This document contains the table information contained in the Generating
System Design Data Sheets and Generating System Setting Data Sheets .
Please refer to the AEMO website for information on how to apply these
http://www.aemo.com.au/registration/118-0001.html

DISCLAIMER
This document is made available to you on the following basis:
(a)
(b)
(c)

(d)

(e)

2011 - AEMO Limited is the owner of the copyright in this document. All rights reserved.

DISCLAIMER
This document is made available to you on the following basis:
Purpose - This document is provided to you for information purposes only. You are not permitted to
Reliance
- Thisit document
may be contained
subsequently
commercialise
or any information
in it.amended. Any reliance on this document is at your
own risk.
Intellectual Property AEMO is the owner of the copyright in this document. All rights are reserved.
All material is subject to copyright under the Copyright Act 1968 (Commonwealth) and permission to
copy it, or any parts of it, must be obtained in writing from AEMO. AEMO is the owner of all other
intellectual property rights in this document and the information contained in it. You must not in any
way, or by any means, store, reproduce or modify it without AEMO's express written consent.
No Warranty - Neither AEMO, nor any of AEMOs advisers, consultants or other contributors to this
document (or their respective associated companies, businesses, partners, directors, officers or
employees) make any representation or warranty, express or implied, as to the currency, accuracy,
reliability or completeness of this document, or the information contained in it.
No Liability - To the maximum extent permitted by law, neither AEMO, nor any of its advisers,
consultants or other contributors to this document (or their respective associated companies,
businesses, partners, directors, officers or employees) shall have any liability (whether arising from
negligence or otherwise) in respect of your use of the information (including any reliance on its
currency, accuracy, reliability or completeness) contained in this document.
2011 - AEMO Limited is the owner of the copyright in this document. All rights reserved.

Generating System Design Data Sheets


and
Generating System Setting Data Sheets
Prepared by: AEMO - Planning
Version 0.44
22-July-2011

Usage Note:
1 This is a supplementary spreadsheet to assist applicants in preparing their generator connection
documents.
2 This spreadsheet should be used in conjunction with the original "Generating System Design Data
Sheets and Generating System Setting Data Sheets - Final" published on 29 February 2008 by
NEMMCO.
3 The "Main" sheet contains a list of all the data sheets. Some typical data sheet "packages" for
generating systems have been provided for reference. The applicant should only select the relevant
ones based on the actual arrangement of the generating plant.
4
Each data sheet listed in the "Main" sheet contains a hyperlink which points to the corresponding tab.
5 All cells in this document are write-protected except those which are allowed to change, e.g. values and
remarks. Users can unprotect these sheets but are not encouraged to do so.
6 The "value" cells are only for information in the specified units. Other information should be entered into
the remark field. One typical use is the name of additional reference material.
7 Additional sheets may be inserted but the plant item(s) should be listed under the "Proposed Plant"
column in the "Main" sheet.
8 This spreadsheet is a testing version and is subject to change with no further notice.
9 Users are encouraged to provide feedback on improvement of this spreadsheet.

11/5/2014

250176768.xls.ms_office

Page 5 of 61

Generator Connection
Data Sheet

Section

6
7
8
8.1
8.2
9
9.1
9.2
9.3
9.4
9.5
9.6
10
10.1
10.2
10.3
11
11.1
11.2
11.3
12
12.1
12.2
12.3
12.4
12.5
13
14
14.1
15
15.1
15.2
15.3
15.4
15.5
16
16.1
16.2
16.3
16.4

11/5/2014

Data Sheet

Proposed Plant

Generating system (Power Station)


Individual Generating Unit Data
Grid Interfaces
Transformer (generating unit and generating system)
AC-DC-AC or DC-AC Converter
Electrical Generator
Synchronous Machine (including synchronous compensator)
Asynchronous Machine (cage rotor)
Asynchronous Machine (variable rotor resistance)
Asynchronous Machine (doubly fed)
Photovoltaic Cell Array
Fuel Cell
Primary Electrical Control systems
Synchronous Machine Excitation System
Asynchronous P-Q (or P-V) Control systems
DC Current Regulator
Secondary Electrical Control systems
Fault Ride-Through Control systems
Other Generating unit control systems
Generating System Control systems (coordinated control of generating system
plant)
Prime Mover and Primary Mechanical Control systems
Steam turbine and turbine governor
Hydro turbine and turbine governor
Gas turbine and turbine governor
Wind turbine aerodynamic model and blade pitch controller model
Diesel and Gas Reciprocating Engine
Secondary Mechanical Control systems
Prime Mover Mechanical Coupling / Subsynchronous Resonance
Shaft Model / Subsynchronous Resonance Frequencies
Auxiliary Compensation Equipment
Mechanically or electronically switched capacitor , reactor or resistor
Static VAR Compensator, Thyristor Controlled (SVC)
Voltage Source Converter or Current Source Converter, self commutated, or
similar (VSC, CSC, Statcon or Statcom)
Flywheel
Storage Battery
Protection systems
Synchronous machine protection systems (backups for excitation limiters)
Asynchronous machine protection systems (for generating unit instability)
Crowbar protection systems
Other protection systems

250176768.xls.ms_office

Page 6 of 61

6.1.1
Symbol
VCON
NMC

Design Data Sheet


Data Description
Connection point to network
Nominal voltage at connection to
network
Total station net maximum capacity
(NMC)
Single line diagram of the power station
showing primary plant configuration,
switching arrangements, earthing
arrangements for plant. On the single line
diagram or separate diagram, show branch
and earthing impedances.

Diagram showing the various control


systems for the generating unit and
generating system together with their
inputs and outputs and how they link with
each other
Three phase short circuit infeed at the
connection point , for the following faults:

Units
Text

Data Category
S, D

kV

MW (sent out)

S, D, R1

Diagram

D, R1

Diagram

Value

Balanced (3 phase)

max
Ia

D, R1

UH

ZS1

Unbalanced (each phase)

Highest Voltage of a system (as


per AS 1824.1)

Supplying Network Positivesequence short-circuit impedance as


viewed from the connection point

11/5/2014

kV

D,R1

(a + jb) % on 100
MVA base and
VCON

D,R1

Remarks

min
Ib

Ic

line-line, max
line-line, min
line-lineground, max
line-lineground, min
line-ground,
max
line-ground,
min

250176768.xls.ms_office

Page 7 of 64

ZS2

ZS0

IKDDO

Supplying Network Negativesequence short-circuit impedance as


viewed from the connection point

Supplying Network Zerosequence short-circuit impedance as


viewed from the connection point

initial symmetrical short-circuit


current with generating system
disconnected

(a + jb) % on 100
MVA base and
VCON

D,R1

(a + jb) % on 100
MVA base and
VCON

D,R1

kA (RMS)

D, R1

kA (RMS)

D, R1

kA (peak)

D, R1

D, R1

kA (RMS)

D, R1

kA (RMS)

D, R1

kA

D, R1

(peak RMS short circuit current, assuming nonmeshed calculation approach for a radial
connection )

IKDD

initial symmetrical short-circuit


current
(peak RMS short circuit current, assuming nonmeshed calculation approach for a radial
connection )

IP

peak short-circuit current

(maximum possible instantaneous value of the


prospective (available) short-circuit current)

TMIN

minimum time delay

(the minimum time from fault inception to the instant


of contact separation of the first pole to open of a
switching device at or near the connection point
the time as agreed with the network service provider
or 60 milliseconds)

symmetrical short-circuit
breaking current

IB

(RMS value of an integral cycle of the symmetrical


AC component of the prospective short circuit
current at TMIN.)

IK

steady-state short-circuit current

(RMS value of the short-circuit current which


remains after the decay of the transient phenomena)

IDC

decaying DC component of shortcircuit current


(mean value between the top and bottom envelope
of a short-circuit current decaying from an initial
value to zero)

11/5/2014

250176768.xls.ms_office

Page 8 of 64

TDC

decay time for DC component of


short-circuit current
(the time taken for DC current component to fall to
1
/2.718 of IDC)

Minimum positive sequence impedance


of Generating System
Minimum negative sequence impedance
ZGS2MIN
of Generating System
Minimum zero sequence impedance of
ZGS0MIN
Generating System
Description of the assumptions used in
the derivation of the above quantities.
Single phase to ground fault at the
connection point
ZGS1MIN

Two Phase to ground fault at the


connection point
Three phase fault at the connection point

Description of the assumptions used in


the derivation of the above quantities.

6.1.2

D, R1

% on 100 MVA
base and VCON
% on 100 MVA
base and VCON
% on 100 MVA
base and VCON

D, R1
D, R1
D, R1

Text

D, R1

3 phase current
waveform vs time

D,R1

3 phase current
waveform vs time

D,R1

3 phase current
waveform vs time

D,R1

Text

D, R1

Setting Data Sheet

Symbol

Data Description
Units
Operational arrangements for the
generating system or within the
generating system where this may affect
Text
switching configuration or plant
operational limits.
Connection point over-voltage and undervoltage trip settings and times (if
kV and seconds
applicable)
Model documentation (in accordance with
Rule s5.2.4 (b)), as specified in the
Generating System Model Guidelines .

11/5/2014

Data Category

Value

Remarks

D, R1, R2

250176768.xls.ms_office

Page 9 of 64

Individual Generating Unit Data

7
Symbol
NGU

7.1.1

Data Description
Number of identical generating units and
identification names or numbers
Type of generating unit (technology),
manufacturer and manufacturers type
designation or product name.
List or table of plant , control systems and
protection systems, applicable to this
generating unit , for which data has been
provided in the Data Sheets.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Text

S, D

Units
MVA
MW (sent out )
MW (Gen)

Data Category
S, D, R1
S, D, R1
D, R1

Value

Remarks

Value

Remarks

Design Data Sheet

Symbol
MBASE
PSO
PMAX
PDMAX

Data Description
Rated MVA
Rated MW (Sent Out )
Nameplate Rating (Generated )
Maximum capacity MW (Generated)
(e.g. short term rating or maximum dispatchable MW)

MW

generated MW value(s)

time(s) that the generated MW


minutes
applies; and

conditions for which the generated


Text
(or chart and text)
MW applies.
Maximum ambient operating temperature
degrees C
(if applicable)
VT
Nominal terminal voltage
kV
PAUX
Auxiliary load at PMAX
MW
Qmax
Rated reactive power output at PMAX
MVAr (sent out )
PMIN
Minimum Load (ML)
MW (sent out )
GCD
Capability chart
Graphical data
Minimum positive sequence impedance
% on 100 MVA
ZGU1MIN
base and VT
Minimum zero sequence impedance
% on 100 MVA
ZGU2MIN
base and VT
Minimum negative sequence impedance
% on 100 MVA
ZGU0MIN
base and VT

11/5/2014

S, D, R1
S, D, R1

S, D
D, R1
S, D, R2
S, D, R1
S, D, R2
D, R1, R2
D, R1
D, R1
D, R1

250176768.xls.ms_office

Page 10 of 63

7.1.2

Setting Data Sheet

Symbol

Data Description
Operational arrangements for the
generating system or within the
generating system where this may affect
switching configuration or plant
operational limits.

11/5/2014

Units

Data Category

Text

250176768.xls.ms_office

Value

Remarks

Page 11 of 63

8.1
Symbol

8.1.1

Transformer (generating unit and generating system)


Data Description
Transformer identification number
If this is a generating unit transformer,
the list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units
Text

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category
S, D
S, D
S, D, R1
S, D, R1

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet

Symbol
GTW
GTVG
GTRn
GTTRn
GTZ1n

GTZOn

GTAPR
GTAPS

8.1.2

Data Description
Number of windings
Vector group
Rated MVA of each winding
Principal tap rated voltage s
Positive sequence impedance of each
winding
(negative sequence impedance [GTZ2n] is expected to
be identical to GTZ1n)

Zero sequence impedance of each


winding
Earthing arrangement
Saturation curve
Tap changer type, on/off load
Tapped winding
Tap change range
Tap change step size
OLTC details of control loop described in
block diagram or schematic form showing
functions of individual elements,
measurement units and measurement
location.

Text
MVA
kV/kV
(a + jb) % on 100
MVA base and
VCON
(a + jb) % on 100
MVA base and
VCON
Text, diagram
Diagram
On/Off
Text, diagram
kV kV
%

S, D, R1

S, D, R1
S, D
R1
D
S, D, R1
S, D
D

Diagram

D, R2

Units
V
V

Data Category
D, R2
D, R2

Setting Data Sheet

Symbol

Data Description

VREFMAX Upper voltage reference

VREFMIN Lower voltage reference

11/5/2014

250176768.xls.ms_office

Page 12 of 63

GTAPV
GTAPD
GTAPVL
GTAPT

Tap change voltage setting range and


setpoint (if any)
Tap change voltage deadband
Tap change high and low voltage
interlocks (monitoring non-tapped side
voltage or other control signal (specify))

kV kV

D, R2

kV

D, R2

kV, kV

D, R2

Tap change cycle time(s)


Line Drop Compensation or reactive
power droop settings

s, text
pu , pu

D, R2

RL and XL

11/5/2014

RL:

(per unit base on GTRn


and nominal voltage of
winding where the
measurement is taken.)

D, R1

XL:

250176768.xls.ms_office

Page 13 of 63

8.2
Symbol

8.2.1
Symbol

AC-DC -AC or DC -AC Converter


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Text

R1, R2

Graphical data
V

D, R1, R2
D, R1

D, R1

Text / Diagram

kV

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Converter type and description including
manufacturers type or product
designation
Capability chart
Nominal DC voltage

UDC
UDCMAX
Maximum and minimum DC voltage
UDCMIN
IDC
Rated DC current
Voltage angle reference (voltage signal
used for reference angle)
Voltage threshold below which the
reference angle tracking stops and
internal reference operates (if
applicable).
Functional block diagram of non-grid-side
and grid-side converters, including

any active power and reactive


power control system ;

any AC voltage control scheme;

Diagram
D, R1

any DC voltage and current


control systems ;

any limiters (e.g. over-voltage or


under-voltage limiters);

any stabilisation functions.


Non-grid-side Converter (where applicable, e.g. rotor side converter of AC -DC -AC
Converter type
Text
S, D
UAC
AC voltage as a function of UDC
Text
D, R1
IAC
Rated AC current
A
D, R1
Crowbar control or protection data (if applicable):
Crowbar description:

its primary function (protecting


against what?)
11/5/2014

250176768.xls.ms_office

Text / Diagram

Page 14 of 61

RC
XC

location (on what plant items


and parts of those items does it
operate);

description of conditions
(including threshold values) under
which it will operate;

description of conditions
(including threshold values and
generating unit trip settings) under
which it will cease to operate.
Crowbar protection resistance
Crowbar protection reactance

Grid-Side Converter:
Converter type
UAC
Rated AC voltage
Rated AC current
IAC

8.2.2
Symbol

Text / Diagram

% on MBASE
and VT
% on MBASE
and VT

D, R1
D, R1

Text
V
A

S, D
D, R1
D, R1

Units

Data Category

Setting Data Sheet


Data Description
All functional block diagram parameters
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.) in accordance with
Rule s5.2.4 (b).

11/5/2014

Value

Remarks

D, R1, R2

250176768.xls.ms_office

Page 15 of 61

9.1
Symbol

9.1.1

Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units
kV

Data Category
D, R1

MVA

S, D, R1

Graphical data

D, R1

MVAr export

S, D, R2

MVAr export

S, D, R2

MVAr import

S, D, R2

MVAr import

S, D, R2

MVAr export

D, R1

MWs/MBASE

D, R1, R2

Text
A

S, D
D, R1
D, R1

D, R1, R2

D, R1, R2

D, R1, R2

Value

Remarks

Value

Remarks

Design Data Sheet

Symbol
VTGEN
MBASEGEN

GCD
Q+PMAX
Q+PMIN
Q-PMAX
Q-PMIN

Q+OEX

Hgen
NP
GSCR
ISTATOR
IROTOR
VROTOR
VF

Synchronous Machine (including synchronous compensator)

Data Description
Nominal terminal voltage
Synchronous machine nameplate rating
(MVA)
Capability chart
Maximum lagging Reactive power at
PMAX
Maximum lagging Reactive power at
PMIN
Maximum leading Reactive power at
PMAX
Maximum leading Reactive power at
PMIN
Maximum lagging short term Reactive
power capability at PMAX, VTGEN and
rated speed (before over-excitation limiter
action)
Synchronous machine inertia constant
(excluding prime mover inertia)
Number of poles
Short circuit ratio
Rated stator current
Rated rotor current at rated MVA and
power factor, rated terminal voltage and
rated speed
Rotor voltage at which IROTOR is
achieved
DC field voltage at VTGEN and rated
speed with unit unsynchronised

11/5/2014

250176768.xls.ms_office

Page 16 of 64

DC field current at VTGEN and rated


speed with unit unsynchronised

IF

RA

RF

D, R1, R2

Stator resistance

% on MBASE
and VTGEN

(at normal or typical operating temperature specify


temperature)

S, D, R1, R2

(temperature in C)

Rotor resistance

% on MBASE
and VTGEN

(at normal or typical operating temperature specify


temperature)

(temperature in C)

XL

Stator leakage reactance

X2

Negative sequence reactance


Zero sequence impedance

Z0

(including any neutral earthing impedance)

XD
XDD
XDDD
XQ
XQQ
XQQQ
TD0
TDD0
TKD
TQ0
TQQ0
GOCC

Direct axis unsaturated synchronous


reactance
Direct axis unsaturated transient
reactance
Direct axis unsaturated sub-transient
reactance
Quadrature axis unsaturated
synchronous reactance
Quadrature axis unsaturated transient
reactance
Quadrature axis unsaturated subtransient reactance
Direct axis open circuit transient time
constant
Direct axis open circuit sub-transient time
constant
Direct axis damper leakage time constant
Quadrature axis open circuit transient
time constant
Quadrature axis open circuit subtransient time constant
Open circuit characteristic

11/5/2014

% on MBASE
and VTGEN
% on MBASE
and VTGEN
(a+jb) % on
MBASE and
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN

S, D, R1, R2

D, R1, R2
D, R1
D, R1
S, D, R1, R2
S, D, R1, R2
S, D, R1, R2
D, R1, R2
D, R1, R2
D, R1, R2

S, D, R1, R2

S, D, R1, R2

S, D, R1, R2

D, R1, R2

D, R1, R2

Graphical data

R1

250176768.xls.ms_office

Page 17 of 64

S10

S12
GSCC
GZPC

Saturation Parameter at 1.0pu terminal


voltage on GOCC (the ratio between
measured voltage and the air-gap line).
Saturation Parameter 1.2pu terminal
voltage on GOCC(the ratio between
measured voltage and the air-gap line).
Short circuit characteristic
Zero power factor curve

11/5/2014

R1

R1
Graphical data
Graphical data

R1
R1

250176768.xls.ms_office

Page 18 of 64

9.2
Symbol

9.2.1

Asynchronous Machine (cage rotor)


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Data Description
Nominal terminal voltage
Asynchronous machine nameplate rating
MBASEGEN
(MVA)
Reactive power consumption over
QN
range of asynchronous machine output
Asynchronous machine and gearbox
inertia constant (excluding prime mover
Hgen
inertia)
NP
Number of poles
SLIP
Rated slip

XS
RM

XM

RR

XR

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units
kV

Data Category
D, R1

MVA

S, D, R1

Chart
(MVAr vs. MW)

D, R1, R2

MWs/MBASE

D, R1, R2

Value

Remarks

Value

Remarks

Design Data Sheet

Symbol
VTGEN

RS

Units

S, D
S, D, R1

Stator resistance

% on MBASE
and VTGEN

(at normal or typical operating temperature specify


temperature)

(temperature in C)

Stator leakage reactance

unsaturated and

at VTGEN
Iron loss resistance, referred to the stator
Magnetizing reactance, referred to the
stator

unsaturated and

at VTGEN
Rotor resistance at rated slip, referred to
the stator
Rotor leakage reactance, referred to the
stator

unsaturated and

at VTGEN

R0

Zero sequence resistance

X0

Zero sequence reactance

R2

Negative sequence resistance

11/5/2014

% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN

S, D, R1, R2

S, D, R1
S, D, R1, R2
S, D, R1, R2

S, D, R1
S, D, R1, R2
D, R1, R2

S, D, R1
S, D, R1, R2
D, R1, R2
D, R1, R2
D, R1
250176768.xls.ms_office

Page 19 of 61

X2

% on MBASE
and VTGEN

D, R1

Magnetising curve (voltage versus


current)

Chart

D, R1

Speed (slip) vs torque (power) curve(s)

Chart

D, R1

Equivalent circuit noting location of


equivalent impedances

Chart

D, R1

Negative sequence reactance

11/5/2014

250176768.xls.ms_office

Page 20 of 61

9.3
Symbol

9.3.1

Asynchronous Machine (variable rotor resistance)


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Data Description
Nominal terminal voltage
Asynchronous machine nameplate rating
MBASEGEN
(MVA)
Reactive power consumption over
QN
range of asynchronous machine output
Asynchronous machine and gearbox
inertia constant (excluding prime mover
Hgen
inertia)
NP
Number of poles
SLIP
Rated slip

XS
RM

XM

RR

XR

RRR

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units
kV

Data Category
D, R1

MVA

S, D, R1

Chart
(MVAr vs. MW)

D, R1, R2

MWs/MBASE

D, R1, R2

Text

S, D
S, D, R1

Value

Remarks

Value

Remarks

Design Data Sheet

Symbol
VTGEN

RS

Units

Stator resistance

% on MBASE
and VTGEN

(at normal or typical operating temperature specify


temperature)

(temperature in C)

Stator leakage reactance

unsaturated and

at VTGEN
Iron loss resistance, referred to the stator
Magnetizing reactance, referred to the
stator

unsaturated and

at VTGEN
Rotor resistance at rated slip, referred to
the stator
Rotor leakage reactance, referred to the
stator

unsaturated and

at VTGEN
Rotor resistance range, referred to the
stator

R0

Zero sequence resistance

X0

Zero sequence reactance

11/5/2014

% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN

S, D, R1, R2

S, D, R1
S, D, R1, R2
S, D, R1, R2

S, D, R1
S, D, R1, R2
D, R1, R2

S, D, R1
S, D, R1, R2
D, R1
D, R1
D, R1
250176768.xls.ms_office

Page 21 of 61

R2

Negative sequence resistance

X2

Negative sequence reactance

Vlr

Locked rotor voltage with open rotor


terminals
Magnetising curve (voltage versus
current)
Speed (slip) vs torque (power) curve(s)
These curves to show effect of variable
rotor resistance
Equivalent circuit noting location of
equivalent impedances

11/5/2014

% on MBASE
and VTGEN
% on MBASE
and VTGEN

D, R1
D, R1

D, R1

Chart

D, R1

Chart

D, R1

Chart

D, R1

250176768.xls.ms_office

Page 22 of 61

9.4
Symbol

9.4.1

Asynchronous Machine (doubly fed)


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Data Description
Nominal terminal voltage
Asynchronous machine nameplate rating
MBASE
(MVA)
GCD
Capability chart
Maximum lagging Reactive power at
Q+PMAX
PMAX
Maximum lagging Reactive power at
Q+PMIN
PMIN
Maximum leading Reactive power at
Q-PMAX
PMAX
Maximum leading Reactive power at
Q-PMIN
PMIN
Asynchronous machine and gearbox
inertia constant (excluding prime mover
Hgen
inertia)
NP
Number of poles
SLIP
Slip at PMAX

XS
RM

XM

RR

XR

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units
kV

Data Category
D, R1

MVA

S, D, R1

Graphical data

D, R1, R2

MVAr export

S, D, R2

MVAr export

S, D, R2

MVAr import

S, D, R2

MVAr import

S, D, R2

MWs/MBASE

D, R1, R2

Text

S, D
S, D, R1, R2

Value

Remarks

Value

Remarks

Design Data Sheet

Symbol
VTGEN

RS

Units

Stator resistance
Stator leakage reactance

unsaturated and

at VTGEN
Iron loss resistance, referred to the stator
Magnetizing reactance, referred to the
stator

unsaturated and

at VTGEN
Rotor resistance at rated slip, referred to
the stator
Rotor leakage reactance, referred to the
stator

unsaturated and

at VTGEN

11/5/2014

% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN

S, D, R1, R2
S, D, R1
S, D, R1, R2
S, D, R1, R2

S, D, R1
S, D, R1, R2
D, R1, R2

S, D, R1
S, D, R1, R2
250176768.xls.ms_office

Page 23 of 61

R0

Zero sequence resistance

X0

Zero sequence reactance

R2

Negative sequence resistance

X2

Negative sequence reactance

Vlr

Locked rotor voltage with open rotor


terminals
Magnetising curve (voltage versus
current)
Equivalent circuit noting location of
equivalent impedances

11/5/2014

% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN
% on MBASE
and VTGEN

D, R1
D, R1
D, R1
D, R1

D, R1

Chart

D, R1

Chart

D, R1

250176768.xls.ms_office

Page 24 of 61

9.5
Symbol

9.5.1
Symbol
MBASEGEN

Photovoltaic Cell Array


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units
MW

Data Category
S, D, R1

Text, Charts

Diagram

D, R1

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Nameplate rating of array
Description of technical characteristics
including (where relevant):

cell array configuration;

plant ratings;

cell or cell array I-V curve and


details of power point tracking (if
applicable)

output power characteristics or


capability diagram as a function of
insolation, cell array terminal voltage
and any other relevant parameters;

rate of change limits on power


controllers (e.g. solar power point
tracker, sun tracking control
systems );

performance under fault


conditions (e.g. for a fault at the
connection point and for more
remote faults, including the
performance of an fault ride-through
control systems ).
Details of plant and control systems in
functional block diagram form, in
accordance with Rule s5.2.4 (b),
including:

dc power control systems ;

if a converter is integral to the


array, active power and reactive
power control systems and voltage
control systems ;

fault ride-through control


systems (if applicable)

11/5/2014

250176768.xls.ms_office

Page 25 of 61

9.5.2
Symbol

Setting Data Sheet


Data Description
All functional block diagram parameters
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.) in accordance with
Rule s5.2.4 (b).

11/5/2014

Units

Data Category

Units to be
specified

D, R1, R2

250176768.xls.ms_office

Value

Remarks

Page 26 of 61

9.6
Symbol

9.6.1

Fuel Cell
Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

MW

S, D, R1

Text, Charts

Graphical

D, R1

Value

Remarks

Value

Remarks

Design Data Sheet

Symbol

Data Description
Fuel cell group (generating unit )
MBASEGEN
nameplate rating
Description of technical characteristics
including (where relevant):

cell array configuration;

plant ratings;

cell or cell array power


characteristics and details of power
controller;

output power capability diagram


as a function of fuel flow, cell array
terminal voltage , ambient
temperature and any other relevant
parameters;

rate of change limits on power


controllers;

performance under fault


conditions (e.g. for a fault at the
connection point and for more
remote faults, including the
performance of an fault ride-through
control systems ).
Functional block diagram descriptions, in
accordance with Rule s5.2.4 (b), of
control systems for:

dc power control systems ;

if a converter is integral to the


array, active power and reactive
power control systems and voltage
control systems ;

fault ride-through control


systems (if applicable)

9.6.2

Units

Setting Data Sheet

11/5/2014

250176768.xls.ms_office

Page 27 of 61

Symbol

Data Description
All functional block diagram parameters
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.), in accordance
with Rule s5.2.4 (b).

11/5/2014

Units

Data Category

Units to be
specified

D, R1, R2

250176768.xls.ms_office

Value

Remarks

Page 28 of 61

10.1
Symbol

10.1.1
Symbol
VCEIL
VFMIN

Synchronous Machine Excitation System


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

D, R1

D, R1

Rising V/s

D, R1

Falling V/s

D, R1

Text

D, R1

Diagram

D, R1

Functional block
diagram

S, D, R1

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Rotor voltage capable of being supplied
for 5s at rated voltage (VTGEN) and
rated speed
Minimum field voltage
Maximum rate of change of field voltage
Maximum rate of change of field voltage
Exciter description including type, ratings,
connection schematic, source of any
external supplies, etc.
If applicable, exciter saturation curve over
50%-120% of rated voltage.
Details of the excitation control system
described in functional block diagram
form showing:

voltage control systems (AVR );

power system stabiliser (PSS );

exciter;

reactive current or reactive


power compensation (if fitted)
(e.g. Load drop compensation/VAr sharing, also
referred to as line drop compensation or reactive
power droop);

11/5/2014

over-excitation limiter;
under-excitation limiter;
stator current limiter (if fitted);

250176768.xls.ms_office

Page 29 of 63


flux (V/f ) limiter (if fitted);

manual restrictive limiter (if


fitted); and

any other limiters that may


restrict excitation system operation.
Details of excitation control system
components failover (e.g. for multiple
AVR channels, or AVR to manual
control) or generator trip, describing
conditions that cause the failover or trip.

10.1.2
Symbol

Text

D, R1

Units
V/V

Data Category
D, R1

Setting Data Sheet


Data Description
DC gain of excitation control loop
Active power operating range of the
generating unit when the PSS is in
operation.
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, etc.) for:

voltage control systems (AVR );

power system stabiliser;

exciter;

reactive current or reactive


power compensation;

over-excitation limiter;

under-excitation limiter;

stator current limiter;

flux (V/f ) limiter; and

any other limiters that may


restrict excitation control system
operation.

11/5/2014

Value

Remarks

D, R1

D, R2
D, R2
D, R2
D, R2
D, R2
D, R2
D, R2
D, R2
D, R2

250176768.xls.ms_office

Page 30 of 63

10.2
Symbol

10.2.1
Symbol

Asynchronous P-Q (or P-V) Control systems


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Diagram

D, R1

Units

Data Category

Graphical data

D, R2

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Functional block diagram, in accordance
with Rule s5.2.4 (b), of active power ,
reactive power and voltage (e.g. P-Q or
P-V) control systems , showing:

active power control systems ;

reactive power control systems


(e.g. through direct reactive power
control or power factor control);

voltage control systems (e.g.


through direct reactive power control)

any limiters (e.g. over-voltage or


under-voltage limiters);

any stabilisation functions (e.g.


drive train damping).

10.2.2
Symbol
GCD

Setting Data Sheet


Data Description
Capability chart (as applied by P-Q or PV control system )
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

D, R1, R2

250176768.xls.ms_office

Page 31 of 61

10.3
Symbol

10.3.1
Symbol

10.3.2
Symbol

DC Current Regulator
Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Functional Block
Diagram/Text

D, R1, R2

Units

Data Category

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Details of control system including
functional block diagram, in accordance
with Rule s5.2.4 (b).

Setting Data Sheet


Data Description
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

D, R1, R2

250176768.xls.ms_office

Page 32 of 61

11.1
Symbol

11.1.1
Symbol

11.1.2
Symbol

Fault Ride-Through Control systems


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Text / Diagram

S, D, R1

Functional block
diagram

S, D, R1

Units

Data Category

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Details of the fault ride through control
system showing principles of operation,
trigger levels, etc.
Details of the fault ride through control
system described in functional block
diagram form, in accordance with Rule
s5.2.4 (b).

Setting Data Sheet


Data Description
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

D, R1, R2

250176768.xls.ms_office

Page 33 of 61

11.2
Symbol

11.2.1
Symbol

Other Generating unit control systems


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Text / Diagram

S, D, R1

Symbol

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Details of the control system showing
principles of operation, trigger levels, etc.

Details of the control system described in


Functional block
functional block diagram form, in
diagram
accordance with Rule s5.2.4 (b).
Details of how this controller interfaces
with other control systems or directly to
generating system plant (if applicable), or Text / Diagram
how this controller effects its control
action.

11.2.2

Value

S, D, R1

Setting Data Sheet


Data Description
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

Units

Data Category

D, R1, R2

250176768.xls.ms_office

Page 34 of 62

11.3
Symbol

11.3.1
Symbol

Generating System Control systems (coordinated control of generating system plant)


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Text / Diagram

S, D, R1

Data Description
Details of the control system showing
principles of operation, trigger levels, etc.

Details of how this controller interfaces


with other control systems or directly to
generating system plant (if applicable), or
how this controller effects its control
action.

Symbol

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet

Details of the control system described in


functional block diagram form, in
Functional block
accordance with Rule s5.2.4 (b).
diagram

11.3.2

Value

S, D, R1

Text / Diagram

Units

Data Category

Setting Data Sheet


Data Description
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

D, R1, R2

250176768.xls.ms_office

Page 35 of 62

12.1
Symbol

12.1.1

Steam turbine and turbine governor


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.
If this is the steam cycle part of a
combined cycle gas turbine, list the
generating unit (s) that forms the gas
cycle part of the generating system and
describe the power output relationship
between the cycles.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Text / Chart

Data Description
Units
Description of steam turbine
configuration (e.g. cross compound,
Text
single reheat)
Functional block diagram for turbine
governor and turbine model, in
Diagram
accordance with Rule s5.2.4 (b).
Power fractions and rated power(s) (whichever apply):
Symbol
Data Description
Units
Very high pressure turbine power fraction
Per-unit of PMAX
FVHP

FIP
FLP1
FLP2
PM1
PM2

Remarks

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet

Symbol

FHP

Value

High pressure turbine power fraction


Intermediate pressure turbine power
fraction
Low pressure turbine 1 power fraction
Low pressure turbine 2 power fraction
Rated mechanical power, shaft 1
Rated mechanical power, shaft 2
(if applicable)

Summated turbine inertias (excluding


HT1, HT2 electrical generator), as seen on each
generator shaft.
Turbine time constants (whichever apply) :
Symbol
Data Description
Steam chest time constant (control
TCH
valves to HP or VHP) Exhaust
Very high pressure turbine time constant
TVHP

Data Category
D

Data Category
D, R2

Per-unit of PMAX

D, R2

Per-unit of PMAX

D, R2

Per-unit of PMAX
Per-unit of PMAX

MW

D, R2
D, R2
D

MW

MWs/MBASE

D, R1, R2

Units

Data Category

(possible alternative to TCH)


11/5/2014

250176768.xls.ms_office

Page 36 of 60

THP
TRH1
TRH2
TCO
TLP1
TLP2

12.1.2

High pressure turbine


(possible alternative to TCH)

Boiler reheat #1 time constant


Boiler reheat #2 time constant
Crossover time constant (IP exhaust to
LP exhaust)
Low pressure turbine 1 time constant
(possible alternative to TCO)

Low pressure turbine 2 time constant


(possible alternative to TCO)

s
s

D
D

Units

Data Category

S, D, R1

D, R1

D, R1

MW/Hz

D, R2

MW/Hz

D, R2

MW

S, D, R2

Setting Data Sheet

Turbine governor
Symbol

Data Description
Maximum Droop

RMAX

(% change in frequency / per-unit change in generating


unit output)

RNORM

(% change in frequency / per-unit change in generating


unit output)

RMIN

(% change in frequency / per-unit change in generating


unit output)

Value

Remarks

Normal Droop
Minimum Droop
Sustained response to frequency change
Non-sustained response to frequency
change
PLR
Load Rejection Capability
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).
FDBMAX Maximum Frequency Dead band
FDBN
Normal Frequency Deadband
FDBMIN Minimum Frequency Deadband
PDB
MW Deadband
Governor/servomotor rate limits

raise MW output

lower MW output

11/5/2014

D, R1, R2

Hz
Hz
Hz
MW

D, R1
D, R1
D, R1
D, R1

MW/s
MW/s

D
D

250176768.xls.ms_office

Page 37 of 60

12.2
Symbol

Hydro turbine and turbine governor


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.
Description of hydro-turbine type (e.g.
Francis turbine, Pelton wheel, etc.)
Functional block diagram, in accordance
with Rule s5.2.4 (b), for turbine governor
and turbine model showing:

functional structure;

mathematical model details


within each block (gains, time
constants and non-linear elements);

input and output quantities for


each function block; and

units for functional block diagram


input and output quantities (if perunit, specify base).

12.2.1
Symbol
PM1
PTMAX
PTMIN
TW
TG
TP
TR

HT

12.2.2
Symbol
RMAX

Units

Data Category

Text

S, D,R1,R2

Text

R1, R2

Text

Diagram

Units
MW

Data Category
D, R2

MW

D, R2

s
s
s
s

D, R2
D, R2
D, R2
D, R2

MW/s
MW/s

D
D

MWs/MBASE

D, R1, R2

Units

Data Category

S, D, R1

D, R1

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Rated mechanical power
Power limits imposed by valve or gate
travel
Water starting time
Gate servomotor time constant
Pilot valve time constant
Dashpot time constant
Governor/gate rate limits

raise MW output

lower MW output
Turbine inertia (excluding electrical
generator)

Setting Data Sheet


Data Description
Maximum Droop
(% change in frequency / per-unit change in generating
unit output)

Normal Droop
RNORM
11/5/2014

250176768.xls.ms_office

Page 38 of 61

RNORM

(% change in frequency / per-unit change in generating


unit output)

RMIN

(% change in frequency / per-unit change in generating


unit output)

D, R1

D, R1

MW/Hz

D, R2

MW/Hz

D, R2

S, D, R2

MW

S, D, R2

Minimum Droop
Sustained response to frequency
change
Non-sustained response to frequency
change
Governor control system time
constant(s)
(specify)

PLR

Load Rejection Capability


All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).
FDBMAX Maximum Frequency Dead band
FDBN
Normal Frequency Deadband
FDBMIN Minimum Frequency Deadband
MW Deadband
PDB

11/5/2014

D, R1, R2

Hz
Hz
Hz
MW

D, R1
D, R1
D, R1
D, R1

250176768.xls.ms_office

Page 39 of 61

12.3
Symbol

12.3.1
Symbol
PM1
KFC

Gas turbine and turbine governor


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.
Description of gas turbine type (e.g.
combined cycle, open cycle, etc.)
Fuel capability (gas, distillate, other)
Functional block diagram for turbine
governor and turbine model, in
accordance with Rule s5.2.4 (b),
showing:

functional structure;

mathematical model details


within each block (gains, time
constants and non-linear elements);

input and output quantities for


each function block; and

units for functional block diagram


input and output quantities (if per-unit,
specify base).
Details of the temperature control system
and its impact on sustainable generating
unit output (e.g. characteristic of output
power versus frequency ).

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Text

Text

Diagram

Diagram

Data Description
Rated mechanical power
Fuel control system gain

Units
MW

Data Category
D, R2

(per unit valve position / per unit governor output)

pu/pu

D, R2

s
s
s

D, R2
D, R2
D, R2

pu/pu

D, R2

Value

Remarks

Value

Remarks

Design Data Sheet

(specify per unit bases)

TFC
TVP
TFS

Fuel control system time delay


Valve positioner time constant
Fuel system time constant
Valve positioner forward gain

KVP
11/5/2014

250176768.xls.ms_office

Page 40 of 64

KVP

(per unit fuel flow / per unit valve position)

pu/pu

D, R2

pu/pu

D, R2

pu

D, R2

pu/s

D, R2

D, R2

D, R2

Graph

D, R2

MWs/MBASE

D, R1, R2

Units

Data Category

S, D, R1

D, R1

D, R1

MW/Hz

D, R2

MW/Hz

D, R2

S, D, R2

(specify per unit bases)

Valve positioner feedback gain


KVPF

(per unit valve position / per unit fuel flow)


(specify per unit bases)

VPMAX
VPMIN

Valve positioner range limits


(maximum and minimum)
(specify per unit bases)

VPMAXR Valve positioner rate or change limits


VPMAXL (maximum raise and lower rates)
(specify per unit bases)

TC
TCD

Combustor time delay


Gas turbine output time constant
(compressor discharge time constant)

max:
min:
p.u. base:
max raise rate:
max lower rate:
p.u. base:

Output power characteristic / torque function


(per unit output power versus per unit fuel flow and
speed, excluding limiting effects of temperature
controller)
(specify per unit bases)

HT

12.3.2
Symbol

Turbine and compressor inertia


(excluding electrical generator), as
measured on generator shaft.

Setting Data Sheet


Data Description
Maximum Droop

RMAX

(% change in frequency / per-unit change in generating


unit output)

RNORM

(% change in frequency / per-unit change in generating


unit output)

RMIN

(% change in frequency / per-unit change in generating


unit output)

Value

Remarks

Normal Droop
Minimum Droop
Sustained response to frequency change
Non-sustained response to frequency
change
Governor control system time constant(s)
(specify)

11/5/2014

250176768.xls.ms_office

Page 41 of 64

Load Rejection Capability


All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).
FDBMAX Maximum Frequency Dead band
FDBN
Normal Frequency Deadband
FDBMIN Minimum Frequency Deadband
MW Deadband
PDB

11/5/2014

MW

S, D, R2

D, R1, R2

Hz
Hz
Hz
MW

D, R1
D, R1
D, R1
D, R1

250176768.xls.ms_office

Page 42 of 64

12.4
Symbol

12.4.1
Symbol
UCI
UFP
UCO

Wind turbine aerodynamic model and blade pitch controller model


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.
Description of wind turbine type (e.g.
active stall, passive stall, pitch controlled,
etc.)
Functional block diagram for pitch
controller and turbine model, in
accordance with Rule s5.2.4 (b),
showing:

functional structure;

mathematical model details


within each block (gains, time
constants and non-linear elements);

input and output quantities for


each function block; and

units for functional block diagram


input and output quantities (if perunit, specify base).

Data Description
Cut-in wind speed
Wind speed at which full power is
attained
Cut-out wind speed
Efficiency (Cp) curves

Pitch control:
Symbol
Data Description
Power curve
(turbine output power versus wind speed characteristic)

BETA_REST

Data Category

Text

S, D, R1, R2

Text

R1, R2

Text

D. R1

Diagram

D, R1

Units
m/s

Data Category
D, R1, R2

m/s

D, R1, R2

m/s

D, R1

Data / Equations

D, R1

Units

Data Category

Diagram

D, R1, R2

Degrees

D, R1

Degrees

D, R1

Diagram

D, R1

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet

(efficiency versus tip speed ratio and blade pitch angle)

BETA_MAX
BETA_MIN

Units

Blade pitch limits


Blade resting pitch angle
(pitch angle below rated power, if not BETA_MIN)

Pitch controller setpoint characteristic


(e.g. generator speed setpoint versus generator output
power)

Blade pitch rate limits:


11/5/2014

250176768.xls.ms_office

Page 43 of 61

RMAX
RMIN
TP
HT

12.4.2
Symbol

increase angle

decrease angle
Blade pitch controller
servomotor/actuator time constant
Turbine and blade inertia (excluding
electrical generator), as measured on
generator shaft.

Degrees / s
Degrees / s

D, R1
D, R1

D, R1

MWs/MBASE

D, R1, R2

Units

Data Category

Setting Data Sheet


Data Description
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

Value

Remarks

D, R1

250176768.xls.ms_office

Page 44 of 61

12.5
Symbol

12.5.1
Symbol
PM1

Diesel and Gas Reciprocating Engine


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units
Text
MW

Data Category
D
D, R2

Data Description
Description engine type
Rated mechanical power
Actuator functional block diagram

ACMAXL
TD

Actuator range limits


(maximum and minimum)

Actuator rate of change limit (raise)


(specify per unit base)

Actuator rate of change limit (lower)


(specify per unit base)

Engine combustion time delay (dead


time)
Output power characteristic
(per unit output power versus per unit actuator position
and speed)
(specify per unit bases)

HT

12.5.2
Symbol

Value

Remarks

Value

Remarks

D, R2
pu

D, R2

pu/s (raise)

D, R2

pu/s (lower)

D, R2

D, R2

Graph

D, R2

MWs/MBASE

D, R1, R2

Diagram

Units

Data Category

(specify per unit bases)

ACMAXR

Remarks

Design Data Sheet

(including gains, time constants and locations of range


and rate limits)

ACMAX
ACMIN

Value

Engine rotating inertia (excluding


electrical generator), as measured on
generator shaft.
Functional block diagram for governor
controller and engine model, in
accordance with Rule s5.2.4 (b).

max:
min:
p.u. base:
raise:
p.u. base:
lower:
p.u. base:

Setting Data Sheet


Data Description
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

D, R1, R2

250176768.xls.ms_office

Page 45 of 60

13
Symbol

13.1.1
Symbol

Secondary Mechanical Control systems


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.
Description of controller type (e.g. overspeed controller, etc.) and a description
of its purpose.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Text

Units

Data Category

Text / Diagram

S, D, R1

Symbol

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Details of the control system showing
principles of operation, trigger levels, etc.

Details of the control system described in


Functional block
functional block diagram form, in
diagram
accordance with Rule s5.2.4 (b).
Details of how this controller interfaces
with the primary mechanical control
Text / Diagram
systems (if applicable), or how this
controller effects its control action.

13.1.2

Value

S, D, R1

Setting Data Sheet


Data Description
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

Units

Data Category

D, R1, R2

250176768.xls.ms_office

Page 46 of 62

14.1
Symbol

14.1.1
Symbol

T
N

Shaft Model / Subsynchronous Resonance Frequencies


Data Description
The list of generating units to which this
information applies.

Units

Data Category

Text

S, D, R1, R2

Units

Data Category

Diagram

D, R1

Hz
Nepers/s
Nm
Text

D, R1
D, R1
D, R1
D, R1

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Dynamic model of turbine/ generator
shaft system in lumped element form
showing:
component inertia,
damping,
shaft stiffness and
any gearbox or shaft driven
rotating exciter.
Proposed minimum model to be provided
for each turbine type (steam, wind turbine
generator, hydro or gas)
Natural damping of shaft torsional
oscillation modes (for each mode):
- Modal frequency
- Logarithmic decrement
Shaft torque on low speed shaft
Gear ratio

11/5/2014

250176768.xls.ms_office

Page 47 of 61

15.1
Symbol

15.1.1
Symbol
VNOM
NSTEPS
XC
NL
XL
NR
RR

15.1.2
Symbol

Mechanically or electronically switched capacitor , reactor or resistor


Data Description
The list of units to which this information
applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units
kV

Ohm

Data Category
D
D, R1
D, R1
D, R1
D, R1
D, R1
D, R1

Text / Diagram

S, D, R1

Diagram

S, D

Functional block
diagram

S, D, R1

Text / Diagram

Units

Data Category

Text

D, R1, R2

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Nominal voltage
Number of capacitor steps
Capacitive reactance per step
Number of reactor steps
Inductive reactance per step
Number of resistor steps
Resistance per step
Details of the control system showing
principles of operation, trigger levels,
switching times, discharge times, etc.
3 phase electrical connection diagram,
including earthing arrangements
Details of the control system described
in functional block diagram form, in
accordance with Rule s5.2.4 (b).
Details of how this controller interfaces
with the primary electrical or mechanical
control systems (if applicable), or how
this controller effects its control action.

MVAr at VNOM
MVAr at VNOM

Setting Data Sheet


Data Description
Number of steps normally on at PMAX
and PMIN
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

D, R1, R2

250176768.xls.ms_office

Page 48 of 60

15.2
Symbol

15.2.1

Static VAR Compensator, Thyristor Controlled (SVC)


Data Description
The list of units to which this information
applies.
Manufacturer and manufacturers type
designation or product name.

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units
MVA
kV

Data Category
S, D, R1
S, D

Chart

S, D, R1

% on BASE and
VNOM

D,R1

% on BASE and
VNOM

D,R1

Functional Block
Diagram/Text

D,R1

Value

Remarks

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet

Symbol
BASE
VNOM

Data Description
Nameplate rating
Rated voltage
Capability diagram (reactive power
SCD
versus voltage )
Capacitor reactance (thyristor switched
XC
capacitor)
SVC inductor
reactance (thyristor
controlled reactor)
XL
(If a different configuration is used,
please describe)
Details of the control system described
in functional block diagram form, in
accordance with Rule s5.2.4 (b).
Transformer data:
Symbol
Data Description
GTW
Number of windings
GTVG
Vector group
GTRn
Rated MVA of each winding
GTTRn Principal tap rated voltage s
Positive sequence impedance of each
GTZ1n
winding
Negative sequence impedance of each
GTZ2n
winding
Zero sequence impedance of each
GTZOn
winding
Earthing arrangement
Saturation curve
Tap changer type, on/off load
Tapped winding
GTAPR Tap change range
GTAPS Tap change step size

15.2.2

Units

Units
Text
MVA
kV/kV
(a + jb) % on 100
MVA base
(a + jb) % on 100
MVA base
(a + jb) % on 100
MVA base
Text, diagram
Diagram
On/Off
Text, Diagram
kV kV
%

Data Category
S, D
S, D
S, D, R1
S, D, R1
S, D, R1
S, D, R1
S, D, R1
S, D
R1
D
S, D, R1
S, D
D

Setting Data Sheet

Symbol
11/5/2014

Data Description

Units

Data Category
250176768.xls.ms_office

Page 49 of 61

All functional block diagram parameters,


in accordance with Rule s5.2.4 (b),
Functional block
(gains, time constants, mathematical
diagram
functions, non-linear characteristics,
limits, set-points, etc.).
Transformer data:
OLTC details of control loop described in
block diagram form, in accordance with
Rule s5.2.4 (b), showing transfer
Diagram
functions of individual elements and
measurement units.
VREFMAX Upper voltage reference
V
VREFMIN Lower voltage reference
V
Tap change voltage setting range and
GTAPV
kV kV
setpoint (if any)
GTAPD Tap change voltage deadband
kV
Tap change high and low voltage
GTAPVL interlocks (monitoring non-tapped side
kV, kV
voltage or other control signal (specify))
GTAPT Tap change cycle time(s)
s, Text

11/5/2014

D, R1, R2

D, R2

D, R2
D, R2
D, R2
D, R2
D, R2
D, R2

250176768.xls.ms_office

Page 50 of 61

15.3
Symbol

15.3.1
Symbol
BASE
VNOM
SCD

ICMAX

ILMAX

Voltage Source Converter or Current Source Converter, self commutated, or similar (VSC, CSC, Statcon or
Statcom)
Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units
MVA
kV

Data Category
S, D, R1
S, D

Chart

S, D, R1

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Nameplate rating
Rated voltage
Capability diagram (reactive
versus voltage )
Maximum capacitive current

power

% on BASE and
VNOM

(If the device has an overload rating, include the overload


(Diagram for any
rating and any time characteristics.)
overload rating with time
characteristics)

Maximum inductive current

% on BASE and
VNOM

S, D, R1

S, D, R1

Details of the control system described


in block diagram form, in accordance
with Rule s5.2.4 (b), showing transfer
functions of individual elements and Functional block
diagram / Text
measurement units.

D, R1, R2

(If the device has an overload rating, include the control


system characteristics to control this functionality)

Transformer data:
Symbol
Data Description
GTW
Number of windings
GTVG
Vector group
GTRn
Rated MVA of each winding
GTTRn Principal tap rated voltage s
GTZ1n

Positive sequence impedance of each


winding

GTZ2n

Negative sequence impedance of each


winding

GTZOn

Zero sequence impedance of each


winding
Earthing arrangement

11/5/2014

Units
Text
MVA
kV/kV
(a + jb) % on 100
MVA base and
VNOM
(a + jb) % on 100
MVA base and
VNOM
(a + jb) % on 100
MVA base and
VNOM
Text, diagram

Data Category
S, D
S, D
S, D, R1
S, D, R1
S, D, R1

S, D, R1

S, D, R1
S, D

250176768.xls.ms_office

Page 51 of 61

GTAPR
GTAPS

15.3.2

Saturation curve
Tap changer type, on/off load
Tapped winding
Tap change range
Tap change step size

Diagram
On/Off
Text, diagram
kV kV
%

R1
D
S, D, R1
S, D
D

Setting Data Sheet

Symbol

Data Description
Units
Data Category
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
Functional block
(gains, time constants, mathematical
D, R1, R2
diagram
functions, non-linear characteristics,
limits, set-points, etc.).
Transformer data:
OLTC details of control loop described in
block diagram form, in accordance with
Rule s5.2.4 (b), showing transfer
Diagram
D, R2
functions of individual elements and
measurement units.
VREFMAX Upper voltage reference
kV
D, R2
VREFMIN Lower voltage reference
kV
D, R2
Tap change voltage setting range and
GTAPV
kV kV
D, R2
setpoint (if any)
GTAPD Tap change voltage deadband
kV
D, R2
Tap change high and low voltage
GTAPVL interlocks (monitoring non-tapped side
kV, kV
D, R2
voltage or other control signal (specify))
GTAPT Tap change cycle time(s)
s, Text
D, R2

11/5/2014

250176768.xls.ms_office

Value

Remarks

Page 52 of 61

15.4
Symbol

15.4.1
Symbol
BASE
VNOM
H
SCD

Flywheel
Data Description
The list of units to which this information
applies.
Manufacturer and manufacturers type
designation or product name.

Symbol

Data Category

Text

S, D,R1,R2

Text

R1, R2

Units
MVA
kV

Data Category
S, D, R1
S, D

MWs/BASE

Chart

S, D, R1

Text / Diagram

S, D, R1

Functional block
diagram

S, D, R1

Text / Diagram

Units

Data Category

Functional block
diagram

D, R1, R2

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Nameplate rating
Rated voltage
Stored energy in flywheel inertia
(normal or rated value)

Capability diagram
(active power versus voltage and speed)

Description of the control system


showing principles of operation, trigger
levels, switching times, etc., and
conditions for discharging active power
to the power system .
Details of the control system in
functional block diagram form, in
accordance with Rule s5.2.4 (b).
Details of how this controller interfaces
with the primary electrical or mechanical
control systems (if applicable), or how
this controller effects its control action.

15.4.2

Units

Setting Data Sheet


Data Description
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

250176768.xls.ms_office

Page 53 of 61

15.5
Symbol

15.5.1
Symbol
BASE
VNOM
EMAX
SCD

Storage Battery
Data Description
The list of units to which this information
applies.
Manufacturer and manufacturers type
designation or product name.

Symbol

Data Category

Text

S, D,R1,R2

Text

R1, R2

Units
MVA
kV
MWh

Data Category
S, D, R1
S, D
D, R1, R2

Chart

S, D, R1

Text / Diagram

S, D, R1

Functional block
diagram

S, D, R1

Text / Diagram

Units

Data Category

Functional block
diagram

D, R1, R2

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Nameplate rating
Rated voltage
Nominal capacity
Capability diagram
(e.g. active power versus voltage )

Description of the control system


showing principles of operation, trigger
levels, switching times, etc., and
conditions for discharging active power
to the power system .
Details of the control system in
functional block diagram form, in
accordance with Rule s5.2.4 (b).
Details of how this controller interfaces
with the primary electrical or mechanical
control systems (if applicable), or how
this controller effects its control action.

15.5.2

Units

Setting Data Sheet


Data Description
All functional block diagram parameters,
in accordance with Rule s5.2.4 (b),
(gains, time constants, mathematical
functions, non-linear characteristics,
limits, set-points, etc.).

11/5/2014

250176768.xls.ms_office

Page 54 of 61

16.1
Symbol

16.1.1
Symbol

16.1.2
Symbol

Synchronous machine protection systems (backups for excitation limiters)


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Text / Diagram

S, D, R1

Text / Diagram

Units

Data Category
D

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Details of the protection system showing
principles of operation, trigger levels,
switching times, etc.
Details of how this protection system
effects its protection action (e.g. trips the
generating unit at the generating unit
circuit breaker, turbine trip, etc.).

Setting Data Sheet


Data Description
Protection trigger levels and timings.

11/5/2014

250176768.xls.ms_office

Page 55 of 62

16.2
Symbol

16.2.1
Symbol

16.2.2
Symbol

Asynchronous machine protection systems (for generating unit instability)


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Text / Diagram

S, D, R1

Text / Diagram

Units

Data Category
D

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Details of the protection system showing
principles of operation, trigger levels,
switching times, etc.
Details of how this protection system
effects its protection action (e.g. trips the
generating unit at the generating unit
circuit breaker, etc.).

Setting Data Sheet


Data Description
Protection trigger levels and timings.

11/5/2014

250176768.xls.ms_office

Page 56 of 61

16.3

Crowbar protection systems

Symbol

Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

16.3.1
Symbol

16.3.2
Symbol

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Text / Diagram

S, D, R1

Text / Diagram

Units

Data Category
D

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Details of the protection system showing
principles of operation, trigger levels,
switching times, etc., and conditions for
discharging active power to the power
system.
Details of how this protection system
interfaces to the primary plant or control
systems and effects its protection action
(e.g. applies resistor or short circuits
induction generator rotor inputs or
converter capacitor, etc.).

Setting Data Sheet


Data Description
Protection trigger levels and timings.
Resistance of applied crowbar (if on an
asynchronous machine, referred to the
stator, if possible)

11/5/2014

% of MBASE and
VTGEN

250176768.xls.ms_office

Page 57 of 61

16.4
Symbol

16.4.1
Symbol

16.4.2
Symbol

Other protection systems


Data Description
The list of generating units to which this
information applies.
Manufacturer and manufacturers type
designation or product name.

Units

Data Category

Text

S, D, R1, R2

Text

R1, R2

Units

Data Category

Text / Diagram

S, D, R1

Text / Diagram

Units

Data Category
D

Value

Remarks

Value

Remarks

Value

Remarks

Design Data Sheet


Data Description
Details of the protection system showing
principles of operation, trigger levels,
switching times, etc., and conditions for
discharging active power to the power
system.
Details of how this protection system
effects its protection action (e.g. trips the
generating unit at the generating unit
circuit breaker, turbine trip, etc.).

Setting Data Sheet


Data Description
Protection trigger levels and timings.

11/5/2014

250176768.xls.ms_office

Page 58 of 62