UL Type MV-105+ PowerGuard-XL Underground Distribution Cable

AL Conductor 345 Mils TRXLPE 100% Insulation Level Concentric Neutral XLPE Jacket
Manufactured by Seoul Electric Cable Co., Ltd

Description
Single conductor cable with filled strand aluminum conductors, triple extruded dry cured insulation
system consisting of a thermosetting semiconducting conductor shield, high dielectric strength
PowerGuard-XL TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, water blocking agents, black encapsulating cross-linked polyethylene jacket.

Insulation Temperature Rating


Normal ..................................................105C
Emergency*..........................................140C
Short Circuit .........................................250C
*Operation at the emergency overload temperature shall not exceed 1500 hours cumulative during
the lifetime of the cable.
Specifications
ASTM B-231
AEIC CS8
ICEA S-94-649
ICEA T-31-610
ICEA T-34-664 as applicable for TRXLPE insulated concentric neutral cable
UL 1072 MV-105
Applications
PowerGuard-XL cables are intended for use in wet or dry locations for distribution of single or
three phase medium-voltage power. These cables may be installed in ducts or direct buried.
Options
Copper Conductors
Factory Warranty
20 Years

AMERICAN WIRE GROUP


1920 E. Hallandale Beach Blvd.
Suite PH8
Hallandale, Florida 33009
Telephone: 1-954-455-3050
Fax: 1-954-455-9886
E-Mail: sales@buyawg.com

TOLL FREE 1-800-342-7215


www.buyawg.com

Information on this sheet subject to change without notice.


Copyright 2013, American Wire Group, Inc. Hallandale, Florida

315
20130213

MEDIUM VOLTAGE CABLES

Design Parameters
Conductor: Class A or B Compressed concentric stranded aluminum alloy 1350 per ASTM B 231.
Stranded conductors are water-blocked with conductor filling compound.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the
conductor and bonded to the insulation.
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in
ANSI/ICEA S-94-649 - 100% insulation level.
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: Solid bare copper wires helically applied and uniformly spaced.
Water Block: Water-blocking agents applied over the insulation shield and around the neutral wires
to resist longitudinal water penetration. Longitudinal water penetration shall be tested in accordance with the latest edition of ICEA T-34-664 except that the minimum requirement is 15 psig for 1
hour.
Jacket:The outer jacket is an extruded-to-fill black non-conducting cross-linked polyethylene jacket,
meeting the physical requirements of Table 1 when tested by the methods specified in ANSI/ICEA S94-649. The jacket shall be free-stripping and not interfere with an intimate contact between the neutral wires and the underlying extruded insulation shield. The jacket shall contain a print legend
marking, sequential length marking and three longitudinal extruded red stripes.
Physical Properties of Extruded-to-Fill XLPE Jacket
Unaged Tensile Strength, min. (PSI) ....1500
Aged* Tensile Strength, min. ret. (%).......70
Unaed Elongated, min. (%)...................1500
Aged* Elongated, min. ret. (%) ................70
Heat Distortion 1 hr at 131C, max. (%) ...30
* Aged for 168 hrs at 121C

UL Type MV-105+ PowerGuard-XL Underground Distribution Cable


AL Conductor 345 Mils TRXLPE 100% Insulation Level Concentric Neutral XLPE Jacket
Manufactured by Seoul Electric Cable Co., Ltd

CONDUCTOR

MEDIUM VOLAGE CABLES

AL Size Nominal
AWG or Diameter1
kcmil
(in)
1/0
1/0
1/0
1/0
2/0
2/0
2/0
2/0
3/0
3/0
3/0
3/0
4/0
4/0
4/0
4/0
250
250
250
250
350
350
350
350
500
500
500
500
750
750
750
750
1000
1000
1000
1000
1250
1250
1250
1500
1500
1500

0.362
0.362
0.362
0.362
0.406
0.406
0.406
0.406
0.456
0.456
0.456
0.456
0.512
0.512
0.512
0.512
0.558
0.558
0.558
0.558
0.661
0.661
0.661
0.661
0.789
0.789
0.789
0.789
0.968
0.968
0.968
0.968
1.117
1.117
1.117
1.117
1.250
1.250
1.250
1.370
1.370
1.370

INSULATION1

CONCENTRIC NEUTRAL

JACKET

Minimum
Diameter
(in)

Maximum
Diameter
(in)

Size

No. of
Wires

Size of
Wires

Nominal
Diameter
(in)

1.045
1.045
1.045
1.045
1.090
1.090
1.090
1.090
1.140
1.140
1.140
1.140
1.195
1.195
1.195
1.195
1.250
1.250
1.250
1.250
1.355
1.355
1.355
1.355
1.480
1.480
1.480
1.480
1.670
1.670
1.670
1.670
1.815
1.815
1.815
1.815
1.960
1.960
1.960
2.100
2.100
2.100

1.145
1.145
1.145
1.145
1.190
1.190
1.190
1.190
1.240
1.240
1.240
1.240
1.295
1.295
1.295
1.295
1.350
1.350
1.350
1.350
1.455
1.455
1.455
1.455
1.580
1.580
1.580
1.580
1.770
1.770
1.770
1.770
1.920
1.920
1.920
1.920
2.065
2.065
2.065
2.205
2.205
2.205

Full
2/3
1/2
1/3
Full
2/3
1/2
1/3
Full
2/3
1/2
1/3
Full
2/3
1/2
1/3
2/3
1/2
1/3
1/6
2/3
1/2
1/3
1/6
2/3
1/2
1/3
1/6
1/2
1/3
1/6
1/12
1/2
1/3
1/6
1/12
1/3
1/6
1/12
1/3
1/6
1/12

12
13
10
7
15
16
12
9
19
13
15
11
23
15
12
8
19
14
10
8
16
20
13
11
23
18
12
10
17
18
14
15
22
23
12
10
18
15
12
22
18
14

14
16
16
16
14
16
16
16
14
14
16
16
14
14
14
14
14
14
14
16
12
14
14
16
12
12
12
14
10
12
14
16
10
12
12
14
10
12
14
10
12
14

1.409
1.382
1.382
1.382
1.453
1.427
1.427
1.427
1.503
1.503
1.477
1.477
1.559
1.559
1.559
1.559
1.663
1.663
1.663
1.637
1.803
1.770
1.770
1.743
1.927
1.927
1.927
1.894
2.188
2.146
2.112
2.086
2.339
2.297
2.297
2.263
2.484
2.442
2.408
2.654
2.612
2.578

WEIGHTS
Aluminum
Weight
/MFT
(lb)
99
99
99
99
125
125
125
125
157
157
157
157
199
199
199
199
235
235
235
335
329
329
329
329
469
469
469
469
704
704
704
704
939
939
939
939
1173
1173
1173
1408
1408
1408

Copper
Weight
/MFT
(lb)
153
104
80
56
192
129
96
72
243
166
120
88
294
192
153
102
243
179
128
64
325
256
166
88
467
366
244
128
549
366
179
120
711
467
244
128
582
305
153
711
366
179

Net
Weight4
/MFT
(lb)
946
869
850
831
1038
948
923
904
1151
1090
1013
987
1278
1196
1166
1125
1404
1353
1312
1216
1718
1602
1530
1420
2083
2001
1904
1746
2709
2468
2246
2142
3226
2931
2752
2581
3513
3185
2952
4081
3691
3454

AMPACITY
DIRECT BURIED
Flat2
Tre-Foil3

216
217
217
217
250
250
250
251
285
285
286
286
326
327
327
328
360
361
361
362
427
429
431
435
505
511
522
530
592
610
638
651
659
682
727
761
720
727
836
759
821
892

217
217
217
217
250
250
251
251
266
286
286
287
328
328
329
329
362
362
363
363
431
433
434
436
522
525
530
533
628
637
648
656
718
735
757
772
798
837
863
855
899
934

1) Extruded layer thicknesses and insulation and insulation shield diameters are in accordance with ANSI/ICEA S-94-649 for concentric neutral cables rated 5-46 kV and also meet the requirements of the latest revisions
of AEIC CS8. Dimensions and weights not designated as minimum or maximum are nominal values and are subject to manufacturing tolerances.
2) Ampacities based on cables operating in a 3-phase installation with one cable per phase, flat spaced and touching, earth rho of 90C-cm/ W, earth ambient of 20C, neutral wires grounded at both ends, 75% load factor, conductor temperature of 90C, and 36 depth of burial.
3) Ampacities based on cables operating in a 3-phase installation with one cable per phase, flat spaced and touching, earth rho of 90C-cm/ W, earth ambient of 20C, neutral wires grounded at both ends, 75% load factor, conductor temperature of 90C, and 36 depth of burial.
+) UL Type MV-105 PowerGuard-XL is rated MV-105 in accordance with the UL 1072 Standard. It should be noted that utilizing a 105C normal operating conductor temperature will increase cable ampacity rating but
will reduce the shield fault capability slightly. If the user plans on operating these cables at 105C conductor temperature for normal operation and 140C for emergency overload, please contact American Wire Group
for the applicable cable ampacity and shield fault capability ratings. Another important consideration is that the migration of soil moisture away from the cable is more likely at the higher operating conductor temperature and can result in an increase in soil thermal resistivity, resulting in an increase in conductor and soil temperature.

AMERICAN WIRE GROUP

TOLL FREE 1-800-342-7215


www.buyawg.com
315
20130213

1920 E. Hallandale Beach Blvd.


Suite PH8
Hallandale, Florida 33009
Telephone: 1-954-455-3050
Fax: 1-954-455-9886
E-Mail: sales@buyawg.com

Information on this sheet subject to change without notice.


Copyright 2013, American Wire Group, Inc. Hallandale, Florida

You might also like