VRV Systems Air-cooled selection procedure 1
Air-cooled selection procedure
1 Selection procedure VRVII system based on cooling load. . . . 2
Indoor unit selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Outdoor unit selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Actual performance data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Selection example based on cooling load . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Capacity correction ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
VRVII-S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
VRVIII cooling only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
VRVIII heat pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VRVII heat recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3 Integrated heating capacity coefficient . . . . . . . . . . . . . . . . . . . . . . . . . 33
4 Refnet pipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5 Example of Refnet piping layouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6 Refrigerant pipe selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
VRVIII-S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
VRVIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
VRVII heat recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Piping thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
TABLE OF CONTENTS
1 Air-cooled selection procedure
Air-cooled selection procedure
1
VRV Systems Air cooled selection procedure 2
1 Selection procedure VRVII system based on cooling load
1 - 1 Indoor unit selection
Enter indoor unit capacity tables at given indoor and outdoor temperature.
Select the unit that the capacity is the nearest to and higher than the given load.
NOTE
1 Individual indoor unit capacity is subject to change by the combination. Actual capacity has to be calculated according to the combination by using
outdoor units capacity table.
1 - 2 Outdoor unit selection
Allowable combinations are indicated in indoor unit combination total capacity index table.
In general, oudoor units can be selected as follows though the location of the unit, zoning and usage of the rooms should be considered.
The indoor and outdoor unit combination is determined that the sum of indoor unit capacity index is nearest to and smaller than the capacity index at
100 % combination ratio of each outdoor unit. Up to 16 indoor units can be connected to one outdoor unit. It is recommended to choose a larger
outdoor unit if the installation space is large enough.
If the combination ratio is higher than 100 %, the indoor unit selection will have to be reviewed by using actual capacity of each indoor unit.
Indoor unit combination total capacity index table
Indoor unit capacity index
Outdoor unit
Indoor unit combination ratio
130 % 120 % 110 % 100 % 90 % 80 % 70% 60 % 50 %
RXYSQ4PV 130 120 110 100 90 80 70 60 50
RXYSQ5PV 162.5 150 137.5 125 112.5 100 87.5 75 62.5
RXYSQ6PV 182 168 154 140 126 112 98 84 70
Outdoor unit
Indoor unit combination ratio
130 % 120 % 110 % 100 % 90 % 80 % 70% 60 % 50 %
RX(Y)Q5P 162.5 150 137.5 125 112.5 100 87.5 75 62.5
RX(Y)Q8P/REYQ8M 260 240 220 200 180 160 140 120 100
RX(Y)Q10P/REYQ10M 325 300 275 250 225 200 175 150 125
RX(Y)Q12P/REYQ12M 390 360 330 300 270 240 210 180 150
RX(Y)Q14P/REYQ14M 455 420 385 350 315 280 245 210 175
RX(Y)Q16P/REYQ16M 520 480 440 400 360 320 280 240 200
RX(Y)Q18P/REYQ18M 585 540 495 450 405 360 315 270 225
RXYQ20P/REYQ20M 650 600 550 500 450 400 350 300 250
RXYQ22P/REYQ22M 715 660 605 550 495 440 385 330 275
RXYQ24P/REYQ24M 780 720 660 600 540 480 420 360 300
RXYQ26P/REYQ26M 845 780 715 650 585 520 455 390 325
RXYQ28P/REYQ28M 910 840 770 700 630 560 490 420 350
RXYQ30P/REYQ30M 975 900 825 750 675 600 525 450 375
RXYQ32P/REYQ32M 1,040 960 880 800 720 640 560 480 400
RXYQ34P/REYQ34M 1,105 1,020 935 850 765 680 595 510 425
RXYQ36P/REYQ36M 1,170 1,080 990 900 810 720 630 540 450
RXYQ38P/REYQ38M 1,235 1,140 1,045 950 855 760 665 570 475
RXYQ40P/REYQ40M 1,300 1,200 1,100 1,000 900 800 700 600 500
RXYQ42P/REYQ42M 1,365 1,260 1,155 1,050 945 840 735 630 525
RXYQ44P/REYQ44M 1,430 1,320 1,210 1,100 990 880 770 660 550
RXYQ46P/REYQ46M 1,495 1,380 1,265 1,150 1,035 920 805 690 575
RXYQ48P/REYQ48M 1,560 1,440 1,320 1,200 1,080 960 840 720 600
RXYQ50P 1,625 1,500 1,375 1,250 1,125 1,000 875 750 625
RXYQ52P 1,690 1,560 1,430 1,300 1,170 1,040 910 780 650
RXYQ54P 1,755 1,620 1,485 1,350 1,215 1,080 945 810 675
Model 20 25 32 40 50 63 71 80 100 125 200 250
Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 200 250
1
VRV Systems Air cooled selection procedure 3
Air-cooled selection procedure
1 Selection procedure VRVII system based on cooling load
1 - 3 Actual performance data
Use outdoor unit capacity tables
Determine the correct table according to the outdoor unit model and combination ratio.
Enter the table at given indoor and outdoor temperature and find the outdoor capacity and power input. The individual indoor unit capacity (power
input) can be calculated as follows:
ICA =
OCA x INX
TNX
ICA: Individual indoor unit capacity (power input)
OCA: Outdoor unit capacity (power input)
INX: Individual indoor unit capacity index
TNX: Total capacity index
Then, correct the indoor unit capacity according to the piping length.
If the corrected capacity is smaller than the load, the size of indoor unit has to be increased. Repeat the same selection procedure.
1 - 4 Selection example based on cooling load
1 Given
Design condition
Cooling: indoor 20CWB, outdoor 33CDB
Cooling load
Power supply: 3-phase 380V/50Hz
2 Indoor unit selection
Enter indoor unit capacity table at:
20CWB indoor temperature
33CDB outdoor air temperature.
Selection results are as follows:
3 Outdoor unit selection
Assume that the indoor and outdoor unit combination is as follows.
Outdoor unit: RXYQ10M
Indoor unit: FXCQ25M7 x 3, FXCQ40M7 x 5
Indoor unit combination total capacity index
25 x 3 + 40 x 5 = 275 (110 %)
Room A B C D E F G H
Load (kW) 2.9 2.7 2.5 4.3 4.0 4.0 3.9 4.2
Room A B C D E F G H
Load (kW) 2.9 2.7 2.5 4.3 4.0 4.0 3.9 4.2
Unit size 25 25 25 40 40 40 40 40
Capacity 3.0 3.0 3.0 4.8 4.8 4.8 4.8 4.8
Air-cooled selection procedure
1
VRV Systems Air cooled selection procedure 4
1 Selection procedure VRVII system based on cooling load
1 - 4 Selection example based on cooling load
4 Actual performance data (50Hz)
Outdoor unit cooling capacity: 30.5kW (RXYQ10M, 110 %)
Individual capacity
Capacity of FXCQ25M = 30.5 x
25
= 2.77kW
275
Capacity of FXCQ40M = 30.5 x
40
= 4.44kW
275
Actual combination capacity
The unit size for room A has to be increased from 25 to 32 because the capacity is less than the load. For new combination, actual capacity is calculated
as follows.
Indoor unit combination total capacity index
(25 x 2) +31.25 + (40 x5) = 281.25 (112.5 %)
Outdoor unit cooling capacity:
27,610 kcal/h (direct interpolation between 110 % and 120 % in the table)
Individual capacity
Capacity of FXCQ25M = 30.0 x
25
= 2.7kW
281.25
Capacity of FXCQ32M = 30.0 x
32
= 3.4kW
281.25
Capacity of FXCQ40M = 30.0 x
40
= 4.3kW
281.25
Actual capacity of new combination
Then, the capacities have to be corrected for actual piping length according to the location of indoor and outdoor units and the distance between them.
Room A B C D E F G H
Load (kW) 2.9 2.7 2.5 4.3 4.0 4.0 3.9 4.2
Unit size 25 25 25 40 40 40 40 40
Capacity 2.77 2.77 2.77 4.44 4.44 4.44 4.44 4.44
Room A B C D E F G H
Load (kW) 2.9 2.7 2.5 4.3 4.0 4.0 3.9 4.2
Unit size 32 25 25 40 40 40 40 40
Capacity 3.4 2.7 2.7 4.3 4.3 4.3 4.3 4.3
2
VRV Systems Air cooled selection procedure 5
Air-cooled selection procedure
2 Capacity correction ratio
2 - 1 VRVIII-S
RXYSQ4,5PV
Rate of change in cooling capacity Rate of change in heating capacity
3D045710B
NOTES
1 These figures illustrate the rate of change of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard
conditions.
Moreover, under partial load conditions, there is only a minor deviation from the rate of change in capacity, shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3 Method of calculating cooling/heating capacity (max. capacity for combination with standard indoor unit)
Cooling/heating capacity = cooling/heating capacity obtained from performance characteristics table x each capacity rate of change
In the case length of piping differs depending on the indoor unit, maximum capacity of eacht unit during simultaneous operation is:
Cooling/heating capacity = cooling/heating capacity obtained from performance characteristics table x each capacity rate of change
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased..
[Diameter of above case]
5 When the main section of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when Hp=0m is thus approximately 0.78
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units where indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units where indoor unit in superior position
L : Equivalent pipe length (m)
: Capacity correction factor
50
40
40
30
30
30 40 50 60 70 80 90 100 110
20
20
20
10
10
10 0
0
.7
5
0
.7
7
0
.8
0
0
.8
5
0
.9
0
0
.9
5
1
.0
0
.7
5
0
.7
7
0
.8
0
0
.8
5
0
.9
0
0
.9
5
1
.0
H
P
(m)
(m)
L (m)

H
M
0
0
50
40
40
30
30
30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180
20
20
20
10
10
10 0
1
.0
1
.0
H
P
(m)
(m)
L (m)

H
M
0
0
Model gas pipe liquid pipe
RXYSQ4,5P7V3B 19.1 Not increased
Model gas pipe liquid pipe
RXYSQ4,5P7V3B 15.9 9.5
Equivalent lenght Equivalent lenght
Indoor unit
Outdoor unit
Branch
80 m 40 m
Size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 6
2 Capacity correction ratio
2 - 1 VRVIII-S
RXYSQ6PV
Rate of change in cooling capacity Rate of change in heating capacity
3D045961B
NOTES
1 These figures illustrate the rate of change of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard
conditions.
Moreover, under partial load conditions, there is only a minor deviation from the rate of change in capacity, shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.
3 Method of calculating cooling/heating capacity (max. capacity for combination with standard indoor unit)
Cooling/heating capacity = cooling/heating capacity obtained from performance characteristics table x each capacity rate of change
In the case length of piping differs depending on the indoor unit, maximum capacity of eacht unit during simultaneous operation is:
Cooling/heating capacity = cooling/heating capacity obtained from performance characteristics table x each capacity rate of change
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased..
[Diameter of above case]
5 When the main section of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when Hp=0m is thus approximately 0.86
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units where indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units where indoor unit in superior position
L : Equivalent pipe length (m)
: Capacity correction factor
50
40
40
30
30
30 40 50 60 70 80 90 100 110
20
20
20
10
10
10 0
0
.8
2
0
.8
5
0
.8
7
0
.8
7
0
.9
0
0
.9
2
0
.9
2
0
.9
5
0
.9
7
0
.9
7
1
.0
0
.8
2
0
.8
5
0
.9
0
0
.9
5
1
.0
H
P
(m)
(m)
L (m)

H
M
0
0
50
40
40
30
30
30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180
20
20
20
10
10
10 0
1
.0
1
.0
H
P
(m)
(m)
L (m)

H
M
0
0
Model gas pipe liquid pipe
RXYSQ6P7V3B 22.2 Not increased
Model gas pipe liquid pipe
RXYSQ6P7V3B 19.1 9.5
Equivalent lenght Equivalent lenght
Indoor unit
Outdoor unit
Branch
80 m 40 m
Size increase
2
VRV Systems Air cooled selection procedure 7
Air-cooled selection procedure
2 Capacity correction ratio
2 - 2 VRVIII cooling only
RXQ5P
Correction ratio for cooling capacity
3TW27302-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.78
50
60
40
-40
-50
30
30 40 50 60 70 80 90 100 110
-30
20
20
-20
10
10 0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.94
0.92
0.92
0.90
0.88
0.86
0.84 0.82 0.80 0.78 0.76 0.74
0.84 0.86 0.88 0.90 0.82 0.80 0.78 0.76
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length
Model gas pipe liquid pipe
RXQ5P 19.1 9.5
Model gas pipe liquid pipe
RXQ5P 15.9 9.5
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 8
2 Capacity correction ratio
2 - 2 VRVIII cooling only
RXQ8P
Correction ratio for cooling capacity
3TW27302-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.86
50
60
40
-40
-50
30
40 30 50 70 60 80 100 110 90
-30
20
20 10
-20
10
0
1.00
0.75
1.00
0.98
0.98
0.96
0.96
0.94
0.94
0.92
0.92
0.90 0.88 0.86 0.84 0.82
0.84 0.86 0.88 0.90
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXQ8P 22.2 12.7
Model gas pipe liquid pipe
RXQ8P 19.1 9.5
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
2
VRV Systems Air cooled selection procedure 9
Air-cooled selection procedure
2 Capacity correction ratio
2 - 2 VRVIII cooling only
RXQ10P
Correction ratio for cooling capacity
3TW27302-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6).
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.87
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.94
0.92
0.92
0.90 0.88 0.86 0.84
0.84 0.82
0.82
0.80
0.80
0.78
0.78
0.86 0.88 0.90
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXQ10P 25.4* 12.7
Model gas pipe liquid pipe
RXQ10P 22.2 9.5
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 10
2 Capacity correction ratio
2 - 2 VRVIII cooling only
RXQ12,14P
Correction ratio for cooling capacity
3TW27302-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.89
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.94
0.92
0.92
0.90 0.88 0.86 0.84
0.84 0.86 0.88 0.90
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXQ12-14P 28.6 15.9
Model gas pipe liquid pipe
RXQ12-14P 28.6 12.7
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
2
VRV Systems Air cooled selection procedure 11
Air-cooled selection procedure
2 Capacity correction ratio
2 - 2 VRVIII cooling only
RXQ16P
Correction ratio for cooling capacity
3TW27302-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.88
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.94
0.92
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.78
0.84 0.86 0.88 0.90 0.82 0.80 0.78
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length
Model gas pipe liquid pipe
RXQ5P 31.8* 15.9
Model gas pipe liquid pipe
RXQ5P 28.6 12.7
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 12
2 Capacity correction ratio
2 - 2 VRVIII cooling only
RXQ18P
Correction ratio for cooling capacity
3TW27302-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6).
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.83
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.94
0.92
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.78
0.84 0.86 0.88 0.90 0.82 0.80 0.78
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length
Model gas pipe liquid pipe
RXQ18P 31.8* 19.1
Model gas pipe liquid pipe
RXQ18P 28.6 15.9
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
2
VRV Systems Air cooled selection procedure 13
Air-cooled selection procedure
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ5P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 120m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.78
heating capacity when height difference = 0 is thus approximately 1.0
50
60
40
-40
-50
30
30 40 50 60 70 80 90 100 110
-30
20
20
-20
10
10 0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.94
0.92
0.92
0.90
0.88
0.86
0.84 0.82 0.80 0.78 0.76 0.74
0.84 0.86 0.88 0.90 0.82 0.80 0.78 0.76
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110 130 150 170 190
-30
20
-20
10
10
1.00
1.00
-10
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ5P 19.1 9.5
Model gas pipe liquid pipe
RXYQ5P 15.9 9.5
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 14
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ8P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.86
heating capacity when height difference = 0 is thus approximately 1.0
50
60
40
-40
-50
30
30 40 50 60 70 80 90 100 110
-30
20
20
-20
10
10 0
1.00
1.00
0.70
0.98
0.98
0.96
0.96
0.94
0.94
0.92
0.92
0.90 0.88 0.86 0.84 0.82
0.84 0.86 0.88 0.90
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ8P 22.2 12.7
Model gas pipe liquid pipe
RXYQ8P 19.1 9.5
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
2
VRV Systems Air cooled selection procedure 15
Air-cooled selection procedure
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ10P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6).
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.87
heating capacity when height difference = 0 is thus approximately 0.90
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.94 0.92 0.84 0.82 0.80 0.78 0.86 0.88 0.90
0.92
0.84 0.82 0.80 0.78 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
0.80 0.82 0.84 0.86 0.88 0.90 0.92 0.94 0.96 0.98
0.80 0.82 0.84 0.86 0.88 0.90 0.92 0.94 0.96 0.98
-30
20
-20
10
10 0 20 40 60 80 100
1.00
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ10P 25.4* 12.7
Model gas pipe liquid pipe
RXYQ10P 22.2 9.5
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 16
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ12,14,24,36P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.89
heating capacity when height difference = 0 is thus approximately 1.0
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94 0.92 0.90 0.88 0.86 0.84
0.94 0.92 0.84 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ12-14P 28.6 15.9
RXYQ24P 34.9 19.1
RXYQ36P 41.3 22.2
Model gas pipe liquid pipe
RXYQ12-14P 28.6 12.7
RXYQ24P 34.9 15.9
RXYQ36P 41.3 19.1
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
2
VRV Systems Air cooled selection procedure 17
Air-cooled selection procedure
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ16P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6).
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.88
heating capacity when height difference = 0 is thus approximately 0.99
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.79
0.94 0.92 0.84 0.82 0.80 0.79 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
0.93 0.95 0.97 0.99
0.93 0.95 0.97 0.99
-30
20
-20
10
10 0 20 40 60 80 100
1.00
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ16P 31.8* 15.9
Model gas pipe liquid pipe
RXYQ16P 28.6 12.7
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 18
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ18,26,30,38,44P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6).
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 1.0
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.79
0.94 0.92 0.84 0.82 0.80 0.79 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ18P 31.8* 19.1
RXYQ26-30P 38.1* 22.2
RXYQ38-44P 41.3 22.2
Model gas pipe liquid pipe
RXYQ18P 28.6 15.9
RXYQ26-30P 34.9 19.1
RXYQ38-44P 41.3 19.1
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
2
VRV Systems Air cooled selection procedure 19
Air-cooled selection procedure
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ20,32,34P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6).
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.88
heating capacity when height difference = 0 is thus approximately 1.0
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.78
0.94 0.92 0.84 0.82 0.80 0.78 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ20P 31.8* 19.1
RXYQ32-34P 38.1* 22.2
Model gas pipe liquid pipe
RXYQ20P 28.6 15.9
RXYQ32-34P 34.9 19.1
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 20
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ22P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
* If not available on site, do not increase. If not increased, no correction factor should be applied to the equivalent length (see note 6).
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.88
heating capacity when height difference = 0 is thus approximately 1.0
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
0.70
1.00
0.98
0.98
0.96
0.96
0.94
0.92 0.90 0.88 0.86 0.84 0.82 0.80 0.78
0.94 0.92 0.84 0.82 0.80 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ22P 31.8* 19.1
Model gas pipe liquid pipe
RXYQ22P 28.6 15.9
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
2
VRV Systems Air cooled selection procedure 21
Air-cooled selection procedure
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ46P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 1.0
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.78
0.78 0.94 0.92 0.84 0.82 0.80 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
0.99 0.97 0.95
0.97 0.95 0.99
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ46P 41.3 22.2
Model gas pipe liquid pipe
RXYQ46P 41.3 19.1
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 22
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ48P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.97
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.78
0.78 0.94 0.92 0.84 0.82 0.80 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
0.99 0.97 0.95 0.93 0.91 0.89
0.99 0.97 0.95 0.93 0.91 0.89
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ48P 41.3 22.2
Model gas pipe liquid pipe
RXYQ48P 41.3 19.1
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
2
VRV Systems Air cooled selection procedure 23
Air-cooled selection procedure
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ50P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.92
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.70
0.98
0.98
0.96
0.96
0.94
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.78
0.78 0.94 0.92 0.84 0.82 0.80 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
0.99 0.97 0.95 0.93 0.91 0.89 0.87 0.85
0.99 0.97 0.95 0.93 0.91 0.89 0.87 0.85
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ50P 41.3 22.2
Model gas pipe liquid pipe
RXYQ50P 41.3 19.1
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 24
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ52P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.88
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.70
0.98
0.98
0.96
0.96
0.94
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.78
0.78 0.94 0.92 0.84 0.82 0.80 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
0.99
0.98
0.00 0.00 0.00 0.00 0.00 0.04 0.04 0.02 0.02
0.99 0.980.00 0.00 0.00 0.00 0.00 0.04 0.04 0.02 0.02
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ52P 41.3 22.2
Model gas pipe liquid pipe
RXYQ52P 41.3 19.1
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
2
VRV Systems Air cooled selection procedure 25
Air-cooled selection procedure
2 Capacity correction ratio
2 - 3 VRVIII heat pump
RXYQ54P
Correction ratio for cooling capacity Correction ratio for heating capacity
3TW27232-6
NOTES
1 These figures illustrate the correction ratio for piping length in capacity for a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation from the capacity correction ratio, shown in the above figures.
2 With this outdoor unit, constant evaporating pressure control when cooling and constant condensing pressure control when heating is carried out.
3 Method of calculating the capacity of the outdoor units:
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned
below, whichever is smaller.
Condition: Indoor connection ratio does not exceed 100%
Maximum capacity of outdoor units = capacity of outdoor units from capacity table at 100% connection ratio
x correction ratio of piping to farest indoor
Condition: Indoor connection ratio exceeds 100%
Maximum capacity of outdoor units = capacity of outdoor from capacity table at installed connection ratio
x correction ratio of piping to farest indoor
4 When the overall equivalent pipe length is 90m or more, main gas and liquid pipe diameters must be increased..
For new diameters see below.
5 When the pipe length after the first refrigerant branch kit is more than 40m, pipe size between first and final branch kit must be increased (refer also
to installation manual).
Diameter of main pipes (standard size)
6 Equivalent length used in the above figures is based upon the following equivalent length.
Equivalent piping length = Equivalent length of main pipe x Correction factor +
Equivalent length of branch pipes x Correction factor
Choose a correction factor from the following table.
When cooling capacity is calculated: gas pipe size
When heating capacity is calculated: liquid pipe size.
7 Example
In the above case
(Cooling) Overall equivalent length = 80m x 1.0 + 40m x 1.0 = 120m
(Heating) Overall equivalent length = 80m x 0.5 + 40m x 1.0 = 80m
The rate of change in:
cooling capacity when height difference = 0 is thus approximately 0.83
heating capacity when height difference = 0 is thus approximately 0.83
50
60
40
-40
-50
30
40 60 80 100 120 140 160 180
-30
20
20
-20
10
0
1.00
1.00
0.98
0.98
0.96
0.96
0.94
0.92
0.90 0.88 0.86 0.84 0.82 0.80 0.78
0.78 0.94 0.92 0.84 0.82 0.80 0.86 0.88 0.90
-10
0
H
e
ig
h
t

d
iffe
re
n
c
e

b
e
t
w
e
e
n

o
u
t
d
o
o
r
a
n
d

fa
re
s
t

in
d
o
o
r
(m
)
Equivalent piping length
50
60
40
-40
-50
30
30 50 70 90 110
-30
20
-20
10
10 0 20 40 60 80 100
1.00
0.99
0.97
0.95
0.93 0.91 0.89 0.89 0.85 0.83 0.81 0.79 0.77 0.75
0.95 0.93 0.91 0.89 0.89 0.85 0.83 0.81 0.79 0.77 0.75
0.99
0.97
1.00
-10
0
H
e
ig
h
t
d
iffe
re
n
c
e

b
e
tw
e
e
n

o
u
td
o
o
r
a
n
d

fa
re
s
t
in
d
o
o
r
(m
)
Equivalent piping length (m)
Model gas pipe liquid pipe
RXYQ54P 41.3 22.2
Model gas pipe liquid pipe
RXYQ54P 41.3 19.1
Correction factor
Standard size Size increase
Cooling (gas pipe) 1.0 0.5
Heating (liquid pipe) 1.0 0.5
80 m 40 m
Main gas pipe size increase
Main liquid pipe size increase
Branch gas pipe size increase
Branch liquid pipe size increase
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 26
2 Capacity correction ratio
2 - 4 VRVII heat recovery
REYQ8,22M
Rate of change in cooling capacity Rate of change in heating capacity
3D042141
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is
carried out.
3 Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit)
cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table x each capacity rate of change
When piping length differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is:
cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas pipes (outdoor unit-branch sections) must be increased.
5 When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows.
(Heating only)
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Heating)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 1.0
6 In the combination which does not include cooling only indoor unit, calculate the equivalent length pipe by the following when you calculate
cooling capacity.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.86
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units with indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units with indoor unit in superior position
L : Equivalent pipe length (m)
: Capacity correction factor
Model Liquid
REYQ8M 12.7
REYQ22M 19.1
Model liquid
REYQ8M 9.5
REYQ22M 15.9
80 m 40 m
Outdoor unit
Indoor unit
Equivalent length Equivalent length
Size increase
Branch
80 m 40 m
Equivalent length Equivalent length
Outdoor unit
Indoor unit
Size increase
Branch
BS unit
2
VRV Systems Air cooled selection procedure 27
Air-cooled selection procedure
2 Capacity correction ratio
2 - 4 VRVII heat recovery
REYQ10M
Rate of change in cooling capacity Rate of change in heating capacity
3D042142
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is
carried out.
3 Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit)
cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table x each capacity rate of change
When piping length differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is:
cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit-branch sections) must be
increased.
5 When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows.
(Heating only)
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Heating)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.91
6 In the combination which does not include cooling only indoor unit, calculate the equivalent length pipe by the following when you calculate
cooling capacity.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.88
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units with indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units with indoor unit in superior position
L : Equivalent pipe length (m)
: Capacity correction factor
Model liquid
REYQ10M 12.7
Model liquid
REYQ10M 9.5
80 m 40 m
Outdoor unit
Indoor unit
Equivalent length Equivalent length
Size increase
Branch
80 m 40 m
Equivalent length Equivalent length
Outdoor unit
Indoor unit
Size increase
Branch
BS unit
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 28
2 Capacity correction ratio
2 - 4 VRVII heat recovery
REYQ12,14,24,36M
Rate of change in cooling capacity Rate of change in heating capacity
3D042143
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is
carried out.
3 Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit)
cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table x each capacity rate of change
When piping length differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is:
cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit-branch sections) must be
increased.
5 When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows.
(Heating only)
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Heating)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 1.0
6 In the combination which does not include cooling only indoor unit, calculate the equivalent length pipe by the following when you calculate cooling
capacity.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.92
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units with indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units with indoor unit in superior position
L : Equivalent pipe length (m)
: Capacity correction factor
Model liquid
REYQ12,14M 15.9
REYQ24M 19.1
REYQ36M 22.2
Model liquid
REYQ12,14M 12.7
REYQ24M 15.9
REYQ36M 19.1
80 m 40 m
Outdoor unit
Indoor unit
Equivalent length Equivalent length
Size increase
Branch
80 m 40 m
Equivalent length Equivalent length
Outdoor unit
Indoor unit
Size increase
Branch
BS unit
2
VRV Systems Air cooled selection procedure 29
Air-cooled selection procedure
2 Capacity correction ratio
2 - 4 VRVII heat recovery
REYQ16M
Rate of change in cooling capacity Rate of change in heating capacity
3D042144
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is
carried out.
3 Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit)
cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table x each capacity rate of change
When piping length differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is:
cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length
4 When overall equivalent pipe length is 90m or more, the diameter of the main liquid pipes (outdoor unit-branch sections) must be increased.
5 When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows.
(Heating only)
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Heating)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 1.0
6 In the combination which does not include cooling only indoor unit, calculate the equivalent length pipe by the following when you calculate
cooling capacity.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.88
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units with indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units with indoor unit in superior position
L : Equivalent pipe length (m)
: Capacity correction factor
Model liquid
REYQ16M 15.9
Model liquid
REYQ16M 12.7
80 m 40 m
Outdoor unit
Indoor unit
Equivalent length Equivalent length
Size increase
Branch
80 m 40 m
Equivalent length Equivalent length
Outdoor unit
Indoor unit
Size increase
Branch
BS unit
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 30
2 Capacity correction ratio
2 - 4 VRVII heat recovery
REYQ18,26,28,30,38,40,42,44M
Rate of change in cooling capacity Rate of change in heating capacity
3D042145
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is
carried out.
3 Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit)
cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table x each capacity rate of change
When piping length differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is:
cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit-branch sections) must be
increased.
5 When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows.
(Heating only)
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Heating)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 1.0
6 In the combination which does not include cooling only indoor unit, calculate the equivalent length pipe by the following when you calculate
cooling capacity.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.88
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units with indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units with indoor unit in superior position
L : Equivalent pipe length (m)
: Capacity correction factor
Model liquid
REYQ18M 19.1
REYQ26,28,30,38,40,42,44M 22.2
Model liquid
REYQ18M 15.9
REYQ26,28,30,38,40,42,44M 19.1
80 m 40 m
Outdoor unit
Indoor unit
Equivalent length Equivalent length
Size increase
Branch
80 m 40 m
Equivalent length Equivalent length
Outdoor unit
Indoor unit
Size increase
Branch
BS unit
2
VRV Systems Air cooled selection procedure 31
Air-cooled selection procedure
2 Capacity correction ratio
2 - 4 VRVII heat recovery
REYQ20,32,34,46M
Rate of change in cooling capacity Rate of change in heating capacity
3D042146
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is
carried out.
3 Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit)
cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table x each capacity rate of change
When piping length differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is:
cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit-branch sections) must be
increased .
5 When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows.
(Heating only)
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Heating)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 1.0
6 In the combination which does not include cooling only indoor unit, calculate the equivalent length pipe by the following when you calculate
cooling capacity.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.87
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units with indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units with indoor unit in superior position
L : Equivalent pipe length (m)
: Capacity correction factor
Model liquid
REYQ20M 19.1
REYQ32,34,46M 22.2
Model liquid
REYQ20M 15.9
REYQ32,34,46M 19.1
80 m 40 m
Outdoor unit
Indoor unit
Equivalent length Equivalent length
Size increase
Branch
80 m 40 m
Equivalent length Equivalent length
Outdoor unit
Indoor unit
Size increase
Branch
BS unit
Air-cooled selection procedure
2
VRV Systems Air cooled selection procedure 32
2 Capacity correction ratio
2 - 4 VRVII heat recovery
REYQ48M
Rate of change in cooling capacity Rate of change in heating capacity
3D042147
NOTES
1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to
maximum) under standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.
2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is
carried out.
3 Method of calculating cooling / heating capacity (max. capacity for combination with standard indoor unit)
cooling / heating capacity = cooling / heating capacity obtained from performance characteristics table x each capacity rate of change
When piping length differs depending on the indoor unit, maximum capacity of each unit during simultaneous operation is:
cooling / heating capacity = cooling / heating capacity of each unit x capacity rate of change for each piping length
4 When overall equivalent pipe length is 90m or more, the diameter of the main gas and liquid pipes (outdoor unit-branch sections) must be
increased except for the gas pipe of REYQ46M7W1B.
5 When the main sections of the interunit gas pipe diameters are increased the overall equivalent length should be calculated as follows.
(Heating only)
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Heating)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.97
6 In the combination which does not include cooling only indoor unit, calculate the equivalent length pipe by the following when you calculate
cooling capacity.
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example
In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when H
p
= 0m is thus approximately 0.87
EXPLANATION OF SYMBOLS
H
p
: Level difference (m) between indoor and outdoor units with indoor unit in inferior position
H
M
: Level difference (m) between indoor and outdoor units with indoor unit in superior position
L : Equivalent pipe length (m)
: Capacity correction factor
Model liquid
REYQ48M 22.2
Model liquid
REYQ48M 19.1
80 m 40 m
Outdoor unit
Indoor unit
Equivalent length Equivalent length
Size increase
Branch
80 m 40 m
Equivalent length Equivalent length
Outdoor unit
Indoor unit
Size increase
Branch
BS unit
3
VRV Systems Air cooled selection procedure 33
Air-cooled selection procedure
3 Integrated heating capacity coefficient
2 The tables do not take account of the reduction in capacity when frost has accumulated or while the defrosting operation is in progress.
The capacity values which take these factors into account, in other words the integrated heating capacity values, can be calculated as follows:
Formula: Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation (kW) = C
A = B x C
3 Correction factor for finding integrated heating capacity
3 Please note that when there is an accumulation of snow against the outside surface of the outdoor unit heat exchanger, there will always be a
temporary reduction in capacity although this will, of course, vary in degree in accordance with a number of other factors such as the outdoor
temperature (CDB), relative humidity (RH) and the amount of frosting which occurs.
Inlet port temperature of heat exchanger (C/RH
85%)
-7 -5 -3 0 3 5 7
Integrating correction factor for frost
accumulation
0.96 0.93 0.87 0.81 0.83 0.89 1.0
Defrosting operation
H
e
a
t
in
g

c
a
p
a
c
it
y
1 cycle
Time
Defrosting operation
NOTE
The figure shows that the integrated
heating capacity expresses the
integrated heating capacity for a single
cycle (from defrost operation to defrost
operation) in terms of time.
Air-cooled selection procedure
4
VRV Systems Air cooled selection procedure 34
4 Refnet pipe systems
4TW25799-4A
Liquid side junction
K
H
R
P
2
2
M
6
4
T
8
K
H
R
P
2
2
M
7
5
T
8
K
H
R
Q
2
2
M
2
0
T
A
8
K
H
R
Q
2
2
M
2
9
T
9
K
H
R
Q
2
2
M
6
4
T
8
K
H
R
Q
2
2
M
7
5
T
8
K
H
R
P
2
3
M
3
3
T
8
K
H
R
P
2
3
M
6
4
T
8
K
H
R
P
2
3
M
7
5
T
8
K
H
R
Q
2
3
M
2
0
T
8
K
H
R
Q
2
3
M
2
9
T
8
K
H
R
Q
2
3
M
6
4
T
8
K
H
R
Q
2
3
M
7
5
T
8
Closed pipes
Discharge gas side junction Suction gas side junction
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
451.5
465.4
421.5
381
381
386.8
465.4
421.5
386.8
451.5
465.4
421.5
381
381
386.8
465.4
421.5
60
80
9
0
9
0
9
0
9
0
9
0
9
0
9
0
9
0
9
0
9
0
9
0
9
0
9
0
ID 19.10
ID 19.10
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 6.35
ID 9.52
ID 19.10
ID 19.10
ID 19.10
ID 19.10
ID 19.10
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 9.52
ID 19.10
ID 22.20 ID 19.10
ID 19.10
ID 22.20
ID 9.52
ID 9.52
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 6.35
ID 6.35
ID 6.35
ID 6.35
ID 6.35
ID 19.10
ID 19.10
ID 22.20 ID 19.10
ID 9.52
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 6.35
ID 6.35
ID 6.35
ID 6.35
ID 6.35
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
OD 6.35
OD 15.90
ID 12.70
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 19.10
ID 19.10
ID 19.10 ID 22.20
ID 15.90
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
60
80
OD 9.52
OD 19.10
80
OD 12.70
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
ID 15.90
465.4
526.5
526.5
421.5
9
0
9
0
9
0
ID 19.10
ID 19.10
ID 19.10
ID 19.10
ID 19.10
ID 19.10
ID 22.20
ID 12.70
ID 12.70
ID 25.40
ID 25.40
ID 25.40
ID 25.40
ID 28.60
ID 28.60
ID 31.80
ID 31.80
ID 19.10
ID 12.70
ID 12.70
386.8
9
0
ID 9.52
ID 9.52
ID 6.35
ID 12.70
ID 15.90
ID 15.90
ID 12.70
ID 12.70
ID 15.90
ID 15.90
ID 15.90
ID 15.90
451.5
461.5
9
0
9
0
ID 19.10
ID 25.40 ID 22.20
ID 15.90
ID 19.10
ID 19.10
ID 19.10
ID 9.52
ID 9.52
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 12.70
ID 15.90
ID 15.90
526.5
9
0
ID 19.10
ID 19.10
ID 12.70
ID 25.40
ID 25.40
ID 28.60
ID 31.80
ID 15.90
ID 38.10
ID 31.80
ID 38.10
ID 38.10
ID 44.50
ID 19.10
547.4
699.5
9
0
9
0
ID 25.40
ID 25.40
ID 25.40
ID 25.40
ID 28.60
ID 31.80
ID 31.80
ID 31.80
ID 15.90
ID 25.40
ID 15.90
ID 9.52
ID 15.90
ID 15.90
ID 15.90
465.4
461.5
421.5
9
0
9
0
ID 19.10
ID 19.10
ID 22.20
ID 22.20
ID 19.10
ID 19.10
ID 12.70
ID 12.70
ID 12.70
ID 15.90
ID 15.90
526.5
9
0
ID 19.10
ID 19.10
ID 12.70
ID 25.40
ID 25.40
ID 28.60
ID 31.80
ID 15.90
ID 15.90
526.5
9
0
ID 19.10
ID 19.10
ID 12.70
ID 25.40
ID 25.40
ID 28.60
ID 31.80
ID 15.90
ID 15.90
526.5
9
0
ID 19.10
ID 19.10
ID 12.70
ID 25.40
ID 25.40
ID 28.60 ID 31.80
ID 15.90
ID 38.10
ID 31.80
ID 19.10
547.4
9
0
ID 25.40
ID 25.40
ID 28.60
ID 31.80
ID 15.90
ID 44.50
ID 38.10
ID 38.10
ID 38.10
ID 31.80
ID 31.80
ID 19.10
547.4
699.5
9
0
9
0
ID 25.40
ID 25.40
ID 25.40
ID 25.40
ID 28.60
ID 31.80
ID 31.80
ID 15.90
ID 38.10
ID 31.80
ID 19.10
547.4
9
0
ID 25.40
ID 25.40
ID 28.60
ID 31.80
ID 25.40
ID 9.52
ID 15.90
ID 15.90
461.5
9
0 ID 19.10
ID 22.20
ID 19.10
ID 12.70
ID 12.70
ID 15.90
ID 15.90
ID 15.90
465.4
421.5
9
0
ID 19.10
ID 22.20 ID 19.10
ID 12.70
4
VRV Systems Air cooled selection procedure 35
Air-cooled selection procedure
4 Refnet pipe systems
4TW25799-4A
Liquid side header
K
H
R
Q
2
2
M
2
9
H
8
K
H
R
Q
2
2
M
6
4
H
8
K
H
R
Q
2
2
M
7
5
H
8
K
H
R
Q
2
3
M
2
9
H
8
K
H
R
Q
2
3
M
6
4
H
8
K
H
R
Q
2
3
M
7
5
H
8
K
H
R
Q
2
5
0
H
8
K
H
R
P
1
2
7
H
B
8
K
H
R
Q
1
2
7
H
8
R
e
d
u
c
e
r
s

-

E
x
p
a
n
d
e
r
s
Discharge gas side header Suction gas side header
ID 15.90
ID 15.90
ID 6.35 (6x)
ID 9.52 (6x) ID 6.35 (2x)
79 40
500
7 x 60 = 420
76
9
3
6
0
ID 15.90
ID 19.10 ID 19.10
ID 15.90
ID 6.35 (6x)
ID 9.52 (6x)
ID 9.52 (8x)
ID 6.35 (2x)
79 40
500
520
7 x 60 = 420
7 x 60 = 420
76
76
9
3
6
0
ID 15.90
ID 15.90
ID 6.35 (6x)
ID 9.52 (6x) ID 6.35 (2x)
79 40
50
500
7 x 60 = 420
76
9
3
6
0
ID 15.90
ID 15.90
ID 6.35 (6x)
ID 9.52 (6x) ID 6.35 (2x)
79 40
50
500
7 x 60 = 420
76
9
3
6
0
6
0
ID 19.10
ID 9.52
ID 12.70
ID 15.90
ID 19.10
ID 9.52 (8x)
ID 9.52 (3x)
ID 6.32 (3x)
520
279
339
399
7 x 60 = 420
76
6
0
1
3
7
ID 9.52
ID 12.70
ID 15.90
ID 9.52 (3x)
ID 6.32 (3x)
279
339
399
1
3
7
ID 9.52
ID 12.70
ID 12.70 ID 9.52 OD 15.90
ID 15.90
ID 9.52 (3x)
ID 6.32 (3x)
279
130
ID 28.60
ID 6.35
OD 25.40
OD 9.52
100
50
ID 12.70
OD 15.90
80
ID 19.10 OD 15.90
80
ID 12.70 OD 9.52
60
ID 9.52 OD 6.35
60
339
399
1
3
7
ID 12.70
OD 9.52
60
ID 28.60
OD 22.20
100
ID 41.28 ID 34.95
OD 31.80
150
ID 12.70
ID 15.90
OD 19.10
88
ID 9.52
OD 12.70
60
ID 22.20
OD 19.10
90
ID 31.80
ID 28.60
OD 25.40
150
ID 9.52 (2x) ID 12.70 (3x)
ID 9.52 (3x) ID 9.52 (3x)
ID 15.90 (3x)
ID 25.40
ID 22.20
ID 19.10
ID 12.70 (3x)
150
620
7 x 60 = 420
1
7
9
8
5 1
2
7
ID 9.52 (2x) ID 12.70 (3x)
ID 9.52 (3x) ID 9.52 (3x)
ID 15.90 (3x)
ID 25.40
ID 22.20
ID 19.10
ID 12.70 (3x)
150
620
7 x 60 = 420
1
7
9
8
5 1
2
7
ID 12.70 (3x) ID 12.70 (3x) ID 19.10 (3x)
ID 15.90 (3x)
ID 15.90 (3x)
ID 25.40
ID 28.60
ID 31.80
ID 12.70 (2x)
150
720
5 x 80 = 400 2 x 60 = 120
1
7
7
8
6 1
2
8
ID 12.70
ID 15.90 (2x) ID 12.70 (5x)
ID 22.20
ID 19.10
ID 19.10
ID 15.90
ID 15.90
ID 12.70 (2x)
150
620
7 x 60 = 420
1
7
5
8
5 1
2
7
ID 12.70
ID 15.90 (2x)
ID 15.90 (2x)
ID 12.70 (5x)
ID 22.20
ID 19.10
ID 19.10
ID 15.90
ID 15.90
ID 12.70 (2x)
150
165
620
775
7 x 60 = 420
7 x 80 = 560
1
7
5
1
3
8
8
5
9
5
1
2
7
ID 15.90 (6x) ID 19.10 (6x)
ID 15.90 (2x)
ID 31.80
ID 38.10
165
775
7 x 80 = 560
1
3
8
1
2
9
9
5
1
7
7
ID 12.70 (3x) ID 12.70 (3x) ID 19.10 (3x)
ID 15.90 (3x)
ID 15.90 (2x)
ID 19.10 (2x)
ID 15.90 (3x)
ID 25.40
ID 28.60
ID 31.80
ID 12.70
ID 19.10
ID 25.40
ID 15.90 ID 28.60
ID 12.70 (2x)
ID 12.70 (2x)
150
150
720
370
5 x 80 = 400 2 x 60 = 120
2 x 80 = 160
1
2
9
1
7
7
1
2
6
ID 15.90 (2x)
ID 19.10 (2x)
ID 12.70
ID 12.70
ID 19.10
ID 19.10
ID 25.40
ID 15.90 ID 28.60
ID 15.90
ID 12.70 (2x)
ID 12.70 (3x) ID 9.52 (3x)
150
150
370
370
2 x 80 = 160
2 x 80 = 160
1
7
7
8
6 1
2
8
ID 12.70 (3x) ID 12.70 (3x) ID 19.10 (3x)
ID 19.10 (6x)
ID 15.90 (3x)
ID 15.90 (3x)
ID 15.90 (6x)
ID 25.40
ID 28.60
ID 38.10
ID 31.80
ID 31.80
ID 12.70 (2x)
150
720
5 x 80 = 400 2 x 60 = 120
1
7
7
8
6 1
2
8
ID 22.20 ID 25.40
OD 19.10
130
ID 38.10 OD 31.80
150
ID 9.52
ID 6.35 OD 12.70
95
ID 15.90
ID 19.10
ID 12.70
OD 25.4
144
ID 15.90 OD 12.70
60
ID 41.28
OD 38.10
120
ID 19.10 OD 12.70
100
Air-cooled selection procedure
4
VRV Systems Air cooled selection procedure 36
4 Refnet pipe systems
4TW27239-1
G
a
s
-
s
id
e

ju
n
c
t
io
n
BHFQ22P1007 BHFQ22P1517
ID

3
1
.8
ID

2
8
.6
ID

2
5
.4
ID

2
2
.2
ID

1
9
.1
L
iq
u
id
-
s
id
e

ju
n
c
t
io
n
R
e
d
u
c
e
r
s
I
n
s
u
la
t
io
n

t
u
b
e
f
o
r

g
a
s

p
ip
e
f
o
r

liq
u
id

p
ip
e
f
o
r

liq
u
id

p
ip
e
f
o
r

g
a
s

p
ip
e
ID

2
8
.6
ID

2
5
.4
ID

3
1
.8
ID

3
8
.1
ID

2
5
.4
ID

2
8
.6
ID

3
1
.8
ID

3
1
.8
ID

2
8
.6
ID

2
5
.4
ID

2
2
.2
ID

1
9
.1
ID

2
8
.6
ID

2
5
.4
ID

1
5
.9
ID

1
9
.1
ID

1
5
.9
ID

1
2
.7
ID

9
.5
ID

1
5
.9
ID

1
9
.1
ID

1
9
.1
ID

1
5
.9
ID

2
2
.2
ID

1
2
.7
ID

9
.5
ID

1
9
.1 ID

1
5
.9
ID

1
5
.9
ID

2
2
.2
ID

3
8
.1
ID

1
9
.1
ID

1
9
.1
ID

2
5
.4
ID

2
5
.4
O
D

2
5
.4
O
D

3
1
.8
O
D

2
5
.4
ID

2
8
.6
ID

2
8
.6
ID

2
2
.2
ID

2
2
.2
ID

1
9
.1
ID

1
9
.1
ID

2
5
.4
ID

2
5
.4
O
D

2
5
.4
O
D

2
5
.4
(2
x
)
(2
x
)
(2
x
)
(2
x
)
(2
x
)
(2
x
)
(2
x
)
ID

2
8
.6
ID

2
8
.6
ID

2
8
.6
ID

3
1
.8
O
D

3
1
.8
ID

2
2
.2
ID

2
2
.2
ID

4
1
.3
O
D

3
1
.8
O
D

3
8
.1
ID

4
1
.3
ID

3
1
.8
O
D

3
1
.8
O
D

3
8
.1
O
D

2
8
.6
ID

2
8
.6
ID

2
2
.2
ID

2
5
.4
O
D

2
8
.6
O
D

1
9
.1
O
D

2
5
.4
ID

9
.5
ID

9
.5
ID

1
2
.7
O
D

1
2
.7
O
D

3
1
.8
ID

1
2
.7
ID

4
1
.3
ID

3
4
.9
ID

1
9
.1
ID

1
5
.9
O
D

3
8
.1
O
D

1
5
.9
O
D

1
5
.9
O
D

3
1
.8
O
D

1
5
.9
ID

3
4
.9
ID

9
.5
ID

9
.5
ID

1
2
.7
ID

1
2
.7
O
D

1
2
.7
O
D

1
5
.9
ID

1
5
.9
O
D

1
9
.1
ID

1
5
.9
O
D

1
2
.7
ID

1
5
.9
4
VRV Systems Air cooled selection procedure 37
Air-cooled selection procedure
4 Refnet pipe systems
S
u
c
t
i
o
n

g
a
s

s
i
d
e

j
u
n
c
t
i
o
n
D
i
s
c
h
a
r
g
e

g
a
s

s
i
d
e

j
u
n
c
t
i
o
n
L
i
q
u
i
d

s
i
d
e

j
u
n
c
t
i
o
n
R
e
d
u
c
e
r
s

/

E
x
p
a
n
d
e
r
s
J
o
i
n
t

f
o
r

o
i
l

p
i
p
e
F
o
r

s
u
c
t
i
o
n

g
a
s

p
i
p
e
F
o
r

d
i
s
c
h
a
r
g
e

g
a
s

p
i
p
e
F
o
r

l
i
q
u
i
d

p
i
p
e
B H F Q 2 3 M 9 0 7B H F Q 2 3 M 1 3 5 7
2
T
W
2
5
7
9
9
-
2
A
ID

1
9
.1
0
ID

2
2
.2
0
ID

2
5
.4
0
ID

2
5
.4
0
ID

2
8
.6
0
ID

2
8
.6
0
ID

3
1
.8
0
ID

9
.5
2
ID

9
.5
2
ID

1
2
.7
0
ID

1
2
.7
0
ID

2
2
.2
0
ID

1
9
.1
0
ID

1
5
.9
0
O
D

2
5
.4
0
I
D

2
5
.4
0
I
D

3
8
.1
0
I
D

3
4
.9
5
I
D

2
8
.6
0
I
D

2
2
.2
0
I
D

1
9
.1
0
O
D

3
1
.8
0
O
D

3
1
.8
0
ID

1
9
.1
0
O
D

3
1
.8
0
ID

3
4
.9
5
ID

2
8
.6
0
ID

2
2
.2
0
ID

2
5
.4
0
O
D

2
5
.4
0
ID

1
5
.9
0
ID

1
5
.9
0
ID

1
5
.9
0
ID

2
2
.2
0
ID

2
2
.2
0
O
D

2
5
.4
0
ID

1
9
.1
0
ID

1
9
.1
0
ID

1
9
.1
0
ID

9
.5
2
O
D

1
5
.9
0
ID

1
2
.7
0
ID

2
5
.4
0
ID

3
1
.8
0
ID

3
1
.8
0
ID

3
1
.8
0
ID

2
8
.6
0
ID

2
5
.4
0
ID

2
5
.4
0
ID

2
2
.2
0
ID

2
8
.6
0
ID

2
8
.6
0
ID

3
1
.8
0
ID

9
.5
2
ID

1
5
.9
0
ID

1
5
.9
0
ID

1
2
.7
0
ID

1
9
.1
0
ID

1
9
.1
0
ID

2
5
.4
0
ID

2
2
.2
0
ID

3
4
.9
5
ID

2
8
.6
0 O
D

2
5
.4
0
O
D

3
1
.8
0
ID

4
1
.2
8
O
D

3
8
.1
0
ID

2
2
.2
0
ID

2
2
.2
0
ID

2
2
.2
0
ID

1
9
.1
0
ID

1
9
.1
0
ID

1
5
.9
0
O
D

2
5
.4
0
ID

1
9
.1
0
ID

9
.5
2
ID

1
2
.7
0
O
D

1
5
.9
0
ID

1
9
.1
0
ID

2
5
.4
0
ID

2
5
.4
0
ID

3
1
.8
0
ID

2
8
.6
0
ID

2
8
.6
0
ID

2
2
.2
0
ID

2
5
.4
0
ID

1
9
.1
0
ID

2
8
.6
0
ID

2
2
.2
0
ID

2
2
.2
0
ID

2
5
.4
0
ID

9
.5
2
ID

1
5
.9
0
ID

1
5
.9
0
ID

1
2
.7
0
ID

1
9
.1
0
Air-cooled selection procedure
5
VRV Systems Air cooled selection procedure 38
5 Example of Refnet piping layouts
Type of fitting Sample systems
D
i
s
t
r
i
b
u
t
i
o
n

b
y

R
E
F
N
E
T

j
o
i
n
t
s
D
i
s
t
r
i
b
u
t
i
o
n

b
y

R
E
F
N
E
T

h
e
a
d
e
r
D
i
s
t
r
i
b
u
t
i
o
n

b
y

R
E
F
N
E
T

j
o
i
n
t
s

a
n
d

h
e
a
d
e
r
s
Outdoor unit Outdoor unit Outdoor unit Outdoor unit
REFNET joint
REFNET joint
REFNET joint
REFNET joint
Simultaneous
control of
cooling/heating
Simultaneous
control of
cooling/heating
Indoor unit
Indoor unit
Indoor unit Indoor unit
Cooling only
Cooling only
Cooling only
Cooling only
Cooling only
Outdoor unit Outdoor unit
REFNET header (8 branch fitting)
REFNET header (8 branch fitting)
REFNET header (8 branch fitting)
Indoor unit
Indoor unit
Indoor unit
Simultaneous
control of
cooling/heating
Can be added
Cooling only
Can be added
Cooling
only
Can be added
Outdoor unit
REFNET joint
Indoor unit
REFNET header (8 branch fitting)
Simultaneous control of cooling/heating
Can be added
Outdoor unit
Simultaneous control of cooling/heating
Indoor unit
REFNET header (8 branch fitting)
Can be added
Cooling only
6

V
R
V

S
y
s
t
e
m
s

A
i
r

c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
3
9

A
i
r
-
c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
6
R
e
f
r
i
g
e
r
a
n
t

p
i
p
e

s
e
l
e
c
t
i
o
n
6

-

1
V
R
V
I
I
I
-
S
Example of connection
(Connection of 8 indoor units Heat pump system)
Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
Maximum
allowable
length
Between outdoor and
indoor units
Actual pipe length
Pipe length between outdoor and indoor units 150 m
[Example] unit 8: a+b+c+d+e+f+g+p150 m [Example] unit 6: a+b+h150 m, unit 8: a+i+k150 m [Example] unit 8: a+i150 m
Equivalent length Equivalent pipe length between outdoor and indoor units 175 m (Assume equivalent pipe length of refnet joint to be 0.5 m and of the refnet header to be 1.0 m. (for calculation purposes))
Total extension
length
Total piping length from outdoor unit to all indoor units between 10 m and 300 m
Allowable
height
Between outdoor and
indoor units
Difference in
height
Difference in height between outdoor and indoor units (H1)50 m (40 m if outdoor unit is located in a lower position).
Between indoor and indoor
units
Difference in
height
Difference in height between adjacent indoor units (H2)15 m
Allowable length after the branch Actual pipe length
Pipe length from rst refrigerant branch kit (either refnet joint or refnet header) to indoor unit 40 m
[Example] unit 8: b+c+d+e+f+g+p40 m [Example] unit 6: b+h40 m, unit 8: i+k40 m [Example] unit 8: i40 m
Refrigerant branch kit selection
Refrigerant branch kits can only be used with R410A.
Use the following refnet joint Use the following refnet header
Pipe size selection
Caution on selecting connection pipes
If the overall equivalent piping length is 90 m, be sure to
enlarge the pipe diameter of the gas-side main piping. If the
recommended pipe size is not available, stick to the original
pipe diameter (which may result in a small capacity decrease).
[Gas side]
RXYSQ4+5: 15.919.1
RXYSQ6: 19.122.2
A. Piping between outdoor unit and refrigerant branch kit
Match to the size of the connection piping on the outdoor unit.
Outdoor unit connection piping size
B. Piping between refrigerant branch kits
Use the pipe size from the following table.
C. Piping between refrigerant branch kit and indoor unit
Pipe size for direct connection to indoor unit must be the same as the
connection size of indoor unit.
How to calculate the additional refrigerant to be charged
Additional refrigerant to be charged R (kg)
R should be rounded off in units of 0.1 kg
indoor unit
refnet joint
refnet header
a b c d e f g
h i j k l m n
1 2 3 4 5 6 7
8
H2
H1
p
A B C D E F G H1
H2
a
i
b
c d e f g h
1 2 3 4 5 6
k
j
7 8
A B
a
H1
H2
c d e f g h i b
1 2 3 4 5 6 7
8
Outdoor unit capacity type Refrigerant branch kit name
RXYSQ4~6 KHRQ22M20T
Outdoor unit capacity type Refrigerant branch kit name
RXYSQ4~6 KHRQ22M29H
1 2
3
1 Main pipe (enlarge)
2 First refrigerant branch kit
3 Indoor unit
Outdoor unit
capacity type
Piping size (outer diameter x minimum
thickness)
Gas pipe Liquid pipe
RXYSQ4+5 15.9x1.0
(19.1x1.0)
9.5x0.8
RXYSQ6 19.1x1.0
(22.2x1.0)
Piping size (outer diameter x minimum thickness)
Gas pipe Liquid pipe
15.9x1.0 9.5x0.8
Indoor capacity
index
Piping size
(outer diameter x minimum thickness)
Gas pipe Liquid pipe
20+25+32+40+50 12.7x0.8 6.4x0.8
63+80+100+125 15.9x1.0 9.5x0.8
R=
(
Total length (m) of liquid
piping size at 9.5
)
x0.054+
(
Total length (m) of liquid
piping size at 6.4
)
x0.022
Example for refrigerant branch using refnet joint and refnet header
R=[73 x 0.054] + [69 x 0.022] = 5.46 5.5 kg
a: 9.5x30 m d: 9.5x13 m g: 6.4x10 m j: 6.4x10 m
b: 9.5x10 m e: 6.4x10 m h: 6.4x20 m k: 6.4x9 m
c: 9.5x10 m f: 6.4x10 m i: 9.5x10 m

A
i
r
-
c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
6

V
R
V

S
y
s
t
e
m
s

A
i
r

c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
4
0
6
R
e
f
r
i
g
e
r
a
n
t

p
i
p
e

s
e
l
e
c
t
i
o
n
6

-

2
V
R
V
I
I
I
Example of connection
(Connection of 8 indoor units Heat pump system)
Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
One outdoor unit
installed
(RX(Y)Q5~18)
Outdoor units
installed in a
multiple outdoor
unit system
(RXYQ20~54)
Install the joint part ( part in the gure) of the outdoor unit multi connection piping kit
horizontally with attention to the installation restrictions described in "connecting the
refrigerant piping".
(*) If the system capacity is RXYQ20 or more, re-read to the rst outdoor branch as
seen from the indoor unit.
Maximum allowable length
Between outdoor and indoor units
Actual pipe length
Pipe length between outdoor(*) and indoor units 165 m
[Example] unit 8: a+b+c+d+e+f+g+p165 m [Example] unit 6: a+b+h120 m, unit 8: a+i+k165 m [Example] unit 8: a+i165 m
Equivalent length
Equivalent pipe length between outdoor(*) and indoor units 190 m (Assume equivalent pipe length of refnet joint to be 0.5 m and of the refnet header to be 1.0 m. (for
calculation purposes))
Total extension
length
Total piping length from outdoor unit* to all indoor units 1000 m
Between outdoor branch and outdoor unit (Only for
RXYQ20 or more)
Actual pipe length Piping length from outdoor branch to outdoor unit 10 m. Approximate length: max. 13 m
Allowable height
Between outdoor and indoor units
Difference in
height
Difference in height between outdoor and indoor units (H1)50 m (40 m if outdoor unit is located in a lower
position).
Between indoor and indoor units
Difference in
height
Difference in height between adjacent indoor units (H2)15 m
Between outdoor and outdoor units
Difference in
height
Difference in height between outdoor unit (main) and outdoor unit (sub) (H3)5 m
Allowable length after the branch Actual pipe length
Pipe length from rst refrigerant branch kit (either refnet joint or refnet header) to indoor unit 40 m (See note 1 on next page)
[Example] unit 8: b+c+d+e+f+g+p40 m [Example] unit 6: b+h40 m, unit 8: i+k40 m [Example] unit 8: i40 m
Refrigerant branch kit selection
Refrigerant branch kits can only be used with R410A.
How to select the refnet joint
When using refnet joints at the rst branch counted from the outdoor unit side.
Choose from the following table in accordance with the capacity of the outdoor unit.
For refnet joints other than the rst branch, select the proper branch kit model based on
the total capacity index.
How to select the refnet header
Choose from the following table in accordance with the total capacity of all the indoor
units connected below the refnet header.
Note: 250 type cannot be connected below the refnet header.
How to choose an outdoor multi connection piping kit (needed if the outdoor
unit capacity type is RXYQ20 or more.)
Choose from the following table in accordance with the number of outdoor units.
Example of downstream indoor units
[Example]
in case of refnet joint C; indoor units 3+4+5+6+7+8
[Example]
in case of refnet joint B; indoor units 7+8,
in case of refnet header; indoor units 1+2+3+4+5+6
[Example]
in case of refnet header;
indoor units 1+2+3+4+5+6+7+8
Use the outdoor unit multi connection piping kit that is sold separately as an option
(BHFQ22P1007+1517) for the multi installation of outdoor units. Selection method is
as shown in the right table.
Do not use the outdoor unit multi connection piping kit (BHFQ22M909+1359) that
are sold separately as an option of the M-type series and do not use T-joints.
indoor unit
refnet joint
refnet header
outdoor multi connection piping kit
a b c d e f g H1
p
A B C D E F G
1 2 3 4 5 6 7
8
H2
h i j k l m n
H1
H2
a
i
b
c d e f g h
k
j
7 8
A B
1 2 3 4 5 6
a
H1
H2
c d e f g h i b
1 2 3 4 5 6 7
8
A B C D E F G
a b c d e f g
8
H2
H1
H3
p
h i j k l m n
1 2 3 4 5 6 7
H1
H2
a
i
b
c
1 2 3 4 5 6
k
j
7 8
H3
A B
d e f g h
H1
H3
a
H2
c d e f g h i b
1 2 3 4 5 6 7
8
r s t
r10 m (Approximate length:
max. 13 m)
s10 m (Approximate length:
max: 13 m)
t10 m (Approximate length:
max: 13 m)
Outdoor unit capacity type Refrigerant branch kit name
RX(Y)Q5 KHRQ22M20T
RX(Y)Q8+10 KHRQ22M29T9
RX(Y)Q12~18 + RXYQ20+22 KHRQ22M64T
RXYQ24~54 KHRQ22M75T
Indoor capacity type (kW) Refrigerant branch kit name
<200 KHRQ22M20T
200x<290 KHRQ22M29T9
290x<640 KHRQ22M64T
640 KHRQ22M75T
Indoor capacity type (kW) Refrigerant branch kit name
<290 KHRQ22M29H (Max. 8 branch)
290x<640 KHRQ22M64H (Max. 8 branch)
(a)
640 KHRQ22M75H (Max. 8 branch)
(a) See note 2 on next page
Number of outdoor units Branch kit name
2 BHFQ22P1007
3 BHFQ22P1517
6

V
R
V

S
y
s
t
e
m
s

A
i
r

c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
4
1

A
i
r
-
c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
6
R
e
f
r
i
g
e
r
a
n
t

p
i
p
e

s
e
l
e
c
t
i
o
n
6

-

2
V
R
V
I
I
I
Pipe size selection
For an outdoor unit multi installation (RXYQ20~54P7W1B),
select the pipe size in accordance with the following gure.
A,B,C. Piping between outdoor unit and refrigerant branch kit
Choose from the following table in accordance with the outdoor unit total
capacity type, connected downstream.
Outdoor unit connection piping size
D. Piping between refrigerant branch kits
Choose from the following table in accordance with the total capacity of
all the indoor units connected below this.
Do not let the connection piping exceed the refrigerant piping size
chosen by general system model name.
E. Piping between refrigerant branch kit and indoor unit
Pipe size for direct connection to indoor unit must be the same as the
connection size of indoor unit.
When the equivalent pipe length between outdoor and indoor units is 90 m or more, the size of the main pipes (both gas side and liquid side) must be increased.
Depending on the length of the piping, the capacity lay drop, but even in such a case it is possible to increase the size of the main pipes.
How to calculate the additional refrigerant to be charged
Additional refrigerant to be charged R (kg)
R should be rounded off in units of 0.1 kg
Example for refrigerant branch using refnet joint and refnet
header for RXYQ34P7W1B
If the outdoor unit is RXYQ34P7W1B and the piping lengths are as
below
R = [30x0.26]+[10x0.18]+[10x0.12]+[40x0.059]+[49x0.022] = 14.238
R = 14.2 kg
Note 1 Allowable length after the rst refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are fullled.
Required conditions Example drawings
It is necessary to increase the pipe size between the rst branch kit and the nal branch kit. (Reducers
must be procured on site.) However, if the pipes are of the same pipe size as the main pipe there is no
need to increase the pipe size.
indoor unit 8:
b+c+d+e+f+g+p90 m
increase the pipe size
of b, c, d, e, f, g
Increase the pipe size as follows
* If available on the site. Otherwise it can not be increased.
For calculation of total extension length, the actual length of above pipes must be doubled. (except main
pipe and the pipes that not increase the pipe size)
a+b*2+c*2+d*2+e*2+f*2+g*2
+h+i+j+k+l+m+n+p1000 m
Indoor unit to the nearest branch kit 40 m h, i, j....... p40 m
The difference between the distance of the outdoor unit to the farthest indoor unit and the distance of the
outdoor unit to the nearest indoor unit 40 m
The farthest indoor unit 8
The nearest indoor unit 1
(a+b+c+d+e+f+g+p)(a+h)40 m
Note 2 If the pipe size above the refnet header is 34.9 or more,
KHRQ22M75H is required.
B A
C D E
B B
Outdoor unit
capacity type
Piping size (outer diameter) (mm)
Gas pipe Liquid pipe
RX(Y)Q5 15.9
9.5 RX(Y)Q8 19.1
RX(Y)Q10 22.2
RX(Y)Q12~16
28.6
12.7
RX(Y)Q18 +
RXYQ20+22 15.9
RXYQ24
34.9
RXYQ26~34
19.1
RXYQ36~54 41.3
Indoor or outdoor unit
total capacity (kW)
Piping size (outer diameter) (mm)
Gas pipe Liquid pipe
<150 15.9
9.5 150x<200 19.1
200x<290 22.2
290x<420
28.6
12.7
420x<640 15.9
640x<920 34.9
19.1
920 41.3
Indoor capacity type
Piping size (outer diameter) (mm)
Gas pipe Liquid pipe
20~50 12.7 6.4
63~125 15.9
9.5 200 19.1
250 22.2
Gas side Liquid side
RX(Y)Q5 15.9 19.1 RX(Y)Q5 9.5
RX(Y)Q8 19.1 22.2 RX(Y)Q8+10 9.5 12.7
RX(Y)Q10 22.2 25.4
(a)
(a) If not available, increase is not allowed
RX(Y)Q12~16 12.7 15.9
RX(Y)Q12+14 28.6 RX(Y)Q18 +
RXYQ20~24
15.9 19.1
RX(Y)Q16+18 +
RXYQ20+22
28.6 31.8
(a)
RXYQ26~54 19.1 22.2
RXYQ24 34.9 Increase is not allowed
RXYQ26~34 34.9 38.1
(a)
RXYQ36~54 41.3
Increase is not allowed
1 Outdoor unit
2 Main pipes
3 Increase
4 First refrigerant branch kit
5 Indoor unit
1 5 2 4 3
The refrigerant charge of the system must be less
than 100 kg. This means that in case the calculated
refrigerant charge is equal to or more than 95 kg you
must divide your multiple outdoor system into smaller
independent systems, each containing less than
95 kg refrigerant charge.
For factory charge, refer to the unit name plate.
R=
(
Total length (m) of liquid
piping size at 22.2
)
x0.37+
(
Total length (m) of liquid
piping size at 19.1
)
x0.26+
(
Total length (m) of liquid
piping size at 15.9
)
x0.18+
(
Total length (m) of liquid
piping size at 12.7
)
x0.12+
(
Total length (m) of liquid
piping size at 9.5
)
x0.059+
(
Total length (m) of liquid
piping size at 6.4
)
x0.022
a: 19.1x30 m d: 9.5x10 m g: 6.4x10 m j: 6.4x10 m
b: 15.9x10 m e: 9.5x10 m h: 6.4x20 m k: 6.4x9 m
c: 9.5x10 m f: 9.5x10 m i: 12.7x10 m
6.4 9.5 15.9 19.1 22.2 25.4*
9.5 12.7 19.1 22.2 28.6 31.8*
12.7 15.9 34.9 38.1*
a b c d e f g H1
p
A B C D E F G
1 2 3 4 5 6 7
8
H2
h i j k l m n
1
2
3
1 Outdoor unit
2 Refnet joints
(a~g)
3 Indoor units (1~8)

A
i
r
-
c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
6

V
R
V

S
y
s
t
e
m
s

A
i
r

c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
4
2
6
R
e
f
r
i
g
e
r
a
n
t

p
i
p
e

s
e
l
e
c
t
i
o
n
6

-

3
V
R
V
I
I

h
e
a
t

r
e
c
o
v
e
r
y
Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
One outdoor
unit installed
(REYQ8~16)
When multiple
outdoor units
installed
(REYQ18~...)
Maximum
allowable
length
Between outdoor and
indoor units
Actual pipe
length
Pipe length between outdoor and indoor units 150 m
[Example] unit 8: a+b+c+d+e+s150 m [Example] unit 6: a+b+l 150 m, unit 8: a+m+n+p150 m [Example] unit 8: a+o150 m
Equivalent
length
Equivalent pipe length between outdoor and indoor units 175 m (Assume equivalent pipe length of refnet joint to be 0.5 m and of the refnet header to be 1.0 m, that of BSVQ100 and BSVQ160 to be 4 m
and that of BSVQ250 to be 6 m (for calculation purposes)).
Total extension
length
Total piping length from outdoor unit* to all indoor units 300 m
Between outdoor branch
and outdoor unit (Only for
REYQ18 or more)
Actual pipe
length
Piping length from outdoor branch to outdoor unit 10 m. Approximately length: max. 13 m
Allowable
height
Between outdoor and
indoor units
Difference in
height
Difference in height between outdoor and indoor units (H1)50 m (40 m if outdoor unit is located in a lower position).
Between indoor and indoor
units
Difference in
height
Difference in height between adjacent indoor units (H2)15 m
Between outdoor and
outdoor units
Difference in
height
Difference in height between outdoor unit (main) and outdoor unit (sub) (H3)5 m
Allowable length after the branch
Actual pipe
length
Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit 40 m
[Example] unit 8: b+c+d+e+s40 m [Example] unit 6: b+l40 m, unit 8: m+n+p40 m [Example] unit 8: o40 m
Refrigerant branch kit selection
Refrigerant branch kits can only be used with R-410A.
How to select the refnet joint
When using refnet joints at the first branch counted from the outdoor unit side.
Choose from the following table in accordance with the capacity of the outdoor unit.
For refnet joints other than the first branch, select the proper branch kit model based on the total capacity
index.
How to select the refnet header
Choose from the following table in accordance with the total capacity of all the indoor units connected below
the refnet header.
Note: 250 type cannot be connected below the refnet header.
How to choose an outdoor branch kit (needed if the outdoor unit capacity type is REYQ18 or more.)
Choose from the following table in accordance with the number of outdoor units.
Example of downstream indoor units
[Example]
in case of refnet joint C; indoor units 5+6+7+8
[Example]
in case of refnet joint B; indoor units 7+8,
in case of refnet header; indoor units 1+2+3+4+5+6
[Example]
in case of refnet header;
indoor units 1+2+3+4+5+6+7+8
indoor unit
BS box
refnet joint
refnet header
(3 pipes) (2 pipes)
1 4
2
3 3
1 Discharge gas side
2 Suction gas side
3 Liquid pipe
4 Gas pipe
B1
Piping from BS unit to indoor unit and piping
from refrigerant branch kit to indoor unit used
as cooling only must be composed by 2 pipes
(suction gas pipe and liquid pipe).
* If the system capacity is REYQ18 or more,
measure to the first outdoor branch as seen
from the indoor unit.
A
F
B1
1
h
f
g i k
b
m
a
l
c
G
2
j
3 4
B
B2
o
n
5
B3
q
p
6
B4
C D
r
H2
H1
s
7
8
E
d e
1 ~ 6 Cool/heat selection possible
7 + 8 Cooling only
A
B5
d
c
1
B1
H2
H1
a
b
f
e
2
B2
h
g
3
B3
j
i
4
B4
k
5
l o
n
p
6 7
8
B
1 ~ 4 , 7 + 8 Cool/heat selection possible
5 + 6 Cooling only
H2
H1
a
i
h
4
B4
g
f
3
B3
e
d
2
B2
c
b
1
B1
k
j
5
B5
m
l
6
B6
n
7
o
8
1 ~ 6 Cool/heat selection possible
7 + 8 Cooling only
H3
REFNET joint ( ~ )
A
A G
F
B1
1
h
f
g i k
b
m
a
l
c
G
2
j
3 4
B
B2
o
n
5
B3
q
p
6
B4
C D
r
H2
H1
s
7
8
E
d e
1 ~ 6 Cool/heat selection possible
7 + 8 Cooling only
H3
A
B5
d
c
1
B1
H2
H1
a m
b
f
e
2
B2
h
g
3
B3
j
i
4
B4
k
5
l o
n
p
6 7
8
B
1 ~ 4 , 7 + 8 Cool/heat selection possible
5 + 6 Cooling only
H3
H2
H1
a
i
h
4
B4
g
f
3
B3
e
d
2
B2
c
b
1
B1
k
j
5
B5
m
l
6
B6
n
7
o
8
1 ~ 6 Cool/heat selection possible
7 + 8 Cooling only
s
r
t
r10 m (Approximately length: max. 13 m)
s10 m (Approximately length: max: 13 m)
t10 m (Approximately length: max 13 m)
Outdoor unit capacity type Refrigerant branch kit name
REYQ8+10 KHRQ23M29T7
REYQ12~22 KHRQ23M64T7
REYQ24 KHRQ23M75T7
Indoor capacity type Refrigerant branch kit name
<200 KHRQ23M20T7 KHRQ22M20T7
200x<290 KHRQ23M29T7 KHRQ22M29T7
290x<640 KHRQ23M64T7 KHRQ22M64T7
>640 KHRQ23M75T7
Indoor capacity type
Refrigerant branch kit name
In case of 3 pipes In case of 2 pipes
<200
KHRQ23M29T7 KHRQ22M29H7
200x<290
290x<640 KHRQ23M64H7 KHRQ22M64H7
>640 KHRQ23M75H7
Number of outdoor units Branch kit name
2 BHFQ23M907
3 BHFQ23M1357
6

V
R
V

S
y
s
t
e
m
s

A
i
r

c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
4
3

A
i
r
-
c
o
o
l
e
d

s
e
l
e
c
t
i
o
n

p
r
o
c
e
d
u
r
e
6
R
e
f
r
i
g
e
r
a
n
t

p
i
p
e

s
e
l
e
c
t
i
o
n
6

-

3
V
R
V
I
I

h
e
a
t

r
e
c
o
v
e
r
y
Pipe size selection
For an outdoor unit multi installation (REYQ18~48), make
the settings in accordance with the following figure.
A. Piping between outdoor unit and refrigerant branch kit
Match to the size of the connection piping on the outdoor unit.
Outdoor unit connection piping size
Pipe size when overall equivalent pipe length is 90 m or more
When overall equivalent pipe length is 90 m or more, the size of the
main liquid pipe (outdoor unit branch sections) must be increased.
(Only main liquid pipe!)
Main liquid pipe size
B. Piping between outdoor branches
Choose from the following table in accordance with the total capacity
of all the outdoor units connected above this.
Between two immediately adjacent refrigerant branch kits
and BS unit
Choose from the following table in accordance with the total capacity
of all the indoor units connected below this.
Do not let the connection piping exceed the refrigerant piping size
chosen by general system model name.
C. Piping between outdoor branch and outdoor unit
D. Oil-equalizing line (Only for REYQ18 or greater)
Between BS unit (refrigerant branch kit) and indoor unit
Pipe size for direct connection to indoor unit must be the same as the
connection size of indoor unit.
How to calculate the additional refrigerant to be
charged
Additional refrigerant to be charged R (kg)
R should be rounded off in units of 0.1 kg
Example for refrigerant branch using refnet joint and refnet header for REYQ34
If the outdoor unit is REYQ34 and the piping lengths are as below
R = [30x0.25]+[10x0.17]+[10x0.11]+[40x0.054]+[49x0.022]x1.156 = 9.569 R = 9.6 kg
A B C
C C D
Outdoor unit
capacity type
Piping size (outer diameter)
Gas pipe
Liquid pipe Suction Discharge
REYQ8
9.5
19.1 15.9
REYQ10 22.2
19.1
REYQ12
12.7
28.6
REYQ14+16
22.2
REYQ18
15.9 REYQ20+22
28.6
REYQ24
34.9
REYQ26~34
19.1 REYQ36
41.3
REYQ38~48 34.9
Outdoor
capacity type
Piping size (outer diameter)
Normal size Size up
REYQ8+10 9.5 12.7
REYQ12~16 12.7 15.9
REYQ18~24 15.9 19.1
REYQ26~48 19.1 22.2
Outdoor
capacity index
Piping size (outer diameter)
Gas pipe
Liquid pipe Suction Discharge
REYQ18
15.9
28.6
22.2
REYQ20+22
28.6 REYQ24
34.9
REYQ26 19.1
Indoor
capacity
index
Piping size (outer diameter)
Gas pipe
Liquid pipe Suction Discharge
<62.5
(*)
(*) The BS unit (BSVQ100MV1) port and
connection pipe are different sizes. Use the
reducing joints included with the BS unit.
6.4 12.7 9.5
62.5x200
9.5
15.9 12.7
200x<290 22.2
19.1
290x<420 12.7
28.6
420x<640 15.9
28.6 640x<920
19.1
34.9
920 41.3
When two pipes are connected between two adjacent refrigerant branch
kits, select the proper gas pipe size based on data mentioned under
"suction gas pipe" column in the table above.
Outdoor unit
capacity type
Piping size (outer diameter)
Gas pipe
Liquid pipe Suction Discharge
REYQ8
9.5
19.1 15.9
REYQ10 22.2
19.1
REYQ12
12.7 28.6
REYQ14+16 22.2
Piping size 6.4
Indoor
capacity index
Piping size (outer diameter)
Gas pipe Liquid pipe
20, 25, 32,40, 50
(*)
(*) The BS unit (BSVQ100MV1) port and
connection pipe are different sizes. Use the
reducing joints included with the BS unit.
12.7 6.4
63, 80, 100, 125 15.9
9.5 200 19.1
250 22.2
NOTE If a negative result is gotten for R from
the formula at right, no refrigerant
needs to be added nor removed.
R=
{
(
Total length (m) of liquid
piping size at 22.2
)
x0.35+
(
Total length (m) of liquid
piping size at 19.1
)
x0.25+
(
Total length (m) of liquid
piping size at 15.9
)
x0.17+
(
Total length (m) of
liquid
piping size at 12.7
)
x0.11
+
(
Total length (m) of liquid
piping size at 9.5
)
x0.054+
(
Total length (m) of liquid
piping size at 6.4
)
x0.022
}
x 1.15
Model Amount of refrigerant
REYQ8~16 0 kg
REYQ18~32 3 kg
REYQ34~48 6 kg
a: 19.1x30 m d: 9.5x10 m g: 6.4x10 m j: 6.4x10 m
b: 15.9x10 m e: 9.5x10 m h: 6.4x20 m k: 6.4x9 m
c: 9.5x10 m f: 9.5x10 m i: 12.7x10 m
Air-cooled selection procedure
6
VRV Systems Air cooled selection procedure 44
6 Refrigerant pipe selection
6 - 4 Piping thickness
:O : annealed
1/2H : half-hard
For half hard pipes the maximum allowed tensile stress is 61 N/mm
2
. For this reason the 0.2% proof strength
of the half hard pipe shall be minimum 61 N/mm
2
.
The bending radius is more than or equal to 3 times the diameter of the pipe.
Piping diameter Material Minimum thickness [mm]
6.4 O 0.8
9.5 O 0.8
12.7 O 0.8
15.9 O 0.99
19.1 1/2H 0.8
22.2 1/2H 0.8
28.6 1/2H 0.99
34.9 1/2H 1.21
41.3 1/2H 1.43
ISO14001 assures an effective environmental
management system in order to help protect human
health and the environment from the potential impact of
our activities, products and services and to assist in
maintaining and improving the quality of the
environment.
Daikin Europe N.V. is approved by LRQA for its Quality
Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance regarding
design, development, manufacturing as well as to services
related to the product.
Daikin units comply with the European
regulations that guarantee the safety of the
product.
Zandvoordestraat 300
B-8400 Ostend - Belgium
www.daikineurope.com
E
E
D
E
0
6
-
2


0
7
/
2
0
0
6
P
r
i
n
t
e
d

i
n

B
e
l
g
i
u
m

b
y

L
a
n
n
o
o
"The present publication is drawn up by way of
information only and does not constitute an offer
binding upon Daikin Europe N.V.. Daikin Europe N.V.
has compiled the content of this publication to the
best of its knowledge. No express or implied warranty
is given for the completeness, accuracy, reliability or
fitness for particular purpose of its content and the
products and services presented therein. Specifications
are subject to change without prior notice. Daikin
Europe N.V. explicitly rejects any liability for any direct
or indirect damage, In the broadest sense, arising from
or related to the use and/or interpretation of this
publication. All content is copyrighted by Daikin
Europe N.V.."
!""#"$%&'()*
VRV products are not within the scope of
the Eurovent certification programme.
Daikin equipment is designed for comfort
applications. For use in other applications,
please contact your local Daikin
representative.