C-Linx Configuration Software

Fike Corporation

C-Linx Configuration Software Version 6.4.4.0


Copyright 2014 Fike Corporation
Report Printed on 23/12/2014
Project Filename 'C:\Users\cbonilla\Desktop\Programaciones\19-12-14 DC GART OSINERGMIN.lnx'

Cheetah Xi Panel 001 Configuration


Sales Outlet Information
WESTFIRE SUDAMERICA SRL
Calle Las Palomas 277
Lima, Surquillo Lima 34

Customer Information
Name
Address
City, State ZIP

Page 1 of 12

C-Linx Configuration Software

Fike Corporation

Cheetah Xi Panel 001


Miscellaneous Settings
AC Trouble Delay

12 hours

Abort Type

Panel Walktest

Enabled

Fan Restart

Automatic Restart

Auxiliary Loop Module

No Module

Auxiliary Power Module

No Module

Aux Battery Supervision

Disabled

Transformer Type

240VAC

Main Battery Supervision

Enabled

SLC Wiring Style

Style 4 - Class B

Ground Fault Supervision

L1 Enb L2 Enb

Unsilence Time

24 hours

Silence Reminder

Disabled

Silence Inhibit

Disabled

Silence Mode

UL Silence Mode

Panel Sync Protocol

System Sensor

Panel Switch Operation

Drill/Silence/Acknowledge Switches Enabled

Positive Alarm Sequence

Disabled

New Device Record Missing Trb

Disabled

Auto Message Sent at 12:00AM

Disabled

Eclipse Device Error

Device Error is Trouble

AHU Fire Dept Key

Not Required to restart AHU

Defaults
Panel Line 2 Message

WESTFIRE SUDAMERICA

Password 1

1000

Password 2

0000

Password 3

0000

Password 4

0000

Password 5

0000

Password 6

0000

Password 7

0000

Password 8

0000

Default Photo Sensor

Page 2 of 12

C-Linx Configuration Software

Fike Corporation

Common Settings
Custom Message Line 1

'1-001 PHOTO DETECT'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Zone Assignments

001

Alarm Verification

Alarm Verification Disabled

Alarm Sensitivity Settings


Sensor Broadcast State

Sensor Broadcasts ALARM

Pre-Alarm 1

Disabled

Pre-Alarm 2

Disabled

Acclimate High

2.0%

Acclimate Low

2.5%

Pre-Discharge Type

Type A: Alarm Only

Drift Compensation Warning

80%

Drift Compensation Trouble

100%

Walktest Level

Walktest using Smoke at Alarm Level

Device Summing Settings


Broadcast Threshold 1

Disabled

Broadcast Threshold 2

Disabled

Broadcast Threshold 3

Disabled

Broadcast Threshold 4

Disabled

Broadcast Threshold 5

Disabled

Broadcast Threshold 6

Disabled

Broadcast Threshold 7

Disabled

Broadcast Threshold 8

Disabled

Summing Address 1

No Device

Summing Address 2

No Device

Summing Address 3

No Device

Summing Address 4

No Device

Summing Address 5

No Device

Summing Address 6

No Device

Summing Address 7

No Device

Summing Address 8

No Device

Summing Alarm Level

Disabled

Summing Activation State

Summing Disabled

Remote Annunciator Settings


Remote Annunciator Type

No Annunciator

Remote Annunciator Silence

Non-Silenceable

Remote Annunciator PAS

Disabled
Page 3 of 12

C-Linx Configuration Software

Fike Corporation

Default Photo/Heat Sensor


Common Settings
Custom Message Line 1

'1-001 PHO/HT DETECT'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Zone Assignments

001

Alarm Verification

Alarm Verification Disabled

Alarm Sensitivity Settings


Sensor Broadcast State

Sensor Broadcasts ALARM

Pre-Alarm 1

Disabled

Pre-Alarm 2

Disabled

Acclimate High

2.0%

Acclimate Low

2.5%

Flame Enhancement

Enabled

Pre-Discharge Type

Type A: Alarm Only

Drift Compensation Warning

80%

Drift Compensation Trouble

100%

Walktest Level

Walktest using Smoke at Alarm Level

Device Summing Settings


Broadcast Threshold 1

Disabled

Broadcast Threshold 2

Disabled

Broadcast Threshold 3

Disabled

Broadcast Threshold 4

Disabled

Broadcast Threshold 5

Disabled

Broadcast Threshold 6

Disabled

Broadcast Threshold 7

Disabled

Broadcast Threshold 8

Disabled

Summing Address 1

No Device

Summing Address 2

No Device

Summing Address 3

No Device

Summing Address 4

No Device

Summing Address 5

No Device

Summing Address 6

No Device

Summing Address 7

No Device

Summing Address 8

No Device

Summing Alarm Level

Disabled

Summing Activation State

Summing Disabled

Page 4 of 12

C-Linx Configuration Software

Fike Corporation

Remote Annunciator Settings


Remote Annunciator Type

No Annunciator

Remote Annunciator Silence

Non-Silenceable

Remote Annunciator PAS

Disabled

Default Photo/Duct Sensor


Common Settings
Custom Message Line 1

'1-001 DUCT DETECT'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Zone Assignments

001

Alarm Verification

Alarm Verification Disabled

Alarm Sensitivity Settings


Sensor Broadcast State

Sensor Broadcasts ALARM

Pre-Alarm 1

Disabled

Pre-Alarm 2

Disabled

Acclimate High

2.0%

Acclimate Low

2.5%

Pre-Discharge Type

Type A: Alarm Only

Drift Compensation Warning

80%

Drift Compensation Trouble

100%

Walktest Level

Walktest using Smoke at Alarm Level

Page 5 of 12

C-Linx Configuration Software

Fike Corporation

Device Summing Settings


Broadcast Threshold 1

Disabled

Broadcast Threshold 2

Disabled

Broadcast Threshold 3

Disabled

Broadcast Threshold 4

Disabled

Broadcast Threshold 5

Disabled

Broadcast Threshold 6

Disabled

Broadcast Threshold 7

Disabled

Broadcast Threshold 8

Disabled

Summing Address 1

No Device

Summing Address 2

No Device

Summing Address 3

No Device

Summing Address 4

No Device

Summing Address 5

No Device

Summing Address 6

No Device

Summing Address 7

No Device

Summing Address 8

No Device

Summing Alarm Level

Disabled

Summing Activation State

Summing Disabled

Remote Annunciator Settings


Remote Annunciator Type

No Annunciator

Default Ion Sensor


Common Settings
Custom Message Line 1

'1-001 ION

Custom Message Line 2

'LOOP 1'

DETECT'

Custom Message Line 3

'ADDRESS 001'

Zone Assignments

001

Alarm Verification

Alarm Verification Disabled

Page 6 of 12

C-Linx Configuration Software

Fike Corporation

Alarm Sensitivity Settings


Sensor Broadcast State

Sensor Broadcasts ALARM

Pre-Alarm 1

Disabled

Pre-Alarm 2

Disabled

Acclimate High

065 MIC

Acclimate Low

065 MIC

Pre-Discharge Type

Type A: Alarm Only

Drift Compensation Warning

90%

Drift Compensation Trouble

100%

Walktest Level

Walktest using Smoke at Alarm Level

Smoldering Enhancement

Disabled

Device Summing Settings


Broadcast Threshold 1

Disabled

Broadcast Threshold 2

Disabled

Broadcast Threshold 3

Disabled

Broadcast Threshold 4

Disabled

Broadcast Threshold 5

Disabled

Broadcast Threshold 6

Disabled

Broadcast Threshold 7

Disabled

Broadcast Threshold 8

Disabled

Summing Address 1

No Device

Summing Address 2

No Device

Summing Address 3

No Device

Summing Address 4

No Device

Summing Address 5

No Device

Summing Address 6

No Device

Summing Address 7

No Device

Summing Address 8

No Device

Summing Activation Level

Disabled

Summing Activation State

Summing Disabled

Remote Annunciator Settings


Remote Annunciator Type

No Annunciator

Remote Annunciator Silence

Non-Silenceable

Remote Annunciator PAS

Disabled

Default Heat Sensor

Page 7 of 12

C-Linx Configuration Software

Fike Corporation

Common Settings
Custom Message Line 1

'1-001 HEAT DETECT'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Zone Assignments

001

Alarm Verification

Alarm Verification Disabled

Alarm Sensitivity Settings


Pre-Alarm 1

Disabled

Pre-Alarm 2

Disabled

Daytime Alarm

135F

Nighttime Alarm

135F

Pre-Discharge Type

Type A: Alarm Only

Walktest Level

Walktest using Heat at 135F

Fixed Temp or Rate

Sensor Implements Fixed Temperature Detection

Remote Annunciator Settings


Remote Annunciator Type

No Annunciator

Remote Annunciator Silence

Non-Silenceable

Remote Annunciator PAS

Disabled

Default Monitor Module


Common Settings
Custom Message Line 1

'1-001 INPUT MANALRM'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Input Function

Manual Alarm

Input Latching Type

Latching Input

Input Contact Type

Normally Open Contact

Input Wiring Style

Class B

Input Short Detection

Short Detection is Disabled

Zone Assignments

001

Default Mini Monitor Module

Page 8 of 12

C-Linx Configuration Software

Fike Corporation

Common Settings
Custom Message Line 1

'1-001 MINI MANALRM'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Input Function

Manual Alarm

Input Latching Type

Latching Input

Input Contact Type

Normally Open Contact

Input Short Detection

Short Detection is Disabled

Zone Assignments

001

Default Pull Station Module


Common Settings
Custom Message Line 1

'1-001 PULL STATION'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Input Function

Manual Alarm

Zone Assignments

001

Default Control Module


Common Settings
Custom Message Line 1

'1-001 OUTPUT MODULE'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Zone Assignments

001

Drill Output Pattern

On Continuous

Silence

Output is Silenceable

Positive Alarm Sequence

PAS is Disabled

Power Supply Monitor

Monitor is Enabled

Output Control Settings


Priority

State

Action

Pattern

01

Alarm

Zone 001

On Continuous

32

Test Alarm

Zone 001

Walktest

Default Relay Module

Page 9 of 12

C-Linx Configuration Software

Fike Corporation

Common Settings
Custom Message Line 1

'1-001 RELAY MODULE'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Zone Assignments

001

Drill Operation

Drill Operation Disabled

Silence

Output is Non Silenceable

Positive Alarm Sequence

PAS is Disabled

Relay Monitoring

Relay Monitoring is Disabled

Dry Contact

Dry Contact Not Used

Output Control Settings


Priority

State

Action

Relay State

01

Alarm

Zone 001

On

Default Release Module


Common Settings
Custom Message Line 1

'1-001 RELEASING MOD'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Zone Assignments

No Zone Assignments

Output Control Settings


Output Type

No Output Device

Output State

No Output State

Default FAAST Sensor


Common Settings
Custom Message Line 1

'1-001 FAAST DETECT'

Custom Message Line 2

'LOOP 1'

Custom Message Line 3

'ADDRESS 001'

Zone Assignments

001

FAAST States
Fire 2

Disabled

No Alarm Verification

Fire 1

Alarm, Latching

No Alarm Verification

Action 2

Disabled, Non-Latching

No Alarm Verification

Action 1

Disabled, Non-Latching

No Alarm Verification

Alert

Disabled, Non-Latching

No Alarm Verification

Acclimate

Disabled
Page 10 of 12

C-Linx Configuration Software

Fike Corporation

FAAST Daytime Sensitivity


Fire 2

Range 1 [0.00046% to 0.04980%]Disabled

Fire 1

Range 4 [1.00000% to 3.98819%]2.50000% ft

Action 2

Range 1 [0.00046% to 0.04980%]Disabled

Action 1

Range 1 [0.00046% to 0.04980%]Disabled

Alert

Range 1 [0.00046% to 0.04980%]Disabled

FAAST Nighttime Sensitivity


Fire 2

Range 1 [0.00046% - 0.04980%] Disabled

Fire 1

Range 4 [1.00000% to 3.98819%]2.50000% ft

Action 2

Range 1 [0.00046% to 0.04980%]Disabled

Action 1

Range 1 [0.00046% to 0.04980%]Disabled

Alert

Range 1 [0.00046% to 0.04980%]Disabled

FAAST Miscellaneous
Pre-Discharge Type

Type A: Alarm Only

Walktest

Disabled

Particulate Level Display

Fire 1 Level

Air Flow Display

020% Off Normal, Indicate Trouble After 000 seconds

Security

Test Button Locked, Isolate Button Locked, Passcode = 1111

Device Disable

Device cannot be Disabled by Holding the Isolate Button

Analog Broadcast

Increasing Step Disabled, Decreasing Step Disabled

Reference Address

Disabled

Isolate Broadcasts

No Alarm is Broadcast during Isolate

Relay Configuration
Relay 1

Non-latching, Fire 2

Relay 2

Non-latching, Fire 1

Relay 3

Non-latching, Action 2

Relay 4

Non-latching, Action 1

Relay 5

Non-latching, Alert

Relay 6 A

Non-latching, High Airflow, Low Airflow, Isolate

Relay 6 B

Filter Minor, Filter Urgent, Filter Door, Configuration

Relay 6 C

Aspirator, Low Voltage, Comm, Time, Sensor

Addressable Devices
Adr

1-001

Type
Function
Mini Monitor Module
Manual Release

Custom Message 1
Custom Message 3

Custom Message 2
Zone 1

'SW PRESION DESCARGA'


'2000-FMM-1003'

Page 11 of 12

Zone 2

Zone 3

Zone 4

'DATA CENTER GART'


002

000

000

000

C-Linx Configuration Software

1-002

1-003

1-004

1-005

1-006

1-007

1-008

1-009

1-010

1-011

1-012

1-013

1-014

1-015

1-016

1-017

1-018

1-019

Mini Monitor Module


Supervisory
Mini Monitor Module
Supervisory
Release Module
Output - Solenoid
Control Module
Output
Photo/Heat Sensor
Photo-Alarm, Heat-Alarm
Photo/Heat Sensor
Photo-Alarm, Heat-Alarm
Photo/Heat Sensor
Photo-Alarm, Heat-Alarm
Photo/Heat Sensor
Photo-Alarm, Heat-Alarm
Control Module
Output
Mini Monitor Module
Abort
Pull Station Module
Manual Release
Photo/Heat Sensor
Photo-Alarm, Heat-Alarm
Photo/Heat Sensor
Photo-Alarm, Heat-Alarm
Relay Module

Fike Corporation

'SW PRESION BAJA'


'2000-FMM-1002'

'2000-FMM-1001'

'2000-FMD-1001'

'2000-FDF-1002'

'2000-FMO-1002'

'2000-FDF-1005'

Supervisory

002

002

Page 12 of 12

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

000

'DATA CENTER GART'


002

000

000

000

'DATA CENTER GART'


002

000

000

000

'DATA CENTER GART'


002

000

000

000

'DATA CENTER GART'


002

000

000

000

'DATA CENTER GART'


002

'ALARMA SHP PRO'


'2000-FMM-1007'

000

'DATA CENTER GART'


002

'SUPERVISION SHP PRO'


'2000-FMM-1006'

000

'DATA CENTER GART'

'PROBLEMA SHP PRO'


'2000-FMM-1005'

000

'DATA CENTER GART'


002

'APAGADO A/A'

'2000-FMO-1003'

000

'DATA CENTER GART'

'DETECTOR FALSO PISO'


'2000-FDF-1006'

000

'DATA CENTER GART'


002

'DETECTOR FALSO PISO'

Output

Mini Monitor Module

002

'EST. MAN. DESCARGA'


'2000-FED-1001'

000

'DATA CENTER GART'

'PULSADOR DE ABORTO'
'2000-FMM-1004'

000

'DATA CENTER GART'


002

'LUZ NIVEL 1'

'LUZ DESCARGA'

Supervisory

002

'DETECTOR FALSO TECHO'


'2000-FDF-1004'

000

'DATA CENTER GART'

'DETECTOR TECHO'
'2000-FDF-1003'

000

'DATA CENTER GART'


002

'DETECTOR FALSO TECHO'

Control Module

Mini Monitor Module

002

'DETECTOR TECHO'
'2000-FDF-1001'

000

'DATA CENTER GART'

'LUZ NIVEL 2'


'2000-FMO-1001'

000

'DATA CENTER GART'


002

'DESCARGA NOVEC 1230'

'2000-FMR-1001'

Supervisory

002

'SW DESCONEXION'

Output

Mini Monitor Module

'DATA CENTER GART'

000

000

000

'DATA CENTER GART'


002

000

000

000