210T, 211T, 210K

TRANSCOPEPNEUMATIC
TRANSMITTER & INDICATOR
PRODUCT DESCRIPTION
The 210T and 211T Transmitters are available for the measurement of temperature, pressure,
volumetric pressure, liquid level or absolute pressure. They provide an output signal proportional
to the measured variable in the range of 3 to 15 psi (0.2 to 1.0 kg/cm2) (20 to 100 kPa). Measuring
element driven alarms are available. For piped and mounted air supply sets see File 7-1B.
The 210K is an Indicator only. It matches the 210T in performance specifications and
appearance. This indicator can also be equipped with measuring element driven alarms.
Large Dial Indication 11 3/4 in. (298 mm) Long
Single Package Pneumatics Simplifies Maintenance
Proven Actual Elements Interchangeale with FULSCOPE Recorders,
Controllers and Indicators
Enclosed Motion Amplifier Eliminates Dead Spot
Low Cost Alarms Servo Actuated
SPECIFICATIONS
Accuracy:
+Transmission Signal: 0.5%
+Indication: 1%
Threshold Sensitivity: 0.1%
Hysteresis: 0.1% of input span
Air Supply: 18 psi Minimum(125kPa)
20 psi Recommended (140 kPa)
25 psi Maximum (170 kPa)
Warning: Use of a supply gas other than air can
create a hazardous environment because a small
amount of gas continuously vents to atmosphere.
Ambient Temperature Limits: -40
0
F(-40
0
C) minimum
and 180
0
F(82
0
C) maximum.
Ambient Temperature Effect:0.5% for 100
0
change
in case temperature between 50F and 150F (10
0
C
and 65
0
C):
Suppression: Available on some elements. Consult
individual Measwing element.
+ For most primary elements.
Case: 7 9/16 in. x 9 3/4 in. x 4 1/2 in.
(192 mm x 248 mm x 114 mm)
Materials: Die cast aluminium
Finish:Grey Butoxy Resin
Weight : Approx. 9 lb. (4.1 kg) for Pressure Transmitter
with Bourdon Element.
Mounting: Universal Bracket
Air Connections: 1/4 Int. NPT
Bottom : Std. Back: Optional
Scale: 11 3/4 in. (298mm) long 270 ARC black figures
and graduations on white
Glass: Std.- Double strength Plate.
Optional: Safety glass, Antiglare or clear plastic.
Not available on Termination No. 36 & 42
ABB
ORDERING INFORMATION
Refer to the sample catalog number and select an appropriate code to describe the instrument from each of the underlined
categories.
BASE INSTRUMENT
210T_ _ Indicating Transcope Pneumatic Transmitter (Note 1)
211T_ _ Non-Indicating Transcope Pneumatic Transmitter (Note 1)
210K_ _ Transcope Indicator only (Note 1)
ACTUATION
Process Actuating Element Term No. Range Limits Refer to
Variable File No.
A Abs Pressure Brass Bellows 36 0 to 30 psia (200kPa) 4-2
F Gage Receiver Bellows 37 0 to 27.5 psig(190kPa) 4-2
F Pressure Brass Bellows 36 20.4 Hg Vac. -30 psig (69 kPa to 200 kPa) 4-2
F 316SS Capsule. 42 0-30 psig (200 kPa) 4-2
F 316SS Bourdan 38 30 Hg Vac - 1800 psig(101kPa to 12,000kPa) 4-2A
D Differential Brass Bellows 36 30 Hg Vac to 30 psig (101 kPa to 200kPa) 4-2
Pressure
M Temperature Mercury Class V-A -38
0
F to 1,200
0
F (-38.9
0
C to 667
0
C) 4-1
G Gas Class III-B -40
0
F to 392
0
F (-40
0
C to 200
0
C) 4-1
MOVEMENT
0 Non Indicating(211T only)
1 Indicating with Primary Driven Pointer
ELEMENT TERMINATION NUMBER
36 See Element Termination Table Above
SAMPLE CATALOG NUMBER
210T F 1 36
MEASURING ELEMENT DRIVEN (Available in 210T Series)
Hermetically sealed Mercury Bottle Type for Class 1, Division 2 Service, Groups A, B, C, D
One Electric without index pointer
Two Electric without index pointer
One Electric with index pointer
Two Electric with index pointer
Not Available on 211T Non-Indicating Transmitters
NOTES: 1. Specify Dial Range.
Measuring Element Driven Alarms
for 210T Series Transmitters
Low Detent Less Than 0.1%
Primary Actuated Independent of Air Supply
Set Point Indication On 11 3/4 in. Scale
Single Or Double Alarms For High and Low Protection
PRODUCT DESCRIPTION
A permanent magnet attached to the primary linkage actuates the leaf contact in a
mercury bottle switch. This switch is positioned by a colour-coded knob located inside
the instrument case to prevent unauthorised adjustment. In the indicating form (available
only on 210T and 210K instruments) a colour-coded pointer shows the alarm set point.
Red denotes HIGH or Rising and Orange LOW or Falling. Double alarms have two
magnets, switches and adjusting knobs.
SPECIFICATIONS
Adjustment Span: Low Alarm - 0 to 90%
High Alarm - 0 to 100%
Detent: Less than 0.1% of Span with most
primaries
Differential Gap: 4% of Span
Differential Between Alarms: 5% to 100% of Span
Number of Alarms: Two Electrical
Repeatability: Within 0.5%
Accuracy of Alarm-Set Indication: 0.25% in center of span;
2.0% in balance of range.
Contact Arrangement: Single Pole, Single Throw(NO or NC)
Electrical Connections:Barrier Type Terminal Strip
Electrical Classification: Class I Div. 2 Groups A,B,C,D
Contact Rating- Volts 24 115 230
Amps 0.9ac 0.3ac 0.15ac
0.45 dc 0.15 dc 0.07 dc
HIGH LOW TYPE
0 - None 0 - None 1- Without Set-Point Indication
1 - N.O. 1 - N.O. 2 - With Set-Point Indication
2 - N.C 2 - N.C.
Factory Setting of Alarms
Single Alarm: Factory set on rising process variable
Dual Alarms: High - set on rising process variable
Low - set on falling process variable
Example: Catalog Number 210TF138 denotes an Indicating Pressure Transmitter. To order with High
and Low Indicating Alarms and contacts that open when alarm point is reached, change the
catalog number to 210TF138-222.
ORDERING INFORMATION
Add a dash and a suffix number to the instrument catalog number, as shown below:
Sample Suffix Number
High
Low
Type
2 2 2
ABB
Asea Brown Boveri Limited
14, Mathura Road,
P.O. Amar Nagar,
Faridabad-121003, Haryana (India)
Phone: 5275592/5593/5597
5276350/6354/6362/6367
Fax: 0129-5275019
S
S

2
-
1
-
I
N
D

I
S
S
U
E

9
The Companys policy is one of continuous product
improvement and the right is reserved to modify the
specifications contained herein without notice.
2002 ABB Printed in India

You might also like