Technical Data C264R/EN TD/C12

MiCOM C264-R


TECHNICAL DATA
Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 1/20

CONTENT
1. SCOPE OF THE DOCUMENT 3

2. CONFORMITY 4

3. GENERAL DATA 5
3.1 Design 5
3.2 Installation Position 5
3.3 Degree of Protection 5
3.4 Weight 5
3.5 Dimensions and Connections 5
3.6 Terminals 5
3.7 Creepage Distances and Clearances 6
4. RATINGS 7
4.1 Auxiliary Voltage 7
4.2 Digital inputs 7
4.2.1 DIU200 7
4.2.2 DIU210 8
4.2.3 CCU200 9
4.3 Digital outputs 10
4.3.1 DOU200 10
4.3.2 CCU200 10
4.3.3 BIU241 11
4.4 Analogue inputs 11
4.5 Analog Output 12
5. BURDENS 14
5.1 Auxiliary Voltage 14
5.2 Power supply 14
5.3 CPU board 14
5.4 Digital inputs 14
5.4.1 DIU200 14
5.4.2 DIU210 14
5.4.3 CCU200 15
5.5 Digital outputs 15
5.5.1 DOU200 15
5.5.2 CCU200 15
C264R/EN TD/C12 Technical Data

Page 2/20

MiCOM C264-R

5.6 Analogue inputs 15
5.7 Analogue outputs 15
5.8 Ethernet Switches 15
5.9 Front panels 16
6. ACCURACY 17

7. TYPE TESTS 18
7.1 Dielectric Withstand 18
7.2 Mechanical Test 18
7.3 Atmospheric Test 19
7.4 DC Auxiliary Supply Test 19
7.5 AC Auxiliary Supply Test 20
7.6 EMC 20

Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 3/20

1. SCOPE OF THE DOCUMENT
This document is a chapter of MiCOM C264 documentation binders, describing the
Technical data of this computer.
C264R/EN TD/C12 Technical Data

Page 4/20

MiCOM C264-R

2. CONFORMITY
(Per Article 10 of EC Directive 72/73/EC).
The product designated MiCOM C264/C264C computer has been designed and
manufactured in conformance with the European standards EN 60255-6 and EN 61010-1
and with the EMC Directive and the Low Voltage Directive issued by the Council of the
European Community.
Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 5/20

3. GENERAL DATA
3.1 Design
Surface-mounted case suitable for wall installation or flush-mounted case for 19 cabinets
and for control panels.
3.2 Installation Position
Vertical 15
3.3 Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 60529.
IP52 for the front panel.
IP52 for the rack of MiCOM C264C.
IP20 for the rack of MiCOM C264.
3.4 Weight
Case 40 TE: approx. 4 kg
Case 80 TE: approx. 8 kg
3.5 Dimensions and Connections
See dimensional drawings (Hardware description section C264_EN_HW) and terminal
connection diagrams (C264_EN_CO).
3.6 Terminals
PC Interface:
DIN 41652 connector, type female D-Sub, 9-pin on the front panel.
A direct wired cable is required.
Ethernet LAN (in the rear panel through the CPU260 board):
RJ-45 female connector, 8-pin for the 10/100Base-T self-negotiation.
ST female connector for the 100Base-F.
IRIG-B Input (optional, in the rear panel through the CPU260 board):
BNC plug.
Conventional communication links:
M3 threaded terminal ends, self-centring with wire protection for conductor cross sections
from 0.2 to 2.5 mm for BIU241 board.
DIN 41652 connector; type D-Sub, 9-pin on the CPU260 board in the rear panel.
Optical fibres trough ECU200 (external RS232/optical converter): optical plastic fibre
connection per IEC 874-2 or DIN 47258 or ST glass fibre optic connection (ST is a
registered trademark of AT&T Lightguide Cable Connectors)
Inputs /Outputs or power supply modules:
M3 threaded terminal ends, self-centring with wire protection for conductor cross sections
from 0.2 to 2.5 mm for DIU200, DIU210, DOU200, CCU200, AIU201, AIU210, AOU200 and
BIU241 boards.
The I/O boards and BIU241 are equipped with a 24-way 5.08 mm pitch male connector.
C264R/EN TD/C12 Technical Data

Page 6/20

MiCOM C264-R

3.7 Creepage Distances and Clearances
Per EN 61010-1 and IEC 664-1.
Pollution degree 2, working voltage 250 V.
Overvoltage category III, impulse test voltage 5 kV.
Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 7/20

4. RATINGS
4.1 Auxiliary Voltage
MiCOM C264/C264C computers are available in four auxiliary voltage versions, specified in
the table below:
Version Nominal ranges Operative DC range Operative AC range
A01 24 V
DC
19.2 28.8 V -
A02 48 to 60 V
DC
38.4 72 V -
A03 110 to 125 V
DC
88 150 V -
A04 220 V
DC
and V
AC
176 264 V 176 264 V
The nominal frequency (Fn) for the AC auxiliary voltage is dual rated at 50/60Hz, the operate
range is 45Hz to 65Hz.
The main characteristics of the BIU241 board are:
Power supply: 40 W
Nominal output voltage: + 5V
Supply monitoring
Power loss withstands capacity: 50 ms
Protection against polarity reversal
Insulation resistance: >100 M ( CM) at 500 V
DC

Dielectric withstand: 2 kV (CM) 50 Hz during 1min
4.2 Digital inputs
4.2.1 DIU200
The DIU200 board is available in four nominal voltage versions that characteristics are
specified in the table below.
The DIU200 board has 16 digital inputs.
Version Nominal voltage (+/-20%) Triggering threshold (V
DC
)
A01 24 V
DC
if V >10.1 V
DC
Input status is set
if V < 5 V
DC
Input status is reset
A02 48 to 60 V
DC
if V >17.4 V
DC
Input status is set
if V < 13.5 V
DC
Input status is reset
A03 110 to 125 V
DC
if V > 50 V
DC
Input status is set
if V< 34.4 V
DC
Input status is reset
A04 220 V
DC
if V > 108 V
DC
Input status is set
if V< 63 V
DC
Input status is reset

C264R/EN TD/C12 Technical Data

Page 8/20

MiCOM C264-R

The DIU200 board is designed to allow 2 inputs serially connected. This answers to the
following need:
C0124ENa
C264
IN1 IN2
0 VDC
Un
R

If R is open then IN1 and IN2 are set.
If R is closed then IN1 is set, IN2 is reset.
With this scheme, when IN1 is reset, this means that there is a problem into the external
wiring.
The input current at nominal voltage is detailed in chapter 5.4.
There are at maximum 15 DIU boards (including DIU200 and DIU210) inside a C264 rack.
4.2.2 DIU210
The DIU210 board works for all voltages between 24V and 220 DC (+/- 20%).
The DIU210 board has 16 digital inputs.
Whichever voltage, the triggering threshold is 19V
DC
The maximum number of DIU210 board in one C264 rack depends on the rack type and on
the voltage level of inputs.
Please refer to the following table:
Maximum
DIU210 boards in 40TE racks
Maximum
DIU210 boards in 80TE racks
24V 2 8
48V 6 15
110-125V 3 10
>=220V 1 5
Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 9/20

The DIU210 board is designed to allow 2 inputs serially connected. This answers to the
following need:
C0124ENa
C264
IN1 IN2
0 VDC
Un
R

If R is open then IN1 and IN2 are set.
If R is closed then IN1 is set, IN2 is reset.
With this scheme, when IN1 is reset, this means that there is a problem into the external
wiring.
The input current at nominal voltage is detailed in chapter 5.4.
There are at maximum 15 DIU boards (including DIU200 and DIU210) inside a C264 rack.
4.2.3 CCU200
For versions A1 to A4 of the CCU200 board the characteristics of the eight inputs are the
same as the DIU200 board.
For version A7 of the CCU board the characteristics of the eight inputs are:
nominal voltage ( +/- 20%): 110-125 Vcc with
triggering threshold: if V
input
> 86 V
DC
input status is set
triggering threshold: if V
input
< 67 V
DC
input status is reset
There are at maximum 15 CCU200 boards inside a C264 rack.
C264R/EN TD/C12 Technical Data

Page 10/20

MiCOM C264-R

4.3 Digital outputs
4.3.1 DOU200
The characteristics of the Output Relay Contacts of the DOU200 board are specified in the
table below:
Features Values
Operating voltage 24 to 250 V
DC
/ 230 V
AC

Make 2,5A
Carry 2,5A continuous
30 A for 500 ms or 100 A for 30 ms
Break DC: 50 W resistive, 15 W inductive (L/R = 20 ms)
AC: 1250 VA resistive, 1250 VA inductive (cos = 0,7)
In these conditions, the contact resistance is still lower
than 250 m for 10000 operations
Operating time Break < 7 ms
8 simple pole contacts Normally open
2 double pole contacts 1 Normally open +1 Normally close
Isolation: 2 kV 50 Hz (CM)
The board is designed and monitored to avoid inadvertent controls.
There are at maximum 15 DOU200 boards inside a C264 rack..
4.3.2 CCU200
The characteristics of the 4 Output Relay Contacts of the CCU200 board are specified in the
table below:
Each relay of the CCU board has double pole contacts. To get the characteristics described
below, the two output contacts of each relay are to be wired in serial.
Features Values
Operating voltage 24 to 250 V
DC
/ 230 V
AC

Make 5A
Carry 5A continuous
30 A for 500 ms or 250 A for 30 ms
Break DC: 100 W resistive, 30 W inductive (L/R = 40 ms)
AC: 1250 VA resistive, 1250 VA inductive (cos = 0,7)
In these conditions, the contact resistance is still lower
than 250 m for 10000 operations.
Operating time Break < 7 ms
Double pole contacts Normally open
Isolation: 2 kV 50 Hz (CM).
The board is designed and monitored to avoid inadvertent controls.
There are at maximum 15 CCU200 boards inside a C264 rack.
Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 11/20

4.3.3 BIU241
The characteristics of the Watchdog Relay Contacts of the BIU241 board are the same as
the contacts NO+NC contacts of the DOU200 board.
The characteristics of the two output relays used for C264 redundancy are the same as the
single pole one on the DOU200 board.
4.4 Analogue inputs
The AIU201 board provides 4 independent analogue inputs. Each AI can be configured in
voltage or current range individually as specified in the table below:
Type Ranges
Current input range 1mA
2,5 mA
5 mA
10 mA
20 mA
4-20 mA
Voltage input range 1,25V
2,5V
5 V
10V
Sampling period 100 ms
Accuracy 0,1% full scale at 25C
AD conversion 16 bit
Common mode rejection ratio (CMMR) > 100dB
Serial mode rejection ratio (SMMR) > 40dB
gains range (user-selectable) 1, 2, 4, 10
Input impedance for voltage inputs 11 K
Input impedance for current inputs 75
The ranges are defined during the configuration phase.
The current/voltage selection is done by choosing the input number of the connector.
There are at maximum 6 AIU boards (including AIU201 and AIU210) inside a C264 rack.
C264R/EN TD/C12 Technical Data

Page 12/20

MiCOM C264-R

The AIU210 board provides 8 analogue inputs (1 common point for two inputs) . Each AI
can be configured in the current range as specified in the table below:
Type Ranges
Current input range 1mA
2,5 mA
5 mA
10 mA
20 mA
4-20 mA
Sampling period 100 ms
Accuracy 0,1% full scale at 25C
AD conversion 16 bit
Common mode rejection ratio (CMMR) > 100dB
Serial mode rejection ratio (SMMR) > 40dB
gains range (user-selectable) 1, 2, 4, 10
Input impedance for current inputs 75
The ranges are configured during the configuration phase.
A maximum of 6 AIU boards (including AIU201 and AIU210) can be installed inside a C264
rack.
4.5 Analog Output
The AOU200 board provides 4 current analogue outputs. Each output is associated to a
Read Inhibit relay. The Outputs are powered using an external power supply.
The analogue outputs, the relays and the power supply are designed as one isolated group.
The external power supply has to provide a regulated voltage of +48V5% 120W.
Up to 4 AOU200 boards can be used in one computer rack.
Output Characteristics:
Value Maximal Impedance
5 mA
( 20% 6mA)
4K
10 mA
( 20% 12mA)
2K
20 mA
( 20% 24mA)
1K
Precision is 0,1% of full scale + 20% at 25C after calibration.
The maximum deviation is <100ppm/C between -10C et +70C.
Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 13/20

The current output is stable 100ms after the order. In association with a RI relay, the
management is as follows (the value can be read when the RI relay is closed):

AOUx
RI relay
10 ms 10 ms
100 ms
C0287ENa

Relays characteristics: WatchDog Relay and RI relays
Contact type NO
Max operating voltage 250 Vdc / 230 Vac
Make and Carry
2,5 A continuous
30A for 500ms
100A for 30ms
Break dc: 50 W resistive, 15W inductive(L/R =
40ms).
ac: 1250 VA resistive,
1250VA inductive (cos=0,7 relay
duration is lower)
Operating time < 7ms


C264R/EN TD/C12 Technical Data

Page 14/20

MiCOM C264-R

5. BURDENS
5.1 Auxiliary Voltage
The MiCOM C264/C264C computer burdens are specified in the table below:
Version Nominal Maximum
C264C 15W 22W
C264 20W 40W
5.2 Power supply
The BIU241 board burden on the internal 5V bus is 1,25W. This takes into account
watchdog, redundancy relays and communication ports.
The efficiency of the power supply is 78%.
5.3 CPU board
The CPU200 board burden on the internal 5V and 12V bus is 3,3W.
5.4 Digital inputs
5.4.1 DIU200
The DIU200 board burdens are specified in the table below:
Version Nominal wetting voltage Current at Un (mA)
A01 24 V
DC
3.5
A02 48 to 60 V
DC
5 for 48 V
DC

6.8 for 60 V
DC

A03 110 to 125 V
DC
2.5 for110 V
DC

3 for 125 V
DC

A04 220 V
DC
2
The DIU200 board burden on the internal 5V bus is 75mW.
5.4.2 DIU210
The DIU210 board burdens are specified in the table below:
Nominal wetting voltage Current at Un (mA)
24 V
DC
>25
48 to 60 V
DC
3.8
110 to 125 V
DC
4
220 V
DC
4.1
The DIU210 board burden on the internal 5V bus is 75Mw.
Power consumption per input:
Un = 24V to 110V DC: 0,5W 30% per input
Un > 110V: 5mA 30%
From 48V to 220Vdc wetting voltage, a high current consumption is created on binary inputs
during a short period and circulates through external binary contacts to clean them. See the
peak current response curve.
WARNING: FOR THE 24V WETTING VOLTAGE, THERE IS NO SHORT PEAK
CURRENT BECAUSE OF THE PERMANENT HIGH CONSUMPTION ON
INPUTS >25mA.
Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 15/20

The current peak response curve.
C0159ENa
Tension (V)
C
u
r
r
e
n
t

(
m
A
)
35
30
25
20
15
10
5
0
0 50 100 150 200 250 300


5.4.3 CCU200
The CCU200 inputs consumption is specified in the table below:
Version Nominal wetting voltage Current at Un (mA)
A01 24 V
DC
3.5
A02 48 to 60 V
DC
5 for 48 V
DC

6.8 for 60 V
DC

A03 110 to 125 V
DC
2.5 for 110 V
DC

3 for 125 V
DC

A04 220 V
DC
2
A07 110 to 125 V
DC
3.4 for 110V
DC
5.4 for 132V
DC
5.5 Digital outputs
5.5.1 DOU200
The DOU200 board burden on the internal 5V bus is 250mW plus 200mW per activated
relay.
5.5.2 CCU200
The CCU200 board burden on the internal 5V bus is 400mW plus 200mW per activated
relay.
5.6 Analogue inputs
The AIU201 and the AIU210 boards burden on the internal 5V bus is 1 W.
5.7 Analogue outputs
The AOU200 board burden on the internal 5V bus is 120 mA (maxi).
On the external power supply source , the board burden is 160 mA (integrating the output
consumption: 4*20mA).
5.8 Ethernet Switches
The SWU200/SWU202 board burden on the internal 5V bus is 3,85W with 2 optical ports.
The SWR202 board burden on the internal 5V bus is 4 W.
C264R/EN TD/C12 Technical Data

Page 16/20

MiCOM C264-R

5.9 Front panels
The GHU200 and GHU210 board burden on the internal 5V bus is 600mW when the LCD
screen is not back-lighted and 3W when the LCD screen is back-lighted.
The GHU201 and GHU211 board burden on the internal 5V bus is 600mW.
The GHU202 and GHU212 board burden on the internal 5V bus is <1mW.
Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 17/20

6. ACCURACY
For all specified accuracy, the repeatability is 2.5% unless otherwise specified.
If no range is specified for the validity of the accuracy, then the specified accuracy shall be
valid over the full setting range.
Reference Conditions
Quantity Reference conditions Test tolerance
General
Ambient temperature 20 C 2 C
Atmospheric pressure 86kPa to 106kPa -
Relative humidity 45 to 75 % -
Input energising quantity
Current I
N
5%
Voltage V
N
5%
Frequency 50 or 60Hz 0.5%
Auxiliary supply DC 48V, 110V or 220V
AC 220V
5%
C264R/EN TD/C12 Technical Data

Page 18/20

MiCOM C264-R

7. TYPE TESTS
7.1 Dielectric Withstand
Type Test Name Type Test Standard Conditions
Insulation Resistance IEC 60255-5 100 M at 500 Vdc (CM & DM)
Dielectric Withstand IEC60255-5
IEEE C37.90
50 Hz, 1mn, 2kV (CM), 1kV (DM)
High Voltage Impulse
Test
IEC 60255-5 5 kV CM & 3 kV DM
7.2 Mechanical Test
Type Test Name Type Test Standard Conditions
2 falls of 5 cm (Computer not powered) Free Fall Test
Free Fall Packaging
Test
IEC 60068-2-31
IEC 60068-2-32
25 falls of 50 cm (Packaging computer)
Vibration Response
Powered On
IEC 60255-21-1 Class 2:
Acceleration: 1g from 10 to 150Hz
Vibration Response
Not Powered On
IEC 60255-21-1 Class 2:
Acceleration: 2g from 10 to 500Hz
Vibration Endurance
Not Powered On
IEC 60068-2-6 Class 2:
Acceleration: 1g from 10 to 500Hz
Shocks Not Powered
On
IEC 60255-21-2 Class 1:
15g, 11 ms
Shocks Powered On IEC 60255-21-2 Class 2:
10g, 11 ms
Bump Test Not
Powered On
IEC 60255-21-2 Class 1:
10g, 16ms, 2000/axis
Seismic Test Powered
On
IEC 60255-21-3 Class 2:
Acceleration: 2g
Displacement: 7.5mm upon axe H
Acceleration: 1g
Displacement: 3.5mm upon axe V
Technical Data C264R/EN TD/C12

MiCOM C264-R

Page 19/20

7.3 Atmospheric Test
Type Test Name Type Test Standard Conditions
Damp Heat Test
Operating
IEC 60068-2-3 Test Ca:
+40C / 10 days / 93% RH
Cold Test - Operating IEC 60068-2-1 Test Ab: - 25c / 96 H
Cold Test - Storage IEC60068-2-1 Test Ad:
-40C / 96h
Powered On at 25C (for information)
Dry Heat Test
Operating
IEC 60068-2-2 70c / 24 H
Dry Heat Long Test
Operating
DICOT HN 46-R01-06 55c / 10 days
Dry Heat Test Storage IEC 60068-2-1 Test Bd:
+70C / 96h
Powered On at +70C
Enclosure Protection IEC 60529 Front: IP=52
7.4 DC Auxiliary Supply Test
Type Test Name Type Test Standard Conditions
Inrush current (start-up) DICOT HN 46-R01-4 T < 1.5 ms / I < 20 A
1.5ms < T < 150 ms / I < 10 A
T > 500 ms / I < 1.2 In
Supply variation IEC 60255-6 Vn 20%
Vn+30% & Vn-25% for information
Overvoltage (peak
withstand)
IEC 60255-6 1.32 Vn max
2 Vn during 10 ms (for information)
Ramp down to zero / From Vn down to 0 within 1 minute
From Vn down to 0 within 100 minutes
Ramp up from zero / From 0 up to Vn within 1 minute
From 0 up to Vn within 100 minutes
Supply interruption IEC 60255-11 From 2.5 ms to 1 s at 0.8 Vn
50 ms at Vn, no malfunction
Reverse polarity / Polarity for the lower potential of the
supply
Polarity + for the lower potential of the
supply
Ripple (frequency
fluctuations)
IEC 60255-11 12% Vn at f=100Hz or 120Hz
12% Vn at f=200Hz for information
C264R/EN TD/C12 Technical Data

Page 20/20

MiCOM C264-R

7.5 AC Auxiliary Supply Test
Type Test Name Type Test Standard Conditions
Supply variations IEC 60255-6 Vn 20%
AC Voltage dips & short
interruptions
EN 61000-4-11 2ms to 20ms & 50ms to 1s
50 ms at Vn, no malfunction
Frequency fluctuations IEC 60255-6 50 Hz: from 47 to 54 Hz
60 Hz: from 57 to 63 Hz
Voltage withstand / 2 Vn during 10 ms (for information)
7.6 EMC
Type Test Name Type Test Standard Conditions
High Frequency
Disturbance
IEC 60255-22-1
IEC 61000-4-12
IEEE C37.90.1
Class 3: 2.5kV (CM) / 1kV (DM)
Electrostatic discharge IEC 60255-22-2
IEC 61000-4-2
Class 4:
8kV contact / 15 kV air
Class 3:
10 V/m 80 to 1000 MHz
& spot tests
Radiated Immunity IEC 60255-22-3
IEC 61000-4-3
IEEE C37.90.2
35 V/m 25 to 1000 MHz
Fast Transient Burst IEC 60255-22-4
IEC 61000-4-4
IEEE C37.90.1
Class 4: 4kV 2.5kHz (CM)
Class 4: 2.5kV 2.5kHz (DM) on DI/DO
Surge immunity IEC 61000-4-5

Class 4:
4kV (CM) 2kV (DM)
High frequency
conducted immunity
IEC 61000-4-6 Class 3:
10 V, 0.15 80 MHz
Harmonics Immunity IEC 61000-4-7 5% & 10% de H2 H17
Power Frequency
Magnetic Field Immunity
IEC 61000-4-8 Class 5:
100A/m for 1mn
1000A/m for 3s
Pulse magnetic field
immunity
IEC 61000-4-9 Class 5:
6.4 / 16 s
1000A/m for 3s
Damped oscillatory
magnetic field immunity
IEC 61000-4-10 Class 5:
100 kHz & 1 MHz 100A/m
Power Frequency IEC 61000-4-16 CM 500 V / DM 250 V via 0.1 F
Conducted emission EN 55022 Gr. I, class A: from 0.15 to 30 MHz
Radiated emission EN 55022 Gr. I, class A: from 30 to 1000 MHz