Doctor/Nurse Calling System


Application :
In any Hospital it is essential to facilitate Patients to
call the Duty Doctor/Staff Nurse/House-Keepers for
attention /assistance during emergencies.
It is desirous that the Doctor/Nurse Calling System
be Fool-Proof & attention to Patients is 100%

Technical Specifications
Operate Volts
Choice of
Windows per
DCU

85 to 275 V AC or DC
Min :
Max :

08 Windows per DCU


Any No. of Windows per DCU

Individual
Window Size

70mm x 35mm

Doctor/Nurse Calling Unit [DCU] is usually mounted

Operate Temp

0 C to 70 C, Upto 95% RH

in a Centralised-Area, say ~ the Duty-Room of

Storage Temp

-10 C to 90 C, Upto 95% RH

Burden

2.5 Watts @ 230 VAC [Max]


per DCU Window

Choice of
Sequences of
Operation

[1]. Auto-RESET [AR-01]


[2]. Manual-RESET [MR-01 & MR-02]
[3]. Ringback [RBM-01]

Choice of
Switch Types

[1]. Regular ON/OFF [Toggle type]


[2]. Calling-Bell [Spring-Return type]

assured, beyond ambiguity.

Doctors/Nurses, in each floor of a Hospital.

DCU announces the Call from Patient by means of


Visual & Audible Alarms, to alert the Duty
Doctors/Nurses and to initiate remedial action.

For Visual Alarm, Rear-Illuminated Windows are


provided. Patients Room/Bed No. is inscribed on
Front-side of Window.

For Audible Alarm, in-built Buzzer is provided.

Description :

[Default size]

Refer : Sequences of Operation [overleaf]


for details of Recommended Switch types

Doctor/Nurse Calling Unit [DCU] consists of :

DEDEDE

1. Windows to indicate Patients Room / Bed No.


One Window for each Room/Bed is provided.
2. Push Buttons for ACCEPT, Lamp TEST & MUTE
3. Built-in Audible Alarm.
4. Each Room/Bed is provided with one Call-Switch
for use by the Patient
M e t h o d o f O p e r a t i o n : {Auto-RESET [AR-01]}

To call Doctor/Nurse, Patient has to Press the


Switch provided by his/her Bed-side.

Rear-Illuminated Window displaying Patients


Room/Bed No., starts Flashing & Audible Alarm

Ordering Information
Following Ordering Information to be specified by
User, beyond ambiguity, for Enquiry or Purchase Order
No. of Windows
per DCU
required
Sequence of
Operation
required

_____ No. of Windows / DCU


______________________
[specify any ONE from above THREE]

switches ON, thus alerting the Doctor/Nurse.


Doctor/Nurse should press ACCEPT Push Button

DEDEDE

to acknowledge Call from the Patient.


Flashing Window become Steady glow & Audible
Alarm switches OFF.
Doctor/Nurse should go to Patients Room/Bed,
attend to his/her needs and before returning
should switch OFF the Patients bed-side CallSwitch to RESET the Call from Patient.
As soon as Call-Switch is switched OFF, Steady
glow of Window on DCU is switched OFF, thereby

for further details, please contact :

Bharani Electronics
Door # 27, 46th Street, Ashok Nagar,
Chennai : 600 083. India.
Phone/Fax : [044] 2489 5421 / 2489 1226
E-Mail : bharani_electronics@vsnl.net

completing the episode.


Product improvement is a continuous feature.
Specifications / Design listed in this Publication are therefore subject to revision, without notice.

Choice of Sequences of Operation


Sequence Designation

Auto-RESET

AR-01

Line
No

Initiating
Contact

Push
Button
Pressed

Normal

--

OFF

OFF

--

Abnormal

--

Flash

ON

Lock-in

Abnormal

ACCEPT

Steady

OFF

-Auto-RESET
acted

Visual
Alarm

Audible
Alarm

Remarks

Normal

--

OFF

OFF

Normal before
ACCEPT

--

Flash

ON

Lock-in

OFF

Auto-RESET
acted

Normal

RESET

Regular ON/OFF

Recommended Switch type

Manual-RESET

OFF

[Toggle type]

ONLY

Sequence Designation

Sequence Designation

MR-01

MR-02

Line
No

Initiating
Contact

Push
Button
Pressed

Normal

--

OFF

OFF

--

OFF

OFF

--

Abnormal

--

Flash

ON

Lock-in

Flash

ON

Lock-in

Abnormal [or]
Normal

ACCEPT

Steady

OFF

Steady

OFF

Manual RESET
required

4A

Abnormal

RESET

Flash

ON

Manual RESET
required
To Line 2,
ACCEPT reqd
Manual RESET
acted

Steady

OFF

To Line 3

OFF

Manual RESET
acted

4B

Normal

RESET

Visual
Alarm

Audible
Alarm

Remarks

Visual
Alarm

Audible
Alarm

Remarks

OFF

Recommended Switch type

OFF

OFF

[1]. Regular ON/OFF [Toggle type] or


[2]. Calling-Bell [Spring-Return type]

Sequence Designation

Ringback

RBM-01

Line
No

Initiating
Contact

Push Button
Pressed

Visual
Alarm

Audible
Alarm

Ringback
Audible Device

Normal

--

OFF

OFF

OFF

Abnormal

--

Fast Flash

ON

OFF

Abnormal

ACCEPT

Steady

OFF

OFF

Normal

--

Slow Flash

OFF

ON

Abnormal

--

<<<<<

To Line 2

>>>>>

Normal

RESET

OFF

OFF

OFF

Normal before ACCEPT

--

Fast Flash

ON

OFF

Normal

ACCEPT

Slow Flash

OFF

ON

Abnormal

--

<<<<<

To Line 2

>>>>>

10

Normal

RESET

OFF

OFF

OFF

11

Normal

TEST

Slow Flash

OFF

ON

Recommended Switch type

[1]. Regular ON/OFF [Toggle type] or


[2]. Calling-Bell [Spring-Return type]

You might also like