You are on page 1of 11

Home Technical Articles Article Categories Contact us Subscribe to articles Subscribe to

downloads El. Enginering Guides


EE General guides
Power Substations
Schneider Electric CTs
Siemens Basics of EE
ABB Drives Guides
Industry Automation
Relay control/protection
Alternative Energy
Electrical Software MS Excel Spreadsheets Electrical Design Docs Engineering Resources
Video Lectures Electrical Engineering
PLC Programming Training
Electric Testing and Maintenance (VIDEO)
Network Theorems and Laws
-
Instrument transformers (CTs, VTs) in the
system
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
1 of 11 01/08/14 12:41 PM
Instrument transformers from ABB
Three main tasks of CTs and VTs
TThhee tthhrreeee mmaaiinn ttaasskkss ooff iinnssttrruummeenntt ttrraannssffoorrmmeerrss aarree::
To transform currents or voltages from a usually high value to a value easy to handle for
relays and instruments.
1.
To insulate the metering circuit from the primary high voltage system. 2.
To provide possibilities of standardizing the instruments and relays to a few rated currents
and voltages.
3.
Instrument transformers are special types of transformers intended to measure cur- rents and
voltages. The common laws for transformers are valid.
HHeerree wwee wwiillll ccoovveerr ssiixx iimmppoorrttaanntt aassppeeccttss ooff uussiinngg iinnssttrruummeenntt ttrraannssffoorrmmeerr iinn tthhee ppoowweerr ssyysstteemm::
Terminal designations for current transformers 1.
Secondary grounding of current transformers 2.
Secondary grounding of voltage transformers 3.
Connection to obtain the residual voltage 4.
Fusing of voltage transformer secondary circuits 5.
Location of current and voltage transformers in substations 6.
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
2 of 11 01/08/14 12:41 PM
Different substation arrangements
1. Terminal designations for current transformers
According to IEC publication 60044-1, the terminals should be designated as shown in the
following diagrams. All terminals that are marked P1, S1 and C1 are to have the same polarity.
Figure 1 left Transformer with one secondary winding; Figure 2 right Transformer with
two secondary windings
Figure 3 left Transformer with one secondary winding which has an extra tapping; Figure 4
right Transformer with two primary windings and one secondary winding
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
3 of 11 01/08/14 12:41 PM
Go back to main aspects !
2. Secondary grounding of current transformers
To prevent the secondary circuits from attaining dangerously high potential to ground, these
circuits have to be grounded. Connect either the S1 terminal or the S2 terminal to ground.
For protective relays, ground the terminal that is nearest to the protected objects. For meters and
instruments, ground the terminal that is nearest to the consumer.
WWhheenn mmeetteerriinngg iinnssttrruummeennttss aanndd pprrootteeccttiivvee rreellaayyss aarree oonn tthhee ssaammee wwiinnddiinngg,, tthhee pprrootteeccttiivvee rreellaayy
ddeetteerrmmiinneess tthhee ppooiinntt ttoo bbee ggrroouunnddeedd..
If there are unused taps on the secondary winding, they must be left open.
If there is a galvanic connection between more than one current transformer, these shall
be grounded at one point only (e.g. differential protection).
If the cores are not used in a current transformer they must be short-circuited be- tween
the highest ratio taps and shall be grounded.
It is dangerous to open the secondary circuit when the CT is in operation. High voltage will be
induced.
Figure 5 left Transformer; Figure 6 right Cables
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
4 of 11 01/08/14 12:41 PM
Figure 7 Busbars
Go back to main aspects !
3. Secondary grounding of voltage transformers
To prevent secondary circuits from reaching dangerous potential, the circuits shall be
grounded. Grounding shall be made at only one point on a voltage transformer secondary
circuit or galvanically interconnected circuits.
A voltage transformer, which on the primary is connected phase to ground, shall have the
secondary grounding at terminal n.
A voltage transformer, with the primary winding connected between two phases, shall have the
secondary circuit, which has a voltage lagging the other terminal by 120 degrees, grounded.
Windings not in use shall be grounded.
Figure 8 Voltage transformers connected between phases
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
5 of 11 01/08/14 12:41 PM
Figure 9 set of voltage transformers
Go back to main aspects !
4. Connection to obtain the residual voltage
The residual voltage (neutral displacement voltage, polarizing voltage) for earth-fault relays can be
obtained from a voltage transformer between neutral and ground, for instance at a power
transformer neutral.
It can also be obtained from a three-phase set of voltage transformers, which have their primary
winding connected phase to ground and one of the secondary windings connected in a broken delta.
Figure 10 illustrates the measuring principle for the broken delta connection during an
earth-fault in a high-impedance grounded (or ungrounded) and an effectively grounded power
system respectively.
From the figure, it can be seen that a solid close-up earth-fault produces an output voltage of
U
rsd
= 3 x U
2n
in a high-impedance earthed system and
U
rsd
= U
2n
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
6 of 11 01/08/14 12:41 PM
in an effectively grounded system. Therefore a voltage transformer secondary voltage of
U
2n
= 110 / 3 V
is often used in high-impedance grounded systems and U
2n
= 110 V in effectively grounded
systems. A residual voltage of 110 V is obtained in both cases. Voltage transformers with two
secondary windings, one for connection in Y and the other in broken delta can then have the
ratio:
for high-impedance and effectively grounded systems respectively. Nominal
voltages other than 110 V, e.g. 100 V or 115 V, are also used depending on
national standards and practice.
Figure 10 Residual voltage (neutral displacement voltage) from a
broken delta circuit
5. Fusing of voltage transformer secondary
circuits
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
7 of 11 01/08/14 12:41 PM
Fuses should be provided at the first box where the three phases are brought together. The
circuit from the terminal box to the first box is constructed to minimize the risk of faults in the
circuit.
It is preferable not to use fuses in the voltage transformer terminal box, as this will make
the supervision of the voltage transformers more difficult. The fuses in the three-phase box
enable a differentiated fusing of the circuits to different loads like protection and metering
circuits.
The fuses must be selected to give a fast and reliable fault clearance, even for a fault at the end
of the cabling. Earth faults and two-phase faults should be checked.
Go back to main aspects !
6. Location of current and voltage transformers in substations
Instrument transformers are used to supply measured quantities of current and voltage in an
appropriate form to controlling and protective apparatus, such as energy meters, indicating
instruments, protective relays, fault locators, fault recorders and synchronizers.
Instrument transformers are thus installed when it is necessary to obtain measuring quantities for
the above mentioned purposes.
Read more // Location of Current Transformers in HV Substation
Typical points of installation are switchbays for lines, feeders, transformers, bus couplers, etc., at
transformer neutral connections and at the busbars.
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
8 of 11 01/08/14 12:41 PM
Figure 11 Current and voltage transformers in a substation
Go back to main aspects !
Location in different substation arrangements
Below are some examples of suitable locations for current and voltage transformers in a few
different switchgear arrangements.
Figure 12 Double busbar station
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
9 of 11 01/08/14 12:41 PM
Figure 13 Station with transfer busbar
Figure 14 Double breaker and double busbar station
Figure 15 Sectionalized single busbar station
Go back to main aspects !
RReeffeerreennccee:: Instrument Transformers Application Guide ABB
Recommended EE articles
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
10 of 11 01/08/14 12:41 PM
Edvard - Electrical engineer, programmer and founder of EEP. Highly
specialized for design of LV high power busbar trunking (<6300A) in power
substations, buildings and industry fascilities. Designing of LV/MV switchgears.
Professional in AutoCAD programming and web-design. Present on Google+.
2014 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | 30 queries in
0.252 seconds.
Powered by CsanyiGroup
SHARE
TOP
Get
PDF
Instrument transformers (CTs, VTs) in the system | EEP http://electrical-engineering-portal.com/instrument-transforme...
11 of 11 01/08/14 12:41 PM

You might also like