April 2006
April 2006
OWTS methodology
on-site PD detection and localisation as well as
dielectric losses measurement in cable
insulation and accessories using
Damped AC voltages up to 250kV
April 2006
Damped AC voltage
Dielectric losses
April 2006
HV
Divider
1600
Control and
data
processing
unit
April 2006
Resistor R
250kV HV
Supply
April 2006
HV Divider and PD
analyser Unit
Example 1:
After-laying test and PD
inspection of a 50kV
XLPE cable section
Substation of Railway
Power supply
April 2006
Example 1:
L3:
April 2006
PDIV @ 82kV
PD~180 pC
Example 1:
April 2006
Example 2:
PD diagnosis of a
service aged 50kVpaper-oil-cable
April 2006
2500pC
1780pC
2300pC
Example 2:
PD diagnosis of a
service aged 50kVpaper-oil-cable
PD vs Ut
14000
12000
Fase L1
Ontladingsniveau (pC)
10000
8000
Fase L2
6000
4000
Fase L3
2000
0
0.5
0.7
1.3
Meetspanning Uo
April 2006
1.5
1.7
Example 3:
PD diagnosis of a service aged 150kV XLPE cable
April 2006
Example 3:
PD diagnosis of a
service aged 150kV
XLPE -insulated
power cable
April 2006
Example 3:
PD diagnosis of a
service aged 150kV
XLPE -insulated
power cable
April 2006
Individual
cable
components
PD mapping (interpretation)
PD level
PD occurrence
frequency
Phase resolved PD
pattern
April 2006
Weight factor
Average at U0
Maximum at U0
Average at 2U0
Maximum at 2U0
At U0
At 2U0
Interpretation
Example:
Norm Generation (PD level @ 1.0U0) for Mass-insulated Cable
Terminations Type with Interfacial Discharges on the HV Connectors
(a)
(b)
Summary
I.
II.
III.
April 2006
ii.