You are on page 1of 134

Refer to the service manual in the GSPN(see the rear cover) for the more information.

AIR CONDITIONER CONTENTS


SYSTEM AIR CONDITIONER
Model : NS0904DXEA
NS0904PXEA
NS1004DXEA
NS1004PXEA
NS1254DXEA
NS1254PXEA
NS1404DXEA
NS1004ZXEA
NS0714PXEA
RC090DHXEA
RC090PHXEA
RC100DHXEA
RC100DHXGA
RC100PHXEA
RC100ZHXEA
RC125DHXEA
RC125DHXGA
RC125PHXEA
RC125PHXGA
RC140DHXEA
RC140DHXGA
RC071DHXEA
RC071PHXEA
INDOOR UNIT OUTDOOR UNIT
1. Precautions
2. Product Specifications
3. Disassembly and Reassembly
4. Troubleshooting
5. Exploded Views and Parts List
6. PCB Diagram
7. Wiring Diagram
8. Schematic Diagram
9. Reference Sheet
NS1004PXEA_E_33124A(1)_co.indd 1 2011-04-29 4:19:19


Contents
11. Precautions
........................................................................................................................................
1-1
1-1 Precautions for the Service
..............................................................................................................
1-1
1-2 Precautions related to static electricity and PL
............................................................................
1-1
1-3 Precautions related to product safety
...........................................................................................
1-2
1-4 Other precautions
..............................................................................................................................
1-2

12. Product Specifications
...............................................................................................................
2-1
2-1 The Feature of Product
.....................................................................................................................
2-1
2-1-1 Features
....................................................................................................................................
2-1
2-2 Product Specifications
......................................................................................................................
2-5
2-3 Specifications of optional items
......................................................................................................
2-12
2-3-1 Accessories
...............................................................................................................................
2-12
2-3-2 Filter specifications
.................................................................................................................
2-18
13. Disassembly and Reassembly ............................................................................................... 3-1
3-1 Indoor Unit ......................................................................................................................................... 3-2
3-2 Outdoor Unit ..................................................................................................................................... 3-8

14. Troubleshooting
............................................................................................................................
4-1
4-1 Setting an indoor unit address and installation option ............................................................ 4-1
4-1-1 The procedure of setting option ......................................................................................... 4-1
4-1-2 The procedure of setting option ......................................................................................... 4-2
4-1-3 Setting an indoor unit address (MAIN/RMC) ..................................................................... 4-5
4-1-4 Setting an indoor unit installation option (suitable for the condition of
each installation location) ..................................................................................................... 4-6
4-1-5 Changing a particular option ............................................................................................... 4-8
4-1-6 Option code for each model ................................................................................................ 4-9
4-2 Items to check before diagnostics ................................................................................................. 4-11
4-2-1 Four directions cassette type ............................................................................................... 4-11
4-2-2 Test run mode and View mode ........................................................................................... 4-12
4-2-3 ECO mode(Power save) ......................................................................................................... 4-13
4-2-4 Troubleshooting for outdoor unit ....................................................................................... 4-14
4-2-5 Wired remote controller ....................................................................................................... 4-15
4-3 Troubleshooting by symptoms ...................................................................................................... 4-17
4-3-1 Indoor temperature sensor (open/short) .......................................................................... 4-17
4-3-2 Indoor heat exchanger temperature sensor (open/short) ............................................. 4-18
4-3-3 Indoor FAN error ..................................................................................................................... 4-19
NS1004PXEA_E_SM_33124A(1)_1.indd 1 2011-04-29 4:19:36

Contents
4-3-4 Communication error after finishing Tracking
.................................................................
4-20
4-3-5 Indoor unit float sensor error
...............................................................................................
4-21
4-3-6 EEPROM circuit failure
...........................................................................................................
4-22
4-3-7 Outdoor unit is not powered on
.........................................................................................
4-23
15. Exploded Views and Parts List
.............................................................................................
5-1
5-1 Indoor Unit
.........................................................................................................................................
5-1
5-2 Panel
....................................................................................................................................................
5-5
5-3 Outdoor Unit
.....................................................................................................................................
5-9
5-4 Ass'y Control Out
..............................................................................................................................
5-17
16. PCB Diagram
.....................................................................................................................................
6-1
6-1 PCB Diagram
......................................................................................................................................
6-1
6-1-1 Indoor Unit
..............................................................................................................................
6-1
6-1-2 Panel PCB
.................................................................................................................................
6-2
6-1-3 Outdoor Unit PCB
...................................................................................................................
6-3
6-2 Parts List
.............................................................................................................................................
6-12
6-2-1 Indoor Unit PCB
......................................................................................................................
6-12
17. Wiring Diagram
..............................................................................................................................
7-1
18. Schematic Diagram
......................................................................................................................
8-1
8-1 Indoor Unit
.........................................................................................................................................
8-1
8-1-1 MAIN PCB
.................................................................................................................................
8-1
8-1-2 Panel PCB
.................................................................................................................................
8-3
8-1-3 Outdoor Unit PCB
...................................................................................................................
8-5
1
9. Reference Sheet
..............................................................................................................................
9-1
9-1 Index for Model Name
......................................................................................................................
9-1
9-2 Refrigerating Cycle Diagram
............................................................................................................
9-4
9-3 Pressure Graph
...................................................................................................................................
9-5
NS1004PXEA_E_SM_33124A(1)_1.indd 2 2011-04-29 4:19:36
Samsung Electronics 1-1
1. Precautions
1-1 Precautions for the Service
Use the standard parts when replacing the electric parts.
Confirm the model name, rated voltage, rated current of the electric parts.
When repairing the equipment, connection of the harness parts must be firm and solid.
A loose connection may cause noise or other malfunction.
When assembling and disassembling the equipment while it is laid down, lay it on soft cloth.
Otherwise it may scratch the back of the exterior of the product.
Remove dust or dirt completely from the housing block, wiring block and service parts during repair.
This helps prevent the danger of fire caused by tracking or short circuit.
Fasten the valve caps of service valves and charging valves of outdoor unit as much as possible using adjustable wrenches.
Check the status of the components assembly after repair service.
The status must be the same as before the repair service.
1-2 Precautions related to static electricity and PL
The PCB power supply block is susceptible to static electricity. Therefore, care must be taken during repair or measuring
while the power is on.
Wear insulation gloves for PCB repair or measuring.
Check whether the installation location is at least two meters away from other electronic products such as TV, video, or
audio.
Otherwise, the video quality might be degraded or noise might be generated.
Do not let end users repair the products themselves.
Unauthorized disassembly might cause electric shock or fire.
NS1004PXEA_E_SM_33124A(1)_1.indd 1 2011-04-29 4:19:36
1-2 Samsung Electronics
1-3 Precautions related to product safety
Do not pull the power cord and do not touch the power plug or aux power switch with wet hands.
It might cause electric shock or fire.
A damaged power line or power plug must be replaced to prevent danger.
Do not bend the power cable with excessive force, and do not place a heavy weight on the case as it might damage the
cable.
It might cause electric shock or fire.
Do not use multiple electric outlets.
This might cause electric shock or fire.
Connect the ground terminal when necessary.
You must connect the ground terminal if you determine that there is a danger of electric leakage due to moisture or water.
Unplug the power cable or turn off the auxiliary power switch for electric part replacement and repair service.
Otherwise it might cause electric shock.
Instruct end users to separate the batteries from the remote controllers and store them separately when the product is not
used for long time.
Otherwise leakage from the dry cell may cause problems with the remote controller.
1-4 Other precautions
The pipes should have no leaks during installation, and the compressor must be stopped before removing connecting
pipes for pump down work. Operating the compressor while the service valve is open and coolant pipe is not properly
connected may cause explosion or injury due to abnormal high pressure created inside the coolant cycle as the air can be
absorbed through the pipe.
Pump Down work procedure (When uninstalling the product)
Turn on the air conditioner, select cooling operation, and run the compressor for more than three minutes.
Release the high pressure and low pressure valve caps.
Close the high pressure valve completely using an L-wrench
After about two minutes, close the low pressure valve completely.
Stop running the air conditioner.
Separate the connecting pipe.
NS1004PXEA_E_SM_33124A(1)_1.indd 2 2011-04-29 4:19:36
Samsung Electronics 2-1
Convenient and efficient installation
Corner separable panel for simple leveling
The panel structure with four corners that can be separated enables
convenient installation and service as only the required corner can
be separated to adjust leveling when necessary.
Maintain pleasant temperature with fine temperature control
with a resolution of 0.1C
The equipment operates with minimum power to maintain the
optimum temperature and it always maintains a pleasant room
temperature in small temperature steps of 0.1C that you may
not be able to sense.
Easy installation of ultra-lightweight indoor unit
A filter that obviates the need for replacement and/or
maintenance up to 1,000~2,000 hours and retains its initial
cleanness.
[Comparison of weights with other companies 11kg]
HAUZEN
Other companies
Weight
20Kg
17kg
35%
29kg
[Comparison of weights with other companies 11kg]
SAMSUNG
20kg
2. Product Specifications
2-1 The Feature of Product
2C
1C
Setting
temperature
-1C
-2C
Smart inverter air conditioner General air conditioner
Four-direction cassette with powerful three-dimensional cooling and heating from
four directions offers gapless pleasant environment and has the right design for high
class interior and will provide an extra-stylish look.
2-1-1 Features
What is four-direction cassette type air conditioner?
Stylish design and pleasant cooling/heating will provide a pleasant ambience.
NS1004PXEA_E_SM_33124A(1)_1.indd 1 2011-04-29 4:19:39
2-2 Samsung Electronics
Product Specifications
Rich and pleasant cooling/heating without gaps

Superior heating performance even at -15C
The equipment achieves a stable heating performance with the
superior reliability of low temperature heating so that the indoor
unit blows air of 40C or higher in a cold winter when the outside
temperature is below -15C.
Pleasant room with a check valve for preventing backflow
A check valve is installed to prevent condensed water drained from the indoor unit flowing back into the indoor unit
for various reasons such as improper drain pipe installation or power cut, and indoor leak or bad smell by backflow
is fundamentally blocked.
Function to control optimum room temperature that
reduces temperature variation
Room temperature sense condition can be set to
Indoor + average of wired remote controller to minimize the
variation in temperature between the upper and lower levels
generated by the effects of indoor air flow so that optimum
room temperature will be maintained.
Obtained Sterilization Treatment SF mark that removes
the threat of mildew.
The equipment is very sanitary as an indoor heat exchange unit
and filters are treated with world-recognized sterilization treatment
technology to prevent the growth of mildew inside the unit.
X
*30%
33mm 30%

.
*2
2

.
.
'+ '

.
ABS
(Mold)20kg
.

.
4

High strength
X frame
ABS cabinet

, .

,
.
SF

Wide
30%

1

W
a
y

4

W
a
y

2
0
l
2
1
4 Way
4Way
HAUZEN

*ABS ?
ABS, ,
.

Blade 27 Blade 27
Center 17
Temperature setting (A): Indoor unit temperature setting
Temperature setting (B): Wired remote controller temperature setting
Patent registered in Korea, USA, Japan, and Italy
(Patent number: Korea P-082555/ Italy 1294250/USA 5947194/Japan 3048541)

[Comparison of weights with other companies 11kg]
HAUZEN
Other companies
Weight
20Kg
19.8kg
29kg

, 0.1
.
0.1
-15
40
.
-15
15
0
2C
1C
Setting
temperature
-1C
-2C
Smart inverter air conditioner General air conditioner
X
*30%
33mm 30%

.
*2
2

.
.
'+ '

.
ABS
(Mold)20kg
.

.
4

High strength
X frame
ABS cabinet

, .

,
.
SF

Wide
30%

1

W
a
y

4

W
a
y

2
0
l
2
1
4 Way
4Way
HAUZEN

*ABS ?
ABS, ,
.

Blade 27 Blade 27
Center 17
Temperature setting (A): Indoor unit temperature setting
Temperature setting (B): Wired remote controller temperature setting
Patent registered in Korea, USA, Japan, and Italy
(Patent number: Korea P-082555/ Italy 1294250/USA 5947194/Japan 3048541)

[Comparison of weights with other companies 11kg]
HAUZEN
Other companies
Weight
20Kg
19.8kg
29kg

, 0.1
.
0.1
-15
40
.
-15
15
0
2C
1C
Setting
temperature
-1C
-2C
Smart inverter air conditioner General air conditioner
X
*30%
33mm 30%

.
*2
2

.
.
'+ '

.
ABS
(Mold)20kg
.

.
4

High strength
X frame
ABS cabinet

, .

,
.
SF

Wide
30%

1

W
a
y

4

W
a
y

2
0
l
2
1
4 Way
4Way
HAUZEN

*ABS ?
ABS, ,
.

Blade 27 Blade 27
Center 17
Temperature setting (A): Indoor unit temperature setting
Temperature setting (B): Wired remote controller temperature setting
Patent registered in Korea, USA, Japan, and Italy
(Patent number: Korea P-082555/ Italy 1294250/USA 5947194/Japan 3048541)

[Comparison of weights with other companies 11kg]
HAUZEN
Other companies
Weight
20Kg
19.8kg
29kg

, 0.1
.
0.1
-15
40
.
-15
15
0
2C
1C
Setting
temperature
-1C
-2C
Smart inverter air conditioner General air conditioner
Convenient control for high ceilings with wind velocity
control function
When the unit is installed indoors, air flow can be set to
reach the floor through the PCB option so that the unit can
be installed on a ceiling with a height of 3.5 meters.
Open
PCB , 3.5m.

()
,

PCB ,

.
PCB
,
. 750mm
.

, Quick Lock
.
Quick Lock
!
4Way
HAUZEN

1

W
a
y

4

W
a
y

2
2
l
2
3
[Cleaning alarm function]

2
,
1,

.
.
1
HAUZEN

[When installing on a ceiling
of 3m or higher]
[When installing on a ceiling
of 3m or lower]
m 7 . 2
m 5 . 3
Indoor PCB option setting
ON: Increase wind velocity OFF: Decrease wind velocity
*4
4

.
*,
Kit
.
*

,
.

1.5

2.5

3.5 (m)
NS1004PXEA_E_SM_33124A(1)_1.indd 2 2011-04-29 4:19:42
Samsung Electronics 2-3
Product Specifications
Convenience with more added details
Convenient filter cleaning with smart automatic elevating
grille. (Optional)
Stability is secured with the four points support for the main
body
When the smart auto elevating grille function is used, the grille
can be separated easily with stable lowering through the four
points support for the main body so that cleaning and managing
the filter is more convenient.
No additional ceiling height is added, saving installation space
Installation space can be saved further by applying the smart auto
elevating grille kit as the additional ceiling height is not necessary.
Convenient management with filter cleaning alarm function
Filter management is very convenient as filter pollution status is
checked in real time and the cleaning time is notified so that users
do not have to check the filters
Two grille designs (classic pattern & interior pattern) to match
your style
While competing firms can only offer a variety of colors for
customers, we also provide different grille designs to further
diversity our products. This enables customers to select products
that are better suited to their preferences and geographic location.
Easier than Ever to Clean the Blade
Other products require you to disassemble and remove the panel
in order to clean the blade, but our product is designed so that the
blade safely and easily detaches and re-attaches, enabling you to
easily clean it.
Ceiling height Low High
Auto stop (m) 2 4
<Interior pattern>
<Classic pattern>
NS1004PXEA_E_SM_33124A(1)_1.indd 3 2011-04-29 4:19:46
2-4 Samsung Electronics
Product Specifications
Rich and pleasant cooling/heating without gaps (cont.)

Self diagnostic function of indoor unit to minimize
inconvenience in case of malfunction
If the indoor unit malfunctions due to equipment failure
during operation, the type of problem can be checked from
the panel display, and the service time and inconvenience can
be minimized by submitting a service request based on the
information from the self diagnostics of indoor unit.
Minimum installation cost by built-in high head drain pump
The high head pump is built into the indoor unit and the
condensed water generated during the cooling operation will
be drained to the outside. The pumping height can be up to
750mm so that drain pip installation can be easier and save
time and cost of installation.
Individual Blade Control
- Capable of realizing optimal air current in accordance to
customer preference and diverse structures located in
different directions through individual control of each of the
4 blades.
- Individual control can be realized through both cable and
wireless remote control.
NS1004PXEA_E_SM_33124A(1)_1.indd 4 2011-04-29 4:19:48
Samsung Electronics 2-5
ITEM NS0714DXEA/RC071DHXEA NS0714PXEA/RC071PHXEA
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 1, 220~240V/50Hz 1, 220~240V/50Hz
Indoor L x H x D mm 840 x 204 x 840 840 x 204 x 840
Panel L x H x D mm 950 x 45 x 950 950 x 45 x 950
Outdoor L x H x D mm 798 x 880 x 310 798 x 880 x 310
Indoor Product kg(Net) 15.0 15.0
Outdoor Product kg(Net) 54.0 54.0
Capacity
Cooling(STD) W 7,100 7,100
Heating(STD) W 8,000 8,000
Power
Consumption
Cooling(STD) W 2,210 1,920
Heating(STD) W 2,220 1,950
Operation
current
Cooling(STD) A 10.5 9.5
Heating(STD) A 10.5 9.5
Noise
(Cooling/
Heating)
Indoor unit
In case of strongest air
blow
A 43/43 45/45
Outdoor unit
In case of strongest air
blow
A 60/60 60/60
Refrigerant g 1,800 2,000
Connecting Pipe
Liquid mm 6.35 6.35
Gas mm 15.88 15.88
Additional Refrigerant g/m 30 30
Standard m 5 5
Extension length(Total) m 50 50
Extension length(Elevation) m 30 30
Option Code
Product Option 014077-1660C8-274750-370000 014077-1360D8-274750-370020
Installation Option 020000-100000-200000-300000 020000-100000-200000-300000
2-2 Product Specifications
NS1004PXEA_E_SM_33124A(1)_1.indd 5 2011-04-29 4:19:49
2-6 Samsung Electronics
ITEM
NS1004ZXEA/
RC100ZHXEA
NS1404PXEA/
RC140PHXEA
NS1404PXEA/
RC140PHXGA
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 1, 220-240V/50Hz 1, 220-240V/50Hz 3, 380~415V/50Hz
Indoor L x H x D mm 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840
Panel L x H x D mm 950 x 45 x 950 950 x 45 x 950 950 x 45 x 950
Outdoor L x H x D mm 940 x 1,420 x 330 940 x 1,420 x 330 940 x 1,420 x 330
Indoor Product kg(Net) 21.0 21.0 21.0
Outdoor Product kg(Net) 98.0 98.0 101.0
Capacity
Cooling(STD) W 10,000 14,000 14,000
Heating(STD) W 11,200 16,000 16,000
Power
Consumption
Cooling(STD) W 2,210 4,000 4,000
Heating(STD) W 2,335 4,100 4,100
Operation
current
Cooling(STD) A 9.7 17.8 7.1
Heating(STD) A 10.3 18.7 7.2
Noise
(Cooling/
Heating)
Indoor unit
In case of strongest air
blow
A 50/50 50/50 50/50
Outdoor unit
In case of strongest air
blow
A 58/60 60/62 60/62
Refrigerant g 3,800 3,800 3,800
Connecting Pipe
Liquid mm 9.52 9.52 9.52
Gas mm 15.88 15.88 15.88
Additional Refrigerant g/m 50 50 50
Standard m 5 5 5
Extension length(Total) m 75 75 75
Extension length(Elevation) m 30 30 30
Option Code
Product
Option
014077-156249-
276470-370040
014077-15624B-
278CA0-370040
014077-15624B-
278CA0-370040
Installation
Option
020000-100000-
200000-300000
020000-100000-
200000-300000
020000-100000-
200000-300000
Product Specifications (cont.)
NS1004PXEA_E_SM_33124A(1)_1.indd 6 2011-04-29 4:19:51
Samsung Electronics 2-7
ITEM
NS1004DXEA/
RC100DHXEA
NS1004DXEA/
RC100DHXGA
NS0904DXEA/
RC090DHXEA
NS0904PXEA/
RC090PHXEA
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 1, 220~240V/50Hz 3, 380~415V/50Hz 1, 220~240V/50Hz 1, 220~240V/50Hz
Indoor L x H x D mm 840 x 246 x 840 840 x 246 x 840 840 x 246 x 840 840 x 288 x 840
Panel L x H x D mm 950 x 45 x 950 950 x 45 x 950 950 x 45 x 950 950 x 45 x 950
Outdoor L x H x D mm 940 x 998 x 330 940 x 998 x 330 940 x 998 x 330 940 x 998 x 330
Indoor Product kg(Net) 17.0 17.0 17.0 19.0
Outdoor Product kg(Net) 72.0 81.0 72.0 72.0
Capacity
Cooling(STD) W 10,000 10,000 9,000 9,000
Heating(STD) W 11,200 11,200 10,000 10,000
Power
Consumption
Cooling(STD) W 3,120 3,120 2,800 2,500
Heating(STD) W 3,100 3,100 2,770 2,500
Operation
current
Cooling(STD) A 13.8 5.0 12.5 11.0
Heating(STD) A 13.8 5.0 12.2 11.0
Noise
(Cooling/
Heating)
Indoor unit
In case of strongest air
blow
dB 48/48 48/48 46/46 47/47
Outdoor unit
In case of strongest air
blow
dB 59/63 59/63 58/60 57/59
Refrigerant g 3,000 3,100 3,000 3,000
Connecting Pipe
Liquid mm 9.52 9.52 9.52 9.52
Gas mm 15.88 15.88 15.88 15.88
Additional Refrigerant g/m 50 50 50 50
Standard m 5 5 5 5
Extension length(Total) m 50 50 50 50
Extension length(Elevation) m 30 30 30 30
Option Code
Product
Option
014077-156219-
276470-370020
014077-156219-
276470-370020
014077-1560E8-
275A64-370020
014077-156219-
275A64-370040
Installation
Option
020000-100000-
200000-300000
020000-100000-
200000-300000
020000-100000-
200000-300000
020000-100000-
200000-300000
Product Specifications (cont.)
NS1004PXEA_E_SM_33124A(1)_1.indd 7 2011-04-29 4:19:52
2-8 Samsung Electronics
Product Specifications (cont.)
ITEM NS1004PXEA/RC100PHXGA NS1254PXEA/RC125PHXGA
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 3, 380~415V/50Hz 3, 380~415V/50Hz
Indoor unit
Product
L x H x D mm 840 x 288 x 840 840 x 288 x 840
Panel L x H x D mm 950 x 45 x 950 950 x 45 x 950
Outdoor unit Product L x H x D mm 940 x 1,210 x 330 940 x 1,210 x 330
Indoor unit Product kg(Net) 21.0 21.0
Outdoor unit Product kg(Net) 91.0 91.0
Capacity
Cooling(STD) W 10,000 12,500
Heating(STD) W 11,200 14,000
Power consumption
Cooling(STD) W 2,380 3,470
Heating(STD) W 2,490 3,590
Operation current
Cooling(STD) A 4.0 5.8
Heating(STD) A 4.2 5.8
Noise
(Cooling/Heating)
Indoor
unit
In case of strongest
air blow
dB 50/50 50/50
Outdoor
unit
In case of strongest
air blow
dB 58/60 59/61
Refrigerant g 3,400 3,400
Connecting Pipe
Liquid mm 9.52 9.52
Gas mm 15.88 15.88
Additional Refrigerant(g/m) g/m 50 50
Standard m 5 5
Extension length(Total) m 75 75
Extension length(Elevation) m 30 30
Option Code
Product
Option
014077-157239-276470-370040 014077-15723A-277D8C-370040
Installation
Option
020000-100000-200000-300000 020000-100000-200000-300000
NS1004PXEA_E_SM_33124A(1)_1.indd 8 2011-04-29 4:19:55
Samsung Electronics 2-9
ITEM NS1254DXEA/RC125DHXGA NS1254DXEA/RC125DHXEB
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 3, 380~415V/50Hz 1, 220-240V~/50Hz
Indoor unit
Product
L x H x D mm 840 x 288 x 840 840 x 288 x 840
Panel L x H x D mm 950 x 45 x 950 950 x 45 x 950
Outdoor unit Product L x H x D mm 940 x 1,210 x 330 940 x 1,210 x 330
Indoor unit Product kg(Net) 19.0 19.0
Outdoor unit Product kg(Net) 91.0 88.0
Capacity
Cooling(STD) W 12,500 12,500
Heating(STD) W 14,000 14,000
Power consumption
Cooling(STD) W 3,890 3,890
Heating(STD) W 3,880 3,880
Operation current
Cooling(STD) A 6.1 18.0
Heating(STD) A 6.1 18.0
Noise
(Cooling/Heating)
Indoor
unit
In case of strongest
air blow
dB 50/50 50/50
Outdoor
unit
In case of strongest
air blow
dB 59/61 59/61
Refrigerant g 2,900 2,900
Connecting Pipe
Liquid mm 9.52 9.52
Gas mm 15.88 15.88
Additional Refrigerant(g/m) g/m 50 50
Standard m 5 5
Extension length(Total) m 75 75
Extension length(Elevation) m 30 30
Option Code
Product
Option
014077-15723A-277D8C-370040 014077-15723A-277D8C-370040
Installation
Option
020000-100000-200000-300000 020000-100000-200000-300000
Product Specifications (cont.)
NS1004PXEA_E_SM_33124A(1)_1.indd 9 2011-04-29 4:19:58
2-10 Samsung Electronics
Product Specifications (cont.)
ITEM NS1254PXEA/RC125PHXEA NS1404DXEA/RC140DHXEB
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 1, 220-240V~/50Hz 1, 220-240V~/50Hz
Indoor unit
Product
L x H x D mm 840 x 288 x 840 840 x 288 x 840
Panel L x H x D mm 950 x 45 x 950 950 x 45 x 950
Outdoor unit Product L x H x D mm 940 x 1,210 x 330 940 x 1,210 x 330
Indoor unit Product kg(Net) 21.0 21.0
Outdoor unit Product kg(Net) 88.0 88.0
Capacity
Cooling(STD) W 12,500 14,000
Heating(STD) W 14,000 16,000
Power consumption
Cooling(STD) W 3,470 4,360
Heating(STD) W 3,590 4,430
Operation current
Cooling(STD) A 15.5 20.0
Heating(STD) A 16.0 20.0
Noise
(Cooling/Heating)
Indoor
unit
In case of strongest
air blow
dB 50/50 50/50
Outdoor
unit
In case of strongest
air blow
dB 59/61 60/62
Refrigerant g 3,400 3,400
Connecting Pipe
Liquid mm 9.52 9.52
Gas mm 15.88 15.88
Additional Refrigerant(g/m) g/m 50 50
Standard m 5 5
Extension length(Total) m 75 75
Extension length(Elevation) m 30 30
Option Code
Product
Option
014077-15723A-277D8C-370040 014077-15723B-278CA0-370040
Installation
Option
020000-100000-200000-300000 020000-100000-200000-300000
NS1004PXEA_E_SM_33124A(1)_1.indd 10 2011-04-29 4:20:00
Samsung Electronics 2-11
ITEM NS1404DXEA/RC140DHXGA NS1004PXEA/RC100PHXEA
IMAGE
Indoor Unit
Outdoor Unit
Remote Controller
Power Product 3, 380~415V/50Hz 1, 220-240V~/50Hz
Indoor unit
Product
L x H x D mm 840 x 288 x 840 840 x 288 x 840
Panel L x H x D mm 950 x 45 x 950 950 x 45 x 950
Outdoor unit Product L x H x D mm 940 x 1,210x 330 940 x 1,210 x 330
Indoor unit Product kg(Net) 21.0 21.0
Outdoor unit Product kg(Net) 91.0 88.0
Capacity
Cooling(STD) W 14,000 10,000
Heating(STD) W 16,000 11,200
Power consumption
Cooling(STD) W 4,360 2,380
Heating(STD) W 4,430 2,490
Operation current
Cooling(STD) A 7.5 10.5
Heating(STD) A 7.4 11.5
Noise
(Cooling/Heating)
Indoor
unit
In case of strongest
air blow
dB 50/50 50/50
Outdoor
unit
In case of strongest
air blow
dB 60/62 58/60
Refrigerant g 3,400 3,400
Connecting Pipe
Liquid mm 9.52 9.52
Gas mm 15.88 15.88
Additional Refrigerant(g/m) g/m 50 50
Standard m 5 5
Extension length(Total) m 75 75
Extension length(Elevation) m 30 30
Option Code
Product
Option
014077-15723B-278CA0-370040 014077-157239-276470-370040
Installation
Option
020000-100000-200000-300000 020000-100000-200000-300000
Product Specifications (cont.)
NS1004PXEA_E_SM_33124A(1)_1.indd 11 2011-04-29 4:20:03
2-12 Samsung Electronics
Item Description Code No. Qty Remark
Ass'y drain hose DB94-02719B 1
Essential Offer
(Indoor Unit)
Cable-tie DB65-00191A 5
Seal-drain ass'y DB62-05810A 1
Seal-drain ass'y DB62-05810B 1
Seal-drain ass'y DB62-05810C 1
Fastener-Nut Flare DB60-30010B 1
Cap Drain DB63-10355C 3
Essential Offer
(Outdoor Unit)
Drain Plug DB67-00806A 1
Rubber Leg DB73-20134A 4
BOLT-FLANGE 6011-003975 4
Essential Offer
(Panel)
ASSY-INSTALLATION
MANUAL
DB98-32728A 1
CARD WARRNATY DB68-02596B 1
2-3 Specifications of optional items
2-3-1 Accessories
NS1004PXEA_E_SM_33124A(1)_1.indd 12 2011-04-29 4:20:04
Samsung Electronics 2-13
Product Specifications
Item Descriptions Code-No. Q'TY Remark
Wireless remote controller DB93-11115N 1
Optional
Batteries for remote controller
(specification: "AAA" type)
DB47-90024A 2
Remote controller holder DB61-04899A 1
M416 screw 6002-000581 2
Users manual DB98-33129A 1
Accessories (cont.)
Wireless remote controller (MR-DH00) [Code No. : DB97-17546B]
NS1004PXEA_E_SM_33124A(1)_1.indd 13 2011-04-29 4:20:04
2-14 Samsung Electronics
Product Specifications
Accessories (cont.)
Wired remote controller (MWR-WE10) [Code No. : DB97-17002B]
Item Descriptions Code-No. Q'TY Remark
Wired remote controller DB93-11251B 1
Optional
Cable tie DB65-10088B 2
Cable clamp DB65-10074E 3
M416 Screw 6002-000474 5
Users manual DB98-32810A 1
Installation guide DB98-32811A 1
NS1004PXEA_E_SM_33124A(1)_1.indd 14 2011-04-29 4:20:05
Samsung Electronics 2-15
Product Specifications
Accessories (cont.)
Central controller (MCM-A202D) [Code No. : DB97-18602B]
Item Descriptions Code-No. Q'TY Remark
Central controller DB93-03425N 1
Optional
Cable tie DB65-10088B 2
Cable clamp DB65-10074E 5
M4 X 16 Screw 6002-000474 7
Users manual DB98-33437A 1
Installation guide DB98-33434A 1
NS1004PXEA_E_SM_33124A(1)_1.indd 15 2011-04-29 4:20:05
2-16 Samsung Electronics
Product Specifications
Accessories (cont.)
Function controller (MCM-A100) [Code No. : DB97-01077A]
Item Descriptions Code-No. Q'TY Remark
Function controller DB93-00757G 1
Optional
Cable tie DB65-10088B 2
Cable clamp DB65-10074E 6
M416 Screw 6002-000474 7
Users manual DB98-27317A 1
Installation guide DB98-27315A 1
* PC control and DMS cannot be used when using the function controller
NS1004PXEA_E_SM_33124A(1)_1.indd 16 2011-04-29 4:20:05
Samsung Electronics 2-17
Product Specifications
Accessories (cont.)
Relay (MIM-B13D) [Code No. : DB97-18519A]
Relay (MIM-B13E) [Code No. : DB97-04416J)
Item Descriptions Code-No. Q'TY Remark
Relay DB93-12203A 1
Optional
Relay power cable
(300mm)
DB39-00378B 1
Relay communication cable
(300mm)
DB39-00253B 1
Item Descriptions Code-No. Q'TY Remark
Relay DB93-03568D 1
Optional
Relay sub DB93-03590B 1
Relay power cable
(1,000mm)
DB93-07895A 1
Relay power cable
(1,000mm)
DB93-07895B 1
Relay communication cable
(100mm)
DB93-12164A 1
NS1004PXEA_E_SM_33124A(1)_1.indd 17 2011-04-29 4:20:05
2-18 Samsung Electronics
Product Specifications
2-3-2 Filter specifications
Item Descriptions Code-No. Remark
Dust filter DB63-02739A
Basic/
Water wash
NS1004PXEA_E_SM_33124A(1)_1.indd 18 2011-04-29 4:20:05
Samsung Electronics 3-1
Item Remarks
+SCREW DRIVER
Adjustable Wrench
(8mm, 10mm, 13mm)
M6, M8 Hex Wrench
Necessary Tools
3. Disassembly and Reassembly
NS1004PXEA_E_SM_33124A(1)_1.indd 1 2011-04-29 4:20:06
3-2 Samsung Electronics
No Parts Procedure Remark
1 Panel 1) Push the handles on both sides of the
Samsung logo towards the products interior
to open the Grille.
2) Push up the green knob in the Open
direction, and detach the white link from
the panel. Detach the safety clip.
3) Remove the 2 fixed screws to remove the
Control-Box Cover. (Use +Screw Driver)
4) Remove the Remocon-Receiver and Blade
Connector Wire from the PBA. (3EA)
5) Push the 4 panel corners and cover
downwards to remove it.
3-1 Indoor unit
NS1004PXEA_E_SM_33124A(1)_1.indd 2 2011-04-29 4:20:06
Samsung Electronics 3-3
Disassembly and Reassembly
No Parts Procedure Remark
6) Disassemble the bolts that are assembled
with the indoor unit at the 4 panel corners.
7) Press the Steel Hangers at both sides of the
panel inwards, and rotate them 90 degrees
to remove it from the indoor units Hock.
Remove the panel from the indoor unit.
2 Control-Box 1) Disconnect the Connector Wire that is
connected to the indoor units PBA from
the PBA.
2) Unscrew the 2 fixed screws on both
sides of the Control Box, and disassemble
the Control Box from the indoor unit.
(Use +Screw Driver)
NS1004PXEA_E_SM_33124A(1)_1.indd 3 2011-04-29 4:20:07
3-4 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
3 Bell-Mouth 1) Unscrew the screw fixed on the Bell-Mouth.
(Use +Screw Driver)
2) Push the Bell-Mouth in the direction
opposite to where its installed on the
Control-Box to remove it.
4 Drain Pan 1) Unscrew the screws on the 4 corners
of the indoor unit. (Use +Screw Driver)
2) Remove the Drain Pan from the indoor unit.
NS1004PXEA_E_SM_33124A(1)_1.indd 4 2011-04-29 4:20:08
Samsung Electronics 3-5
Disassembly and Reassembly
No Parts Procedure Remark
5 Drain Pump
&
Hose
1) Remove the 2 fixed screws and
disconnect the white drainage hose from
the Drain Pump. (Use +Screw Driver)
2) Remove the 2 screws and take the
Drain-Hose out from the indoor unit to
disassemble the transparent Drain-Hose
fixed on the side of the indoor unit.
(Use +Screw Driver)
6 Evap.
Temperature
Sensor
1) Use your hand to remove the temperature
sensor attached to the Evap Pipe along with
the fixing clip.
NS1004PXEA_E_SM_33124A(1)_1.indd 5 2011-04-29 4:20:08
3-6 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
7 Fan
&
Motor
1) Turn the hexangular nut attached to the
top of the Fan counterclockwise to remove it.
Take the Fan out of the Motor.
2) Turn the three hexangular nuts on the
Motor counterclockwise to remove the nuts.
Take the Motor Wires attached to these
three locations out with your hands prior to
removing the Motor.
8 Evaporator 1) Remove the screws of the 2 Steel Holder
Evaps that are used to fix the Heat Exchanger,
and then remove it. (Use +Screw Driver)
2) Remove the 2 fixing screws of the Partition
Evap at the Heat Exchangers In/Out Pipe.
(Use +Screw Driver)
NS1004PXEA_E_SM_33124A(1)_1.indd 6 2011-04-29 4:20:09
Samsung Electronics 3-7
Disassembly and Reassembly
No Parts Procedure Remark
3) Remove the screw of the Cover Pipe
that is used to fix the In/Out Pipe.
Remove the In/Out Pipe. (Use +Screw Driver)
4) Remove the Heat Exchanger from the
indoor units cabinet.
NS1004PXEA_E_SM_33124A(1)_1.indd 7 2011-04-29 4:20:09
3-8 Samsung Electronics
3-2 Outdoor Unit
RC071DHS/RC071PHS
No Parts Procedure Remark
1 Common Work 1) Loosen 1 fixing screw of the Cover-Control
and detach the Cover Control.
2) Loosen each 7 fixing screws and detach
the Cabinet Upper.
NS1004PXEA_E_SM_33124A(1)_1.indd 8 2011-04-29 4:20:10
Samsung Electronics 3-9
Disassembly and Reassembly
No Parts Procedure Remark
3) Loosen 2 screws fixed to assemble
Control Box with Cabinet-Side RH.
4) Loosen fixing screws and detach the
Cabinet-Side RH.
5) Loosen 2 screws fixed on the Guide
Condenser.
NS1004PXEA_E_SM_33124A(1)_1.indd 9 2011-04-29 4:20:10
3-10 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
6) Loosen fixing screws of the Cabinet Front.
NS1004PXEA_E_SM_33124A(1)_1.indd 10 2011-04-29 4:20:11
Samsung Electronics 3-11
Disassembly and Reassembly
No Parts Procedure Remark
2 Fan
&
Motor
1) Detach the Nut Flange like the picture on
the right side. (Turn counter clockwise
because the screw is right-handed.)
2) Detach the Fan Propeller.
3) Loosen 4 fixing screws to detach the Motor.
4) Disconnect the wire between ASS'Y
Control Out and Motor.
5) Loosen 2 fixing bolts and detach the
Bracket Motor.
NS1004PXEA_E_SM_33124A(1)_1.indd 11 2011-04-29 4:20:11
3-12 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
3 ASS'Y Control Out 1) Detach several connectors from the
ASS'Y Control Out.
2) Detach several connectors from the PCB
of ASS'Y Control Out.
3) Pull up the ASS'Y Control Out.
4 Heat Exchanger 1) Release the refrigerant at first.
2) Loosen fixing screw on both sides.
3) Disassemble the pipes in both inlet and
outlet with welding torch.
4) Detach the Heat Exchanger.
5) Loosen 4 bolts fixed to assemble Valve
Service with Bracket Valve like the picture
on the right side.
NS1004PXEA_E_SM_33124A(1)_1.indd 12 2011-04-29 4:20:12
Samsung Electronics 3-13
Disassembly and Reassembly
No Parts Procedure Remark
5 Compressor 1) Loosen the fixing nut and detach the
Compressor Lead Wire.
2) Disassemble the Felt Compressor Sound.
3) Loosen the 3 bolts at the bottom of
Compressor like the picture on the
right side.
NS1004PXEA_E_SM_33124A(1)_1.indd 13 2011-04-29 4:20:12
3-14 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
1 Cabi Front RH You must turn off the Power before
disassembly.
1) Unscrew and remove two mounting screw
in the Cabinet Front RH. (Use +Screw Driver)
2 Cabi Top 1) Unscrew and remove 9 screws
on each side of the Cabinet-Top.
(Use +Screw Driver)
3 Cabi Install Front 1) Unscrew and remove 1 screw
in the Cabinet-Install Front.
(Use +Screw Driver)
RC090DHS/RC090PHS/RC100DHS
NS1004PXEA_E_SM_33124A(1)_1.indd 14 2011-04-29 4:20:12
Samsung Electronics 3-15
Disassembly and Reassembly
No Parts Procedure Remark
4 Guard Cond 1) Pull the sensor from Guard Cond.
2) Unscrew and remove 4 screws
in the Guard Cond.
(Use +Screw Driver)
5 Cabi Back RH 1) Pull the sensor from Cabi Back RH.
2) Unscrew and remove 4 screws
on each side of the Cabinet Back RH.
(Use +Screw Driver)
NS1004PXEA_E_SM_33124A(1)_1.indd 15 2011-04-29 4:20:13
3-16 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
6 Cabi Install Back 1) Unscrew and remove 1 screw
in the Cabinet-Install Back.
(Use +Screw Driver)
7 Cabi Front LF 1) Unscrew and remove 10 screws
in the Cabinet-Front LF.
(Use +Screw Driver)
NS1004PXEA_E_SM_33124A(1)_1.indd 16 2011-04-29 4:20:13
Samsung Electronics 3-17
Disassembly and Reassembly
No Parts Procedure Remark
8 Fan 1) Turn 2 mounting nuts as shown in the
picture and remove it. (Use Adjustable
Wrench)
NS1004PXEA_E_SM_33124A(1)_1.indd 17 2011-04-29 4:20:13
3-18 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
9 Motor 1) Separate the Fan Propeller.
2) Unscrew and remove the 8 Motor mounting
screws. (Use +Screw Driver)
3) Disconnect the Motor wire From
Ass'y Control Out.
10 Bracket Motor 1) Unscrew and remove 2 mounting screws
in Bracket Motor. (Use +Screw Driver)
NS1004PXEA_E_SM_33124A(1)_1.indd 18 2011-04-29 4:20:13
Samsung Electronics 3-19
Disassembly and Reassembly
No Parts Procedure Remark
11 Control Out 1) Disconnect 4 Connecters From
Ass'y Control Out.
2) Unscrew and remove 1 mounting screw
in Control Out. (Use +Screw Driver)
3) Separate Ass'y Control Out.
NS1004PXEA_E_SM_33124A(1)_1.indd 19 2011-04-29 4:20:14
3-20 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
12 Ass'y 4way Valve 1) Purge the Coolant first.
2) Unscrew and remove 2mounting screws
in muffler.
3) Unscrew and remove 2 mounting screws
in Service Valve. (Use +Screw Driver)
4) Separate the pipe from the Entrance/Exit
using a welder.
When removing the compressor,
Heat Exchanger, and Pipe, purge the
Coolant inside the Compressor
completely and remove the pipe
with a welding flame.
NS1004PXEA_E_SM_33124A(1)_1.indd 20 2011-04-29 4:20:14
Samsung Electronics 3-21
Disassembly and Reassembly
No Parts Procedure Remark
13 Ass;y EEV Valve 1) Unscrew and remove 2 mounting screws
in Service Valve. (Use +Screw Driver)
2) Separate the pipe from the Entrance/Exit
using a welder.
14 Compressor 1) Unscrew and remove 1 mounting nut
in Cover Terminal. (Use Adjustable Wrench)
2) Separate the Compressor Felt Sound.
NS1004PXEA_E_SM_33124A(1)_1.indd 21 2011-04-29 4:20:15
3-22 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
3) As shown in the picture, unscrew and
remove 3 mounting screws from the
bottom. (Use Adjustable Wrench)
15 Cond Out 1) Unscrew and remove 3 screws
on each side of the Assy Cond Out.
(Use +Screw Driver)
2) Separate the Compressor Felt Sound.
NS1004PXEA_E_SM_33124A(1)_1.indd 22 2011-04-29 4:20:15
Samsung Electronics 3-23
Disassembly and Reassembly
No Parts Procedure Remark
1 Cabi Front RH You must turn off the Power before
disassembly.
1) Unscrew and remove 2 mounting screw
in the Cabinet Front RH.
(Use +Screw Driver)
2 Cabi Top 1) Unscrew and remove 9 screws
on each side of the Cabinet-Top.
(Use +Screw Driver)
3 Cabi Install Front 1) Unscrew and remove 1 screw
in the Cabinet-Install Front.
(Use +Screw Driver)
RC100PHS/RC100ZHS/RC125DHS/RC125PHS/RC140DHS/RC140PHS
NS1004PXEA_E_SM_33124A(1)_1.indd 23 2011-04-29 4:20:16
3-24 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
4 Guard Cond 1) Pull the sensor from Guard Cond.
2) Unscrew and remove 4 screws
in the Guard Cond.
(Use +Screw Driver)
5 Cabi Back RH 1) Pull the sensor from Cabi Back RH.
2) Unscrew and remove 4 screws
on each side of the Cabinet Back RH.
(Use +Screw Driver)
NS1004PXEA_E_SM_33124A(1)_1.indd 24 2011-04-29 4:20:17
Samsung Electronics 3-25
Disassembly and Reassembly
No Parts Procedure Remark
6 Cabi Install Back 1) Unscrew and remove 1 screw
in the Cabinet-Install Back.
(Use +Screw Driver)
7 Cabi Front LF 1) Unscrew and remove 10 screws
in the Cabinet-Front LF.
(Use +Screw Driver)
NS1004PXEA_E_SM_33124A(1)_1.indd 25 2011-04-29 4:20:17
3-26 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
8 Fan 1) Turn 2 mounting nuts as shown in the
picture and remove it. (Use Adjustable
Wrench)
NS1004PXEA_E_SM_33124A(1)_1.indd 26 2011-04-29 4:20:18
Samsung Electronics 3-27
Disassembly and Reassembly
No Parts Procedure Remark
9 Motor 1) Separate the Fan Propeller.
2) Unscrew and remove the 8 Motor mounting
screws. (Use +Screw Driver)
3) Disconnect the Motor wire From
Ass'y Control Out.
10 Bracket Motor 1) Unscrew and remove 2 mounting screws
in Bracket Motor. (Use +Screw Driver)
NS1004PXEA_E_SM_33124A(1)_1.indd 27 2011-04-29 4:20:18
3-28 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
11 Control Out 1) Disconnect 4 Connecters From
Ass'y Control Out.
2) Unscrew and remove 1 mounting screw
in Control Out. (Use +Screw Driver)
3) Separate Ass'y Control Out.
NS1004PXEA_E_SM_33124A(1)_1.indd 28 2011-04-29 4:20:19
Samsung Electronics 3-29
Disassembly and Reassembly
No Parts Procedure Remark
12 Ass'y 4way Valve 1) Purge the Coolant first.
2) Unscrew and remove 2 mounting screws
in Service Valve. (Use +Screw Driver)
3) Separate the pipe from the Entrance/Exit
using a welder.
When removing the compressor,
Heat Exchanger, and Pipe, purge the
Coolant inside the Compressor
completely and remove the pipe
with a welding flame.
13 Ass;y EEV Valve 1) Unscrew and remove 2 mounting screws
in Service Valve. (Use +Screw Driver)
2) Separate the pipe from the Entrance/Exit
using a welder.
NS1004PXEA_E_SM_33124A(1)_1.indd 29 2011-04-29 4:20:19
3-30 Samsung Electronics
Disassembly and Reassembly
No Parts Procedure Remark
14 Compressor 1) Unscrew and remove 1 mounting nut
in Cover Terminal. (Use Adjustable Wrench)
2) Separate the Compressor Felt Sound.
3) As shown in the picture, unscrew and
remove 3 mounting screws from the
bottom. (Use Adjustable Wrench)
NS1004PXEA_E_SM_33124A(1)_1.indd 30 2011-04-29 4:20:20
Samsung Electronics 3-31
Disassembly and Reassembly
No Parts Procedure Remark
15 Cond Out 1) Unscrew and remove 3 screws
on each side of the Assy Cond Out.
(Use +Screw Driver)
NS1004PXEA_E_SM_33124A(1)_1.indd 31 2011-04-29 4:20:20
4-1 Samsung Electronics
4. Troubleshooting
4-1 Setting an indoor unit address and installation option
Set the indoor unit address and installation option with remote controller option.
Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the
same time.You need to set twice when setting indoor unit address and installation option.
4-1-1 The procedure of setting option
High Temp Button High Fan Button
Mode change
Low Temp Button
Low Fan Button
Entering mode for
setting option
Option setting mode
Step 1
Entering mode to set option
1. Remove batteries from the remote controller.
2. Insert batteries and enter the option setting mode while pressing High Temp button and Low Temp button .
3. Check if you have entered the option setting status.
Step 2
The procedure of option setting
After entering the option setting status, select the option as listed below.
Option setting is available from SEG1 to SEG 24
SEG1, SEG7, SEG13, SEG19 are not set as page option.
Set the SEG2~SEG6, SEG8~SEG12 as ON status and SEG14~18, SEG20~24 as OFF status.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
0 X X X X X 1 X X X X X
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
2 X X X X X 3 X X X X X
On(SEG1~12) Of(SEG13~24)
NS1004PXEA_E_SM_33124A(1)_1.indd 1 2011-04-29 4:20:21
Samsung Electronics 4-2
Troubleshooting
4-1-2 The procedure of setting option
Option setting Status
1. Setting SEG2, SEG3 option
Press Low Fan button() to enter SEG2 value.
Press High Fan button() to enter SEG3 value.
Each time you press the button, will be selected in rotation.

2. Setting Cool mode
Press Mode button to be changed to Cool mode in the ON status.
3. Setting SEG4, SEG5 option
Press Low Fan button() to enter SEG4 value.
Press High Fan button() to enter SEG5 value.
Each time you press the button, will be selected in rotation.
4. Setting Dry mode
Press Mode button to be changed to DRY mode in the ON status.
5. Setting SEG6, SEG8 option
Press Low Fan button() to enter SEG6 value.
Press High Fan button() to enter SEG8 value.
Each time you press the button, will be selected in rotation.
6. Setting Fan mode
Press Mode button to be changed to FAN mode in the ON status.
7. Setting SEG9, SEG10 option
Press Low Fan button() to enter SEG9 value.
Press High Fan button() to enter SEG10 value.
Each time you press the button, will be selected in rotation.
8. Setting Heat mode
Press Mode button to be changed to HEAT mode in the ON status.
9. Setting SEG11, SEG12 option
Press Low Fan button() to enter SEG11 value.
Press High Fan button() to enter SEG12 value.
Each time you press the button, will be selected in rotation.
10. Setting Auto mode
Press Mode button to be changed to AUTO mode in the OFF status.
SEG2 SEG3
SEG4 SEG5
SEG6 SEG8
SEG9 SEG10
SEG11 SEG12
NS1004PXEA_E_SM_33124A(1)_1.indd 2 2011-04-29 4:20:24
4-3 Samsung Electronics
Troubleshooting
The procedure of setting option (cont.)
Option setting Status
11. Setting SEG14, SEG15 option
Press Low Fan button() to enter SEG14 value.
Press High Fan button() to enter SEG15 value.
Each time you press the button, will be selected in rotation.

12. Setting Cool mode
Press Mode button to be change to Cool mode in the OFF status.
13. Setting SEG16, SEG17 option
Press Low Fan button() to enter SEG16 value.
Press High Fan button() to enter SEG17 value.
Each time you press the button, will be selected in rotation.
14. Setting Dry mode
Press Mode button to be change to Dry mode in the OFF status.
15. Setting SEG18, SEG20 option
Press Low Fan button() to enter SEG18 value.
Press High Fan button() to enter SEG20 value.
Each time you press the button, will be selected in rotation.
16. Setting Fan mode
Press Mode button to be change to Fan mode in the OFF status.
17. Setting SEG21, SEG22 option
Press Low Fan button() to enter SEG21 value.
Press High Fan button() to enter SEG22 value.
Each time you press the button, will be selected in rotation.
18. Setting Heat mode
Press Mode button to be change to HEAT mode in the OFF status.

19. Setting SEG23, SEG24 mode
Press Low Fan button() to enter SEG23 value.
Press High Fan button() to enter SEG24 value.
Each time you press the button, will be selected in rotation.
SEG14 SEG15
SEG16 SEG17
SEG18 SEG20
SEG21 SEG22
SEG23 SEG24
NS1004PXEA_E_SM_33124A(1)_1.indd 3 2011-04-29 4:20:27
Samsung Electronics 4-4
Troubleshooting
Step 3
Check the option you have set
After setting option, press button to check whether the option code you input is correct or not.
Step 4
Input option
Press operation button with the direction of remote control for set.
For the correct option setting, you must input the option twice.
Step 5
Check operation
1. Reset the indoor unit by pressing the RESET button of indoor unit or outdoor unit.
2. Take the batteries out of the remote controller and insert them again and then press the operation button.

NS1004PXEA_E_SM_33124A(1)_1.indd 4 2011-04-29 4:20:28


4-5 Samsung Electronics
Troubleshooting
4-1-3 Setting an indoor unit address (MAIN/RMC)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply
in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Before installing the indoor unit, assign an address to the indoor unit according
to the air conditioning system plan.
4. Assign an indoor unit address by wireless remote controller.
- The initial setting status of indoor unit ADDRESS(MAIN/RMC) is "0A0000-100000-200000-300000".
- There is no need to assign extra ADDRESS for 1:1 installation between indoor unit and outdoor unit.
- Main address will be set automatically and manual address setting will be only available when outdoor unit option status is
set as 'Manual address'
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
You can set the Main address from 0~3 range and if you input other numbers, 'communication error' will occur.
When A~Fis entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
If you set the SEG 3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the option value of SEG5~6.
If you set the SEG 9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value of SEG11~12.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
Setting Main
address
RESERVED RESERVED
The unit digit of an
indoor unit
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
0 A
0
No Main
address
0~3
A single
digit
1
Main
address
setting
mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
RESERVED
Setting RMC
address
RESERVED
Group channel(*16) Group address
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0
No RMC
address
RMC1 0~2 RMC2 0~F
1
RMC
address
setting
mode
Indoor Unit
1(L)
F2
F1 2(N)
NS1004PXEA_E_SM_33124A(1)_1.indd 5 2011-04-29 4:20:29
Samsung Electronics 4-6
Troubleshooting
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply
in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air conditioner.
- The default setting of an indoor unit installation option is 02000-100000-
200000-300000.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is more
than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to 'USE + 3minute delay' even if the drain pump is set to 0.
1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using flter(SEG18) will be set to '1000hour' even if the SEG18 is set to
exept for 2 or 6.
If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as "indoor 1".
4WAY MODEL : Even when the value of Heating setting compensation(SEG21) is set to '0', it wil be recognized as '5C'.





4-1-4 Setting an indoor unit installation option (suitable for the condition of each installation location)
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 RESERVED
Exterior temperature
sensor
Central control RESERVED
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 Drain pump RESERVED RESERVED RESERVED Master / Slave
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
External control
output
S-Plasma ion Buzzer
Number of hours
using flter
SEG19 SEG20 SEG21
3
Individual control of a
remote controller
Heating setting
compensation
Indoor Unit
1(L)
F2
F1 2(N)
NS1004PXEA_E_SM_33124A(1)_1.indd 6 2011-04-29 4:20:29
4-7 Samsung Electronics
Troubleshooting
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
RESERVED
Use of external
temperature sensor
Use of central
control
RESERVED
Remote
Controller
Display
Indication
and
Details
Indication Details Indication Details Indication Details Indication Details
0 2
0 Disuse 0 Disuse
1 Use 1 Use
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE Use of drain pump
RESERVED RESERVED RESERVED
Master / Slave
Remote
Controller
Display
Indication
and
Details
Indication Details Indication Details Indication Details
1
0 Disuse 0 slave
1 Use 1 master
2
Use +
3minute
delay
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation PAGE
Use of external
control
Setting the output
of external control
S-Plasma ion Buzzer control
Number of hours
using flter
Remote
Controller
Display
Indication
and
Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
2
0 Disuse 0
Thermo
on
0 Disuse 0
Use of
buzzer
2
1000
Hour
1
ON/OFF
Control
1
Operation
on
1 Use 1
Non use
of buzzer
6
2000
Hour
2
OFF
Control
Option SEG19 SEG20 SEG21
Explanation PAGE
Individual control of
a remote controller
Heating setting
compensation
Remote
Controller
Display
Indication
and
Details
Indication Details Indication Details Indication Details
3
0 or 1 Indoor 1
0 Disuse
2 Indoor 2
1 2C
3 Indoor 3
2 5C
4 Indoor 4
NS1004PXEA_E_SM_33124A(1)_1.indd 7 2011-04-29 4:20:30
Samsung Electronics 4-8
Troubleshooting
4-1-5 Changing a particular option
You can change each digit of set option.
When changing a digit of an indoor unit address setting option, set the SEG3 as A.
When changing a digit of indoor unit installation option, set the SEG3 as 2.
Ex) When setting the 'buzzer control' into disuse status.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
The option
mode you want
to change
The tens digit of
an option SEG
you will change
The unit digit of
an option SEG
you will change
The changed
value
Indication 0 D 2 1 7 1
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
The option mode
you want to change
The tens digit of an
option SEG you will
change
The unit digit of an
option SEG you will
change
The changed value
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0 D
Option
mode
0~F
Tens digit
of SEG
0~9
Unit digit
of SEG
0~9
The
changed
value
0~F
NS1004PXEA_E_SM_33124A(1)_1.indd 8 2011-04-29 4:20:31
4-9 Samsung Electronics
Troubleshooting
4-1-6 Option code for each model
Model SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Remocon
display
NS0714DXEA 0 1 4 0 7 7 1 6 6 0 C 8
NS0714PXEA 0 1 4 0 7 7 1 3 6 0 D 8
NS0904DXEA 0 1 4 0 7 7 1 5 6 0 E 8
NS0904PXEA 0 1 4 0 7 7 1 5 6 2 1 9
NS1004DXEA 0 1 4 0 7 7 1 5 6 2 1 9
NS1004PXEA 0 1 4 0 7 7 1 5 7 2 3 9
NS1004ZXEA 0 1 4 0 7 7 1 5 6 2 4 9
NS1254DXEA 0 1 4 0 7 7 1 5 7 2 3 A
NS1254PXEA 0 1 4 0 7 7 1 5 7 2 3 A
NS1404DXEA 0 1 4 0 7 7 1 5 7 2 3 B
NS1404PXEA 0 1 4 0 7 7 1 5 6 2 4 B
Model SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Remocon
display
NS0714DXEA 2 7 4 7 5 0 3 7 0 0 0 0
NS0714PXEA 2 7 4 7 5 0 3 7 0 0 2 0
NS0904DXEA 2 7 5 A 6 4 3 7 0 0 2 0
NS0904PXEA 2 7 5 A 6 4 3 7 0 0 4 0
NS1004DXEA 2 7 6 4 7 0 3 7 0 0 4 0
NS1004PXEA 2 7 6 4 7 0 3 7 0 0 2 0
NS1004ZXEA 2 7 6 4 7 0 3 7 0 0 4 0
NS1254DXEA 2 7 7 D 8 C 3 7 0 0 4 0
NS1254PXEA 2 7 7 D 8 C 3 7 0 0 4 0
NS1404DXEA 2 7 8 C A 0 3 7 0 0 4 0
NS1404PXEA 2 7 8 C A 0 3 7 0 0 4 0
NS1004PXEA_E_SM_33124A(1)_1.indd 9 2011-04-29 4:20:32
MEMO
Samsung Electronics 4-10
NS1004PXEA_E_SM_33124A(1)_1.indd 10 2011-04-29 4:20:32
Samsung Electronics
Error Mode
Cause Measures
Product operation with error
Diagnosis method
Operation Defrost Timer Filter
Outdoor
heat exchanger
compressor
Outdoor
heat exchanger fan
Indoor
heat exchanger fan
X X X Power reset - operation-off operation-off operation-off -
X X X
Error of roomtemperature sensor in the indoor
unit (Open/Short)
Check indoor temperature sensor connection.
Check indoor temperature sensors resistance value to see if its short/open.
operation-off operation-off operation-off page 4-17
X X
Error of heat exchanger IN/OUT sensor in the
indoor unit (Open/Short)
Check EVA IN/OUT sensor connection.
Check EVA IN/OUT sensors resistance value to see if its short/open.
operation-off operation-off operation-off page 4-18
X X X Error of fan motor in the indoor unit
Check the connection of motor connector
Check the speed of the motor fan
operation-off operation-off operation-off page 4-19
X X
Error of the outdoor temperature sensor
Error of the condensor temperature sensor
Error of the discharge temperature sensor
Check indoor temperature sensor connection.
Check indoor temperature sensors resistance value to see if its short/open.
operation-off operation-off operation-off -
X X
No communication for 2 minutes between indoor
and outdoor unit (communication error for more
than 2 minutes)
Check connection between indoor and outdoor heat exchangers communication
cables
operation-off operation-off operation-off page 4-20
X Error of outdoor unit Check error occurred with outdoor heat exchanger. operation-off operation-off operation-off -
X X Detection of the float switch
Check float switch connection.
Check whether the drain has been filled with water.
operation-off operation-off operation-off page 4-21
X EEPROMerror Check if there is damage with EEPROMcomponent. operation-off operation-off operation-off page 4-22
EEPROMoption error
Check the indoor model to set the options.
Inspection for match between indoor and outdoor machine models
operation-off operation-off operation-off -
4-2 Items to check before diagnostics
4-2-1 Four directions cassette type
4-11
: On : Blink X : Off
NS1004PXEA_E_SM_33124A(1)_1.indd 11-12 2011-04-29 4:21:19
4-12 Samsung Electronics
Troubleshooting
4-2-2 Test run mode and View mode
Display Option Key
KEY KEY operation 7-segment display
K1
Press once : Heating test run BLANK BLANK
Press twice : Defrost test run BLANK BLANK
K2 Press once : Cooling test run BLANK BLANK
K3 Reset
K4 View mode Refer to View mode display
VIEW mode display
Number
of press
Display contents
Display
Units
Segment 1 Segment 2 Segment 3 Segment 4
1 Order frequency 1 Three digits Two digits One digit Hz
2 Current frequency 2 Three digits Two digits One digit Hz
3 Number of indoor heat exchangers 3 Three digits Two digits One digit Hz
4 Out sensor 4 Two digits One digit First decimal C
5 Discharge sensor 5 Two digits One digit First decimal C
6 OLP sensor 6 Two digits One digit First decimal C
7 Cond sensor 7 Two digits One digit First decimal C
8 Current 8 Two digits One digit First decimal C
9 Fan RPM 9 Three digits Two digits One digit rpm
10 Target discharge temperature A Three digits Two digits One digit C
11 EEV B Three digits Two digits One digit step
12 Total indoor heat exchanger capacity C Two digits One digit First decimal kW
13 Protection control D
0 : air conditioning
1 : heating
Protection control
0 : no protection
control
1 : freezing
2 : non-stop
defrosting
3 : over-load
4 : discharge
Frequency state
0 : Normal
1 : Hold
2 : Down
3 : Up_limit
4 : Sown_limit
-
14
Group address of indoor heat
exchanger
E Three digits Two digits One digit -
15 S/W check F - - - -
7-segment display
Key Switch
NS1004PXEA_E_SM_33124A(1)_1.indd 12 2011-04-29 4:20:33
Samsung Electronics 4-13
Troubleshooting
4-2-3 ECO mode(Power save)
Mode
Display ECO mode lamp
Segment 1 Segment 2 Segment 3 Segment 4 RED color
ECO mode BLANK BLANK BLANK BLANK On
Exit ECO mode Press K3 to exit Off
ECO mode lamp : RED
NS1004PXEA_E_SM_33124A(1)_1.indd 13 2011-04-29 4:20:33
4-14 Samsung Electronics
Troubleshooting
4-2-4 Troubleshooting for outdoor unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.
No.
LED Display
Displayed
PCB Assy
Meaning Remarks Error Code
Red Green Yellow
- MAIN/INVERTER
Normal operation
(MAIN : IndoorOutdoor : Green ON)
(INVERTER : MAIN PCBINVERTER PCB :
Green ON)
-
1 MAIN
Unit quantity miss matching between
indoor and outdoor.
Check indoor quantity
setting in outdoor (Refer
to page 17.)
E201
2

MAIN/INVERTER
Abnormal state, no communication
between Indoor and Outdoor Main PCB
Check electrical
connection and setting
E202

3 MAIN/INVERTER
1min. Time out of communcation
error(MainInverter)
Check electrical
connection and setting
E203
4 MAIN Outdoor temp sensor error
Check Outdoor sensor
Open/Short
E221
5 MAIN Cond. temp sensor error
Check Cond. sensor
Open/Short
E231
6 MAIN Discharge temp sensor error
Check Discharge sensor
Open/Short
E251
7 MAIN OLP Sensor Error
Check OLP sensor
Open/Short
E320
8 MAIN
Detection of Outdoor Freezing when
Comp. Stop
Check Outdoor Cond. E403
9 MAIN
Protection of Outdoor Overload when
Comp. Stop
Check Comp. when it start E404
10 MAIN
Discharge temperature of a compressor
in an outdoor unit is overheated.
E416
11 MAIN
Heating operation is not available since
the outdoor air temperature is over 30C.
Heating E440
Cooling operation is not available since
the outdoor air temperature is lower than
-5C.
Cooling E441
12 MAIN/INVERTER Outdoor unit BLDC Fan 1 or Fan 2 error
FAN1 error E458
FAN2 error E475
13 MAIN/INVERTER Comp. Starting error E461
14 MAIN Primary Current Trip error E462
15 MAIN Over current trip / PFC over current error Check OLP sensor E463
16 MAIN/INVERTER IPM(IGBT Module) Over Current(O.C) E464
17 MAIN/INVERTER Comp. Over load error E465
18 MAIN/INVERTER DC-Link voltage under/over error
Check AC Power or
DC_Link voltage
E466
19 MAIN/INVERTER Comp. wire missing error Check Comp. wire E467
20 MAIN/INVERTER Current sensor error
Check Outdoor Inverter
PBA
E468
21 MAIN Outdoor EEPROM error
Check Outdoor EEPROM
date
E471
22 MAIN/INVERTER
IPM(IGBT Module) or PFCM Temperature
sensor Error
Check Outdoor Inverter
PBA
E474
23 MAIN/INVERTER PFC Overload Error
Check Outdoor Inverter
PBA
E484
24 MAIN/INVERTER IPM is over heated.
Check Outdoor Inverter
PBA
E500
25 MAIN GAS Leak error
Check indoor and outdoor
unit model
E554
26 MAIN
Capacity miss match between indoor and
outdoor
Check indoor and outdoor
unit model
E556
27 MAIN
Option code miss matching among the
indoors (only for DPM)
Check indoor option code E557
Off Blink On
NS1004PXEA_E_SM_33124A(1)_1.indd 14 2011-04-29 4:20:34
Samsung Electronics 4-15
Troubleshooting
4-2-5 Wired remote controller
- If an error occurs, ( ) icon will be displayed on the wired remote controller.
- Press the Test button to see the error code.
Error mode Contents Measure
Product operation in
error condition
Error type
Outdoor unit/
Compressor/Indoor unit
Indoor unit communication
error
Check the communication cable of indoor unit. Check
the DC output voltage at the communication terminal
Operation Off
Communication
error
Indoor unit/outdoor unit
communication time-out error:
errors in more than 6 packets
Check the outdoor communication cable connection.
Check DC output voltage and the communication
terminal
Operation Off
Communication
error
Indoor temperature sensor
(open/short error)
Check indoor unit room temperature sensor. Check
indoor unit PCB connector CN41 (White)
Operation Off
Indoor sensor
error
Indoor unit Eva In sensor
(Open/Short)
Check indoor unit pipe sensor. Check indoor PCB
connector CN41(White)
Operation Off
Indoor sensor
error
Indoor unit Eva In sensor
disconnection
Check the disconnection of indoor unit pipe sensor Operation Off
Indoor sensor
error
Indoor floating switch
secondary detection
Check indoor unit float sensor. Check indoor PCB
connector CN5 (black)
Operation Off
Self diagnostic
error
Indoor/outdoor
communication error (1 min)
Check the communication connection between
indoor and outdoor units. Check the power line and
communication cable connection status
Operation Off
Communication
error
Communication error between
indoor/outdoor INVMAIN
MICOM (1 min)
Check MAIN MICOM
Check INVERTER MICOM
-
Communication
error
Outdoor temperature sensor
error
Check sensor connection status
Check sensor location
Check sensor resistance
Operation Off
Outdoor sensor
error
COND temperature sensor error
Check sensor connection status
Check sensor location
Check sensor resistance
Operation Off
Outdoor sensor
error
[Inverter] Emission temperature
sensor error
Check sensor connection status
Check sensor location
Check sensor resistance
Operation Off
Outdoor sensor
error
Emission temperature
excessively high
No error (DISCHARGE temperature control) -
Outdoor unit
protection
control error
Heating operation blocked
Check the operation setting state
Check temperature sensor
Operation Off
Self diagnostic
error
Cooling operation blocked
Check the operation setting state
Check temperature sensor
Operation Off
Self diagnostic
error
Outdoor fan 1 error
Check input power connection status
Check the connection status between the motor and
outdoor unit PCB
Check indoor/outdoor fuse
Operation Off
Self diagnostic
error
[Inverter] Compressor startup
error
Check the compressor connection status
Check the resistance between difference phases of the
compressor
Operation Off
Outdoor unit
protection
control error
[Inverter] Total current error/
PFC over current error
Check the input power
Check the coolant charging status
Check the normal operation of outdoor fan
Operation Off
Outdoor unit
protection
control error
NS1004PXEA_E_SM_33124A(1)_1.indd 15 2011-04-29 4:20:34
4-16 Samsung Electronics
Troubleshooting
Wired remote controller (cont.)
Error mode Contents Measure
Product operation in
error condition
Error type
Outdoor unit/
Compressor/Indoor
unit
[Inverter] IPM over current
error
Check coolant charging
Check the compressor connection status and normal
operation
Check the obstacles around the indoor and outdoor units
Check whether the outdoor unit service valve is open
Check whether the indoor/outdoor installation pipe/
wiring are correct
Operation Off
Outdoor unit
protection
control error
Compressor V limit error
Check the compressor connection status
Check the resistance between difference phases of the
compressor
Operation Off
Outdoor unit
protection
control error
DC LINK over/low voltage error
Check input power
Check AC power connection
Restart in 3 minutes
Outdoor unit
protection
control error
[Inverter] Compressor rotation
error
Check the compressor connection status
Check the resistance between difference phases of the
compressor
Operation Off
Outdoor unit
protection
control error
[Inverter] Current sensor error
Check EEPROM DATA
Check the normal operation of PCB
Operation Off
Outdoor unit
protection
control error
[Inverter] DC LINK voltage
sensor error
Check the input power connection
Check the status of RY21 and R200 in the INVERTER PCB
Operation Off
Outdoor unit
protection
control error
[Inverter] OTP error
Check EEPROM DATA
Check the normal operation of PCB
Operation Off
Outdoor unit
protection
control error
AC ZERO CROSSING SIGNAL
OUT error
Check the input power status Operation Off
Outdoor unit
protection
control error
Compressor LOCK error
Check the compressor connection status
Check the resistance between difference phases of the
compressor
Operation Off
Outdoor unit
protection
control error
Outdoor fan 2 error
Check the input power connection status
Check the connection status of the motor and the
outdoor unit PCB
Check the indoor/outdoor unit fuse
Operation Off
Self diagnostic
error
Gas leak error
Check the coolant charging status
Check the indoor EVA sensor
Check if the outdoor unit service value is open
Check that the indoor/outdoor installation pipe/wiring
are correct
Operation Off
Self diagnostic
error
Capacities not matched Check the option code of the indoor unit Operation Off
Outdoor unit
protection
control error
Communication error between
the indoor unit and wired
remote controller
Check the connection wire between the indoor unit and
the wired remote controller
Normal operation
Wired remote
controller error
Communication error between
the Master and Slave wired
remote controllers
Check the option switch for defining the Master and
Slave (only one Master and one Slave can exist)
Normal operation
Wired remote
controller error
COM1/COM2 cross installation
error
Check that wired remote controller is connected to the
COM2 terminal of the indoor unit
Normal operation
Wired remote
controller error
Wired remote controller COM2
option setting error
Check that Com1, Com2 setting DIP switch is set to Com2 Normal operation
Wired remote
controller error
NS1004PXEA_E_SM_33124A(1)_1.indd 16 2011-04-29 4:20:35
Samsung Electronics 4-17
Indoor unit display X (Operation) (Defrost) X (Timer) X (Filter)
Symptom In case of open or short circuit of indoor temperature sensor
Failure Short or leakage of the corresponding sensor
Yes
No
No
In this case, is the resistance
value out of range in the temperature
table on the right?
Yes
Is indoor temperature
sensor disconnected from the
connector in PCB?
Restart the system after replacing the PCB
Restart the system after connecting
to the PCB connector
Indoor temperature sensor
failure (replace)
Remove the indoor temperature sensor
connector from the PCB and measure the
resistance between two terminals
4-3 Troubleshooting by symptoms
4-3-1 Indoor temperature sensor (open/short)
Current
temperature
(C)
Resistance
(k)
40 5.800
35 6.900
30 8.300
25 10.00
20 12.10
15 14.70
10 18.00
5 22.00
0 28.30
-5 33.90
-10 42.30
<Temperature sensor
resistance value>
NS1004PXEA_E_SM_33124A(1)_1.indd 17 2011-04-29 4:20:35
4-18 Samsung Electronics
Troubleshooting
Yes
No
No
In this case, is the resistance
value out of range in the temperature table
on the right?
Yes
Is the indoor heat exchanger
temperature sensor connector disconnected
from the PCB?
Restart the system after replacing the PCB
Restart the system after
connecting the connector to PCB
Failure of the indoor heat
exchanger temperature sensor
(replace)
Remove the indoor heat exchanger
temperature sensor connector from
the PCB and measure the resistance
between two terminals
Indoor unit display
(Operation) (Defrost) X (Timer) X (Filter)
Symptom Short or open circuit of indoor heat exchanger temperature sensor
Failure Short or open circuit in the corresponding sensor
4-3-2 Indoor heat exchanger temperature sensor (open/short)
Current
temperature
(C)
Resistance
(k)
40 5.800
35 6.900
30 8.300
25 10.00
20 12.10
15 14.70
10 18.00
5 22.00
0 28.30
-5 33.90
-10 42.30
<Temperature sensor
resistance value>
NS1004PXEA_E_SM_33124A(1)_1.indd 18 2011-04-29 4:20:35
Samsung Electronics 4-19
Troubleshooting
Indoor unit display
X (Operation) X (Defrost) (Timer) X (Filter)
Symptom Indoor unit fan does not run /Runs at excessive high speed and stops
Failure Check if the motor connector is disconnected/ check the motor fan assembly status
4-3-3 Indoor FAN error
Yes
No
Yes
Is there foreign substance
stuck in the motor fan?
Yes Is the motor connector
disconnected from the PCB?
Replace the PCB and restart the unit
Connect the connector to
PCB and restart the unit
Remove the foreign substance
and restart the unit
NS1004PXEA_E_SM_33124A(1)_1.indd 19 2011-04-29 4:20:35
4-20 Samsung Electronics
Troubleshooting
Indoor unit display
X (Operation) (Defrost) (Timer) X (Filter)
Symptom Communication error between the indoor and outdoor unit for two minutes
Failure Communication error between the indoor unit and outdoor unit
4-3-4 Communication error after finishing Tracking
No
Yes
No
Yes
Is there a response from the indoor PCB?
(LED01 (RED) is not ON)
In this case, is the
voltage waveform between the lines square
wave with amplitude over 0.7V as shown
in the following picture?
+0.7V
-0.7V
Good
Bad
Check the communication cable and
replace the indoor unit PCB
Remove the communication cable
connecting the outdoor unit to indoor unit,
and measure the signal on LINE 2 of the
outdoor unit with a scope
Reconnect the cable connecting
the outdoor unit to the indoor unit
and restart the unit.
If the communication still doesnt work,
replace the indoor unit PCB.
Check the communication
cable in the outdoor unit PCB
and replace the PCB
LED01
NS1004PXEA_E_SM_33124A(1)_1.indd 20 2011-04-29 4:20:35
Samsung Electronics 4-21
Troubleshooting
Indoor unit display
X (Operation) X (Defrost) (Timer) (Filter)
Symptom The indoor unit floating sensor is open and that state is maintained for more than one minute
Failure
Increase in the drain pan water level due to failure of the indoor unit drain pump,
or float sensor failure
4-3-5 Indoor unit float sensor error
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Remove the floating sensor
connector connected to the indoor unit
PCB and the resistance measured between the
two terminals. Is the resistance ?
(open circuit)
Is the water level in the drain pan high?
Does drain pump operate
when compressor operates?
Same error occurs again
No
Drain pump PCB
Is the terminal voltage around
AC 220V?
Is the water level in
drain pan decreasing?
Reset the indoor unit power and
check the operation of the drain pump.
(it vibrates when operating)
Normal operation
Replace the indoor unit PCB
Reassemble the floating sensor
connector and reset the outdoor unit
power. (Indoor unit power reset is
required)
Normal operation
Replace the floating sensor
when it fails and reset the
indoor unit power
Replace the drain pump
Replace the drain pump Replace the indoor unit PCB
Error occurs
Float sensor error is cleared only
when the indoor power is reset
NS1004PXEA_E_SM_33124A(1)_1.indd 21 2011-04-29 4:20:36
Samsung Electronics 4-22
Troubleshooting
Restart the unit after replacing the PCB
Indoor unit display
(Operation) (Defrost) (Timer) X (Filter)
Symptom EEPROM circuit failure
Failure EEPROM component failure, EEPROM circuit parts missing/damaged/soldering failure
4-3-6 EEPROM circuit failure
No
Yes
Are the EEPROM circuit
components in good conditions?
(missing components / damage /
soldering failure)
Replace the PCB if the restart fails
NS1004PXEA_E_SM_33124A(1)_1.indd 22 2011-04-29 4:20:36
Samsung Electronics 4-23
Troubleshooting
4-3-7 Outdoor unit is not powered on Initial diagnosis (RCSSSXGA : 3phase)
1. Check items
1) Is the power supply voltage 380V?
2) Is the AC power connected correctly?
3) Are the LEDs in the main PCB and inverter PCB of the outdoor unit ON?
4) Is the input power voltage of the indoor unit 220V?
5) Is the wired remote controller connected correctly?
2. Check procedure
Yes
Turn off the main power switch
(circuit break of power outlet) and turn on
again after 30 seconds.
Check the input power
No Is the outdoor unit power
supply (N-R, N-S, N-T) 220Vac?
Yes
Check connection of the outdoor unit
terminal block
No
Is the outdoor unit power
voltage (L-N) 220Vac?
Yes
Check the connection wires and
connectors of the indoor and outdoor units
No
Is the indoor unit power supply
voltage (L-N) 220Vac?
Yes
Replace the PCB of the indoor unit if
the PCB (Transformer, fuse, pcd, etc.) fails
No Is the indoor unit power supply
voltage (V1-V2) 12Vdc?
Yes
Replace the wired remote controller
No
Does the air conditioner
operate when pressing ON/OFF button of the
wired remote controller?
cont.
NS1004PXEA_E_SM_33124A(1)_1.indd 23 2011-04-29 4:20:36
4-24 Samsung Electronics
Troubleshooting
Outdoor unit is not powered on Initial diagnosis (RCSSSXGA : 3phase) (cont.)
Yes
Reconfigure the option DIP switches
No
Are the option DIP switches
inside the wired remote controller configured
correctly?
cont.
No
Check the system depending
on the error display
Yes
Is there an error
message displayed on the wired remote
controller display?
Check the target temperature
NS1004PXEA_E_SM_33124A(1)_1.indd 24 2011-04-29 4:20:36
Samsung Electronics 4-25
Troubleshooting
Outdoor unit is not powered on Initial diagnosis (RCSSSXES : 1phase)
1. Check items
1) Is the power supply voltage 220V?
2) Is the AC power connected correctly?
3) Are the LEDs in the main PCB and inverter PCB of the outdoor unit ON?
4) Is the input power voltage of the indoor unit 220V?
5) Is the wired remote controller connected correctly?
2. Check procedure
Yes
Turn off the main power switch
(circuit break of power outlet) and turn on
again after 30 seconds.
Check the input power
No Is the outdoor unit power
supply (L-N) 220V?
Yes
Check the connection of the terminal block
No Is the outdoor unit power
voltage (L-N) 220V?
Yes
Replace the inverter PBA
No
Is the voltage between
the terminal 2 (~) and 4 (~) of the
bridge diode 220V?
Yes
Replace the fuse
No
Is the fuse connected?
Yes
Replace the inverter PBA
No
Is the resistance value of R001 200?
Cont.
NS1004PXEA_E_SM_33124A(1)_1.indd 25 2011-04-29 4:20:36
4-26 Samsung Electronics
Troubleshooting
Yes
Outdoor unit is not powered on Initial diagnosis (RCSSSXES : 1phase) (cont.)
Yes
Connect the reactor
No
Is the reactor connector
connected correctly?
Replace the PBA.
Cont.
NS1004PXEA_E_SM_33124A(1)_1.indd 26 2011-04-29 4:20:36
MEMO
Samsung Electronics 4-27
NS1004PXEA_E_SM_33124A(1)_1.indd 27 2011-04-29 4:20:36
5-1 Samsung Electronics
1
5
6
2
20
9
9-1
23
26
19
8
7
21
13
17
15
16
14
18
12
10
11
3
22
25
24
4
27
5. Exploded Views and Parts List
5-1 Indoor Unit
NS1004PXEA_E_SM_33124A(1)_2.indd 1 2011-04-29 4:23:09
Samsung Electronics 5-2
Exploded Views and Parts List
Parts List
1 DB61-04515A CASE-CABI IN PP,T0.7,W836.4,L836.4 1 - - - - SNA
DB61-04514A CASE-CABI IN PP,T0.7,W836.4,L836.4 - 1 1 - - SNA
DB61-04468A CASE-CABI IN PP,T0.7,W836.4,L836.4 - - - 1 1 SNA
2 DB61-04495A PLATE-HANGER GI-SGCC, T0.6 4 4 4 4 4 SA
3 DB63-02710A CUSHION-CABI IN EPS,T10,W832.6,L832.6 1 - - - - SNA
DB63-02709A CUSHION-CABI IN EPS,T10,W832.6,L832.6 - 1 1 - - SNA
DB63-02694A CUSHION-CABI IN EPS,T10,W832.6,L832.6 - - - 1 1 SNA
4 DB90-05821A ASS'Y BRACKET MOTOR ASS'Y 1 1 1 1 1 SNA
5 DB90-05829A ASS'Y COVER-PIPE ASS'Y 1 1 1 1 1 SNA
6 DB94-03171A ASS'Y DRAIN-SOCKET ASS'Y 1 - - - - SA
DB94-02693A ASS'Y DRAIN-SOCKET ASS'Y - 1 1 1 1 SA
7 DB61-04491A PLATE-COVER CONTROL GI-SGCC, T0.5 1 1 1 1 1 SNA
8 DB93-10635A ASS'Y PCB MAIN-IN ASS'Y 1 1 1 1 1 SA
9 DB93-10648A ASS'Y CONTROL IN ASS'Y 1 1 1 1 1 SNA
9-1 DB95-04459A ASS'Y THERMISTOR IN-ROOM ASS'Y 1 1 1 1 1 SA
10 DB61-04496A CASE-BELL MOUTH HIPS,T0.2,448.5,499 1 1 1 1 1 SA
11 DB63-02702B COVER-SAFETY ABS,T3.0,414,379 1 1 1 1 1 SA
12 DB94-02667C ASS'Y DRAIN PAN ASS'Y 1 1 1 1 1 SA
13 DB61-04498A CASE-PUMP HIPS,T0.2,139,98.6 1 1 1 1 1 SNA
14 DB63-02703A COVER-PUMP HIPS,T0.2,81.2,57.9 1 1 1 1 1 SA
15 DB67-00982C DRAIN-PUMP ASS'Y 1 1 1 1 1 SA
16 DB73-00521A RUBBER-CAP PUMP EPDM 1 1 1 1 1 SA
17 DB73-00523A RUBBER-BASE PUMP NBR 1 1 1 1 1 SA
18 DB95-04462A ASS'Y SENSOR FLOAT ASS'Y 1 1 1 1 1 SA
19 DB31-00578A MOTOR FAN FMC6531SSF - 1 1 - - SA
DB31-00578B MOTOR FAN FMC6531SSF 1 - - - - SA
DB31-00577A MOTOR FAN DAI33585ZLB/SEC - - - 1 1 SA
20 DB94-03093A ASS'Y FAN-TURBO ASS'Y 1 - - - - SA
DB94-02718A ASS'Y FAN-TURBO ASS'Y - 1 1 - - SA
DB94-02663A ASS'Y FAN-TURBO ASS'Y - - - 1 1 SA
21 DB60-00406A FASTENER-NUT FLANGE NSWR3,M6 1 1 1 1 1 SA
22 DB61-04517B CASE-PARTITION EVAP HIPS,T2.0 1 - - - - SNA
DB61-04516B CASE-PARTITION EVAP HIPS,T2.0 - 1 1 - - SNA
DB61-04511B CASE-PARTITION EVAP HIPS,T2.0 - - - 1 - SNA
DB61-04501B CASE-PARTITION EVAP HIPS,T2.0 - - - - 1 SNA
23 DB61-04518A HOLDER-EVAP STS430,T0.6 2 - - - - SNA
DB61-04519A HOLDER-EVAP STS430,T0.6 - 2 2 - - SNA
DB61-02669B HOLDER-EVAP STS430,T0.6 - - - 2 - SNA
DB61-04509A HOLDER-EVAP STS430,T0.6 - - - - 2 SNA
Q'TY
S0714DS S0714PS
S0904DS
S1004DS
S0904PS
S1254DS
S1004ZS
S1004PS
S1254PS
S1404DS
S1404PS
No. SA/SNA Description Specification Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 2 2011-04-29 4:23:10
5-3 Samsung Electronics
Exploded Views and Parts List
Parts List (cont.)
24 DB96-15347A ASS'Y TUBE-INLET PART ASS'Y 1 - - - - SNA
DB96-15477A ASS'Y TUBE-INLET PART ASS'Y - - 1 - - SNA
DB96-15477B ASS'Y TUBE-INLET PART ASS'Y - 1 - - - SNA
DB96-14714B ASS'Y TUBE-INLET PART ASS'Y - - - 1 - SNA
DB96-14624B ASS'Y TUBE-INLET PART ASS'Y - - - - 1 SNA
25 DB96-15346A ASS'Y COLLECTOR ASS'Y 1 - - - - SNA
DB96-15470A ASS'Y COLLECTOR ASS'Y - 1 1 - - SNA
DB96-14726A ASS'Y COLLECTOR ASS'Y - - - 1 - SNA
DB96-14632A ASS'Y COLLECTOR ASS'Y - - - - 1 SNA
26 DB96-15326A ASS'Y EVAP BENDING ASS'Y 1 - - - - SNA
DB96-15440A ASS'Y EVAP BENDING ASS'Y - 1 1 - - SNA
DB96-14905A ASS'Y EVAP BENDING ASS'Y - - - 1 - SNA
DB96-14659A ASS'Y EVAP BENDING ASS'Y - - - - 1 SNA
27 DB95-04461A ASS'Y THERMISTOR IN-EVA IN OUT ASS'Y 1 1 1 1 1 SA
Q'TY
S0714DS S0714PS
S0904DS
S1004DS
S0904PS
S1254DS
S1004ZS
S1004PS
S1254PS
S1404DS
S1404PS
No. SA/SNA Description Specification Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 3 2011-04-29 4:23:10
MEMO
Samsung Electronics 5-4
NS1004PXEA_E_SM_33124A(1)_2.indd 4 2011-04-29 4:23:10
5-5 Samsung Electronics
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
25
23
24
26
27
28
1
2
3
4
5
5-2 Panel
PC4NUSKA
NS1004PXEA_E_SM_33124A(1)_2.indd 5 2011-04-29 4:23:14
Samsung Electronics 5-6
Exploded Views and Parts List
Parts List
1 DB64-02538A PANEL-BASE HIPS(VICTORY GRAY) 1 SA
2 DB66-01545A BLADE A ABS(VICTORY GRAY) 2 SA
3 DB66-01546A BLADE B ABS(VICTORY GRAY) 2 SA
4 DB64-02539A PANEL-GRILL HIPS(VICTORY GRAY) 1 SA
5 DB63-02739A FILTER ABS(INNER GRAY) 1 SA
6 DB66-01542A LEVER-CLAMP L HIPS(VICTORY GRAY) 1 SA
7 DB66-01543A LEVER-CLAMP R HIPS(VICTORY GRAY) 1 SA
8 DB61-04689A SPRING ETC-KNOB STS304 2 SA
9 DB63-02732A COVER-CORNER HIPS(VICTORY GRAY) 3 SA
10 DB61-04544A HOLDER-BLADE POM(WHT) 4 SA
11 DB63-02734A COVER-BACK A HIPS(BLK) 1 SNA
12 DB63-02735A COVER-BACK B HIPS(BLK) 1 SNA
13 DB63-02736A COVER-BACK C HIPS(BLK) 1 SNA
14 DB63-02737A COVER-BACK D HIPS(BLK) 1 SNA
15 DB66-01544A LINK-CLAMP HIPS(VICTORY GRAY) 2 SA
16 DB63-02740A CUSHION-IN EPS,25 2 SNA
17 DB63-02741A CUSHION-IN L EPS,25 1 SNA
18 DB63-02742A CUSHION-IN R EPS,25 1 SNA
19 DB63-02744A COVER-DISPLAY HIPS(VICTORY GRAY) 1 SA
20 DB64-02542A WINDOW-SENSOR PC(WAFFLE MILKY) 1 SA
21 DB63-02738A COVER-PBA PP(NTR) 1 SA
22 DB64-02541A WINDOW-LED PC(WAFFLE FLOCKING GRAY) 4 SA
23 DB66-01412A LINK-HINGE A POM(WHT) 1 SA
24 DB66-01419A LINK-SWITCH A ABS(GREEN) 1 SA
25 DB66-01410A LINK-HINGE B POM(WHT) 1 SA
26 DB66-01420A LINK-SWITCH B ABS(GREEN) 1 SA
27 DB93-10649A ASS'Y PCB PANEL DISPLAY ASS'Y 1 SA
28 DB31-00371B MOTOR STEP ASS'Y 4 SA
No. SA/SNA Description Specification Q'TY Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 6 2011-04-29 4:23:14
5-7 Samsung Electronics
Exploded Views and Parts List
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
PC4NUSK5
NS1004PXEA_E_SM_33124A(1)_2.indd 7 2011-04-29 4:23:14
Samsung Electronics 5-8
Exploded Views and Parts List
Parts List
1 DB64-02538A PANEL-BASE HIPS(VICTORY GRAY) 1 SA
2 DB66-01545A BLADE A ABS(VICTORY GRAY) 2 SA
3 DB66-01546A BLADE B ABS(VICTORY GRAY) 2 SA
4 DB64-02540A PANEL-GRILL HIPS(VICTORY GRAY) 1 SA
5 DB63-02739A FILTER ABS(INNER GRAY) 1 SA
6 DB66-01542A LEVER-CLAMP L HIPS(VICTORY GRAY) 1 SA
7 DB66-01543A LEVER-CLAMP R HIPS(VICTORY GRAY) 1 SA
8 DB61-04689A SPRING ETC-KNOB STS304 2 SA
9 DB63-02732A COVER-CORNER HIPS(VICTORY GRAY) 3 SA
10 DB61-04544A HOLDER-BLADE POM(WHT) 4 SA
11 DB63-02734A COVER-BACK A HIPS(BLK) 1 SNA
12 DB63-02735A COVER-BACK B HIPS(BLK) 1 SNA
13 DB63-02736A COVER-BACK C HIPS(BLK) 1 SNA
14 DB63-02737A COVER-BACK D HIPS(BLK) 1 SNA
15 DB66-01544A LINK-CLAMP HIPS(VICTORY GRAY) 2 SA
16 DB63-02740A CUSHION-IN EPS,25 2 SNA
17 DB63-02741A CUSHION-IN L EPS,25 1 SNA
18 DB63-02742A CUSHION-IN R EPS,25 1 SNA
19 DB63-02744A COVER-DISPLAY HIPS(VICTORY GRAY) 1 SA
20 DB64-02542A WINDOW-SENSOR PC(WAFFLE MILKY) 1 SA
21 DB63-02738A COVER-PBA PP(NTR) 1 SA
22 DB64-02541A WINDOW-LED PC(WAFFLE FLOCKING GRAY) 4 SA
23 DB66-01412A LINK-HINGE A POM(WHT) 1 SA
24 DB66-01419A LINK-SWITCH A ABS(GREEN) 1 SA
25 DB66-01410A LINK-HINGE B POM(WHT) 1 SA
26 DB66-01420A LINK-SWITCH B ABS(GREEN) 1 SA
27 DB93-10649A ASS'Y PCB PANEL DISPLAY ASS'Y 1 SA
28 DB31-00371B MOTOR STEP ASS'Y 4 SA
No. SA/SNA Description Specification Q'TY Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 8 2011-04-29 4:23:14
5-9 Samsung Electronics
RC071DHXEA/RC071PHXEA
5-3 Outdoor Unit
2
29
30
1
10
4
11
5
12
18
17
13
6
15
31
3
8
9
16
24
25
26
27
28
21
22
23
20
19
7
14
NS1004PXEA_E_SM_33124A(1)_2.indd 9 2011-04-29 4:23:15
Samsung Electronics 5-10
Exploded Views and Parts List
Parts List
1 DB90-03275A ASS'Y CABINET-UP MH060,SSEC 1 SA
2 DB63-02395A GUARD-COND BAR WW CHASSIS,SG-90073T,W609,L736.3,--,SSEC 1 SA
3 DB90-03932B ASS'Y CABINET-SIDE LF PAINT MH080,SSEC 1 SA
4 DB94-03086A ASS'Y PARTITION maldive,SSEC 1 SA
5 DB27-00043C COIL CHOKE-REACTOR forte,5mH,5%,20A 1 SA
6 DB96-14022B ASS'Y COND UNIT Maldives3,SSEC 1 SA
7 DB90-04433A ASS'Y-PLATE COND -,SSEC 2 SA
8 DB90-04127F ASS'Y-CABI SIDE RH UH070EAV1,SSEC 1 SA
9 DB90-03652C ASS'Y COVER CONTROL Q-PJT,RAC,SSEC 1 SA
10 DB90-04194B ASS'Y BRACKET MOTOR UH070EAV1,SSEC 1 SA
11 DB31-00512F MOTOR FAN FMBC531SSK,124[W],1050RPM,DC310V, 1 SA
MAX IC 85oC,1500mm , Class E
12 DB67-00861A FAN-PROPELLER WW3,AS+GF20%,460,3,T3.5,SSEC, 1 SA
13 DB90-03278H ASS'Y BASE OUT-TOTAL P CHASSIS,SSEC 1 SA
14 DB61-01593A BRACKET-VALVE HP-SR2371GB,AFP_G1,1.6,SUPREME-PJT,282g 1 SA
15 DB90-03918P ASS'Y CABI FRONT P,SSEC 1 SA
16 DB63-02226B GUARD FAN PP,SMART GRAY,UL746C 1 SA
17 DB96-16228A ASS'Y-VALVE 4WAY H/P,RC071DHXEA,SSEC 1 SA
17-1 DB96-06998D ASS'Y-SOLENOID COIL WW3,SSEC 1 SA
18 DB99-01005B ASS'Y VALVE EEV Maldives3,SSEC 1 SA
18-1 DB62-04065A VALVE-EXPANSION BODY DPF(Q)1.65C-06-RK(E),-,500,DC12V,1/2,1.6mm 1 SA
18-2 DB62-04067J VALVE-EXPANSION COIL DVMPlus4,SPCC,1000,DC12V 1 SA
19 6021-001142 NUT-HEXAGON FLANGE -,M5,ZPC(YEL),SWCH10A,SERRATION 1 SNA
20 DB63-02312A COVER TERMINAL 39F,44F,48F,CEXP-0021C,2.5,BLACK,30.0 1 SNA
21 DB63-01416C GASKET A/C model,SIR,T1.2,25.0,L55,A/C model use 1 SNA
22 UG4T200FUAE4SS RCP,44,F,R410A 1 SA
23 DB63-02296A GROMMET ISOLATOR -,NR,-,-,32.5,ID11.5,OD34.0,BLACK,SSEC 3 SNA
24 DB60-30028A SCREW-HEX HWH,-,WP,M8,-,ZPC(WHT),SWRCH18A,-,P1.25 3 SNA
25 DB63-02868B FELT-COMP SIDE RC071DHXEA,FELT+PVC,T5+T1.6 1 SNA
26 DB63-03052A FELT-COMP SOUND RC071DHXEA,FELT+PVC,T5+T2 1 SNA
27 DB63-03053A FELT-COMP SOUND RC071DHXEA,FELT+PVC,T5+T2 1 SNA
28 DB63-01718A FELT-COMP BASE Forte2-INV,PET+EVA,T8+T2,291.4,293.6, 1 SNA
GRAY,SSEC 18K
29 DB95-01976C ASS'Y THEMISTOR CAC 1 SA
30 DB95-04329A ASS'Y THEMISTOR-AIR/DIS SYSTEM 1 SA
31 DB93-12229A ASS'Y CONTROL OUT HP,INV,RC071DHXEA,SSEC 1 SA
No. SA/SNA Description Specification Q'TY Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 10 2011-04-29 4:23:16
5-11 Samsung Electronics
Exploded Views and Parts List
RC100DHXEA/RC090DHXEA/RC090PHXEA/RC100DHXGA
7
7-1
14
15
13
22
21
16
9
8
1
11
5
18 23
23-1
23-2
4
3
19
20
17
6
2
23-3
10
12
NS1004PXEA_E_SM_33124A(1)_2.indd 11 2011-04-29 4:23:41
Samsung Electronics 5-12
Exploded Views and Parts List
Parts List
1 DB63-02730A GUARD-COND MSWR-6B, TOUCH GRAY 1 1 SA
2 DB64-02525A CABI INSTALL BACK EGI, T0.7 1 1 SA
3 DB64-02526A CABI INSTALL FRONT EGI, T0.7 1 1 SA
4 DB90-05873B ASS'Y BASE OUT ASS'Y 1 1 SA
5 DB90-05903B ASS'Y CABI BACK RH ASS'Y 1 1 SA
6 DB90-05904B ASS'Y CABI FRONT RH ASS'Y 1 1 SA
7 DB90-05971B ASS'Y CABI FRONT LF ASS'Y 1 1 SA
7-1 DB63-02728A GUARD FAN PP, MT72TG 1 1 SA
8 DB90-05902A ASS'Y CABINET TOP ASS'Y 1 1 SA
9 DB94-02720C ASS'Y PARTITION ASS'Y 1 1 SA
10 DB93-08235E ASS'Y CONNECTOR WIRE COMP ASS'Y, 1 1 - SNA
DB93-08235D ASS'Y CONNECTOR WIRE COMP ASS'Y, 3 - 1 SNA
11 DB93-11292C ASS'Y CONTROL OUT ASS'Y, 1 1 - SNA
DB93-11349C ASS'Y CONTROL OUT ASS'Y, 3 - 1 SNA
12 DB95-04522A ASS'Y THERMISTOR OUT ASS'Y 1 1 SA
13 DB31-00579A MOTOR FAN DAO335130ZRC, CLASS E 1 1 SA
14 DB60-00405A FASTENER WASHER M8 1 1 SNA
15 DB67-01061B FAN PROPELLER PP+MICA+GF, 520PI 1 1 SA
16 DB90-05918B ASS'Y BRACKET MOTOR ASS'Y 1 1 SA
17 DB60-30028A SCREW HEX HWH,WP,M8,ZPC(WHT),SWRCH18A 3 3 SNA
18 DB63-02953A CLOTH COMP TOP FELT, BLACK,1 1 - SNA
DB63-02987A CLOTH COMP TOP FELT, BLACK,3 - 1 SNA
19 DB63-02954A CLOTH COMP SIDE FELT, BLACK,1 1 - SNA
DB63-02987A CLOTH COMP SOUND FELT, BLACK,3 - 1 SNA
20 UG8T300FUBJUSG COMPRESSOR ASS'Y, 1 1 - -
UG5T450FUFJXSG COMPRESSOR ASS'Y, 3 - 1 -
21 DB90-02316E ASS'Y HOLDER PLATE COND ASS'Y 2 2 SA
22 DB96-15469A ASS'Y COND OUT ASS'Y 1 1 SA
23 DB96-15476C ASS'Y VALVE ASS'Y, 1 1 - SA
DB96-15476B ASS'Y VALVE ASS'Y, 3 - 1 SA
23-1 DB90-05874B ASS'Y BRACKET VALVE ASS'Y 1 1 SA
23-2 DB96-14880A ASS'Y VALVE 4WAY RC100DHXEA, R410A, 1 1 - SA
DB96-14886A ASS'Y VALVE 4WAY RC100DHXGA, R410A, 3 - 1 SA
23-3 DB96-14885A ASS'Y TUBE EEV RC100DHXEA, R410A 1 1 SA
No. SA/SNA Description Specification
Q'TY
RC100DHXEA
RC090DHXEA
RC090PHXEA
RC100DHXGA
Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 12 2011-04-29 4:23:42
5-13 Samsung Electronics
Exploded Views and Parts List
14
18
19
23
5
11
1
8
23-1
23-2
23-3
17
20
3
10
12
4
2
6
15
13
16
21
22
9
7
7-1
RC100PHXEA/RC125PHXEA/RC125DHXEB/RC140DHXEB/RC100PHXGA/RC125PHXGA/RC125DHXGA/RC140DHXGA/
RC100ZHXEA/RC140PHXEA/RC140PHXGA
NS1004PXEA_E_SM_33124A(1)_2.indd 13 2011-04-29 4:24:21
Samsung Electronics 5-14
Exploded Views and Parts List
Parts List(RC125/140DHS, RC100/125PHS)
1 DB63-02706A GUARD COND MSWR-6B, TOUCH GRAY 1 1 SA
2 DB64-02525A CABINET-INSTALL BACK EGI, T0.7 1 1 SA
3 DB64-02526A CABINET-INSTALL FRONT EGI, T0.7 1 1 SA
4 DB90-05873B ASS'Y BASE OUT ASS'Y 1 1 SA
5 DB90-05876B ASS'Y CABI BACK-RH ASS'Y 1 1 SA
6 DB90-05877B ASS'Y CABI FRONT RH ASS'Y 1 1 SA
7 DB90-05878A ASS'Y CABI FRONT-LF ASS'Y 1 1 SA
7-1 DB63-02696A GUARD FAN PP, MT72TG 2 2 SA
8 DB90-05902A ASS'Y CABINET-TOP ASS'Y 1 1 SA
9 DB94-02697C ASS'Y PARTITION ASS'Y 1 1 SA
10 DB93-08235G ASS'Y CONNECTOR WIRE-COMP ASS'Y, 1 1 - SNA
DB93-08235F ASS'Y CONNECTOR WIRE-COMP ASS'Y, 3 - 1 SNA
11 DB93-11292C ASS'Y CONTROL OUT ASS'Y, 1 1 - SNA
DB93-11349C ASS'Y CONTROL OUT ASS'Y, 3 - 1 SNA
12 DB95-04522B ASS'Y THERMISTOR OUT-MANU ASS'Y 1 1 SA
13 DB31-00579A MOTOR FAN DAO335130ZRC, CLASS E 2 2 SA
14 DB60-00405A FASTENER-WASHER M8 2 2 SNA
15 DB67-01057B FAN-PROPELLER PP+MICA+GF, 480PI 2 2 SA
16 DB90-05875B ASS'Y BRACKET MOTOR ASS'Y 1 1 SA
17 DB60-30028A SCREW-HEX HWH,WP,M8,ZPC(WHT),SWRCH18A 3 3 SNA
18 DB63-02832A CLOTH-COMP TOP FELT, BLACK 1 - SNA
DB63-02987A CLOTH-COMP TOP FELT, BLACK - 1 SNA
19 DB63-02834A CLOTH-COMP SOUND FELT, BLACK 1 1 SNA
20 UG5T450FUEJXSG COMPRESSOR ASS'Y, 1 1 - -
UG5T450FUFJXSG COMPRESSOR ASS'Y, 3 - 1 -
21 DB90-02316E ASS'Y HOLDER-PLATE COND ASS'Y 2 2 SA
22 DB96-14661A ASS'Y COND OUT ASS'Y 1 1 SA
23 DB96-14898A ASS'Y-VALVE ASS'Y 1 1 SA
23-1 DB90-05874A ASS'Y BRACKET-VALVE RC100PHXEA,ManU 1 1 SA
23-2 DB96-14488A ASS'Y-VALVE 4WAY RC100PHXEA,R410A 1 1 SA
23-3 DB96-14510A ASS'Y TUBE-EEV RC100PHXEA,R410A 1 1 SA
No. SA/SNA Description Specification
Q'TY
RC100PHXEA
RC125PHXEA
RC125DHXEB
RC140DHXEB
RC100PHXGA
RC125PHXGA
RC125DHXGA
RC140DHXGA
Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 14 2011-04-29 4:24:22
5-15 Samsung Electronics
Exploded Views and Parts List
Parts List(RC140PHS, RC100ZHS)
1 DB63-02729B GUARD COND MSWR-6B, TOUCH GRAY 1 1 1 SA
2 DB64-02525A CABINET-INSTALL BACK EGI, T0.7 1 1 1 SA
3 DB64-02526A CABINET-INSTALL FRONT EGI, T0.7 1 1 1 SA
4 DB90-05873B ASS'Y BASE OUT ASS'Y 1 1 1 SA
5 DB90-05905B ASS'Y CABI BACK-RH ASS'Y 1 1 1 SA
6 DB90-05906B ASS'Y CABI FRONT RH ASS'Y 1 1 1 SA
7 DB90-06030A ASS'Y CABI FRONT-LF ASS'Y 1 1 1 SA
7-1 DB63-02728A GUARD FAN PP, MT72TG 2 2 2 SA
8 DB90-05902A ASS'Y CABINET-TOP ASS'Y 1 1 1 SA
9 DB94-02721B ASS'Y PARTITION ASS'Y 1 1 1 SA
10 DB93-08235J ASS'Y CONNECTOR WIRE-COMP ASS'Y, 1 1 - 1 SNA
DB93-08235H ASS'Y CONNECTOR WIRE-COMP ASS'Y, 3 - 1 - SNA
11 DB93-11292D ASS'Y CONTROL OUT ASS'Y, 1 1 - 1 SNA
DB93-11349C ASS'Y CONTROL OUT ASS'Y, 3 - 1 - SNA
12 DB95-04522C ASS'Y THERMISTOR OUT-MANU ASS'Y 1 1 1 SA
13 DB31-00579A MOTOR FAN DAO335130ZRC, CLASS E 2 2 2 SA
14 DB60-00405A FASTENER-WASHER M8 2 2 2 SNA
15 DB67-01061B FAN-PROPELLER PP+MICA+GF, 520PI 2 2 2 SA
16 DB90-05970B ASS'Y BRACKET MOTOR ASS'Y 1 1 1 SA
17 DB60-30028A SCREW-HEX HWH,WP,M8,ZPC(WHT),SWRCH18A 3 3 3 SNA
18 DB63-02832A CLOTH-COMP TOP FELT, BLACK 1 1 1 SNA
19 DB63-02834A CLOTH-COMP SOUND FELT, BLACK 1 1 1 SNA
20 UG5T450FXAJXSG COMPRESSOR ASS'Y, 1, 3 1 1 1 -
21 DB90-06494A ASS'Y HOLDER-PLATE COND ASS'Y 2 2 2 SA
22 DB96-15771A ASS'Y COND OUT ASS'Y 1 1 1 SA
23 DB96-15866A ASS'Y-VALVE ASS'Y 1 1 1 SA
23-1 DB90-05874A ASS'Y BRACKET-VALVE RC100PHXEA,ManU 1 1 1 SA
23-2 DB96-15865A ASS'Y-VALVE 4WAY RC140PHXEA,R410A 1 1 1 SA
23-3 DB96-15864A ASS'Y TUBE-EEV RC140PHXEA,R410A 1 1 1 SA
Q'TY
RC140PHXEA RC140PHXGA RC100ZHXEA
No. SA/SNA Description Specification Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 15 2011-04-29 4:24:22
MEMO
Samsung Electronics 5-16
NS1004PXEA_E_SM_33124A(1)_2.indd 16 2011-04-29 4:24:22
5-17 Samsung Electronics
3
4
5
2
6
12
11
1
7
8
13
10
9
12-2
8-5
8-4
8-3
8-2
8-1
12-4
12-1
12-3
5-4 ASS'Y CONTROL OUT
RRC090DHXEA, RC100DHXEA, RC125DHXEB, RC140DHXEB, RC090PHXEA, RC100PHXEA,
RC125PHXEA, RC140PHXEA, RC100ZHXEA, RC100DHXGA, RC125DHXGA, RC140DHXGA,
RC100PHXGA, RC125PHXGA, RC140PHXGA
NS1004PXEA_E_SM_33124A(1)_2.indd 17 2011-04-29 4:24:23
Samsung Electronics 5-18
Exploded Views and Parts List
Parts List (RC090/100/125/140DS, RC090/100/125/140PS, RC100ZS)
1 DB59-00015A AC REACTOR-3PHASE 20A 20A, 3 - - 1 SA
DB59-00016A AC REACTOR-1PHASE 30A 30A, 1 1 - - SA
DB59-00017A AC REACTOR-1PHASE 50A 50A, 1 - 1 - SA
2 DB61-04504B CASE-INV ABS, BLACK 1 - - SNA
DB61-04657B CASE-INV 3PHASE ABS, BLACK - 1 1 SNA
3 DB62-09441A HEAT SINK-1PHASE 30A AL, 1 1 - - SA
DB62-09441B HEAT SINK-1PHASE 50A AL, 1 - 1 - SA
DB62-09441C HEAT SINK-3PHASE AL, 3 - - 1 SA
4 0205-000178 GREASE-SILICON TH1111,TOSHIBA(NTR) 7g 7g 7g SNA
5 6001-001054 SCREW-MACHINE TH,M4,L10 4 4 4 SNA
6 6002-000635 SCREW-TAPPING PH,M4,L8 2 2 2 SNA
7 6002-000231 SCREW-TAPPING TH,M4,L12 7 7 7 SNA
8 DB90-06115A ASS'Y CASE-PCB ASSY, 1 1 1 - SA
DB90-06115B ASS'Y CASE-PCB ASSY, 3 - - 1 SA
8-1 DB61-04502A CASE-EMI ABS,BLACK 1 1 1 SNA
8-2 DB61-04503A CASE-MAIN ABS,BLACK 1 1 1 SNA
8-3 DB93-10809A ASS'Y CONNECTOR WIRE ASS'Y 1 1 1 SN
8-4 DB93-11109A ASS'Y PCB MAIN-OUT Inverter Platform #4, #5, #6 MAIN 1 1 1 SA
8-5 DB93-11110A ASS'Y PCB SUB-EMI Inverter Platform #4, #5 EMI, 1 1 1 - SA
DB93-11111A ASS'Y PCB SUB-EMI Inverter Platform #6 EMI, 3 - - 1 SA
9 DB91-00306A ASS'Y-SCREW MACHINE M3, L16 2 2 2 SA
10 DB91-00307A ASS'Y-SCREW MACHINE M4, L16 2 2 2 SA
11 DB93-10807A ASS'Y CONNECTOR WIRE ASS'Y, MAIN TO INVERTER 1 1 1 SA
12 DB93-10966A ASS'Y CONTROL OUT-PLATE ASSY, 1 1 1 - SA
DB93-10966B ASS'Y CONTROL OUT-PLATE ASSY, 3 - - 1 SA
12-1 DB65-00296A TERMINAL BLOCK-POWER 4P, 1 1 1 - SNA
DB65-00185C TERMINAL BLOCK-POWER 6P, 3 - - 1 SNA
12-2 DB65-00297A TERMINAL BLOCK-COMM 2P 1 1 1 SA
12-3 DB90-05889A ASS'Y CASE CONTROL OUT ASS'Y 1 1 1 SA
12-4 DB93-10808A ASS'Y CONNECTOR WIRE ASS'Y, MAIN TO INVERTER 1 1 1 SA
13 DB93-11112A ASS'Y PCB MAIN-INVERTER Inverter Platform #4 EMI, 1 1 - - SA
DB93-11113A ASS'Y PCB MAIN-INVERTER Inverter Platform #5 EMI, 1 - 1 - SA
DB93-11114A ASS'Y PCB MAIN-INVERTER Inverter Platform #6 EMI, 3 - - 1 SA
14 DB93-10864B ASS'Y CONNECTOR WIRE RST AWG #14 - - 1 SA
15 DB93-11241A ASS'Y CONNECTOR WIRE REACTOR AWG #12 - - 1 SA
Q'TY
RC090DHXEA
RC100DHXEA
RC125DHXEB
RC140DHXEB
RC090PHXEA
RC100PHXEA
RC125PHXEA
RC140PHXEA
RC100ZHXEA
RC100DHXGA
RC125DHXGA
RC140DHXGA
RC100PHXGA
RC125PHXGA
RC140PHXGA
No. SA/SNA Description Specification Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 18 2011-04-29 4:24:24
5-19 Samsung Electronics
Exploded Views and Parts List
1
2
3
5
6-1
4
6-2
6
6-3
6-4
6-5
RC071DHXEA, RC071PHXEA
NS1004PXEA_E_SM_33124A(1)_2.indd 19 2011-04-29 4:24:24
Samsung Electronics 5-20
Exploded Views and Parts List
Parts List(RC071DHS, RC071PHS)
1 DB61-04910A CASE CONTROL-UPPER Q CHASSIS,ABS+PC,GRAY,5V,SSEC 1 SA
2 DB93-10939E ASS`Y PCB MAIN-OUT RC071DHXEA,SSEC,Y,SMPS 1 SA
3 DB62-10653A HEAT SINK FJM2 PF3 MODEL,AL,SCREW 1 SA
4 DB61-04908A CASE CONTROL-OUT Q CHASSIS,ABS+PC,GRAY,5V,SSEC 1 SA
5 DB93-12212A ASS`Y PCB SUB RC071DHXEA,SSEC,N 1 SA
6 DB93-12230A ASS`Y-T/B PLATE HP,RC071DHXEA,T/B PLATE 1 SA
6-1 DB65-00061H TERMINAL BLOCK FORTE-PJT,PBT,2-TAB,2-SCREW,Max2.5MM^2, 1 SA
36.4*24.2MM^2,BLK,300V,25A,2P
6-2 DB65-00176H TERMINAL BLOCK EAGLE-INV,PBT,4-TAB_4-SCREW,MAX 4MM^2, 1 SA
36.4*47.0MM,4P,B_Type
6-3 DB61-04755A CASE-SUB PCB ABS+PC 1 SA
6-4 DB90-06600A ASS`Y-CONTROL PLATE INV P,SSEC 1 SA
6-5 DB61-04710A HOLDER-WIRE CLAMP A ABS,2.0 2 SNA
No. SA/SNA Description Specification Q'TY Code No.
NS1004PXEA_E_SM_33124A(1)_2.indd 20 2011-04-29 4:24:24
6-1 Samsung Electronics
TB01- INPUT POWER CN42-EVAIN/OUT TemperatureSensor CN74 - AC Drain Pump CN73-BLDC FAN MOTOR
1(L) : Phase L
2(N) : Phase N

# 1 : Phase N
# 3 : Phase L

#1 : DC310V #2 : Not used


#3 : AGND #4 : DC15V
#5 : FAN RPM #6 : RPM FEEDBACK

#1 : EVA IN temperature sensor
#2 : GND
#3 : EVA OUT temperature sensor
#4 : GND

#1 : Float sensor
#2 : GND

#1 : 12V
#2 : GND

#1: SPI CONTROL #2: SPI CONTROL
#3 : DC 12V #4 : Not used


#1 : DC 12V #2 : ERROR check
#3 : DC 12V #4 : Operating Check

Downloading

#1: DC12V
#2 : Drain pump signal

F1 : Communication signal F1
F2 : Communication signal F2
V1 : DC 12V
V2 : GND
F3 : Communication signal F3
F4 : Communication signal F4

#1 : DC12V
#2~5 : Louver control signal
#6 : DC 12V
#7~10 : Louver control signal

#1 : DC12V
#2~5 : Louver control signal
#6 : DC 12V
#7~10 : Louver control signal

#1 : DC 12V
#2~5 : LED control signal
#6 : Remocon signal out
#7~8 : Not used
#9 : Remocon signal IN
#10 : GND
#11 : DC 5V

#1 : ON/OFF contack signal
# 2 : GND

#1 : INDOOR ROOM temperature sensor
#2 : GND

CN10-DOWNLAOD
TB02- COM1/COM2 Communication
CN83-External signal(ON/OFF)
CN41- INDOOR RoomTemperatureSensor
CN51- FLOAT SENSOR
CN81-External Contack control check
CN60-LOUVER1/2
CN101-Earth wire
CN75-Ventilator
CN88-AS-PRO
CN60-LOUVER3/4
Cn45-SPI
DC DRAIN PUMP
CN91-DISPLAY
6. PCB Diagram and Parts List
6-1 PCB Diagram
6-1-1 Indoor Unit
2 3 4 5
18 17 15 11 9
16 14 7 6 13 8 10 12 1
NS1004PXEA_E_SM_33124A(1)_2.indd 1 2011-04-29 4:24:27
Samsung Electronics 6-2

#1 : DC 12V
#2~5 : LED control signal
#6 : Remocon signal out
#7~8 : Not used
#9 : Remocon signal IN
#10: GND
#11: DC 5V
CN01-DISPLAY
6-1-2 Panel PCB
PCB Diagram and Parts List
1
NS1004PXEA_E_SM_33124A(1)_2.indd 2 2011-04-29 4:24:28
6-3 Samsung Electronics
PCB Diagram and Parts List
6-1-3 Outdoor Unit PCB
Main PCB
- RC090DHS/RC100DHS/RC100PHS/RC100ZHS/RC125DHS/RC125PHS/RC140DHS/RC140PHS
1 5 6 2 3 4
15
7 16 9 11 13
8 10 12 14
NS1004PXEA_E_SM_33124A(1)_2.indd 3 2011-04-29 4:24:39
Samsung Electronics 6-4
PCB Diagram and Parts List

#1-#3 : 220~240Vac

#1-#3 : 220~240Vac

#1-#3 : 220~240Vac

#1-#3 : 220~240Vac

#1 : RXD_INV
#2 : TXD_INV
#3, #8 : N.C
#4 ~ #7 : Data signal
#9 : GND
#10 : DC 5V

#1 : DC 5V
#2 : MODE
#3 : Reset
#4~#6 : GRID_3/1/2
#7 : GND

#1-#2 : Outdoor Temp.
#3-#4 : Cond. Temp.
#5-#6 : Discharge Temp.
#7-#8 : OLP Temp.

#1~#4 : Motor signal


#5 : DC 12V

#1~#4 : Motor signal
#5 : DC 12V

#1~#4 : Motor signal


#5 : DC 12V

#1 : TXD
#2 : RXD
#3 : GND
#4 : DC 5V
#5 : DC 12V
#6 : INV. SMPS signal

#1 : Temp. signal
#2 : GND

#1 : High Pressure temp. signal


#3 : GND
#4 : DC 5V

#1 : DC 12V
#2 : GND

#1 : COM1
#2 : COM2

#1 : DC 12V
#2 : GND
#3 : DC 5V
#4 : COM1
#5 : COM2
CN11-AC POWER CN74-AC LOAD1 CN75-4WAY V/V CN71-AC LOAD2(Option)
CN37-Micom Download
CN82-EEV 2(Option)
CN42-High Pressure(Option)
CN35-AS-PRO
CN83-EEV 3(Option)
CN12-DC12V
CN43-Sensor
CN39-COMM-INV
CN31-Comm.
CN81-EEV 1
CN44-TEMP OPTION(Option)
CN33-Sub Comm.
NS1004PXEA_E_SM_33124A(1)_2.indd 4 2011-04-29 4:24:40
6-5 Samsung Electronics
PCB Diagram and Parts List
Outdoor Unit PCB (cont.)
Main PCB
- RC071DHXEA/RC071PHXEA
OLP /COND THERMISTOR CONNECTOR SMAW250A-04 WHT
OUT/DISCHARGE THERMISTOR CONNECTOR SMAW250A-04 RE
BLDC-FAN CONNETCOR YAN396-06V WHT
EEV-A CONNECTOR SMAW250A-05 RED
DISPLAY CONNECTOR SMW200-10 NTR
DISPLAY CONNECTOR SMAW250A-03 RED
PC DOWNLOADCONNECTOR SMW200-10 BLK
S NE T CONNECTOR SMW200-04 NTR
AS-PRO DOWNLOAD CONNECTOR SMAW200A-07 WHT
DISPLAY CONNE CTORS MW200-05 NTR
DOWNLOAD-INV CONNECTOR S MW200-10 RED
7 6
5
4
3
2
1
8 9 10 11
NS1004PXEA_E_SM_33124A(1)_2.indd 5 2011-04-29 4:24:42
Samsung Electronics 6-6
PCB Diagram and Parts List
Outdoor Unit PCB (cont.)
Sub PCB
- RC071DHXEA/RC071PHXEA (cont.)
12V POWER CONNECTOR YW396-02V BLU
MAIN -SUB SIGNAL CONNECTOT SMW250-04 WHT
MAIN -SUB SIGNAL CONNECTOT SMW200-15NTR
1 2 3
NS1004PXEA_E_SM_33124A(1)_2.indd 6 2011-04-29 4:24:43
6-7 Samsung Electronics
PCB Diagram and Parts List
Outdoor Unit PCB (cont.)
Inverter PCB : 1Phase I
- RC090PHXEA / RC090DHXEA / RC100DHXEA/ RC100PHXEA / RC125PHXEA / RC125DHXEB / RC140DHXEB

2 3 4
6
5 8
7

#Reactor-A2 : WHT
#Reactor-B2 : WHT

#Reactor-A2 : BLK
#Reactor-B2 : BLK

#1 : RXD, #2 : TXD
#3 : GND, #4 : DC 5V
#5 : DC 12V, #6 : INV. SMPS signal

#1 : RXD_ATARO, #2 : TXD_ATARO
#3, #8 : N.C, #4~#7 : DATA signal
#9 : GND, #10 : DC 5V

For S/W engineer debugging

#1 : DC 360V
#2 : N.C
#3 : GND
#4 : DC 15V
#5 : FAN RPM
#6 : FAN RPM feedback

#1 : DC 360V
#2 : N.C
#3 : GND
#4 : DC 15V
#5 : FAN RPM
#6 : FAN RPM feedback

#1 : COMP. U-phase(RED)
#2 : COMP. V-phase(BLU)
#3 : COMP. U-phase(YEL)
Reactor-A1/B1 Reactor-A2/B2 CN50(2PIN/RED)-Communication CN22-Downloader
CN21-DAC/ENCODER CN91-FAN2 CN90-FAN1 CN71-COMP.
1
NS1004PXEA_E_SM_33124A(1)_2.indd 7 2011-04-29 4:24:43
Samsung Electronics 6-8
PCB Diagram and Parts List
Outdoor Unit PCB (cont.)
Inverter PCB : 1Phase II
- RC100ZHXEA / RC140PHXEA
6 7
4
8 2 5

#Reactor-A2 : WHT
#Reactor-B2 : WHT

#Reactor-A2 : BLK
#Reactor-B2 : BLK

#1 : RXD#2 : TXD
#3 : GND, #4 : DC 5V
#5 : DC 12V, #6 : INV. SMPS signal

#1 : RXD_ATARO, #2 : TXD_ATARO
#3, #8 : N.C, #4~#7 : DATA signal
#9 : GND, #10 : DC 5V

For S/W engineer debugging

#1 : DC 360V
#2 : N.C
#3 : GND
#4 : DC 15V
#5 : FAN RPM
#6 : FAN RPM feedback

#1 : DC 360V
#2 : N.C
#3 : GND
#4 : DC 15V
#5 : FAN RPM
#6 : FAN RPM feedback

#1 : COMP. U-phase(RED)
#2 : COMP. V-phase(BLU)
#3 : COMP. U-phase(YEL)
Reactor-A1/B1 Reactor-A2/B2 CN31-MAIN COMM CN22-Downloader
CN21-DAC/ENCODER CN91-FAN2 CN90-FAN1 CN71-COMP.
1 3
NS1004PXEA_E_SM_33124A(1)_2.indd 8 2011-04-29 4:24:44
6-9 Samsung Electronics
PCB Diagram and Parts List
Outdoor Unit PCB (cont.)
Inverter PCB : 3Phase
- RC100DHXGA/ RC100PHXGA / RC125PHXGA / RC125DHXGA / RC140PHXGA

2 6 7 3 4 5
9 8

#R : AC 380~400V : WHT
#S : AC 380~400V : BRN
#T : AC 380~400V : BLK

#1-#3 : AC 220~240V


#1 : RXD , #2 : TXD
#3 : GND, #4 : DC 5V
#5 : DC 12V, #6 : INV. SMPS signal

#1 : RXD_ATARO, #2 : TXD_ATARO
#3, #8 : N.C, #4~#7 : DATA signal
#9 : GND, #10 : DC 5V

For S/W engineer debugging


#1 : DC 360V , #2 : N.C
#3 : GND, #4 : DC 15V
#5 : FAN RPM, #6 : FAN RPM feedback

#1 : DC 360V, #2 : N.C
#3 : GND, #4 : DC 15V
#5 : FAN RPM, #6 : FAN RPM feedback

#1 : COMP. U-phase(RED)
#2 : COMP. V-phase(BLU)
#3 : COMP. U-phase(YEL)

#1-#2 : DCL Reactor
RST-AC POWER 3phase CN100-AC POWER CN31-MAIN COMM CN22-Downloader
CN21-DAC/ENCODER
CN600-REACTOR
CN91-FAN2 CN90-FAN1 CN800-COMP.
1
NS1004PXEA_E_SM_33124A(1)_2.indd 9 2011-04-29 4:25:00
Samsung Electronics 6-10
PCB Diagram and Parts List
Outdoor Unit PCB (cont.)
EMI PCB : 1Phase
- RCSSSXES

L1 : BRN

N1 : SKY-BLU

#1-#3 : AC 220~240V
L1-AC POWER L phase N1-AC POWER N phase CN01-AC POWER
3 1 2
NS1004PXEA_E_SM_33124A(1)_2.indd 10 2011-04-29 4:25:09
6-11 Samsung Electronics
PCB Diagram and Parts List
Outdoor Unit PCB (cont.)
EMI PCB : 3Phase
- RCSSSXGA

#R : AC 380~400V : WHT
#S : AC 380~400V : BRN
#T : AC 380~400V : BLK

#1-#3 : AC 220~240V
RST-AC POWER 3phase CN100-AC POWER
2 1
NS1004PXEA_E_SM_33124A(1)_2.indd 11 2011-04-29 4:25:18
Samsung Electronics 6-12
6-2 Parts List
6-2-1 INDOOR UNIT PCB
INDOOR PBA : DB93-10635A
INDOOR DISPLAY PBA : DB93-10649A
F701 3601-000400 FUSE-CARTRIDGE 250V,2.5A,TIME-LAG,GLASS, 5.2x20mm 1 SA
Location No. Code No. Description Specification Q'TY SA/SNA Remark
NS1004PXEA_E_SM_33124A(1)_2.indd 12 2011-04-29 4:25:18
7-1 Samsung Electronics
7. Wiring Diagram
7-1 Indoor Unit
Louver part
Sensor part
BLDC Fan part
Drain Pump part
Panel Display part
This Document can not be used without Samsungs authorization.
NS1004PXEA_E_SM_33124A(1)_2.indd 1 2011-04-29 4:25:19
Samsung Electronics 7-2
Wiring Diagram
Outdoor Unit : RC071DHXEA/RC071PHXEA
7-2 Outdoor Unit
This Document can not be used without Samsungs authorization.
NS1004PXEA_E_SM_33124A(1)_2.indd 2 2011-04-29 4:25:20
7-3 Samsung Electronics
Outdoor Unit : RC090DHXEA/RC100DHXEA/RC100PHXEA/RC100ZHXEA
RC125DHXEB/RC125PHXEA/RC140DHXEB/RC140PHXEA
Outdoor Unit (cont.)
This Document can not be used without Samsungs authorization.
NS1004PXEA_E_SM_33124A(1)_2.indd 3 2011-04-29 4:25:23
Operating Instructions and Installation
Samsung Electronics 7-4
Outdoor Unit : RCSSSXGA
Outdoor Unit (cont.)
This Document can not be used without Samsungs authorization.
NS1004PXEA_E_SM_33124A(1)_2.indd 4 2011-04-29 4:25:26
8. Schematic Diagram
8-1 Indoor Unit
8-1-1 MAIN PCB
Samsung Electronics 8-1
This Document can not be used without Samsungs authorization.
Sensor part
Louver control part
Communication part
AC Power part
AC Zero Cross circuit part
BLDC FANpart
NS1004PXEA_E_SM_33124A(1)_2.indd 1-2 2011-04-29 4:27:20
Schematic Diagram Schematic Diagram
MAIN PCB (cont.)
This Document can not be used without Samsungs authorization.
Communication part
Samsung Electronics 8-2
NS1004PXEA_E_SM_33124A(1)_2.indd 3-4 2011-04-29 4:27:20
Samsung Electronics 8-3
Schematic Diagram
8-1-2 PANEL PCB
Led Display Part
This Document can not be used without Samsungs authorization.
NS1004PXEA_E_SM_33124A(1)_2.indd 5 2011-04-29 4:25:30
MEMO
Samsung Electronics 8-4
NS1004PXEA_E_SM_33124A(1)_2.indd 6 2011-04-29 4:25:30
Schematic Diagram Schematic Diagram
This Document can not be used without Samsungs authorization.
8-1-3 OUTDOOR UNIT PCB
MAINPCB (RC071DHXEA/RC071PHXEA)
Samsung Electronics 8-5
NS1004PXEA_E_SM_33124A(1)_2.indd 7-8 2011-04-29 4:28:35
Schematic Diagram Schematic Diagram
This Document can not be used without Samsungs authorization.
OUTDOOR UNIT PCB
SUB PCB (RC071DHXEA/RC071PHXEA)
Samsung Electronics 8-6
NS1004PXEA_E_SM_33124A(1)_2.indd 9-10 2011-04-29 4:28:36
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
MAINPCB (RC090DHS/RC100DHS/RC100PHS/RC100ZHS/RC125DHS/RC125PHS/RC140DHS/RC140PHS)
Samsung Electronics
Schematic Diagram
8-7
NS1004PXEA_E_SM_33124A(1)_2.indd 11-12 2011-04-29 4:29:03
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
Inverter PCB : 1Phase I
- RC090PHXEA/ RC090DHXEA/ RC100DHXEA/ RC100PHXEA/ RC125PHXEA/ RC125DHXEA/ RC140DHXEA

Samsung Electronics
Schematic Diagram
8-8
NS1004PXEA_E_SM_33124A(1)_2.indd 13-14 2011-04-29 4:29:06
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
Inverter PCB : 1Phase II
- RC100ZHXEA/ RC140PHXEA
Samsung Electronics
Schematic Diagram
8-9
NS1004PXEA_E_SM_33124A(1)_2.indd 15-16 2011-04-29 4:29:08
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
EMI PCB : 1Phase
- RCSSSXES
Samsung Electronics
Schematic Diagram
8-10
NS1004PXEA_E_SM_33124A(1)_2.indd 17-18 2011-04-29 4:29:08
This Document can not be used without Samsungs authorization.
Schematic Diagram
OUTDOOR UNIT PCB (cont.)
EMI PCB : 3Phase
- RCSSSXGA
Samsung Electronics
Schematic Diagram
8-11
NS1004PXEA_E_SM_33124A(1)_2.indd 19-20 2011-04-29 4:29:09
9-1 Samsung Electronics
Model Code
H
E

H
X

H
A

H
SER

H
/

H
100

H
NS

H
H

H
H

9. Reference Sheet
9-1 Index for Model Name
9-1-1 Indoor Unit
Product Type
N S Single
Capacity (3 DIGIT)
KW / BTU / Liter
Chassis Category
1 1 WAY
CST
2 2 WAY
M MINI 4 WAY
4 4 WAY
H
High Static
Pressure
Duct
S
Middle Static
Pressure
L
Low Static
Pressure(Slim)
E Air handler
G CCD (Slim)
C Ceiling
Conv J Console
F Floor type
P FAC & Mid/Large Size
B Mont Blanc
RAC
V Vivace
Q Neo Forte (EEV)
N Neo-Forte
W
Korean market
use
R Crystal
A Max
Rating Voltage
A 115V, 60Hz
B 220V, 60Hz
C 208~230V, 60Hz
D 200~220V, 50Hz
E 220~240V, 50Hz
F 208~230V, 60Hz, 3Phase
G 380~415V, 50Hz, 3Phase
M 127V, 50Hz
H 380V, 60Hz, 3Phase
J 460V, 60Hz, 3Phase
Version
1~9
Change point
(Korean market)
A~Z
Change point
(export/foreign market)
Z
The Z version is a
high-efficiency EEV Mode
indoor unit.
Mode
C C/O
H H/P
T Tender
V Value
When grade
classification is necessary
Z H/P (Flagship)
P H/P (Premium)
D H/P (Deluxe)
S H/P (Standard)
CP H/P (Premium)
Refrigerant
R R-22
X R410A
"/" can be removed from the buyer card if there are not enough digits.
Buyer Name
NS1004PXEA_E_SM_33124A(1)_2.indd 1 2011-04-29 4:26:34
Samsung Electronics 9-2
Reference Sheet
Index for Model Name (cont.)
Model Code
H
X

H
H

H
G

H
A

H
SER

H
/

H
140

H
RC

H
V

H

9-1-2 Outdoor Unit

MCD: Dummy mock-up model


/ can be removed from the buyer card if there are not enough digits.

Buyer Name
Product Type
N C Single (CAC)
Capacity (3 DIGIT)
HP / KW / BTU / TON
Chassis Category
P Inverter RPM
D Inverter DLX
S Inverter STD
F Constant rate (value)
X Constant rate (tender)
Z Flagship
T Tower (Top Discharge)
U Ice box
Refrigerant
R R-22
X R410A
Separator
1 Universal
1 1 WAY
CST
2 2 WAY
M MINI 4 WAY
4 4 WAY
H
High Static
Pressure
Duct S
Middle Static
Pressure
L
Low Static
Pressure(Slim)
C Ceiling
Conv J Console
F Floor type
P FAC & Mid/Large Size
Mode
C C/O
H H/P
T TROPICAL C/O
Q TROPICAL H/P
Rating Voltage
A 115V, 60Hz
B 220V, 60Hz
C 208~230V, 60Hz
D 200~220V, 50Hz
E 220~240V, 50Hz
F 208~230V, 60Hz, 3Phase
G 380~415V, 50Hz, 3Phase
M 127V, 50Hz
H 380V, 60Hz, 3Phase
J 460V, 60Hz, 3Phase
Version
1~9
Change point
(Korean market)
A~Z
Change point
(export/foreign market)
NS1004PXEA_E_SM_33124A(1)_2.indd 2 2011-04-29 4:26:34
9-3 Samsung Electronics
Reference Sheet
Index for Model Name (cont.)
Model Code
9-1-3 Panel
Model name for the column/bundle packaging is ~S.

Only display the Global 4 way with Korean/
English K separator.
H
K

H
A

H
1

H
C

H
P

H
4N

H
B

Product design classification
P Panel
Product Type
C CST
Product classification
1N Standard 1 way
CST
1B Large-size 1 way
2N 2 WAY
4N 4 WAY
4S MINI 4 WAY
4R Round

Panel version
1, 2, .... Korean market use
A, B, ....
Export/
foreign market use
Color
B Black
E WINE
U White
V Ivory

Language
K Korean
C Chinese
M 8 Languages
E English
TYPE
A
Automatic
boarding/slide
S STANDARD
H PREMIUM
Global
4 Way
Panel
Pattern Wafe Stripe
Korean
market use
1 5
Export/
foreign
market use
A E
NS1004PXEA_E_SM_33124A(1)_2.indd 3 2011-04-29 4:26:34
Operating Instructions and Installation
Samsung Electronics 9-4
CONDENSER
High temperature and high pressure gas state coolant discharged from the compressor is converted to a liquid state as it is cooled
down by the heat emission in the outdoor condenser unit, and sent to the evaporator.
COMPRESSOR
Low temperature and low pressure coolant is compressed and sent to the cycling system
EVAPORATOR
Liquid coolant sucked in through the capillary tubes cools down the room by absorbing the surrounding heat as it evaporates
(converting from liquid to gas). (Absorbing heat required for evaporation)
SERVICE VALVE
You can open the valve by turning the need valve counterclockwise using hex wrench, and it is used for vacuum, gas purging, coolant
injection, coolant purging, and indoor-outdoor unit connection.
ACCUMULATOR
Accumulator prevents the flow of liquid-state coolant into the compressor. (Liquid-state coolant flowing into the compressor will
overload the compressor.)
Indoor Unit Outdoor Unit
Heat exchanger
Evaporator
Liquid pipe
Gas pipe
3-way valve
3-way valve
Electronic expansion valve
Compressor
Oil separator
4-way valve
Cooling
Heating
Leak check points
Aux accumulator
Fan
Heat exchanger
Evaporator
Fan
9-2 Refrigerating Cycle Diagram
NS1004PXEA_E_SM_33124A(1)_2.indd 4 2011-04-29 4:26:34
9-5 Samsung Electronics
9-3 Pressure Graph
-10
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
0 10 20 30 40 50 60
Outdoor Temp.(C)
Cooling
P
r
e
s
s
u
r
e
(
k
g
f
/
c
m

G
)
S Cooling
32/23 27/19 21/15
50 10.0 9.1 8.0
35 9.0 8.3 7.2
20 6.8 6.3 6.4
7 7.6 7.1 6.5
-5 7.7 7.2 6.5
Indoor (C)
Outdoor(C)
Outdoor Temp.(C)
Waiting Mode
P
r
e
s
s
u
r
e
(
k
g
f
/
c
m

G
)
S Waiting Mode
32/23 27/19 21/15
50 18.5 16.7 15.9
35 15.7 14.7 13.4
20 15.2 14.3 13.6
7 9.1 9.1 9.1
-5 5.6 5.6 5.6
-20 3.0 3.0 3.0
Indoor (C)
Outdoor(C)
Outdoor Temp.(C)
Heating
P
r
e
s
s
u
r
e
(
k
g
f
/
c
m

G
)
S Heating
28/18 27/19 20/15
20 33.6 33.3 30.1
7 27.9 27 23.5
-5 24.2 23.9 19.9
-20 22.5 22.2 17.9
Indoor (C)
Outdoor(C)
NS1004PXEA_E_SM_33124A(1)_2.indd 5 2011-04-29 4:26:35
This Service Manual is a property of Samsung Electronics Co., Ltd.
Any unauthorized use of Manual can be punished under applicable
International and/or domestic law.
Samsung Electronics Co., Ltd. Apr. 2011.
Printed in Korea.
Code No. DB98-33124A(1)
GSPN(Global Service Partner Network)
Area Web Site
North America http://service.samsungportal.com
Latin America http://latin.samsungportal.com
CIS http://cis.samsungportal.com
Europe http://europe.samsungportal.com
China http://china.samsungportal.com
Asia http://asia.samsungportal.com
Mideast & Africa http://mea.samsungportal.com
NS1004PXEA_E_33124A(1)_co.indd 2 2011-04-29 4:19:20