You are on page 1of 494

MiCOM

C264/C264C
Bay Computer

Technical Guide
C264/EN T/C30


Technical Guide C264/EN T/C30

MiCOM C264/C264C

Page 1/2

MiCOM C264/C264C
BAY COMPUTER
CONTENT
Safety & Handling C264/EN SA/C30
Introduction C264/EN IT/C30
Technical data C264/EN TD/C30
Functional Description C264/EN FT/C30
Hardware Description C264/EN HW/C30
Connection C264/EN CO/C30
Installation C264/EN IN/C30
Settings C264/EN ST/C30
Communications C264/EN CT/C30
Commissioning C264/EN CM/C30
Commissioning Record Sheet C264/EN RS/C30
Maintenance C264/EN MF/C30
Lexical C264/EN LX/C30
C264/EN T/C30 Technical Guide

Page 2/2

MiCOM C264/C264C

BLANK PAGE
Safety & Handling C264/EN SA/C30

MiCOM C264/C264C


SAFETY & HANDLING
Safety & Handling C264/EN SA/C30

MiCOM C264/C264C

Page 1/12

CONTENT
1. INTRODUCTION 3

2. HEALTH AND SAFETY 4
2.1 Health and Safety 4
2.2 Installing, Commissioning and Servicing 4
3. DECOMMISSIONING AND DISPOSAL 6

4. TECHNICAL SPECIFICATIONS FOR SAFETY 7

5. HANDLING OF ELECTRONIC EQUIPMENTS 8

6. PACKING AND UNPACKING 9

7. GUARANTEES 10

8. COPYRIGHTS & TRADEMARKS 11
8.1 Copyrights 11
8.2 Trademarks 11
9. WARNINGS REGARDING USE OF AREVA T&D EAI PRODUCTS 12

C264/EN SA/C30 Safety & Handling

Page 2/12

MiCOM C264/C264C

BLANK PAGE
Safety & Handling C264/EN SA/C30

MiCOM C264/C264C

Page 3/12

1. INTRODUCTION
This document is a chapter of the MiCOM C264/C264C documentation binder. It describes
the safety, handling, packing and unpacking procedures applicable to MiCOM C264/C264C
modular computer series and associated equipment's and software tools.
C264/EN SA/C30 Safety & Handling

Page 4/12

MiCOM C264/C264C

2. HEALTH AND SAFETY
For all the safety purposes please refer to the AREVA T&D Safety Guide: SFTY/4L M/F11
(or later issue) and to the following chapters.
WARNING: THIS SAFETY SECTION SHOULD BE READ BEFORE COMMENCING
ANY WORK ON THE EQUIPMENT.
2.1 Health and Safety
The information in the Safety Section of the product documentation is intended to ensure
that products are properly installed and handled in order to maintain them in a safe condition.
It is assumed that everyone who will be associated with the equipment will be familiar with
the contents of the Safety Section.
2.2 Installing, Commissioning and Servicing
Equipment connections
Personnel undertaking installation, commissioning or servicing work on this equipment
should be aware of the correct working procedures to ensure safety. The product
documentation should be consulted before installing, commissioning or servicing the
equipment.
Terminals exposed during installation, commissioning and maintenance may present a
hazardous voltage unless the equipment is electrically isolated.
If there is unlocked access to the rear of the equipment, care should be taken by all
personnel to avoid electrical shock or energy hazards.
Voltage and current connections should be made using insulated crimp terminations to
ensure that terminal block insulation requirements are maintained for safety. To ensure that
wires are correctly terminated the correct crimp terminal and tool for the wire size should be
used.
Before energising the equipment it must be earthed using the protective earth terminal, or
the appropriate termination of the supply plug in the case of plug connected equipment.
Omitting or disconnecting the equipment earth may cause a safety hazard.
The recommended minimum earth wire size is 2.5mm, unless otherwise stated in the
technical data section of the product documentation.
When the protective (earth) conductor terminal (PCT) is also used to terminate cable
screens, etc., it is essential that the integrity of the protective (earth) conductor is checked
after the addition or removal of such functional earth connections.
For M4 stud PCTs the integrity of the protective (earth) connection should be ensured by use
of a locknut or similar."
Before energising the equipment, the following should be checked:
Voltage rating and polarity;
CT circuit rating and integrity of connections;
Integrity of earth connection (where applicable)
Note: The term earth used throughout the product documentation is the direct equivalent of
the North American term ground.
Equipment operating conditions
The equipment should be operated within the specified electrical and environmental limits.
Current transformer circuits
Do not open the secondary circuit of a live CT since the high level voltage produced may be
lethal to personnel and could damage insulation.
Safety & Handling C264/EN SA/C30

MiCOM C264/C264C

Page 5/12

Insulation and dielectric strength testing
Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of
each part of the test, the voltage should be gradually reduced to zero, to discharge
capacitors, before the test leads are disconnected.
Insertion of modules and boards
These must not be inserted into or withdrawn from equipment whist it is energised since this
may result in damage.
Fibre optic communication
Where fibre optic communication devices are fitted, these should not be viewed directly.
Optical power meters should be used to determine the operation or signal level of the device.
C264/EN SA/C30 Safety & Handling

Page 6/12

MiCOM C264/C264C

3. DECOMMISSIONING AND DISPOSAL
Decommissioning:
The auxiliary supply circuit in the MiCOM computers may include capacitors across the
supply or to earth. To avoid electric shock or energy hazards, after completely isolating the
supplies to the MiCOM computers (both poles of any dc supply), the capacitors should be
safely discharged via the external terminals prior to decommissioning.
Disposal:
It is recommended that incineration and disposal to watercourses be avoided. The product
should be disposed of in a safe manner. Any products containing batteries should have them
removed before disposal, in order to avoid short circuits. Particular regulations within the
country of operation may apply to the disposal of lithium batteries.
Safety & Handling C264/EN SA/C30

MiCOM C264/C264C

Page 7/12

4. TECHNICAL SPECIFICATIONS FOR SAFETY
The recommended maximum rating of the external protective fuse for this equipment is 16A,
High rupture capacity (HRC) Red Spot type NIT or TIA, or equivalent unless otherwise
stated in the technical data section of the product documentation. The protective fuse should
be located as close to the unit as possible.
1. Fuse rating is dependent of auxiliary voltage and circuit loading.
2. Differential protective switch on DC power supply is recommended.
3. Differential protective switch on AC power supply is mandatory (printers, PACiS
workstation).
Protective class: IEC 60255-27:

2005

Class I This equipment requires
a protective (safety)
earth connection to
ensure user safety.
Installation
Category:
IEC 60255-27:
EN 60255-27:

2005
2006


Installation Category III
Distribution level, fixed
installation.
Equipment in this
category is qualification
tested at 5kV peak,
1.2/50s, 500. 0.5J,
between all supply
circuits and earth and
also between
independent circuits.
Environment: IEC 60255-27:
Pollution degree 2
EN 60255-27:
2005

2006

Compliance is
demonstrated by
reference to safety
standards.
Product Safety: 73/23/EEC Compliance with the
European Commission
Low Voltage Directive.


C264/EN SA/C30 Safety & Handling

Page 8/12

MiCOM C264/C264C

5. HANDLING OF ELECTRONIC EQUIPMENTS
A persons normal movements can easily generate electrostatic potentials of several
thousand volts.
Discharge of these voltages into semiconductor devices when handling circuits can cause
serious damage, which often may not be immediately apparent but the reliability of the circuit
will have been reduced.
The electronic circuits of AREVA T&D Energy Automation & Information products are
immune to the relevant levels of electrostatic discharge when housed in their cases. Do not
expose them to the risk of damage by withdrawing modules unnecessarily.
Each module incorporates the highest practicable protection for its semiconductor devices.
However, if it becomes necessary to withdraw a module, the following precautions should be
taken in order to preserve the high reliability and long life for which the equipment has been
designed and manufactured.
1. Before removing a module, ensure that you are a same electrostatic potential as the
equipment by touching the case.
2. Handle the module by its front-plate, frame, or edges of the printed circuit board. Avoid
touching the electronic components, printed circuit track or connectors.
3. Do not pass the module to any person without first ensuring that you are both at the
same electrostatic potential. Shaking hands achieves equipotential.
4. Place the module on an antistatic surface, or on a conducting surface, which is at the
same potential as you.
5. Store or transport the module in a conductive bag.
More information on safe working procedures for all electronic equipment can be found in
IEC 60147-0F and BS5783.
If you are making measurements on the internal electronic circuitry of any equipment in
service, it is preferable that you are earthen to the case with a conductive wrist strap.
Wrist straps should have a resistance to ground between 500k 10M Ohms. If a wrist strap
is not available you should maintain regular contact with the case to prevent the build up of
static. Instrumentation which may be used for making measurements should be earthen to
the case whenever possible.
AREVA T&D Energy Automation & Information strongly recommends that detailed
investigations on the electronic circuitry, or modification work, should be carried out in a
Special Handling Area such as described in IEC 60147-0F or BS5783.
Safety & Handling C264/EN SA/C30

MiCOM C264/C264C

Page 9/12

6. PACKING AND UNPACKING
All MiCOM C264/C264C computers are packaged separately in their own cartons and
shipped inside outer packaging. Use special care when opening the cartons and unpacking
the device, and do not use force. In addition, make sure to remove from the inside carton the
supporting documents supplied with each individual device and the type identification label.
The design revision level of each module included with the device in its as-delivered
condition can be determined from the list of components. This list should be carefully saved.
After unpacking the device, inspect it visually to make sure it is in proper mechanical
condition.
If the MiCOM C264/C264C computer needs to be shipped, both inner and outer packaging
must be used. If the original packaging is no longer available, make sure that packaging
conforms to ISO 2248 specifications for a drop height 0.8m.
C264/EN SA/C30 Safety & Handling

Page 10/12

MiCOM C264/C264C

7. GUARANTEES
The media on which you received AREVA T&D EAI software are guaranteed not to fail
executing programming instructions, due to defects in materials and workmanship, for a
period of 90 days from date of shipment, as evidenced by receipts or other documentation.
AREVA T&D EAI will, at its option, repair or replace software media that do not execute
programming instructions if AREVA T&D EAI receive notice of such defects during the
guaranty period. AREVA T&D EAI does not guaranty that the operation of the software shall
be uninterrupted or error free.
A Return Material Authorisation (RMA) number must be obtained from the factory and clearly
marked on the package before any equipment acceptance for guaranty work. AREVA T&D
EAI will pay the shipping costs of returning to the owner parts, which are covered by
warranty.
AREVA T&D EAI believe that the information in this document is accurate. The document
has been carefully reviewed for technical accuracy. In the event that technical or
typographical errors exist, AREVA T&D EAI reserves the right to make changes to
subsequent editions of this document without prior notice to holders of this edition. The
reader should consult AREVA T&D EAI if errors are suspected. In no event shall AREVA
T&D EAI be liable for any damages arising out of or related to this document or the
information contained in it.
Expect as specified herein, AREVA T&D EAI makes no guaranties, express or implied and
specifically disclaims and guaranties of merchantability or fitness for a particular purpose.
Customer's rights to recover damages caused by fault or negligence on the part AREVA
T&D EAI shall be limited to the amount therefore paid by the customer. AREVA T&D EAI will
not be liable for damages resulting from loss of data, profits, use of products or incidental or
consequential damages even if advised of the possibility thereof. This limitation of the liability
of AREVA T&D EAI will apply regardless of the form of action, whether in contract or tort,
including negligence. Any action against AREVA T&D EAI must be brought within one year
after the cause of action accrues. AREVA T&D EAI shall not be liable for any delay in
performance due to causes beyond its reasonable control. The warranty provided herein
does not cover damages, defects, malfunctions, or service failures caused by owner's failure
to follow the AREVA T&D EAI installation, operation, or maintenance instructions. Owner's
modification of the product; owner's abuse, misuse, or negligent acts; and power failure or
surges, fire, flood, accident, actions of third parties, or other events outside reasonable
control.
Safety & Handling C264/EN SA/C30

MiCOM C264/C264C

Page 11/12

8. COPYRIGHTS & TRADEMARKS
8.1 Copyrights
Under the copyright laws, this publication may not be reproduced or transmitted in any form,
electronic or mechanical, including photocopying, recording, storing in an information
retrieval system, or translating, in whole or in part, without the prior written consent of
AREVA T&D EAI.
8.2 Trademarks
PACiS, PACiS SCE, PACiS ES, PACiS CMT, PACiS SMT, PACiS PS, PACiS SCE, AREVA
T&D EAI, pacis.biz and pacis.com - are trademarks of AREVA T&D EAI. Product and
company names mentioned herein are trademarks or trade names of their respective
companies.
C264/EN SA/C30 Safety & Handling

Page 12/12

MiCOM C264/C264C

9. WARNINGS REGARDING USE OF AREVA T&D EAI PRODUCTS
AREVA T&D EAI products are not designed with components and testing for a level of
reliability suitable for use in connection with surgical implants or as critical components in
any life support systems whose failure to perform can reasonably be expected to cause
significant injuries to a human.
In any application, including the above reliability of operation of the software products can be
impaired by adverse factors, including - but not limited - to fluctuations in electrical power
supply, computer hardware malfunctions, computer operating system, software fitness,
fitness of compilers and development software used to develop an application, installation
errors, software and hardware compatibility problems, malfunctions or failures of electronic
monitoring or control devices, transient failures of electronic systems (hardware and/or
software), unanticipated uses or misuses, or errors from the user or applications designer
(adverse factors such as these are collectively termed "System failures").
Any application where a system failure would create a risk of harm to property or persons
(including the risk of bodily injuries and death) should not be reliant solely upon one form of
electronic system due to the risk of system failure to avoid damage, injury or death, the user
or application designer must take reasonably steps to protect against system failure,
including - but not limited - to back-up or shut-down mechanisms, not because end-user
system is customised and differs from AREVA T&D EAI testing platforms but also a user or
application designer may use AREVA T&D EAI products in combination with other products.
These actions cannot be evaluated or contemplated by AREVA T&D EAI; Thus, the user or
application designer is ultimately responsible for verifying and validating the suitability of
AREVA T&D EAI products whenever they are incorporated in a system or application, even
without limitation of the appropriate design, process and safety levels of such system or
application.
Introduction C264/EN IT/C30

MiCOM C264/C264C


INTRODUCTION
Introduction C264/EN IT/C30

MiCOM C264/C264C

Page 1/8

CONTENT
1. INTRODUCTION TO MiCOM 3

2. INTRODUCTION TO MiCOM GUIDES 4
2.1 Chapters description 4
2.1.1 Chapter Safety (SA) 4
2.1.2 Chapter Introduction (IT) 4
2.1.3 Chapter Technical Data (TD) 4
2.1.4 Chapter Functional Description (FT) 4
2.1.5 Chapter Hardware Description (HW) 4
2.1.6 Chapter Connection diagrams (CO) 4
2.1.7 Chapter HMI, Local control and user interface (HI) 4
2.1.8 Chapter Installation (IN) 4
2.1.9 Chapter Settings (ST) 4
2.1.10 Chapter Communications (CT) 5
2.1.11 Chapter Commissioning (CM) 5
2.1.12 Chapter Record Sheet (RS) 5
2.1.13 Chapter Maintenance, Fault finding, Repairs (MF) 5
2.1.14 Chapter Lexical (LX) 5
2.1.15 Chapter Applications (AP) 5
2.2 Operation guide 5
2.3 Technical guide 5
3. INTRODUCTION TO MiCOM APPLICATIONS 6
3.1 MiCOM Computers 6
3.2 Applications and Scope 6

C264/EN IT/C30 Introduction

Page 2/8

MiCOM C264/C264C

BLANK PAGE
Introduction C264/EN IT/C30

MiCOM C264/C264C

Page 3/8

1. INTRODUCTION TO MiCOM
MiCOM is a comprehensive solution capable of meeting all electricity supply requirements. It
comprises a range of components, systems and services from AREVA T&D Energy
Automation & Information.
Central to the MiCOM concept is flexibility.
MiCOM provides the ability to define an application solution and, through extensive
communication capabilities, to integrate it with your power supply control system.
The components within MiCOM are:
P range protection relays;
C range control products;
M range measurement products for accurate metering and monitoring;
S range versatile PC support and substation control packages.
MiCOM products include extensive facilities for recording information on the state and
behaviour of the power system using disturbance and fault records. They can also provide
measurements of the system at regular intervals to a control centre enabling remote
monitoring and control to take place.
The MiCOM range will continue to be expanded. The general features of MiCOM will also be
enhanced, as we are able to adopt new technology solutions.
For up-to-date information on any MiCOM product, visit our website: www.areva-td.com

C264/EN IT/C30 Introduction

Page 4/8

MiCOM C264/C264C

2. INTRODUCTION TO MiCOM GUIDES
The guides provide a functional and technical description of the MiCOM C264/C264C
computers and a comprehensive set of instructions for the computers use and application.
MiCOM guides is divided into two volumes, as follows:
Operation Guide: includes information on the application of the computers and a technical
description of its features. It is mainly intended for protection & control engineers concerned
with the selection and application of the computers for the Control, Monitoring, Measurement
and Automation of electrical power processes.
Technical Guide: contains information on the installation and commissioning of the
computer, and also a section on fault finding. This volume is intended for site engineers who
are responsible for the installation, commissioning and maintenance of the MiCOM
C264/C264C computer.
2.1 Chapters description
2.1.1 Chapter Safety (SA)
This chapter contains the safety instructions, handling and reception of electronic equipment,
packing and unpacking parts, Copyrights and Trademarks.
Chapters on product definition and characteristics
2.1.2 Chapter Introduction (IT)
This is this document containing the description of each chapter of the MiCOM computer
guides. It is a brief introduction to MiCOM computer capabilities.
2.1.3 Chapter Technical Data (TD)
This chapter contains the technical data including, accuracy limits, recommended operating
conditions, ratings and performance data.
It also describes environment specification, compliance with technical standards.
2.1.4 Chapter Functional Description (FT)
This chapter contains a description of the product. It describes functions of the MiCOM
computer.
2.1.5 Chapter Hardware Description (HW)
This chapter contains the hardware product description (product identification, case,
electronic boards, operator interface, etc.).
2.1.6 Chapter Connection diagrams (CO)
This chapter contains the external wiring connections to the C264/C264C computers.
2.1.7 Chapter HMI, Local control and user interface (HI)
This chapter contains the operator interface description, Menu tree organisation and
navigation, LEDs description, Setting/configuration software.
Set of chapter upon Computer installation
2.1.8 Chapter Installation (IN)
This chapter contains the installation procedures.
2.1.9 Chapter Settings (ST)
This chapter contains the list of the setting with default values and range.
Introduction C264/EN IT/C30

MiCOM C264/C264C

Page 5/8

2.1.10 Chapter Communications (CT)
This chapter provides the companion standard of all supported protocols toward SCADA
(Telecontrol BUS) and IED on LBUS. This is the list of protocol function that computer use in
this communication.
User minimal actions
2.1.11 Chapter Commissioning (CM)
This chapter contains instructions on how to commission the computer, comprising checks
on the settings and functionality of the computer.
2.1.12 Chapter Record Sheet (RS)
This chapter contains record sheet to follow the maintenance of the computer.
2.1.13 Chapter Maintenance, Fault finding, Repairs (MF)
This chapter advises on how to recognise failure modes, fault codes and describes the
recommended actions to repair.
2.1.14 Chapter Lexical (LX)
This chapter contains lexical description of acronyms and definitions.
2.1.15 Chapter Applications (AP)
Comprehensive and detailed description of the features of the MiCOM C264/264C including
both the computer elements and the other functions such as transducerless (CT/VT)
measurements, events and disturbance recording, interlocking and programmable scheme
logic. This chapter includes a description of common power system applications of the
MiCOM C264/C264C computer, practical examples of how to do some basic functions,
suitable settings, some typical worked examples and how to apply the settings to the
computer.
2.2 Operation guide
This binder contains the following chapters:
SA, IT, TD, FT, HW, CO, HI, AP, LX.
2.3 Technical guide
This binder contains the following chapters:
SA, IT, TD, FT, HW, CO, IN, ST, CT, CM, RS, MF, LX.
C264/EN IT/C30 Introduction

Page 6/8

MiCOM C264/C264C

3. INTRODUCTION TO MiCOM APPLICATIONS
AREVA philosophy is to provide a range of computers, gateways and IEDs products. Each of
these products can be used independently, or can be integrated to form a PACiS system, a
Digital Control System (DCS) or a SCADA system.
3.1 MiCOM Computers
Driven by the requirements around the world for advanced applications in SCADA, Digital
Control Systems, Automation, control and monitoring, AREVA has designed and developed
a complete range of computer products, MiCOM C264 specifically for the power process
environment and electric utility industry. It allows building a personalised solution for Control,
Monitoring, Measurement and Automation of electrical processes.
MiCOM C264/C264C computers range are designed to address the needs of a wide range
of installations, from small to large and customer applications. Emphasis has been placed on
strong compliance to standards, scalability, modularity and openness architecture. These
facilitate use in a range of applications from the most basic to the most demanding. They
also ensure interoperability with existing components and, by providing building computers,
PLC or IEDs approach, provide a comprehensive upgrade path, which allows PACiS
capabilities to track customer requirements.
Key features are that this computer family is based on a Ethernet client/server architecture,
its a modular computer that offers a large variety of applications such as Bay Computer,
Remote Terminal Unit and Programmable Logic Controller.
Phase in time, dedicated computer available for each application will be purposed.
3.2 Applications and Scope
The MiCOM C264/C264C modular bay controller, RTU or PLC is used to control and monitor
switchbays. The information capacity of the MiCOM C264/C264C is designed for controlling
operated switchgear units equipped with electrical check-back signalling located in medium-
voltage or high-voltage substations.
External auxiliary devices are largely obviated by the integration of binary inputs and power
outputs that are independent of auxiliary voltages, by the direct connection option for current
and voltage transformers, and by the comprehensive interlocking capability.
This simplifies handling of bay protection and control technology from planning to station
commissioning. During operation, the user-friendly interface makes it easy to set the unit and
allows safe operation of the substation by preventing non-permissible switching operations.
Continuous self-monitoring reduces maintenance costs for protection and control systems.
A built-in liquid crystal display (optional front face with LCD) shows not only switchgear
settings but also measured data and monitoring signals or indications.
The bay is controlled interactively by using the control keys and the display.
Adjustment to the quantity of information required is made via the PACiS System
Configurator Editor (PACiS SCE).
The MiCOM C264/C264C can be connected to a higher control level, local control level or
lower levels by way of a built-in communications interface.
Introduction C264/EN IT/C30

MiCOM C264/C264C

Page 7/8

C0001ENc
Fast Ethernet
IEC 61850
Master clock
(GPS)
I/Os
WEB access
COMMON BAY

MV FEEDER BAYS
HV FEEDER BAY
MV FEEDER BAYS
C264C
SCADA Interface
DNP3 & IEC 60870-5-101
& IEC 60870-5-104
Cubicle/ Switchboard
integration
C264
C264
C264C
Operator
Interface
Main protection
EHV FEEDER BAY
I/Os
TRANSFORMER BAY

FIGURE 1 : TYPICAL USE OF A MiCOM C264 BAY CONTROLLER
Remote
HMI
PSTN or
dedicated
line
NP3,
DBUS,
IE 0-5-103,
I 870-5-101
PLC
M720
Px20
Px30
BC
C0002ENb
Px30
Px40
I/Os
I/Os
SCADA Interface
DNP3 & IEC 60870-5-101
& IEC 60870-5-104

FIGURE 2 : TYPICAL USE OF A MiCOM C264 RTU APPLICATION
The figures show some typical cases that can be mixed to face specific constraint. Two
examples can illustrate this case:
The system application on figure 1 uses several C264 with several communication
links to SCADA (one per voltage level for example).
RTU application can use several C264 linked together on SBUS Ethernet. One of the
C264 RTUs is in charge of the concentration of data and of the communication with
the remote SCADA.
C264/EN IT/C30 Introduction

Page 8/8

MiCOM C264/C264C

BLANK PAGE
Technical Data C264/EN TD/C30

MiCOM C264/C264C


TECHNICAL DATA
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 1/22

CONTENT
1. SCOPE OF THE DOCUMENT 3

2. CONFORMITY 4

3. GENERAL DATA 5
3.1 Design 5
3.2 Installation Position 5
3.3 Degree of Protection 5
3.4 Weight 5
3.5 Dimensions and Connections 5
3.6 Terminals 5
3.7 Creepage Distances and Clearances 6
4. RATINGS 7
4.1 Auxiliary Voltage 7
4.2 Digital inputs 7
4.2.1 DIU200 7
4.2.2 DIU210 8
4.2.3 CCU200 9
4.3 Digital outputs 10
4.3.1 DOU200 10
4.3.2 CCU200 11
4.3.3 BIU241 11
4.4 Analogue inputs 12
4.4.1 AIU201 12
4.4.2 AIU210 13
4.4.3 AIU211 13
4.5 CT/VT inputs 14
4.5.1 TMU200/TMU220 - Currents 14
4.5.2 TMU200/TMU220 Voltages 14
4.5.3 TMU200/TMU220 - A/D converter 14
5. BURDENS 15
5.1 Auxiliary Voltage 15
5.2 Power supply 15
5.3 CPU boards 15
5.4 Digital inputs 15
5.4.1 DIU200 15
5.4.2 DIU210 15
5.4.3 CCU200 16
C264/EN TD/C30 Technical Data

Page 2/22

MiCOM C264/C264C

5.5 Digital outputs 16
5.5.1 DOU200 16
5.5.2 CCU200 16
5.6 Analogue inputs 16
5.7 Ethernet Switches 16
5.8 CT/VT inputs 17
5.9 Front panels 17
6. ACCURACY 18
6.1 Reference Conditions 18
6.2 Measurement Accuracy 18
7. TYPE TESTS 19
7.1 Dielectric Withstand 19
7.2 Mechanical Test 19
7.3 Atmospheric Test 20
7.4 DC Auxiliary Supply Test 20
7.5 AC Auxiliary Supply Test 21
7.6 EMC 21

Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 3/22

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264 documentation binders, describing the
Technical data of this computer.
C264/EN TD/C30 Technical Data

Page 4/22

MiCOM C264/C264C

2. CONFORMITY
(Per Article 10 of EC Directive 73/23/EEC).
The product designated MiCOM C264/C264C computer has been designed and
manufactured in conformance with the standard IEC 60255-27:2005 and is compliant with
the European Commission Low Voltage Directive 73/23/EEC.
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 5/22

3. GENERAL DATA
3.1 Design
Surface-mounted case suitable for wall installation or flush-mounted case for 19 cabinets
and for control panels.
3.2 Installation Position
Vertical 15
3.3 Degree of Protection
Per DIN VDE 0470 and EN 60255-27:2006 or IEC 60255-27:2005.
IP52 for the front panel with LCD or Leds.
IP10 for the blind front panel (GHU220,GHU221).
IP50 for the body case of MiCOM C264C.
IP20 for the rack of MiCOM C264.
IP20 for rear panels of C264/C264C, except reduced to IP10 when the black MiDOS 28 way
terminal block is mounted (for TMU200 ,TMU210 and TMU220 boards).
3.4 Weight
Case 40 TE: approx. 4 kg
Case 80 TE: approx. 8 kg
3.5 Dimensions and Connections
See dimensional drawings (Hardware description section C264_EN_HW) and terminal
connection diagrams (C264_EN_CO).
3.6 Terminals
PC Interface:
DIN 41652 connector, type female D-Sub, 9-pin on the front panel.
A direct wired cable is required.
Ethernet LAN (in the rear panel through the CPU260 board):
RJ-45 female connector, 8-pin for the 10/100Base-T self-negotiation.
ST female connector for the 100Base-F.
IRIG-B Input (optional, in the rear panel through the CPU260 board):
BNC plug.
Conventional communication links:
M3 threaded terminal ends, self-centring with wire protection for conductor cross sections
from 0.2 to 2.5 mm for BIU241 board.
DIN 41652 connector; type D-Sub, 9-pin on the CPU260 board in the rear panel.
Optical fibres trough ECU200 (external RS232/optical converter): optical plastic fibre
connection per IEC 874-2 or DIN 47258 or ST glass fibre optic connection (ST is a
registered trademark of AT&T Lightguide Cable Connectors).
Inputs /Outputs or power supply modules:
M3 threaded terminal ends, self-centring with wire protection for conductor cross sections
from 0.2 to 2.5 mm for DIU200, DIU210, DIU220, DOU200, CCU200, AIU201, AIU210,
AIU211 and BIU241 boards.
The I/O boards and BIU241 are equipped with a 24-way 5.08 mm pitch male connector.
C264/EN TD/C30 Technical Data

Page 6/22

MiCOM C264/C264C

Current-measuring and Voltage-measuring inputs:
M5 threaded terminal ends, self-centring with wire protection for conductor cross sections
between 2.5 and 4 mm for TMU200 Transducerless (4CT+4VT) board.
The TMU200 (4CT+4VT) board is equipped with a MiCOM: ASSEMBLY CONNECTEUR
BLOCKL GJ104 connector.
3.7 Creepage Distances and Clearances
Per IEC 60255-27:2005 and IEC 664-1:1992.
Pollution degree 2, working voltage 250 V.
Overvoltage category III, impulse test voltage 5 kV.
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 7/22

4. RATINGS
4.1 Auxiliary Voltage
MiCOM C264/C264C computers are available in four auxiliary voltage versions, specified in
the table below:
Version Nominal ranges Operative DC range Operative AC range
A01 24 V
DC
19.2 28.8 V -
A02 48 to 60 V
DC
38.4 72 V -
A03 110 to 125 V
DC
88 150 V -
A04 220 V
DC
and 230 V
AC
176 264 V 176 264 V
The nominal frequency (Fn) for the AC auxiliary voltage is dual rated at 50/60Hz, the operate
range is 45Hz to 65Hz.
The main characteristics of the BIU241 board are:
Power supply: 40 W
Nominal output voltage: + 5V
Supply monitoring
Power loss withstands capacity: 50 ms
Protection against polarity reversal
Insulation resistance: >100 M ( CM) at 500 V
DC

Dielectric withstand: 2 kV (CM) 50 Hz for 1minute
4.2 Digital inputs
4.2.1 DIU200
The DIU200 board is available in four nominal voltage versions that characteristics are
specified in the table below.
The DIU200 board has 16 digital inputs.
Version Nominal voltage (+/-20%) Triggering threshold (V
DC
)
A01 24 V
DC
if V >10.1 V
DC
Input status is set
if V < 5 V
DC
Input status is reset
A02 48 to 60 V
DC
if V >17.4 V
DC
Input status is set
if V < 13.5 V
DC
Input status is reset
A03 110 to 125 V
DC
if V > 50 V
DC
Input status is set
if V< 34.4 V
DC
Input status is reset
A04 220 V
DC
if V > 108 V
DC
Input status is set
if V< 63 V
DC
Input status is reset

C264/EN TD/C30 Technical Data

Page 8/22

MiCOM C264/C264C

The DIU200 board is designed to allow 2 inputs serially connected. This answers to the
following need:
C0124ENa
C264
IN1 IN2
0 VDC
Un
R

If R is open then IN1 and IN2 are set.
If R is closed then IN1 is set, IN2 is reset.
With this scheme, when IN1 is reset, this means that there is a problem into the external
wiring.
The input current at nominal voltage is detailed in chapter 5.4.
There are at maximum 15 DIU boards (including DIU200 and DIU210) inside a C264 rack.
4.2.2 DIU210
The DIU210 board works for all voltages between 48 VDC and 220 VDC (+/- 20%).
The DIU210 board has 16 digital inputs.
Whichever voltage, the triggering threshold is 19V
DC
The maximum number of DIU210 board in one C264 rack depends on the rack type and on
the voltage level of inputs.
Please refer to the following table:
Maximum
DIU210 boards in 40TE racks
Maximum
DIU210 boards in 80TE racks
24V 2 8
48V 6 15
110-125V 3 10
220V 1 5
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 9/22

The DIU210 board is designed to allow 2 inputs serially connected. This answers to the
following need:
C0124ENa
C264
IN1 IN2
0 VDC
Un
R

If R is open then IN1 and IN2 are set.
If R is closed then IN1 is set, IN2 is reset.
With this scheme, when IN1 is reset, this means that there is a problem into the external
wiring.
The input current at nominal voltage is detailed in chapter 5.4.
There are at maximum 15 DIU boards (including DIU200 and DIU210) inside a C264 rack.
the voltage level of inputs.
4.2.3 CCU200
For versions A1 to A4 of the CCU200 board the characteristics of the eight inputs are the
same as the DIU200 board.
For version A7 of the CCU board the characteristics of the eight inputs are:
nominal voltage ( +/- 20%): 110-125 Vcc with
triggering threshold: if V
input
> 86 V
DC
input status is set
triggering threshold: if V
input
< 67 V
DC
input status is reset
Maximum number of CCU200 boards to be installed in the C264 racks:
15 in the C264 racks (80TE) not equiped with a TMUxxx board
14 in the C264 racks(80TE) equiped with a TMUxxx board (CCU is not to be installed
in Slot P)
6 in the C264C racks (40TE) not equiped with a TMUxxx board
3 in the C264C racks (40TE) equiped with a TMUxxx board (CCU is not to be installed
in slot F)

C264/EN TD/C30 Technical Data

Page 10/22

MiCOM C264/C264C

4.3 Digital outputs
4.3.1 DOU200
The characteristics of the Output Relay Contacts of the DOU200 board are specified in the
table below:
Features Values
Nominal operating voltage range 24V to 250 V
DC
/ 230 V
AC

Make 2,5A
Carry 2,5A continuous
30 A for 500 ms or 100 A for 30 ms
Break DC: 50 W resistive, 30 W inductive (L/R = 40 ms)

AC: 1250 VA resistive, 1250 VA inductive (cos = 0,7)
In these conditions, the contact resistance is still lower
than 250 m for 10000 operations
Operating time Break < 7 ms
8 simple pole contacts Normally open
2 double pole contacts 1 Normally open +1 Normally close
Isolation: 2 kV (CM) 50 Hz-for 1 min.
The board is designed and monitored to avoid inadvertent controls.
There are at maximum 15 DOU200 boards inside a C264 rack.
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 11/22

4.3.2 CCU200
The characteristics of the 4 Output Relay Contacts of the CCU200 board are specified in the
table below:
In the table bellow, the Break characteristic are indicated for two application cases:
- each of the output contact is used separately
- the two output contacts of each relay are wired in serial. The relays break characteristics
are optimal in these conditions.
Features Values
Operating voltage 24 to 250 V
DC
/ 230 V
AC

Make 5A
Carry 5A continuous
30 A for 500 ms or 250 A for 30 ms
Break (output contact used
separately)
DC : 50 W resistive, 30 W inductive (L/R = 40 ms)
AC : 1250 VA resistive, 1250 VA inductive (cos = 0,7)
In these conditions, the contact resistance is still lower
than 250 m for 10000 operations
Break (Output contacts wired in
serial)
DC : 80 W resistive for current lower than 1A,
100W resistive for current upper than 1A,
30 W inductive (L/R = 40 ms)
AC : 1250 VA resistive, 1250 VA inductive
(cos = 0,7)
In these conditions, the contact resistance is still lower
than 250 m for 10000 operations
Operating time Break < 7 ms
Isolation: 2 kV (CM) 50 Hz for 1 min.
The board is designed and monitored to avoid inadvertent controls.
There are at maximum 15 CCU200 boards inside a C264 rack.
4.3.3 BIU241
The characteristics of the Watchdog Relay Contacts of the BIU241 board are the same as
the contacts NO+NC contacts of the DOU200 board.
The characteristics of the two output relays used for C264 redundancy are the same as the
single pole one on the DOU200 board.
C264/EN TD/C30 Technical Data

Page 12/22

MiCOM C264/C264C

4.4 Analogue inputs
4.4.1 AIU201
The AIU201 board provides 4 independent analogue inputs. Each AI can be configured in
voltage or current range individually as specified in the table below:
Type Ranges
Current input range 1mA
5 mA
10 mA
20 mA
4-20 mA
Voltage input range 1,25V
2,5V
5 V
10V
Sampling period 100 ms
Accuracy 0,1% full scale at 25C
AD conversion 16 bits (15bits+sign)
Common mode rejection ratio (CMMR) > 100dB
Serial mode rejection ratio (SMMR) > 40dB
gains range (user-selectable) 1, 2, 4, 10
Input impedance for voltage inputs 11 K
Input impedance for current inputs 75
Temperature derive: up to 30ppm/C.
The ranges are defined during the configuration phase.
The current/voltage selection is done by choosing the input number of the connector.
There are at maximum 6 AIU boards (including AIU201 and AIU210) inside a C264 rack.
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 13/22

4.4.2 AIU210
The AIU210 board provides 8 analogue inputs (1 common point for two inputs). Each AI can
be configured in the current range as specified in the table below:
Type Ranges
Current input range 1mA
5 mA
10 mA
20 mA
4-20 mA
Sampling period 100 ms
Accuracy 0,1% full scale at 25C
AD conversion 16 bits (15 bits+sign)
Common mode rejection ratio (CMMR) > 100dB
Serial mode rejection ratio (SMMR) > 40dB
gains range (user-selectable) 1, 2, 4, 10
Input impedance for current inputs 75
Temperature derive: up to 30ppm/C.
The ranges are configured during the configuration phase.
The current selection is done by choosing the input number of the connector.
A maximum of 6 AIU boards (including AIU201, AIU210 and AIU211) can be installed inside
a C264 rack.
4.4.3 AIU211
The AIU211 board provides 8 isolated analogue inputs. Each AI can be configured in the
current range as specified in the table below:
Type Ranges
Current input range 1mA
5 mA
10 mA
20 mA
Sampling period 100 ms
Accuracy 0,1% full scale at 25C
AD conversion 16 bits (15 bits+sign)
Common mode rejection ratio (CMMR) > 100dB
gains range (user-selectable) 1, 2, 4, 10
Input impedance for current inputs 75
Temperature derive: up to 30ppm/C.
The ranges are configured during the configuration phase.
The current selection is done by choosing the input number of the connector.
A maximum of 6 AIU boards (including AIU201, AIU210 and AIU211) can be installed inside
a C264 rack.
C264/EN TD/C30 Technical Data

Page 14/22

MiCOM C264/C264C

4.5 CT/VT inputs
The TMU200 board provides 4 Current Transformer (CT) inputs and 4 Voltage Transformer
(VT) Inputs.
The TMU220 board provides 4 Current Transformer (CT) inputs and 5 Voltage Transformer
(VT) Inputs.
4.5.1 TMU200/TMU220 - Currents
There are two available nominal currents with two different allocations on the terminal block.
The four measurement Current Transformers (4 CT) inputs have the following
characteristics:
Operating range
Features
1 A 5 A
Nominal AC current (I
N
) 1 A
eff
5 A
eff

Minimum measurable current with same
accuracy
0.2 A
eff
0.2 A
eff

Maximum measurable current 4 A
eff
20 A
eff

Frequency 50 or 60 Hz 10% 50 or 60 Hz 10%
CT load rating:
Withstand
Duration
1 A 5 A
3 second (not measurable, without destruction) 6 A
eff
30 A
eff

1 second (not measurable, without destruction) 20 A
eff
100 A
eff

4.5.2 TMU200/TMU220 Voltages
The measurement Voltage Transformers (VT) inputs have the following characteristics:
Features Operating range
Nominal AC voltage (V
N
) range 57.73 V
eff
to 500 V
eff
.
Minimum measurable voltage 7 V
eff

Maximum measurable voltage 577 V
eff

Frequency operating range 50 or 60 Hz 10%
VT load rating:
Duration Withstand
10 second without destruction 880 V
eff

4.5.3 TMU200/TMU220 - A/D converter
The A/D converter of the TMU200/TMU220 boards has the following characteristics:
Features Values
Width 16 bits
Conversion period < 30 s
Scanning period 64 samples/period
Linearity error 2 LSB
SINAD ratio up to 1kHz 0db
Low passed filter at 1khz -40db/decade
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 15/22

5. BURDENS
5.1 Auxiliary Voltage
The MiCOM C264/C264C computer burdens are specified in the table below:
Version Nominal Maximum
C264C 15W 22W
C264 20W 40W
5.2 Power supply
The BIU241 board burden on the internal 5V bus is 1,25W. This takes into account
watchdog, redundancy relays and communication ports.
The efficiency of the power supply is 78%.
5.3 CPU boards
The CPU260 board ( also named CPU type 2 or CPU2) burden on the internal 5V and 12V
bus is 3,3W.
The CPU270 board ( also named CPU type 3 or CPU3) burden on the internal 12V bus is
2,7W.
5.4 Digital inputs
5.4.1 DIU200
The DIU200 inputs burdens are specified in the table below:
Version Nominal voltage Current at Un (mA)
A01 24 V
DC
3.5
A02 48 to 60 V
DC
5 for 48 V
DC

6.8 for 60 V
DC

A03 110 to 125 V
DC
2.5 for 110 V
DC

3 for 125 V
DC

A04 220 V
DC
2
The DIU200 board burden on the internal 5V bus is 75mW
5.4.2 DIU210
The DIU210 inputs burdens are specified in the table below:
Nominal voltage Current at Un (mA)
24 V
DC
>25
48 to 60 V
DC
3.8
110 to 125 V
DC
4
220 V
DC
4.1
The DIU210 board burden on the internal 5V bus is 75mW.
Power consumption per input:
Un = 24VDC to 110V DC: 0,5W 30% per input
Un > 110VDC: 5mA 30%
From 48Vdc to 220Vdc voltage, a high current consumption is created on binary inputs
during a short period and circulates through external binary contacts to clean them. See the
peak current response curve.
C264/EN TD/C30 Technical Data

Page 16/22

MiCOM C264/C264C

WARNING: FOR THE 24V VOLTAGE, THERE IS NO SHORT PEAK CURRENT
BECAUSE OF THE PERMANENT HIGH CONSUMPTION ON INPUTS
>25mA.
The current peak response curve.
C0159ENa
Tension (V)
C
u
r
r
e
n
t

(
m
A
)
35
30
25
20
15
10
5
0
0 50 100 150 200 250 300


5.4.3 CCU200
The CCU200 inputs consumption is specified in the table below:
Version Nominal voltage Current at Un (mA)
A01 24 V
DC
3.5
A02 48 to 60 V
DC
5 for 48 V
DC

6.8 for 60 V
DC

A03 110 to 125 V
DC
2.5 for 110 V
DC

3 for 125 V
DC

A04 220 V
DC
2
A07 110 to 125 V
DC
3.4 for 110V
DC
5.4 for 132V
DC
5.5 Digital outputs
5.5.1 DOU200
The DOU200 board burden on the internal 5V bus is 250mW plus 200mW per activated
relay.
5.5.2 CCU200
The CCU200 board burden on the internal 5V bus is 400mW plus 200mW per activated
relay.
5.6 Analogue inputs
The AIU201 and the AIU210 boards burden on the internal 5V bus is 1 W.
5.7 Ethernet Switches
The SWU20x board burden on the internal 5V bus is 3,85W with 2 optical ports.
The SWR20x board burden on the internal 5V bus is 4 W.
The SWD202/SWD204 board burden on the internal 5V bus is 4W.
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 17/22

5.8 CT/VT inputs
The TMU200/TMU220 burdens on the internal transformers are specified in the table below:
Nominal consumption (VA) CT burden (at nominal current I
N
)
TMU200 TMU220
1A < 0.1 < 0.02
5A < 0.5 < 0.2

VT burden (at nominal voltage V
N
) Nominal consumption (VA)
TMU200 TMU220
Vn = 130 V
eff
<0.1 < 0.01
The TMU200 board burden on the internal 5V bus is 600mW.
The TMU220 board burden on the internal 5V bus is 300mW.
5.9 Front panels
The GHU200 and GHU210 board burden on the internal 5V bus is 600mW when the LCD
screen is not back-lighted and 3W when the LCD screen is back-lighted.
The GHU201 and GHU211 board burden on the internal 5V bus is 600mW.
The GHU202 and GHU212 board burden on the internal 5V bus is <1mW.
C264/EN TD/C30 Technical Data

Page 18/22

MiCOM C264/C264C

6. ACCURACY
For all specified accuracy, the repeatability is 2.5% unless otherwise specified.
If no range is specified for the validity of the accuracy, then the specified accuracy shall be
valid over the full setting range.
6.1 Reference Conditions
Quantity Reference conditions Test tolerance
General
Ambient temperature 20 C 2 C
Atmospheric pressure 86kPa to 106kPa -
Relative humidity 45 to 75 % -
Input energising quantity
Current I
N
5%
Voltage V
N
5%
Frequency 50 or 60Hz 0.5%
Auxiliary supply 24VDC, 48VDC-60VDC,
110VDC-125VDC,
220VDC
230VAC
5%
6.2 Measurement Accuracy
The TMU200 board has the following characteristics:
Quantity Accuracy
Current 0.2% full scale
Voltage 0.2% full scale
Frequency 0.01 Hz
Amplitude < 1%
Phase 1
Overall temperature coefficient 10 ppm/C
Harmonics 15H
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 19/22

7. TYPE TESTS
7.1 Dielectric Withstand
Type Test Name Type Test Standard Conditions
Insulation Resistance IEC 60255-5 (2000) 100 M at 500 Vdc (CM & DM)
Dielectric Withstand IEC60255-5 (2000)
IEEE C37.90 (1989)
50 Hz for 1mn, 2kV (CM), 1kV (DM)
High Voltage Impulse
Test
IEC 60255-5 (2000) 5 kV CM & 3 kV DM
7.2 Mechanical Test
Type Test Name Type Test Standard Conditions
2 falls of 5 cm (Computer not powered) Free Fall Test
Free Fall Packaging
Test
IEC 60068-2-31 (1969)
+ A1 (1982)
IEC 60068-2-32 (1975)
+A1 (1982) + A2
(1990)
25 falls of 50 cm (Packaging computer)
Vibration Response
Powered On
IEC 60255-21-1 (1988) Class 2:
Acceleration: 1g from 10 to 150Hz
Vibration Response
Not Powered On
IEC 60255-21-1 (1988) Class 2:
Acceleration: 2g from 10 to 500Hz
Vibration Endurance
Not Powered On
IEC 60068-2-6 (1995) Class 2:
Acceleration: 1g from 10 to 500Hz
Shocks Not Powered
On
IEC 60255-21-2 (1988) Class 1:
15g, 11 ms
Shocks Powered On IEC 60255-21-2 (1988) Class 2:
10g, 11 ms
Bump Test Not
Powered On
IEC 60255-21-2 (1988) Class 1:
10g, 16ms, 2000/axis
Seismic Test Powered
On
IEC 60255-21-3 (1993) Class 2:
Acceleration: 2g
Displacement: 7.5mm upon axe H
Acceleration: 1g
Displacement: 3.5mm upon axe V
C264/EN TD/C30 Technical Data

Page 20/22

MiCOM C264/C264C

7.3 Atmospheric Test
Type Test Name Type Test Standard Conditions
Damp Heat Test
Operating
IEC 60068-2-3 (1969) Test Ca:
+40C / 10 days / 93% RH
Cold Test - Operating IEC 60068-2-1 (1990) Test Ab: - 25c / 96 H
Cold Test - Storage IEC60068-2-1 (1990) Test Ad:
-40C / 96h
Powered On at 25C (for information)
Dry Heat Test
Operating
IEC 60068-2-2 (1974) 70c / 24 H
Dry Heat Long Test
Operating
DICOT HN 46-R01-06
(1993)
55c / 10 days
Dry Heat Test Storage IEC 60068-2-1 (1990) Test Bd:
+70C / 96h
Powered On at +70C
Enclosure Protection IEC 60529 (1989) + A1
(1999)
Front: IP=52
7.4 DC Auxiliary Supply Test
Type Test Name Type Test Standard Conditions
Inrush current (start-up) DICOT HN 46-R01-4
(1993)
T < 1.5 ms / I < 20 A
1.5ms < T < 150 ms / I < 10 A
T > 500 ms / I < 1.2 In
Supply variation IEC 60255-6 (1988) Vn 20%
Vn+30% & Vn-25% for information
Overvoltage (peak
withstand)
IEC 60255-6 (1988) 1.32 Vn max
2 Vn during 10 ms (for information)
Ramp down to zero N/A From Vn down to 0 within 1 minute
From Vn down to 0 within 100 minutes
Ramp up from zero N/A From 0 up to Vn within 1 minute
From 0 up to Vn within 100 minutes
Supply interruption IEC 60255-11 (1979) From 2.5 ms to 1 s at 0.8 Vn
50 ms at Vn, no malfunction
Reverse polarity N/A Polarity for the lower potential of the
supply
Polarity + for the lower potential of the
supply
Ripple (frequency
fluctuations)
IEC 60255-11 (1979) 12% Vn at f=100Hz or 120Hz
12% Vn at f=200Hz for information
Technical Data C264/EN TD/C30

MiCOM C264/C264C

Page 21/22

7.5 AC Auxiliary Supply Test
Type Test Name Type Test Standard Conditions
Supply variations IEC 60255-6 (1988) Vn 20%
AC Voltage dips & short
interruptions
EN 61000-4-11 (1994) 2ms to 20ms & 50ms to 1s
50 ms at Vn, no malfunction
Frequency fluctuations IEC 60255-6 (1988) 50 Hz: from 47 to 54 Hz
60 Hz: from 57 to 63 Hz
Voltage withstand N/A 2 Vn during 10 ms (for information)
7.6 EMC
Type Test Name Type Test Standard Conditions
High Frequency
Disturbance
IEC 60255-22-1 (1988)
IEC 61000-4-12 (1995)
IEEE C37.90.1 (1989)
Class 3: 2.5kV (CM) / 1kV (DM)
Electrostatic discharge IEC 60255-22-2 (1996)
IEC 61000-4-2 (1995) +
A1 (1998) + A2 (2001)
Class 4:
8kV contact / 15 kV air
Class 3:
10 V/m 80 to 1000 MHz

& spot tests
Radiated Immunity IEC 60255-22-3 (2000)
IEC 61000-4-3 (2002) +
A1 (2002)
IEEE C37.90.2 (1987)
35 V/m 25 to 1000 MHz
Fast Transient Burst IEC 60255-22-4 (2002)
IEC 61000-4-4 (1995) +
A1 (2001)
IEEE C37.90.1 (1989)
Class 4: 4kV 2.5kHz (CM)
Class 4: 2.5kV 2.5kHz (DM) on DI/DO
Surge immunity IEC 61000-4-5 (1995) +
A1 (2001)
Class 4:
4kV (CM) 2kV (DM)
High frequency
conducted immunity
IEC 61000-4-6 (2003) Class 3:
10 V, 0.15 80 MHz
Harmonics Immunity IEC 61000-4-7 (2002) 5% & 10% de H2 H17
Power Frequency
Magnetic Field Immunity
IEC 61000-4-8 (1993) Class 5:
100A/m for 1mn
1000A/m for 3s
Pulse magnetic field
immunity
IEC 61000-4-9 (1993) Class 5:
6.4 / 16 s
1000A/m for 3s
Damped oscillatory
magnetic field immunity
IEC 61000-4-10 (1993)
+ A1 (2001)
Class 5:
100 kHz & 1 MHz 100A/m
Power Frequency IEC 61000-4-16 (1998) CM 500 V / DM 250 V via 0.1 F
C264/EN TD/C30 Technical Data

Page 22/22

MiCOM C264/C264C

Type Test Name Type Test Standard Conditions
Conducted emission EN 55022 (1998) + A1
(2000) + A2 (2003)
Gr. I, class A: from 0.15 to 30 MHz
Radiated emission EN 55022(1998) + A1
(2000) + A2 (2003)
Gr. I, class A: from 30 to 1000 MHz


Functional Description C264/EN FT/C30

MiCOM C264/C264C


FUNCTIONAL DESCRIPTION
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 1/132

TABLE OF CONTENTS
1. SCOPE OF THE DOCUMENT 5
1.1 Software features 5
2. MiCOM C264/C264C MANAGEMENT 7
2.1 Operating mode management 7
2.1.1 Definitions 7
2.1.2 Initialisation mode 7
2.1.3 Operational mode 8
2.1.4 Maintenance mode 9
2.1.5 Test mode 9
2.1.6 Faulty mode 10
2.1.7 Halt mode 10
2.2 Database management 11
2.3 Time management 13
2.3.1 External clock 14
2.3.2 Clock message from a SCADA gateway 15
2.3.3 System master clock 15
2.3.4 Time set by an operator 15
2.3.5 Local clock update 16
2.4 Redundancy Management 18
3. COMMUNICATIONS 20
3.1 Telecontrol bus 20
3.2 Legacy bus 21
3.3 Station bus 21
3.3.1 Exchanges 22
3.3.2 Supported Common Data Classes 22
3.3.3 Controls 22
4. DIRECT PROCESS ACCESS 23
4.1 Input check 23
4.2 Output check 23
4.3 Time tagging 23
4.4 Digital input acquisition (DI) 23
4.4.1 Acquisition 23
4.4.2 Debouncing and filtering 24
4.4.3 Toggling 24
4.5 Counters acquisition (CT) 25
4.5.1 Single counter (SCT) 25
C264/EN FT/C30 Functional Description

Page 2/132

MiCOM C264/C264C

4.5.2 Double counter (DCT) 25
4.6 Digital measurement (DM) 26
4.6.1 Acquisition without Read Inhibit signal 26
4.6.2 Acquisition with Read Inhibit signal 27
4.6.3 Encoding 28
4.7 Analogue input acquisition (AI) 29
4.7.1 Input ranges 29
4.7.2 Acquisition cycle 29
4.8 Digital outputs (DO) 29
4.9 Digital Setpoints 30
4.9.1 Encoding 30
4.9.2 Read Inhibit 30
5. DATA PROCESSING 31
5.1 Binary Input processing 31
5.1.1 Binary Input definition 31
5.1.2 Processing of Single Point Status 32
5.1.3 Processing of Double Point Status 34
5.1.4 Processing of Multiple Point Status 38
5.1.5 System Inputs 39
5.1.6 IED inputs 40
5.1.7 Group processing 40
5.1.8 SBMC Mode Processing 41
5.1.9 BI sent to automatism features 41
5.2 Measurement Input Processing 42
5.2.1 Open circuit management 42
5.2.2 Scaling 42
5.2.3 Zero value suppression 43
5.2.4 Thresholds detection 43
5.2.5 Manual suppression 44
5.2.6 Substitution 44
5.2.7 Forcing an invalid measurement 44
5.2.8 Measurement resulting states 44
5.2.9 Transmission 45
5.2.10 CT/VT additional processing 46
5.2.11 Digital Measurement Processing 50
5.3 Tap Position Indication processing 51
5.3.1 Acquisition from Digital Inputs 51
5.3.2 Acquisition from Analogue Inputs 51
5.3.3 Manual suppression 51
5.3.4 Substitution 51
5.3.5 Forcing an invalid TPI 51
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 3/132

5.3.6 TPI resulting states 52
5.3.7 Transmission 52
5.4 Accumulator Input Processing 52
5.5 Energy counting 53
6. CONTROL SEQUENCES 54
6.1 Generic description 54
6.1.1 Generalities 54
6.1.2 Control sequence phase management 55
6.1.3 Direct Execution mode 58
6.1.4 SBO once mode 59
6.1.5 SBO many mode 62
6.1.6 Generic selection checks 64
6.1.7 Selection behaviour 68
6.1.8 Generic execution checks 69
6.1.9 Execution behaviour 69
6.1.10 Controls time sequencing 70
6.2 Control of non synchronised breakers 73
6.2.1 Non synchronised circuit breakers features 73
6.2.2 Control sequence of non-synchronised circuit breakers 73
6.3 Control of synchronised breakers 74
6.3.1 Circuit breakers features 74
6.3.2 Circuit breakers with external synchrocheck 75
6.3.3 Circuit breakers with internal synchrocheck 80
6.4 Control of disconnectors 84
6.4.1 Disconnectors features 84
6.4.2 Control sequence of disconnectors 84
6.5 Control of transformers 85
6.5.1 Transformers features 85
6.5.2 Control sequence of transformers 85
6.6 Control of ancillary devices 88
6.7 Control of Intelligent Electrical Devices (IED) 89
6.7.1 Control to IEDs 89
6.7.2 IED controls 89
6.7.3 Digital setting point (SP) 89
6.8 System controls 89
6.9 Kind of control sequence 90
6.10 Control sequences checks 90
6.10.1 Mode Management 90
6.10.2 IED connected 90
6.10.3 Control mode 90
6.10.4 Uniqueness of control 91
C264/EN FT/C30 Functional Description

Page 4/132

MiCOM C264/C264C

6.10.5 Inter-control delay 91
6.10.6 Status of the device 91
6.10.7 Lock device 91
6.10.8 Running Automation 91
6.10.9 Interlocking 91
6.11 HV Control Sequences 91
6.11.1 Circuit breaker 91
6.11.2 Disconnector 91
6.11.3 Transformer 91
7. AUTOMATIONS 92
7.1 Built-in Automation functions 92
7.1.1 Synchrocheck 92
7.1.2 Auto-Recloser (AR) 94
7.1.3 Trip Circuit Supervision 100
7.1.4 Automatic Voltage Regulation (AVR) 102
7.2 Interlocking: logical equations 116
7.2.1 Inputs 116
7.2.2 Outputs 116
7.2.3 Control 116
7.2.4 Behaviour 117
7.2.5 Limits and performance 119
7.3 Slow automation: Programmable Logic Control (PLC) 120
7.3.1 Inputs 121
7.3.2 Outputs 121
7.3.3 Control 121
7.3.4 Behaviour 122
7.3.5 Limits and performances 122
7.4 Fast automation: Programmable Scheme Logic (PSL) 123
8. USER INTERFACE 124

9. RECORDS 125
9.1 Permanent records storage 125
9.1.1 Data storage 125
9.1.2 Waveform Recording 125
9.1.3 Events 127
9.2 Non-permanent data storage 127
9.2.1 Alarms 127

Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 5/132

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264/C264C documentation binders. It is the
functional description of this computer. The hardware description is defined in HW chapter
and all connection diagrams in CO chapter. The technical data of the computer (capabilities,
performances, environmental limits) are grouped in TD chapter.
1.1 Software features
The MiCOM C264/C264C computer belongs to the new range of modular product at
hardware, software and functional levels. All functionalities are fully configurable following
customer needs and requirements. MiCOM C264/C264C computers assume:
Direct process interface through Digital Inputs (DI), Digital Outputs (DO), Analogue
Inputs (AI), and CT/VT boards.
Direct operator interface
Embedded parameterised control of all common plant or device
High communication abilities to IED, Ethernet, and RTU
User configurable automation modules
Events, alarms, measurement display, printing and archiving
Enhanced inner management with databases handling, self-test controls and
synchronisation means
Computer Kernel
Embedded Automation
(basic+AR, Synchrocheck+AVR)
Configurable Automation
(Fast PSL / Sequential PLC)
Telecontrol
Interface
IEC 61850
T-BUS
S-BUS
RTU, SCADA PACiS system, IEC 61850 IEDs
Human
Interface
(LCD)
RTC
Printing
C0003ENb
Synchronsation
Time tagging
I/O boards Legacy Gateway
L-Bus
IED
DI DO AI CT/VT
Archives
CT, Disturb
SOE
Alarms

FIGURE 1: SOFTWARE FEATURES
C264/EN FT/C30 Functional Description

Page 6/132

MiCOM C264/C264C

The components of the software management are:
Inputs/Outputs board (DI, DO, AI)
Analogue Inputs (AI, from CT/VT board - optional)
Automatic functions (Built-in, PLC, PSL)
Communications with Telecontrol Bus, Station Bus and Legacy Bus (see chapter
Communication)
RTC (Real Time Clock), time management; synchronisation, time tagging (see Time
management chapter)
Communication with peripherals such as:
Local Operator Interface (LCD, front panel)
Local Printer (local sequence of events - SOE)

Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 7/132

2. MiCOM C264/C264C MANAGEMENT
2.1 Operating mode management
2.1.1 Definitions
The terms defined below are used in this whole section 2.
Anomaly: an anomaly is a fault causing a downgraded behaviour of the computer.
There are hardware and/or software anomalies:
Board failure
Loss of synchronisation
Loss of communication
Software fault: A software fault results of a major software error. In this case the
computers enters the Faulty mode.
Vital harware fault: a vital hardware fault is a fault causing a software halt. This kind
of fault causes the computer to stop the application software.
CPU fault
Power supply fault
Bus fault
Permanent Interruption fault
2.1.2 Initialisation mode
After power on or manual reset the computer enters the initialisation mode and performs
different types of checks:
Vital hardware tests
Non-volatile memory test: in case of a problem the computer tries to repair this non-volatile
memory. If a vital hardware test fails, the initialisation is stopped and the computer enters the
Halt mode.
Non vital hardware tests
Non-vital hardware tests are only performed on present boards:
Inputs and outputs boards:
To determinate the number and the type of the present input and output
boards
To check the presence of the previously input and output boards and to be
informed if a board is absent
To check the good working order of the present input and output boards and
to be informed if a board is out of order
Communication boards: this test is performed within the communication protocol.
Display (LCD, LEDs): the single test that can be done is the presence of the HMI
board.
Peripheral devices (printer, external clock ..). Check of the presence of the devices
by use of timeouts.
If any of these non-vital hardware tests fails the computer enters the
operational/downgraded mode depending on the type of the fault.
Software tests (database coherency tests)
C264/EN FT/C30 Functional Description

Page 8/132

MiCOM C264/C264C

These tests are performed at each restart of the computer. The checks of the database
guarantees that the database is compatible with the hardware and the software of the
computer and that it does not contain incoherent data of configuration. The following checks
are performed:
Check of the presence of a database
Check of the DB/ software compatibility
This control makes it possible to check that the software and the database are
coherent. The computer contains in its static data a version and a revision number
indicating which structure of database it is able to interpret. The database must have
the same version to be accepted.
Check of the DB/ equipment compatibility
This control makes it possible to check that the database is intended for the
equipment on which it was downloaded. To check it, the type and the number of
equipment contained in the heading of the database are compared with the type and
the number of equipment contained in the static data of the software.
Check of the validity of the data of the database
This control checks that the configured inputs and outputs are present and that the
number of objects (bays, digital inputs ) remains within acceptable limits.
If any of these checks fails, the computer enters the Maintenance mode.
The initialisation of the computer does not exceed one minute.
2.1.3 Operational mode
This mode can be divided into two sub-modes: Normal mode and Downgraded mode.
2.1.3.1 Normal mode
This is the nominal operating mode of the active computer. In this mode the watchdog relay
is activated and all the functionalities of the computer are available. Nevertheless, detection
of an error can lead to the Downgraded mode, to the Faulty mode or to the Halt mode,
depending on the nature and the gravity of the failure.
From this mode a transition to the Maintenance mode can be requested by an operator from
local HMI or upper level (maintenance request).
From this mode a transition to the Test mode can be requested by an operator from local
HMI or upper level (simulation request).
In this mode, the operations that can be done on databases are the following:
Download a standby database
Swap the databases: then the computer automatically restarts
Modify a database
Display database information
This mode is transmitted to local HMI and upper level (RCP).
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 9/132

2.1.3.2 Downgraded mode
This mode is entered in case of an anomaly. In this mode the general working of the
computer is not very disturbed because it involves the degradation of only few functions. The
watchdog relay is activated.
The downgraded mode depends on the hardware configuration of the computer. But we can
define the different kinds of downgraded modes that can happen:
Operation without DO on a board
Operation without DI on a board
Operation without AI on a board
Operation without communication with some relays
Operation without communication with some station devices
A combination of two, or more, of these previous items
When the cause(s) of the transition into Downgraded mode disappear(s), the computer
returns to the Normal mode.
2.1.4 Maintenance mode
In Maintenance mode, communication on the station bus is operational in order to manage
the database. This mode is displayed on local HMI (led and LCD) and on upper level.
The watchdog relay is de-activated.
In this mode the operator can manage the database:
Download a database
Swap the databases
Modify a database
Display database information
From this mode a transition to the operational mode can be requested by an operator from
local HMI or upper level (active request).
2.1.5 Test mode
In Test mode, the computer works normally but output relays are not activated. This mode is
entered on operator request in order to simulate the functioning of distributed automatisms
such as interlocking. Instead of activating the output relays, the computer sends a test OK
message to the SCP if the command is valid otherwise a test NOK message.
NOTE: to realise the tests, the operator has to manually create the testing
conditions by forcing BI or Measurements on different computers.
Once the conditions are realised, he can generate a command and
see at the SCP level (HMI) if the result corresponds to the expected
one.
This mode is displayed on local HMI (led and LCD) and on upper level.
From this mode a transition to the operational mode can be requested by an operator from
local HMI or upper level (end of simulation).
C264/EN FT/C30 Functional Description

Page 10/132

MiCOM C264/C264C

2.1.6 Faulty mode
The Faulty mode is entered when a fault, that prevents the exploitation, happens. This mode
can be entered from any mode described above.
This mode is also entered when a failure is detected on DO boards and if the configuration
allows this mode on DO faults.
The only way to leave this mode is an automatic reset or a transition to the Halt mode. Each
time the computer enters this mode, an internal counter is incremented. As long as the value
of this counter is lower than Max_Fault (parameter defined during the configuration step) the
Initialisation mode is entered. The value of this counter is automatically reset when the
lasted time since the last incrementation of the counter reaches the value
Fault_Detection_Lasting (parameter defined during the configuration step). When the value
of this counter reaches Max_Fault the computer enters the Halt mode.
2.1.7 Halt mode
In this mode the computer doesnt operate anymore. The watchdog relay and all the outputs
relays are deactivated. The only way to get out of this mode is to operate a manual reset.
The following figure summarises the different operating modes of the computer and the
transitions.

FAULTY
automatic reset
manual reset
HALT
TEST
simulation request
end of simulation
major hardware fault
or software fault
OPERATIONAL MAINTENANCE

INITIALISATION
Init OK
hardware test OK
and coherency not OK
maintenance request
active request
boot
software fault or
major hardwraefault
no DB
vital hardware
fault

vital hardware fault
major hardware fault
Counter of faults = Max_Fault
vital hardware fault
C0307ENa

vital
hardware
fault
DB/software compatibility not OK
or
DB/equipment compatibility not OK
or
data of database not valid

swapping of the databases

FIGURE 2: OPERATING MODES OF THE COMPUTER

Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 11/132

2.2 Database management
The MiCOM C264/C264C uses structured databases for data management. A database
(DB) is a file which contains the description of the whole of the electric process, as of the
whole of the equipment which the computer is likely to dialogue with (IED, HMI ,etc.). It
contains also some parameter settings of the software and of the transmission. Databases
are generated and versioned by an independent equipment: the System Configuration Editor
(SCE). Each database file has an associated V
dbs
(System Baseline Version) A database is
downloaded into the non-volatile memory of the computer via the IEC61850 station bus with
the System Management Tool (SMT) or directly over Ethernet with the Computer
Maintenance Tool (CMT).
The computer stores at any moment up to two DBs in its non-volatile memory. The two DBs
(and these associated V
dbs
) are called thereafter DB1 and DB2 (and these associated V
dbs1

and V
dbs2
).
Each database (DB1 and DB2) of the computer can take one of the following states:
Missing: the DB is not present in non-volatile memory of the computer;
Standby: the DB was downloaded in non volatile memory of the computer; however,
this version is not taken into account by the software;
Current: the downloaded DB is taken into account by the software;
Current Modified: the DB, currently taken into account by the software, underwent a
parameter setting;
Standby Modified: the DB underwent a parameter setting, but it is not taken any
more into account by the software.
The following diagram represents the life cycle of the databases in the computer:
C0308ENa
Standby Current
Switching
Standby
Modified
Parameter setting
Current
Modified
Switching
Downloading
Absent
Parameter setting

FIGURE 3: THE DIFFERENT STATUS OF A DATABASE
At any moment, there is only one Current or Current Modified database. In the same way,
there is only one Standby or Standby Modified database.
A file descriptor (DB context) stored in non-volatile memory contains the configuration of the
DB present on the equipment. This file, containing the state of each of the two databases
(DB1 and DB2) and the V
dbs
(V
dbs1
and V
dbs2
) of each one, makes it possible to know the
configuration of the databases at the moment of the boot, and to start again with the current
database (if it exists). DB Context is updated by the sub-functions "Download a database",
"Switch the databases", "Check a database", "Modify a Database".
C264/EN FT/C30 Functional Description

Page 12/132

MiCOM C264/C264C

To download a database ( via Ethernet)
The downloading of a database is usually performed with SMT tool via the station bus.
The first downloading of a database (and its associated Vdbs) can be performed only
when the computer is in maintenance mode.
The downloading of a standby database (and its associated Vdbs) can be performed
when the computer, running with the current database, is either in operational mode or
in maintenance mode.
The sequencing is:
To work out and transmit to the calling equipment a response to the request: the
request can be refused if another request on database is already in progress;
To carry out the transfer of the DB file (and associated Vdbs) and to check its
integrity (calculation of checksum and control of the database);
In case of fault, to announce to the calling equipment the failure of the transfer;
In case of successful transfer, to control the database compatibility;
In case of invalid DB, to announce to the calling equipment the failure of the
installation;
In case of valid DB, to assign to the downloaded database (and associated Vdbs)
the state standby by removing a possible standby database (and associated
Vdbs) present in the computer; to signal to the calling equipment the success of
the installation;
To update the file descriptor (Context database) in non-volatile memory.
To switch the databases
This function answers to a request of DB switching coming from the station bus. This
request specifies the Version of the standby DB (Vdbs) to become current. After
a DB switch the computer automatically reboots and goes into active Mode if the DB is
coherent with the software.
C0309ENa
Vdbs n.m
DB
1
Vdbs x.y
DB
2
CURRENT STANDBY
Vdbs x.y
DB
2
Vdbs n.m
DB
1
CURRENT STANDBY
SWITCH
MAINTENANCE
MAINTENANCE
T0 T0 + T1
Vdbs x.y
DB
2
Vdbs n.m
DB
1
CURRENT STAND-BY
OPERATIONAL
T0 + T1
T0 + T1

FIGURE 4: DATABASES SWITCHING
To check the database
This function is carried out at each reboot. (refer to 3.2.1 Initialisation mode)
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 13/132

To modify the database
The parameter setting of database consists in modifying some values of configuration
present in the database. A parameter setting can be carried out only on the current
database (Current or Current Modified). Following a parameter setting, file database is
modified: the new value taken by the data is memorised there. The index of parameter
setting of the database is incremented, and the checksum of the file is recomputed.
The database then takes the Current Modified state. Only certain data are settable.
This is performed from the local HMI.
To carry out a parameter setting of data
This function treats the requests of parameter setting:
To check the coherence of the request: known object (the object is really
present in the database), settable data, value of parameter setting compatible
with the type of data conveyed (value belonging to the range of acceptable
variation),
If the request is incoherent, to emit a negative report to the emitter of the
request,
To write in database file the current value of the data,
To write in database file the date of modification of the data,
To compute the checksum and to write it in data base file,
To assign the state Current Modified to it,
To emit a positive report with the emitting equipment of the request,
To update the file descriptor (Context database) in non-volatile memory.
To consult a settable data
This function treats the requests of consultation of parameter issued from the Operator
Station:
To check the coherence of the request: known object (the object is quite present in
the database), settable data and current DB
If the request is incoherent, to emit a negative response to the transmitter of the
request
To work out the response to the transmitter of the request by giving the current
value of the data
2.3 Time management
The main purposes of the time management are:
Synchronisation of the computer by:
The external clock
Station/legacy bus
Operator
Updating of the internal clock
Synchronisation of other equipments via station bus
Time synchronisation of a computer can be done by four means:
External clock (IRIG-B signal
Clock message from a SCADA gateway (T-Bus)
Clock message from the system master clock (S-Bus)
Time set by an operator
C264/EN FT/C30 Functional Description

Page 14/132

MiCOM C264/C264C

Concerning these four external time references, there is a priority rule: if the external clock is
operating, modifications on the computer clock are not possible by other ways (for example
from SCADA gateway, system master clock or operator). In case of external clock is
disconnected or not operating, there is a priority order: clock message from a SCADA
gateway or from the system master clock takes priority over operator.
When the computer is master of legacy bus, it synchronises the IED according to the
synchronisation procedure of the protocol. The synchronisation is done just after the
computer has been synchronised by external clock or station bus or RCP. If the computer is
not synchronised, it synchronises periodically the IED all the same.
When the computer is synchronised all events and measurements have a time tag with
synchronised attribute. If synchronisation is lost, or has never been received attributes
indicates that time tag is not synchronised.
The time management organisation is based on the following scheme:
C0004ENc
External clock
Which
synchronises
IEC
equipment
Which synchronises
through station bus
IEDs
Which synchronises
through legacy bus
Synchronisation signal
SCADA
Which synchronises
through SCADA bus
System Master
Clock
Operator
time setting

FIGURE 5: TIME MANAGEMENT
2.3.1 External clock
A computer gets functionality of system master clock: it is the architecture equipment which
receives periodically, from an external IRIG-B clock reference, messages containing the date
and the hour.
The external clock device receives the synchronisation signal through several possible
protocols (GPS, DCF77, etc) and then sends it periodically to the dedicated IRIG-B input
of the MiCOM C264/C264C.
The external clock transmits to the computer the hour and date that itself receives.
In case of loss of the radio signal by the external clock two cases have to be considered:
1. Some external clocks can synchronise the computer for 8 hours after loss of radio
signal because they have an oscillator with a very good accuracy. The external clock
indicates via the protocol two informations: no radio received and loss radio
signal since more 8 hours. The computer remains synchronised until the indicator
"loss radio signal since more 8 hours" is activated. Then the status of internal clock
becomes not-synchronised.
2. Some external clocks haven't internal accuracy circuit to back up the radio signal. In
this case, the status of internal clock of computer becomes not-synchronised after
confirmation of loss radio signal (few minutes).
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 15/132

If the computer is master clock for the other equipment of the substation then it sends the
synchronisation message to the other equipment even if it is not synchronised. In this same,
it stays synchronised even if it loses the external clock communication. A dedicated binary
input is associated to the external clock status.
2.3.2 Clock message from a SCADA gateway
SCADA clock acquisition is a SCADA gateway specification. The purpose of this part is to
detail acquisition of clock message from SCADA gateway.
SCADA clock synchronisation depends on the protocol. The synchronisation message is
directly acquired by the MiCOM C264/C264C through the SCADA link.
The clock message from SCADA gateway is in UTC time.
The SCADA clock to local clock update function. This clock is transmitted after acquired
frame from the SCADA gateway has been checked and its control fields removed.
When the acquisition of clock message from SCADA gateway is operating (depending on the
priority), the computer receives a clock synchronisation message from the SCADA. An
interruption is related to the frame arrival and clock message from SCADA gateway can be
acquired. The delay transmission from SCADA gateway is compensated.
Whatever the protocol, clock message from SCADA gateway must contain:
Day / month / year / hour / minutes / seconds / milliseconds
The update of computer internal clock upon the clock message from SCADA gateway is
managed as specified in local clock update function.
2.3.3 System master clock
On an IEC61850 network, time synchronisation is based on SNTP ( Simple Network Time
Protocol). In a PACiS system up to two computers can be defined as System Master Clock
and so are SNTP servers. All others IEC61850 equipment are SNTP clients. In case of
failure of one SNTP server ( computer lost) or external clock failure, the SNTP clients will
automatically reconnect to the second server.
2.3.4 Time set by an operator
The user may set time and date directly using the MiCOM C264/C264C local Operator
Interface or the Computer Maintenance Tool (CMT)
If the computer does not receive synchronisation messages from external clock, from
SCADA gateway or from system master clock, an operator is allowed to set its time
manually.
In case of external time reference is operating (external clock, SCADA clock or system
master clock), the time set by an operator is not possible.
Time set by an operator is allowed and activated only if external clock, SCADA gateway and
System Master clock are faulty.
Normally, only the system master clock should be manually time set by an operator. The
device used by the operator to perform this operation depends on which equipment is the
system master clock. Any other equipment in a PACiS system architecture can not be time
set by an operator while it is synchronised by the system master clock. However, it can be
time set if the system master clock can not synchronise it anymore (system master clock
faulty or connection lost).
Then, the computer is time set via the HMI in front panel or by maintenance laptop computer
(CMT). Functionally, time is set by operator thanks to both modifying commands: one for the
date and one for the hour (in practice, another command could be reserved to check the
date and the hour values). Therefore, operator might have two menus available: one menu
to change the date (year/month/day) and another to change the time
(hour/minutes/seconds).
When operator sets time, the internal clock of the computer is suggested to the operator at
the display.
Furthermore, a manual time set indication must be raised and the operator action is logged.
C264/EN FT/C30 Functional Description

Page 16/132

MiCOM C264/C264C

2.3.5 Local clock update
Each computer has its internal clock (local clock) with its own drift. Therefore, this internal
clock must be updated according to external time reference.
So, the purpose of this specification is then to describe the local clock update method from
external time reference.
As this function is based on the acquisition of external time reference, it is the one which
deals with the loss of external time reference clock and manages the synchronisation status
of the computer.
Time information, it includes:
Loss of external clock, SCADA gateway clock message or system master clock.
Indication that time has been roughly updated. Consequently, this indication allows
detecting any difference between internal and received clock greater than the fixed
value (
threshold =
20 millisecond). This time discrepancy is signaled: printed and archived
event.
Indication that time was set by an operator. This manual time set indication is
required in order to time-tag events occurring.
The internal time format is GMT. The time difference between GMT and local time is a
parameter set at configuration time.
Internal clock of the computer deals automatically with all dates including leap years up to
2037. Computer clock deals also automatically with seasonal time changes by using
indications given in the DST information in TZTAB file. If DST rules change computer can be
set with new rules.
The computer manages milliseconds itself with its quartz.
At initialisation, the synchronisation upon external clock is declared not-synchronised. This
status remains the same till a control has been made upon driver initialisation which role is to
receive external synchronisation frames. When the control is OK and at the reception of the
first external clock message, the synchronisation upon external clock is declared valid and
the external clock is considered connected.
Once synchronisation upon external clock validated, the synchronisation upon external clock
could come back in invalidity: the computer has not received external synchronisation
message for N minute(s) (external clock failure). The value of this timing is 300 seconds. The
internal clock keeps the frequency it had before the external clock failure.
In case of external clock failure (disconnection or message contains invalid data), an internal
signaling or an alarm must be activated by internal generation and the system master clock
is declared invalid. In this case, the events must be marked by a non-synchronisation
indication as long as the default is present.
When a station bus equipment has not received synchronisation messages for 180 seconds
it raises an alarm. Events processed by this equipment are time tagged with a local fault
indication and stops the IEDs synchronisation.
So, this function manages the synchronisation status of the computer as following:
Not synchronized: this is the status at initialization, the computer has never been
synchronized since booting or rebooting. Date and time are invalid.
Synchronized: the computer receives periodically the date and time. Date and time
are valid. Or the computer is master clock on the Ethernet network for other
equipment.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 17/132

2.3.5.1 Management of loss of external time reference
As the local clock update function receives external time reference, it manages the loss of
external time reference.
So:
if external clock is lost then local clock update points out loss of external clock
if clock message from SCADA gateway is lost then local clock update points out loss
of SCADA gateway clock message
if system master clock is lost then local clock update points out loss of system master
clock
2.3.5.2 Update method
When the external clock acquisition is validated, the synchronisation of internal system
master clock on the external time reference is managed as following:
If a difference between the internal clock value and the external time reference value
transmitted exists, |C
internal
C
external
| 0:
If |C
internal
C
external
| < 1 ms, the internal clock is not modified
If |C
internal
C
external
| > 1ms, two different cases are processed:
1. if |C
internal
C
external
|
threshold
(20 ms), the value of internal clock is progressively corrected
(reduced or increased). This compensation is performed in a set time (t
1
=60 s).
2. if |C
internal
C
external
|
threshold
(20 ms), the internal hour is updated roughly.
In case of external clock is received from time setting by an operator, local clock must be
directly updated roughly.
2.3.5.3 Limits an performances
The quartz drift (i.e. deviation of the internal oscillator of the computer) is lower than 0,5
s/day (i.e. 5,8 s/s). This quartz drift is assured on all the operating temperature range.

C264/EN FT/C30 Functional Description

Page 18/132

MiCOM C264/C264C

2.4 Redundancy Management
Equipment redundancy is managed using two identical computers with same hardware and
database.
The two redundant computers are the main computer and backup computer. The computer
that performs the bay(s) management is the active computer; the other one is the standby
computer. So, a redundant computer can be main/active, main/standby, backup/active
and backup/standby. During the boot time, the main computer will be the active one (if
both computers are fully operational).
The two computers perform simultaneously the same functions (inputs acquisition and
processing, archiving, automation), but at a given time, only the active computer sends
controls to the electrical process or on the Station Bus. A PACiS IEC-61850 client
receives information from the two computers: so, a dedicated mechanism allows to process
only information received from the active computer. Only the active computer manages
communication with IED or SCADA.
This switchover from the active to the standby (and vice-versa) is performed automatically
according to following features.
C0125ENb
MAIN
COMPUTER
BACKUP
COMPUTER
Station Bus
Active State Control/Indication
IEC 61850 client state Control/Indication
DI1 DO1 DI2 DO2 DI1 DO1 DI2 DO2

FIGURE 6: REDUNDANCY MANAGEMENT
The two computers exchange information using:
The Station Bus, to give their internal status (IS)
2 couples of DI/DO of the BIU board:
DI1/DO1 to indicate the Active Status: DO1 is closed if the computer is Active
DI2/DO2 to indicate a Station Bus failure: DO2 is open in case of failure
A value is given to each type of computer failure: the computer IS is calculated by
summing all failure values. The healthiest computer is the one with the minimal
internal status. The healthiest computer is active.
Computer failure Value
DOU board failure 0x20
CCU board failure 0x10
CT/VT board failure 0x08
DIU board failure 0x04
BIU board failure 0x02
AIU board failure 0x01
The algorithm to elect the Active computer is described in the table below.
The initial state is Initialisation (state 0) and the DI11 event is generated.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 19/132

L_IS is the internal status of the computer, R_IS is the internal status of the redundant
one.
The confirmed DI2 1 event is a detection of a Station Bus failure on the other computer
(DI2 = 0) confirmed during 20 seconds.
T1 is the timer of Active status confirmation during the computer initialisation (default value:
5 seconds for the Main computer, marked in configuration, 30 seconds for the Backup one).
T2 is the timer of master election (default value: 5 seconds).
The switching time is less than 30 seconds.
State 0:
Initialisation
State 1:
Waiting end of
initialisation / T1
timer on going
State 2:
Standby
State 3:
Standby / T2
timer on-
going
State 4:
Active
State 5:
Standby mode
on-going
DI11 T1 timer
launching
go to state 1
/ close DO1
go to state 4
stop T2 timer
go to state 4
/ /
DI1=1 go to state 2 stop T1 timer
go to state 2
/ open DO1
stop T2 timer
go to state 2
go to state 5 /
confirmed
DI21
/ / T2 timer
launching
close DO1
go to state 3
/ / /
Remore IS / / If (L_IS<R_IS)
then
T2 timer
launching
close DO1
go to state 3
If (L_IS>R_IS)
then
stop T2 timer
open DO1
go to state 2
/ /
End of T1
timer
/ If DI11
then:
T2 timer
launching
close DO1
go to state 3
else:
go to state 2
/ not possible not possible /
End of T2
timer
/ / / go to state 4 / /
End of
standby mode
going-on
/ not possible not possible not possible not possible open DO1 if
conditions to enter
standby mode are
not true anymore
then
T2 timer
launching
go to state 3
else
go to state 2


C264/EN FT/C30 Functional Description

Page 20/132

MiCOM C264/C264C

3. COMMUNICATIONS
MiCOM C264/C264C computer ensures up to three different types of communications:
Telecontrol Bus (T-Bus),
Station Bus (S-Bus),
Legacy Bus (L-Bus).
Main characteristics are given below.
C0005ENc
Computer Kernel
Telecontrol
Interface
IEC 61850
T-BUS S-BUS
RTU, SCADA PACiS system, IEC 61850 IEDs
I/O boards Legacy Gateway
L-Bus
IED

FIGURE 7: COMMUNICATIONS
3.1 Telecontrol bus
The available slave protocols are:
IEC 60870-5-101 (T101)
IEC 60870-5-104 (T104)
DNP3.0
DNP3 over IP
MODBUS
MiCOM C264/C264C computer behaves as a slave into master/slave protocol (DNP3.0,
T101, DNP3 over IP, MODBUS) or balanced protocol (T101, T104).
The connection with SCADA is direct or via modem.
Physical layer:
T101, DNP3.0, MODBUS: RS232, RS485
T104, DNP3 over IP: Ethernet 10 or 100 Mb/s: RJ45 connector or optical fibre
(multimode or monomode)
Up to two protocols can be configured, same protocol or not, with or without redundant
channels. The C264 computers have up to four serial ports. Be careful, for the CPU, the
baudrate must be the same on both serial ports.
The redundancy is not available for T104, DNP3 over IP and MODBUS.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 21/132

3.2 Legacy bus
MiCOM C264/C264C computer behaves as a master.
Protocols:
IEC 60870-5-103 (T103)
IEC 60870-5-101 (T101)
ModBus
DNP3
Devices connected to: IEDs
Physical layer:
RS232, RS485
Optical fibre
Four serial ports are available to make four networks with different protocols or not.
For T103 and Modbus, a tunnelling mode is available. This allows a setting software running
on a personal computer to access the IEDs through the MiCOM C264/C264C.
3.3 Station bus
The S-BUS Protocol is used for PACiS subsystems communication but it is also available for
other equipment.
A MiCOM C264/C264C computer behaves mainly as a server but it can be also a client of
other MiCOM C264/C264C computers (distributed automations) or IEC 61850 IED.
Protocol:
IEC 61850
Devices connected to:
PACiS devices (OI, SMT, PACiS Gateway)
Other MiCOM C264/C264C computers
IEC 61850 IEDs
Link layer: Ethernet 10 or 100 Mb/s
Physical support:
Copper twisted pair (RJ45 connector)
Optical fibber (multimode or monomode)
The optical port is optional. To increase the number of Ethernet port, two Ethernet switch
boards are available:
SWU with 4 RJ45 ports and up 2 optical ports (multimode or monomode)
SWR with 4 RJ45 ports and 2 optical ports for a redundant ring (multimode or
monomode)
C264/EN FT/C30 Functional Description

Page 22/132

MiCOM C264/C264C

3.3.1 Exchanges
MiCOM C264/C264C computer acquires and sends data on IEC-61850 network using two
mechanisms:
REPORT
GOOSE
The REPORT is specific between a server and one client, it provides:
data value
data state or quality attribute (validity and several kind of invalid state)
time tag of last data value change
time tag quality attribute (server synchronised or not when event has occured)
Data quality defines if data is valid or several kind of invalidity: unknown when disconnected,
Saturated, Undefined REPORTS are sent/received with their RFI (Reason For Inclusion):
periodic, spontaneous state/value change or following control.
The GOOSE is a short message ( data value and quality) sent in multicast to all SBUS
equipment, this is quicker than Report.
3.3.2 Supported Common Data Classes
MiCOM C264/C264C computer exchanges data using Common Data Classes. The following
list gives implemented ones:
Kind of information IEC 61850 Common Data Classes
Single Point Status (SPS)
Double Point Status (DPS)
Integer Status (INS)
Protection Activation Information (ACT)
Directional Protection Activation Information (ACD)
Status Information
Binary Counter Reading (BCR)
Measured Value (MV)
WYE
Measurand Information
Delta (DEL)
Controllable Single Point (SPC)
Controllable Double Point (DPC)
Controllable Integer Status (INC)
Controllable Status Information
Binary Controlled Step Position Information (BSC)
Controllable Analogue Information Controllable Analogue Setpoint Information (APC)
TABLEAU 1: DATA MANAGEMENT
3.3.3 Controls
MiCOM C264/C264C supports Common Data Classes control expressed with SPC, DPC,
INC and APC configured as Direct Execute or SBO.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 23/132

4. DIRECT PROCESS ACCESS
Several kinds of boards can be used in MiCOM C264/C264C. Digital Input & Outputs,
Measurement acquisitions are checked to validate information/action and time tagged on any
change of state or value.
The MiCOM C264/C264C computer acquires digital and analogue inputs, counters, digital
measurements, and analogue measurements from CT/VT. Configuration parameters,
filtering and triggering are applied to these inputs and depend on their type.
4.1 Input check
Input data coming from the physical MiCOM C264/C264C boards or from the different
communication networks are periodically checked. Invalidity status of these data is internally
fixed for:
Self-test (DI, AI, board self test failure)
Unknown (DI, AI, communication failure to remote acquisition like IED)
Toggling (DI, X change of state in given time)
Over-range (AI, saturation of its transducer, or Counter value reaching limits)
Open Circuit (AI kind 4-20mA with current value under 4mA)
Undefined (Digital Measurement or Counter with invalid DI coding)
4.2 Output check
Output boards are periodically checked at their logical level. In the event of a logical circuit
test fails the board is set faulty. Controls on this board or upon disconnected IEDs are
refused.
4.3 Time tagging
All physical input data are time tagged with a 1ms accuracy. All internal logic data are time
stamped with a 1ms accuracy.
Analogue acquisition time tagging is done but driven by periodic polling of this kind of board.
Periods are based on multiple of 100ms.
Information coming from IED is time tagged by IED itself if it has this facility otherwise it is
performed at computer level when receiving the data.
4.4 Digital input acquisition (DI)
4.4.1 Acquisition
Acquisition of binary information is done via DIU200/DIU210 (16 DIs) or CCU200 (8 DIs + 4
DOs) boards:
Digital Input (DI) can take one among two values: 1 or 0. The value 1 is associated with the
presence of an external voltage; the value 0 is associated with the absence of the voltage.
The values, 1 or 0 are written by the hardware when the external voltage is above (or below
a threshold). The value of the threshold is given in the hardware specification document.
A transition from 0 to 1 or 1 to 0 is generally followed by a succession of transitions
(bounces) before the value stabilises. It is necessary that the software filters these bounces.
Each change of state of a digital input is time stamped with a resolution better than 1 ms.
C264/EN FT/C30 Functional Description

Page 24/132

MiCOM C264/C264C

C0126ENa
Hardware
acquisition
Time
stamping
Software
acquisition
Debouncing &
Filtering for BI
Debouncing &
Filtering for
DM
Debouncing &
Filtering for
counters
Toggle
Filtering for
BI
Special
treatment
for DM
Special
treatment
for
counters
To BI
treatment
To measurements
treatment
To counters
treatment

FIGURE 8: DIGITAL INPUT PROCESSING
4.4.2 Debouncing and filtering
A filtering is applied on digital inputs as follow:
C0127ENa
Filtering time
t
0 t
1
t
2
Debouncing
time

FIGURE 9: DIGITAL INPUT FILTERING AND DEBOUNCING
t
0
is the instant of detection of the first transition. t
1
is the instant of validation of the change of
state. t
2
is the end of the filtering. (the signal has remained stable from t
1
to t
2
). The change of
state is time stamped at t
0 .

A value of 0 means that no filter is applied: a change of state is validated as soon as it is
detected.
Three couple of delays (debouncing / filtering) are defined:
one for all DI which will be used as BI
one for all DI which will be used as DM
one for all DI which will be used as counters
4.4.3 Toggling
A digital input is said to be toggling if its state has changed more than N times in a given
period of time T
1
.
A toggling DI returns in the normal state if its state has not changed within another period of
time T
2
.
N, T
1
and T
2
are parameters determined at configuration time on a per system basis (same
parameters for all MiCOM C264/C264C computers of a system).
The toggle filtering applies only on DI that will be used as BI (there is no toggle filtering on DI
that will be used for counters or DM).
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 25/132

4.5 Counters acquisition (CT)
The counters are acquired on the same boards as the DIs. There are two types of counters
SCT (Single counter) and DCT (Double counters).
This interface allows acquisitions of pulses delivered from energy metering devices
corresponding to a calibrated quantity of energy.
Each valid pulse increments the value of an accumulator used to compute the quantity of
energy delivered during a given period.
Counter values are stored in static memory (secured with a capacitor, > 48h autonomy);
Counters are kept for more than 48H when the C264 power supply is off.
The pulse frequency should be 20 Hz as a maximum. So, the debouncing and filtering
values must be chosen in consequence.
4.5.1 Single counter (SCT)
A SCT is acquired on a single contact.
The value of the accumulator is incremented after a low to high transition, confirmed after a
filtering time (T
count
). T
count
is defined for the whole system, with a step of 5ms: the chosen
value must be coherent with the pulse frequency (i.e. all counters of a system use the same
T
count
).
A subsequent pulse can be taken into account only after a high to low transition.
C0128ENa
T
count T
count
Low to high transition
Transition discarded
Low to high transition
Transition validated,
counter is incremented

FIGURE 10: SINGLE COUNTER CHRONOGRAM
4.5.2 Double counter (DCT)
A double counter is acquired on two contacts: one is called the true contact (TC), the other is
the complemented contact (CC). Normally these contacts should have complementary
states.
Pulses are detected in the same manner as for SCT, on the TC variations, using the T
count

delay (the same T
count
value is used for SCT and DCT).
A subsequent pulse can be taken into account only after a high to low transition on TC (and
so a low to high transition on CC).
The difference is that both contacts should be in complementary states for transitions to be
detected and validated. The counter is invalid if there exists a non-complementarity between
the 2 contacts during a delay T
def
. This delay is defined for the whole system (i.e. all DCT use
the same delay).
C264/EN FT/C30 Functional Description

Page 26/132

MiCOM C264/C264C

C0129ENa
T
count T
count
Low to high transition
Low to high transition
Transition discarded, and
high to low transition
Transition validated,
counter is incremented
Non-complementarity
confirmed, counter is invalid
Detection of non-complementarity
TC
CC
T
def
Low to high transition, but no
validated high to low transition
before -> T
count
is not launched

FIGURE 11: DOUBLE COUNTER CHRONOGRAM
4.6 Digital measurement (DM)
The digital measurements (DM) are derived from the Digital Inputs. They are acquired on the
same boards as the DIs.
This interface, allowing acquisitions of a digital measurement, is a digital value coded on N
wired inputs. Each wired input represents a bit of the value, and can take only one of two
values: low or high. The maximum number of digital inputs can be used for a digital
measurement is 64.
DM are used to process measurements and tap position indications.
A DM can be associated to a Read Inhibit (RI) signal. The acquisition process is different
depending on the presence of this RI signal.
4.6.1 Acquisition without Read Inhibit signal
The DM is calculated at each change of state of one of its inputs.
A stability processing is applied at each calculation to confirm the value.
If the difference between the current value and the previous confirmed value is less or equal
than V
stab
(value defined in configuration), then the current value is confirmed.
If the difference is greater than V
stab
, then the T
stab
delay is launched (value defined in
configuration, from 0 to 60s, with a 10 ms step). If a T
stab
delay is already launched, this one
is cancelled. At the end of the delay, the DM value is confirmed.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 27/132

C0130ENa
Confirmed
DM value
Bit change => new
calculation
V
stab
=> confirmed
DM value
Confirmed
DM value
Bit change =>
new calculation
>V
stab
=> T
stab
launched
T
stab
Bit change =>
new calculation
>V
stab
=> T
stab
re-launched
T
stab
Confirmed
DM value
Note : = |confirmed DM value new calculation|

FIGURE 12: DM VALUE CONFIRMED
Furthermore, an invalidity processing is applied: at the first change of state of one bit
following a confirmed DM value, the T
Inv
delay is launched (value defined in configuration,
from 0 to 300s, with a 10 ms step). If the value is not confirmed at the end of this delay, the
DM is declared UNDEFINED.
C0131ENa
Confirmed
DM value
Bit change =>
new calculation
>V
stab
=> T
stab
launched
T
stab
Bit change =>
new calculation new calculation
>V
stab
=> T
stab
re-launched
T
stab
DM UNDEFINED
T
Inv
Bit change =>
>V
stab
=> T
stab
re-launched
T
stab


FIGURE 13: DM UNDEFINED
If V
stab
is equal to 0, there is no stability processing: all DM values are sent at each
calculation.
4.6.2 Acquisition with Read Inhibit signal
When the RI signal changes to set state, the T
inh
delay is launched. If the signal is always set
at the end of the delay, the DM is declared UNDEFINED. Otherwise, if the RI signal changes
to reset state before the end of the delay, the current DM value is transmitted.
C0132ENa
T
inh
RI
DM value transmitted
T
inh
DM UNDEFINED

FIGURE 14: ACQUISITION WITH RI
If the RI signal is invalid, the DM will be invalid.
C264/EN FT/C30 Functional Description

Page 28/132

MiCOM C264/C264C

4.6.3 Encoding
The following codes are allowed for DM:
CODE Number of bits ( max. 64) Range of value
4 (1 BCD decade) 0 to 9
8 (2 BCD decades) 0 to 99
12 (3 BCD decades) 0 to 999
16 (4 BCD decades) 0 to 9,999
32 (8 BCD decades) 0 to 99,999,999
BCD
64 (16 BCD decades) 0 to 9,999,999,999,999,999
Binary n 0 to 2
n
-1
Gray n 0 to 2
n
-1
16
(1 bit among 6 for the tens,
1 among 10 for the units)
0 to 69
32
(1 bit among 4 for the thousands,
1 bit among 9 for the hundreds,
1 bit among 9 for the tens,
1 bit among 10 for the units)
0 to 4999
Decimal
64
(1 bit among 9 for the millions,
1 bit among 9 for the hundreds of thousands,
1 bit among 9 for the tens of thousands,
1 bit among 9 for the thousands,
1 bit among 9 for the hundreds,
1 bit among 9 for the tens,
1 bit among 10 for the units)
0 to 9,999,999
1 among N n 0 to n
One supplementary bit can be used for the sign (0 indicates a positive value, 1 indicates a
negative value).
Capability extension for the Tap Position Indication only:
CODE Number of bits Range of value
1 among N 2 to 64 0 to 2
to 0 to 64
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 29/132

4.7 Analogue input acquisition (AI)
Acquisition of AC voltages and currents coming from the electrical network is done via
TMU200 (4CT + 4 VT) board.
Acquisition of DC voltages or currents signals is done via AIU201 (4 AIs) or AIU210 (8 AIs)
boards. For those AI an input range and an acquisition cycle are defined in configuration.
4.7.1 Input ranges
The different input ranges are:
For voltage inputs (AIU201 only): 10 V, 5 V, 2.5 V, 1.25 V
For current inputs: 0 - 1 mA, 1 mA, 0 - 5 mA, 5 mA, 0 - 10 mA, 10 mA, 4 - 20 mA,
0 - 20 mA, 20 mA
The saturation value depends on the selected range.
4.7.2 Acquisition cycle
The analogue inputs are acquired on a periodical basis (short or long cycle, defined in
configuration).
4.8 Digital outputs (DO)
Digital outputs are used to apply a switching voltage to an external device in order to execute
single or dual, transient or permanent commands. The applied voltage is fed from an
external power supply. The external voltage is connected to the controlled device by a relay,
thus isolating the logic part of the board from the external power supply.
Two types of Digital Outputs are available into MiCOM C264/C264C:
CCU200 boards for controls (8 DIs+4 normal open DOs), this board allows double
pole switching controls.
DOU200 boards for alarms (8 normal open DOs + 2 normal open/normal close DOs).
C264/EN FT/C30 Functional Description

Page 30/132

MiCOM C264/C264C

4.9 Digital Setpoints
Digital setpoints are digital values coded on multiple outputs. Each output represents a bit of
the value. Digital setpoints are used to send instruction values to the process or to auxiliary
devices. The maximum number of outputs that can be used for a digital setpoint is 48.
Digital Setpoints are processed on the same boards as the Digital Outputs. The Digital
Outputs characteristics described above apply on Digital Setpoints. Nevertheless, only
standard DO boards with single pole N/O relays can be used.
4.9.1 Encoding
The following codes are allowed:
CODE Number of bits ( max. 48) Range of value
4 ( 1 BCD decade) 0 to 9
8 ( 2 BCD decades) 0 to 99
12 ( 3 BCD decades) 0 to 999
16 ( 4 BCD decades) 0 to 9999
32 ( 8 BCD decades) 0 to 99,999,999
BCD
48 ( 12 BCD decades) 0 to 999,999,999,999
Binary n 0 to 2
n
-1
Gray n 0 to 2
n
-1
16
( 1 bit among 6 for the tens,
1 among 10 for the units)
0 to 69
32
(1 bit among 4 for the thousands,
1 bit among 9 for the hundreds,
1 bit among 9 for the tens,
1 bit among 10 for the units)
0 to 4999
Decimal
48
(bit among 2 for the tens of thousands,
1 bit among 9 for the tens of thousands,
1 bit among 9 for the thousands,
1 bit among 9 for the hundreds,
1 bit among 9 for the tens,
1 bit among 9 for the units)
0 to 299,999
1 among N n 0 to n
Moreover a supplementary bit can be used for the sign ( 0 indicates a positive value, 1
indicates a negative value).
4.9.2 Read Inhibit
A dedicated binary output can be used to allow or forbid the reading of the value by the
external device.
There is one (or none) Read Inhibit (RI) output per value.
If the RI output is a logical one (external polarity applied), the reading is allowed.
The procedure used to output a value with a RI output is:
Reset the RI output to a logical 0: read forbidden.
Wait for N ms
Output the value
Wait for N ms
Set the RI output to a logical 1: reading is allowed.
The 0 to 1 transition on the RI output can be used by the external device as a trigger,
indicating that a new value is available.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 31/132

5. DATA PROCESSING
MiCOM C264/C264C treatment entries can be Binary Inputs or Analogue Inputs. They are
issued from
IOs boards
MiCOM C264/C264C internal information (System Input, automation)
Communication acquisition (IED or other computer from LBUS or SBUS)
5.1 Binary Input processing
5.1.1 Binary Input definition
The five types of Binary Inputs (BI) are:
Single Point (SP): derived from one BI
Double Point (DP): derived from two BIs
Multiple Point (MP): derived from multiple BIs
System Input (SI): information related to the system, to configurable and built-in
automations or to electrical process but without acquisition possibilities
Group: logical combination of BIs
SP, DP and MP are acquired via digital input boards or via IEDs connected by a serial link.
5.1.1.1 Toggling Input
A binary input is said to be toggling if its state has changed more than N times within a given
period of time T.
After the acquisition on digital inputs boards, the computer performs toggle filtering, this
avoids loading the computer itself or other equipment when an input has an hazardous
behaviour
A SP associated with a toggling Binary Input is in the TOGGLING state.
A DP or a MP whose one of the associated DI is toggling ist in the TOGGLING state.
5.1.1.2 Suppression
A binary input can be suppressed by an order issued from an operator. No subsequent
change of state on a suppressed BI can trigger any action e.g. display, alarm, transmission.
The BI takes the SUPPRESSED state. When the operator unsuppresses the BI, this one
takes its actual state.
5.1.1.3 Substitution
A BI can be substituted to a manual set state by an operator (state SUBSTITUTED xxx).
The BI stays in the state determined by the operator until he unsubstitutes it. When a BI is
substituted, no changes of state are transmitted, and computations, for instance groupings,
are made with the substituted state. When the BI is unsubstituted, the actual state is
transmitted to higher control levels and subsequent changes of state are transmitted again.
5.1.1.4 Forcing
When an information is invalid (i.e. SELFCHECK FAULTY, TOGGLING, UNDEFINED or
UNKNOWN), it can be manually forced by an operator (state FORCED xxx). This feature is
similar to the substitution but the information is automatically updated when valid information
is available again. A SUPPRESSED or SUBSTITUTED datapoint cannot be forced. The
forcing could also be automatic: in this case, the invalid information is automatically replaced
by the state defined in configuration.
C264/EN FT/C30 Functional Description

Page 32/132

MiCOM C264/C264C

5.1.1.5 Transmission
By configuration, a BI could be transmitted on a client-server basis on the station bus using
the two modes:
Report based mode: in this mode, a confirmed change of status is spontaneously
transmitted to the subscribers with the time stamping and the reason for change. The
Report mode is used to transmit filtered data for displaying, printing and archiving.
GOOSE based mode: in this mode, the change of status is transmitted in multicast to
the configured receivers. On IEC61850 network, all types of BI can be transmitted
using GOOSE. Only the BI unfiltered states are transmitted with their time stamping,
the reason for change is not. The GOOSE mode is used to transmit data as soon as
possible after their acquisition and as quickly as possible, for automation purpose.
During a loss of communication, the events detected on the computer are not buffered.
5.1.2 Processing of Single Point Status
C0133ENa
Toggle
filtering
Persistance
filtering
Group
processing
Manual
suppression
Substitution
Forcing
To RCP
To HMI
To Printer
To Archive
From
acquisition
To
automation
Transmission
Report based
Transmission
GOOSE based
From IED
IED
inputs
System
Inputs
DI/DO
association

FIGURE 15: SINGLE POINT STATUS PROCESSING
A preliminary treatment (filtering) is applied to specific Single Points (SP) in order to confirm
the state.
The choice of these SPs and the filtering time are fixed by the MiCOM C264/C264C
configuration. If the opposite transition occurs before this delay, both transitions are
discarded.
This treatment is said to be a persistent filtering.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 33/132

The SP resulting states are:
States (Report) Goose
RESET 01
SET 10
TOGGLING 11
SELFCHECK FAULTY 11
UNKNOWN 11
SUPPRESSED 11
FORCED RESET 01
FORCED SET 10
SUBSTITUTED RESET 01
SUBSTITUTED SET 10
For automation (interlock, PSL, PLC, and built in functions), GOOSE are used. Each valid
state (01, 10 and 00) is configurable to be seen by automation in False, True or Invalid sate.
5.1.2.1 Persistence filtering
For some SP, a transition must be confirmed on a certain period of time. If the opposite
transition occurs before this delay, both transitions are discarded.
Two time-out values can be associated with each SP:
T
S
: delay for the SET state confirmation
T
R
: delay for the RESET state confirmation
Both delays are in the range 0 to 120 s by step of 100 ms. A value of 0 means that no filter is
applied.
The time tag is user-selectable:
Mode 1: the status is stamped with the time of the transition.
Mode 2: the status is stamped at the end of the persistent filtering.
C264/EN FT/C30 Functional Description

Page 34/132

MiCOM C264/C264C

C0310ENa
T
S
t
0
t
1
t
2
t
3
t
4
t
5
t
6
t
7
T
R
T
R
T
S
RESET
SET
t
0
: RESET to SET transition
t
1
: SET to RESET transition ; SET state not confirmed. The
transition is discarded (T
R
is not launched because there is no
change of state).
t
2
: RESET to SET transition
t
3
: SET state confirmed (stamped t
2
if mode 1, stamped t
3
if mode 2)
t
7
: RESET state confirmed (stamped t
6
if mode 1, stamped t
7
if
mode 2)
t
4
: SET to RESET transition
t
5
: RESET to SET transition ; RESET state not confirmed. The
transition is discarded (T
S
is not launched because there is no
change of state).
t
6
: SET to RESET transition

SP before filtering
SP after filtering, mode 1
SP after filtering, mode 2
RESET
SET
RESET
SET

FIGURE 16: PERSISTENCE FILTERING
5.1.2.2 DI/DO association for SP
The aim of this automation is to create a direct association between a Single Point and a
Digital Output: a state change on the input produces the opening of the closure of the output.
The relation between the state and the order is defined during the configuration phase.
5.1.3 Processing of Double Point Status
A DP is derived from two Digital Inputs. One is called the Closed contact, the other one is the
Open contact.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 35/132

C0134ENa
Toggle
filtering
Persistance
filtering
Motion
filtering
Group
processing
Manual
suppression
Substitution
Forcing
To RCP
To HMI
To Printer
To Archive
Open
contact
From
acquisition
To
automation
Transmission
Report based
Transmission
GOOSE based
From IED
IED
inputs
System
Inputs
DI/DO
association
Toggle
filtering
Close
contact
From
acquisition

FIGURE 17: DOUBLE POINT STATUS PROCESSING
DPS are commonly used for all switchgears position. From board valid acquisition the two
contacts are Close and Open (set by configuration when voltage is present). The position of
the switch is:
Close Contact Open Contact DPS State
0 0 Below motion delay, the state is valid motion. For
REPORT no transmission of the transitory state.
After Motion filtering, state is invalid JAMMED
0 1 OPEN
1 0 CLOSE
1 1 UNDEFINED after a permanent filtering
Preliminary treatment (filtering) for some DPs is applied to filter the MOTION state during a
certain period of time. This avoids the transmission of this (normally) transient state.
This treatment is called motion filtering.
The time tag is user-selectable:
Mode 1: the valid state (OPEN or CLOSE) is stamped with the time of the beginning of
the MOTION state
Mode 2: the valid state (OPEN or CLOSE) is stamped with the time of this valid
transition
This time stamping can be superseded if a persistence filtering applies.
If the MOTION state is confirmed, it is always stamped with the time of the beginning of the
MOTION state. Furthermore, the BI takes the state JAMMED (in case of confirmed
MOTION00 state) or UNDEFINED (in case of confirmed MOTION11 state). In this case, the
following valid state (OPEN or CLOSE) is always time-stamped with the time of this valid
transition (depending on the persistence filtering feature).
C264/EN FT/C30 Functional Description

Page 36/132

MiCOM C264/C264C

5.1.3.1 Motion filtering
For some DP, the MOTION state must be filtered during a certain period of time in order to
avoid the transmission of this (normally) transient state.
Two time-out values can be associated with each DP:
T
00
: delay for the MOTION00 state filtering
T
11
: delay for the MOTION11 state filtering
Both delays are in the range 0 to 60 s by step of 100 ms. A value of 0 means that no filter is
applied.
The time tag is user-selectable:
Mode 1: the valid state (OPEN or CLOSE) is stamped with the time of the beginning of
the MOTION state
Mode 2: the valid state (OPEN or CLOSE) is stamped with the time of this valid
transition
This time stamping can be superseded if a persistence filtering applies.
If the MOTION state is confirmed, it is always stamped with the time of the beginning of the
MOTION state. Furthermore, the BI takes the state JAMMED (in case of confirmed
MOTION00 state) or UNDEFINED (in case of confirmed MOTION11 state). In this case, the
following valid state (OPEN or CLOSE) is always time-stamped with the time of this valid
transition (depending on the persistence filtering feature).

C0311ENa
T
00
T
11
T
11
T
00
CLOSE
OPEN
t
0
t
1
t
2
t
3
t
4
t
5
t
6
t
7
t
8
t
0
: MOTION00 transition
t
1
: MOTION00 state not confirmed, CLOSE state time-stamped t
0
if mode 1, t
1
if mode 2
(if no persistence filtering applies)
t
2
: MOTION00 transition
t
3
: MOTION00 state confirmed, state JAMMED time-stamped t
2
t
4
: OPEN transition, time-stamped t
4
whatever was the mode (if no persistence filtering applies)
t
5
: MOTION11 transition
t
6
: MOTION11 state not confirmed
t
7
: MOTION11 transition
t
8
: MOTION11 state confirmed, state UNDEFINED time-stamped t
8

FIGURE 18: MOTION FILTERING
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 37/132

5.1.3.2 DP persistence filtering
For some DP, a valid state (OPEN or CLOSE) must be confirmed on a certain period of time.
If a transition occurs before this delay, the state is discarded.
Two time-out values can be associated with each DP:
T
C
: delay for the CLOSE state confirmation
T
O
: delay for the OPEN state confirmation
Both delays are in the range 0 to 60 s by step of 100 ms. A value of 0 means that no filter is
applied.
The time tag is user-selectable:
Mode 1: the status is stamped with the time of the transition
Mode 2: the status is stamped at the end of the delay.
NOTE: If a persistence filtering is applied, the OPEN or CLOSE state cannot
be time-stamped from the beginning of non-complementarity (i.e.
mode 1 of motion filtering cannot apply).
C0312ENa
T
C
T
C
T
O
T
O
CLOSE
OPEN
t
0
t
1
t
2
t
3
t
4
t
5
t
6
t
7
t
0
: CLOSE transition
t
1
: CLOSE state not confirmed
t
2
: CLOSE transition
t
3
: CLOSE state confirmed (stamped t
2
if mode 1, stamped t
3
if mode 2)
t
4
: OPEN transition
t
5
: OPEN state not confirmed
t
6
: OPEN transition
t
7
: OPEN state confirmed (stamped t
6
if mode 1, stamped t
7
if mode 2)

FIGURE 19: DP PERSISTENCE FILTERING
C264/EN FT/C30 Functional Description

Page 38/132

MiCOM C264/C264C

The DP resulting states are:
States (report) Goose
JAMMED 11
MOTION 00
OPEN 10
CLOSE 01
UNDEFINED 11
TOGGLING 11
SELFCHECK FAULTY 11
UNKNOWN 11
SUPPRESSED 11
FORCED JAMMED 11
FORCED OPEN 10
FORCED CLOSED 01
SUBSTITUTED JAMMED 11
SUBSTITUTED OPEN 10
SUBSTITUTED CLOSED 01
5.1.3.3 DI/DO association for DP
The aim of this automation is to create a direct association between a Double Point and a
Digital Output: a state change on the input produces the opening or the closure of the output.
The relation between the state and the order is defined during the configuration phase.
5.1.4 Processing of Multiple Point Status
A Multiple Point (MP) is derived from N Digital Inputs. It could be also called 1 among N
BIs. Transient filtering is also added on acquisition for the cases where no Digital Inputs is
SET or more than one Digital Inputs are SET. After this delay, the MP becomes
UNDEFINED.
N is fixed by MiCOM C264/C264C configuration from 2 to 32. There is no GOOSE
transmission mechanism.
A MP can be used in two ways:
as a status (MPS): in this case, N is up to 16
as a value, only for TPI: in this case, N is up to 64
C0135ENa
Toggle
filtering
MP filtering
Manual
suppression
Substitution
Forcing
contact N
From
acquisition Transmission
Report based
System
Inputs
Toggle
filtering
contact 1
From
acquisition

FIGURE 20: MULTI POINT STATUS PROCESSING
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 39/132

5.1.4.1 Multiple Point resulting states
The MP resulting states, following the various filters that can be applied, are:
STATE1 to STATE32
UNDEFINED
TOGGLING
SELFCHECK FAULTY
UNKNOWN
SUPPRESSED
FORCED STATE1 to FORCED STATE32
SUBSTITUTED STATE1 to SUBSTITUTED STATE32
NOTE 1: State names that will be displayed at the user interface are defined at
configuration time.
NOTE 2: For TPI states, refer to TPI chapter.
5.1.4.2 Multiple Point filtering
MP is not being considered in the UNDEFINED state if the position has changed by more
than one step.
MP is UNDEFINED after a user selectable time filtering (from 0 to 60 seconds, step 100 ms)
when no DI is in the SET state (all RESET) or if more than one are in the SET state:
C0313ENa
undefined
valid
MP after
filtering
MP before
filtering
undefined
valid
Time-out Time-out

FIGURE 21: MULTIPLE POINT FILTERING
The MP is time-tagged with the date of the last BI change.
5.1.5 System Inputs
System inputs are binary information related to:
an equipment or system internal state, such as hardware faults or system faults
a configurable or built-in automation (status of the automation, binary input created by
the automation, )
electrical process information which have no acquisition possibilities (i.e. no
acquisition through DI or through serial communication) but which must be managed
by the MiCOM computer: the status of these information are saved in non-volatile
memory.
A SI is of SP, DP or MP type and can belong to any type of group.
The processing of a SI is given in the SP / DP / MP data flow.
C264/EN FT/C30 Functional Description

Page 40/132

MiCOM C264/C264C

5.1.6 IED inputs
These inputs are acquired from IEDs or protective relays via serial links.
If they are not time tagged by the IED, they are by the computer at the time of reception. This
must be configured for each IED.
An IED input is of SP, DP or MP type.
Double inputs can be processed in IEDs. If they are not, the computer must receive each
individual input and perform the DP processing. This must be configured for each IED.
The processing of an IED input is given in the SP / DP / MP data flow.
5.1.7 Group processing
A group is a logical OR, AND, NOR or NAND combination of Binary Inputs (BIs) or groups.
A group component can be a SP, DP (direct or via IED), SI, Group. A component can belong
to several groups.
A group is processed as a SP. It is time stamped with the date / time of the last data-point
which has modified the group status.
A group is calculated with filtered BIs (persistent filtering or motion filtering if configured).
Other computer BIs coming from reports.
The binary inputs states are taken into account as follows:
Single Point Status treated in a group as
SET, FORCED SET,
SUBSTITUTED SET
SET
RESET, FORCED RESET,
SUBSTITUTED RESET
RESET
SELFCHECK FAULTY, TOGGLING,
UNKNOWN
INVALID
SUPPRESSED SUPPRESSED

Double Point Status treated in a group as
CLOSE, FORCED CLOSE,
SUBSTITUTED CLOSE
SET
OPEN, FORCED OPEN,
SUBSTITUTED OPEN
RESET
JAMMED, FORCED JAMMED,
SUBSTITUTED JAMMED,
UNDEFINED, SELFCHECK
FAULTY, TOGGLING, UNKNOWN
INVALID
SUPPRESSED SUPPRESSED

OR SET RESET INVALID SUPPRESSED
SET SET SET SET SET
RESET SET RESET INVALID RESET
INVALID SET INVALID INVALID INVALID
SUPPRESSED SET RESET INVALID SUPPRESSED

Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 41/132

AND SET RESET INVALID SUPPRESSED
SET SET RESET INVALID SET
RESET RESET RESET RESET RESET
INVALID INVALID RESET INVALID INVALID
SUPPRESSED SET RESET INVALID SUPPRESSED

NOT
SET RESET
RESET SET
INVALID INVALID
SUPPRESSED SUPPRESSED
SP and SI from different hierarchical levels can be mixed, for instance a group at substation
computer level can be composed of SP acquired at bay computer level or at substation
computer level.
A group is time stamped with the date / time of the last datapoint which has modified the
group status.
5.1.8 SBMC Mode Processing
When a Bay is in SBMC mode (Site Based Maintenance Control), the status of the Binary
Inputs (associated to this Bay and defined as SBMC dependant), takes the forced state
defined in the configuration.
This forced information is delivered to the Remote Control Point (RCP) as long as the SBMC
mode is active on the Bay.
For a group a special feature is implemented: a BI belonging to a group, which is dependent
of SBMC bay state, is not taken into account in group computation if the bay is set in SBMC
mode. If all the BI of a group belong to one or more bays, which are all in SBMC mode, the
group is then in the suppressed state. At the end of a bay SBMC mode, all groups owning BI
of this bay are re-computed.
5.1.9 BI sent to automatism features
In case of automatism running on a client computer, with BI information coming from a
server computer, BI are generally transmitted in the GOOSE based mode. In some cases
where the GOOSE based mode is not used, BI information received by IEC61850 reports
must be used in automatism features.
In any cases where GOOSE based mode and report based mode are used at the same time,
the BI information used is the one receive by GOOSE ( faster transmission than reports).

C264/EN FT/C30 Functional Description

Page 42/132

MiCOM C264/C264C

5.2 Measurement Input Processing
Measurement Value can be Analogue Measurement, or Digital Measurement. Analogue
Measurements are acquired from communication or from computer boards (AIU201 or
AIU210 or AIU211 for DC or TMU200 or TMU220 for AC). Digital Measurement comes from
Digital input boards.
The processing of a measurement is represented by the following dataflow:
Open circuit
management
Zero value
suppression
Scaling
Threshold
detection
CT/VT
calculations
Manual
suppression
Substitution
Forcing
Transmission
from IED
acquisition
from analogue
acquisition
from digital
acquisition
from CT/VT
acquisition
to:
RCP
HMI
Printer
Archive
Automation
Scaling
C0136ENb

FIGURE 22: ANALOGUE PROCESSING
5.2.1 Open circuit management
For 4-20 mA transducers, a special feature is implemented to avoid fleeting values around
4 mA:
in the range [0 .. 3 mA[, the measurement value is set to 0 and the status is set to
OPEN CIRCUIT
in the range [3 .. 4 mA], the analogue input is considered to be equal to 0 mA.
5.2.2 Scaling
The real value represented by the measurement can be computed by a linear or a quadratic
transformation:
Linear, single slope
Value = A*X + B
Linear, multisegments
Value = A
i
*X + B
i
with X
i
X<X
i+1
.
Up to 20 configurable segments [X
i
.. X
i
+1]
Quadratic
Value = A X + B or
Value = AX B +
Transformation law and A / B coefficients are defined in configuration.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 43/132

5.2.3 Zero value suppression
The function Y=f( X) representative of this processing is defined as follows:
if X[ -deadband/2, +deadband/2] Y=0 and state = VALID
if X[ -deadband/2, +deadband/2] Y=X and state = VALID
NOTEs:
X is an analogue measurement
deadband is a percentage of the full scale value of the measurement. These two
parameters have to be set during the configuration of the computer.
zero suppression
area
Zero value
suppression
X Y
X
Y
+ deadband/2
- deadband/2
C0359ENa

FIGURE 23: ZERO VALUE SUPPRESSION
5.2.4 Thresholds detection
Six thresholds can be defined for each measurement: 3 upper thresholds and 3 lower
thresholds.
A hysteresis value configured on a per measurement basis is associated to the threshold
management. This value is a percentage of the full scale value of the measurement.
C0313ENa
upper
lower
HYST
HYST
t
1
t
3
t
4
t
2
t
1
: upper threshold violation
t
2
: end of upper threshold violation
t
3
: lower threshold violation
t
4
: end of lower threshold violation

FIGURE 24: THRESHOLDS DETECTION
C264/EN FT/C30 Functional Description

Page 44/132

MiCOM C264/C264C

5.2.5 Manual suppression
A measurement can be assigned to the SUPPRESSED state by an order issued from an
operator. No subsequent change of value or state on a "SUPPRESSED" measurement can
trigger any action e.g. display, alarm, transmission. The measurement takes the
SUPPRESSED state. When the operator "unsuppresses" the measurement, this one takes
its actual state.
5.2.6 Substitution
The value of a measurement can be substituted by an operator (state SUBSTITUTED,
value defined by the operator). The measurement stays in this state until he unsubstitutes it.
When a measurement is substituted, no change of value nor state is transmitted, and
computations are made with the substituted state. When the measurement is unsubstituted,
the actual state and value are transmitted to higher control levels and subsequent changes
of state and value are transmitted again.
5.2.7 Forcing an invalid measurement
When a measurement is invalid (i.e. SELFCHECK FAULTY, UNDEFINED, OPEN CIRCUIT,
SATURATED or UNKNOWN), it can be manually forced by a user (state FORCED, value
defined by the operator). This feature is similar to the substitution but the information is
automatically updated when valid information is available again.
The forcing could also be automatic: in this case, the invalid information takes automatically
the FORCED state and the value defined in configuration.
5.2.8 Measurement resulting states
The Measurement resulting states, following the various filters, which can be applied, are:
State Meaning
VALID Not in one of the following states
SELFCHECK FAULTY AI, DI board fault
SUBSTITUTED Operator action set MV value as valid state
FORCED Automatic valid state and configured value when AI is invalid
SUPPRESSED Operator set MV in this invalid state
UNKNOWN MV is acquired via a transmission link, and the link is
disconnected
SATURATED MV is beyond its nominal input range
UNDEFINED MV is Digital Measurement with invalid coding or computation on
analogue leads to error
OPEN CIRCUIT MV is DC 4-20 mA with input value under 4mA
OVERSHOOT[1..3] One of the 3 overshoot values has been crossed
UNDERSHOOT[1..3] One of the 3 undershoot values has been crossed
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 45/132

5.2.9 Transmission
The measurement value and state are transmitted on a client-server basis on the Ethernet
IEC-61850 network, using two modes:
Report based mode: the measurement is transmitted to the subscribers with its
value, its status, its time stamping and the reason for change.
GOOSE based mode (only on IEC61850 network): the measurement is transmitted
in multicast to the configured receivers
During a loss of communication between a client and a server, all server measurements are
set to UNKNOWN on the client.
The measurement information transmitted in a report are:
the real value (i.e. after scaling)
the resulting state (mapped on the quality field on IEC-61850)
the time stamping (in GMT time) and time quality
the reason for change, which could be one of the below values:
change of quality (set if the measurement resulting state has changed)
cyclic change (set if the measurement value has changed, without modification of
the resulting state)
A Measurement value can be transmitted periodically or upon variation (% of nominal), and
anyway on state change.
5.2.9.1 Periodic Transmission
Two periods are defined in database, on a per MiCOM computer basis:
a short period from 0,1 to 60 seconds (step 0,1 second)
a long period, from 0,5 to 60 seconds (step 0,5 second)
Each measurement is associated to one of the two periods. All measurements of one period
are transmitted at the beginning of each cycle.
All measurements values transmitted within one transmission cycle are the latest acquired
values.
5.2.9.2 Transmission upon variation
Measurements can be transmitted upon variation: a value is sent if the acquired value (Vacq)
is different from more than a specified amount V from the previously transmitted value (Vt) (
i.e |Vacq-Vt| > V).
V is computed either from the last transmitted value (mode 1) or from the full scale value
(mode 2):
V = (p/1000) * |Vt| where p is a value in the range 0 .. 255 and Vt is the last transmitted
value.
or
V = (p/1000) * |Vmax| where p is a value in the range 0 .. 255 and Vmax is the full scale
value.
5.2.9.3 Transmission upon trigger
One or more measurements can be associated to a single or double BI trigger. When the
BI goes to the state SET / CLOSED (or FORCED SET, SUBSTITUTED SET, FORCED
CLOSED / SUBSTITUTED CLOSED) all associated measurements are transmitted
immediately. The same behaviour if the BI is in this state at the initialisation of the computer.
As much the BI is in this state the associated measurements are transmitted after change of
state or according to the configuration (periodically, upon variation, threshold variation)
C264/EN FT/C30 Functional Description

Page 46/132

MiCOM C264/C264C

5.2.10 CT/VT additional processing
As it is impossible to plug directly the computers to the high voltage electric network, the
information that they receive come from Current Transformers (CT) and from Voltage
Transformers (VT).
From an electrical point of view, the CT and VT have several purposes:
To deliver a current or a voltage at their secondary, reliable picture of what append in
the concerned high voltage part,
To make the galvanic insulation between the high voltage part and the measurand and
protection circuits,
To protect the measurand circuits against damage when a fault comes onto the high
voltage network.
On the output of the CT / VT inputs acquisitions function, I and V signals issued by the CT
and the VT are represented by samples.
The CT/VT calculation function carries out basic mathematical processing on the memorised
samples and gives derived values from I and V such as power, frequency, This function
then makes it possible to place useful quantities at the disposal of the computer and the
user.
This function is used only for computation of measures used by synchrocheck module or as
information (measurements) for the operator.
5.2.10.1 Inputs
The inputs of the CT/VT Calculation function, issued from the conventional CT/VT inputs,
are:
In case of star coupling:
Samples of I
a

Samples of V
a

Samples of I
b

Samples of V
b

Samples of I
c

Samples of V
c

Samples of V
0
(V
r
) or V
BUSBAR
in case of presence of the synchrocheck function
Validity of I
a
, I
b
, I
c
, I
r
, V
a
, V
b
, V
c
, V
0

In case of delta coupling:
Samples of I
ab

Samples of I
bc

Samples of I
ca
(Ir)


Samples of V
ab

Samples of V
bc

Samples of V
ca

Samples of V
BUSBAR
or V
r

Validity of each sample.
NOTE: 64 samples per period are available;
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 47/132

5.2.10.2 Outputs
The CT/VT calculation functionality provides:
RMS values, for currents and voltages
Frequency of the network
Active power (total and on a per phase basis)
Reactive power (total and on a per phase basis)
Apparent power (total and on a per phase basis)
Power factor (total and on a per phase basis)
Phase angles
Sequence components (I
d
, I
i
, I
0
, V
d
, V
i
, V
0
)
Ratio of harmonics (up to the 15
th
harmonic)
Total Harmonic Distorsion (THD) and Total Demand Distorsion (TDD). Harmonics are
evaluated up to the 15
th
order.
With the additional synchrocheck option, following values are computed:
Slip frequency
Amplitude
Phase difference
Synchrocheck voltage
5.2.10.3 Behaviour
5.2.10.3.1 Principle
The use of power electronics distorts what would ideally be a perfect sine wave. These
distortions are called harmonics. Each individual harmonic has a sine wave shape. The order
of the harmonic is defined by the frequency of the harmonic divided by basic frequency (50 /
60 Hz). The total harmonic distortion represents the sum of all voltage harmonics. The total
demand distortion (TDD) is similar to the THD but applied to currents and with a rated
current (I
n
) as reference.
5.2.10.3.2 Calculation of measurements
Let N be the number of samples recovered for one period of the signal (i.e. 64 samples per
period whatever the network frequency).
All these samples must be gathered in a revolving list stored in active memory. There is thus
in memory an active list of k.N elements. k is the number of sample channels.
Types
The following primary measurements shall be derived directly from sample values:
RMS Current and Voltage
Active Power (Watts)
Vars (Using Active Power calculation method with the voltage samples retarded by
90)
The following measurements shall be obtained from the Fourier of sample values or the
Fourier values of the above-derived measurements.
Sequence Components (Id, Ii, I0, Vd, Vi, V0).
Magnitudes.
Phase angles.
Power Factor.
C264/EN FT/C30 Functional Description

Page 48/132

MiCOM C264/C264C

VA.
THD and TDD.
Specials (for products with check-sync.).
Algorithms
Frequency
The frequency is directly computed through the timer frequency.
Fast Fourier Transform
At each period, the FFT (Fast Fourier Transform) is performed. This gives (among other
things) the value of the phase angle and the magnitude of the fundamental.
RMS values

64
1
63
0

=
=
i
i
V Vrms
Powers
Active power:

=
=
63
0
64
1
i
i i
I V P
Reactive power:

=
63
0
16
64
1
i
i i
I V Q
NOTE: The reactive power is computed by taking the values of the current a
quarter of period before (sin(x) = cos (x pi/2)
Apparent power: Q P S + =
Power factor:
S
P
= ) cos(
Angle: ) ( tan
1
P
Q

=
Harmonics
Harmonic values are directly issued from the FFT.
Sequence components
The sequence component computation is based on the fundamental values of phase and
magnitude (from the FFT), i.e. its imaginar and real part.
Direct component
( )
( ) ) 120 sin( ) ( Re ) 120 cos( ) Im( ) 120 sin( ) ( Re ) 120 cos( ) Im( ) Im(
3
1
) ( Im
) 120 sin( ) Im( ) 120 cos( ) ( Re ) 120 sin( ) Im( ) 120 cos( ) ( Re ) ( Re
3
1
) ( Re
+ + + =
+ + + =
C C B B A direct
C C B B A direct
Inverse component
( )
( ) ) 120 sin( ) ( Re ) 120 cos( ) Im( ) 120 sin( ) ( Re ) 120 cos( ) Im( ) Im(
3
1
) ( Im
) 120 sin( ) Im( ) 120 cos( ) ( Re ) 120 sin( ) Im( ) 120 cos( ) ( Re ) ( Re
3
1
) ( Re
+ + + =
+ + + =
C C B B A direct
C C B B A direct

Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 49/132

Homopolar component
( )
( ) ) Im( ) Im( ) Im(
3
1
) ( Im
) ( Re ) ( Re ) ( Re
3
1
) ( Re
C B A direct
C B A direct
+ + =
+ + =

Check synchronising
The check synchronising mode is the default synchronising mode.
It is performed if the F value is less than a user configured value (generally less than 0.1
Hz). If so, the CT-VT module computes V and . If these values are less than a user
configured threshold, the system closes the breaker. In the other hand, the CT-VT module
prevents the closure of the breaker if the system synchronising has not been activated and
one of the previous conditions is not achieved.
System synchronising
In opposite to the check synchronising, the system synchronising mode is entered when a
close control is received by the CT-VT module and if the F value is under a user defined
threshold.
The system synchronising should have a predictive role. This means that the CT-VT module
should calculate the time to wait before the authorisation of the closure by taking into
account the complete command line, including the mechanical characteristics of the circuit
breaker. This time should be user configured.
Notice that CT-VT module should exit the system synchronising mode after a user defined
tmporisation.
Synchrocheck calculation
Whatever the synchronising mode V, and F have to be calculated. These values are
available through the measurement module.
V is calculated through the RMS value of the voltages on both bus bar and line side.
The value of F is assumed to be constant across the period. As a result, knowing
(through measurement), we know when the synchrocheck conditions are achieved (this will
easily include the reaction time of the breaker aso).
time_synchro = 2 * pi *F /
5.2.10.4 Limits and performances
In order to secure proper accuracy for calculations, the sampling frequency must be exactly
adapted to the signal frequency that fluctuates around basic frequency (50 / 60 Hz).
The accuracy shall be:
0.2% I
n
for the current (with Measurement CT)
0.2% V
n
for the voltage (with voltage droppers)
0.01Hz for the frequency
1 for the angle
1 ms for the time
Up to fifteenth harmonic
0.5% for the power (with measurement CT)
C264/EN FT/C30 Functional Description

Page 50/132

MiCOM C264/C264C

5.2.11 Digital Measurement Processing
A Digital Measurement is derived from a Digital input. Digital Measurements are used for
process measures or Tap indications.
The DM is UNDEFINED in the followings conditions:
The value is not stable.
BCD: a quartet is more than 9
Decimal: no bit is set or more than one for tens or unit
Two others bits can be used:
For read inhibit: in this case, the DM is acquired when the Read Inhibit bit is set.
For the sign
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 51/132

5.3 Tap Position Indication processing
5.3.1 Acquisition from Digital Inputs
The tap position is acquired on digital input boards . It could be:
A Multiple Point , if so, the resulting states are considered as values
A digital measurement using one of the following encoding:
Decimal
Gray
BCD
5.3.2 Acquisition from Analogue Inputs
The tap position is acquired by measuring a current input.
A minimum value Imin (mA) corresponds to the lowest position 1 of the tap , and a maximum
value Imax corresponds to the highest value N.
The input current should take only discrete values: Ik =Imin + (K -1)(Imax_Imin)/(N-1) , with
K the position of the tap.
However the tap is considered in the position K if the current is in the range [Ik-I/2 ..
Ik+I/2], with I = N% of (Imax Imin). The N percentage is defined in configuration.
The tap position is considered UNDEFINED outside of this range.
5.3.3 Manual suppression
A TPI can be suppressed by an order issued from an operator. No subsequent change of
value or state on a suppressed TPI can trigger any action e.g. display, alarm, transmission.
The TPI takes the SUPPRESSED state. When the operator unsuppresses the TPI, this one
takes its actual state.
5.3.4 Substitution
The value of a TPI can be substitute by an operator (state SUBSTITUTED, value defined
by the operator). The TPI stays in this state until he unsubstitutes it.
When a TPI is substituted, no changesof value nor state is transmitted, and computations,
for instance groupings, are made with the substituted state. When the TPI is unsubstituted,
the actual state and value are transmitted to higher control levels and subsequent changes
of state and value are transmitted again.
5.3.5 Forcing an invalid TPI
When a TPI is invalid (i.e. SELFCHECK FAULTY, UNDEFINED or UNKNOWN), it can be
manually forced by a user (state FORCED, value defined by the operator). This feature is
similar to the substitution but the information is automatically updated when valid information
is available again.
The automatic forcing function is not provided for TPI.
C264/EN FT/C30 Functional Description

Page 52/132

MiCOM C264/C264C

5.3.6 TPI resulting states
The state of a tap position can be:
State Comment
VALID not in one of the below states
SELFCHECK FAULTY Due to an AI board fault or a DI board fault
SUBSTITUTED See 4.4
FORCED
SUPPRESSED
UNKNOWN If the tap position is acquired via a transmission link, the
information is unknown when the link is disconnected.
UNDEFINED Due to a wrong encoding for a digital acquisition, or a saturation,
an open-circuit or an out-of-range value for an analogue
acquisition
OVERSHOOT[1..3] It exists 3 Overshoot states, one for each upper threshold
violation. Only one could be set at one time
UNDERSHOOT[1..3] It exists 3 Undershoot states, one for each lower threshold
violation. Only one could be set at one time
5.3.7 Transmission
The TPI are transmitted on a client-server basis on the IEC-61850 network using the report
mechanism.
During a loss of communication between a client and a server, all server TPI are set to
UNKNOWN on the client.
The TPI is transmitted as soon as a value change or a status change is detected. The TPI
information transmitted in a report are:
the TPI value
the resulting state (mapped on the quality field on IEC 61850)
the time stamping (in GMT time) and time quality
the reason for change, which could be one of the below values:
change of data (set if the value has changed)
change of quality (set if the quality has changed)
change due to control (set if the state or quality change is due to a control)
The TPI information transmitted in a GOOSE is the same than in a report, except for the
"reason for change" and the time-stamping.
5.4 Accumulator Input Processing
The accumulator stores its current value in a static memory volatile memory (secured with a
capacitor, >48h autonomy). At configured sample an accumulated value is extracted for
inner computation and transmission (Common Data Class BCR on IEC 61850).
Digital Inputs are used to count pulses. There is Single counter (SCT) based on one DI and
Double Counter (DCT) based on two DIs which count complementary states.
At processing level special persistent and complementary filters eliminate non-stable pulses.
The integer counter (also transmitted) can be scaled (among of energy of valid pulse).
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 53/132

5.5 Energy counting
The energy counting function aims to calculate exported and imported active energy
(in kWh) and exported and imported reactive energy (in kVarh) from active and reactive
power issued from CT/VT calculation, digital, analogue boards measurements or IEDs
measurements..
Calculation of the energy is done periodically. The period is defined either by an external
pulsed applied on a digital input, or by the internal clock of the computer. The choice of the
origin of the periodic signal is defined during the configuration phase on a per computer
basis.
Whatever is the origin of an integrated measurement, the integration is done after scaling
with a step of one second.
The integration method used is the trapezium one:

=
i
E E
( )

+
=

3600
*
2
) (
*
1 1 i i i i
f
i
t t M M
E
S

With:
E = total Energy counter value (continuous register)
E
i
= Integration result at time t
i

S
f
= Scaling Factor (defined during the configuration phase)

M
i
= absolute value of the Measurement at time t
i
t
i
t
i-1
= 1 second
For a given measurement, the integration can be done only after receiving two consecutive
valid values with the same sign of the measurement. The integration result (E
i
) is added to
the associated export or import counter according to the sign of the measurement.
The integration is stopped as soon as the power measurement becomes invalid or changes
of sign. The integration is restarted as soon as two consecutive valid measurement values
with the same sign are received.
Current values of energy counters are stored in secured memory ( 48h autonomy when
power supply is off). Current values of energy counters can be modified by an operator.
Values of energy counters are transmitted on a client-server basis on the IEC-61850 network
using mechanism through the LN MMTR.
During a loss of communication between a client and a server, all server energy counters are
set to UNKNOWN state on the client.
WARNING: THE ENERGY COUNTER VALUES ARE NOT TO BE USED FOR BILLING
APPLICATION.

C264/EN FT/C30 Functional Description

Page 54/132

MiCOM C264/C264C

6. CONTROL SEQUENCES
6.1 Generic description
A Control Sequence is a basic built-in function on a module (switch, relay, and function). It
receives control order, sending back acknowledgement. After checks, control sequence
sends control (protocol or DO), and check correct execution with feed back from protocol or
from DI.
6.1.1 Generalities
The MiCOM C264/C264C allows the following functions:
Control of switching devices (circuit breaker, switch, )
Control of transformers
Control of secondary devices
Locking of switching devices
Control of IEDs
Control of automatisms
The following control types are allowed:
Select control request
Execute control request
Unselect control request
Cancel control request
Upon reception of one of these requests, the computer behaviour is different according to:
The configuration of the device control,
The type of the device,
The computer operating mode.
6.1.1.1 Device control configuration
By configuration, at SCE level, a control may be executed in one of the following modes:
Direct Execute mode: usually for ancillary devices a control may be performed
directly without the selection phase.
Select Before Operate once mode (SBO once): usually for circuits breakers and
disconnectors. The device must be selected before allowing the execution. In that
case the device is managed in two phases: selection and execution. Device
unselection is done automatically by the computer.
Select Before Operate many (SBO many): usually for transformers. The device
must be selected before execute one or more controls before reaching the expected
position (low/raise). In that case the device is managed in three phases: selection,
execution and unselection. The execution phase is repeated for every new control. To
end the controls sequence, the initiator of the request must send an unselection
request.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 55/132

6.1.1.2 Types of devices
Every control sequence may be different according to the type of the device to control. The
complexity of the control sequence may be more or less important depending on the device:
Synchronised or not synchronised circuit breakers, disconnectors and earthing
switches: They are managed in Direct execute mode or SBO once mode with
optional hardware selection of the device in SBO mode.
Transformers: They are managed in the three modes: Direct Execute, SBO
once and SBO many mode with optional hardware selection of the device in SBO
mode.
Ancillary devices: they are usually managed in Direct Execute mode but can be
managed also in SBO once mode.
System Controls: System outputs are used to activate or inactivate automatic
functions on the computer (e.g. Auto-recloser ON/OFF), change operating modes etc.
Controls via Setpoints: are managed in Direct Execute mode and in SBO once
mode.
6.1.2 Control sequence phase management
According to the configuration of the device control, a control sequence is performed in one,
two, or three phases. Each phase of a control sequence (selection, execution and
unselection) may have a normal or abnormal termination and positive or negative
acknowledgement is sent to the IEC-61850 clients subscribed during the configuration
process.
one phase Direct Execute mode:
1. execution phase: If the execution phase ends normally the computer generates
a positive acknowledgement and the control sequence ends. In case of abnormal
termination, the control sequence is aborted and the computer generates a
negative acknowledgement. The hardware selection of the device in Direct
Execute mode is not allowed.
two phases SBO once mode:
1. selection phase: In the selection phase for a normal termination the computer
generates a positive acknowledgement and proceeds to the next phase of the
sequence (execution phase).
2. execution phase: If the execution phase ends normally the computer generates
a positive acknowledgement and the control sequence ends. In case of abnormal
termination, the control sequence is aborted and the computer generates a
negative acknowledgement.
three phases SBO many mode:
1. selection phase: ditto SBO once mode
2. execution phase: If the execution phase ends normally the computer generates
a positive acknowledgement and waits a new execution request. In case of
abnormal termination, the control sequence is aborted and the computer
generates a negative acknowledgement.
3. unselection phase: The computer proceeds to the deselection of the device and
ends control sequence sending positive acknowledgement. In case of fail
deselecting the device the computer sends a negative acknowledgement.
C264/EN FT/C30 Functional Description

Page 56/132

MiCOM C264/C264C

The following figures shows the three control modes of the computer:
C0314ENa
S
e
l
e
c
t

B
e
f
o
r
e

O
p
e
r
a
t
e

m
o
d
e

m
a
n
y

w
i
t
h

d
e
v
i
c
e

s
e
l
e
c
t
i
o
n


S
e
l
e
c
t
i
o
n
c
h
e
c
k
s
E
x
e
c
u
t
i
o
n
c
h
e
c
k
s
S
e
l
e
c
t
i
o
n
c
h
e
c
k
s
H
a
r
d
w
a
r
e
s
e
l
e
c
t
i
o
n
H
a
r
d
w
a
r
e
D
e
s
e
l
e
c
t
i
o
n
E
x
e
c
u
t
i
o
n
c
h
e
c
k
s
E
x
e
c
u
t
i
o
n
c
h
e
c
k
s
E
x
e
c
u
t
i
o
n

v
i
a
I
/
O

b
o
a
r
d
s
o
r
o
r
o
r
o
r
E
x
e
c
u
t
i
o
n

v
i
a
I
E
D
E
x
e
c
u
t
i
o
n

v
i
a
I
/
O

b
o
a
r
d
s
E
x
e
c
u
t
i
o
n

v
i
a
I
E
D
E
x
e
c
u
t
i
o
n

v
i
a
I
/
O

b
o
a
r
d
s
E
x
e
c
u
t
i
o
n

v
i
a
I
E
D
S
y
s
t
e
m
c
o
n
t
r
o
l
s
S
e
l
e
c
t

B
e
f
o
r
e

O
p
e
r
a
t
e

m
o
d
e



D
i
r
e
c
t

e
x
e
c
u
t
e

m
o
d
e

e
x
e
c
u
t
i
o
n

p
h
a
s
e
e
x
e
c
u
t
i
o
n

p
h
a
s
e
s
e
l
e
c
t
i
o
n

p
h
a
s
e
e
x
e
c
u
t
i
o
n

p
h
a
s
e
s
e
l
e
c
t
i
o
n

p
h
a
s
e


FIGURE 25: CONTROL MODES OF THE COMPUTER (1)
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 57/132

C0315ENa



(
1
)

A
n

e
x
e
c
u
t
i
o
n

p
h
a
s
e

w
i
t
h

t
w
o

e
x
e
c
u
t
i
o
n

r
e
q
u
e
s
t
s

i
s

g
i
v
e
n

a
s

a
n

e
x
a
m
p
l
e
,

i
t

m
a
y

h
a
v
e

m
o
r
e

o
r

l
e
s
s

o
r

o
r

S
e
l
e
c
t

B
e
f
o
r
e

O
p
e
r
a
t
e

m
o
d
e

m
a
n
y
S
e
l
e
c
t

B
e
f
o
r
e

O
p
e
r
a
t
e

m
o
d
e

m
a
n
y

w
i
t
h

h
a
r
d
w
a
r
e

d
e
v
i
c
e


E
x
e
c
u
t
i
o
n

v
i
a
I
/
O

b
o
a
r
d
s
E
x
e
c
u
t
i
o
n

v
i
a
I
E
D
E
x
e
c
u
t
i
o
n

v
i
a
I
/
O

b
o
a
r
d
s
D
e
v
i
c
e

u
n
s
e
l
e
c
t
D
e
v
i
c
e

u
n
s
e
l
e
c
t
E
x
e
c
u
t
i
o
n

v
i
a
I
E
D
E
x
e
c
u
t
i
o
n
c
h
e
c
k
s
D
e
v
i
c
e
S
e
l
e
c
t
i
o
n
c
h
e
c
k
s
E
x
e
c
u
t
i
o
n
c
h
e
c
k
s
e
x
e
c
u
t
i
o
n

p
h
a
s
e

(
1
)
s
e
l
e
c
t
i
o
n

p
h
a
s
e
s
e
l
e
c
t
i
o
n

p
h
a
s
e
o
r

o
r

E
x
e
c
u
t
i
o
n

v
i
a
I
/
O

b
o
a
r
d
s
E
x
e
c
u
t
i
o
n

v
i
a
I
E
D
E
x
e
c
u
t
i
o
n

v
i
a
I
/
O

b
o
a
r
d
s
E
x
e
c
u
t
i
o
n

v
i
a
I
E
D
E
x
e
c
u
t
i
o
n
c
h
e
c
k
s
E
x
e
c
u
t
i
o
n
c
h
e
c
k
s
e
x
e
c
u
t
i
o
n

p
h
a
s
e

(
1
)
u
n
s
e
l
e
c
t
i
o
n

p
h
a
s
e
u
n
s
e
l
e
c
t
i
o
n

p
h
a
s
e
H
a
r
d
w
a
r
e
D
e
s
e
l
e
c
t
i
o
n
H
a
r
d
w
a
r
e
S
e
l
e
c
t
i
o
n
S
e
l
e
c
t
i
o
n
c
h
e
c
k
s

FIGURE 26: CONTROL MODES OF THE COMPUTER (2)
C264/EN FT/C30 Functional Description

Page 58/132

MiCOM C264/C264C

6.1.3 Direct Execution mode
In this mode a control of device is directly executed without need to be previously selected.
Usually concerns ancillary devices managed via I/O boards (SPC, DPC, and Setpoints) or
via IED.
The Direct Execute sequence ends normally after reception of the expected position
information of the device or correct value (if setpoint control). Abnormally if the received
position or value is unexpected, or not received in the predefined delay by configuration.
Note that a cancel request in Direct Execute mode has no guarantee to be performed
before the execution of the request. An unselect request has no meaning in Direct
Execute mode.
C0316ENa
execution already in
progress ?
Direct execution request
Execution OK
yes
no
device direct execute
no
All checks OK
execution in progress
no
yes
End CO in progress End CO in progress
End of
sequence
start of
sequence
send negative
acknowledge
send positive
acknowledge
Perform execution
Perform execution
checks

FIGURE 27: EXECUTION PHASE FOR DIRECT EXECUTE MODE
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 59/132

6.1.4 SBO once mode
6.1.4.1 Selection phase in SBO once mode
During the selection phase initialised by a selection request of the control, the computer
performs selection checks in order to verify if the device is selectable or not.
If no fail occurs during these checks, the device is selected and positive acknowledgement is
sent. Otherwise the selection request is refused and a negative acknowledgement is sent
giving fails cause. If the selection of the device is accepted the computer starts a delay in
which it waits:
An execution request (open/close, low/raise)
A cancel of the selection request
After the end of this delay if the execution or the cancel request is not sent, the device is
automatically unselected and a negative acknowledgement is sent. The selection delay is
defined during the configuration step.
Note that only one selection is allowed at a time for a device. When a device is already
selected any other selection is not taken into account (none acknowledgement is sent)
whichever of the initiator.
The following diagram shows the selection phase of a device configured in SBO once mode.
C264/EN FT/C30 Functional Description

Page 60/132

MiCOM C264/C264C

C0317ENa
Device selectable ?
Selection request
yes
no
All checks OK
Device Already
selected
Selection Time-out
launching
Unselected
device
Perform Selection
checks
send positive
acknowledge
send negative
acknowledge
Time-out
Deselect hardware
selection Device
Cancel request
Execution request
Wait new request
or time-out
Execution
phase
Device selection
Device selection OK
no
no
Set device selected
Set device
unselected

FIGURE 28: SELECTION PHASE IN SBO ONCE MODE
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 61/132

6.1.4.2 Execution phase in SBO once mode
The execution phase can start only after reception of an execution request and if the device
has been selected before.
In this phase, the computer performs the execution checks, and if no fail, it proceeds to the
execution according to the configuration, via the IO boards or IED communication.
If the execution ends normally, a positive acknowledgement is sent, and the control
sequence ends. In case of fail the control sequence is aborted and the computer sends a
negative acknowledgement.
During this phase a cancel request is not guaranteed except for synchronised circuit
breakers devices (refer to specifics treatments for synchronised circuit breakers below).
C0318ENa
EXECUTION PHASE IN SBO ONCE MODE
Execution OK
yes
no
All checks OK
execution in progress
to the device
no
End of
sequence
Execution request SBO
once device selected
send negative
acknowledge
send positive
acknowledge
Perform execution
Perform execution
checks
Reset execution in
progress
deselect the device
Execution in progress
yes
send negative
acknowledge
Operator
Cancel request

FIGURE 29: EXECUTION PHASE ON SBO ONCE MODE
C264/EN FT/C30 Functional Description

Page 62/132

MiCOM C264/C264C

6.1.5 SBO many mode
This mode allows to perform one or more control executions after the selection phase. It is
usually used for the tap positioning process in which many controls are sent before reaching
the desired position.
6.1.5.1 Selection phase in SBO many mode
The selection phase is identical to the SBO once mode selection phase.
6.1.5.2 Execution phase in SBO many mode
The difference with the SBO once mode is that after having performed an execution
request, the computer stays in execution phase waiting a new execution order or an
unselect request. The execution phase ends only after an unselect request or cancel
request by the initiator.
Upon reception of an unselect request the computer ends the execution phase and goes
to the selection phase.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 63/132

C0319ENa
Device selected
Execution Phase SBO many
Execution OK
yes
no
no
All checks OK
execution in progress
to the device
no
End of
sequence
Execution phase- device
SBO many selectd
send negative
acknowledge
send positive
acknowledge
Perform execution
Perform execution
checks
Reset execution in
progress
Execution in progress
yes
send negative
acknowledge
Execution request
Unselect request
Wait request
Deselect the device
Unselection
phase
cancel request

FIGURE 30: EXECUTION PHASE IN SBO MANY MODE
C264/EN FT/C30 Functional Description

Page 64/132

MiCOM C264/C264C

6.1.5.3 Unselection phase in SBO many mode
The computer deselects the device and sends a positive acknowledgement.
C0320ENa
Unselection Phase SBO many
End of sequence
Unselection phase
Deselect the device
Send positive
acknowledge
Send negative
acknowledge
hardware selection
Not configured
Error during
deselection
Set device
deselected

FIGURE 31: UNSELECTION PHASE IN SBO MANY MODE
6.1.6 Generic selection checks
Checks performed during the selection phase are:
Inter-control delay
Computer mode
Substation and bay mode states
Interlock and topological interlocking states
Automation running control
Device selectable
Locked device state
Status of the device
Uniqueness
In case of fail, the initiator of the request may bypass the following checks:
Substation and bay mode states
Interlock and topological interlocking states
Automation running control
Locked device state
Uniqueness
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 65/132

Next diagram schematises controls and bypass according the description of the device.
C0321ENa
Selection checks for SBO device
Current status of the
device OK
Unselected device
no
Uniqueness
OK
Bypass interlock
checks
Interlock checks
OK
Automatism running
no
no
Bypass uniqueness
check
no
yes
Device locked
Bypass locked device
no
Computer faulty or in
maint
Continue
selection
phase
yes
yes
yes
Not configured
Not configured
Not configured
Not configured
Not configured
Inter-control delay
expired
Not configured
Abort
selection
phase
Bypass automatism
Bypass mode checks
no
Not configured
Device selectable
no
yes
no
Substation and bay
mode OK
no
yes
no
no
yes
yes

FIGURE 32: SELECTION CHECKS FOR SBO DEVICE
C264/EN FT/C30 Functional Description

Page 66/132

MiCOM C264/C264C

6.1.6.1 Inter-control delay
A user-selectable delay can be defined in which a new order to the same device is forbidden.
If this delay is configured and not expired since the last order the request is refused with
negative acknowledgement.
6.1.6.2 Computer mode
Control requests are accepted or not depending on the operating mode of the computer.
Maintenance mode: control requests are not accepted if the computer is in
maintenance mode except system controls concerning control mode or database
management.
Faulty mode: no control is accepted when the computer is in this mode.
Changing mode:
From operational mode to test mode: the specific control test mode is
refused if at least one control is in progress.
From test mode to operational mode: the specific control test mode is
refused if at least one control is in progress.
From operational mode to maintenance mode: all device controls in
progress are aborted and no acknowledgement is sent.
6.1.6.3 Substation and bay mode control
A device control may be dependant or not to the substation mode and bay mode. For every
device control the configuration gives the dependency or not to the following modes:
Substation mode dependency (local/remote)
SBMC mode dependency (bay in maintenance or not)
Bay mode dependency (local/remote)
Bay mode is checked by the computer managing the device if the bay mode dependency is
configured for this device.
Substation and SBMC modes are checked by the computer having slave protocols and only
for controls coming from SCADA and if substation mode dependency is configured for this
device.
If the request is refused the selection sequence is aborted with negative acknowledgement.
6.1.6.4 Interlock control
The configuration process allows to assign or not a logical equation to each order (close and
open) of the device. If configured by the user, its state (true/false) may affect the control
sequence. If is false, the selection is refused, excepted if bypass is set.
In case of fail the sequence is aborted with a negative acknowledgement.
6.1.6.5 Automation running control
Each device may be locked by the presence of an input information (digital input, IED input
etc) assigned during configuration. A system input information giving automatism state
(active/inactive) can be used to prevent manually control execution in case an automatism is
active for device monitoring (e.g. ATCC).
In this case the sequence is aborted with a negative acknowledgement, except if the user
asks to bypass this check.
6.1.6.6 Device selectable
A device is selectable if during configuration step its control is described to be managed in
SBO once or SBO many mode and is not already selected. Otherwise the selection
request is refused with negative acknowledgement.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 67/132

6.1.6.7 Locked device control
The user may lock a device in order to avoid any wrong move. If the selection concerns a
locked device the request is refused, except if the user force to bypass this control in the
selection request.
In case the device is locked the sequence is aborted with a negative acknowledgement.
6.1.6.8 Current status of the device
The status check of the device is optional. It is given by a binary input or computed using
more than one binary input (case of circuit breakers). Its behaviour can be chosen ( during
the configuration step) among one of the four following cases:It is given by a binary input or
computed using more than one binary input (case of circuit breakers).
the request is accepted whatever the status of the device ( no check)
the request is accepted only if the device is in the opposite state and valid
the request is accepted only if the device is in the opposite state, jammed or undefined
the request is refused only if the device is in the same state and valid
In any case, if the request is refused, a negative acknowledgement is sent back
6.1.6.9 Uniqueness
It is possible by configuration to prevent to have more than one control at a time.
For the whole substation
Inside a bay
The following figure describes the algorithm used between computers.
C0322ENa
Uniqueness must be checked for this
device and there is no bypass
A
Uniqueness does not be checked for
this device or uniqueness is bypass
B
No control on going inside the
substation ( corresponding DI in OFF
or invalid states)
C
One control on going
inside the
substation
A goose is received from an
other bay which also requires
the uniqueness token
Uniqueness check is NOK
Uniqueness check is OK
Goose is sent to other bays in
order to ask for the token
Time out (defined in
database)
Uniqueness check is OK
Uniqueness check is NOK
D
Goose is sent to other bays

FIGURE 33: CHECK OF UNIQUENESS
C264/EN FT/C30 Functional Description

Page 68/132

MiCOM C264/C264C

If a device is under control and another control is sent on this device, the second one is
ignored.
In case of uniqueness of the command at least to one of these levels the selection is
refused, with negative acknowledgement. The user may bypass this control during selection
request.
6.1.7 Selection behaviour
In SBO once mode and SBO many mode, the configuration process allows to describe
optionally, a device selection to control the device.
The following configurations must be considered:
Configuration 1: device with a control for selection and its associated selection
position information.
Configuration 2: device with a control for selection (without input selection
information).
Whatever the request control (select open/select close, select raise/select low) the selection
of the device is performed as follow:
Configuration 1:
The computer
1. verifies the selection position information, it must be open: if it is close, it is an
abnormal situation, the selection sequence is stopped with a negative
acknowledgement.
2. sends a close order of the selection control (via I/O boards or IED) and waits the
selection position information in a given delay (by configuration).
If the selection control has been normally executed, and the selection position
information of the device become set in the given delay, the selection sequence
ends sending a positive acknowledgement. The computer starts its execution
sequence. In case of fail of the execution of the selection control or if the selection
position information remains open in the given delay the selection sequence ends
abnormally sending a negative acknowledgement.
Configuration 2:
For this configuration, in which only the output control of the selection is configured,
the computer: sends a close order of the selection control (via I/O boards or IED). If
the selection control has been normally executed, the selection sequence ends by
sending a positive acknowledgement and the computer start its execution sequence.
In case of fail of the execution of the selection control, the sequence ends abnormally
by sending a negative acknowledgement.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 69/132

6.1.8 Generic execution checks
During the execution phase, whatever the execution mode (SBO once, SBO many or Direct
Execute) the computer, before proceeding to the execution of the request, performs the
following checks:
Inter-control delay
Computer mode
Substation and bay mode states
Interlock and topological interlocking states
Automation running control
Device selectable (SBO mode only)
Locked device state
Current status of the device
Uniqueness
Execution checks and bypasses are identical to those of the selection phase. Moreover, in
case of SBO once mode or SBO many mode the computer verifies that the device was
previously selected.
The checks of the execution phase in SBO many mode are identical as above but they
are repeated for every execution request (low/raise).
In Direct Execute mode the device selection is not verified because it is not allowed.
6.1.9 Execution behaviour
On this stage the control request is executed via:
I/O boards
IED communication
System supervisor of the computer for system outputs
The execution via I/O boards is performed only if the computer is in operational mode. If
the computer is in test mode, the output relay is not set. In this case the computer
simulates a positive acknowledgement of hardware execution. It allows to perform control
sequence safety in order to test Automatisms configuration, control sequence configuration
etc. Controls to IEDs are sent if the computer is in operational mode or test mode.
6.1.9.1 Execution via I/O boards
According to the devices features the execution of the control via I/O boards may be
performed using:
Single Points Control
Double Control Points
Digital Setpoints
Single Point Control and Double Point Control
However, the execution control sequence depends on the activation mode of the xPC. By
configuration, this activation mode of SPC and DPC may be transient, permanent or
permanent until feedbackuntil feedback.
Transient: the contact is closed and then re-opened automatically after a delay
(defined during the configuration of the xPC). For a DPC, configuration gives two
delays need to be configured, one for open and one for close.
C264/EN FT/C30 Functional Description

Page 70/132

MiCOM C264/C264C

Permanent: For this type of output control, the contact is held in the requested
position state until the a reverse order is received.
Permanent until feedback: The contact is held in the requested position state until
confirmation of the position of the device or after timeout awaiting the new position of
the device. In this case, the input information of the device status must be configured.
Digital Setpoints
A control sequence via Digital Setpoints has particular treatments during the control request
6.1.9.2 Execution via IED communication
When an execution request is performed via IED communication, the requested order is
converted to a message to be sent to the intelligent devices, according the communication
protocol.
6.1.9.3 System controls execution
For systems outputs the computer activate/deactivate the associated function (ATCC,
computer mode, etc) and if a specific system input (SPS or DPS) is configured for this
control, it takes the requested state and it stored in non-volatile memory.
6.1.10 Controls time sequencing
Time sequencing of control is dependent of its configuration:
Control mode: Direct Execute, SBO once, SBO many
Device features: selection control wired/not wired, selection position wired/not wired,
device position wired/not wired etc.
Output control type: permanent , pulse
Destination: I/O board, IED
Time-out delays: selection phase time-out, selection Feedback delays, open/close
Feedback delay etc.
6.1.10.1 Direct execute time sequencing
The following chronogram shows an example of normal termination on Direct Execute
sequence.
C0323ENa
DPC open
(resp. close)
DPS open/ resp close
(close/ resp open)
0-5s
0-60s
CO Pulse Delay
Feedback Delay
1 execution request
3 4 5

FIGURE 34: NORMAL TERMINATION OF DIRECT EXECUTE SEQUENCE
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 71/132

The following chronogram shows an abnormal termination of Direct Execute sequence. The
device hasnt taken the expected position in the given delay.
C0324ENa
DPC open
(resp. close)
SPS close
(resp. open)
SPS open
(resp. close)
0-5s
0-60s
CO Pulse Delay
Feedback Delay
1 execution request
3 4 5

FIGURE 35: ABNORMAL TERMINATION OF DIRECT EXECUTE SEQUENCE
6.1.10.2 SBO Once time sequencing
The configurations below are given as examples
Device Configuration A: the optional selection control and Selection position information
are configured
The following chronogram shows a normal termination of the control sequence.
C0325ENa
Device status
Selection
Feedback
Delay
1-10mn
0-60s
Open/Close
Feedback
Delay
3 4
Execution phase
Selection of the
device
Selection position
input
2
1
0-1 s
5
Selection time-out
Selection
Feedback
Delay
Device output control
0-1 s
Selection phase

FIGURE 36: NORMAL TERMINATION OF THE CONTROL SEQUENCE
Stage 1: device selection (closing the associated output control)
Stage 2: the selection is confirmed by the associated input information in the feedback
delay (0 1-sec user selectable)
Stage 3: close the device before the end of the selection timeout delay (0 10 MN
user selectable)
Stage 4: the device has taken the expected position (close) in the feedback delay (0
60 sec user selectable). The computer deselect the device (open selection output
control)
Stage 5: confirmation of the deselecting of the device in the same given delay than
stage 2.
C264/EN FT/C30 Functional Description

Page 72/132

MiCOM C264/C264C

The following chronogram shows controls sequence which is aborted after time-out of the
selection delay.
Device status
Input information
Selection
Feedback
Delay
1-10mn
1 3
Selection of the
device
Selection position
input
2
0-1 s
Selection time-out
Selection
Feedback Delay
Device output
control
0-1 s
Selection phase
4
C0326ENa

FIGURE 37: ABORTED CONTROL SEQUENCE
Stage 1: device selection (closing the associated output control)
Stage 2: the selection is confirmed by the associated input information in the feedback
delay.
Stage 3: timeout of the delay - the device is deselected
Stage 4: confirmation of the deselecting of the device
Device Configuration B: the optional selection control is configured and Selection position
information is not configured
The following chronogram shows a normal termination of the control sequence.
C0327ENa
Device status
1-10mn
0-60s
Open/Close
Feedback
Delay
2 1 3
Execution phase
Selection of the
device
Selection time-out
Output Control Of
The Device
Selection phase

FIGURE 38: NORMAL TERMINATION OF THE CONTROL SEQUENCE
Stage 1: device selection (closing the associated output control)
Stage 2: close the device before the end of the selection timeout delay (0 10 MN
user selectable)
Stage 3: The device has taken the expected position (close) in the feedback delay (0
1-sec user selectable). The computer deselect the device (open selection output
control)
6.1.10.3 SBO many time sequencing
SBO many mode is exclusively used for control of transformers. Refer to associated section.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 73/132

6.2 Control of non synchronised breakers
6.2.1 Non synchronised circuit breakers features
The following table gives inputs and outputs circuit breakers features controlled by the
computer:
THREE PHASED CIRCUIT BREAKERS ONE PHASED CIRCUIT BREAKERS
OUTPUTS
CB TYPE A
OUTPUTS CB
TYPE B (4)
INPUTS CB
ALL TYPES
OUTPUTS CB
TYPE A
OUTPUTS
TYPE B (4)
INPUTS
ALL TYPES
DEVICE
CONTROL
DPC
control for
open/close
of device

SPC control
for open of
device
SPC control
for close of
device

DPS physical
position of the
device(1 phase)
SPS (optional)
phase not
together
information
system DPS the
feedback of the
control (1)
DPC control
for open/close
of device

DPC control for
open phase A
DPC control for
open phase B
(pulse)
DPC control for
open phase C
DPC control for
close of device

SPS/ DPS
physical position
of phase A
SPS/ DPS
physical position
of phase B
SPS/ DPS
physical position
of phase C
system SPS
phase not
together
information (2)
system DPS:
the feedback of
the control (3)
DEVICE
SELECTION
SPC /DPC
(optional)
control of
device
selection
SPC /DPC
(optional)
control of
device
selection
SPS /DPS
(optional) device
selection
position
information
SPC /DPC
(optional)
control of
device
selection
SPC /DPC
(optional) control
of device
selection
SPS /DPS
(optional) device
selection
position
information
(1) The computed double signal is equal to the physical status if the phase not together
status is equal to false else the computed signal is equal to jammed.
(2) The computed phases not together is equal to false if all phases are in the same
position else it is equal to true.
(3) The computed signal is equal to the phase A status if the phase not together status is
equal to false else the computed signal is equal to jammed.
(4) Only the DPC close is known by the other IEC-61850 equipment:
For open the device they send the DPC close with open request
For close the device they send the DPC close with close request
6.2.2 Control sequence of non-synchronised circuit breakers
Circuit breakers devices are managed in Direct Execute mode and in SBO once mode.
Refer to the generic description above.
C264/EN FT/C30 Functional Description

Page 74/132

MiCOM C264/C264C

6.3 Control of synchronised breakers
Circuit breakers devices are managed in SBO once mode only. The following paragraph
describes the specific features of synchronised circuit breakers whether are synchronised by
an external or internal synchrocheck module.
6.3.1 Circuit breakers features
THREE PHASED CIRCUIT BREAKERS ONE PHASED CB
OUTPUTS
CB TYPE A
OUTPUTS CB
TYPE B (6)
INPUTS CB
ALL TYPES
OUTPUTS
(6) TYPE A
OUTPUTS
TYPE B
INPUTS ALL
TYPES
DEVICE
CONTROL
DPC control
for
open/close
of device
SPC/DPC
control for
close with
synchrocheck
(5)
SPC control
for open of
device
SPC control
for close of
device
SPC/DPC
control for
close with
synchrocheck
(5)
SPS/DPS
physical
position of the
device (1
phase)
SPS (optional)
phase not
together
information
system DPS
optional): the
feedback of
the control (1)
DPC control
for
open/close
of device
SPC/DPC
control for
close with
synchrocheck
(5)
SPC/DPC
control for
open phase
A
SPC/DPC
control for
open phase
B
SPC/DPC
control for
open phase
C
SPC/DPC
control for
close of
device
SPC control
for close with
synchrocheck
SPS/DPS
physical
position of
phase A
SPS/DPS
physical
position of
phase B
SPS/DPS
physical
position of
phase C
system
SPS/DPS
phase not
together
information (2)
system DPS:
the feedback
of the control
(3)
DEVICE
SELECTION
SPC
(optional)
control of
device
selection
SPC (optional)
control of
device
selection
SPS (optional)
device
selection
position
information
SPC
(optional)
control of
device
selection
SPC
(optional)
control of
device
selection
SPS (optional)
device
selection
position
information
SYNCHROCHEC
K SET ON/SET
OFF (4)
SPC/DPC
(optional)
control of
ON/OFF
synchrocheck
SPC/DPC
(optional)
control of
ON/OFF
synchrocheck
SPS/DPS
(optional)
ON/OFF
synchrocheck
information
SPC/DPC
(optional)
control of
ON/OFF
synchrocheck
SPC/DPC
(optional)
control of
ON/OFF
synchrocheck
SPS/DPS
/DPS(optional)
ON/OFF
synchrocheck
information
(1) The computed double signal is equal to the physical status if the phase not together
status is equal to false else the computed signal is equal to jammed.
(2) The computed phases not together is equal to false if all phases are in the same
position else it is equal to true.
(3) The computed signal is equal to the phase A status if the phase not together status is
equal to false else the computed signal is equal to jammed.
(4) Wired SPC and SPS for external synchrocheck and system SPC and SPS for internal
synchrocheck. If is not configured the external synchrocheck module or the
synchrocheck automatism is considered always set on. DPC and DPS are used only
for manual synchrocheck.
(5) For external synchrocheck only.
Open control sequence of synchronised circuit breakers remains identical to the non-
synchronised circuit breakers.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 75/132

Close control sequence is different according to the configuration the synchrocheck type:
External synchrocheck: The closure of the device is assumed by an external
synchrocheck module
Internal synchrocheck: The closure of the device is assumed by an internal
synchrocheck automatism
A Close control sequence can be configured with:
Manual set on of the external synchrocheck module or internal synchrocheck
automatism
Automatic set on of the external synchrocheck module or internal synchrocheck
automatism
Furthermore, waiting closes the CB by the external module the initiator of the request may:
Cancel the request
Close the device by forcing request
6.3.2 Circuit breakers with external synchrocheck
6.3.2.1 Close CB by external synchrocheck with automatic set on
The following scheme shows a close control for a device in which the external
synchrocheck module is set on automatically by the computer.
C0328ENa
OI
or
GATE
WAY
Synchro
Check
Module
CIRCUIT
BREAKER
C26X
SPC close with
synchrocheck
SPC/DPC ON/OFF
synchrocheck
SPC Select device
SPC Close with
synchrocheck
DPC open/Close
device
select close
Execute close
force close
(1)
(2)
(3)
SPC/DPC
MES/MHS
synchrocheck
(x) sequences order

FIGURE 39: CLOSE CB BY EXTERNAL SYNCHROCHECK WITH AUTOMATIC SET ON
The close control sequence performed on the MiCOM C264/C264C is done as follows:
Selection phase:
1. Set on synchrocheck module (if the control is configured)
2. Verify synchrocheck on/off information associated to the output (if is configured)
3. Close device selection output to select the device (if is configured)
4. Verify selection device input information associated to the output (if is configured)
5. Wait the execution request or timeout selection
In case of fail to one of these operations the controls sequence is stopped with a negative
acknowledgement
C264/EN FT/C30 Functional Description

Page 76/132

MiCOM C264/C264C

Execution phase:
1. Close the device using synchrocheck output control
2. Verify the device position become close in the given delay.
3. Set off synchrocheck module if it previously set on
4. Deselect the device if it previously selected
The following chronogram shows a successful control sequence close with synchrocheck.
C0329ENa
DPS open
close
Feedback
Delay
0-10mn
0-60mn
Feedback for DO
sync close
1 selection request
1
3 4
3 execution request
SPC ON/OFFt Sync
SPS ON/OFF Sync
2
0-1 s
SPC select
SPS select
SPC sync close
Feedback
Delay
0-5 s
5
5 End of control
Selection timeOut
DPC open/close
device

FIGURE 40: CHRONOGRAM OF A SUCCESSFUL "CLOSE WITH SYNCHROCHECK"
The following chronogram shows an abnormal termination of control sequence close with
synchrocheck. The device has not taken the expected position close in the given delay.
The control sequence is aborted with negative acknowledgement, deselecting previously
synchrocheck and device.
DPS open
close
Feedback
Delay
0-10mn
0-60mn
Feedback for DO
sync close
1 selection request
1
3 4
3 execution request
SPC ON/OFF Sync
SPS ON/OFF Sync
2
0-1 s
SPC select
SPS select
SPC sync close
Feedback
Delay
0-5 s
5
5 End of control
Selection timeOut
DPC open/close
device
C0330ENa

FIGURE 41: ABNORMAL TERMINATION OF "CLOSE WITH SYNCHROCHECK"
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 77/132

6.3.2.2 Close CB by external synchrocheck with manual set on
By configuration the close control of the device may be done in two or three control
sequences:
Two sequences:
1. a Direct Execute sequence to put in service the external synchrocheck module
2. a SBO once sequence to close the CB by the synchrocheck module and put out of
service the synchrocheck module
Three sequences:
1. a Direct Execute sequence to put in service the external synchrocheck module
2. a SBO once sequence to close the CB by the synchrocheck module
3. a direct execute sequence to put out service the external synchrocheck module
The following scheme shows a close control request in which the external synchrocheck
module is managed manually from the OI or gateway.
C0331ENa
OI
or
GATE
WAY
Synchro
Check
Module
CIRCUIT
BREAKER
C26X
DPC open/close
device
SPC/DPC ON/OFF
synchrocheck
SPC Select device
SPC/DPC Close
with synchrocheck
DPC open/Close
device
select close
Execute close
force close
SPC/DPC SET
ON synchrocheck
Direct execute The external synchrocheck module is set off automatically at the
end of the SBO sequence (if it is configured)
(1)
(2)
(3)
(4)
(x) sequences order
(5)
SPC/DPC SET
OFFsynchrocheck
(optional)

FIGURE 42: CLOSE CONTROL REQUEST
First sequence (DIRECT EXECUTE): Set on the external synchrocheck module:
1. close set on/setoff output control of the synchrocheck module
2. verify that the synchrocheck module is set (if on/off synchrocheck input information is
configured)
In case of fail to one of these operation the sequence ends with a negative
acknowledgement
Second sequence (SBO ONCE): close the device with synchrocheck
Selection phase:
1. Close device selection output to select the device (if is configured)
2. Verify selection device input information associated to the output (if is
configured)
3. Wait the execution request or timeout selection
4. In case of fail to one of these operations the controls sequence is stopped with
a negative acknowledgement
C264/EN FT/C30 Functional Description

Page 78/132

MiCOM C264/C264C

Execution phase:
5. Close the device via the close with synchrocheck control
6. Verify the device position become close in the given delay
7. Set off the synchrocheck module if is configured to be set off automatically
8. Deselect the device if it previously selected
Third sequence (DIRECT EXECUTE): set off the external synchrocheck module
This sequence takes place only if the setting off of the synchrocheck module is
configured manual
1. open set on/setoff output control of the synchrocheck module
2. verify that the synchrocheck module is set on (if on/off synchrocheck input
information is configured)
The following chronogram shows a successful control sequence close with synchrocheck
performed in three sequences. In case of automatic setting off of the synchrocheck module
the chronogram remain identical. It is performed at the end of the SBO sequence.
DPS open
close
Feedback
Delay
0-10mn
0-60mn
Feedback for DO
sync close
3 selection request :
close the device
1
4 5
4 execution request
SPC ON/OFF Sync
SPS ON/OFF Sync
2
0-1 s
SPC select
device
SPS select device
SPC sync close
Feedback
Delay
0-5 s
6
6 End of control
Selection timeOut
DPC open/close
device
3
1 DE request set on
synchrocheck
5 DE request set
off synchrocheck
C0332ENa

FIGURE 43: SUCCESSFUL CLOSE WITH SYNCHROCHECK
NOTE: During SBO sequence after step 5 the initiator of the request may
force the closing of the device.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 79/132

6.3.2.3 Close synchronised circuit breakers with forcing
The following chronogram shows controls sequence close with synchrocheck with forcing
close request. The SBO sequence is performed in the same way whether the synchrocheck
module is set on manually or automatically.
Awaiting the device be closed by the external synchrocheck module, the initiator of the
request force to close without synchrocheck
SPS open
close
Feedback Delay
0-10mn 0-20s
1 selection request
1
3 4
SPC select Sync
(optional)
SPS select Sync
(optional)
2
0-1 s
SPC select
(optional)
SPS select
(optional)
SPC sync close
Feedback
Delay
0-5 s
Forcing on DPC
close : DPC close
is set
0-60mn
Feedback for DO sync close
4 synchrocheck bypass
Selection Timeout Feedback
Delay
5
5 End of control 3 execution request
6
C0333ENa

FIGURE 44: CLOSE WITH SYNCHROCHECK WITH FORCING CLOSE REQUEST
6.3.2.4 Cancel Close CB with external synchrocheck
Awaiting close the device (0 to 60 a MN) by the external synchrocheck module, the initiator
of the close request may cancel this one by a cancel request.
The following chronogram shows a cancel close request awaiting close the device by the
external synchrocheck module.
DPS open
close
Feedback
Delay
0-10mn
0-60mn
FeedBack Delay
1 selection request
1
3 4
3 execution request
SPC select Sync
SPS select Sync
2
0-1 s
SPC select
SPS select
SPC sync close
Feedback
Delay
0-5 s
5
5 End of control
Selection timeOut
6
4 Operator CANCEL
C0334ENa

FIGURE 45: CANCEL CLOSE REQUEST
C264/EN FT/C30 Functional Description

Page 80/132

MiCOM C264/C264C

6.3.3 Circuit breakers with internal synchrocheck
On this configuration synchrocheck is assumed by an internal computer automatism, which
proceeds to the synchrocheck voltage calculations and gives or not the authorisation to close
the device.
The controls sequence remains similar with the external synchrocheck instead of the setting
on/off of the synchrocheck and close with synchrocheck output control which are not exist on
this configuration
6.3.3.1 Close CB with internal synchrocheck with automatic set on
The following sequence describes a close request of circuit breaker with internal
synchrocheck in SBO once mode. Synchrocheck automatism is set on automatically.
In Direct Execute mode the processing remain similar without selection of the device.
C0335ENa
OI
or
GATE
WAY
CIRCUIT
BREAKER
C26X
SPC/DPC close
with synchrocheck
SPC/DPC system
ON/OFF fonction
synchorcheck
SPC Select device
SPC/ DPC system
Close with
synchorcheck
DPC open/Close
device
select close
Execute close
force close
Fonction
Synchro
Check
(1)
(2)
(3)
(x) sequences order

Selection phase:
1. Close device selection output to select the device (if is configured)
2. Verify selection device input information associated to the output (if is configured)
3. Wait the execution close request or timeout selection
In case of fail to one of these operations, the device is deselected and the controls
sequence is aborted with a negative acknowledgement.
Execution phase:
1. Active the associated internal synchrocheck automatism for authorisation to close the
device
2. Wait authorisation to close
Case 1: Synchrocheck automatism respond OK before the time-out of the given delay
Close the device
Deselect the device (if it was previously selected)
Send a positive acknowledgement
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 81/132

Case 2: Synchrocheck automatism responds NO before the time-out of the given
delay
Deselect the device (if it was previously selected)
Send a negative acknowledgement
Case 3: time-out of the given delay without synchrocheck response
stop the synchrocheck automatism
Deselect the device (if it was previously selected)
Send a negative acknowledgement
Case 4: reception of cancel request awaiting synchrocheck response
stop the synchrocheck automatism
Deselect the device (if it was previously selected)
Send a negative acknowledgement
The following chronogram shows a successful control sequence close with internal
synchrocheck.
DPS open
Feedback
Delay
0-10mn
0-60mn
feedback Delay
1 selection close request
1
3 4
3 execution request
2
0-1 s
SPC select
SPS select
Close/open
Device control
Feedback
Delay
0-5 s
5
5 End of control
Selection time-out
close
C0336ENa

C264/EN FT/C30 Functional Description

Page 82/132

MiCOM C264/C264C

The following chronogram shows an abnormal termination of control sequence close with
internal synchrocheck.
DPS open
close
Feedback
Delay
0-10mn
0-60mn
FeedBack Delay
1 selection close request
1
3 4
3 execution request
2
0-1 s
SPC select
SPS select
Close/open
Device contro
Feedback
Delay
0-5 s
5
5 End of control
Selection timeOut
C0337ENa

6.3.3.2 Close CB with internal synchrocheck with manual set on
The following sequence describes a close request of circuit breaker with internal
synchrocheck in SBO once mode. Synchrocheck automatism is set on by a separate
direct execute control.
C0338ENa
OI
or
GATE
WAY
CIRCUIT
BREAKER
C26X
SPC open/close
device
SPC Select device
SPC/ DPC Close
with synchrocheck
DPC open/Close
device
select close
Execute close
force close
SPC/ DPC set on
synchrocheck
Direct execute
The external synchrocheck module is set off automatically at the
end of the SBO sequence (if it is configured)
Synchro
Check
Module
(2)
(3)
(4)
(1)
(5)
SPC/DPC set off
synchrocheck
(x) sequences order


Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 83/132

First sequence (DIRECT EXECUTE): Set on the internal synchrocheck automatism:
1. set on synchrocheck automatism for the device
2. set system input on/off synchrocheck (if its is configured)
Second sequence (SBO ONCE): close the device with synchrocheck
Selection phase:
1. Close device selection output to select the device (if is configured)
2. Verify selection device input information associated to the output (if is
configured)
3. Wait the execution request or timeout selection
4. In case of fail to one of these operations the controls sequence is stopped with
a negative acknowledgement
Execution phase:
5. Ask to the internal automatism to close the device
6. Verify the device position become close in the given delay
7. Set off the synchrocheck automatism if is configured to be set off automatically
8. Deselect the device if it previously selected
Third sequence (DIRECT EXECUTE): set off the internal synchrocheck automatism
This sequence takes place only if the setting off of the synchrocheck automatism is
configured manual
1. set off synchrocheck automatism
2. reset system input on/off synchrocheck (if its is configured)
NOTE: During SBO sequence after step 5 the initiator of the request may
force the closing of the device.
6.3.3.3 Close CB with internal synchrocheck with forcing
Awaiting authorization from the internal synchrocheck for closing the device, the initiator of
the request may force the closing.
After time-out of the given delay without synchrocheck response
stop the synchrocheck automatism
close the device
Deselect the device (if it was previously selected)
Send a positive acknowledgement
C264/EN FT/C30 Functional Description

Page 84/132

MiCOM C264/C264C

DPS open
close
Feedback
Delay
0-10mn
0-60mn
FeedBack Delay
1 selection request
1
3 4
3 execution request
2
0-1 s
SPC select
SPS select
Close via output
control
Feedback
Delay
0-5 s
5
6 End of control
Selection timeOut
6
C0339ENa

6.4 Control of disconnectors
6.4.1 Disconnectors features
MiCOM C264/C264C computers manage all types of disconnecting switches such as:
disconnectors
earthing switch
quick break switch
DISCONNECTORS SWITHES
OUTPUTS TYPE A INPUTS ALL TYPES
DEVICE
CONTROL
DPC control for open/close of device DPS physical position of the device
DEVICE
SELECTION
SPC (optional) control of device
selection
SPS (optional) device selection
position information
6.4.2 Control sequence of disconnectors
The control sequence of disconnectors is identical to control sequence of the non-
synchronised circuit breakers.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 85/132

6.5 Control of transformers
6.5.1 Transformers features
OUTPUTS INPUTS
TRANFORMER
CONTROL
DPC: raise/lower TPI value
SPS (optional) tap change in progress
(TCIP)
TRANSFORMER
SELECTION
SPC (optional) transformer
selection
SPS (optional) selection position
information
TRANFORMER
TYPE (1)
Double wound or Auto-wound
(1) Transformer type (auto-wound or double-wound) is user selectable.
Double wound (or two winding transformer) is a transformer with galvanic isolation between
primary and secondary coil. Tap Changer (with additional winding) is usually located at HV-
neutral side for economic reasons. Tapping-up (raise order) reduces primary winding and
increase LV tension.
Auto-wound (or auto-transformer or single wound) is a transformer without galvanic
isolation between primary and secondary. Secondary coil follows primary coil, (winding are
serial). Tap Changer (with tap of additional winding) is serial. Increasing tap position (raise
order) acts simultaneously on primary and secondary, it reduces transformer ratio then
voltage at LV side.
6.5.2 Control sequence of transformers
The control of transformer can be performed in the three modes Direct Execute, SBO
once and SBO many.
Additionally of the selection and execution checks described in the previous paragraphs the
following checks are performed:
A raise control is refused if the current tap position value corresponds to the
maximum position of the tap.
A lower control is refused if the current tap position value corresponds to the
minimum position of the tap.
In case of go to min, go to max or go to position x request, an internal
automatism ( via ISAGRAF) has to be added. This automatism generates the desired
controls sequences in order to reach automatically the expected position. It may
generate Direct execute, SBO once or SBO many sequences according the
configuration of the device
NOTE: If the command of a transformer is configured in SBO many mode, it is
impossible to configure the requests go to min, go to max
TCIP feature: The TCIP input information (tap change in progress), is used to confirm the
right execution of the low/raise execution. Two delays are given by the configuration for the
TCIP management:
TCIP apparition delay: The TCIP information must appear before the time-out of this
delay.
TCIP disappearance delay: The TCIP information must disappear before the time-out
of this delay.
TPI feature: Because the TCIP input information is not always configured, the tap control is
performed using only the Tap Position Indication (TPI) value to verify the right execution of
the request. The TPI value must change in the given delay.
The following examples are given in SBO many mode which is the more complex. The
main difference with the SBO once mode remains to the possibility to execute many
raise or low controls before ending the sequence. Moreover, the device is not deselected
automatically but only after an unselect order sent by the initiator of the control request.
C264/EN FT/C30 Functional Description

Page 86/132

MiCOM C264/C264C

6.5.2.1 Control of transformer with TCIP
In this mode, when the TCIP input information is configured, the selection and execution
phase are performed as follows: It is possible by configuration to prevent to have more than
one control at a time.
Selection phase:
1. Close device selection output to select the device (if configured)
2. Verify selection device input information associated to the output (if is
configured)
3. Wait the execution request (low/raise) or timeout selection
In case of fail to one of these operations, the device is deselected, the controls
sequence is aborted with a negative acknowledgement.
Execution phase:
4. According the request raise or lower and the type of device, execute the
associate control
5. Wait the TCIP information and TIP value to confirm execution. Two cases:
Case 1: The TCIP information appears and is disappears in the given
delays, the TPI takes the expected value: The computer sends a positive
acknowledgement and waits a new request (execution or unselection).
Case 2: Timeout awaiting the TCIP appearance or disappearance, or the
TPI value is wrong: The device is deselected (if it was previously
selected), and the sequence is aborted with a negative
acknowledgement.
6. Wait new execution request or unselection request to deselect the device
In case of new request the computer repeat the steps 4 and 5.
In case of unselection request the computer deselects the device (if it
was previously selected), and ends the sequence with a positive
acknowledgement
The following chronogram shows a successful sequence with device selection, two raise
controls and device unselection
raise/lower
CLOSE
Feedback
Delay
0-10mn
0-1 s
1 selection raise request
1 3
4
3 first execution
request
SPC select
(optional)
SPS select
(optional)
2
0-1 s
DPC raise/lower
OPEN
SPS TCIP
TCIP apparition
time Delay
0-5 s
6
11 End of control
Selection
timeOut
TCIP
disappearance
time Delay
0-1 s
7 5
Pulse
Delay
0-5 s
4
8 9 10
11
6 second execution
request
10 unselect request
TPI Value
(1)
FeedBack
Delay
C0340ENa

(1) the TPI value must take the expected value at least at the end of TCIP disappearance
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 87/132

The following chronogram shows an abnormal termination of tap changer control sequence
due to absence TCIP confirmation. In this case the device is automatically deselected and
the sequence ends with a negative acknowledgement
raise/lower
CLOSE
Feedback
Delay
0-10mn
0-1 s
FeedBack
Delay
1 selection request raise
1
3
4
3 execution request
SPC select
(optional)
SPS select
(optional)
2
0-1 s
OPEN
SPS TCIP
TCIP apparition time
Delay
0-5 s
5
6 End of control
Selection
timeOut
6
Pulse
Delay
0-5 s
TIP value
C0340ENa

6.5.2.2 Control of transformer without TCIP
In case the TCIP input information is not configured the selection and execution phase are
performed as follows:
Selection phase:
1. Close device selection output to select the device (if configured)
2. Verify selection device input information associated to the output (if configured)
3. Wait the execution close request or timeout selection
In case of fail to one of these operations, the device is deselected, the controls
sequence is aborted with a negative acknowledgement.
Execution phase:
4. According the request raise or lower and the type of device, execute the
associate control
5. Wait the TPI information and compare with the previous value. The difference
must confirm the low or raise execution. Two cases:
Case 1: The TPI value confirms in the given delay the execution request:
The computer sends a positive acknowledgement and waits a new
request (execution or unselection) from the initiator.
Case 2: Timeout awaiting the TPI value or unexpected TPI value: The
device is deselected (if it was previously selected), and the sequence is
aborted with a negative acknowledgement.
6. Wait new execution request or unselection request to deselect the device
In case of new request the computer repeat the steps 4 and 5.
In case of unselection request the computer deselects the device (if it
was previously selected), and ends the sequence with a positive
acknowledgement.
C264/EN FT/C30 Functional Description

Page 88/132

MiCOM C264/C264C

The following chronogram shows a successful sequence with device selection, a raise
control and device unselection
raise/lower
CLOSE
Feedback
Delay
0-10mn 0-1 s
feedback
Delay
1 selection raise request
1
3
4
3 execution request
SPC select
(optional)
SPS select
(optional)
2
0-1 s
DPC raise/lower
OPEN
TPI
new TPI value
Delay
0-5 s
7 End of control
Selection
time-out
6
5
Pulse
Delay
0-5 s
6 Unselect request
C0342ENa

The following chronogram shows an abnormal termination due to the absence of change of
the TPI value in the given delay. The device is automatically deselected, and the sequence
is aborted with negative acknowledgement.
raise/lower
CLOSE
Feedback
Delay
0-10mn 0-1 s
FeedBack
Delay
1 selection request raise
1
3
4
3 execution request
SPC select
(optional)
SPS select
(optional)
2
0-1 s
DPC raise/lower
OPEN
TPI
new SPI value
Delay
0-5 s
6 End of control
Selection
timeOut
6
5
Pulse
Delay
0-5 s
C0343ENa

6.5.2.3 Suppression, Forcing or Substitution of the TPI
In case of suppress or substitution of TPI value the control sequence is aborted with
negative Acknowledgement. In case of Forcing the sequence is not aborted but the value of
TPI taken in account during the control sequence is the forced value.
6.6 Control of ancillary devices
Ancillary devices are managed in Direct Execute or in SBO once mode. Refer to
generic explanations above.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 89/132

6.7 Control of Intelligent Electrical Devices (IED)
6.7.1 Control to IEDs
Control requests to manage device via IEDs may be performed in the three modes (DE,
SBO once, SBO many).
6.7.1.1 Direct Execute mode
If execution checks are successful
1. The computer sends the control (open/close, low/raise, setpoint) via the
communication protocol to IED.
2. Expects IEDs control acknowledgement in the given delay (If is supported by the
protocol).
3. Expects the reception of the feedback of the request (device position SPS, DPS, TPI)
in the given delay (if is configured).
In case of fail in step 2 or 3 the sequence ends with a negative acknowledgement otherwise
the sequence ends with a positive acknowledgement.
6.7.1.2 SBO once mode
This mode can be configured only if is supported by the protocol.
6.7.1.2.1 Selection phase
After having performed the selection checks
1. The computer sends a selection request to the IED,
2. Expects selection acknowledgement from IED in the given delay,
3. Generates a positive or negative selection acknowledgement according to the result of
the selection phase,
4. If positive acknowledgement, the computer starts selection time-out and waits
execution request, otherwise ends the controls sequence.
6.7.1.2.2 Execution phase
Ditto execution phase of Direct Execute mode.
6.7.1.3 SBO many mode
In comparison with the SBO once mode, in this mode execution phase is repeated until an
unselection request. Unselection request allows to end the sequence within the computer, is
not sent to IED.
6.7.2 IED controls
6.7.3 Digital setting point (SP)
6.8 System controls
System control is used to activate or deactivate automatic functions, change computers
mode, bay mode, database management, etc.
A system output control remains internal on the computer (has no digital or IED output) and
may generate a system input information. They are managed in Direct Execute mode
only. A hardware selection has no meaning.
For some uses, such as automatisms activation/deactivation, it is necessary to generate a
system input, which gives the state of the controlled function (e.g. ATCC ON/OFF). This
system input may be able to be used by the control sequence or enter to an interlocking
equation etc. The configuration process allows the user to assign or not a system input,
which may a SPS or DPS. System inputs generated by system outputs are stored in non-
volatile memory. In case of computers initialisation they are restored.
C264/EN FT/C30 Functional Description

Page 90/132

MiCOM C264/C264C

6.9 Kind of control sequence
The control sequences automation receives three kinds of input triggers (as order from
higher level) with selection, execution and unselection. Control order may have a normal or
abnormal termination with positive or negative acknowledgement to operator and to
communication.
By configuration, each DPC order (close order or open order) and each SPC can activate
simultaneously two DO contacts.
6.10 Control sequences checks
Receiving control, the control sequence executes configured checks:
Operational conditions
MiCOM C264/C264C mode management (Operational, Test, Maintenance..),
IED connected,
Substation control mode (Remote/Local),
Bay control mode,
SBMC mode,
Uniqueness of control inside the substation.
Module conditions
Inter-control delay,
Status of the device,
Lock condition,
Automation already running (AR, AVR, ),
Interlock equations (substation, bay, local of the module).
Execution conditions
Delays upon selection feed back, start moving, final position reached.
6.10.1 Mode Management
Control sequences are only performed if the computer mode is in operational mode. In test
mode, control sequences are allowed but digital outputs are not set.
6.10.2 IED connected
If a control has to be sent to an IED, it is only accepted if this IED is connected to the
computer.
6.10.3 Control mode
This control sequence receives requests from the various control points:
Automation (Auto Recloser, voltage regulation, PLC),
MiCOM C264/C264C Local Control Display,
MiCOM C264/C264C TBUS communication from SCADA,
Station BUS (other computer in distributed automation, PACiS Operator Interface,
PACIS Gateway),
Legacy BUS (from One Box Solution IED).
To avoid conflict between the control points, substation and bay modes are checked. Each
control sequence can be subject or not to these checks. The switches Remote/Local can be
hardware or software (saved in non-volatile memory).
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 91/132

The SBMC Site Based Maintenance Control allows controlling one specific bay from Local
Display or Operator interface even if substation is in remote. This feature is dedicated to
commissioning or maintenance and has also the possibility to filter data transmitted from the
bay to SCADA.
6.10.4 Uniqueness of control
It is possible by configuration to prevent having more than one control at a time.
6.10.5 Inter-control delay
It is possible by configuration to define an inter-control delay that is a minimum delay
between two consecutive controls on the same device.
6.10.6 Status of the device
It is possible by configuration to prevent control if the status of the device is not valid.
6.10.7 Lock device
Controls are not allowed on a lock device.
6.10.8 Running Automation
Controls are not allowed on a device if there is an associated automation in running.
For example controls issued from PACiS OI or gateway are not allowed on a transformer
controlled by voltage regulation.
6.10.9 Interlocking
The operating of a switching device (Circuit breakers, Traditional disconnecting switches,
Disconnecting switches with abrupt rupture, Ground disconnecting switches) is directly
related on its nature and its environment.
To operate these devices some conditions have to be respected. These conditions, called
interlocking, are managed by logical equations within the MiCOM C264/C264C.
The goal of the function of interlocking is to prohibit control sequence that may violate device
operating condition (e.g. break capability, isolation) or plant operating condition.
6.11 HV Control Sequences
6.11.1 Circuit breaker
Several kind of circuit breaker can be managed:
Three phases or single phase circuit breaker,
Synchronised or non-synchronised, with internal or external synchrocheck,
With and without Auto Recloser.
For three phase breaker each phase DPS is provided separately and it is managed globally
by single (grouped) control and global DPS position. Pole Discrepancy management is
available.
6.11.2 Disconnector
The control sequence of disconnectors is identical to single non-synchronised circuit
breakers.
6.11.3 Transformer
Transformer position is determined using TPI (Tap Position Indication). TPI can be a Digital
Measurement or Analogue Measurement (from DC Analogue Input).
Transformer is the only device supporting the SBO Many control sequences. It is linked to
voltage regulation, also its Raise and Lower controls are defined for secondary voltage (and
not tap position). Except for auto wounded transformer, raise/lower voltage is also a
raise/lower tap.
C264/EN FT/C30 Functional Description

Page 92/132

MiCOM C264/C264C

7. AUTOMATIONS
MiCOM C264/C264C provides three different ways to perform automation functions:
Built-in applications
Programmable Scheme Logic
Programmable Logic Controller
The choice between these three solutions is time and complexity dependent.
7.1 Built-in Automation functions
Within the MiCOM C264/C264C some built-in automation functions are available and can be
set directly by the user:
Synchrocheck
Auto-Recloser
Trip Circuit Supervision
Automatic Voltage regulation
7.1.1 Synchrocheck
MiCOM C264/C264C synchrocheck functionality is designed to measure two voltages with
respect to phase angle, frequency and magnitude to safeguard against the interconnection
of two unsynchronised systems.
The voltage measurements come from the CT/VTs board (TMU200).
The synchrocheck functionality can work in the following schemes:
Automatic and manual network locking on live line / live bar in locking or coupling
mode
Automatic and manual network connection on live line / dead bar
Automatic and manual network connection on dead line / live bar
Automatic and manual network connection on dead line / dead bar
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 93/132

Check
synchroniser
Check
synchroniser
Close
Generator
Network
#
Network
# 1
Network
Close
Line A CB 1
Busbar
(a) Application to generator
(b) Application to two networks
Busbar B
CB
close
controls
CB
close
controls
C0006ENa

FIGURE 46: CHECK SYNCHRONISER APPLICATIONS ~
The absolute values of the two voltages (V
line
and V
busbar
) must be above or below settable
thresholds, to allow the circuit breaker closing.
The following voltage controls are available:
V
line
and V
busbar
for network coupling
V
line
and V
busbar
for network locking
V
line
and not(V
busbar
)
not(V
line
) and V
busbar

not(V
line
) and not(V
busbar
)
With V
line
and V
busbar
TRUE if the measured voltage is above the threshold V>, and not(V
line
)
and not(V
busbar
) TRUE if the measured voltage is below the threshold V<.
The selection of the voltage control is made during the configuration phase.
By configuration, a single synchrocheck can manage two circuit breakers. Be careful, in this
case the voltage switching is not managed by the computer.
C264/EN FT/C30 Functional Description

Page 94/132

MiCOM C264/C264C

7.1.2 Auto-Recloser (AR)
7.1.2.1 Introduction
80-90% of faults on the electrical network are transient, such as lightning or insulator
flashover. When a fault occurs, the Circuit Breaker is tripped in order to protect the system.
The Auto-Recloser function is then used to close the circuit breaker after a set time, a time
that is long enough to allow the fault to clear. This duration is called cycle temporisation and
is defined in the database during the configuration phase.
But, as permanent fault can occur, an auto-recloser scheme has to be provided in order to
allow the elimination of a transient fault by an open/close sequence (auto-reclosing cycle)
and the elimination of permanent fault by, after a defined number of auto-reclosing cycle (4
cycles maximum), leaving the circuit breaker in the open state by closing the trip relay.
A transient fault, such as a lightning strike, is one that is cleared by immediate tripping of one
or more CBs to isolate the fault, and does not recur when the line is re-energised.
This means that in the majority of fault incidents, if the faulty line is immediately tripped out,
and if time is allowed for the arc to de-ionise, reclosure of the CB will result in the line being
successfully re-energised. (A Closed/Open/Closed cycle)
However, some faults will be permanent (such as a line fallen to earth). In this case the auto-
recloser must be able to react to the permanent fault, and on the first reclose and detection
of the permanent fault open the CBs (and, if required lock out the auto-reclose functionality).
(This is a Closed/Open/Closed/Open, 4 cycle system).
Auto-recloser (AR) schemes are implemented to carry out this duty automatically.
7.1.2.2 Behaviour
The general diagram of the auto-recloser function is:

Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 95/132

C0137ENa
Auto-recloser out
of service
In Service request
Auto-recloser in
service
TRIP /TRIP_1P_X
Analysis of the
received trip
1 phase
3 phases
AR locked
CB open
Launch cycle timer
(for first single-
phase cycle)
TRIP_1P_X
always set
TRIP End of
timer
Closing the CB
End of 150 ms timer
AR locked
TRIP CB closed
Launch
recovering timer
End of
timer
TRIP
Last cycle?
AR locked
yes
no
Waiting CB
opening
AR locked
CB open
Launch cycle timer
(for 3-phases cycle)
Cycle n=1
Cycle n=2
TRIP
always set
End of
timer
AR locked
Closing the CB
CB
closed
Cycle = cycle +1
Launch
recovering timer
New
TRIP
End of
timer
TRIP
End of 150 ms
timer
Waiting CB
opening
AR_BLOCKING
= RESET ?
yes
no
yes
no
CB_HEALTHY
= SET ?
no
yes
AR_BLOCKING
= RESET ?
no
yes
CB_HEALTHY
= SET ?

FIGURE 47: AUTO-RECLOSER SCHEME LOGIC
7.1.2.2.1 In Service / Out of service
The auto-recloser function can be in or out of service due to an operator control (through the
station bus, the computer local HMI or a BI).
If the auto-recloser is out of service, no cycle is authorised.
If an out of service request is received during an auto-reclosing cycle, the cycle is
immediately stopped.
C264/EN FT/C30 Functional Description

Page 96/132

MiCOM C264/C264C

7.1.2.2.2 Analysis of the receiving trip
This analyse allows to detect the type of auto-recloser cycle, which can be:
the first single-phase cycle
the first 3-phases fast cycle
the second 3-phases slow cycle
the third 3-phases slow cycle
the fourth 3-phases slow cycle
This detection is done by using:
the current cycle number
the TRIP_1P_X or TRIP signal sent by the protection relay (single-phase trip / 3-
phases trip)
the configured auto-recloser cycles
During this phase, if the CB_HEALTHY signal is not in the SET state, the cycle will be not
authorised and the automation will be re-initialised to wait the first cycle. The CB_HEALTHY
BI is optional: if it doesnt exist, no check is done.
7.1.2.2.3 Waiting CB opening
As soon as the trip has been detected, a 150 ms timer is launched to wait the circuit breaker
opening.
For a 3 single poles CB:
If the CB position is on a per pole basis:
In a single phase cycle, only one phase position is awaited in the OPEN state
(CB_STATE_1P_X)
In a 3-phases cycle, each one phase positions is awaited in the OPEN state
If the CB position is given globally:
In a single phase cycle, the position (CB_STATE) is awaited in the MOTION00
state
In a 3-phases cycle, the position (CB_STATE) is awaited in the OPEN state
For a triple poles CB:
Whatever was the cycle, the 3 phase position is awaited in the OPEN state
(CB_STATE)
For a 3-phases cycle, the DO AR_TRIP_3P is closed (if configured) as soon as the CB is
detected as open.
The auto-recloser function is locked if the CB is not opened at the end of the timer.
7.1.2.2.4 Launch cycle timer
As soon as the CB is detected as open, the timer associated to the current auto-recloser
phase is launched.
During the single-phase cycle, the trip signal must disappear: if not, the auto-recloser
function will be locked. Furthermore, a 3-phases trip could appear. In this case, the current
cycle is stopped and the second 3-phases slow cycle is launched.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 97/132

7.1.2.2.5 Closing the CB
At the end of the cycle timer, the AR_BLOCKING BI is tested: if it is in RESET state, a close
order is sent to the Circuit Breaker. Note that, if present, the synchrocheck function is used
to control the breaker during the second, third and fourth 3-phases slow cycles. The use of
the synchrocheck function during the first 3-phases fast cycle is configurable.
If the AR_BLOCKING BI is in another state, the automation is re-initialised to wait the first
cycle.
7.1.2.2.6 Launch recovering time
As soon as all concerned CB phases are closed, the Reclaimc recovering timer is launched.
If the CB remains closed during the timer, the reclosing is considered to be successful and
the cycle number is set to 0. The AR_STATE signal is set at AR_RECLAIMC state during
this timer.
If a new trip occurs during the timer, the next configured cycle is launched. If the trip occurs
during the last cycle, the auto-recloser is locked.
7.1.2.2.7 Particular treatments
Reclaim time on manual close
If the CB becomes closed (through an external manoeuvre) during an auto-recloser cycle,
the Reclaimmc timer is launched during which the auto-recloser function is inhibited and the
AR_STATE signal is set at the AR_RECLAIMMC state.
CB closing failure
If the CB closing order fails, due to DO hardware failure, interlocking scheme, or
synchrocheck inhibition, the AR_FAIL signal is set.
This SI is reset as soon as the CB is closed.
Lock of the auto-recloser
The conditions which lead to an auto-recloser locking are:
A trip during the last auto-recloser cycle (in this case, the AR_STATE signal is set at
the AR_BAR_SHOTS state)
A lock signal through the AR_LOCK Binary Input at the SET state
Trip BI state is Invalid (this BI cannot be suppressed, forced or substitued)
CB position BI(s) state is (are) Invalid
The Trip BI is always set at the end of the cycle timer
There is no pole discordance at the end of the single-phase cycle (i.e. the three
phases are opened)
2 phases are in an opened state at the end of the single-phase cycle without 3-phases
trip signal
the CB is not opened at the end of the 150 ms timer
The AR_STATE signal is set at the AR_BAR_LOCK state if the auto-recloser function is
locked, and the cycle counter is set to 0.
There are two configurable methods to unlock the function. These methods are selected
during the configuration phase and can be used separately or together:
1. a manual closing of a circuit breaker: in this case, the Reclaimmc timer is launched.
2. an AR_LOCK signal at the RESET, received either through a BI or an operator order.
If none of these methods are selected, the auto-recloser is automatically unlocked if no lock
condition is set and circuit breaker is closed. In this case, the Reclaimml timer is launched. If
the CB is not closed at the end of this timer, the auto-recloser is locked again.
C264/EN FT/C30 Functional Description

Page 98/132

MiCOM C264/C264C

7.1.2.3 Informations and parameters
Information Description Type
CB_STATE_1P_x CB status, on a per pole basis BI (DP)
CB_STATE CB status (global) BI (DP)
TRIP_1P_x Trip status, on a per pole basis BI (SP)
TRIP 3-phases Trip status BI (SP)
AR_IS/OS Request to put in / out of service the auto-recloser BI (DP) or operator control
AR_LOCK Signal to lock / unlock the auto-recloser BI (SP, Group) or output of a
configurable automation or
operator control
CB_HEALTHY Availability of the breaker to be closed BI (SP)
AR_BLOCKING Signal to block the closure of the circuit breaker BI (SP, Group) or output of a
configurable automation
CB_ORDER_1P_x CB order, on a per pole basis DO
CB_ORDER CB order (global) DO
AR_TRIP_3P 3 phases trip forcing order This information can be wired
to a DO or can be used as an
internal signal.
AR_IS/OS Auto-recloser status: In / Out Of Service SI (DP)
AR_STATE Auto-recloser current state SI (MP)
AR_READY Indicate the auto-recloser is in service, unlocked
and no cycle is in progress
State1
AR_WAIT_FOR_OPEN_CB Indicate the auto-recloser is waiting CB opening State2
AR_FIRST_CYCLE_1P Indicate the first single-phase cycle is in progress State3
AR_FIRST_CYCLE_3P Indicate the first 3-phases cycle is in progress State4
AR_SECOND_CYCLE_3P Indicate the second 3-phases cycle is in progress State5
AR_THIRD_CYCLE_3P Indicate the third 3-phases cycle is in progress State6
AR_FOURTH_CYCLE_3P Indicate the fourth 3-phases cycle is in progress State7
AR_WAIT_FOR_CLOSE_CB Indicate the auto-recloser is waiting CB closing State8
AR_RECLAIMC Indicate the Reclaimc timer is launched State9
AR_BAR_SHOTS Indicate an auto-recloser locking due to a max
number of reclosing cycles
State10
AR_BAR_LOCK Indicate an auto-recloser locking State11
AR_RECLAIMML Indicate the reclaimml timer is launched State12
AR_RECLAIMMC Indicate the reclaimmc timer is launched State13
AR_FAIL Failure of the close order SI (MP)
AR_SYNC_NOK Due to the synchrocheck State0
AR_HARD_ERROR Due to hardware failure, lock of device or another
running automation linked to the device
State1
AR_ILOCK_NOK Due to interlocking function State2
AR_NO_FAULT No failure State3

Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 99/132

Parameter Description Value
AR_TYPE Auto-recloser type o cycle configuration Mono / Tri
AR_CYCLE_NUMBER Number of cycles 1, 2, 3 or 4
1P_CYCLE1_TIMER Timer of the first single-phase cycle From 10 ms to 5 seconds,
with a 10 ms step
3P_CYCLE1_TIMER Timer of the first 3-phases cycle From 10 ms to 60 seconds,
with a 10 ms step
3P_CYCLE2_TIMER Timer of the second 3-phases cycle From 1 to 3600 seconds,
with a 1 second step
3P_CYCLE3_TIMER Timer of the third 3-phases cycle From 1 to 3600 seconds,
with a 1 second step
3P_CYCLE4_TIMER Timer of the fourth 3-phases cycle From 1 to 3600 seconds,
with a 1 second step
RECLAIM_TIMER Reclaim timer From 1 to 600 seconds,
with a 1 second step
RECLAIMMC_TIMER Reclaimmc timer From 1 to 600 seconds,
with a 1 second step
RECLAIMML_TIMER Reclaimml timer From 1 to 600 seconds,
with a 1 second step
UNLOCKING_METHOD Method to unlock the auto-recloser None, manual close, unlock
signal, both
SYNC_ENABLE Use the synchrocheck function during the 3-
phases first cycle
Yes / No
C264/EN FT/C30 Functional Description

Page 100/132

MiCOM C264/C264C

7.1.3 Trip Circuit Supervision
The trip circuit supervision monitors the trip circuit wiring continuity irrespective of CB
position but only when the trip relay is not activated. Activation of the trip relay is indicated to
the C264 by a separate input and inhibits the detection of continuity.
The MiCOM C264/C264C computer is able to support the two diagrams used in Trip Circuit
Supervision:
Trip Circuit Supervision with one Digital Input + external resistor.
The resistor in the trip circuit supervision scheme (R) should have a value according to 2
criteria:
1. High enough so that once the CB is open, the tripping coil powered via the resistor
has no magnetic effect anymore so that the tripping mecanism is released (within a
possible delay due to inductive effect of the coil).
2. Low enough so that the C264 input powered via the resistor (and the tripping coil) is
detected active.
Therefore:
1. It is assumed that 10% of nominal voltage applied on the tripping coil makes its
magnetic effect low enough to release the tripping mechanism after activation. Taking
into account normal tolerance on power supply, this leads to a minimum value of R
being approximately 10 to 12 times the resistance of the tripping coil.
2. The BCPU input has been tested to operate with a series resistor up to 40kohm, still
leaving voltage across the input above the minimum. Taking into account tolerances,
this defines a maximum value for the resistor of 20kohm.
Areva recommends the value in the middle of the range (geometrically). If Rc is the
resistance of the tripping coil, then:
R / 12xRc = 20kohm / R
The power rating of the resistor must be such that it withstands permanent application of
maximum trip circuit voltage . Therefore:
P = (1.2 x Uaux)
2
/ R
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 101/132

C0138ENb
Vn+
Vn-
Vn+
Vn-
+ Uaux
Protection relay
CB
- Uaux
Computer
DI -1
DI-2
R
Vn+
Vn-
DI-3

FIGURE 48: TRIP CIRCUIT SUPERVISION WITH ONE DI
Trip Circuit Supervision with two Digital Inputs without external resistor.
C0139ENb
Vn+
Vn-
Vn+
Vn-
+ Uaux
Protection relay
CB
- Uaux
Computer
DI-1
DI-2
Vn+
Vn-
Vn+
Vn-
DI -3
DI-4

FIGURE 49: TRIP CIRCUIT SUPERVISION WITH TWO DI
NOTE: This diagram can be used with inputs which detection threshold of the
"set" state is > 55% Vn (example CCU A07).
C264/EN FT/C30 Functional Description

Page 102/132

MiCOM C264/C264C

7.1.4 Automatic Voltage Regulation (AVR)
7.1.4.1 Introduction
The Automatic Voltage Regulation function is used to automatically maintain the correct
voltage at the lower voltage of transformers. Secondary voltage is changed by controlling the
tap changer of transformers.
AVR is able to manage one transformer or several transformers in parallel. Transformers are
in parallel if their secondary poles are interconnected. Each transformer is controlled by one
computer but AVR function is only activated on one computer. The following figure shows an
example of architecture for AVR function controlling two transformers.
AVR function is activated on computer C264-1. This computer gets analogues values from
computers C264-2 and C264-3 through the station bus and sends tap changer commands
through the station bus.
C0344ENa
station bus
(iec 61850)
C264-2
C264-1
acquisition of U,I,Q,P

Tr2
command of tap changer
AVR on
C264-3
acquisition of U,I,Q,P

Tr3
command of tap changer

AVR also manages:
Active and reactive compounding in order the maintain the voltage at a remote
location,
Homing in order to adjust a transformer to the voltage of the busbar which it will be
connected to,
Minimisation of circulating currents.
7.1.4.2 Interfaces
For each transformer, the MiCOM C264/C264C that acquires:
Active and reactive compounding in order to maintain the voltage at a remote location,
Electrical topology of the LV side, including connection of the transformer to the
busbar and coupling of busbars into the LV level,
Tap Changer MCB state (Tap Position Indication).
The operator, through PACiS OI or TE, has an access to the following controls:
Global AVR on/off,
AVR on/off per busbar,
Five target voltages per busbar (5 floating values pre-set in configuration in the range
+/-10% with a resolution of 1%.
The current busbar AVR mode is equal to (busbar AVR mode) AND (Global AVR mode).
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 103/132

The following specific alarms and indications are available:
Substation alarms or indications
Homing On/Off (defined during the configuration phase)
Target Not Achievable
AVR defective
Error Log Indication
DBI override
Busbar alarms or indications
Invalid voltage (when different values for parallel transformers)
More than four transformers in the group
Under-voltage or over-voltage: AVR INHIBITED
A circuit breaker or a disconnector in an invalid state in the group
Transformer alarms or indications
AVR on/off
Hunting: this alarm is reset 30 seconds after the group is switched to AVR Off
MCB tripped
bad TCIP: this alarm is reset 30 seconds after the group is switched to AVR OFF
Tap Position is not the expected one
current > Overcurrent value
AVR disconnected
Bay in local mode
Voltage, current, MW and MVAR
AVR homing
Invalid Voltage
Low Voltage
Over Voltage
Run Away: this alarm is reset 30 seconds after the group is switched to AVR OFF
Tap long TCIP
The AVR Defective Alarm and the AVR Error Log Indication are grouped alarms with the
following inputs:
Per busbar
Invalid voltage (when different values for parallel transformers)
More than 4 transformers in the group
A circuit breaker or a disconnector in an invalid state in the group
C264/EN FT/C30 Functional Description

Page 104/132

MiCOM C264/C264C

Per transformer
hunting
MCB tripped
Bad TCIP
Tap position is not the expected one
Bay disconnected (this takes into account power supply fail)
Bay in local mode
Invalid voltage
The AVR Defective Alarm is set if one of the inputs is set, and is reset if all the inputs are
reset.
The AVR Error Log Indication is set if one of the input is set and is reset if the operator
selects the "Clear AVR Faults" command.
7.1.4.3 Groups
7.1.4.3.1 Definition
A group defines a set of interconnected busbars. A transformer belongs to a group if it is
electrically connected to a busbar of this group into the low voltage level.
Group mode is used to allow the automatic control of transformers. Group mode is either In
automatic control, or Out of automatic control. Busbars and transformers have their own
modes used to calculate the group mode.
7.1.4.3.2 Group mode calculation
This section details the group mode calculation. Each transformer, busbar and group is
characterised by attributes, used to calculate the transformer, busbar and group modes.
Attributes are entered during the configuration phase or calculated with the dynamic
electrical topology and settings of the system. Attributes may be ignored to calculate the
mode, this is defined during the configuration phase.
Transformer attributes are:
Type (Auto or double wound)
Transformer rating in MVA
Number of taps
Tap span
Its actual connection with a busbar (topology)
The state of its MCB (Open or Closed)
Tertiary reactor capacities (in MVAR)
The state of its tap changer: normal, abnormal (tap changer control) the state is
abnormal if:
TCIP signal too late or too long,
the tap is invalid,
the tap number is not the required tap, we may have this problem after a tap
operation if the tap number is not the expected one.
Its hunting status (True or False). Hunting is detected if more than N changes occurs
in less than T. The window time for hunting is comprised between 120 seconds to
1800 seconds in 0,1 second increments.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 105/132

Its homing status (On, Off or Inhibited)
Status of the bay containing the tap change control: local/remote,
connected/disconnected (supervision values)
Associated Voltage, current, MWs, MVARs, and their validity (measured values)
Its mode: In or Out (of automatic control). Mode is Out if:
The transformer is disconnected AND it is not in Homing mode
OR
The transformer is connected OR it is not in Homing mode,
AND
Tap changer is tripped OR tap changer state is abnormal OR transformer is
hunting OR its voltage is invalid OR the bay containing the tap changer control is
in local mode OR the bay containing the tap changer control is not accessible
OR
The busbar is OUT of automatic control
A transformer is disconnected if it is not electrically connected to a busbar.
Busbar attributes are:
Its transformers (configuration and topology)
Its topology (busbar section and coupler)
Its voltage target
Its priority. This is given by configuration.
Its actual voltage: This voltage is the average of the LV voltages of the connected
transformers. If one of the voltages differs by more than x% from the average, or if one
voltage is invalid then actual voltage is invalid.
Its mode: In or Out (of automatic control). Mode is Out if:
The mode of one of the transformers connected to it is Out
OR
Actual Voltage is invalid.
Group attributes are:
Its voltage target. This target is deduced from the busbar target composing the group.
The busbar with the highest priority forces the target.
Its actual voltage. This voltage is the average of the busbar actual voltages. If one of
the voltages differs by more than x% from the average, or if one voltage is invalid then
actual voltage is invalid.
busbars. This is given by the topology.
Its mode: In or Out (of automatic control). Mode is Out if:
Global AVR is Out
OR
The mode of one of the busbars composing the group is Out and the mode
group connexion is "IN and OUT => OUT.
OR
Actual voltage is invalid
C264/EN FT/C30 Functional Description

Page 106/132

MiCOM C264/C264C

OR
More than 4 transformers in the group.
OR
Invalid state of a disconnector or a circuit breaker in the group.
When a group is set OUT of automatic control, it remains in this state until the operator sets
the group IN automatic control.
It is only necessary to select one busbar in a group to automatic control to place the whole
group under automatic control.
When the substation control mode is Remote, the AVR control is allowed from the RCP and
inhibited from the SCP. When the substation control mode is Standby, the AVR control is
allowed from the SCP and inhibited from the RCP.
7.1.4.4 Tap changer control
If a transformer is in automatic control and if there is an invalid evolution of the tap changer,
then the tap changer MCB is tripped and the RunAway alarm is set.
7.1.4.5 Moving Tap Changers
7.1.4.5.1 General
Automatic control of a transformer is only allowed if it belongs to a group in Automatic control
mode or for homing. Manual control of a transformer is only allowed if its setting mode is Out
of automatic control.
Note that:
Automatic control of a tap changer is independent of the mode of the substation
(SCP/RCP)
Automatic control of a tap changer may be used in conjunction with manual control of
transformer belonging to an other group in manual mode or with manual control of the
rest of the apparatus (breaker, disconnector, protections, ...)
Simultaneous operations on transformers belonging to independent groups is allowed,
since the electrical topology is not affected.
Decision to move one or more tap changers is caused by one of the following reasons:
Voltage in one group is outside of the Voltage Target Deadband. This is the most
common situation.
Voltage is correct, but there is a circulating current between parallel transformers .
This will happen when two groups are interconnected.
Voltage is correct, but the tap span and patterning may be changed when any of the
relevant switchgear change state.
Homing of one transformer. This will happen when the circuit breaker at the LV side of
the transformer is open, and Homing status is on.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 107/132

7.1.4.5.2 Voltage is outside of the Voltage Target Deadband
This paragraph specifies the algorithm used to decide the change of a tap, when voltage is
outside the voltage deadband.
The target voltage that must be reached is defined by:
Target Voltage = [Selected Target Voltage + Voltage Compounding] * Voltage SetPoint,
where:
Selected Target Voltage is one of the five pre-programmed Selected Target Voltages.
(when the AVR starts up, the selected target voltage is a target voltage pre-set in
database)
Voltage Compounding is line drop compensation, it allows to maintain the nominal
voltage at a remote location of the actual measurement point.
Voltage SetPoint is a coefficient typically comprised between 0.9 and 1.
There are two methods for line drop compensation. According to the customer, one is
defined during the configuration phase:
1. First line drop compensation method:
Voltage Compounding = Actual busbar load (MW ) * Resistive multiplier
+ Actual busbar load (MVAR ) * Reactive multiplier.
2. Second line drop compensation method:
Alternatively the line drop compensation can also be achieved by using the resistance R and
reactance X of the connection circuit as compounding settings. In this method, the measured
voltage is adjusted such that:
V = ((V0 A) + B)
Where
V0 actual measured value
V adjusted measured value. V is used to determine the tapping action by comparing
with the target voltage
A = (R*P + X*Q) / V0
B = (X*P - R*Q) / V0
P active power, Q reactive power,
R et X are the resistance and the reactance of the connection circuit for the resistive
and reactive compounding respectively.
Voltage deadband
The Voltage Deadband is expressed as a percentage of the nominal voltage. By
configuration, coefficients are set to adjust the deadband with the number of transformers in
a group.
Voltage deadband = Initial Voltage deadband * coefficient.
C264/EN FT/C30 Functional Description

Page 108/132

MiCOM C264/C264C

Two examples:
case 1 case 2
Group with 1 transformer 1 1
Group with 2 transformers 1 1
Group with 3 transformers 1 2/3
Group with 4 transformers 1 1/2
Decision to move the tap changer is made when:
Voltage > Target Voltage + Voltage Deadband * Nominal Voltage
OR
Voltage < Target Voltage - Voltage Deadband * Nominal Voltage for more than a time-
out T1.
Dual deadbands are used to ensure that the post tapping voltage is sufficiently closed to the
selected target voltage. Deadband 1 is used to initiate tapping and deadband 2 is used to
end tapping.
7.1.4.5.3 Timeouts
Moving the taps of the transformers is achieved with respect of some time-outs.
The "first tap" of a transformer is delayed by a time out T1, the next ones by a time out T2.
Several taps are used if one is not enough to reach the voltage target or the optimisation of
the circulating current. T2 begins after the end of the TCIP.
When the voltage is drifting in and out of the deadbands, the system counts up to T1 when
the voltage is outside of the deadband1. If before T1 is reached the voltage returns within the
deadband2 then the system counts down to 0.
When the voltage is crossing from one side of the deadband1 to the other side, the count is
reset to zero and the new time delay is T1.
After an auto-recloser operation , the group (or the two new groups) keeps the same AVR
modes; however the count is reset to zero and the new time delay is T1.
T1 is adjustable between 15 and 120 seconds in 0,1 second increments.
T2 is adjustable between 0 and 120 seconds in 0,1 second increments.
Moreover, the AVR shall not drive the system voltage by more than a pre-set rate (defined in
database). This rate, maximum voltage change rate is settable between 0,1kV/min and
5kV/min in 0,1kV/min increment.
If a Tapping is required after a previous tap control:
Ti is the date when the previous tapping was performed
T is the current date
MVCR is the Max voltage change rate
T2 is the inter Tap delay
Vi was the secondary voltage at Ti
V is the current secondary voltage
For a Tap Up(to increase voltage), tapping is performed as soon as the following are TRUE
T > Ti + T2
V < Vi + MVCR * (T - Ti)
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 109/132

For a Tap Down (to decrease voltage), tapping is performed as soon as the following are
TRUE
T > Ti + T2
V > Vi - MVCR * (T - Ti)
The maximum voltage rate is achieved as described in the example below:
C0010ENa
Volt
Time
T1 T2 T2
T0
Tap RAISE 1 Tap RAISE 2 Tap RAISE 3
RateMax

FIGURE 50: VOLTAGE REGULATION
Tap RAISE 1 is performed after T1.
Tap RAISE 2 is performed T2 after Tap RAISE 1, at this time the voltage change rate is
lower than the maximum rate.
Tap RAISE 3 is NOT performed T2 after Tap RAISE 2, because at this time the voltage
change rate is greater than the maximum rate. It is performed when the current voltage
change rate becomes lower than the maximum rate.
It is possible to choose by configuration a T1 delay as a fixed delay or as an inverse time
delay.
When inverse initial time delay is selected:
DV = | actual group voltage - deadband limit voltage |
IF DV < 1% target voltage THEN initial tap time delay = T1.
IF 1% <= DV < 10% target voltage THEN initial tap time delay = T1/DV.
IF DV >= 10% target voltage THEN initial tap time delay = T1/10.
When a transformer belongs to a group of several transformers, the time out is applied to the
group. Two different groups have separate time out references, thus allowing simultaneous
taps.
The tap is defined as the "first one" when (logical OR):
The group mode has changed.
The voltage comes back into the deadband2.
When the voltage is crossing from one side of the deadband to the other side.
7.1.4.5.4 Single transformer management
If a group is restricted to one transformer and is in automatic control mode, raise and lower
commands are issued if the voltage exceeds the voltage deadband with respect of the time
outs.
C264/EN FT/C30 Functional Description

Page 110/132

MiCOM C264/C264C

7.1.4.5.5 Multiple transformers management
If a group is composed of more than one transformer and is in automatic control mode, then
the coordination of the transformers of the group aims at minimising the circulating power. To
achieve this, there exist three methods depending on the substation constraint and customer
requirement. By configuration one of these three methods has to be chosen.
For the three following methods, if all the transformer tap-changers reach their end stop
while tapping is required to go further, then the substation alarm "target not achievable" is
generated. This alarm disappears when the problem is cleared.
First method: TAP
In this case, assumption is made that:
the primary voltages of the transformers are identical
the number of taps and tapping ranges of the transformers are identical
Then the maximum tap span between the transformers will be 1 and there will be a balanced
control of them when the voltage is changing.
Calculation is as follows:
1. if voltage is out of the deadband,
1.1. and under the deadband -> action is raise on the transformer with the lowest
Tap
1.2. and upper the deadband -> action is lower on the transformer with the highest
Tap
2. if voltage is in the deadband, the system sets the transformer within one tap
Second method: Transformer ratio
In this case, assumption is made that the primary voltages of the transformers are identical.
Calculation is as follows:
1. if voltage is out of the deadband,
1.1. and under the deadband -> action is raise on the transformer with the lowest
transformer ratio
1.2. and upper the deadband -> action is lower on the transformer with the highest
transformer ratio
2. if voltage is in the deadband, the system sets the transformer within a percentage of
transformer ratio. This percentage P is calculated for all groups:
P = Maximum (tapping range / (number of taps - 1 ))
Example:
Group with 3 transformers:
SGT1: 19 taps, tapping range = 30 %
SGT2: 19 taps, tapping range = 30 %
SGT3: 16 taps, tapping range = 20 %
P = Max(30 / 18; 30 / 18; 20 / 15) = 30/18 % = 1.67 %
So, the 3 transformers stay within 1.67 %.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 111/132

Tap operation if (ratioMax - ratioMin) > 0,0167 ratioNom, with:
ratioMin = Minimum transformer ratio of the 3 transformers
ratioMax = Maximum transformer ratio of the 3 transformers
ratioNom = Nominal secondary voltage / Nominal primary voltage (defined in
configuration)
Third method: circulating current minimisation
In this case, there is no assumption that the primary voltages of the transformers are
identical.
With a sample example of two transformers:

SGT1 SGT2
I1 I2
I

Per transformer, we know
Sn (rating),
x (Impedance in % on Sbase: e.g.100 MVA),
U,
I,
P,
Q,
Current tap
Unom (nominal secondary voltage)
X (reactance) = x * (Unom) / Sbase
One transformer can be presented as below:
X
E
I

C264/EN FT/C30 Functional Description

Page 112/132

MiCOM C264/C264C

The both transformers can be presented as below:
X1
E1
I1
X2
E2
I2
U
I
Ic

We have
U = E1 - X1*I1 = E2 - X2*I2 => E1-E2 = X1*I1 - X2*I2
I = I1 + I2
E1 - E2 = (X1 + X2 ) * Ic
=> Ic = (X1*I1 - X2*I2) / (X1 + X2)
For each transformer, we have U,I,P,Q (So U1,I1,P1,Q1 and U2,I2,P2,Q2)
We have for i=1 or i=2, Qi/Pi = tan i
According to the signs of Pi and Qi: - < i <
If there is a circulating current from transformer 1 to transformer 2 then 1 > 2.
U1 = U2
I2
I1
1
I

Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 113/132

Voltage out of the deadband
If the voltage is out of the deadband and active power > 0 (|| < /2) then
If the voltage is under the target then transformer with highest || is tapped UP
If the voltage is over the target then transformer with lowest || is tapped DOWN
If the voltage is out of the deadband and active power < 0 (|| > /2) then
If the voltage is under the target then transformer with lowest || is tapped UP
If the voltage is over the target then transformer with hughest || is tapped DOWN
For three or four transformers, the same algorithm is used.
Voltage into the deadband
If the voltage is into the deadband then the circulating current must be checked to know if it
is possible to reduce it.
U = E1 E2 = |X1*I1 - X2*I2|
U is compared to the voltage step corresponding to one tap (U1tap).
TapSpan: tap span for the transformer
NbTap: number of taps for the transformer
Unominal: nominal secondary voltage
U1tap = (TapSpan/(NbTap -1)) * Unominal
if U > U1tap and if i > j so
If the voltage is out of the deadband and active power > 0 (|| < /2) then
If the voltage is under the target then transformer with highest || is tapped UP
If the voltage is over the target then transformer with lowest || is tapped DOWN
If the voltage is out of the deadband and active power < 0 (|| > /2) then
If the voltage is under the target then transformer with lowest || is tapped UP
If the voltage is over the target then transformer with highest || is tapped DOWN
For three or four transformers, the same algorithm is used.
7.1.4.5.6 Target voltage
When the operator changes a target voltage, the new target voltage is indicated immediately.
The actual target voltage will not be changed by more than the corresponding pre-set value if
the busbar is under automatic control. If the busbar is not under automatic control the new
target voltage is immediately achieved.
7.1.4.5.7 AVR inhibited
AVR is inhibited for the corresponding group while the measured system voltage is less than
a pre-set value or higher than an other pre-set value.
Overcurrent on a transformer will also inhibit the transformer's group.
C264/EN FT/C30 Functional Description

Page 114/132

MiCOM C264/C264C

7.1.4.5.8 Homing
Homing is a facility which taps transformers such that their open circuit terminal volts follows
the volts on the busbars that they are selected to within 3% of the busbar voltage when the
mode of this busbar is In automatic control.
Homing is only able if there is at least one transformer connected on the corresponding
busbar and if transformer busbar disconnector is closed and LV circuit breaker open.
Homing is disabled while the busbar voltage is less than Umin (80% of nominal voltage).
If a transformer is under Homing Mode, a manual control is not accepted.
Homing ceases when the tap changer is faulty and until the operator selects "Clear AVR
faults". If the Tap Changer is still faulty then the transformer remains OUT of automatic
control.
Time out T3 is used for the first tap in the homing mode.
Time out T4 is used between successive taps.
7.1.4.6 Capacity
AVR is able to manage a maximum of:
7 transformers,
4 transformers in parallel,
8 busbars,
4 transformers per busbar,
2 reactors per transformer,
2 voltage levels.
7.1.4.7 List of configurable parameters
General parameters:
AVR used / or not
Homing ON / OFF
Presence of an external ARS / or not
Initial tap time delay (T1) fixed / or not
Calculation mode:
method TAP
method transformer ratio
method circulating current minimisation
Period of AVR calculation (default value: 1 second)
Percentage of the Homing deadband (default value: +/-3%)
Initial tap time delay: T1 (default value: 60 seconds; range 15 to 120)
Inter tap time delay: T2 (default value: 10 seconds; range 0 to 120)
Initial tap time delay: T3 (default value: 60 seconds; range 15 to 120)
Inter tap time delay: T4 (default value: 10 seconds; range 0 to 120)
Hunting window: T5 (default value: 500 seconds; range 120 to 1800)
Coefficients for 1, 2, 3 and 4 transformers (default values: 1)
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 115/132

Maximal number of successive taps in opposite direction for hunting (default value: 4 )
Overcurrent setting (default value: 140%; range 100 to 200% )
Percentage of accepted difference between secondary voltages for transformers in the
same group. (default value: +2%)
Under-voltage: percentage of nominal voltage under which AVR or Homing is inhibited
(default value: 80%)
Over-voltage: percentage of nominal voltage over which AVR or Homing is inhibited
(default value: 120%)
Mode group interconnexion: IN and OUT => IN or IN and OUT => OUT
Mode if bay in local: IN / OUT
Compounding method: setpoint adjust or voltage adjust
Parameters per busbar:
Resistive multiplier (default value: 0.01%; range 0,1% to +0,1%)
Reactive multiplier (default value: 0.01%; range 0,1% to +0,1%)
SetPoint value (default value: 1; range 0.9 to 1 )
Priority: 0 to 4
Parameters per transformer:
AVR tap minimum and maximum value
AVR transformer rating (default value: 240 MVA)
AVR transformer impedance on nominal tap on 100 MVA base
AVR transformer type (autotransformer or double wound)
AVR tapping range:
upper value (default value: +20%)
lower value (default value: -20%)
Nominal ratio
Parameters per voltage level:
Target voltage ramping rate (default value: 1.5 kv per minute)
Max voltage change rate (default value: 0,1 kv per minute)
voltage deadband1 (default value: +/-1%; range +/-0.5% to +/-5% )
voltage deadband2 (default value: +/-1%; range +/-0.5% to +/-5% )
Target voltage 1 (default value: 90% of nominal voltage; range +/- 10% of nominal
voltage)
Target voltage 2 (default value: 95% of nominal voltage; range +/- 10% of nominal
voltage)
Target voltage 3 (default value: nominal voltage; range +/- 10% of nominal voltage)
Target voltage 4 (default value: 105% of nominal voltage; range +/- 10% of nominal
voltage)
Target voltage 5 (default value: 110% of nominal voltage; range +/- 10% of nominal
voltage)
C264/EN FT/C30 Functional Description

Page 116/132

MiCOM C264/C264C

To maintain a system voltage supply within a given deadband, it is necessary to regulate the
system voltage. The On-Line Tap Changing (OLTC) transformer maintains a stable
secondary voltage by selecting appropriate tapping on the secondary transformer windings.
Selection orders are issued from the Voltage Regulation function that continuously monitors
the transformer.
The motors-driven OLTC received the "Raise" and "Lower" control commands from the
Voltage Regulation module. These orders change the OLTC position and the transformer
voltage value is adapted to the pre-set required voltage level.
7.2 Interlocking: logical equations
In an electrical substation, the switching devices are primarily the followings:
Circuit breakers
Traditional disconnecting switches
Disconnecting switches with abrupt rupture
Ground disconnecting switches
The operating of a switching device is directly related on its nature and its environment. It
can be operated only with respect of certain conditions. These conditions, therefore called
interlocking, are managed in the form of logical equations within the computer.
Moreover, interlocking can be applied on whatever module or whatever control.
The goal of the function of interlocking is to prohibit operating which would be ordered by
error, in remote control, to a switching device beyond its standard conditions of operation.
Some equations of substation interlocking also manage the operations of the disconnecting
switches according to topology and by respecting some preset rules: topological interlocking.
The equations of topological interlocking, awashed with substation equations, are generated
by independent software. This software takes in account the topology and some predefined
rules to provide these equations
7.2.1 Inputs
Interlocking function can use the following inputs:
Digital inputs from the systems digital input boards, from other system computers,
from protection relays and other IEDs via communication network (single and double
point, digital groups),
Internal indications (e. g. system failures, equipment operation modes, ...),
Limits derived from measured values from the systems analog input boards (CT, VT,
transducers), from other system computers, from protection relays and other IEDs via
communication network.
7.2.2 Outputs
Result of the interlocking equation is transmitted through a system binary output and saved,
locally in RAM, by the function managing interlocking logical equations.
And, a service is available for any task to get the result of the computation.
Thus , the function managing control of sequence uses this service to know whether control
can be executed.
Then, a simple transient binary input can be set if defined in configuration. The same SPS is
used for the commands open and close of a xPC
7.2.3 Control
No control. An equation is computed each time that one of its input changes of state or of
validity.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 117/132

7.2.4 Behaviour
7.2.4.1 Principle
In computer, a logical interlocking equation is defined as a sum of product (AB+CDE+F for
example).
7.2.4.1.1 Introduction
Interlocking function uses up to two interlocking equations per switching device on bay-level
and on substation-level. During configuration process the definition of the switching devices
can be:
without associated interlocking equations,
with only one interlocking equation, e. g. for opening, closing being not checked or
vice-versa,
with two interlocking equations (for opening and closing). The interlocking equations
can be different but can also be identical.
The equation is composed of Boolean information mainly representing the position of other
switching devices.
The interlocking for a switching device may be composed of substation interlocking
equations and local interlocking equations.
Both interlocking are managed by the computer which controls the switching device.
Local equation is made up of information obtained from its own digital inputs and IEDs
connected to this computer.
Substation interlocking is made up information obtained from its digital inputs and inputs
provided by the communication network from other computers, from bay computers and from
IEDs (protection relays, etc.). Substation interlocking can also be managed by the
topological interlocking function (Refer to Topological interlocking for more details.
7.2.4.1.2 Local interlocking
The local interlocking is done by calculation of a logical equation. It can exist up to one
equation per switching device and per each direction (open and close). If there is no
equation for a switching device for a direction, the corresponding variable is true.
7.2.4.1.3 Substation interlocking
The substation interlocking analyses the position of all switching devices in the substation
and calculates the substation interlocking equation to authorise control of a switching device
according to the mechanical and electrical capabilities of the switching device. If there is no
equation for a switching device for a direction, the corresponding variable is true.
7.2.4.1.4 Validity of information
The interlocking equation does not only use the value of the information but also the validity
of the information (invalid, ...).
Thus the result, saved in RAM, of a logical equation is only TRUE or FALSE, An Interlocking
equation in the INVALID state will be considered as FALSE .
But, the system binary input also generated can be valid (SET or RESET) or invalid.
The evaluation of the result of basic logical function such as NOT, AND or OR is defined as
follows:
NOT
True False
False True
Invalid Invalid

C264/EN FT/C30 Functional Description

Page 118/132

MiCOM C264/C264C

OR True False Invalid
True True True True
False True False Invalid
Invalid True Invalid Invalid

AND True False Invalid
True True False Invalid
False False False False
Invalid Invalid False Invalid
An Interlocking equation in the INVALID state will be considered as FALSE.
7.2.4.1.5 Interlocking bypass
Bypass made by key switch
Interlocking can be overridden (interlocking bypass mode). Overriding of interlocking can be
set from the local control point.
During configuration optional overriding of interlocking from any other control point can be
defined according to customer requirements. This includes the possibility of overriding of
interlocking per switching device or per bay or per substation entity basis.
If an interlocking is overridden, the associated variable is true.
Bypass within the control
From any control point, operator can bypass the interlocking check. Bypass is then an
attribute of the control. If bypass is set, the function managing the control of sequence does
not use the service giving the current result of the interlocking equations.
7.2.4.2 Software tasks
A logical equation is a sum of products. Each product comprises logical data that can be
complemented. Each electrical component has two logical equations at the most, and each
logical equation is associated with one electrical component.
Example of Logical equation: X = A.B + C.D.E
In this example, the component X can be operated only if:
(A is in the higher state) AND (B is in the lower state)
OR
(C is in the lower state) AND (D is in the higher state) AND (E is in the lower state)
The terms of these equations can be issued from:
Simple point status. (BI)
Double point status (BI)
1 among N BI (SIG)
Measurement (MEAS)
At configuration time, operator has to define the interlocking profile of each data included in
an interlocking equation. It means that operator must select for each state or validity of a
data a logical state (TRUE, FALSE or INVALID).
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 119/132

Interlocking computation
As said before, an interlocking equation;
is computed each time that one of its element changes of quality or state and
is defined by a sum of product.
Upon reception ofa new state or quality for a data
Get logical state associated to the received state and validity of the data
For each equation that includes the data
Compute the sum of product
Determine the result of the interlocking equation (TRUE or FALSE)
Send new state of the system binary input representing the result of the interlock.
BI can be: SET, RESET or INVALID
Interlocking consultation
On reception of open or close request, if the logical equation associated with the switching
device exists, the control of sequence function used the service offered by the interlocking
function to get the result of the interlocking associated to the received request.
If result of the interlocking is TRUE, the check is considered as achieved, else request must
be refused and a negative acknowledgement sent to the origin of the request.
Simulation and test of interlocking equations
The interlocking system is checked during the in house test of the substation control system.
Each interlocking equation may be checked by issuing a control to the corresponding
switching device.
For checking the interlocking on site a SIMULATION mode is implemented in the computer.
In this operating mode, a valid control is sent to the output, but closing the contact is not
performed and a positive acknowledgement message is generated.
7.2.5 Limits and performance
Up to 256 operands can be used on a per equation basis.
Up to 256 equations can be defined in a computer.
A datapoint can be used in up to 255 interlocking equations.
C264/EN FT/C30 Functional Description

Page 120/132

MiCOM C264/C264C

7.3 Slow automation: Programmable Logic Control (PLC)
The MiCOM C264/C264C allows the user to configure specific control sequences or
automations (e.g. switching sequences, busbar transfer, load shedding, GIS-pressure
supervision) during the substation configuration phase.
The Programmable Logic Controls (PLC) or Configurable Automations are entered and built
onto a logic development workbench. The real time kernel of the computer runs them.
The solution retained for developing control logic programs in the computer is a Soft Logic
package.
The Soft Logic package Workbench is a host-based software development environment
associated to the System Configurator. It is used to create control logic programs.
It is a full-featured set of tools providing:
Editing
Code generation
Simulation
Debugging
Project management
The Soft Logic package supports standard programming languages of the IEC 1131-3:
Sequential Function Chart, SFC (GRAFCET)
This language can be used with Function Block Diagram (FBD), Ladder Diagram (LD) or
Instruction List (IL) for action and transition descriptions.
Structured Text, ST
The code generated by the Soft Logic package workbench is uploaded to the computer
target system that runs it.
C0019ENa
Control logic
application
code
Target
hardware
Soft Logic
package

FIGURE 51: PLC WORKBENCH
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 121/132

7.3.1 Inputs
All the datapoints of the computer can be used as an input of a PLC.
7.3.1.1 Data acquired by the computer
BI: non filtered change of states are transmitted to PLC kernel
MEAS
CT
Tap position (TPI or SPI)
7.3.1.2 Data managed by the computer
CO
NOTE: A CO can be used as input of a PLC function, but only through the
use of C function present by default with the kernel.
7.3.1.3 Acknowledgement of control
A PLC function can manage a control sequence:
Send control
Process acknowledgement to the sent control
7.3.2 Outputs
A PLC function can:
generate a BI, e.g. PLC is considered as source of acquisition of the data point,
generate a MEAS,
generate a CT,
generate a SPI,
generate a SIG,
modify quality of a Binary Input defined in the computer: force, suppress or
substitution request,
modify quality of a MEAS defined in the computer: force, suppress or substitution
request,
modify quality of a SIG defined in the computer: force, suppress or substitution
request,
send binary order to computer boards or IED or to another computer,
send digital setpoints to computer boards or IED or to another computer.
7.3.3 Control
Automations can be triggered:
by operator request,
by events (digital or analogue input state changes),
cyclically (each day, each week or each month),
at a specific date and time (e. g.: 20. 12. at 10:00).
C264/EN FT/C30 Functional Description

Page 122/132

MiCOM C264/C264C

7.3.4 Behaviour
The computer has a software execution engine designed to interpret the automation
application code according to the cycle described hereafter.
C0345ENa
Read inputs
Execute programs
Write outputs

Basically, the cycle duration depends on the number of I/O to be scanned and the complexity
of the operations to be performed. It will be set during the configuration process.
7.3.4.1 Interfacing with a HMI or a RCP/SCADA
A remotely sited master station can send and receive data to and from the automation
applications of the computer.
In DB, the data sent by a master station to an automation application include DO and BI
entities. Conversely, the data received by a master station from automation applications
include DI, Measurements, Metering (non-tariff), and Tap Changer Position entities. These
data have a unique transmission address for the computer.
7.3.5 Limits and performances
The execution of the automation sequences can be cyclic and/or event-driven.
Maximum number of cyclic PLC-programs is 32.
The two different time cycles of a PLC-program can be set from 10 ms up to several
seconds. For some specific equations a cycle less or equal to 10ms and a cycle less
or equal to 100ms for the other logic equations. The time cycle for the automatic
functions shall be less than 100ms.
Each PLC-program runs on one computer, which means a PLC-program cannot be
distributed within the system. However, it is possible to use information obtained by
other computers.
Routing of the automatism applications to the memory must be carry out according the
memory and hardware design.
The debugging of the applications must be possible in connecting a local PC on the
front face. The hardware design will take in account this possibility and will separate
out the debugging and the application download.


Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 123/132

7.4 Fast automation: Programmable Scheme Logic (PSL)
As automatisms created through ISaGRAF are dependent from the ISaGRAF cycle whose
value is about 50ms in the best case, it is necessary to implement some configurable
automatisms that can be achieved in less than 50ms.
PSL is the solution for implementation of automatism that must be performed as quickly as
possible.
Designed solution is mainly based on mechanism used for the computation of logical
interlocking (refer to logical interlocking for more details). Indeed, logical gates AND, OR,
NOT, NAND, NOR or a combination of these gates can be processed as a logical equation.
Some other functions (drop-off and pickup timer, bistables) are added to these logic gates.
These automations are event-driven: they are calculated each time an input changes (i.e.
there is no cycle time).
Only BI and measurements described are usable as inputs (controls are not).
PSL are logical equations that use the following functions:
AND, OR, XOR, NOT, NAND, NOR operators
"bistable" functions
pickup and drop-off timers (from 10 ms to 60 seconds, by step of 10 ms)
BI setting the system BI is:
SET if the PSL is TRUE
RESET if the PSL is FALSE
INVALID if the PSL is INVALID
Digital Output setting the DO is:
closed if the PSL is TRUE
opened if the PSL is FALSE or INVALID (only in case of permanent DO)
INVALID if the PSL is INVALID
The equations management rules described for interlocking equations apply on PSL.
Digital outputs used as outputs are mandatory local hardwired DO directly managed by the
computer
C0140ENa
&
&
&
1
1
1
t
1 1
DO1
setting
I1
I2
I3
I4
DO2
setting
BI1
setting

FIGURE 52: EXAMPLE OF PSL
C264/EN FT/C30 Functional Description

Page 124/132

MiCOM C264/C264C

8. USER INTERFACE
This section is described in the chapter Human Interface.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 125/132

9. RECORDS
Several kinds of records are stored into MiCOM C264/C264C.
9.1 Permanent records storage
They are stored on flash disk.
9.1.1 Data storage
All parameters or settings that can be modified via front face LCD are stored in flash disk.
Lists of system information are also stored in the flash disk.
9.1.2 Waveform Recording
A waveform recording deals with the storage of measurement and logical information in
order to visualise the electrical network behaviour when electrical event appear, such as the
start of the generator. These types of events are called trigger of waveform recording.
In order to see the influence of a trigger, data are recorded before (pre trigger time) and after
(post trigger time) the raise of the trigger.
Two types of waveform recording can be performed in the computer:
Fast Waveform recording which gives access to samples
Slow wave form which gives access to RMS values
9.1.2.1 Fast Waveform Recording
The inputs for the fast waveform records are up to 4 CT samples and 4 VT samples, and the
values of the selected digital inputs and outputs. Up to 128 digital channels may be captured.
The choice of selected inputs/outputs is defined in configuration.
The waveform recorder provides up to 8 analogue measurements and up to 128 digital
channels for extraction by a remote device.
A maximum of 480 cycles ( 9,6 seconds at 50 Hz) of measurements samples, with 32
samples per cycle, can be stored, divided in 1, 2, 4 or 8 files saved in flash disk.
A timer channel is also required to provide accurate timing information for each sample. The
delay between each sample is assumed constant over a single cycle.
Number of Files Number of cycles
8 60
4 120
2 240
1 480
The waveform recorder can be triggered by the following events, each of which is user
configurable:
Changes in state of binary inputs (SP, DP, MP, SI or Groups)
Changes in state of digital outputs
Measurement threshold violations
Operator request
Only one re-trig is allowed: it means that a new trigger can only be accepted after the end of
recording of the current waveform.
Waveform records are available in COMTRADE 2001 format.
C264/EN FT/C30 Functional Description

Page 126/132

MiCOM C264/C264C

9.1.2.2 Slow Waveform Recording
The inputs for the slow waveform records are:
analogue values coming from CT VT calculation (RMS values)
analogue values coming from AIU boards
Digital inputs
Digital outputs
The slow waveform manages up to 24 analogue and 48 digital values.
Data from CT/VT can be chosen among:
RMS Values of phase voltage
RMS values of busbar voltage
RMS values of phase current
RMS values of residual voltage and current
Fundamental sequence components
Active Power
Reactive Power
Apparent Power
Frequency
Harmonics levels
MiCOM C264/C264C stores at maximum 5000 integrated values as follow:
Number of Files Number of integrated values
1 5000
2 2500
5 1000
10 500
20 250
50 100
The integrated value has duration up to one hour. It is defined in configuration.
For analogue, the stored value is the average value during integrated period.
For digital, the stored value depends also on the average:
If average value > x then the stored value is 1 else it is 0, x is defined in configuration and it
is a value between 0.1 and 0.9.
The slow waveform recorder can be triggered by the following events, each of which is user
configurable:
Changes in state of binary inputs (SP, DP, MP, SI or Groups)
Changes in state of digital outputs
Measurement threshold violations
Operator request
Periodically (i.e. every day at 00h00)
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 127/132

9.1.3 Events
All data change or events declared in MiCOM C264/C264C configuration database To be
logged are stored in a circular queue.
The event records are available for viewing either via the front panel LCD, via slave protocol
at SCADA level or on CMT equipment. They also can be printed.
Events, following MiCOM C264/C264C configuration, may typically contain the MiCOM
C264/C264C description, the date of the event and the time of the event with an accuracy of
1 ms, plus specific information regarding the causes of the events.
The MiCOM C264/C264C under the following circumstances may create events:
Changes of state of Binary Inputs (SP, DP, MP, SI, Groups)
Changes of state of Measurements
Changes of state and value of Tap Position Indications
Devices Control actions and acknowledgements
Alarm acknowledgement
The size queue is:
200 data for front panel
2000 data for CMT
configurable per slave protocol for SCADA
9.2 Non-permanent data storage
9.2.1 Alarms
9.2.1.1 Definitions
9.2.1.1.1 Definition of an alarm
An alarm is a visual (and optionally audible) annunciation of the appearance and/or
disappearance, within the controlled electrical process or within the system itself, of an
event, defined during the configuration phase as to be alarmed.
These definitions, of what is to be alarmed and what it is not, are completely user relevant.
However the concept of alarms into PACiS has been introduced to inform the operators of
abnormal or special events or other miscellaneous events which must absolutely not be
overlooked.
9.2.1.1.2 Types of alarmed data
An alarm can be generated by the following events:
each Binary Input (SP, DP, MP, SI, IED input, Groups) state
each Measurement state
each TPI state or value
each metering state
associated to the reason for change of these events.
For example, the OPEN state of a circuit breaker can be un-alarmed if the change is due to a
control, and alarmed if the change is due to an other reason.
Furthermore, an alarm can be associated to a control acknowledgement. In this case, the
alarm is considered as spurious.
C264/EN FT/C30 Functional Description

Page 128/132

MiCOM C264/C264C

9.2.1.1.3 Alarm states definition
An alarm is generated by an event (e.g. a particular datapoint in a state defined during the
configuration phase as to be alarmed).
While this event is still present (e.g. the previous particular datapoint is still in the same
state) the alarm is active.
When this event disappears (e.g. the previous particular datapoint is now in another not
alarmed state) the previous alarm is inactive.
An existing alarm (active or inactive), can be acknowledged by an operator from the front
panel.
So an alarm can have the following states:
inactive: no transition, no event
active-acknowledged: the cause is still present but the active state has been taken into
account by the operator
active-unacknowledged: the cause is still present and the active state has not been
taken into account by the operator
inactive-unacknowledged: the cause has disappeared but the inactive state has not
been taken into account by the operator (only available for events alarmed on
appearance and disappearance)
inactive-acknowledged: the cause has disappeared and the inactive state has been
taken into account by the operator
inactive-active-unacknowledged: the cause has disappeared but the active state
(previous state) has not been taken into account by the operator
9.2.1.1.4 Parameters associated to an alarm
The following user-selectable parameters can be associated with each alarm definition. The
values are set during the configuration phase on a per alarm basis:
immediate or differed:
an immediate alarm is displayed as soon it has been detected.
a differed alarm is displayed only after a user-selectable time delay following its
detection (the event associated with the alarm must remain present during the
delay; if not, the alarm will be not displayed) ; this delay is in the range of 1 to 120
seconds and can be set to particular value for each differed alarm.
gravity level: this level is defined for each alarm allowing a hierarchical classification to
deal with the urgency of the events; the gravity level value can be: 0, 1, 2, 3, 4 or 5, 5
being the most grave and 0 meaning that there is no gravity level.
alarm generated:
only when the associated event appears
OR
when the associated event appears AND when it desappears
In this case the differed parameter is taken into account only when event appears;
when event disappears the new state of the alarm is displayed immediately.
alarm clearing mode:
manual: the alarm is cleared only on an operator request; this clearing command
is only allowed on inactive-acknowledged alarms.
automatic: an alarm is automatically cleared when it reaches the appropriate state.
gravity basis
audible or not when detected
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 129/132

9.2.1.2 Alarm processing
Only one alarm (the last one) associated with a state change of a data is displayed. The
previous one (concerning the data) is replaced by the current one.
According to the previous example, only one from the three alarmed states can be displayed
for the switching device: e.g. JAMMED or TOGGLING or OPEN state (the last
one which has appeared).
By configuration, one of the following behaviour is chosen:
C0143ENa
AL- (auto)
AL-
Alarm inactive
/ cleared
Alarm active-
unacknowledged
Alarm active-
acknowledged
Alarm inactive-
active-
unacknowledged
Alarm inactive-
acknowledged
AL+
AL+
AL+ CLEAR
ACK
ACK
AL-
0
1
4
2 3
ACK (auto)
AL+
AL+

FIGURE 53: EVENT ALARMED ON APPEARANCE ONLY
C264/EN FT/C30 Functional Description

Page 130/132

MiCOM C264/C264C

C0144ENa
Alarm inactive
/ cleared
Alarm active-
unacknowledged
Alarm active-
acknowledged
Alarm inactive-
unacknowledged
AL+
AL+
AL+ CLEAR
ACK
AL-
ACK
AL-
0
1
4
2 3
ACK (auto)
Alarm inactive-
active-
unacknowledged
5
ACK
AL+
AL+
AL+
Alarm inactive-
acknowledged

FIGURE 54: EVENT ALARMED ON APPEARANCE AND DISAPPEARANCE
Transition events:
AL+: alarmed event appearance
AL-: alarmed event disappearance
ACK: operator acknowledgement of the alarm
CLEAR: operator clearing of the alarm
NOTE: In that case alarmed event disappears (AL-) means that the
associated data is now in another state which is not alarmed. The time
stamp of the alarm is modified.
Transition conditions:
(auto) means Automatic clearing
Transition description:
The transition from alarm state "0" to alarm state "1" is crossed when the alarmed event
appears (AL+).
The alarm state transitions "1 1" and "2 1" are crossed when the state of the data
associated with the alarm goes from a state which is flagged to be alarmed with any gravity
level to another state which is also flagged to be alarmed with any gravity level (AL+). In this
case the active alarm stays active but the time tagging of the alarm is changed. The new
alarm time stamp corresponds to the last associated data state change. The alarm becomes
unacknowledged if not already unacknowledged.
The alarm state transitions "1 2", "3 4" and 5 3 are crossed on operator
acknowledge action. The time stamp of the alarm is unchanged.
Functional Description C264/EN FT/C30

MiCOM C264/C264C

Page 131/132

The alarm state transitions "1 3" and 1 5 are crossed when the alarmed event
disappears (AL-). The time stamp of the alarm is modified.
The alarm state transition "2 4" is crossed when the event disappears (AL-) the alarm
being configured to be activated only "on appearance of the event". The time stamp of the
alarm is modified.
The alarm state transition "2 3" is crossed when the event disappears (AL-) the alarm
being configured to be activated "on appearance and disappearance of the event". The time
stamp of the alarm is modified and the alarm will have to be acknowledged again.
The alarm state transitions "3 1", "4 1" and 5 1 are crossed when the previous
alarmed event appears again or when another state which is also flagged to be alarmed with
any gravity level appears (AL+). The alarm becomes active-unacknowledged. The time
stamp of the alarm is modified.
The alarm state transition "2 0" is crossed when the event disappears (AL-) the alarm
being configured to be activated only "on appearance of the event" and to be cleared
automatically. The alarm is suppressed from the alarm list.
The alarm state transition "3 0" is crossed on operator acknowledgement only if the alarm
associated with the event is configured as to be cleared automatically. The alarm is
suppressed from the alarm list.
The alarm state transition "4 0" is crossed on operator clearing action. The alarm is
suppressed from the alarm list.
9.2.1.2.1 Acknowledgement
Acknowledgement of an alarm can be done by two ways:
On operator request: an operator can acknowledge an existing alarm from the
front panel to signify that it has been taken into account.
Globally: at substation level it is possible to use a SPS ( named Global alarm
ack) specially dedicated to a global acknowledgement of alarms.: When this
SPS is set to the SET state all alarms present in the computer are
acknowledged. As long as this SPS remains in the SET state, any new alarm is
inserted in the alarm list with the ACKLOWLEDGED status.
9.2.1.2.2 Clearing
Whatever the clearing mode is, the clearing of an alarm is immediately taken into account:
suppression from the alarm list.
Automatic clearing
An alarm can be configured as to be cleared automatically. It means that when this alarm
reaches the appropriate state, it is cleared automatically without any operator action. The
cases of automatic clearing are:
the alarm is in the active-acknowledged state and the alarm disappears (for event
alarmed on appearance only)
the alarm is in the inactive-active-unacknowledged state and the operator
acknowledges it (for event alarmed on appearance only)
the alarm is in the inactive-unacknowledged state and the operator acknowledges it
(for event alarmed on appearance and disappearance)
This feature can be configured on a per alarm basis.
C264/EN FT/C30 Functional Description

Page 132/132

MiCOM C264/C264C

Operator request clearing
An alarm which is not configured as to be cleared automatically has to be cleared by an
explicit operator action (this action being only possible when it is in the inactive-
acknowledged state). Otherwise it remains present in the alarm list.
As for acknowledgement done by an operator, clearing of alarms by an operator can be
configured as to be printed or not printed.
A global clearing procedure, which allows to clear all inactive-acknowledged alarms in a
single operation, will be provided.
Audible alarms
An audible alarm can be associated with the unacknowledged state of an alarm. This
facility is configurable on a per alarm basis.
If an alarm is configured audible then the sound appears when the alarm is displayed.
The audible alarm is stopped when all audible alarms are acknowledged.
An audible alarm can be associated with the unacknowledged state of an alarm. This
facility is configurable on a per alarm basis.
If an alarm is configured as audible then the sound appears when the alarm is displayed.
The audible alarm is stopped when all audible alarms are acknowledged.

Hardware C264/EN HW/C30

MiCOM C264/C264C


HARDWARE
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 1/44

CONTENT
1. SCOPE OF THE DOCUMENT 3

2. HARDWARE DESCRIPTION 4
2.1 Concept 4
2.1.1 Components 4
2.1.2 Hardware Overview 5
2.2 MiCOM C264C 6
2.2.1 Hardware presentation 6
2.2.2 Modularity 7
2.2.3 I/O Capabilities 8
2.2.4 Front Back Plane FBP242 8
2.2.5 Front Panels 9
2.3 MiCOM C264 11
2.3.1 Hardware presentation 11
2.3.2 Modularity 12
2.3.3 I/O Capabilities 13
2.3.4 Front Back Plane FBP280 13
2.3.5 Front Panels 13
2.4 Coding of board address 14
2.5 Modules description 15
2.5.1 Power auxiliary supply and legacy ports board BIU241 15
2.5.2 Central Processing Unit and base communications board CPU260 17
2.5.3 Central Processing Unit and base communications board CPU270 19
2.5.4 Digital Inputs Unit DIU200 20
2.5.5 Digital Inputs Unit DIU210 21
2.5.6 Digital Outputs Unit DOU200 22
2.5.7 Circuit breaker Control Unit - CCU200 23
2.5.8 Analogue Input Unit AIU201 24
2.5.9 Analogue Input Unit AIU210 25
2.5.10 Analogue Input Unit AIU211 26
2.5.11 Transducer less Measurements Unit TMU200/TMU220 27
2.5.12 Ethernet Switch Unit SWU200/SWU202 28
2.5.13 Ethernet Redundant Switch Unit SWR202/SWR212, SWR204/SWR214 30
2.5.14 Dual Homing Ethernet Switch Unit SWD202/SWD204 36
2.5.15 Extended communication Unit ECU200 43
2.5.16 Extended communication Unit ECU201 44
2.6 Hardware tropicalisation 44

C264/EN HW/C30 Hardware

Page 2/44

MiCOM C264/C264C

BLANK PAGE
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 3/44

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264/C264C documentation binders. It describes the
product hardware which is not the commissioning chapter.
C264/EN HW/C30 Hardware

Page 4/44

MiCOM C264/C264C

2. HARDWARE DESCRIPTION
2.1 Concept
2.1.1 Components
The MiCOM C264/C264C is based on a modular and scalable architecture to support
dedicated hardware modules adapted to the plant data interfaces.
Each MiCOM C264/C264C rack can be equipped with the following modules:
BIU241: Basic Interface Unit. This board includes the auxiliary power supply
converter, the watchdog relay, 2 digital outputs/2 digital inputs for computer
redundancy and 2 insulated RS485/RS232 interface
CPU260 (also named CPU2) or CPU270 (also named CPU3) : Central Processing
Unit and communications board based on PowerPC processor
DSP200: Digital Signal Processing board is the processor board for CT VT calculation.
It is the CPU200 daughter board
FBP280: Front BackPlane : bus for 80TE case
FBP242: Front BackPlane: bus for 40TE case
DIU200: Digital Inputs Unit each with 16 digital inputs
DIU210 : Digital Inputs Unit each with 16 digital inputs with current-peak and voltages
from 24V to 220V
DIU220 : Digital Inputs Unit each with 16 digital inputs for voltages 48/60V and
110/125V
DOU200: Digital Outputs Unit each with 10 digital outputs for alarms
CCU200: Circuit breaker Control Unit each with 8 digital inputs and 4 digital outputs
AIU201: Analogue Input Unit each with 4 analogue inputs direct current or voltage
AIU210/AIU211: Analogue Input Unit each with 8 analogue inputs direct current
TMU200 (TMU220): Transducerless Measurements Unit board for direct CT/VT
measuring acquisition with 4 CT and 4 VT ( 5 VT for TMU220)
SWU20x: Ethernet SWitch Unit board with 4 electrical links and x= 0 or x=2 optical
links
SWR2xx: Ethernet SWitch board for Redundant Ethernet ring with 4 electrical links
and 2 optical links for the redundant ring.
SWD2xx: Ethernet SWitch board for Dual Homing Ethernet star, with 4 electrical links
and 2 optical links for a Dual star.
ECU200: Extended Communication Unit board to convert non insulated RS232 into
optical signal
ECU201: Extended Communication Unit board to convert non insulated RS232 into
insulated RS485 signal
GHU201 (for C264) or GHU200 (for C264C): Graphical Human machine interface
Unit: Front Panel including 17 LEDs (13 free configurable) + 7 pushbuttons (L/R,
Open, Close, etc) + LCD (resolution of 128 x 128 pixels /16 lines of 21 characters
each) and a keypad at the front plate for local MMI management
GHU211 (for C264) or GHU210 (for C264C): Front Panel including 17 LEDs (12 free
configurable) + 1 pushbutton (L/R)
GHU221 (for C264) or GHU220 (for C264C): Front Face used to connect a detachable
HMI (GHU20x or GHU21x)
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 5/44

2.1.2 Hardware Overview
C0117 ENh
FBP280
or FBP242
BIU241
(1)
Watchdog
Redundancy
Power Supply
COM 1 / COM 2
CPU260
or
CPU270
(1)
DSP 260
SWU200
(up to 1)
Ethernet
IRIG-B
OR
COM 1 / COM 2
Optical 1 / Optical 2
Electrical 1 to 4
GHU200 or GHU201
Mandatory
Optional
ECU20x
ECU20x
SWR200
(up to 1)
or
SWD200
(up to 1)
AIU201 or AIU210 or AIU211
(up to 6)
DOU200
(up to 15)
CCU200
(up to 15)
DIU200 or DIU210 or DIU220
(up to 15)
TMU200 or TMU220
Optical 1 / Optical 2
Electrical 1 to 4
RS232 or RS485 or RS422
RS232 or RS485
Electrical RJ 45 link
Optical link (CPU260) or Electrical link (CPU270)
RS232
RS485
RS422
Optical RS232
(up to 1)
10 digital outputs
4 digital outputs
8 digital inputs
16 digital inputs
N digital inputs
( N=4 for AIU201, N=8 for AIU210, AIU211)
4 current inputs
N voltage inputs
( N =4 for TMU200, N =5 for TMU220)
OR
GHU210 or GHU211
OR
GHU220 or GHU221 GHU20x or GHU21x

FIGURE 1: HARDWARE OVERVIEW
C264/EN HW/C30 Hardware

Page 6/44

MiCOM C264/C264C

2.2 MiCOM C264C
2.2.1 Hardware presentation
The MiCOM C264C mechanical rack has the following features:
Height: 4 U
Width: 40 TE
Dimensions of this rack are in the figure below:

FIGURE 2: MiCOM C264C RACK SIZE
Case properties:
Case degree of protection: IP52 in standard
Front Panel degree of protection: IP52
Metallic case
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 7/44

C264C fixation holes position:

FIGURE 3: FIXATION HOLES POSITION FOR C264C
2.2.2 Modularity
The MiCOM C264C is available in two case versions allowing flexibility and scalability in the
use of the I/O modules:

FIGURE 4: MiCOM C264C REAR PANEL OVERVIEW WITH CT/VT BOARD
C264/EN HW/C30 Hardware

Page 8/44

MiCOM C264/C264C


FIGURE 5: MiCOM C264C REAR PANEL OVERVIEW WITHOUT CT/VT BOARD
2.2.3 I/O Capabilities
Inside the Case with CT/VT, there are 4 available slots for I/O boards (DIU200, DIU210,
DIU220, AIU201, AIU210, AIU211, DOU200 or CCU200) or switch boards (SWU20x or
SWR2xx or SWD2xx).
Inside the Case without CT/VT, there are 6 available slots for I/O boards (DIU200, DIU210,
DIU220, AIU201, AIU210, AIU211, DOU200 or CCU200) or switch boards (SWU20x or
SWR2xx or SWD2xx).
2.2.4 Front Back Plane FBP242
The FBP242 board is the back plane used for the MiCOM C264C.

FIGURE 6: MiCOM C264C FBP242 BOARD
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 9/44

2.2.5 Front Panels
2.2.5.1 GHU200
The GHU200 is the front panel with LCD and LEDs used for the MiCOM C264C:
17 LEDs (13 free configurable)
7 pushbuttons (L/R, Open, Close, etc)
a keypad at the front plate for local MMI management with 5 pushbuttons
a LCD (resolution of 128 x 128 pixels /16 lines of 21 characters each)

FIGURE 7: MiCOM C264C GHU200 BOARD
2.2.5.2 GHU210
The GHU210 is the front panel with LEDs used for the MiCOM C264C:
17 LEDs (12 free configurable)
1 pushbuttons (L/R)

FIGURE 8: MiCOM C264C GHU210 BOARD
C264/EN HW/C30 Hardware

Page 10/44

MiCOM C264/C264C

2.2.5.3 GHU220
The GHU220 is the front panel used for the MiCOM C264C. This includes only a RJ11
coupler in order to connect a remote GHU20x or GHU21x.

FIGURE 9: MiCOM C264C GHU220 BOARD

Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 11/44

2.3 MiCOM C264
2.3.1 Hardware presentation
The MiCOM C264 mechanical rack has the following features:
Height: 4 U
Width: 80 TE
Dimensions of this rack are in the figure bellow:

FIGURE 10: MiCOM C264 FRONT PANEL OVERVIEW
Case properties:
Case degree of protection: IP20 in standard
Front Panel degree of protection: IP52 (for front panel with Leds or LCD)
Metallic case
C264/EN HW/C30 Hardware

Page 12/44

MiCOM C264/C264C

C264 fixation holes position:

FIGURE 11: FIXATION HOLES POSITION FOR C264
2.3.2 Modularity
The MiCOM C264 is available in two case versions allowing flexibility and scalability in the
use of the I/O modules:

FIGURE 12: MiCOM C264 REAR PANEL OVERVIEW WITH CT/VT BOARD

FIGURE 13: MiCOM C264 REAR PANEL OVERVIEW WITHOUT CT/VT BOARD
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 13/44

2.3.3 I/O Capabilities
Inside the Case with CT/VT, there are 14 available slots for I/O boards (DIU200, DIU210,
DIU220, AIU201, AIU210, AIU211, DOU200 or CCU200) or switch boards (SWU20x or
SWR2xx or SWD2xx).
Inside the Case without CT VT, there are 15 available slots for I/O boards (DIU200, DIU210,
DIU220, AIU201, AIU210, AIU211, DOU200 or CCU200) or switch boards (SWU20x or
SWR2xx or SWD2xx).
2.3.4 Front Back Plane FBP280
The FBP280 board is the back plane used for the MiCOM C264.

FIGURE 14: MiCOM C264 FBP280 BOARD
2.3.5 Front Panels
2.3.5.1 GHU201
The GHU201 is the front panel with LCD and LEDs used for the MiCOM C264:
17 LEDs (13 free configurable)
7 pushbuttons (L/R, Open, Close, etc)
a keypad at the front plate for local MMI management with 5 pushbuttons
a LCD (resolution of 128 x 128 pixels /16 lines of 21 characters each)

FIGURE 15: MiCOM C264 GHU201 BOARD
C264/EN HW/C30 Hardware

Page 14/44

MiCOM C264/C264C

2.3.5.2 GHU211
The GHU211 is the front panel with LEDs used for the MiCOM C264:
17 LEDs (12 free configurable)
1 pushbutton (L/R)

FIGURE 16: MiCOM C264 GHU211 BOARD
2.3.5.3 GHU221
The GHU221 is the front panel used for the MiCOM C264. This includes only a RJ11 coupler
in order to connect a remote GHU20x or GHU21x.

FIGURE 17: MiCOM C264 GHU221 BOARD
2.4 Coding of board address
Same rule is applicable to all I/O boards (DIU200, DIU210, DIU220, AIU201, AIU210,
AIU211, DOU200, and CCU200):
Binary coding on 4 jumpers top down (From 0 to 15)
Jumper
missing => 1
present => 0
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 15/44

Example:
C0030ENa
1
0
0
0
0
2
0
8
address = 1 address = 10

NOTE: Two boards of the same type must not have the same address
2.5 Modules description
2.5.1 Power auxiliary supply and legacy ports board BIU241
This board includes:
the auxiliary power supply converter
the watchdog relay (closed if the product is healthy)
2 outputs (Normally open contacts) and 2 inputs for redundancy
2 insulated interfaces (Port 1: RS232 or RS485, Port 2: RS232, RS422 or RS485)
The power auxiliary supply board is protected against reversal polarity;

FIGURE 18: MiCOM C264 - BIU241 BOARD
The BIU241 board provides two insulated serial links.
C264/EN HW/C30 Hardware

Page 16/44

MiCOM C264/C264C

This following figure shows how to configure the serial links.
C0033ENa

FIGURE 19: ZOOM ON BIU JUMPERS
2.5.1.1 Configurable communication Port 1 - RS232/485
The communication link characteristics are:
full duplex serial protocol
Transmission rate: 50 b/s to 56 kb/s (configurable with PACiS configurator or settable
via GHU20x)
Configuration:
The hardware jumpers arrangement is as follow.
In RS232 set the jumpers S14, S16 and between S12.1 and S12.3
In RS485 set the jumpers S13, S15 and between S12.1 and S12.2. It is possible to
end the line with a 124 resistor by setting S17. (See CO chapter to know when the
resistor has to be used).
2.5.1.2 Configurable communication Port 2 - RS232/422/485
The communication link characteristics are:
full duplex serial protocol
Transmission rate: 50 b/s to 56 kb/s (configurable with PACiS configurator or settable
via GHU20x)
Configuration:
The hardware jumpers arrangement is as follow.
In RS232 set the jumpers S5, S6, S9 and S3
In RS485 set the jumpers S7, S8, S2. It is possible to end the line with a 124 resistor
by setting S11. (See CO chapter to know when the resistor has to be used).
In RS422 set the jumpers S7, S8, S4 and S2. It is possible to end the line with a 124
resistor by setting the jumpers S10 and S11. (See CO chapter to know when the
resistor has to be used).
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 17/44

2.5.2 Central Processing Unit and base communications board CPU260
The CPU260 board is based on a PowerPC processor including the 10/100BaseT Ethernet
communication.
Optionally, this board includes the following capabilities:
One 100BaseF Ethernet port (ST connector)
Two non insulated RS232 links. The transmission rate must be the same on both links
(values from 50 to 56000 bps configurable with the configuration tool or settable via
GHU20x)
One IRIG-B input
One daughter board (DSP260) for CT/VT management
This board is interfaced with all I/O boards and the front panel.
CPU260 has the following key features:
32-bit Power PC-based microprocessor (MPC860DP or MPC860P) clocked at
80 MHz;
64 Mbytes Dynamic memory DRAM
16 Mbytes Flash memory
256 Kbytes static memory SRAM
Calendar saved

FIGURE 20: MiCOM C264 - CPU260 BOARD
C264/EN HW/C30 Hardware

Page 18/44

MiCOM C264/C264C


FIGURE 21: MiCOM C264 DSP200 DAUGHTER BOARD ON CPU260
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 19/44

2.5.3 Central Processing Unit and base communications board CPU270
The CPU270 board is based on a PowerPC processor including the 10/100BaseT Ethernet
communication.
Two 100BaseTx Ethernet port
Two non insulated RS232 links. The transmission rate must be the same on both links
(values from 50 to 56000 bps configurable with the configuration tool or settable via
GHU20x)
One IRIG-B input
One daughter board (DSP260) for CT/VT management
This board is interfaced with all I/O boards and the front panel.
CPU270 has the following key features:
64-bit Power PC-based microprocessor (MPC8270VR) clocked at 266 MHz;
256 Mbytes SDRAM
64 Mbytes Flash memory
128 Kbytes static memory SRAM
Calendar saved

FIGURE 22: MiCOM C264 - CPU270 BOARD

C264/EN HW/C30 Hardware

Page 20/44

MiCOM C264/C264C

2.5.4 Digital Inputs Unit DIU200
The Digital Input module provides 16 optically insulated digital inputs.
The capabilities of the DIU200 boards are:
16 optically insulated digital inputs
1 negative common contact for 2 inputs
Protection against reversal polarity
The digital inputs can be used for single or double status, pulse or digital
measurement input on the same module.

FIGURE 23: MiCOM C264 - DIU200 BOARD
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 21/44

2.5.5 Digital Inputs Unit DIU210
The Digital Input module provides 16 optically insulated digital inputs.
The capabilities of the DIU210 boards are:
16 optically insulated digital inputs
1 negative common contact for 2 inputs
Protection against reversal polarity
The digital inputs can be used for single or double status, pulse or digital
measurement input on the same module.
All voltages between 24V and 220V DC
From 48V to 220VDC : High current circulation inside binary contacts inputs during a
short time (to clean external contacts) : see the current peak response curve
With 24Vdc voltage, the high current consumption (>25mA) is permanent

FIGURE 24: MiCOM C264 - DIU210 BOARD
Current peak response curve:
C0159ENa
Tension (V)
C
u
r
r
e
n
t

(
m
A
)
35
30
25
20
15
10
5
0
0 50 100 150 200 250 300

C264/EN HW/C30 Hardware

Page 22/44

MiCOM C264/C264C

2.5.6 Digital Outputs Unit DOU200
The Digital Outputs Unit (DOU200) board provides 10 outputs (10 DO) using integrated
relays.
The DOU200 board capabilities are:
8 single pole relays with one normally open (NO) contact
2 single pole relays with 1 common for 2 outputs (NO/NC)
A self-monitoring device for the output control chain is provided (address check, state
monitoring)
The +5V voltage is monitored to avoid issuing inadvertent controls.
The digital outputs can be configured in single or double remote control or set point outputs
on the same module.

FIGURE 25: MiCOM C264 - DOU200 BOARD
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 23/44

2.5.7 Circuit breaker Control Unit - CCU200
The Circuit breaker Control Unit (CCU200) board provides 8 digital inputs (8 DI) and 4
double pole outputs (4 DO) using integrated relays.
The CCU200 provides 8 optically insulated digital inputs.
The digital input (DI) capabilities of the CCU200 boards are:
8 optically insulated digital inputs
1 common contact for 2 inputs
Protection against reversal polarity
The digital inputs can be configured in single or double remote signalling inputs on the same
module.
The digital output (DO) capabilities of the CCU200 boards are:
4 double pole switching relays with normally open (NO) contacts
1 common + and 1 common - contacts per 2 relays
A self-monitoring device for the output control chain is provided (address check, state
monitoring)
The +5V voltage is monitored to avoid issuing inadvertent controls.
The digital outputs can be configured in double remote signalling only.

FIGURE 26: MiCOM C264 - CCU200 BOARD
C264/EN HW/C30 Hardware

Page 24/44

MiCOM C264/C264C

2.5.8 Analogue Input Unit AIU201
The Analogue input module (AIU201) has 4 independent analogue inputs. Each AI can be
configured in voltage or current range individually between.

FIGURE 27: MiCOM C264 - AIU201 BOARD
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 25/44

2.5.9 Analogue Input Unit AIU210
The Analogue input modules AIU210 has 8 analogue inputs ( 1 negative common for 2
inputs). Each AI can be configured in the current range.

FIGURE 28: MiCOM C264 - AIU210 BOARD
C264/EN HW/C30 Hardware

Page 26/44

MiCOM C264/C264C

2.5.10 Analogue Input Unit AIU211
The Analogue input module (AIU211) has 8 isolated analogue inputs. Each AI can be
configured in the current range.

FIGURE 29: MiCOM C264 - AIU211 BOARD
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 27/44

2.5.11 Transducer less Measurements Unit TMU200/TMU220
The transducers less measurement capabilities are the following:
4 measurement Current Transformers (4 CT) inputs
Transformers have two ranges 1 and 5 amperes
for the TMU200 4 measurement Voltage Transformers (4 VT) inputs. For the TMU220
5 measurement Voltage Transformers (5 VT) inputs
AC voltage (V
N
): 57.73 V
eff
to 500 V
eff

Frequency operating range: 50 or 60 Hz 10%

FIGURE 30: MiCOM C264 TMU200 BOARD
C264/EN HW/C30 Hardware

Page 28/44

MiCOM C264/C264C

2.5.12 Ethernet Switch Unit SWU200/SWU202
The SWU200 board is an Ethernet switch with 4 electrical links.
The SWU202 board is an Ethernet switch with 4 electrical links and 2 optical links (multi-
mode).

FIGURE 31: MiCOM C264 SWU200 BOARD
Some jumpers are used to adapt the switch to your network:
N Open Closed
Factory
setting
W1 No watching port 5 Fault watching Port 5 (Fx) Open
W3 Enable more aggressive
back-off
Enable less aggressive back-off Open
W4 Max length is 1536 byte Enable enforce the max frame length for
VLAN is 1522
Open
W5 Enable half duplex back
pressure
Disable half duplex back pressure Open
W6 Continue sending frame
regardless of number of
collisions
Enable to drop frame after 16 collisions Open
W7 Enable flow control Disable flow control Closed
W8 No priority reserve Enable 6KB priority buffer reserved Closed
W9 Half duplex for port 5 (Fx) Full duplex for port 5(Fx) Closed
W10 Unlimited broadcast frames Enable 5% broadcast frame allowed Open
W11 Half duplex for port 6 (Fx) Full duplex for port 6 (Fx) Closed
W12 Enable 802.1p selected by
EEPROM
Enable 802.1p field for all port Closed
W13 Share buffers up to 512
buffers on a single port
Enable equal amount of buffers per port
(113 buffers)
Open
Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 29/44

OPEN CLOSE
W13
W4
W5
W8
W9
W11
W3
W6
W7
W10
Port 6
C0118ENa
Port 5 (optional)
Port 4
Port 3
Port 2
Port 1
W12
LED6
LED5
LED4
LED3
LED2
LED1
W1

SWU202 optical links: these 2 optical links are monitored; if one link comes down the default
is announced by the contacts (250V/5A):
Components side
1 2 3
Pin State
1 Open
2 Common
3 Close
C0119ENa
Close if default

C264/EN HW/C30 Hardware

Page 30/44

MiCOM C264/C264C

2.5.13 Ethernet Redundant Switch Unit SWR202/SWR212, SWR204/SWR214
These boards are Ethernet switches with 4 electrical links and 2 optical links for a redunded
ring.
The SWR21x switches are SNMP managed
The SWR202/SWR212 models hav a Multi-mode optical interface.
The SWR204/SWR214 models have a Single mode (mono-mode) optical interface.

FIGURE 32: MiCOM C264 SWR202 BOARD

FIGURE 33: MiCOM C264 SWR204 BOARD WITH SC CONNECTOR

Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 31/44


FIGURE 34: MiCOM C264 SWR212 BOARD
C0120ENa
J1
J5
J4
J3
J2
1 _
2 _
3 _
4 _
Fx1
L1 L2
L3 L4
L17 L18 L19 L20
L13 L14 L15 L16
Rp
Es
Rs
Ep
L9 L10 L11 L12
L5 L6 L7 L8
J6-1
J6-4
J9
J7-1
J7-7
J8-1
J8-6
S4

C264/EN HW/C30 Hardware

Page 32/44

MiCOM C264/C264C

Some jumpers are used to adapt the switch to your network:
N Open Closed
Factory
setting
S4 Open
J7-1 Board address bit 1 = 1 Board address bit 1 = 0 Close
J7-2 Board address bit 2 = 1 Board address bit 2 = 0 Close
J7-3 Board address bit 4 = 1 Board address bit 4 = 0 Close
J7-4 Board address bit 8 = 1 Board address bit 8 = 0 Close
J7-5 Board address bit 16 = 1 Board address bit 16 = 0 Close
J7-6 Board address bit 32 = 1 Board address bit 32 = 0 Close
J7-7 Board address bit 64 = 1 Board address bit 64 = 0 Close
Address of the board:
Each board on the ring has a specific address. Each address must be single and included
between 1 and 127.
The address is equal to the sum of the open bits .
At the beginning address = 0
If J7-1 = open address = address + 1 if not address = address + 0
If J7-2 = open address = address + 2 if not address = address + 0
If J7-3 = open address = address + 4 if not address = address + 0
If J7-4 = open address = address + 8 if not address = address + 0
If J7-5 = open address = address + 16 if not address = address + 0
If J7-6 = open address = address + 32 if not address = address + 0
If J7-7 = open address = address + 64 if not address = address + 0
Example:
Address = 0
J7-1 = open address = address + 1
J7-2 = open address = address + 2
J7-3 = close address = address + 0
J7-4 = open address = address + 8
J7-5 = close address = address + 0
J7-6 = close address = address + 0
J7-7 = close address = address + 0
Address = 11

OPEN CLOSE

Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 33/44

Internal LED:
Some LED are used to indicate the state of the links.
The table below indicates the function of each LED:
LED
number
FUNCTION DESCRIPTION
L1 Receive RpEs
L2 Link RpEs
L3 Receive RsEp
L4 Link RsEp
L5 Link and activity port 1 Off: no connection
Green: link
Green + blink: link + activity
L6 Link and activity port 2
L7 Link and activity port 3
L8 Link and activity port 4
L9 Speed port 1 Off : 10Mbps Green : 100Mbps
L10 Speed port 2
L11 Speed port 3
L12 Speed port 4
L13 Address board bit 0 Only the first 4 bits are visualized
L14 Address board bit 1
L15 Address board bit 2
L16 Address board bit 3
L17 Number of repeter detected on the ring bit 0 Only the first 4 bits are visualized
L18 Number of repeter detected on the ring bit 1
L19 Number of repeter detected on the ring bit 2
L20 Number of repeter detected on the ring bit 3
Fault signal output:
The optical ring is monitored. If one link comes down the default is announced by the
contacts (250V/5A):
C0121ENa
Components side Pin State
1 Default Rp-Es
2 Common
3 Default Rs-Ep
Close if default
1 2 3


C264/EN HW/C30 Hardware

Page 34/44

MiCOM C264/C264C

Switch management:
It is possible to manage the switch with the MDIO bus (J6)
C0122ENa
11
Sub D 25 male
J2
8
18
19
20
21
22
9
MDC
1
2
3
4

Ethernet cable type
Use data quality twisted pair shielded cable rated category 5 with standard RJ45 connectors.
The maximum cable length for 10/100BaseT(x) is typically 100 meters.
Ethernet Optical Fibre
The FO cables are connected to the corresponding FO elements.
On the SWR202, the connector type for the multi mode fibre is ST.
On the SWR204 (Ref 2071021 A02 up to Index B), the connector type for the single mode
fibre is ST.
On the SWR204 (Ref 2071021 A02 from Index C and upper), the connector type for the
single mode fibre is SC.
Fibre Optic budget calculations
Optical power is expressed in Watts. However, the common unit of power measure is the
dBm and defined by the following equation: Power (dBm) = 10 log Power (mW) / 1 mW.
The following example shows the calculation of the maximum range for various types of
fibres
C0123ENa
SWR200
SWR200
SWR200
SWR200
SWR200
SWR200
1
Patch
Panel
Patch
Panel

Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 35/44

Fibre type Multi mode (SWR202) Single mode (SWR204)
Wavelengh:1310nm
62,5/125 micron

9/125 micron
Power coupled into
fiber
- 19 dBm - 15 dBm
sensitivity - 31 dBm - 34 dBm
Example 1: between two repeaters
Link budget 12 dB 19 dB
Connector loss (2) 0,8 dB 0,8 dB
Safety Margin 4 dB 4 dB
Allowed link attenuation 6,4 dB 13,4 dB
Typical cable attenuation 1 dB/km 0,4 dB/km
Maximum range 6,4 km 33 km
Example 2: between two repeaters via patch panel
Link budget 12 dB 19 dB
Connector loss (6) 0,8 dB 0,8 dB
Patch loss (2) 2 dB 1 dB
Safety Margin 4 dB 4 dB
Allowed link attenuation -0,8 dB 8,2 dB
Typical cable attenuation 1 dB/km 0,4 dB/km
Maximum range 0 20 km
The values given above are only approximate ones. Always use cable and connector losses
as specified by the manufacturer.
C264/EN HW/C30 Hardware

Page 36/44

MiCOM C264/C264C

2.5.14 Dual Homing Ethernet Switch Unit SWD202/SWD204
These boards are Ethernet switches with 4 electrical links and 2 optical links for a dual
homing solution.
The SWD202 model has a multi-mode optical interface.
The SWD204 model has a single mode (mono-mode) optical interface.

FIGURE 35: MiCOM C264 SWD202 BOARD ST CONNECTOR

FIGURE 36: MiCOM C264 SWD204 BOARD WITH SC CONNECTOR

Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 37/44

J1
J5
J4
J3
J2
1 _
2 _
3 _
4 _
Fx1
L1 L2
L3 L4
L17 L18 L19 L20
L13 L14 L15 L16
R Link A
E Link A
R Link B
E Link B
L9 L10 L11 L12
L5 L6 L7 L8
J6-1
J6-4
J9
J7-1
J7-7
J8-1
J8-6
S4
C0296ENa
C264/EN HW/C30 Hardware

Page 38/44

MiCOM C264/C264C

Some jumpers are used to adapt the switch to your network:
N Open Closed
Factory
setting
S4 Open
J7-1 Board address bit 1 = 1 Board address bit 1 = 0 Close
J7-2 Board address bit 2 = 1 Board address bit 2 = 0 Close
J7-3 Board address bit 4 = 1 Board address bit 4 = 0 Close
J7-4 Board address bit 8 = 1 Board address bit 8 = 0 Close
J7-5 Board address bit 16 = 1 Board address bit 16 = 0 Close
J7-6 Board address bit 32 = 1 Board address bit 32 = 0 Close
J7-7 Board address bit 64 = 1 Board address bit 64 = 0 Close
Address of the board:
Each board on the ring has a specific address. Each address must be single and included
between 1 and 127.
The address is equal to the sum of the open bits .
At the beginning address = 0
If J7-1 = open address = address + 1 if not address = address + 0
If J7-2 = open address = address + 2 if not address = address + 0
If J7-3 = open address = address + 4 if not address = address + 0
If J7-4 = open address = address + 8 if not address = address + 0
If J7-5 = open address = address + 16 if not address = address + 0
If J7-6 = open address = address + 32 if not address = address + 0
If J7-7 = open address = address + 64 if not address = address + 0
Example:
Address = 0
J7-1 = open address = address + 1
J7-2 = open address = address + 2
J7-3 = close address = address + 0
J7-4 = open address = address + 8
J7-5 = close address = address + 0
J7-6 = close address = address + 0
J7-7 = close address = address + 0
Address = 11

OPEN CLOSE

Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 39/44

Internal LED:
Some LED are used to indicate the state of the links.
The table below indicates the function of each LED:
LED
number
FUNCTION DESCRIPTION
L1 Receive Link A
L2 Status Link A
L3 Receive Link B
L4 Status Link B
L5 Link and activity port 1 Off: no connection
Green: link
Green + blink : link + activity
L6 Link and activity port 2
L7 Link and activity port 3
L8 Link and activity port 4
L9 Speed port 1 Off: 10Mbps Green: 100Mbps
L10 Speed port 2
L11 Speed port 3
L12 Speed port 4
L13 Number of repeaters detected on the ring bit 0 Only the first 4 bits are visualized
L14 Number of repeaters detected on the ring bit 1
L15 Number of repeaters detected on the ring bit 2
L16 Number of repeaters detected on the ring bit 3
L17 Number of repeaters detected on the ring bit 4 Only the first 4 bits are visualized
L18 Number of repeaters detected on the ring bit 5
L19 Number of repeaters detected on the ring bit 6
L20 Number of repeaters detected on the ring bit 7
Fault signal output:
Dual homing links are monitored. If one link comes down the default is announced by the
contacts (250V/5A):
Components side Pin State
1 Default Link A
2 common
3 Default Link B
Close if default
1 2 3
C0297ENa

C264/EN HW/C30 Hardware

Page 40/44

MiCOM C264/C264C

Switch management:
It is possible to manage the switch with the MDIO bus (J6).
C0122ENa
11
Sub D 25 male
J2
8
18
19
20
21
22
9
MDC
1
2
3
4

Ethernet cable type
Use data quality twisted pair shielded cable rated category 5 with standard RJ45 connectors.
The maximum cable length for 10/100BaseT(x) is typically 100 meters.
Ethernet Optical Fibre
The FO cables are connected to the corresponding FO elements.
On the SWD202, the connector type for the multi mode fibre is ST.
On the SWD204 (Ref 2071355 A02 up to index Z), the connector type for the single mode
fibre is ST.
On the SWD204 (Ref 2071355 A02 from index A and upper), the connector type for the
single mode fibre is SC.
Fibre Optic budget calculations
Optical power is expressed in Watts. However, the common unit of power measure is the
dBm and defined by the following equation: Power (dBm) = 10 log Power (mW) / 1 mW.
The following example shows the calculation of the maximum range for various types of
fibres.
C0123ENa
SWR200
SWR200
SWR200
SWR200
SWR200
SWR200
1
Patch
Panel
Patch
Panel

Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 41/44

Fibre type Multi mode (SWD202) Single mode (SWD204)
Wavelengh:1310nm
62,5/125 micron

9/125 micron
Power coupled into
fiber
- 19 dBm - 15 dBm
sensitivity - 31 dBm - 34 dBm
Example 1: between two repeaters
Link budget 12 dB 19 dB
Connector loss (2) 0,8 dB 0,8 dB
Safety Margin 4 dB 4 dB
Allowed link attenuation 6,4 dB 13,4 dB
Typical cable attenuation 1 dB/km 0,4 dB/km
Maximum range 6,4 km 33 km
Example 2: between two repeaters via patch panel
Link budget 12 dB 19 dB
Connector loss (6) 0,8 dB 0,8 dB
Patch loss (2) 2 dB 1 dB
Safety Margin 4 dB 4 dB
Allowed link attenuation -0,8 dB 8,2 dB
Typical cable attenuation 1 dB/km 0,4 dB/km
Maximum range 0 20 km
The values given above are only approximate ones. Always use cable and connector losses
as specified by the manufacturer.
Connecting Dual Homing.
Between 2 Dual Homing SWD20x
Rp
Es
Rs
Ep
SWD20x
Rp
Es
Rs
Ep
SWD20x
A
LINK A
LINK B
LINK A
LINK B
C0298ENa


C264/EN HW/C30 Hardware

Page 42/44

MiCOM C264/C264C

Between more than 2 Dual Homing SWD20x
Rp
Es
Rs
Ep
SWD20x
Rp
Es
Rs
Ep
SWD20x
LINK A
LINK B
LINK A
LINK B
Rp
Es
Rs
Ep
SWD20x
LINK A
LINK B
Rp
Es
Rs
Ep
SWD20x
LINK A
LINK B
C0299ENa


Hardware C264/EN HW/C30

MiCOM C264/C264C

Page 43/44

2.5.15 Extended communication Unit ECU200
This is an additional module plugged on DB9 connector of the CPU board. This module
converts non-insulated RS232 into optical signal.
There is a jumper onto ECU200.
When the jumper is set, light is sent for the 1 level.
When the jumper is not set, light is sent for the 0 level.
For IEC870-5-103 standard, there is no jumper. Otherwise, set the jumper.

FIGURE 37: MiCOM C264 ECU200 MODULE
Optical characteristics:
Connector type: ST
Wavelength: 820 nm
Recommended Fibre cable ; 62,5/125 micron
C264/EN HW/C30 Hardware

Page 44/44

MiCOM C264/C264C

2.5.16 Extended communication Unit ECU201
This is an additional module plugged on DB9 connector of the CPU board. This module
converts non-insulated RS232 into insulated RS485/RS422.
There is a jumper onto ECU201.
RS422 conversion: Set the jumper.
RS485 conversion: no jumper.
The indication on the module is as follows:
TA (+)
TB (-)
Ground
RA (+)
RB (-)
In RS422 Mode, TA (+), TB(-), RA (+) and RA (-) are used.
In RS485 Mode, only TA (+), TB (-)- are used.

FIGURE 38: MiCOM C264 ECU201 MODULE
2.6 Hardware tropicalisation
In option, the MiCOM C264/C264C hardware is available in a tropicalised version.
In this case, each board is covered by a dedicated varnish.

Connections C264/EN CO/C30

MiCOM C264/C264C


CONNECTIONS
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 1/38

CONTENT
1. SCOPE OF THE DOCUMENT 3

2. CONNECTOR BLOCKS 4
2.1 I/O Connector Block 4
2.2 CT/VT Connector Block 5
2.3 Serial communications connections 6
2.4 Optical communications connections 7
2.5 Ethernet-based communications connections 8
3. CONNECTION OF THE PROTECTIVE CONDUCTOR (EARTH) 9
3.1 Earthing 9
3.2 Cable fitting 9
4. CONNECTION DIAGRAMS FOR EACH I/O BOARDS 12
4.1 Power auxiliary supply and legacy ports board BIU241 12
4.2 Central Processing Unit CPU260/CPU270 14
4.3 Digital Inputs module DIU200 16
4.3.1 Block diagram 16
4.3.2 Connector description 17
4.4 Digital Inputs module DIU210 18
4.4.1 Connector description 19
4.5 Digital Outputs module DOU200 20
4.5.1 Block diagram 20
4.5.2 Connector description 21
4.6 Circuit breaker Control Unit - CCU200 22
4.6.1 Block diagram 22
4.6.2 Connector description 23
4.7 Analogue Input module AIU201 24
4.7.1 Block diagram 24
4.7.2 Connector description 25
4.8 Analogue Input module AIU210/AIU211 26
4.8.1 Connector description 28
4.9 Transducerless Measurements Unit module TMU200 30
4.9.1 Block diagram 30
4.9.2 Connector description 31
4.10 Transducerless Measurements Unit module TMU220 32
4.10.1 Block diagram 32
4.10.2 Connector description 33
C264/EN CO/C30 Connections

Page 2/38

MiCOM C264/C264C

4.11 Ethernet Switch Unit - SWU200/SWU202 34
4.11.1 Ethernet connectors description 34
4.11.2 Fault signal connector description 34
4.12 Ethernet Redundant Switch Unit - SWR202/SWR212, SWR204/SWR214 35
4.12.1 Ethernet connectors description 35
4.12.2 Fault signal connector description 35
4.13 Dual Homing Ethernet Switch Unit - SWD202/SWD212, SWD204/SWD214 36
4.13.1 Ethernet connectors description 36
4.13.2 Fault signal connector description 36
4.14 Front panel 37
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 3/38

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264/C264C documentation binders. It describes the
connectors of the product IOs connectors and the connection diagrams of each I/O boards.
C264/EN CO/C30 Connections

Page 4/38

MiCOM C264/C264C

2. CONNECTOR BLOCKS
2.1 I/O Connector Block
All the I/O connection uses a standard type of connector block with a 24-way and 5.08 mm
pitch.
The I/O connector block characteristics are the following:
Parameter Value
Continuous rating 10 A
Connection method Screw M3
Cable size 1.0 - 2.5 mm
2

Connection pitch 5,08 mm
Isolation to other terminal and to earth 300 V basic insulation
Standards UL, CSA
TABLE 1: I/O CONNECTOR BLOCKS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
C0041ENa

FIGURE 1: SAMPLE OF FEMALE CONNECTOR
NOTE: The connector is fixed with 2 screws M3 located on both vertical sides
of the connector.
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 5/38

2.2 CT/VT Connector Block
MiCOM C264 uses a standard black MiDOS 28 terminal block for transformer connection.
CT connection has 2 dual terminal groups, this allows dual rated transformer (1A/5A). Each
group has shorting contact to allow disconnection of CTs without damage.
The CT/VT connector block characteristics are the following:
Parameter Value
VT connection
Continuous rating 10 A
3 second rating 30 A
30 ms rating 250 A
Connection method Screw M4
Cable size 2 off 2.5 mm
2

Isolation to other terminal and to earth 500 V basic insulation
CT connection
Continuous rating 20 A
10 second rating 150 A
1 second rating 500 A
Connection method Screw M4
Cable size 2 off 2.5 mm
2
/ 1 off 4 mm
2

Isolation to other terminal and to earth 300 V basic insulation
TABLE 2: CT/VT CONNECTOR BLOCK
C0042ENa
1
3
5
7
9
11
13
15
17
19
21
23
25
27
2
4
6
8
10
12
14
16
18
20
22
24
26
28

FIGURE 2: STANDARD MIDOS 28 CONNECTOR
NOTE: The connector is fixed to the rack with 4 Phillips screws M4; 2 are
located on the top part and 2 on the bottom part.
C264/EN CO/C30 Connections

Page 6/38

MiCOM C264/C264C

2.3 Serial communications connections
For a RS485 or RS422 serial communication interface a termination resistor has to be
connected at each extremity of the bus.
If the IEDs or remote equipment (like Control Centre, printer, etc) are located at a long
distance (>10 m for RS232, >100 m for RS422 and >1000 m for RS485) from the
communication equipment or if the cables run through a noisy area, then optical fibre
communication should be used.
For both RS422 and RS485, the cable should be terminated at each end with a 120 ohm
resistor or the resistance of the BIU board can be used.
C0043ENb
MiCOM C264
Rear panel
RS485 connector
Rx Tx Gnd
120 Ohms
(Sl ave)
Relay or IED
Rx Tx Gnd
(Slave)
Rx Tx Gnd
(Sl ave)
Rx Tx Gnd
Earthing
(
*
)
120 Ohms
Relay or IED Relay or IED
Earthing
(
*
)
only if the IEDs are in the same cubicle

FIGURE 3: EXAMPLE OF RS485 CONNECTIONS
There must be no more than two wires connected to each terminal, this ensures that a
Daisy Chain or straight line configuration is used.
C0044ENa
MiCOM C264
(Slave)
Relay or IED
(Slave)
Relay or IED
(Slave)
Relay or IED

FIGURE 4: DAISY CHAIN CONNECTION
NOTE: The Daisy Chain or straight line configuration is recommended and
the correct way to construct fieldbus.
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 7/38

MiCOM C264
(Slave)
Relay or IED
(Slave)
Relay or IED
(Slave)
Relay or IED
MiCOM C264
(Slave)
Relay or IED
(Slave)
Relay or IED
(Slave)
Relay or IED
C0045ENa
(Slave)
Relay or IED

FIGURE 5: STAR NETWORK OR NETWORK WITH TEES WRONG CONNECTIONS
NOTE: A Star or a network with Stubs (Tees) is not recommended as
reflections within the cable may result in data corruption.
Wiring recommendation for RS422:
Master (c264) Slave(IED)
TA(+) R+
TB(-) R-
RA(+) T+
RB(-) T-

2.4 Optical communications connections
WARNING ABOUT LASER RAYS:
Where fibre optic communication devices are fitted, these should not be viewed directly.
Optical power meters should be used to determine the operation or signal level of the device.
Nonobservance of this rule could possibly result in personal injury.
Signals transmitted via optical fibres are unaffected by interference. The fibres guarantee
electrical isolation between the connections.
If electrical to optical converters are used, they must have management of character idle
state capability (for when the fibre optic cable interface is "Light off").
C264/EN CO/C30 Connections

Page 8/38

MiCOM C264/C264C

2.5 Ethernet-based communications connections
The Ethernet-based communication available in the MiCOM C264 works in full duplex mode,
using either fibre optic media (ST connector) or 4 pair twisted cable.
Only the cable insulated category 5 (FTP: Foil Twisted Pair) or insulated (STP - Shielded
Twisted Pairs) with RJ45 connectors must be used.
C0046ENa
1 2 3 4 5 6 7 8

FIGURE 6: RJ45 CONNECTOR
Only pins N1, 2, 3 and 6 is used in RJ45 Ethernet 10/100BaseTX.
The norm is:
1 = white / orange
2 = orange
3 = white / green
4 = blue (non used)
5 = white / blue (non used)
6 = green
7 = white / brown (non used)
8 = brown (non used)
The RJ45 connector when seen face on, flat side on bottom, side tab on top, then pin 1 is on
the left and pin 8 on the right.
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 9/38

3. CONNECTION OF THE PROTECTIVE CONDUCTOR (EARTH)
3.1 Earthing
MiCOM C264/C264C must be connected to the earth according to product safety standard
EN60255-27:2005 clause 5.1.5 using the protective conductor (earth) terminal located on
the rear panel.
Connection of the Protective conductor (earth).
The MiCOM C264/C264C racks must be earthed, for safety reasons, by connection of the
protective conductor (earth) to the M4 threaded stud allocated as the protective conductor
terminal (PCT), marked with the symbol shown.
WARNING TO MAINTAIN THE SAFETY FEATURES OF THE EQUIPMENT
IT IS ESSENTIAL THAT THE PROTECTIVE CONDUCTOR
(EARTH) IS NOT DISTURBED WHEN CONNECTING OR
DISCONNECTING FUNCTIONAL EARTH CONDUCTORS
SUCH AS CABLE SCREENS, TO THE PCT STUD.
THE PROTECTIVE CONDUCTOR MUST BE CONNECTED FIRST, IN
SUCH A WAY THAT IT IS UNLIKELY TO BE LOOSENED OR REMOVED
DURING INSTALLATION, COMMISSIONING OR MAINTENANCE. IT IS
RECOMMENDED THAT THIS IS ACHIEVED BY USE OF AN ADDITIONAL
LOCKING NUT.
The protective conductor (earth) must be as short as possible with low resistance and
inductance. The best electrical conductivity must be maintained at all times, particularly the
contact resistance of the plated steel stud surface. The resistance between the MiCOM
C264/C264C protective conductor (earth) terminal (PCT) and the protective earth conductor
must be less than 10 m at 12 Volt, 100 Hz.
C0047ENb
Good conductor surface
Cable crimp
Copper cable
minimum section: 2.5mm

FIGURE 7: EARTHING CABLE EXAMPLE
3.2 Cable fitting
It is recommended to use cables (0.8 mm
2
) as following:
Screened multi-strand cable has to be used for digital input-output signals. For cables
within the cubicle the cable screen can be connected to the earth at both ends of the
cable. If the cable is taken beyond the system cubicle the cable screen should be
earthed at one end only to prevent current flowing in the screen due any differences in
ground potential.
Screened and twisted pair has to be used for analogue input-output signals. The
screen is connected to the earth by the end of Bay Module side.
One or two screened and twisted pairs have to be used for lower communication
signals. The screen is connected to the earth by two cable ends.
It is recommended to group cables and fit them as near as possible to an earth plane or to
an element of an earth wire-mesh.
C264/EN CO/C30 Connections

Page 10/38

MiCOM C264/C264C

First example: MiCOM C264/C264C fitted without metallic cubicle.
Functional earth
Protective
Conductor (earth)
Terminal
C0048ENd
Signal cable earth should
be connected to the
suitable functional earth
connector
Power supply cable earth
should be connected to
the suitable functional
earth connector
MiCOM C264 - Rear panel

FIGURE 8: FIRST EXAMPLE OF EARTHING ARRANGEMENT

Connections C264/EN CO/C30

MiCOM C264/C264C

Page 11/38

Second example: MiCOM C264/C264C fitted in a metallic cubicle with other devices.
other device
MiCOM Cx64 or other device
Auxiliary power
Metallic cubicle
Protective Conductor
(earth) Terminal
Functional Earth
Protective Conductor
(earth)
Earth
Power
connector
Analogue
boundary
connector
Digital
boundary
connector
Mount cables with fixings attached to the cubicle metallic surface
C0049ENd
Protective Conductor
(earth)

FIGURE 9: SECOND EXAMPLE OF CABLE FITTING
C264/EN CO/C30 Connections

Page 12/38

MiCOM C264/C264C

4. CONNECTION DIAGRAMS FOR EACH I/O BOARDS
4.1 Power auxiliary supply and legacy ports board BIU241
This board includes the auxiliary power supply converter, the watchdog relay, 2 inputs
/outputs for computer redundancy and 2 legacy ports (Ports N1 / N2).
The factory settled possibilities for the two insulated base legacy ports are:
Case Port N1 Port N2
1 RS232 RS232
2 RS232 RS485
3 RS422 RS232
4 RS422 RS485
5 RS485 RS232
6 RS485 RS485
TABLE 3: BASE LEGACY PORTS (PORTS N1 / N2) - CAPABILITIES
Connector description:
Pin n Signal
1 Redundancy relay 2 - NO contact
2 Redundancy relay - common 1-2
3 Redundancy relay 1 - NO contact
4 Watchdog relay - NO contact
5 Watchdog relay - NC contact
6 Watchdog relay - common
7 Redundancy input - 1+
8 Redundancy input - common 1 / 2
9 Redundancy input - 2+
10
11
12 RS232: RxD RS485 : B - Port 1
13 Telecom Ground - Port 1
14 RS232: TxD RS485 : A - Port 1
15 Telecom Ground - Port 2
16 RS232: CTS - Port 2
17 RS232: RxD RS485 B RS422: TB - Port 2
18 RS232: TxD RS485 A RS422: TA - Port 2
19 RS232: RTS RS422: RB - Port 2
20 RS422: RA - Port 2
21 RS232: DCD - Port 2
22 Voltage input: Gnd Gnd
23
Voltage input: AC/DC ( + )
24 Voltage input: AC/DC ( )
TABLE 4: BIU241 BOARD - CONNECTOR DESCRIPTION
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 13/38

Block diagram:
RS232/
RS485
#
SG
TXD / TA
RXD / TB
Serial
link 1
Watchdog
V aux
-
+
-
Power
supply
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
VIN
-
VIN
-
- -
+ +
DI2 DI1
RS232/
RS422
RS485
#
SG
TXD / TA
RXD / TB
Serial
link 2
DCD
RTS / RB
CTS
RA
Output relays
O 2
O 1
Power auxiliary supply BIU241/
BIU100 and legacy ports board
C0050ENe

FIGURE 10: BIU241 AND BIU100 BOARD BLOCK DIAGRAM
WARNING: FOR SAFETY REASONS, WHEN THE COMMUNICATION PORT OF
BOARDS BIU241 REFERENCED 2070879 A03-Z AND 2070879 A04-Z IS
CONNECTED TO DEVICES, IT IS MANDATORY TO EARTH SOME OF
THE "SG PIN" OF THE COMMUNICATION PORT, ACCORDING TO THE
FOLLOWING APPLICATIONS.

C264/EN CO/C30 Connections

Page 14/38

MiCOM C264/C264C

RS232:
If the C264/BIU241/Port 1 is used -> Pin No 13 (SG) is to be earthed
If the C264/BIU241/Port 2 is used - > Pin No 15 (SG) is to be earthed
RS485 / RS422 : daisy chain and equipements in the same cubicle:
If the C264/BIU241/Port 1 is used -> Pin No 13 (SG) is to be earthed
If the C264/BIU241/Port 2 is used - > Pin No 15 (SG) is to be earthed
The GND signal of the daisy chain extremity is to be earthed.
RS485 / RS422 : daisy chain and equipements in various cubicles:
If the C264/BIU241/Port 1 is used -> Pin No 13 (SG) is to be earthed
If the C264/BIU241/Port 2 is used - > Pin No 15 (SG) is to be earthed
Remark: In this case, the GND signal of the daisy chain extremity is not to be
earthed.
4.2 Central Processing Unit CPU260/CPU270
In base, this board includes the 10/100BaseT Ethernet interface (RJ45 connector).
This board includes:
The IRIG-B interface ( standard NF S 87-500, May 1987) with the following
characteristics:
interface: BNC plug
modulated amplitude, 1 kHz carrier signal
time-of-year code : BCD
Two non-insulated RS232 interfaces (DB9 male connector)
The external modules ECU200/ECU201 convert non-insulated RS232 into optical
link/insulated RS485 or RS422.
The DB9 connectors description:
1 CD
2 RX
3 TX
4 5V ( for ECU20x supply)
5 ground
6 Not used
7 RTS
8 CTS
9 Not used

Note: Unlike standardized RS232 connector, pin 4 is not normally used as
the DTR signal (Data Terminal ready). It is here permanently
connected to power supply +5 V. So this pin 4 must not be used in a
null-modem cable.

Connections C264/EN CO/C30

MiCOM C264/C264C

Page 15/38

C0152ENa
1
5
6
9
Connector DB 9
5
1
9
6

FIGURE 11: OPTIONAL LEGACY PORTS (PORTS N3 / N4) - DESCRIPTION
The ECU201 module has a 5 wires female connector.
1 TA (+)
2 TB (-)
3 Ground
4 RA (+)
5 RB (-)
TABLE 5: ECU201 - DESCRIPTION
For RS422 connection : TA(+), TB(-), RA(+), RB(-) are used. Jumper S1 must be set.
For RS485 connection: only TA(+) and TB(-), are used. Jumper S1 must not be set.
The ECU200 module has 2 optical fibre connectors (ST type):
TX: optical emitter
RX: optical receiver

C264/EN CO/C30 Connections

Page 16/38

MiCOM C264/C264C

4.3 Digital Inputs module DIU200
The Digital Input module (DIU200) provides 16 optically insulated digital inputs (with 1
common for 2DI).
4.3.1 Block diagram
C0056ENa
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Digital I nput Unit
board
DIU200
V IN
-
V IN
-
- -
+ +
DI8 DI7
V IN
-
V IN
-
- -
+ +
DI2 DI1
V IN
-
V IN
-
- -
+ +
DI4 DI3
V IN
-
V IN
-
- -
+ +
DI6 DI5
V IN
-
V IN
-
- -
+ +
DI10 DI9
V IN
-
V IN
-
- -
+ +
DI12 DI11
V IN
-
V IN
-
- -
+ +
DI14 DI13
V IN
-
V IN
-
- -
+ +
DI16 DI15
Signal inputs

FIGURE 12: DIU200 BOARD BLOCK DIAGRAM
NOTE: Different types of DIU200 boards exists depending on the input
voltage range
Before connection, a special attention is to be paid about the version
of the board:
- version A01 for 24V
DC
,
- version A02 for 48/60 V
DC
,
- version A03 for 110/125V
DC
- version A04 for 220 V
DC


Connections C264/EN CO/C30

MiCOM C264/C264C

Page 17/38

4.3.2 Connector description
The DIU200 board is equipped with a 24-way 5.08 mm pitch connector.
Pin N. Signal
1 Digital Input 1+
2 Digital Input 2+
3 Negative Common Digital Input 1 / 2
4 Digital Input 3+
5 Digital Input 4+
6 Negative Common Digital Input 3 / 4
7 Digital Input 5+
8 Digital Input 6+
9 Negative Common Digital Input 5 / 6
10 Digital Input 7+
11 Digital Input 8+
12 Negative Common Digital Input 7 / 8
13 Digital Input 9+
14 Digital Input 10+
15 Negative Common Digital Input 9 / 10
16 Digital Input 11+
17 Digital Input 12+
18 Negative Common Digital Input 11 / 12
19 Digital Input 13+
20 Digital Input 14+
21 Negative Common Digital Input 13 / 14
22 Digital Input 15+
23 Digital Input 16+
24 Negative Common Digital Input 15 / 16
TABLE 6: DIU200 BOARD - CONNECTOR DESCRIPTION
C264/EN CO/C30 Connections

Page 18/38

MiCOM C264/C264C

4.4 Digital Inputs module DIU210
The Digital Input module (DIU210) provides 16 optically insulated digital inputs split in eight
groups of two inputs. Both inputs of a group have a common pin which can be used either as
a negative common pin or a positive common pin.
Block diagram
C0056ENd
Digital Input Unit
board
DIU 210
1
PIN
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Signal inputs
DI 1 DI 2
DI 3 DI 4
DI 5 DI 6
DI 7 DI 8
DI 9 DI 10
DI 11 DI 12
DI 13 DI 14
DI 15 DI 16
VIN VIN
VIN VIN
VIN VIN
VIN VIN
VIN VIN
VIN VIN
VIN VIN
VIN VIN
com com
com com
com com
com com
com com
com com
com com
com com

FIGURE 13: DIU210 BOARD BLOCK DIAGRAM
NOTE: There is only one type of DIU210 board, including all wetting voltages
between 24 and 220V AC/DC
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 19/38

4.4.1 Connector description
The DIU210 board is equipped with a 24-way 5.08 mm pitch connector.
Pin N. Signal
1 Digital Input 1
2 Digital Input 2
3 Common Digital Input 1 / 2
4 Digital Input 3
5 Digital Input 4
6 Common Digital Input 3 / 4
7 Digital Input 5
8 Digital Input 6
9 Common Digital Input 5 / 6
10 Digital Input 7
11 Digital Input 8
12 Common Digital Input 7 / 8
13 Digital Input 9
14 Digital Input 10
15 Common Digital Input 9 / 10
16 Digital Input 11
17 Digital Input 12
18 Common Digital Input 11 / 12
19 Digital Input 13
20 Digital Input 14
21 Common Digital Input 13 / 14
22 Digital Input 15
23 Digital Input 16
24 Common Digital Input 15 / 16
TABLE 7: DIU210 BOARD - CONNECTOR DESCRIPTION
C264/EN CO/C30 Connections

Page 20/38

MiCOM C264/C264C

4.5 Digital Outputs module DOU200
The Digital Outputs Unit (DOU200) board provides 10 outputs (10 DO) using relays.
4.5.1 Block diagram
C0057ENb
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Digital Output Unit
board
DOU200
Signal outputs
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
DO 7
DO 8
DO 10
DO 9

FIGURE 14: DOU200 BOARD BLOCK DIAGRAM
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 21/38

4.5.2 Connector description
The DOU200 board is equipped with a 24-way 5.08 mm pitch connector.
Pin N. Signal
1 Digital output 1 +
2 Digital output 1 -
3 Digital output 2 +
4 Digital output 2 -
5 Digital output 3 +
6 Digital output 3 -
7 Digital output 4 +
8 Digital output 4 -
9 Digital output 5 +
10 Digital output 5 -
11 Digital output 6 +
12 Digital output 6 -
13 Digital output 7 +
14 Digital output 7 -
15 Digital output 8 +
16 Digital output 8 -
17 NC
18 NC
19 Digital output 9 NO contact
20 Digital output 9 NC contact
21 Common Digital output 9
22 Digital output 10 NO contact
23 Digital output 10 NC contact
24 Common Digital output 10
TABLE 8: DOU200 BOARD - CONNECTOR DESCRIPTION

C264/EN CO/C30 Connections

Page 22/38

MiCOM C264/C264C

4.6 Circuit breaker Control Unit - CCU200
The Circuit breaker Control Unit (CCU200) board provides 8 digital inputs (8 DI with one
common for 2DI) and 4 double pole outputs (4 DO) using integrated relays.
4.6.1 Block diagram
C0058ENa
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Circuit breaker
Control Unit
board
CCU 200
Digital Outputs
VIN
-
VIN
-
- -
+ +
DI2 DI1
VIN
-
VIN
-
- -
+ +
DI4 DI3
VIN
-
VIN
-
- -
+ +
DI6 DI5
VIN
-
VIN
-
- -
+ +
DI8 DI7
Digital Inputs
CO 2
CO 1
B
A
B
A
CO 4
CO 3
B
A
B
A

FIGURE 15: CCU200 BOARD BLOCK DIAGRAM
NOTE: Different types of CCU200 boards exist depending on the input
voltage range so before connection, a special attention is to be paid
about the version of the board:
- version A01 for 24V
DC
,
- version A02 for 48/60 V
DC
,
- version A03 for 110/125V
DC
- version A04 for 220 V
DC

Connections C264/EN CO/C30

MiCOM C264/C264C

Page 23/38

4.6.2 Connector description
The CCU200 board is equipped with a 24-way 5.08 mm pitch connector.
Pin N. Signal
1 Digital Input 1+
2 Digital Input 2+
3 Common Digital Input 1 / 2
4 Digital Input 3+
5 Digital Input 4+
6 Common Digital Input 3 / 4
7 Digital Input 5+
8 Digital Input 6+
9 Common Digital Input 5 / 6
10 Digital Input 7+
11 Digital Input 8+
12 Common Digital Input 7 / 8
13 Digital Output 1 B
14 Digital Output 1 A
15 Common Digital Output 1 - 2 A
16 Digital Output 2 A
17 Digital Output 2 B
18 Common Digital Output 1 - 2 B
19 Digital Output 3 B
20 Digital Output 3 A
21 Common Digital Output 3 4 A
22 Digital Output 4 A
23 Digital Output 4 B
24 Common Digital Output 3 - 4 B
TABLE 9: CCU200 BOARD - CONNECTOR DESCRIPTION

C264/EN CO/C30 Connections

Page 24/38

MiCOM C264/C264C

4.7 Analogue Input module AIU201
The Analogue input module (AIU201) provides 4 independent Analogue inputs (4AI).
4.7.1 Block diagram
C0059ENb
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Analogue Input Unit
board
AIU201
Signal inputs
Insulated
GND
GND
-
+
#
AI 1
U
V
-
+
#
AI 1
U
mA
Insulated
GND
GND
-
+
#
AI 2
U
V
-
+
#
AI 2
U
mA
Insulated
GND
GND
-
+
#
AI 3
U
V
-
+
#
AI 3
U
mA
Insulated
GND
GND
-
+
#
AI 4
U
V
-
+
#
AI 4
U
mA

FIGURE 16: AIU201 BOARD BLOCK DIAGRAM
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 25/38

4.7.2 Connector description
The AIU201 board is equipped with a 24-way 5.08 mm pitch connector.
Pin N. Signal
1 Analogue Input 1+ (voltage)
2 Analogue Input 1-(voltage)
3 Analogue Input 1+(current)
4 Analogue Input 1-(current)
5 Insulated Ground 1
6 Ground
7 Analogue Input 2+ (voltage)
8 Analogue Input 2-(voltage)
9 Analogue Input 2+(current)
10 Analogue Input 2-(current)
11 Insulated Ground 2
12 Ground
13 Analogue Input 3+ (voltage)
14 Analogue Input 3-(voltage)
15 Analogue Input 3+(current)
16 Analogue Input 3-(current)
17 Insulated Ground 3
18 Ground
19 Analogue Input 4+ (voltage)
20 Analogue Input 4-(voltage)
21 Analogue Input 4+(current)
22 Analogue Input 4-(current)
23 Insulated Ground 4
24 Ground
TABLE 10: AIU201 BOARD - CONNECTOR DESCRIPTION


C264/EN CO/C30 Connections

Page 26/38

MiCOM C264/C264C

4.8 Analogue Input module AIU210/AIU211
The Analogue input module AIU210 provides 8 Analogue inputs (8AI) with one common
point (-) for 2 inputs.
The Analogue input module AIU211 provides 8 Isolated Analogue inputs (8AI)
The AIU210/AIU211 boards are equipped with a 24-way 5.08 mm pitch connector.
AIU210 block diagram:
C0059ENd
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PIN
Analogue Input Unit
board
AIU210
Signal inputs
Insulated
GND
GND
-
+
#
AI 5
U
mA
-
+
#
AI 1
U
mA
mA
mA
mA
mA
mA
mA
Insulated
GND
GND
-
+
#
AI 6
U
-
+
#
AI 2
U
Insulated
GND
GND
-
+
#
AI 7
U
-
+
#
AI 3
U
Insulated
GND
GND
-
+
#
AI 8
U
-
+
#
AI 4
U

FIGURE 17: AIU210 BOARD BLOCK DIAGRAM
WARNING: WITH AIU210 IN ORDER TO ENSURE THE MEASUREMENT
CHARACTERISTICS AND PRECISION, THE EXTERNAL CURRENT
SOURCE ARE TO BE FULLY INDEPENDENT OR AS A MINIMUM, THEY
ARE TO BE WIRED TO TAKE CARE OF THE AIU210 INPUT COMMON
POINTS(-).
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 27/38

AIU211 Block diagram:
Analogue Input Unit
board
AIU 211
1
PIN
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
- mA
mA
mA
mA
mA
mA
mA
mA
Signal inputs
AI 5
AI 1
AI 6
AI 2
AI 7
AI 3
AI 8
AI 4
GND
GND
GND
GND
U
#
U
#
U
#
U
#
U
#
U
#
U
#
U
#
C0365ENa

FIGURE 18: AIU211 BOARD - BLOCK DIAGRAM
C264/EN CO/C30 Connections

Page 28/38

MiCOM C264/C264C

4.8.1 Connector description
The AIU210 board is equipped with a 24-way 5.08 mm pitch connector.
Pin N. Signal
1 Analogue Input 5+ (current)
2 Common Analogue Input 1/5
3 Analogue Input 1+(current)
4 Common Analogue Input 1/5
5 Insulated Ground 1( not wired)
6 Ground
7 Analogue Input 6+ (current)
8 Common Analogue Input 2/6
9 Analogue Input 2+(current)
10 Common Analogue Input 2/6
11 Insulated Ground 2 ( not wired)
12 Ground
13 Analogue Input 7+ (current)
14 Common Analogue Input 3/7
15 Analogue Input 3+(current)
16 Common Analogue Input 3/7
17 Insulated Ground 3 ( not wired)
18 Ground
19 Analogue Input 8+ (current)
20 Common Analogue Input 4/8
21 Analogue Input 4+(current)
22 Common Analogue Input 4/8
23 Insulated Ground 4 ( not wired)
24 Ground
TABLE 11: AIU210 BOARD - CONNECTOR DESCRIPTION
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 29/38

The AIU211 board is equipped with a 24-way 5.08 mm pitch connector.
Pin N. Signal
1 Analogue Input 5+ (current)
2 Analogue Input 5- (current)
3 Analogue Input 1+(current)
4 Analogue Input 1-(current)
5 Not Connected
6 Ground
7 Analogue Input 6+ (current)
8 Analogue Input 6- (current)
9 Analogue Input 2+(current)
10 Analogue Input 2-(current)
11 Not Connected
12 Ground
13 Analogue Input 7+ (current)
14 Analogue Input 7- (current)
15 Analogue Input 3+(current)
16 Analogue Input 3-(current)
17 Not Connected
18 Ground
19 Analogue Input 8+ (current)
20 Analogue Input 8- (current)
21 Analogue Input 4+(current)
22 Analogue Input 4-(current)
23 Not Connected
24 Ground
TABLE 12: AIU211 BOARD - CONNECTOR DESCRIPTION
C264/EN CO/C30 Connections

Page 30/38

MiCOM C264/C264C

4.9 Transducerless Measurements Unit module TMU200
The Transducerless Measurements Unit module (TMU200) provides 4 transducerless
voltage inputs (VT) and 4 transducerless current inputs (CT).
4.9.1 Block diagram
C0060ENb
Transducerless 1A
Current and Voltage
Unit board
TMU 200
Transducerless
current inputs
N2
N1
C2
C1
B2
B1
A2
A1
PIN
1
3
5
7
9
11
13
15
19
23
27
17
21
25
2
4
6
8
10
12
14
16
20
24
28
18
22
26
U2
U1
V2
V1
W2
W1
N2
N1
Transducerless
voltage inputs
Transducerless 5A
Current and Voltage
Unit board
Transducerless
current inputs
N2
N1
C2
C1
B2
B1
A2
A1
PIN
1
3
5
7
9
11
13
15
19
23
27
17
21
25
2
4
6
8
10
12
14
16
20
24
28
18
22
26
U2
U1
V2
V1
W2
W1
N2
N1
Transducerless
voltage inputs
TMU 200

FIGURE 19: CT/VT BOARD BLOCK DIAGRAM
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 31/38

4.9.2 Connector description
The TMU200 board is equipped with a standard MiDOS 28 connector (see Figure 2:
Standard MiDOS 28 connectors).
Pin N. Signal
1 Current Input 5A - N1
2 Current Input 5A N2
3 Current Input 1A N1
4 Current Input 1A N2
5 Current Input 5A C1
6 Current Input 5A C2
7 Current Input 1A C1
8 Current Input 1A C2
9 Current Input 5A B1
10 Current Input 5A B2
11 Current Input 1A B1
12 Current Input 1A B2
13 Current Input 5A A1
14 Current Input 5A A2
15 Current Input 1A A1
16 Current Input 1A A2
17 NC
18 NC
19 NC
20 NC
21 Voltage Input U1
22 Voltage Input U2
23 Voltage Input V1
24 Voltage Input V2
25 Voltage Input W1
26 Voltage Input W2
27 Voltage Input N1
28 Voltage Input N2
TABLE 13: TMU200 BOARD - CONNECTOR DESCRIPTION

C264/EN CO/C30 Connections

Page 32/38

MiCOM C264/C264C

4.10 Transducerless Measurements Unit module TMU220
The Transducerless Measurements Unit module (TMU220) provides 5 transducerless
voltage inputs (VT) and 4 transducerless current inputs (CT).
4.10.1 Block diagram
Transducerless 1A
Current and Voltage
Unit board
TMU 220
Transducerless 5A
Current and Voltage
Unit board
TMU 220
4 Transducerless
current inputs
4 Transducerless
current inputs
5 Transducerless
voltage inputs
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
PIN
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
21 22
23 24
25 26
27 28
PIN
N1
N2
C1
C2
B1
B2
A1
A2
U1
U2
V1
V2
W1
W2
N1
N2
N1
N2
C1
C2
B1
B2
A1
A2
U1
U2
V1
V2
W1
W2
N1
N2
C0060ENc
5 Transducerless
voltage inputs
X1
X2
19 20
X2
X1

FIGURE 20: CT/VT BOARD BLOCK DIAGRAM
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 33/38

4.10.2 Connector description
The TMU220 board is equipped with a standard MiDOS 28 connector (see Figure 2:
Standard MiDOS 28 connectors).
Pin N. Signal
1 Current Input 5A - N1
2 Current Input 5A N2
3 Current Input 1A N1
4 Current Input 1A N2
5 Current Input 5A C1
6 Current Input 5A C2
7 Current Input 1A C1
8 Current Input 1A C2
9 Current Input 5A B1
10 Current Input 5A B2
11 Current Input 1A B1
12 Current Input 1A B2
13 Current Input 5A A1
14 Current Input 5A A2
15 Current Input 1A A1
16 Current Input 1A A2
17 NC
18 NC
19 Voltage Input X1
20 Voltage Input X2
21 Voltage Input U1
22 Voltage Input U2
23 Voltage Input V1
24 Voltage Input V2
25 Voltage Input W1
26 Voltage Input W2
27 Voltage Input N1
28 Voltage Input N2
TABLE 14: TMU220 BOARD - CONNECTOR DESCRIPTION


C264/EN CO/C30 Connections

Page 34/38

MiCOM C264/C264C

4.11 Ethernet Switch Unit - SWU200/SWU202
The SWU200 board provides four electrical links.
The SWU202 board provides four electrical links and two optical links.
4.11.1 Ethernet connectors description
These boards are equipped with four RJ45 connectors.
The lower connector is for port 1. The upper connector is for port 4.
Pin N. Signal
1 Rx+
2 Rx-
3 Tx+
4 not used
5 not used
6 Tx-
7 not used
TABLE 15: SWU200/202 BOARD RJ45 CONNECTOR DESCRIPTION
4.11.2 Fault signal connector description
These boards are equipped with a 3 pin connector block to deliver a communication fault
signal.
Components side
1 2 3
Pin State
1 Open
2 Common
3 Close
C0119ENa
Close if default

Wiring recommendation :
Due to the proximity of the port 4 Ethernet connector, it is strongly recommended that the
Fault signal connector connections are visually checked before any hand manipulation of
the Ethernet connectors.
Particular attention is to be paid during the wiring phase, not to damage the cables isolation.

FIGURE 21: SWITCHES: PORT 4 ETHERNET AND FAULT SIGNAL CONNECTORS
Connections C264/EN CO/C30

MiCOM C264/C264C

Page 35/38

4.12 Ethernet Redundant Switch Unit - SWR202/SWR212, SWR204/SWR214
These boards are Ethernet switches with 4 electrical links and 2 optical links for a
redundancy ring.
The SWR21x switches are SNMP managed (they integrate an SNMP server) and can be
remotely accessed from SNMP client.
The SWR202/SWR212 model has a Multi-mode optical interface.
The SWR204/SWR214 model has a Single mode (mono-mode) optical interface.
4.12.1 Ethernet connectors description
These boards are equipped with four RJ45 connectors.
The upper connector is for port 1. The lower connector is for port 4.
Pin N. Signal
1 Rx+
2 Rx-
3 Tx+
4 not used
5 not used
6 Tx-
7 not used
TABLE 16: SWR2X2/2X4 BOARD RJ45 CONNECTOR DESCRIPTION
4.12.2 Fault signal connector description
These boards are equipped with a 3 pin connector block to deliver a communication fault
signal.
If one link of the optical ring comes down the default is announced by the output contacts
(max 250V/5A):
C0121ENa
Components side Pin State
1 Default Rp-Es
2 Common
3 Default Rs-Ep
Close if default
1 2 3

Wiring recommendation :
Due to the proximity of the port 4 Ethernet connector, it is strongly recommended that the
Fault signal connector connections are visually checked before any hand manipulation of
the Ethernet connectors.
Particular attention is to be paid during the wiring phase, not to damage the cables isolation.

C264/EN CO/C30 Connections

Page 36/38

MiCOM C264/C264C

4.13 Dual Homing Ethernet Switch Unit - SWD202/SWD212, SWD204/SWD214
These boards are Ethernet switches with 4 electrical links and 2 optical links for a dual
homing solution.
The SWD21x switches are SNMP managed (they integrate an SNMP server) and can be
remotely accessed from SNMP client
The SWD202/SWD212 model has a multi-mode optical interface.
The SWD204/SWD214 model has a single mode (mono-mode) optical interface.
4.13.1 Ethernet connectors description
These boards are equipped with four RJ45 connectors.
The upper connector is for port 1. The lower connector is for port 4.
Pin N. Signal
1 Rx+
2 Rx-
3 Tx+
4 not used
5 not used
6 Tx-
7 not used
TABLE 17: SWD2X2/SWD2X4 BOARD RJ45 CONNECTOR DESCRIPTION
4.13.2 Fault signal connector description
These boards are equipped with a 3 pin connector block to deliver a communication fault
signal.
If one link of the optical ring comes down the default is announced by the output contacts
(max 250V/5A):
Components side Pin State
1 Default Link A
2 common
3 Default Link B
Close if default
1 2 3
C0297ENa

Wiring recommendation :
Due to the proximity of the port 4 Ethernet connector, it is strongly recommended that the
Fault signal connector connections are visually checked before any hand manipulation of
the Ethernet connectors.
Particular attention is to be paid during the wiring phase, not to damage the cables isolation.

Connections C264/EN CO/C30

MiCOM C264/C264C

Page 37/38

4.14 Front panel
The front panel includes a RS232 interface , not galvanically isolated. This RS232 interface
is dedicated for maintenance and settings.
The properties of the serial link (DB9 female connector) for the maintenance dialogue are:
Baud rate: 19200
Data bits: 8
Parity: No
Stop bit: 1
Control Xon/Xoff
Connector description:
C0061ENa
1 2 3 4 5
6 7 8 9

FIGURE 22: FRONT PANEL CONNECTOR VIEW
Pin N. Signal
1 Data Carrier Detect (DCD) input
2 Receive Data (RxD) input
3 Transmit data (TxD) output
4 Data Terminal Ready (DTR) output
5 Signal Ground (SG) - 0V
6 Data Set Ready (DSR) input
7 Ready To Send (RTS) input
8 Clear To Send (CTS) input
9 NC
TABLE 18: FRONT PANEL - CONNECTOR DESCRIPTION

C264/EN CO/C30 Connections

Page 38/38

MiCOM C264/C264C

MiCOM C264C Front panel:
RS 232 port: This serial port
is dedicated to a PC for
Tunnelling.
C0062ENc

FIGURE 23: MiCOM C264C FRONT PANEL
Installation C264/EN IN/C30

MiCOM C264/C264C


INSTALLATION
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 1/44

CONTENT
1. SCOPE OF THE DOCUMENT 3

2. REQUIREMENT 4
2.1 MiCOM C264 4
2.2 Personal Computer 4
2.3 Communication wiring 4
3. DELIVERY RECEPTION 5
3.1 Packing inspection and opening 5
3.2 Delivery form checking 5
4. MECHANICAL MOUNTING 6
4.1 Rack mounting 6
4.2 Panel mounting 6
5. WIRING INSTALLATION 7
5.1 General wiring 7
5.2 Power supply wiring 7
5.3 I/O board wiring 7
5.4 Networks wiring 7
6. MiCOM C264 POWER UP 9

7. MiCOM C264 SOFTWARE INSTALLATION 10
7.1 Tools installation on the PC 10
7.1.1 Recommendation for the PC performances 10
7.1.2 Installation on the PC 10
7.2 Connection between the PC and C264 16
7.2.1 Without Ethernet Switch 16
7.2.2 With Ethernet Switch 16
7.3 Settings to enter 17
7.4 Input new settings 17
7.5 C264 Software installation 18
7.6 C264 Software upgrade 18
8. DOWNLOADING DATABASE 19
8.1 Database download with CMT 19
8.1.1 Loading DB under CMT 19
8.1.2 Download DB onto C264 19
C264/EN IN/C30 Installation

Page 2/44

MiCOM C264/C264C

8.2 Database download with SMT 19
8.2.1 Loading DB under SMT 19
8.2.2 Download DB onto C264 19
8.2.3 Switch to downloaded data base 19
9. AFTER COMPUTER INSTALLATION 20

10. OPTIONAL INSTALLATION 21
10.1 External master clock connection 21
10.2 Printer installation 21
11. CMT ONLINE HELP 22
11.1 INTRODUCTION 22
11.1.1 Scope 22
11.2 Pacis Computer Maintenance Tool (CMT) overview 22
11.2.1 Generalities 22
11.2.2 Launching the software 22
11.2.3 CMT main window 23
11.2.4 Operations performed by CMT buttons 27

Installation C264/EN IN/C30

MiCOM C264/C264C

Page 3/44

1. SCOPE OF THE DOCUMENT
This document is a chapter MiCOM C264 documentation binder. It describes the product
installation and start-up settings. Before any computer handling the chapter C264/EN SA
should be read carefully.
This document is split in the following parts:
Delivery reception
Mechanical fixation
I/O board wiring
Networks wiring
Power supply wiring
Power-up without I/O
Network setting
Data Base Download
This document should be used in conjunction with the C264/EN CM.
C264/EN IN/C30 Installation

Page 4/44

MiCOM C264/C264C

2. REQUIREMENT
MiCOM C264 boot setting and software installation is carried out using a Windows PC with
common utilities and serial/Ethernet link to the computer.
The PACiS CD-ROM System installation is needed to run the C264s install software on the
Host PC.
2.1 MiCOM C264
The MiCOM C264 needs at least
CPU board CPU260
Power board BIU241
Backplane FBP242 (for MiCOM C264C) or FBP280 (for MiCOM C264)
The BIU241 needs to be correctly wired to its voltage level as described in chapter C264/EN
CO (Connections). Before any operational voltage is applied the shield wiring should be
checked following rules of the AREVA T&D Safety Guide: SFTY/4L M/C11 (or later issue)
and rules of chapter C264/EN SA (Safety & Handling).
The CPU260 has default factory parameters.
NOTE: The computer needs to be installed with the software that allows
booting in flash. Installation or reinstallation of BOOTPROM software
in PROM is described in C264/EN MF Maintenance chapter, and out
of scope of this chapter.
Before starting installation the following information is required:
Computer IP address
Computer alias name
Both parameters are also defined in computer database. If parameters inside database differ
from actual setting then the UCA2 communication with other PACiS equipment will not be
possible.
2.2 Personal Computer
A Personal Computer is used for setting and download. The required Windows operating
system is WinNT or Win2000 or Windows XP SP2.
The PC hardware requirement is:
Ethernet port 10 Mb/s or 100 Mb/s
100 Mb of free space on hard disk
The PC software's needed is:
Computer package named Computer_X.YZ.exe ( X.YZ is the computer version)
2.3 Communication wiring
The link between PC and MiCOM C264 is Ethernet.
For a direct connection (without Ethernet Switch) between the PC and the MiCOM C264, a
crossed wire is required.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 5/44

3. DELIVERY RECEPTION
Delivery reception is composed of:
Packing inspection and opening
Delivery form checking
Feeling up commissioning
3.1 Packing inspection and opening
On receipt of the unit, inform the delivery agent if there is any sign of damage.
Check the box for documentation, or computer hardware option added in the delivery form
like ribbon, screws, port extension etc.
3.2 Delivery form checking
The delivery form is based on the order form issued from CORTEC. It lists computer type,
boards (with supply, serial numbers and position in the rack) and options.
Verify that the composition of the device is as ordered.
Computer is delivered with the required connectors.
C264/EN IN/C30 Installation

Page 6/44

MiCOM C264/C264C

4. MECHANICAL MOUNTING
The chapter C264/EN HW gives the size of MiCOM C264 rack, the fixation diameters and
their position.
If electric screwdriver is used the torque limitation should be set to the small diameters of the
screws.
The MiCOM C264 can be mounted in racks or panel.
4.1 Rack mounting
MiCOM C264 may be rack mounted using single tier rack frames (our part number is
FX0021 001):

These frames have been designed to have dimensions in accordance with IEC60297 and
are supplied pre-assembled ready to use.
The two horizontal rails of the rack frame have holes drilled at approximately 26mm intervals
and C264 cases are attached via their mounting flanges using M4 Taptite self-tapping
screws with captive 3 mm thick washers to ensure a good earth contact (our part number is
ZB5865250).
It is possible to install two C264C side by side on the assembly panel or one C264.
Ensure that the computers are earthed, using the screw terminal on the rear of the unit.
4.2 Panel mounting
MiCOM C264 can be flush mounted into panels using M4 Taptite self-tapping screws with
captive 3 mm thick washers to ensure a good earth contact (our part number is ZB5865250).
Alternatively tapped holes can be used if the panel has a minimum thickness of 2.5 mm.
Where several MiCOM C264 are to be mounted in a single cut-out in the panel, it is advised
that they are mechanically grouped together horizontally and/or vertically to form rigid
assemblies prior to mounting in the panel.
NOTE: It is not advised that MiCOM C264 are fastened using pop rivets as
this will not allow the device to be easily removed from the panel in the
future if repair is necessary.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 7/44

5. WIRING INSTALLATION
Wiring has to be prepared before installation. The MiCOM C264 is delivered with required
connectors for I/O boards and Ethernet switches. The wire diameters stated in chapter
C264/EN CO are mandatory. Tighten the screws in a cross pattern (e.g. top left, then bottom
right etc), take care not to over torque the screws.
5.1 General wiring
Only two wires can be screwed together on any one MiCOM connector. The AC and DC
analogues, digital signal, and communication wires should use separate shielded cable.
From a practical point of view the power supply of each computer should have a switch
(MCB, link, or fuse) to turn off the power during installation and commissioning tests.
The MiCOM C264 description sheet describes the type of board Installed on each slot (C, D
etc.) It is very important to use it to correctly plug the connectors.
Connection diagrams of the C264 are given in chapter C264/EN CO. Wires should be
connected with the connector unplugged. Each wired signal has to be tested before plugging
and fixing the connectors. The connectors have to be fixed on the C264 case with the
screws available at each extremity of the connector.
For connection of the protective (earth) conductor please refer to the section 3.1 of the
Connections chapter (C264/EN CO)
5.2 Power supply wiring
The BIU connector wiring is vital as it provides the power supply. Power voltage should be
tested and checked to BIU reference defined in chapter C264/EN HW to ensure that supply
is compliant to BIU voltage.
The power has to be switched off before plugging in the connector.
5.3 I/O board wiring
Several DIU, CCU, BIU board voltage are available for Digital Input. Check that the DIU
voltage as stated on the delivery form matches with the nominal signal input before plugging
connector to the computer.
DOU, and CCU board generate Digital Output with a defined inductive characteristic. On the
other side of the wire the inductance should be compliant. To avoid damage to the DO board
connected to inductive circuits it may be necessary to connect an anti-surge diode.
5.4 Networks wiring
Network wiring can be fibre optic or copper. Fibre optic communication is an option, and
should be ordered as such along with the required mechanical modules. There are specific
rules governing the installation of fibre optics (refer to the chapter C264/EN CO). Specific
care should be taken with the bend radius of the fibres, and the use of optical shunts is not
recommended as these can degrade the transmission path over time.
Never look into the end of a fibre optic due to the risk of causing serious damage to the eye.
Copper networks should follow class recommendation and shielding. When using Legacy
bus (with IED mounted in daisy chain) the correct resistor, at both ends only, should be fitted
(120 ohms for RS422 and RS485).
Copper Ethernet network have to stay inside a cubicle. Fibre optic has to be used between
cubicles.
C264/EN IN/C30 Installation

Page 8/44

MiCOM C264/C264C

For the use of SWR20x or SWD20x, the optical ring has to be connected as follows:

Rp
Es
Rs
Ep
SWR20x
or
SWD20x
Rp
Es
Rs
Ep
SWR20x
or
SWD20x
Rp
Es
Rs
Ep
SWR20x
or
SWD20x
C0295ENa



Installation C264/EN IN/C30

MiCOM C264/C264C

Page 9/44

6. MiCOM C264 POWER UP
The MiCOM C264 as delivered has the following installed:
Bootrom start-up software
Factory Start-up Setting
Before powering up the computer all the DI/DO board connectors should be disconnected.
Tests are described in the C264/EN CM chapter to check that the computer with its factory
settings has not suffered damage during transport.
C264/EN IN/C30 Installation

Page 10/44

MiCOM C264/C264C

7. MiCOM C264 SOFTWARE INSTALLATION
While you have inserted the PACiS CD-ROM System installation into your CD-drive you will
find the install software of the computer into the following directory:
\System\Delivery\PACiS Va.b.c\C264 VX.YZ (Va.b.c is the PACiS system version, X.YZ is
the computer version).
Install the Computer_X.YZ.exe on your PC.
It is recommended to use default installation parameters. This will install CMT (Computer
Maintenance Tool), FTP server and set the C264 application in a directory accessible by the
MiCOM C264.
Connect the MiCOM C264 and the PC on the same Ethernet switch or directly with a
crossed Ethernet wire.
7.1 Tools installation on the PC
The tools and C264 softwares are delivered on a CD-ROM, these softwares have to be
installed on a PC.
7.1.1 Recommendation for the PC performances
At least Pentium 3 or similar
At least 700MHz
Windows 2000, Windows NT or Windows XP SP2
At least 100 Mb fee space on hard disk
A CD-ROM drive
An Ethernet port
7.1.2 Installation on the PC
The software is in the C264/VX.YZ folder (X.YZ is the computer version).
Insert the CD-ROM in the CD-drive
Launch the Computer_X.YZ.exe file
During installation select parameters as detailed below:
Note: The following screenshots describe installation of release 4.33A of the
computer. Installation for later releases (4.41,) issimilar.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 11/44


Click on Next

Click on Nex

C264/EN IN/C30 Installation

Page 12/44

MiCOM C264/C264C


Select I accept the agreement and click on Next

Choose the path to install the software but it is better to keep the default parameters.
Click on Next.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 13/44


Click on Next

Click on Next
C264/EN IN/C30 Installation

Page 14/44

MiCOM C264/C264C


Click on Next

Click on Install
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 15/44


Click on Finish
C264/EN IN/C30 Installation

Page 16/44

MiCOM C264/C264C

7.2 Connection between the PC and C264
Connect the PC and the C264 via Ethernet following one of the following architecture.
7.2.1 Without Ethernet Switch
C0146ENa
PC C264
Crossed Ethernet
wire

The crossed Ethernet wire is as below:
Connector RJ-45 EIA/TIA-232
Wire colors T-568B:
1 (connected to pin 8)
2 DTR
3 TxD
4 GND
5 GND
6 RxD
7 DSR
8 (connected to pin 1)
1 ORANGE/
2 ORANGE
3 GREEN/
4 BLUE
5 BLUE/
6 GREEN
7 BROWN/
8 BROWN
C0148ENa
Wire colors T-568A:
1 GREEN/
2 GREEN
3 ORANGE/
4 BLUE
5 BLUE/
6 ORANGE
7 BROWN/
8 BROWN
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
1
8
8

7.2.2 With Ethernet Switch
C0147ENa
PC C264
Direct Ethernet
cables
Ethernet Switch

The crossed Ethernet wire is as below:
1 connected to 1, 2 connected to 2, etc
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 17/44

7.3 Settings to enter
The computer has a default factory IP address and alias, this needs to be changed to the
application specific values.
The settings to enter are:
host IP address: your maintenance laptop IP@
target name: should be the Computer name defined by SCE for its database
C264 IP address: should be the Computer IP address defined by SCE for its database
Other parameters should not be modified.
The following item describes how to modify the parameters.
7.4 Input new settings
Launch PACiS FTPD server previously installed.
There is the following icon on your PC desk:

Launch CMT software previously installed.

There is the following icon on your PC desk:
NOTE: CMT provides an online HELP. This Help is also included in the end of
this IN chapter.
Access your C264 by select Search computers button
NOTE: If there is no computer in the list, it is perhaps due to the Ethernet
interface of your PC. Go into file in the top of the window and Network
interface to choose the right interface.
Select your MiCOM C264 in the list
Go into Boot Parameters Menu
Select Network boot option
Modify:
IP on Ethernet (e) and set the Ethernet address you have chosen for the MiCOM
C264
host IP (h) and set the Ethernet address of the PC that supports CMT
target name (tn) and set a name for the MiCOM C264
Click on Set Boot Parameters button in order to send the new parameters to the
MiCOM C264.
Select Reboot Computer in order to restart the C264. It will restart with the software
installed on the PC.
C264/EN IN/C30 Installation

Page 18/44

MiCOM C264/C264C

7.5 C264 Software installation
On the CMT application:
Access your C264 by select Search computers button
Select your MiCOM C264 in the list
Go into Boot Parameters Menu
Select flash boot option
Click on Set Boot Parameters button in order to take into account the new
parameters
Click on BootInstall Menu
Choose C264_cpu2 directory
Click on Updatebootrom
Wait for the end of installation
Click on Start bootInstall
Wait for the end of installation, MiCOM C264 installation takes around 1 minute
When it is finished restart your computer by clicking on reboot computer to take into
account the new parameters and software
After the reboot the computer C264 will switch into maintenance mode. Computer is ready
for receiving the application database.
7.6 C264 Software upgrade
To upgrade a software, the sequence is quite identical with the CMT:
Access your C264 by select Search computers button
Select your MiCOM C264 in the list
Click on BootInstall Menu
Choose C264_cpu2 directory
Click on Updatebootrom
Wait for the end of installation
Click on Start bootInstall
Wait for the end of installation, MiCOM C264 installation takes around 1 minute
When it is finished restart your computer by clicking on reboot computer to take into
account the new parameters and software
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 19/44

8. DOWNLOADING DATABASE
MiCOM C264 requires a database to operate. It stores up to two databases, named current
and stand-by. Only the current database is used for operation. The second database can
be downloaded when the computer is in operational or maintenance mode. A specific control
allows switching between the two stored databases.
PACiS SCE ( System Configuration Editor) is used to generate the databases. SMT (System
Management Tool) or CMT (Computer Maintenance Tool) are used to download and switch
the databases.
The use of SMT or CMT depends on the number of computers. For several computers on
the same Ethernet network, it is recommended to use SMT in order to insure database
coherency between computers.
8.1 Database download with CMT
8.1.1 Loading DB under CMT
First action is to copy the .zip database issued from SCE on your PC.
8.1.2 Download DB onto C264
On the CMT application:
Access your C264 by select Search computers button
Select your MiCOM C264 in the list
Go into Key and DB Menu
click on Select a Data Base version button, choose the bd.x.xx.zip file
corresponding to the database you want to use and click on OK
Click on Download Data Base button, choose the .adb file of your computer and
click on OK
When it is done, click on Switch Data Bases button, the MiCOM C264 computer
will restart on the database you have downloaded
8.2 Database download with SMT
8.2.1 Loading DB under SMT
First action under SMT is to load the DB version. The DB is then stored on the hard disk and
prepared for communication (with communication setting).
The DB will appear in the database list, a right click allows to set current the DB, then to
send a connect all. SMT should then be communicating with the computer, if not
communication wiring and settings should be checked.
8.2.2 Download DB onto C264
Still using right buttons chose the download all option and wait for the acknowledgement of
a successful transfer.
8.2.3 Switch to downloaded data base
If no database has previously been installed then the database is automatically set to be the
running database. If there is a database already installed then the downloaded database will
become the standby database, in which case the new database will have to be switched to
make it the running database. In both cases it is necessary to reboot the computer to put the
database into running mode.
C264/EN IN/C30 Installation

Page 20/44

MiCOM C264/C264C

9. AFTER COMPUTER INSTALLATION
Installation is now complete.
In the event of any problems refer to the chapter C264/EN MF Maintenance and faultfinding.

Installation C264/EN IN/C30

MiCOM C264/C264C

Page 21/44

10. OPTIONAL INSTALLATION
Optional hardware modules are:
IRIG B connection
Printer
10.1 External master clock connection
With the option of the CPU board, an external standard BNC connection is used to receive
external master clock synchronisation. The recommended external master clock is the hopf
6870 radio clock.
Installation should follow the standard rules of BNC cable installation including length limit
and optional 50 ohms termination.
For installation of the external master clock, refer to its documentation and to the summary in
PACiS system/EN IN chapter.
External IRIG B synchronisation should be configured in the computer database.
10.2 Printer installation
A printer can be installed permanently for the SOE, or temporally for
commissioning/maintenance use. Data labelling is defined with PACiS SCE.
The printer should be connected to either port 1,2,3 or port 4 of the computer.
If the port is on the BIU board, the board has to be configured for RS232 by using the correct
jumper configuration.
Furthermore, a configuration file (included in database) has to be installed onto the computer
with the printer communication parameters.
C264/EN IN/C30 Installation

Page 22/44

MiCOM C264/C264C

11. CMT ONLINE HELP
11.1 INTRODUCTION
11.1.1 Scope
This document is an operating manual and describes how to use the Pacis Computer
Maintenance Tool.
Each section explains a particular operation made with the CMT.
11.2 Pacis Computer Maintenance Tool (CMT) overview
11.2.1 Generalities
The CMT provides a friendly way to maintain MICOM Cx6x computers.
Typing commands in the computer shell is not required; the graphical interface does main
operations.
CMT is running on Personal Computers (PC) using Windows 98, NT and 2000.
Moreover, a serial link between the operator PC and the computers is not needed: all the
operations are performed using the local Ethernet network. CMT uses raw Ethernet packet,
in direct Mac addressing mode.
11.2.2 Launching the software
CMT is shipped with the default installation of the MiCOM COMPUTER software.
The CMT is usually found in C:\Program Files\Areva\PACiS\Computer\Cmt, or by clicking on
the "Start menu"/ Program/Areva /Pacis /Computer/Cmt.
When the software is launched, it shows a starting view during 3 seconds.


Installation C264/EN IN/C30

MiCOM C264/C264C

Page 23/44

11.2.3 CMT main window
This window is divided in four sections.
A menu, a "computer" part at the top right, an "operation" section with buttons at the left, and
the most important part, at the center, containing the output of the chosen operations.

11.2.3.1 The menu: File, Tools, and Help
11.2.3.1.1 File menu
File menu contains two submenus: Network Interface and Quit.
Network interface submenu ( F2 )

It selects the Networks Interface board used by the PC to access computer Network.
A chooses window opens and proposes Network interface board existing on your PC.
Select the board you want to use and click OK, or close the window using Windows close
mechanism
For a PC with only one Ethernet board the right board is automatically selected
example:
MS TCP Loop back interface : (not useable by CMT)
3Com 3C90x Ethernet Adapter:
3Com Ether Link PCI:
AT-2500 NDIS Series 4.0 driver:
NdisWan Adapter : (not useable by CMT)
The selection is saved in Registry
Quit submenu (CTRL + q)
It's used to exit the software
C264/EN IN/C30 Installation

Page 24/44

MiCOM C264/C264C

11.2.3.1.2 Tools menu
Tools menu contains two submenus: Language and Background color.
Language submenu
Its proposing you to choose the language used by CMT. The default language is English,
submenu English ( F3 ) alternate language is French ( F4 ).
The selected language is saved in Registry.
Background colour
It proposes you to choose the background colour used by CMT windows. The default colour
is Grey
Background colour pops up a panel of the 256 colours you can use and lets you pick one of
them. This colour will be the new default background colour. It's better to choose a colour in
the middle of a line.

The selected colour is saved in Registry.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 25/44

11.2.3.1.3 Help menu
File menu contains two submenus :Index and About.
Index submenu ( F1)
Displays the CMT help file, this file .
About submenu ( F5)
Displays a "about" box : CMT's version and copyrights.

11.2.3.2 The "Search computers" button
It is used to search for computers on the current Local Area Network (LAN).
When pressed, application starts the search, and wait answers for 3 seconds.
After this delay, a list of all the "responding" computers is displayed, with their name, IP
address, Type and serial number.
C264/EN IN/C30 Installation

Page 26/44

MiCOM C264/C264C


Just click left on a computer to select it.
Each button is colored representing computer internal state :
application software running or normal : green
application software stopped : blue
Bootprom : red
The selected computer name, IP address, Type and serial number is shown in the top right
white box "Selected Computer:".

Each window can show 20 buttons, clicking the tab ( Next...) makes the next 20 computers
visible. A maximum of one hundred computers is possible.
11.2.3.3 The "Computer's list" button
The list of all the "responding" computers is displayed, with their name, IP address, Type and
serial number, without searching on network.
11.2.3.4 The left bar
It contains all the operations that can be performed on the selected computer:
Simply click on a button to launch the desired task.
Each operation is described in the next section of this manual.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 27/44

11.2.4 Operations performed by CMT buttons
11.2.4.1 Computer version
The output window software and database information from Cx6x computer:
Version
Database compatibility
UCA2 agency version
Isagraf software version
Triangle software version
creation date of the application software
Information on the running database is also given ( if a database is running ...):
device name
device type
model
company
description
substation
database name
version
path of the database.
database creation date and last setting date
Information on the computer state:
ACTIVE or MAINTENANCE or INITIALIZATION or SIMULATION or STANDBY or
FAULTY or HALTED or STOPPED
11.2.4.2 Boot Parameter
"Boot Parameters" button shows current computer boot parameters.
Modifications of the values can be done for all the fields displayed in white box ("inet on
Ethernet", "host inet" and "target name").
The radio buttons "Network boot" and "Flash boot" and "Bootprom boot". These three
buttons automatically change the required fields in the boot line to make the computer boot
using FTP (Network ) or using its flash memory (Flash ) or stopped after boot (Bootprom ).

The normal mode is "Flash boot"
Ethernet Interface Type can be selected and saved in computer flash using the white choose
box "Ethernet interface".
possible selection :
[Composant FrontPage Enregistreur de rsultats]

RJ45 auto detect is the default mode : auto negotiation between the computer and switch
"Get Boot parameters" button gets information reading computer flash memory.
C264/EN IN/C30 Installation

Page 28/44

MiCOM C264/C264C

Once the modifications are finished, the "Set boot Parameters" button has to be pressed in
order to apply the changes on the computer.
Modifications are saved in the flash memory of The CX6X
Modifications will be used only after the next reboot.
11.2.4.3 Key and Data base Management
"Key and DB" button shows the key and data base window management.
11.2.4.3.1 Key Management
Computer software utilization is limited by a software key mechanism.
Each computer is associated with a permission key. This window allows user to read "Get
computer key" or to update "Set computer key" the computer with a new key.
Keys are unique and associated to the computer Ethernet address.

Authorized functions are marked with a black radio button.
11.2.4.3.2 Data base Management

The data base part of the window is used to manage computer data base.
"Data base 1" shows the first data base version revision and its state "CURRENT" or
"STANDBY"
"Data base 2" shows the second data base version revision and its state "CURRENT" or
"STANDBY"
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 29/44

"Clean all DB" removes the first and the second data base.
"Switch data bases" switches the two data bases from "CURRENT" becomes
"STANDBY" and "STANDBY" becomes "CURRENT".
"Select a Data base version" with this button user can select a versioned system data base ,
generated by "System configurator" (S.C.E ).selecting this button opens a new window, type
file chooser, and user can select a "*.x.yy.zip" file.

Once the file "*.x.yy.zip" selected, the file is unzipped and his version revision x.yy is
memorized for the future download operation: "New DB version".
"My Computer" button gives access to the file system of your PC.

C264/EN IN/C30 Installation

Page 30/44

MiCOM C264/C264C


Once a data base version is selected user can download the "*.adb" file to computer using
"Download data base".
A file chooser window opens and proposes the "*.adb" files compressed in the "*.x.yy.zip" file
and unzipped by using "Select a Data base version".

Clicking on "OK" will start download database process to computer.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 31/44

11.2.4.4 Data and Time
This section reads or changes date and time information from or to computer
11.2.4.4.1 Computer use
This section reads memorized data on computer :
"first running date" of the computer: The value stored in "/flash/MAINT/firstrd" is directly
displayed here.
"Computer use "the number of hours the computer has been running. This value is read in
"/flash/MAINT/ophours".

11.2.4.4.2 Get computer date
This section reads time on computer ( local time).

11.2.4.4.3 Set date
This section selects a time and date value from PC and sends it to computer.
"Set date" is used to modify the computer date and time. The current date and time are
taken from Windows on the operator PC and displayed. They can be changed if needed. The
"OK" button is used to confirm the changes and to update the settings on the computer.

Clicking "OK" sends time to computer, if the new time is accepted or not, this confirmation
window will open.


C264/EN IN/C30 Installation

Page 32/44

MiCOM C264/C264C

11.2.4.4.4 Set year
This section selects a year value from PC and sends it to computer.
"Set year" acts like "Set date" but only the year is changed. Its useful to set year on a new
computer because IRIG B does not contain the year information. The default value is taken
from Windows and can be changed. "OK" set the value on the computer.

Clicking "OK" sends time to computer, if the new year is accepted or not, this confirmation
window will open.

11.2.4.4.5 IRIG-B
This section reads IRIG B information from computer.
If IRIG-B interface is present on the CPU board :

If IRIG-B interface is not present on CPU :

Installation C264/EN IN/C30

MiCOM C264/C264C

Page 33/44

11.2.4.4.6 Synchronism
This section reads synchronism information from computer.

11.2.4.5 Errors
The content of "/flash/systrap/index.txt" is displayed. It shows the number of errors since the
initialization of the index, the date and time of the last error and the name of the file
containing information on this error.

This file (containing the last systrap) is pre-selected in the "File to display" choose box.
On a CX6X the last tenth error files are archived, you can select one of this file using "File to
display" choose box
Once a file is selected you visualize it, clicking :
"Open" shows the file on the output window.
C264/EN IN/C30 Installation

Page 34/44

MiCOM C264/C264C


"Print" sends the file to the Windows printer.

"Save as ..." save the file on the PC disk. It opens a new file chooser window.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 35/44


Note that the file filename refers to the file "/flash/SYSTRAP/STxx.TXT" on the computer.
C264/EN IN/C30 Installation

Page 36/44

MiCOM C264/C264C

11.2.4.6 File Explorer
This section is designed like many FTP clients or files explorer.
The left part is an image of the local PC file system, the right one an image of the computer
file system.

11.2.4.6.1 Local PC Side ( Left )
On the PC-side , the default current directory is the latest selected directory ( value saved in
Registry )
Directories are displayed with a bold font. They can be browsed by simple click. The
content of the browser is automatically updated to reflect the new directory files or
subdirectories.
Files are shown with a normal font. To select a file, just simple click on it ( dark blue
background indicates the selection).
The top box "Change disk" list all the drives of the PC used as root for the browser.
A grey box shows the current path or selected file ( bold).
11.2.4.6.2 Remote Computer Side ( Right )
On the right size, you first have to choose the root of the computer file system. /RAMDEV (
ramdisk ) and /flash ( flash memory ) are available. click on the "Change root" box.
a simple click on a directory shows its content and simple click on a file selects it ( dark
blue background indicates the selection).
For each file, its size and modification date is also displayed.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 37/44

11.2.4.6.3 Download ( Left to Right Arrow )
To begin a transfer, use the two arrows between the two browsers:
The "Left to Right Arrow" download the file selected on the PC browser in the directory
selected on the computer.
Name is not changed, only files with DOS name format ( 8 . 3 character format ) can be
copied .Files is automatically overwritten on the computer if it's already exist.
The progress-meter shows the advancement of the transfer in yellow, write time on flash
memory is represented by a full red progress-meter
11.2.4.6.4 Upload ( Right to Left Arrow )
The "Right to Left Arrow" uploads a file. The file selected on the computer is uploaded on the
PC, in the current directory.
Name is not changed. Files is automatically overwritten on the computer if it's already exist.
The progress-meter shows the advancement of the transfer in yellow.
11.2.4.6.5 Delete
The "Delete" button delete the selected file on the computer file system.
A confirmation window opens showing the full path of the file to be deleted and user can
confirm or cancel.

11.2.4.6.6 Format
The "Format" button erases and reformats the computer file system , all files are deleted.
This button is only useable wile computer is stopped or on boot mode.

A confirmation window opens and user has to confirm or cancel his click.

C264/EN IN/C30 Installation

Page 38/44

MiCOM C264/C264C

11.2.4.7 BootInstall
This function is equivalent to the BootInstall command, launched from a shell. It's
downloaded automatically a set of files mandatory for a Cx6x computer application.

The set of file is selected automatically by the user (u ) name of the boot info windows
( c264_cpu0, c264_cpu1, c264_cpu2, c364)
The left part is an image of the local PC file system.
11.2.4.7.1 Local PC Side ( Left )
On the PC-side , the default current directory is the latest selected directory ( value saved in
Registry )
Directories are displayed with a bold font. They can be browsed by simple clicks. The
content of the browser is automatically updated to reflect the new directory files or
subdirectories.
Files are shown with a normal font. To select a file, just simple clicks on it ( dark blue
background indicates the selection).
The top box "Change disk" list all the drives of the PC used as root for the browser.
A grey box show the current path ( bold). If a file is selected, only the path is used, the
filename is ignored.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 39/44

11.2.4.7.2 Start BootInstall
If the computer is not in the mode : STOPPED or BOOT

After a confirmation window , the BootInstall begins.

The upper progress-meter, shows the advancement file by file ( yellow for the transfer and
red for write ).
The lower progress-meter, shows the advancement of the global process (yellow).
the "Start BootInstall" button is deleted after each used , you have to re-click on "BootInstall"
button and reselect a directory.
11.2.4.7.3 Abort BootInstall
The "Abort BootInstall" button can stop the file transfer process. Click is memorized and stop
the download after a full file transfer, it can't stop inside a file transfer. No confirmation is
needed.
11.2.4.7.4 Update bootrom
The "Update bootrom" button is used to update the bootrom part of the computer flash (
software executed after a restart) . Computer must be in stop mode to allow this function.

First user must select a directory witch contains "bootrom.flh" file. A confirmation is
requested.
C264/EN IN/C30 Installation

Page 40/44

MiCOM C264/C264C



The file is downloaded first to computer /RAMDEV/bootrom.flh and after copied in flash.
Be sure of your choice, if a bad file is selected the computer will not reboot at next
restart.
11.2.4.8 Telnet
This button launches the default Windows Telnet client on the operator PC. Telnet is
connected to the selected computer.

It can be used to easily get a shell on the computer, in order to perform tasks that CMT can't
handle.
the "logout" command or the Windows close can be use to terminate the session.
As Telnet is launched independently of CMT, multi sessions on two or more computers are
possible.
Telnet used TCP/IP stack and the computer have to be accessible from the PC in this
mode ...
11.2.4.9 Event log storage
This section reads or changes event log storage and printer configuration from or to
computer.
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 41/44

11.2.4.9.1 Event log storage management

Function Information
"Function information" gives information about event log storage mechanism.
Enable/Disable event log storage
"Disable event log storage" (default state) disables event log storage mechanism. The state
is updated in function information window.

"Enable event log storage" (default state) enables event log storage mechanism. The state is
updated in function information window.

Get stored event log
"Get stored event log" reads event log saved in computer flash memory, transfers it in a
"temporary" file : c:\Temp\ArchX.lst

and opens a "notepad" window.
C264/EN IN/C30 Installation

Page 42/44

MiCOM C264/C264C


The file can be edited, printed, saved like a regular PC file.
11.2.4.9.2 Printer management
Get Printer Parameter
"Get Printer Parameter" reads printer configuration.

Device can be one of :
"no printer"
"Frontal RS232" : subd 9 points on front panel ( setting or shell connector )
"/Scc1/tty" : port 1 on BIU
"/Scc2/tty" : port 2 on BIU
"/Scc3/tty" : port 3 on Cpu260 board ( rear side)
"/Scc4/tty" : port 4 on Cpu260 board ( rear side)
Installation C264/EN IN/C30

MiCOM C264/C264C

Page 43/44

Control can be one of:
"0 (none)" no control
"1 (Xon/Xoff)" software control
"2 (Hard)" hardware control
"3 (Both)" software and hardware control
Printer mode
"printer mode" changes printer mode from NORMAL ( prints events marked as printable in
configuration) to OFF ( don't print any events even if printable in configuration ) or DEBUG
(print all events even if they are not marked printable in configuration).

Event log mode
"Event log mode" changes event log mode from NORMAL ( saves events marked as "log"
in configuration) to DEBUG (saves all the events even if they are not marked "log" in
configuration).

11.2.4.10 Stop Computer
This operation stops the selected computer application software, It suspends alls tasks
except "SYNCHRO" and "SUPERV". A confirmation is needed.

11.2.4.11 Reboot Computer
This operation reboots the selected computer. A confirmation is needed.

C264/EN IN/C30 Installation

Page 44/44

MiCOM C264/C264C

BLANK PAGE
Settings C264/EN ST/C30

MiCOM C264/C264C


SETTINGS
Settings C264/EN ST/C30

MiCOM C264/C264C

Page 1/10

CONTENT
1. SCOPE OF THE DOCUMENT 3
1.1 Tree Panel Navigation 3
1.2 Tree Panel Parameters 4

C264/EN ST/C30 Settings

Page 2/10

MiCOM C264/C264C

BLANK PAGE
Settings C264/EN ST/C30

MiCOM C264/C264C

Page 3/10

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264 documentation binders. It describes the Settings
-or on-line- parameters, which can be modified in runtime on MiCOM C264 computers. The
setting is done through the LCD Local Control Display. It is only available with a GHU200 or
a GHU201 front face.
This chapter details settings mentioned in C264/EN HI (Human Interface) part with default
and range values.
1.1 Tree Panel Navigation
Tree panel is accessible from bay panels by selecting the following key:
All data points are grouped into features and folders. To access a given feature the operator
should navigate the panels using the arrow keys. The folders hierarchy is displayed in each
panel.
switches to neighbouring folder
switches to neighbouring folder
select and expand the folder switching to its first item
go up to father folder
At the bottom of the hierarchy, the folder is the single point of information, control or
parameter. Edit mode allows the operator to change values.
Enter into Edit mode. It then asks to enter the level 2 password.
Cancel edition and the data point modification
The most commonly used settings and controls are selected into a list. To browse the list the
operator navigates using the arrow keys. The modification/control sequence is cancelled by
. The selection is confirmed by .

C264/EN ST/C30 Settings

Page 4/10

MiCOM C264/C264C

1.2 Tree Panel Parameters
MENU TREE
Available Values
Or
[min;max](step)(unit)
Parameter
signification
COMMAND
MAIN

- RESET OP HOURS RESET To reset the number of
the C264 operating
hours.
- CHANGE MODE OP OPERAT, MAINT, TEST To change the C264
mode into active,
maintenance or test
mode.
- GLB ACK ALARM ACK To acknowledge all
C264 alarms
- GLB CLR ALARM CLEAR To clear all
acknowledged and
reset alarms
- DATE DATE To change the date.
Accepted if the C264 is
not synchronised
- TIME TIME To change the time.
Accepted if the C264 is
not synchronised. The
time format is hh : mn :
sec.
- DB SWITCH YES To switchover active
and standby
databases.
- LANGUAGE LG1, LG2 To switchover
Language1 and
language2.
COUNTER
Counter 1

Counter N

- COUNTER value Counter value To change the counter
value.
CONFIG
COMPUTER

MAIN
- IP ADDRESS xxx.xxx.xxx.xxx To read the C264 IP
address
BAY
Bay 0

Bay N
INTERNAL S/C

- S/C associated Dev XXXX To read the name of
the device associated
to the synchrocheck
Settings C264/EN ST/C30

MiCOM C264/C264C

Page 5/10

MENU TREE
Available Values
Or
[min;max](step)(unit)
Parameter
signification
- THRES PRES LINE [0.5;1.1](0.01)(V) Multiplier of nominal
voltage above which
the line is LIVE.
- THRES ABS LINE [0.1;0.6](0.01)(V) Multiplier of nominal
voltage below which
the line is DEAD.
- THRES PRES BUS [0.5;1.1](0.01)(V) Multiplier of nominal
voltage above which
the bus is LIVE.
- THRES ABS BUS [0.1;0.6](0.01)(V) Multiplier of nominal
voltage below which
the bus is DEAD.
- DELTA VOLT LOCK [0.02;0.5](0.01)(V) Voltage difference
between bus and line
above which locking
close is not possible.
- DELTA FREQ LOCK [0;1](0.01)(hz) Frequency difference
between bus and line
above which locking
close is not possible.
- DELTA PHASE LOCK [0;30](1)(deg) Phase difference
between bus and line
above which locking
close is not possible.
- FMIN LOCK [45;65](0.01)(hz) Minimum acceptable
frequency for locking
close.
- FMAX LOCK [45;65](0.01)(hz) Maximum acceptable
frequency for locking
close.
- DELTA VOLT COUPL [0.02;0.5](0.01)(V) Voltage difference
between bus and line
above which coupling
close is not possible.
- DELTA FREQ COUPL [0;1](0.01)(hz) Frequency difference
between bus and line
above which coupling
close is not possible.
- DELTA PHASE COUPL [0;30](1)(deg) Phase difference
between bus and line
above which coupling
close is not possible.
- FMIN COUPL [45;65](0.01)(hz) Minimum acceptable
frequency for coupling
close.
- FMAX COUPL [45;65](0.01)(hz) Maximum acceptable
frequency for coupling
close.
C264/EN ST/C30 Settings

Page 6/10

MiCOM C264/C264C

MENU TREE
Available Values
Or
[min;max](step)(unit)
Parameter
signification
- REAC TIME [0; 1000](10)(ms) Circuit breaker close
time in order to
anticipate the close
order for the coupling.
- ABS V CONF TIME [200;10000](20)(ms) Time after which the
line and the bus are
considered dead.
- ONLY V CONF TIME [200;10000](20)(ms) Time after which only
one voltage among the
line or the bus is
considered live.
- PRES V CONF TIME [200;10000](20)(ms) Time after which the
line and the bus are
considered live.
- CLOSE TO MAN SYN [200;10000](20)(ms) Time waited for having
locking conditions.
- CLOSE TO MAN SY C [1; 3600](20)(s) Time waited for having
coupling conditions.
- CLOSE TO MANUAL [200;10000](20)(ms) Time waited for having
dead-dead or dead-live
conditions.
- CLOSE TO AUTO [200;10000](20)(ms) Time waited for closing
conditions in case of
auto-recloser control.
- MAN SYN CLO COUPL YES, NO Flag to permit or not
the coupling for a
close with
synchrccheck
operator control.
- MAN SYN CLO LCK YES, NO Flag to permit or not
the locking for a close
with synchrccheck
operator control.
- MAN SYN CLO LDBL YES, NO Flag to permit or not a
control with a dead line
and a live bus for a
close with
synchrccheck
operator control.
- MAN SYN CLO LLBD YES, NO Flag to permit or not a
control with a live line
and a dead bus for a
close with
synchrccheck
operator control.
- MAN SYN CLO LDBD YES, NO Flag to permit or not a
control with a dead line
and a dead bus. for a
close with
synchrccheck
operator control.
Settings C264/EN ST/C30

MiCOM C264/C264C

Page 7/10

MENU TREE
Available Values
Or
[min;max](step)(unit)
Parameter
signification
- MAN CLO LCK YES, NO Flag to permit or not
the locking for a
normal close operator
control.
- MAN CLO LDBL YES, NO Flag to permit or not a
control with a dead line
and a live bus for a
normal close operator
control.
- MAN CLO LLBD YES, NO Flag to permit or not a
control with a live line
and a dead bus for a
normal close operator
control.
- MAN CLO LDBD YES, NO Flag to permit or not a
control with a dead line
and a dead bus. for a
normal close operator
control.
- AUTO CLO LCK YES, NO Flag to permit or not
the locking in case of
auto-recloser control.
- AUTO CLO LDBL YES, NO Flag to permit or not a
control with a dead line
and a live bus in case
of auto-recloser
control.
- AUTO CLO LLBD YES, NO Flag to permit or not a
control with a live line
and a dead bus in case
of auto-recloser
control.
- AUTO CLO LDBD YES, NO Flag to permit or not a
control with a dead line
and a dead bus. in
case of auto-recloser
control.
AR
Circuit breaker name

- FIRST CYCLE MONO [100;5000](10)(ms) Time between the first
protection trip and the
Circuit Breaker close
order for a 1 phase
trip.
- FIRST CYCLE TRI [100;60000](10)(ms) Time between the first
protection trip and the
Circuit Breaker close
order for a 3 phases
trip.
C264/EN ST/C30 Settings

Page 8/10

MiCOM C264/C264C

MENU TREE
Available Values
Or
[min;max](step)(unit)
Parameter
signification
- SECOND CYCLE [1000;3600000](1000)(ms) Time between the
second protection trip
and the Circuit Breaker
close order.
- THIRD CYCLE [1000;3600000](1000)(ms) Time between the third
protection trip and the
Circuit Breaker close
order.
- FOURTH CYCLE [1000;3600000](1000)(ms) Time between the
fourth protection trip
and the Circuit Breaker
close order.
- RECLAIM TIME [1000;600000](1000)(ms) Time during which the
Circuit Breaker must
remain closed to
consider that the
reclose has
succeeded.
- UNLOCK TIME [1000;600000](1000)(ms) Time during which the
Circuit Breaker must
remain closed after a
manual close or reinit
message in the lock
state to consider that
the unlocked has
succeeded
- MAN CLOSE TIME [1000;600000](1000)(ms) Time during which the
Circuit Breaker must
remain closed after a
manual close in clear
state to consider that
the closure has
succeeded and to
avoid locking
definitively in case of
trip.
- 1PH TRIP SCHEME 0 to 4 Indicates how to use
the autorecloser with 1
phase trip:
0: AR_NOT_USED
1: AR_1P
2: AR_1P3P
3: AR_1P3P3P
4: AR_1P3P3P3P
- 3PH TRIP SCHEME 0 to 4 Indicates how to use
the autorecloser with 3
phases trip:
0: AR_NOT_USED,
1: AR_3P,
2: AR_3P3P,
3: AR_3P3P3P,
4: AR_3P3P3P3P
Settings C264/EN ST/C30

MiCOM C264/C264C

Page 9/10

MENU TREE
Available Values
Or
[min;max](step)(unit)
Parameter
signification
DEVICE
short name 1

short name N

- TIME OPEN [0;1000](1)(ms) Time duration for the
open contact.
- TIME CLOSE [0;1000](1)(ms) Time duration for the
close contact.
BI
Bi 1

Bi N

- MOTION00 FILT [0;600](100)(ms) Time of non
complementarity
filtering in the state 00:
only use for double
digital input.
- MOTION11 FILT [0;600](100)(ms) Time of non
complementarity
filtering in the state 11:
only use for double
digital input.
- PERS OPEN FILT [0;1200](100)(ms) Time of persistence
filtering in the state
Open or 0
- PERS CLOSE FILT [0;1200](100)(ms) Time of persistence
filtering in the state
Close or 1
- TOGGLING OPTION YES, NO Flag to validate or
inhibit the The toggling
option.
MV
Mv 1

Mv N

- HYSTERESIS [1;50](1)(%) % of hysteresis applied
on thresholds.
- DEADBAND [1;50](1)(%) % of variation within
the Analogue Input is
not transmitted.
- THRESHOLD 1 [Min;Max](0.01)(XXX) Low low low threshold
(Lowest threshold of
the analogue input)
- THRESHOLD 2 [Min;Max](0.01)(XXX) Low low threshold
- THRESHOLD 3 [Min;Max](0.01)(XXX) Low threshold
- THRESHOLD 4 [Min;Max](0.01)(XXX) High threshold
- THRESHOLD 5 [Min;Max](0.01)(XXX) High high threshold
C264/EN ST/C30 Settings

Page 10/10

MiCOM C264/C264C

MENU TREE
Available Values
Or
[min;max](step)(unit)
Parameter
signification
- THRESHOLD 6 [Min;Max](0.01)(XXX) High high high
threshold (highest
threshold of the
analogue input)
COMM. PORT
Com 1

Com 4

- BAUDRATE baudrate * Baudrate of the
communication port
among:
50,100,200,300,600,12
00,2400,4800,9600,19
200,38400, 56000.
- NB STOP BIT 1, 2 Number of stop bits
- NB BIT PER CHAR 7, 8 Number of bits per
character
- PARITY odd, even, none Parity
HMI
MAIN
- EXIT MT TIME [5;300](1)(s) Time after which the
Menu tree is
automatically left if
there is no pressed
button.
- BACK LIGHT DELAY [5;300](1)(s) Time after which the
back light disappears if
there is no pressed
button.
- SELECT EXIT TIME [5;300](1)(s) Maximum time
between selection and
execution orders.
- PASSWORD XXXX Password: needed to
modify parameters.
- BYPASS DELAY [20;120](1)(s) Time after which a
bypass is automatically
deselected.
BAY
Bay 0

Bay N

- SBMC DISPLAY YES, NO Flag to validate or
inhibit the display of
the SBMC mode
- DISPLAY DEV NAME YES, NO Flag to validate or
inhibit the display of
the Name od Devices
in the Bay Panel.
FIGURE 1 : MENU TREE FOLDER ORGANISATION
Communications C264/EN CT/C30

MiCOM C264/C264C


COMMUNICATIONS
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 1/92

CONTENT
1. SCOPE OF THE DOCUMENT 5

2. SCP COMMUNICATION 6
2.1 Communication on Station bus 6
2.1.1 Finality 6
2.1.2 Inputs 6
2.1.3 Supported services 7
2.1.4 Supported data objects 7
3. SCADA COMMUNICATION 8
3.1 Overview 8
3.2 SCADA common functionality 8
3.2.1 Interface to SCADA 8
3.2.2 Behaviour and specific treatments 9
3.2.3 Data sent to SCADA 10
3.2.4 Data sent to MiCOM C264 12
3.3 Slave DNP3 profile 13
3.3.1 DNP3 level 3: IMPLEMENTATION TABLE 16
3.4 Slave IEC 60870-5-101 profile 20
3.4.1 System or device 20
3.4.2 Network configuration 20
3.4.3 Physical layer 21
3.4.4 Link layer 21
3.4.5 Application layer 22
3.4.6 Basic application functions 26
3.4.7 Protocol Requirements 30
3.4.8 Application Functions 30
3.5 Slave IEC 60870-5-104 Server profile 32
3.5.1 System or device 32
3.5.2 Network configuration (Network-specific parameter) 32
3.5.3 Physical layer (Network-specific parameter) 33
3.5.4 Link layer (Network specific parameter) 33
3.5.5 Protocol Requirements 34
3.5.6 Application layer 34
3.5.7 Basic application functions 40
3.6 Slave DNP3 (TCP/IP) profile 43
C264/EN CT/C30 Communications

Page 2/92

MiCOM C264/C264C

3.7 Slave Modbus (MODICON) profile 44
3.7.1 Introducing MODBUS 44
3.7.2 Slave responses 45
3.7.3 Serial transmission mode 46
3.7.4 MODBUS Functions 47
3.7.5 Function 01 / 02: Read Coil Status Read Input Status 48
3.7.6 Function 03 / 04: Read Holding Registers / Input Registers 49
3.7.7 Function 05: Force Single Coil 51
3.7.8 Function 06: Preset single register 51
3.7.9 Function 08: Diagnostic [Sub-function 0 only] 52
3.7.10 Function 15: Force Multiple Coils 52
3.7.11 Function 16: Preset multiple registers 52
4. IED COMMUNICATION 53
4.1 Overview 53
4.2 IED Common functionality 53
4.2.1 Interface to IEDs 53
4.2.2 Behaviour 54
4.2.3 Data received from IEDs 58
4.2.4 Data sent to IEDs 58
4.2.5 Tunnelling 59
4.2.6 Limits and Performances 62
4.3 MODBUS communication 62
4.3.1 Finality 62
4.3.2 Interface to IEDs 62
4.3.3 Behaviour 63
4.3.4 Data received from IEDs 63
4.3.5 Data sent to IEDs 64
4.3.6 Error management 64
4.3.7 Limits and Performances 64
4.4 DNP 3.0 Communication 65
4.4.1 Finality 65
4.4.2 Interface to IEDs 65
4.4.3 Behaviour 66
4.4.4 Data received from IEDs 67
4.4.5 Data sent to IEDs 67
4.4.6 Master DNP3.0 Profile 68
4.4.7 DNP.3 Level 3 IMPLEMENTATION TABLE 71
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 3/92

4.5 IEC 60870-5-103 Communication 75
4.5.1 Finality 75
4.5.2 Interface to IEDs 75
4.5.3 Behaviour 76
4.5.4 Data received from IEDs 77
4.5.5 Data sent to IEDs 79
4.6 IEC 60870-5-101 Communication 80
4.6.1 Finality 80
4.6.2 Master IEC 60870-5-101 profile 80

C264/EN CT/C30 Communications

Page 4/92

MiCOM C264/C264C

BLANK PAGE
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 5/92

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264 documentation binders. It describes the various
standard communications protocols implemented in the MiCOM C264.
MiCOM C264 supports 3 different types of communications:
SCP Communication: communication over Ethernet IEC61850
SCADA Communication: communication with an upper level SCADA system over
protocols (IEC 60870-5-101, IEC 60870-5-104, DNP3.0, MODBUS, DNP3 on TCP)
IED Communication: communication with legacy IEDs. The MiCOM C264 is
considered as a master (IEC 60870-5-103, DNP3.0, MODBUS, IEC 60870-5-101)
C264/EN CT/C30 Communications

Page 6/92

MiCOM C264/C264C

2. SCP COMMUNICATION
2.1 Communication on Station bus
2.1.1 Finality
This item describes IEC61850-8-1 implementation inside MiCOM C264.
2.1.2 Inputs
2.1.2.1 Information: MiCOM C264 application SCP
The type of information that can be transmitted are:
Changes of state of binary inputs
Measurements (Analogue or CT/VT)
Counters
Controls
Control acknowledgements
Time synchronisation message
Records (Event, fault, disturbance)
MiCOM C264 information (Init. report, Operating mode, control mode, Date)
2.1.2.2 Information SCP MiCOM C264 application
The type of information that can be transmitted are:
Changes of state of binary inputs
Measurements (Analogue or CT/VT)
Counters
Controls
Control acknowledgements
Time synchronisation message
Request for records
Database downloading
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 7/92

2.1.3 Supported services
Services supported by the IEC61850 agency integrated in the MiCOM C264 are listed in the
ACSI service conformance statement defined in Table A.3 of document
MiCOM C264/C264P PICS.
2.1.4 Supported data objects
The following table describes the common class supported by the IEC61850 agency
integrated in the MiCOM C264:
Common Class Comment
Client
support
Server
support
Status
SPS Single input status YES YES
DPS Double input status YES YES
INS Integer input status YES YES
ACT Protection activation information YES YES
ACD Directional protection activation
information
YES YES
Measurements
MV Measurement value YES YES
CMV Complex measurement value YES YES
WYE 3 phase + N measurement YES YES
DELTA Phase to phase measurement YES YES
Counters
BCR Binary counter YES YES
Control
SPC Single point control YES YES
DPC Double control output YES YES
BSC Binary step control YES YES
APC Analogue output YES YES
INC Integer control output YES YES
ISC Integer step control output YES YES
Description
LPL Logical node name plate YES YES
DPL Device name plate YES YES
Report Control Block
URCB Unbuffered report control block YES YES
BRCB Buffered report control block NO YES

C264/EN CT/C30 Communications

Page 8/92

MiCOM C264/C264C

3. SCADA COMMUNICATION
3.1 Overview
A MiCOM C264 can be connected to a SCADA through networks using various protocols:
1. DNP3 (serial link)
2. T101 (serial link)
3. T104 (TCP/IP link)
4. DNP3 (TCP/IP link)
5. MODBUS (serial link)
It is possible to have:
Two different protocols running in parallel on different links
The same protocol on two links (redundant mode). This is actually not supported for
Modbus protocol.
For protocols running on TCP/IP link, there is only one Ethernet port. So redundancy
is not available for those protocols, and they all are physically running on the same
network (including IEC61850 protocol).
In T104 protocol the C264 (server) can manage two clients. These two clients have
separate configurations but may have same data. On the SCADA port, up to four front
ends can be defined, corresponding to one active port and three backup ports. So, up
to four IP addresses will be defined during the configuration of each T104 client. If
both clients are communicating with the computer, they must manage thein own
redundancy for doing controls with coherency.
Common features to all SCADA communication and all protocols are specified below.
Specific features to each protocol are specified in subsequent paragraphs.
3.2 SCADA common functionality
3.2.1 Interface to SCADA
This paragraph describes the exchange of data between the SCADA communication
function and the Master SCADA. It is split into two sub-paragraphs:
Inputs: data received from SCADA.
Outputs: data sent from the SCADA communication function to SCADA.
For each kind of protocol, it is indicated if the data is treated or not:
3.2.1.1 Input
Data DNP3 T101 T104 DNP3 on IP MODBUS
Remote link initialisation Treated Treated Treated Treated Treated
General interrogation Treated Treated Treated Treated Not Treated
Control Treated Treated Treated Treated Treated
Setpoint Treated Treated Treated Treated Treated
Time synchronisation Treated Treated Treated Treated Not Treated
Database (download) Not Treated Not Treated Not Treated Not Treated Not Treated
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 9/92

3.2.1.2 Output
Data DNP3 T101 T104 DNP3 on IP MODBUS
Digital input Treated Treated Treated Treated Treated
Dated Digital input Treated Treated Treated Treated Not Treated
Measurement (Events) Treated Treated Treated Treated Not Treated
Measurement (Cyclical) Treated Treated Treated Treated Treated
Counter Treated Treated Treated Treated Treated
Tap position Treated Treated Treated Treated Treated
Control acknowledgement Treated Treated Treated Treated Treated
Setpoint acknowledgement Treated Treated Treated Treated Treated
MiCOM C264 Disturbance Not Treated Not Treated Not Treated Not Treated Not Treated
Sequence Of Event File Not Treated Treated Treated Not Treated Not Treated
3.2.2 Behaviour and specific treatments
NOTE: In subsequent paragraphs, the master station (e.g.: SCADA) is referred to
as the controlling station.
3.2.2.1 Initialisation
There is a running database for each SCADA link. At initialisation, a GI is performed on the
application in order to initialise these databases.
The GI sequence consists of different requests to the MiCOM C264 application in order to
get the value and state of all data (Binary input, measurement, counter, step position
indication).
3.2.2.2 General interrogation
The Outstation interrogation function is used for updating the controlling station after the
internal station initialisation procedure, or when the controlling station detects a loss of
information, or when the link layer connection has been re-established. The general
interrogation function of the controlling station requests the MiCOM C264 to transmit the
actual values of all addressed datapoints.
The MiCOM C264 marks the end of the general interrogation procedure by sending an
indication to the controlling station when the protocols allow it.
3.2.2.3 Clock synchronisation
Clock in MiCOM C264 may be synchronised by the controlling station.
NOTE: The clock can be synchronised by other means: external clock, Master
Clock, operator. Only one source will be selected at a given time. This
selection is performed by the clock synchronisation function based on
configuration and priority level. However the controlling station is not
informed of this fact and must continue to send clock synchronisation
commands.
The controlling station must perform the correction made on the time sent in synchronisation
commands.
3.2.2.4 Database downloading and switching
This function is only implemented in T101 and T104 protocols. The SCADA can download a
database and only a database. Then the type of file is 1 (Transparent file) and the IOA
(information object address) must be 1. The database downloaded will be the standby
database.
To switch over this database, the SCADA must send a reset process command
(C_RP_NA_1 (105)) with cause of transmission equal to 6 (activation) and QRP field set to 1
(general reset of process)
C264/EN CT/C30 Communications

Page 10/92

MiCOM C264/C264C

3.2.2.5 Local/remote mode
A substation or a bay can be in local or remote mode. When it is in local mode it can not be
controlled remotely and when it is in remote mode, it can not be controlled locally.
Each Mode can be associated to a binary input.
3.2.2.6 Taking Control
A Substation can be configured in taking control mode. This means:
At a given time, only one SCADA can send controls to the substation (the one which
has the control).
To be allowed to send controls, a SCADA must take control of the substation by
sending a specific command to the MiCOM C264.
On each SCADA link, there is a binary input indicating if the corresponding SCADA has the
control of the substation.
On reception of a Taking Control command, the MiCOM C264:
Puts the substation in Remote mode (if it was in Local Mode)
Gives the control to the (last) SCADA which asks for it
Reset the Taking Control Binary input of the SCADA which had previously the
control
Set the Taking Control Binary input of the SCADA which asks the control
If the take control command is set for a SCADA, MiCOM C264 should refuse all commands
from other SCADAs.
3.2.2.7 SBMC mode
This mode is used to test a substation while it is in Remote mode. As this mode is a test
mode, MiCOM C264 wont send all changes of state to SCADA.
When bay turns to SBMC mode, MiCOM C264 will send to SCADA all concerned data
(configured Bay Based in the SCE) at specific states defined in the SCE for the management
of SBMC.
For those data, change of state wont be transmitted, but will be memorised by MiCOM C264
while the Bay is in SBMC mode.
When the Bay returns to Non SBMC mode, MiCOM C264 will send the current state of any
data that has changed whilst the Bay has been in SBMC mode.
3.2.2.8 Redundancy
Serial links can be configured as redundant. In this case, SCADA can send requests on both
serial links: main link or redundant link.
MiCOM C264 always responds on the link used by SCADA for requesting the slave
3.2.2.9 Automatic synchrocheck
SCADA can send control to synchronised circuit breakers with a facility to bypass the
synchrocheck.
3.2.3 Data sent to SCADA
After the initialisation sequence, MiCOM C264 Slave sends the state of all of its data to the
SCADA. The current state of data is sent as state or as change of state messages,
depending on the protocol.
The data, which can be sent to SCADA, is detailed in the paragraphs below.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 11/92

3.2.3.1 Binary inputs
Binary inputs can be sent as states or as changes of state depending on the protocol.
A binary input can be associated with a single point or a double point.
NOTE: Multipoint status is not treated.
3.2.3.2 Measurements
Measurements can be sent in various formats: float, integer, normalised, scaled
Measurements can be sent as periodical messages or as changes of state: variation,
threshold, and invalidity.
The choices of format and mode of transmission are done by configuration according to the
protocol.
3.2.3.3 Counters
Counters can be sent as spontaneous messages (changes of state) or on demand (counter
General Interrogation).
The choice whether to use spontaneous messages for a counter is done by configuration,
according to the protocol.
3.2.3.4 Tap position
Tap position indication (TPI) can be sent to SCADA as states or as changes of state. The
choice between state or change of state depends on the protocol. If the protocol allows the
both, the choice is done by configuration.
A digital input can be associated with a single point or a double point.
3.2.3.5 Computer disturbance file
Only Slow Wave Form is implemented for T101 or T104. maximum five slow wave form files
can be available at a time. The IOA of the first file is configured and the others are
consecutive. the type of file is 1 (Transparent file). When a slow wave form file is available,
an ASDU Directory (F_DR_TA_1 (126)) is sent by the computer with cause of transmission
spontaneous (3). The file is already available until a new file is created and replaces it. The
Scada can identify the file only with its date. The size of file must be lower or equal to the
size of one section
3.2.3.6 Sequence Of Events File (SOE)
The SOE is a circular file where Events of the MiCOM C264 are stored. There is one SOE
for each SCADA link.
The Events, which can be stored in SOE, are Binary Input and measurements. The choice is
done by configuration.
Following information in MiCOM C264 configuration are used to manage SOE file:
For each SCADA protocol
A flag indicating if SOE file have to be managed
Identification of the SOE file on the link (Name, Address, )
The maximum size of the file
The percentage of filling from which the MiCOM C264 will try to transmit the SOE
file
For each BI / measurement
A flag indicating if it must be stored in SOE
C264/EN CT/C30 Communications

Page 12/92

MiCOM C264/C264C

Rules for the SOE management are the following:
At starting of the MiCOM C264, the SOE file is Empty
When the SOE is full, the oldest Event is deleted and the new one is added
As soon as the percentage of filling indicated in configuration is reached, the MiCOM
C264 tries to up-load the SOE file
Once a SOE file has been successfully up-loaded, all Event sent are deleted from
SOE
3.2.3.7 Synchronisation status
MiCOM C264 can inform the controlling station about its synchronisation status.
According to the protocol, this may be done by a specific message or by a binary input.
3.2.4 Data sent to MiCOM C264
SCADA can send data to MiCOM C264. The type of data is described in subsequent
paragraphs.
3.2.4.1 Digital Controls or setpoints
A control is transmitted to the handling of control sequences function.
At the end of the control sequence an acknowledgement is sent to SCADA if protocol allows
it.
3.2.4.2 Counter commands
The commands allowed on counters are:
Reset of a group of Counters
Reset of all Counters
Freeze of a group of counters
Freeze of all counters
Read ( frozen value) of a group of Counters
Read ( frozen value) of all Counters
3.2.4.3 Synchronisation
Depending on the configuration, MiCOM C264 can be synchronised by a SCADA.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 13/92

3.3 Slave DNP3 profile
DNP V3.00 Device Profile
Highest DNP Level Supported:
For Requests Level 3
For Responses Level 3
Device Function:
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
supported:
_____________________________________________________________________________
_____________________________________________________________________________
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: (must be 292)
Maximum Application Fragment Size (octets):
Transmitted 2048
(configurable: 15 to 2048 bytes)
Received 2048
Maximum Data Link Re-tries:
None
Fixed at _______________________
Configurable, range _________ to ____
Maximum Application Layer Re-tries:
None
Configurable, range ____ to _____
(Fixed is not permitted)
Requires Data Link Layer Confirmation:
Never
Always
Sometimes If Sometimes, when?
________________________________________________________________
Configurable If Configurable, how?
User option to set Data Link Confirmation to:
Always device will always request Data Link Confirmations.
Multi-packet only the device will request Data Link Confirmations when sending multi-packet
responses.
Never the device will never request Data Link Confirmations.
Requires Application Layer Confirmation:
Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes _________ If 'Sometimes', when?
________________________________________________________________
Configurable If 'Configurable', how? _________________________________
C264/EN CT/C30 Communications

Page 14/92

MiCOM C264/C264C

DNP V3.00 Device Profile
Timeouts while waiting for:
Data Link Confirm None Fixed at ___ Variable Configurable
Complete Appl. Fragment None Fixed at ___ Variable Configurable
Application Confirm None Fixed at 10s Variable Configurable
Complete Appl. Response None Fixed at ___ Variable Configurable
Others
________________________________________________________________
Attach explanation if 'Variable' or 'Configurable' was checked for any timeout
Sends/Executes Control Operations:
WRITE Binary Outputs Never Always Sometimes Configurable
SELECT/OPERATE Never Always Sometimes Configurable
DIRECT OPERATE Never Always Sometimes Configurable
DIRECT OPERATE - NO ACK Never Always Sometimes Configurable

Count > 1 Never Always Sometimes Configurable
Pulse On Never Always Sometimes Configurable
Pulse Off Never Always Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable

Queue Never Always Sometimes Configurable
Clear Queue Never Always Sometimes Configurable
Select timeout: configurable (same value for all controls)
A pulse duration can be specified from Scada, for trip and close control with a transient DO.
When no value is specified, the default configured value is used.
FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY:
Reports Binary Input Change Events when no
Specific variation requested:
Never
Only time-tagged
Only non-time-tagged
Configurable to send both, one or the other
(explanation below)
User option to have all Binary Input
Change Events returned as either:
time-tagged OR
non-time-tagged
Reports time-tagged Binary Input Change Events
When no specific variation requested:
Never
Binary Input Change With Time
Binary Input Change With Relative Time
Configurable (attach explanation)
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 15/92

DNP V3.00 Device Profile
Send Unsolicited Responses:
Never
Configurable (attach explanation)
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
Function codes supported
Send Static Data in Unsolicited Responses:
Never
When Device Restarts
When Status Flags Change

No other options are permitted.
Default Counter Object/Variation:
No Counters Reported
Configurable (explanation below)
Default Object ____ 20 ______
Default Variation ____ 02 ______
Point-by-point list attached


User option to return all static counters in
One of the following variations:
32-Bit Binary Counter
32-Bit Binary Counter Without Flag
16-Bit Binary Counter
16-Bit Binary Counter Without Flag
Counters Roll Over at:
No Counters Reported
Configurable (explanation below)
16 Bits
32 Bits
Other Value ____________
Point-by-point list attached

User option to select roll over:
32 bit counters roll over at 2^32.
16 bit counters roll over at 2^16
Send Multi-Fragment Responses: Yes No
Binary Input (BI) double management:
For a BI double, two binary inputs are configured, with a point address for the open contact and the
address + 1 for the close contact. All the BI double are transmitted this way.

C264/EN CT/C30 Communications

Page 16/92

MiCOM C264/C264C

3.3.1 DNP3 level 3: IMPLEMENTATION TABLE
OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj Var Description
Func
Codes
(dec)
Qual
Codes (2)
(hex)
Func Codes
(dec)
Qual Codes
(hex)
1 0 Binary Input All Variations 1 00,01,06,17,28
1 1 Binary Input 1 00,01,06, 17,28 129 00,17,28
1 2 Binary Input with Status 1 00,01,06,17,28 129 00,17,28
2 0 Binary Input Change - All Variations 1 06,07,08 129,130 17
2 1 Binary Input Change without Time 1
2 2 Binary Input Change with Time 1 06,07,08 129,130 17
2 3 Binary Input Change with Relative Time 1
10 0 Binary Output - All Variations 1
10 1 Binary Output
10 2 Binary Output Status 1
12 0 Control Block - All Variations (1)
12 1 Control Relay Output Block (1) 3,4,5,6 17,28 129 Request
echo
12 2 Pattern Control Block
12 3 Pattern Mask
20 0 Binary Counter - All Variations 1,7,8,9,10 00,01,06,17,28
20 1 32-Bit Binary Counter 1 00,01,06,17,28 129 00,17,28
20 2 16-Bit Binary Counter 1 00,01,06,17,28 129 00,17,28
20 3 32-Bit Delta Counter
20 4 16-Bit Delta Counter
20 5 32-Bit Binary Counter without Flag 1 00,01,06,17,28 129 00,17,28
20 6 16-Bit Binary Counter without Flag 1 00,01,06,17,28 129 00,17,28
20 7 32-Bit Delta Counter without Flag
20 8 16-Bit Delta Counter without Flag
1. Qualifier Codes (in hexa) (example of Binary Input)
Request Qualifier Response Qualifier
Range of Points (8 bits) 0 0
Range of Points (16 bits) 1 0
All Points 6 0
Count of Points (8 bits) 7 0
Count of Points (16 bits) 8 0
List of Points (8 bits) 17 17
List of Points (16 bits) 28 28
2. Qualifier Codes 17 and 28 are only available on one point, except for controls (controls can be selected/executed on one
or more points)
3. Binary Counter - All Variations (Object 20, Var 0):
Functions 7,8 ,9 & 10 are only available with qualifiers 06, 17 and 28
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 17/92

OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj Var Description
Func
Codes
(dec)
Qual
Codes (2)
(hex)
Func Codes
(dec)
Qual Codes
(hex)
21 0 Frozen Counter - All Variations 1 00,01,06,17,28
21 1 32-Bit Frozen Counter 1 00,01,06,17,28 129 00,17,28
21 2 16-Bit Frozen Counter 1 00,01,06,17,28 129 00,17,28
21 3 32-Bit Frozen Delta Counter
21 4 16-Bit Frozen Delta Counter
21 5 32-Bit Frozen Counter with Time of
Freeze

21 6 16-Bit Frozen Counter with Time of
Freeze

21 7 32-Bit Frozen Delta Counter with Time
of Freeze

21 8 16-Bit Frozen Delta Counter with Time
of Freeze

21 9 32-Bit Frozen Counter without Flag 1 00,01,06,17,28 129 00,17,28
21 10 16-Bit Frozen Counter without Flag 1 00,01,06,17,28 129 00,17,28
21 11 32-Bit Frozen Delta Counter without
Flag

21 12 16-Bit Frozen Delta Counter without
Flag

22 0 Counter Change Event - All Variations 1 06,07,08
22 1 32-Bit Counter Change Event without
Time

22 2 16-Bit Counter Change Event without
Time

22 3 32-Bit Delta Counter Change Event
without Time

22 4 16-Bit Delta Counter Change Event
without Time

22 5 32-Bit Counter Change Event with Time 1 06,07,08 129,130 17
22 6 16-Bit Counter Change Event with Time 1 06,07,08 129,130 17
22 7 32-Bit Delta Counter Change Event with
Time

22 8 16-Bit Delta Counter Change Event with
Time

23 0 Frozen Counter Event - All Variations 1 06,07,08
23 1 32-Bit Frozen Counter Event without
Time

23 2 16-Bit Frozen Counter Event without
Time

23 3 32-Bit Frozen Delta Counter Event
without Time

23 4 16-Bit Frozen Delta Counter Event
without Time

23 5 32-Bit Frozen Counter Event with Time 1 06,07,08 129,130 17
23 6 16-Bit Frozen Counter Event with Time 1 06,07,08 129,130 17
23 7 32-Bit Frozen Delta Counter Event with
Time

23 8 16-Bit Frozen Delta Counter Event with
Time

C264/EN CT/C30 Communications

Page 18/92

MiCOM C264/C264C

OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj Var Description
Func
Codes
(dec)
Qual
Codes (2)
(hex)
Func Codes
(dec)
Qual Codes
(hex)
30 0 Analog Input - All Variations 1 00,01,06,17,28
30 1 32-Bit Analog Input 1 00,01,06,17,28 129 00, 17,28
30 2 16-Bit Analog Input 1 00,01,06,17,28 129 00,17,28
30 3 32-Bit Analog Input without Flag 1 00,01,06,17,28 129 00,17,28
30 4 16-Bit Analog Input without Flag 1 00,01,06,17,28 129 00,17,28
31 0 Frozen Analog Input - All Variations
31 1 32-Bit Frozen Analog Input
31 2 16-Bit Frozen Analog Input
31 3 32-Bit Frozen Analog Input with Time of
Freeze

31 4 16-Bit Frozen Analog Input with Time of
Freeze

31 5 32-Bit Frozen Analog Input without Flag
31 6 16-Bit Frozen Analog Input without Flag
32 0 Analog Change Event - All Variations 1 06,07,08
32 1 32-Bit Analog Change Event without
Time
1 06,07,08 129,130 17
32 2 16-Bit Analog Change Event without
Time
1 06,07,08 129,130 17
32 3 32-Bit Analog Change Event with Time 1 06,07,08 129,130 17
32 4 16-Bit Analog Change Event with Time 1 06,07,08 129,130 17
33 0 0 Frozen Analog Event - All Variations
33 1 32-Bit Frozen Analog Event without
Time

33 2 16-Bit Frozen Analog Event without
Time

33 3 32-Bit Frozen Analog Event with Time
33 4 16-Bit Frozen Analog Event with Time
40 0 Analog Output Status - All Variations
40 1 32-Bit Analog Output Status
40 2 16-Bit Analog Output Status
41 0 Analog Output Block - All Variations
41 1 32-Bit Analog Output Block 3,4,5,6 17,28 129 Request
echo
41 2 16-Bit Analog Output Block 3,4,5,6 17,28 129 Request
echo
50 0 Time and Date - All Variations
50 1 Time and Date 1,2 07 (quantity=1)
50 2 Time and Date with Interval
51 0 Time and Date CTO - All Variations
51 1 Time and Date CTO
51 2 Unsynchronized Time and Date CTO
52 0 Time Delay - All Variations
52 1 Time Delay Coarse
52 2 Time Delay Fine
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 19/92

OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj Var Description
Func
Codes
(dec)
Qual
Codes (2)
(hex)
Func Codes
(dec)
Qual Codes
(hex)
60 0
60 1 Class 0 Data 1 06,07,08
1 06,07,08 60 2 Class 1 Data
20,21 06
1 06,07,08 60 3 Class 2 Data
20,21 06
1 06,07,08 60 4 Class 3 Data
20,21 06
70 0 File management All variations
70 2 Authentication Object 29 5b 129 5b
70 3 File Command Object 25,27 5b 129 5b
70 4 File Command Status Object 26,30 5b 129 5b
70 5 File Transfert Object 1,2 5b 129 5b
70 7 File Description 28 5b 129 5b
80 1 Internal Indications

81 1 Storage Object
82 1 Device Profile
83 1 Private Registration Object
83 2 Private Registration Object Descriptor
90 1 Application Identifier
100 1 Short Floating Point
100 2 Long Floating Point
100 3 Extended Floating Point
101 1 Small Packed Binary-Coded Decimal
101 2 Medium Packed Binary-Coded Decimal
101 3 Large Packed Binary-Coded Decimal
No Object (Cold Restart)
No Object (Warm Restart)
No Object (Delay Measurement
C264/EN CT/C30 Communications

Page 20/92

MiCOM C264/C264C

3.4 Slave IEC 60870-5-101 profile
The companion standard presents sets of parameters and alternatives from which subsets
have to be selected to implement particular telecontrol systems. Certain parameters values,
such as the number of bytes in the COMMON ADDRESS of ASDUs represent mutually
exclusive alternatives. This means that only one value of the defined parameters is admitted
per system.
Other parameters, such as the listed set of different process information in command and in
monitor direction allow the specification of the complete set or subsets, as appropriate for
given applications. This clause summarizes the parameters of the previous clauses to
facilitate a suitable selection for a specific application. If a system is composed of equipment
stemming from different manufacturers it is necessary that all partners agree on the selected
parameters.
The selected parameters should be marked in the white boxes as follows:
Function or ASDU is not used
Function or ASDU is used as standardized (default)
R Function or ASDU is used in reverse mode
B Function or ASDU is used in standard and reverse mode
The possible selection (blank, X, R or B) is specified for each specific clause or parameter.
NOTE: In addition, the full specification of a system may require individual selection of
certain parameters for certain parts of the system, such as the individual selection
of scaling factors for individually addressable measured values.
3.4.1 System or device
(system specific parameter, indicates the definition of a system or a device by marking one
of the following with X)
System definition
Controling station definition (Master)
Controlled station definition (Slave)
3.4.2 Network configuration
(network specific parameter, all configurations that are used are to be marked X)
Point-to-point Multipoint-party line
Multiple point-to-point Multipoint-star
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 21/92

3.4.3 Physical layer
(network specific parameter, all interfaces and data rates that are used are to be marked X)
Transmission speed (control direction)
Unbalanced interchange
CIRCUIT V24/V28
Standard
Recommended if
> 1200 bits/s
Balanced interchange
Circuit X24/X27
100 bits/s 2400 bits/s 2400 bits/s 56000 bits/s
200 bits/s 4800 bits/s 4800 bits/s 64000 bits/s
300 bits/s 9600 bits/s 9600 bits/s

600 bits/s 19200 bits/s 19200 bits/s

1200 bits/s

38400 bits/s

Transmission speed (monitor direction)
Unbalanced interchange
Circuit V24/V28
Standard
Recommended if
> 1200 bits/s
Balanced interchange
Circuit X24/X27
100 bits/s 2400 bits/s 2400 bits/s 56000 bits/s
200 bits/s 4800 bits/s 4800 bits/s 64000 bits/s
300 bits/s 9600 bits/s 9600 bits/s

600 bits/s 19200 bits/s 19200 bits/s

1200 bits/s

38400 bits/s

3.4.4 Link layer
(network specific parameter, all options that are used are to be marked X. Specify the
maximum frame length. If a non-standard assignment of class 2 messages is implemented
for unbalanced transmission, indicate the type ID and COT of all messages assigned to
class 2.)
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively
in this companion standard.
Link transmission procedure Address field of the link
Balanced transmission Not present (balanced transmission only)
Unbalanced transmission One octet
Two octets
Structured
Unstructured
Frame length (number of bytes)
255 Maximum length L in control direction
up to 255 Maximum length L in monitor direction configurable
C264/EN CT/C30 Communications

Page 22/92

MiCOM C264/C264C

3.4.5 Application layer
Transmission mode for application data
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is used
exclusively in this companion standard.
Common address of ASDU
(system-specific parameter, all configurations that are used are to be marked X)
One octet Two octets
Information object address
(system-specific parameter, all configurations that are used are to be marked X)
One octet Structured
Two octets Unstructured
Three octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked X)
One octet Two octets (with originator address)
Selection of standard ASDUs
Process information in monitor direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<1> := Single-point information M_SP_NA_1
<2> := Single-point information with time tag M_SP_TA_1
<3> := Double-point information M_DP_NA_1
<4> := Double-point information with time tag M_DP_TA_1
<5> := Step-position information M_ST_NA_1
<6> := Step-position information with time tag M_ST_TA_1
<7> := BitString of 32 bit M_BO_NA_1
<8> := BitString of 32 bit with time tag M_BO_TA_1
<9> := Measured value, normalized value M_ME_NA_1
<10> := Measured value, normalized value with time tag M_ME_TA_1
<11> := Measured value, scaled value M_ME_NB_1
<12> := Measured value, scaled value with time tag M_ME_TB_1
<13> := Measured value, short floating point value M_ME_NC_1
<14> := Measured value, short floating point value with time tag M_ME_TC_1
<15> := Integrated totals M_IT_NA_1
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 23/92

<16> := Integrated totals with time tag M_IT_TA_1
<17> := Event of protection equipment with time tag M_EP_TA_1
<18> := Packed start events of protection equipment with time tag M_EP_TB_1
<19> := Packed output circuit transmission of protection equipment with time tag M_EP_TC_1
<20> := Packed single-point information with status change detection M_PS_NA_1
<21> := Measured value, normalized value without quality descriptor M_ME_ND_1
<30> := Single-point information with time tag CP56Time2a M_SP_TB_1
<31> := Double-point information with time tag CP56Time2a M_DP_TB_1
<32> := Step-position information with time tag CP56Time2a M_ST_TB_1
<33> := Bistring of 32 bits with with time tag CP56Time2a M_BO_TB_1
<34> := Measured value, normalized with time tag CP56Time2a M_ME_TD_1
<35> := Measured value, scaled with time tag CP56Time2a M_ME_TE_1
<36> := Measured value, short floating point number with time tag CP56Time2a M_ME_TF_1
<37> := Integrated totals with time tag CP56Time2a M_IT_TB_1
<38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1
<39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
<40> := Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1
Process information in control direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<45> := Single command C_SC_NA_1
<46> := Double command C_DC_NA_1
<47> := Regulating step command C_RC_NA_1
<48> := Set point command, normalized value C_SE_NA_1
<49> := Set point command, scaled value C_SE_NB_1
<50> := Set point command, short floating point value C_SE_NC_1
<51> := BitString of 32 bits C_BO_NA_1
System information in monitor direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<70> := End of initialisation M_EI_NA_1
C264/EN CT/C30 Communications

Page 24/92

MiCOM C264/C264C

System information in control direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<100> := Interrogation command C_IC_NA_1
<101> := Counter Interrogation Command C_CI_NA_1
<102> := Read command C_RD_NA_1
<103> := Clock synchronisation command C_CS_NA_1
<104> := Test command C_TS_NB_1
<105> := Reset process command C_RP_NC_1
<106> := Delay acquisition command C_CD_NA_1
Parameter in control direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<110> := Parameter of measured value, normalized value P_ME_NA_1
<111> := Parameter of measured value, scaled value P_ME_NB_1
<112> := Parameter of measured value, short floating point value P_ME_NC_1
<113> := Parameter activation P_AC_NA_1
File transfer
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<120> := File ready F_FR_NA_1
<121> := Section ready F_SR_NA_1
<122> := Call directory, select file, call file, call section F_SC_NA_1
<123> := Last section, last segment F_LS_NA_1
<124> := Ack file, ack section F_AF_NA_1
<125> := Segment F_SG_NA_1
<126> := Directory F_DR_TA_1
Special use (private range)
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<136> := Database version M_DB_NA_1
<137> := Regulating delay command C_RC_NB_1
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 25/92

Type identifier and cause of transmission assignments
(station-specific parameters)
Shaded boxes are not required.
Blank = function or ASDU is not used
Mark type identification/cause of transmission combinations:
X if used only in the standard direction
R if used only in the reverse direction
B if used in both directions
Type ID Cause of transmission

1 2 3 4 5 6 7 8 9 10 11 12 13
20
to
36
37
to
41
44 45 46 47
<1> M_SP_NA_1 X X X X
<2> M_SP_TA_1 X X


<3> M_DP_NA_1 X X X X
<4> M_DP_TA_1 X X
<5> M_ST_NA_1 X X X X
<6> M_ST_TA_1 X X
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1 X
<11> M_ME_NB_1 X X X X
<12> M_ME_TB_1 X
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1 X
<15> M_IT_NA_1 X X
<16> M_IT_TA_1 X X
<17> M_EP_TA_1
<18> M_EP_TB_1 X
<19> M_EP_TC_1 X
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X X
<31> M_DP_TB_1 X X
<32> M_ST_TB_1 X X
<33> M_BO_TB_1
<34> M_ME_TD_1 X
<35> M_ME_TE_1 X
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1 X
<40> M_EP_TF_1 X
<45> C_SC_NA_1 X X X X X X X X
C264/EN CT/C30 Communications

Page 26/92

MiCOM C264/C264C

Type ID Cause of transmission

1 2 3 4 5 6 7 8 9 10 11 12 13
20
to
36
37
to
41
44 45 46 47
<46> C_DC_NA_1 X X X X X X X X
<47> C_RC_NA_1 X X X X X X X X
<48> C_SE_NA_1 X X X X X X X X
<49> C_SE_NB_1 X X X X X X X X
<50> C_SE_NC_1 X X X X X X X X
<51> C_BO_NA_1 X
<70> M_EI_NA_1 X
<100> C_IC_NA_1 X X X X X X X X
<101> C_CI_NA_1 X X X X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X X X
<104> C_TS_NA_1 X X X X X
<105> C_RP_NA_1 X
<106> C_CD_NA_1 X X X
<110> P_ME_NA_1 X


<111> P_ME_NB_1 X
<112> P_ME_NC_1 X
<113> P_AC_NA_1 X
<120> F_FR_NA_1 X X X X
<121> F_SR_NA_1 X X X X
<122> F_SC_NA_1 X X X X
<123> F_LS_NA_1 X X X X
<124> F_AF_NA_1 X X X X
<125> F_SG_NA_1 X X X X
<126> F_DR_TA_1 X X

<136> M_DB_NA_1 X

<137> C_RC_NB_1 X X X X X X X X
3.4.6 Basic application functions
Station initialisation
(station-specific parameter, mark X if function is used)
Remote initialisation
Cyclic data transmission
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Cyclic data transmission
Read procedure
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Read procedure
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 27/92

Spontaneous transmission
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Spontaneous transmission
Link state between Controlling and Controlled Station
Management of the COM lost (Problem detecting on the link)
Management of the COM recovering (Problem not detecting on the link)
General interrogation
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
global
group 1 group 7 group 13
group 2 group 8 group 14
group 3 group 9 group 15
group 4 group 10 group 16
group 5 group 11 Addresses per group have to be defined
group 6 group 12
Counter General interrogation
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
global
group 1 group 2 group 3
group 4
Clock synchronisation
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Clock synchronisation
Notes: The controlled station does not report the change of hour by
sending a clock synchronisation message (ASDU 103) to the
controlling station.
When the controlling station send to controlled station a clock
synchronisation and if the system (includes controlled station), isnt
synchronized by an other source: the clock synchronisation
response is positive.
When the controlling station send to controlled station a clock
synchronisation and if the system (includes controlled station), is
synchronized by an other source: the clock synchronisation
response is negative.
C264/EN CT/C30 Communications

Page 28/92

MiCOM C264/C264C

Command transmission
(object -specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Direct command transmission
Direct set-point command transmission
Select and execute command
Select and execute set-point command
C_SE ACTTERM used
No additional definition
Short pulse duration (duration determined by a system parameter in the outstation)
Long pulse duration (duration determined by a system parameter in the outstation)
Persistent output
Transmission of integrated totals
(object -specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Mode A: local freeze with spontaneous transmission
Mode B: local freeze with counter interrogation
Mode C: freeze and transmit by counter interrogation commands
Mode D: freeze by counter interrogation command, frozen values reported
spontaneously
Counter read General request counter
Counter freeze without reset Request counter group 1
Counter freeze with reset Request counter group 2
Counter reset Request counter group 3
Request counter group 4
Parameter loading
(object-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Threshold value
Smoothing factor
Low limit for transmission of measured value
High limit for transmission of measured value
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 29/92

Parameter activation
(object-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Act/deact of persistent cyclic or periodic transmission of the addressed object
Test procedure
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Test procedure
File transfer
(station-specific parameter), mark X if function is used)
File transfert in monitor direction
Transparent file
Transmission of disturbance data of protection equipment
Transmission of sequences of events
Transmission of sequences of recorded analogue values
File transfer in control direction
Transparent file
Background scan
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Background scan
Acquisition of transmission delay
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Acquisition of transmission delay
Management events priorities
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Digitals Inputs and Analogs Inputs, management events priorities.
See: T101 standard Amendment 2 7.2.2.2
C264/EN CT/C30 Communications

Page 30/92

MiCOM C264/C264C

3.4.7 Protocol Requirements
Class 1 data
The following types of information must be configured at the controlled station to be Class 1:
The following types of information are to be configured at the controlled station to be Class 1:
Single point information with or without time tag (on change)
Double point information with or without time tag (on change)
Step position information with or without time tag (on change)
Measured value, normalised with or without time tag (on change)
Measured value, scaled with or without time tag (on change)
Measured value, floated with or without time tag (on change)
Integrated totals with or without time tag (on change)
Time messages
All command responses (ACT_CONF, and ACT_TERM)
Class 2 data
The following types of information must be configured at the controlled station to be Class 2:
Single point information (GI scan, or BackGroundScan cycle)
Double point information (GI scan, or BackGroundScan cycle)
Step position information with or without time tag (on change)
Measured values, normalised (GI scan, or Periodic cycle, or BackGroundScan cycle)
Measured values, scaled (GI scan, or Periodic cycle, or BackGroundScan cycle)
Measured values, floated (GI scan, or Periodic cycle, or BackGroundScan cycle)
Step position values (GI scan, or BackGroundScan cycle)


Integrated totals (Counter GI scan)
3.4.8 Application Functions
The following IEC-60870-5-5 standard application processes are required to be supported.
Station Initialisation
Station initialisation consists of a reset of the communications link, followed by a general
interrogation of the controlled station. Once this initialisation sequence performed the
controlling station can start the polling for data report.
Communications failure
Communications to the controlled station must be re-initialised by the controlling station
when the frame repeat process has completed without successfully transmitting the frame (ie
the frame time-out period times the number of repeats).
If the controlled station fails to communicate with the controlling station then the controlling
station should perform a communications system initialisation for that controlled station.
Controlled station failure
The controlled station shall indicate to the controlling station that it has initialised by sending
a frame indicating End of Initialisation with a Cause of Initialisation (COI) field, which will
identify the reason for the initialisation in unbalanced mode only)
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 31/92

Data Acquisition by Polling
The default for all analogue values shall be reporting as Class 2 data (COT=1,
periodic/cyclic, or COT = 2, BackgroundScan cyclic).
Values returned as Class 2 data do not have a time tag (since they are constantly repeated).
The controlled station may return Class 1 data in response to a Class 2 request if no Class 2
data is available and Class 1 data is awaiting transmission.
At the controlled station, if a request for Class 2 data is received and no data is available a
negative response, data not available, shall be returned to the controlling Station. The
negative response may be a fixed length frame (FC=9), which in this case is treated as a
NACK.
Normal Acquisition of Events
The default for all status changes are reported as Class 1 data (COT=3, spontaneous).
Values returned as Class 1 data shall have a time tag (either CP24Time2a, or CP56Time2a).
Status changes at the controlled station shall cause the ACD bit to be set in the next Class 1
or Class 2 data response. The controlling station shall respond to ACD set by inserting a
scan for Class 1 (spontaneous) data as the next scan.
The response to a Class 1 data request shall also have the ACD bit set if more Class 1 data
is awaiting transmission. In this case a further scan for Class 1 data shall be scheduled by
the controlling station.
Abnormal Acquisition of Events
At the controlled station, if a request for Class 1 data is received and no data is available an
error should be raised and a negative response, data not available, returned to the
controlling Station. The negative response shall be a fixed length frame (FC=9), which in
this case is treated as a NACK.
At the controlling station, if a response to a scan for Class 1 data indicates no data is
available an error shall be raised and scanning returned to Class 2 data requests.
General Interrogation
The GI return the current status information directly from the Computer database.
Time tags are not used for data items returned as part of the GI response.
The GI groups are supported so, these will be set up in the Computer configuration and each
of the (up to 16) groups shall be requested/reported individually.
Clock synchronisation
The System (including the controlled station) may have different synchronisation sources
(IRIG-B, SCADA).
When the controlling station send to controlled station a clock synchronisation and if the
system isnt synchronized by an other source: the clock synchronisation response is
positive.
When the controlling station send to controlled station a clock synchronisation and if the
system is synchronized by an other source: the clock synchronisation response is negative.
All Class 1 data are time-tagged with:
Either the 3 bytes time-stamp (CP24Time2a), giving minutes and milliseconds within the
hour, or the 7 bytes time-stamp (CP56Time2a), giving minutes, milliseconds, hours, day,
month and year according to the Computer configuration.
The invalid bit in the time-stamp is set when the computer is not synchronised.
C264/EN CT/C30 Communications

Page 32/92

MiCOM C264/C264C

Command transmission
All control commands shall be Select before Execute, or Direct Execute.
For only the control commands: Activation termination is returned to the controlling station to
signal the end of a control sequence.
The QU field of the Qualifier of Command shall be set to zero (0), no additional definition.
Test procedure
A test command may be issued by the controlling station to ensure the availability of the
communications link and the commands subsystem.
Test commands are received at the controlled station on the active link. The controlled
station mirrors the test command, on the link from which it was received, with a cause of
transmission indicating activation confirmation.
An error response should be sent if the command is incorrect, with a cause of transmission
indicating negative activation confirmation.
3.5 Slave IEC 60870-5-104 Server profile
This companion standard presents sets of parameters and alternatives from which subsets
have to be selected to implement particular telecontrol systems. Certain parameter values,
such as the choice of structured or unstructured fields of the INFORMATION OBJECT
ADDRESS of ASDU represent mutually exclusive alternatives. This means that only one value
of the defined parameters is admitted per system. Other parameters, such as the listed set of
different process information in command and in monitor direction allow the specification of
the complete set or subsets, as appropriate for given applications. This clause summarises
the parameters of the previous clauses to facilitate a suitable selection for a specific
application. If a system is composed of equipment stemming from different manufacturers it
is necessary that all partners agree on the selected parameters.
Paragraph in grey are those which are not applicable for the IEC 60870-5-104 profile.
The selected parameters should be filled up ( ).
NOTE: In addition, the full specification of a system may require individual selection of
certain parameters for certain parts of the system, such as the individual selection
of scaling factors for individually addressable measured values.
To simplify the PID , we use the following conventions:
Not supported
Supported
3.5.1 System or device
System definition
Controlling station definition (Master)
Controlled station definition (Slave)
3.5.2 Network configuration (Network-specific parameter)
Point-to-point Multipoint-party line
Multiple point-to-point Multipoint-star
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 33/92

3.5.3 Physical layer (Network-specific parameter)
Transmission speed (control direction):
Unbalanced interchange
circuit V.24/V.28
Standard
Unbalanced interchange
circuit V.24/V.28
Recommended if >1 200 bit/s
Balanced interchange
circuit X.24/X.27, V35

100 bit/s

2 400 bit/s

2 400 bit/s

200 bit/s

4 800 bit/s

4 800 bit/s

300 bit/s

9 600 bit/s

9 600 bit/s

600 bit/s

19 200 bit/s

19 200 bit/s

1 200 bit/s

38 400 bit/s


56 000 bit/s


64 000 bit/s
Transmission speed (monitor direction):
Unbalanced interchange
circuit V.24/V.28
Standard
Unbalanced interchange
circuit V.24/V.28
Recommended if >1 200 bit/s
Balanced interchange
circuit X.24/X.27, V35

100 bit/s

2 400 bit/s

2 400 bit/s

200 bit/s

4 800 bit/s

4 800 bit/s

300 bit/s

9 600 bit/s

9 600 bit/s

600 bit/s

19 200 bit/s

19 200 bit/s

1 200 bit/s

38 400 bit/s


56 000 bit/s


64 000 bit/s
3.5.4 Link layer (Network specific parameter)
(Network-specific parameter, all options that are used should be filled up ( ). Specify
the maximum frame length. If a non-standard assignment of class 2 messages is
implemented for unbalanced transmission, indicate the type ID and COT of all messages
assigned to class 2.)
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively
in this companion standard.
Link transmission procedure Address field of the link

Balanced transmission

Not present (balanced transmission
only)

Unbalanced transmission

One octet


Two octets



Structured


Unstructured
Frame length
_255_ Maximum length L (number of bytes)
When using an unbalanced link layer, the following ASDU types are returned in class 2
messages (low priority) with the indicated causes of transmission:
C264/EN CT/C30 Communications

Page 34/92

MiCOM C264/C264C

The standard assignment of ASDUs to class 2 messages is used as follows:
Type Identification Cause of transmission
9,11,13,21 <1>
A special assignment of ASDUs to class 2 messages is used as follows:
Type Identification Cause of transmission
1,3,5 <20> to <41>
NOTE: In response to a class 2 poll, a controlled station prevent the controlling station with
ACD parameter, when there is no class 2 data available.
3.5.5 Protocol Requirements
3.5.5.1 Event
The following types of information are to be configured at the controlled station to be Event:
Single point information with or without time tag (on change)
Double point information with or without time tag (on change)
Step position information with or without time tag (on change)
Measured value, normalised with or without time tag (on change)
Measured value, scaled with or without time tag (on change)
Measured value, floated with or without time tag (on change)
Integrated totals with or without time tag (on change)
3.5.5.2 Static
The following types of information are to be configured at the controlled station to be Static:
Single point information (GI scan, or BackGroundScan cycle)
Double point information (GI scan, or BackGroundScan cycle)
Measured values, normalised (GI scan, or Periodic cycle, or BackGroundScan cycle)
Measured values, scaled (GI scan, or Periodic cycle, or BackGroundScan cycle)
Measured values, floated (GI scan, or Periodic cycle, or BackGroundScan cycle)
Step position values (GI scan, or BackGroundScan cycle)
Integrated totals (Counter GI scan)
3.5.6 Application layer
Transmission mode for application data
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is used
exclusively in this companion standard.
Common address of ASDU
(System specific parameter)
The address field of the link and the common address of ASDU could have a different
number of bytes

One octet

Two octets
Information object address
(System specific parameter)

One octet

Structured

Two octets

Unstructured

Three octets
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 35/92

Cause of transmission
(System-specific parameter)

One octet

Two octets (with originator address)
Length of APDU
(System-specific parameter)
The maximum length of APDU is 253 (default) The maximum length may be reduced by the
system.
Configurable Maximum length of APDU per system
Selection of standard ASDUs
Process information in monitor direction
(Station-specific parameter)

<1>: = Single-point information M-SP-NA-1

<2>: = Single-point information with time tag M-SP-TA-1

<3>: = Double-point information M-DP-NA-1

<4>: = Double-point information with time tag M-DP-TA-1

<5>: = Step position information M-ST-NA-1

<6>: = Step position information with time tag M-ST-TA-1

<7>: = Bit-string of 32 bit M-BO-NA-1

<8>: = Bit-string of 32 bit with time tag M-BO-TA-1

<9>: = Measured value, normalised value M-ME-NA-1

<10>: = Measured value, normalised value with time tag M-ME-TA-1

<11>: = Measured value, scaled value M-ME-NB-1

<12>: = Measured value, scaled value with time tag M-ME-TB-1

<13>: = Measured value, short floating point value M-ME-NC-1

<14>: = Measured value, short floating point value with time tag M-ME-TC-1

<15>: = Integrated totals M-IT-NA-1

<16>: = Integrated totals with time tag M-IT-TA-1

<17>: = Event of protection equipment with time tag M-EP-TA-1

<18>: = Packed starts events of protection equipment with time tag M-EP-TB-1

<19>: = Packed output circuit information of protection equipment
with time tag
M-EP-TC-1

<20>: = Packed single-point information with status change detection M-PS-NA-1

<21>: = Measured value, normalised value without quality
descriptor
M-ME-ND-1
C264/EN CT/C30 Communications

Page 36/92

MiCOM C264/C264C

Process information in monitor direction with the Extension of time tag
(Station-specific parameter)

<30>: = Single-point information with time tag CP56Time2a M-SP-TB-1

<31>: = Double-point information with time tag CP56Time2a M-DP-TB-1

<32>: = Step position information with time tag CP56Time2a M-ST-TB-1

<33>: = Bit-string of 32 bit with time tag CP56Time2a M-BO-TB-1

<34>: = Measured value, normalised value with time tag
CP56Time2a
M-ME-TD-1

<35>: = Measured value, scaled value with time tag CP56Time2a M-ME-TE-1

<36>: = Measured value, short floating point value, time tag CP56Time2a M-ME-TF-1

<37>: = Integrated totals with time tag CP56Time2a M-IT-TB-1

<38>: = Event of protection equipment with time tag CP56Time2a M-EP-TD-1

<39>: = Packed start event of protection equipment, time tag
CP56Time2a
M-EP-TE-1

<40>: = Packed output circuit information of protection equipment
with time tag CP56Time2a
M-EP-TF-1
Process information in control direction
(station specific parameter)

<45>: = Single command C-SC-NA-1

<46>: = Double command C-DC-NA-1

<47>: = Regulating step command C-RC-NA-1

<48>: = Set point command normalised value C-SE-NA-1

<49>: = Set point command scaled value C-SE-NB-1

<50>: = Set point command, short floating point value C-SE-NC-1

<51>: = Bit-string of 32 bit C-BO-NA-1

<58>: = Single command with time tag CP56Time2a C_SC_TA_
1

<59>: = Double command with time tag CP56Time2a C_DC_TA_
1

<60>: = Regulating step command with time tag CP56Time2a C_RC_TA_
1

<61>: = Set point command normalized value with time tag CP56Time2a C_SE_TA_
1

<62>: = Set point command scaled value with time tag
CP56Time2a
C_SE_TB_
1

<63>: = Set point command short floating point value with time tag
CP56Time2a
C_SE_TC_
1

<64>: = Bitstring of 32 bits with time tag CP56Time2a C_BO_TA_
1
NOTE: Time tag command (ASDU 58 to 63) are managed as standard
command (ASDU 45 to 50), i.e. the time tag is not used.
System information in monitor direction
(station specific parameter)

<70>: = End of initialisation M-EI-NA-1
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 37/92

System information in control direction
(station-specific parameter)

<100>: = Interrogation commands C-IC-NA-1

<101>: = Counter interrogation command C-CI-NA-1

<102>: = Read command C-RD-NA-1

<103>: = Clock synchronisation command C-CS-NA-1

<104>: = Test command C-TS-NA-1

<105>: = Reset process command C-RP-NA-1

<106>: = Delay acquisition command C-CD-NA-1

<107>: = Test command with time tag CP56time2a C-TS-TA-1
Parameter in control direction
(station specific parameter)

<110>: = Parameter of measured value, normalised value P-ME-NA-1

<111>: = Parameter of measured value, scaled value P-ME-NB-1

<112>: = Parameter of measured value, short floating point value P-ME-NC-1

<113>: = Parameter activation P-AC-NA-1
File transfer
(station specific parameter)

<120>: = File ready F-FR-NA-1

<121>: = Section ready F-SR-NA-1

<122>: = Call directory, select file, call file, call section F-SC-NA-1

<123>: = Last section, last segment F-LS-NA-1

<124>: = Ack file, ack section F-AF-NA-1

<125>: = Segment F-SG-NA-1

<126>: = Directory F-DR-TA-1
File transfer is only implemented in computer gateway.
Special use
(private range)

<136>: = Data base version M-DB-NA-1

<137>: = Regulating delay command C-RC-NB-1

<138>: = Regulating delay command with time tag CP56Time2a C-RC-TB-1
Type identifier and cause of transmission assignments
(station specific parameters)
X Mark type identification/cause of transmission combinations: X if used
Shaded boxes are not required
Blank = function or ASDU is not used
. Required in 1995 standard, suppressed in 2000.

C264/EN CT/C30 Communications

Page 38/92

MiCOM C264/C264C

Type ID Cause of transmission

1 2 3 4 5 6 7 8 9 10 11 12 13
20
to
36
37
to
41
44 45 46 47
<1> M_SP_NA_1 X X X X
<2> M_SP_TA_1
<3> M_DP_NA_1 X X X X
<4> M_DP_TA_1 .
<5> M_ST_NA_1 X X X X
<6> M_ST_TA_1 .
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1
<11> M_ME_NB_1 X X X X
<12> M_ME_TB_1
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X X
<31> M_DP_TB_1 X X
<32> M_ST_TB_1 X X
<33> M_BO_TB_1
<34> M_ME_TD_1 X
<35> M_ME_TE_1 X
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1 X
<40> M_EP_TF_1 X
<45> C_SC_NA_1 X X X X X X X X
<46> C_DC_NA_1 X X X X X X X X
<47> C_RC_NA_1 X X X X X X X X
<48> C_SE_NA_1 X X X X X X X X
<49> C_SE_NB_1 X X X X X X X X
<50> C_SE_NC_1 X X X X X X X X
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 39/92

Type ID Cause of transmission

1 2 3 4 5 6 7 8 9 10 11 12 13
20
to
36
37
to
41
44 45 46 47
<51> C_BO_NA_1
<58> C_SC_TA_1 X X X X X X X X
<59> C_DC_TA_1 X X X X X X X X
<60> C_RC_TA_1 X X X X X X X X
<61> C_SE_TA_1 X X X X X X X X
<62> C_SE_TB_1 X X X X X X X X
<63> C_SE_TC_1 X X X X X X X X
<64> C_BO_TA_1
<70> M_EI_NA_1 X
<100> C_IC_NA_1 X X X X X X X X
<101> C_CI_NA_1 X X X X X X
<102> C_RD_NA_1
<103> C_CS_NA_1 X X X X X
<104> C_TS_NA_1
<105> C_RP_NA_1
<106> C_CD_NA_1
<107> C_TS_TA_1 X X X
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1 X X
<121> F_SR_NA_1 X X
<122> F_SC_NA_1 X X X
<123> F_LS_NA_1 X X
<124> F_AF_NA_1 X X
<125> F_SG_NA_1 X X
<126> F_DR_TA_1 X X
<136> M_DB_NA_1
<137> C_RC_NB_1 X X X X X X X X
<138> C_RC_TB_1 X X X X X X X X
COT <45>:= Unknown Cause of Transmission
C264/EN CT/C30 Communications

Page 40/92

MiCOM C264/C264C

3.5.7 Basic application functions
Station initialisation
(Station specific parameter)

Remote initialisation
(Between Reset User ASDUs).
Cyclic data transmission
(Station specific parameter)

Cyclic data transmission
(Its the same cyclic for all data).
Read procedure
(Station specific parameter)

Read procedure
Spontaneous transmission
(Station-specific parameter)

Spontaneous transmission
Double transmission of information objects with cause of transmission spontaneous
(station specific parameter), each information is marked where both a Type ID without time
and corresponding Type ID with time are issued in response to a single spontaneous change
of a monitored object
The following type identifications may be transmitted in succession caused by a single status
change of an information object. The particular information object addresses for which
double transmission is enabled are defined in a project-specific list.

Single point information M_SP_NA_1, M_SP_TA_1, M_SP_TB_1 and
M_PS_NA_1

Double point information M_DP_NA_1, M_DP_TA_1 and M_DP_TB_1

Step position information M_ST_NA_1, M_ST_TA_1 and M_ST_TB_1

Bitstring of 32 bit M_BO_NA_1, M_BO_TA_1 and M_BO_TB_1
(if defined for a specific project)

Measured value, normalized value M_ME_NA_1, M_ME_TA_1, M_ME_ND_1 and
M_ME_TD_1

Measured value, scaled value M_ME_NB_1, M_ME_TB_1 and M_ME_TE_1

Measured value, short floating
point number
M_ME_NC_1, M_ME_TC_1 and M_ME_TF_1
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 41/92

General interrogation
(System or station-specific parameter)

Global

Group 1

Group 7

Group 13

Group 2

Group 8

Group 14

Group 3

Group 9

Group 15

Group 4

Group 10

Group 16

Group 5

Group 11

Group 6

Group 12 Information Object Addresses
assigned to each group must be
shown in a separate table
Counter General interrogation
(System or station specific parameter)

Global

Group 1

Group 3

Group 2

Group 4
Clock synchronisation
(Station specific parameter)

Clock synchronisation
Command transmission
(Object specific parameter)

Direct command transmission

Select and execute command

Direct set point command transmission

Select and execute set point
command


C-SE ACTTERM used


No additional definition

Short pulse duration (duration determined by a system parameter in the outstation)

Long pulse duration (duration determined by a system parameter in the outstation)

Persistent output
Transmission of integrated totals
(Station or object-specific parameter)

Mode A: local freeze with spontaneous.

Mode B: local freeze with counter.

Mode C: freeze and transmit by counter interrogation.

Mode D: freeze by counter interrogation command, frozen values reported.

C264/EN CT/C30 Communications

Page 42/92

MiCOM C264/C264C


Counter read

General request counter

Counter freeze without reset

Request counter group 1

Counter freeze with reset

Request counter group 2

Counter reset

Request counter group 3


Request counter group 4
Parameter loading
(Object-specific parameter)

Threshold value

Smoothing factor

Low limit for transmission of measured value

High limit for transmission of measured value
Parameter activation
(Object-specific parameter)

Act/Desactivation of persistent cyclic or periodic transmission of the addressed
object
Test procedure
(Station-specific parameter)

Test procedure
File transfer
(Station-specific parameter)
File transfer in monitor direction

Transparent file

Transmission of disturbance data of protection equipment

Transmission of sequences of events

Transmission of sequences of recorded analogue values
Only in computer gateway
File transfer in control direction

Transparent file
Background scan
(Station-specific parameter)

Background scan
Acquisition of transmission delay
(Station-specific parameter)

Acquisition of transmission delay
Management events priorities
(Station-specific parameter)

Digital Inputs, Step-position, Analogues Inputs and Integrated Totals, management
events priorities.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 43/92

Definition of time outs
Parameter Default
value
Remarks Selected
value
t
0
30s Time out of connection establishment configurable
t
1
15s Time out of send or test APDUs configurable
t
2
10s Time out for acknowledges in case of no
data messages t
2
< t
1

configurable
t
3
20s Time out for sending test frames in case
of a long idle state
configurable
Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s
Maximum number of outstanding I format APDUs k and latest acknowledge
Parameter Default
value
Remarks Selected
value
K 12 APDUs Maximum difference receive sequence
number to send state variable
configurable
W 8 APDUs Latest acknowledge after receiving w I-
format APDUs
configurable
Maximum range of values k: 1 to 255 APDUs, accuracy 1 APDU
Maximum range of values w: 1 to 255 APDUs, accuracy 1 APDU (Recommendation: w
should not exceed 2/3 of k).
Portnumber
Parameter Value Remarks
Portnumber 2404 In all cases, but configurable in Registry (only for Gateway
PC)
RFC 2200 suite
RFC 2200 is an official Internet Standard which describes the state of standardization of
protocols used in the Internet as determined by the Internet Architecture Board (IAB). It
offers a broad spectrum of actual standards used in the Internet. The suitable selection of
documents from RFC 2200 defined in this standard for given projects has to be chosen by
the user of this standard.

Ethernet 802.3

Serial X.21 interface

Other selection from RFC 2200
3.6 Slave DNP3 (TCP/IP) profile
See Slave DNP3 Profile
C264/EN CT/C30 Communications

Page 44/92

MiCOM C264/C264C

3.7 Slave Modbus (MODICON) profile
The purpose of this chapter is to describe the support of the MODBUS RTU protocol in the
PACiS system.
The MODBUS RTU protocol defines a message structure that controllers will recognise and
use. It describes the process a controller uses to request access to another device, how it
will respond to requests from other devices, and how errors will be detected.
3.7.1 Introducing MODBUS
Controllers communicate using a master-slave scheme, in which only the master (called
SCADA) can initiate requests. The MODBUS gateway is a slave device that responds by
supplying the requested data to the master.
Transmission mode used is the MODBUS RTU. Queries and replies have the same format
on a master-slave query-response cycle:
Query message from Server Response message from Slave
Function code Function code
Eight-bit Data bytes Eight-bit data bytes
Error check Error check
3.7.1.1 Device address field
The device address field of a message frame contains eight bits. Valid slave device
addresses in queries are in the range 0 247, but individual slave devices are assigned
addresses in the range 1- 247 and address 0 is reserved for broadcast operations.
The device address field of a message frame always identifies a slave (slave destination in
master to slave queries and slave source in slave to master responses).
If the gateway receives a frame with a broadcast device address, no reply is returned.
If the gateway receives a frame with a not expected device address, no reply is returned.
3.7.1.2 Function code field
The function code field of a message frame contains eight bits. Valid codes are in the range
1-255.
In master to slave queries, the function code identifies the operation that is to be executed by
the slave.
In slave to master responses, the function code is used to indicate either a normal (error-
free) response or a failure of the operation execution (called an exception response). For a
normal response, the slave simply echoes the original function code. For an exception
response, the slave returns a code that is equivalent to the original function code with its
MSB set to 1. In addition to the modification of the function code the slave places a unique
code into the data field of the response message, which identifies the reason for the
exception.
3.7.1.3 Data field
The data field of a message frame is constructed using sets of two hexadecimal digits, in the
range 00h to FFh.
In master to slave queries, the data field contains additional information to be used by the
slave to execute the operation defined by the function code.
In slave to master responses, the data field contains the data requested by the master.
The data field can be non-existent in some kind of messages.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 45/92

3.7.1.4 Error check field
The error-checking field contains a 16-bit value implemented as two 8-bit bytes [low
significant byte first]. The error check value is the result of a Cyclical Redundancy Check
[CRC] calculation performed on the message contents.
The gateway do not reply to corrupted data messages, i.e when the CRC is not correct or
when parity is not correct.
3.7.2 Slave responses
3.7.2.1 When the slave answers
Except for broadcast messages (no response in this case), when a master device sends a
query to a slave device it expects a normal response.
One of four possible events can occur from the masters query:
If the slave device receives the query without communication error, and can handle
the query normally, it returns a normal response.
If the slave does not receive the query due to a communication error, no response is
returned. The master program will process a timeout condition for query.
If the slave receives the query, but detect a communication error [ bad CRC or framing
error for example ], no response is returned. The master program will process a
timeout condition for query.
If the slave device receives the query without communication error, but cannot handle
it, the salve will return an exception response informing the master of the nature of the
error.
3.7.2.2 Exception Responses Codes
The exception code is sent as an 8-bit data, the range of valid codes is 1-8 in the protocol.
Supported exception responses codes are:
Code Name Meaning
01 ILLEGAL
FUNCTION
The function code received in the query is not an allowable
action for the slave.
An illegal function will be send in the main following cases:
An unsupported request [ see after, the table with the functions
supported ]
An unsupported sub-function code for Diagnostic request
02 ILLEGAL DATA
ADDRESS
The data address received in the query is not an allowable
address for the slave.
An illegal data address will be send in the main following
cases:
A read coil / input status starting to a none existent point in
configuration
A read holding registers / input registers starting to a none
existent point in configuration
A force coil / multiple coils request starting on an non-
configured address.
A preset single / multiple register(s) on an non-configured point
C264/EN CT/C30 Communications

Page 46/92

MiCOM C264/C264C

Code Name Meaning
03 ILLEGAL DATA
VALUE
A value contained in the query data field is not an allowable
value for the slave.
An illegal data value exception will be send in the main
following cases:
An illegal value received in force coils request (so value
different from FF00h and 0000h)
Illegal count value for multiple preset registers
04 SLAVE DEVICE
FAILURE
Not used in the gateway
05 ACKNOWLEDG
E
Not used in the gateway
06 SLAVE DEVICE
BUSY
Not used in the gateway
07 NEGATIVE
ACKNOWLEDG
E
The slave cannot perform the program function received in the
query.
A negative acknowledge will be send in the main following
cases:
Some errors in the frame
A read coil / input status on more than 2000 points
Force coil refused if command is incorrect or cannot be
executed (equipment absent, invalid, in local, )
08 MEMORY
PARITY ERROR
Not used in the gateway
3.7.3 Serial transmission mode
When messages are transmitted on standard MODBUS serial networks, each byte is sent
LSB first.
The format for each byte in MODBUS RTU mode is:
Coding system: 8-bit binary, hexadecimal 0-9, A-F
Two hexadecimal characters contained in each 8-bit field of
the message
Bits per Byte: 1 start bit8 data bits,
LSB sent first2 stop bits if no parity, or 1 parity bit and 1 stop
bit)
Error Check Field: Cyclical Redundancy Check (CRC-16)
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 47/92

3.7.4 MODBUS Functions
MODBUS defines 24 functions, valid codes are in the range of 1-24.
3.7.4.1 Supported functions
Code Function name Supported
01 READ COIL STATUS [ identical to function code 02 ] YES
02 READ INPUT STATUS [ identical to function code 01 ] YES
03 READ HOLDING REGISTERS [ identical to function code 04 ] YES
04 READ INPUT REGISTERS [ identical to function code 03 ] YES
05 FORCE SINGLE COIL YES
06 PRESET SINGLE REGISTER YES
07 READ EXCEPTION STATUS YES
08 DIAGNOSTICS [ only sub function 0 is supported ] YES
09 PROGRAM 484 NO
10 POLL 484 NO
11 FETCH COMM. EVENT CTR. NO
12 FETCH COMM. EVENT LOG NO
13 PROGRAM CONTROLLER NO
14 POLL CONTROLLER NO
15 FORCE MULTIPLE COILS [ identical to function code 05, one point only ] YES
16 PRESET MULTIPLE REGISTERS [ identical to function code 06, one
point only ]
YES
17 REPORT SLAVE ID NO
18 PROGRAM 884/M84 NO
19 RESET COMM. LINK NO
20 READ GENERAL REFERENCE NO
21 WRITE GENERAL REFERENCE NO
22 MASK WRITE 4X REGISTER NO
23 READ/WRITE 4X REGISTERS NO
24 READ FIFO QUEUE NO
3.7.4.2 General format of MODBUS functions
A query message typically contains some of the following 8-bit fields:
Starting Address Hi
Starting Address Lo
No. of Registers / Points Hi
No. of Registers / Points Lo
Force / Preset Data Hi
Force / Preset Data Lo
C264/EN CT/C30 Communications

Page 48/92

MiCOM C264/C264C

A response message typically contains some of the following fields:
Byte Count *
Data
Data Hi
Data Lo
No. of Registers / Points Hi
No. of Registers / Points Lo
Force / Preset Data Hi
Force / Preset Data Lo
(*) Byte Count Field:A Byte Count Field is used in slave responses to indicate the number of
8-bit bytes in the Data field; the value is exclusive of all other field contents, including the
Byte Count field.
3.7.4.3 MODBUS Data Addresses
Point addresses in the data field are 16-bit values in the range 0 65535 for each item type.
Thats means that you can have a coil item configured at address 100 for example, and a
holding register item configured at address 100 too.
Starting addresses in queries from SCADA may begin from address 0.
Example: request to read the 16 first coils on device 17.
Slave address 11
Function 01
Starting Address HI 00
Starting address LO 00
Number of points HI 00
Number of points LO 10
CRC XX
3.7.5 Function 01 / 02: Read Coil Status Read Input Status
The request function 01 or 02 reads the ON / OFF status of digital inputs in the slave. These
status may be any digital points (physical, automations, system information, grouping, ).
These two functions are the only way to read digital points with the MODBUS protocol.
Sequence of events, digital flags (validity, topical, ..) are not supported.
This is equal using the Read Coil Status request or the Read Input Status request.
Broadcast is not supported.
Addresses in frames may start from 065535.
Query:
Slave
Address
Function Code
= 01
Starting
Address
(H)
Starting
Address
(L)
No. of
Points (H)
No. of
Points
(L)
CRC
(L)
CRC
(H)
The query message specifies the starting coil address and the quantity of coils to be read.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 49/92

Response:
Slave
Address
Function
Code
= 01
Byte Count
= <nbytes>
Data Byte
#1
Data Byte
#i
Data Byte
#nbytes
CRC
(L)
CRC
(H)
The coil or status in the response message is packed as one coil per bit of the data field.
Digital inputs can be single (coded on one bit) or double (in this case 1 or 2 bits defined in
configuration).
For Single DI or Double DI coded on one bit, status is indicated as: 1 = ON, 0 = OFF.
For double DI coded on two bits, status indicates: [open contact, closed contact] = [0,1] for
open, [1,0] for closed, [0,0] for jammed], [0,1] for the other states
The less significant bit of the first data byte contains the coil addressed in the query. The
other coils follow toward the high order end of this byte, and from 'low order to high order' in
subsequent bytes, as described in the frame example.
Important notes:
1. If the returned coil quantity is not a multiple of eight, the remaining bits in the final byte
will be padded with zeros (toward the high order end of the byte). The Byte Count
Field specifies the quantity of complete bytes of data.
For easiest understanding between the gateway and the SCADA, it is recommended
to read a number of points which is a multiple of 8.
2. If the starting address is not a point in configuration, the message will be not be
accepted, and an error exception 2 will be returned.
3. If the starting address is in configuration and if there is some holes (addresses not in
configuration) theses holes will be padded with 0 (i.e value OFF).
3.7.6 Function 03 / 04: Read Holding Registers / Input Registers
The request function 03 or 04 reads the values of analogue inputs, tap position and counters
values in the slave.
In case of tap position and counters values, only natural coding is supported.
These two functions are the only way to read registers points with the MODBUS protocol.
Flags (validity, topical, ..) are not supported in the MODBUS protocol base.
This is equal using the Read Holding Registers request or the Read Input Registers request.
Broadcast is not supported.
Addresses in frames may start from 065535.
Query:
Slave
Address
Function Code
= 03
Starting
Address
(H)
Starting
Address
(L)
No. of
Points (H)
No. of
Points
(L)
CRC
(L)
CRC
(H)
The query message specifies the starting register and the quantity of registers to be read.
Response:
Slave
address
Function
code
= 03
Byte
Count
=
<nbytes>
Data
(H)
#1
Data
(L)
#1
Data
(H)
#i
Data
(L)
#i
Data
(H)
#nbytes/ 2
Data
(L)
#nbytes/
2
CRC
(L)
CRC
(H)
The register data in the response message are packed as two bytes per register, with the
binary contents right justified within each byte. For each register, the first byte contains the
high order bits and the second contains the low order bits.
C264/EN CT/C30 Communications

Page 50/92

MiCOM C264/C264C

Important notes:
1. If the starting address is not a point in configuration, the message will be not be
accepted, and an error exception 2 will be returned.
2. If the starting address is in configuration and if there is some holes (addresses not in
configuration) theses holes will be padded with the value 0
3.7.6.1 Signed normalised coding
The signed normalised coding is used to encode the 16 bits-registers. Analogue maximal
value will be coded 7FFFh (decimal value + 32767), and minimal value will be coded 8000h
(decimal value 32768).
For this mode, the gateway may now code the value on 8 to 16 bits [ low part of the register
will be used ]. But, 16 bits is normally the standard to use the full scale conversion.
Example:
in configuration the maximal value for an analogue point is +3000 and minimum value for
this analogue is 0.
That means that when the analogue is received with value 0 from the system, the gateway
will send to the SCADA the register with 8000h value. If this analogue is equal to the
maximal value +3000, the value sent to the SCADA is 7FFFh. Calculation is linear for the
coding between the min and max values.
3.7.6.2 Unsigned normalised coding
The unsigned normalised coding is used to encode the 16 bits-registers. Analogue maximal
value will be coded FFFFh (decimal value + 65535), and minimal value will be coded 0000h
(decimal value 0).
For this mode, the gateway may now code the value on 8 to 16 bits [ low part of the register
will be used ]. But, 16 bits is normally the standard to use the full scale conversion.
Example:
in configuration the maximal value for an analogue point is +3000 and minimum value for
this analogue is 0.
That means that when the analogue is received with value 0 from the system, the gateway
will send to the SCADA the register with 0h value. If this analogue is equal to the maximal
value +3000, the value sent to the SCADA is FFFFh. Calculation is linear for the coding
between the min and max values.
3.7.6.3 Natural coding
The natural coding is used to encode data without any calculation. Thats means that integer
value will be send.
Example:
if the gateway receives the value 10.xxxx, the value 0Ah will be set in the appropriate
register. The gateway receives the value 10,xxxx the value FFF6h will be coded. Sent
values are considered as signed values which are included between 32768 and +32767.
When minimum and maximum values are reached values FFF6h and FFFFh are
respectively sent.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 51/92

3.7.7 Function 05: Force Single Coil
This request function 05 is used to realise a control on an address point.
When broadcast, the function forces the same coil reference in all attached slaves.
Query:
Slave
Address
Function Code
= 05
Point
Address
(H)
Point
Address
(L)
Force
Data
(H)
Force
Data
(L)
CRC
(L)
CRC
(H)
The query message specifies the coil reference to be forced. Points addresses are between
065535. The requested ON / OFF state is specified by a constant in the query data field.
A value of FF00h requests the coil to be ON.
A value of 0000h requests it to be OFF.
Response:
Slave
Address
Function Code
= 05
Point
Address
(H)
Point
Address
(L)
Force
Data
(H)
Force
Data
(L)
CRC
(L)
CRC
(H)
The normal response is an echo of the query, returned after the command has been sent to
the system.
NOTE: If value is incorrect, or if the control is refused for any reason (equipment absent,
equipment present and in local mode, equipment invalid, ) an exception error 7 is
returned.
3.7.8 Function 06: Preset single register
This request function 06 is used to preset a value in a register.
Query:
Slave
Address
Function Code
= 06
Point
Address
(H)
Point
Address
(L)
Force
Data
(H)
Force
Data
(L)
CRC
(L)
CRC
(H)
The query message specifies the register address to be preset. Points addresses are
between 065535. The requested value is specified by in the query data field.
Response:
Slave
Address
Function Code
= 06
Point
Address
(H)
Point
Address
(L)
Force
Data
(H)
Force
Data
(L)
CRC
(L)
CRC
(H)
The normal response is an echo of the query, returned after the register has been preset.
NOTE: Only natural setpoints are managed by this function (no scaling is done)
C264/EN CT/C30 Communications

Page 52/92

MiCOM C264/C264C

3.7.9 Function 08: Diagnostic [Sub-function 0 only]
This request function 08 sub-function 0 is used to test the transmission.
Query:
Slave
Address
Function Code
= 08
Sub Function
code
(H)
Sub Function
code
(L)
Data
(H)
Data
(L)
CRC
(L)
CRC
(H)
The query message specifies the data that will be echoed.
Response:
Slave
Address
Function Code
= 08
Sub Function
code
(H)
Sub Function
code
(L)
Echoed
Data
(H)
Echoed
Data
(L)
CRC
(L)
CRC
(H)
The normal response is an echo of the query with the same data send in the request.
NOTE: If the sub-function is different from 0, an exception error illegal function is
returned.
3.7.10 Function 15: Force Multiple Coils
Normally, this request function 15 is used to realise a control on several contiguous
addresses.
This function can be used, but only one control can be send at the same time.
NOTE: Only a count number equal to 1 is allowed, otherwise an exception error 3 will be
replied.
3.7.11 Function 16: Preset multiple registers
Normally, this request function 16 is used to preset on several contiguous addresses.
This function can be used, but only one preset can be send at the same time.
NOTE: Only a count number equal to 1 is allowed, otherwise an exception error 3 will be
replied.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 53/92

4. IED COMMUNICATION
4.1 Overview
Different types of IEDs are connected to a MiCOM C264 through networks using various
legacy protocols:
1. IEC 60870-5-103 (T103)
2. Modbus
3. DNP3
4. IEC 60870-5-101 (T101)
All these networks use a serial link to communicate with IEDs. As there are several serial
links on a MiCOM C264, it is possible to have:
Different protocols running in parallel on different links
The same protocol on several links
All these networks use a Master / Slave protocol where the MiCOM C264 is the Master. So,
there are two kinds of exchange:
Request / reply
Master emits a request to a slave of its choice and wait for the response. Between
master and slave, only one transaction can be initiated. Then, in order to transmit the
same request to two different slaves, two transactions are required.
Broadcast
Master transmits a command to all of slaves connected to the network. They perform it
without send any response.
Common features to all IEDs and all protocols are specified below in the paragraph 0
Specific features to each protocol are specified in subsequent paragraphs.
4.2 IED Common functionality
4.2.1 Interface to IEDs
4.2.1.1 Input
Data Note
Digital input Treated
Measurement Treated
Default position Depending on the protocol
Counter Treated
Tap position Treated
Control acknowledgement Treated
Setpoint acknowledgement Treated
Alarm Not Treated
Disturbance record Depending on the protocol
Tunnelling Frame response Depending on the protocol
C264/EN CT/C30 Communications

Page 54/92

MiCOM C264/C264C

4.2.1.2 Output
Data Note
Control Treated
Setpoint Depending on the protocol
Alarm acknowledgement Not Treated
Tunnelling Frame question Depending on the protocol
Time synchronisation Treated
4.2.2 Behaviour
4.2.2.1 Network supervision
The number of networks and IEDs is known by configuration.
Each network is managed independently of the other networks.
The management of a network consists of:
Initialising the serial line
At start-up of the network monitoring, the serial line has to be initialised according to
the configuration.
Synchronising the IEDs connected to the network.
Polling the IEDs
This polling allows to connect IEDs, to exchange data with IEDs and to monitor the
connection of IEDs.
Performing the monitoring of the each IED connected to this network.
Each IED is managed independently of the other IEDs. The state of each IED, i.e.
connected, disconnected, is monitored and every change of state is signalled to the
MiCOM C264 management function.
4.2.2.2 Time synchronisation
If the network has to be synchronised, the synchronisation is performed in one of two ways:
1. At connection of an IED, a synchronisation frame is sent to this IED.
2. Regularly, a synchronisation frame is broadcasted on the network.
When this is supported by the IEDs, the calculation of the transmission delay is performed.
NOTE: The synchronisation is a network attribute [not an IED attribute]. That means, that
the synchronisation is either sent to all the IEDs, or is not sent.
4.2.2.3 Polling of IED
Once the line is initialised, the MiCOM C264 has to try to connect IEDs and to manage
exchanges of data with each IEDs.
Thats done by polling: cyclically the MiCOM C264 questions each IED one after the other.
The polling manages the following items:
Sequencing the questioning of the IEDs
Connection of an IED [when a disconnected IED responds, it becomes Connected]
Repetitions [if an IED doesnt answer to a request, this request will be repeated the
next cycle]
Disconnection of an IED [after N

questions without answer, an IED becomes
Disconnected]
Maximum time to wait for a response
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 55/92

Minimum time between two frames on the network
Sending functional requests to IEDs
Optimisation of polling may be done according to the followings ideas:
When an IED is disconnected, it may be questioned only time to time [not all cycles]
When an IED has important data to transmit [DI], it may be questioned successively
several times
The maximum time to wait an answer may be configurable
The polling sequencing may be only stopped in the two following cases:
Time synchronisation
Synchronisation is done periodically by sending a broadcast frame. After the
synchronisation frame has been sent, the polling starts again.
Remote control to transmit to a slave
Control is a priority request. So, when a control must be sent to an IED, the polling is
stopped, the control is sent and the polling starts again.
4.2.2.4 Monitoring of an IED
Each IED is managed according to the following graph:
NOT_
INITIALISED
DISCON-
NECTED
CONNECTED
NOT_SYNCHRONISED
OUT_OF_
SERVICE
0
1
2
2
3
4
1
IN_SERVICE
GI
C0109ENa
NORMAL
TUNNELING
DISTUR-
BANCE
8
7 6
5
11
10
9
12

Description of the possible states of an IED:
NOT_INITIALISED: Thats the initial state of an IED. The MiCOM C264 polls the IED
every cycle in order to connect it.
If the IED responds, it becomes CONNECTED 2 .
If after some attempts the IED doesnt respond, it becomes DISCONNECTED 1 .
DISCONNECTED: The IED is disconnected. The MiCOM C264 polls the IED time to
time in order to connect it.
If the IED responds, it becomes CONNECTED 2 .
C264/EN CT/C30 Communications

Page 56/92

MiCOM C264/C264C

CONNECTED: The IED is connected. This state includes several states. When an IED
becomes Connected, it goes to the NOT_SYNCHRONISED state.
NOT_SYNCHRONISED: The IED has just became Connected. It must be
synchronised. Once it is synchronised, according to the information given by the IED,
it becomes IN_SERVICE 3 or OUT_OF_SERVICE 4 . (This information isnt
available for some protocols. In this case, the IED becomes IN_SERVICE by default).
OUT_OF_SERVICE: The IED is connected and says it is Out of service. The MiCOM
C264 polls the IED time to time waiting for the IED to become IN_SERVICE 5 .
IN_SERVICE: The IED is connected and it says it is In Service. This state includes
several states. When an IED becomes In Service, it goes to the GI state.
GI: The IED is In Service and a General Interrogation is going on.
For each information received during the GI, the information becomes available and its
state is transmitted to the application [see below for more information on GI
treatment].
At the end of the GI, the IED goes in the NORMAL state 6 .
NORMAL: The IED is In Service and the monitoring of DI, AO and DO are performed.
If a disturbance record becomes present and the MiCOM C264 have enough places to
store the file, the IED goes in the DISTURBANCE state 8 .
If a request to open a tunnel for the IED arrives, it is accepted and the IED goes in the
TUNNELING state 10 .
Time to Time, a GI may be done. In this case the IED goes in the GI state 7 .
DISTURBANCE: The IED is In Service and a disturbance record is being uploaded.
When the uploading of the disturbance file is finished, the IED goes back in the
NORMAL state 9 .
TUNNELING: Tunnelling communication is going on.
When the Tunnelling communication is finished, the IED goes back in the NORMAL
state 9 .
That shows that GI, Disturbance uploading and tunnelling are mutually exclusive. That is
done for 2 reasons:
To limit the overload of the network
To suppress interaction between Tunnelling access and MiCOM C264 access.
Description of the transitions between states:
0: Initialisation of the transmission.
1: The IED becomes DISCONNECTED.
The disconnection is signalled to the application.
Every data normally received from the IED is marked as unknown and a change of
state is signalled for each one.
2: The IED becomes CONNECTED.
A synchronisation frame is sent to it and after, the status of the IED is red.
3: The status of the IED is indicates the IED is In Service.
A General Interrogation is activated.
4: The status of the IED is indicates the IED is Out Of Service.
5: see 3
6: The general Interrogation is finished.
7: A general Interrogation is activated [cyclical GI].
8: A disturbance file is available in the IED and there are enough places to store it in
the MiCOM C264.
A disturbance uploading is activated.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 57/92

9: End of disturbance file upload.
10: A request to open a communication channel throw tunnelling is received.
11: End of tunnelled communication.
12: Request to send a control command to the IED.
The polling is interrupted and the command is sent as soon as possible.
Initialisation procedure
Initially, all data normally received from an IED is marked as unknown. When an IED is first
connected, a general interrogation request is sent. A table is updated with data received in
response to the general interrogation. When the general interrogation is finished, the content
of the table is sent to the processing functions: binary inputs processing and measurement
treatment. Messages received subsequently are checked against the content of the table
and a change of state message is sent when there is a difference.
General interrogation
A general interrogation is performed:
at initialisation time
upon reconnection
Cyclically [optional]
Messages received during the initial general interrogation are not sent to the processing
function. Instead the content of the table is sent at the end of the sequence.
Messages received during a general interrogation performed after the initialisation sequence
are sent immediately to the processing function
Some IEDs send a message indicating the end of the response to a general interrogation.
When this message is received, the sequence is considered as finished. If the IED does not
send this message, the MiCOM C264 must check that all data are received.
If all data are not received within a given time another request is sent. This process can be
repeated N times. If the response is still not received after N times a fault message is sent,
however the IED is still polled.
Disturbance File Management
The following rules apply for the management of the Disturbance Files of the IED:
For each IED, there is an information in the configuration indicating if automatic upload
of Disturbance File has to be done. This indication may be overwritten by a command
from the application.
When the MiCOM C264 detects that an IED has a Disturbance File ready to be
uploaded and that automatic upload is enabled, it uploads and stores it. When the
upload is finished, an indication is sent to the Upper transmission management to
inform it that a Disturbance file is ready.
When there isnt enough places to store a Disturbance File, the oldest file is deleted.
The upper transmission management can only get Disturbance files stored in the
MiCOM C264. Once the upper transmission management has treated a file it is
deleted.
C264/EN CT/C30 Communications

Page 58/92

MiCOM C264/C264C

4.2.3 Data received from IEDs
After the initialisation sequence, IEDs are polled regularly. Depending on the type of IED the
current state of data can be received as state messages, or as change of state messages.
When a state message is received, the content is checked against the table and if there is a
difference a message is sent to processing functions and the table is updated. In this case,
the MiCOM C264 time stamps the change.
When a change of state message is received, the table is updated and the message is
transmitted to processing functions. In this case, the time stamping is made by the IED.
The data, which can be received from IEDs, are detailed in the paragraphs below.
4.2.3.1 Digital inputs
Digital inputs can be received as states or as changes of state. The choice between state
and change of state depends on the IED and on the protocol. This is known by configuration.
Even if digital inputs are received as change of state, it is still possible to request data as
states for general interrogations.
The conversion from digital input to binary input is performed by the binary input processing
function. A digital input can be associated with a single point or a double point.
4.2.3.2 Measurements
Measurements can be received in various formats: float, binary, BCD, etc. The received
value is converted into an internal format, which is common to all measurements in the
MiCOM C264.
Measurements can be received as periodical messages or as changes of state: variation,
threshold, and invalidity.
A message is sent to the processing function whenever a measurement is received from an
IED.
4.2.3.3 Counters
Counters are treated for DNP3.0
4.2.3.4 Tap position
Tap position are treated like measurements
4.2.3.5 Disturbance File
MiCOM C264 stores disturbance files as they are sent by IEDs without control of the format
of the Disturbance Files (Comtrade, ).
4.2.4 Data sent to IEDs
After the initialisation sequence, data can be sent to IEDs. The type of data, which can be
sent to IEDs, is described in subsequent paragraphs.
4.2.4.1 Controls
Controls are priority message. The polling sequence must be interrupted in order to send the
control as soon as possible.
Not all IEDs send control acknowledgement. If they do not, an acknowledgement is
simulated and sent to the handling of control sequences function.
When an IED is disconnected [or out of service] a negative acknowledgement is sent.
If the command is a select before operate command, the application must send two
commands to the transmission software: the first one for the selection and the second for the
execution.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 59/92

If the command is a double command, the application send one order, and depending on the
protocol, two cases have to be distinguished:
The Double command is referenced only once in the IED Mapping. In this case, if an
OPEN (respectively CLOSE) command is received from the application, the master
send an OFF (respectively ON) order to the IED at the corresponding address.
The double command is referenced by two addresses in the IED Mapping: one refers
to the Open Contact and the other to the Close Contact. In this case, if an OPEN
(respectively CLOSE) command is received from the application, the master sends an
ON order to the IED, at the address corresponding to the Open Contact (respectively
Close Contact).
4.2.4.2 Setpoints
SP controls are priority message. The polling sequence must be interrupted in order to send
the SP control as soon as possible.
Not all IEDs send SP control acknowledgement. If they do not, an acknowledgement is
simulated and sent to the handling of SP control sequences function.
When an IED is disconnected [or out of service] a negative acknowledgement is sent.
If the SP commands are always "direct execute" command (no select before operate).
For an IED, only one SP command is possible at a time.
4.2.5 Tunnelling
The serial tunnelling enable to connect a lap top computer which run an IED setting
software to a serial (RS232) line of the PACiS computer in order to communicate with an
IED connected to a legacy bus of the PACiS computer.
C0149ENa
Lap Top
C264
Computer
IED
RS232 link
dedicated to
serial tunneling
Legacy bus
(Modbus, T103)

All serial RS232 lines of the computer including the port onto the front panel can be used
for serial tunnelling.
The choice of the serial line to be used for serial tunnelling is done by the computer
configuration.
The cable dedicated to tunnelling must be disconnected from the front panel when
tunnelling is not used.
4.2.5.1 Interface through the tunnelling serial line
The tunnelling serial line gives access to a user dialog.
This dialog enables an user to give commands to the Tunnelling RS232 software.
Commands are ASCII string terminated by (code ASCII 13H) and are case sensitive.
A command is executed at the reception of the character. An ASCII message is sent in
response, and a prompt message may be sent in order to indicate the computer is ready to
treat a new command.
If a command is unknown, an error message Unknown command ! is sent.
C264/EN CT/C30 Communications

Page 60/92

MiCOM C264/C264C

List of the available commands:
TunRSLines: List the legacy lines for which tunnelling is enabled.
Each line of the list corresponds to a legacy line for which tunnelling is enabled and have the
following format:
Line <line Number>: <Protocol>
If there is not any legacy line available for Tunnelling, the response is No line available for
serial tunnelling.
TunRSIed nl: List the IED of a legacy line and their state [ln = line number].
The first line of the response gives information on the line:
Line <line Number>: <Protocol>
Each following line of the response corresponds to an IED and have the following format:
IED <Address>: <State>
Where <State> can be available or not available
If the line isnt available for Tunnelling, the response is The line nl is not available for serial
tunnelling.
TunRSStart ln, ad: Start a serial tunnelling session with the specified legacy line
[ln = legacy line number; ad = IED address].
The response is either Serial Tunnelling started or an error message explaining why the
command cant be executed.
If the response is Serial Tunnelling started, legacy frames are awaited on the serial
Tunnelling link.
TunRSStop: Stop the current serial tunnelling session.
The response is Serial Tunnelling stopped.
4.2.5.2 C264 Behaviour
Once the TunRSStart is accepted, the computer waits for Legacy frames on the serial
Tunnelling line.
Received frames are sent to the target legacy IED.
Response frames coming from the IED are sent back on the serial Tunnelling line.
If a tunnelling session is already running, the current session is ended and a new one is
started.
4.2.5.3 Procedure of use of the serial tunnelling
Connect a LapTop to the computer with a RS232 serial cable
(On the computer, the cable is connected to the serial line dedicated to the tunnelling)
Launch Hyperterminal on the LapTop
Enter the serial tunnelling starting command [TunRSStart]
The computer answers Serial Tunnelling started.
Quit Hyperterminal (be sure to close the connection)
Launch an IED setting Software [e.g.: MiCOM S1] on the LapTop
Execute settings actions with the setting Software (that implies exchange of legacy
frames between the setting software and the IED through the computer)
Quit the setting Software
Launch Hyperterminal on the LapTop
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 61/92

Enter the serial tunnelling stopping command [TunRSStop]
The computer answers Serial Tunnelling stopped.
Quit Hyperterminal (be sure to close the connection)
4.2.5.4 End of a serial tunnelling session
As described above, a serial tunnelling session may be ended by the TunRSStop
command.
If the user forgets to end the tunnelling session with the TunRSStop command, the session
will be automatically ended after expiry of a deadline - of about 2 minutes - without
exchange.
4.2.5.5 Fault case behaviours
If the questioned IED does not answer, no frame of answer is returned to the setting
Software.
If the setting software sends a new question frame [or repeats the last frame] whereas
the computer is still awaiting the answer from the IED, this new frame is ignored.
4.2.5.6 Serial tunnelling through a modem
C0150ENa
Lap Top
C264
Computer
IED
RS232 link
dedicated to serial
tunneling
Legacy bus
(Modbus,
T103)
Modem
Modem
Specialised
or RTC line

If modems are well configured, this operating mode is transparent for the computer and no
specific management is needed in the software.
4.2.5.7 Tunnelling limits and Performances
The legacy protocols supported [protocols for which serial tunnelling is available] are the
following:
MODBUS
T103
The line to be used for serial tunnelling can be set through computer configuration.
If The serial tunnelling line is frontal RS232, its automatically configured:
19200Bd, 8 bits data, no parity, 1 stop bit.
For the other ports (COM1 to COM4), it follows the configuration parameters.
Only RS232 mode is supported.
C264/EN CT/C30 Communications

Page 62/92

MiCOM C264/C264C

4.2.6 Limits and Performances
The number of serial links available limits the number of legacy network that can be
managed simultaneously by a MiCOM C264.
The maximum number of IED that can be managed for a network is 16.
Performance depends on the protocol used and on the number of IEDs connected to
each Network.
4.3 MODBUS communication
4.3.1 Finality
MODBUS is a legacy bus master/slave protocol that is used by many devices such as
relays, MiCOM C264s or monitoring devices. The aim of this chapter is not to describe the
protocol itself and its mechanisms (other documents and norms are there for that) but to give
the specificity of the functions that will be implemented in the MiCOM C264. These are the
MODBUS function numbers that will be used, the way in which each type of data will be
internally or externally updated, the general mechanisms used for the time synchronisation
and the configuration needs.
As the MiCOM C264 is the master on the legacy bus - regards to protections and IEDs - this
protocol is referenced as Master Modbus in the MiCOM C264.
4.3.2 Interface to IEDs
The following MODBUS functions are implemented in the MiCOM C264:
Function
number
Sub-code Used for Commentary
1 2 / Read DIs Read N bits
3 4 / Read DIs / MEAS /
Disturbance files
Read N words
5 / Write CO Write 1 bit
15 / Write CO Write N bits
This function could be used with the
following restriction: you can only write
COs one after the other.
7 / Polling Read status byte
This function is used for detecting a DI
change of state, the presence of
disturbance files (Areva IEDs)
8 0 Polling Echo
This function could be used for
detecting if a device is connected or
not.
6 / Eventually for
tunnelling
Write 1 word
16 / Eventually for
tunnelling
Write N words
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 63/92

4.3.3 Behaviour
4.3.3.1 Polling
During a polling procedure, each slave is polled one after the other. This means that the
master waits for the answer to a request sent to a device before sending a new request to
the same or an other device.
There will be 2 types of polling:
the polling performed by the application for the measurements and the digital inputs
a low level polling used for detecting if a device is present or not.
If an IED does not correctly answer after a defined timeout (configured), the request is resent
by the MiCOM C264. If the IED do not correctly answer after a defined number of retries
(configured) it is considered as disconnected. Then it is polled regularly (not too often) to
eventually be reconnected to the network.
4.3.4 Data received from IEDs
4.3.4.1 Measurements
The processing applied to the measurements is the same for all devices.
The application reads the measurements by polling the device at a defined frequency.
We define a block of measurements as a set of measurements that have been configured at
consecutive addresses. As a result, to improve the polling performance, all the
measurements of a block will be read thanks to just one exchange having regard to the
number of measurements to be read.
4.3.4.2 Digital Inputs
The processing applied to the DIs depends on the IEDs. Each change of a DI is dated, either
in the MiCOM C264 or in the IED, depending on the IED type.
We define a block of DIs as a set of DIs that have been configured at consecutive
addresses. As a result, to improve the polling performance, all the DIs of a block will be read
thanks to just one exchange having regard to the number of DIs to be read.
Processing for generic IEDs
By default, the DI blocks are regularly polled by the application. Then the application
compares the state of each DI with the previous state. So the MiCOM C264 itself performs
the time stamping of a change of state.
Processing for Areva IEDs
The status byte-taking place in an Areva IED contains the information indicating that events
(DI changes) are present. As a result, the status byte is regularly polled by the link layer
through a low level polling and compared with the previous one. If a change is detected, the
master reads the event queue inside the IED, checks which data have changed, checks if
they have been configured and then reads the information itself. Notice that in this case, the
DI changes are dated in the IED and the MiCOM C264 downloads their date and time.
4.3.4.3 Disturbance files
Disturbance files are only treated for devices that conform to the MODBUS Areva rules and,
if needed for other devices (specific developments).
C264/EN CT/C30 Communications

Page 64/92

MiCOM C264/C264C

4.3.5 Data sent to IEDs
4.3.5.1 Connection check
Generic IEDs
Each device on the network is regularly polled with a specific frame to know if it is connected
or not. This frame could be the status byte polling frame if it exists, the measurement polling
frame if it exists, the BI polling frame if it exists, the mirror frame if it has been implemented
in the device or a user defined frame. This choice is performed through the configuration
options.
Areva IEDs
The Read status byte frame is used for checking the connection of the device.
4.3.5.2 Time synchronisation
Preliminary remark: All the devices connected to a given network must have the same
synchronisation procedure (address and time and date format)
because the synchronisation is performed through a broadcast frame.
There will be three types of synchronisation depending on a configuration parameter:
No synchronisation;
Areva synchronisation: date and time conform to the inverted IEC 870-5-4
CP56Time2a format and is set at address 800h;
SEPAM synchronisation: date and time conform to the SEPAM (Merlin Gerin)
documentation ( SEPAM1000+S20, SEPAM1000+S40, PM500, PM650, SEPAM2000)
No calculation of the transmission delay is performed.
4.3.5.3 Commands
Commands are sent to the IED and have the highest priority level. They come from the
application and have to be transmitted to the destination device as fast as possible. An
acknowledge (which is the answer from the IED to the MiCOM C264 in the MODBUS
exchange) is waited by the application. If the acknowledge is not received after a defined
timeout, you consider that the command has not been taken into account.
4.3.6 Error management
The MODBUS protocol handles a mechanism of exception answer. This means that an IED
could answer with an exception frame if it does not understand the request. There are
different exception codes:
Exception
code
Meaning Processing performed by the master
01 Illegal function Send a Configuration error message to the
application and continue
02 Illegal data address Send a Configuration error message to the
application and continue
03 Illegal data value Send a Configuration error message to the
application and continue
04 Slave device failure Send a IED error message to the application
05 IED busy because of a
long treatment duration
Retry after a defined temporisation
06 IED busy Retry after a defined temporisation
07 Treatment not possible Send a IED error message to the application
08 IED memory parity error Send a IED error message to the application
4.3.7 Limits and Performances
The performances depend a lot on the number of devices connected on the network. It is
advised to connect devices that have similar performance level on a given network, i.e. the
same reply time for instance.
Each device on a MODBUS network must have the same synchronisation mode.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 65/92

4.4 DNP 3.0 Communication
4.4.1 Finality
The purpose of this chapter is not to describe the DNP3 protocol but to specify the use of the
DNP3 protocol on a legacy bus of the MiCOM C264.
As the MiCOM C264 is the master on the legacy bus - regards to protections and IEDs - this
protocol is referenced as Master DNP3 in the MiCOM C264.
Here are described:
Specific behaviours attached to the protocol DNP3
Restriction and enhancement
Part of the DNP3 protocol used and not used
4.4.2 Interface to IEDs
4.4.2.1 Input
Object Variation Data GI Polling Function
01 0 Static BI [1] READ
02 0 BI Event [1] READ
20 0 Static Counter [1] READ
22 0 Counter Event [1] READ
30 0 Static Measurement [1] READ
32 0 Measurement Event [1] READ
60 01 Class 0 [1] READ
60 02, 03, 04 Class 1,2,3 [1] READ
NOTE: BI, Measurement and Counter are polled with the variation 0. That means
that all variations are required.
All other DNP3 objects are not treated.
4.4.2.2 Output
Object Variation Data Function Note
12 01 Command: Control
Relay Output Block
[3] SELECT Treated
[4] OPERATE Treated
[5] DIRECT OPERATE Treated
[4] OPERATE Treated
[5] DIRECT OPERATE Treated
50 01 Time and Date [2] WRITE Treated
The DNP3 Master manages both direct control Command and Select before Operate for
digital control only.
When operate command is received from application, the Master checks in database to
know if the command is:
1. An execute command, which belongs to a SBO Control: OPERATE function is used in
this case.
2. A direct control: DIRECT OPERATE function is used is this case
C264/EN CT/C30 Communications

Page 66/92

MiCOM C264/C264C

4.4.3 Behaviour
Synchronisation:
The Master DNP3 is always synchronised by the MiCOM C264. No calculation of
the transmission delay is performed.
The DNP3 object used to synchronise IEDs is Write Date and Time Request
(Object 50, Variation 01).
Synchronisation is performed first at connection of an IED.
Then, synchronisation is sent cyclically to all the IEDs.
Initialisation:
To connect an IED, a Reset CU (function 0) frame is sent to the IED.
When the response is OK, the Master DNP3 send a message to the application to
tell that connection step is passed.
Next step is General Interrogation
General Interrogation:
When the IED is connected, the MiCOM C264 ask for static data state and value with
a sequence of:
Read BI,
Read Measurement,
Read TPI,
Read Counter
This Sequence is the General Interrogation. Next step is Polling
Polling:
The polling cycle depends on the configuration:
Poll BI, Poll Measurement, Poll counter, Poll BI .
Poll C1, Poll C2, Poll C3, Poll C1
The polling cycle must be interrupted at minimum in the two following case:
Clock Synchronisation
Remote control
Event acquisition:
Event occurs spontaneously. The slave device waits for being polled by the master.
IED monitoring:
A General Interrogation may be done after connection of an IED
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 67/92

4.4.4 Data received from IEDs
Digital inputs:
A DI is identified by an Index, associated to a couple Object + Variation which
identify the type of data.
Digital inputs which are received as changes of state are identified by the DNP3
object number 02
Digital inputs which are received as static data are identified by the DNP3 object
number 01
Measurements:
A Measurement is identified by an Index, associated to a couple Object +
Variation which identify the type of data.
Both analogue and numeric measurements are treated
Measurements which are received as changes of state are identified by the DNP3
object number 32
Measurements which are received as static data are identified by the DNP3 object
number 30
Counters:
A Counter is identified by an Index, associated to a couple Object + Variation
which identify the type of data.
Counters which are received as changes of state are identified by the DNP3
object number 22
Counters which are received as static data are identified by the DNP3 object
number 20
4.4.5 Data sent to IEDs
Controls:
A Control is identified by an Index, associated to a couple Object + Variation
which identify the type of data.
In case of basic control (Set, Reset, Trip, Close), DNP3 object 12 is used with the
Variation 01
C264/EN CT/C30 Communications

Page 68/92

MiCOM C264/C264C

4.4.6 Master DNP3.0 Profile
DNP V3.00 Device Profile
Vendor Name: AREVA T&D
Device Name: PACIS Computer
Highest DNP Level Supported:
For Requests Level 3
For Responses Level 3
Device Function:
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
supported:
______________________________________________________________________________
______________________________________________________________________________
Maximum Data Link Frame Size (octets):
Transmitted 292

Received: (must be 292)
Maximum Application Fragment Size (octets):
Transmitted 2048
(configurable: 15 to 2048 octects)
Received 2048
Maximum Data Link Re-tries:
None
Fixed at _______________________
Configurable, range 1 to 10
Maximum Application Layer Re-tries:
None
Configurable, range ___ to _____
(Fixed is not permitted)
Requires Data Link Layer Confirmation:
Never
Always
Sometimes If Sometimes, when?

Configurable If Configurable, how?
User option to set Data Link Confirmation to:
Always device will always request Data Link Confirmations.
Multi-packet only the device will request Data Link Confirmations when
sending multi-packet responses.
Never the device will never request Data Link Confirmations.
Requires Application Layer Confirmation:
Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes _______ If 'Sometimes', when?

Configurable If 'Configurable', how? ____________________________________________
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 69/92

DNP V3.00 Device Profile
Timeouts while waiting for:
Data Link Confirm None Fixed at 3s _ Variable Configurable
Complete Appl. Fragment None Fixed at ___ Variable Configurable
Application Confirm None Fixed at ___ Variable Configurable
Complete Appl. Response None Fixed at ___ Variable Configurable

Others
______________________________________________________________________________
Attach explanation if 'Variable' or 'Configurable' was checked for any timeout
Sends/Executes Control Operations:
WRITE Binary Outputs Never Always Sometimes Configurable
SELECT/OPERATE Never Always Sometimes Configurable
DIRECT OPERATE Never Always Sometimes Configurable
DIRECT OPERATE - NO ACK Never Always Sometimes Configurable

Count > 1 Never Always Sometimes Configurable
Pulse On Never Always Sometimes Configurable
Pulse Off Never Always Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable

Queue Never Always Sometimes Configurable
Clear Queue Never Always Sometimes Configurable
Select timeout: configurable
FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY:
Reports Binary Input Change Events when no

Specific variation requested:

Never
Only time-tagged
Only non-time-tagged
Configurable to send both, one or the
other (explanation below)

User option to have all Binary Input
Change Events returned as either:
time-tagged OR
non-time-tagged
Reports time-tagged Binary Input Change
Events
when no specific variation requested:

Never
Binary Input Change With Time
Binary Input Change With Relative Time
Configurable (attach explanation)
C264/EN CT/C30 Communications

Page 70/92

MiCOM C264/C264C

DNP V3.00 Device Profile
Sends Unsolicited Responses:
Never
Configurable (attach explanation)
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
Function codes supported
Sends Static Data in Unsolicited Responses:
Never
When Device Restarts
When Status Flags Change

No other options are permitted.
Default Counter Object/Variation:
No Counters Reported
Configurable (explanation below)
Default Object _____20_______
Default Variation _____02_______
Point-by-point list attached

User option to return all static counters in
one of the following variations:
32-Bit Binary Counter
32-Bit Binary Counter Without Flag
16-Bit Binary Counter
16-Bit Binary Counter Without Flag
Counters Roll Over at:
No Counters Reported
Configurable (explanation below)
16 Bits
32 Bits
Other Value _____________
Point-by-point list attached
User option to select roll over:
32 bit counters roll over at 2^32.
16 bit counters roll over at 2^16
Sends Multi-Fragment Responses: Yes No

Communications C264/EN CT/C30

MiCOM C264/C264C

Page 71/92

4.4.7 DNP.3 Level 3 IMPLEMENTATION TABLE
Underlined information in grey are not implemented
OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj Var Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func Codes
(dec)
Qual Codes
(hex)
1 0 Binary Input All Variations 1, 22 00,01,06
1 1 Binary Input 1 00,01,06 129,130 00,01
1 2 Binary Input with Status 1 00,01,06 129,130 00,01
2 0 Binary Input Change - All Variations 1 06,07,08
2 1 Binary Input Change without Time 1 06,07,08 129,130 17,28
2 2 Binary Input Change with Time 1 06,07,08 129,130 17,28
2 3 Binary Input Change with Relative Time 1 06,07,08 129,130 17,28
10 0 Binary Output - All Variations 1 00,01,06
10 1 Binary Output
10 2 Binary Output Status 1 00,01,06 129,130 00,01
12 0 Control Block - All Variations (1)
12 1 Control Relay Output Block (1) 3,4,5,6 17,28 129 Request
echo
12 2 Pattern Control Block 5,6 17,28 129 Request
echo
12 3 Pattern Mask 5,6 00,01 129 Request
echo
20 0 Binary Counter - All Variations 1,7,8,9,10,
22
00,01,06
20 1 32-Bit Binary Counter 1 00,01,06 129,130 00,01
20 2 16-Bit Binary Counter 1 00,01,06 129,130 00,01
20 3 32-Bit Delta Counter 1 00,01,06 129,130 00,01
20 4 16-Bit Delta Counter 1 00,01,06 129,130 00,01
20 5 32-Bit Binary Counter without Flag 1 00,01,06 129,130 00,01
20 6 16-Bit Binary Counter without Flag 1 00,01,06 129,130 00,01
20 7 32-Bit Delta Counter without Flag 1 00,01,06 129,130 00,01
20 8 16-Bit Delta Counter without Flag 1 00,01,06 129,130 00,01
1. Commands must be selected/executed on one point
C264/EN CT/C30 Communications

Page 72/92

MiCOM C264/C264C

OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj Var Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func Codes
(dec)
Qual Codes
(hex)
21 0 Frozen Counter - All Variations 1 00,01,06
21 1 32-Bit Frozen Counter 1 00,01,06 129,130 00,01
21 2 16-Bit Frozen Counter 1 00,01,06 129,130 00,01
21 3 32-Bit Frozen Delta Counter 1 00,01,06 129,130 00,01
21 4 16-Bit Frozen Delta Counter 1 00,01,06 129,130 00,01
21 5 32-Bit Frozen Counter with Time of
Freeze
1 00,01,06 129,130 00,01
21 6 16-Bit Frozen Counter with Time of
Freeze
1 00,01,06 129,130 00,01
21 7 32-Bit Frozen Delta Counter with Time of
Freeze

21 8 16-Bit Frozen Delta Counter with Time of
Freeze

21 9 32-Bit Frozen Counter without Flag 1 00,01,06 129,130 00,01
21 10 16-Bit Frozen Counter without Flag 1 00,01,06 129,130 00,01
21 11 32-Bit Frozen Delta Counter without Flag
21 12 16-Bit Frozen Delta Counter without Flag
22 0 Counter Change Event - All Variations 1 06,07,08
22 1 32-Bit Counter Change Event without
Time
1 06,07,08 129,130 17,18
22 2 16-Bit Counter Change Event without
Time
1 06,07,08 129,130 17,18
22 3 32-Bit Delta Counter Change Event
without Time
1 06,07,08 129,130 17,18
22 4 16-Bit Delta Counter Change Event
without Time
1 06,07,08 129,130 17,18
22 5 32-Bit Counter Change Event with Time 1 06,07,08 129,130 17,18
22 6 16-Bit Counter Change Event with Time 1 06,07,08 129,130 17,18
22 7 32-Bit Delta Counter Change Event with
Time

22 8 16-Bit Delta Counter Change Event with
Time


Remarks:
Frozen counters (type21) are uploaded during general interrogation, but never polled after this.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 73/92

OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj Var Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func Codes
(dec)
Qual Codes
(hex)
23 0 Frozen Counter Event - All Variations 1 06,07,08
23 1 32-Bit Frozen Counter Event without
Time
1 06,07,08 129,130 17,18
23 2 16-Bit Frozen Counter Event without
Time
1 06,07,08 129,130 17,18
23 3 32-Bit Frozen Delta Counter Event
without Time
1 06,07,08 129,130 17,18
23 4 16-Bit Frozen Delta Counter Event
without Time
1 06,07,08 129,130 17,18
23 5 32-Bit Frozen Counter Event with Time 1 06,07,08 129,130 17,18
23 6 16-Bit Frozen Counter Event with Time 1 06,07,08 129,130 17,18
23 7 32-Bit Frozen Delta Counter Event with
Time

23 8 16-Bit Frozen Delta Counter Event with
Time

30 0 Analogue Input - All Variations 1 00,01,06
30 1 32-Bit Analogue Input 1 00,01,06 129,130 00,01
30 2 16-Bit Analogue Input 1 00,01,06 129,130 00,01
30 3 32-Bit Analogue Input without Flag 1 00,01,06 129,130 00,01
30 4 16-Bit Analogue Input without Flag 1 00,01,06 129,130 00,01
31 0 Frozen Analogue Input - All Variations
31 1 32-Bit Frozen Analogue Input
31 2 16-Bit Frozen Analogue Input
31 3 32-Bit Frozen Analogue Input with Time
of Freeze

31 4 16-Bit Frozen Analogue Input with Time
of Freeze

31 5 32-Bit Frozen Analogue Input without
Flag

31 6 16-Bit Frozen Analogue Input without
Flag

32 0 Analogue Change Event - All Variations 1 06,07,08
32 1 32-Bit Analogue Change Event without
Time
1 06,07,08 129,130 17,18
32 2 16-Bit Analogue Change Event without
Time
1 06,07,08 129,130 17,18
32 3 32-Bit Analogue Change Event with
Time
1 06,07,08 129,130 17,18
32 4 16-Bit Analogue Change Event with
Time
1 06,07,08 129,130 17,18
33 0 0 Frozen Analogue Event - All Variations
33 1 32-Bit Frozen Analogue Event without
Time

33 2 16-Bit Frozen Analogue Event without
Time

33 3 32-Bit Frozen Analogue Event with Time
33 4 16-Bit Frozen Analogue Event with Time
40 0 Analogue Output Status - All Variations 1 00,01,06
40 1 32-Bit Analogue Output Status 1 00,01,06 129,130 00,01
40 2 16-Bit Analogue Output Status 1 00,01,06 129,130 00,01
C264/EN CT/C30 Communications

Page 74/92

MiCOM C264/C264C

OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj Var Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func Codes
(dec)
Qual Codes
(hex)
41 0 Analogue Output Block - All Variations 3,4,5,6 17,28 129 Request
echo
41 1 32-Bit Analogue Output Block 5,6 17,28 129 Request
echo
41 2 16-Bit Analogue Output Block 5,6 17,28 129 Request
echo
50 0 Time and Date - All Variations
50 1 Time and Date 2 07 (quantity=1)
50 2 Time and Date with Interval
51 0 Time and Date CTO - All Variations
51 1 Time and Date CTO 129,130 07
(quantity=1)
51 2 Unsynchronized Time and Date CTO 129,130 07
(quantity=1)
52 0 Time Delay - All Variations
52 1 Time Delay Coarse 129,130 07
(quantity=1)
52 2 Time Delay Fine 129,130 07
(quantity=1)
60 0
60 1 Class 0 Data 1 06,07,08
1 06,07,08 60 2 Class 1 Data
20,21,22 06
1 06,07,08 60 3 Class 2 Data
20,21,22 06
1 06,07,08 60 4 Class 3 Data
20,21,22 06

70 1 File Identifier
2 00 (index=7 ou
index=4)
80 1 Internal Indications
1 00,01
81 1 Storage Object
82 1 Device Profile
83 1 Private Registration Object
83 2 Private Registration Object Descriptor
90 1 Application Identifier
100 1 Short Floating Point
100 2 Long Floating Point
100 3 Extended Floating Point
101 1 Small Packed Binary-Coded Decimal
101 2 Medium Packed Binary-Coded Decimal
101 3 Large Packed Binary-Coded Decimal
No Object (Cold Restart)
No Object (Warm Restart)
No Object (Delay Measurement

Communications C264/EN CT/C30

MiCOM C264/C264C

Page 75/92

4.5 IEC 60870-5-103 Communication
4.5.1 Finality
The purpose of this chapter is not to describe the T103 but to specify the use of the T103
protocol on a legacy bus of the MiCOM C264.
As the MiCOM C264 is the master on the legacy bus - regards to protections and IEDs - this
protocol is referenced as Master T103 in the MiCOM C264.
Here are described:
Specific behaviours attached to the protocol T103
Restrictions and enhancements
Part of the T103 protocol used and not used
Specific behaviours attached to implementation of Private Range of T103
4.5.2 Interface to IEDs
4.5.2.1 Input
ASDU Data Note
1 Dated Digital input (absolute dating)
Control acknowledgement
Treated
2 Dated Digital input (relative dating) Treated
3 Measurement Treated
4 Measurement: Default position Treated
5 Identification Not treated
6 Time synchronisation acknowledgement Treated
8 End of GI Treated
9 Measurement Treated
10 General Data Not treated
11 General Identification Not treated
17 Measurement Reg D only
23 31 Disturbance file management Treated
45 Ack of Single Command MiCOM Px3x only
46 Ack of Double Command MiCOM Px3x only
49 Analog protection signal
Only adress 0 which is DVICE: Device type
MiCOM Px3x only
65 Single Point MiCOM Px3x only
66 Single Point with Time Tag MiCOM Px3x only
67 Double Point MiCOM Px3x only
68 Double Point with Time Tag MiCOM Px3x only
71 BitString 32 Bit without time tag
couple FUN/TYP computed:
F8h / 70h: State of the IED
F8h / 74h: Request Station Interlock
MiCOM Px3x only
72 BitString 32 Bit with time tag see ASDU 71 MiCOM Px3x only
73 Measurement, Normalised value MiCOM Px3x only
77 Measurement MiCOM Px2x only
79 Energy Counter MiCOM Px3x only
C264/EN CT/C30 Communications

Page 76/92

MiCOM C264/C264C

4.5.2.2 Output
ASDU Data Note
6 Time synchronisation Treated
7 Request a GI Treated
20 Command Treated
23 31 Disturbance file management Treated
45 Single Command MiCOM Px3x only
46 Double Command MiCOM Px3x only
140 Read protection parameter
Only adress 0 which is DVICE: Device type
MiCOM Px3x only
144 Setpoint Reg D only
4.5.3 Behaviour
4.5.3.1 Synchronisation
The Master T103 link is always synchronised by the MiCOM C264. No calculation of the
transmission delay is performed.
4.5.3.2 Polling
To connect an IED, a Reset CU frame is sent to the IED.
By default an IED is polled by a Polling C2 frame, allowing to get non priority information.
If an IED signals it has priority information, it is polled with a Polling C1 frame.
4.5.3.3 IED monitoring
The OUT_OF_SERVICE state is managed. It corresponds to the Lock of communication
[DI 20].
A GI may be done after each end of Tunnelling session.
The MiCOM C264 may regularly look for Disturbance file presence
4.5.3.4 Tunnelling mode
During tunnelling mode, only polling C2 may be done by the MiCOM C264 [Normally, if
priority information is present, the remote Master may send a polling C1 frame].
The MiCOM C264 must spy the tunnelling exchange in order not to loose information [DI and
AI change]
For security raison, at the end of a tunnelling session, a GI is done
4.5.3.5 Station Interlocking
This functionality is only available on MiCOM P139 in private T103 range (Alstom D protocol
variant)
After GI, and only if IED is MiCOM Px3x, we send a read on MiCOM Px3x parameter adress
0 which corresponds to Device Type. If MiCOM Px3x responds with analog parameter set to
139, we activate Station Interlocking Management.
Case of local control (front panel of the MiCOM P139) with Station interlock:
As soon as a user will try to control a switchgear by the front panel, the MiCOM P139 will
send an ASDU 72 with FUN/TYP = F8h/74h in order to request to PACiS system the station
interlock conditions. PACiS system should check if the command is allowed (specific
treatment done by CONDUITE of the computer) and respond to the MiCOM P139.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 77/92

Case of remote control (from PACiS system) with Station interlock:
As soon as a user will try to control a device managed by MiCOM P139 by PACiS system
through T103 communication, the MiCOM P139 will send an ASDU 72 with FUN/TYP =
F8h/74h in order to request to PACiS system the station interlock conditions. PACiS system
should respond to the MiCOM P139 with a positive acknowledgement (checks have already
been done before)
If station Interlock is de-activated on MiCOM P139, the control of a switchgear on MiCOM
P139 by PACiS system through T103 communication is done by an EXECUTE ORDER
(selection will be refused by MiCOM P139)
4.5.3.6 REG D
The Reg D equipment manages 2 ASDU (144 and 17), for control of setpoints (144) and
setpoint value feedback (17), which is treated as a measurement in the computer. Setpoints
managed by the Reg D are "Direct Execute" only, there is no SBO management. The Reg D
setpoint command sequence is like the command sequence (ASDU20). The computer sends
the setpoint (ASDU 144), with the setpoint value, the Reg D sends its acknowledge
(ASDU1), if the acknowledge is OK, the Reg D sends the setpoint value feedback
(ASDU17).
4.5.4 Data received from IEDs
4.5.4.1 Digital inputs
An ASDU number [(1,2) in public Range],[(66,67,68,69) in private Range]
A DI is identified by a couple (Function Type, Information Number).
Digital inputs are received as changes of state.
Special DI may be managed:
DI 20: Lock of the communication. A GI must be done when the communication is
unlocked
DI 23 to 26: Change of configuration number
DI which are not transmitted during a GI. For these DI, the IED signals only
change of state from OFF to ON. The MiCOM C264 must generate by itself the
change from ON to OFF.
4.5.4.2 Measurements
A Measurement is identified by:
An ASDU Number [(3,4,9) in public range, (73,77) in private range]
a couple (Function Type, Information Number)
the rank of the Measurements in the ASDU
the kind of Measurements [Current, Voltage, Power, Frequency, Other]
the common address of ASDU
4.5.4.3 Bitstring 32-bits:
The state of the IED is identify by the ASDU 71 or 72 with couple FUN / TYP = F8h / 70h.
This ASDU describes the status of the IED (Station Interlocking active or not )
A request to check station interlocking is identify by the ASDU 71 or 72 with couple FUN /
TYP = F8h / 74h. In this request, the couple FUN/TYP of the command to spend is defined.
4.5.4.4 Analog protection signal (ASDU 49):
Only for MiCOM Px3x, an analogue protection signal is received after GI
Only address 0 is managed. It is used to recognise MiCOM P139 in order to activate station
interlocking management.
C264/EN CT/C30 Communications

Page 78/92

MiCOM C264/C264C

4.5.4.5 Energy counter (ASDU 79):
Only for MiCOM Px3x, four energy counters are available.
Energy counters are identified by:
An ASDU number (79) in private range
a couple Function Type, Information number
the rank of the counter in the ASDU
the common address of the ASDU
Description TI VSQ COT ADR FUN INF DB0-DB4 DB5-DB9 DB10-DB14 DB15-DB19
Energy
counter
4FH 04H 01H CAD F8H 6CH Active + Active - Reactive + Reactive -
TI = Type identification
VSQ = variable structure qualifier
COT = cause of transmission
ADR = CAD = common address
FUN = function number
INF= information number
DB0-DB4 = active energy output
DB5-DB9 = active energy input
DB10-DB14 = reactive energy output
DB15-DB19 = reactive energy input
Format of the energy counter value
Value
Value
Value
S Value
IV CA CY Sequence number
S: 0 Value positive, 1 = value negative
CY: 0 = no carry, 1= carry
CA: 0 = not adjusted, 1 = adjusted
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 79/92

4.5.5 Data sent to IEDs
4.5.5.1 Controls
An ASDU Number and a couple (Function Type, Information Number) identify a control.
The acknowledgement of a control is to be waited as:
A DI with the same (Function Type, Information Number) as the control and with a
Cause Of Transmission equals to positive return or negative return in public range
A ASDU 45 or 46 with a Cause Of Transmission equals to end of activation OK or
en of activation KO, or deactivation OK, or deactivation KO in private range
4.5.5.2 Setpoints Controls:
A setpoint control is identified by an ASDU Number plus a couple (Function Type,
Information Number). In the case of the Reg D equipment the ASDU is 144.
The acknowledgement of a setpoint control is to be waited as:
A DI (ASDU 1) with the same (Function Type, Information Number) as the control and
with a Cause Of Transmission equals to positive return or negative return in public
range.
An ASDU 17 with a Cause Of Transmission equals to Local Operation in public
range. The ASDU is a measurement which contains the setpoint feedback value.
4.5.5.3 Read protection parameter:
Only for MiCOM Px3x, a read of protection parameter (ASDU 140) address 0 (Device Type)
is sent to IED
The IED responds with ASDU 49 in which Device Type is set (139 if IED is a MiCOM P139
for example).
C264/EN CT/C30 Communications

Page 80/92

MiCOM C264/C264C

4.6 IEC 60870-5-101 Communication
4.6.1 Finality
The purpose of this chapter is not to describe the T101 but to specify the implementation of
T101 protocol on a legacy bus inside the MiCOM C264.
4.6.2 Master IEC 60870-5-101 profile
The companion standard presents sets of parameters and alternatives from which subsets
have to be selected to implement particular telecontrol systems. Certain parameters values,
such as the number of bytes in the COMMON ADDRESS of ASDUs represent mutually
exclusive alternatives. This means that only one value of the defined parameters is admitted
per system.
Other parameters, such as the listed set of different process information in command and in
monitor direction allow the specification of the complete set or subsets, as appropriate for
given applications. This clause summarises the parameters of the previous clauses to
facilitate a suitable selection for a specific application. If a system is composed of equipment
stemming from different manufacturers it is necessary that all partners agree on the selected
parameters.
The selected parameters should be marked in the white boxes as follows:
Function or ASDU is not used
Function or ASDU is used as standardised (default)
R Function or ASDU is used in reverse mode
B Function or ASDU is used in standard and reverse mode
The possible selection (blank, X, R or B) is specified for each specific clause or parameter.
NOTE: In addition, the full specification of a system may require individual
selection of certain parameters for certain parts of the system, such as
the individual selection of scaling factors for individually addressable
measured values.
4.6.2.1 System or device
(system specific parameter, indicates the definition of a system or a device by marking one
of the following with X)
System definition
Controlling station definition (Master)
Controlled station definition (Slave)
4.6.2.2 Network configuration
(network specific parameter, all configurations that are used are to be marked X)
Point-to-point Multipoint-party line
Multiple point-to-point Multipoint-star
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 81/92

4.6.2.3 Physical layer
(network specific parameter, all interfaces and data rates that are used are to be marked X)
Transmission speed (control direction)
Unbalanced interchange
CIRCUIT V24/V28
Standard
Recommended if
> 1200 bits/s
Balanced interchange
Circuit X24/X27
100 bits/s 2400 bits/s 2400 bits/s 56000 bits/s
200 bits/s 4800 bits/s 4800 bits/s 64000 bits/s
300 bits/s 9600 bits/s 9600 bits/s

600 bits/s 19200 bits/s 19200 bits/s

1200 bits/s

38400 bits/s

Transmission speed (monitor direction)
Unbalanced interchange
CIRCUIT V24/V28
Standard
Recommended if
> 1200 bits/s
Balanced interchange
Circuit X24/X27
100 bits/s 2400 bits/s 2400 bits/s 56000 bits/s
200 bits/s 4800 bits/s 4800 bits/s 64000 bits/s
300 bits/s 9600 bits/s 9600 bits/s

600 bits/s 19200 bits/s 19200 bits/s

1200 bits/s

38400 bits/s

4.6.2.4 Link layer
(network specific parameter, all options that are used are to be marked X. Specify the
maximum frame length).
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively
in this companion standard.
Link transmission procedure Address field of the link
Balanced transmission Not present (balanced transmission only)
Unbalanced transmission One octet
Two octets
Structured
Unstructured
Frame length (number of bytes)
255 Maximum length L in control direction
up to 255 Maximum length L in monitor direction configurable
C264/EN CT/C30 Communications

Page 82/92

MiCOM C264/C264C

4.6.2.5 Application layer
Transmission mode for application data
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is used
exclusively in this companion standard.
Common address of ASDU
(system-specific parameter, all configurations that are used are to be marked X)
One octet Two octets
Information object address
(system-specific parameter, all configurations that are used are to be marked X)
One octet Structured
Two octets Unstructured
Three octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked X)
One octet Two octets (with originator address)
Set to zero in case of no originator address.
Selection of standard ASDUs
Process information in monitor direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<1> := Single-point information M_SP_NA_1
<2> := Single-point information with time tag M_SP_TA_1
<3> := Double-point information M_DP_NA_1
<4> := Double-point information with time tag M_DP_TA_1
<5> := Step-position information M_ST_NA_1
<6> := Step-position information with time tag M_ST_TA_1
<7> := BitString of 32 bit M_BO_NA_1
<8> := BitString of 32 bit with time tag M_BO_TA_1
<9> := Measured value, normalized value M_ME_NA_1
<10> := Measured value, normalized value with time tag M_ME_TA_1
<11> := Measured value, scaled value M_ME_NB_1
<12> := Measured value, scaled value with time tag M_ME_TB_1
<13> := Measured value, short floating point value M_ME_NC_1
<14> := Measured value, short floating point value with time tag M_ME_TC_1
<15> := Integrated totals M_IT_NA_1
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 83/92

<16> := Integrated totals with time tag M_IT_TA_1
<17> := Event of protection equipment with time tag M_EP_TA_1
<18> := Packed start events of protection equipment with time tag M_EP_TB_1
<19> := Packed output circuit transmission of protection equipment with time tag M_EP_TC_1
<20> := Packed single-point information with status change detection M_PS_NA_1
<21> := Measured value, normalized value without quality descriptor M_ME_ND_1
<30> := Single-point information with time tag CP56Time2a M_SP_TB_1
<31> := Double-point information with time tag CP56Time2a M_DP_TB_1
<32> := Step-position information with time tag CP56Time2a M_ST_TB_1
<33> := Bistring of 32 bits with with time tag CP56Time2a M_BO_TB_1
<34> := Measured value, normalized with time tag CP56Time2a M_ME_TD_1
<35> := Measured value, scaled with time tag CP56Time2a M_ME_TE_1
<36> := Measured value, short floating point number with time tag CP56Time2a M_ME_TF_1
<37> := Integrated totals with time tag CP56Time2a M_IT_TB_1
<38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1
<39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
<40> := Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1
Process information in control direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<45> := Single command C_SC_NA_1
<46> := Double command C_DC_NA_1
<47> := Regulating step command C_RC_NA_1
<48> := Set point command, normalized value C_SE_NA_1
<49> := Set point command, scaled value C_SE_NB_1
<50> := Set point command, short floating point value C_SE_NC_1
<51> := BitString of 32 bits C_BO_NA_1
System information in monitor direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<70> := End of initialisation M_EI_NA_1
C264/EN CT/C30 Communications

Page 84/92

MiCOM C264/C264C

System information in control direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<100> := Interrogation command C_IC_NA_1
<101> := Counter Interrogation Command C_CI_NA_1
<102> := Read command C_RD_NA_1
<103> := Clock synchronisation command C_CS_NA_1
<104> := Test command C_TS_NB_1
<105> := Reset process command C_RP_NC_1
<106> := Delay acquisition command C_CD_NA_1
Parameter in control direction
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<110> := Parameter of measured value, normalized value P_ME_NA_1
<111> := Parameter of measured value, scaled value P_ME_NB_1
<112> := Parameter of measured value, short floating point value P_ME_NC_1
<113> := Parameter activation P_AC_NA_1
File transfer
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
<120> := File ready F_FR_NA_1
<121> := Section ready F_SR_NA_1
<122> := Call directory, select file, call file, call section F_SC_NA_1
<123> := Last section, last segment F_LS_NA_1
<124> := Ack file, ack section F_AF_NA_1
<125> := Segment F_SG_NA_1
<126> := Directory F_DR_TA_1
Special use
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
None
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 85/92

Type identifier and cause of transmission assignments
(station-specific parameters)
Shaded boxes are not required.
Blank = function or ASDU is not used
Mark type identification/cause of transmission combinations:
X if used only in the standard direction
R if used only in the reverse direction
B if used in both directions
Type ID Cause of transmission

1 2 3 4 5 6 7 8 9 10 11 12 13
20 to
36
37 to
41
44 45 46 47
<1> M_SP_NA_1 X X X X X
<2> M_SP_TA_1 X X X


<3> M_DP_NA_1 X X X X X
<4> M_DP_TA_1 X X X
<5> M_ST_NA_1 X X X X X
<6> M_ST_TA_1 X X X
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1 X
<11> M_ME_NB_1 X X X X
<12> M_ME_TB_1 X
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1 X
<15> M_IT_NA_1 X X
<16> M_IT_TA_1 X
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1 X X X
<30> M_SP_TB_1 X X
<31> M_DP_TB_1 X X
<32> M_ST_TB_1 X X
<33> M_BO_TB_1
<34> M_ME_TD_1 X
<35> M_ME_TE_1 X
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X X X X X
<46> C_DC_NA_1 X X X X X X X X X
C264/EN CT/C30 Communications

Page 86/92

MiCOM C264/C264C

Type ID Cause of transmission

1 2 3 4 5 6 7 8 9 10 11 12 13
20 to
36
37 to
41
44 45 46 47
<47> C_RC_NA_1 X X X X X X X X X
<48> C_SE_NA_1 X X X X X X X X X
<49> C_SE_NB_1 X X X X X X X X X
<50> C_SE_NC_1 X X X X X X X X X
<51> C_BO_NA_1
<70> M_EI_NA_1 X
<100> C_IC_NA_1 X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1
<103> C_CS_NA_1 X X
<104> C_TS_NA_1 X X
<105> C_RP_NA_1
<106> C_CD_NA_1

<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1 X
<121> F_SR_NA_1 X
<122> F_SC_NA_1 X
<123> F_LS_NA_1 X
<124> F_AF_NA_1 X
<125> F_SG_NA_1 X
<126> F_DR_TA_1 X X

4.6.2.6 Basic application functions
Station initialisation
(station-specific parameter, mark X if function is used)
Remote initialisation
Cyclic data transmission
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Cyclic data transmission
Read procedure
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Read procedure
Spontaneous transmission
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Spontaneous transmission
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 87/92

Link state between Controlling and Controlled Station
Management of the COM lost (Problem detecting on the link)
Management of the COM recovering (Problem not detecting on the link)
General interrogation
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Global
Group 1 Group 7 Group 13
Group 2 Group 8 Group 14
Group 3 Group 9 Group 15
Group 4 Group 10 Group 16
Group 5 Group 11 Addresses per group have to be defined
Group 6 Group 12
Counter General interrogation
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Global
Group 1 Group 2 Group 3
Group 4
Clock synchronisation
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Clock synchronisation
Notes:
The controlled station reports the change of hour by sending a clock synchronisation message (ASDU 103) to the
controlling station.
Command transmission
(object -specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Direct command transmission
Direct set-point command transmission
Select and execute command
Select and execute set-point command
C_SE_ACTTERM used
No additional definition
Short pulse duration (duration determined by a system parameter in the outstation)
C264/EN CT/C30 Communications

Page 88/92

MiCOM C264/C264C

Long pulse duration (duration determined by a system parameter in the outstation)
Persistent output
Transmission of integrated totals
(object -specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Mode A: local freeze with spontaneous transmission
Mode B: local freeze with counter interrogation
Mode C: freeze and transmit by counter interrogation commands
Mode D: freeze by counter interrogation command, frozen values reported
spontaneously
Counter read General request counter
Counter freeze without reset Request counter group 1
Counter freeze with reset Request counter group 2
Counter reset Request counter group 3
Request counter group 4
Parameter loading
(object-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Threshold value
Smoothing factor
Low limit for transmission of measured value
High limit for transmission of measured value
Parameter activation
(object-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Act/deact of persistent cyclic or periodic transmission of the addressed object
Test procedure
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Test procedure
File transfer
(station-specific parameter), mark X if function is used)
File transfert in monitor direction
Transparent file
Transmission of disturbance data of protection equipment
Transmission of sequences of events
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 89/92

Transmission of sequences of recorded analogue values
File transfer in control direction
Transparent file
Background scan
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Background scan
Acquisition of transmission delay
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Acquisition of transmission delay
Management events priorities
(station-specific parameter, mark each type ID X if it is only used in the standard direction,
R if only used in the reverse direction, and B is used in both directions)
Digital Inputs and Analog Inputs, management events priorities.
See: T101 standard Amendment 2 7.2.2.2
4.6.2.7 Application Functions
The following IEC-60870-5-5 standard application processes are required to be supported.
Station Initialisation
Station initialisation consists of a reset of the communications link, followed by a general
interrogation of the controlled station. Once this initialisation sequence performed the
controlling station can start the polling for data report.
Communications failure
Communications to the controlled station must be re-initialised by the controlling station
when the frame repeat process has completed without successfully transmitting the frame (ie
the frame time-out period times the number of repeats).
If the controlled station fails to communicate with the controlling station then the controlling
station should perform a communications system initialisation for that controlled station.
Controlled station failure
The controlled station shall indicate to the controlling station that it has initialised by sending
a frame indicating End of Initialisation with a Cause of Initialisation (COI) field, which will
identify the reason for the initialisation.
Data Acquisition by Polling
The default for all analogue values shall be reporting as Class 2 data (COT=1,
periodic/cyclic, or COT = 2, BackgroundScan cyclic).
Values returned as Class 2 data do not have a time tag (since they are constantly repeated).
The controlled station may return Class 1 data in response to a Class 2 request if no Class 2
data is available and Class 1 data is awaiting transmission.
At the controlled station, if a request for Class 2 data is received and no data is available a
negative response, data not available, shall be returned to the controlling Station. The
negative response is a fixed length frame (FC=9).
C264/EN CT/C30 Communications

Page 90/92

MiCOM C264/C264C

Normal Acquisition of Events
The default for all status changes are reported as Class 1 data (COT=3, spontaneous).
Values returned as Class 1 data shall have a time tag (either CP24Time2a, or CP56Time2a).
Status changes at the controlled station shall cause the ACD bit to be set in the next Class 1
or Class 2 data response. The controlling station shall respond to ACD set by inserting a
scan for Class 1 (spontaneous) data as the next scan.
The response to a Class 1 data request shall also have the ACD bit set if more Class 1 data
is awaiting transmission. In this case a further scan for Class 1 data shall be scheduled by
the controlling station.
Abnormal Acquisition of Events
At the controlled station, if a request for Class 1 data is received and no data is available an
error should be raised and a negative response, data not available, returned to the
controlling Station. The negative response shall be a fixed length frame (FC=9.
At the controlling station, if a response to a scan for Class 1 data indicates no data is
available an error shall be raised and scanning returned to Class 2 data requests.
General Interrogation
The GI returns the current status information directly from the Computer database.
Time tags are not used for data items returned as part of the GI response.
The GI groups are not supported, only the global general interrogation is supported.
Clock synchronisation
The System (including the controlled station) may have different synchronisation sources
(IRIG-B, SCADA).
When the controlling station send to controlled station a clock synchronisation and if the
system isnt synchronised by an other source: the clock synchronisation response is
positive.
When the controlling station send to controlled station a clock synchronisation and if the
system (including the controlled station) is synchronised by an other source: the clock
synchronisation response is negative.
All Class 1 data are time-tagged with:
Either the 3 bytes time-stamp (CP24Time2a), giving minutes and milliseconds within the
hour, or the 7 bytes time-stamp (CP56Time2a), giving minutes, milliseconds, hours, day,
month and year according to the Computer configuration.
In case of using relative time-Tag (CP24Time2a), the controlled station reports:
the change of hour
any time correction
by sending a clock synchronisation message (ASDU 103) to the controlling station, as
Class 1 data, with a cause of transmission spontaneous (3).
The invalid bit in the time-stamp is set when the time source is not available.
Command transmission
All control commands shall be Select before Execute, or Direct Execute.
For only the control commands: Activation termination is returned to the controlling station to
signal the end of a control sequence.
The QU field of the Qualifier of Command shall be set to zero (0), no additional definition.
Communications C264/EN CT/C30

MiCOM C264/C264C

Page 91/92

Test procedure
A test command may be issued by the controlling station to ensure the availability of the
communications link and the commands subsystem.
Test commands are received at the controlled station on the active link. The controlled
station mirrors the test command, on the link from which it was received, with a cause of
transmission indicating activation confirmation.
An error response should be sent if the command is incorrect, with a cause of transmission
indicating negative activation confirmation.
In the case of balanced mode, the controlled station may also send a test command to the
controlling station, to ensure the availability of the communications link as there is no polling
made by the controlling station.
C264/EN CT/C30 Communications

Page 92/92

MiCOM C264/C264C

BLANK PAGE
Commissioning C264/EN CM/C30

MiCOM C264/C264C


COMMISSIONING
Commissioning C264/EN CM/C30

MiCOM C264/C264C

Page 1/14

CONTENT
1. SCOPE OF THE DOCUMENT 3
1.1 Introduction 3
1.2 Definition 3
1.3 Commissioning the product 3
1.4 Responsibility 3
1.5 Setting familiarisation 4
2. REQUIREMENTS 5

3. COMMISSIONING TESTS WITH GHU200 OR GHU201( WITH LCD) 6
3.1 Preparation 6
3.2 Check version & number 7
3.3 Faults 8
3.4 Check the boards status 8
3.5 Checking the binary signal inputs 9
3.6 Checking the output relays 10
3.7 Testing the communication with external devices 11
3.8 Testing the control functions 12
3.9 Switching from local to remote control 12
3.9.1 Local control 12
3.9.2 Remote control 12
4. COMMISSIONING TESTS WITH GHU210 OR GHU211(WITHOUT LCD) 13

C264/EN CM/C30 Commissioning

Page 2/14

MiCOM C264/C264C

BLANK PAGE
Commissioning C264/EN CM/C30

MiCOM C264/C264C

Page 3/14

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264/C264C documentation binders. It describes the
commissioning of the product and should not be confused with application commissioning.
This chapter follows the C264/EN IN (Installation) chapter.
1.1 Introduction
To commission MiCOM C264/C264C, it is necessary to verify that the hardware is
functioning correctly and that the application-specific software settings have been applied to
the MiCOM C264/C264C.
To verify that the MiCOM C264/C264C is operating correctly, a database has to be loaded
into the computer. Once the database has been loaded, tests should be performed on each
a single MiCOM C264/C264C element.
As the MiCOM C264/C264Cs menu language is user-selectable, it is acceptable for the
Commissioning Engineer to change it to allow accurate testing as long as the menu is
restored to the customers preferred language on completion.
Before carrying out any work on the equipment, the user should be familiar with the contents
of the chapter C264/EN SA (Safety), of the AREVA T&D Safety Guide: SFTY/4L M/C11 ( or
later issue), and of all the C264 technical data.
1.2 Definition
The objective of commissioning is to prove that the equipment, and any interconnections to
process and other system components, is suitable for its intended purpose.
Commissioning is the activity that demonstrates that the equipment is acceptable for service.
As digital devices are configured for specific application, the commissioning can be split into
two main parts:
Commissioning the product.
Commissioning the application (when product has had its database loaded). This
second part is documented and carried out through FAT (Factory Acceptance Tests),
and SAT (Site Acceptance Tests) activities.
The scope of this chapter is the description of commissioning tests that prove that the
MiCOM C264 is suitable for further application tests.
1.3 Commissioning the product
Commissioning the product starts with product reception and is continued through all off the
installation procedures. Activities are divided between: -
Visual inspection at reception.
Inspection at Front Panel when MiCOM C264/C264C is powered up.
The starting point is the delivery form that describes all of the delivered hardware
components that constitute the MiCOM C264/C264C.
1.4 Responsibility
Most commissioning activities involve a power supply that can damage the installation or
cause injury to the operator. The chapter C264/EN SA (Safety) should be read carefully
before any handling.
Before starting commissioning, the contractual and human responsibilities should be clearly
defined.
Only qualified and competent persons should carry out commissioning and the validation
tests.
C264/EN CM/C30 Commissioning

Page 4/14

MiCOM C264/C264C

1.5 Setting familiarisation
Commissioning the MiCOM C264 requires operation of its Human Machine Interface (the
Local Control Display). The chapter C264/EN HI contains a detailed description of the menu
structure of MiCOM C264.
The commissioning engineer should have had training on the HMI or sufficient time should
be allowed to become familiar with it (with an already commissioned device).
Commissioning C264/EN CM/C30

MiCOM C264/C264C

Page 5/14

2. REQUIREMENTS
It is essential that all requirements expressed in C264/EN IN (Installation) chapter have been
fulfilled.
The delivery form is the starting document.
C264/EN CM/C30 Commissioning

Page 6/14

MiCOM C264/C264C

3. COMMISSIONING TESTS WITH GHU200 OR GHU201( WITH LCD)
3.1 Preparation
After the MiCOM C264 has been installed and connected as described in Chapters
C264/EN IN and C264/EN CO, the commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked:
Is the device connected to the protective ground at the specified location?
Does the nominal (and measured) voltage of the battery agree with the nominal
auxiliary voltage of the device?
Are the current and voltage transformer (if used) connections, grounding, and phase
sequences correct?
After the wiring work is completed, check the system to make sure it is properly isolated.
Once all checks have been made, the power supply voltage may be turned on.
After the voltage has been applied, the MiCOM C264 starts up.
During start-up, various tests are carried out (see section entitled Diagnose level1 in
Chapter C264/EN MF (Maintenance)).
The LED indicator labelled HEALTHY (Fourth LED) will light up.
After approximately 30 s, the MiCOM C264 is ready for operation.
In initial, factory-set condition or after a cold restart, the front panel displays a message
AREVA.
After the settings have been made, the following checks should be carried out before any
interlocks or isolation is cancelled:
Are the software and database versions compatible with the hardware?
Are all boards correctly assigned within the MiCOM C264?
Are all IOs correctly configured and recognised by the C264?
Are all communications (S-BUS, T-BUS and L-BUS) correctly configured and
recognised?
Are the control functions fully operational?
Is the automation running?
The following chapters describe the checks to be performed to answer these questions and
ensure that the MiCOM C264 is fully operational in its application.
Commissioning C264/EN CM/C30

MiCOM C264/C264C

Page 7/14

3.2 Check version & number
In the commissioning process this panel is the first to check. The MiCOM C264 serial
number tells if the C264 is the ordered one, and indirectly gives the hardware version.
The software version from the VC document gives features and limitation of the MiCOM
C264/C264C.
The database version is given by PACiS SCE database version and describes all the
settings on the MiCOM C264/C264C.
The operational mode indicates whether the device is in a maintenance or operational mode.
S E R V I C E <time>

S E R I A L N B :

S O F T W A R E V E R S I O N :

D B 1 V E R S I O N S T A T E :

D B 2 V E R S I O N S T A T E :

O P E R A T I N G H O U R S :

O P E R A T I N G M O D E :

R E D U N D A N C Y M O D E :

C264/EN CM/C30 Commissioning

Page 8/14

MiCOM C264/C264C

3.3 Faults
If the first LED is alight, this means that there is something wrong inside the C264.
The FAULT panel gives information about the problem.
F A U L T <time>

<Description of the problem>










3.4 Check the boards status
MiCOM C264 front panel gives access to C264 boards status (refer to chapter C264/EN HI).
Board labels are defined during the configuration phase. They are based on short names
and are indexed automatically. The default configuration model is:
GHU Graphical Human Unit
BIU Basic Interface Unit (power supply)
CCU Circuit breaker Control Unit (SBO board)
DIU Digital Input Unit
DOU Digital Output Unit
AIU Analogue Input Unit (DC current and voltage input)
TMU Transducerless Measurements Unit (CT/VT board)
The product checks whether the number of installed boards matches with the number of
boards configured, the following messages are generated depending on the results:
PresConf Board configured present and operational
Failure Board configured present and faulty
ConfButMissing Board configured not present
Too Many Board not configured but present (spare)
Commissioning C264/EN CM/C30

MiCOM C264/C264C

Page 9/14

B O A R D <time>
<Board Label><Number>
<Board Status>
<Board Label><Number>
<Board Status>
<Board Label><Number>
<Board Status>
<Board Label><Number>
<Board Status>
<Board Label><Number>
<Board Status>
<Board Label><Number>
<Board Status>
Npage/Number of Pages

3.5 Checking the binary signal inputs
MiCOM C264 front panel gives access to input status for all DI boards (DIU200, DIU210,
DIU220 or CCU200).
For DIU200, DIU210 and DIU220 boards:
D I <time>
DIU <Number>

DI 0 <status> DI 8 <status>
DI 1 <status> DI 9 <status>
DI 2 <status> DI 10 <status>
DI 3 <status> DI 11 <status>
DI 4 <status> DI 12 <status>
DI 5 <status> DI 13 <status>
DI 6 <status> DI 14 <status>
DI 7 <status> DI 15 <status>

Npage/Number of Pages


C264/EN CM/C30 Commissioning

Page 10/14

MiCOM C264/C264C

For CCU200 boards:
D I <time>
CCU <Number>

DI 0 <status>
DI 1 <status>
DI 2 <status>
DI 3 <status>
DI 4 <status>
DI 5 <status>
DI 6 <status>
DI 7 <status>

Npage/Number of Pages

3.6 Checking the output relays
MiCOM C264 front panel gives access to output relays status for all DO boards (DOU200 or
CCU200).
For DOU200 boards:
D O <time>
DOU <Number>

DO 0 <status> DO 8 <status>
DO 1 <status> DO 9 <status>
DO 2 <status>
DO 3 <status>
DO 4 <status>
DO 5 <status>
DO 6 <status>
DO 7 <status>

Npage/Number of Pages


Commissioning C264/EN CM/C30

MiCOM C264/C264C

Page 11/14

For CCU200 boards:
D O <time>
CCU <Number>

DO 0 <status>
DO 1 <status>
DO 2 <status>
DO 3 <status>





Npage/Number of Pages

3.7 Testing the communication with external devices
The IED panel gives access to the connection state with external devices on Ethernet
protocol or serial links:
I E D <time>

IP CLIENT NB:

IP SERVER : <protocol>
<Server 1 Name>
<Server 1 IP address> <connection state>
<Server 2 Name>
<Server 2 IP address> <connection state>

LEGACY DEVICE : <protocol>
<IED 1 name>
<IED 1 address> <connection state>
<IED 1 name>
<IED 1 address> <connection state>

Npage/Number of Pages


C264/EN CM/C30 Commissioning

Page 12/14

MiCOM C264/C264C

3.8 Testing the control functions
The selected bay type is displayed on the Bay Panel. The activation of the Bay Panel
display is described in Chapter C264/EN HI.
If the position signals of the switchgear units are connected correctly to the MiCOM C264,
then the updated switching status of the switchgear units will be displayed on the bay panel.
If the switching status is not displayed correctly, the user can check the physical state
signals of the binary inputs to determine whether the status signals in the MiCOM C264 are
correct.
3.9 Switching from local to remote control
Bays can be controlled locally using the keys on the local control panel or remotely through
the communication interface (SCADA or operator interface).
The control point Local or Remote is selected either by means of the L/R key on the local
control panel or via appropriately configured binary signal input. If binary signal input has
been configured, then the L/R key has no effect.
Switching from Remote to Local using the L/R key on the local control panel is only possible
if the L/R password has been entered. The selected control point is displayed on the Bay
Panel.
3.9.1 Local control
Bay to be controlled is selected by pressing the Selection key on the local control panel.
If the bay is to be controlled through binary signal inputs, then the appropriate signal input
must be triggered.
3.9.2 Remote control
The switchgear units can be controlled via the communication interface or appropriately
configured binary signal inputs.
Commissioning C264/EN CM/C30

MiCOM C264/C264C

Page 13/14

4. COMMISSIONING TESTS WITH GHU210 OR GHU211(WITHOUT LCD)
After the MiCOM C264 has been installed and connected as described in Chapters C264/EN
IN and C264/EN CO, the commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked:
Is the device connected to the protective ground at the specified location?
Does the nominal (and measured) voltage of the battery agree with the nominal
auxiliary voltage of the device?
Are the current and voltage transformer (if used) connections, grounding, and phase
sequences correct?
After the wiring work is completed, check the system to make sure it is properly isolated.
Once all checks have been made, the power supply voltage may be turned on.
After the voltage has been applied, the MiCOM C264 starts up.
During start-up, various tests are carried out (see section entitled Diagnose level1 in
Chapter C264/EN MF (Maintenance)).
The LED indicator labelled HEALTHY (Fourth LED) will light up.
After approximately 30 s, the MiCOM C264 is ready for operation.
After the settings have been made, it is necessary to check that the software and the
database versions are compatible with the hardware.
The following chapters describe the checks to be performed with CMT to answer these
questions and ensure that the MiCOM C264 is fully operational in its application.
The CMT is fully described in IN chapter.
With the CMT, the Computer version button gives access to the current C264 software
version, the active database and the computer operational mode.
For a normal behaviour, the computer mode is ACTIVE
C264/EN CM/C30 Commissioning

Page 14/14

MiCOM C264/C264C

BLANK PAGE
Record Sheet C264/EN RS/C30

MiCOM C264/C264C


RECORD SHEET
Record Sheet C264/EN RS/C30

MiCOM C264/C264C

Page 1/6

CONTENT
1. SCOPE OF THE DOCUMENT 3

2. COMMISSIONING RECORD 4

3. MAINTENANCE RECORD SHEET 5

C264/EN RS/C30 Record Sheet

Page 2/6

MiCOM C264/C264C

BLANK PAGE
Record Sheet C264/EN RS/C30

MiCOM C264/C264C

Page 3/6

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264 documentation binders. It describes the
Commissioning record sheet (RS) and the Maintenance Record of this computer.
The purpose of this chapter is to follow the history of the MiCOM C264 hardware
replacement.
C264/EN RS/C30 Record Sheet

Page 4/6

MiCOM C264/C264C

2. COMMISSIONING RECORD
Commissioning Date:
Engineer:
Station Name:
Circuit Name:
Front Plate Information
Under the top access cover, there is the following type of label:
C0151ENa
C264M11I2B00012530000111S1
110 125
117268
110 / 125
Vdc
N srie
Serial n
Nominal wetting
Voltage digital inputs
S.A
Vdc
Cortec number
Serial number
Nominal Power
supply Input
Voltage
Nominal wetting
voltage for digital
inputs

Fill in the following array according to the label under the top access cover:
Serial number
Cortec number
Auxiliary voltage for power supply
Nominal wetting voltage for digital inputs

*Delete as appropriate
Have all relevant safety instructions been followed? Yes/No*
Product checks
Visual inspection with the computer de-energized
Relay damaged? Yes/No*
Rating information correct for installation? Yes/No*
Case earth installed? Yes/No*
Record Sheet C264/EN RS/C30

MiCOM C264/C264C

Page 5/6

3. MAINTENANCE RECORD SHEET
Product Serial number

DATE Engineer Board type
Slot letter in
the rack
(between A
and Q)
Previous board
Serial number
New board
Serial number
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /
/ /



C264/EN RS/C30 Record Sheet

Page 6/6

MiCOM C264/C264C

BLANK PAGE
Maintenance C264/EN MF/C30

MiCOM C264/C264C


MAINTENANCE
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 1/28

CONTENT
1. SCOPE OF THE DOCUMENT 3

2. STANDARD MAINTENANCE OPERATION 4
2.1 Level 1 diagnosis facilities 4
2.1.1 Front panel LED indications 4
2.1.2 Front panel LCD indications 6
2.1.3 Adjustment of the brightness of the front panel LCD 7
2.2 Maintenance period 7
2.3 Method of repair 7
2.3.1 Replacing the complete MiCOM C264/C264C 8
2.3.2 Replacing a board 9
2.4 Cleaning 13
3. THE EMBEDDED MAINTENANCE WEB-SERVER 14
3.1 Maintenance data pages 16
3.1.1 C264 general information page 16
3.1.2 Databases general information page 17
3.1.3 Racks and boards status page 18
3.1.4 IED networks page 19
3.1.5 CPU time and synchronisation page 20
3.2 Process data pages 22
3.2.1 Binary inputs page 22
3.2.2 Measurements page 23
3.2.3 Counters page 24
3.2.4 TPI page 25
3.3 Files upload pages 26
3.3.1 Systrap error file upload page 26
3.3.2 Stored event log file upload page 27
4. ENGINEERING MAINTENANCE OPERATION 28

C264/EN MF/C30 Maintenance

Page 2/28

MiCOM C264/C264C

BLANK PAGE
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 3/28

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264/C264C documentation binders. It describes the
Maintenance and FaultFinding procedures of the MiCOM C264/C264C. Reading of
C264/EN SA chapter is mandatory.
C264/EN MF/C30 Maintenance

Page 4/28

MiCOM C264/C264C

2. STANDARD MAINTENANCE OPERATION
The aim of this chapter is to describe standard methods to diagnose the MiCOM
C264/C264C status, and provide common maintenance procedures for the replacement
and/or addition of components.
Before any maintenance operation, please refer to the documentation chapter SA (Safety)
and to the AREVA T&D Safety Guide: SFTY/4L M/C11 (or later issue).
2.1 Level 1 diagnosis facilities
When maintenance action is planned, the operator should prepare, act and report.
The minimal preparation is to get the commissioning Record Sheet (see the C264/EN RS
chapter) of installed MiCOM C264/C264C in order to see the product configuration and its
history. The User should refer also to his own experience besides this manual. It is also
recommended to extract the logbook history in order to be informed of the intervention
conditions.
At a first level the product provides several methods to check the context of the fault. The
main ones are:
LEDs
LCD (Liquid Crystal Display)
2.1.1 Front panel LED indications
Refer to C264/EN HI chapter for the precise Leds description.
On the main rack:

Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 5/28

The first 5 LEDs indicate the MiCOM C264/C264C status information. With reference to the
C264/EN HI (Human Interface) chapter, the LEDs indicate from top to down:
LED id Colour LED on LED slow
blinking
LED fast blinking LED off
1 Red There is at least one
major fault
(hardware, database)
There is at least
one minor fault
(I/O board,
communication to
IEDs, )
Not used There is
no fault
2 yellow All the alarms are
acknowledged, but
there is at least one
alarm still active.
NOTE: When the
alarm disappears, the
LED returns
automatically to OFF
All alarms
displayed in the
alarm panel are
inactive and
acknowledged
There is at least
one not
acknowledged
alarm displayed in
the alarm panel
There is
no alarm.
3 yellow Computer in service Computer in
maintenance
Computer in test Computer
in reboot
4 Green Power up is present Not used Not used Power up
is out
5 (Fixed
only for
without
LCD panel:
GHU2x1)
Red All bays managed by
the computer are in
LOCAL mode
Bays managed by
the computer are
not in the same
control mode
Not used All bays
managed
by the
computer
are in
REMOTE

C264/EN MF/C30 Maintenance

Page 6/28

MiCOM C264/C264C

A minor fault is a fault causing only the non-availability of a part of the functionality:
Phenomenon LED status Possible reason Way to solve
Functions like
communication,
automation, printing
are well operating
and the watch dog on
BIU (see chapter
C264/EN CO) is
SET.
All LEDs are OFF The cable between CPU
and GHU2xx, or
GHU2xx itself is not
operational
Verify the connection
between CPU or
GHU2xx.
If connection is OK and
the problem is not
already solved then
change the GHU2xx
board.
The supply is ON and
the watch dog on BIU
(see chapter
C264/EN CO) is
RESET.
All LEDs are OFF Problem with BIU board
or CPU board
Replace BIU board or
CPU board.
C264 is not running
or not fully
operational
LED1 ON Incoherent database Download a coherent
database.
Hardware fault Go in Fault panel and
Board panel to
determine the faulty
board and change it.
C264 is not fully
operational
LED1 is blinking A IED is disconnected Go into IED panel to
determine the
disconnected IED and
verify the cable, the BIU
configuration, the
communication
parameters inside the
PACiS configurator, the
communication
parameters inside the
relay.
The printer is
disconnected
Go into Fault panel and
verify that paper is
available, the printer is
switch ON, the printer
cable.
A problem about clock
synchronisation
Go into Fault panel and
verify that the external
clock is switch ON, the
external clock is
connected to the
antenna, the external
clock is connected to the
C264.
A problem about PLC
(ISaGRAF)
Go into Fault panel and
connect the ISaGRAF
workbench to the C264.
Verify the behaviour of
the PLC.
2.1.2 Front panel LCD indications
GHU200 or GHU210 board gives access to the status of the boards, the state of digital
inputs, the state of digital outputs, the connection state with external devices. The CM
chapter describes this.
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 7/28

2.1.3 Adjustment of the brightness of the front panel LCD
When button and button are pressed simultaneously it is possible to
increase (resp. decrease) the brightness of the front panel LCD by pressing button
(resp. button )
2.2 Maintenance period
It is recommended that AREVA T&D EAI products receive periodic monitoring after their
installation. Deterioration may occur over time. Because of the electrical and disturbed
environment, it is recommended to confirm at regular intervals that the MiCOM C264 is
operating correctly.
The AREVA MiCOM C264/C264C has been designed for a life cycle of over 15 years.
MiCOM C264/C264C is self-supervising and therefore requires less maintenance than
previous products. Most problems will lead to an alarm so fast and appropriate action can be
done. However, some periodic tests should be done to ensure the MiCOM C264/C264C is
operating correctly and that the external wiring in a good condition.
If a Preventative Maintenance Policy exists within the customers organisation then the
recommended product checks should be included in the regular programme. Maintenance
periods will depend on many factors, such as:
the operating environment
the accessibility of the site
the amount of available manpower
the importance of the installation in the power system
the consequences of failure
2.3 Method of repair
If the MiCOM C264/C264C should develop a fault whilst in service, depending on the nature
of the fault, the watchdog contacts will change state and an alarm condition will be flagged.
Due to the extensive use of surface-mount components (SMC) faulty boards should be
replaced, as it is not possible to perform repairs on damaged circuits with SMC technology.
Thus either the complete MiCOM C264/C264C or just the faulty board, identified by the in-
built diagnostic software, can be replaced.
The preferred method is to replace the complete MiCOM C264/C264C as it ensures that the
internal circuitry is protected against electrostatic discharge and physical damage at all times
and overcomes the risk of incoherency with the new boards. In some cases, it may be
difficult to remove an installed MiCOM C264/C264C due to limited access in the back of the
cubicle and rigidity of the scheme wiring then only the faulty elements will be replaced.
Replacing boards can reduce transport costs but requires clean, dry on site conditions and
higher skills from the person performing the repair. If an unauthorised service centre
performs the repair, the warranty will be invalidated.
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT,
THE USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE
SAFETY AND TECHNICAL DATA CHAPTERS (AREVA T&D SAFETY
GUIDE: SFTY/4L M/C11 OR LATER ISSUE) AND THE RATINGS ON THE
EQUIPMENT'S RATING LABEL.
THIS SHOULD AVOID INCORRECT HANDLING OF THE ELECTRONIC
COMPONENTS AND DAMAGE.
C264/EN MF/C30 Maintenance

Page 8/28

MiCOM C264/C264C

2.3.1 Replacing the complete MiCOM C264/C264C
The case and rear terminal blocks have been designed to facilitate removal of the complete
MiCOM C264/C264C.
Before working at the rear of the MiCOM C264/C264C, isolate all the voltages and currents
connected to the MiCOM C264/C264C.
NOTE: The MiCOM C264/C264C have current transformer shorting switches
which close when terminal block is removed.
2.3.1.1 Replacing the complete MiCOM C264/C264C
Before any disconnection, check the labels correctly define the connectors and match with
the wishing description you have. Otherwise, note the current wiring in order to prepare the
new C264 installation.
1. Disconnect the power supply connector
2. Disconect the MiCOM C264/C264C IRIG-B, fibre optic, Ethernet RJ45 and serial links
connected on CPU board.
3. Disconnect the input/output connectors
4. Disconnect earth connection
There are two types of terminal block used on the MiCOM C264/C264C:
C0112ENa
2
4
6
8
10
12
14
16
18
20
22
24
26
28
1
1
24
CT/VT
Earthing
connection
Connector
fixation screw
Connector
fixation screw
3
5
7
9
11
13
15
17
19
21
23
25
27

FIGURE 1: LOCATION OF SECURING SCREWS FOR TERMINAL BLOCKS
NOTE: The use of a magnetic bladed screwdriver is recommended to
minimise the risk of the screws being left in the terminal block or lost.
A 3 mm flat head screwdriver is recommended for fixation screws. A 6
mm flat head screwdriver is recommended for CT/VT earthing
connections.
Without exerting excessive force or damaging the scheme wiring, pull the terminal blocks
away from their internal connectors.
Remove the screws used to fasten the MiCOM C264/C264C to the panel, rack, etc. These
are the screws with the larger diameter cross heads that are accessible when the access
covers are fitted and open.
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 9/28

IF THE TOP AND BOTTOM ACCESS COVERS HAVE BEEN REMOVED,
DO NOT REMOVE THE SCREWS WITH THE SMALLER DIAMETER
HEADS WHICH ARE ACCESSIBLE. THESE SCREWS HOLD THE FRONT
PANEL ON THE MiCOM C264/C264C.
5. Withdraw the MiCOM C264/C264C from the panel or rack carefully and take care of
its weight because there are some heavy parts due to the internal transformers.
2.3.1.2 Installation of new C264
To reinstall the repaired or new MiCOM C264/C264C, follow the above previous in reverse.
Ensure that each terminal block is relocated in the correct position and the case correctly
earthed, IRIG-B and fibre optic connections are put back in place.
Once reinstallation is complete the MiCOM C264/C264C should be commissioned again
using the instructions in CM chapter.
2.3.2 Replacing a board
To replace any of the MiCOM C264/C264Cs boards it is necessary to remove the front
panel.
Before removing the front panel the auxiliary supply must be switched off. It is also strongly
recommended that the voltage and current transformer connections and trip circuit are
isolated.
Open the top and bottom access covers. With size 80TE cases the access covers have two
hinge-assistance T-pieces which clear the front panel moulding when the access covers are
opened by more than 120, thus allowing their removal.
If fitted, remove the transparent secondary front cover. A description of how to do this is
given in Chapter C264/EN IT (Introduction).
By applying outward pressure to the middle of the access covers, they can be bowed
sufficiently so as to disengage the hinge lug allowing the access cover to be removed. The
screws that fasten the front panel to the case are now accessible.
The size 40TE case has four cross head screws fastening the front panel to the case, one in
each corner, in recessed holes. The size 80TE case has an additional two screws, one
midway along each of the top and bottom edges of the front plate. Undo and remove the
screws.
DO NOT REMOVE THE SCREWS WITH THE LARGER DIAMETER
HEADS WHICH ARE ACCESSIBLE WHEN THE ACCESS COVERS ARE
FITTED AND OPEN. THESE SCREWS HOLD THE MiCOM C264/C264C IN
ITS MOUNTING (PANEL OR CUBICLE).
When the screws have been removed, the complete front panel can be pulled forward and
separated from the metal case.
CAUTION SHOULD BE OBSERVED AT THIS STAGE BECAUSE A CABLE
CONNECTS THE FRONT PANEL TO THE REST OF THE MICOM
C264/C264C CIRCUITRY.
Additionally, from here on, the internal circuitry of the MiCOM C264/C264C is exposed and
not protected against electrostatic discharges, dust ingress, etc. Therefore ESD precautions
and clean working conditions should be maintained at all times.
C264/EN MF/C30 Maintenance

Page 10/28

MiCOM C264/C264C


FIGURE 2: MiCOM C264C WITH TMU200/TMU220 BOARD

FIGURE 3: MiCOM C264C WITHOUT TMU200/TMU220 BOARD
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 11/28


FIGURE 4: MiCOM C264 WITH TMU200/TMU220 BOARD

FIGURE 5: MiCOM C264 WITHOUT TMU200/TMU220 BOARD
The boards within the MiCOM C264/C264C are now accessible. Figures above show the
board locations for the MiCOM C264/C264Cs in size 40TE (C264C) and size 80TE (C264)
cases respectively.
Looking to the front of the MiCOM C264/C264C with the front panel off, you can have access
to a printed circuit that connects all the boards together: this is the backplane board.
C264/EN MF/C30 Maintenance

Page 12/28

MiCOM C264/C264C

To remove a card you need to:
Pull the backplane board (FBP280 for C264 or FBP242 for C264C) out by holding it by
the two extremities.
Remove the screws and the maintain bar at the bottom of the case.
NOTE: To ensure compatibility, always replace a faulty board with one of an
identical part number and set jumpers in identical position.
All the boards are shown and described in HW chapter.
2.3.2.1 Replacement of the Binary Input Unit (BIU241)
The BIU is the power supply board located on the extreme left-hand side (slot A) of MiCOM
C264/C264C.
Pull the power supply module forward, away from the rear terminal blocks and out of the
case. A reasonable amount of force will be required to achieve this due to the friction
between the contacts of the two medium duty terminal blocks. It is then recommended to use
the special tool for extracting board (internal reference is 2070860).
Do not forget to set the jumpers on the new board in the same position as the previous one.
2.3.2.2 Replacement of the main processor board (CPU260/CPU270)
Depending on the model of the MiCOM C264/C264C the processor board carried out the
IRIG-B functionalitys so if you identify an IRIG-B connection problem you will have to
replace the processor board.
After replacement of the main processor board, all the settings required for the application
will need to be re-entered.
The CPU board is located next to the BIU board (slot B).
Do not forget to disconnect the rear cables (RJ45 Ethernet, optical fibres, IRIG-B connector
and serial links) before replacing the board and to reconnect them after.
Do not forget to set the jumpers on the new board in the same position as the previous one.
2.3.2.3 Replacement of the Ethernet switch boards (SWU20x or SWR20x or SWD20x)
The Ethernet switch board is located on slot C.
Do not forget to disconnect the rear cables (RJ45 Ethernet and optical fibres) before
replacing the board and to reconnect them after.
Do not forget to set the jumpers on the new board in the same position as the previous one.
2.3.2.4 Replacement of the I/O boards (DIU200, DIU210, DOU200, CCU200, AIU201, AIU210,
AIU211)
The I/O boards can be located in any slot from C to Q.
Do not forget to set the jumpers on the new board in the same position as the previous one.
2.3.2.5 Replacement of the Transducerless Measurements Unit (TMU)
The measurement unit is on the extreme right-hand side of MiCOM C264/C264C.
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 13/28

2.3.2.6 Refit the MiCOM C264/C264C
Before re-assembling the module with a replacement board, make sure that the address for
the replacement board is the same address that the board replaced by checking the jumpers
on the boards.
Refit the FBP board.
Screw the bar in the bottom of the case.
Refit the front panel. After refitting and closing the access covers, press at the location of the
hinge-assistance T-pieces so that they click back into the front panel moulding.
Once the relay has been reassembled after repair, it must be commissioned again (see
chapter CM).
2.4 Cleaning
Before cleaning the MiCOM C264/C264C ensure that all ac/dc supplies, current transformer
and voltage transformer connections are isolated to prevent any chance of an electric shock
whilst cleaning.
Front panel cleaning: use a smooth cloth. Do not use abrasive material or detergent
chemicals.
C264/EN MF/C30 Maintenance

Page 14/28

MiCOM C264/C264C

3. THE EMBEDDED MAINTENANCE WEB-SERVER
The Maintenance Web server is only embedded in a CPU270 ( also name CPU 3) board.
This server can be accessed via the Internet Network with a standard web browser ( Internet
Explorer 5.0 minimum or Mozilla Firefox 1.5 minimum).
An URL is defined to access this webserver. Operator has to know the IP address of the
computer to establish the link.
Two level of access rights are defined depending on User name and associated password
according to the following table:
User name password Access rights
level1 level1 Maintenance data
level2 level2 Maintenance data and upload files
When operator connects to the webserver the following dialog box is displayed.

FIGURE 6: THE LOGIN DIALOG BOX
After correct name and password are entered the home page is displayed. The user can
choose the language ( English / French / Deutch / Spanish) then select the information to be
displayed.
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 15/28


FIGURE 7: WEBSERVER HOME PAGE
C264/EN MF/C30 Maintenance

Page 16/28

MiCOM C264/C264C

3.1 Maintenance data pages
3.1.1 C264 general information page
This page gives the following information:
the computer identification ( name, serial number, IP addresses for port 1 and 2)
information about software ( version, date, database compatibility)
the computer operating mode ( OPERATIONAL / MAINTENANCE / TEST)
the computer operating mode ( ACTIVE / STANDBY / NO REDUNDANCY)

FIGURE 8: C264 GENERAL INFORMATION PAGE
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 17/28

3.1.2 Databases general information page
For each of the two databases this page gives the following information:
name
version
status (STANDBY / CURRENT)

FIGURE 9: DATABASE GENERAL INFORMATION PAGE
C264/EN MF/C30 Maintenance

Page 18/28

MiCOM C264/C264C

3.1.3 Racks and boards status page
This page gives the following information:
the composition of the computer
the status of each board ( configured and present / configured and absent / present
and not configured / faulty)
the status ( valid ON / valid OFF) of the binary inputs of boards BIU241, DIU2x0,
CCU200 ( if configured and present)
the status ( valid OPEN / valid CLOSE) of the binary outputs of boards BIU241,
DOU200, CCU200 ( if configured and present)

FIGURE 10: RACKS AND BOARDS STATUS PAGE
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 19/28

3.1.4 IED networks page
This page gives the following information:
list of the configured IEDs
protocol type and port for each legacy bus
status ( connected / not connected) of each IED

FIGURE 11: IED NETWORKS PAGE
C264/EN MF/C30 Maintenance

Page 20/28

MiCOM C264/C264C

3.1.5 CPU time and synchronisation page
This page gives the following information:
3.1.5.1 CPU information
the computer date and time
the total functioning time
Temperature
Voltage
year number stored in SRAM
3.1.5.2 IRIG-B information
status ( present / not present)
validity
signal level
3.1.5.3 Synchronisation information
UTC date
local date
time zone
synchronism status ( synchronous / not synchronous)
synchronism equipment active ( Operator / IRIG-B / RCP / Sbus)
synchronism equipment present ( Present / Not present)
synchronism equipment priority ( 0 to 3)
System master clock ( Yes / No)

Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 21/28


FIGURE 12: CPU TIME AND SYNCHRONISATION PAGE

C264/EN MF/C30 Maintenance

Page 22/28

MiCOM C264/C264C

3.2 Process data pages
When the user requests the display of one these pages the computer performs the
acquisition of all the related information ( binary inputs, measurement, counters, TPI) then
displays them ( date and time, name, status).
3.2.1 Binary inputs page

FIGURE 13: BINARY INPUTS PAGE
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 23/28

3.2.2 Measurements page

FIGURE 14: MEASUREMENTS PAGE
C264/EN MF/C30 Maintenance

Page 24/28

MiCOM C264/C264C

3.2.3 Counters page

FIGURE 15: COUNTERS PAGE
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 25/28

3.2.4 TPI page

FIGURE 16: TPI PAGE
C264/EN MF/C30 Maintenance

Page 26/28

MiCOM C264/C264C

3.3 Files upload pages
This page allows the operator to upload two types of files
3.3.1 Systrap error file upload page

FIGURE 17: SYSTRAP ERROR FILE UPLOAD PAGE

FIGURE 18: A SYSTRAP ERROR FILE
Maintenance C264/EN MF/C30

MiCOM C264/C264C

Page 27/28

3.3.2 Stored event log file upload page

FIGURE 19: STORED EVENT LOG FILE UPLOAD PAGE

FIGURE 20: AN STORED EVENT LOG FILE
C264/EN MF/C30 Maintenance

Page 28/28

MiCOM C264/C264C

4. ENGINEERING MAINTENANCE OPERATION
The CMT software is able to:
Upgrade the C264 software
Download and switch the databases
Download the software key
These functions are needed for customising the C264. Please report to the IN chapter.
The CMT user guide is also completely described inside the CMT online help.

Lexical C264/EN LX/C30

MiCOM C264/C264C


LEXICAL
Lexical C264/EN LX/C30

MiCOM C264/C264C

Page 1/12

CONTENT
1. SCOPE OF THE DOCUMENT 3

2. LEXICAL 4

C264/EN LX/C30 Lexical

Page 2/12

MiCOM C264/C264C

BLANK PAGE
Lexical C264/EN LX/C30

MiCOM C264/C264C

Page 3/12

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264 documentation binders. It is the lexical.
C264/EN LX/C30 Lexical

Page 4/12

MiCOM C264/C264C

2. LEXICAL
AC Alternating Current
A/D Analog/Digital
ADC Analogue to Digital Converter
AI Analogue Input (Measurement Value including state attribute)
Commonly Voltage or current DC signals delivered by transducers,
and representing an external value (refer to CT/VT for AC).
AIS Air Insulated Substation
AIU Analogue Input Unit
Computer C264 Board name for DC Analogue Input
Alarm An alarm is any event tagged as an alarm during configuration phase
AO Analogue Output
Value corresponding to a desired output current applied to a DAC.
API Application Programming Interfaces
AR Auto-Reclose
ARS Auto-Recloser
ASCII American Standard Code for Information Interchange
ASDU Application Specific Data Unit
Name given in OSI protocol for applicative data (T103, T101..)
ATCC Automatic Tap Change Control
Same as AVR, automation charged to regulate secondary voltage
AVR Automatic Voltage Regulator
Automatism used to regulate secondary voltage by automatic tap
changer control (see ATCC). Set of features can be added, see
chapter C264 FD
Bay Set of LV, MV or HV plants (switchgears and transformers) and
devices (Protective, Measurement) usually around a Circuit
Breaker and controlled by a bay computer.
BCD Binary Coded Decimal
One C264 supported coding on a set of Digital Input, that determine a
Digital Measurement, then Measurement value (with specific invalid
code when coding is not valid). Each decimal digit is coded by 4
binary digit.
BCP Bay Control Point
Name given to the device or part used to control a bay. It can be
Mosaic Panel , C264 LCD Local Control Display), Usually
associate with Remote/Local control.
BI Binary Input (or Information)
Name given into Computer C264 of information already filtered,
before it becomes a SPS, DPS with time tag and quality attributes
BIU Basic Interface Unit
Computer C264 Board for auxiliary power supply, watchdog relay,
redundancy I/O
BNC A connector for coaxial cable.
B-Watch Monitoring and control device for GIS substation.
CAD Computer Aided Design
Computer application dedicated to design like wiring, protective
setting
CAS CASe
Computer C264 rack
Lexical C264/EN LX/C30

MiCOM C264/C264C

Page 5/12

CB

Circuit Breaker
Specific dipole switch with capability to make line current and break
fault current. Some have isolation capability (nominal-earth at each
side)
CC Complemented Contact
CCU Circuit breaker Control Unit
Computer C264 Board dedicated to switch control with 8DI, 4 DO
CDM Conceptual Data Modelling
Is the modelisation of system/devices data using a hierarchy of
structured data (called object of class) with their attributes, method or
properties and the relations between themselves.
It maps common data to devices or components of devices, with
guaranty of interoperability.
CM
CMT Computer Maintenance Tool
COMTRADE Common Format For Transient Data Exchange ( international
standard IEC 60255-24)
CPU Central Processing Unit
Computer C264 main Board based on PowerPC
CRC Cyclic Redundancy Check
Coding result send with packet of transmitted data to guarantee their
integrity. Usually result of a division of transmitted data by polynomial.
CSV Character Separate Values
ASCII values separated by predefined character or string like in Excel
or ASCII Comtrade.
CT Current Transformer
Basically the electric device connected to process and extracting a
current measurement. By extension part of a device (C264) that
receives AC values and convert it to numerical measurement value.
CT/VT
(Conventional)
Current and Voltage transformers
By extension, it is the C264 TMU board.
CT/VT
(Non-Conventional or
intelligent)
Current and Voltage transformers
New generation of captor based for example on light diffraction under
electric field, without transformer, that give s directly numerical
measurement of voltage and current like communicating IED.
DAC Digital to Analogue Converter
Used to generate analogue signals (usually DC) from a digital value.
DB DataBase
Tool or set of data that define all configuration of a system or specific
device like computer. Opposed to setting or parameter DB has a
structure that can not be modified on line. DB are always versioned.
DB-9 A 9-pin family of plugs and sockets widely used in communications
and computer devices.
DBI Dont Believe It
Term used for undefined state of a double point when input are not
complementary. DBI00 is state motion or jammed. DBI11 is
undefined.
DC Direct Current
DC, DPC Double (Point) Control
Two digit and/or relays outputs used for device control with
complementary meaning (OPEN, CLOSE).
C264/EN LX/C30 Lexical

Page 6/12

MiCOM C264/C264C

DCF77 External master clock and protocol transmission
LF transmitter located at Mainflingen, Germany, about 25 km south-
east of Frankfurt/Main, broadcasting legal time on a 77.5 kHz
standard frequency.
DCP Device Control Point
Located at device level (electric device or IED). It should have its own
Remote/Local switch.
DCS Digital Control System
Generic name of system based on numeric communication and
devices, to be opposed to traditional electrically wired control.
DCT Double CounTer
Counter based on 2 DI with complementary states (counting
switchgear manoeuvre for example)
DE Direct Execute
Device Term used for one of the following unit:
Protective relays, metering units, IED, switchgear (switching device
such as CB, disconnector or earthing switch), disturbance or quality
recorders.
DI Digital Input:
Binary information related to the presence or to the absence of an
external signal, delivered by a voltage source.
DIN Deutsche Institut fr Normung
The german standardisation body.
DIU DC Input Unit
Computer C264 Board name for Digital Input
DM Digital Measurement
Is a measurement value which acquisition is done by DI and a
specific coding BCD, Gray, 1 among N
DNP3.0 Distributed Network Protocol
DNP3 is a set of communication protocols used between components
in process automation systems.
DO Digital Output
Used to apply a voltage to an external device via a relay, in order to
execute single or dual, transient or permanent commands.
DOU Digital Output Unit
Computer C264 Board name for Digital Output
DP Double Point
Information/control derived from 2 digital inputs/output; usually used
for position indication of switching devices (OPEN, CLOSE).
DPC Double Point Control
DPS Double Point Status
Position indication of switching devices (OPEN, CLOSE).
ECU Extended Communication Unit.
External module connected to the CPU board. This module converts
non-insulated RS232 into optical signal or insulated RS485/RS422.
EH90 Transmission protocol dedicated to time synchronisation and
standardised by EDF. Specification document: D.652/90-26c, March
1991.
EMC Electro-Magnetic Compatibility
Event An event is a time tagged change of state/value acquired or
transmitted by a digital control system.
Lexical C264/EN LX/C30

MiCOM C264/C264C

Page 7/12

FAT Factory Acceptance Test
Validation procedures execution with the customer at factory.(i.e.
SAT)
FBD Functional Block Diagram
One of the IEC61131-3 programming languages (language used to
define configurable automation).
FIFO First In First Out
FO Fibre Optic
FP Front Panel
FTP Foil Twisted Pair
Gateway Level 6 session of OSI, the gateway is any device transferring data
between different networks and/or protocol. The RTU function of
C264 gives a gateway behaviour to SCADA or RCP level. PACIS
Gateway is separate PC base device dedicated to this function.
GHU Graphic Human interface Unit
Computer C264 Front Panel digital part (LCD, buttons, Front RS)
GHU Graphical Human Unit
Front panel of C264 with LCD and buttons
GIS Gas Insulated Substation
GMT Greenwich Mean Time
Absolute time reference
GPS Global Positioning System
Based on triangulation from satellite signal, that transmit also
absolute GMT time used to synchronise a master clock
GOOSE Generic Object Oriented Substation Event
Group Logical combination of BI (i.e. SP, DP, SI or other groups).
Hand Dressing Facility for an operator to set manually the position of a device
(acquired by other means) from the HMI at SCP level; e.g. from
OPEN to CLOSE (without any impact on the physical position of
the electrical switching device).
HMGA Horizontal Measurement Graphical Area
HMI Human Machine Interface
Can be PACIS OI (Operator Interface) or C264 LCD (Local Control
Display) or Leds, mosaic...
HSR High Speed autoRecloser
First cycles of AR
HTML Hyper Text Mark-up Language
Used as standard for formatting web display
HV High Voltage (for example 30kV to 150kV)
I/O Input/Output
IEC International Electrotechnical Commission
IED Intelligent Electronic Device
General expression for a whole range of microprocessor based
products for data collection and information processing
IP Internet Protocol
IRIG-B Inter-Range Instrumentation Group standard format B. This is an
international standard for time synchronisation based on analogue
signal.
C264/EN LX/C30 Lexical

Page 8/12

MiCOM C264/C264C

JAMMED Invalid state of a Double Point:
Occurs when the two associated digital inputs are still in state 0 after
an user-selectable delay (i.e. when the transient state motion is
considered as ended).
Kbus
(Kbus Courier)
Term used for the protocol Courier on K-Bus network (kind of
RS422).
LAN Local Area Network
L-BUS Legacy Bus
Generic name of Legacy or field networks and protocols used to
communicate between C264 (Legacy Gateway function) and IED on
field bus. Networks are based on (RS232,) 422, 485. Protocols are
IEC 60850-5-103 (T103 or VDEW), Modbus AREVA or MODICON
LCD Liquid Crystal Display
Local Control Display
On C264
LD Ladder Diagram
One of the IEC1131-3 programming languages (language used to
define configurable automation).
LSB Least Significant Bit
LED Light Emitting Diode
LF Low Frequency
LOC Local Operator Console
Dedicated to maintenance operation
L/R Local / Remote
Local / Remote
Control Mode
When set to local for a given control point it means that the
commands can be issued from this point, else in remote control are
issue for upper devices.
LV Low Voltage
MAFS Marketing And Functional Specification
MC Modular Computer
MCB Mini Circuit Breaker. Its position is associated to tap changer.
MDIO Management Data Input/Output
A standard driven, dedicated-bus approach that is specified in
IEEE802.3
Measurements Values issued from digital inputs or analogue inputs (with value, state
and time tag).
Metering
(non-tariff)
Values computed depending on the values of digital or analogue
inputs during variable periods of time (time integration).
Metering
(tariff)
Values computed depending on the values of digital or analogue
inputs during variable periods and dedicated to the energy
tariffication. These values are provided by dedicated tariff
computer which are external to the MiCOM Systems.
MIDOS AREVA Connector: Used for CT/VT acquisition
MMC Medium Modular Computer
ModBus Communication protocol used on secondary networks with IED or
with SCADA RCP. 2 versions exist with standard MODICON or
AREVA one.
Module Word reserved in PACIS SCE for all electric HV devices. It groups all
switch-gears, transformer, motors, generators, capacitors,
Lexical C264/EN LX/C30

MiCOM C264/C264C

Page 9/12

MOTION Transient state of a Double Point
Occurs when the two associated digital inputs are momentarily in
state 0 (e.g. position indication when an electrical device is
switching). The concept of momentarily depends on a
user-selectable delay.
MPC Protection Module for Computer
MV Medium Voltage
MVAR Mega Volt Ampere Reactive
NBB Numerical Busbar Protection
NC Normally Closed (for a relay)
NO Normally Open (for a relay)
OBS One Box Solution
Computer that provides protection and control functions with local
HMI. The prime application of this device is intended for use in
substations up to distribution voltage levels, although it may also be
used as backup protection in transmission substations. Likewise, the
OBS may be applied to the MV part of a HV substation that is being
controlled by the same substation control system.
OI Operator Interface
OLE Object Linking and Embedding
OLE is a Microsoft specification and defines standards for interfacing
objects.
OLTC On Line Tap Changing
OPC OLE for process control
OPC is a registered trademark of Microsoft, and is designed to be a
method to allow business management access to plant floor data in a
consistent manner.
Operation hours Sum of time periods, a primary device is running under carrying
energy, e.g. circuit breaker is in Close state and the current is
unequal 0 A.
OSI Open System Interconnection
Split and define communication in 7 layers : physical, link, network,
transport, session, presentation, application
PACiS Protection, Automation and Control Integrated Solutions
PLC Programmable Logic Control
Within the PLC-programs are defined the configurable control
sequences or automations taken into account by the MiCOM
Systems.
POW Point On Wave
Point on wave switching is the process to control the three poles of
an HV-circuit breaker in a way, to minimise the effects of switching.
PSL Programmable Scheme Logic
PSTN Public Switched Telephone Network
PT100 Probes of temperatures providing analogue signals.
RCC Remote Control Centre
Is a computer or system that is not part of MiCOM system. RCC
communicates with and supervises MiCOM system using a protocol.
C264/EN LX/C30 Lexical

Page 10/12

MiCOM C264/C264C

RCP Remote Control Point
Name given to the device or part used to control remotely several bay
or sub-station. Usually associate with Remote/Local sub-station
control. It is a SCADA interface managed by the MiCOM system
through Telecontrol BUS. Several RCPs can be managed with
different protocols.
Remote Control Mode When set for a given control point it means that the commands are
issued from an upper level and are not allowed from this point.
Remote HMI Remote HMI is a client of the substation HMI server. The client may
provide all or part of functions handled by the substation HMI.
RI Read Inhibit
This output indicates the availability of an analogue output (e.g.
during DAC converting time)
RJ-45 Registered Jack-45
A 8-pin female connector for 10/100 Base-T Ethernet network
RMS Root Mean Square
RRC Rapid ReClosure
RS-232 Recommended standard 232
A standard for serial transmission between computers and peripheral
devices.
RS-422 A standard for serial interfaces that extends distances and speeds
beyond RS-232. Is intended for use in multipoint lines.
RS-485 A standard for serial multipoint communication lines. RS-485 allows
more nodes per line than RS-422
RSVC Relocatabled Static Var Compensator
RTC Real Time Clock
RTU Remote Terminal Unit
Stand alone computer that acquires data and transmit them to RCP
or SCADA. Typically it is the C964. RTU link is the TBUS.
SAT Site Acceptance Test
Validation procedures executed with the customer on the site.
SBMC Site Based Maintenance Control mode
A bay in SBMC mode does not take into account the commands
issued from RCP; moreover, some of its digital points and
measurements (defined during the configuration phase) are not sent
anymore to the RCP (they are automatically suppressed).
SCADA Supervisory Control And Data Acquisition
SCE System Configuration Editor
SBO Select Before Operate
A control made in two steps, selection and execution. Selection
phase give a feedback. It can be used to prepare, reserve during
time, configure circuit before execution.
Controls are done into a protocol, or physical (DO select with DI
Select then DO execute).
S-BUS Station Bus
Federal network between PACIS devices.
SCADA Supervisory Control And Data Acquisition
Equivalent to RCC
SCP Substation Control Point
Name given to the device or part used to control locally several bays
or sub-station. Usually associate with Remote/Local sub-station
control. It is commonly PACIS Operator Interface.
Lexical C264/EN LX/C30

MiCOM C264/C264C

Page 11/12

SCS Substation Control System
SCT Single Counter
Setpoints (analogue) Analogue setpoints are analogue outputs delivered as current loops.
Analogue setpoints are used to send instruction values to the process
or to auxiliary devices.
Setpoints (digital) Digital values sent on multiple parallel wired outputs Each wired
output represent a bit of the value. Digital setpoints are used to send
instruction values to the electrical process or to auxiliary devices.
SFC Sequential Function Chart
One of the IEC1131-3 programming languages (language used to
define configurable automation).
SI System Indication
Binary information that do not come from external interface. It is
related to an internal state of the computer (time status, hardware
faults). It is the result of all inner function (AR, ), PSL, or
ISaGRAF automation.
SICU 4 Switchgear Intelligent Control Unit
Control unit of an intelligent circuit breaker (fourth generation)
SINAD Signal-plus-Noise-plus-Distorsion to Noise-plus-Distorsion ratio.
SINAD is fully expressed in dB.
SOE Sequence Of Events
Other term for the event list.
SP
SPS
SPC
Single Point
Single Point Status
Single Point Control
ST Structured Text
One of the IEC1131-3 programming languages (language used to
define configurable automation).
STP Shielded Twisted Pair
Substation computer Bay computer used at substation level.
Suppression
(Automatic)
A binary information belonging to a bay in SBMC mode will be
automatically suppressed for the remote control. However changes of
state will be signalled locally, at SCP.
Suppression (Manual) A binary information can be suppressed by an order issued from an
operator. No subsequent change of state on a suppressed
information can trigger any action such as display, alarm and
transmission.
SWR Switch Redundant
Computer C264 board Ethernet switch with redundant Ethernet
SWU Switch Unit
Computer C264 board Ethernet switch
T101 Term used for IEC60870-5-101 protocol
T103 Term used for IEC60870-5-103 protocol
T104 Term used for IEC60870-5-104 protocol
TBC To Be Completed
TBD To Be Defined
T-BUS Telecontrol Bus
Generic name of networks and protocols used to communicate
between PACIS Gateway or C264 Telecontrol Interface function and
the RCP. Networks are based on RS232, 485, or Ethernet (T104).
Protocols are IEC 60850-5-101 (T101), Modbus MODICON
C264/EN LX/C30 Lexical

Page 12/12

MiCOM C264/C264C

TC True Contact
TCIP Tap Changer in Progress
TCU Transformer Current Unit
Computer C264 CT/VT Board : Current acquisition
TDD Total Demand Distorsion
The total demand distortion is similar to the THD but applied to
currents and with a rated current (I
n
) as reference
THD Total Harmonic Distorsion
The total harmonic distortion represents the sum of all voltage
harmonics
TMU Transducerless Measurement Unit
Topological
interlocking
Interlocking algorithm, based on evaluation of topological information
of the switchgear arrangement in the HV network, the switchgear kind
and position, and defined rules for controlling this kind of switch (e.g.
continuity of power supply)
TPI Tap Position Indication (for transformers).
Frequently acquired via a Digital Measurement
TVU Transformer Voltage Unit
Computer C264 CT/VT Board : Voltage acquisition
UCA Utility Communications Architecture
Communication standard (mainly US) used for PACIS SBUS
communication
UPI Unit Per Impulse
Parameter of counter to convert number of pulse to Measurement
value. Both data (integer and scaled float) are in common class
UCA2 Accumulator.
UTC Universal Time Co-ordinates (or Universal Time Code)
Naming that replace GMT (but it is the same)
VDEW Term used for IEC60870-5-103 protocol
VMGA Vertical Measurement Graphical Area
Voltage level Set of bays whose plants and devices are dealing with the same
voltage (e.g. 275kV, 400 kV).
VT Voltage Transformer
Basically the electric device connected to process and extracting a
voltage measurement. By extension part of a device (C264) that
receives this AC value and convert it to numerical measurement
value. VT are wired in parallel.
WYE Three phases + neutral AI values



AREVA T&D's Automation & Information Systems Business www.areva-td.com