Structural System Construction
Question
Is the structural system free of distress,
settlement, shifting, or cracking in columns or
walls?
Description
Masonry cracks and minor cracks were found on
beams at 1st & 6th Floor. No cracks found on the
columns.
Is a program in place to ensure that the live loads There is no program that ensures the designated
for which a floor or roof is or has been designed
load in each floor will not be exceeded.
will not be exceeded?
Can documentation be provided that the building No clear information was available in the design
is compliant with the requirements for wind
document about the storm surge and wind
loading and storm surge loadings as detailed in
loading for the design of the building.
BNBC Part 6 Section 1.5.3?
Are areas used for storage of work materials and There was no marking on the floor to designate
work products, clearly marked to indicate the
spaces and height for storage of work materials.
acceptable loading limits as described in the Load
Plan for that floor?
Is expansion joint material free from cracking and Expansion joint material is filled with mortar
other forms of deterioration?
which is currently free from cracking but
preventing adequate expansion joint movement.
Suggested Deadline
Standard
Date 30-Nov-14 Alliance Standard Part 8 Section 8.3.3
Factory CAP
Factory Responsible
Person
Source of Findings
Visual Assessment: Visually confirmed.
Level
High
Non-Compliance Level
1
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Medium
Low
Low
Low
Low
Low