Sub : OFFER FOR SUPPLY, INSTALLATION,TESTING & COMMISSIONING OF 1500KVA
SUB STATION INCLUSIVE OF TRANSFORMER, HT, LT, & PFI FOR YOUR PROJECT.
Unit price Total price
in Taka in Taka
01) 11KV DROP-OUT FUSE: 1 SET 10,000.00 10,000.00
-Cost of complete 11KV Drop-out fuse as
per attached technical specification.
02) 11KV LIGHTNING ARRESTER: 1 SET 10,000.00 10,000.00
-Cost of complete 11KV Lightning Arrester
As per attached technical specification.
03) 11KV HT SWITCHGEAR (VCB) : 1 NO. 560,000.00 560,000.00
Cost of complete HTSwitchgear as per
attached technical specification.
04) 1500KVA OIL IMMERSED TRANSFORMER : 1 No 1,800,000.00 1,800,000.00
Cost of complete 1500KVA X-Former
as per attached technical specification.
05) LT SWITCHGEAR : 1 Set 688,517.75 688,517.75
Cost of complete LT Switchgear asper
attached technical specification.
06) 900KVAR AUTO/MANUAL PFI PLANT : 1 Set 838,462.35 838,462.35
Cost of complete 900 KVAR PFI Plant
as per attached technical specification.
Project: Regal Fashion
FINANCIAL OFFER
SL # Descriptions Qty. Unit
07) EARTHING OF SUBSTATION : 6 Sets 25,000.00 150,000.00
Cost of earthing of substation as per spec.
08) HEAT SHRINK CABLE KIT : 6 Sets 3,500.00 21,000.00
09) INSTALLATION & TESTING : 1 Job 50,000.00 50,000.00
-Cost of installation & testing of the above
without any cable & civil works.
4,127,980.10
TERMS & CONDITIONS :
01) Validity : Our offer will remain valid for a period of 30 days from the date of this offer.
02) Delivery : Within 60 days after receipt of confirmed order & payment asper clause # 3.
03) Payment : 50% Cash/PO/DD alongwith order & remaining
50% after factory inspection, before delivery.
04) Fabrication &
assembly : Fabrication & assembly will be done at our Gazipur factory.
05) Guarantee : We guarantee the goods of our supply against any defects in materials & work-
manship during manufacturing for a period of 01 year from the date of supply
subject to non - repairing/dismantling equipments without our prior permission.
06) After-sales
service : Our trained & skilled Engineers & technicians will be available within 24 hrs. notice
for any problems related with our supplied equipments. All spare parts are available
ready stock from our store located at 56,Purana Paltan,Dhaka.
Thanking you.
Yours very truly,
Adex Corporation Ltd.,
Suvash Dev Engr. Harunor Rashid
Manager Sales Operative Director
Mob: 01713 493331 Mob: 01713 164505
Total Taka :
TECHNICAL SPECIFICATION
1500KVA SUB-STATION EQUIPMENT.
01) 11KV Drop-out fuse : 1 Set.
11KV Drop -out fuse of following specifications :-
Rated voltage (nominal) : 11KV
Rated max. voltage : 15KV
Rated current (conti.) RMS : 60A
Interrupt current RMS : 10KA
Rated frequency : 50Hz
BIL : 75KV
Withstand test voltage :
Dry 1 Min. : 33KV
Wet, 10 sec : 30KV
GM Plant/Equivalent
02) Lightning Arrester : 1 Set.
11KV Lightning arrester of following specification :-
Rated voltage (Nominal) : 11KV
Rated system voltage : 12KV
Frequency : 50Hz
Minimum spark over (Rms) : 14KV
Maximum spark over (Rms) : 40KV
Max. impulse spark (crest) : 45KV
Withstand voltage
(Power frequency 1 Min. dry) : 28KV
Withstand voltage
(Power frequency 10 sec. wet) : 24KV
Nominal discharge current : 5KA
Impulse current withstand : 55KA
GM Plant/Equivalent
03) 11KV HT SWITCHGEAR ( VCB ): 1 Set.
This specification cover the supply of 11kV indoor, metal
enclosed switchgear according to IEC publication-298.

The medium voltage switchgear panel shall be used for
secondary distribution sub-station upto 12kV & suitable
for an ambient temperature of 45 C and rated rupture
capacity of 350 MVA complete with all accessories,
diagrams, levels, wirings & terminals.
The 11 kV, 350 MVA rated switchboard would comply
compulsory electricity regulations by standards. All
cubicles are fitted with security interlocks and earthing
switch.
The erection of the panel can be done directly on the
levelled floor.Cable trenches are necessary.Cables can
easily installed from the bottom side of the panel.
The design is done to allow safe operation in extremely
tropical cilmate conditions :
Technical Data :
Service voltage : 11kV
Rated voltage : 12kV
Rated current of busbars : 800A
Rated current of circuit breaker : 630A
Insulation level :
Impulse withstand voltage 1.2/50 -sec : 75kV (Peak)
Power frequency withstand voltage/1 min : 28kV (rms).
The equipment proposed under this offer has been designed,
manufactured and tested in accordance with the following
applicable IEC standards.
- common clause for high voltage switchgear standards : IEC 694
- high voltage switchgear in metallic enclosure : IEC 298
- high voltage ac circuit breakers : IEC 56
- ac switches and earthing switches : IEC 129
- high voltage switches : IEC 265
- high voltage combined switch/fuse for ac current : IEC 420
- current transformers : IEC 185
- voltage transformers : IEC 186
- high voltage fuses : IEC 282
- control monitoring : IEC 801
The switchgear panels shall comprise of :
1 Set of Manually operated 11KV, 630A earth switch.
1 630A,12KV,25KA ,rated triple pole 50Hz, Fixed type
Vaccum Circuit Breaker (VCB) with manual operated
mechanism, tripping coil & axiliary contacts.
SQ Electric, UK.
3 Cast resin insulated dry type 11KV double core current
transformer, ratio : 100/5/5A.
Core 1 : 10VA, class 0.5M5 for metering
Core 2 : 15VA, class 10P10 for protection
SADTEM, France

2 Dry type cast resin insulated potential transformer
for open delta connection.
Ratio : 11000/110V
Burden : 50VA, Class : 0.5
SADTEM, France
1 TP MCB for PT secondary protection.
Protection,Measurement and control unit :
1 Protection Unit :
- Overcurrent (ANSI code 50/51) protection.
- Earth fault (50N/51N) protection .
- 1 reset key to clear faults and to reset.
- 1 Connection port for the RS232 link with the PC.
The tripping characteristics of the protection unit shall be
of IDMT nature with a setting possibility to various IDMT
tripping curves.
SEPAM 10, Schneider Electric, France
1 Digital power meter type NRG96 with display of operational
measurement for :
# Amperes with phase selection.
# Voltages with phase selection.
# Kwh
# Kvarh
# Kw
# Kvar
# p.f
Circutor, Spain
ORIGIN : ALL ABOVE COMPONENTS ARE OFUK / EUROPEAN ORIGIN AND
ASSEMBLED IN BANGLADESH BY ADEX CORPORATION LTD.
04) 1500KVA OIL IMMERSED TRANSFORMER : 1NO.
Three phased transformers ground mounted,oil
immersed, with standard accessories. Indoor use.
Routine tests and first filling oil included.
Design, manufacturing, routine tests & tolerances
according to IEC 76 standards.
Standard fittings : 4 flat bi-directional rollers.
2 lifting lugs
2 earthing points.
1 rating plate(on HV side)
1 Bucholz Relay
1 Silica Gel with Box,
1 Temperature Meter.
HV connections : porcelain bushing
LV connections : porcelain bushing, without cable box.
Rated power in KVA : 1500 kVA
Frequency : 50Hz
System voltage : 12KV
Primary voltage : 11000V
HV tapping by links(off circuit) in : 2.5%, -5%,-7.5%
Secondary voltage : 415V
HV impulse KV peak in KV : 75 kV
Power frequency KV rms : 28 kV
Vector group : DYN11
Max. ambient temp. in Deg. C : 40
Altitude lower thank in meter : 1000
Temp. rise in winding/oil in Deg. C : 65/55
No load loss : 1690 W
Load loss at 75 Deg. C : 17000W
Impedance voltage : 6%
Brand: Adex-transfo
Origin: CRGO M4 Grade Silicon steel sheet from UGO France.
HV wires (Gazi or BRB wires limited), Bangladesh.
LV insulated copper bar , France.
Other insulated materials and fittings, Italy.
05) LT SWITCHGEAR : 1 Set.
Sheet steel fabricated, floor mounting, tropicalized design,
indoor type, low tension switchgear for 3 phase, 4 wire,
50 Hz, 380/415V AC system & shall be supplied complete
TP + N busbars suitably sized & properly insulated arrange
to withstand & short current of 50KA for 1 sec.
The boards are designed & constructed in accordance
with BS5486/IEC439.
Busbars and other live parts are spaced and insulated in
accordance with European standards IEC 158, UTE C 20 -
- 040, VDE - C 110 for 660V.
All ACB/MCCB units & panel boards shall fully comply
regulations of the 15th edition IEE wiring regulation
for isolation and switching.
The panel shall comprises of followin & powder coated :
INCOMING :

1 3200A, TP, 75KA,415V,50Hz,(ACB) fixed type with motor
operated electronics micropocess based protection unit
having adjustable overcurrent & short circuit protection
with under voltage release and 4NO+4NC auxiliary
contact and door frame
Origin: SQ Electric of UK.
3 Current transformer ratio : 3000/5A with suitable
accuracy and burden.
1 Digital power meter type NRG 96 with display of operational
measurement for :
# Amperes with phase selection.
# Voltages with phase selection.
# Kwh
# Kvarh
# Kw
# Kvar
# p.f
Circutor of Spain
3 Phase indicating lamp RED/YELLOW/BLUE.
1 6A TP MCB for control circuit protection
1 Set Control Fuse
OUTGOING:
1 2000A, TP, 50KA,415V,50Hz,(ACB) fixed type with motor
operated electronics micropocess based protection unit
having adjustable overcurrent & short circuit protection
with under voltage release and 4NO+4NC auxiliary
contact and door frame(For PFI)
Origin: SQ Electric of UK.
2 400A, TP, 36KA, 415V,50Hz, Moulded Case circuit Breaker (MCCB)
with adjustable overcurrent & Magnetic short circuit protection.
Origin : SQ Electric of UK
1 200A, TP, 36KA,415V, 50Hz, Moulded Case Circuit Breaker (MCCB)
with fixed type thermal overcurrent & Magnetic short circuit protection.
Origin : SQ Electric of UK
1 100A, TP, 25KA,415V, 50Hz, Moulded Case Circuit Breaker (MCCB)
with fixed type thermal overcurrent & Magnetic short circuit protection.
Origin : SQ Electric of UK
1 63A, TP, 25KA,415V, 50Hz, Moulded Case Circuit Breaker (MCCB)
with fixed type thermal overcurrent & Magnetic short circuit protection.
Origin : SQ Electric of UK
1 Enclosure with suitably sized TP+N copper busbar
ORIGIN : ALL ABOVE COMPONENTS ARE OFUK / EUROPEAN ORIGIN AND
ASSEMBLED IN BANGLADESH BY ADEX CORPORATION LTD.
06) 900KVAR Auto/Manual PFI plant :
The boards are designed & constructed in accordance with
BS5486/IEC439.
Busbars & other live parts are spaced & insulated in accordance
with European standards IEC158,UTE C20 - 040, VDE - C 110
for 660V.
All panel boards shall fully comply regulations of the 15th
edition IEE wiring regulation for isolation & switchgear
The panel shall comprise of the following :
6 100(50+50)KVAR,415V,50Hz ,3 phase ,dry type, self healing
compact PF capacitors bank with discharge resistor.
Roderstain of Germany
5 50KVAR,415V,50Hz ,3 phase ,dry type, self healing
compact PF capacitors bank with discharge resistor.
Roderstain of Germany
1 50KVAR,415V,50Hz ,3 phase ,dry type, self healing ( Fixed)
compact PF capacitors bank with discharge resistor.
Roderstain of Germany
6 LC1-D150M
150A,triple phase air contactor for 100Kvar capacitor.
Telemecanique of France
5 LC1-D80M
80A,triple phase air contactor for 50Kvar capacitor.
Telemecanique of France
6 200A TP MCCB instead of HRC fuse
5 100A TP MCCB instead of HRC fuse
12 ON pushbutton.
12 Stop pushbutton.
1 Auto manual selector switch with adder block.
4 Control relay with base.
12 Indicating lamp.
3 Fuse carrier with fuse for control circuit.
1 12 Steps reactive power regulator which performs the switching
of capacity bank in automatic power factor correction equipments
depending on changes of reactive power complete with p. f. I
Luminiescent indicators and digital power factor meter.
Brand : Circutor, Spain
1 LT current transformer.
1 Set TP+N busbar suitably sized.
ORIGIN : ALL ABOVE COMPONENTS ARE OF EUROPEAN ORIGIN
AND ASSEMBLED IN BANGLADESH BY ADEX CORPORATION LTD.
Ref :
13th August, 2009
The Managing Director
Khadim Ceramics Ltd.
Dholaipara, Khadimnagar,
Sylhet
SL # Descriptions Qnty Unit Unit price Total price
IN TAKA IN TAKA
1500KVA Substation
Sub Head -A (Demand note,Charges,etc)
01) Application Fee 1 JOB 250.00 250.00
02) Demand Note Charge 1200 KW 600.00 720,000.00
03) Deposit for HT Meter(At Actual) 1 No 25,000.00 25,000.00
04) Electrical Liecensing Board(At Actual) 1 JOB 5,000.00 5,000.00
05) Earthing Connection Cable(At Actual) 1 JOB 20,000.00 20,000.00
Total Taka = 770,250.00
Sub Head -B (Miscellaneos Expenditure)
01) Load Sanction Purpose (BPDB) 1 JOB 420,000.00 420,000.00
02) Electrical Liecensing Board 1 JOB 35,000.00 35,000.00
03) CT,PT,HT Meter Collection 1 JOB 15,000.00 15,000.00
04) CT,PT,HT Meter Connection 1 JOB 10,000.00 10,000.00
05) Line Shut Down Fee 1 JOB 5,000.00 5,000.00
06) DOF & LA Chennel Fittings 1 JOB 10,000.00 5,000.00
07) Energy Audit 1 JOB 10,000.00 10,000.00
08) Roadcutting 1 Meter 1,500.00
Total Taka = 500,000.00