You are on page 1of 92

Hi gh Vol t age Cabl e

Connecting the World


Hi gh Vol tage
Ser vi ci ng Uti l i ty, Industri al , Commerci al
And Speci al ty Appl i cati ons
This new catalog contains in-depth information on the most comprehensive
line of High Voltage Power Cable available today.
The spec-on-a-page format was developed to meet your needs. It features
up-to-the-minute product information, from applications and constructions to
detailed technical and specification data. There s also a glossary of technical
terms for additional assistance.
And, of course, if you need any fur ther data, General Cable's Customer Service
staff provides the answer you need quickly and efficiently.
All information in this catalog is presented solely as a guide product selection and is believed to be
reliable. All printing errors are subject to correction in subsequent releases of this catalog. Although
General Cable has taken precautions to ensure the accuracy of the product specifications at the time
of publication, the specifications of all products contained herein are subject to change without
notice.

E-mail: info@generalcable.co.in
General Cabl e Energy Indi a Pvt Ltd
Corporate office: Centrum Plaza, Level 3, Tower A,
312 S, Golf Course Road, Sector- 53,
Gurgaon-122 002, Haryana.
Phone: (0124) 4326000 Fax: (0124) 4326019
Connectingthe World
I N T ERN A T I ON A L
ISO 9001:2000
CERT I F I CA T I O N
General Cable Corporation, headquar tered in Highland Heights Kentucky, a USD 6.2 billion revenue and over 13000 associates,
is a world leader in cable manufacturing with 46 modern production facilities in Nor th America, Europe and rest of the world and
provides service to global network of clients.
General Cable is a leader in the development, design, manufacture, marketing and distribution from power cables to
telecommunication cables including electric cables for utility , buildings, data transmission, instrumentation, optic fiber cables,
submarine cables, control and special cables and extra high voltage cables for market segments namely Energy, Industrial &
Specialty, and Communication.
General Cable's breadth of products is very extensive, including IS, IEC, IEEE, VDE, and other international standards covering
entire range of cable products.
General Cable has best- in- class research and development, testing and production facilities worldwide. The development of
unique compounds designed and tested to meet specific needs and stringent specifications, differentiates General Cable from all
others.

With superior R&D, engineering and manufacturing, leading logistics capabilities, the broadest product range in all the industry
segments, with a strong group of associates seamlessly teaming up to satisf y customers worldwide, makes General Cable as
world leader in wire and cable.

General Cabl e bases its activities on a series of Corporate Val ues which guide all its operations: Customer Sati sfacti on as an
absolute priority; Integri ty in all of its actions; Peopl e as the main source of value; Teamwork as a path to excellence; speed of
del i ver y as a competitive advantage; and conti nuous i mprovement as a constant objective.
This philosophy can only be assumed by a global company such as General Cable with extremely broad, diversified range, able
to meet any requirement, however specific, anywhere on the planet.

General Cable India is catering to Indian customer through its state of the ar t modern facility in 20 acre (Approx 80937 sq. mtrs)
situated at the Industrial town of Baddi in the beautiful state of Himachal Pradesh. The range of products manufactured includes
low voltage, high voltage, and extra high voltage and specialty cables. General Cable has extensive sales network across India.
One of the worl d's bi ggest compani es i n the Cabl e and Wi re Industr y...
Connectingthe World
General Cabl e s Gl obal Reach
General Cable serves customers through a global network of 46 manufacturing facilities in 23 countries
and sales representatives and distribution centers worldwide. The Company is solely dedicated to the
production of high-quality energy, industrial, specialty and communications wire and cable products. In
addition to its breadth of product line and strong brand recognition, the Company offers competitive
strengths in such areas as technology, manufacturing, distribution and logistics, and sales and customer
service. This combination enables General Cable to better serve its customers as they expand into new
geographic markets.
International Corp
NSW
BRAND

General Cabl e Footpri nt


Connecting the World
General Cable is a leader in the development,
des i gn, manuf ac t ur e, mar ket i ng and
distribution of copper, aluminum and fiber
optic wire and cable for the energy, industrial,
specialty and communications markets.
Our products inspire progress worldwide.....
.
Customers use our value-added products to
create global infrastructure that improves the
standard of living for people everywhere.
Eac h d ay w e r e b u i l d i n g b u s i n es s
momentum- developing ideas into innovative
solutions and industr y- leading products,
expanding geographic access and fur thering
our investment in highly capable associates,
Lean Manufacturing, material science and
technology resources.
General Cable is influencing the world...with more than two-thirds of our
sales generated outside Nor th America and more than 13,000 associates
in 46 manufacturing facilities throughout 23 countries. As the fif th largest
wire and cable manufacturer, we are the One Company Connecting the
World.
Energy Cabl es
Our cables carry energy across the world-through the air, underground
and under the sea. Increasing demand for energy is accelerating
investment in exploration, extraction, power generation, transmission
and distribution- whether based on coal, natural gas, oil, nuclear, wind or
water.
Industri al & Speci al ty Cabl es
We have the competitive product mix and global reach to suppor t the
production of oil, gas and petrochemical; construction of new factories
and maintenance of existing industrial facilities; factory automation; and
special applications such as military, nuclear, marine, mining, transit and
automotive.
Communi cati ons Cabl es
Our cables keep information flowing- facilitating a non-stop stream of
words and images around the world. We meet the high-speed bandwidth
needs of global communications networks from fiber optic, submarine
communications cables, copper and fiber aerial and underground cables
to copper and fiber optic enterprise cables and system solutions.
Indi a Headquar ters
General Cable Energy India Pvt Ltd
Corporate office: Centrum Plaza, Level 3, Tower A,
312 S, Golf Course Road, Sector- 53,
Gurgaon-122 002, Haryana.
Phone: (0124) 4326000 Fax: (0124) 4326019
E-mail: info@generalcable.co.in
Worl d Headquar ters
General Cable
4 Tesseneer Drive
Highland Heights, KY
41076-9753 U.S.A
Di r ecti ng Tr affi c without Gridlock
Bui l di ng Br i dges in the Sky
Maki ng Contact with the World
Connectingthe World
Qual i ty i s Forethought.
General Cable is committed to exceeding our customers expectations for quality and per formance.
We strive to ensure this quality through extensive in-house and third-par ty testing, with strict adherence
to our product specification and industr y standards. At General Cable, quality is not just a process, it
is forethought. It is the forethought of using the best materials and proactive prevention. This level of
quality is best represented in three core steps: Desi gn, Tec hnol ogy and Cont r ol .
General Cable Corporation is committed to developing, producing and marketing products that meet
the per formance, quality, value and safety requirements of our customers by continuously improving all
areas of our business. We apply Lean Sigma Company-wide, seeking innovative ways to differentiate our
products and ser vices and to ser ve as our customers and suppliers most valued business par tner.
Design
Design
Control
Control
Technology
Technology
Quality
Quality
International Corp
NSW
Connectingthe World
Commi tment to Qual i ty
Indian cable industr y is highly saturated with various organised / unorganised cable manufacturers.
The fierce competition leading to price war, may result into dilution in quality of product.
Under this scenario General Cable is giving maximum emphasis on quality of its cable products
and there by ensuring uninterr upted production to industries, safety to equipments and personnel.
Qual i ty Assurance Guaranteed
Through an ongoing quality assurance initiative, General Cable ensures the quality of product design,
manufacture, installation and expected service life, as well as environmentally sound products, processes
and policies, continuous research and development, combined with process control, quality audits and
prolonged stringent testing, provide an ever-growing range of specialty materials and designs that meet
industry approvals and standards.
Aerial view of General Cable factory at Baddi, H.P., India
BRAND

Connectingthe World
Our Green Ini ti ati ve symbol recogni zes our rol e
and responsi bi l i ty i n promoti ng sustai nabi l i ty.
The symbol al so refl ects our commi tment to achi evi ng
i ndustr y-l eadi ng standards and respondi ng
proacti vel y to envi ronmental gl obal i ssues.
IN T I N I E A
T E
I R V
G E
Commi tment To Envi ronment - Green Factor y
Compl i ant to Indi an Green Bui l di ng Counci l Rati ng
Commi tment To Envi ronment - Green Factor y
Compl i ant to Indi an Green Bui l di ng Counci l Rati ng
International Corp
NSW
Products
for al l
markets
Connectingthe World
BRAND

S M
Underground Hi gh-Vol tage and
Extra-Hi gh-Vol tage Cabl es
General Cable s complete line of Silec insulated
high- and extra-high-voltage underground energy
cables, from 63kV up to 500kV, and our state-of the-ar t
accessories - such as pre-molded joints and terminals -
enable us to provide turnkey design and engineering
services for the global, systems engineered, electric
utility market.
Bare Overhead Hi gh-Vol tage Transmi ssi on and
Di stri buti on Conductors
Our TransPowr bare aluminum overhead conductors
are available in standard ACSR, specialized T-2 designs
and high temperature ACSS/ TW designs. Our new
ACCC/ TW conductors feature an innovative composite
core construction which possesses high temperature
and increased strength characteristics.
Low- and Medi um-Vol tage Di stri buti on Cabl es
General Cable s extensive line of BICC Brand
PowrServ and EmPowr copper and aluminum
cables serve the total distribution needs of electric
utilities, rural electric co-ops and the public power
market for both traditional and renewable energy
resources.
Industri al Cabl es
General Cable s industrial instrumentation, power
and control cables serve an extensive range of
markets including power generation, refining and
petrochemical, natural gas production, steel, pulp and
paper, and factory automation.
Speci al ty Cabl es
General Cable manufactures a broad range of specialty
cables that meet the exacting specifications for original
equipment manufacturers (OEMs), military, transit,
offshore and marine shipboard, nuclear, and mining
applications. General Cable s engineered Brand Rex and
Anaconda Brand wire and cable solutions provide
great lifecycle per formance and reliability - meeting
customer applications requirements today, while setting
tomorrow s standards.
Energy Cabl es Industri al & Speci al ty Cabl es
Speci al ty Wi re Harnesses
We supply application-specific and custom-designed
cable, harnesses and assemblies for a wide variety of OEM
applications, including business machines, material
handling equipment, factory automation, medical
equipment and the automotive af termarket. General Cable
is a global leader in the manufacture of automotive wire
and cable from ignition wire sets and single leads to bulk
ignition wire, primary wire and battery star ter cable.
Cord and Cordset Products
General Cable s Carol Brand is the most recognized
name in flexible cords for temporary power. Our extensive
line includes por table cord, cordsets, por table power cable
and premium-grade cable for commercial and industrial
applications.
El ectroni c Cabl es
Our Carol Brand and Helix/ HiTemp products fulfill the
complete wire and cable requirements of the fast-changing
electronics, sound and security marketplaces. We offer
hookup wire; communications cable; computer, coaxial
and microphone cables; and special designs for security
systems, fire alarms, and audio, video and digital
broadcasts.
Communi cati ons Cabl es
Data Communi cati ons Cabl es
Our GenSPEED Brand products are on the job wherever
enhanced per formance is critical from Gigabit Ethernet,
token ring and broadband applications to patch panels,
communications closets and plenum applications.
We offer one of the most comprehensive lines of
enhanced high-speed Category products, including
PanGen structured cabling system solutions.
Fi ber Opti c Cabl es
We provide a full menu of NextGen Brand fiber optic
cables for data communications and voice and video
networks. Our products range from tight buffer and
armored products for military applications to loose tube
and hybrid cables for communications networks. We also
offer advanced Blolite blown fiber systems for Local
Area Networks and campus applications.
Tel ecommuni cati ons Cabl es
Our broad range of industry-standard General Cable
outside plant wire and cable products ensures reliable,
cost-effective per formance. We provide air core, filled
core and specialty wire products for aerial, buried and
duct applications.
Now one industry leader focuses its worldwide resources on delivering
maximum value to customers. It s the cost-effective advantage of a
single resource, a single company that provides the broadest product
range, the highest level of commitment to customer and technical
suppor t, the most cost-effective manufacturing and distribution, and the
most responsive customer-first service. In today s highly competitive
worldwide markets, General Cable provides the single-source
solution with benefits that go straight to your bottom line. Ask your
representative about other General Cable products.
International Corp NSW
BRAND

CONNECTING THE WORLD


Maki ng Cabl es i s about Creati ng
Potenti al
General Cabl e products hel p to i l l umi nate the worl d,
i nspi re progress and open l i nes of communi cati on.
We connect peopl e wi th energy, i nformati on, i deas
and oppor tuni ti es.
For more than a century, General Cable has been a leader in
the development, manufacture, marketing and distribution of
wire and cable-our sole business. Today, we continue to
direct our worldwide resources to deliver maximum value to
customers through a power ful combination of product and
service innovations.
At General Cable we aim to add value to our customers
businesses by understanding and competitively servicing
their needs through customer intimacy operational
excellence.
General Cabl e provi des a si ngl e source sol uti on
The cost effective advantage of a single resource, a single
company that provides one of the broadest product ranges,
highest levels of customer and technical suppor t and
responsive customer-first service.
THE POWER OF ONE
At General Cable, THE POWER OF ONE embodies our
integrated approach to business: one company with the
power of our products, exper tise, systems and people all
focused on one goal - fulfilling our customers needs. It
means one source customers can count on for DATA,
COMMUNICATION, INDUSTRIAL and ENERGY cables. Most
of all, THE POWER OF ONE means one team, well trained and
wholly committed to the highest level of customer
satisfaction.
Manufacturi ng and
l ogi sti cs
With superior engineering and
m a n u f a c t u r i n g o p er a t i o n s ,
i n d u s t r y - l e a d i n g l o g i s t i c s
capabilities, one of the broadest
product ranges in the industry, and
a strong group of employees
seamlessly teaming to satisf y
cust omers, General Cabl e i s
s t r ong, di ver s i f i ed and w el l
positioned to meet the challenges
of tomorrow.
Sal es and Di stri buti on
Network
General Cable has a distribution
network throughout India and a
team of people committed to
meeting the total needs of our
customers- by providing enhanced
di st r i but i on and war ehousi ng
services, and an unprecedented
level of technical suppor t.
Strength, Di versi ty
and Teamwork
Every product reflects our POWER
OF ONE business philosophy. We
have become a leading cable
supplier in Asla pacific through
excellent customer relationships,
the quality of our people and the
highest standards of service.
GENERAL CABLE INDIA
Qual i ty Products, Peopl e and Ser vi ce
ConnectingtheWorld
OUR VISION
Strive for leadership through growth and excellence.
General Cabl e Indi a i s a l eadi ng suppl i er of cabl e sol uti ons for energy, i ndustri al , data, communi cati ons and
speci al i st appl i cati ons. As par t of the US based General Cabl e Corporati on (one of the worl d s l argest wi re
and cabl e manufacturers) we ser ve customers through a gl obal network of for ty si x manufacturi ng faci l i ti es
i n twenty three countri es, wi th sal es and di stri buti on centers worl dwi de.
As par t of a global business we are able to draw on innovative engineering developments, a comprehensive product range
and the best research and technical suppor t available, ensuring our customers are offered a competitive edge.
High Voltage Cable
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
PRODUCT SELECTION LOCATOR
TYPE LETTER CODE REFERENCE STANDARD CABLE DESCRIPTION PAGE NO. HV CABLES
TECHNICAL INFORMATION 49 - 73
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
2XWaY
2XY
A2XWaY
A2XY
1 - 4
3.3 KV, Single Core XLPE
Power Cables
IS : 7098 Part - 2
5 - 8
6.6 KV(E), Single Core XLPE
Power Cables
2XWaY
A2XY
A2XWaY
2XY
A2XFY
2XFY
A2XWY
2XWY
A2XFY
2XFY
A2XWY
2XWY
A2XFY
2XFY
A2XWY
2XWY
A2XFY
2XFY
A2XWY
2XWY
A2XFY
2XFY
A2XWY
2XWY
A2XFY
2XFY
A2XWY
2XWY
2XWaY
2XY
A2XWaY
A2XY
2XWaY
2XY
A2XWaY
A2XY
2XWaY
2XY
A2XWaY
A2XY
2XWaY
2XY
A2XWaY
A2XY
IS : 7098 Part - 2
33 KV(E), Three Core XLPE
Armoured Power Cables
22 KV(E), Three Core XLPE
Armoured Power Cables
11 KV(E), Three Core XLPE
Armoured Power Cables
6.6 KV(E), Three Core XLPE
Armoured Power Cables
3.3 KV, Three Core XLPE
Armoured Power Cables
33 KV(E), Single Core XLPE
Power Cables
22 KV(E), Single Core XLPE
Power Cables
11 KV (E), Single Core XLPE
Power Cables
45 - 48
41 - 44
37 - 40
33 - 36
29 - 32
25 - 28
21 - 24
17 - 20
13 - 16
9 - 12
11 KV(UE), Three Core XLPE
Armoured Power Cables
11 KV(UE), Single Core XLPE
Power Cables
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Conductor : Round Compact Stranded Aluminium
Insulation : Cross - Linked Polyethylene (XLPE)
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces #
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
10 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
#Applicable for Screened cables, available
upon request.
Options :
SINGLE CORE 3.3 KV (E) & (UE)
ALUMINIUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor
Outer Sheath
Armour
Insulation
1
25 2.5 1.4 1.24 19.0 350 0.23 0.136 100 90 115 500
35 2.5 1.4 1.24 20.0 400 0.26 0.130 120 110 140 500
50 2.5 1.4 1.40 21.0 450 0.29 0.125 140 125 165 500
70 2.5 1.6 1.40 23.0 600 0.34 0.116 170 155 210 500
95 2.5 1.6 1.40 25.0 700 0.39 0.110 205 180 250 500
120 2.5 1.6 1.40 26.5 800 0.43 0.106 230 205 290 500
150 2.5 1.6 1.40 28.0 900 0.47 0.103 255 225 335 500
185 2.5 1.6 1.40 29.5 1,050 0.52 0.099 290 255 395 500
240 2.5 1.6 1.56 32.0 1,250 0.58 0.096 330 295 450 500
300 2.6 1.6 1.56 34.5 1,500 0.62 0.093 370 330 510 500
400 2.6 2.0 1.56 38.0 1,850 0.70 0.090 415 370 610 500
500 2.8 2.0 1.56 42.0 2,250 0.74 0.088 465 425 695 500
630 3.1 2.0 1.72 46.5 2,800 0.76 0.086 520 480 795 500
800 3.3 2.0 1.88 52.0 3,500 0.81 0.085 560 520 880 500
1000 3.6 2.5 2.04 58.5 4,450 0.84 0.085 600 550 980 500
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
Standard
Delivery
Length
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground Air Duct
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
Approx.
Reactance
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Conductor : Round Compact Stranded Plain Copper
Insulation : Cross - Linked Polyethylene (XLPE)
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath
Armour
Insulation
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces #
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
10 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
#Applicable for Screened cables, available
upon request.
Options :
SINGLE CORE 3.3 KV (E) & (UE)
COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
2
25 2.5 1.4 1.24 19.0 500 0.23 0.136 125 115 145 500
35 2.5 1.4 1.24 20.0 600 0.26 0.130 150 135 175 500
50 2.5 1.4 1.40 21.0 750 0.29 0.125 175 155 210 500
70 2.5 1.6 1.40 23.0 1,000 0.34 0.116 220 190 255 500
95 2.5 1.6 1.40 25.0 1,250 0.39 0.110 255 230 320 500
120 2.5 1.6 1.40 26.5 1,500 0.43 0.106 295 260 370 500
150 2.5 1.6 1.40 28.0 1,750 0.47 0.103 325 290 425 500
185 2.5 1.6 1.40 29.5 2,100 0.52 0.099 365 325 480 500
240 2.5 1.6 1.56 32.0 2,650 0.58 0.096 415 375 565 500
300 2.6 1.6 1.56 34.5 3,250 0.62 0.093 460 420 645 500
400 2.6 2.0 1.56 38.0 4,100 0.70 0.090 515 470 750 500
500 2.8 2.0 1.56 42.0 5,150 0.74 0.088 565 520 850 500
630 3.1 2.0 1.72 46.5 6,550 0.76 0.086 615 575 950 500
800 3.3 2.0 1.88 52.0 8,250 0.81 0.085 645 600 1030 500
1000 3.6 2.5 2.04 58.5 10,400 0.84 0.085 675 630 1110 500
Standard
Delivery
Length
Ground Air Duct
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
Approx.
Reactance
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Conductor : Round Compact Stranded Aluminium
Insulation : Cross - Linked Polyethylene (XLPE)
Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath
Screen
Insulation
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces #
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
10 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
#Applicable for Screened cables, available
upon request.
Options :
SINGLE CORE 3.3 KV (E) & (UE)
ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
3
25 2.2 1.8 16.0 250 0.26 0.125 100 90 110 500
35 2.2 1.8 17.0 300 0.29 0.119 115 100 135 500
50 2.2 1.8 18.0 350 0.32 0.114 135 120 160 500
70 2.2 1.8 19.5 400 0.38 0.105 170 155 195 500
95 2.2 2.0 22.0 550 0.44 0.102 200 185 250 500
120 2.2 2.0 23.5 600 0.48 0.098 225 210 280 500
150 2.2 2.0 25.0 700 0.53 0.095 255 230 325 500
185 2.2 2.0 26.5 850 0.58 0.092 285 260 370 500
240 2.2 2.0 29.0 1,000 0.65 0.089 330 300 440 500
300 2.2 2.0 31.0 1,200 0.72 0.086 375 330 510 500
400 2.2 2.2 34.5 1,550 0.82 0.084 425 380 600 500
500 2.4 2.2 38.5 1,900 0.85 0.082 480 430 700 500
630 2.6 2.2 42.5 2,350 0.90 0.080 540 500 830 500
800 2.8 2.4 47.5 2,950 0.94 0.079 620 540 950 500
1000 3.0 2.6 53.0 3,700 0.99 0.078 685 600 1080 500
Standard
Delivery
Length
Air Duct Ground
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces #
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
10 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
#Applicable for Screened cables, available
upon request.
Options :
Conductor
Outer Sheath
Screen
Insulation
SINGLE CORE 3.3 KV (E) & (UE)
COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Insulation : Cross - Linked Polyethylene (XLPE)
Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
4
25 2.2 1.8 16.0 400 0.26 0.125 125 115 140 500
35 2.2 1.8 17.0 500 0.29 0.119 150 140 170 500
50 2.2 1.8 18.0 600 0.32 0.114 175 160 200 500
70 2.2 1.8 19.5 800 0.38 0.105 220 200 250 500
95 2.2 2.0 22.0 1,100 0.44 0.102 260 235 310 500
120 2.2 2.0 23.5 1,300 0.48 0.098 290 270 360 500
150 2.2 2.0 25.0 1,550 0.53 0.095 330 300 420 500
185 2.2 2.0 26.5 1,900 0.58 0.092 370 335 470 500
240 2.2 2.0 29.0 2,400 0.65 0.089 425 385 560 500
300 2.2 2.0 31.0 3,000 0.72 0.086 480 430 650 500
400 2.2 2.2 34.5 3,800 0.82 0.084 540 490 760 500
500 2.4 2.2 38.5 4,800 0.85 0.082 605 545 870 500
630 2.6 2.2 42.5 6,100 0.90 0.080 675 600 1000 500
800 2.8 2.4 47.5 7,750 0.94 0.079 745 660 1140 500
1000 3.0 2.6 53.0 9,700 0.99 0.078 810 715 1260 500
Standard
Delivery
Length
Air Duct Ground
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
12 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 6.6 KV (E)
ALUMINUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath Insulation Shield
Conductor Shield
Armour
Insulation
5
25 2.8 1.6 1.40 23.0 500 0.23 0.148 100 90 120 500
35 2.8 1.6 1.40 24.0 550 0.26 0.141 120 110 145 500
50 2.8 1.6 1.40 25.0 650 0.28 0.136 140 125 170 500
70 2.8 1.6 1.40 26.5 750 0.32 0.125 170 155 215 500
95 2.8 1.6 1.40 28.5 850 0.37 0.119 205 180 260 500
120 2.8 1.6 1.40 30.0 1,000 0.41 0.114 230 210 300 500
150 2.8 1.6 1.56 32.0 1,100 0.45 0.111 255 230 340 500
185 2.8 1.6 1.56 33.5 1,250 0.49 0.107 290 260 390 500
240 2.8 2.0 1.56 36.5 1,550 0.54 0.104 330 300 460 500
300 3.0 2.0 1.56 39.0 1,800 0.56 0.101 370 340 520 500
400 3.3 2.0 1.72 43.0 2,200 0.58 0.098 415 385 600 500
500 3.5 2.0 1.72 47.0 2,650 0.62 0.095 465 430 690 500
630 3.5 2.0 1.88 51.0 3,200 0.69 0.092 520 480 815 500
800 3.5 2.5 2.04 56.5 4,000 0.78 0.091 560 520 890 500
1000 3.6 2.5 2.20 62.0 4,800 0.85 0.089 600 550 985 500
DIMENSIONS
Standard
Delivery
Length
ELECTRICAL PARAMETERS
Current Rating
Ground Air Duct
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
Approx.
Reactance
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
12 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 6.6 KV (E)
COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Outer Sheath
Conductor Shield
Insulation Shield
Insulation
Conductor
Armour
6
25 2.8 1.6 1.40 23.0 650 0.23 0.148 130 115 155 500
35 2.8 1.6 1.40 24.0 800 0.26 0.141 155 135 185 500
50 2.8 1.6 1.40 25.0 900 0.28 0.136 180 155 220 500
70 2.8 1.6 1.40 26.5 1,150 0.32 0.125 220 195 275 500
95 2.8 1.6 1.40 28.5 1,400 0.37 0.119 260 230 330 500
120 2.8 1.6 1.40 30.0 1,650 0.41 0.114 290 265 380 500
150 2.8 1.6 1.56 32.0 1,950 0.45 0.111 330 295 435 500
185 2.8 1.6 1.56 33.5 2,350 0.49 0.107 365 330 500 500
240 2.8 2.0 1.56 36.5 2,950 0.54 0.104 415 380 575 500
300 3.0 2.0 1.56 39.0 3,600 0.56 0.101 460 425 650 500
400 3.3 2.0 1.72 43.0 4,450 0.58 0.098 510 470 740 500
500 3.5 2.0 1.72 47.0 5,550 0.62 0.095 560 525 835 500
630 3.5 2.0 1.88 51.0 6,950 0.69 0.092 615 575 960 500
800 3.5 2.5 2.04 56.5 8,800 0.78 0.091 640 600 1020 500
1000 3.6 2.5 2.20 62.0 10,800 0.85 0.089 675 625 1105 500
Minimum
Outer
Sheath
Thickness
Standard
Delivery
Length
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground Air Duct
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
Approx.
Reactance
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
12 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 6.6 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Insulation
Conductor
Conductor Shield
Insulation Shield
Outer Sheath
Metallic Insulation Screen
7
25 2.8 1.8 20.0 350 0.23 0.137 100 90 115 500
35 2.8 2.0 21.5 450 0.26 0.132 120 110 140 500
50 2.8 2.0 22.5 500 0.28 0.127 140 130 165 500
70 2.8 2.0 24.0 600 0.32 0.116 175 160 210 500
95 2.8 2.0 26.0 700 0.37 0.111 205 190 255 500
120 2.8 2.0 27.5 800 0.41 0.107 230 215 295 500
150 2.8 2.0 29.0 900 0.45 0.104 260 240 335 500
185 2.8 2.0 30.5 1,000 0.49 0.099 295 275 385 500
240 2.8 2.2 33.0 1,250 0.54 0.096 340 315 455 500
300 3.0 2.2 36.0 1,500 0.56 0.095 380 355 525 500
400 3.3 2.2 39.5 1,800 0.58 0.092 435 405 610 500
500 3.5 2.4 43.5 2,250 0.62 0.089 495 460 710 500
630 3.5 2.4 47.5 2,700 0.69 0.087 570 530 840 500
800 3.5 2.6 52.5 3,350 0.78 0.085 640 600 985 500
1000 3.6 2.8 57.5 4,100 0.85 0.083 705 660 1110 500
Standard
Delivery
Length
Air Duct Ground
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
12 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
25 2.8 1.8 20.0 500 0.23 0.137 130 120 150 500
35 2.8 2.0 21.5 600 0.26 0.132 155 140 180 500
50 2.8 2.0 22.5 750 0.28 0.127 180 165 215 500
70 2.8 2.0 24.0 950 0.32 0.116 220 200 270 500
95 2.8 2.0 26.0 1,250 0.37 0.111 265 240 325 500
120 2.8 2.0 27.5 1,500 0.41 0.107 300 275 375 500
150 2.8 2.0 29.0 1,750 0.45 0.104 335 310 430 500
185 2.8 2.0 30.5 2,100 0.49 0.099 375 350 495 500
240 2.8 2.2 33.0 2,650 0.54 0.096 435 410 580 500
300 3.0 2.2 36.0 3,250 0.56 0.095 490 450 670 500
400 3.3 2.2 39.5 4,050 0.58 0.092 550 515 770 500
500 3.5 2.4 43.5 5,150 0.62 0.089 615 570 890 500
630 3.5 2.4 47.5 6,450 0.69 0.087 700 650 1050 500
800 3.5 2.6 52.5 8,150 0.78 0.085 770 720 1190 500
1000 3.6 2.8 57.5 10,100 0.85 0.083 840 780 1320 500
Conductor Shield
Insulation Shield
Conductor
Insulation
Metallic Insulation Screen
Outer Sheath
SINGLE CORE 6.6 KV (E)
COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
8
Standard
Delivery
Length
Air Duct Ground
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
17 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 11 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath Insulation Shield
Conductor Shield
Armour
Insulation
9
25 3.6 1.60 1.40 24.5 600 0.19 0.152 100 90 120 500
35 3.6 1.60 1.40 25.5 650 0.21 0.145 120 110 145 500
50 3.6 1.60 1.40 26.5 700 0.23 0.139 140 125 170 500
70 3.6 1.60 1.40 28.5 800 0.27 0.129 170 155 215 500
95 3.6 1.60 1.40 30.0 950 0.30 0.122 205 185 260 500
120 3.6 1.60 1.56 32.0 1,100 0.33 0.118 230 210 300 500
150 3.6 1.60 1.56 33.5 1,200 0.36 0.114 255 230 340 500
185 3.6 2.00 1.56 36.0 1,450 0.39 0.112 290 260 390 500
240 3.6 2.00 1.56 38.0 1,650 0.44 0.107 330 300 460 500
300 3.6 2.00 1.56 40.5 1,900 0.48 0.104 370 335 530 500
400 3.6 2.00 1.72 43.5 2,250 0.54 0.099 415 380 605 500
500 3.6 2.00 1.72 47.0 2,650 0.60 0.095 460 430 685 500
630 3.6 2.00 1.88 51.0 3,200 0.68 0.092 515 485 800 500
800 3.6 2.50 2.04 57.0 4,000 0.76 0.091 555 520 890 500
1000 3.6 2.50 2.20 62.0 4,800 0.85 0.089 600 550 990 500
Standard
Delivery
Length
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground Air Duct
Approx.
Capacitance
Approx.
Reactance
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) Z (Sqmm) (mm) (mm) (mm) (mm) (Kg/km)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
17 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 11 KV (E)
COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Outer Sheath
Conductor Shield
Insulation Shield
Insulation
Conductor
Armour
10
25 3.6 1.60 1.40 24.5 700 0.19 0.152 130 115 155 500
35 3.6 1.60 1.40 25.5 850 0.21 0.145 150 135 185 500
50 3.6 1.60 1.40 26.5 1,000 0.23 0.139 180 160 220 500
70 3.6 1.60 1.40 28.5 1,200 0.27 0.129 220 200 275 500
95 3.6 1.60 1.40 30.0 1,500 0.30 0.122 260 230 330 500
120 3.6 1.60 1.56 32.0 1,750 0.33 0.118 295 265 385 500
150 3.6 1.60 1.56 33.5 2,050 0.36 0.114 325 300 435 500
185 3.6 2.00 1.56 36.0 2,500 0.39 0.112 365 330 495 500
240 3.6 2.00 1.56 38.0 3,050 0.44 0.107 415 380 585 500
300 3.6 2.00 1.56 40.5 3,650 0.48 0.104 460 425 660 500
400 3.6 2.00 1.72 43.5 4,500 0.54 0.099 510 470 745 500
500 3.6 2.00 1.72 47.0 5,550 0.60 0.095 560 525 835 500
630 3.6 2.00 1.88 51.0 6,950 0.68 0.092 615 570 960 500
800 3.6 2.50 2.04 57.0 8,800 0.76 0.091 640 590 1030 500
1000 3.6 2.50 2.20 62.0 10,800 0.85 0.089 670 620 1110 500
Standard
Delivery
Length
Ground Air Duct
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
Approx.
Reactance
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
25 3.6 2.0 22.0 450 0.19 0.143 100 90 115 500
35 3.6 2.0 23.0 500 0.21 0.137 120 110 140 500
50 3.6 2.0 24.0 550 0.23 0.131 140 130 165 500
70 3.6 2.0 25.5 650 0.27 0.120 175 160 210 500
95 3.6 2.0 27.5 750 0.30 0.115 205 190 255 500
120 3.6 2.0 29.0 850 0.33 0.110 235 220 295 500
150 3.6 2.0 30.5 950 0.36 0.107 260 240 335 500
185 3.6 2.2 32.5 1,150 0.39 0.104 295 275 385 500
240 3.6 2.2 35.0 1,350 0.44 0.100 340 315 455 500
300 3.6 2.2 37.0 1,550 0.48 0.096 385 360 525 500
400 3.6 2.2 40.0 1,850 0.54 0.092 435 410 610 500
500 3.6 2.4 44.0 2,250 0.60 0.090 495 460 710 500
630 3.6 2.4 47.5 2,750 0.68 0.087 570 530 840 500
800 3.6 2.6 52.5 3,400 0.76 0.085 640 600 985 500
1000 3.6 2.8 57.5 4,100 0.85 0.083 710 660 1110 500
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
17 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 11 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Insulation
Conductor
Conductor Shield
Insulation Shield
Outer Sheath
Metallic Insulation Screen
11
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
DIMENSIONS
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Standard
Delivery
Length
Air Duct Ground
ELECTRICAL PARAMETERS
Current Rating
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
17 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 11 KV (E)
COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor Shield
Insulation Shield
Conductor
Insulation
Metallic Insulation Screen
Outer Sheath
12
Standard
Delivery
Length
Duct Ground
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Air
(Mtr./Drum) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm) (Amp)
25 3.6 2.0 22.0 600 0.19 0.143 130 120 150 500
35 3.6 2.0 23.0 700 0.21 0.137 155 140 180 500
50 3.6 2.0 24.0 800 0.23 0.131 180 165 215 500
70 3.6 2.0 25.5 1,050 0.27 0.120 220 205 270 500
95 3.6 2.0 27.5 1,300 0.30 0.115 265 240 325 500
120 3.6 2.0 29.0 1,550 0.33 0.110 300 275 380 500
150 3.6 2.0 30.5 1,800 0.36 0.107 335 310 430 500
185 3.6 2.2 32.5 2,200 0.39 0.104 380 340 495 500
240 3.6 2.2 35.0 2,750 0.44 0.100 435 410 585 500
300 3.6 2.2 37.0 3,300 0.48 0.096 490 460 670 500
400 3.6 2.2 40.0 4,100 0.54 0.092 550 515 770 500
500 3.6 2.4 44.0 5,150 0.60 0.090 620 570 890 500
630 3.6 2.4 47.5 6,500 0.68 0.087 700 650 1050 500
800 3.6 2.6 52.5 8,200 0.76 0.085 770 720 1190 500
1000 3.6 2.8 57.5 10,100 0.85 0.083 840 780 1320 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
28 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 11 KV (UE)
ALUMINIUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath Insulation Shield
Conductor Shield
Armour
Insulation
13
25 5.5 1.60 1.40 28.5 750 0.14 0.162 100 90 120 500
35 5.5 1.60 1.40 29.5 800 0.16 0.155 120 110 145 500
50 5.5 1.60 1.56 31.0 900 0.17 0.149 140 125 175 500
70 5.5 1.60 1.56 32.5 1,050 0.19 0.138 170 155 215 500
95 5.5 2.00 1.56 34.5 1,150 0.22 0.131 205 185 265 500
120 5.5 2.00 1.56 36.5 1,400 0.24 0.127 230 210 305 500
150 5.5 2.00 1.56 38.0 1,500 0.26 0.122 255 235 345 500
185 5.5 2.00 1.56 39.5 1,650 0.28 0.118 290 270 390 500
240 5.5 2.00 1.72 42.5 1,950 0.31 0.114 330 310 465 500
300 5.5 2.00 1.72 44.5 2,200 0.33 0.110 370 340 530 500
400 5.5 2.00 1.88 48.0 2,600 0.37 0.105 415 390 605 500
500 5.5 2.00 1.88 51.5 3,000 0.42 0.101 465 440 700 500
630 5.5 2.50 2.04 56.5 3,750 0.46 0.099 510 480 790 500
800 5.5 2.50 2.20 61.0 4,450 0.52 0.095 555 520 880 500
1000 5.5 2.50 2.20 65.5 5,200 0.58 0.092 595 560 970 500
Approx.
Reactance
Standard
Delivery
Length
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground Air Duct
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
28 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 11 KV (UE)
COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Outer Sheath
Conductor Shield
Insulation Shield
Insulation
Conductor
Armour
14
25 5.5 1.60 1.40 28.5 900 0.14 0.162 130 115 155 500
35 5.5 1.60 1.40 29.5 1,000 0.16 0.155 155 140 185 500
50 5.5 1.60 1.56 31.0 1,200 0.17 0.149 180 160 225 500
70 5.5 1.60 1.56 32.5 1,450 0.19 0.138 210 200 280 500
95 5.5 2.00 1.56 34.5 1,700 0.22 0.131 260 240 340 500
120 5.5 2.00 1.56 36.5 2,050 0.24 0.127 290 270 390 500
150 5.5 2.00 1.56 38.0 2,350 0.26 0.122 325 300 440 500
185 5.5 2.00 1.56 39.5 2,750 0.28 0.118 365 335 500 500
240 5.5 2.00 1.72 42.5 3,350 0.31 0.114 415 385 585 500
300 5.5 2.00 1.72 44.5 3,950 0.33 0.110 460 430 660 500
400 5.5 2.00 1.88 48.0 4,850 0.37 0.105 505 470 740 500
500 5.5 2.00 1.88 51.5 5,900 0.42 0.101 560 520 850 500
630 5.5 2.50 2.04 56.5 7,450 0.46 0.099 600 560 935 500
800 5.5 2.50 2.20 61.0 9,200 0.52 0.095 640 600 1020 500
1000 5.5 2.50 2.20 65.5 11,200 0.58 0.092 675 630 1100 500
Standard
Delivery
Length
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground Air Duct
Approx.
Capacitance
Approx.
Reactance
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
28 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 11 KV (UE)
ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Insulation
Conductor
Conductor Shield
Insulation Shield
Outer Sheath
Metallic Insulation Screen
15
25 5.5 2.0 26.0 600 0.14 0.154 100 95 120 500
35 5.5 2.0 27.0 650 0.16 0.147 120 115 145 500
50 5.5 2.0 28.0 700 0.17 0.141 140 130 170 500
70 5.5 2.0 29.5 800 0.19 0.130 175 160 215 500
95 5.5 2.0 31.5 950 0.22 0.123 205 190 260 500
120 5.5 2.2 33.5 1,050 0.24 0.120 235 215 300 500
150 5.5 2.2 35.0 1,200 0.26 0.116 260 240 340 506
185 5.5 2.2 36.5 1,350 0.28 0.111 295 275 390 500
240 5.5 2.2 38.5 1,550 0.31 0.106 340 320 460 500
300 5.5 2.2 41.0 1,800 0.33 0.103 385 360 530 500
400 5.5 2.4 44.5 2,150 0.37 0.099 435 410 615 500
500 5.5 2.4 47.5 2,550 0.42 0.095 500 470 725 500
630 5.5 2.6 52.0 3,100 0.46 0.092 570 535 840 500
800 5.5 2.8 57.0 3,750 0.52 0.090 640 605 975 500
1000 5.5 2.8 61.5 4,450 0.58 0.087 710 670 1100 500
Standard
Delivery
Length
Air Duct Ground
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
DIMENSIONS
Standard
Delivery
Length
Air Duct Ground
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
ELECTRICAL PARAMETERS
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
28 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 11 KV (UE)
COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor Shield
Insulation Shield
Conductor
Insulation
Metallic Insulation Screen
Outer Sheath
16
25 5.5 2.0 26.0 750 0.14 0.154 130 120 150 500
35 5.5 2.0 27.0 850 0.16 0.147 155 145 185 500
50 5.5 2.0 28.0 950 0.17 0.141 180 170 220 500
70 5.5 2.0 29.5 1,200 0.19 0.130 220 205 275 500
95 5.5 2.0 31.5 1,500 0.22 0.123 265 245 335 500
120 5.5 2.2 33.5 1,750 0.24 0.120 300 275 385 500
150 5.5 2.2 35.0 2,050 0.26 0.116 335 310 440 500
185 5.5 2.2 36.5 2,400 0.28 0.111 380 350 500 500
240 5.5 2.2 38.5 2,950 0.31 0.106 435 410 590 500
300 5.5 2.2 41.0 3,550 0.33 0.103 490 460 675 500
400 5.5 2.4 44.5 4,400 0.37 0.099 555 515 775 500
500 5.5 2.4 47.5 5,400 0.42 0.095 625 580 910 500
630 5.5 2.6 52.0 6,850 0.46 0.092 705 660 1050 500
800 5.5 2.8 57.0 8,550 0.52 0.090 775 730 1185 500
1000 5.5 2.8 61.5 10,400 0.58 0.087 845 795 1310 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
Standard
Delivery
Length
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground Air Duct
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
Approx.
Reactance
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
32 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 22 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath Insulation Shield
Conductor Shield
Armour
Insulation
17
35 6.0 1.60 1.40 31.0 900 0.15 0.158 120 105 150 500
50 6.0 1.60 1.56 32.5 1,000 0.16 0.153 140 125 175 500
70 6.0 1.60 1.56 34.0 1,100 0.18 0.141 170 155 215 500
95 6.0 2.00 1.56 36.5 1,350 0.21 0.134 200 185 265 500
120 6.0 2.00 1.56 38.0 1,450 0.22 0.129 230 215 305 500
150 6.0 2.00 1.56 39.5 1,600 0.24 0.125 255 235 345 500
185 6.0 2.00 1.56 41.0 1,750 0.26 0.120 285 265 395 500
240 6.0 2.00 1.72 44.0 2,050 0.29 0.116 325 305 460 500
300 6.0 2.00 1.72 46.0 2,300 0.31 0.112 365 340 530 500
400 6.0 2.00 1.88 49.5 2,700 0.35 0.107 410 380 605 500
500 6.0 2.50 2.04 54.0 3,350 0.39 0.104 450 420 690 500
630 6.0 2.50 2.04 58.0 3,900 0.43 0.101 500 460 800 500
800 6.0 2.50 2.20 62.5 4,600 0.48 0.097 545 500 890 500
1000 6.0 2.50 2.36 67.5 5,400 0.54 0.094 580 540 970 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Standard
Delivery
Length
Ground Air Duct
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
Approx.
Reactance
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
32 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 22 KV (E)
COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Outer Sheath
Conductor Shield
Insulation Shield
Insulation
Conductor
Armour
18
35 6.0 1.60 1.40 31.0 1,100 0.15 0.158 150 135 190 500
50 6.0 1.60 1.56 32.5 1,250 0.16 0.153 175 165 225 500
70 6.0 1.60 1.56 34.0 1,500 0.18 0.141 220 200 280 500
95 6.0 2.00 1.56 36.5 1,900 0.21 0.134 255 235 335 500
120 6.0 2.00 1.56 38.0 2,150 0.22 0.129 290 265 390 500
150 6.0 2.00 1.56 39.5 2,450 0.24 0.125 320 300 435 500
185 6.0 2.00 1.56 41.0 2,850 0.26 0.120 360 330 500 500
240 6.0 2.00 1.72 44.0 3,450 0.29 0.116 405 380 580 500
300 6.0 2.00 1.72 46.0 4,050 0.31 0.112 455 425 660 500
400 6.0 2.00 1.88 49.5 4,950 0.35 0.107 500 470 755 500
500 6.0 2.50 2.04 54.0 6,200 0.39 0.104 545 500 835 500
630 6.0 2.50 2.04 58.0 7,600 0.43 0.101 590 550 940 500
800 6.0 2.50 2.20 62.5 9,400 0.48 0.097 630 590 1020 500
1000 6.0 2.50 2.36 67.5 11,400 0.54 0.094 660 620 1100 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
32 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 22 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Insulation
Conductor
Conductor Shield
Insulation Shield
Outer Sheath
Metallic Insulation Screen
19
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Standard
Delivery
Length
ELECTRICAL PARAMETERS DIMENSIONS
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
Air Duct Ground
35 6.0 2.0 28.5 700 0.15 0.151 120 110 145 500
50 6.0 2.0 29.5 750 0.16 0.145 140 130 170 500
70 6.0 2.0 31.0 900 0.18 0.133 170 160 210 500
95 6.0 2.2 33.5 1,050 0.21 0.127 205 190 255 500
120 6.0 2.2 35.0 1,150 0.22 0.123 235 220 300 500
150 6.0 2.2 36.5 1,300 0.24 0.118 260 240 340 500
185 6.0 2.2 38.0 1,450 0.26 0.114 295 275 390 500
240 6.0 2.2 40.0 1,650 0.29 0.109 335 315 455 500
300 6.0 2.2 42.5 1,900 0.31 0.105 380 360 535 500
400 6.0 2.4 46.0 2,250 0.35 0.101 435 410 615 500
500 6.0 2.6 50.0 2,700 0.39 0.098 495 460 710 500
630 6.0 2.6 53.5 3,200 0.43 0.094 560 530 850 500
800 6.0 2.8 58.5 3,900 0.48 0.092 630 600 985 500
1000 6.0 3.0 63.5 4,650 0.54 0.089 700 660 1110 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
32 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 22 KV (E)
COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor Shield
Insulation Shield
Conductor
Insulation
Metallic Insulation Screen
Outer Sheath
20
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
Standard
Delivery
Length
Air Duct Ground
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
DIMENSIONS
Current Rating
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
ELECTRICAL PARAMETERS
35 6.0 2.0 28.5 900 0.15 0.151 155 140 185 500
50 6.0 2.0 29.5 1,050 0.16 0.145 180 170 220 500
70 6.0 2.0 31.0 1,300 0.18 0.133 220 205 275 500
95 6.0 2.2 33.5 1,600 0.21 0.127 260 245 330 500
120 6.0 2.2 35.0 1,850 0.22 0.123 295 275 385 500
150 6.0 2.2 36.5 2,150 0.24 0.118 330 310 430 500
185 6.0 2.2 38.0 2,500 0.26 0.114 375 350 500 500
240 6.0 2.2 40.0 3,050 0.29 0.109 430 410 580 500
300 6.0 2.2 42.5 3,650 0.31 0.105 485 465 680 500
400 6.0 2.4 46.0 4,500 0.35 0.101 550 515 780 500
500 6.0 2.6 50.0 5,600 0.39 0.098 610 575 900 500
630 6.0 2.6 53.5 6,950 0.43 0.094 700 655 1050 500
800 6.0 2.8 58.5 8,700 0.48 0.092 770 730 1190 500
1000 6.0 3.0 63.5 10,700 0.54 0.089 835 790 1320 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
Standard
Delivery
Length
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground Air Duct
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
Approx.
Reactance
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
48 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 33 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath Insulation Shield
Conductor Shield
Armour
Insulation
21
50 8.8 2.00 1.56 39.0 1,400 0.13 0.164 140 125 175 500
70 8.8 2.00 1.56 40.5 1,550 0.14 0.152 170 155 220 500
95 8.8 2.00 1.72 42.5 1,750 0.16 0.144 200 185 265 500
120 8.8 2.00 1.72 44.0 1,900 0.17 0.139 230 210 305 500
150 8.8 2.00 1.72 45.5 2,050 0.18 0.134 250 230 345 500
185 8.8 2.00 1.72 47.5 2,200 0.20 0.129 285 260 395 500
240 8.8 2.00 1.88 50.0 2,550 0.22 0.124 325 310 465 500
300 8.8 2.50 2.04 53.5 3,000 0.23 0.121 360 335 530 500
400 8.8 2.50 2.04 56.5 3,400 0.26 0.116 405 375 605 500
500 8.8 2.50 2.20 60.0 3,900 0.28 0.111 450 420 690 500
630 8.8 2.50 2.20 64.0 4,500 0.32 0.107 500 460 790 500
800 8.8 2.50 2.36 68.5 5,250 0.35 0.103 545 500 880 500
1000 8.8 3.15 2.52 75.0 6,400 0.39 0.101 575 530 970 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Armouring shall constitute the metallic part of insulation screening.
(3) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
Standard
Delivery
Length
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground Air Duct
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Nominal
Armour
Wire
Diameter
Minimum
Outer
Sheath
Thickness
Approx.
Overall
Cable
Diameter
Approx.
Cable
Wt.
Approx.
Capacitance
Approx.
Reactance
(Mtr./Drum) (Amp) (Amp) (Amp) (Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
48 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 33KV (E)
COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Armour : Round Aluminium Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Outer Sheath
Conductor Shield
Insulation Shield
Insulation
Conductor
Armour
22
50 8.8 2.00 1.56 39.0 1,700 0.13 0.164 180 165 225 500
70 8.8 2.00 1.56 40.5 1,950 0.14 0.152 215 200 280 500
95 8.8 2.00 1.72 42.5 2,300 0.16 0.144 255 235 340 500
120 8.8 2.00 1.72 44.0 2,600 0.17 0.139 290 270 390 500
150 8.8 2.00 1.72 45.5 2,900 0.18 0.134 320 305 435 500
185 8.8 2.00 1.72 47.5 3,300 0.20 0.129 355 335 500 500
240 8.8 2.00 1.88 50.0 3,950 0.22 0.124 405 380 585 500
300 8.8 2.50 2.04 53.5 4,750 0.23 0.121 445 420 650 500
400 8.8 2.50 2.04 56.5 5,650 0.26 0.116 495 460 745 500
500 8.8 2.50 2.20 60.0 6,800 0.28 0.111 540 500 835 500
630 8.8 2.50 2.20 64.0 8,200 0.32 0.107 590 550 935 500
800 8.8 2.50 2.36 68.5 10,000 0.35 0.103 630 580 1025 500
1000 8.8 3.15 2.52 75.0 12,400 0.39 0.101 650 600 1100 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
48 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 33 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Insulation
Conductor
Conductor Shield
Insulation Shield
Outer Sheath
Metallic Insulation Screen
23
(Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm) (Mtr./Drum)
Current Rating
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
Air Duct Ground
Standard
Delivery
Length
DIMENSIONS ELECTRICAL PARAMETERS
50 8.8 2.2 35.5 1,100 0.13 0.156 140 130 170 500
70 8.8 2.2 37.5 1,200 0.14 0.145 170 160 215 500
95 8.8 2.2 39.0 1,350 0.16 0.137 205 190 260 500
120 8.8 2.2 40.5 1,500 0.17 0.132 235 215 300 500
150 8.8 2.2 42.0 1,600 0.18 0.127 260 240 340 500
185 8.8 2.4 44.0 1,850 0.20 0.123 290 275 390 500
240 8.8 2.4 46.5 2,050 0.22 0.118 340 320 465 500
300 8.8 2.6 49.0 2,400 0.23 0.114 380 360 530 500
400 8.8 2.6 52.0 2,750 0.26 0.109 435 420 620 500
500 8.8 2.8 56.0 3,250 0.28 0.106 495 465 715 500
630 8.8 2.8 60.0 3,750 0.32 0.102 565 535 845 500
800 8.8 3.0 64.5 4,500 0.35 0.098 635 600 975 500
1000 8.8 3.2 69.5 5,300 0.39 0.095 710 670 1125 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Standard
Delivery
Length
Air Duct Ground
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Approx.
Reactance
Approx.
Capacitance
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Nominal
Outer
Sheath
Thickness
Nominal
Area of
Conductor
Nominal
Insulation
Thickness
(Mtr./Drum) (Amp) (Amp) (Amp) (F/km) (Kg/km) (mm) (mm) (Sqmm) (mm)
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
48 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
SINGLE CORE 33 KV (E)
COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor Shield
Insulation Shield
Conductor
Insulation
Metallic Insulation Screen
Outer Sheath
24
50 8.8 2.2 35.5 1,350 0.13 0.156 180 170 220 500
70 8.8 2.2 37.5 1,600 0.14 0.145 220 205 275 500
95 8.8 2.2 39.0 1,900 0.16 0.137 265 245 335 500
120 8.8 2.2 40.5 2,200 0.17 0.132 300 280 390 500
150 8.8 2.2 42.0 2,500 0.18 0.127 330 315 435 500
185 8.8 2.4 44.0 2,900 0.20 0.123 375 350 500 500
240 8.8 2.4 46.5 3,500 0.22 0.118 430 410 600 500
300 8.8 2.6 49.0 4,150 0.23 0.114 490 460 675 500
400 8.8 2.6 52.0 5,000 0.26 0.109 550 525 790 500
500 8.8 2.8 56.0 6,100 0.28 0.106 620 575 900 500
630 8.8 2.8 60.0 7,500 0.32 0.102 700 660 1060 500
800 8.8 3.0 64.5 9,300 0.35 0.098 770 730 1190 500
1000 8.8 3.2 69.5 11,300 0.39 0.095 850 800 1350 500
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces #
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
10 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
#Applicable for Screened cables, available
upon request.
Options :
THREE CORE 3.3 KV (E) & (UE)
ALUMINIUM CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Shaped Stranded Aluminium
Insulation : Cross - Linked Polyethylene (XLPE)
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Armour
Insulation
Inner Sheath
Outer Sheath
25
25 2.2 0.3 4X3.4X0.8 1.40 28.5 1,000 0.23 0.103 95 80 100 500
35 2.2 0.3 4X3.4X0.8 1.56 30.5 1,100 0.26 0.099 115 95 125 500
50 2.2 0.4 4X3.4X0.8 1.56 33.0 1,300 0.28 0.096 135 115 150 500
70 2.2 0.4 4X3.4X0.8 1.56 35.5 1,600 0.32 0.089 170 140 185 500
95 2.2 0.4 4X3.4X0.8 1.72 39.0 2,000 0.37 0.086 200 170 230 500
120 2.2 0.5 4X3.4X0.8 1.72 41.5 2,300 0.40 0.083 220 190 260 500
150 2.2 0.5 4X3.4X0.8 1.88 44.5 2,600 0.44 0.082 250 210 300 500
185 2.2 0.5 4X3.4X0.8 2.04 47.5 3,100 0.48 0.079 280 240 340 500
240 2.2 0.6 4X3.4X0.8 2.20 52.0 3,700 0.53 0.077 320 280 400 500
300 2.2 0.6 4X3.4X0.8 2.20 56.0 4,400 0.58 0.076 360 310 460 500
400 2.2 0.7 4X3.4X0.8 2.52 62.5 5,400 0.64 0.074 410 360 535 500
500 2.4 0.7 4X3.4X0.8 2.68 68.5 6,600 0.68 0.074 450 400 615 250
630 2.6 0.7 4X3.4X0.8 3.00 76.0 8,300 0.72 0.073 500 450 700 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
25 2.2 0.3 4X3.4X0.8 1.40 28.5 1,400 0.23 0.103 120 100 125 500
35 2.2 0.3 4X3.4X0.8 1.56 30.5 1,700 0.26 0.099 145 120 155 500
50 2.2 0.4 4X3.4X0.8 1.56 33.0 2,200 0.28 0.096 170 150 190 500
70 2.2 0.4 4X3.4X0.8 1.56 35.5 2,800 0.32 0.089 210 180 235 500
95 2.2 0.4 4X3.4X0.8 1.72 39.0 3,600 0.37 0.086 255 215 290 500
120 2.2 0.5 4X3.4X0.8 1.72 41.5 4,400 0.40 0.083 290 245 330 500
150 2.2 0.5 4X3.4X0.8 1.88 44.5 5,200 0.44 0.082 315 275 380 500
185 2.2 0.5 4X3.4X0.8 2.04 47.5 6,300 0.48 0.079 360 305 435 500
240 2.2 0.6 4X3.4X0.8 2.20 52.0 8,000 0.53 0.077 410 350 510 500
300 2.2 0.6 4X3.4X0.8 2.20 56.0 9,700 0.58 0.076 460 395 590 250
400 2.2 0.7 4X3.4X0.8 2.52 62.5 12,200 0.64 0.074 520 445 675 250
500 2.4 0.7 4X3.4X0.8 2.68 68.5 15,400 0.68 0.074 560 495 740 250
630 2.6 0.7 4X3.4X0.8 3.00 76.0 19,700 0.72 0.073 620 550 825 250
DIMENSIONS
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) z (Sqmm)
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces #
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
10 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
#Applicable for Screened cables, available
upon request.
Options :
Conductor
Armour
Insulation
Inner Sheath
Outer Sheath
THREE CORE 3.3 KV (E) & (UE)
COPPER CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Shaped Stranded Plain Copper
Insulation : Cross - Linked Polyethylene (XLPE)
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
26
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
25 2.2 0.3 1.60 1.56 30.0 1,300 0.23 0.103 95 80 100 500
35 2.2 0.3 1.60 1.56 32.0 1,500 0.26 0.099 115 95 125 500
50 2.2 0.4 2.00 1.56 35.5 1,900 0.28 0.096 135 115 150 500
70 2.2 0.4 2.00 1.56 38.0 2,200 0.32 0.089 170 140 185 500
95 2.2 0.4 2.00 1.72 41.5 2,700 0.37 0.086 200 170 230 500
120 2.2 0.5 2.00 1.88 44.5 3,100 0.40 0.083 220 190 260 500
150 2.2 0.5 2.50 2.04 48.5 3,800 0.44 0.082 250 210 300 500
185 2.2 0.5 2.50 2.04 51.0 4,300 0.48 0.079 280 240 340 500
240 2.2 0.6 2.50 2.20 55.5 5,100 0.53 0.077 320 280 400 500
300 2.2 0.6 2.50 2.36 59.5 5,900 0.58 0.076 360 310 460 500
400 2.2 0.7 3.15 2.68 67.5 7,800 0.64 0.074 410 360 535 500
500 2.4 0.7 3.15 2.84 73.5 9,300 0.68 0.074 450 400 615 250
630 2.6 0.7 4.00 3.00 82.0 12,200 0.72 0.073 500 450 700 250
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces #
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
10 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
#Applicable for Screened cables, available
upon request.
Options :
Conductor
Armour
Insulation
Inner Sheath
Outer Sheath
THREE CORE 3.3 KV (E) & (UE)
ALUMINIUM CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Shaped Stranded Aluminium
Insulation : Cross - Linked Polyethylene (XLPE)
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
27
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces #
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
10 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
#Applicable for Screened cables, available
upon request.
Options :
Armour
Insulation
Conductor
Inner Sheath
Outer Sheath
THREE CORE 3.3 KV (E) & (UE)
COPPER CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Shaped Stranded Plain Copper
Insulation : Cross - Linked Polyethylene (XLPE)
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
28
25 2.2 0.3 1.60 1.56 30.0 1,800 0.23 0.103 120 100 125 500
35 2.2 0.3 1.60 1.56 32.0 2,100 0.26 0.099 145 120 155 500
50 2.2 0.4 2.00 1.56 35.5 2,700 0.28 0.096 170 150 190 500
70 2.2 0.4 2.00 1.56 38.0 3,400 0.32 0.089 210 180 235 500
95 2.2 0.4 2.00 1.72 41.5 4,300 0.37 0.086 255 215 290 500
120 2.2 0.5 2.00 1.88 44.5 5,200 0.40 0.083 290 245 330 500
150 2.2 0.5 2.50 2.04 48.5 6,400 0.44 0.082 315 275 380 500
185 2.2 0.5 2.50 2.04 51.0 7,600 0.48 0.079 360 305 435 500
240 2.2 0.6 2.50 2.20 55.5 9,400 0.53 0.077 410 350 510 500
300 2.2 0.6 2.50 2.36 59.5 11,300 0.58 0.076 460 395 590 250
400 2.2 0.7 3.15 2.68 67.5 14,600 0.64 0.074 520 445 675 250
500 2.4 0.7 3.15 2.84 73.5 18,000 0.68 0.074 560 495 740 250
630 2.6 0.7 4.00 3.00 82.0 23,000 0.72 0.073 620 550 825 200
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
12 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
THREE CORE 6.6 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen: Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Metallic Insulation Screen
Insulation
Conductor
Outer Sheath
Armour
29
25 2.8 0.4 4X3.4X0.8 1.56 40.5 1,900 0.23 0.119 95 85 105 500
35 2.8 0.4 4X3.4X0.8 1.72 43.0 2,100 0.26 0.114 115 100 130 500
50 2.8 0.5 4X3.4X0.8 1.72 45.5 2,400 0.28 0.110 130 115 155 500
70 2.8 0.5 4X3.4X 0.8 1.88 49.5 2,900 0.33 0.101 160 145 190 500
95 2.8 0.5 4X3.4X0.8 1.88 53.5 3,400 0.37 0.097 190 170 230 500
120 2.8 0.6 4X3.4X0.8 2.04 57.0 3,800 0.41 0.093 220 195 260 500
150 2.8 0.6 4X3.4X0.8 2.20 60.5 4,300 0.45 0.092 245 215 295 500
185 2.8 0.6 4X3.4X0.8 2.20 64.0 4,900 0.49 0.088 275 245 340 500
240 2.8 0.7 4X3.4X0.8 2.36 69.5 5,800 0.55 0.085 315 285 395 250
300 3.0 0.7 4X3.4X0.8 2.52 75.5 6,800 0.57 0.084 360 320 450 250
400 3.3 0.7 4X3.4X0.8 2.84 84.0 8,400 0.59 0.082 400 360 525 250
500 3.5 0.7 4X3.4X0.8 3.00 92.5 10,100 0.62 0.081 450 405 595 250
630 3.5 0.7 4X3.4X0.8 3.00 102.0 12,000 0.70 0.079 500 450 700 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Armour
Outer Sheath
Conductor Shield
Insulation Shield
Inner Sheath
Metallic Insulation Screen
Insulation
Conductor
Fillers
THREE CORE 6.6 KV (E)
COPPER CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
12 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
DIMENSIONS
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
30
25 2.8 0.4 4X3.4X0.8 1.56 40.5 2,300 0.23 0.119 120 105 135 500
35 2.8 0.4 4X3.4X0.8 1.72 43.0 2,800 0.26 0.114 145 125 165 500
50 2.8 0.5 4X3.4X0.8 1.72 45.5 3,200 0.28 0.110 170 150 195 500
70 2.8 0.5 4X3.4X0.8 1.88 49.5 4,100 0.33 0.101 210 180 240 500
95 2.8 0.5 4X3.4X0.8 1.88 53.5 5,000 0.37 0.097 250 215 295 500
120 2.8 0.6 4X3.4X0.8 2.04 57.0 5,800 0.41 0.093 280 245 335 500
150 2.8 0.6 4X3.4X0.8 2.20 60.5 6,900 0.45 0.092 310 275 380 500
185 2.8 0.6 4X3.4X0.8 2.20 64.0 8,100 0.49 0.088 350 305 435 500
240 2.8 0.7 4X3.4X0.8 2.36 69.5 10,100 0.55 0.085 400 350 500 250
300 3.0 0.7 4X3.4X0.8 2.52 75.5 12,200 0.57 0.084 445 395 570 250
400 3.3 0.7 4X3.4X0.8 2.84 84.0 15,200 0.59 0.082 490 440 650 250
500 3.5 0.7 4X3.4X0.8 3.00 92.5 18,900 0.62 0.081 530 485 720 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
12 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
Conductor
Outer Sheath
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
THREE CORE 6.6 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen: Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
31
25 2.8 0.4 2.00 1.72 43.5 2,700 0.23 0.119 95 85 105 500
35 2.8 0.4 2.00 1.72 45.5 2,900 0.26 0.114 115 100 130 500
50 2.8 0.5 2.00 1.88 48.0 3,300 0.28 0.110 130 115 155 500
70 2.8 0.5 2.00 1.88 52.0 3,800 0.33 0.101 160 145 190 500
95 2.8 0.5 2.50 2.04 57.0 4,800 0.37 0.097 190 170 230 500
120 2.8 0.6 2.50 2.20 61.0 5,400 0.41 0.093 220 195 260 500
150 2.8 0.6 2.50 2.20 64.0 5,900 0.45 0.092 245 215 295 500
185 2.8 0.6 2.50 2.36 68.0 6,600 0.49 0.088 275 245 340 500
240 2.8 0.7 3.15 2.52 74.5 8,500 0.55 0.085 315 285 395 250
300 3.0 0.7 3.15 2.68 80.5 9,700 0.57 0.084 360 320 450 250
400 3.3 0.7 4.00 3.00 91.0 12,800 0.59 0.082 400 360 525 250
500 3.5 0.7 4.00 3.00 99.0 15,000 0.62 0.081 450 405 595 250
630 3.5 0.7 4.00 3.00 107.0 17,200 0.70 0.079 500 450 700 250
DIMENSIONS
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) z (Sqmm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
25 2.8 0.4 2.00 1.72 43.5 3,100 0.23 0.119 120 105 135 500
35 2.8 0.4 2.00 1.72 45.5 3,500 0.26 0.114 145 125 165 500
50 2.8 0.5 2.00 1.88 48.0 4,100 0.28 0.110 170 150 195 500
70 2.8 0.5 2.00 1.88 52.0 5,000 0.33 0.101 210 180 240 500
95 2.8 0.5 2.50 2.04 57.0 6,500 0.37 0.097 250 215 295 500
120 2.8 0.6 2.50 2.20 61.0 7,500 0.41 0.093 280 245 335 500
150 2.8 0.6 2.50 2.20 64.0 8,500 0.45 0.092 310 275 380 500
185 2.8 0.6 2.50 2.36 68.0 9,900 0.49 0.088 350 305 435 500
240 2.8 0.7 3.15 2.52 74.5 12,800 0.55 0.085 400 350 500 250
300 3.0 0.7 3.15 2.68 80.5 15,100 0.57 0.084 445 395 570 250
400 3.3 0.7 4.00 3.00 91.0 19,700 0.59 0.082 490 440 650 250
500 3.5 0.7 4.00 3.00 99.0 23,800 0.62 0.081 530 485 720 200
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
12 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
DIMENSIONS ELECTRICAL PARAMETERS
Ground
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) z (Sqmm)
Conductor
Outer Sheath Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
THREE CORE 6.6 KV (E)
COPPER CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen: Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
32
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
17 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
25 3.6 0.4 4X3.4X0.8 1.72 44.5 2,200 0.19 0.126 95 85 105 500
35 3.6 0.5 4X3.4X0.8 1.72 46.5 2,400 0.21 0.120 115 100 130 500
50 3.6 0.5 4X3.4X0.8 1.88 49.5 2,700 0.23 0.116 130 115 155 500
70 3.6 0.5 4X3.4X0.8 1.88 53.0 3,200 0.27 0.107 160 145 190 500
95 3.6 0.6 4X3.4X0.8 2.04 57.5 3,700 0.31 0.102 190 170 230 500
120 3.6 0.6 4X3.4X0.8 2.20 61.0 4,200 0.33 0.098 220 195 260 500
150 3.6 0.6 4X3.4X0.8 2.20 64.0 4,700 0.36 0.096 245 215 295 500
185 3.6 0.7 4X3.4X 0.8 2.36 68.0 5,300 0.40 0.092 275 245 335 500
240 3.6 0.7 4X3.4X0.8 2.52 73.5 6,200 0.44 0.089 315 285 400 250
300 3.6 0.7 4X3.4X0.8 2.68 78.5 7,200 0.48 0.087 360 320 455 250
400 3.6 0.7 4X3.4X0.8 2.84 85.5 8,500 0.54 0.083 400 360 525 250
500 3.6 0.7 4X3.4X0.8 3.00 93.0 10,100 0.61 0.081 450 405 595 250
630 3.6 0.7 4X3.4X0.8 3.00 101.0 12,000 0.68 0.079 500 450 700 250
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Ground
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
THREE CORE 11 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Metallic Insulation Screen
Insulation
Conductor
Outer Sheath
Armour
33
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
17 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
DIMENSIONS
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
THREE CORE 11 KV (E)
COPPER CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Armour
Outer Sheath
Conductor Shield
Insulation Shield
Inner Sheath
Metallic Insulation Screen
Insulation
Conductor
Fillers
34
25 3.6 0.4 4X3.4X0.8 1.72 44.5 2,600 0.19 0.126 120 105 135 500
35 3.6 0.5 4X3.4X0.8 1.72 46.5 3,000 0.21 0.120 145 125 165 500
50 3.6 0.5 4X3.4X0.8 1.88 49.5 3,600 0.23 0.116 170 150 200 500
70 3.6 0.5 4X3.4X0.8 1.88 53.0 4,400 0.27 0.107 210 180 245 500
95 3.6 0.6 4X3.4X0.8 2.04 57.5 5,400 0.31 0.102 255 215 295 500
120 3.6 0.6 4X3.4X0.8 2.20 61.0 6,300 0.33 0.098 280 245 340 500
150 3.6 0.6 4X3.4X0.8 2.20 64.0 7,300 0.36 0.096 310 275 380 500
185 3.6 0.7 4X3.4X0.8 2.36 68.0 8,600 0.40 0.092 355 305 430 500
240 3.6 0.7 4X3.4X0.8 2.52 73.5 10,500 0.44 0.089 400 355 505 250
300 3.6 0.7 4X3.4X0.8 2.68 78.5 12,600 0.48 0.087 445 400 570 250
400 3.6 0.7 4X3.4X0.8 2.84 85.5 15,400 0.54 0.083 490 440 655 250
500 3.6 0.7 4X3.4X0.8 3.00 93.0 18,900 0.61 0.081 530 490 720 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
DIMENSIONS
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
17 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
THREE CORE 11 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
35
25 3.6 0.4 2.00 1.72 46.5 3,000 0.19 0.126 95 85 105 500
35 3.6 0.5 2.00 1.88 49.5 3,400 0.21 0.120 115 100 130 500
50 3.6 0.5 2.50 2.04 53.0 4,100 0.23 0.116 130 115 155 500
70 3.6 0.5 2.50 2.04 56.5 4,700 0.27 0.107 160 145 190 500
95 3.6 0.6 2.50 2.20 61.0 5,300 0.31 0.102 190 170 230 500
120 3.6 0.6 2.50 2.20 64.5 5,800 0.33 0.098 220 195 260 500
150 3.6 0.6 2.50 2.36 68.0 6,500 0.36 0.096 245 215 295 500
185 3.6 0.7 3.15 2.52 73.0 8,000 0.40 0.092 275 245 335 500
240 3.6 0.7 3.15 2.68 78.5 9,200 0.44 0.089 315 285 400 250
300 3.6 0.7 3.15 2.84 83.5 10,200 0.48 0.087 360 320 455 250
400 3.6 0.7 4.00 3.00 92.0 13,000 0.54 0.083 400 360 525 250
500 3.6 0.7 4.00 3.00 99.5 15,000 0.61 0.081 450 405 595 250
630 3.6 0.7 4.00 3.00 108.0 17,000 0.68 0.079 500 450 700 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
17 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
THREE CORE 11 KV (E)
COPPER CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
36
25 3.6 0.4 2.00 1.72 46.5 3,500 0.19 0.126 120 105 135 500
35 3.6 0.5 2.00 1.88 49.5 4,000 0.21 0.120 145 125 165 500
50 3.6 0.5 2.50 2.04 53.0 5,000 0.23 0.116 170 150 200 500
70 3.6 0.5 2.50 2.04 56.5 5,900 0.27 0.107 210 180 245 500
95 3.6 0.6 2.50 2.20 61.0 7,000 0.31 0.102 255 215 295 500
120 3.6 0.6 2.50 2.20 64.5 7,900 0.33 0.098 280 245 340 500
150 3.6 0.6 2.50 2.36 68.0 9,000 0.36 0.096 310 275 380 500
185 3.6 0.7 3.15 2.52 73.0 11,200 0.40 0.092 355 305 430 500
240 3.6 0.7 3.15 2.68 78.5 13,400 0.44 0.089 400 355 505 250
300 3.6 0.7 3.15 2.84 83.5 15,600 0.48 0.087 445 400 570 250
400 3.6 0.7 4.00 3.00 92.0 20,000 0.54 0.083 490 440 655 250
500 3.6 0.7 4.00 3.00 99.5 23,800 0.61 0.081 530 490 720 200
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
28 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
25 5.5 0.5 4X3.4X0.8 1.88 53.5 3,000 0.15 0.140 95 85 110 500
35 5.5 0.5 4X3.4X0.8 2.04 56.0 3,200 0.16 0.134 120 100 135 500
50 5.5 0.6 4X3.4X0.8 2.20 58.5 3,600 0.17 0.128 130 115 160 500
70 5.5 0.6 4X3.4X0.8 2.20 62.0 4,100 0.20 0.118 160 145 195 500
95 5.5 0.6 4X3.4X0.8 2.36 66.5 4,700 0.22 0.112 195 170 235 500
120 5.5 0.7 4X3.4X0.8 2.36 70.0 5,200 0.24 0.108 220 195 260 500
150 5.5 0.7 4X3.4X0.8 2.52 73.5 5,800 0.26 0.106 245 220 300 500
185 5.5 0.7 4X3.4X0.8 2.68 77.5 6,500 0.28 0.101 275 245 340 500
240 5.5 0.7 4X3.4X0.8 2.84 82.5 7,500 0.31 0.097 315 290 400 250
300 5.5 0.7 4X3.4X0.8 3.00 87.5 8,500 0.34 0.094 355 315 455 250
400 5.5 0.7 4X3.4X0.8 3.00 94.0 9,800 0.38 0.090 400 360 520 250
500 5.5 0.7 4X3.4X0.8 3.00 102.0 11,500 0.42 0.088 450 410 610 250
630 5.5 0.7 4X3.4X0.8 3.00 110.0 13,500 0.47 0.085 495 450 680 250
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
THREE CORE 11 KV (UE)
ALUMINIUM CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Metallic Insulation Screen
Insulation
Conductor
Outer Sheath
Armour
37
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Capacitance
Approx.
Reactance
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
25 5.5 0.5 4X3.4X0.8 1.88 53.5 3,400 0.15 0.140 120 110 140 500
35 5.5 0.5 4X3.4X0.8 2.04 56.0 3,900 0.16 0.134 145 130 165 500
50 5.5 0.6 4X3.4X0.8 2.20 58.5 4,400 0.17 0.128 170 150 200 500
70 5.5 0.6 4X3.4X0.8 2.20 62.0 5,300 0.20 0.118 210 185 245 500
95 5.5 0.6 4X3.4X0.8 2.36 66.5 6,400 0.22 0.112 250 220 300 500
120 5.5 0.7 4X3.4X0.8 2.36 70.0 7,300 0.24 0.108 280 250 340 500
150 5.5 0.7 4X3.4X0.8 2.52 73.5 8,400 0.26 0.106 310 280 385 500
185 5.5 0.7 4X3.4X0.8 2.68 77.5 9,700 0.28 0.101 350 310 435 500
240 5.5 0.7 4X3.4X0.8 2.84 82.5 11,800 0.31 0.097 400 360 510 250
300 5.5 0.7 4X3.4X0.8 3.00 87.5 13,800 0.34 0.094 445 400 570 250
400 5.5 0.7 4X3.4X0.8 3.00 94.0 16,600 0.38 0.090 490 445 645 250
500 5.5 0.7 4X3.4X0.8 3.00 102.0 20,200 0.42 0.088 530 490 730 250
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
28 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
THREE CORE 11 KV (UE)
COPPER CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen: Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Armour
Outer Sheath
Conductor Shield
Insulation Shield
Inner Sheath
Metallic Insulation Screen
Insulation
Conductor
Fillers
38
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
25 5.5 0.5 2.50 2.04 57.0 4,500 0.15 0.140 95 85 110 500
35 5.5 0.5 2.50 2.20 59.5 4,800 0.16 0.134 120 100 135 500
50 5.5 0.6 2.50 2.20 62.0 5,200 0.17 0.128 130 115 160 500
70 5.5 0.6 2.50 2.36 66.0 5,800 0.20 0.118 160 145 195 500
95 5.5 0.6 3.15 2.52 71.5 7,300 0.22 0.112 195 170 235 500
120 5.5 0.7 3.15 2.52 75.0 8,000 0.24 0.108 220 195 260 500
150 5.5 0.7 3.15 2.68 78.5 8,700 0.26 0.106 245 220 300 500
185 5.5 0.7 3.15 2.84 82.5 9,500 0.28 0.101 275 245 340 500
240 5.5 0.7 3.15 3.00 87.5 10,700 0.31 0.097 315 290 400 250
300 5.5 0.7 4.00 3.00 94.0 13,000 0.34 0.094 355 315 455 250
400 5.5 0.7 4.00 3.00 101.0 14,800 0.38 0.090 400 360 520 250
500 5.5 0.7 4.00 3.00 108.0 16,800 0.42 0.088 450 410 610 250
630 5.5 0.7 4.00 3.00 116.0 19,200 0.47 0.085 495 450 680 250
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
DIMENSIONS ELECTRICAL PARAMETERS
Standard
Delivery
Length
Current Rating
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Ground Duct Air
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
28 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
THREE CORE 11 KV (UE)
ALUMINIUM CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen: Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
39
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
28 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
THREE CORE 11 KV (UE)
COPPER CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
40
25 5.5 0.5 2.50 2.04 57.0 4,900 0.15 0.140 120 110 140 500
35 5.5 0.5 2.50 2.20 59.5 5,400 0.16 0.134 145 130 165 500
50 5.5 0.6 2.50 2.20 62.0 6,100 0.17 0.128 170 150 200 500
70 5.5 0.6 2.50 2.36 66.0 7,000 0.20 0.118 210 185 245 500
95 5.5 0.6 3.15 2.52 71.5 8,900 0.22 0.112 250 220 300 500
120 5.5 0.7 3.15 2.52 75.0 10,100 0.24 0.108 280 250 340 500
150 5.5 0.7 3.15 2.68 78.5 11,300 0.26 0.106 310 280 385 500
185 5.5 0.7 3.15 2.84 82.5 12,800 0.28 0.101 350 310 435 500
240 5.5 0.7 3.15 3.00 87.5 15,000 0.31 0.097 400 360 510 250
300 5.5 0.7 4.00 3.00 94.0 18,500 0.34 0.094 445 400 570 250
400 5.5 0.7 4.00 3.00 101.0 21,600 0.38 0.090 490 445 645 250
500 5.5 0.7 4.00 3.00 108.0 25,500 0.42 0.088 530 490 730 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
32 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
THREE CORE 22 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Metallic Insulation Screen
Insulation
Conductor
Outer Sheath
Armour
41
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
35 6.0 0.6 4X3.4X0.8 2.04 59.5 3,600 0.15 0.137 110 100 135 500
50 6.0 0.6 4X3.4X0.8 2.20 61.5 3,900 0.17 0.132 130 115 155 500
70 6.0 0.6 4X3.4X0.8 2.36 65.5 4,500 0.19 0.121 160 140 195 500
95 6.0 0.7 4X3.4X0.8 2.36 70.0 5,100 0.21 0.115 190 170 230 500
120 6.0 0.7 4X3.4X0.8 2.52 73.5 5,700 0.23 0.111 215 190 265 500
150 6.0 0.7 4X3.4X0.8 2.68 77.0 6,300 0.24 0.108 240 215 300 500
185 6.0 0.7 4X3.4X0.8 2.68 80.5 6,900 0.26 0.103 270 245 345 250
240 6.0 0.7 4X3.4X0.8 2.84 86.0 8,000 0.29 0.099 310 280 400 250
300 6.0 0.7 4X3.4X0.8 3.00 91.0 9,000 0.32 0.096 350 315 455 250
400 6.0 0.7 4X3.4X0.8 3.00 97.5 10,300 0.35 0.092 395 360 520 250
500 6.0 0.7 4X3.4X0.8 3.00 105.0 12,000 0.39 0.090 440 400 590 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
32 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
THREE CORE 22 KV (E)
COPPER CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Armour
Outer Sheath
Conductor Shield
Insulation Shield
Inner Sheath
Metallic Insulation Screen
Insulation
Conductor
Fillers
42
DIMENSIONS
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
35 6.0 0.6 4X3.4X0.8 2.04 59.5 4,200 0.15 0.137 145 130 170 500
50 6.0 0.6 4X3.4X0.8 2.20 61.5 4,800 0.17 0.132 170 150 200 500
70 6.0 0.6 4X3.4X0.8 2.36 65.5 5,700 0.19 0.121 205 185 250 500
95 6.0 0.7 4X3.4X0.8 2.36 70.0 6,800 0.21 0.115 245 220 300 500
120 6.0 0.7 4X3.4X0.8 2.52 73.5 7,800 0.23 0.111 275 250 340 500
150 6.0 0.7 4X3.4X0.8 2.68 77.0 8,900 0.24 0.108 305 280 385 500
185 6.0 0.7 4X3.4X0.8 2.68 80.5 10,200 0.26 0.103 345 310 440 250
240 6.0 0.7 4X3.4X0.8 2.84 86.0 12,200 0.29 0.099 390 355 510 250
300 6.0 0.7 4X3.4X0.8 3.00 91.0 14,300 0.32 0.096 440 395 580 250
400 6.0 0.7 4X3.4X0.8 3.00 97.5 17,200 0.35 0.092 485 440 650 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
32 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
THREE CORE 22 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
43
DIMENSIONS ELECTRICAL PARAMETERS
Ground
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) z (Sqmm)
35 6.0 0.6 2.50 2.20 63.0 5,300 0.15 0.137 110 100 135 500
50 6.0 0.6 2.50 2.36 65.5 5,700 0.17 0.132 130 115 155 500
70 6.0 0.6 2.50 2.36 69.0 6,300 0.19 0.121 160 140 195 500
95 6.0 0.7 3.15 2.52 75.0 7,900 0.21 0.115 190 170 230 500
120 6.0 0.7 3.15 2.68 78.5 8,600 0.23 0.111 215 190 265 500
150 6.0 0.7 3.15 2.68 82.0 9,200 0.24 0.108 240 215 300 500
185 6.0 0.7 3.15 2.84 85.5 10,100 0.26 0.103 270 245 345 250
240 6.0 0.7 4.00 3.00 92.5 12,500 0.29 0.099 310 280 400 250
300 6.0 0.7 4.00 3.00 97.0 13,700 0.32 0.096 350 315 455 250
400 6.0 0.7 4.00 3.00 104.0 15,400 0.35 0.092 395 360 520 250
500 6.0 0.7 4.00 3.00 111.0 17,500 0.39 0.090 440 400 590 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
32 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
THREE CORE 22 KV (E)
COPPER CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen: Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
44
DIMENSIONS ELECTRICAL PARAMETERS
Ground
Current Rating
Duct Air
Standard
Delivery
Length
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
35 6.0 0.6 2.50 2.20 63.0 5,900 0.15 0.137 145 130 170 500
50 6.0 0.6 2.50 2.36 65.5 6,500 0.17 0.132 170 150 200 500
70 6.0 0.6 2.50 2.36 69.0 7,500 0.19 0.121 205 185 250 500
95 6.0 0.7 3.15 2.52 75.0 9,500 0.21 0.115 245 220 300 500
120 6.0 0.7 3.15 2.68 78.5 10,700 0.23 0.111 275 250 340 500
150 6.0 0.7 3.15 2.68 82.0 11,800 0.24 0.108 305 280 385 500
185 6.0 0.7 3.15 2.84 85.5 13,400 0.26 0.103 345 310 440 250
240 6.0 0.7 4.00 3.00 92.5 16,800 0.29 0.099 390 355 510 250
300 6.0 0.7 4.00 3.00 97.0 19,000 0.32 0.096 440 395 580 250
400 6.0 0.7 4.00 3.00 104.0 22,000 0.35 0.092 485 440 650 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
48 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
THREE CORE 33 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Metallic Insulation Screen
Insulation
Conductor
Outer Sheath
Armour
45
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
50 8.8 0.7 4X3.4X0.8 2.52 75.0 5,500 0.13 0.146 130 115 160 500
70 8.8 0.7 4X3.4X0.8 2.68 79.0 6,200 0.14 0.135 160 140 200 500
95 8.8 0.7 4X3.4X0.8 2.84 83.5 6,900 0.16 0.128 190 170 235 500
120 8.8 0.7 4X3.4X0.8 2.84 87.0 7,500 0.17 0.123 215 195 270 250
150 8.8 0.7 4X3.4X0.8 3.00 90.0 8,100 0.18 0.120 240 215 300 250
185 8.8 0.7 4X3.4X0.8 3.00 93.5 8,800 0.20 0.114 270 245 350 250
240 8.8 0.7 4X3.4X0.8 3.00 98.5 9,900 0.22 0.109 310 285 410 250
300 8.8 0.7 4X3.4X0.8 3.00 104.0 11,000 0.24 0.106 350 315 455 250
400 8.8 0.7 4X3.4X0.8 3.00 110.0 12,400 0.26 0.101 395 360 530 250
500 8.8 0.7 4X3.4X0.8 3.00 117.0 14,200 0.29 0.098 440 405 600 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
48 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
THREE CORE 33 KV (E)
COPPER CONDUCTOR XLPE INSULATED
STRIP ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Flat Galvanized Steel Strips
Outer Sheath : Black PVC (Type - ST2)
Construction :
Armour
Outer Sheath
Conductor Shield
Insulation Shield
Inner Sheath
Metallic Insulation Screen
Insulation
Conductor
Fillers
46
Nominal
Dimensions of
Flat Strips
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
DIMENSIONS
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
50 8.8 0.7 4X3.4X0.8 2.52 75.0 6,400 0.13 0.146 170 150 205 500
70 8.8 0.7 4X3.4X0.8 2.68 79.0 7,400 0.14 0.135 205 190 250 500
95 8.8 0.7 4X3.4X0.8 2.84 83.5 8,600 0.16 0.128 245 225 300 500
120 8.8 0.7 4X3.4X0.8 2.84 87.0 9,600 0.17 0.123 275 250 345 250
150 8.8 0.7 4X3.4X0.8 3.00 90.0 10,700 0.18 0.120 305 280 385 250
185 8.8 0.7 4X3.4X0.8 3.00 93.5 12,100 0.20 0.114 345 315 440 250
240 8.8 0.7 4X3.4X0.8 3.00 98.5 14,200 0.22 0.109 395 355 510 250
300 8.8 0.7 4X3.4X0.8 3.00 104.0 16,300 0.24 0.106 435 400 575 250
400 8.8 0.7 4X3.4X0.8 3.00 110.0 19,200 0.26 0.101 490 445 650 250
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
48 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
THREE CORE 33 KV (E)
ALUMINIUM CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Aluminium
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen : Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath
Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
47
50 8.8 0.7 3.15 2.68 80.50 8,500 0.13 0.146 130 115 160 500
70 8.8 0.7 3.15 2.84 84.50 9,300 0.14 0.135 160 140 200 500
95 8.8 0.7 3.15 3.00 88.50 10,100 0.16 0.128 190 170 235 500
120 8.8 0.7 4.00 3.00 93.50 12,000 0.17 0.123 215 195 270 250
150 8.8 0.7 4.00 3.00 96.50 12,800 0.18 0.120 240 215 300 250
185 8.8 0.7 4.00 3.00 100.0 13,800 0.20 0.114 270 245 350 250
240 8.8 0.7 4.00 3.00 105.0 15,000 0.22 0.109 310 285 410 250
300 8.8 0.7 4.00 3.00 110.0 16,400 0.24 0.106 350 315 455 250
400 8.8 0.7 4.00 3.00 117.0 18,000 0.26 0.101 395 360 530 250
500 8.8 0.7 4.00 3.00 124.0 20,000 0.29 0.098 440 405 600 250
DIMENSIONS ELECTRICAL PARAMETERS
Standard
Delivery
Length
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Ground
Current Rating
Duct Air
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1.
(2) Standard delivery Length specified above are for guidance only.
Cables can be however supplied in longer lengths as per specific requirement of the Customer.
(3) Dimensions and weights are subject to industry tolerances.
Normal Operation..................................................90C
Emergency* Operation.........................................130C
Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall
not exceed 100 hours in 12 consecutive months &not more
than 500 hours during the lifetime of the cable.
Triple-extruded for clean interfaces
Dry nitrogen cure for enhanced performance
Excellent moisture resistance
High dielectric strength
Low dielectric loss
Excellent resistance to treeing
Features & Benefits :
IS : 7098 Part -2
Reference Standard :
48 KV (AC) for 5 minutes.
H.V. Test Voltage :
Preferably used for Power distribution network.
Suitable for exposed in Air, direct burial, open
tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type
Cables are available upon request.
Options :
THREE CORE 33 KV (E)
COPPER CONDUCTOR XLPE INSULATED
WIRE ARMOURED CABLES
Conductor : Round Compact Stranded Plain Copper
Conductor Shield : Semi-conducting Compound
Insulation : Cross - Linked Polyethylene (XLPE)
Insulation Shield : Semi-conducting Compound
Metallic Insulation Screen: Copper Tape
Filler : Thermoplastic Material
Inner Sheath : Thermoplastic Material
Armour : Round Galvanized Steel Wires
Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath Inner Sheath
Fillers
Insulation Shield
Conductor Shield
Armour
Metallic Insulation Screen
Insulation
48
DIMENSIONS
Nominal
Diameter of
Armour
Wires
Min.Inner
Sheath
Thickness
Nominal
Insulation
Thickness
Approx.
Cable
Wt.
Approx.
Overall
Cable
Diameter
Approx.
Capacitance
Ground
ELECTRICAL PARAMETERS
Current Rating
Duct Air
Standard
Delivery
Length
Approx.
Reactance
Min.
Outer
Sheath
Thickness
Nominal
Area of
Conductor
(mm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) (Mtr./Drum) (Amp) (Amp) (Amp) Y (Sqmm)
50 8.8 0.7 3.15 2.68 80.50 9,300 0.13 0.146 170 150 205 500
70 8.8 0.7 3.15 2.84 84.50 10,500 0.14 0.135 205 190 250 500
95 8.8 0.7 3.15 3.00 88.50 11,800 0.16 0.128 245 225 300 500
120 8.8 0.7 4.00 3.00 93.50 14,200 0.17 0.123 275 250 345 250
150 8.8 0.7 4.00 3.00 96.50 15,400 0.18 0.120 305 280 385 250
185 8.8 0.7 4.00 3.00 100.0 17,000 0.20 0.114 345 315 440 250
240 8.8 0.7 4.00 3.00 105.0 19,000 0.22 0.109 395 355 510 250
300 8.8 0.7 4.00 3.00 110.0 21,800 0.24 0.106 435 400 575 250
400 8.8 0.7 4.00 3.00 117.0 25,000 0.26 0.101 495 450 660 200
High Voltage Power Cable
Connectingthe World
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
TECHNICAL INFORMATION
S.NO. INFORMATION
PAGE
NO.
49
1 Short Circuit Rating & A. C. Resistance 50
2 Graph For Short Circuit Rating 51
3 Standard Laying Conditions & Rating Factors 52
4 Rating Factors For Variation in Thermal Resistivity of Soil 53
5 Group Rating Factors 54
6 Properties of Fire Performance in Cables 55
7 Details of Fire Test 56-57
8 Reference International Standards 58-62
9 Checklist for Specifications 63
10 Metric Conversion Factors 64
11 Recommended Reel Handling Practices 65
12 Recommended Cable Handling Practices 66
13 Recommended Cable Storage Practices 67
14 Pre-Installation Instructions 68
15 Installation Overview and Checklist 69
16 Installation Feed-In Setups 70-71
17 DC Hi-Pot Testing Guidelines 72
18 Field Electrical Hi-Pot Testing Guidelines 73
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Nomical Area of
Conductor
(Sqmm)
Recommended Short Circuit Rating of
Conductor for a duration of one Second
Aluminium Conductor Copper Conductor
(kA) (kA)
Approx A. C. Resistance at 90C
Conductor Temperature
Aluminium Conductor Copper Conductor
X H
SHORT CIRCUIT RATING
& A. C. RESISTANCE
The permissible short circuit current in a cable is determined by the maximum permissible conductor temperature
during normal operation & during short circuit operation and by the duration of short circuit. The maximum
permissible conductor temperature is 250C during short circuit condition and 90C during normal operation (ie,
initial conductor temperature).
Short Circuit Rating :
A. C. Resistance :
The Approx A. C. Resistance in a cable is determined by the maximum permissible conductor temperature during
normal operation i.e. - 90C & maximum D. C. Resistance of conductor at 20C as per IS:8130 for each size of
conductor. The calculation is done by the method specified in IEC:60287. However, the values of A. C. Resistance
for each of cable have been specified below.
K =Constant (0.094 for Aluminium Conductor
& 0.143 for Copper Conductor)
A =Area of Conductor in sqmm.
t =Duration of short circuit in second.
The short circuit current rating of conductor,
I =
Sh
KA
t
Where,
The values of the short circuit current ratings of conductors have been specified below for each size of conductors.
The graph for short circuit current rating have been drawn in next page.
50
25 2.35 3.58 1.536 0.931
35 3.29 5.01 1.111 0.671
50 4.70 7.15 0.821 0.496
70 6.58 10.01 0.567 0.344
95 8.93 13.59 0.410 0.248
120 11.28 17.16 0.324 0.197
150 14.10 21.45 0.265 0.160
185 17.39 26.46 0.211 0.129
240 22.56 34.32 0.162 0.099
300 28.20 42.90 0.130 0.080
400 37.60 57.20 0.102 0.064
500 47.00 71.50 0.081 0.052
630 59.22 90.09 0.064 0.043
800 75.20 114.40 0.052 0.036
1000 94.00 143.00 0.044 0.032
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
GRAPH FOR SHORT CIRCUIT RATING
51
GRAPHICAL REPRESENTATION OF SHORT CIRCUIT CURRENT RATINGS
OF XLPE INSULATED ALUMINIUM CONDUCTOR
- 1000
- 800.0
- 630.0
- 500.0
- 400.0
- 300.0
- 240.0
- 185.0
- 150.0
- 120.0
- 95.0
- 70.0
- 50.0
- 35.0
- 25.0
500.00
200.00
100.00
50.00
20.00
10.00
5.00
2.00
1.00
0.50
0.20
0.10
0.05
0.02
300.00
0.1 0.2 0.5 1.0 2.0 5.0 10.0
S
h
o
r
t

c
i
r
c
u
i
t

c
u
r
r
e
n
t

r
a
t
i
n
g

i
n

K
i
l
o
-
a
m
p
e
r
e
s
.
Duration of short circuit in seconds
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
STANDARD LAYING CONDITIONS
TABLE-1
Ground temperature = 30C
Ambient air temperature = 40C
Maximum conductor temperature for continuous operation = 90C
Maximum conductor temperature during overload = 130c
Maximum conductor temperature during short circuit = 250C.
Thermal Resistivity of soil = 150C-cm/watt
Thermal Resistivity of insulation = 350C-cm/watt
Dielectric Constant = 2.5
Depth of laying for cables laid in ground = 900mm for cables upto 11 KV
= 1050mm for cables above 11 KV
Method of Installation =For Three Core cables = Singly
=For Single Core cables = 3 Cables in Trefoil Touching Formation
Bonding of Screen OR Armour of Single Core Cables = Both End Bonded & Earthed
[
[
RATING FACTORS FOR VARIATION IN GROUND TEMPERATURE WHEN CABLE LAID DIRECT IN GROUND
Ground Temperature (C)
Rating Factors
15 20 25 30 35 40 45 50
1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82
RATING FACTORS FOR VARIATION IN GROUND TEMPERATURE WHEN CABLE LAID IN GROUND
Ground Temperature (C)
Rating Factors
15 20 25 30 35 40 45 50
1.12 1.08 1.04 1.00 0.96 0.91 0.87 0.82
RATING FACTORS FOR VARIATION IN DEPTH OF LAYING WHEN CABLE LAID
DIRECT IN GROUND IN DUCTS
3.3, 6.6 & 22 & 33 KV
11 KV Cables Cables
900 1.00
1050 0.99 1.00
1200 0.98 0.99
1500 0.96 0.97
1800 0.95 0.96
2000 0.93 0.95
2500 0.91 0.92
3000 or more 0.90 0.91
Depth of laying 3.3, 6.6 & 22 & 33 KV
mm 11 KV Cables Cables
900 1.00
1050 0.99 1.00
1200 0.98 0.99
1500 0.96 0.98
1800 0.95 0.96
2000 0.94 0.95
2500 0.93 0.94
3000 or more 0.92 0.93
RATING FACTORS FOR VARIATION IN AMBIENT AIR TEMPERATURE WHEN CABLE LAID IN AIR
Air Temperature (C)
Rating Factors
25 30 35 40 45 50 55 60
1.14 1.10 1.05 1.00 0.95 0.89 0.84 0.77
STANDARD LAYING CONDITIONS
& RATING FACTORS
RATING FACTORS
TABLE-2
52
Depth of laying
mm mm
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
3-Nos. SINGLE CORE CABLES IN TREFOIL MADE ONE CIRCUIT WHEN LAID
25 1.16 1.09 1.00 0.89 0.81 0.75 1.12 1.05 1.00 0.91 0.85 0.79
35 1.16 1.10 1.00 0.89 0.81 0.75 1.12 1.06 1.00 0.91 0.84 0.79
50 1.16 1.10 1.00 0.89 0.81 0.74 1.12 1.06 1.00 0.91 0.84 0.78
70 1.17 1.10 1.00 0.89 0.81 0.74 1.12 1.06 1.00 0.91 0.84 0.78
95 1.18 1.10 1.00 0.89 0.80 0.74 1.13 1.07 1.00 0.91 0.84 0.78
120 1.18 1.10 1.00 0.88 0.80 0.74 1.13 1.07 1.00 0.91 0.84 0.78
150 1.18 1.10 1.00 0.88 0.80 0.74 1.13 1.07 1.00 0.91 0.83 0.78
185 1.18 1.10 1.00 0.88 0.80 0.74 1.13 1.07 1.00 0.91 0.83 0.78
240 1.18 1.11 1.00 0.88 0.80 0.73 1.14 1.07 1.00 0.90 0.83 0.77
300 1.19 1.11 1.00 0.88 0.80 0.73 1.14 1.07 1.00 0.90 0.83 0.77
400 1.19 1.11 1.00 0.88 0.79 0.73 1.14 1.08 1.00 0.90 0.83 0.77
500 1.20 1.11 1.00 0.87 0.79 0.72 1.14 1.08 1.00 0.90 0.83 0.77
630 1.21 1.11 1.00 0.87 0.78 0.72 1.14 1.08 1.00 0.90 0.82 0.76
800 1.21 1.11 1.00 0.87 0.78 0.72 1.15 1.08 1.00 0.90 0.82 0.76
1000 1.21 1.11 1.00 0.87 0.78 0.72 1.15 1.08 1.00 0.90 0.82 0.76
(Sqmm) 100 120 150 200 250 300 100 120 150 200 250 300
DIRECT IN GROUND
Thermal Resistivity of Soil (C-cm/watt)
IN DUCTS
Thermal Resistivity of Soil (C-cm/watt)
Nominal
Area of
Conductor
RATING FACTORS FOR VARIATION
IN THERMAL RESISTIVITY OF SOIL
53
THREE CORE CABLES WHEN LAID
Nominal
Area of
Conductor
DIRECT IN GROUND
Thermal Resistivity of Soil (C-cm/watt)
IN DUCTS
Thermal Resistivity of Soil (C-cm/watt)
25 1.13 1.08 1.00 0.91 0.84 0.78 1.08 1.04 1.00 0.94 0.89 0.84
35 1.13 1.08 1.00 0.91 0.83 0.78 1.08 1.04 1.00 0.94 0.88 0.84
50 1.14 1.08 1.00 0.91 0.83 0.77 1.08 1.04 1.00 0.94 0.88 0.84
70 1.14 1.09 1.00 0.90 0.83 0.77 1.09 1.04 1.00 0.94 0.88 0.83
95 1.14 1.09 1.00 0.90 0.83 0.77 1.09 1.05 1.00 0.94 0.88 0.83
120 1.14 1.09 1.00 0.90 0.83 0.77 1.09 1.05 1.00 0.93 0.88 0.83
150 1.15 1.09 1.00 0.90 0.83 0.77 1.09 1.05 1.00 0.93 0.88 0.83
185 1.15 1.09 1.00 0.90 0.83 0.77 1.09 1.05 1.00 0.93 0.87 0.83
240 1.15 1.09 1.00 0.90 0.83 0.77 1.10 1.05 1.00 0.93 0.87 0.82
300 1.15 1.09 1.00 0.90 0.82 0.77 1.10 1.05 1.00 0.93 0.87 0.82
400 1.15 1.09 1.00 0.90 0.82 0.76 1.10 1.06 1.00 0.92 0.86 0.81
500 1.16 1.09 1.00 0.89 0.81 0.75 1.10 1.06 1.00 0.92 0.86 0.81
630 1.17 1.09 1.00 0.89 0.81 0.74 1.10 1.06 1.00 0.92 0.86 0.81
(Sqmm) 100 120 150 200 250 300 100 120 150 200 250 300
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
GROUP RATING FACTORS
1 1.00 1.00 0.98 0.95 0.91 1.0 0.88 0.82 0.79 0.76 0.73
2 1.00 0.99 0.96 0.92 0.87 1.0 0.87 0.80 0.77 0.73 0.68
3 1.00 0.98 0.95 0.91 0.86 1.0 0.86 0.79 0.76 0.71 0.66
6 1.00 0.95 0.92 0.88 0.84 1.0 0.84 0.75 0.74 0.68 0.64
2 0.80 0.86 0.90 0.92 0.94 0.85 0.88 0.92 0.94 0.95
3 0.69 0.77 0.82 0.86 0.89 0.75 0.80 0.85 0.88 0.91
4 0.62 0.72 0.79 0.83 0.87 0.69 0.75 0.82 0.86 0.89
5 0.57 0.68 0.76 0.81 0.85 0.65 0.72 0.79 0.84 0.87
6 0.54 0.65 0.74 0.80 0.84 0.62 0.69 0.77 0.83 0.87
7 0.51 0.63 0.72 0.78 0.83 0.59 0.67 0.76 0.82 0.86
8 0.49 0.61 0.71 0.78 - 0.57 0.65 0.75 0.81 -
9 0.47 0.60 0.70 0.77 - 0.55 0.64 0.74 0.80 -
10 0.46 0.59 0.69 - - 0.54 0.63 0.73 - -
11 0.45 0.57 0.69 - - 0.52 0.62 0.73 - -
12 0.43 0.56 0.68 - - 0.51 0.61 0.72 - -
Spacing between Duct centres (mm)
Nos. of
Cables
in Group
Spacing between cable centres (mm)
Touching 200 400 600 800 Touching 200 400 600 800
DIRECT IN GROUND
IN DUCTS
THREE CORE CABLES WHEN LAID
3-Nos. SINGLE CORE CABLES IN TREFOIL MADE ONE CIRCUIT WHEN LAID
2 0.73 0.83 0.88 0.90 0.92 0.78 0.85 0.89 0.91 0.93
3 0.60 0.73 0.79 0.83 0.86 0.66 0.75 0.81 0.85 0.88
4 0.54 0.68 0.75 0.80 0.84 0.59 0.70 0.77 0.82 0.86
5 0.49 0.63 0.72 0.78 0.82 0.55 0.66 0.74 0.80 0.84
6 0.46 0.61 0.70 0.76 0.81 0.51 0.64 0.72 0.78 0.83
7 0.43 0.58 0.68 0.75 0.80 0.48 0.61 0.71 0.77 0.82
8 0.41 0.57 0.67 0.74 - 0.46 0.60 0.70 0.76 -
9 0.39 0.55 0.66 0.73 - 0.44 0.58 0.69 0.76 -
10 0.37 0.54 0.65 - - 0.43 0.57 0.68 - -
11 0.36 0.53 0.64 - - 0.42 0.56 0.67 - -
12 0.35 0.52 0.64 - - 0.40 0.55 0.67 - -
Spacing between Circuit centres (mm)
600 800 Touching 200 400 600 800
Spacing between Circuit centres (mm)
Number of
Trefoil
Group
Touching 200 400
IN DUCTS DIRECT IN GROUND
54
1 0.95 0.90 0.88 0.85 0.84
2 0.90 0.85 0.83 0.81 0.80
3 0.88 0.83 0.81 0.79 0.78
6 0.86 0.81 0.79 0.77 0.76
0N CABLE TRAY INSIDE CONCRETE TRENCH with REMOVABLE COVERS & RESTRICTED AIR CIRCULATION
No. of Cable
Trays in Tier
No. of cables per Tray (Spacing of Cables - One cable diameter)
1 2 3 6 9
ON RACKS / TRAYS IN COVERED TRENCH WITH
REMOVABLE COVERS & RESTRICTED AIR CIRCULATION
ON RACKS / TRAYS EXPOSED TO
OPEN AIR
NOTE : For Laying in Cable Trays - Trays in Tiers by 300 mm & Clearance of 1st. Cable from the Wall is 25 mm for each Tray.
1 0.95 0.90 0.88 1.00 0.98 0.96
2 0.90 0.85 0.83 0.97 0.93 0.89
3 0.88 0.83 0.81 0.96 0.92 0.86
6 0.86 0.81 0.79 0.94 0.90 0.84
1 2 3 1 2 3
No. of Racks/
Trays in Tiers
No. of Circuits per tray (Two cable dia. Spacing) No. of Circuits per tray (Two cable dia. Spacing)
No. of
Cable Trays
in Tier
No. of Cables per Tray (One cable dia. Spacing) No. of Cables per Tray (Cables Touching)
0N CABLE TRAYS EXPOSED TO OPEN AIR
1 2 3 4 6 1 2 3 4 9 6
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
FLAME RETARDANT - IEC 60332-1
FLAME RETARDANT - IEC 60332-3
LOW EMISSION OF DARK FUMES - ASTM D-2843
HALOGEN FREE - IEC 60754-1
LOW TOXICITY AND CORROSIVITY OF EMITTED GASES- IEC 60754-2
PROPERTIES OF FIRE
PERFORMANCE IN CABLES
PROPERTIES COVERED
PROPERTIES REF. STANDARD
TYPES
FR FRLS ZHLS
Flame Retardant Flame Retardant
Low Smoke
Zero Halogen
Low Smoke
Flame Spread
Resistant
Applicable Limit Applicable Applicable Applicable
Oxygen Index ASTMD-2863
29%
(Min.)
29%
(Min.)
30%
(Min.)
30%
(Min.)
Temperature
Index
ASTMD-2863
250C
(Min.)
250C
(Min.)
250C
(Min.)
250C
(Min.)
Smoke Density
Rating
ASTMD-2843
IEC:61034
40%
(Max.)
20%
(Max.)
Halogen Acid Gas
Generation
IEC:60754-1
EN-50267-2-1
20%
(Max.)
Toxicity
Index
Corrosive
Gases
5%
(Max.)
Flame Test on
Single Cable
IEC:60332-1
EN-50265
As per
Specification
Fire Test on
Bunched Cable
IEC:60332-3
EN-50266-2
Applicable
Symbols
0.5%
(Max)
IEC:60754-2
EN-50267-2-2
IEC:60754-2
EN-50267-2-2
PH>4.3
Conductivity
<100 s/cm
Limit Limit Limit
As per
Specification
As per
Specification
As per
Specification
As per
Specification
As per
Specification
55
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
In order to determine the behavior of cables in case of fire, a
group of standards has been developed in order to establish
conditions of fire and to measure the behavior of the cable in
this situation, but it should be taken into account that those
tests are used to assess the behavior of the cables under
established, reproducible conditions and that they are not
necessarily those of the actual installation.
Performance of cables in the event of fire
A flame in contact with the sheath of the cable for an
established period of time should not lead to propagation.
This prevents the cable from being the origin of a fire caused
by a minor incident or an external source of heat coming into
contact with the cable.
A fire unrelated to the cable can affect a cable tray (worst case if it is in a vertical position allowing air circulation
creating the so called chimney effect). If the decomposition temperature of the organic materials is reached, an
exothermic combustion (with the contribution of energy) of the cables takes place with the consequent
propagation of the fire. The insulation and sheath compounds can be formulated to make this exothermic reaction
limited (by the addition of inhibitors). To simulate this situation, the test consists of the application of a high energy
gas burner to a bunch of cables arranged to reproduce a vertical cable tray with forced air. Under those conditions,
the fire provoked in the cables should extinguish within a time established in the standard. Based on the amount of
combustible material per meter for bunch exposed to the fire action, the IEC standard defines different categories.
Flame retardant (Standard IEC 60332-1)
Flame spread (Standard IEC 60332-3-22)
The current IEC regulation considers the following cases:
DETAILS OF FIRE TESTS
56
IEC 60332-3-22 (before fire) IEC 60332-3-22 (at fire)
IEC 60332-1
IEC 60331
IEC 60754
IEC 61034
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
If the cables are immersed in a situation of fire and depending on
the constituent materials, they can release gases which are toxic
for the health of people or corrosive affecting the correct operation
and preservation of the electronic and computer components in
the vicinity. They can also release smoke which, due to its opacity,
makes it difficult to see the escape routes from the spaces affected.
To minimize those effects, General Cable has developed the low
smoke zero halogen series which minimizes harmful halogenated
emissions (IEC 60754-1 and 60754-2) and reduces substantially the
opaque smoke emissions in accordance with IEC 61034-1 & 2.
Zero halogen and low smoke cables
DETAILS OF FIRE TESTS
For circuit integrity and all those systems which need to maintain service under fire conditions, there is the IEC
60331 standard where the fire conditions to which the cables are tested is defined, and which have to continue in
service even if the fire has destroyed the organic parts of same.
In the standard, the cable is exposed to a ribbon gas burner for a maximum time of 180 minutes or higher as
specified in standard and at a minimum temperature of 750 C or higher as specified in standard, while being
subjected every 5 minutes to shocks simulating debris fallout. We produce better fire-resistant cables to withstand
higher temperatures than standard, giving an extra margin of safety in this field. During the test and at the end of it
the cable has to maintain circuit integrity although all of its organic parts have disappeared.
Fire-resistant (Standard IEC 60331)
57
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
CAN/CSA C68.3: Standard for Shielded
and Concentric Neutral Power
Cables Rated 5-46 kV
CAN/CSA T529: Standard Design Guide
for Telecommunications Wiring
Systems in Commercial Buildings
CSA C22.1: Canadian Electrical Code,
Part 1, Safety Standard for
Electrical Installations
CSA C22.2 No. 0.3: Standard for Test
Methods for Electrical Wires and
Cables
CSA C22.2 No. 16: Standard for
Insulated Conductors for Power-
Operated Electronic Devices
CSA C22.2 No. 35: Standard for Extra-
Low-Voltage Control Circuit Cables,
Low-Energy Control Cable, and
Extra-Low-Voltage Control Cable
CSA C22.2 No. 38: Standard for
Thermoset Insulated Wires and
Cables
CSA C22.2 No. 52: Standard for Service-
Entrance Cables
CSA C22.2 No. 75: Standard for
Thermoplastic-Insulated Wires and
Cables
CSA C22.2 No. 116: Standard for Coil-
Lead Wires
CSA C22.2 No. 123: Standard for
Aluminum Sheathed Cables
CSA C22.2 No. 124: Standard for
Mineral-Insulated Cable
CSA C22.2 No. 127: Standard for
Equipment Wires
CSA C22.2 No. 129: Standard for
Neutral Supported Cable
CSA C22.2 No. 130: Standard for Heating
Cables and Heating Cable Sets
CSA C22.2 No. 138: Standard for Heat
Tracing Cable and Cable Sets for
Use in Hazardous Locations
CSA C22.2 No. 174: Standard for Cables
and Cable Glands for Use in
Hazardous Locations
CSA C22.2 No. 179: Standard for Airport
Series Lighting Cables
CSA C22.2 No.188: Standard for
Splicing Wire and Cable Connectors
CSA C22.2 No. 198.2: Standard for
Underground Cable Splicing Kits
CSA C22.2 No. 208: Standard for Fire
Alarm and Signal Cable
CSA C22.2 No. 222: Standard for Type
FCC Under-Carpet Wiring System
CSA C22.2 No. 230: Standard for Tray
Cable
CSA C22.2 No. 232: Standard for
Optical Fiber Cables
CSA/CAN3 C22.3 No. 7: Standard for
Underground Systems
CSA C49.2: Standard for Compact
Aluminum Conductors Steel
Reinforced (ACSR)
CSA C49.3: Standard for Aluminum
Alloy 1350 Round Wire, All
Tempers, for Electrical Purposes
CSA C49.4: Standard for Concentric-Lay
Aluminum Stranded Conductors
(ASC)
CSA C49.5: Standard for Compact
Round Concentric-Lay Aluminum
Stranded Conductors (Compact ASC)
CSA CAN3-C49.6: Standard for Zinc-
Coated Steel Wires for Use in
Overhead Electrical Conductors
CSA CAN3-C49.7: Standard for
Aluminum Round Wires for Use in
Overhead Electrical Conductors
CSA C68.1: Standard Specifications for
Impregnated Paper-Insulated,
Metallic-Sheathed Cable, Solid- Type
CSA C170.2: Standard for Polyethylene
Protective Covering on Paper-
Insulated Metallic Sheathed Power
Cable
CSA C170.3: Standard for Polyvinyl-
Chloride (PVC) Protective Covering
on Paper-Insulated Metallic-
Sheathed Power Cable
CSA M421: Standard for Use of
Electricity in Mines
EIA/TIA-568: Commercial Building
Telecommunications Wiring
Standard
EIA/TIA-569: Commercial Building
Standard for Telecommunications
Pathways and Spaces
EIA/TIA-606: Administration Standard for
the Telecommunications
Infrastructure of Commercial
Buildings
EIA/TIA TSB-36: Additional Cable
Specifications for Unshielded
Twisted Pair Cables (Technical
Systems Bulletin 36)
EIA/TIA TSB-40: Additional
Transmission Specifications for
Unshielded Twisted Pair
Connecting Hardware (Technical
Systems Bulletin 40)
FP-4: TM-4 CSA CBC and UL CMR
(Riser) Cable
FP-16: TD-16 Plastic Insulated, Two
Parallel Conductor, Telephone Drop
Wire
FP-28: Air Core, Solid PIC, ALPETH-
DCAS Cable and PAP-DCAS Cable
FP-67: PHD Plastic Insulated and
J acketed, Four Conductor,
Telephone Drop Wire
FP-68: TM-68 CSA PCC FT4, Shielded
Inside Wiring Cable
FP-71: TM-28 CSA PCC FT4, Inside
Wiring Cable
FP-75: PHILPLAST CSA PCC FT4, PVC
Insulated and J acketed,
Switchboard Cable
FP-81: TM-81 CSA ZSW FT1, Telephone
Station Wire
FP-90: CONCEL Cellular Polyethylene
Insulated, Air Core, ALPETH-DCAS
Sheathed, Telephone Cable
FP-93: TM-91, TM-92, TM-93 and TM-
97, Filled, Buried Wire
FP-95: Quasi-Solid Polyethylene
Insulated, Filled, Regular and Twin
Core, ALPETHDCAS Sheathed
Cable
FP-98: CELSEAL Cellular Polyethylene
Insulated, Filled, ALPETH-DCAS
Sheathed Cable
FP-99: DUCTCEL Cellular Polyethylene
Insulated, Air Core, ALPETH-DCAS
Sheathed Telephone Cable
FP-8859: PHILSYM UL 444 CMR and
CSA PCC FT4 Switchboard Cable
HP: See NEMA listing
ICEA P-32-382: ICEA Standards
Publication for Short Circuit
Characteristics of Insulated Cable
High Voltage Power Cable
REFERENCE INTERNATIONAL STANDARDS
58
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
REFERENCE INTERNATIONAL STANDARDS
ICEA P-45-482: ICEA Standards
Publication for Short-Circuit
Performance of Metallic Shields and
Sheaths of Insulated Cable
ICEA P-53-426: ICEA/NEMA Standards
Publication for Ampacities, Including
Effect of Shield Losses for Single-
Conductor Solid-Dielectric Power
Cable 15 kV through 69 kV (NEMA
WC 50)
ICEA P-54-440: ICEA/NEMA Standards
Publication for Ampacities of Cables
in Open-Top Cable Trays (NEMA
WC 51)
ICEA P-79-561: ICEA Guide for Selecting
Aerial Cable Messengers and Lashing
Wires
ICEA S-56-434: ICEA/ANSI Standards
Publication for Polyolefin Insulated
Communications Cables for Outdoor
Use
ICEA S-67-401: ICEA/NEMA Standards
Publication for Steel Armor and
Associated Coverings for
Impregnated- Paper-Insulated
Cables (NEMA WC 2)
ANSI/ICEA S-70-547: ICEA/ANSI
Standards Publication for Weather-
Resistant Polyolefin-Covered Wire
and Cable
ICEA S-73-532: ICEA/NEMA/ANSI
Standards Publication for Control
Cables (NEMA WC 57)
ICEA S-75-381: ICEA/NEMA/ANSI
Standards Publication for Portable
and Power Feeder Cables for Use
in Mines and Similar Applications
(NEMA WC 58)
ANSI/ICEA S-76-474: ICEA/ANSI
Standards Publication for Neutral-
Supported Power Cable Assemblies
with Weather-Resistant Extruded
Insulation, 600 Volts
ICEA S-77-528: ICEA/ANSI Standards
Publication for Outside Plant
Communications Cables, Specifying
Metric Wire Sizes
ICEA S-80-576: ICEA/ANSI Standards
Publication for Communications Wire
and Cable for Wiring of
Premises
ANSI/ICEA S-81-570: Standard for 600
volt rated cables of Ruggedized
Design For Direct Burial installations
of single conductors or assemblies
of single Conductors.
ICEA S-82-552: ICEA/NEMA Standards
Publication for Instrumentation
Cables and Thermocouple Wire
(NEMA WC 55)
ICEA S-83-596: ICEA/ANSI Standards
Publication for Fiber Optic Premises
Distribution Cable
ICEA S-84-608: ICEA/ANSI Standards
Publication for Telecommunications
Cable, Filled Polyolefin Insulated,
Copper Conductor
ICEA S-85-625: ICEA/ANSI Standards
Publication for Aircore, Polyolefin
Insulated, Copper Conductor
Telecommunications Cable
ICEA S-86-634: ICEA/ANSI Standards
Publication for Buried Distribution
and Service Wire, Filled Polyolefin
Insulated, Copper Conductor
ICEA S-87-640: ICEA/ANSI Standards
Publication for Fiber Optic Outside
Plant Communication Cable
ICEA-S-93-639: ICEA/NEMA Standard
for Shielded Power Cables Rated 5-
46 KV for the Distribution of
Electrical Energy (NEMA WC 74)
ANSI/ICEA-S-94-649: Standard for
Concentric Neutral Cables Rated 5-
46 KV
ICEA S-95-658: ICEA/NEMA Standard
for Non-shielded Power Cables
Rated 2000 Volts or Less for the
Distribution of Electrical Energy
(NEMA WC 70)
ICEA S-96-659: ICEA/NEMA Standard
for Non-shielded Cables Rated
2001-5000 Volts for use in the
Distribution of Electrical Energy
(NEMA WC 71)
ANSI/ICEA S-97-682: Standard for Utility
Shielded Power Cable Rated 5-46 KV
ANSI/ICEA S-105-692: Standard for 600
Volt Single Layer Thermoset
Insulated Utility Underground
Distribution Cable
ICEA T-22-294: ICEA Standard Test
Procedures for Extended Time-
Testing of Wire and Cable Insulations
for Service in Wet Locations
ICEA T-25-425: ICEA Guide for
Establishing Stability of Volume
Resistivity for Conducting Polymeric
Components of Power Cables
ICEA T-26-465: ICEA/NEMA Guide for
Frequency of Sampling Extruded
Dielectric Power, Control,
Instrumentation and Portable
Cables for Test (NEMA WC 54)
ICEA T-27-581: ICEA/NEMA Standard
Test Methods for Extruded Dielectric
Power, Control, Instrumentation and
Portable Cables (NEMA WC 53)
ANSI/ICEA T-28-562: ICEA Standard Test
Method for Measurement of Hot
Creep of Polymeric Insulations
ICEA T-29-520: ICEA Standard for
Vertical Tray Flame Tests at
210,000 Btu
ICEA T-30-520: ICEA Standard for Vertical
Tray Flame Tests at 70,000 Btu
ICEA T-31-610: ICEA Standard for Water
Penetration Resistance Test, Sealed
Conductor
ICEA T-32-645: ICEA Standards
Publication for Compatibility of
Sealed Conductor Filer Compounds
IEC 92-3: International Electrotechnical
Commission Electrical Installation in
Ships - Part 3 Cables Constructions,
Testing and Installations)
IEEE 45: IEEE Recommended Practice
for Electric Installations on Shipboard
IEEE 48: IEEE Standard Test Procedures
and Requirements for High-Voltage
Alternating Current Cable
Terminations
IEEE 100: IEEE Standard Dictionary of
Electrical and Electronics Terms
IEEE 141: IEEE Recommended Practice
for Electric Power Distribution for
Industrial Plants (IEEE Red Book)
IEEE 142: IEEE Recommended Practice
for Grounding of Industrial and
Commercial Power Systems
(IEEE Green Book)
IEEE 241: IEEE Recommended Practice
for Electric Power Systems in
Commercial Buildings (IEEE Gray
Book)
IEEE 242: IEEE Recommended Practice
for Protection and Coordination of
Industrial and Commercial Power
Systems (IEEE Buff Book)
IEEE 323: IEEE Standard for Qualifying
Class 1E Equipment for Nuclear
Power Generating Stations
IEEE 383: IEEE Standard for Type Test
of Class 1E Electric Cables, Field
Splices and Connections for
Nuclear Power Generating Stations
59
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
REFERENCE INTERNATIONAL STANDARDS
IEEE 400: IEEE Guide for Making High-
Direct-Voltage Tests on Power
Cable Systems in the Field
IEEE 404: IEEE Standard for Cable
J oints for Use with Extruded
Dielectric Cable Rated 5,000V
Through 46,000V, and Cable J oints
for Use with Laminated Dielectric
Cable Rated 2,500V Through
500,000V (Adopted as a National
Standard of Canada, CAN/CSA-
C22.2 No. 241)
IEEE 446: IEEE Recommended Practice
for Emergency and Standby Power
Systems for Industrial and
Commercial Applications (IEEE
Orange Book)
IEEE 493: IEEE Recommended Practice
for the Design of Reliable Industrial
and Commercial Power Systems
(IEEE Gold Book)
IEEE 515: IEEE Recommended Practice
for the Testing, Design, Installation,
and Maintenance of Electrical
Resistance Heat Tracing for
Industrial Applications
IEEE 524: IEEE Guide to the Installation
of Overhead Transmission Line
Conductors
IEEE 525: IEEE Guide for the Design
and Installation of Cable Systems in
Substations
IEEE 575: IEEE Guide for the Application
of Sheath-Bonding Methods for
Single-Conductor Cables and the
Calculation of Induced Voltages and
Currents in Cable Sheaths
IEEE 576: IEEE Recommended Practice
for Installation, Termination, and
Testing of Insulated Power Cable as
Used in the Petroleum and
Chemical Industry
IEEE 590: IEEE Cable Plowing Guide
IEEE 602: IEEE Recommended Practice
for Electric Systems in Health Care
Facilities (IEEE White Book)
IEEE 635: IEEE Guide for Selection and
Design of Aluminum Sheaths for
Power Cables
IEEE 644: IEEE Standard Procedures for
Measurement of Power Frequency
Electric and Magnetic Fields from
AC Power Lines
IEEE 738: IEEE Standard for Calculation
of Bare Overhead Conductor
Temperature and Ampacity Under
Steady-State Conditions
IEEE 789: IEEE Standard Performance
Requirements for Communications
and Control Cables for Application
in High Voltage Environments
IEEE 802.3: IEEE Standard for
Information Processing Systems -
Local and Metropolitan Area
Networks - Part 3: Carrier Sense
Multiple Access with Collision
Detection (CSMA/CD) Access Method
and Physical Layer Specifications
(ISO/IEC) (ANSI/IEEE Std 802.3)
IEEE 802.5: IEEE Standard for Information
Technology - Local and Metropolitan
Area Networks - Part 5: Token Ring
Access Method and Physical Layer
Specifications (ISO/IEC) (ANSI/IEEE
Std 802.5)
IEEE 816: IEEE Guide for Determining
the Smoke Generation of Solid
Materials Used for Insulations and
Coverings of Electric Wire and Cable
IEEE 844: IEEE Recommended Practice
for Electrical Impedance, Induction,
and Skin Effect Heating of Pipelines
and Vessels
IEEE 1017: IEEE Recommended
Practice for Field Testing Electric
Submersible Pump Cable
IEEE 1018: IEEE Recommended
Practice for Specifying Electric
Submersible Pump Cable Ethylene-
Propylene Rubber Insulation
IEEE 1019: IEEE Recommended
Practice for Specifying Electric
Submersible Pump Cable
Polypropylene Insulation
IEEE 1120: IEEE Guide to the Factors to
Be Considered in the Planning,
Design, and Installation of Submarine
Power and Communications Cables
IEEE 1202: IEEE Standard for Flame
Testing of Cables for Use in Cable
Tray in Industrial and Commercial
Occupancies
IEEE/ICEA S-135: Power Cable Ampacities
Mil-C-17: General Specifications for
Flexible and Semirigid Radio
Frequency Cables
Mil-C-915F: General Specification for
Electrical Cable and Conductors for
Shipboard Use
Mil-C-13777: General Specification for
Special Purpose Electrical Cable
Mil-C-24640: General Specification for
Lightweight Electrical Cable for
Shipboard Use
Mil-C-24643: General Specification for Low
Smoke Electrical Cable and
Conductors for Shipboard Use
Mil-C-27500: General Specification for
Shielded and Unshielded Electrical
Power Cable and Special Purpose
Cable
Mil-C-85045: General Specification for
Fiber Optic Cables [Metric]
Mil-W-16878: General Specification for
Insulated Electrical Wire
Mil-W-22759: General Specification for
Copper or Copper Alloy
Fluoropolymer-Insulated Electrical
Wire
Mil-W-81044: General Specification for
Copper or Copper Alloy, Crosslinked
Polyalkene, Crosslinked Alkane-Imide
Polymer or Polyalkene Insulated
Electrical Wire
Mil-W-81381: General Specification for
Replacement Wire
Mil-W-85485: General Specification for
Radio Frequency Absorptive Filter
Line Electrical Cable
NAVSEA 6710782: Fiber Optic and
Multimode Cable
NEMA HP 3: Electrical and Electronic
PTFE (Polytetrafluoro-ethylene)
Insulated High Temperature Hook-Up
Wire; Types (600 Volt), EE (1000
Volt), and ET (250 Volt)
NEMA HP 4: Electrical and Electronic FEP
Insulated High Temperature Hook-Up
Wire; Types K, KK, and KT
NEMA HP 100: High Temperature
Instrumentation and Control Cables
NEMA HP 100.1: High Temperature
Instrumentation and Control Cables
Insulated and J acketed with FEP
Fluorocarbons
NEMA HP 100.2: High Temperature
Instrumentation and Control Cables
Insulated and J acketed with ETFE
Fluoropolymers
NEMA HP 100.3: High Temperature
Instrumentation and Control Cables
Insulated and J acketed with Cross-
Linked (Thermoset) Polyolefin (XLPO)
60
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
REFERENCE INTERNATIONAL STANDARDS
NEMA HP 100.4: High Temperature
Instrumentation and Control Cables
Insulated and J acketed with ECTFE
Fluoropolymers
NEMA WC 2: Steel Armor and Associated
Coverings for Impregnated-Paper-
Insulated Cables (ICEA S-67-401)
NEMA WC 3: Rubber-Insulated Wire
and Cable for the Transmission and
Distribution of Electrical Energy
(ICEA S-19-81)
NEMA WC 5: Thermoplastic-Insulated
Wire and Cable for the
Transmission and Distribution of
Electrical Energy (ICEA S-61-402)
NEMA WC 7: Cross-Linked-
Thermosetting-Polyethylene-
Insulated Wire and Cable for the
Transmission and Distribution of
Electrical Energy (ICEA S-66-524)
NEMA WC 8: Ethylene-Propylene-
Rubber-Insulated Wire and Cable
for the Transmission and Distribution
of Electrical Energy (ICEA S-68-516)
NEMA WC 26: Wire and Cable
Packaging
NEMA WC 50: Ampacities, Including
Effect of Shield Losses for Single-
Conductor Solid Dielectric Power
Cable 15 kV through 69 kV (ICEA P-
53-426)
NEMA WC 51: Ampacities of Cables in
Open-Top Cable Trays (ICEA P-54-
440)
NEMA WC 52: High Temperature and
Electronic Insulated Wire-Impulse
Dielectric Testing
NEMA WC 53: Standard Test Methods
for Extruded Dielectric Power,
Control, Instrumentation, and
Portable Cables (ICEA T-27-581)
NEMA WC 54: Guide for Frequency of
Sampling Extruded Dielectric
Power, Control, Instrumentation, and
Portable Cables for Test (ICEA T26-
465)
NEMA WC 55: Instrumentation Cables
and Thermocouple Wire (ICEA S-
82-552)
NEMA WC 56: 3.0 kHz Insulation
Continuity Proof Testing of Hook-Up
Wire
NEMA WC 57: Standard for Control
Cables (ICEA S-73-532)
NEMA WC 58: Standard for Portable and
Power Feeder Cables for Use in
Mines and Similar Applications
(ICEA-S-75-381)
NEMA WC 61: Transfer Impedance
Testing
NEMA WC 62: Repeated Spark/Impulse
Dielectric Testing
NEMA WC 70: Standard for Non-
shielded Power Cables Rated 2000
Volts or Less for the Distribution of
Electrical Energy (ICEA S-95-658)
NEMA WC 71: Standard for Non-
shielded Cables Rated 2001-5000
Volts for Use in the Distribution of
Electrical Energy (ICEAS-96-659)
NEMA WC 74: Standard for Shielded
Power Cables Rated 5-46 KV for
the Distribution of Electrical Energy
(ICEA S-93-639)
NFPA 70: National Electrical Code
NFPA 70HB: National Electrical Code
Handbook
NFPA 262: Test for Fire and Smoke
Characteristics of Wires and Cables
ONT M-302-84: Cable, Secondary, for
Direct Burial
ONT M-355-82: Cable, Primary
Submarine
ONT M-538-84: Cable, For Use in
Generating Stations (5 kV and
Above)
ONT M-570-84: Cable, For Use in
Generating Stations (600V)
ONT M-695-88: Cable, Primary and
Subtransmission Submarine,
Concentric Neutral
SAE 1560: Low Tension, Thin Wall
Primary Cable
SAE J 1127: Battery Cable
SAE J 1128: Low Tension Primary Cable
TIA: See EIA/TIA
UL 4: Standard for Armored Cable
UL 13: Standard for Power-Limited
Circuit Cables
UL 44: Standard for Rubber-Insulated
Wires and Cables
UL 62: Standard for Flexible Cord and
Fixture Wire
UL 83: Standard for Thermoplastic-
Insulated Wires and Cables
UL 183: Standard for Manufactured
Wiring Systems
UL 444: Standard for Communications
Cables
UL 486A: Standard for Wire Connectors
and Soldering Lugs for Use With
Copper Conductors
UL 486B: Standard for Wire Connectors
and Soldering Lugs for Use With
Aluminum Conductors
UL 486C: Standard for Splicing Wire
Connectors
UL 486D: Standard for Insulated Wire
Connectors for Use With
Underground Conductors
UL 486E: Standard for Equipment Wiring
Terminals for Use With Aluminum
and/or Copper Conductors
UL 493: Standard for Thermoplastic-
Insulated Underground Feeder and
Branch-Circuit Cables
UL 498: Standard for Attachment Plugs
and Receptacles
UL 514B: Standard for Fittings for
Conduit and Outlet Boxes
UL 719: Standard for Nonmetallic-
Sheathed Cables
UL 758: Standard for Appliance Wiring
Material - Component
UL 814: Standard for Gas-Tube-Sign and
Ignition Cable
UL 817: Standard for Cord Sets and
Power-Supply Cords
UL 854: Standard for Service-Entrance
Cables
UL 910: Standard for Test for Flame-
Propagation and Smoke-Density
Values for Electrical and Optical- Fiber
Cables Used in Spaces Transporting
Environmental Air
UL 1023: Standard for Household
Burglar-Alarm System Units
UL 1063: Standard for Machine-Tool
Wires and Cables
UL 1072: Standard for Medium-Voltage
Power Cables
UL 1084: Standard for Hoistway Cables
UL 1263: Standard for Irrigation Cables
61
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
UL 1277: Standard for Electrical Power
and Control Tray Cables With
Optional Optical Fiber Members
UL 1309: Standard for Marine Shipboard
Cable
UL 1424: Standard for Cables for Power-
Limited Fire-Protective-Signaling
Circuits
UL 1426: Standard for Cables for Boats
UL 1446: Standard for Systems of
Insulating MaterialsGeneral
UL 1462: Standard for Mobile Home
Pipe Heating Cable
UL 1569: Standard for Metal-Clad Cables
UL 1581: Reference Standard for Electrical
Wires, Cables and Flexible Cords
UL 1588: Standard for Roof and Gutter
De-Icing Cable Units
UL 1666: Standard Test for Flame
Propagation Height of Electrical and
Optical-Fiber Cables Installed
Vertically in Shafts
UL 1673: Standard for Electric Space
Heating Cables
UL 1685: Standard for Vertical-Tray Fire-
Propagation and Smoke-Release
Test for Electrical and Optical-Fiber
Cables
UL 1690: Standard for Data Processing
(DP) Cables
UL 1712: Standard Tests for Ampacity of
Insulated Electrical Conductors
Installed in the Fire Protective
System
UL 1807: Standard for Fire Resistant
Cable Coating Materials
UL 2023: Standard Test Method for
Flame and Smoke Characteristics of
Nonmetallic Wiring Systems
(Raceway and Conductors) for
Environmental Air-Handling Spaces
UL 2029: Standard for Gas/Vapor-
Blocked Cable Classified for Use in
Class 1 Hazardous (Classified)
Locations
UL 2049: Standard for Residential Pipe
Heating Cable
WC: See NEMA listing
High Voltage Power Cable
REFERENCE INTERNATIONAL STANDARDS
62
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
Insulation Shielding
___ Extruded
___ Tape
Metallic Shielding
___ Bare/Coated
___ Helical copper tapes
___ Helical wires
___ Longitudinal drain wires
___ Other
J acket
___ CPE
___ CSPE
___ LSZH/XLPO
___ Neoprene
___ Polyurethane
___ PVC
___ XLPE
___ XL-CPE
___ XL-LSZH
___ Other
Cable Assembly
___ Cabled (Yes/No)
___ Other (Any Speciality)
Grounding Conductors
___ Bare/Coated
___ Insulated/Uninsulated
___ Quantity
___ Size (sqmm)
Neutral Conductors
___ Bare/Coated
___ Fillers
___ Flame-retardant
___ Fiber
___ Quantity
___ Insulated
___ Paper
___ Other
___ Size
Covering
___ Corrugated continuous
welded armor
___ Interlocked armor
___ Lead
___ Nonmetallic
___ Other
Color
Voltage rating
Temperature rating
Approvals
CHECKLIST FOR SPECIFICATIONS
63
General Checklist
Standards
___ ISS
___ BSS
___ J IS
___ AEIC
___ CANENA
___ CSA
___ ICEA
___ IEC
___ IEEE
___ UL
___ Other
Testing Procedures
___ ISS
___ BSS
___ J IS
___ AEIC
___ CAN ENA
___ CSA
___ ICEA
___ IEC
___ IEEE
___ UL
___ Other
Special Requirements
___ Cold bend
___ Direct burial
___ Flame-retardant
___ Oil-resistant
___ Sunlight-resistant
___ Other
Documentation
___ Certificates of Compliance
___ Certified Test Reports
___ Drawings
___ Warranties
___ Other
System Characteristics
Shipping Details
___ Cut lengths
___ Installation
recommendation
___ Lagging
___ Returnable reels
___ Other
Identification
___ Cable
___ Circuit
___ Reel
Note: This checklist must be
accompanied by exact system
details about the environment and
electrical characteristics.
Checklist for Specifications
Control Cable
Power Cable
Conductor Type
Size (sqmm)
Solid/Stranded/Flexible
Bare/Coated
Insulation
J acket
Temperature rating
Voltage rating
Number of Conductors
Identification Method
___ Color code
___ Numbering
Grounding Conductor (if any)
___ Bare/Coated
___ Size
___ Insulated
Size (sqmm)
Conductor Type (metal)
Stranding (Circular/Shaped)
Bare/Coated
Conductor Shielding
___ Extruded
___ Tape
Insulation
___ EPR
___ EVA
___ FEP
___ FR-EP
___ LSZH
___ Polyethylene/PVC
___ PVC/Nylon
___ Silicone
___ XLPE
___ Other
Insulation Level
___ Earthed
___ Unearthed
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
METRIC CONVERSION FACTORS
To Convert From To Multiply By
Length
Area
Weight
Electrical
Mechanical
Inches Millimeters 25.4
Millimeters Inches 0.03937
Inches Centimeters 2.54
Centimeters Inches 0.3937
Feet Meters 0.3048
Meters Feet 3.2808
Kilofeet (1000 ft) kilometers 0.3048
kilometers kilofeet (1000 ft) 3.2808
Square Inches Square Millimeters 645.16
Square Millimeters Square Inches 0.00155
Square Inches Square Centimeters 6.4516
Square Centimeters Square Inches 0.155
Square Inches Circular Mils 1,273,240
-7
Circular Mils Square Inches 7.854 x 10
4
Circular Mils Square Millimeters 5.066 x 10
Square Millimeters Circular Mils 1973.51
Square Feet Square Meters 0.0929
Square Meters Square Feet 10.764
Pounds Kilograms 0.4536
Kilograms Pounds 2.2046
Pound/Kilofeet Kilograms/Kilometer 1.4882
Kilograms/Kilometer Pounds/Kilofeet 0.6720
Ohms/Kilofeet Ohms/Kilometer 3.2808
Ohms/Kilometer Ohms/Kilofeet 0.3048
Microfarads/Kilofeet Microfarads/Kilometer 3.2808
Microfarads/Kilometer Microfarads/Kilofeet 0.3048
Insulation Resistance:
MegohmsKilofeet MegohmsKilometer 0.3048
MegohmsKilometer MegohmsKilofeet 3.2808
Pounds/Square Inch Kilo Pascal* 6.895
Kilo Pascal* Pounds/Square Inch 0.1432
Pounds (force) Newtons 4.448
* 1 Pascal =1 newton/m2
64
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
RECOMMENDED REEL
HANDLING PRACTICES
Upended heavy reels will often arrive
damaged. Refuse or receive subject to
inspection for hidden damage.
Reels can be hoisted with a shaft
extending through both flanges.
Do not lift by top flange. Cable or reel
will be damaged.
Lower reels fromtruck using
hydraulic gate, hoist or fork lift.
LOWER CAREFULLY.
Never allow forks to touch cable surface
or reel wrap.
Always load with flanges on edge and
chock and block securely.
Never drop reels.
Cradle both reel flanges between forks.
65
How to Handle Cable Reels
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
Cable reels are never shipped upended (flat side down). Cable reels that arrive in this manner should be rejected or
received only after a thorough inspection for damage.
See Recommended Reel Handling Practiceson the following pages.
Upon receipt, a cables protective covering and/or lagging should be inspected for evidence of damage during shipment.
If evidence of damage is found, a report should immediately be made to the carrier.
Under no circumstances should reels be dropped from the delivering vehicle to the ground.
Unloading and reel handling should be accomplished so that the equipment used does not contact the cable surface,
and in the case of protective wrap, that the equipment does not contact the protective wrap.
If unloading and reel handling is accomplished by crane, either a cradle supporting the reel flanges or a shaft through the
bore hole should be used. If a fork lift is utilized, the forks must lift the reel at 90 to the flanges and the forks must be
long enough to make complete lifting contact with both flanges. Under no circumstances should the forks come into
contact with the cable surface or the protective wraps.
When a reel of cable is rolled from one point to another, care must be taken to see that there are no objects on the
surface area which could contact or damage the cable surface or protective wrap.
If an inclined ramp is used for unloading, the ramp must be wide enough to contact both flanges completely. The
stopping of the reels at the bottom shall be accomplished by using the reel flanges and not the surface of the cable.
High Voltage Power Cable
RECOMMENDED CABLE
HANDLING PRACTICES
66
Unloading and Moving of Reels:
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
RECOMMENDED CABLE
STORAGE PRACTICES
High Voltage Power Cable
67
Finished cables have no established shelf-life. Moisture and atmospheric conditions can cause exposed conductors to
oxidize and discolor. Uncovered/unsheltered cable will degrade due to exposure to direct sunlight and/or the elements. If
the cables are protected, there should be no degradation of the insulation.
In general, any cable for use indoors should be stored indoors. Any cable suitable for installation outdoors is suitable for
storage outdoors. Cables stored outdoors should have the ends sealed to prevent moisture ingress into the cable.
Cables should be stored in a sheltered area. While on the reel, cable should be covered with Masonite or a dark film
wrap (to block the suns rays and shield from the elements).
Cables with a cold temperature marking i.e. 10C, 25C, or 40C may be stored in low ambient temp. area. Cables
without a cold temperature marking should not be stored in the low temp. area.
Cable reels must remain in the upright position. Cable reels must not be stored on their sides. Reels must not be
stacked.
Cable reels should be stored with the protective covering or lagging in place. If a length of cable has been cut
from the reel, the cable end should be immediately resealed to prevent the entrance of moisture. If a part length is
returned to storage, the reels protective covering should be restored.
Wooden reels should be stored off the ground to prevent rotating. Reels should be stored on a flat, hard surface so that
flanges do not sink into the earth. The weight of the reel and cable must be carried at all times by the reel flanges.
Cable reels and lagging must not be stored for an extended time period sitting in direct contact with water or
dampness. Timbers or metal supports must be placed under the reel flanges to provide elevated storage of the reels
away from the direct contact with water or damp soil.
Reels should be stored in an area where construction equipment, falling or flying objects or other materials will not
contact the cable.
Cable should be stored in an area where chemicals or petroleum products will not be spilled or sprayed on the cable.
Cable should be stored in an area away from open fires or sources of high heat.
If the reels are relocated, they should be handled as suggested in the Recommended Reel Handling Practicessection,
and inspection made on each reel during the relocation.
If the cables are stored in a secure area and not exposed to the effects of the weather, an annual inspection
should be satisfactory.
Where the reels are exposed to the weather, a bimonthly inspection should be performed to observe any sign of
deterioration.
If the reels are exposed in a non-secure area, policing of the area at frequent intervals may be required depending on
circumstances.
Records of delivery date, manufacturer, installation date, any extenuating circumstances, along with all test
reports should be kept on file.
Storage and Storage Maintenance:
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
PRE-INSTALLATION
INSTRUCTIONS
To ensure safety during cable
installation and reliability once the
cable is installed, you should confirm
the following prior to installation:
The cable selected is proper for
your application
The cable has not been
damaged in transit or storage
Review all applicable state and
national codes to verify that the
cable chosen is appropriate for the
job. Also, consult your local authority.
Next, you must identify any existing
cable damage and prevent any
further damage from occurring. This
is done through proper cable
inspection, handling and storage.
68
Overview
Inspect every cable reel for damage
before accepting the shipment. Be
particularly alert for cable damage if:
A reel is laying flat on its side
Several reels are stacked
Other freight is stacked on a reel
Nails have been driven into reel
flanges to secure shipping
blocks
A reel flange is damaged
A cable covering is removed,
stained or damaged
A cable end seal is removed or
damaged
A reel has been dropped
(Hidden damage likely)
Cable Inspection
Remove all nails and staples from
the reel flanges before moving a
reel, and avoid all objects that could
crush, gouge or impact the cable
when moving. NEVER use the cable
as a means to move a reel.
When unreeling, observe
recommended bending radii, use
swivels to prevent twisting and avoid
overruns.
Cabling Handling
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
INSTALLATION OVERVIEW
AND CHECKLIST
Most cables are subjected to more
mechanical stress during installation
than they ever experience in actual
operation. Needless to say, handling
and pulling your cable according to
manufacturers recommendations
is extremely important.
There are five main considerations in
any cable installation:
Ambient temperature
Equipment
Conduit fill
Mechanical fit in raceway
Physical limitations
Low temperatures are a cause for
concern when installing cable in low
Ambient temp area. Cable should
not be installed when temperatures
are less than the cold bend
temperature rating of the cable
product plus 15C (i.e.,
minimum installation temperature =
cold bend temperature rating +
15C). Above may not be marked for
cable installing in normal temp
region.
Prior to performing a low
temperature (less than 10F) cable
installation, cable should be stored
for a minimum of 24 hours at a
temperature of 55F or higher.
Cable should be pulled more slowly
and trained in place the same day it
is removed from storage. Do not
impact, drop, kink or bend cable
sharply in low temperatures.
Also, maximum possible ambient
temp. should be less than the high
temp. limit of the cables.
Installation
69
The proper use of appropriate
equipment is crucial to a successful
cable installation. The equipment
needed for most installations
is detailed in the following checklist:
0-1/5/10 kip dynamometer
Basket grip pullers
Cable cutter
Cable pulling lubricant
Cable tray bend sheaves
Cable tray rollers
Capstan type puller
Diameter tape
Duct cleaning mandrels
Duct testing mandrels
Electric safety blankets and
clamps
Extension cords and GFCI
protection
Fishtape or string blower/vacuum
Flood lamps
Gang rollers; with at least 4 ft.
effective radius
Gloves
Guide-in flexible tubing (elephant
trunks)
Hand winches (come-a-long)
HiPot tester
Lint-free rags
Manhole cover hooks
Manhole edge sheave
Measuring tape
Personal protection clothing
Plywood sheets
Portable electric generator
Pre-lubing devices
Pulling rope
Pump, diaphragm
Radios or telephones
Reel arbor
Reel brakes
Reel jacks
Several wire rope slings of
various lengths
Shackles/clevis
Short ropes for temp tie-offs
Silicone caulking (to seal cable
ends)
Swivels
Warning flags, signs
Make-up air blower and hose
Overview Installation Temperature Equipment
Cable Feed-In Setups
The following diagrams illustrate various cable feed-in setups:
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
INSTALLATION
FEED-IN SETUPS
The feed-in setup should unreel the
cable with a natural curvature
(Figure 1) as opposed to a reverse
Scurvature (Figure 2).
70
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
INSTALLATION
FEED-IN SETUPS
Cable Feed-In Setups (continued)
Single Sheaves may be
used only for GUIDING cables.
Arrange multiple blocks to hold
bending radii whenever cable
is deflected.
Remember to use the radius of the
surface over which the cable is bent,
not the outside flange diameter of the
pulley. A 10 inchcable sheave typically
has an inside (bending) radius
of 3 inches.
The pulleys must be positioned to ensure that
the effective curvature is smooth and deflected
evenly at each pulley. Never allow a polygon
curvature to occur (Figure 3).
The fit of a pulley around the cable is also
important when pulling heavy weights
(i.e. pulleys at the top of a vertical drop).
For pulling around bends,
use conveyor sheave
assemblies of the
appropriate radius series
71
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
DC HI-POT
TESTING GUIDELINES
The direct current test voltage
may be applied either continuously
or in predetermined steps to the
maximum value in accordance with
applicable specifications.
Continuous Method Apply test
voltage at an approximate rise
rate of 1 kV per second or 75%
of the rated current output of the
equipment, whichever is less.
Some equipment will take longer
to reach the maximum test voltage
because of the amount of charging
current.
Step Method Apply test voltage
slowly in 5 to 7 increments of equal
value to the maximum specified.
Allow sufficient time at each stop for
the leakage current to stabilize.
HI-POT TESTING PROCEDURES
Normally this requires only a few
seconds unless cable circuits of
high capacitance are involved.
Record leakage current at each
Step.
Maintain the test voltage at the
prescribed value for the time
designated in applicable
specifications. The following times
are usually considered adequate: at
the end of the test period, set the
test set voltage control to zero,allow
the residual voltage on the circuit to
decay, then ground the conductor just
tested.
CAUTION
It should be recognized that dc charges on
cable can build up to potentially dangerous
levels if grounds are removed too quickly.
Maintain solid grounds after the test on the
cable for at least 4 times the duration of the
test. On exceptionally long cable lengths, it
may be necessary to increase the
grounding time. It is advantageous to
maintain these grounds longer and while
reconnecting circuit components.
Acceptance Testing After
installation and before the cable is
placed in regular service, the
specified test voltage shall be
applied for 5 minutes.
Proof Testing At any time
during the period of guarantee, the
cable circuit may be removed
from service and tested at a
reduced voltage (1.5 times rated
voltage) for 5 minutes.
Record the leakage current at
one minute intervals for the duration
of the test time involved.
Testing Problems
Extra Leakage Current:
Failure to guard against corona
Failure to clean insulation surface
Failure to keep cable ends dry
Failure to provide adequate
clearance to ground
Improper shield termination
Erratic Readings:
Fluctuating voltage to test set
Improper test leads
Environmental Influences:
High relative humidity
Dampness, dew, fog
Wind, snow
Results vs. Cable Life
To date there is no bases for
correlation between dc test
results and cable life expectancy.
Important Note :
Frequent high voltage tests on
cable installation should not be
carried out. This test should be
carried out only when essential.
72
DC High Potential (HI-POT) Testing of Cable
Overview
This procedure is intended to provide
general guidelines for high potential
dc testing of power cables.
All tests made after cable installation
and during the guarantee period shall
be made in accordance with applicable
specifications.
All safety precautions must be
observed during testing at
high voltage.
Read and understand and follow the
Operators Manual for the particular
test set being used.
Test Equipment
Direct current test equipment
is available commercially
with a wide range of voltages.
Accessory equipment necessary
to safely conduct high voltage
testssuch as safety
barriers, rubber gloves and
nonconducting hard hatsmust
be used; consult appropriate
safety officer.
Test Procedures
As guided in IS:1255, However
detailed here also.
Before performing any dc overpotential
tests:
All equipment must be
disconnected from the cable circuit,
i.e. disconnect transformers, switch
taps, motors, circuit breakers,
surge arrestors, etc. This will
preclude damage to such
equipment and will prevent test
interruptions due to flashovers
and/or trip-outs resulting from
excessive leakage current.
Establish adequate clearance
between the circuit test ends
and any grounded object, and to
other equipment not under test
(about 2.5 feet).
Ground all circuit conductors not
under test with all cable shields
including nearby equipment.
Consult termination manufacturers
for maximum test voltage
recommendations and time
limitations, which should follow
IS:1255 guidelines.
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
FIELD ELECTRICAL HI-POT
TESTING GUIDELINES
73
This test is performed to detect any defects in cable insulation and terminations which may result from poor workmanship or mechanical
damage. dc testing is not expected to reveal deterioration due to aging in service.
This proof test confirms the integrity of the insulation and accessories before the cable is put into service. Tests are recommended during
installation at the dc test voltage specified in the Table below, applied for 5 minutes before commissioning.
After the cable has been completely installed and placed in service, a dc proof test may be made at any time within the first five years at a
voltage 1.5 times rated voltage applied for five minutes. After that time, dc testing is not recommended. However, test voltage here will be
determined depending on the condition of cable, joints, terminations, etc. or if repaired somewhere, test voltage will be less but not less than
rated voltage.
DC test voltages are applied to discover gross problems such as improperly installed accessories or mechanical damage. DC testing is not
expected to reveal deterioration due to aging in service. There is some evidence that DC testing of aged cross-linked polyethylene cables can
lead to early cable failures. Information on this subject is available in EPRI project report TR-101245, Effect of DC Testing in Extruded Cross-
Linked Polyethylene Insulated Cables.
1.9/3.3
3.3/3.3
3.8/6.6
6.6/6.6
6.35/11
11/11
12.7/22
19/33
5
9
10.5
18
18
30
37.5
60
TEST VOLTAGE
KV
RATED VOLTAGE
(Uo/U) KV
Acceptance Test
Maintenance Test After Installation
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
73
Notes
CentrumPlaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, Harayana
Phone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connectingthe World
High Voltage Power Cable
73
Notes
If you've been looking for the Best-Bui l t
Medium Voltage Cable in the market, your search just
ended. General Cabl e offers ful l range of premium
General cable Brand cables engineered for superi or
per formance in the most chal l engi ng appl i cati ons.
And they're manufactured at the world class
production facility, to the exacting specifications that
made the General Cable brand name famous
worldwide. As always, specially designed
conductors, insulation and jacketed that exceed
i ndustr y standards have made General Cable
brand cables the Most rel i abl e choice for Medium
Voltage application. For over 100 years, they've been
the right cable. And now, they're right here.
You al ready Know
i t's the Best.
Now you
know where
to fi nd i t.
ConnectingtheWorld
General Cable Energy India Pvt Ltd
Corporate office: Centrum Plaza, Level 3, Tower A, 312 S,
Golf Course Road, Sector- 53, Gurgaon-122 002, Haryana, India
Phone: (0124) 4326000 Fax: (0124) 4326019
E-mail: info@generalcable.co.in
Factory:
Village Bhatouli Khurd, Baddi
Dist. - Solan, Pin - 173205
Himachal Pradesh, India