ITSMT Series
Temperature Controllers
MT48VMOperatingManual
US
Easy Control
Fuzzy + PID
Run/Stop
Operated on the Panel
Multi-Input
K/J/RTD Selectable
Auto Tuning
Bias Value Settable
Communication
RS-485
Input Shift
PV Bias Correctable
Temperature Controllers
Description
Certification
ITSMT-48R
1/16 DIN Relay-Relay-Relay Controller (100 mm)
CUL-CE
ITSMT48RM1/16DINRelayRelayRelayController(100mm),ManualOutputCULCE
ITSMT48V1/16DINSSR12VDCRelayRelayController(100mm)CULCE
ITSMT48VM1/16DINSSR12VDCRelayRelayController(100mm),ManualOutputCULCE
ITSMT48RDV1/16DINRelayRelayRelayController(100mm),HeatingCoolingCULCE
ITSMT48VDV1/16DINRelayRelayRelayController(100mm),HeatingCoolingCULCE
ITSMT48RMRS1/16DINRelayRelayRelayController(100mm),Manual,RS485CULCE
ITSMT48RVMRS1/16DINSSR12VDCRelayRelayController(100mm),Manual,RS485CULCE
ITSMT48LMRS1/16DIN420mARelayRelayController(100mm),Manual,RS485CULCE
ITSMT48RMCT1/16DINRelayRelayRelayController(100mm),Manual,CTCULCE
ITSMT48VMCT1/16DINSSR12VDCRelayRelayController(100mm),Manual,CTCULCE
ITSMT48LMCT1/16DIN420mARelayRelayController(100mm),Manual,CTCULCE
ITSMT20R1/8DINRelayRelayRelayController(80mm)CULCE
ITSMT20RM1/8DINRelayRelayRelayController(80mm),ManualOutputCULCE
ITSMT20V1/8DINSSR12VDCRelayRelayController(80mm)CULCE
ITSMT20L1/8DIN420mARelayRelayController(80mm)CULCE
ITSMT21R1/8DINHorizontalRelayRelayRelayController(80mm)CULCE
ITSMT21V1/8DINHorizontalSSR12VDCRelayRelayController(80mm)CULCE
ITSMT96R1/4DINRelayRelayRelayController(80mm)CULCE
ITSMT96V1/4DINSSR12VDCRelayRelayController(80mm)CULCE
ITSMT96L1/4DIN420mARelayRelayController(80mm)CULCE
Description
Certification
InputVoltage:1560VDC
ISSR25AAL25AmpOperatingVoltage:24380VACCURCE
Description
Certification
45 mm W x 62 mm L x 31 mm H
Page3
Electronic Temperature
Controllers and SSRs (Solid State Relays)
Description
Certification
IInput:420mA
Input
Voltage: 4-20 mA
ISSR50LAH50AmpOperatingVoltage:250480VACCE
ISSR75LAH75AmpOperatingVoltage:250480VACCE
ThreePhaseSolidStateRelaysDescriptionCertification
SinglePhaseSolidStateRelaysContDescriptionCertificationThreePhaseSolidStateR
IInputVoltage:432VDC
ITSR25DAH25AmpOperatingVoltage:90480VACCE
ITSR40DAH40AmpOperatingVoltage:90480VACCE
ITSR75DAH75AmpOperatingVoltage:90480VACCE
IESR100DAH100AmpOperatingVoltage:90480VACCE
InputVoltage:80250VAC
Description
eification
ITSR25AAH25AmpOperatingVoltage:90480VACCE
76mmWx100mmLx30mmH
ITSR40AAH40AmpOperatingVoltage:90480VACCE
Input Voltage: 4-32VDC
ITSR75AAH75AmpOperatingVoltage:90480VACCE
IESR100AAH100AmpOperatingVoltage:24550VACCE
SolidStateRelayAccessoriesDescription
PPCSSRProtectivePlasticCoverforSSRs(TouchSafe)
Input Voltage: 80-250VAC
IHS501PhaseHeatSink(3.75Hx2Wx4L)
IHS1503PhaseHeatSink(3.75Hx6Wx4L)
ITSR1003PhaseHeatSink(3.75Hx4Wx4L)
ISF11592A110VACFanfor3PhaseHeatSink
ISF23092A220VACFanfor3PhaseHeatSink
IHS4258HeatTransferFilm(.017Thick/.45mmThick)For1PhaseHeatSink
IHSESR100HeatSinkforIHPR100DAHSolidStateRelay,(3.25Hx4Lx3.75W)
CF100DAH1CoolingFanforIHPR100DAHSolidStateRelay,120V,(3.125x3.125x1T)
CF100DAH2CoolingFanforIHPR100DAHSolidStateRelay,240v,(3.125x3.125x1"T)
ISSR1PhaseSolidStateRelayWiringDiagramITSR3PhaseSolidStateRelayWiringDiagram
ITSR25DA(H)
ITSR40DA(H)
ITSR75DA(H)
ITSMT Series
Temperature Controlers
HOWTOBUILDPARTNUMBERS:
ITSMT- 4896 - R - RS - mA
1
2
3 4
5
1 SERIES
ITSMT Series Temperature Controller
2 OUTLINE
4896=48<W>x96<H> mmxmm
48=48<W>x48<H< mmxmm
72=72<W>x72<H> mm/mm
96-96<W>x96<H> mmxmm
20=48(W)x96<H> mmxmm
21=96(W)x 48(H) mmxmm
3 OUTPUT METHOD
R=Relay Output
V=Voltage Pulse Output
L=Linear 4-20 mA Output
TERMINOLOGY:
PV:Process Value Key
SV:Display of the Setting Value
SET: Setting Value Key
Setting Key
Shift and Function Key
Increasing or Autotunning Key
Decreasing and ON/OFF Key
4 OTHER
Non=Standard
RS=RS-485
CT Current Transmitter
S:PV Resender
5 INPUT
NON=K/J/RTD(PT)
MA=MA
V=0~10V
VR=VARIABLE RESISTANCE
Page5
Page 6
SettingofParameters
Default Values
FunctionSymbolRangeRemarks
For Setting Process Value: Press Set Key for 1 Second and release, Process Value is Blinking.NowyoucanraiseorlowertheSetValuebypressingupanddownkeys
PressKeyandKeyfor3SecondsorPressKeyfor3Seconds
Seconds
IfCTissetto0,thenControlisOn/Off
If CT is set to 0, then Control is On/Off
IfCTissetto0,thenControlisOn/Off
C / F
C / F
C / F
ControllerNo.
ITSMTSeries
TemperatureControllers
Page 7
Default Values
PressSetKeyfor3Seconds
F / C
Deviation Alarm; See Mode of Alarm
F / C
Page 8
MT Series
PID+Fuzzy Temperature
Controllers
Page 9
Auto Tuning<AT>
PV Resender
The range of transmitter is set by the SLH. Ex. SLH-200, 0~200 will be transmitted to 4~20mA
OUTPUT
6
7
SENSOR
3
2
H
1
B
A
AL1
5
4
1 ~ 24-380VAC
~2
AL 2
11
12
+3
SSR-25 DA
25 Amp Solid State Module
90 / 250VAC
50/60 Hz
3A / 250VAC
INPUT
To turn OFF all output or Temperature Controller, and only display the
value of PV
POWER
10
9
OFF Key
Page 10
Page 11
CE/UL
Auto control
- EllIJmlliU~tl\
Output controlled by
r PID +Fuzzy J
iiitl:l~--.! J~ID_+Fuzzy
ElIMUU
-'FlIJmlliU~ltl\
How to select
The control status
~pv
lZDfOJWJt!!mlliU~!i,!\
ff~~l:![
El !liiJ1=F!liiJt!t~
Press ~
key 3 see to change the control status
~T !Manu ~ 3ft); PJwJt!!mlliU~!i,!\
Manual control
Note
F25-J
MT-ooM
Series
Specific function
~7*Jjjfi~
sv
which set by
~&t!Ikey
Manual control
Press ~ke~
1 00
3 sec
~PVPress
~key
n.050 sv
-'FlIJmlliu~t~ , iiitl:lmlliUtE
Auto control
3 sec
~ ~PV
1 00 sv
[j!lJ5Eiiitl:lfl:J l'j':.~UVI:
When operating in Manual Mode the temperature can overshoot as the Control has a fixed output and is NOT affected by temperature
sensor!
ForAuto Tuning(At): Press and hold the 2nd Key (From the left) for 3 seconds; then press the Set Key
once and then change the value to 1 (using the far right key). Press the Set Key until the display stops
blinking. You are now in the auto-tuning mode and the display shows a green light on
the face of the control. Itmaytakeseveralminutesorlongertocompleteautotuning.Once
autotuninghasbeencompletedthegreenlightisturnedoff.YoucannotAutoTuneinManualMode!
Notice of Safety
Page 12
WARNING
1. Please do not touch the Terminals while the power is
on. May result in electric shock.
2. Please do not let the metal or wire cuttings drop into
the inside of the Temperature Controller. It may
result in malfunction or burn out.
3. Be sure to wire the controller correctly before power
is turned on. If not, a malfunction or burn out may
occur,
CAUTION
1. Be sure to rate the power supply voltage within the
specified range, If not, a malfunction or burn out
may occur.
2. Be sure to rate the load within the specified value. If
not, it may result in a malfunction or burn out.
3. Please install a separate Alarm System to ensure
safety protection in the event of a malfunction. If not,
a serious accident may occur.
Notice of Use
1. Install Temperature Controller in an ambient:
Temperature;: -20C ~ +75C (Without icing
or condensation)
Relative Humidity; 35% ~ 85% RH
The high ambient temperature may shorten the
service life of the Temperature Controller.
DO NOT LET IT EXCEED 75C.
2. The service life of relays are affected by the switching load. Be sure the switching load is under the
rated current.
3. Thermocouple: If you need to extend the
thermocouple lead wires, be sure to use the compensation wires that match the Thermocouple Type.
Trouble Shooting
WARNING
This procedure requires access to the circuitry of a live power unit. Dangerous accidental contact with the line voltage is
possible. Only qualified personnel are to perform these procedures. Potentially lethal voltages are present.
Experience has proven that many control problems are not caused by a defective instrument. See below for some of the
other common causes of failures.
Incorrect parameters entered in menu
Excessive electrical interference
Line wires improperly connected
No voltage between line terminals
Incorrect voltage between line terminals
Connections to terminals are open, missing or loose
Thermocouple (or RTD) is open at tip
Thermocouple (or RTD) lead is broken
Shorted thermocouple ( or RTD) leads
If the points listed above have been checked and the controller still does not function, it is suggested that the instrument be returned
for inspection.Do not attempt to make repairs. Also, it is advisable to use adequate packing to prevent damage in shipment.