Ref: ETA/ICML/9MW/BC/SClKW035
Date: July 26, 2011

DGM BUSINESS DEVELOPMENT (POWER)


MIS CESC Limited
CESC House
Chowringhee Square
Kolkata - 700 0022
West Bengal.

KIND ATTN: MR ADRlT PALCHOUDHURY


SUB: ICML 9MW SOLAR POWER PROJECT AT PRATAPGARH, DlST
KUTCH, GUJARAT - CLARIFICATION TO DSLP CQACULATIONS AND
SWITCH YARD LIGHTING PROTECTION LAYOUT
REF: (1) ICML REF: LII GEOE 11055-E-11-12-015 DT 51712011
Dear Sir,
Further to your queries vide your mail referred (1) above regarding SCADA
System, we are pleased to attach herewith point-wise clarifications with respect
to the above system for your kind perusal.

We hope the above is in line with your requirements and would request you to
kindly let us have your approval to enable us to proceed further.
Thanking you and assuring you of our best services at all times.
Yours faithfully
For ETA ENGINEERING PVT LTD

SAURABH CHAUHAN
GENERAL MANAGER
Encl: as above

.............................

Regd. Office : 5, Moores Road, Chennai - 600 006 Tamil Nadu, India
Branches (Tel.)

- Bangalore : 41802300,

Chennai : 28297626, Hyderabad : 27763529130, Mumbai : 67742700, Pune : 26051310, Kolkata : 24864329

subject to incorporation of Commentslmodificatlons as noted. Resubmit revised drgs.ldocs after Incorporating the comments

DOCUMENT No.: ETA/ICML/SOLAR/GUJ/ELECT/ERTH/OS9-A

Lightning Protection Calculation f o r 66/11kV SIS Control Room


CONTROL ROOM BUILDING
For design of lightning protection we have analysed the tallest part of the building.
i.e. Top terrace level area of the control room.
Annual thunderstrom days

30 days

Estimation of exposure of risk ( Ref CI.No.8.1.2 of IS 2309)


Control Room Area :
Length
W~dth
Height

L
W
H

--

Collection Area
Ac . =
TOTAL COLLECTION AREA:
Ac

20
11.6
4.2

m
m
m

Ac = [ LXW + 2[U(H] + 2[WXH] + P X H


552.86488 m2

552.86488 m2

~ i g h t n i flashes
n~
per km2 per year 'Ng' for thunderstrom dayslyear as per
Ref. Clause no. 8.1.2 of IS 2309.
Ng

1.9

Probable number of strikes ( risk) to the structure per.year is


P
P

=ACXN~XIO"
=
1.05E-03

Weighting factor ( Ref CI.No. 8.1.5 of IS 2309)


A
1.O
B
0.4
C
1.O
D
1.O
E
0.3

from table-IA,for use of structure.


from table-1B,for type of construction.
from table-1C,for content or consequential effects.
from table-I D,for degree of isolation.
from table-I E,for type of company.

The overall weighting factor = A*B*C*D*E =

0.12

After applying the weighting factor, Probable risk factor

Probable risk factor

1.05E-03 x

:P

1.26E-04 per year

As per cl.no:8.1.3 of IS 2309 suggested acceptable risk figure =

0.12

per year. (Protection is not required)

Now from the above calculation i t has been found that probable risk factor P
is more than the acceptable risk factor.Hence protection is necessary.

One down conductor is required for each 30m o f perimeter of the


structures protected as per 18-2309 CI.No.12.2.3 (B)
Total Perimeter to be protected

--

63.2 m

Hence, from IS 2309 CI. No. 12.2.3 (b) minimum Three down conductors are required.As shown
i n layout we are providing four down conductors.

SCHEDULE OF EQUIPMENT - 6 6 k V

IS.NO. II

1 1

II

DESCRIPTION
72.5KV.B30&31.WA FOR 3%
aRculT BREWER.

SF6

Qlv.

II

01 NO..

72.WV.630AJl.SKA FOR S a c , ENTER BREAK


ISOUmR THREE PHASE WTH EARTH SmTM

OZ

1-1

SYMBOL 1

I PHASE 7 Z W V WlDM)R PT (3 SCONObRY)

P/P/PIypu

03 NO..

SURGE ARRESTOR

08 N h

. ZINC OXIDE . 8CUV.lWA

IASPER BW(

I SlRlNG INSULATOR

12.5 MVhll/BBKV. 3Ph. DYnll


ONAN/~S

or NO..

mmama

-I
2.1

CLEARANCE TABLE

m A s

m PHASE (PP)

PHASE TD EARTH (PE)

scncu

CLE*RANCE (SC)

CROVNO CLEARANCE
TO THE NEbREST PART NOT AT EARTH
P o m n A L w AN I N ~ A T W

42M
2440

72.5 kV

A. HIMEST SlSTDl WLTADE


B. UMlNINC IMPVLSE WLTAGE

SWOLY EARTHED

C TIPES OF SISTDl EARTHING

0. SISrm FRECUENCY

NOTES:
1. AU DIMENSIONS ARE IN MM. UNLESS D T H W S E SPECIFIED.
2. CREEPAGE DISTANCE- 25mm/kV, MINIMUM CREEPAG: 1825mm.
NO.^ DISC INSULATORS: BNOS (TENSION)
5NOS (SUSPENSION)
3. CONDUCTOR SIZE/DElAILS.
W N BUS : ACSR SINGLE ZEBRA
EOUIPMENTS IWER CONNECTION. WAF0 BAY & UNE BAYS : ACSR SINGLE ZEBRk
4. CONDUCTOR TENSION
W N BUS : 1000 ko/CONWCTOR/PHASE.
'
OMER BUS : 1000 &/PwE.
SHIELD WIRE : 5 0 0 kg.
5. PUNTH HEIGHT OF AU. EOUIPMENT FOUNOATlON W I U BE +300MM PlUlrm
MCEPT CB FROM M E FINISHED COUND L M L (F.C.L). GRAVEL TOP LEML
WlLL BE +150MM FROM THE F.G.L
6. DETAILS OF CABLE TRMCH W l U BE SHWM IN OUTDOOR, INDOOR TRENCH LAYOUT.
7. DElAILS OF CULVERT TYPE TRENCH AND CABLE ENTRY INSIDE CONTROL R W M
WlLL BE SHOWN IN TRENCH MYOUT.

8 REFER PRESENT DRAWlNC FOR LAYOUT PURPOSE ONLY

NAN
ISIUDBY A m
01 m nnmi
-

W ANL 2 4 . ~ 1 1
S.K BY DATI

HXI APPROVU
F I N APPROVAL
OtSCRIPTION

ypBByY AnBlnn
m
PRIP.BY

CiSW1BY

M I A

XU[
nrrr

ASSIM11
>L O ~ ~ I I

INTEGRATED COAL htMNG m

~P((OIIFIACT(R
- - --- -= =-

*
?

= =

- .

.i
.

~?'-PRIVA~~UMIIPD

PROECT

91~~SOWW~KiOETATKllNl~AIUT

.-'------,-II.I-UYI

IU*M,

I-ul.#-n-

br*

ntlt

SWITCHYARD LAYOUT PLAN


BTA-KIm

hv.

IY n

lahn

I h ~ P , " . " , m ~ ~ ~fit ~ ~ f i ~ ~