You are on page 1of 78

Product catalog | March 2014

Remote Terminal Units


RTU500 series

Remote Terminal Units


Content
1

RTU product catalog 2014

RTU500 series Overview

RTU560 product line

RTU540 product line

RTU520 product line

RTU511 product line

RTU500 series modules

RTU500 series functions and software

Product catalog | RTU500 series | 1/1

Remote Terminal Units


RTU product catalog 2014
1

Dear Madam and Sir,


this catalog will give you an overview of our Remote Terminal Units (RTU) product portfolio - the RTU500 series.
The products are divided into the product lines RTU560 (rack), RTU540 (DIN rail), RTU520 (DIN rail), RTU511 (migration) and
RTU500 series modules. The catalog will inform you about each single module and its additional material.
For your information: All existing and new products have been integrated in the different product lines of the RTU500 series.
The names of the established modules have not been changed.
With more than 100,000 installed RTUs at around 2,000 customers in more than 100 countries, ABB is among the world
market leader for RTU applications.
ABB has been working successfully in the area of remote control applications for more than 40 years and offers the security of
a strong and experienced partner. Worldwide presence with local partners in almost all regions allows quick access to service
and support.
For more information please ask your local sales and service contact or visit us at www.abb.com/substationautomation.
Yours sincerly,

Dr. Ditmar Heinz Sigbert Reimann Helmut Weber


Global product line manager RTU
Global product manager RTU
Global sales manager RTU

1/2 | RTU500 series | Product catalog

Remote Terminal Units


RTU500 series Overview
Your benefits at a glance
Substation automation products

2/2

Requirements for modern RTUs

2/2

Remote control products by ABB

2/2

RTU service and support

2/2

RTU500 series
Introducing RTU500 series

2/3

Product catalog | RTU500 series | 2/1

Remote Terminal Units


Overview Your benefits at a glance

Substation automation products


ABBs world-class substation automation solutions ensure
reliable power transmission and distribution. Our products
have been designed to provide interoperable and future-proof
solutions.This combined with our long experience in the field
and full scope of services and support make us a leader and
pioneer in substation automation and protection. Whats best
you will find us close to you in all parts of the world.

Requirements for modern RTUs


Today Remote Terminal Units (RTUs) can be used in a broad
range of electrical and process automation applications. Due
to different market and customer requirements, RTUs are
equipped with a flexible and modular design. Innovative technologies ensure that RTUs include modern functionalities to
continuously meet your requirements. In addition, you do not
only get reliable and efficient products, but also easy handling
and efficient services.

2/2 | RTU500 series | Product catalog

Remote control products by ABB


ABB has been working successfully in the field of remote
control applications for more than 40 years. The product portfolio comprises RTUs for various applications ranging from
transmission to distribution and feeder automation. More than
100,000 installed RTUs at around 2,000 customers in more
than 100 countries underline ABBs reputation as one of the
world market leader in RTU installations.
Continuous technological innovativeness and a close relationship to partners guarantee that ABBs RTUs will always meet
the requirements of markets and customers.
RTU Service and support
Professional service and support over the complete product
lifecycle have always been of great interest within ABB. The
high quality of technical support also adds to the track record
of RTUs, ensuring optimized and reliable system operations.
Product support of RTU specialists worldwide and support
with engineering and programming provide you effective and
reliable solutions.

Remote Terminal Units


Overview - RTU500 series

RTU500 series modules

2
RTU500 series functions and software

RTU560 product line


RTU540 product line

5,000 data points

5,000 data points

RTU520 product line

750 data points

RTU511 product line *

750 data points


* Migration RTU211 to RTU511

Feeder automation

Primary distribution
substations

Secondary distribution
substations

Product life cycle management


Through the extensive product lifecycle policy ABB has a long
standing commitment to protect its customers investments in
ABB products and technologies.
To protect your investments over a long time, existing installations can be ugraded to modern RTUs with only little effort.
The available migration kits and ABBs extensive knowledge
makes it very easy to exchange your installed base in just a
few steps.
The RTU500 series
The RTU500 series comprises ABBs complete RTU product
portfolio with a clear structure and a maximum of flexibility.
The open architecture enables adaptations to a variety of
electrical and process automation applications. Functional
and hardware extensions can be realized quickly and easily.

Transmission /
sub transmission

To ensure that our product are suitable for your specific system the RTU500 series is structured in:

RTU560
RTU540
RTU520
RTU511
RTU500
RTU500

product line
product line
product line
product line
series modules
series functions and software.

The product lines represent the basic RTU products plus those modules which can be used with a product line. Modules
which can be combined with all product lines are comprised
under RTU500 series modules, enabling customers to adapt
RTUs to their demands. For appropriate functionality of specific requirements the RTU500 series functions and software
offer one software to support all product lines.
The product lines of RTU500 series make it easy to find the
perfect match for a specific application.

Product catalog | RTU500 series | 2/3

Remote Terminal Units


RTU560 product line Reliable products for transmission and
sub-transmission

The rack-based RTU560 product line offers a flexible and


modular design with maximum possibilities for expandability.
The multi-processor architecture combined with the support
of the full software functionality of the RTU500 series provide the perfect solution for applications in transmission and
sub transmission as well as primary distribution substations.
Furthermore, the RTU560 product line offers a redundancy
concept for high reliability.
Highlights of RTU560 product line
Redundancy concept
RTU560 product line increases availability with a flexible redundancy concept which is suitable for all types of redundant
requirements:
Redundant power supply
Redundant communication links to the control center and
sub devices
Redundant pairs of communication units (CMUs)
Redundant power supplies and communication units can be
replaced even during operation, ensuring a reliable system.
Integrated human machine interface (HMI)
An integrated HMI allows RTU560 configurations without any
external components, such as additional PCs.
Multi-processor architecture
The RTU560 product line features a multi-processor
3/1 | RTU500 series | Product catalog

architecture with up to 16 CMUs. With this architecture the


RTU560 offers a higher flexible performance. It furthermore
provides a better usage of CMUs by distributing the load
among the CMUs.
Integrated real time clocks
The easy to use real time clock modules are ready for plug
and play.
ABBs real time clocks are available as:
GPS receiver: Worldwide, time information received from
global positioning system (GPS)
DCF77 Receiver: for installations in Germany and central
Europe
IRIG-B/AFNOR connector: for installations in North and
Central America
Application areas
Transmission
Sub transmission
Primary distribution substations
Your benefits
Maximum possibilities for expandability and enhancement
Modular platform with high flexibility
Different possibilities for redundancy
Multi-processor architecture with up to 16 CMUs
Support of full software functionality and available host and
sub device communication protocols
Integrated real time clock modules

Remote Terminal Units


RTU560 product line Reliable solutions for transmission and
sub-transmission
RTU560 Communication units

560CMU02
p. 3/3

560CMU05
p. 3/3

560HMR01
p. 3/4

RTU560 Power supply units

560PSR00
p. 3/5

560PSU01
p. 3/5

560PSU02
p. 3/6

RTU560 Input/output modules

23BE23
p. 3/7

23BA20
p. 3/7

23BA23
p. 3/8

23AE23
p. 3/8

23AA21
p. 3/9

23BE50
p. 3/9

23BA40
p. 3/10

23BE40
p. 3/10

RTU560 Racks

560MPR01
p. 3/11

560MPR03
p. 3/12

560SFR02
p. 3/13

RTU560 Serial communication

23OK24
p. 3/15

23WT23
p. 3/15

223WT24
p. 3/16

23WT25
p. 3/16

560NMS24
p. 3/18

560NMS34
p. 3/18

RTU560 Ethernet communication

560NUS04
p. 3/17

560NUS12
p. 3/17

RTU560 Real time clocks

560RTC01
p. 3/19

560RTC02
p. 3/19

560RTC03
p. 3/20

Product catalog | RTU500 series | 3/2

Remote Terminal Units


RTU560 product line Communication units
Communication unit (CMU) for RTU560, 2 serial ports,
2 Ethernet ports
Application
The 560CMU02 communication unit is one of the CMU boards of
the RTU560.

560CMU02
1KGT012600R0002

Description
Central module of the RTU560 with 32 bit CPU
2x serial communication interface (RS-232 or
RS-485) for local/remote communication
2x Ethernet interface (10/100BaseT)
1x serial peripheral bus
Licences for protocol, functions and compact flash
are not included.

The essential tasks are:


Managing and controlling of the I/O boards via the interfaces
to the RTU serial peripheral bus
Reading process events from the input boards
Send commands to the output boards
Communication with control centers and local HMI systems
via the integrated serial line interfaces and the implemented
Ethernet 10/100 BaseT LAN interface
Managing the time base for the RTU560 station and
synchronizing the I/O boards
Handling the dialouge between RTU560 and web browser
via LAN interface
Within the RTU racks the board occupies one slot. It contacts
itself via a DIN F socket connector to the rack. The Communication unit 560CMU02is able to handle Ethernet-, UART- and
non UART-character based communication protocols, and serial
peripheral bus.

Communication unit (CMU) for RTU560, 4 serial ports,


2 Ethernet ports
Application
The 560CMU05 communication unit is one of the CMU boards of
the RTU560.

560CMU05
1KGT012700R0002

Description
Central module of the RTU560 with 32 bit CPU
4x serial communication interface (RS-232 or
RS-485) for local/remote communication
2x Ethernet interface (10/100BaseT)
Licences for protocol, functions and compact flash
are not included.

3/3 | RTU500 series | Product catalog

The essential tasks are:


Managing and controlling of the I/O boards via the interfaces
to the RTU serial peripheral bus
Reading process events from the input boards
Send commands to the output boards
Communication with control centers and local HMI systems
via the integrated serial line interfaces and the implemented
Ethernet 10/100 BaseT LAN interface
Managing the time base for the RTU560 station and
synchronizing the I/O boards
Handling the dialouge between RTU560 and web browser
via LAN interface
Within the RTU560 racks the board occupies two slots. It contacts itself via a DIN F socket connector to the rack. The Communication unit 560CMU05is able to handle Ethernet-, UARTand all non UART-character based commuinication protocols,
and serial peripheral bus.

Remote Terminal Units


RTU560 product line Communication units
Human machine interface (HMI) for RTU560, 2 Ethernet ports,
4 USB ports, VGA, audio
Application
The 560HMR01 is a rack based human machine interface board
of the RTU560 system.

560HMR01
1KGT030100R0001

Description
Interface board to RTU500 integrated web HMI
Windows Embedded Standard 7 (english, 32 bit)
2x Ethernet interface (10/100BaseT)
4x USB port (for keyboard and mouse)
1x VGA port (for monitor)
1x stereo audio-out

The essential tasks of the 560HMR01 are:


Interface to RTUs that are running web-server and RTU560
integrated HMI. It communicates via Ethernet LAN interfaces
and provides interfaces to connect a local monitor, mouse and
keyboard
R uns Windows based operating system for RTU560 integrated HMI
The 560HMR01 takes two slots of the module rack. The connection from the 560HMR01 to the 19 rack is done via a DIN 41612
F-connector.

Product catalog | RTU500 series | 3/4

Remote Terminal Units


RTU560 product line Power supply units
Power supply unit for RTU560, 24...60 VDC, 44.3W
Application
The power supply unit 560PSR00 generates the two supply
voltages (5 VDC and 24 VDC) for the RTU560 racks 560MPR03
and 560SFR02. The output power is sufficient to supply a subrack with up to 4 communication units.

560PSR00
1KGT026500R0001

Description
Power supply unit for RTU560 racks
Input voltage 24...60 VDC
Output voltage: 5 and 24 VDC
Suitable for redundant power supply in
560MPR03/560SFR02

It is possible to configure redundant power supplies for project


configurations with higher requirements to availability. In this
configuration 2 power supply units 560PSR00 are operating in
parallel mode. They are able to take over the load, if one power
supply fails. Only power supplies of the same type and rubric
should be used for redundant operation.
The power supply unit 560PSR00 is available in the following
version (rubric):
R0001: Input range 24...60 VDC (-20...+15%)

Power supply unit for RTU560, 110...220 VDC, 44.3W


Application
The power supply unit 560PSU01 generates the two supply
voltages (5 VDC and 24 VDC ) for the RTU560 racks 560MPR03
and 560SFR02. The output power is sufficient to supply a subrack with up to 4 communication units.

560PSU01
1KGT006600R0002

Description
Power supply unit for RTU560 racks
Input voltage 110...220 VDC
Output voltage: 5 and 24 VDC
Suitable for redundant power supply in
560MPR03/560SFR02

3/5 | RTU500 series | Product catalog

It is possible to configure redundant power supplies for project


configurations with higher requirements to availability. In this
configuration 2 power supply units 560PSU01 are operating in
parallel mode. They are able to take over the load, if one power
supply fails.
The power supply unit 560PSU01 is available in the following
version (rubric):
R0002: Input range 110220 VDC (-20...+15%)

Remote Terminal Units


Product line RTU560 Power supply units
Power supply unit for RTU560, 48...220 VDC, 85W
Application
The power supply unit 560PSU02 generates the two supply
voltages (5 VDC and 24 VDC ) for the RTU560 communication
units (CMU) within the rack. The output power is sufficient to
supply the whole communication subrack with up to 8 CMU
modules.

560PSU02
1KGT011900R0001

Description
Power supply unit for RTU560 racks
Input voltage: 48...220 VDC
Output voltage: 5 and 24 VDC
Suitable for redundant power supply in
560MPR03/560SFR02

It is possible to configure redundant power supplies for project


configurations with higher requirements for availability. In this
configuration 2 power supply units 560PSU02 are operating
in parallel mode. They are able to take over the full load, if one
power supply fails.
The power supply unit 560PSU02 is available in the following
version (rubric):
R0001: Input range 48...220 VDC (-20...+15%)

Product catalog | RTU500 series | 3/6

Remote Terminal Units


RTU560 product line Input/output modules
Binary input, 16 channels, LEDs
Application
Isolated input of up to 16 binary process signals. Scanning and
processing of the inputs are executed with the high time resolution of 1ms. Allocation of an input to a processing function can be
done according to the rules of configuration.

23BE23
1KGT012100R5001

Description
To be used for single indications, double indications,
digital measurands and pulse counters.
Resolution: 1ms
Process voltage: 24...60VDC
LED signal for each input

The board 23BE23 can process the following types of signals:


16 single indications with time stamp
8 double indications with time stamp
2 digital measured values with 8 bit
1 digital measured value with 16 bit
16 pulse counters (max. 120Hz)
2 step position information each with 8 bit
Two 8 bit string information
One 16 bit string information

Binary output, 16 channels


Application
The binary output board 23BA20 can be used for the potentially
isolated output of up to 16 binary signals to the process. The assignment of an output to a number of processing functions can
be managed within the scope of the configuration rules.

23BA20
GSNE000700R5312

Description
16 output contacts configured as
- 1-pole command
- 2-pole command
- 1.5-pole command in configuration with 23BA23
Operating voltage 24...60VDC, 60W
Imax:2A with 24VDC (ohmic load)

3/7 | RTU500 series | Product catalog

The 23BA20 can be used for the following types of signal:


Object commands with 1 or 2 pole output without
(1 out of n) check
Object command with 1.5 or 2 pole output with
(1 out of n) check
Set-point messages
General output messages

Remote Terminal Units


RTU560 product line Input/output modules
Command output monitoring (1 out of n) check
Application
The 23BA23 board is intended for use in the RTU560 product
line. The 23BA23 board should be installed if the output circuit of
an object command has to be checked before the actual command is given. The 23BA23 board executes a (1 out of n) check.
It checks if only one interposing relay will be activated in the output circuit. This is feasible only if all interposing relays connected
to one check circuit have the same resistance value.
23BA23
1KGT020800R0001

Description
Two test and switching circuits
Auxiliary test voltage 24...60 VDC

The 23BA23 board allows to check two different interposing relay


types by using two separated check circuits. The permissible
tolerance range is defined by means of parameters. Up to 16
23BA23 boards can be used in one RTU560.
Galvanic isolation of the check circuit
Suppression of line frequency during measuring

23AE23
1KGT012200R5001

Description
Resolution 12bit +sign
Measuring ranges: +/-2mA; +/-5mA; +/-10mA;
+/-20mA; +/-40mA; +/-2VDC; 0...20VDC

Analog input, 8 channels


Application
The 23AE23 board records up to 8 analog measured values. The
23AE23 board allows it to connect all typical measured value
ranges. It can be configured for the following measurement ranges by setting switches and jumpers:
2mA
5mA
10mA
20mA
40mA
2VDC
0...+20VDC
Other effective ranges and live zero signals become generated
out of these ranges through conversion of the communication
unit (CMU).

Product catalog | RTU500 series | 3/8

Remote Terminal Units


RTU560 product line Input/output modules
Analog output, 2 channels with potential isolation
Application
Via the analog output board 23AA21 analog control outputs for
sequential or closed loop control, display instruments, measurand recorders etc. can be connected to the RTU560. The
23AA21 board has 2 output channels which are isolated and
can be configured to different output current ranges. The output
format, unipolar or bipolar resp. live zero (4...20mA) can be configured by software parameters.

23AA21
1KGT020700R0001

Description
Analog signal represented digitally by 11bit +sign
Selectable current outputs: +/-2.5mA; +/-5mA;
+/-10mA; +/-20mA; +4...20mA

The following output current ranges can be configured independently per channel via plug-in jumpers:
2.5mA
5mA
10mA
20mA (4...20mA)

Binary input, 64 channels, LEDs


Application
The binary input board 23BE50 is used for the isolated input of
64 process signals in 4 groups with each up to 16 binary signals.
Scanning and processing of the inputs are executed with the
high time resolution of 1ms.

23BE50
1KGT020900R0001

Description
To be used for single indications, double indications,
digital measurands and pulse counters.
Resolution: 1ms
Process voltage: 24...60VDC
LED signal for each input

3/9 | RTU500 series | Product catalog

Allocation of an input to a processing function can be done


according to the rules of configuration. The board 23BE50 can
process the following types of signals:
64 single indications with time stamp
32 double indications with time stamp
8 step position information each with 8 bit
8/16 bit digital measured value(s)
8/16 bit string information
64 pulse counters (max. 120Hz)

Remote Terminal Units


RTU560 product line Input/output modules
Command output module 110...220VDC
Application
The binary output board 23BA40 can be used for the potentially
isolated output of up to 16 binary output signals to the process.
The assignment of an output to a number of processing functions can be freely undertaken within the scope of the configuration rules. Secure command output with (n out of 16) check of
the output relays.

23BA40
1KGT011200R0011

Description
16 output contacts configured as 16 single contact
outputs or 8 double contact outputs
Switching voltage: 24...220 VDC / 250 VAC
Max. switching capacity: 120W (DC)
Max. switching current: 300mA at 110 VDC,
200mA at 220 VDC (L/R = 40ms)
Isolated relay output contacts NO, 2-pole
connection

The 23BA40 can be used for the following types of signal:


Object commands with single or double contact outputs
Regulation commands
Digital setpoints
Bitstring output, 1, 2 or 16 bit

Binary input, 16 channels 110...125 VDC (R0011) and


220...250 VDC (R0012)
Application
The binary input board 23BE40 is used for the isolated input of
up to 16 binary process signals. Scanning and processing of the
inputs are executed with the high time resolution of 1 ms.

23BE40
1KGT011100R0011
1KGT011100R0012

Description
16 channel potential isolated inputs, without common return
Process voltage: 110...125 VDC and
220...250 VDC

The board is available in two versions (rubrics):


23BE40R0011: 110...125 VDC
23BE40R0012: 220...250 VDC
Allocation of an input signal to a processing function can be
done according to the rules of configuration. The 23BE40 can
process the following types of signals:
16 single indications with time stamp
8 double indications with time stamp
2 step position information each with 8bit
8/16 bit digital measured value(s)
8/16 bit string information
16 pulse counters (max. 25Hz)

Product catalog | RTU500 series | 3/10

Remote Terminal Units


RTU560 product line Racks
Rack with 9 slots, wall mounted
Application
The mounting plate rack 560MPR01 accommodates up to 2
communication units (CMU) 560CMU02 or 560CMU05 and up
to 8 peripheral modules in a RTU560 substation. One additional (extension) mounting plate rack can be connected to the
560MPR01 via the RTU560 serial peripheral bus (SPS).

3
560MPR01
1KGT012500R0001

Description
Mounting panel for RTU with plug for serial
peripheral bus for extension
Max. 8 slots for peripheral modules
Max. 2 CMUs (560CMU02/05)

Additional material:
Bus connection unit for 560MPR01
560BCU02R0001

Alarm and warning contacts


Minute pulse in- and output

1KGT007900R0001

Process connector 2-/17-/19-pole for 560MPR01/03

23XS20R2019
19-pole connector with screw-terminals AWG12 for process
connections to the I/O modules on 560MPR01/03 (one connector per
module); 100 pcs per package

23XS20R2017

1KGN000556R2019
1KGN000556R2017
1KGN000556R2002

17-pole connector with screw-terminals AWG12 for process


connections to the I/O modules on 560MPR01/03 (one connector per
module); 100 pcs per package
23XS20R2002
2-pole connector with screw-terminals AWG12 for process
connections to the I/O modules on 560MPR01/03; 100 pcs per package

Blanking front plate


23VF21R1001

Frontplate: light beige, plastic


Blanking front plate to cover free slots within a module subrack
(1 slot; with ABB Logo grip)
1KGT007900R1001

Incl. screws
100 pcs per package

3/11 | RTU500 series | Product catalog

Remote Terminal Units


RTU560 product line Racks

560MPR03
1KGT022100R0001

Description
With flexible configuration for I/O, CMU and power
supply (23XS20 not included).

Mounting panel for redundant power supply


Application
The 560MPR03 rack is designed to be used with or without
redundant power supply. Therefore, it has 2 slots for redundant
power supply units (PSU). Up to 18 slots can be used for I/O
boards, communication units (CMU) or a mixture of both. It is interfaced to other racks via the RTU560 serial peripheral bus. Up
to 7 560MPR03 racks can be connected to an I/O bus segment.
By using the bus connection unit 560BCU04, the 560MPR03
becomes a rack with up to 8 communication units (560CMU05/
560CMU02).
Also for some functions the usage of 560BCU04 is required, even if only one communication unit is inserted The rack
560MPR03 is mounted on a mounting plate in a cubicle.
Only in slot 19 the second PSU can be inserted and will be
operated. It is not allowed to put in other modules. Slot 18 is
available when the option of the second PSU is not used.

Additional material:
Bus connection unit for 560MPR03 (Basic, Extension and

560BCU04R0001 (Basic)

Alarm and warning contacts

CAN bus termination)

Minute pulse in- and output


Supervision of redundant power supply

For 2 units 560CMU0x (one basic unit, one extension unit)
1KGT007900R0001
1KGT007900R0002
1KGT007900R0003

560BCU04R0002 (Extension)
Extension kit for 10 additional 560CMU0x
560BCU04R0003 (CAN bus termination)
Single CMU CAN bus temrination only (no alarm and warning contacts, no
minute pulse in- and output, no supervision of redundant power supply)

Process-connector 2-/17-/19-pole for 560MPR03/01

23XS20R2019
19-pole connector with screw-terminals AWG12 for process
connections to the I/O modules on 560MPR03/01 (one connector per
module); 100 pcs per package

1KGN000556R2019
1KGN000556R2017
1KGN000556R2002


23XS20R2017
17-pole connector with screw-terminals AWG12 for process
connections to the I/O modules on 560MPR03/01 (one connector per
module); 100 pcs per package
23XS20R2002
2-pole connector with screw-terminals AWG12 for process
connections to the I/O modules on 560MPR03/01; 100 pcs per package
23VF21R1001

Blanking front plate

Frontplate: light beige, plastic


1KGT007900R1001

Blanking front plate to cover free slots within a module subrack


(1 slot; with ABB Logo grip)
Incl. screw
100 pcs per package
Product catalog | RTU500 series | 3/12

Remote Terminal Units


RTU560 product line Racks
19 Swing frame rack for optional redundant power supply
Application
The 560SFR02 rack is designed to be used with or without
redundant power supply. Therefore, it has 2 slots for redundant
power supply units (PSU). Up to 18 slots can be used for I/O
boards, communication units (CMU) or a mixture of both.

3
560SFR02
1KGT022200R0001

Description
With flexible configuration for I/O, CMU and power
supply

It is interfaced to other racks via the RTU560 serial peripheral


bus. Up to 7 560SFR02 racks can be connected to an I/O bus
segment. By using the bus connection unit 560BCU05, the
560SFR02 becomes a rack with up to 8 communication units
(560CMU05/560CMU02). Also for some functions the usage
of 560BCU05 is required, even if only one CMU is inserted It is
installed in a swing frame cabinet or in a frame.
Only in slot 19 the second PSU can be inserted and will be
operated. It is not allowed to put in other modules. Slot 18 is
available, when the option of the second PSU is not used.

Additional material:
Bus connection unit for 560MPR03 (Basic, Extension and

560BCU05R0001 (Basic)

Alarm and warning contacts

CAN bus termination)

Minute pulse in- and output


Supervision of redundant power supply
1KGT022400R0001


For 2 units 560CMU0x (one basic unit, one extension unit)
1KGT022400R0002
1KGT022400R0003

560BCU05R0002 (Extension)
Extension kit for 10 additional 560CMU0x
560BCU05R0003 (CAN bus termination)
Single CMU CAN bus temrination only (no alarm and warning contacts, no
minute pulse in- and output, no supervision of redundant power supply)

Process-connector-housing 560SFR02

23XS40R3001
18-pole plug for connectors of 560SFR02
(housing only, without snap-in contacts)

1KGN000758R3001

Snap-in contacts for 23XS40R3001

100 pcs per package

23XS40R4001
Snap-in contacts for 23XS40R3001 (18 contacts per plug required)
Suitable for AWG20-AWG26

1KGN000758R4001

3/13 | RTU500 series | Product catalog

500 pcs per package

Remote Terminal Units


RTU560 product line Racks
Additional material:

23XS41R0001

Crimp tool for 23XS40R4001

Tool to connect wires to snap-in contacts (23XS40R4001)



1KGN000797R0001

3
Removal tool for snap-In contacts

23XS42R0001
Tool to extract snap-in contacts (23XS40R4001)

1KGN000798R0001

Removal tool for process connector 23XS40R3001

23XS43R0001
Tool to remove connector housing 23XS40R3001 from subrack 560SFR02

1KGN000799R0001

Blanking front plate

23VF21R1001
Frontplate: light beige, plastic
Blanking front plate to cover free slots within a module subrack
1KGT007900R1001

(1 slot; with ABB Logo grip)


Incl. screws
100 pcs per package

Product catalog | RTU500 series | 3/14

Remote Terminal Units


RTU560 product line Serial communication
Fibre optic coupler (BFOC/2.5) for 2glass-fibre optic lines
Application
The fiber optic coupler 23OK24 is intended for use in the
RTU560. The module is used to transmit data via 2 independent
optical links (receive and transmit).

23OK24
1KGT011800R5001

Description
Fibre optic coupler for glass-fibre optic cable with
emission wave length of 820nm
Fiber optic connection with bayonet socket
BFOC/2.5 (IEC-SC86B)
Optical isolation of RTU560 bus
Suitable as star coupler for RS-485 bus and
RS-232 bus
Interfacing of IEC 60870-5-103 devices
Connector for 2 optical lines on frontplate

Optical fiber cables are not sensitive to inductive and capacitive


interferences, as well for potential differences between the 2 data
communication equipments. Fiber optic cables will be used to
bridge over distances in critical environments, or if a potential
isolation is required. The maximum distance can be up to 2600m
via fiber optic cable type 200m.
The board can be used for signal conversion to fiber optic
signals of the received and transmitted data for the following
electrical interface standards:
RTU560 I/O bus
RS-485 bus
RS-232 C
The fiber optic coupler 23OK24 can be connected to the
RTU500 coupler 560FOC40 and to the RTU511 adapter 23AD64
R0002.

Modem V.23, power supply 5...24 VDC


Application
The 23WT23 board is a modem which converts the serial data
according to FSK-channel CCITT V.23 standard. Therefore it can
be used for transmission via leased PTT-lines or private networks.
The modem 23WT23 is available in two versions (rubrics):
23WT23 R0001: V.23 modem power supply +5VDC
23WT23 R0002: V.23 modem power supply +24VDC
23WT23
1KGT008200R0001
1KGT008200R0002

Description
Voice frequency telegraphy device (VFT) according
CCITT V.23 standard with max.1200baud

3/15 | RTU500 series | Product catalog

Two- or four-wire operation mode is selectable by jumper. The


voice frequency (VF) output has a high impedance which allows
that up to 10 remote stations can be connected to a multi-drop
line.

Remote Terminal Units


RTU560 product line Serial communication
Modem 9600baud, power supply 5 VDC
Application
The 23WT24 board is a modem with 9600 baud transmission
speed. Therefore it can be used for the transmission via private
networks over pilot cables.

23WT24
1KGT010500R0001

The board operates on the frequency shift keying principle (FSK).


Two- or four-wire operation mode is selectable by jumper. The
frequency output can be set to high impedance which allows that
up to 10 remote stations can be connected to a multi-drop line.

Description
FSK device with 9600baud transmission speed
Connector for RS-232 testing and disconnecting
on frontplate
Communication over pilot cables

Modem 50-2400baud, power supply 5...24VDC


Application
The 23WT25 modem is designed for the operation on telecontrol
lines together with the RTU560. However it can also be connected to other data terminal equipments because it operates at the
interfaces like a universal FSK-modem in the voice-band range
(300-3400Hz) according to CCITT.

23WT25
1KGT012400R0001
1KGT012400R0002

Description
Voice frequency telegraphy device (VFT)
Channel-frequencies and -bandwidth are selectable
according to CCITT standards (R35...R38) and
V.23/ 1200baud
Additional 600baud and 2400baud channels

The 23WT25 modem allows the assignment of a two- or


four-wire line with communication channels for 50baud up to
2400baud (24channels 50baud, 12channels 100baud, 6channels 200baud, 2channels 600baud, 1channel 1200baud).
There are two versions (rubrics) available:
23WT25R0001: 5VDC supply
23WT25R0002: 24VDC supply

Additional material:
Programming cable for 23WT25

23PK31
For download of project specific firmware version to 23WT25


1KGT013200R0001

Product catalog | RTU500 series | 3/16

Remote Terminal Units


RTU560 product line Ethernet communication
Integrated unmanaged switch with 4 Ethernet ports
Application
The RTU component 560NUS04 is an unmanaged plug and play
10/100Mbps Ethernet switch providing 4 fast Ethernet autonegotiating RJ45-ports with auto MDI/X (automatic crossover
detection and correction). The switch is intended for distributing
Ethernet within a station and supplying a local area network
(LAN) with additional ports and can be used with rack types
560MPR01, 560MPR03, 560SFR02.

560NUS04
1KHW001891R0001

Description
Unmanaged switch
4x10/100BaseT port (electrical)
Linear network structure supported

Integrated unmanaged switch with 2 SFP slot


Application
The RTU component 560NUS12 is an unmanaged plug and play
10/100 Mbps Ethernet switch providing 2 fast Ethernet autonegotiating RJ45-ports with auto MDI/X (automatic crossover
detection and correction) and 2 fiber optic 100Mbps slots for
use with SFP (small form-factor pluggable) modules.
The switch is intended for distributing Ethernet within a station
through the RJ45-ports. The fiber optic ports can be used for
interconnecting stations with a maximum distance of 40km.
560NUS12
1KHW001892R0001

Description
Unmanaged switch
2xSFP slot, without optical transmitter/receiver
Additional SFP modules are required (see 560NFOxx)
2x10/100BaseT port (electrical)
Linear network structure supported
Additional material:

SFP (small form-factor pluggable) for optical switch


560NFO13
For 5560NUS12, 560NMD11, 500NMD20; monomode, distance of typically 15km

1KHW001893R0001

560NFO15
1KHW001894R0001


For 560NUS12, 560NMD11, 500NMD20; monomode, distance of typically 40km
1KHW001895R0001
560NFO85
For 560NUS12, 560NMD11, 500NMD20; multimode, distance of typically 2km

3/17 | RTU500 series | Product catalog

Remote Terminal Units


RTU560 product line Ethernet communication
Integrated managed switch with 2 SDSL-ports and
4 Ethernet ports
Application
The RTU component 560NMS24 is a managed plug and play
Layer-2-switch providing 4 fast Ethernet auto-negotiating RJ45ports with auto MDI/X (Automatic Crossover Detection and Correction) and two 2-wire SDSL-ports for use with private copper
cables. It can be used with rack types 560MPR01, 560MPR03
and 560SFR02.
560NMS24
1KHW002108R0001

Description
Integrated managed layer-2-switch
4x10/100 BaseT port (RJ45, electrical, autonegotiating)
2xSDSL-port for copper wire
Provides redundant topologies by the (Rapid)
Spanning Tree Protocol (RSTP)
1x RS-232 port suitable for serial protocols

The switch is intended for distributing Ethernet within a station


through the RJ45-ports. The SDSL-ports can be used for interconnecting stations with a maximum distance of 20km (copper
cable with diameter of 0.8mm). Longer distances can be achieved by cascading multiple 560NMS24. The switch is able to provide redundant topologies by the (Rapid) Spanning Tree Protocol.
The switch supports VLAN frames and tunneling of serial data.

Integrated managed switch with 1 SDSL-port and


4 Ethernet ports
Application
The RTU component 560NMS34 is a managed plug and play
Layer-2-switch providing 4 fast Ethernet auto-negotiating
RJ45-ports with auto MDI/X (automatic crossover detection and
correction) and one 2-wire SDSL-port for use with private copper
cables. It can be used with rack types 560MPR01, 560MPR03
and 560SFR02.
560NMS34
1KHW023538R0001

Description
Integrated managed layer-2-switch
4x10/100BaseT port (RJ45, electrical, autonegotiating)
1xSDSL-port for copper wire
Provides redundant topologies by the (Rapid)
Spanning Tree Protocol (RSTP)
1x RS-232 port suitable for serial protocols

The switch is intended for distributing Ethernet within a station


through the RJ45-ports. The SDSL-port can be used for interconnecting stations with a maximum distance of 20km (copper
cable with diameter of 0.8mm). The switch is able to provide
redundant topologies by the (Rapid) Spanning Tree Protocol. The
switch supports VLAN frames and tunneling of serial data.

Product catalog | RTU500 series | 3/18

Remote Terminal Units


RTU560 product line Real time clocks
Real time clock GPS for RTU560
Application
A RTU560 product line unit can be synchronized with the time
information received from the global positioning system (GPS)
satellites using the module 560RTC01. The RTU560 reads the
time and date from the module 560RTC01 and synchronizes
its internal time to the standard time by the means of a minute
pulse. The use of the module 560RTC01 ensures that process
information from several terminal units are synchronized, when
they include time information.

560RTC01
1KGT006700R0001

Description
Real time clock for synchronization of the RTU560
with the standard time of the GPS satellite including
configuration tool.
Antenna and cable have to be ordered separately

Real time clock DCF77 for RTU560


Application
A RTU560 product line unit can be synchronized with the
standard time of the long-wave transmitter DCF77 using the
module 560RTC02. The RTU560 reads the time and date from
the module 560RTC02 and synchronizes its internal clock to the
standard time by means of a minute pulse. The use of the module 560RTC02 ensures that indications from several terminal units
are synchronized, when they include time information.
560RTC02
1KGT007800R0001

Description
For synchronization of the RTU560 with the standard
time of the long-wave transmitter DCF77.
Antenna and cable have to be ordered separately

3/19 | RTU500 series | Product catalog

Remote Terminal Units


RTU560 product line Real time clocks
Real time clock IRIG-B for RTU560
Application
A remote terminal unit RTU560 can be synchronized with the
standard time of the IRIG-B signal using the module 560RTC03.
The RTU560 reads the time and date from the module
560RTC03 and synchronizes its internal clock to the standard time by means of a minute pulse. The use of the module
560RTC03 ensures that indications from several terminal units
are synchronized, if they include time information.
560RTC03
1KGT012000R0001

Description
For synchronization of the RTU560 with the standard
time of the IRIG-B signal.
Receiver and cable have to be ordered separately

Additional material:
Connection cable 20m/50m for real time clock

23AC02R0020
Cable to connect real time clock module 560RTC01 with 23AN02 or


560RTC02 with 25AN01

Length 20 meters
1KGT006900R0020
1KGT006900R0050

23AC02R0050
Cable to connect real time clock module 560RTC01 with 23AN02
or 560RTC02 with 25AN01
Length 50meters
Ferrite antenna for outside installation

25AN01R0003
Ferrite antenna for real time clock module 560RTC02
Incl. wall mounting kit, 360rotatable

GSNP812601R0003

23AN02R0001

GPS antenna

Active antenna for real time clock module 560RTC01


1KGT006800R0001

Product catalog | RTU500 series | 3/20

Remote Terminal Units


RTU540 product line Smart solutions for distribution
automation

The RTU540 product line comprises DIN rail RTUs in a compact housing for limited space requirements. Nonetheless,
the RTU540 product line offers high functionality ranging from
communication redundancy and support of full software functionality to central or distributed I/O modules. To correspond
to specific requirements the RTU540 product line is optionally
available with integrated GPRS or integrated I/Os.

Applications areas:
Sub transmission
Primary distribution substations
Secondary distribution substations
Process automation: Oil, gas, water, waste water, district
heating
Railways, public transportation

The high functionality combined with the compact housing


make the RTU540 product line suitable for applications in sub
transmission and primary and secondary distribution substations.

Your benefits
Full functionality in a solid compact housing even under
critical environmental conditions
Extendable with central and distributed I/Os
Compact housing available with:
Integrated GPRS
Integrated I/Os
Communication redundancy
Support of full software functionality and all available byteoriented host and sub device communication protocols

Highlights of RTU540 product line


The products of RTU540 product line feature a compact
housing which takes up only a limited amount of space, yet
offering a high level of functionality and flexibility. For this, the
product line offers 4 product versions including a variety of
functionalities ranging from a different amount of serial interfaces and Ethernet ports to integrated I/Os. What is more, an
integrated GPRS modem allows for wireless communication
without any additional devices. Furthermore, all product versions can be expanded with local or remote I/Os.

4/1 | RTU500 series | Product catalog

Remote Terminal Units


RTU540 product line Smart solutions for distribution
automation
RTU540 Communication units

560CMG10
p. 4/3

560CMD11
p. 4/4

560CIG10
p. 4/5

560CID11
p. 4/5

Product catalog | RTU500 series | 4/2

Remote Terminal Units


RTU540 product line Communication units
Base module
Application
The 560CMG10 is a communication unit (CMU) of the RTU540
product line. The 560CMG10 consists of a metal DIN rail housing,
which includes a CPU and a power supply.

560CMG10
1KGT017600R0001

Description
DIN rail mounted base module RTU540
Metal housing
3x serial port (2x RS-232, 1x RS-485)
1x Ethernet interface (10/100BaseT)
Power supply 24 VDC
With connection interface to RTU500 I/O-extension
modules

4/3 | RTU500 series | Product catalog

The essential tasks of the 560CMG10 are:


Managing and controlling of the I/O boards via the interface to
the RTU560 serial peripheral bus (I/O interface/Wired-OR-Bus)
Reading process events from the input boards
Writing commands to the output boards
Communication with control centers and local HMI systems via
the integrated serial line interfaces and the implemented Ethernet 10/100BaseT LAN interface
Managing the time base for RTU540 station and synchronizing
the I/O boards
Handling the dialogue between RTU540 and web browser via
LAN interface

Remote Terminal Units


RTU540 product line Communication units
Base module, optionally with internal GPRS modem
Application
The 560CMD11 is a communication unit (CMU) of the RTU540
product line. The 560CMD11 consists of a metal DIN rail housing,
which includes a CPU and a power supply.
The essential tasks of the 560CMD11 are:
Managing and controlling of the I/O boards via the interface to
the RTU560 serial peripheral bus (I/O-Interface/Wired-OR-Bus)
Reading process events from the input boards
Writing commands to the output boards
Communications with control centers and local HMI systems
via integrated serial line interfaces and implemented Ethernet
10/100BaseT LAN interfaces
Managing the time base for the RTU540 station and synchronizing the I/O boards
Handling the dialogue between RTU540 and web browser via
LAN interface
Communication via integrated GPRS-Modem (R0011)

560CMD11
1KGT023400R0001
1KGT023400R0011

Description
DIN rail mounted base module RTU540
Metal housing
4x serial port (RS-232, RS-485)
2x Ethernet interface (10/100BaseT)
Power supply 24 VDC
With connection interface to RTU500 I/O-extension
modules
Internal GPRS-Modem (R0011)
SIM-Card and antenna have to be ordered separately

The CMU is available in the following versions (rubrics):


R0001: without GPRS
R0011: with internal GPRS

Additional material:
Bar antenna for 560CMD11 and 560MDD10

560ANA01R0001


Bar Antenna for 560CMD11 and 560MDD10

1KGT023600R0001

10pcs per package

Wall mounted antenna for 560CMD11 and 560MDD10

560ANA02R0005
Wall mounted antenna for 560CMD11 and 560MDD10, 5m cable

1KGT023700R0005

Antenna cable RG58, 15m

560CAB02R0015
Extension cable for wall mounted GPRS antenna 560ANA02, RG58, 15m

1KGT033800R0015

Product catalog | RTU500 series | 4/4

Remote Terminal Units


RTU540 product line Communication units
Base module
Application
560CID11 is a module of the product line RTU540 consisting
of a communication unit (CMU), a multi-I/O module (MIO) and a
power supply (PSU) in a metal DIN rail housing.

560CID11
1KGT030400R0001
1KGT030400R0002

Description
DIN rail mounted base module RTU540
Metal housing
4x serial port (RS-232, RS-485)
2x Ethernet interface (10/100BaseT)
Power supply 24 VDC
Integrated I/O (16 binary inputs, 8 binary outputs,
8 analog inputs
(1 out of n) check
With connection interface to RTU500 I/O-extension
modules
Process voltage R0001: 24...60 VDC
Process voltage R0002: 110...125 VDC

The essential tasks of the 560CID11 are:


Capturing of 8 analog input signals (mA or V signals), fast
scan of 100ms for 2 inputs
Capturing of 16 digital input signals, 1 high speed counter
input (max.16 Hz)
8 output contacts NO, 2 terminals for single commands,
double regulation
(1 out of n) check
Managing and controlling of the RTU511 I/O modules via the
10 pole Wired-OR-Bus (WRB)
Reading process events from the input boards
Writing commands to the output boards
Communicating with control systems and local HMI systems
via 4 integrated serial line interfaces and 2 Ethernet 10/100
BaseT LAN interfaces
Managing the time base for the RTU540 station and synchronizing I/O modules
Handling the dialogue between RTU540 and web browser via
Ethernet LAN interface

Base module
Application
The 560CIG10 is a RTU540 product line module consisting of a
communication unit, a multi I/O-board and a power supply in a
metal DIN rail housing.

560CIG10
1KGT021600R0001
1KGT021600R0002

Description
DIN rail mounted base module RTU540
Metal housing
3x serial port (2x RS-232, 1x RS-485)
1x Ethernet interface (10/100BaseT)
Power supply 24 VDC
Integrated I/O (16 binary inputs, 8 binary outputs,
8 analog inputs
(1 out of n) check
With connection interface to RTU500 I/O-extension
modules
Process voltage R0001: 24...60 VDC
Process voltage R0002: 110...125 VDC

4/5 | RTU500 series | Product catalog

The essential tasks of the 560CIG10 are:


Capturing of 8 analog input signals (mA/V signals), fast scan
of 100 ms for 2 inputs
Capturing of 16 digital input signals, 1 high speed counter
input (max.16 Hz)
Output of 8 output contacts NO, 2 terminals for single commands, double, regulation
(1 out of n) check
Managing and controlling of the RTU511 I/O boards via serial
interface (Wired-OR-Bus)
Reading process events from input boards
Writing commands to output boards
Communications with control centers and local HMI systems
via integrated serial line interfaces and implemented Ethernet
10/100BaseT LAN interface
Managing the time base for the RTU540 station and synchronizing I/O boards
Handling the dialogue between RTU540 and web browser
via Ethernet LAN interface

Product catalog | RTU500 series | 4/6

Remote Terminal Units


RTU520 product line Flexible adjustable to feeder and process
automation

The compact and modular RTU520 product line makes monitoring and control of feeder and process automation very
easy. The DIN rail modules can be flexibly assembled to meet
the specific requirements of different applications.
Thanks to the flexible integration of I/O modules RTU520
product line represents a cost-efficient solution to your requirements.
RTU520 product line offers a fast and time-saving engineering. With the RTU Wizard, the proven engineering tool for
ABBs DIN rail RTUs, the complete configuration can be done
in only a few minutes without any special training.
Highlights of RTU520 product line
Fast and simple adaptation to changing requirements
within one compact footprint
Quick and easy configuration of the RTU thanks to RTU
Wizard
Stable and reliable provision of power based on monitoring
of the complete network
Measurement of power quality, over current and overloads
Fault detection, isolation and restoration for faster reaction
time
High investment security
Option for battery buffered real time clocks

5/1 | RTU500 series | Product catalog

Application areas in feeder automation


Monitoring and control of ring main units
Monitoring and control of pole top switches
Supervision of decentralized energy resources (DER)
Volt/Var regulation
Direct measurement of voltage and current, energy and
power calculation
Application areas in process automation
Oil and gas
Wellhead automation
Pipeline supervision
Monitoring and control of pumping stations
Water
Monitoring and control of water reservoirs
Monitoring and control of pumping stations
Waste water treatment

Remote Terminal Units


RTU520 product line Flexible adjustable to feeder and process
automation
RTU520 Communication units

520CMD01
p. 5/3

RTU520 Power supply units

520PSD01
p. 5/4

RTU520 Input/output modules

520AID01
p. 5/5

520AOD01
p. 5/5

520BID01
p. 5/6

520BOD01
p. 5/6

520PTD01
p. 5/7

RTU520 Input/output adapters

520ADD01
p. 5/8

520ADD02
p. 5/8

Product catalog | RTU500 series | 5/2

Remote Terminal Units


RTU520 product line Communication units
Base module
Application
The 520CMD01 is the communication unit (CMU) of the remote terminal unit RTU520 for DIN rail mounting. The device is
designed to communicate with the I/O modules (e.g. 520BID01,
520BOD01, 520AID01) and with control centers.

520CMD01
1KGT031900R0001
1KGT031900R0002

Description
DIN rail mounted base module RTU520
3x serial port (2x RS-232, 1x RS-485)
1x Ethernet interface (10/100BaseT)
1x USB port
With connection interface to RTU520 I/O-extension
modules
Battery buffered real time clock (R0002)

5/3 | RTU500 series | Product catalog

The essential tasks of the 520CMD01 are:


Managing and controlling of the I/O boards via the interface to
the RTU520 serial I/O bus (Wired-OR-Bus)
Reading process events from the input boards
Writing commands to the output boards
Communication with the control centers and local HMI systems via the integrated serial line interfaces and the implemented Ethernet 10/100BaseT LAN interface

Remote Terminal Units


RTU520 product line Power supply unit
Power supply unit
Application
The power supply unit 520PSD01 consists of a plastic housing
build for DIN rail mounting and has following characteristics and
functions:
Cooling by natural convection
Reverse voltage protection
LEDs for supervision of the voltages
Able to handle up to 16 I/O modules of RTU520
520PSD01
1KGT031500R0001

Description
Power supply unit in combination with 520CMD01
Input voltage: 24 VDC
Output power: 20 W

In interaction with the 520CMD01 the input voltage (24 VDC)


is passed through to the I/O devices. During Power-On the
520CMD01 is switching the output voltage active.

Product catalog | RTU500 series | 5/4

Remote Terminal Units


RTU520 product line Input/Output modules
6 analog inputs, mA signals/ V signals
Application
The 520AID01 board records up to 6 analog measurement
values. Various sensitivity ranges for voltage and current measurement are available.
The device 520AID01 is available in two versions (rubrics):
R0001: Current measurement version
R0002: Voltage measurement version
520AID01
1KGT033100R0001
1KGT033100R0002

Description
R0001:
Resolution 11 bit +sign; accuracy class 0.25
Measuring range: +/-5mA; +/-10mA; +/-20mA;
420mA
Resolution 10 bit +sign; accuracy class 0.5
Measuring range: +/-2,5mA

The following measurement ranges can be configured:


R0001:
unipolar: 02,5mA; 05,0mA; 010mA; 020 mA;
420mA
bipolar: 2,5mA; 5,0mA; 10,0mA; 20mA
R0002:
unipolar: 01,0 VDC; 010 VDC
bipolar: 1,0 VDC; 10 VDC

R0002:
Resolution 11 bit + sign; accuracy class 0.25
Measuring range: +/- 1 V DC; +/- 10 VDC

2 analog outputs
Application
Analog control outputs for sequential or closed-loop control, display instruments, measurement recorders etc. can be connected
by the analog output board 520AOD01. The board 520AOD01
has two output channels, which can be configured to different output voltage/current ranges. The output format unipolar,
bipolar or live zero (420 mA) will be configured by software
parameter.
520AOD01
1KGT024500R0001

Description
Resolution 12 bit +sign; accuracy class 0.25
Measuring range: +/-2,5mA; +/-5mA; +/-10mA;
+/-20mA; 420mA; +/-1 VDC; +/-10 VDC

5/5

| RTU500 series | Product catalog

The following output ranges can be configured by onboard


switches:
2.5 mA
1.25 VDC
5.0 mA
2.50 VDC
10 mA
5.0 VDC
20 mA
10 VDC
420mA

Remote Terminal Units


RTU520 product line Input/Output modules

520BID01
1KGT033200R0001
1KGT033200R0002

Description
To be used for single indications, double indications, digital measurands and pulse counters
Resolution: 1ms
Process voltage: 2460 VDC / 110...125 VDC
LED signal for each input
Common return per 8 inputs

16 binary inputs, 2460/110...125 VDC


Application
The binary input device 520BID01 provides 16 galvanic isolated
inputs for 16 binary process signals. Scanning and processing of
the inputs are executed with the high time resolution of 1ms. The
allocation of an input signal to the processing functions are done
according to the configuration rules. The module 520BID01 is
able to process the following types of signals:
16 single indications with time stamp
8 double indications with time stamp
2 digital status messages with 8 bit
1 digital status message with 16 bit
16 pulse counters
The board is available in two versions (rubrics):
R0001: process voltage 2460 VDC
LED signal for each input, common return per 8 inputs
R0002: process voltage 110125 VDC
LED signal for each input, common return per 8 inputs

8 binary outputs, relays


Application
The binary output device 520BOD01 can be used for the control
of 8 binary process signals using relay contacts. The allocation of
an output signal to the processing functions are done according
to the configuration rules.

520BOD01
1KGT033300R0002

Description
8 single commands 1-pole NO contact (high capacity relays)
Max. switching voltage: 150 VDC
Max. load: 110 VDC/3A

The 520BOD01 can be used for the following types of signal:


Object commands with 1 or 2 pole output without (1 out of n)
check
Object commands with 1.5 pole output with (1 out of n) check
via 560CIG10, 560CID11 or 511CIM01
Regulation Commands, 1 and 2 pole
Digital Setpoints (8 Bit)
Bitstring Output, 1 or 8 Bit
The board 520BOD01 is available in one version:
R0002: Switching voltage up to 150 VDC, or
max. 8 A continuously

Product catalog | RTU500 series | 5/6

Remote Terminal Units


RTU520 product line Input/Output modules
6 PT100 inputs
Application
The 520PTD01 board is used to connect PT100 temperature
transmitter directly. Up to 6 transmitters can be connected to the
board.
The measurement range is 200C.

520PTD01
1KGT024700R0001

Description
6 PT100 inputs
24 wires per channel
Resolution: 11 bit +sign
Accuracy class: +/-1 C (-25 C...125 C)
Measuring range: -25 C150 C
Overrange: -200 C200 C
Measuring current: 6 mA

5/7

| RTU500 series | Product catalog

Remote Terminal Units


RTU520 product line Input/Output adapters
I/O adapter
Application
The adapter for I/O modules 520ADD01 is the standard adapter to connect RTU520 I/O modules within an RTU500 DIN rail
solution.
The adapter terminates the RTU I/O bus of the RTU520 (WiredOR Bus) and generates the addresses for the connected I/Omodules automatically.
520ADD01
1KGT033000R0001

The adapter is equipped with two green LEDs, indicating the


activities on the RTU I/O bus.

Description
Standard adapter board for up to 8 I/O modules
520BID01, 520BOD01, 520AID01, 520AOD01,
520PTD01
Incl. 20 pole ribbon cable, cable length 300mm

I/O adapter, RS-485, optionally with fiber optical interface


Application
The device 520ADD02 is an adapter to support extension I/O
modules. This can be done serial via RS485 or via fiber optical. It
is also used to extend the serial peripheral bus over distances of
more than 30 cm/ 11,81 inch.

520ADD02
1KGT024300R0001
1KGT024300R0002

Description
Standard adapter board for up to 8 I/O modules
520BID01, 520BOD01, 520AID01, 520AOD01,
520PTD01 and interface to further I/O extension
RS-485: 19,2 kbaud, 200 m
Glass fibre: 2km, SF connector
Incl. 20 pole ribbon cable, cable length 300 mm

The adapter is used to terminate the serial peripheral bus (WiredOR- Bus). In addition it will generate automatically the module
address within the housing. The wired-OR bus will be converted
to RS-485 or fiber optical by the adapter 520ADD02.
The adapter is equipped with two green LEDs, showing the activities on the serial peripheral bus.
The board is available in two versions (rubrics):
R0001: RS-485
R0002: RS-485, fiber optical

Product catalog | RTU500 series | 5/8

Remote Terminal Units


RTU511 product line Optimized products for migration
projects

The RTU511 product line includes DIN rail RTUs in a


compact, tailored housing offering high functionality. The
tailored housing allows for flexible integration of I/Os to meet
specific project requirements. Furthermore, existing RTU211
installations can be migrated to RTU511 re-using the existing
configuration and wiring. With the RTU Wizard you can
configure small RTUs in eight guided steps. A battery buffered
real time clock is optionally available for a start-up of RTU511
with an up to date time stamp for events.
Highlights of RTU511 product line
Integrated I/Os for limited space
The RTU511 product line comes with a tailored housing
allowing for a flexible integration of I/Os. It is possible to
integrate extension and dezentralized I/O modules.
Thanks to these integrated I/Os combined with the scalable
housing, the RTU511 is suitable for limited spaces. If
necessary, further local and remote I/Os can be added. This
scalability of RTU511 enables you to adapt the product to
their requirements with an adequate functionality for an
optimized price.

6/1 | RTU500 series | Product catalog

Migration from RTU211 to RTU511


To protect your investments over a long time, existing RTU211
installations can be upgraded to RTU511 with only little effort.
The available migration kit makes it very easy to exchange the
CMU and the housing in just a few steps. The RTU211 multi
I/O module and power supply unit can be re-used in the new
housing together with the new CMU module.
Besides the hardware upgrade, the import of existing RTU211
configurations is supported within RTUtil500.
Application areas
Migration of installed base in secondary distribution
substations and feeder automation
Your benefits
Cost-efficient RTU in a tailored housing
Processor with ARM-based technology
Flexible number of I/Os which can be integrated thanks to
scalable housing
Suitable for limited space requirements
Easy migration of existing RTU211 installations

Remote Terminal Units


RTU511 product line Optimized solutions for feeder
automation
RTU511 Communication units

511CIM01
p. 6/3

560CMU01
p. 6/3

511MKM01
p. 6/4

RTU511 Power supply units

500PSM01
p. 6/5

560PSU10
p. 6/5

RTU511 Input/output modules

23BI61
p. 6/6

23BO61
p. 6/6

23BO62
p. 6/7

23AI60
p. 6/7

23AO60
p. 6/8

23IO96
p. 6/8

23PT60
p. 6/9

RTU511 Input/output adapters

23AD62
p. 6/10

23AD63
p. 6/10

23AD64
p. 6/11

Product catalog | RTU500 series | 6/2

Remote Terminal Units


RTU511 product line Communication units
Base module
Application
The 511CIM01 is a unit consisting of a communication unit (CMU),
a multi-I/O board and a power supply in a durable module housing,
which can be mounted on a standard DIN rail.

511CIM01
1KGT032300R0001
1KGT032300R0002
1KGT032300R0011
1KGT032300R0012

Description
DIN rail mounted base module RTU511
3x serial port (2x RS-232, 1x RS-485)
1x Ethernet interface (10/100BaseT)
1x USB port
Including integrated power supply 24...110 VDC
Integrated I/O (16 binary inputs, 8 binary outputs,
6 analog inputs)
(1 out of n) check
With connection interface to RTU500 I/O-extension
modules
Battery buffered real time clock (R0011/R0012)

| exam
ple o

f a co
mp

lete R
TU5

11

560CMU01
1KGT013100R0001

Description
CMU board for housing type 23HS60R000x for
RTU560
3x serial port (2x RS-232, 1x RS-485)
1x Ethernet interface (10/100BaseT)
With up to 4 integrated I/O modules
With connection interface to RTU500 I/O-extension
modules

The essential tasks of the 511CIM01 are:


Capturing of 6 analog input signals (mA or V measurement)
Capturing of 16 binary input signals
8 contact outputs NO
(1 out of n) check
Managing and controlling of external I/O modules via serial interface (Wired-OR-Bus)
Communicating with control centers and local HMI systems via
integrated serial line and LAN interfaces
Managing the time base for the base module and synchronizing
I/O boards
Handling the dialogue between RTU and web browser via LAN
or USB interface
The 511CIM01 is available in following 4 versions (rubrics):
R0001: 2448 VDC process voltage
R0011: 2448 VDC process voltage with battery buffered RTC
R0002: 60110 VDC process voltage
R0012: 60110 VDC process voltage with battery buffered RTC

Board
Application
The 560CMU01 is the Communication Unit (CMU) of the remote
terminal unit RTU560 for DIN rail mounting. It is designed to be
used together with DIN rail I/O-devices (e.g. 23BI61, 23BO62 or
23AI60).
The essential tasks of the 560CMU01 are:
Managing and controlling of I/O boards via the interface to the
RTU560 serial I/O bus (local I/O interface/Wired- OR-Bus)
Reading Process events from input boards
Writing commands to output boards
Communications with control centers and local MMI systems
via the integrated serial line interfaces and the implemented
Ethernet 10/100BaseT LAN interface
Managing the time base for the RTU560 station and synchronizing the I/O boards
Handling the dialogue between RTU560 and Web-Browser via
LAN interface
The communication unit 560CMU01 will be mounted in a DINrail housing, together with the power module 560PSU10, and
up to 4 DIN rail I/O modules
The Communication unit 560CMU01 is able to handle Ethernetand UART-character based communication protocols, and the
serial I/O bus.

6/3 | RTU500 series | Product catalog

Remote Terminal Units


RTU511 product line Communication units
Migration kit
Application
The Migration kit 511MKM01 consists of a 511CMM01, plastic
housing with bottom, top and 2 side plates.
The CMU 511CMM01 enables to use the functionalities and
protocols of RTU500 product lines and tools. With RTUtil500 the
configuration of 23CM61 can be imported to generate RTU511
configuration files.
511MKM01
1KGT032400R0001
1KGT032400R0002
1KGT032400R0011
1KGT032400R0012

Description
Kit to migrate RTU211 to RTU511
Plastic housing with additional space for WT
511CMM01 with:
- 3x serial port (2x RS-232, 1x RS-485)
- 1x Ethernet Interface (10/100BaseT)
- 1x USB port
With connection interface to RTU500 I/O-extension
modules
Battery buffered real time clock (R0011/R0012)

Migration kit allows to continue operation with already installed


RTU211 equipment and wiring by using modern technology.
Therefore all valuable installations will be kept because only CMU
and housing will be replaced.
Migration will be done easily:
0) Shared configuration; rebuild RTU511 load files
1) Switch off power
2) Remove terminal blocks and cable plugs
3) Unscrew 23PU63 and 23WT63, if applicable
4) Insert 23IO96 and 23PU63 into new housing
5) Insert 511CMM01 and if applicable 23WT63; now 511CIM01
is finished
6) Plug in flashcard (SD)
7) Reconnect power, process and communication terminal blocks
to RTU511
8) Switch power on and load RTU files

Additional material:
Comport adapter RTU511 to modem 23WT63/23RS61

511CAB01


Comport adapter RTU511 to modem 23WT63/23RS61
Cable with RJ45 connector, cable length 500 mm

1KGT030800R0001

Product catalog | RTU500 series | 6/4

Remote Terminal Units


RTU511 product line Power supply units
Power supply unit
Application
The power supply unit 500PSM01 generates fol-lowing internal
supply voltages for the RTU511:
24 VDC
18 VDC
15 VDC
5 VDC
500PSM01
1KGT026400R0001

Description
Power supply unit in combination with 511CIM01
or 23AD64
Input voltage: 24...125 VDC
Output power: 30 W
Module length: 175mm

It is placed on top of the multi I/O board 23IO96 or adaptor


23AD64.
The power supply unit 500PSM01 is able to supply an RTU511
system with 23IO96, 511CMM01 and 23WT63. In addition an I/O
subrack with up to 16 I/O boards could be fed.
The power supply unit 500PSM01 is available in one wide input
range version:
Input Voltage 24...125 VDC

Power supply unit


Application
The power supply unit 560PSU10 generates the supply voltages (5 VDC, 15 VDC and 18 VDC) for 560CMU01 of RTU511
product line. The power supply unit 560PSU10 is placed on the
top of the communication unit 560CMU01. The 560PSU10 is
able to supply a RTU511 system with one communication unit
560CMU01 and up to 16 I/O boards.
560PSU10
1KGT013400R0001

Description
Power supply unit for 560CMU01
Input voltage: 24VDC
Output power: 38W
Module length 170mm

6/5 | RTU500 series | Product catalog

Remote Terminal Units


RTU511 product line Input/output modules
16 binary inputs
Application
The binary input board 23BI61 is used for the isolated input of
up to 16 binary process signals. Scanning and processing of the
inputs are executed with the high time resolution of 1ms. Allocation of an input to a processing function can be done according
to the rules of configuration.
23BI61
1KGT014300R0001
1KGT014300R0002

Description
To be used for single indications, double indications,
digital measurands and pulse counters.
Resolution: 1ms
LED signal for each input
Common return per 8 inputs
Module length 105mm
Incl. label for plastic housing 23HS60
Incl. connectors

The board 23BI61 can process the following types of signals:


16 single indications with time stamp
8 double indications with time stamp
2 digital measured values with 8 bit
1 digital measured value with 16 bit
8 pulse counters (at the 8 lower channels)
The I/O module is available in the following versions (rubrics):
Process voltage R0001: 24...48VDC
Process voltage R0002: 60110VDC

8 binary outputs, transistor


Application
The binary output board 23BO61 can be used for the output of
up to 8 binary signals to the process, using solid state relays.
The assignment of an output to a number of processing functions can be freely undertaken within the scope of the configuration rules.
23BO61
1KGT014400R0001

Description
8 single commands 1-pole (transistor) + go output
Max. operating voltage = 50VDC/0,2A
Module length 70mm
Incl. label for plastic housing 23HS60
Incl. connectors

The 23BO61 can be used for the following types of signal:


Object commands with 1- or 2-pole output with
1.5-pole output over go-relays
Regulation commands, 1- and 2-pole
Digital set points (8 Bit) (optional with Strobe)
Bitstring output, 1, 2 or 8 bit
The board is available in one version (rubric):
23BO61R0001 for up to 50 VDC, max. 0.2A

Product catalog | RTU500 series | 6/6

Remote Terminal Units


RTU511 product line Input/output modules
8 binary outputs, relays
Application
The binary output board 23BO62 can be used for the output of
up to 8 binary signals to the process, using relay contacts. The
assignment of an output to a number of processing functions can
be freely undertaken within the scope of the configuration rules.

23BO62
1KGT014600R0001
1KGT014600R0009

Description
8 single commands 1-pole (high capacity relays)
Module length 140mm
Incl. label for plastic housing 23HS60
Incl. connectors

The 23BO62 can be used for the following types of signal:


Object commands with 1- or 2-pole output without (1 out of n)
check
Object commands with 2- pole output with (1 out of n) check
Regulation commands, 1- and 2- pole
Digital set points (8 Bit)
Bitstring output, 1 or 8 bit
The board is available in the follwing versions (rubrics):
23BO62 R0001: For 24...150 VDC or max. 110 VDC / 3 A
23BO62R0009: For 24...60 VDC or max. 4A

6 analog inputs
Application
The 23AI60 board records up to 6 analog measured values. The
23AI60 board allows it to connect all typical measured value
ranges.

23AI60
1KGT014700R0001

Description
Resolution 11 bit +sign; accuracy class 0.25
Resolution 10bit +sign; accuracy class 0.5
for 2.5 mA
Module length 70mm
Incl. label for plastic housing 23HS60
Incl. connectors

6/7 | RTU500 series | Product catalog

It can be configured for the following measurement ranges:


02.5 mA
2.5 mA
05,0 mA
5.0 mA
010 mA
10 mA
020 mA
20 mA
420 mA
01.0 VDC
1.0 VDC
0...10 VDC
10 VDC
Other effective ranges and live zero signals become generated
out of these ranges through conversion of the communication
unit (CMU).

Remote Terminal Units


RTU511 product line Input/output modules
2 analog outputs
Application
Analog control outputs for sequential or closed-loop control,
display instruments, measurement recorders etc. can be connected by the analog output board 23AO60. The board 23AO60 has
two output channels, which can be configured to different output
voltage/current ranges. The output format unipolar, bipolar or live
zero (420 mA) will be configured by software parameter.
23AO60
1KGT014800R0001

Description
Resolution 11bit + sign; accuracy class 0.25
Module length 105mm
Incl. label for plastic housing 23HS60
Incl. connectors

The following output ranges can be configured by onboard switches:


2.5 mA
1.25 VDC
5.0 mA
2.50 VDC
10 mA
5.0 VDC
20 mA
10 VDC
420mA
Other effective ranges and live zero signals become generated
out of these ranges through conversion of the communication
unit (CMU).

Combined I/O board


Application
The 23IO96 support the following I/O:
6 analog inputs (mA, Vsignals)
16 binary inputs
8 binary outputs
(1 out of n) check for commands
23IO96
1KGT017800R0001
1KGT017800R0002

There are two voltage ranges (rubrics) available for binary inputs
and (1 out of n) check:
R0001: 24...48 VDC process voltage
R0002: 60...110 VDC process voltage

Description
Combined I/O board 24...48 VDC (R0001),
60...110 VDC (R0002)
Multi I/O board for 511CIM01
Incl. connectors

Product catalog | RTU500 series | 6/8

Remote Terminal Units


RTU511 product line Input/output modules
6 PT100 inputs
Application
The 23PT60 board is used to extend the RTU511 with another
16 I/O boards. Up to 6 transmitter can be connected to the
board. The measurement range is 20 mA.

23PT60
1KGT014900R0001

Description
2...4 wires per channel
Resolution: 11 bit +sign
Accuracy class: +/-1C (-25C...125C)
Measuring range: -25C150C
Overrange: -200C200C
Measuring current: 6mA
Module length 140mm

6/9 | RTU500 series | Product catalog

Remote Terminal Units


RTU511 product line Input/output adapters
I/O adapter board
Application
The adapter 23AD62 is the standard adapter to connect RTU511
I/O modules within a RTU511 rack.

23AD62
1KGT018400R0001

The adapter is used to terminate the serial peripheral bus (WiredOR Bus of the RTU511). In addition it will generate automatically
the housing address within the rack. The adapter is equipped
with two green LEDs, showing the activities on the serial peripheral bus.

Description
Standard adapter board for RTU511 I/O modules
(23BIxx, 23BOxx, 23AIxx, 23AOxx, 23PTxx)
Module length 35mm
Incl. 20 pole ribbon cables, cable length 200mm

I/O adapter board (RS-485 and plastic/glass fiber)


Application
The adapter 23AD63 is an adaptor to connect the last housing
of the RTU511 rack with a new rack; each rack consists of up
to 4 housings and up to 16 I/O boards. It is also used to extend
the serial peripheral bus over distances of more than app.
30cm.
23AD63
1KGT018500R0001
1KGT018500R0002

The board is available in the following versions (rubrics):


R0001: Plastic fiber, 650nm
R0002: Glass fiber, 820nm

Description
Adapter board for interface to further RTU511 I/O
racks
RS-485: 19.2kbaud, 200m
Module length 35mm
Incl. 20 pole ribbon cables, cable length 200mm

Product catalog | RTU500 series | 6/10

Remote Terminal Units


RTU511 product line Input/output adapters
23AD64: I/O adapter board remote I/O with glass/ plastic fiber
Application
The adapter 23AD64 is an adapter to connect virtual I/O racks of
the RTU511 consisting of up to 4 housings and 16 I/O boards. It
is also used to extend the serial peripheral bus over distances of
more than app. 30cm. The adapter is always used together with
the power supply unit 500PSM01.

23AD64
1KGT018600R0002
1KGT018600R0003

Description
Adapter board for interface to remote RTU511 I/O
racks only works together with power supply,
e.g. 500PSM01
Plastic fiber: 50m, 650nm/HCS fibre: 500m,
650nm/RS-485: 19,2kbaud, 200m (R0003)
Glass fiber, multimode: ST-connector, 820nm
distance up to 2000m, 62,5/125m (R0002)
Module length 175mm

6/11 | RTU500 series | Product catalog

The module 23AD64 is available in two versions (rubrics):


R0002: Glass fiber, max. 2000m
R0003: Plastic fiber, max. 500m

Product catalog | RTU500 series | 6/12

Remote Terminal Units


RTU500 series modules Flexible extension modules for the
whole RTU500 series

The RTU500 series modules can be used with all product


lines to provide additional and extended functionality. The
modules offer special functions to complete a RTU for your
specific application.
RTU500 series modules include:
RTU500 series power supply units
RTU500 series I/Os
RTU500 series I/O adapter
RTU500 series multimeters
RTU500 series serial communication
RTU500 series ethernet communication
Multimeters
RTUs multimeter devices enable direct measurement of
voltage, current and power. The configuration of the devices
is completely integrated into the easy-to-use RTUtil500 and
the DIN rail wizard. Multimeters provide for a detailed monitoring of the network. To locate a fault, multimeters offer fault
current detection with directional information. Additionally, the
increased and reliable information about the network protect
your investments and allow for precise new investments, if
need be.

7/1 | RTU500 series | Product catalog

Communication
Flexibility of communication is a precondition for modern RTU
systems. To guarantee an error-free and comprehensive communication to a variety of devices, the RTU500 series offers
modules for Ethernet and serial communication.
Serial communication:
Modems are used for serial communcation. The RTU500
series modules offer modems with speed rates up to 9.600
Baud for distances up to 20 km. The modems operate in
wide or voice band range to meet your requirements. What
is more, the modems are available for CCITT V.23 standard.
Ethernet communication:
unmanaged switches
4 port Ethernet switches distribute Ethernet with support
of redundant topologies. Copper as well as fiber optical
media are supported.
managed switches with DSL
Available copper lines in combination with new fiber optical
lines can be re-used for TCP/IP communication, allowing
for an independent network for private communication.
Additionally, tunneling of serial data via RS 232 interface
allows for an easy migration from serial to Ethernet communication.

Remote Terminal Units


RTU500 series modules Flexible extension modules for the
whole RTU500 series
RTU500 Power supply units

500PSU40
p. 7/3

CP-E 24/2.5
p. 7/3

560PSU41
p. 7/4

23VG23
p. 7/4

23VG24
p. 7/5

RTU500 Input/output modules

211BID51
p. 7/6

211BOD52
p. 7/6

211AID50
p. 7/7

RTU500 Input/output adapters

7
211ADD52
p. 7/8

RTU500 Multimeters

560CVD03
p. 7/9

560CVD11
p. 7/10

500CVD21
p. 7/10

RTU500 Serial communication

560FOC40
p. 7/11

560FSM10
p. 7/11

560FSM11
p. 7/12

25LU40
p. 7/12

500LTD02
p. 7/13

560NMD11
p. 7/15

500NMD20
p. 7/16

500LTD03
p. 7/16

RTU500 Ethernet communication

560NMD01
p. 7/14

560NMD02
p. 7/14

560MDD10
p. 7/17

Product catalog | RTU500 series | 7/2

Remote Terminal Units


RTU500 series modules Power supply units
DIN rail power supply unit for 100240 VAC (85264 VAC,
90375 VDC), 60 W
Application
The primary switch mode power supply offers two voltage input
ranges. This enables the supply with AC or DC. Furthermore it
is equipped with two generous capacitors, which ensure mains
buffering of at least 30ms (at 230 VAC). That is why the devices
can be used worldwide also in high fluctuating net-works and
battery powered plants.
CP-E 24/2.5
1SVR427032R0000

Description
Power supply module for DIN rail mounting
Input voltage: 85264 VAC, 90375 VDC
Output voltage: 24 VDC, max. 2.5A, 60W
Typical efficiency of 89%
Ambient temperature range during operation
-40+70C
Power failure buffering time: min. 20ms at
115V AC, min. 30 ms at 230 V AC

DIN rail power supply unit for 110...220VDC, 230VAC


Application
The power supply unit 560PSU40 is a galvanic isolated DIN rail
power supply. It is designed to supply the DIN rail I/O-modules
the 560MPR01 and the communication modules of RTU500
series.

560PSU40
1KGT011600R0001

Description
Power supply module for DIN rail mounting
Input voltage: 85...264 VAC or 85...375 VDC
Output voltage: 24 VDC, max. 2.5A, 60W
Suitable for supply of up to 8 interposing modules
23BEx0/23BA40/560FSMxx/560MPR01/
560CVDxx/RTU540/RTU511/RTU520
Suitable for redundant supply

7/3 | RTU500 series | Product catalog

In order to increase the availability 2 power supplies can be operated in parallel. External diodes are not necessary.

Remote Terminal Units


RTU500 series modules Power supply units
DIN rail power supply unit for 24...60VDC
Application
The power supply unit 560PSU41 is a galvanic isolated DIN
rail power supply. It is designed to supply the RTU560 DIN rail
I/O-modules the 560MPR01 and the communication modules of
RTU500 series.

560PSU41
1KGT017700R0001

Description
Power supply module for DIN rail mounting
Input voltage: 24...60 VDC
Output voltage: 24 VDC, max. 2.5A, 60W
Suitable for supply of up to 8 interposing modules
23BEx0/23BA40/560FSMxx/560MPR01/
560CVDxx/RTU540/RTU511/RTU520

Mains adapter 115...230 VAC -> 24VDC, 48W


Application
The mains adapter 23VG23 is an AC/DC converter in combination with an external back up battery for the use as an uninterruptible power system (UPS). It contains a switch-mode power
supply of 92VAC to 265VAC without switch over the input
voltage. The mains adapter supplies an output voltage of
24VDC with an output current of min. 0,2A and max. 2A.
23VG23
1KGT005500R0001

Charge current: max. 0.35A

Description
Mains adapter AC/DC converter for 115...230VAC
input, output 24VDC, 2A max.
Designed for use with back-up battery 24VDC
nominal for maximum 1.5 hours full operation

Product catalog | RTU500 series | 7/4

Remote Terminal Units


RTU500 series modules Power supply units
Mains adapter 115...230 VAC -> 24VDC, 240W
Application
The mains adapter 23VG24 is an AC/DC converter for an input
voltage of 115 or 230VAC. It supplies an output voltage of
24VDC with an output current of max. 10A.

23VG24
1KGT005600R0001

Description
Mains adapter AC/DC converter for 230 or 115VAC
input, output 24VDC, 10A max.

7/5 | RTU500 series | Product catalog

It can supply the module racks, the mounting panels and the I/O
modules of a RTU560 station with a power output of approx.
240W.

Remote Terminal Units


RTU500 series modules Input/output modules
16 binary inputs, 24...60/110...125 VDC
Application
The binary input device 211BID51 provides 16 galvanic isolated
inputs for 16 binary process signals. Scanning and processing of
the inputs are executed with the high time resolution of 1ms. The
allocation of an input signal to the functional processing can be
done according to the rules of configuration.
211BID51
1KGT024100R0001
1KGT024100R0002

Description
To be used for single indications, double indications,
digital measurands and pulse counters.
Resolution: 1ms
LED signal for each intput
Common return per 8 inputs

The module 211BID51 is able to process the following types of


signals:
16 single indications with time stamp
8 double indications with time stamp
2 digital status messages with 8 bit
1 digital status message with 16 bit
16 pulse counters
The board is available in two versions (rubrics):
R0001: Process voltage 24...60 VDC, LED signal for each
input, common return per 8 inputs
R0002: Process voltage 110...125 VDC, LED signal for each
input, common return per 8 inputs

8 binary outputs, relays


Application
The binary output device 211BOD52 can be used for the control
of 8 binary process signals using relay contacts. Type NO specific processing function of an output can be configured by the
user according to the configuration rules.

211BOD52
1KGT024200R0002

Description
8 single commands 1-pole NO contact (high capacity relays)
Max. switching voltage 150 VDC
Max. load=110VDC/3A

The 211BOD52 can be used for the following types of signal:


Object commands with 1- or 2-pole output
Object commands with 1.5- or 2-pole output with (1 out of n)
check via 560CIG10 or 560CID11
Digital set point commands (8 bit)
String output commands, 1or 8 bit
Regulation commands, 1- and 2-pole

Product catalog | RTU500 series | 7/6

Remote Terminal Units


RTU500 series modules Input/output modules
6 analog inputs, mV signals/ V signbals
Application
The 211AID50 board records up to 6 analog measurement
values. Various sensitivity ranges for voltage and current measurement are available.

211AID50
1KGT024000R0001
1KGT024000R0002

Description
R0001:
Resolution 11bit +sign; accuracy class: 0.25
Measuring range: +/-5mA; +/-10mA; +/- 20mA;
4...20mA
Resolution 10bit + sign; accuracy class 0.5
Measurement range: +/-1VDC and +/-10VDC
R0002:
Resolution 11bit + sign; accuracy class 0.5
Measurement range: +/-1VDC and +/-10VDC

7/7 | RTU500 series | Product catalog

The device 211AID50 is available in two versions (rubrics):


R0001: Current measurement version
R0002: Voltage measurement version

Remote Terminal Units


RTU500 series modules - Input/output adapters
I/O adapter board
Application
The adapter 211ADD52 is the standard adapter to connect
RTU500 I/O-modules to the RTU500 I/O bus (wired OR bus).

211ADD52
1KGT023900R0001

Description
Standard adapter board for up to 8 I/O modules
211BIDxx, 211BODxx, 211AIDxx
Incl. 20 pole ribbon cable
Cable length 200 mm

Product catalog | RTU500 series | 7/8

Remote Terminal Units


RTU500 series modules - Multimeters
Multimeter, 1A/5A, 3U3I
Application
The multimeter 560CVD03 is used for monitoring input signals
from three independent phases with 3 or 4 wire connections. For
each phase voltage, current and power are measured directly, and a number of other parameters are derived from these
according users configuration. The results are collected by the
RTU500 CMU.
560CVD03
1KGT028000R0021
1KGT028000R0025
1KGT028000R0041
1KGT028000R0045

Description
CT/VT interface with 3 voltage and 3 current inputs
for direct monitoring of 3 wire 85400VAC
1A/5A inputs from AC transformers
Serial interface to RTU500 (RS-485)

Versions

Type

LO

560CVD03R0021

3U3I

HI

560CVD03R0025

3U3I

560CVD03R0041

3U3I

560CVD03R0045

3U3I

1A

5A

x
x
x
x

LO power supply: 20...48 VDC


HI power supply: 80...260 VAC, 80...330 VDC

Multimeter with display, 1A/5A, 3U3I


Application
The multimeter 560CVD03 is used for monitoring input signals
from three independent phases with 3 or 4 wire connections. For
each phase voltage, current and power are measured directly, and a number of other parameters are derived from these
according users configuration. The results are collected by the
RTU500 CMU.
560CVD03
1KGT028000R0031
1KGT028000R0035
1KGT028000R0051
1KGT028000R0055

Description
CT/VT interface with 3 voltage and 3 current inputs
for direct monitoring of 3 wire 85400VAC
1A/5A inputs from AC transformers
Serial interface to RTU500 (RS-485)
With display on front

It can be set to automatically change the screen of measurement


page and each screen display every 6 seconds.
If you change it to button push mode, each screen will automatically display for 240 seconds. The scroll mode can be set up by
RTUtil560.
Versions

Type

LO

560CVD03R0031

3U3I

HI

560CVD03R0035

3U3I

560CVD03R0051

3U3I

560CVD03R0055

3U3I

1A

x
x

LO power supply: 20...48 VDC


HI power supply: 80...260 V AC, 80...330 VDC

7/9 | RTU500 series | Product catalog

5A

Remote Terminal Units


RTU500 series modules Multimeters

560CVD11
1KGT030000R0021
1KGT030000R0025
1KGT030000R0041
1KGT030000R0045

Description
CT/VT interface with 4 voltage and 4 current inputs
for direct monitoring of 3/4 wire 10300 VAC
1A/5A signals
Serial interface to RTU560 (RS-485)
Fault current detection (FCD), directional information, 20x In

500CVD21
1KGT030300R0121
1KGT030300R0125
1KGT030300R0141
1KGT030300R0145

Description
CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0300 VAC
(line to earth), 0...500 VAC (phase to phase)
1A/5A from AC transformers
Serial interface to RTU500 (RS-485)
Fault current detection (FCD), directional
information, 20x In

Multimeter with FCD, 1A/5A, 4U4I


Application
The multimeter is used for measuring analog AC input signals
from three independent phases with addition input for neutral
current and voltage and to detect the fault current (FCD) and
over current direction. For each phase voltage, current and power are measured directly, and a number of other parameters are
derived from these according users configuration. The results are
collected by the RTU500 CMU.
Versions

Type

LO

560CVD11R0021

4U4I

HI

560CVD11R0025

4U4I

560CVD11R0041

4U4I

560CVD11R0045

4U4I

1A

5A

x
x
x
x

LO power supply: 20...48 VDC


HI power supply: 80...260 VAC, 80...330 VDC

Multimeter with FCD, 1A/5A, 4U24I


Application
The multimeter is used for measuring analog AC input signals
from three independent phases with addition input for neutral
current and voltage and to detect the fault current (FCD) and
over current direction. For each phase voltage, current and power are measured directly, and a number of other parameters are
derived from these according users configuration. The results are
collected by the RTU500 CMU.
Versions

Type

LO

500CVD11R0121

4U24I

HI

500CVD11R0125

4U24I

500CVD11R0141

4U24I

500CVD11R0145

4U24I

1A

5A

x
x
x
x

LO power supply: 24...60 VDC


HI power supply: 80...330 VDC, 80...260 VAC

Additional material:
Configuration kit for 560CVDxx

560KCA01

Set containing one cable mini-USB to DB-9 for RS-232 configuration port and
CD with configuration tool for 560CVDxx devices

1KGT030800R0001

Product catalog | RTU500 series | 7/10

Remote Terminal Units


RTU500 series modules - Serial communication
560FOC40 optical coupler (850 nm)
Application
The 560FOC40 module is intended for use in RTU560 configurations with binary I/O modules 23BA40/23BE40/23BE50. The module 560FOC40 is used to transmit data via fiber optical cables.
Fiber-optic cables are not sensitive to inductive and capacitive
interference as well as to differences in potential between two
data communication units/systems. The 560FOC40 can be connected to 23OK24 for rack mounting.
560FOC40
1KGT011500R0001

Description
Direct connection to serial peripheral bus (SPB)
For potential isolation of SPB
Emission wave length: 850nm
Input optical power:
- Min. - 24.0dBm
- Max. -10.0dBm
- Transmission rate: 1Mbit max.
Connects in star or multipoint T-configuration
Auxilliary voltage: 24 VDC

Fiber optic links will be used to cover large distances in critical


environments or if potential isolation is required. Available version
is 820 nm multimode glass fiber optic.
RTU560 I/O bus
RS-485 (inactive signal=light OFF)
The board 560FOC40 is snap mounted on DIN rail.

Modem V.23
Application
The 560FSM10 is a modem which converts the serial data according to CCITT V.23 standard with 1200baud. It operates on the
frequency shift keying principle (FSK).

560FSM10
1KGT019200R0001

Description
Voice frequency telegraphy device (VFT)
According CCITT V.23 standard with max.
1200baud
Can be connected to 23WT23
DIN rail mounted
Auxilliary voltage: 24...60 VDC

7/11 | RTU500 series | Product catalog

Two- or four-wire operation mode is selectable by DIP-switch.


The line output is capable to drive up to 10 remote stations connected in a multi-drop line. It can be connected to the 23WT23
modem for rack mounting and can be used as a self-contained
counterpart of it.

Remote Terminal Units


RTU500 series modules Serial communication
Modem 9600baud
Application
The 560FSM11 is a modem for transmitting serial data at rates
up to 9600baud. It operates on the frequency shift keying principle (FSK). Two- or four wire operation mode is selectable by
DIP-switch.

560FSM11
1KGT019300R0001

The line output is capable to drive up to 10 remote stations connected in a multi-drop line. It can be connected to the 23WT24
modem for rack mounting and can be used as a self-contained
counterpart of it.

Description
FSK device with 9600 baud transmission speed
Communication over pilot cable
Can be connected to 23WT24
DIN rail mounted
Isolation test voltage 3kV
Auxilliary voltage: 24...60 VDC

25LU40
1KGN000865R0001

Description
Isolated line transformer for galvanic isolation of
transmission line
Ideal for 23WT23/23WT25 and 560FSM10
Lightning protection 7.5kV
Snap locked
Optimized for line impedance of 600
Ratio 1:1
Isolation test voltage 2.5kV

Line transformer 600/600 + lightning protection


Application
The DIN rail mountable voice frequency line transformer 25LU40
is intended to isolate the RTU500 FSK modems (frequency shift
keying) from the pilot line and to protect the RTU500 equipment
from high voltage disturbances. The 25LU40 operates with very
low transmission loss in the working frequency range from 300 to
3400Hz applies to line impedances of 600Ohms and to the ABB
modems 23WT23, 23WT25 and 560FSM10. The test voltage is
2.5kV at 50Hz. Protection is guaranteed through the integrated
sparking gap, fuses and 10kA arrestors.
A high-resistance staggering is possible with both types of modems on e.g. party lines and multidrop lines. This is because the
line transformer has no additional load at the line.

Product catalog | RTU500 series | 7/12

Remote Terminal Units


RTU500 series modules - Serial communication
Line transformer 7.5 kV, 2-50 kHz
Application
The line transformer 500LTD02 is designed for FSK channels
with 9600 baud to isolate and protect the RTU560 Modems
23WT24 and 560FSM11 from the telecontrol line. Moreover it
can also be connected to other data terminal equipments. It
operates at a frequency range from 2 kHz to 50 kHz and is optimized for line impedances of 150 Ohms which applies to above
mentioned modems.
500LTD02
1KGT026600R0002

Description
Isolated line transformer for galvanic isolation of transmission line
Operates at a frequency range from 2kHz to
50kHz (23WT24 and 560FSM11)
Isolation test voltage 7.5kV
Optimized for line impedances of 150
Ratio1:1
Insulation resistance: 10000M at 500V between
windings and the case

7/13 RTU500 series | Product catalog

A high resistance staggering is possible with both types of


modems on e.g. party lines and multi-drop lines. This is because
the line transformer has no additional load at the line. In configurations using full duplex communication channels two line
transformers are required, one for transmitting direction and one
for receiving direction.

Remote Terminal Units


RTU500 series modules Ethernet communication

560NMD01
1KHW025096R0001

DIN rail integrated managed switch with 1 SDSL-port,


4 Ethernet ports and 1 serial RS-232 port
Application
The DIN rail mountable 560NMD01 is a managed plug and play
layer-2-switch providing 4 fast Ethernet auto-negotiating RJ45ports with auto MDI/X (Automatic Crossover Detection and Correction) and one 2-wire SDSL-port for use with private copper
cables. The switch is intended for distributing Ethernet within a
station through the RJ45-ports. The SDSL-port can be used for
interconnecting stations with a maximum distance of 20km (copper cable with diameter of 0.8mm). The switch is able to provide
redundant topologies by the (Rapid) Spanning Tree Protocol. The
modem can be connected to 560NMS4 and 560NMS34.

Description
Integrated managed layer-2-switch
4x10/100BaseT port (RJ45, electrical,
autonegotiating)
1xSDSL-port for copper wire (pilot cable)
Provides redundant topologies by the (Rapid)
Spanning Tree Protocol (RSTP)
1x RS-232 port suitable for tunneling of serial
protocols

500NMD02
1KHW025097R0001

Description
Integrated managed layer-2-switch
4x 10/100 BaseT port (RJ45, electrical, autonegotiating)
2x SDSL-port for copper wire
Provides redundant topologies by the (Rapid)
Spanning Tree Protocol (RSTP)
2x RS-232 port suitable for tunneling of serial
protocols

DIN rail integrated managed switch with 2 SDSL-ports,


4 Ethernet ports and 2 serial RS-232 ports
Application
The DIN rail mountable 560NMD02 is a managed plug and play
layer-2-switch providing 4 fast Ethernet auto-negotiating RJ45ports with auto MDI/X (Automatic Crossover Detection and Correction) and two 2-wire SDSL-ports for use with private copper
cables. The switch is intended for distributing Ethernet within a
station through the RJ45-ports. The SDSL-ports can be used for
interconnecting stations with a maximum distance of 20km (copper cable with diameter of 0.8mm). The switch is able to provide
redundant topologies by the (Rapid) Spanning Tree Protocol in
one device. The modem can be connected to 560NMS4 and
560NMS34.

Product catalog | RTU500 series | 7/14

Remote Terminal Units


RTU500 series modules Ethernet communication

560NMD11
1KHW027869R0001

Description
Integrated managed layer-2-switch
4x 10/100BaseT port (RJ45, electrical, autonegotiating)
1xSFP slot (without optical transmitter/receiver)
Additional SFP modules are required (see 560NFOxx)
1x SDSL-port for copper wire
Provides redundant topologies by the (Rapid) Spanning Tree Protocol (RSTP)
2x RS-232 port suitable for tunneling of serial protocols

DIN rail integrated managed switch with 1 SDSL-port, 1 FX-port


and 4 Ethernet ports
Application
The DIN rail mountable 560NMD11 is a managed plug and play
layer-2 switch providing 4 auto-negotiating fast Ethernet RJ45ports with auto MDI/X (Automatic Crossover Detection and Correction), one 2-wire SDSL-port for use with private copper cables
and one SFP (small form-factor pluggable) module slot for use
with fiber optic transceivers. Ethernet may be distributed within a
station through the 4 RJ45-ports of the switch.
The SDSL-port can be used for interconnecting stations with a
maximum distance of 20km (diameter of 0.8mm) copper cable.
Depending on the SFP-module equipped, the unit is able to span
distances by fiber optic cable up to 40km. The switch is able
to provide redundant topologies by the (Rapid) Spanning Tree
Protocol in one device.

Additional material:
SFP (small form-factor pluggable) for optical switch

560NFO13

For 560NUS12, 560NMD11 and 500NMD20 board; monomode,

560NFO15

distance of typically 15km

1KHW001893R0001
1KHW001894R0001
1KHW001895R0001

For 560NUS12, 560NMD11 and 500NMD20 board; monomode,


distance of typically 40km
560NFO85
For 560NUS12, 560NMD11 and 500NMD20 board; multimode,
distance of typically 2km

Configuration adapter for 560NMDxx

560NMA01
Saves configuration for one DIN rail integrated switch
Enable PC free replacement of modules

1KHW027870R0001

7/15 | RTU500 series | Product catalog

Remote Terminal Units


RTU500 series modules Ethernet communication

500NMD20
1KHW025098R0001

DIN rail integrated managed switch with 2 FX-ports and 4


Ethernet ports
Application
The DIN rail mountable 500NMD20 is a managed plug and play
layer-2 switch providing four Fast Ethernet auto-negotiating
RJ45-ports with auto MDI/X (Automatic Crossover Detection and
Correction) and two SFP (small form-factor pluggable) module
slots for use with fibre optic transceivers. Depending on the SFP
module equipped, the unit is able to span distances by fibre
optic cable up to 40 km (or even more with special SFP modules). The switch is able to provide redundant topologies by the
(Rapid) Spanning Tree Protocol.

Description
Integrated managed layer-2-switch
4x 10/100 BaseT port (RJ45, electrical, autonegotiating)
2x SFP-slot (without optical transmitter/receiver)
Additional SFP module is required (see 560NFOxx)
Provides redundant topologies by the (Rapid) Spanning Tree Protocol (RSTP)
2x RS-232 port suitable for tunneling of serial protocols

Line Transformer 7.5 kV, 1-1000 kHz


Application
The line transformer 500LTD03 is designed for DSL channels
with up to 7168 kbps and to isolate and protect the RTU500
DSL Modems 560NMD01, 500NMD02, 560NMD11, 560NMS24
and 560NMS34 from the telecontrol line. Moreover it can also be
connected to other data terminal equipments.

500LTD03
1KGT026600R0003

Description
Isolated line transformer for galvanic isolation of transmission line
Designed for DSL channels with up to 7168 kbps
Isolates and protects the RTU500 SDSL modems
560NMDxx, 500NMDxx, 560NMSxx from the
telecontrol line
Operates at a frequency range from 1 kHz to
1000 kHz
Isolation test voltage > 10 kV
Optimized for line impedances of 100 Ohms
Ratio 1:1
Insulation resistance: 10.000 Mohm at 500 V
between windings and the case

It operates at a frequency range from 1 kHz to 1 MHz and is


optimized for line impedances of 100 Ohms.
In DSL modem configurations one line transformer is required at
both ends of the line.

Product catalog | RTU500 series | 7/16

Remote Terminal Units


RTU500 series modules - Ethernet communication

GSM/GPRS modem for DIN rail


Application
The 560MDD10 is a GSM/GPRS modem that provides Ethernet
communication via serial interface with point-to-point protocol
(PPP). The modem consists of a compact DIN rail housing.

560MDD10
1KGT030100R0001

Description
Ethernet communication via serial interface with
point-to-point protocol (PPP)
Plastic DIN rail housing
Quad band GSM/GPRS
SIM card and antenna have to be ordered separately

Additional material:
Bar antenna for 560CMD11 and 560MDD10

560ANA01R0001

1KGT023600R0001

Bar Antenna for 560CMD11 and 560MDD10


10 pcs per package

Wall mounted antenna for 560CMD11 and 560MDD10

560ANA02R0005
Wall mounted antenna for 560CMD11 and 560MDD10, 5m cable

1KGT023700R0005

Antenna cable RG58, 15m

560CAB02 R0015
Extension cable for wall mounted GPRS antenna 560ANA02, RG58, 15m

1KGT033800R0015

7/17 | RTU500 series | Product catalog

Product catalog | RTU500 series | 7/18

Remote Terminal Units


RTU500 series functions and software One software for all
product lines of RTU500 series

8
Webserver functionality: archive (upper left) | RTUtil500 Setup (upper right) | Integrated HMI with example for station control (lower left) | Presentation of analog trends (lower right)

8/1 | RTU500 series | Product catalog

Remote Terminal Units


RTU500 series functions and software One software for all
product lines of RTU500 series
Licenses Release 10
Basic license

8/3

PLC/Archive license

8/3

HMI (human machine interface) license

8/3

Licenses Release 11
Release 11 for RTU520 productline and RTU511 product line
Basic license

8/4

PLC/Archive license

8/4

Release 11 for RTU540 productline and RTU560 product line


Basic license

8/4

PLC/Archive license

8/4

HMI (human machine interface) license

8/4

PC Tools
COMPROTware Tool

8/5

ITT600 SA Explorer

8/5

RTUtil500 8/5
RTUtil560 8/5
IET600 8/5
MULTIPROGwt 8/5

Product catalog | RTU500 series | 8/2

Remote Terminal Units


RTU500 series modules functions and software

Licences Release 10:


50DP/250DP/750DP/5000DP

Basic license

Incl. IEC 61850 Server and Client

1KGT201446R0001
1KGT201443R0001
1KGT201440R0001
1KGT201437R0001

(50 DP)
(250 DP)
(750 DP)
(5000 DP)

Compact flashcard 128MB

50DP/250DP/750DP/5000DP

PLC/Archive
1KGT201447R0001
1KGT201444R0001
1KGT201441R0001
1KGT201438R0001

All protocols

(50 DP)
(250 DP)
(750 DP)
(5000 DP)

Compact flashcard 128MB

50DP/250DP/750DP/5000DP

HMI license
1KGT201448R0001
1KGT201445R0001
1KGT201442R0001
1KGT201439R0001

Incl. Basic licence

(50 DP)
(250 DP)
(750 DP)
(5000 DP)

8/3 | RTU500 series | Product catalog

Incl. Basic and PLC/Archives licences


Compact flashcard 128 MB

Remote Terminal Units


RTU500 series modules functions and software

Licences Release 11 for RTU520 product line and RTU511 product line:
Basic license

50DP/250DP/750DP

All protocols

1KGT201599R0011 (50 DP)


1KGT201596R0011 (250 DP)

1KGT201593R0011
(750 DP)

SD card



50DP/250DP/750DP

PLC/Archive

Incl. Basic licence


1KGT201600R0011 (50 DP)
1KGT201597R0011 (250 DP)
1KGT201594R0011 (750 DP)

SD card

Licences Release 11 for RTU540 product line and RTU560 product line:
Basic license

50DP/250DP/750DP/5000DP

Incl. IEC 61850 Server and Client

1KGT201446R0011
1KGT201443R0011
1KGT201440R0011
1KGT201437R0011

(50 DP)
(250 DP)
(750 DP)
(5000 DP)

Compact flashcard 128MB

50DP/250DP/750DP/5000DP

PLC/Archive
1KGT201447R0011
1KGT201444R0011
1KGT201441R0011
1KGT201438R0011

All protocols

(50 DP)
(250 DP)
(750 DP)
(5000 DP)

Compact flashcard 128MB

50DP/250DP/750DP/5000DP

HMI license
1KGT201448R0011
1KGT201445R0011
1KGT201442R0011
1KGT201439R0011

Incl. Basic licence

(50 DP)
(250 DP)
(750 DP)
(5000 DP)

Incl. Basic and PLC/Archives licences


Compact flashcard 128 MB

Product catalog | RTU500 series | 8/4

Remote Terminal Units


RTU500 series modules functions and software
Tools:
COMPROTware Tool

Integrated testtool for telecontrol protocols

The following protocols are available:


IEC870-5-101, IEC870-5-102, IEC870-5-103, IEC870-5-104, MODBUS serial

1KGT0000000R0003

and over TCP/IP, SPABUS, RP570, DNP3.0 (serial), DNP3.0 on LAN/WAN

Scope of supply: installation CD and hardlock

ITT600 SA Explorer

IEC61850 testing tool (single license) with following functions:


Explore IEDs
Explore data models

Integrated Testing Tool ITT600


Version X.X.X

Explore Ethernet
1KGT0210239R0001

Document ID
ABB AG 03/2013

www.abb.com/substationautomation

Explore GOOSE
Scope of supply: CD and hardlock

RTUtil500

Utility software for industrial standard PC containing the program modules running under Windows XP/Windows 7 (single license)

Configuration of RTU500 (signal tree, network tree, hardware tree)

RTUtil500
Version X.X.X

1KGT210278R0001
Document ID
ABB AG 03/2013

Creation of download files for RTU500


EXCEL-Import/Export function

www.abb.com/substationautomation

Scope of supply: one CD


For firmware release 11
RTUtil560

Software package utilities RTU560


Utility software for industrial standard PC containing the program
modules running under Windows XP, Windows 7 (single license)

RTUtil560
Version X.X.X

Configuration of RTU560 (signal tree, network tree, hardware tree)


1KGT210203R0001

Document ID
ABB AG 03/2013

www.abb.com/substationautomation

Creation of download files for RTU560


EXCEL-Import/Export function
Scope of supply: one CD
For firmeware release 10

IET600

Integrated Engineering Tool IET600


IET600 acts as a system tool which is used to define and share the

Integrated Engineering Tool IET600


Version X.X.X

1KGT030900R0001
Document ID
ABB AG 03/2013

system-wide 61850 parameters, such as communication addresses,


horizontal communication data and its priorities and client/server (system

www.abb.com/substationautomation

level/IED) connections. The actual configuration of the IED and the down
loading of configuration changes are done with PCM600.
MULTIPROGwt

Software package utilities RTU500 for PLC


Utility software for industrial standard-PC containing the program
modules running under Windows XP, Windows 7 (single license)
PLC programming according to IEC1131-3, function-block-diagram (FBD),
1KGT210204R0001

instruction list (IL), structured text (ST), sequential function chart (SFC), ladder
diagram (LD)
Scope of supply: dongle (hardlock USB), software is part of RTUtil560 and
RTUtil500 CD

8/5 | RTU500 series | Product catalog

For your notes

Product catalog | RTU500 series | 8/6

ABB AG
Power Systems Divsion
P.O. Box 10 03 51
68128 Mannheim, Germany
Phone: +49 (0) 621 381-3000
Fax: +49 (0) 621 381-7602
E-Mail: rtu-sales-support@de.abb.com
www.abb.com/substationautomation

Note: We reserve the right to make technical changes or


modify the contents of this document without prior notice.
With regard to purchase orders, the agreed particulars shall
prevail. ABB AG does not accept any responsibility whatsoever
for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
to third parties or utilization of its contents in whole or in parts
is forbidden without prior written consent of ABB AG.
Copyright 2014 ABB
All rights reserved

Scan this QR code to visit our website

DEABB 1816 13 EN printed in Germany (14.03-1000-NI)

Contact us