You are on page 1of 2

THREE PHASE

FOUR WIRE
ELECTRONIC
ENERGY METER
CREATIVE ELECTRONICS (PVT) LTD
OFFICE & WORKS
Www.creative.com.pk
Creative Electronics Pvt Ltd
Plot # 476,Sundar Industrial Estate
Raiwind,Lahore
(Pakistan)
35298601-3 Ph: (92-42)
Three Phase fourwire connection.
3230/ 400V50 Hz 5(10)A
10000 impulse/kWh, 10000impulse/kvarh
Specification complies with WAPDA
standard and with the International
standard IEC 62052 for class 1, static
energy meters
Tempering information along with date
andtime stampis recorded
Works under individual phase failure and
records Acti ve, Reactive energi es
consumedcorrectly evenonlowvoltage.
All electronic design without any moving
parts.
Micro-processor based using advanced
technology for higher accuracy, reliability,
programming flexibility and upgrade
ability.
Built-inpowerline transient protection.
High frequency sampling to maintain
accuracy even with distorted line voltage
andcurrent.
Ideal for Commercial and Industrial
energy metering requirements
Zero reset-able for periodic energy
management.
Independent of mounting style/orientation
Not effectedbypartial orfullyearthedload
Not effectedbymagnetic tampering.
OPENED indication on the LCD in case of
MeterTopCoverOpening.
FEATURES
STATIC MULTI RATE 3 PHASE (T.O.U) ENERGY METER
10000 imp/kvarh 10000 imp/kWh
LT
Class: 2.0 Class: 1.0
3 X 230 / 400 V
3 X 5(10) A 50HZ YEAR
P.O. NO.:
Sr. No.
Warranty upto
CREATIVE ELECTRONICS PVT LTD
DISCO
MADE IN PAKISTAN
MODEL CE-17-01 YEAR 2014
STATIC MULTI RATE 3 PHASE (T.O.U) ENERGY METER
10000 imp/kvarh 10000 imp/kWh
LT
Class: 2.0 Class: 1.0
3 X 230 / 400 V
3 X 5(10) A 50HZ YEAR
P.O. NO.:
Sr. No.
Warranty upto
CREATIVE ELECTRONICS PVT LTD
DISCO
MADE IN PAKISTAN
MODEL CE-17-01 YEAR 2014
Date
TIME OF USE
A
B
C
D
SEASON T1 T2
1st December - End Feb.
1st March - 31st May
1st June - 31st August
1st September - 30th Nov.
17-21
18-22
19-23
18-22
21-17
22-18
23-19
22-18
(Peak Hours) (Off Peak Hours)
* Press upper scrolling button for 3sec to enter in ALTERNATE MODE.
Multiplying factor
For actual reading use the following Formula:
Actual Reading = Reading on LCD X (CT Ratio)
e.g. For 100/5 CT, CT Ratio is 20
LCD Reading is 10kWh
Actual Reading = 10 X (20) = 200 kWh
:
CODE: A0.01(20)
RAM self diagnose failure
Info flash diagnose failure
Flash self diagnose failure
FRAM self diagnose failure
1st EEPROM self diagnose failure
2nd EEPROM self diagnose failure
00000001
00000010
00000100
00001000
00010000
00100000
CODE: E0.01(19)
Error Description Error Code
1st EEPROM Failure 00000100
2nd EEPROM Failure 00001000
00001100
1st EEPROM &
2nd EEPROM Failure
ERRORS & CODES
CODE: A0.02(21)
Under Voltage
Over Voltage
Reverse Energy
Phase/Line Exchange
Bypass
Reverse Phase Sequence
Demand Overload
00000001
00000010
00000100
00001000
00010000
00100000
01000000
CODE: A0.03
Un-Programmed Meter 10000000
Total Average P.F of Prev 1 Month
Tariff 1 Average P.F of Prev 1 Month
Tariff 2 Average P.F of Prev 1 Month
TEST MODE
** In ALTERNATE MODE Press upper scrolling button for 3sec to
enter in TEST MODE.
*
**
1.
2.
3.
NORMAL MODE
ALTERNATE MODE
ALTERNATE MODE
No.
1.
2.
3.

You might also like