development and improved piles and pile driving systems. Today there are many advanced
techniques of pile installation.
1.3 Function of piles
As with other types of foundations, the purpose of a pile foundations is:
to transmit a foundation load to a solid ground
to resist vertical, lateral and uplift load
A structure can be founded on piles if the soil immediately beneath its base does not have
adequate bearing capacity. If the results of site investigation show that the shallow soil is
unstable and weak or if the magnitude of the estimated settlement is not acceptable a pile
foundation may become considered. Further, a cost estimate may indicate that a pile foundation
may be cheaper than any other compared ground improvement costs.
In the cases of heavy constructions, it is likely that the bearing capacity of the shallow soil will
not be satisfactory, and the construction should be built on
pile foundations. Piles can also be used in normal ground conditions to resist horizontal loads.
Piles are a convenient method of foundation for works over water, such as jetties or bridge
piers.
water. Load is transmitted to the soil through friction or cohesion. But sometimes, the soil
surrounding the pile may adhere to the surface of the pile and causes "Negative Skin Friction"
on the pile. This, sometimes have considerable effect on the capacity of the pile. Negative skin
friction is caused by the drainage of the ground water and consolidation of the soil. The founding
depth of the pile is influenced by the results of the site investigate on and soil test.
An extension of the end bearing pile when the bearing stratum is not hard, such as a firm clay.
The pile is driven far enough into the lower material to develop adequate frictional resistance. A
farther variation of the end bearing pile is piles with enlarged bearing areas. This is achieved by
forcing a bulb of concrete into the soft stratum immediately above the firm layer to give an
enlarged base. A similar effect is produced with bored piles by forming a large cone or bell at the
bottom with a special reaming tool. Bored piles which are provided with a bell have a high
tensile strength and can be used as tension piles (see fig.1-3)
Timber
Concrete
Steel
Composite piles
Figure 1-4 a) concrete pile connecting detail. b) squared pre-cast concert pile
The Hercules type of pile joint (Figure 1-5) is easily and accurately cast into the pile and is
quickly and safely joined on site. They are made to accurate dimensional tolerances from high
grade steels.
Steel piles: (figure 1.4) steel/ Iron piles are suitable for handling and driving in long lengths.
Their relatively small cross-sectional area combined with their high strength makes penetration
easier in firm soil. They can be easily cut off or joined by welding. If the pile is driven into a soil
with low pH value, then there is a risk of corrosion, but risk of corrosion is not as great as one
might think. Although tar coating or cathodic protection can be employed in permanent works.
It is common to allow for an amount of corrosion in design by simply over dimensioning the
cross-sectional area of the steel pile. In this way the corrosion process can be prolonged up to
50 years. Normally the speed of corrosion is 0.2-0.5 mm/year and, in design, this value can be
taken as 1mm/year
a) X- cross-section
b) H - crosssection
c) steel pipe
Drilled-in tubes
Mini piles
Prefabricated concrete piles (reinforced) and pre stressed concrete piles. (driven)
affected by the ground water conditions.
+ Do not corrode or rot.
+ Are easy to splice. Relatively inexpensive.
+ The quality of the concrete can be checked before driving.
+ Stable in squeezing ground, for example, soft clays, silts and peats pile material can be
inspected before piling.
+ Can be re driven if affected by ground heave. Construction procedure unaffected by ground
water.
+ Can be driven in long lengths. Can be carried above ground level, for example, through water
for marine structures.
+ Can increase the relative density of a granular founding stratum.
-- Relatively difficult to cut.
-- Displacement, heave, and disturbance of the soil during driving.
-- Can be damaged during driving. Replacement piles may be required.
-- Limitation in length owing to lifting forces required to withdraw casing, nose vibration and
ground displacement may a nuisance or may damage adjacent structures.
-- Cannot be driven where headroom is limited.
-- Relatively expensive.
-- Time consuming. Cannot be used immediately after the installation.
-- Limited length.
-- Sinking piles may cause loss of ground I cohesion-less leading to settlement of adjacent
structures.
Task
1. Describe the main function of piles
2. In the introduction, it is stated that piles transfer load to the bearing ground. State
how this is achieved.
3. Piles are made out of different materials. In short state the advantages and
disadvantages of these materials.
4. Piles can be referred as displacement and non-displacement piles. State the
differences and the similarities of these piles
5. Piles can be classified as end-bearing piles cohesive or friction piles. Describe the
differences and similarity of these piles.
6. Piles can be classified as bored or driven state the differences.
Copyright of the material in this suite of web pages belongs to the authors.
Last updated: May 14, 1999.
LOAD ON PILES
2.1 Introduction
This section of the guide is divided into two parts. The first part gives brief summary on basic
pile arrangements while part two deals with load distribution on individual piles.
Piles can be arranged in a number of ways so that they can support load imposed on them.
Vertical piles can be designed to carry vertical loads as well as lateral loads. If required,
vertical piles can be combined with raking piles to support horizontal and vertical forces.
often, if a pile group is subjected to vertical force, then the calculation of load distribution on
single pile that is member of the group is assumed to be the total load divided by the number
of piles in the group. However if a group of piles is subjected to lateral load or eccentric
vertical load or combination of vertical and lateral load which can cause moment force on the
group which should be taken into account during calculation of load distribution.
In the second part of this section, piles are considered to be part of the structure and force
distribution on individual piles is calculated accordingly.
Objective: In the first part of this section, considering group of piles with limited number of
piles subjected to vertical and lateral forces, forces acting centrally or eccentrically, we learn
how these forces are distributed on individual piles.
The worked examples are intended to give easy follow through exercise that can help quick
understanding of pile design both single and group of piles. In the second part, the
comparison made between different methods used in pile design will enable students to
appreciate the theoretical background of the methods while exercising pile designing.
Learning outcome
c) SYMMETRICALLY ARRANGED
VERTICAL AND RAKING PILES
Copyright of the material in this suite of web pages belongs to the authors.
Last updated: May 14, 1999.
LOAD DISTRIBUTION
To a great extent the design and calculation (load analysis) of pile foundations is
carried out using computer software. For some special cases, calculations can
be carried out using the following methods...For a simple understanding of the
method, let us assume that the following conditions are satisfied:
The pile is rigid
The pile is pinned at the top and at the bottom
Each pile receives the load only vertically (i.e. axially applied );
The force P acting on the pile is proportional to the displacement U due to
compression
P =
k.U
3.
1
Since P = E.A
3.
2
E.A = k.U
3.
3
where:
P = vertical load component
k = material constant
U = displacement
E = elastic module of pile material
A = cross-sectional area of pile
Copyright of the material in this suite of web pages belongs to the authors.
Last updated: May 14, 1999.
Nevertheless, calculation method that can satisfy all of these conditions will be complicated
and difficult to carry out manually, instead two widely used simplified methods are presented.
These two methods are refereed as geotechnical and dynamic methods. This section too has
worked examples showing the application of the formulae used in predicting the bearing
capacity of piles made of different types of materials.
Learning outcome
understand the theoretical back ground of the formulae used in pile design
carry out calculation and be able to predict design bearing capacity of single
piles
appreciate results calculated by means of different formulae
the use of empirical formula to predict capacity from soil properties determined by
testing, or
load test on piles at the site
Fig.4-1, When pile is subjected to gradually increasing compressive load in maintained load
stages, initially the pile-soil system behaves in a linear-elastic manner up to point A on the
settlement-load diagram and if the load is realised at any stage up to this point the pile head
rebound to its original level. When the load is increase beyond point A there is yielding at, or
close to, the pile-soil interface and slippage occurs until point B is reached, when the
maximum skin friction on the pile shaft will have been mobilised. If the load is realised at this
stage the pile head will rebound to point C , the amount of permanent settlement being the
distance OC. When the stage of full mobilisation of the base resistance is reached ( point D),
the pile plunges downwards with out any farther increase of load, or small increases in load
producing large settlements.
No end-bearing is mobilised up to this point. The whole of the load is carried by the skin friction on the pile shaft see figure
4-1 I)
The pile shaft is carrying its maximum skin friction and the pile toe will be carrying some load
At this point there is no further increase in the load transferred in skin friction but the base load will have reached its
maximum value.
Where: Q =
Qb = Rb = base resistance
Qs = Rs = shaft resistance
Wp = weight of the pile
Rt = tensile resistance of pile
In terms of soil mechanics theory, the ultimate skin friction on the pile shaft is related to the
horizontal effective stress acting on the shaft and the effective remoulded angle of friction
between the pile and the clay and the ultimate shaft resistance R s can be evaluated by
integration of the pile-soil shear strength a over the surface area of the shaft:
a = Ca + n tan a
Where: n = Ks v (refer geotechnical notes)
a = Ca + KS v tan a
and
4.1
Nevertheless, in practise, for a given pile at a given site, the undrained shear strength C a
varies considerably with many factors, including, pile type, soil type, and methods of
installations.
Ideally, Ca should be determined from a pile-load test, but since this is not always possible, C a
is correlated with the undrained cohesion C u by empirical adhesion factor so that the general
expression in e.q. (4-1) could be simplified to the following expression:
4.2
For piles in clay, the undrained load capacity is generally taken to be the critical value unless
the clay is highly over consolidated. If the undrained or short-term ultimate load capacity is to
be computed, the soil parameters C, , , should be appropriate to undrained conditions
and v and vb should be the total stresses. If the clay is saturated , the undrained angle of
friction u is zero, and a (angle of friction between pile and soil) may also be taken as zero.
In addition, Nq = 1, N = 1, so that the eq in(4-1) reduces to:
4.3
Where: Nc, Nq, N ,= bearing capacity factors and are functions of the internal angle of friction
of the soil, the relative compressibility of the soil and the pile geometry.
4.3.2 Drained load capacity (effective stress approach)
For piles installed in stiff, over consolidated clays, the drained load capacity is taken as design
criterion. If the simplified assumption is made that the drained pile-soil adhesion C a is zero
and that the term in eq (4-1)involving N c, N ignoring the drained ultimate bearing capacity
of the pile may be expressed as :
4.4
Where: s v, and s vb = effective vertical stress at depth z respective at pile base
f a,= effective angle of friction between pile/soil and implied can be taken as f ,
Nq which is dependant up on the values of f may be taken to be the same as for piles in
sand, and can be decided using table 10-5 & 10-6
4.3.3 Pile in sand
If the pile soil adhesion Ca and term Nc are taken as zero in e.q (4-1) and the terms 0.5 d
N is neglected as being small in relation to the term involving N , the ultimate load capacity
of a single pile in sand may be expressed as follows:
4.5
Where: s v, and s vb = effective vertical stress at depth z respective at pile base
Fw = correction factor for tapered pile ( = 1 for uniform diameter)
Copyright of the material in this suite of web pages belongs to the authors.
Last updated: May 13, 1999.
Guide
hammer
3 TON
4 TON
5 TON
fall height
0.055m2
0.073m2
fall height
0.055m2
0.073m2
0.3
420 kN
450 kN
0.4
390 kN
420 kN
0.4
490
520
0.5
450
480
0.5
560
590
0.6
520
540
0.3
470
510
0.4
440
480
0.4
540
590
0.5
510
550
0.5
610
680
0.6
550
610
0.3
580
640
0.4
550
600
0.4
670
740
0.5
610
660
0.5
760
840
0.6
670
730
Copyright of the material in this suite of web pages belongs to the authors.
Last updated: May 13, 1999.
to calculate and predict design bearing capacity of pile group in different soil
types
to appreciate the governing factors in design of group of piles
to design pile groups with appropriate pile spacing
In general ,the bearing capacity of pile group may be calculated in consideration to block
failure in a similar way to that of single pile, by means of equation 4-1,but hear As as the
block surface area and Ab as the base area of the block or by rewriting the general
equation we get:
................................(6.1)
where:
As, surface area of block
Ab = base area of block (see fig.6-3)
Cb, Cs= average cohesion of clay around the group and beneath the group.
Nc = bearing capacity factor. For depths relevant for piles, the appropriate
value of Nc is 9
Wp and Ws = weight of pile respective weight of soil
a free-standing group, in which the pile cap is not in contact with the underlying soil.
a "piled foundation," in which the pile cap is in contact with the underlying soil.
pile spacing
independent calculations, showing bearing capacity of the block and bearing capacity of individual
piles in the group should be made.
relate the ultimate load capacity of the block to the sum of load capacity of individual piles in the
group ( the ratio of block capacity to the sum of individual piles capacity) the higher the better.
In the case of where the pile spacing in one direction is much greater than that in perpendicular
direction, the capacity of the group failing as shown in Figure 6-2 b) should be assessed.
For pile groups in non-cohesive soil, the group bearing capacity as a block may be calculated by means of
e.q. 4-7
6.1.3 Pile groups in sand
In the case of most pile groups installed in sand, the estimated capacity of the block will be well in excess of
the sum of the individual pile capacities. As a conservative approach in design, the axial capacity of a pile
group in sand is usually taken as the sum of individual pile capacities calculated using formulae in 4-8.
SOLUTION
Calculate single pile bearing capacity:
Rs = Cs As = 0.8 50 18 (0.4) = 904kN
Rb = Nc Cb Ab = 9 50 (0.2)2 = 56.6kN
Rci = Rsi + Rbi = 904 + 56.6 = 960
(Wp +Wcap) - Ws = (60 25+(600-20 5.0 5.0 1.0)) - (20 18 (0.2)2 25 = 469kN
total load capacity of 25 piles = Ruc25 = (Rci = Rsi + Rbi) 25 - {(Wp +Wcap) - Ws} = 960 25 - 469 =
23531kN
calculate block load capacity :
= 4 (18 4.4 50 0.8)+ 50 4.4 4.4 9 = 25650kN
Copyright of the material in this suite of web pages belongs to the authors.
Last updated: May 13, 1999.
pile arrangement.
Solution:
1. recommended minimum pile spacing:
S = 3.5 (d) + 0.02 L = 3.5 (0.25) + 0.02 14 = 1.16 m
2. try arranging the piles into two
rows:
vertical load = 120kN/M
single pile load capacity = 90kN/st
= 1.33m
minimum distance to the edge of the pile = 0.1m B = 2 0.1 + 0.25 + 1.10 = 1.55m
here because of the descending nature of the pile diameter a lesser value can be taken , say 1.10m
Copyright of the material in this suite of web pages belongs to the authors.
Last updated: May 13, 1999.
Dropping weight
Explosion
Vibration
Jacking (restricted to micro-pilling)
5. Jetting
8.3.2 Underreaming
A special feature of auger bored piles which is sometimes used to enable to exploit the
bearing capacity of suitable strata by providing an enlarged base. The soil has to be
capable of standing open unsupported to employ this technique. Stiff and to hard clays,
such as the London clay, are ideal. In its closed position, the underreaming tool is fitted
inside the straight section of a pile shaft, and then expanded at the bottom of the pile to
produce the underream shown in fig. 8-3.Normally, after installation and before concrete is
casted, a man carrying cage is lowered and the shaft and the underream of the pile is
inspected.
Figure 8 -3 a)hydraulic rotary drilling equipment b) C.F.A, c)undrreaming tool open position
8.3.3 C.H.D.P
Figure 8-4, Continuous helical displacement piles: a short, hollow tapered steel former
complete with a larger diameter helical flange, the bullet head is fixed to a hallow drill pipe
which is connected to a high torque rotary head running up and down the mast of a special
rig. A hollow cylindrical steel shaft sealed at the lower end by a one-way valve and fitted
with triangular steel fins is pressed into the ground by a hydraulic ram. There are no
vibrations.
Displaced soil is compacted in front and around the shaft. Once it reaches the a suitably
resistant stratum the shaft is rotated. The triangular fins either side of its leading edge
carve out a conical base cavity. At the same time concrete is pumped down the centre of
the shat and through the one-way valve. Rotation of the fins is calculated so that as soil is
pushed away from the pile base it is simultaneously replaced by in-flowing concrete. Rates
of push, rotation and concrete injection are all controlled by an onboard computer. Torque
on the shaft is also measured by the computer. When torque levels reach a constant low
value the base in formed. The inventors claim that the system can install a\ typical pile in
12 minute. A typical 6m long pile with an 800mm diameter base and 350mm shaft founded
on moderately dense gravel beneath soft overlaying soils can achieve an ultimate capacity
of over 200t. The pile is suitable for embankments, hard standing supports and floor slabs,
where you have a soft silty layer over a gravel strata.
Figure 8 -4 C.H.D.P.
Copyright of the material in this suite of web pages belongs to the authors.
Last updated: May 13, 1999.
9.1 Introduction
Pile load test are usually carried out that one or some of the following reasons are fulfilled:
To obtain back-figured soil data that will enable other piles to be designed.
To confirm pile lengths and hence contract costs before the client is
committed to over all job costs.
To counter-check results from geotechnical and pile driving formulae
To determine the load-settlement behaviour of a pile, especially in the region
of the anticipated working load that the data can be used in prediction of
group settlement.
To verify structural soundness of the pile.
compression test
uplift test
lateral-load test
torsion-load test
the most common types of test loading procedures are Constant rate of penetration (CRP)
test and the maintained load test (MLT).
Copyright of the material in this suite of web pages belongs to the authors.
spread foundations;
raft foundations;
piled foundations;
walls and other structures retaining for supporting soil or water;
excavations;
bridge piers and abutments;
embankment and earthworks;
ground anchors and other tie-back systems;
tunnels in hard, non-fractured rock and not subjected to special water tightness or
other requirement.
vary in position (free actions). The duration of actions affections affects the response of the
ground. It may cause strengthening such as the gain in strength of a clay by long-term
loading, or weakening as in the case of excavation slopes in clay over the medium or long
term. To allow for this Eurocode 7 introduces a classification related to the soil response
and refers to transient actions (e.g. wind loads), short-term actions (e.g. construction
loading) and long-term actions. In order to allow for uncertainties in the calculation of he
magnitude of actions or combinations of actions and their duration and spatial distribution,
Euorcode requires the design values of actions Fd to be used for the geotechnical design
either to be assessed directly or to be derived from characteristic values Fk :
Fd = Fk
10.4 The partial factors
m, n, Rd
The partial factor m: this factor is applied as a safety factor that the characteristic values
of the material is divided by this factor. (m = material index) and covers :
In ultimate limit state, depending upon a given conditions, for Geotechnical Category 2, the
values of the m may be decided using table 10-1& 10-2.
The partial co-efficient n: in order to ensure stability and adequate strength in the
structure and in the ground, in the code, cases A, B, and C have been introduced. Values
of n is given in table 10-3
Partial co-efficient Rd: this co-efficient is applied in consideration of deviation between
test results and future construction. Values of the n should be between 1.4 - 1.8
Table 10-1 partial factors on material properties for conventional design situations for ultimate limit states
Material property
Partial factor m
tan
1.1- 1.25
modules
1.2 - 1.8
other properties
1.6 - 2.0
Table 10-2 partial factors on material properties for conventional design situations for service limit state
Material property
Partial factor m
modules
1.2 - 1.8
other properties
1.6 - 2.0
Normally the design values, d , Ed, tan , can be decided using the following formulae:
fd = fk/(
n m
Ed = Ek /(
n m
n m
Where:
f = reaction force
Class
1.0
1.1
1.2
pile
Concrete piles
0.5
0.005
Steel piles
0.5
0.002
0.5
0.009
NC
Nq
25
6.48
20.7
10.7
26
7.64
22.2
11.8
27
8.99
23.9
13.2
28
10.6
25.8
14.7
29
12.5
27.9
16.4
30
14.7
30.1
18.4
31
17.4
32.7
20.6
32
20.6
35.5
23.2
33
24.4
38.9
26.1
34
29.0
42.2
29.4
35
34.4
46.1
33.3
36
41.9
50.6
37.7
37
49.1
55.6
42.9
38
58.9
61.3
48.9
39
70.9
67.9
56.0
40
85.6
75.3
64.2
41
104
83.9
73.9
42
126
93.7
85.4
43
154
105
99.0
44
190
118
115
45
234
134
135
Copyright of the material in this suite of web pages belongs to the authors.
Last updated: May 13, 1999.