Question
After the installation of the latest RSLogix 5000 AOP for non-CIP drive, you could have the following problems:
Not able to choose the right revision of drive in Module Definition 1.
PowerFlex 755 High Power Drive shown as <Unknown> in the I/O Configuration 2.
Opening the properties of the Unknown module, you get the following error message:
Failed to Create Module Profile.
Module Profile Not Installed.
Error 8609-0
What can I do in this situation?
Answer
Installing the latest RSLogix 5000 Drive Add-On Profiles (non CIP Motion) will allow RSLogix 5000 to be able to add the module profile of the drive under I/O Configuration
especially newly released drives or communication modules.
Once completed the AOP installation, be sure that also the Drive Database installed in your PC is the right one. Go to ALLEN-BRADLEY WEB UPDATES, click on either
PowerFlex 753 or PowerFlex 755 which are under PowerFlex 750-Series Drives -> Dri veTool s SP / RSLogix5000 Dri ve Database Fi les -> click on the Drive Fi rmware and it
will install automatically.
Note: If the firmware revision still not available after the particular AOP of the drive firmware has been installed, try to close the RSLogix 5000 and start again, make sure the
Drive Communication Server and Drive Database Server also have been shut down too.
Figure 1. Drive Communication Server icon found on the Task Bar
Figure 2. Drive Database Server icon found on the Task Bar
Comments (0)
This answer has no comments
Post a Comment
Product Tree for This Answer (expand/collapse)

DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects.
Accordingly, the information in this web site is not intended to constitute application, design, software or other professional engineering advice or services. Before making any
decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor.
509821 PowerFlex 753 and 755 drive: AOP for non-CIP drive https://rockwellautomation.custhelp.com/app/answers/detail/a_id/509821
1 de 2 06/03/2014 22:29
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND
MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO
USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL,
LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.
ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE)
PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that
certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.
This page is best viewed in Internet Explorer 7, Firefox 3.5, Chrome 4, Safari 4 or newer.
509821 PowerFlex 753 and 755 drive: AOP for non-CIP drive https://rockwellautomation.custhelp.com/app/answers/detail/a_id/509821
2 de 2 06/03/2014 22:29

You might also like