Product range MiCOM Px3x

General platform presentation

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

Range MiCOM Px30


Solutions for
Feeder protection devices
Distance protection devices
Line differential protection devices
Transformer differential protection devices
Railway substation protection devices
One box devices (protection & control)
Bay computers

Schneider Electric - AFS/M-F Jens Eilart September 2010

P13x
P43x
P53x
P63x
Px38
Px39
Cx3x

MiCOM Px30 - protection devices


Variants
MiCOM Px3x in 24 TE case

MiCOM Px3x in 40 TE case

MiCOM Px3x in 84 TE case

Schneider Electric - AFS/M-F Jens Eilart September 2010

MiCOM Px30 - protection devices


Variants
Connection via
Pin terminals
Ring teminals

Hybrid
version
available
Schneider Electric - AFS/M-F Jens Eilart September 2010

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

MiCOM Px30 - protection devices


Flush mounting
Version:
Without angle brackets for direct
mounting
With angle brackets and frame

Two variants for


flexible mounting

Schneider Electric - AFS/M-F Jens Eilart September 2010

MiCOM Px30 - protection devices


Surface mounting
Flexible
surface
mounting
solution

Cutout for cables above and below


Easy fixing on the case during installation
Schneider Electric - AFS/M-F Jens Eilart September 2010

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

10

MiCOM Px30 - protection devices


Structure
PC Interface

TRIP

F1

ALARM
OUT OF SERVICE
HEALTHY

F2

EDIT MODE

G
G

F3

Protection Interface
InterMiCOM
A

F4

G
G

MiCOM

G
C

Communication
Interfaces

F5
F6

B
T

Currents / Voltages

Schneider Electric - AFS/M-F Jens Eilart September 2010

Binary signals / Measured data / Commands

Power supply

11

MiCOM Px30 - protection devices


Hardware options
Processor module P
True 16 bit A/D conversion
Automatic SW calibration

Parameter storage
NV-RAM

Logged data storage


Battery backed RAM

Software storage
Flash EPROM

Single processor solution as


32-bit microprocessor system
I386 EX

Schneider Electric - AFS/M-F Jens Eilart September 2010

12

MiCOM Px30 - protection devices


Hardware options
Power supply board V
8 output relays
All output relays are suitable for
both signal and trip duties
connection

4 opto-isolated inputs
Nominal voltage range:
24 to 250 VDC without internal
switching.

Wide range power supply


Nominal voltage range
48 to 250 VDC and
100 to 230 VAC
without internal switching
Separate module for 24 VDC
Schneider Electric - AFS/M-F Jens Eilart September 2010

13

MiCOM Px30 - protection devices


Basic hardware, Terminal connection

Power supply
board V

Schneider Electric - AFS/M-F Jens Eilart September 2010

14

MiCOM Px30 - protection devices


Basic hardware
Transformer module T
Connection
Via pin terminals

Schneider Electric - AFS/M-F Jens Eilart September 2010

Via ring terminals

15

MiCOM Px30 - protection devices


Hardware options
Communication module A
Separate 16 Bit microcontroller
Switchable seral protocols
Interfaces
Serial link
IRIG-B interface
2nd RS485 link for engineering

Serial link available with


RS85 connector
Plastic fiber optic connectors
FSMA
Glass fiber optic connectors ST

Schneider Electric - AFS/M-F Jens Eilart September 2010

16

MiCOM Px30 - protection devices


Hardware options
Compatible CPU interface

Ethernet communication
module A

Integrated Ethernet Interface

Realtime-Multitasking OS
VXWorks

Main communication
with 100MHz Ethernet
RJ45 or ST/SC connection
(Fiber optics)

COMM2 with IEC60870-5-103


Communication via RS485

Schneider Electric - AFS/M-F Jens Eilart September 2010

17

MiCOM Px30 - protection devices


Hardware options
Analog module Y
2 analog outputs 20 mA
10-bit D/A conversion,
with parallel output relays

4 opto-isolated inputs
Nominal voltage range:
24 to 250 VDC without internal
switching.

Measuring input, 0 to 20 mA
optical coupling
10-bit A/D conversion

PT 100 input
optical coupling
10-bit A/D conversion
Schneider Electric - AFS/M-F Jens Eilart September 2010

18

MiCOM Px30 - protection devices


Basic hardware, Terminal connection

Analog modules Y

Schneider Electric - AFS/M-F Jens Eilart September 2010

19

MiCOM Px30 - protection devices


Basic hardware, Terminal connection
Binary
module

Binary
modules
X

Type X
6I / 8O

Ring

Pin

X_1

X_1

Binary
module
Ring

Output relays
K_01

K_02

K_03

11

12

13

14

15

16

17

K_04
K_05
K_06
K_07
K_08

Vin

X_1

Schneider Electric - AFS/M-F Jens Eilart September 2010

20

21

22

23

24

25

26

27

10

11

12

13

14

15

16

17

18

Output relays
K_01

K_02

Ring

Type X
24I

Pin

Signal inputs
X_1

X_1

Vin

U_01
U_02
U_03
U_04
U_05
U_06
U_07
U_08

Binary
module

X_3
19
20

Vin
Vin
Vin
Vin
Vin

U_02
U_03
U_04
U_05

1
2

21

22

23

24

25

26

27

Type X
6O

Ring

Pin

X_1

X_1

Output relays
K_01

K_02

X_2
X_2

K_03
Signalinputs
Vin

U_01

X_3
19

Pin

Binary
module

X_2

Signal inputs
18

6I / 3O

X_1

X_2
10

Type X

Vin
Vin
Vin
Vin
Vin

U_01

10

11

12

13

14

15

16

17

18

U_04
U_05
U_06

U_09
U_10
U_11
U_12
U_13
U_14
U_15
U_16

10

11

12

13

14

15

16

17

18

1)

1)

K_03

X_3

U_02
U_03

Vin

X_3
19

20

21

22

23

24

25

26

27

Vin

U_17
U_18
U_19
U_20
U_21
U_22
U_23
U_24

19

20

21

22

23

24

25

26

27

1)

K_04
1)

K_05

K_06

U_06

20

MiCOM Px30 - protection devices


Basic hardware, Terminal connection
Binary
module

Binary
modules
X

Type X
6I / 6O

Ring

Pin

X_1

X_1

1
2
3
4

8
9

Binary
module

Type X
6I / 6H

Ring

Pin

X_1

X_1

High-break
contacts

Binary
module

Type X
4H

Ring

Pin

X_1

X_1

Output relays

K_01
K_02

K_01
K_02

+
+

K_03

High-break
contacts

K_01

K_03
X_2
10

11

12

X_2

10

10

11

11

13

12

12

14

13

13

15

14

14

16

15

15

17

16

16

18

17

17

18

18

X_3
19

K_05
K_06

Vin

21

22

Vin

23

Vin

24

25

Vin

26

Vin

+
+

K_05
K_06

K_02

Signal inputs

20

27

Schneider Electric - AFS/M-F Jens Eilart September 2010

K_04

X_2

K_04

Vin

_
X_3

U_01
U_02
U_03
U_04
U_05
U_06

19

20

21

22

23

24

25

26

27

Signal inputs
Vin
Vin
Vin
Vin
Vin
Vin

U_01
U_02
U_03
U_04
U_05

X_3
19

20

21

22

23

24

25

26

27

K_03

K_04

U_06

21

MiCOM Px30 - protection devices


Hardware options, Mandatory modules

Schneider Electric - AFS/M-F Jens Eilart September 2010

22

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

23

MiCOM Px30 - protection devices


Detachable HMI
40 TE detachable HMI with graphic display
multicoloured LEDs available

Schneider Electric - AFS/M-F Jens Eilart September 2010

24

MiCOM Px30 - protection devices


Detachable HMI
40 TE detachable HMI with text display
Function keys
multicoloured LEDs available

Schneider Electric - AFS/M-F Jens Eilart September 2010

25

MiCOM Px30 - protection devices


Detachable HMI
Detachable HMI (40 TE)
Insertion depth allows mounting in smallest Medium Voltage switchgears
Simple wiring ( just RJ45- and grounding connection )

107,0

24,0

( Ground connection
not shown !!! )

Schneider Electric - AFS/M-F Jens Eilart September 2010

26

MiCOM Px30 - protection devices


Detachable HMI
Detachable HMI (40 TE)
Same serial HMI modules will be used as fixed HMI (on the device front)
or as Detachable HMI !
Direct connection

Px3x
Bus system
processormodule
with serial
Interface

Detachable User Interface

Device
front plate
Interface

Serial HMI
with multicoloured
LEDs

14-pole
Flat ribbon cable
Ethernet cable
Schneider Electric - AFS/M-F Jens Eilart September 2010

27

MiCOM Px30 - protection devices


Detachable HMI
Detachable HMI (40 TE)
No additional software for detachable HMI necessary
Supervision of serial communication with HMI
(connected / not connected)
Removing the detachable HMI is always possible
Devices without HMI possible, but today no order option

Schneider Electric - AFS/M-F Jens Eilart September 2010

28

MiCOM Px30 - protection devices


Detachable HMI
Operation without HMI
No operational restrictions of device functionality

BUT
Software download only via User Interface
Cold restart initiation only via User Interface

Schneider Electric - AFS/M-F Jens Eilart September 2010

29

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

30

MiCOM Px30 - protection devices


Software, developement process

Operator
Machine
Interface

Universal
Communication
Interface
System

Device
Drivers

System libary

applications
Communication
HMI

Datamodell
generation

Protection /
control

Device software
Developement
Desk

documentation,
manual

Setting tool

MiCOM S1.103

Schneider Electric - AFS/M-F Jens Eilart September 2010

31

MiCOM Px30 - protection devices


Software structure, data model
Documentation
KOMM
ual
Man

VOB
UMZ

...

communication

DIST

Setting
tool

PC

SG01
SG02

P
i386EX

...

n
tio
ec
ot
pr

RMX

SG03

co
nt
ro
l

DIFF

Upload

Download
...

Device
data model

Schneider Electric - AFS/M-F Jens Eilart September 2010

32

MiCOM Px30 - protection devices


Software function flow

NMI: A/D conversion


and data
pre processing

Protection /
Control
Operation /
Communication

Schneider Electric - AFS/M-F Jens Eilart September 2010

33

MiCOM Px30 - protection devices


Basic data processing

Schneider Electric - AFS/M-F Jens Eilart September 2010

34

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

35

MiCOM Px30 - protection devices


Text-HMI
LED indicators
5 fixed, 18 configurable

Alphanumeric Text-LCD
4 lines x 20 characters

Clear key
Reset / Abort modifications

Protocol key
Direct access recording

Function keys
6 configurable

Cursor keys
Navigation / Scroll in the menu

Enter key
Modify settings
Schneider Electric - AFS/M-F Jens Eilart September 2010

36

MiCOM Px30 - protection devices


Graphic-HMI
LED indicators
5 fixed, 12 configurable

Alphanumeric Text-LCD
16 lines x 21 characters

Clear key
Reset / Abort modifications

Protocol key
Direct access recording

Cursor keys
Navigation / Scroll in the menu

Enter key
Modify settings

Control keys
5 fxed
Schneider Electric - AFS/M-F Jens Eilart September 2010

37

MiCOM Px30 - protection devices


Menu tree
Uniform menu structure
Device Type

Parameters

Operation

Events

Device ID

Cyclic measurements

Event counters

Configuration parameters
Function parameters

Global
Main functions
Parameter subset 1
Parameter subset ...

Control and testing


Operation data recording

Measured fault data


Event recording

Measured operating data


Physical state signals
Logical state signals

Control

Schneider Electric - AFS/M-F Jens Eilart September 2010

38

MiCOM Px30 - protection devices


Menu tree
Configure according to the application

21

79

DIST
MCMON
BUOC
ARC
...

Schneider Electric - AFS/M-F Jens Eilart September 2010

Function group DIST


Function group MCMON
Function group BUOC
Function group ARC

With
Without
Without
With

39

MiCOM Px30 - protection devices


global settings
Global power system characteristics
fnom; phase-sequence; dynamic range of current

CT and VT nominal values


primary values (relevant for recording & metering only)
secondary values

CT grounding
standard = line side
opposite

Measurement value release


to force small measurands to zero (e.g. I = 0 if CB is open!)

Configuration of cross blocking signals


Definition of trip conditions
Set CB characteristics and autoreclosing scheme restrains:
tCB,close; no ARC if CB open; ...
Schneider Electric - AFS/M-F Jens Eilart September 2010

40

MiCOM Px30 - protection devices


function key configuration
Inputs freely configurable
Fx

Fct. Assignm. Fx
per selection table

One signal per F-key


Operating mode Fx
Key
Switch

Password protection
Individual password protection
Settable via HMI for each of the F-key

No function keys with graphical


HMI or 24 TE boxes !
Schneider Electric - AFS/M-F Jens Eilart September 2010

41

MiCOM Px30 - protection devices


binary input configuration
Inputs freely configurable
Fct. Assignm. Ux

V in

Uxx

per selection table

One signal per input


Operating mode Ux
Active high
Active low

Active power drain + numerical filter

Binary inputs Check


Apply voltage (or no voltage) to any
binary input and check its internal state
Read physical state signal
Read assigned logical state signal

Schneider Electric - AFS/M-F Jens Eilart September 2010

42

MiCOM Px30 - protection devices


Global settings
Logical input functions (signals) are indicated by appendix EXT to the
description text
They can be fed from
Binary input (opto-coupler) U xx
Function key input F x
Signal assignment in LOGIC
Signal assignment in COMM3 (InterMiCOM)
Signal assignment in GOOSE, GSSE (ethernet comm.)

In case of multiple assignment, the logical signal is ORed from all

Schneider Electric - AFS/M-F Jens Eilart September 2010

43

MiCOM Px30 - protection devices


Output and LED configuration

Kxx

Any logical state signal can be freely


configured to any physical output or
LED:
Function assignment K xx or H xx
Separate per LED colour

Operating modes K xx or Hxx


Hxx

ES updating (ES = Energised on Signal )


ES manual reset
ES reset (fault)
ES reset (syst. dist.)
NE updating ( NE = Normally Energised )
NE manual reset

Operating modes for LED as blinking


lights

Only one signal per output or LED, but


multiple assignment is possible
Schneider Electric - AFS/M-F Jens Eilart September 2010

44

MiCOM Px30 - protection devices


Output relay configuration
Outputs Check
Kxx

Integrated test function to operate any


output contact for a settable time (0..10 s)
Set Px3x in off-line mode:
003.030 MAIN: Protection enabled = OFF
Set the test hold-time:
003.044 OUTP: Hold-time for test = 10 s
Select an output relay:
003.042 OUTP: Relay assign. f.test =
OUTP Fct. assignm. K xx

Operate the output:


003.043 OUTP: Relay test = execute

Schneider Electric - AFS/M-F Jens Eilart September 2010

45

MiCOM Px30 - protection devices


Watchdog functionality
Configurable to any output
Alarm:
Out of Service:

OUTP: Fct. assignm. K xx = SFMON: Warning (relay)


OUTP: Fct. assignm. K xx = MAIN: Blocked/faulty

Set up normally energised signaling,


to get indications also for supply voltage failure or wire interruptions
L+

K_xx
'NE updating'

Schneider Electric - AFS/M-F Jens Eilart September 2010

46

MiCOM Px30 - protection devices


Instrumentation
Use for commissioning and operation

VPG, IP, IDC, T


VPP, V,Imax/min/pos/neg/zero

P, Q, cos, (V,I), f

dt

Wh, Varh, IPmax delayed/stored

Primary & per unit values

Schneider Electric - AFS/M-F Jens Eilart September 2010

47

MiCOM Px30 - protection devices


state controlled measurement panels

Normal condition
(OP_RC)

Overload condition
(OL_RC, OL_DA)

Ground fault
(GF_RC, GF_DA)

Short circuit
(FT_RC, FT_DA)

Schneider Electric - AFS/M-F Jens Eilart September 2010

Voltage B-C prim.


20,8 kV
Current B prim.
1357 A
Therm. repl. buffer
64 %
Pre-trip time left
21 min
Voltage VNG p.u.
0,328 Unom /3
Current IN,act p.u.
0,027 Inom
Fault duration
0,08 s
Fault Location
12,8 km

48

MiCOM Px30 - protection devices


Fault record triggering
Fixed trigger conditions (global):
via user interface:
via input function:

003.041 FT_RC: Trigger USER = execute


036.089 FT_RC Trigger EXT

Fixed trigger conditions (P43x, P13x):


Starting:
Tripping:

036.000 MAIN: General starting


035.071 MAIN: Gen. trip command

User defined trigger conditions:


by setting:

003.085 FT_RC: Fct. assig. trigger = ...

Schneider Electric - AFS/M-F Jens Eilart September 2010

49

MiCOM Px30 - protection devices


Disturbance recording
Use for commissioning and operation
Protocol for messages and measurements
(via PC, COMMx, HMI)
Analogue values
(via PC, COMMx)

Schneider Electric - AFS/M-F Jens Eilart September 2010

50

MiCOM Px30 - protection devices


Limit value monitoring (LIMIT)

measurements:
currents,
temperature,
20 mA DC,
...

Schneider Electric - AFS/M-F Jens Eilart September 2010

signals:
start I>
tI< elapsed,
...

51

MiCOM Px30 - protection devices


Measured data input (MEASI)
DC current input 0 ... 24 mA ( I nom = 20 mA )
load: 100
maximal short-time loading: 50 mA
resolution: 25 A

open-circuit recognizing 0 ... 3 ... 10 mA


overload capacity 24,8 mA ( fixed value )
zero suppression 0 ... 0,2 I nom
measured-value linearization over 20 branches
limit value monitoring via functional group LIMIT

Schneider Electric - AFS/M-F Jens Eilart September 2010

52

MiCOM Px30 - protection devices


Measured data output (MEASO)
2 DC current output 0 ... 20 mA
maximal load: 50
resolution: 20 A

BCD coded output


adjustable scaling
minimal / maximal current
Break point of characteristics ( for expansion of measuring range )

settable hold time, signal value valid


all operation-, overload- and incidents measurements

Schneider Electric - AFS/M-F Jens Eilart September 2010

53

MiCOM Px30 - protection devices


Programmable logic (LOGIC)
Expansion of known functions
hand over transfer functions
triggering of fault detection
group signal

Customer application design of new functions


possible without firmware update
reaction time like protection functions
Boolean Algebra as basis
high transparency
simple definition
minimal effort to work in

Schneider Electric - AFS/M-F Jens Eilart September 2010

54

MiCOM Px30 - protection devices


Programmable logic (LOGIC)
Other devices

protection

MiCOM Px3x

control

communication

Schneider Electric - AFS/M-F Jens Eilart September 2010

protection
communication

control
Programmable
logic

55

MiCOM Px30 - protection devices


Programmable logic (LOGIC)
control inputs

Schneider Electric - AFS/M-F Jens Eilart September 2010

function

Trip command
and signals

56

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

57

MiCOM Px30 - protection devices


Communication interfaces
Use of communication interfaces

IEC /
COMM1
SCADA / substation
control interface

HMI
COMM2

Full access
to all settings,
signals and measured
values

Modem

Modem

Remote access by protection engineer

PC
Schneider Electric - AFS/M-F Jens Eilart September 2010

Local access
by protection engineer

58

MiCOM Px30 - protection devices


Communication protocols
Simply select protocol
Via serial link
IEC 60870-5-103
IEC 60870-5-101
DNP 3.0
Modbus

Copper wire RS 485


Plastic fiber optics
Glass fiber optics 820 nm

Via ethernet link


IEC 61850

Copper wire RJ 45
Glass fiber optics 1300 nm

Schneider Electric - AFS/M-F Jens Eilart September 2010

59

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

60

MiCOM Px30 - protection devices


Parameter subset selection (PSS)
PS 1

PS 2

Select by
Binary input
Function key input
Local control (HMI)

PS 3

PS 4

Schneider Electric - AFS/M-F Jens Eilart September 2010

Communication interfaces
PC
COMMx
IEC

61

Agenda

Variants
Mounting
Hardware
Detachable HMI
Software
Operation
Communication
Parameter subset selection
Device - Identification

Schneider Electric - AFS/M-F Jens Eilart September 2010

62

MiCOM Px30 - protection devices


Hardware identification
Updated during relay start (booting)
HMI

Test
>>>>>>>>
Device type
532
Software version
630
SW date
30.01.10
F number
6.123456.0
...

Module
Module
Module
Module
...

var. slot 1
vers. slot 1
var. slot 2
vers. slot 2

PC

COMMx /
IEC

Schneider Electric - AFS/M-F Jens Eilart September 2010

63

MiCOM Px30 - protection devices


Hardware and software versions
Handling in the cortec
-3xx
-4xx
-5xx
-6xx
-7xx
-8xx

Hardware version
Connection diagram version (doc.relevant)
Customized version
Datamodel version
Software version without datamodel modification
Language pair version

-2xx

IEC 61850 datamodel version

Schneider Electric - AFS/M-F Jens Eilart September 2010

64