Cell No. Volt Cell No. Volt
Recharging Voltage 81.4 Electrolyte temperature
Recharging Current 0 Specific gravity
Parameter
Requirement Reading
Parameter
Requirement Reading
Value Value
Battery Recharging Readings:
Recharging Started at 0 AM / PM Measurement Time AM / PM
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
67
1
2
3
Date 01.01.2012 Date 01.01.2012 Date 01.01.2012
Organization STATRON Organization 0 Organization ADDC
Name Name Name
Tested by Witnessed by Approved by
Signature Signature Signature
Digital Clamp Meter 0 0 0
Comments (if any)
*** End of Test Report ***
List of Instruments used:
Instrument Name Serial number Make Calibration due date
Digital Multi Meter 0 0 0
Ensure that all the cells are filled with cell oil as specified by OEM
Ensure that all the cells are cleaned and all the connectors / busbars are
applied with anti corrosion compound
Sl No Description of Check
Checked
Comments (if any)
(OK / Not OK)
Ensure that the settings of the charger is restored
File # 13
Site Acceptance Test Report - Battery Final Recharging Test
Battery Cell oil filling Checks
68
Test Date:
LED/Lamp Color
LED/Lamp
Indication
Text message in LCD
Red
LED on SLD at I/P,
Rect and Batt
A1: Mains Fault; Out of
Tolerance
Red Mains Failure
A8: Fans Failure alarm from
Fans Monitor Card
Red Charger Failure A11: Common alarm
Red Fans Failure A12: Charger failure
Red Common alarm
Red LED on SLD at Rect
A8: Fans Failure Alarm From
Fans Monitor Card
Red Charger Failure A11: Common alarm
Red Fans Failure A12: Charger failure
Red Common alarm
Red
LED on SLD at Rect
and Batt
A2: Blown Fuses, Blown
Fuses on Bridge 1
Red Charger Failure A11: Common alarm
Red Charger fuse blown A12: Charger failure
Red Common alarm A14: HRC Fuse blown
Red
LED on SLD at Rect
and Batt
A3: High Temperature, High
Temperature on Bridge 1
Red Charger Failure A11: Common alarm
Red Common alarm A12: Charger Failure
Red
LED on SLD at I/P,
RECT and BATT
A1: Mains Fault; Out of
Tolerance
Red Mains Failure
A8: Fans Failure Alarm From
Fans Monitor Card
Red Fans Failure
A9: Open C. Breaker RICB
Open
Red Charger Failure A11: Common alarm
Red Common alarm A12: Charger Failure
Red
LED on SLD at
Output
A9: Open C. Breaker ROCB
Open
Red Charger Failure A11: Common alarm
Red Charger fuse blown A12: Charger Failure
Red Common alarm A14: HRC Fuse blown
5
6
Rectifier output
fuse failure (F- 4 &
F-5 )
Input MCCB
failure (MCCB-
S1/Q1)
Local Indication
File # 14
4
High Temperature
on Bridge
Sl.No
Description /
Origin of Alarm
Remote
Contacts
Result
3
Bridge input fuse
Failure (F-1,F-2, F-3)
2
Fans Failure
(Rectifier & DC DB)
Site Acceptance Test Report - Alarm Test
Alarm Test
1 Mains Failure
69
LED/Lamp Color
LED/Lamp
Indication
Text message in LCD
Red LED on SLD at Rect
A4: Over Load, Rectifier
current > than nominal
current
Red Common alarm A11: Common alarm
Red
LED on SLD at Rect
and Batt
A5: Max Out voltage stop
for out volt > Than out put
Max Voltage
To be
tested by
decreasing
the default
setting
Red Charger Failure A11: Common alarm
Red High DC Voltage A12: Charger Failure
Tested at
.V
Red Common alarm
Red LED on SLD at Rect
A6: Min. Out voltage stop
for out volt < Than out put
Min. Voltage
To be
tested by
increasing
the default
setting
Red Charger Failure A11: Common alarm
Red Low DC Voltage A12: Charger Failure
Tested at
.V
Red Common alarm
Red LED on SLD at Rect
A7: Charging Fault Wrong
Floating High
To be
tested by
decreasing
the default
setting
Red Charger Failure A11: Common alarm
Red Common alarm A12: Charger Failure
Tested at
.V
Red LED on SLD at Rect
A7: Charging Fault Wrong
Floating Low
To be
tested by
increasing
the default
setting
Red Charger Failure A11: Common alarm
Red Common alarm A12: Charger Failure
Tested at
.V
Red
LED on SLD at
Battery
A9: Open C. Breaker BCB
Open
Red
Battery Fuse / BCB
Open
A11: Common alarm
Red Charger Failure A12: Charger Failure
Red Common alarm A14: HRC Fuse blown
13
Electrolyte Level
Low
Red
Electrolyte Level
Low (on DCDB front
panel)
N.A
9
Minimum output
voltage stop
Wrong Floating
Low
11
12
Battery Fuse Fail
(or) Isolator Switch
Open
10
Wrong Floating
High
7
Rectifier Over
Load
Sl.No
Description /
Origin of Alarm
Local Indication
Remote
Contacts
File # 14
Site Acceptance Test Report - Alarm Test
Result
8
Maximum output
voltage stop
70
LED/Lamp Color
LED/Lamp
Indication
Text message in LCD
14
Under voltage
Fault
Red
Distribution Voltage
Level Low
15 Over voltage Fault Red
Distribution Voltage
Level High
16 MCB Tripped Red
MCB Trip Distribution-
1
17 Earth Fault (+ve) Red Earth Fault (+ve)
18 Earth Fault (-ve) Red Earth Fault (-ve)
Make
0
0
Name Name Name
Organization STATRON Organization 0 Organization
Date 0 Date 0 Date
Instrument Name Serial number Calibration due date
Digital Multi Meter
Digital Clamp Meter 0
0 0
0
Signature Signature Signature
Site Acceptance Test Report - Alarm Test
ADDC
0
File # 14
Sl.No
Description /
Origin of Alarm
Local Indication
Remote
Contacts
Result
Comments (if any)
*** End of test report ***
Tested by Witnessed by Approved by
List of Instruments used:
71
%/min-max Value Calculated Measured
0 _ 80 V 43.2 12.64
4 _ 20 mA 48 13.60
1V = 0.2 mA 50.4 14.08
0 _ 80 V 43.2 12.64
4 _ 20 mA 48 13.60
1V = 0.2 mA 50.4 14.08
0 _ 100 A 0 4.0
4 _ 20 mA 100 A 50 12.0
1A = 0.16 mA 100 20.0
0 _ 100 A 0 4.0
4 _ 20 mA 100 A 50 12.0
1A = 0.16 mA 100 20.0
100 0 100 A 0 0.0
20 0 20 mA 100 A 50 10.0
1A = 0.2 mA -50 -10.0
0
0
Signature
Name
Organization
Date
Signature
N.A
Serial number
0
0 0
0
Make
List of Instruments used:
Comments (if any)
*** End of test report ***
Digital Clamp Meter
Approved by
Digital Multi Meter
Name
Organization
Date
STATRON
0
Signature
N.A
Voltage Transducer-
DC Bus 1 Voltage
Voltage Transducer-
DC Bus 2 Voltage
Tested by
5
0
0
2
3 0
4
Current Transducer-
DC Bus 1 Current
Current Transducer-
DC Bus 2 Current
Current Transducer-
Bus Coupler Current
Instrument Name
0
Test Date:
Name
Organization
Date
Witnessed by
Measurement
Channel
Input Applied Output (mA)
1
Sl.No DCDB Rating
File # 15
Rating of Transducer
ADDC
0
Calibration due date
0
Site Acceptance Test Report - Transducer Test
Circuit Designation
0
0
Transducer Test
Terminal Ref.
72
Sl.No.
Position
of S1
Operation (I/C#1) (BC) (I/C#2) DCDB#1 DCDB#2 Remarks
1 Auto Normal ON OFF ON Feed by CH 1 Feed by CH 2
I/C-1 and I/C-2 shall be close. BC
shall be open.
2 Auto Both mains fail ON OFF ON Feed by BB 1 Feed by BB 2
No Change. I/C-1 and I/C-2 shall
remain closed. BC shall remain
open.
3 Auto BB 1 Under Voltage OFF ON ON
Feed by CH 2/BB
2
Feed by CH 2/BB 2
I/C-1 should open first before BC is
closed.
4 Auto BB 2 Under Voltage ON ON OFF
Feed by CH 1/BB
1
Feed by CH 1/BB 1
I/C-2 should open first before BC is
closed.
5 Auto
Fault at DCDB # 1
(Short Circuit)
TRIP OFF ON No supply Feed by CH 2/BB 2 BC shall remain open.
6 Auto
Fault at DCDB # 2
(Short Circuit)
ON OFF TRIP
Feed by CH 1/BB
1
No supply BC shall remain open.
7 Auto Bus coupler trip ON TRIP ON
I/C-1 and I/C-2 shall remain
closed.
8 Manual S4 in 0 position ON OFF ON Feed by CH 1 Feed by CH 2
No Change. Auto Changeover
should be blocked.
9 Manual
S4 selected for CH1
Feed
ON ON OFF
Feed by CH 1/BB
1
Feed by CH 1/BB 1
BC should close first before I/C-2 is
opened (momentary parallel)
10 Manual
S4 selected for CH2
Feed
OFF ON ON
Feed by CH 2/BB
2
Feed by CH 2/BB 2
BC should close first before I/C-1 is
opened (momentary parallel)
1 Red
2 Green
3 Amber
Amber
Red
Red
5 Green
6 Amber
Amber
Red
Red
8 Green
9 Amber
Q200 Incomer Trip
Incomer Off
Incomer Trip
Distribution-2 Voltage
level low
Q300 Bus coupler ON
Q300 Bus coupler OFF
Incomer Off (In DCDB-2
front panel)
Incomer On (In DCDB-2
front panel)
7
Q200 Incomer ON
Incomer On (In DCDB-2
front panel)
4 Q100 Incomer Tripped
Incomer Off
Incomer Trip
Distribution-1 Voltage
level low
Bus Coupler Scheme Alarms
No change in states of I/C-1 and I/C-2
Incomer On (In DCDB-1
front panel)
Q100 Incomer ON
Auto Changeover Auto Changeover
Local Indication
LED Color Lamp Indication
Remote Contacts Sl.No Comments (if any) Description / Origin of Alarm
Q200 Incomer OFF
Incomer Off (In DCDB-2
front panel)
Test Date:
File # 16
Site Acceptance Test Report - Bus Coupler Scheme Test
VCU Test
Incomer Off (In DCDB-1
front panel)
Q100 Incomer OFF
73
Name
STATRON Organization ADDC
0 Date 0 Date Date 0
0
Calibration due date
0
Make
0
Digital Clamp
Meter
0
Approved by
Signature Signature Signature
Witnessed by
Organization 0
File # 16
Site Acceptance Test Report - Bus Coupler Scheme Test
List of Instruments used:
Instrument Name Serial number
Digital Multi
Meter
Organization
Tested by
Comments (if any)
*** End of test report ***