Modbus communication
Presentation
General
Modbus communication enables Sepam to be connected to a remote monitoring
and control system equipped with a master Modbus communication channel and a
physical link of the RS 485 type, or another interface equipped with an appropriate
converter.
The Modbus protocol used by Sepam is a compatible sub-group of the RTU
Modbus (1) protocol (a Modbus master can communicate with several Sepam units).
Sepam is always a slave station.
All the Sepam units can be equipped with the ACE949-2 (2-wire) or ACE959 (4-wire)
interface for connection to the communication network.
Refer to document PCRED399074EN "RS 485 network connection guide" regarding
network implementation.
Data available
The data available depend on the type of Sepam.
Measurement readout
phase and earth fault currents
peak demand phase currents
tripping currents
cumulative breaking current
phase-to-phase, phase-to-neutral and residual voltages
active, reactive and apparent power
active and reactive energy
frequency
temperatures
thermal capacity used
starts per hour and inhibit time
running hours counter
motor starting current and time
operating time before overload tripping
waiting time after tripping
operating time and number of operations
circuit breaker charging time.
Program logic data readout
a table of 144 pre-assigned remote indications (TS) (depends on the type of
Sepam) enables the readout of program logic data status
readout of the status of 10 logic inputs.
Remote control orders
Writing of 16 impulse-type remote control orders (TC) in either direct mode or SBO
(Select Before Operate) mode via 16 selection bits.
Other functions
reading of Sepam configuration and identification
time-tagging of events (synchronization via the network or externally via logic input
I21), time-tagging within a ms
remote reading of Sepam settings
remote setting of protection units
remote control of the analog output (2)
transfer of disturbance recording data.
Supervision zone
This zone includes all the data used by the remote monitoring and control system,
accessible in a single reading operation.
(1) Modbus is a Modicon registered trademark.
(2) with MSA141 option.
5/2
Schneider Electric
Modbus protocol
Modbus communication
Characterization of exchanges
master
MT10248
request
MERLIN GERIN
MERLIN GERIN
MERLIN GERIN
slave
slave
slave
Exchanges are initiated by the master and include a request by the master and a
reply by the slave (Sepam). Requests by the master are either addressed to a given
Sepam identified by its number in the first byte of the request frame, or addressed to
all the Sepam (broadcasting).
master
MT10244
broadcasting
MERLIN GERIN
MERLIN GERIN
MERLIN GERIN
slave
slave
slave
MT10249
request
reply
MERLIN GERIN
master
slave
It is not necessary to have a detailed knowledge of the protocol unless the master is
a central computer which requires the corresponding programming. All Modbus
exchanges include 2 messages: a request by the master and a reply by the Sepam.
All the frames that are exchanged have the same structure. Each message or frame
contains 4 types of data:
slave
number
function
code
data
zones
CRC 16
check zone
Schneider Electric
5/3
Modbus communication
Implementation
Asynchronous serial
Protocol
Rate
Data format
Response time
Less than 15 ms
25
question
broadcasting
reply
Tr 15 ms
Tr 15 ms
Response time
question
The communication coupler response time (Tr) is less than 15 ms, including a
3-character silence (approximately 3 ms at 9600 bauds).
This time is given with the following parameters:
9600 bauds
format: 8 bits, odd parity, 1 stop bit.
Factory setting
Transmission rate,
adjustable from 4800 to 38400 bauds
Slave number assigned to Sepam
adjustable from 1 to 255
Parity: even parity, odd parity, no parity
9600 bauds
Even parity
Direct
N 001
The Modbus slave number should be assigned before Sepam is connected to the
communication network (all Sepams have a slave number that is factory-set to 1).
Set the communication parameters before connecting Sepam to the communication
network.
The communication parameters may be changed while Sepam is operating without
disturbing operation. Sepam ignores the first frame received after it is energized or
after the communication parameters are changed via SFT2841.
"Activity on the line" indicator:
The green indicator on the ACE949-2 or ACE959 accessory is activated by variations
of the electrical signal on the RS 485 network. When the master communicates with
Sepam (sending or receiving), the green indicator flashes.
5/4
Schneider Electric
Modbus communication
Implementation
after wiring, check the indications given by the green "activity on the line" indicator
carry out read and write cycles using the test zone and the Modbus echo mode
use the SFT2819 software to read and write the test zone.
Test zone
Read
Send
Receive
Write
Send
Receive
The Modbus frames opposite, sent by or received by a remote monitoring and control
system, are data used for test purposes when the communication link is first
implemented.
The CRC received by Sepam is recalculated, making it possible to test the
calculation of the CRC sent by the master:
if the CRC received is correct, Sepam replies
if the CRC received is incorrect, Sepam does not reply.
Read
Send
Receive
Receive
Diagnosis counters
The diagnosis counters managed by Sepam are:
CPT1, first word: number of correct frames received, whether or not the slave is
concerned
CPT2, second word: number of frames received with CRC error, or frames
received with more than 255 bytes and not interpreted, or frames received with at
least one character that has a parity error, overrun, framing, break on the line.
An incorrect rate causes incrementation of CPT2
CPT3, third word: number of exception replies generated (even if not sent, as a
result of a broadcast request)
CPT4, fourth word: number of frames specifically addressed to the station
(excluding broadcasting)
CPT5, fifth word: number of broadcast frames received with no errors
CPT6, sixth word: not significant
CPT7, seventh word: number of Sepam not ready replies generated
CPT8, eighth word: number of frames received with at least one character that has
a parity error, overrun, framing, break on the line
CPT9, ninth word: number of correct requests received and correctly executed.
The CPT2 and CPT9 counters may be viewed with SFT2841 (Sepam diagnosis
screen).
The counters may be accessed via the dedicated reading function (Modbus protocol
function 11).
When the value of a counter is equal to FFFFh (65535), it automatically switches to
0000h (0). After an auxiliary supply outage the diagnosis counters are initialized to
zero.
Malfunctions
it is advisable to connect the Sepam to the RS 485 network one by one
the display of the CPT2 and CPT9 diagnosis counters with SFT2841 ("Sepam
diagnosis" screen) makes it possible to check Modbus exchanges
check the slave number, rate and format using SFT2841 or the Sepam UMI.
Make sure that the master is sending frames to the Sepam concerned by checking
the activity on the RS 232 - RS 485 converter, if there is one, and on the ACE949-2
or ACE959 module.
check the wiring on each ACE949-2 or ACE959 module
check the tightening of the screw-type terminals on each module
check the connection of the CCA612 cord linking the ACE949-2 or ACE959
module to the Sepam unit (marked )
check that polarization is only at one point and that impedance matching is at the
ends of the RS 485 network
check that the cable being used is the recommended one
check that the ACE909-2 or ACE919 converter is connected and set up correctly.
Schneider Electric
5/5
Modbus communication
Presentation
Data which are similar from the monitoring and control application viewpoint are
grouped together in adjacent address zones:
Hexadecimal
starting
address
0002
0006
0005
000F
3, 16
3
0040
0041
0040
0060
3, 6, 16
3
0070
0071
0070
0090
3, 6, 16
3
00F0
00F0
00F1
00F1
Status
0100
0112
Measurements
Diagnosis
Tripping context
Switchgear diagnosis
Application
Test zone
0113
0159
0250
0290
02CC
0C00
0158
0185
0275
02A5
02FE
0C0F
3, 4, 6, 16
1, 2, 5, 15*
3, 4, 6, 16
1, 2, 5, 15*
3, 4
1, 2*
3, 4
3, 4
3, 4
3, 4
3
3, 4, 6, 16
1, 2, 5, 15
1E00
1E80
1F00
2000
2080
2100
1E7C
1E80
1F7C
207C
2080
217C
3
3, 6, 16
3, 6
3
3, 6, 16
3, 16
2200
2204
2300
2301
2203
2271
2300
237C
3, 16
3
3, 6, 16
3
Synchronization zone
Identification zone
Event table 1
Exchange word
Events (1 to 4)
Event table 2
Exchange word
Events (1 to 4)
Data
Remote control orders
Protection settings
Read zone 1
Read request zone 1
Remote settings zone 1
Read zone 2
Read request zone 2
Remote settings zone 2
Disturbance recording
Choice of transfer function
Identification zone
Disturb. rec. exchange word
Disturbance recording data
Ending
address
Modbus functions
enabled
N.B. Non-addressable zones may reply by an exception message or else supply nonsignificant data.
(*) these zones may be accessed in word mode or bit mode.
The address of bit i (0 $ i $ F) of address word J is then (J x 16) + i.
Example: 0C00 bit 0 = C000 0C00 bit 7 = C007.
5/6
Schneider Electric
Modbus communication
Synchronization zone
The synchronization zone is a table which contains the absolute date and time for
the time-tagging function. Time messages should be written in a single block
containing 4 words, using function 16: write word.
Messages can be read word by word or by groups of words using function 3.
Synchronization zone
Word address
Access
Modbus function
enabled
3, 16
3
3
3
Read/write
Read
Read
Read
Identification zone
The identification zone contains system-type information pertaining to the
identification of the Sepam equipment.
Some of the information in the identification zone is also found in the configuration
zone at the address 02CCh.
Identification zone
Manufacturer identification
Equipment identification
Marking + equipment type
Communication version
Application version
Sepam check-word
Extension word
Command
Extension zone address
Word address
0006
0007
0008
0009
000A/B
000C
000D
000E
000F
Access
Modbus function
enabled
R
3
R
3
R
3
R
3
R
3
R
3
R
3
R/W
3/16
R
3
(1) MSB word 2: major index
LSB word 2: minor index.
Format
Value
Not managed
0100
0
Idem 02E2
0
(1)
Not managed
Not managed
Idem 0100
0
Init. to 0
02CC
Events 1 zone
The event zone is a table which contains a maximum of 4 time-tagged events. Events
should be read in a single block containing 33 words using function 3.
The exchange word can be written using functions 6 or 16, and read individually using
function 3.
Events 1 zone
Word address
Access
Exchange word
0040
Event n1
0041-0048
Event n2
0049-0050
Event n3
0051-0058
Event n4
0059-0060
See "time-tagging of events" chapter for data format.
Read/write
Read
Read
Read
Read
Modbus function
enabled
3, 6, 16
3
3
3
3
Events 2 zone
The event zone is a table which contains a maximum of 4 time-tagged events.
Events should be read in a single block containing 33 words using function 3.
The exchange word can be written using functions 6 or 16 and read individually using
function 3.
Events 2 zone
Word address
Exchange word
0070
Event n1
0071-0078
Event n2
0079-0080
Event n3
0081-0088
Event n4
0089-0090
See "time-tagging of events" chapter for data format.
Schneider Electric
Access
Read/write
Read
Read
Read
Read
Modbus function
enabled
3, 6, 16
3
3
3
3
5/7
Modbus communication
Word address
00F0
Bit address
0F00
Access
R/W
STC1-STC16
00F1
0F10
R/W
Function
3/4/6/16
1/2/5/15
3/4/6/16
1/2/5/15
Format
B
B
Status zone
The status zone is a table which contains the Sepam check-word, pre-assigned
remote annunciation bits (TS), logic inputs, logic outputs, LEDs and analog output.
Status
Word address
Bit address
Access
R
R
R
R
R
R
R
R
R
R
R
Modbus function
enabled
3/4 or 1, 2, 7
3/4 or 1, 2
3/4 or 1, 2
3/4 or 1, 2
3/4 or 1, 2
3/4 or 1, 2
3/4 or 1, 2
3/4 or 1, 2
3/4 or 1, 2
3/4 or 1, 2
_
Format
Sepam check-word
TS1-TS16
TS17-TS32
TS33-TS48
TS49-TS64 (reserved)
TS65-TS80
TS81-TS96
TS97-TS112
TS113-TS128
TS129-TS144
Reserved
100
101
102
103
104
105
106
107
108
109
10A
1000
1010
1020
1030
1040
1050
1060
1070
1080
1090
10A0
X
B
B
B
B
B
B
B
B
B
_
Logic inputs
Reserved
10B
10C
10B0
10C0
R
R
3/4 or 1, 2
_
B
_
Logic outputs
10D
10D0
3/4 or 1, 2
LEDs
10E
10E0
3/4 or 1, 2
Analog output
10F
10F0
R/W
3, 6, 16
16S
Format
Unit
Measurement zone
Measurements
Word address
Access
Phase current I1 (x 1)
0113
Modbus function
enabled
3, 4
16NS
0.1 A
Phase current I2 (x 1)
0114
3, 4
16NS
0.1 A
Phase current I3 (x 1)
0115
3, 4
16NS
0.1 A
0116
0117
R
R
3, 4
3, 4
16NS
16NS
0.1 A
0.1 A
0118
3, 4
16NS
0.1 A
0119
3, 4
16NS
0.1 A
011A
3, 4
16NS
0.1 A
011B
3, 4
16NS
0.1 A
011C
3, 4
16NS
0.1 A
011D
3, 4
16NS
0.1 A
011E
3, 4
16NS
1V
011F
3, 4
16NS
1V
0120
3, 4
16NS
1V
Phase-to-neutral voltage V1 (x 1)
0121
3, 4
16NS
1V
Phase-to-neutral voltage V2 (x 1)
0122
3, 4
16NS
1V
Phase-to-neutral voltage V3 (x 1)
0123
3, 4
16NS
1V
Residual voltage V0 (x 1)
0124
3, 4
16NS
1V
0125
3, 4
16NS
1V
0126
3, 4
16NS
1V
Frequency
0127
3, 4
16NS
0.01 Hz
Active power P (x 1)
0128
3, 4
16S
1 kW
Reactive power Q (x 1)
0129
3, 4
16S
1 kvar
Apparent power S (x 1)
012A
3, 4
16S
1 kVA
012B
3, 4
16S
1 kW
012C
3, 4
16S
1 kvar
012D
3, 4
16S
0.01
5/8
Schneider Electric
Modbus communication
Word address
Access
Format
Unit
Modbus function
enabled
3, 4
012E/012F
0130/0131
2 x 16NS
100 kW.h
3, 4
2 x 16NS
0132/0133
100 kW.h
3, 4
2 x 16NS
100 kvar.h
0134/0135
0136
3, 4
2 x 16NS
100 kvar.h
3, 4
16NS
0137
3, 4
16NS
1A
1A
0138
3, 4
16NS
1A
0139
3, 4
16NS
1A
013A
3, 4
16NS
1A
013B
3, 4
16NS
1A
013C
3, 4
16NS
1A
013D
3, 4
16NS
1A
013E
3, 4
16NS
1A
013F
3, 4
16NS
1A
0140
3, 4
16NS
1A
0141
3, 4
16NS
10 V
0142
0143
R
R
3, 4
3, 4
16NS
16NS
10 V
10 V
0144
3, 4
16NS
10 V
0145
3, 4
16NS
10 V
0146
3, 4
16NS
10 V
0147
3, 4
16NS
10 V
0148
3, 4
16NS
10 V
0149
3, 4
16NS
10 V
Frequency
014A
3, 4
16NS
0.01 Hz
014B
3, 4
16S
100 kW
014C
3, 4
16S
100 kvar
014D
3, 4
16S
100 kVA
014E
3, 4
16S
100 kW
3, 4
16S
100 kvar
0150
3, 4
16S
0.01
0151/0152
3, 4
2 x 16NS
100 kW.h
0153/0154
3, 4
2 x 16NS
100 kW.h
0155/0156
3, 4
2 x 16NS
100 kvar.h
0157/0158
3, 4
2 x 16NS
100 kvar.h
Format
Unit
Diagnosis
Diagnosis
Word address
Access
Reserved
0159
Modbus function
enabled
-
015A
3, 4
16NS
10 A
015B
3, 4
16NS
10 A
015C
3, 4
16NS
10 A
015D
3, 4
16NS
1A
015E
3, 4
16NS
1(kA)2
Number of operations
015F
3, 4
16NS
Operating time
0160
3, 4
16NS
1 ms
Charging time
0161
3, 4
16NS
0.1 s
0162
3, 4
16NS
1h
Reserved
0163
0164
3, 4
16NS
0165
3, 4
16NS
1 min
0166
3, 4
16NS
1 min
0167
3, 4
16NS
% lb
0168
3, 4
16NS
0.1 s
0169
3, 4
16NS
1A
016A
3, 4
16NS
1 min
016B
3, 4
16NS
Schneider Electric
5/9
Modbus communication
Diagnosis (contd)
Diagnosis
Word address
Access
Format
Unit
Modbus function
enabled
3, 4
Temperatures 1 to 16
016C/017B
017C/017D
017E/017F
0180/0181
0182/0183
0184
16S
1 C
R
R
R
R
R
3, 4
3, 4
3, 4
3, 4
3, 4
2 x 16NS
2 x 16NS
2 x 16NS
2 x 16NS
16NS
100 kW.h
100 kW.h
100 kvar.h
100 kvar.h
mn
0185
3, 4
16NS
mn
Word address
Modbus
0250/0253
Access
R
Modbus function
enabled
3
Format
Unit
IEC
0254
3, 4
32NS
0.1 A
0256
3, 4
32NS
0.1 A
0258
3, 4
32NS
0.1 A
025A
3, 4
32NS
0.1 A
025C
3, 4
32NS
0.1 A
025E
3, 4
32NS
1V
0260
3, 4
32NS
1V
0262
3, 4
32NS
1V
Phase-to-neutral voltage V1
0264
3, 4
32NS
1V
Phase-to-neutral voltage V2
0266
3, 4
32NS
1V
Phase-to-neutral voltage V3
0268
3, 4
32NS
1V
Residual voltage V0
026A
3, 4
32NS
1V
026C
3, 4
32NS
1V
026E
3, 4
32NS
1V
Frequency
0270
3, 4
32NS
0.01 Hz
Active power P
0272
3, 4
32S
1 kW
Reactive power Q
0274
3, 4
32S
1 kvar
Format
Unit
32NS
1 kA2
32NS
1 kA2
Word address
Access
Modbus function
enabled
3, 4
3, 4
3, 4
32NS
1 kA2
0296
3, 4
32NS
1 kA2
0298
3, 4
32NS
1 kA2
029A
3, 4
32NS
1 kA2
029C
3, 4
32NS
1 kA2
Number of trips
029E
3, 4
32NS
Number of operations
(If MES108 or MES114)
Operating time
(With MES108 or MES114)
Charging time
(With MES108 or MES114)
02A0
3, 4
32NS
02A2
3, 4
32NS
1 ms
02A4
3, 4
32NS
1 ms
5/10
Schneider Electric
Modbus communication
Word address
Access
02CC
Modbus function
enabled
3
02CD/02D2
Sepam marking
02D3/02DC
02DD/02DF
02E2
Format
Unit
ASCII
12c
ASCII
20c
ASCII
6c
-
02E3
Communication version
02E4
NG
02E5/02E7
02E8/02EA
02EB/02ED
02EE/02F0
Name of language
02F1/02FA
02FB
ASCII
6c
ASCII
6c
ASCII
6c
ASCII
6c
ASCII
20c
-
02FC
02FD
Extension word
02FE
(2)
(2)
Accuracy
Measurement accuracy depends on the weight of the
unit; it is equal to the value of the point divided by 2.
Schneider Electric
4
3
2
DMS303 MSA141 MET148-1
x
x
x
0
x
x
1
0
MES114 MES108
y
y
y
y
Examples:
I1
Unit = 1 A
U21
Unit = 10 V
Accuracy = 10/2 = 5 V
5/11
Modbus communication
Test zone
The test zone is a 16-word zone that may be accessed via the communication link
by all functions, in both read and write modes, to facilitate communication testing at
the time of commissioning or to test the link.
Test zone
Test
Word address
Bit address
Access
0C00
0C0F
C000-C00F
C0F0-C0FF
Read/write
Read/write
Modbus function
enabled
1, 2, 3, 4, 5, 6, 15, 16
1, 2, 3, 4, 5, 6, 15, 16
Format
None
None
Initialized to 0
Initialized to 0
Access
R
R/W
R/W
5/12
Access
R/W
R
R/W
R
Schneider Electric
Modbus communication
Data encoding
For all formats
If a measurement overruns the maximum permissible value for the related format, the
value read for the measurement will be the maximum permissible value for the
format.
16 NS format
The information is encoded in a 16-bit word, in binary format, absolute value
(unsigned). The 0 bit (b0) is the least significant bit in the word.
16 S format signed measurements (temperatures,)
The information is encoded in a 16-bit word as a complement of 2.
Example:
0001 represents +1
FFFF represents -1.
32 NS format
The information is encoded in two 16-bit words, in binary format, unsigned. The first
word is the most significant word.
32 S format
The information is encoded as a complement of 2 in 2 words. The first word is the
most significant word:
0000, 0001 represents +1
FFFF, FFFF represents -1.
B format: Ix
Rank i bit in the word, with i between 0 and F.
Examples
Logic
input
TS
1 to 16
TS
49 to 64
TC
1 to 16
STC
1 to 16
26
25
24
23
22
21
14
13
12
11
15
14
13
12
11
10
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
16
15
14
13
12
11
10
16
15
14
13
12
11
10
Schneider Electric
5/13
Modbus communication
10
11
Protection 37 (undercurrent)
12
13
14
15
16
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
5/14
33
Protection 67 unit 1
34
Protection 67 unit 2
35
36
37
38
39
40
41
42
TC fault
43
TP Phase fault
44
TP Vo fault
45
Reserved
46
Reserved
47
Reserved
48
Reserved
Schneider Electric
Modbus communication
Reserved
50
Reserved
51
Reserved
52
Reserved
53
Reserved
54
Reserved
55
Reserved
56
Reserved
57
Reserved
58
Reserved
59
Reserved
60
Reserved
61
Reserved
62
Reserved
63
Reserved
64
Reserved
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
Schneider Electric
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
5/15
Communication Modbus
Recloser in service
98
Recloser in progress
99
130 Reserved
131 Reserved
132 Reserved
133 Reserved
134 Reserved
135 Reserved
136 Reserved
137 Reserved
138 Reserved
139 Reserved
140 Reserved
141 Reserved
142 Reserved
143 Reserved
144 Reserved
5/16
Schneider Electric
Modbus communication
Schneider Electric
TC Application
1
Tripping
Closing
5
Sepam reset
6
Peak demand current zero reset
7
Inhibit thermal protection
8
Inhibit disturbance recording triggering (OPG*)
9
Confirm disturbance recording triggering (OPG*)
10 Manual disturbance recording triggering (OPG*)
11 Enable recloser
12 Disable recloser
13 Confirm thermal protection
14 Inhibit undercurrent protection
15 Reserved
16 Reserved
* OPG : French acronym for disturbance recording
5/17
Modbus communication
Time-tagging of events
Presentation
Time-tagging
Sepam time-tagging of events uses absolute time (see
section on date and time). When an event is detected,
it is tagged with the absolute time given by Sepams
internal clock.
All the Sepam internal clocks must be synchronized so
as to avoid drifts and all be the same, thereby allowing
inter-Sepam chronological sorting.
Sepam has two mechanisms for managing its internal
clock:
time-setting:
to initialize or modify the absolute time. A special
Modbus message, called "time message", is used to
time-set each Sepam
synchronization:
to avoid Sepam internal clock drifts and ensure interSepam synchronization.
Synchronization may be carried out according to two
principles:
internal synchronization:
via the communication network without any additional
wiring
external synchronization:
via a logic input with additional wiring.
At the time of commissioning, the user sets the
synchronization mode parameter.
mn
mn
mn
mn
mn
mn
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
word
1
word
2
word
3
word
4
Synchronization clock
A synchronization clock is required to set the Sepam date and time; Schneider
Electric has tested the equipment sold by the following suppliers:
Gorgy Timing, ref.: RT300, equpped with the M540 module
SCLE, ref.: RH 2000 -B.
5/18
Schneider Electric
Modbus communication
Time-tagging of events
Reading of events
Exchange word
The exchange word is used to manage a special protocol to be sure not to lose
events following a communication problem. The event table is numbered for that
purpose.
The exchange word includes two fields:
most significant byte (MSB) = exchange number (8 bits): 0..255
b15 b14
b13
b12
b11
b10
b09
b08
The exchange number contains a numbering byte which identifies the exchanges.
The exchange number is initialized to zero when Sepam is energized. When it
reaches its maximum value (FFh), it automatically returns to 0.
Sepam numbers the exchanges and the master acknowledges the numbering.
b05
b04
b03
b02
b01
b00
Exchange number : 0 .. 4
Sepam indicates the number of significant events in the event table in the least
significant byte of the exchange word. Each non-significant event word is initialized
to zero.
Event table acknowledgment
To inform Sepam that the block read by the master has been correctly received, the
master writes the number of the last exchange made in the Exchange number field,
and resets the "Number of events" field of the exchange word to zero. After
acknowledgment, the 4 events in the event table are initialized to zero and the old,
acknowledged events are erased in Sepam.
Until the exchange word written by the master becomes X,0 (with X = number of the
previous exchange that the master wishes to acknowledge), the exchange word in
the table remains at X, number of previous events.
Sepam only increments the exchange number when new events are present (X+1,
number of new events).
If the event table is empty, Sepam performs no processing operations when the
master reads the event table or the exchange word.
The data are encoded in binary format.
Sepam in data loss (1) / no data loss (0) status
Sepam has two internal storage queues with a capacity of 64 events. If one of the
queues becomes saturated, i.e. 63 events already present, the "data loss" event is
generated by Sepam in the 64th position, and event detection carries on.
The least recent events are lost to make room for the most recent ones.
Schneider Electric
5/19
Modbus communication
Time-tagging of events
00
00
00
Falling edge
00
01
Rising edge
Word 5: year
00
0 to 99 (year)
Word 6: month-day
1 to 12 (month)
1 to 31 (day)
Word 7 : hours-minutes
0 to 23 (hours)
0 to 59 (minutes)
Word 8: milliseconds
0 to 59999
5/20
Schneider Electric
Modbus communication
Time-tagging of events
Synchronization
MT10246
master computer
Sepam 1000+
GERIN
MERLIN GERIN
network
Sepam 1000+
MERLIN
Schneider Electric
5/21
Time-tagging of events
master computer
Synchronization (contd)
MT10247
Modbus communication
clock
Sepam 1000+
MERLIN GERIN
synchronization
link
network
Sepam 1000+
MERLIN GERIN
5/22
Schneider Electric
Modbus communication
Request frame
The request is made by the master using a "write word" operation (code 6 or 16) at
the address 1E80h or 2080h of a 1-word frame consisting of the following:
1E80h/2080h
B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01 B00
Function code
Unit number
The content of the address 1E80h/2080h may be read using a Modbus "read word"
operation (code 3).
The function code field may have the following values:
01h to 99h (BCD encoding) for protection functions.
The unit number field is used as follows:
for protection functions, it indicates the unit involved, varying from 1 to N, N being
the maximum number of relays available in the Sepam
when only one unit of a protection function is available, this number field is not
controlled.
Exception replies
In addition to the usual cases, Sepam can send Modbus type 07 exception replies
(not acknowledged) if another remote reading request is being processed.
Reply frame
The reply, sent back by Sepam, fits into a zone with a maximum length of 25 words
at the address 1E00h or 2000h, which comprises the following:
1E00h-1E7Ch/2000h-207Ch
B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01 B00
Function code
Unit number
Settings
..............
(special field for each function)
..............
This zone is read by a Modbus "read word" operation (code 3) at the address 2000h.
The length of the exchange may concern:
first word only (validity test)
maximum size of the zone (125 mots)
usable size of the zone (determined by the function being addressed).
However, reading must always begin at the first word in the zone (any other address
triggers an exception reply "incorrect address").
The first word in the zone (function code and unit number) may have the following
values:
xxyy: with
function code xx different from 00 and FFh
unit number yy different from FFh.
The settings are available and confirmed. They word is a copy of the "request frame".
The zone contents remain valid until the next request is made.
0000h: no "request frame has yet been formulated.
This is espcially the case when Sepam is energized.
The other words are not significant..
FFFFh: the "request frame" has been processed, but the results in the "reply zone"
are not yet available. It is necessary to repeat "reply frame" reading. The other words
are not significant.
xxFFh: with the function code xx different from 00 and FFh. The read request for the
settings of the designated function is not valid. The function is not included in the
particular Sepam, or remote reading of it is not authorized: refer to the list of functions
which accommodate remote reading of settings.
Schneider Electric
5/23
Modbus communication
Remote setting
Data that can be remotely set
Writing of the settings of all the protection functions may be accessed remotely.
Exchange principle
Remote setting is allowed for Sepam units.
Remote setting is carried out for a given function unit by unit.
It takes place in two steps:
first of all, the master indicates the function code and unit number, followed by the
values of all the settings in the "write request frame". The request is acknowledged
to free the network
the master then reads a reply zone designed for checking that the settings have
been processed. Each function has its own particular reply zone contents.
They are the same as those of the remote reading function reply frame.
To use remote setting, it is necessary to make all the settings for the function
concerned, even if some of them have not changed.
Request frame
The request is made by the master using a "write n words" operation (code 16) at the
address 1F00h or 2100h. The zone to be written contains a maximum of 125 words.
It contains the values of all the settings and consists of the following:
1F00h/2100h
B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01 B00
Function code
Unit number
Settings
..............
(special field for each function)
..............
The content of the address 2100h may be read using a "read n words" operation
(code 3).
The function code field may have the following values:
01h to 99h (BCD encoding) for the list of protection functions F01 to F99.
The unit number field is used as follows:
for protection functions, it indicates the unit involved, varying from 1 to N, N being
the maximum number of units available in the Sepam. It may never be equal to 0.
Exception reply
In addition to the usual cases, le Sepam can send type 07 exception replies (not
acknowledged) if:
another remote reading or setting request is being processed
the remote setting function is inhibited.
5/24
Schneider Electric
Modbus communication
Reply frame
The reply sent back by Sepam is the same as the remote reading reply frame. It fits
into a zone with a maximum length of 125 words at the address 1E00h or 2000h, and
is composed of the effective settings of the function following a semantic check:
1E00h-1E7Ch/2000h-207Ch
B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01 B00
Function code
Unit number
Settings
..............
(special field for each function)
..............
This zone is read by a "read n words" operation (code 3) at the address 1E00h or
2000h.
The length of the exchange may concern:
first word only (validity test)
maximum size of the zone (125 words)
usable size of the zone (determined by the function being addressed).
However, reading must always begin at the first word in the zone (any other address
triggers an exception reply "incorrect address").
The first word in the zone (function code and unit number) has the same values as
those described for the remote reading reply frame.
xxyy: with:
# function code xx different from 00 and FFh
# unit number yy different from FFh.
The settings are available and confirmed. The word is a copy of the "request frame".
The zone contents remain valid until the next request is made.
0000h: no "request frame has yet been formulated.
This is espcially the case when Sepam is energized.
The other words are not significant.
FFFFh: the "request frame" has been processed, but the results in the "reply zone"
are not yet available. It is necessary to repeat "reply frame" reading. The other words
are not significant.
xxFFh: with the function code xx different from 00 and FFh. The read request for
the settings of the designated function is not valid. The function is not included in the
particular Sepam, or access to settings is impossible, in both read and write modes.
Schneider Electric
5/25
Modbus communication
Description of settings
Data format
All the settings are transmitted in signed 32-bit integer format (encoding, as a
complement of 2).
Particular setting value:
7FFF FFFFh means that the setting is out of the validity range.
1 The Enabled or Disabled setting is encoded as follows:
0 = Disabled, 1 = Enabled
2 The tripping curve setting is encoded as follows:
0 = definite
1 = inverse
9 = IEC VIT/B
2 = long time inverse
10 = IEC EIT/C
3 = very inverse
11 = IEEE Mod. inverse
4 = extremely inverse
12 = IEEE Very inverse
5 = ultra inverse
13 = IEEE Extr. inverse
6 = RI
14 = IAC inverse
7 = IEC SIT/A
15 = IAC very inverse
8 = IEC LTI/B
16 = IAC extr. inverse
3 The timer hold delay curve setting is encoded as follows:
0 = definite time
1 = IDMT
4 The H2 restraint variable is encoded as follows:
0 = H2 restraint
1 = no H2 restraint
5 The tripping curve setting is:
0 = definite time
1 = IDMT
6 Setting of latching and CB control
0 = No
1 = Yes
7 Tripping curve for negative sequence undercurrent:
0 = definite
9 = IEC VIT/B
12 = IEEE Very inverse
7 = IEC SIT/A 10 = IEC EIT/C
13 = IEEE Extr. inverse
8 = IEC LTI/B 11 = IEEE Mod. inverse 17 = Schneider specific
8 The activation of each of the cycles is encoded as follows:
Correspondence between bit position / protection according to the table below:
Bit
0
Activation by
Instantaneous phase overcurrent, unit 1
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Schneider Electric
Modbus communication
Data
Rated frequency
Remote setting enabled
Working language
Active group of settings
5
6
7
8
9
10
Setting mode
Phase CT rating
Number of phase CTs
Rated current In
Basic current Ib
Residual current determination mode
11
12
13
14
15
Reserved
Rated primary voltage Unp
Rated secondary voltage Uns
16
17
VT wiring
Residual voltage mode
18
19
20
Type of cubicle
Increment active power
Increment reactive power
Format/Unit
0 = 50 Hz, 1 = 60 Hz
1 = disabled
0 = English, 1 = other
0 = Group A
1 = Group B
3 = Choice by I13
4 = Choice by remote control
0 = TMS, 1 = I/Is
0 = 5 A, 1 = 1 A, 2 = LPCT
0 = 3 CTs, 1 = 2 CTs
A
A
0 = None
1 = 2 A CSH
2 = 20 A CSH
3 = CSH + 1 A CT
4 = CSH + 5 A CT
5 = ACE990 Range 1
6 = ACE990 Range 2
7 = 5 A CSH
8 = CSH + sensitive 1 A CT
9 = CSH + sensitive 5 A CT
A
0 = 5 mn, 1 = 10 mn
2 = 15 mn, 3 = 30 mn
4 = 60 mn
V
0 = 100 V, 1 = 110 V
2 = 115 V, 3 = 120 V
4 = 200 V, 5 = 230 V
0 = 3 V, 1 = 2 U, 2 = 1 U
0 = None 1 = 3 V
2 = external VT Uns/
3 = external VT Uns/3
0 = incomer 1= feeder
0.1 kW.h
0.1 kvar.h
Schneider Electric
Setting
1
Data
Latching
Format/Unit
CB control
Activity
Confirmation
5
6
7
Reserved
Reserved
Group A tripping curve
8
9
10
11
12
13
14
15
16
10 ms
-
17
18
19
0.1 A
10 ms
20
21
22
23
24
0 = none,
1 = neg. seq. overvoltage,
2 = undervoltage
-
0.1 A
10 ms
10 ms
5/27
Modbus communication
Data
Latching
Format/Unit
CB control
Activity
Type of I0
0 calculated, 1 measured
5
6
7
Reserved
Reserved
Group A tripping curve
8
9
10
0.1 A
10 ms
11
12
13
14
15
16
17
10 ms
0 yes, 1 no
-
18
19
20
0.1 A
10 ms
21
10 ms
22
23
24
25
26
Group B H2 restraint
Reserved
Reserved
Reserved
Reserved
0 yes, 1 no
-
Data
Latching
Format/Unit
CB control
Activity
Reserved
5
6
Reserved
Tripping curve
7
8
9
10
11
12
Threshold current
Tripping time delay
Reserved
Reserved
Reserved
Reserved
% Ib
10 ms
-
5/28
Setting
1
Data
Latching
Format/Unit
CB control
Activity
Reserved
5
6
7
8
9
10
11
Reserved
Threshold current
Tripping time delay
Reserved
Reserved
Reserved
Reserved
% Ib
10 ms
-
Schneider Electric
Modbus communication
Data
Latching
CB control
Format/Unit
Activity
Reserved
5
6
7
8
9
10
11
12
13
Reserved
Threshold current
Excessive starting time delay
Locked rotor time delay
Locked rotor on start time delay
Reserved
Reserved
Reserved
Reserved
%
10 ms
10 ms
10 ms
-
Data
Latching
Format/Unit
Reserved
Activity
Reserved
5
6
7
8
9
10
11
12
13
14
Reserved
Period of time
Total number of starts
Number of consecutive hot starts
Number of consecutive starts
Time delay between starts
Reserved
Reserved
Reserved
Reserved
Hours
1
1
1
Minutes
-
Data
Latching
CB control
Format/Unit
Activity
Reserved
5
6
7
8
9
10
11
Reserved
Threshold voltage
Tripping time delay
Reserved
Reserved
Reserved
Reserved
% Unp
10 ms
-
Schneider Electric
Setting
1
Data
Reserved
Format/Unit
-
Reserved
Activity
Reserved
5
6
7
8
9
10
11
Reserved
Threshold voltage
Tripping time delay
Reserved
Reserved
Reserved
Reserved
% Unp
10 ms
-
5/29
Modbus communication
Data
Latching
Format/Unit
CB control
Activity
Reserved
5
6
Reserved
Voltage mode
7
8
9
10
11
12
Threshold voltage
Tripping time delay
Reserved
Reserved
Reserved
Reserved
0 = phase-to-neutral,
1 = phase-to-phase
% Unp/Vnp
10 ms
-
Data
Latching
Format/Unit
CB control
Activity
Reserved
5
6
Reserved
Voltage mode
7
8
9
10
11
12
Threshold voltage
Tripping time delay
Reserved
Reserved
Reserved
Reserved
0 = phase-to-neutral
1 = phase-to-phase
% Unp/Vnp
10 ms
-
Data
Latching
Format/Unit
CB control
Activity
Reserved
5
6
7
8
9
10
11
Reserved
Threshold voltage
Tripping time delay
Reserved
Reserved
Reserved
Reserved
% Unp
10 ms
-
5/30
Setting
1
Data
Latching
Format/Unit
CB control
Activity
Reserved
Reserved
6
7
8
9
10
11
Frequency threshold
Tripping time delay
Reserved
Vs set point
Reserved
Reserved
0.1 Hz
10 ms
% Unp
-
Schneider Electric
Modbus communication
Data
Latching
CB control
Format/Unit
Activity
Reserved
Reserved
6
7
8
Frequency threshold
Tripping time delay
Restraint
Vs set point
0.1 Hz
10 ms
0 none
2 on frequency
variation
% Unp
Data
Latching
CB control
Format/Unit
Activity
Reserved
5
6
7
8
9
10
11
Reserved
Alarm set point
Trip set point
Reserved
Reserved
Reserved
Reserved
C
C
-
Schneider Electric
Setting
1
Data
Activity
Format/Unit
Number of cycles
0 to 4
Reclaim time
10 ms
10 ms
6
7
8
9
10 ms
-
10
11
12
13
10 ms
-
14
15
16
17
18
10 ms
10 ms
10 ms
-
5/31
Modbus communication
Data
Latching
Format/Unit
CB control
Activity
Reserved
5
6
7
8
9
10
11
Reserved
Threshold voltage
Tripping time delay
Reserved
Reserved
Reserved
Reserved
% Unp
10 ms
-
Data
Latching
Format/Unit
Reserved
Activity
Reserved
5
6
7
8
9
10
11
12
Reserved
Use close position of circuit breaker
Is set point
Tripping time delay
Reserved
Reserved
Reserved
Reserved
0.1 A
10 ms
-
5/32
Setting
1
Data
Latching
Format/Unit
CB control
3
4
Activity
Reserved
5
6
7
Reserved
Group A direction
Group A characteristic angle
8
9
0 line, 1 busbar
0 = charact. angle 30
1 = charact. angle 45
2 = charact. angle 60
0 : 1 on 3, 1 : 2 on 3
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
0.1 A
10 ms
10 ms
0 line, 1 busbar
0 = charact. angle 30
1 = charact. angle 45
2 = charact. angle 60
0 : 1 on 3, 1 : 2 on 3
0.1 A
10 ms
10 ms
Schneider Electric
Modbus communication
Schneider Electric
Setting
1
Data
Latching
CB control
Activity
Type
6
7
8
9
Reserved
Reserved
Group A direction
Group A angle
10
Group A sector
Format/Unit
0 = projection
1 = directionalized
0 calculated, 1 measured
0 line, 1 busbar
0 = -45 angle
1 = 0 angle
2 = 15 angle
3 = 30 angle
4 = 45 angle
5 = 60 angle
6 = 90 angle
2 = 76 sector
3 = 83 sector
4 = 86 sector
11
12
13
14
15
0.1 A
10 ms
% Unp
16
17
18
19
20
21
22
23
24
25
Group B sector
10 ms
10 ms
% Unp
0 line, 1 busbar
0 = -45 angle
1 = 0 angle
2 = 15 angle
3 = 30 angle
4 = 45 angle
5 = 60 angle
6 = 90 angle
2 = 76 sector
3 = 83 sector
4 = 86 sector
26
27
28
29
30
0.1 A
10 ms
% Unp
31
32
33
34
35
36
37
10 ms
10 ms
% Unp
-
5/33
Modbus communication
Data
Latching
CB control
Activity
Type
Format/Unit
0 = reverse power
1 = overpower
5
6
7
8
9
10
11
12
Reserved
Reserved
Ps set point
Tripping time delay
Reserved
Reserved
Reserved
Reserved
100 W
10 ms
-
Data
Latching
CB control
Activity
Type
Format/Unit
0 = reverse power
1 = overpower
5
6
7
8
9
10
11
12
Reserved
Reserved
Qs set point
Tripping time delay
Reserved
Reserved
Reserved
Reserved
100 var
10 ms
-
5/34
Setting
1
Data
Latching
Format/Unit
CB control
Activity
Reserved
5
6
7
8
9
Reserved
Tripping curve
Threshold current
Tripping time delay
Timer hold curve
10
11
12
13
14
0.1 A
10 ms
10 ms
-
Schneider Electric
Modbus communication
Data
Reserved
Format/Unit
-
Reserved
Activity
Reserved
5
6
7
8
9
10
11
Reserved
Behavior on 46, 51N, 32P, 32Q functions
Tripping time delay
Reserved
Reserved
Reserved
Reserved
0 none, 1 inhibition
10 ms
-
Schneider Electric
Setting
1
Data
Reserved
Format/Unit
-
Reserved
Activity
Reserved
5
6
7
8
9
10
Reserved
Check loss of 3 V/2 U
Test current
Use Vi, Ii criterion
Behavior on 27/27S, 27D, 32P, 32Q,
47, 51V, 59, 59N functions
Behavior on 67 function
11
12
13
14
15
16
17
18
19
Vi set point
Ii set point
Time delay loss 3 V/ 2 U
Time delay Vi, Ii
Reserved
Reserved
Reserved
Reserved
0 none, 1 inhibition
0 non directional,
1 inhibition
0 non directional,
1 inhibition
%
%
10 ms
10 ms
-
5/35
Modbus communication
Disturbance recording
Presentation
B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01 B00
Transferring records
mn
mn
mn
mn
mn
mn
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
Exchange number
..............
Data zone
..............
Reading should always begin with the first word in the address zone (any other
address triggers an exception reply "incorrect address").
The configuration and data files are read in their entirety in Sepam. They are
transferred adjacently.
5/36
Schneider Electric
Modbus communication
Disturbance recording
If the master requests more exchanges than necessary, the exchange number
remains unchanged and the number of usable bytes is forced to 0. To guarantee data
transfers, it is necessary to allow a response time of about 500 ms between each
read operation at 2300h.
The first word transmitted is an exchange word. The exchange word comprises two
fields:
the most significant byte contains the exchange number. It is initialized to zero after
an energizing operation. It is incremented by 1 by Sepam each time a transfer takes
place successfully. When it reaches the value FF, it automatically goes back to zero
the least significant byte contains the number of usable bytes in the data zone.
It is initialized to zero after an energizing operation and must be different from FFh.
The exchange word may also have the following values:
xxyy: the number of usable bytes in the data zone yy must be different from FFh
0000h: no "read requeste frame" has yet been formulated.
This is especially the case when Sepam is energized.
The other words are not significant.
FFFFh: the "request frame has been processed, but the results in the reply zone
are not yet available.
It is necessary to repeat "reply frame" reading.
The other words are not significant.
The words that follow the exchange word make up the data zone.
SInce the configuration and data files are adjacent, a frame may contain the edn of
the configuration and the beginning of the data file of a record.
It is up to the remote monitoring and control system software to reconstruct the files
in accordance with the transmitted number of usable bytes and the size of the files
indicated in the identification zone.
Acknowledging a transfer
To inform Sepam that a record block that it has just read has been received correctly,
the master must write the number of the last exchange that it has carried out in the
"exchange number" field and set the "number of usable bytes in the data zone" of the
exchange word to zero.
Sepam only increments the exchange number if new acquisition bursts are present.
Rereading the identification zone
To ensure that the record has not been modified, during its transfer by a new record,
the master rereads the contents of the identification zone and ensures that the date
of the recovered record is still present.