You are on page 1of 6

10

Electric Power Quality

Gerald T. Heydt 10.1 Definition ......................................................................................... 805


Department of Electrical Engineering, 10.2 Types of Disturbances ......................................................................... 805
Arizona State University,
10.3 Measurement of Electric Power Quality ................................................. 805
Tempe, Arizona, USA
10.4 Instrumentation Considerations ........................................................... 808
10.4.1 A d v a n c e d I n s t r u m e n t a t i o n
10.5 Analysis Techniques ............................................................................ 809
10.6 Nomenclature .................................................................................... 809
References ......................................................................................... 810

10.1 Definition of time (and is often periodic) and the transient. The latter
generally exists for a few milliseconds, and then decays to zero.
There is no single acceptable definition of the term electric Controversy surrounds which is more important, and a case
power quality. The term generally applies to the goodness of could be made for either type of disturbance being more prob-
the electric power supply, its voltage regulation, its frequency, lematic as far as cost. The steady-state type of disturbance is
voltage wave shape, current wave shape, level of impulses and generally less evident in its appearance, often at lower voltage
noise, and the absence of momentary outages. Some engineers and current levels, and less harmful to the operation of the
include reliability considerations in electric power quality stud- system. Because steady-state phenomena last for a long period
ies, some consider electromagnetic compatibility, and some per- of time, the integrated effects of active power losses (low or high
form generation supply studies. Narrower definitions of electric voltage) and inaccurate timing signals may be quite costly. Tran-
power quality generally focus on the bus voltage wave shape. sient effects tend to be higher level in amplitude and are often
Electric power quality studies generally span the entire elec- quite apparent in harmful effects as well as occasionally spec-
trical system, but the main points of emphasis are in the tacular in cost (e.g., causing loss of a manufactured product or
primary and secondary distribution systems. This is the case causing long-term outages). The cost of transient power quality
because loads generally cause distortion of bus voltage wave problems has been estimated in the 100 million to 3 billion dollar
shape, and this distortion is mainly noted near the source of range annually in the United States. Table 10.2 lists some types of
the difficulty--namely near the load--in the secondary distri- steady-state and transient power quality problems. The transient
bution system. Because the primary distribution system is problems are often termed e v e n t s .
closely coupled to the secondary system and the load, which
is sometimes served directly by the primary distribution
system, the primary network is also a point of focus. Trans- 10.3 Measurement of Electric
mission and generation systems are also studied in certain
types of power quality evaluation and analyses. Table 10.1
Power Quality
shows the main points in electric power quality.
Many indices have been developed for the specification of
electric power quality. A few are listed in Table 10.3. The
10.2 Types of Disturbances most widely used index of power quality is the total harmonic
distortion, which is an index that compares the intensity of
There are two main classes of electric power quality distur- harmonic signals in voltages and currents to the fundamental
bances: the steady-state disturbance that lasts for a long period component. The main indices are as follows:

Copyright © 2005 by Academic Press. 805


All rights of reproduction in any form reserved.
806 Gerald T. Hey&

TABLE 10.1 Electric Power Quality Considerations

Consideration Focus Comments

Region of analysis • Distribution systems The main region of analysis is the primary and secondary
• Points of utilization of electric power distribution system. This is where nonsinusoidal waves
• Transmission systems are most prevalent and of greatest amplitude.
• Electromagnetic compatibility
Types of problems • Harmonics There is a controversy concerning whether momentary low
• Momentary outages and low voltages voltages (sags) or harmonics are the most problematic in
(sags) terms of cost of the problem.
Analysis methods • Circuit analysis programs A range of commercial software is available for both smaller
• Harmonic power flow studies and larger studies. Many software tools are linked to
• Focused studies on particular events using elaborate graphics. Most methods are data intensive and
circuit theory to obtain solution approximate.
• Pspice
Mitigation techniques • Filters Mitigation techniques are often customized to the particular
• Capacitors problem and application. In general, higher pulse order
• Problematic loads systems give much less problem than single-phase and
• Higher pulse order (e.g., twelve-pulse six-pulse, three-phase systems.
rather than six-pulse systems)

TABLE 10.2 Power Quality Problems

Type Problem Appearance Causes

Transient system Impulses (surges, High-voltage impulse for a short time, typically in the • Lightning
problems pulses) microsecond to 1 ms range • Switching surges
• Rejection of inductive loads
Momentary outages Collapse of ac supply voltage for up to a few (e.g., 20) cycles Circuit breaker operations
Phase shift Sinusoidal supply voltage proportional to a sine function Faults
whose phase angle suddenly shifts by an angle q~
Sags (low voltage) Momentary low voltage caused by faults in the supply Faults
Ringing Damped sinusoidal voltages impressed on the Capacitor switching
ac wave

Steady-state Harmonics Integer multiples of the ac supply frequency (e.g., 60 Hz) of • Nonlinear loads
system (usually) lower amplitude signals impressed on the power • Adjustable speed drives
problems frequency wave • Rectifiers
• Inverters
• Fluorescent lamps
Voltage notches Momentary low voltages of duration much shorter than one Adjustable speed drives
cycle caused by commutated loads
Noise Noise impressed on the power frequency • Static discharge and corona
• Arc furnaces
Radio frequency High-frequency (e.g., f > 500 kHz) sinusoidal signals Radio transmitters
of typically low amplitude impressed on the power
frequency
Interharmonics and Components of noninteger multiples of the power • Cycloconverters
fractional frequency • Kramer drives
harmonics • Certain types of adjustable
speed drives

• P o w e r f a c t o r : T h e r e l a t i o n s h i p o f p o w e r f a c t o r to t h e d i s t r i b u t i o n systems, is well k n o w n . M a n y electric utilities


IEEE S t a n d a r d 519-1992, especially w i t h r e g a r d to t h e h a v e limits to t h e p o w e r factor o f c o n s u m e r loads, b u t
failure o f t h e p o w e r f a c t o r to register h a r m f u l a n d u n - t h e r e m a y n o t b e a clear d e f i n i t i o n o f p o w e r factor for t h e
d e s i r a b l e effects o f h i g h - f r e q u e n c y h a r m o n i c s in p o w e r n o n s i n u s o i d a l case. I n p a r t i c u l a r , m a n y electric utilities
10 Electric Power Quality 807

TABLE 10.3 Voltage Measurement

Instrument Configuration Application considerations

Potential transformer (PT) Energized at full line potential on the high side and typically in the • Bandwidth of the PT
100-V range on the low side • Safety (e.g., upon failure of the PT)
• Turns ratio, accuracy
Voltmeters Energized directly or through a probe • Isolation from the line
• Bandwidth
• True RMS reading questioned
• Accuracy
Voltage divider Energized at full line potential at the upper resistor; resistive voltage • Safety (e.g., opening of low end of string)
divider used to give low voltage at the low end of the string • Heat loss
Capacitively coupled voltage Capacitive voltage divider energized at full line potential at upper • Bandwidth
transformer end; instrument transformer used to obtain some isolation • Resonance of the capacitors and transformer
• Accuracy
• Frequency dependence

do not distinguish between displacement of the power • K-factor: Explanation of the use of the K-factor to derate
factor (i.e., the cosine between the voltage and current transformers that are expected to carry nonsinusoidal
phasors at the fundamental frequency) and the power load currents has been used, and an alternative calcula-
factor defined in Table 10.4. The term t r u e p o w e r factor tion of this index in the time domain has been shown.
has been used by some to refer to P/] V] ]It, but the IEEE • F l i c k e r factor: This flicker factor index has been used in
Standard 100 used the term power factor for this ratio, connection with electric arc furnaces for the purpose of
and this simpler term is used in this chapter. quantifying the load impact on the power system.
• Total h a r m o n i c d i s t o r t i o n : The use of the total harmonic
distortion (THD) is perhaps the most widespread power Perhaps the main application of power quality indices has
quality index, and many electric utilities have adopted a been in guides, recommended practices, and standards. As
THD-based measure of the limits of customer load cur- an example, the IEEE Standard 519-1992 contains an often
rents. cited limit to harmonic load currents and voltages. The ANSI

TABLE 10.4 C o m m o n Power Quality Indices

Index Definition Main applications

Total harmonic distortion ( T H D ) ( ~ / I 1 General purpose; standards

Power factor (PF) Ptot/I VrmsHIrmsI Potentially in revenue metering

Telephone influence factor Irrns Audio circuit interference

C message index (~)/Irms Communications interference

Audio circuit interference, shunt capacitor stress

VTproduct / ~ w ? , V2
~/Z-~ Voltage distortion index
V i=l

K factor h2l2 / Z I 2 Transformer derating


h=l h=l

Crest factor Vpeak/ Vrms Dielectric stress


Unbalance factor ]~ [/I V+l Three-phase circuit balance
Flicker factor A g /I g I Incandescent lamp operation, bus voltage
regulation, sufficiency of short circuit capacity
Total demand distortion (TDD) THD*(fundamental current/circuit rating) In IEEE Standard 519
808 Gerald T. Heydt

Standard 368 contains a well-quoted guide on limits of the IT of these devices is often not much larger than 60 Hz (in 60-Hz
product. The Underwriters Laboratories applies the K-factor systems). Harmonics may be attenuated by the current or
to the specification of transformers that carry nonsinusoidal potential transformer, and this adds intolerable error to the
load currents. measurement. Relaying grade current and relaying potential
transformers are usually not much better because of limited
bandwidth. Revenue meter grade current and voltage trans-
10.4 Instrumentation Considerations formers are generally not designed for high bandwidth appli-
cations. Laboratory grade transformers are usually the best
Because power quality is often stated in terms of voltages and choice. Modern power quality instruments generally have
currents, the main instrumentation needed to assess power companion current and voltage transformers for use with a
quality relates to bus voltages and line and load currents. In given instrument, and the manual for the instrument will
terms of voltages, usually bus voltages are measured using contain the bandwidth measurement of the transformers. It
potential transformers because isolation from the power cir- is noted that for many voltage and current instruments used in
cuit is desirable and because power system voltages are usually power quality tests, current and voltage transformers are the
too high to measure directly. Typical potential transformers are most costly components of the instrumentation system.
capable of bringing circuit voltages (e.g., in the 440-7200V Modern power quality assessment often involves more than
range for distribution circuits and up to 40kV for subtrans- voltage and current measurement. The following are also part
mission circuits) to about 110 V. These potential transformers of the test regimen in most cases:
must have the proper bandwidth to "see" the desired voltages
• Event measurement (i.e., measurement of three-phase
to be instrumented (e.g., harmonic voltages), they must have
voltages and currents, plus neutral ground voltage and
the proper dynamic range to allow measurement of the volt-
neutral current versus time)
age, and they must have isolation suitable for safety. Some
• On-board evaluation of harmonics (of voltages and cur-
voltage measurement instruments are listed in Table 10.3.
rents, often plotted versus time)
Current instrumentation is analogous to voltage measure-
• Measurement of active and reactive power
ment with the replacement of the current transformer for the
• Measurement of total harmonic distortion
potential transformer. Main considerations are appropriate-
• Measurement of active power loss in a system component
ness of the current ratio in the current transformer, isolation
• Assessment of high-frequency effects
for safety, loading with the proper current transformer burden,
• Measurement of rise time
and bandwidth and dynamic range of the current transformer.
• Oscillograph capability (often written digitally to a disk
Table 10.5 shows some of the basic instruments used in current
for subsequent analysis and report writing)
instrumentation.
• Energy measurement.
Both current and voltage transformers are available in sev-
eral grades. General purpose transformers are not generally Table 10.6 illustrates a few of these capabilities in commer-
usable for power quality measurements because the bandwidth cial instruments in use for power quality assessment.

TABLE 10.5 Current Instrumentation

Instrument Configuration Application considerations

Current transformer (CT) Placed around the conductor to be • Bandwidth


instrumented • Safety
• Operation with correct CT burden
Resistive shunt for current Resistor in series with load to be • No ohmic isolation
measurement instrumented • Accuracy
• Heating of the shunt
Ammeter Placed in series with circuit to be • Accuracy
instrumented • Bandwidth
• Safety--no ohmic isolation for circuit
Optical instruments Rotation of plane of polarized light in • Accuracy
a fiber-optic cable around or near • Vibration sensitivity
the instrumented circuit • Cost
Hall-effect device Measurement of magnetic field near • Accuracy
instrumented conductor • Bandwidth
• Vibration and mechanical placement sensitivity
• Linearity
10 Electric Power Quality 809

TABLE 10.6 Power Quality Assessment Instruments

Instrument Typical capability Bandwidth Dynamic range

Digital fault recorder Measurethree-phase voltage and current; perform basic analysison Typicallyto about 3000Hz At least 80 db, possibly 100 db
(DFR) these data; measure digital output
Power quality node Commercializedevent recorder for distribution system Typicallyto about 3000 Hz About 80 db
instrumentation and field rugged, and telephone interrogations
Event recorder, digital Oscilloscopefunctions, digital readout, basic analysis functions, Varies widely--possibly into About 100 db
oscilloscope signal triggers recording the megahertz range

10.4.1 Advanced I n s t r u m e n t a t i o n formulas that may be applied to solve problems. One particu-
larly useful set of formulas is the ideal rectifier set of formulas
In the preceding section, several basic voltage and current
shown in Table 10.8. Rectifier loads are a main source o f
measurement instruments were discussed. Because power
harmonic load currents. The ideal rectifier formulas give the
quality measurements are often demanding in bandwidth
various interrelationships of voltage and current parameters
and dynamic range, several types of advanced instrumentation
for the idealized case of no rectifier power loss and very high
techniques have been studied and developed for this applica-
dc side inductance. These formulas, while useful, should be
tion. A few are listed in Table 10.7.
used with caution because the assumptions made in arriving
at these formulas are all idealizations. Note that the displace-
ment factor is the cosine of the angle between fundamental
10.5 Analysis Techniques voltage and fundamental current. The power factor is the ratio
P/VrmsIrms •
The main analytical techniques for power quality studies are
the following:

• Power flow studies


10.6 Nomenclature
• Injection current analysis
C-message weight
• Simulation methods, such as Pspice and EMTP Ch
C o m p u t e r Business Equipment Manufacturers
• Direct circuit analysis CBEMA
Association
Power flow studies are software tools that rely on steady- CT current transformer
state operation of the system to be studied. These software DF displacement factor
tools use input data such as load type, load level (P, Q), and DPF displacement power factor
circuit data (e.g., impedance, connection diagram). The out- EPRI Electric Power Research Institute
p u t is typically all nodal voltages and all line currents at all IEC International Electrotechnical Commission
frequencies. IT c u r r e n t - - t e l e p h o n e influence factor product, read
Injection current analysis is the analysis of how currents as IT product
injected into a system propagate. This is a simplified form of Ih, Vh harmonic components of current i(t) and v(t)
power flow study. K K-factor
Power quality engineering m a y be taken to be a specialized kiT thousands of IT units
branch of signal analysis. In this regard, there are many useful kVT thousands of VT units

TABLE10.7 Advanced and Unconventional Instrumentation for Electric Power Quality Assessment
Basic instrumentation technique Basis Application

Poeckels effect Rotation of the plane of polarized light in a medium Wideband measurement of voltage
due to electric field strength
Faraday rotation effect Rotation of the plane of polarized light in a medium Wideband measurement of current
due to magnetic field strength
Hall effect Variation of the resistance of a material in a Wideband measurement of current
magnetic field
Global Positioning System (GPS) Triangular spotting of four or more artificial earth Accurate time tagging of measurements,
applications satellitesto obtain time and position of a receiver phasor measurements
810 Gerald T. Heydt

TABLE 10.8 The Ideal Rectifier Formulas )tot total active power (for all h a r m o n i c s )
PCC p o i n t of c o m m o n c o u p l i n g
Single-phase bridge rectifiers
PF power factor
Line commutated: PT potential transformer
Infinite dc inductance Vac = 2 ~ Vac
"iT SCR short circuit ratio
Zero supply inductance
lac, fundamental = 2 ~ ldc rms root m e a n square value ¢ - ~ ~ f 2 ( t ) d t
"iT
/supply, h = [ac, fundamental/h
THDI = 48.4% T period of a periodic wave; time h o r i z o n u n d e r
Displacement factor = DF = 1.0 study for a n aperiodic wave
Displacement power factor = DPF 2x/2 TDD total d e m a n d distortion
'IT
THD total h a r m o n i c distortion
P& = Pac = 2x/2 V~,,~s Idc TIF telephone influence factor
"iT
v+, v_ positive a n d negative sequence c o m p o n e n t s of a
2toIa,Ls
Line commutated: cos(u)= 1 - - - sinusoidal three-phase voltage
Infinite dc inductance Hvs VT v o l t a g e - - t e l e p h o n e influence factor product, read
Nonzero supply V& = 2x/2 Vs - 2coLslacc
'Tr "iT
as VT p r o d u c t
inductance
DF ~ cos (u/2) Wh telephone influence factor weight
P = Vslac,fund.... tal*DF = V&Idc
2o~LsI& References
Forced commutated: cos (ix + u) = cos (ix) - - -
Infinite dc inductance vs~ Arrillaga, ]. (1985). Power system harmonics. New York: John Wiley &
U
Nonzero supply DPF = cos(ix + 5 ) Sons.
inductance 2~oLs I 2 Bollen, M.H.]. (2000). Understanding power quality problems: Voltage
GId~ cos (ix) - ~ - - dc
/supply, fundamental sags and interruptions. New York: IEEE.
v~cos(ix + ~) Dugan, R.C., McGranaghan, M.F., and Beaty, H.W. (1996). Electrical
Vdc = 2X/2 Vs cos (ix) - Z--wLslac power systems quality. New York: McGraw-Hill.
"iT qT
Hey&, G. (1995). Electric power quality. Scottsdale, AZ: Stars in a
Three-phase bridge rectifiers (six pulse) Circle.
IEEE. (1986). IEEE Standard C57.110-1986, IEEE recommended
Line commutated: V& = 3__x/2VtL practice for establishing transformer capability when supplying
Infinite dc inductance 7r nonsinusoidal load currents. New York.
Zero supply inductance I,, rms = x / ~ l a c
IEEE. (1997a). IEEE Standard 368-1977, IEEE recommended prac-
•supply, fundamental ~ ~ Idc tice for measurement of electrical noise and harmonic filter
DF = 1.00 performance of high-voltage direct-current systems. New York.
DPF = 3/~ IEEE. (1997b).
THDI = 31.1% (harmonics 5, 7, 11.... ) IEEE. (1992a). IEEE Standard 1100, IEEE recommended practice for
powering and grounding sensitive electronic equipment. New York.
Line commutated: Vat = 3x/2 VLL -- 3o~LsIac IEEE. (1992b). IEEE Standard 519-1992, IEEE recommended prac-
T¢ 7r
Infinite dc inductance tices and requirements for harmonic control in electrical power
2o3Lsl&
Nonzero supply cos (u) = 1 - x/2VL~ systems. New York.
inductance Kennedy, B.W. (2000). Power quality primer. New York: McGraw-Hill.
DF cos (u/2) Porter, G., and Van Sciver, J.A. (1998). Power quality solutions: Case
P = x/ 3VLLl suppl y, fund . . . . tal studies for troubleshooters. Lilburn, GA: Fairmont Press.
*cos (u/2) = Vacldc Power Quality Assurance Magazine,
http://industrycfick.com/magazine.asp?magazineid=286&siteid=13
Forced commutated: V& = 3x/2 VLL COS (0~) -- 3o~LsIac
Shepherd, W., and Zand, E (1979). Energy flow and power factor in
Infinite dc inductance w "~
nonsinusoidal circuits. Cambridge: Cambridge University.
Nonzero supply cos (ix + u) = cos (ix) - 2~oLsId~
inductance "~VLL
U
DPF ~ cos(ix +~-)

You might also like