Characteristics of MCB
Thread Starter: Import-User-1 Started: 10/24/2011 1:13 PM Replies: 3
Previous thread Next thread
Page 1 of 1 (4 items)
10/24/2011, 1:13 PM
Import-User-1

(0)
Saran Kumar wrote:
Dear Friends,
I need the answers for the following questions,

Joined 8/10/2005
Last visit: 4/9/2014
Posts: 3287
Rating:
(18)

1. What are characteristics of MCB & Where it will applicable?


2. Difference b/w above characteristics? (i.e, Diff b/w B-Curve, C-Curve, K,L,M - Curve)
Kindly Solve this issue.
Regards,
Saran
Top

10/25/2011, 5:50 AM
(0)
Import-User-1 wrote:
Saran Kumar wrote:
Dear Friends,
I need the answers for the following questions,
Ayman Elotaify

1. What are characteristics of MCB & Where it will applicable?


2. Difference b/w above characteristics? (i.e, Diff b/w B-Curve, C-Curve, K,L,M - Curve)
Kindly Solve this issue.

Joined 5/28/2008
Last visit: 4/10/2014
Posts: 2774
Rating:
(532)

Regards,
Saran
Hello Saran,
Based on the Tripping Characteristics, MCBs are available in B, C, D, 'Z', 'K' and
'S' curve to suit different types of applications.
B Curve: for protection of electrical circuits with equipment that does not cause surge
current (lighting and distribution circuits).
Short circuit release is set to (3-5) In
C Curve: for protection of electrical circuits with equipment that causes surge current
(inductive loads and motor circuits).
Short circuit release is set to (5 - 10) In
D Curve: for protection of electrical circuits which causes high inrush current, typically
12-15 times the thermal rated current (transformers, X-ray machines etc.).
Short circuit release is set to (10 - 20) In
K Curve:
Suitable for applications where high levels of inrush current are expected.
Instantaneous trip is (8 - 12) In. The high magnetic trip point is ideal for motors and
transformers. The narrow range (compared with the type D curve) makes it ideal for
applications where nuisance tripping is not an issue.
Z Curve:
Suitable for applications where semiconductors and other components that fail open are

used. Instantaneous trip is (2 - 3) In. The short thermal delay and low magnetic trip point
are ideal for applications where devices and components have low surge and short circuit
tolerances.
S Curve:
Suitable for applications with highly inductive loads, especially in control circuits with coils
and light filaments. Instantaneous response between (13 - 17) In.
Note:

If you use the B MCB in place of D curve MCB, chances are the B curve MCB
contacts can weld together, or there will be nuisance trippings. On the other
hand, if you use a D curve where a B curve MCB has to be used, the system will
damage before the breaker can trip.

Hope this helps.

=== Edited by Ayman Elotaify @ 10/25/2011 5:52 AM [GMT ] ===

Ayman Elotaify
MISC Egypt
www.miscegypt.com
Top
Thank you for this post from:
AMAZINGAHMED, DILIP_1111, Arun Kumar Yadav
10/27/2011, 11:18 AM
Saran Kumar
(0)
Dear Ayman,
Thank you!....
Joined 10/24/2011
Last visit: 7/9/2012
Posts: 2
Rating:

Regards,
Saran
Saran.

(0)

Yahoo India Answers


Search Answers
Search Web
2button

uh3_answers_web

Hi, muthusamy

Signed in as:
seldinesh

Profile

Sign Out

Mail 3
Help

Account Info

Help

Send Feedback

Answers Home

All Categories

Science & Mathematics

Arts & Humanities

Beauty & Style

Business & Finance

Cars & Transportation

Computers & Internet

Consumer Electronics

Dining Out

Education & Reference

Entertainment & Music

More
International

About

Science & Mathematics >

Engineering

Science & Mathematics >

Engineering
Next

Between what two quantity A/B/C OR D-Curves


makes in MCB?
I just want to technical difference between A,b,c, and d curves of Mcb. with proper explanation.And why
we do so.????

Best Answer

Subramaniam answered 3 years ago

A breaker is to protect the system from damage due to high currents or short circuits.
There are B,C and D curve MCBs. Each differ in capability to interrupt the load current safely in certain
time.
B curve MCB trip from 3-5 times of rated current safely meant for smaller inrush current loads.
C curve MCB trip from 5-10 times of rated current safely meant for medium inrush current loads..
D curve MCB trip 10-15 times rated current safely meant for heavy inrush loads like motors.
If you use the B MCB in place of D curve MCB, chances are the B curve MCB contacts can weld together,
or there will be nuisance trippings. On the other hand, if you use a D curve where a B curve MCB has to
be used, the system will damage before the breaker can trip

What is the difference among MCB,MCCB,RCB,RCCB,ELCB


About: 42 terror camps still active in Pak, says Antony

Asked by nitin srivastava, 01 Mar '10 11:16 am


Invite a friend |
Save |
Report abuse
Earn 10 points for answering
Answer this question

[x]
Answer this question

Earn 10 points for answering

15

16654333

postanswer

4000 characters remaining


Source of information
Email Id

Keep me signed in
New User? Sign up

Answers (1)
1.
Many different classifications of circuit breakers can be made, based on their features such as
voltage class, construction type, interrupting type, and structural features.
Low voltage circuit breakers

Low voltage (less than 1000 VAC) types are common in domestic, commercial and industrial
application, include:

MCB (Miniature Circuit Breaker)rated current not more than 100 A. Trip characteristics normally not
adjustable. Thermal or thermal-magnetic operation. Breakers illustrated above are in this category.

MCCB (Molded Case Circuit Breaker)rated current up to 1000 A. Thermal or thermal-magnetic


operation. Trip current may be adjustable in larger ratings.
RCB __ RCCB : -- RESIDUAL CURRENT CIRCUIT BREAKER//CIRCUIT BREAKER//BREAKER
This product provide a high level of protection aganist earth leakage faults by the RCD in addition to
the over and short- circuit protection offered by the MCB.
Rated voltage 400v and below.
Rated current 6A 10A 16A 20A 25A 32A 40A 50A 60A.
It conforms to GB16917-97
It' s pole is 1P, 2P, 3P, 4P. It is 1P.

ELCB :- An Earth Leakage Circuit Breaker (ELCB) is a safety device used in electrical installations
with high earth impedance to prevent shock. ...less
Answered by anantharaman, 01 Mar '10 11:33 am

Yahoo India Answers


Search Answers
Search Web
2button

uh3_answers_web

Hi, muthusamy

Signed in as:
seldinesh

Profile

Sign Out

Mail 3
Help

Account Info

Help

Send Feedback

Answers Home

All Categories

Science & Mathematics

Arts & Humanities

Beauty & Style

Business & Finance

Cars & Transportation

Computers & Internet

Consumer Electronics

Dining Out

Education & Reference

Entertainment & Music

More
International

About

Science & Mathematics >

Engineering

Science & Mathematics >

Engineering
Next

What is the difference between mpcb and mccb?

where should we use mccb and where should we use mpcb. constructural difference

Best Answer

desai b answered 4 years ago

1. MPCB is ment for motor protection only where as MCCB is for various application including Motor.
2. In MPCB we do not talk about Ics / Icu no cat. configuration - class A / class B type of breakers.
For TYpe -2 Coordination we need to have external devices like -- contactor, o/l relay, contactor etc. with
MCCB while with MPCB we have inbuilt configuration of Type -2 coordination (no external device)
3. MPCB has an inbuilt contactor and relay.so need for external contaectors and relays.
MCCB ther is no contactor and relays, we have to provide.
4. MCCB - Moulded case Circuit breaker, is having overload and
s.c. protection & used in Industrial application & Having

high s.c. capacity


MPCB : Motor protection circuit breaker, is used for
protection of motor, having s.c. and overload protection
more effective to protect motor
5.MPCB has got thermal element....with more narrow range, settable to set with reference to motor full
load current.

MCCB SELECTION FOR TRANSFORMER PROTECTION

Thread Starter: jayanta Started: 7/18/2010 10:03 PM Replies: 10


Previous thread Next thread
12 Page 1 of 2 (11 items)
7/18/2010, 10:03 PM
(0)
Dear Experts,
jayanta

can tell me if MCCB (cat no. - 3VT1708-26A36-0AAa0) is suitable for protection of


transformer? If yes, can explane me selection prosidute. Because the above
mention MCCB (80A) is tripping in inrush current of a 37kva (415/240V)
transformer.
Kindly give us reply.

Joined 7/18/2010
Last visit: 8/28/2010
Posts: 4
Rating:
(0)

Thanks in advance.....

=== Edited by jayanta @ 7/18/2010 10:04 PM [GMT ] ===

Top
7/19/2010, 8:20 AM
PISCEAN 2010

(0)
Transformer primary is 2~ or 3~?. How & what type of load is connected to sencondary?.
Thru contactor, relay or directly. How much is seondary fuse or MCCB rating?
DEEP.
Joined 4/23/2010
Last visit: 4/9/2014
Posts: 1540
Rating:

Tell me and I will forget. Show me and I will remember. Involve me and I will understand.
-Confucius

(72)
Top
7/19/2010, 5:02 PM

jayanta

(0)
Transformer's primary & sencondary is 3~. Sencondary open. But actually it will be
connected with thyristor circuit.
Joined 7/18/2010
Last visit: 8/28/2010
Posts: 4
Rating:

Jayanta

(0)
Top
7/20/2010, 6:33 AM
PISCEAN 2010
(0)
Hello Jayanta,
The specified MCCB is of general purpose MCCB & not of dedicated MCCB for only LV
transformer protection. The 80 Amp range selection is correct one but the breaking
capacity 25 KA is not adequate for industrial or your application. Just try MCCB of amp
>70 A rating with 50 KA breaking capacity.
Regards,
DEEP.
Joined 4/23/2010
Last visit: 4/9/2014
Posts: 1540
Rating:

Tell me and I will forget. Show me and I will remember. Involve me and I will understand.
-Confucius

(72)
Top
7/20/2010, 7:42 PM
jayanta

(0)
Mr. Deep,
Joined 7/18/2010
Last visit: 8/28/2010
Posts: 4
Rating:

We also tested this Transformer by useing 63A, 25KA, Cat No. - 3VT1706-2DC36-0AA0
MCCB and no any problem arrive.

(0)
Top
7/21/2010, 7:41 AM
PISCEAN 2010

Joined 4/23/2010

(0)
Mr. Jayanta,
With 63 A, 25 KA MCCB, have you checked the transformer on load or only transformer is
checked? Moreover, if on load you have not faced any problem with 63A 25 KA rating
MCCB & on same transformer, 80A 25 KA MCCB is tripping, then in that case your 80A,
25 KA rating MCCB may be faulty.
Please check.
DEEP.
Tell me and I will forget. Show me and I will remember. Involve me and I will understand.
-Confucius

Last visit: 4/9/2014


Posts: 1540
Rating:
(72)
Top
7/21/2010, 7:41 AM
PISCEAN 2010
(0)
Mr. Jayanta,
With 63 A, 25 KA MCCB, have you checked the transformer on load or only transformer is
checked? Moreover, if on load you have not faced any problem with 63A 25 KA rating
MCCB & on same transformer, 80A 25 KA MCCB is tripping, then in that case your 80A,
25 KA rating MCCB must be faulty.
Please check.
DEEP.
Joined 4/23/2010
Last visit: 4/9/2014
Posts: 1540
Rating:

Tell me and I will forget. Show me and I will remember. Involve me and I will understand.
-Confucius

(72)
Top
8/27/2010, 8:03 PM
(0)

Dear All / Mr. Deep


I like to inform you that the said 63A MCCB is Siemens make
Characteristic D, & 80A MCCB is Characteristic L. I think (after
watching MCCB catalogue) these two types of Characteristic MCCB is
totally different. I also like to inform you that we tested the said
transformer using lots 80A (same type) MCCB. So, please inform/guide
me I/C MCCB selection calculation to avoid MCCB tripping at switching
inrush. it would be better if anyone can give me supporting document
also.

jayanta

Joined 7/18/2010
Last visit: 8/28/2010
Posts: 4
Rating:
(0)

For any information anyone can also mail me


(jayanta.santra1@gmail.com).
Please guide me with supporting document.
Jayanta

=== Edited by jayanta @ 8/28/2010 5:20 PM [GMT ] ===

Top
2/11/2011, 4:24 PM

(0)

Sentronix

Joined 2/4/2010
Last visit: 3/19/2014
Posts: 46
Rating:
(4)

Hello Jayanta,
As I understand problem is line-side protection of a transformer?
We have to see that an inrush current of 20...30 x In (rated current) is realistic.
Instantaneous trip (Ii) of a MCCB is about 10...13 x In. Therefore the circuitbreaker must be operated in its lower setting range.
Example: Inrush current for a transformer In = 500A may be higher than 10000
A.
Selection: Breaker In = 1000A, setting of In = 500 A, Ii = 11 x In = 11000 A (22 x
setting of In).
It must not be forgotten that the circuit breaker has to trip on the minimum shortcircuit Ikmin. So the breaker should provide short time delayed shortcircuit protection (Isd), which normally can be set to 2...10 x In and a time delay
of a few hundred milliseconds.
Please be aware not to use a breaker for motor protection. Phasefailure sensitivity may lead to unintentional tripping behaviour.
Regards,
Sentronix
Top

5/9/2011, 6:49 PM
(0)

Hello Colleagues

VonSiemens

Joined 9/28/2010
Last visit: 1/31/2012
Posts: 6
Rating:
(0)

1.

When switching on low-voltage AC transformers, the extremely


high inrush current peaks place special demands on the trip unit
or on the making capacity of the circuit breakers if these are
also used to switch the transformer.For most applications, an
inrush current of 20 to 30 times the rated operating current is
expected in practice and must be taken into account when
selecting the circuit breakers. The maximum short-circuit
current Ik of the 3VL circuit breakers is 11 x Ie (rated operating
current). A circuit breaker in the lower setting range must
therefore be operated for primary side transformer
protection. Example: A transformer with 500 A rated current; 20
times the inrush currentSelected: ETU with In = 1000 A; setting
range 0.4 - 1 x In = 400 A to 1000 A50% of In = 500 A; Ii = 11 x
In = 1000 A x 11 = 11000 A = 22 x current setting

minerman

Junior Member
Join Date
Aug 2011
Location
Columbus, Ohio, United States
Posts
23
4

MCCB Instantaneous Trip Setting

Does anybody know how to determine an MCCB instantaneous trip setting? I haven't
done this in a couple years. I was thinking 10 or 15x the FLA?
Thanks.

2.

12-08-11, 12:46 PM #2

kingpb
Senior Member
Join Date
Jul 2006
Location
SE USA as far as you can go
Posts
2,171
In general, it must be set to trip below the minimum fault current that it will see,
assuming the maximum capability of the equipment is greater than the minimum fault
current.
"Just because you're paranoid, doesn't mean they're not out to get you"

3.

12-09-11, 09:58 AM #3

Jraef
Senior Member
Join Date
Jul 2006
Location

San Francisco, CA, USA


Posts
3,336
Read Article 430, specifically table 430.52, and read the exceptions as well, and make
sure you understand all of them. If you have more uestions after that, post them here
again.
__________________________________________________ ____________________________
"Dear future generations: Please accept our apologies. We were rolling drunk on
petroleum."
Kilgore Trout (via Kurt Vonnegut)

4.

12-09-11, 10:28 AM #4

raider1
Moderator
Join Date
Jun 2005
Location
North Logan, Utah
Posts
7,919
I think the poster is asking about a molded case circuit breaker.
If that is the case to determine the instantaneous trip threshold you need to get the
circuit breakers trip curve data from the breaker manufacture.
Chris

5.

12-09-11, 12:02 PM #5

zog
Senior Member
Join Date
Feb 2005
Location
Charlotte, NC
Posts
6,291
Originally Posted by minerman

Does anybody know how to determine an MCCB instantaneous trip setting? I haven't done
this in a couple years. I was thinking 10 or 15x the FLA?
Thanks.

Are you asking how to determine WHERE it should be set or how to determine WHAT it is
set at?

6.

12-09-11, 01:20 PM #6

ATSman
Senior Member
Join Date
Aug 2008
Location
Bay Area, CA
Posts
316
Originally Posted by minerman

Does anybody know how to determine an MCCB instantaneous trip setting? I haven't done
this in a couple years. I was thinking 10 or 15x the FLA?

Thanks.

To be compatible with the coordination study, it should be set at just above the inrush
current of the largest connected load on startup. If the breaker is in an MCC then I would
follow the old Westinghouse recommended procedure: 1. Raise the inst dial to max. 2.
Start and stop the motor. 3. Lower the setting 1 notch each time you restart motor until
the breaker trips, then raise the dial 1 notch. 4. Restart motor to prove no-trip. This will
be the final setting. This setting should match the trip curves in the study and also takes
into account cable impedance, as well.
Am I in shape?? I get plenty of exercise pushing my luck!!

7.

12-09-11, 02:27 PM #7

jim dungar
Moderator
Join Date
Feb 2003
Location
Wisconsin
Posts
8,569
Originally Posted by tonytonon

To be compatible with the coordination study, it should be set at just above the inrush
current of the largest connected load on startup. If the breaker is in an MCC then I would
follow the old Westinghouse recommended procedure: 1. Raise the inst dial to max. 2. Start
and stop the motor. 3. Lower the setting 1 notch each time you restart motor until the
breaker trips, then raise the dial 1 notch. 4. Restart motor to prove no-trip. This will be the
final setting. This setting should match the trip curves in the study and also takes into
account cable impedance, as well.

When doing this type of "click and hope" adjustments, make sure you are not exceeding
both the # of starts/hr and the time between starts of the driven equipment.
Just because you can, doesn't mean you should.