PROVISION FOR THE USE OF CERTAIN CONSTRUCTION MATERIALS
FSD-DS-3.15.1_Intumescent Paints Revision A Page 1 of 1 Material: INTUMESCENT PAINTS FSD DS No: 3.15.1 Item Provisions Notes 1.0 Intumescent paints are permitted for use on structural steel members of buildings of all purpose groups with the exception of purpose groups VI (Factories) and VIII (Storage) to achieve the required fire resistance.
2.0 For buildings with a habitable height of not more than 24m, intumescent paints are allowed to be used to protect steel columns and beams.
3.0 For buildings with a habitable height of more than 24m, intumescent paints are permitted fro use only on structural steel beams, excluding load transfer beams.
4.0 Intumescent Paints shall be subjected to and pass fire resistance testing as detailed in BS 476: Part 20/21 or its equivalent.
5.0 Intumescent paints shall also be subjected to weathering tests as detailed in BS8202: Part 2: 1992. Fire test for fire resistance performance shall be conducted on specimens after the weather tests. The fire resistance rating of the tested specimen shall not be les than 75% of the original prototype.
6.0 Intumescent Paints shall be listed by a QCCD approved testing authority. 7.0 In addition to the performance requirements such as but not limited to, fire resistance and flame spread indices, the use of intumescent paints shall comply with the provisions stated hereunder.
8.0 The project QP shall submit a separate set of plans indicating the locations of the structural steel members that are proposed to be coated with intumescent paint.
9.0 If the buildings habitable height exceeds 24m, a fire safety report shall be submitted together with the building plans.
10.0 A sign depicting the following minimum information shall be fixed at a conspicuous location.
10.1 Name of supplier 10.2 Fire resistance rating 10.3 Date of painting 10.4 Next date of re-painting 10.5 Caution note Caution: No other paint/coating shall be applied to the surfaces steel members protected by intumescent paint system
CIVIL DEFENCE DEPARTMENT MINISTRY OF INTERIOR, QATAR
PROVISION FOR THE USE OF CERTAIN CONSTRUCTION MATERIALS
FSD-DS-3.15.1_Intumescent Paints Revision A Page 2 of 1 Material: INTUMESCENT PAINTS FSD DS No: 3.15.1 Item Provisions Notes 11. The Fire Safety Manager, if any, shall carry out regular inspection checks to ensure that the intumescent paint coatings re not damage or tampered with. Records of inspection shall be properly kept. In eth situation where the appointment of a FSM is not required, for example building under Purpose Group II ( ), the building management shall undertake the responsibility.
12. Fore addition and alteration works in a building where structural steel members are protected by intumescent paint, the following shall be complied with.
12.1 The owner or tenant, assisted by the FSM, shall engage a QP who shall submit building plans to the SCDF. The building plans shall be accompanied by the QPs declaration as to whether the existing columns and beams coated with intumescent paint are or will be affected.
12.2 Written certification from the QP stating that he has supervised the application of the coating system(s) shall be provided.
12.3 The fire safety report shall be updated accordingly. 13. There shall be no flammable or combustible material stored within the vicinity of any structural steel members protected by intumescent paint