CLASSIFICATION OF FIRE RESISTANCE

FIRES-CR-094-11-AURE
Wall made of double skin metal faced insulating panels "TOP WALL 50",
PIR core, 50 mm thick

This is an electronic version of a classification report which was made as a copy


of classification report officially issued in a paper form. The electronic version
of a classification report shall be used only for informative purpose. Any information listed
in this classification report is the property of the sponsor and shall not be used or published
without written permission. Contents of this file may only be modified by the editor i.e.
FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only
with written permission of the editor.

FIRES 004/S2-03/11/2009-E-el

www.fires.sk

CLASSIFICATION OF FIRE RESISTANCE


with extended field of application
FIRES-CR-094-11-AURE
Name of the product: Wall made of double skin metal faced insulating panels "TOP WALL 50",
PIR core, 50 mm thick
Sponsor:

TOPANEL PRODUCTION PANELS SA


str. Uzinei, No. 63
Rm Valcea 240401
Romania

Prepared by:

FIRES, s.r.o.
Approved Body No. SK01
Osloboditeov 282
059 35 Batizovce
Slovak republic

Notified Body No.:

1396

Task No.:
Date of issue:

PR-10-0606
02. 06. 2011

Reports:
Copy No.:

3
2

Distribution list:
Copy No. 1
Copy No. 2
Copy No. 3

FIRES, s. r. o., Osloboditeov 282, 059 35 Batizovce, Slovak republic


(electronic version)
TOPANEL PRODUCTION PANELS SA, str. Uzinei, No. 63, Rm Valcea 240401,
Romania (electronic version)
TOPANEL PRODUCTION PANELS SA, str. Uzinei, No. 63, Rm Valcea 240401,
Romania

This classification report consists of 4 pages and may only be used or reproduced in its entirety.

This report includes accreditation mark SNAS with additional mark ILAC-MRA. SNAS is signatory of ILAC-MRA, Mutual recognition
agreement (of accreditation), which is focused on promoting of international acceptance of accredited laboratory data and reducing
technical barriers to trade, such as the retesting of products on markets of signatories. More information about ILAC-MRA is on
www.ilac.org. Signatories of ILAC-MRA are e.g. SNAS (Slovakia), CAI (Czech Republic), PCA (Poland), DakkS (Germany) or BMWA
(Austria). Up to date list of ILAC-MRA signatories is on www.ilac.org/documents/mra_signatories.pdf. FIRES, s.r.o. Batizovce is full
member of EGOLF also, more information www.egolf.org.uk.

FIRES 147/S-22/03/2010-E

FIRES, s.r.o., Osloboditeov 282, 059 35 Batizovce, Slovak republic


tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk
Notified Body No. 1396, Approved Body No. SK01, Member of EGOLF

FIRES-CR-094-11-AURE

1.

INTRODUCTION

This classification report defines the resistance to fire classification assigned to element Wall made
of double skin metal faced insulating panels "TOP WALL 50", PIR core, 50 mm thick in accordance with
the classes given in EN 13501-2 + A1: 2009.

2.

DETAILS OF CLASSIFIED PRODUCT

2.1 GENERAL
The element, Wall made of double skin metal faced insulating panels "TOP WALL 50", PIR core, 50 mm
thick, is defined as a non-loadbearing wall with fire separating function used as either partition or external
wall acc. to EN 14509.
2.2 PRODUCT DESCRIPTION
Wall is made of vertically oriented double skin metal faced insulating panels "TOP WALL 50", 50 mm thick
with symmetrical joints.
Dimensions
panel width
panel thickness
overlap of joints

1000 mm
50 mm
17,1 mm

Panel core
Polyisocyanurate foam with bulk density of 43 kg/m3 (manufacturer: TOPANEL PRODUCTION PANELS
SA, Romania)
Panel covering
- interior steel sheet 0,5 mm thick, grade of metal DX51D+ZN140 (supplier: Galva Turkey) with polyester
coat (05-20) m thick, RAL 9002, profile geometry: wall geometry-classic profile,
- exterior steel sheet 0,5 mm thick, grade of metal DX51D+ZN140 (supplier: Galva Turkey) with
polyester coat (05-20) m thick, RAL 9002, profile geometry: wall geometry-classic profile.
The fire protection sealing tape Intumex L with dimensions (1,8 x 10) mm (manufacturer: Intumex GmbH,
Austria) is used between the panels, in the centre of the panel thickness.
On the both specimen faces, the joints of panels are stitched with steel self-drilling screws
( 4,8 x 22) mm spaced each 200 mm.
More detailed information about product construction is shown in drawings of the test report (see the
clause 3.1 of the report [1]).
2.3 PRODUCT FIXING
Each sandwich panel is fixed to the steel L-profiles by self-drilling steel screws ( 6,3/5,5 x 90) mm placed
50 mm from the panel corners and in the centre of the panel width.
Supports, load-bearing profiles are placed in distance 3000 mm.

3.

EXTENDED APPLICATION REPORTS AND TEST RESULTS IN SUPPORT OF CLASSIFICATION


No.
[1]

Name of laboratory
FIRES, s.r.o.,
Batizovce, Slovak
Republic

FIRES 147/S-22/03/2010-E

Name of sponsor
EXAP report No.
Date of issue
TOPANEL PRODUCTION
PANELS SA, Valcea,
FIRES-ER-022-11-NURE 02. 06. 2011
Romania

Page: 2

FIRES-CR-094-11-AURE

4.

CLASSIFICATION AND FIELD OF APPLICATION

4.1 REFERENCE OF CLASSIFICATION


Classification of partition has been carried out in accordance with classes defined in clause 7.5.2
of EN 13501-2 + A1: 2009
Classification of external wall has been carried out in accordance with classes defined in 7.5.3
of EN 13501-2 + A1: 2009.
4.2 CLASSIFICATION
4.2.1 CLASSIFICATION OF PARTITION
The element, Wall made of double skin metal faced insulating panels "TOP WALL 50", PIR core, 50 mm
thick, is classified according to the following combinations of performance parameters and classes
as appropriate.

1)

Fire resistance classification

Condition:

E 30 / EI 20 / EW 30

- 1)

E 20 / EW 20

Classification is valid for product with vertically or horizontally oriented panels and no
increase in span length above that tested is allowed

Condition A means: Classification is valid for product without change in orientation of panels and there is
allowed to increase the span length up to 12 000 mm provided that panel joints are
stitched the same way as specified in clause 2.2.2 of this report (in accordance with
EN 15254-5).
Condition B means: Classification is valid for product with vertically or horizontally oriented panels and
there is allowed to increase the span length up to 4 000 mm provided that expansion
allowances are increased pro-rata and panel joints are stitched the same way as
specified in clause 2.2.2 of this report (in accordance with EN 14509 and
EN 1364-1).
4.2.2 CLASSIFICATION OF EXTERNAL WALL
The element, Wall made of double skin metal faced insulating panels "TOP WALL 50", PIR core, 50 mm
thick, is classified according to the following combinations of performance parameters and classes
as appropriate.
Fire resistance classification:

Condition:

E 30 (io) / EI 15 (io)* / EW 30 (io)

- 1)

E 15 (io)** / EW 20 (io)

EN 13501-2, paragraph 7.5.3.4 does not define class EI 20 (io) but the product meets criteria
of insulation during 20 minutes

**

EN 13501-2, paragraph 7.5.3.4 does not define class E 20 (io) but the product meets criteria
of integrity during 20 minutes

1)

Classification is valid for product with vertically or horizontally oriented panels and no
increase in span length above that tested is allowed

FIRES 147/S-22/03/2010-E

Page: 3

FIRES-CR-094-11-AURE

Condition A means: Classification is valid for product without change in orientation of panels and there is
allowed to increase the span length up to 12 000 mm provided that panel joints are
stitched the same way as specified in clause 2.2.2 of this report (in accordance with
EN 15254-5).
Condition B means: Classification is valid for product with vertically or horizontally oriented panels and
there is allowed to increase the span length up to 4 000 mm provided that expansion
allowances are increased pro-rata and panel joints are stitched the same way as
specified in clause 2.2.2 of this report (in accordance with EN 14509 and
EN 1364-1).
4.3 FIELD OF APPLICATION
According to clause 5.2 of the report [1].

5.

LIMITATIONS

This classification document does not represent type approval or certification of the product.
The classification is valid provided that the product, field of application and standards and regulations
are not changed.
Approved:

Signed:

Ing. tefan Rstock


leader of the testing laboratory

Ing. Miroslava Gaperov


technician of the testing laboratory

FIRES 147/S-22/03/2010-E

Page: 4