You are on page 1of 8

ZECO AIRCON LIMITED

REF-ZECO/BLR/2013-14/JS/1139
25/02/2014
M/s. SAMARPITA ENGINEERS & CONSULTANTS P LTD,
BANGALORE
Kind Attn: - Mr. P. R. KAMATH
SUB: OFFER FOR DOUBLE SKIN FLOOR MOUNTED / CEILING SUSPENDED AIR HANDLING UNIT
FOR UPCOMING PROJECT, BANGALORE.

Sir,
With reference to your valued enquiry, we are hereby submitting our offer for ZECO make
units having
Following constructional features: DOUBLE SKIN CASING:
Outer skin
Inner Skin
Frame work
Thickness
panels

of

insulated

Material of Drain Pan


Unit Base

0.6 mm Pre- coated GI


0.6 mm Plain G.I
Hollow extruded Al Profile / Thermal break Al profile with
thermal barrier
25 / 46 / 43 mm thick, CFC Free PUF injected (Density: 40 kg / Cu.
m.)
20 G SS-304 Tray duly insulated with 13 mm closed cell Nitrile
insulation.
G.S.S base channel (only for floor mounted unit)

CHW COIL:
Make Of Coil
Coil Casing / Blank offs
Material Of Tube
Tube Dia (mm / inch)
Thickness of tube (SWG /
mm)
Header Material
Thickness
& Material of
fins
No. of Fins per inch (FPI)

ZECO (AHRI certified as per test standard ARI 410 & UL


certified for safety).
GI
Copper
12.7 mm / O.D.
27 SWG / 0.41 mm
MS
0.15 mm Plain Aluminum
11 / 12

DX COIL:
Make Of Coil
Coil Casing / Blank offs
Material Of Tube
Tube Dia (mm / inch)
Thickness of tube (SWG /
mm)
Header Material
Thickness
& Material of
fins
No. of Fins per inch (FPI)

ZECO
GI
Copper
9.52 mm

/ 3/8

O.D.(IGT)

27 SWG / 0.43 mm
Copper
0.15 mm Plain Aluminum
11 / 12

FILTERS:
Make Of Filters
Media of Filters
Efficiency of Pre-filters (EU4)

Sagicofim / Thermadyne / Spectrum / Puramatic / AAF


Synthetic (non woven type)
90 % down to 10 micron.

Bahadurgarh | Delhi | Mumbai | Bangalore | Chennai | Kolkata I Dubai


Tele phone # 011-45666110/111; Fax #011-45666100
Email: sales@zecoaircon.comVisit us at: http://www.zecoaircon.com

Page | 1

ZECO AIRCON LIMITED


REF-ZECO/BLR/2013-14/JS/1139
25/02/2014
Efficiency
(EU-7)

of

Fine-filters

99 % down to 03 micron

Fan & Motor:


Fan make
Motor make

Comefri / Kruger / Nicotra


ABB / CROMPTON /BHARAT BIJLEE/ SIEMENS

1] DOUBLE SKIN FLOOR MOUNTED HORIZONTAL AIR HANDLING UNIT SHALL HAVE: (43 thermal
break with extruded AL profile)

Mixing box with manually operated FA & RA damper in Al constructions.


Filter section with 50 mm thick (EU-4) box type pre filter & 305 mm thick (EU-7) bag (pocket) type fine filter
mounted on
Common GI filter frame.
Coil section with 6 row deep chilled water cooling coil.
Fan section with imported DIDW centrifugal backward curved fan, Drive set with V-belt & Motor (EFF-2).
Manually operated SA damper in AI constructions.

OPERATING PARAMETERS
Air Qty (CFM)
SP (mm wg)
Unit Model
Fan Type
Fan Dia
Fan RPM
Fan Outlet Velocity(M/s)
Shaft Absorbing Power
Motor (Kw)
Coil Area (Sq. ft)
Filter Area (Sq. ft)
Coil RD
L(mm)
W(mm)
H(mm)
Price (Rs.) Each
Qty (Nos.)
Amount(Rs.)

34000
60
ZDS-350
BC
1000
716
10
13.45
15
68
70
6
4080
3020
2700
924300
3
2772900

Option-1 with 25 mm hollow AL extruded profile


2] DOUBLE SKIN CEILING SUSPENDED BELT DRIVEN UNIT SHALL HAVE: (25 mm hollow AL extruded
profile)

25 mm thick (EU-4) box type pre filter.


Coil section with 4 row deep chilled water cooling coil.
Fan section with imported DIDW centrifugal forward curved fan, Drive set with V-belt & Motor
(EFF-2).
Manually operated SA damper in AI constructions.

Bahadurgarh | Delhi | Mumbai | Bangalore | Chennai | Kolkata I Dubai


Tele phone # 011-45666110/111; Fax #011-45666100
Email: sales@zecoaircon.comVisit us at: http://www.zecoaircon.com

Page | 2

ZECO AIRCON LIMITED


REF-ZECO/BLR/2013-14/JS/1139
25/02/2014
OPERATING PARAMETERS
Air Qty (CFM)
SP (mm wg)
Unit Model
Fan Type
Fan Dia
Fan RPM
Fan Outlet Velocity (M/s)
Shaft Absorbing Power
Motor (Kw)
Coil Area (Sq. ft)
CHW Coil RD
L(mm)
W(mm)
H(mm)
Price (Rs.) Each
Qty (Nos.)
Amount(Rs.)

2200
32
ZDCSBD-25
FC
12X12-S1
936
7.71
0.65
0.75
4.4
4
920
1040
670
54900
68
3733200

3200
32
ZDCSBD-30
FC
9X9-S2
1225
9.68
1.06
1.5
6.4
4
800
1480
540
68300
1
68300

3] DOUBLE SKIN CEILING SUSPENDED BELT DRIVEN UNIT SHALL HAVE: (25 mm hollow AL extruded
profile)

25 mm thick (EU-4) box type pre filter.


Coil section with 4 row deep chilled water cooling coil & 4 row deep DX-Type cooling coil with
single distributor.
Fan section with imported DIDW centrifugal forward curved fan, Drive set with V-belt & Motor
(EFF-2).
Manually operated SA damper in AI constructions.

OPERATING PARAMETERS
Air Qty (CFM)
SP (mm wg)
Unit Model
Fan Type
Fan Dia
Fan RPM
Fan Outlet Velocity (M/s)
Shaft Absorbing Power
Motor (Kw)
Coil area (Sq.Ft.)
DX-Coil area (Sq.Ft.)
CHW Coil RD
DX COIL
L(mm)
W(mm)
H(mm)

2200
40
ZDCSBD-25
FC
12X12-S1
1081
7.71
0.85
1.1
4.4
4.4
4
4
1420
1040
670

Bahadurgarh | Delhi | Mumbai | Bangalore | Chennai | Kolkata I Dubai


Tele phone # 011-45666110/111; Fax #011-45666100
Email: sales@zecoaircon.comVisit us at: http://www.zecoaircon.com

Page | 3

ZECO AIRCON LIMITED


REF-ZECO/BLR/2013-14/JS/1139
25/02/2014
75400
6
452400

Price (Rs.) Each


Qty (Nos.)
Amount(Rs.)

Option-2 with 46 mm hollow AL extruded profile


4] DOUBLE SKIN CEILING SUSPENDED BELT DRIVEN UNIT SHALL HAVE: (46 mm hollow AL extruded
profile)

25 mm thick (EU-4) box type pre filter.


Coil section with 4 row deep chilled water cooling coil.
Fan section with imported DIDW centrifugal forward curved fan, Drive set with V-belt & Motor
(EFF-2).
Manually operated SA damper in AI constructions.

OPERATING PARAMETERS
Air Qty (CFM)
SP (mm wg)
Unit Model
Fan Type
Fan Dia
Fan RPM
Fan Outlet Velocity (M/s)
Shaft Absorbing Power
Motor (Kw)
Coil Area (Sq. ft)
CHW Coil RD
L(mm)
W(mm)
H(mm)
Price (Rs.) Each
Qty (Nos.)
Amount(Rs.)

2200
32
ZDCSBD-25
FC
12X12-S1
936
7.71
0.65
0.75
4.4
4
960
1080
710
61000
RO
RO

3200
32
ZDCSBD-30
FC
9X9-S2
1225
9.68
1.06
1.5
6.4
4
840
1520
580
75000
RO
RO

5] DOUBLE SKIN CEILING SUSPENDED BELT DRIVEN UNIT SHALL HAVE: (46 mm hollow AL extruded
profile)

25 mm thick (EU-4) box type pre filter.


Coil section with 4 row deep chilled water cooling coil & 4 row deep DX-Type cooling coil with
single distributor.
Fan section with imported DIDW centrifugal forward curved fan, Drive set with V-belt & Motor
(EFF-2).
Manually operated SA damper in AI constructions.

OPERATING PARAMETERS
Air Qty (CFM)
SP (mm wg)
Unit Model

2200
40
ZDCSBD-25

Bahadurgarh | Delhi | Mumbai | Bangalore | Chennai | Kolkata I Dubai


Tele phone # 011-45666110/111; Fax #011-45666100
Email: sales@zecoaircon.comVisit us at: http://www.zecoaircon.com

Page | 4

ZECO AIRCON LIMITED


REF-ZECO/BLR/2013-14/JS/1139
25/02/2014
FC
12X12-S1
1081
7.71
0.85
1.1
4.4
4.4
4
4
1460
1080
710
84300
RO
RO

Fan Type
Fan Dia
Fan RPM
Fan Outlet Velocity (M/s)
Shaft Absorbing Power
Motor (Kw)
Coil area (Sq.Ft.)
DX-Coil area (Sq.Ft.)
CHW Coil RD
DX COIL
L(mm)
W(mm)
H(mm)
Price (Rs.) Each
Qty (Nos.)
Amount(Rs.)

Dimensions indicated above are tentative and may change during detailed
engineering.

VALUE OF QUOTATION
Total Basic Value (Rs.) with Option -1
Total Basic Value (Rs.) with Option -2
Total Qty (Nos.)

70,26,800/75,01,700/78 Nos.

Notes:
(1) The face velocity across all types of filters & coil has been considered 500 FPM.
(2) We have considered fan outlet velocity up to 10 M/s.
(3) We have considered 32 mm & 40 mm static pressure instead of 25 mm in ceiling
suspended units and 60 mm ststic pressure instead of 55 mm in floor mounted units for
suitable fan selection, Kindly check.
(4) We have consided 4 row deep coil in ceiling suspended units with manually operated dampers
in AI constructions.
(5) We have considered EU-5 fine filter as bag type with mixing chamber in above mentioned floor
mounted unit.
(6) We do not provide limit switch & light in ceiling suspended units , the same shall be provided on
chargeable basis
(if required).
(7) Plz note AHUs are designed based on CFM and Static pressure provided by you, any modification
due to changed CFM or Static Pressure will be done on chargeable basis.

DEVIATION: - We have considered 43 mm thick panel with thermal break profile instead of
45 mm thick panel.

EXCLUSIONS:
Bird Screen, junction box, flanges for coil header, Belt guard, Magnehelic gauges, Electrical
control panels, Accessories, all types of Controls & Instrumentation, actuators, VFD, Sound attenuators,
3/2 way mixing valves, Flow measuring devices, temperature & pressure measuring device and
sensors, grills, speed regulator switch, duct-connection, and any type of Electrical cabling, electrical
work, Unloading, Lifting, shifting of units to respective location, Storage of units at site,

Bahadurgarh | Delhi | Mumbai | Bangalore | Chennai | Kolkata I Dubai


Tele phone # 011-45666110/111; Fax #011-45666100
Email: sales@zecoaircon.comVisit us at: http://www.zecoaircon.com

Page | 5

ZECO AIRCON LIMITED


REF-ZECO/BLR/2013-14/JS/1139
25/02/2014
installation, testing & commissioning or any other which is Not specifically mentioned in our
offer.

Terms & Conditions


Prices

Ex-Works, Bangalore

Excise Duty & CESS

Shall be charged extra @ 10.3 % or as applicable at the time of


dispatch date.
LST /CST shall be charged extra @ 14.5% or 2% against Forms C
OR VAT be charged extra as applicable at the time of dispatch
All units are dispatched with packing of corrugated paper and polyethene
wrap. These basic packing charges are Included.

Sales Tax or VAT or CST


STD Packing
Special packing
Assembly

Special Crate Packing shall be charged extra as per your


specifications.
Included. However any kind of dismantling / re-assembly Work shall be on
Chargeable basis.

Freight

Shall be charged extra at actual.

Insurance

Shall be arranged by you and shall be to your account.

State Entry Tax & Octroi


Warranty (*) manufacturing

Shall be arranged by you and shall be to your account.


Our all units are warranted against any kind of manufacturing defects or
Poor Workmanship for a period of 12 months from the date of dispatch.
During this period the faulty part, if any, partially / fully will be replaced
Or repaired free of charge. However, all consumable like belts, filters Etc.
Are not covered under above warranty. Also, motor burn-out due to
Voltage / frequency fluctuation / single phasing or any other electrical
Disorder at your end will not be covered under the above warranty
Clause.
50% Advance along with the order and balance against Proforma
Invoice
Prior to dispatch.

Payment

Dispatch
Validity

To be confirm at the time of Finalization


30 days

PO address and other


details required.

1.ZECO AIRCON LTD


124-127,KIADB Industrial Area,3 RD Phase
Malur-563130 Dist-Kolar ,Karnataka (INDIA)
OR
1.ZECO AIRCON LTD
O- 1 & O- 5, Old Industrial Area, Bahadurgarh,
Distt. Jhajjar, Haryana (INDIA)
2. Billing & Delivery address shall be mention in your Purchase
Order
3. Site Person name & contact number
4. TIN / CST no.

Special Comments / Certifications


AHUs

Bahadurgarh | Delhi | Mumbai | Bangalore | Chennai | Kolkata I Dubai


Tele phone # 011-45666110/111; Fax #011-45666100
Email: sales@zecoaircon.comVisit us at: http://www.zecoaircon.com

Page | 6

ZECO AIRCON LIMITED


REF-ZECO/BLR/2013-14/JS/1139
25/02/2014

Fans

AHUs
AHUs

shall be with CE certified for Electrical & Mechanical safety.


shall be certified in accordance to EN-1886-1998 Certifications.
Mechanical Strength Class 2A
Casing Air Leakage Class B
Filter Bypass Leakage-Class F9
Thermal Bridging Class TB2

Fans are AMCA certified.

SALES -BANGALORE:
Mr. Samrat Pal
Direct: +91 9880834184
Mail: samratpal@zecoaircon.com

Mr. Raghavendra Gothe


Direct: +91 9900112537
Mail: raghu@zecoaircon.com

Our works & Branch office:


Our Works:

Branch Office

Zeco Aircon Ltd


124-127, KIADB Industrial Area
3 RD Phase
Malur 563130
Distt- Kolar, Karnataka

Zeco Aircon Ltd.


Prestige Court,
Flat No. 202, 2nd Floor, 101, KH Road (Double Rd)
Bengaluru 560027
Tele: 080 42114557
Mail: salesblr@zecoaircon.com

SALES SUPPORT:
Dispatch Related Queries
Mr. Chirag Saxena
Chennai & Bangalore Branch
Direct: 01276 325847/01276244650/651
Mail: chirag@zecoaircon.com

SERVICE/COMPLAINTS AND RETROFIT PROJECT:


CUSTOMER CARE
Mr. C
Surendran
Pan India
Service
Bangalore
Direct: 011- 45666144
Direct:
09880834185
Mail: customercare@zecoaircon.com Mail:
serviceblr@zecoaircon.com

If you have any suggestions/complaints, pls feel free to write to us feedback@zecoaircon.com


or by visiting our website, you can send us your feedback on the prescribed format.
We hope our offer is in line with your requirement. For any further clarification please feel free to
contact undersigned.
Thanks & Regards
For ZECO AIRCON LTD.

Priya Katiyar
Engineer -CQD
Desk.-011-45666158
Email-priya@zecoaircon.com

Bahadurgarh | Delhi | Mumbai | Bangalore | Chennai | Kolkata I Dubai


Tele phone # 011-45666110/111; Fax #011-45666100
Email: sales@zecoaircon.comVisit us at: http://www.zecoaircon.com

Page | 7

ZECO AIRCON LIMITED


REF-ZECO/BLR/2013-14/JS/1139
25/02/2014

Bahadurgarh | Delhi | Mumbai | Bangalore | Chennai | Kolkata I Dubai


Tele phone # 011-45666110/111; Fax #011-45666100
Email: sales@zecoaircon.comVisit us at: http://www.zecoaircon.com

Page | 8

You might also like