BRITISH STANDARD

Graphical symbols for


diagrams
Part 7: Switchgear, controlgear and
protective devices

The European Standard EN 60617-7:1996 has the status of a


British Standard

ICS 01.080.30; 29.120.60

BS EN
60617-7:1996
IEC 617-7:
1996

BS EN 60617-7:1996

Committees responsible for this


British Standard
The preparation of this British Standard was entrusted to Technical
Committee GEL/3, Documentation and graphical symbols, upon which the
following bodies were represented:
British Photographic Association
Consumer Policy Committee of BSI
Federation of the Electronics Industry
GAMBICA (BEAMA Ltd.)
Transmission and Distribution Association (BEAMA Ltd.)

This British Standard, having


been prepared under the
direction of the Electrotechnical
Sector Board, was published
under the authority of the
Standards Board and comes
into effect on
15 December 1996
BSI 10-1998
The following BSI references
relate to the work on this
standard:
Committee reference GEL/3
Draft for comment 92/28838 DC
ISBN 0 580 26761 X

Amendments issued since publication


Amd. No.

Date

Comments

BS EN 60617-7:1996

Contents
Committees responsible
National foreword
Foreword
Text of EN 60617-7:1996

BSI 10-1998

Page
Inside front cover
ii
2
3

BS EN 60617-7:1996

National foreword
This British Standard has been prepared by Technical Committee GEL/3. It is the
English language version of EN 60617-7:1996, Graphical symbols for diagrams
Part 7: Switchgear, controlgear and protective devices published by the European
Committee for Electrotechnical Standardization (CENELEC). It is identical with
IEC 617-7:1996 published by the International Electrotechnical
Commission (IEC).
This British Standard replaces BS 3939-7:1985 which is withdrawn.
NOTE

The French language version of the alphabetic index has not been included.

A British Standard does not purport to include all the necessary provisions of a
contract. Users of British Standards are responsible for their correct application.
Compliance with a British Standard does not of itself confer immunity
from legal obligations.

Summary of pages
This document comprises a front cover, an inside front cover, pages i and ii,
the EN title page, pages 2 to 58 and a back cover.
This standard has been updated (see copyright date) and may have had
amendments incorporated. This will be indicated in the amendment table on
the inside front cover.
ii

BSI 10-1998

EUROPEAN STANDARD

EN 60617-7

NORME EUROPENNE
June 1996

EUROPISCHE NORM
ICS 01.080.30

Descriptors: Electrical equipment, protective device, electric diagram, electrical symbol

English version

Graphical symbols for diagrams


Part 7: Switchgear, controlgear and protective devices
(IEC 617-7:1996)

Graphische Symbole fr Schaltplne


Teil 7: Schaltzeichen fr Schalt- und
Schutzeinrichtungen
(IEC 617-7:1996)

Symboles graphiques pour schmas


Partie 7: Appareillage et dispositifs de
commande et de protection
(CEI 617-7:1996)

This European Standard was approved by CENELEC on 1996-03-05.


CENELEC members are bound to comply with the CEN/CENELEC Internal
Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Central Secretariat or to any
CENELEC member.
This European Standard exists in three official versions (English, French,
German). A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria,
Belgium, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy,
Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and
United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comit Europen de Normalisation Electrotechnique
Europisches Komitee fr Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B-1050 Brussels
1996 Copyright reserved to CENELEC members

Ref. No. EN 60617-7:1996 E

EN 60617-7:1996

Foreword
The text of document 3A/385/FDIS, future edition 2
of IEC 617-7, prepared by SC 3A, Graphical symbols
for diagrams, of IEC TC 3, Documentation and
graphical symbols, was submitted to the
IEC-CENELEC parallel vote and was approved by
CENELEC as EN 60617-7 on 1996-03-05.
The following dates were fixed:

latest date by which the


EN has to be implemented
at national level by
publication of an identical
national standard or by
endorsement
(dop) 1997-02-01
latest date by which the
national standards
conflicting with the EN
have to be withdrawn
(dow) 1997-02-01

Contents
Introduction
Chapter I: General rules
Section 1 Qualifying symbols
Chapter II: Contacts
Section 2 Contacts with two or three
positions
Section 3 Passing contacts with two
positions
Section 4 Early and late operating
contacts
Section 5 Contacts with delayed
operation
Section 6 Automatic return and
non-automatic return contacts
Chapter III: Switches, switchgear and starters
Section 7 Single-pole switches
Section 8 Position switches
Section 9 Temperature sensitive switches
Section 10 Speed change sensitive contacts,
mercury and levelling switches
Section 11 Examples of multi-position
switches, including control switches
Section 12 Block symbols for complex
switches
Section 13 Power-switching devices
Section 14 Block symbols for motor
starters
Chapter IV: All-or-nothing relays

Page
3
5

Section 15 Operating devices


Chapter V: Measuring relays and
related devices
Section 16 Block symbol and qualifying
symbols
Section 17 Examples of measuring relays
Section 18 Other devices
Chapter VI: Proximity and
touch-sensitive devices
Section 19 Sensors and detectors
Section 20 Switches
Chapter VII: Protective devices
Section 21 Fuses and fuse-switches
Section 22 Spark gaps and arresters
Section 23 Fire-extinguishers
Chapter VIII: Miscellaneous symbols
Section 24 Igniters and flag-indicators
Section 25 Static switches
Section 26 Static switching devices
Section 27 Coupling devices and static
relays, block symbols
Annex A (informative) Older symbols
Annex B (informative) English alphabetic
index

Page
31

36
38
41

42
43
44
46
46
47
47
48
49
50
53

7
9
10
11
12
13
15
16
17
17
22
25
29

BSI 10-1998

EN 60617-7:1996

Introduction
This part of IEC 617 forms an element of a series
which deals with graphical symbols for diagrams.
The series consists of the following parts:
Part 1: General information, general index.
Cross-reference tables;
Part 2: Symbol elements, qualifying symbols
and other symbols having general application;
Part 3: Conductors and connecting devices;
Part 4: Basic passive components;
Part 5: Semiconductors and electron tubes;
Part 6: Production and conversion of electrical
energy;
Part 7: Switchgear, controlgear and protective
devices;
Part 8: Measuring instruments, lamps and
signalling devices;
Part 9: Telecommunications: Switching and
peripheral equipment;
Part 10: Telecommunications: Transmission;
Part 11: Architectural and topographical
installation plans and diagrams;
Part 12: Binary logic elements;
Part 13: Analogue elements.
The scope and the normative references for this
series are given in IEC 617-1.
Symbols have been designed in accordance with
requirements given in the future ISO 11714-11). The
module size M = 2,5 mm has been used. For better
readability smaller symbols in this standard have
been enlarged to double size and are
marked 200 % in the symbol column. To save
space larger symbols have been reduced to half size
and are marked 50 % in the symbol column. In
accordance with the future ISO 11714-1, clause 7,
symbol dimensions (for instance height) may be
modified in order to make space for a greater
number of terminals or for other layout
requirements. In all cases, whether the size is
enlarged or reduced, or dimensions modified, the
thickness of the original line should be maintained
without scaling.

1)

The symbols in this standard are laid out in such a


way that the distance between connecting lines is a
multiple of a certain module. The module 2M has
been chosen to provide enough space for a required
terminal designation. The symbols have been drawn
to a size convenient for comprehension, using the
same grid consistently in the representation of all
symbols.
All symbols are designed within a grid in a
computer-aided draughting system. The grid which
was used has been reproduced in the background of
the symbols.
The older symbols which were included in
appendix A of the first edition of IEC 617-7 for a
transitional period, are no longer part of this second
edition, as they will definitely be withdrawn from
use.
The indexes in Annex B and C include an alphabetic
list of symbol names and their corresponding
number. The symbol names are based on the
description of the symbols of this part. A general
index including an alphabetic list of symbols of all
parts is given in IEC 617-1.

At present, at the stage of Draft International Standard (document 3/563/DIS).

BSI 10-1998

I.1

II est permis dajouter la plupart des symboles un petit cercle vide ou plein
pour reprsenter le point de larticulation. Voir par exemple le 07-02-02.

Chapter I: General rules


I.1

Dans quelques symboles, le cercle reprsentant le point darticulation doit tre


figur. Par exemple, voir 07-02-05.
I.2

Pour dautres mthodes de reprsentation dinterrupteurs en particulier les


interrupteurs lectroniques et complexes voir CEI 617-12, Section 17A et 29 et
CEI 617-13, section 17.

A small circle, open or filled in, representing the hinge point, may be added to
most of the symbols. For example, see 07-02-02.
In some symbols the circle indicating the hinge point shall be shown. For example,
see 07-02-05.

I.2

For other methods of representing switches, especially complex, electronic


switches, see IEC 617-12, section 17A and 29, and IEC 617-13, section 17.

EN 60617-7:1996

Chapitre I: Rgles Gnrales

BSI 10-1998

BSI 10-1998

Section 1 Symboles distinctifs


No.

Symbole

Symbol

Section 1 Qualifying symbols


Lgende

Description

07-01-01

Fonction contacteur

Contactor function

07-01-02

Fonction disjoncteur

Circuit breaker function

07-01-03

Fonction sectionneur

Disconnector (isolator) function

07-01-04

Fonction interrupteur-sectionneur

Switch-disconnector (isolating-switch) function

07-01-05

Fonction dclenchement automatique provoqu par relais


de mesure ou dclencheur incorpor

Automatic tripping function initiated by a built-in


measuring relay or release

07-01-06

Fonction contact de position

Position switch function

1. Ce symbole distinctif peut tre utilis avec un contact


simple afin dindiquer un interrupteur de position lorsquil
nest pas ncessaire de prciser ce mode de commande.
Dans les cas complexes o il est souhaitable de prciser ce
mode de commande, on peut appliquer la place, lun des
symboles 02-13-16 02-13-19.

1. This qualifying symbol may be applied to simple contact


symbols to indicate position switches if there is no need to
show the means of operating the contact. In complicated
cases, where it is desireable to show the means of
operation, one of the symbols 02-13-16 through 02-13-19
may be used instead.

2. Pour reprsenter un contact actionn mecaniquement


dans les deux sens, ce symbole doit tre plac des deux
cots du symbole de contact.

2. To depict a contact which is mechanically operated in


both directions, this symbol shall be placed on both sides
of the contact symbol.

EN 60617-7:1996

Symbole

Symbol

Lgende
Fonction retour automatique, par exemple retour
ressort
1. Ce symbole peut tre utilis pour indiquer une fonction
retour automatique. Par exemple, voir 07-06-01.
2. Ce symbole ne doit pas tre utilis conjointement avec
les symboles distinctifs 07-01-01 ... 07-01-04. Dans de
nombreux cas, le symbole 02-12-07 peut tre utilis.

07-01-08

1. This symbols may be used to indicate automatic return.


For example. see 07-06-01.
2. This symbol shall not be used together with qualifying
symbols 07-01-01, 07-01-02, 07-01-03 and 07-01-04. In
many cases, symbol 02-12-07 may be used.

Fonction retour non-automatique ( position maintenue)

Non-automatic return (stay put) function

1. Ce symbole peut tre utilis pour indiquer une fonction


retour non-automatique ( position maintenue). Lorsque
cette convention est utilise il convient de la signaler de
manire approprie.

1. This symbol may be used to indicate non-automatic


return function. When this convention is invoked, its use
should be appropriately referenced.

2. Ce symbole ne doit pas tre utilis conjointement avec


les symboles distinctifs 07-01-01, 07-01-02, 07-01-03
et 07-01-04. Dans de nombreux cas, le symbole 02-12-08
peut tre utilis.
07-01-09

Description
Automatic return function, for example, spring return

2. This symbol should not be used together with qualifying


symbols 07-01-01, 07-01-02, 07-01-03 and 07-01-04. In
many cases, symbol 02-12-08 may be used.

Manoeuvre positive dun interrupteur

Positive operation of a switch

1. Ce symbole doit tre utilis pour indiquer que la


manoeuvre positive de lappareil mcanique de connection
est positive, cest dire que la manoeuvre donne
lassurance que tous les contacts sont dans la position
correspondant celle de lorgane de commande.

1. This symbol shall be used to indicate that the positive


operation of a mechanical device in the direction shown is
ensured or is required. This means that the operation
ensures that all contacts are in the position corresponding
to the activating device.

2. Si les contacts sont repsents avec une liaison, le


symbole doit sappliquer tous les contacts relis, sauf
indication contraire (voir symbole 07-08-07.

2. If contacts are shown linked, the symbol shall apply to


all the linked contacts unless otherwise indicated
(see symbol 07-08-07).

EN 60617-7:1996

No.
07-01-07

BSI 10-1998

BSI 10-1998

Chapitre II: Contacts


Section 2 Contacts deux ou trois positions
No.
07-02-01

Symbole

Lgende

Description

Contact fermeture (contact de travail)

Make contact

Ce symbole peut galement tre utilis comme symbole


gnral dinterrupteur.

This symbol may also be used as the general symbol for a


switch.

07-02-03

Contact ouverture (contact de repos)

Break contact

07-02-04

Contact deux directions sans chevauchement

Change-over break before make contact

07-02-05

Contact deux directions avec position mdiane de


coupure

Change-over contact with off-position in the centre

07-02-02

Forme 1
Form 1

Symbol

Chapter II: Contacts


Section 2 Contacts with two or three positions

Forme 2
Form 2

EN 60617-7:1996

Symbole
Forme 1
Form 1

07-02-07

Forme 2
Form 2

Symbol

Lgende

Description

Contact deux directions avec chevauchement

Change-over make before break contact

07-02-08

Contact deux fermetures

Contact with two makes

07-02-09

Contact deux ouvertures

Contact with two breaks

EN 60617-7:1996

No.
07-02-06

BSI 10-1998

BSI 10-1998

Section 3 Contacts de passage deux positions


No.

Symbole

Symbol

Section 3 Passing contacts with two positions

Lgende

Description

07-03-01

Contact de passage fermant momentanment laction de


son organe de commande

Passing make contact closing momentarily when its


operating device is actuated

07-03-02

Contact de passage fermant momentanment au


relchement de son organe de commande

Passing make contact closing momentarily when its


operating device is released

07-03-03

Contact de passage fermant momentanment laction et


au relchement de son organe de commande

Passing make contact closing momentarily when its


operating device is actuated or released

EN 60617-7:1996

No.

Symbole Symbol

Section 4 Early and late operating contacts


Lgende

Description

07-04-01

Contact (dun ensemble plusieurs contacts) fermeture


anticipe par rapport aux autres contacts fermeture de
lensemble.

Make contact (of a multiple contact assembly) which is


early to close relative to the other make contacts of the
assembly

07-04-02

Contact (dun ensemble plusieurs contacts) fermeture


tardive par rapport aux autres contacts fermeture de
lensemble.

Make contact (of a multiple contact assembly) which is


late to close relative to the other make contacts of the
assembly

07-04-03

Contact (dun ensemble plusieurs contacts) ouverture


tardive par rapport aux autres contacts ouverture de
lensemble.

Break contact (of a multiple contact assembly) which is


late to open relative to the other break contacts of the
assembly

07-04-04

Contact (dun ensemble plusieurs contacts) ouverture


anticipe par rapport aux autres contacts ouverture de
lensemble.

Break contact (of a multiple contact assembly) which is


early to open relative to the other break contacts of the
assembly

EN 60617-7:1996

10

Section 4 Contacts fonctionnement dcal

BSI 10-1998

BSI 10-1998

Section 5 Contacts avec opration retarde


5.1

Section 5 Contacts with delayed operation

Voir les symboles 02-12-05 et 02-12-06. La fermeture et louverture est retarde


par rapport lopration dactivation ou la disparition dactivation.
Le mouvement est retard dans la direction vers le centre de larc (effet de
parachute). Dans le symbole de contact il est permis de figurer le symbole de
retard du ct qui convient le mieux lapplication et la mise en place des
dsignations de matriel.
No.

Symbole

Symbol

5.1

See symbols 02-12-05 and 02-12-06. Closing and opening of the contact is delayed
with respect to the activation or deactivation operation. The movement is
delayed in the direction towards the centre of the arc (parachute effect). The
symbol for delayed action may be drawn on that side of the contact symbol which
is most suitable for the application and for the placing of item designations.

Lgende

Description

Contact fermeture, retard lorsque le dispositif


contenant le contact est activ

Make contact, delayed when the device containing the


contact is being activated

07-05-02

Contact fermeture, retard lorsque le dispositif


contenant le contact nest plus activ

Make contact, delayed when the device containing the


contact is being de-activated

07-05-03

Contact ouverture, retard lorsque le dispositif


contenant le contact est activ

Break contact, delayed when the device containing the


contact is being activated

07-05-04

Contact ouverture, retard lorsque le dispositif


contenant le contact nest plus activ

Break contact, delayed when the device containing the


contact is being de-activated

07-05-05

Contact fermeture, retard la fois lorsque le dispositif Make contact, delayed both when the device containing
contenant le contact est activ et lorsquil nest plus activ the contact is being activated and when it is being
de-activated

11

EN 60617-7:1996

07-05-01

Symbole

Symbol

Lgende
EXAMPLE:

Ensemble dun groupe de contacts comprenant un contact


fermeture non-retard, un contact fermeture retard
lorsque le dispositif contenant les contacts est activ et un
contact ouverture retarde lorsque le dispositif nest plus
activ

Contact assembly with one make contact not delayed, one


make contact delayed when the device containing the
contact is being activated and one break contact delayed
when the device containing the contact is being
de-activated

Section 6 Contacts retour automatique et


position maintenue
6.1

Les rgles des symboles 07-01-07 et 07-01-08 sont applicables.


No.

Symbole

Symbol

Description

EXEMPLE:

Section 6 Automatic return and non-automatic


return contacts
6.1

The rules with symbols 07-01-07 and 07-01-08 apply.

Lgende

Description

07-06-01

Contact fermeture, retour automatique

Make contact with automatic return

07-06-02

Contact fermeture, sans retour automatique


Contact fermeture, position maintenue

Make contact with automatic return


Stay put make contact

07-06-03

Contact ouverture, retour automatique

Break contact with automatic return

07-06-04

Contact deux directions avec position mdiane de


coupure, retour automatique dune position figure
gauche et sans retour automatique dans la position
oppose

Two-way contact with off-position in the centre and


automatic return from one position (shown to the left),
and without automatic return in the opposite position

EN 60617-7:1996

12

No.
07-05-06

BSI 10-1998

BSI 10-1998

Chapitre III: Auxiliaires de commande, appareils


mcaniques de connexion et dmarreurs

Chapter III: Switches, switchgear and starters

III.1

Les appareils action pousser ou tirer sont le plus souvent retour


automatique. II nest donc pas ncessaire de complter leur symbole par celui de
retour automatique (02-12-07). En revanche, le symbole de crantage (02-12-08)
doit tre figur dans les cas o un dispositif de non-retour existe.

III.1

Devices with push or pull operation most often have automatic return. It is
therefore not necessary to show the automatic return symbol (02-12-07). On the
other hand, a detent symbol (02-12-08) shell be shown in those cases where
non-return exists.

III.2

Les appareils commands par rotation ne sont pas, le plus souvent, retour
automatique. II nset donc pas ncessaire de complter leur symbole par celui de
crantage (02-12-08). En revanche, il convient que le symbole de retour
automatique (02-12-07) soit figur dans les cas o un retour automatique existe.

III.2

Devices operated by turning do not usually have automatic return. It is therefore


not necessary for the detent symbol (02-12-08) to be shown. On the other hand,
the automatic return symbol (02-12-07) should be shown in those cases where an
automatic return exists.

Section 7 Commutateurs unipolaires


No.

Symbole

Symbol

Section 7 Single-pole switches


Lgende

Description

Contact fermeture commande manuelle, symbole


gnral

Manually operated switch, general symbol

07-07-02

Interrupteur bouton-poussoir fermeture et retour


automatique

Push-button switch make contact and automatic return

07-07-03

Interrupteur tirette, comportant un contact fermeture


et retour automatique

Pull-switch with make contact and automatic return

07-07-04

Interrupteur bouton rotatif, comportant un contact


fermeture sans retour automatique

Turn-switch with make contact without automatic return

13

EN 60617-7:1996

07-07-01

Symbole

Symbol

Lgende

Description

Interrupteur bouton-poussoir, comportant un contact


fermeture manoeuvre positive de fermeture (par
exemple: alarme)

Push-button switch with positive operation of the make


contact (for example: alarm)

07-07-06

Interrupteur darrt durgence (actionn par bouton


type coup de poing), comportant un contact ouverture,
et position maintenue, manoeuvre positive
douverture

Emergency stop switch (mushroom-head activated) with


positive opening operation of the break contact and
maintain position

EN 60617-7:1996

14

No.
07-07-05

BSI 10-1998

BSI 10-1998

Section 8 Interrupteurs de position

Section 8 Position switches

Si, dans un ensemble de contacts, lun ou plusieurs dentre eux sont construits pour avoir
une manoevre positive, la positivit peut concemer:

soit louverture de contact(s) ouverture (par exemple 07-08-04: Interrupteur de


position et 07-07-06: Interrupteur darrt durgence), ou la fermeture dun
contact fermeture (par exemple 07-07-05: Alarme), et

soit tous les contacts, soit seulement des contacts particuliers (voir par
exemple 07-13-14) mais

pas la fois louverture et la fermeture dun mme contact.

Where in a set of contacts one or some of the them are constructed to have positive
opening operation this positivity may concern:

either the opening of break contact(s) (for example 07-08-04: Position switch and
07-07-06: Emergency stop switch) or the closing of a make contact (for example
07-07-05: Alarm) and

either all the contacts or only particular contacts (see for example 07-013-14) but

No.

Symbole

Symbol

not both the opening and the closing of the same contact.

Lgende

Description

07-08-01

Interrupteur de position, contact fermeture

Position switch, make contact

07-08-02

Interrupteur de position, contact ouverture

Position switch, break contact

07-08-03

Interrupteur de position deux circuits distincts actionn


mcaniquement dans les deux sens

Position switch, mechanically operated in both directions


with two separate circuits

07-08-04

Interrupteur de position comportant un contact


ouverture manoeuvre positive douverture

Position switch with positive opening operation of the


break contact

EN 60617-7:1996

15

No.
07-09-01

Symbole

Symbol

Section 9 Temperature sensitive switches

Lgende
Interrupteur fonctionnant sous leffet de la temprature,
contact fermeture
Q peut tre remplac par les valeurs de temprature de
fonctionnement

07-09-02

Interrupteur fonctionnant sous leffet de la temprature,


contact ouverture
La note du symbole 07-09-01 est applicable

07-09-03

07-09-04

Description
Temperature sensitive switch, make contact
Q may be replaced by the operating temperature
conditions

Temperature sensitive switch, break contact


The note with symbol 07-09-01 applies

Interrupteur agissant par effet thermique direct (par


exemple, bilame) contact ouverture

Self-operating thermal switch (for example, bimetal)


break contact

II est important dtablir une distinction entre le contact


ainsi reprsent et le contact dun relais thermique,
pouvant tre ainsi figur en reprsentation dveloppe:

It is important to distinguish between a contact as shown


and a contact of a thermal relay, which in detached
representation may be shown as follows:

Tube gaz avec bilame


Starter pour lampe fluorescente

Gas discharge tube with thermal element


Starter for fluorescent lamp

EN 60617-7:1996

16

Section 9 Interrupteurs fonctionnant sous leffet de


la temprature

BSI 10-1998

BSI 10-1998

Section 10 Contacts agissant sous leffet dune


variation de vitesse, commutateurs mercure et de
nivellement

Section 10 Speed change sensitive contacts,


mercury and levelling switches

Transfr en annexe A1

Transferred to annex A1

Section 11 Exemples de commutateurs plusieurs


directions incluant les auxiliaires de commande

Section 11 Examples of multi-position switches,


including control switches

11.1

Voir III.1 section 7.

11.1

See III.1 in section 7.

11.2

Voir III.2 section 7.

11.2

See III.2 in section 7.

No.
07-11-01

Symbole

Symbol

Lgende

Description

Commutateur commande par levier trois positions,

Lever-operated switch, three positions,

avec position haute accrochage et position basse


retour automatique en position intermdiaire, figur
avec ses bornes.

locking in the upper position and with automatic return


from the lower position to the middle one, shown with
terminals

EN 60617-7:1996

17

Symbole

Symbol

Lgende

Description

Commutateur commande par bouton

Button-operated switch

Un ensemble de contacts est actionn par pression sur le


bouton (avec retour automatique) et un autre ensemble
de contacts par rotation du bouton (sans retour
automatique), figur avec ses bornes.

One set of contacts is operated by pushing the button


(automatic return) and another set by turning it
(non-automatic return), shown with terminals.

Laccolade indique quil sagit du mme organe de


commande.

The bracket indicates that there is only one actuator.

EN 60617-7:1996

18

No.
07-11-02

BSI 10-1998

BSI 10-1998

No.
07-11-03

Symbole

Symbol

Lgende
Commutateur commande par bouton

Description
Button-operated switch

Le mme ensemble de contacts est actionn, soit par


The same set of contacts may be operated in two different
rotation du bouton (avec accrochage), soit par pression ( ways, either by turning (with non-automatic return) or
retour automatique), figur avec ses bornes.
pushing (with automatic return), shown with terminals.

07-11-04

Commutateur plusieurs directions (multidirectionnel),


reprsent avec 6 directions

Multi-position switch (six positions shown)

EN 60617-7:1996

19

Symbole

Symbol

Lgende
Commutateur plusieurs directions (multidirectionnel)

Description
Multi-position switch

A utiliser pour un petit nombre de directions (4 directions To be used with a small number of
figures).
positions (4 positions shown).

07-11-06

07-11-07

Exemple avec diagramme de position

Example with position diagram

II est parfois utile dindiquer la fonction de chaque


position du commutateur en compltant, par un texte, le
diagramme de position. II est galement possible
dindiquer les limites imposes mcaniquement au
mouvement du dispositif de commande, comme indiqu
dans les exemples suivants:

It is sometimes convenient to indicate the purpose of each


switch position by adding text to the position diagram. It
is also possible to indicate limitations of movement of the
operating device as in the examples which follow:

Le dispositif de commande (par exemple un


bouton rotatif) ne peut tre dplac quentre
les position 1 et 4 dans les deux sens

The operating device (for example


handwheel) can be turned only from
positions 1 to 4 and back

Le dispositif de commande ne peut tourner


que dans le sens des aiguilles dune montre

The operating device can be turned in the


clockwise direction only

Le dispositif de commande peut tre dplac


volont, dans le sens des aiguilles dune
montre, mais ne peut tre dplac dans le
sens inverse quentre les positions 3 et 1

The operating device can be turned in the


clockwise direction without limitation and
may be turned in the counter-clockwise
direction only between positions 3 and 1

Commutateur quatre positions, commande manuelle,


avec quatre circuits indpendants

Four-position switch, manually operated, with four


independent circuits

EN 60617-7:1996

20

No.
07-11-05

BSI 10-1998

BSI 10-1998

No.
07-11-08

07-11-09

07-11-10

07-11-11

Symbole

Symbol

Lgende

Description

Elment de commutateur quatre directions

Single-pole, four-position switch

Aucun circuit ne peut tre raccord sur la deuxime


direction.

The second position cannot be connected.

Elment de commutateur six directions

Single-pole six-position switch

Chevauchement de la partie mobile pendant le passage


dune direction la suivante.

A wiper bridges only while passing from one position to


another.

Elment de commutateur multidirectionnel

Single-pole multi-position switch

Chevauchement de la partie mobile sur trois directions


conscutives dans chaque position.

A wiper bridges three consecutive terminals in each


switch position.

Commutateur multidirectionnel

Multi-position switch

Chevauchement de la partie mobile sur quatre directions A wiper bridges three non-consecutive terminals in each
conscutives sauf la troisime. Figur en omettant la
position, but omits one intermediate terminal in each
connexion lune des bornes.
switch position.

07-11-12

Elment de commutateur multidirectionnel de mise en


parallle ( effet cumulatif)

Single-pole multi-position switch for cumulative parallel


switching

EN 60617-7:1996

21

Symbole

Symbol

Lgende

One pole of a six-position multi-pole switch

Dans llment reprsent, lors du passage de la


position 2 la position 3, la fermeture se produit avant
celles correspondantes des autres lments et lors du
passage de la position 5 la position 6, louverture se
produit aprs celles correspondantes des autres
lments. Lorsque la partie mobile est dplace dans
lautre sens, la fermeture avance devient une ouverture
retarde et louverture.

The pole shown makes earlier than the other poles when
the wiper moves from position 2 to 3 and breaks later
than the other poles when the wiper moves from position
5 to 6. When the wiper moves in the opposite direction the
early make becomes a late break and the late break
becomes an early make.

Section 12 Symboles fonctionnels pour


commutateurs complexes
12.1

Section 12 Block symbols for complex switches

II y a de nombreuses faons de raliser mcaniquement des fonctions complexes


de commutateurs tambour, densembles de contacts actionns par cames, etc. II
y a aussi de nombreuses faons pour symboliser les fonctions de commutation
sur les schmas des circuits (voir CEI 1082-2). Des tudes ont montr quil ny a
pas un systme unique de symbolisation qui soit suprieur aux autres dans tous
les cas dapplication. II convient que le systme employ soit choisi suivant
lusage de schma et le degr de complexit du commutateur que lon dsire
symboliser.

12.1

Pour cette raison, la prsente section propose seulement une des mthodes
possibles de symbolisation des commutateurs complexes. Pour faciliter la
comprhension, chaque exemple donn contient un dessin schmatique de la
ralisation de lappareil symbolis. Cette mthode utilise un symbole gnral
pour un commutateur complexe complt par un tableau des connexions. Deux
exemples sont reprsents.
No.
07-12-01

Symbole

Symbol

Description

Elment de commutateur six directions

There are many ways in which complex switching functions can be achieved
mechanically, for example by rotary wafer switches, slide switches, drum
controllers, cam-operated contact assemblies, etc. There are also many ways in
which the switching functions may be symbolized on circuit diagrams
(see IEC 1082-2). Studies have shown that there is no unique system of
symbolization which is superior in every application. The system employed
should be chosen with due regard to the purpose of the diagram and the degree of
complexity of the switching device that it is desired to symbolize.
Therefore this section presents only one of the possible methods for symbolizing
complex switches. To facilitate understanding, each example includes a
constructional drawing of the device symbolized. The method shown here uses a
general symbol for a complex switch which must be supplemented by a table of
connections. Two examples are shown.

Lgende
Commutateur complexe, symbole gnral

Description
Complex switch, general symbol

EN 60617-7:1996

22

No.
07-11-13

BSI 10-1998

BSI 10-1998

No.

Symbole

Symbol

07-12-02

Lgende

Description

EXEMPLES:

EXAMPLES:

Commutateur galette, 18 positions six bornes,


repres ici A F, ralis comme indiqu ci-dessous
(commutateur reprsent en position 1)

18-position rotary wafer switch with six terminals, here


designated A to F, constructed as shown below (switch
shown in position 1)

Les lettres figures ne font pas partie du symbole.

The letters shown are not part of the symbol.

Tableau des connexions


Table of connections
Direction
Position

Bornes connectes
Interconnections
of terminals
A B C D E F

1
2
3
4
5
6
7
8
9
10
11
12
13
14
16
17
18

23

EN 60617-7:1996

15

Symbole

Symbol

Lgende

Description

Commutateur tambour six positions et cinq bornes,


ralis comme indiqu ci-dessous:

Six-position rotary drum switch with 5 terminals,


constructed as shown below:

Les symboles (+ O) du tableau indiquent les bornes qui


sont respectivement connectes entre elles dans nimporte
quelle position (position de repos ou position
intermdiaire) de lorgane de commande du commutateur,
cest dire que les bornes, ayant le mme symbole qui les
marque, par exemple +, sont relies entre elles.

The symbols (+ O) in the table indicate the terminals


that are connected together at any position (rest-position
or intermediate position) of the switch, i.e. terminals
having the same indicating symbols, for example +, are
interconnected.

Tableau des connexions


Table of connections
Bornes connectes
Interconnections
of terminals

Direction
Position
A
1

+
+
+
+

+
+
+
+
+
+
+

+
+
+

O
O
O
O

O
O
O
O

+
+

Where additional symbols are required, the characters


Si dautres symboles sont ncessaries, on utilisera les
caractres courants sur une machine crire tels que x, =. available on a typewriter should be used, for example x, =.
Les lettres figures ne font pas partie du symbole.

The letters shown are not part of the symbol.

EN 60617-7:1996

24

No.
07-12-03

BSI 10-1998

BSI 10-1998

Section 13 Dispositifs de commutation de


puissance
No.
07-13-01

Symbole
Utiliser le symbole
07-02-01 ou 07-02-02
Use symbol
07-02-01 or 07-02-02

Symbol

Section 13 Power switching devices


Lgende

Description

Interrupteur

Switch

07-13-02

Contacteur
Contact principal fermeture dun contacteur
(Contact ouvert dans la position non active)

Contactor
Main make contact of a contactor
(Contact opened in the unoperated position)

07-13-03

Discontacteur dclanchement automatique provoqu Contactor with automatic tripping initiated by a


par un relais de mesure ou dclencheur incorpors
built-in measuring relay or release

07-13-04

Rupteur
Contact principal ouverture dun contacteur
(contact ferm dans la position de
non-fonctionnement)

Contactor
Main break contact of a contactor
(contact closed in the unoperated position)

07-13-05

Disjoncteur

Circuit breaker

EN 60617-7:1996

25

Symbole

Symbol

Lgende

Description

Sectionneur

Disconnector (isolator)

07-13-07

Sectionneur deux directions avec position de


sectionnement mdiane

Two-way disconnector (isolator) with off-position in


the centre

07-13-08

Interrupteur-sectionneur

Switch-disconnector (on-load isolating switch)

07-13-09

Interrupteur-sectionneur avec ouverture automatique


provoque par relais de mesure ou dclencheur
incorpors

Switch-disconnector with automatic tripping


initiated by a built-in measuring relay or release

07-13-10

Sectionneur, commande manuelle, avec dispositif de


blocage

Disconnector (isolator) with blocking device,


manually operated

EN 60617-7:1996

26

No.
07-13-06

BSI 10-1998

BSI 10-1998

No.
07-13-11

Symbole

Symbol

Lgende
Mcanisme dclenchement libre

Trip-free mechanism

Lignes tiretes reprsentant les diverses parties du


systme de liaisons doivent tre disposes de la faon
suivante:

Dashed lines representing the various parts of the


linkage system shall be located in the following way:

Venant de
lactionneur de
fermeture et
douverture

07-13-12

Description

Vers les
contacts
principaux et
auxiliaires
associs

From the
operating
means for
opening and
closing

To associated
main and
auxiliary
contacts

* Venant de lactionneur ayant une fonction


douverture; deux emplacements au choix figurs.

* From actuator having an overriding opening


function; two alternative locations shown.

EXEMPLE:
Appareil mcanique de connexion tripolaire
commande motorise ou manuelle, avec mcanisme
dclenchement libre et:
dclencheur thermique de surcharge
dclencheur maximum de courant
dclencheur manuel avec crantage
organe de tlcommande du dclenchement
un contact auxiliaire fermeture et un contact
auxiliarie ouverture

EXAMPLE:
Three-pole mechanical switching device, operated by
motor or manually, with trip-free mechanism, and:
thermal overload release
overcurrent release
hand release with detent
coil for remote release
one make and one break auxiliary contact

EN 60617-7:1996

27

No.

Symbole

Symbol

Description

Appareil mcanique de connection tripolaire


commande motorise avec une mmoire ressort et:
trois dclencheurs de surcharge
trois dclencheurs maximum de courant
dclencheur manuel
organe de tlcommande du dclenchement
trois contacts fermeture principaux
un contact auxiliarie fermeture et un contact
auxiliaire ouverture
un interrupteur de position pour dmarrer et arrter
le fonctionnement du moteur

Three-pole mechanical switching device operated by


motor with a spring storage and:
three overload releases
three overcurrent releases
hand release
coil for remote release
three main make contacts
one make and one break auxiliary contact
one position switch to start and stop the operation
of the motor

07-13-14

Interrupteur de scurit, comportant trois contacts


principaux manoeuvre positive douverture et un
contact auxiliaire fermeture sans manoeuvre
positive

Switch with positive opening operation of the three


main break contacts and the auxiliary make contact
without positive operation

EN 60617-7:1996

28

Lgende

07-13-13

BSI 10-1998

BSI 10-1998

Section 14 Dmarreurs de moteurs


No.

Symbole

07-14-01

Symbol

Section 14 Block symbols for motor starters


Lgende

Description

Dmarreur de moteur, symbole gnral

Motor starter, general symbol

Des symboles distinctifs peuvent tre figurs lintrieur


du symbole gnral, pour indiquer des type particuliers de
dmarreurs. Voir symboles 07-14-05, 07-14-07
et 07-14-08.

Qualifying symbols may be shown inside the general


symbol to indicate particular types of starters. See
symbols 07-14-05, 07-14-07 and 07-14-08.

Dmarreur oprant par chelons

Starter operating in steps

Le nombre dchelons peut tre indiqu.

The number of steps may be indicated.

Dmarreur-rgleur

Starter-regulator

Transfer Annexe A: 07-A2-01

Transferred to Annex A: 07-A2-01

07-14-05

Dmarreur direct par contacteurs pour changer le sens de


marche dun moteur

Direct-on-line starter with contactor for reversing the


rotation of a motor

07-14-06

Dmarreur toile-triangle

Star-delta starter

07-14-02

07-14-03

07-14-04

supprim
deleted

EN 60617-7:1996

29

Symbole

Symbol

Lgende

Description

Dmarreur par autotransformateur

Starter with auto-transformer

07-14-08

Dmarreur-rgleur par thyristors

Starter-regulator with thyristors

EN 60617-7:1996

30

No.
07-14-07

BSI 10-1998

BSI 10-1998

Chapitre IV: Relais de tout-ou-rien


Section 15 Organes de commande
No.
07-15-01

07-15-02

Symbole
Forme 1
Form 1

Symbol

Chapter IV: All-or-nothing relays


Section 15 Operating devices
Lgende

Description

Organe de commande, symbole gnral


Bobine de relais, symbole gnral

Operating device, general symbol


Relay coil, general symbol

Un organe de commande dun relais comportant plusieurs


enroulements peut tre figur en ajoutant linterieur du
cadre le nombre appropri de traits obliques
(voir 07-15-04).

Operating devices with several windings may be indicated


by inclusion inside the outline of the appropriate number
of inclined strokes (see 07-15-04).

EXEMPLES:

EXAMPLES:

Organe de commande avec deux enroulements spars,


reprsentation assemble

Operating device with two separate windings, attached


representation

Organe de commande avec deux enroulements spars,


reprsentation dveloppe

Operating device with two separate windings, detached


representation

Forme 2
Form 2

Forme 1
Form 1

07-15-04

Forme 2
Form 2

07-15-05

Forme 1
Form 1

07-15-06

Forme 2
Form 2

31

EN 60617-7:1996

07-15-03

Symbole

Symbol

Lgende

Description

Organe de commande dun relais mise au repos retarde Relay coil of a slow-releasing relay

07-15-08

Organe de commande dun relais mise au travail


retarde

Relay coil of a slow-operating relay

07-15-09

Organe de commande dun relais mise au travail et mise


au repos retardes

Relay coil of a slow-operating and


slow-releasing relay

07-15-10

Organe de commande dun relais rapide ( mise au travail


et mise au repos rapides)

Relay coil of a high speed relay (fast-operating and


fast-releasing)

07-15-11

Organe de commande dun relais insensible au courant


alternatif

Relay coil of a relay unaffected by alternating current

07-15-12

Organe de commande dun relais courant alternatif

Relay coil of an alternating current relay

EN 60617-7:1996

32

No.
07-15-07

BSI 10-1998

BSI 10-1998

No.

Symbole

Symbol

Lgende

Description

07-15-13

Organe de commande dun relais rsonance mcanique

Relay coil of a mechanically resonant relay

07-15-14

Organe de commande dun relais verrouillage


mcanique

Relay coil of a mechanically latched relay

EN 60617-7:1996

33

Symbole

Symbol

Lgende

Description

Organe de commande dun relais polaris

Relay coil of a polarized relay

Des points sont utiliss pour indiquer la relation entre la


direction du courant circulant dans lenroulement dun
relais polaris et le mouvement dun lment de contact
avec la convention suivante.

Polarity dots () may be used to indicate the relationship


between the direction of the current through the winding
of a polarized relay and the movement of the contact arm
according to the following connection.

Quand la borne de lenroulement de commande identifie


par un point est positive par rapport lautre borne, le
contact se dplace ou tend se dplacer vers la position
marque dun point.

When the winding terminal identified by the polarity dot


is positive with respect to the other winding terminal, the
contact arm moves or tends to move towards the position
marked with the dot.

EXEMPLES:

EXAMPLES:

Relais polaris fonctionnant pour un seul sens du courant


dans la bobine et retournant en position de repos aprs
coupure

Polarized relay, self restoring, operating for only one


direction of current in the winding

07-15-17

Relais polaris position mdiane fonctionnant pour les


deux sens du courant dans la bobine et retournant la
position mdiane aprs coupure

Polarized relay with neutral position, self restoring,


operating for either direction of current in the winding

07-15-18

Relais polaris deux positions stables

Polarized relay with two stable positions

07-15-16

EN 60617-7:1996

34

No.
07-15-15

BSI 10-1998

BSI 10-1998

No.

Symbole

07-15-19

Forme 1
Form 1

07-15-20

Forme 2
Form 2

Symbol

Lgende

Description

Organe de commande dun relais rmanence

Relay coil of a remanent relay

07-15-21

Organe de commande dun relais thermique

Operating device of a thermal relay

07-15-22

Organe de commande dun relais lectronique

Operating device of an electronic relay

EN 60617-7:1996

35

No.
07-16-01

Symbole

Symbol

Chapter V: Measuring relays and related devices


Section 16 Block symbol and qualifying symbols
Lgende

Relais de mesure
Dispositif apparent un relais de mesure

Description
Measuring relay
Device related to a measuring relay

1. Lastrisque doit tre remplac par une ou plusieurs


1. The asterisk shall be replaced by one or more letters or
lettres ou par un ou plusieurs symboles distinctifs
qualifying symbols indicating the parameters of the
prcisant les paramtres du dispositif dans lordre suivant: device, in the following order:
grandeur caractristique et son mode de variation;
sens de transit de lnergie;
domaine dajustement;
rapport de retour
action retarde;
valeur de la temporisation.

characteristic quantity and its mode of variation;


direction of energy flow;
setting range;
re-setting ratio;
delayed action;
value of time delay.

2. Les symboles littraux des grandeurs caractristiques


doivent tre en accord avec les normes existantes, par
exemple CEI 27 et ISO 31.

2. Letter symbols for characteristic quantities shall be in


accordance with established standards, for example,
IEC 27 and ISO 31.

3. Un chiffre indiquant le nombre dlments de mesure


3. A figure giving the number of similar measuring
similaires peut tre ajout dans le symbole comme indiqu elements may be included in the symbol as shown in
dans lexemple 07-17-05.
example 07-17-05.
4. Le symbole peut tre utilis soit comme symbole
fonctionnel reprsentant lensemble dun dispositif, soit
comme symbole dorgane de commande du dispositif.

4. The symbol may be used as a functional symbol


representing the whole of the device, or as a symbol
representing only the actuating element of the device.

07-16-02

Tension de dfaut la masse

Voltage failure to frame


(frame potential in case of fault)

07-16-03

Tension rsiduelle

Residual voltage

EN 60617-7:1996

36

Chapitre V: Relais de mesure et dispositifs


apparents
Section 16 Symbole fonctionnel et symboles
distinctifs

BSI 10-1998

BSI 10-1998

No.

Symbole

Symbol

Lgende

Description

07-16-04

Courant de retour

Reverse current

07-16-05

Courant diffrentiel

Differential current

07-16-06

Pourcentage de courant diffrentiel

Percentage differential current

07-16-07

Courant de dfaut la terre

Earth fault current

07-16-08

Courant dans le conducteur neutre

Current in the neutral conductor

07-16-09

Courant entre points neutres de deux systmes


polyphass

Current between neutrals of two polyphase systems

07-16-10

Puissance pour langle de phase a

Power at phase angle a

07-16-11

Caractristique de retard temps inverse

Inverse time-lag characteristic

EN 60617-7:1996

37

No.

Symbole

Symbol

Section 17 Examples of measuring relays


Lgende

Description

07-17-01

Relais manque de tension

No voltage relay

07-17-02

Relais retour de courant

Reverse current relay

07-17-03

Relais minimum de puissance active

Underpower relay

07-17-04

Relais maximum de courant, action retarde

Delayed overcurrent relay

07-17-05

Relais maximum de courant deux lments de mesure,


avec domaine dajustement de 5 A 10 A

Overcurrent relay with two measuring elements and a


setting range from 5 A to 10 A

EN 60617-7:1996

38

Section 17 Exemples de relais de mesure

BSI 10-1998

BSI 10-1998

No.
07-17-06

Symbole

Symbol

Lgende

Description

Relais maximum de puissance ractive:

Overpower relay for reactive power:

transit de lnergie vers les barres


valeur de fonctionnement 1 Mvar
retard ajustable de 5 s 10 s

energy-flow towards the busbars


operating value 1 Mvar
time-lag adjustable from 5 s to 10 s

Relais minimum de tension:

Undervoltage relay:

domaine dajustement de 50 V 80 V
pourcentage de retour 130%

setting range from 50 V to 80 V


resetting ratio 130%

07-17-08

Relais maximum et minimum de courant, figur avec


les limites 3 A et 5 A.

Current relay with maximum and minimum settings,


shown with limits 3 A and 5 A.

07-17-09

Relais minimum dimpdance

Under-impedance relay

07-17-10

Relais de dtection de court-circuit entre spires

Relay detecting short-circuits between windings

07-17-07

EN 60617-7:1996

39

Symbole

Symbol

Lgende

Description

Relais de dtection de coupure denroulement

Divided-conductor detection relay

07-17-12

Relais de dtection de dfaillance de phase dans un


systme triphas

Phase-failure detection relay in a three-phase system

07-17-13

Relais de dtection de rotor bloqu, actionn par la


mesure de courant

Locked-rotor detection relay operating by current


measuring

07-17-14

Relais maximum de courant avec deux sorties, lune est


active lorsque le courant dpasse cinq fois la valeur
dajustement, lautre est active en fonction du rglage du
dispositif selon une caractristique de retard temps
inverse

Overcurrent relay with two outputs, one is active when


the current is above five times the setting value, the other
is active depending on the inverse time-lag characteristic
setting of the device

EN 60617-7:1996

40

No.
07-17-11

BSI 10-1998

BSI 10-1998

Section 18 Autres dispositifs


No.

Symbole

Symbol

Section 18 Other devices


Lgende

Description

07-18-01

Relais Buchholz

Buchholz protective device (gas relay)

07-18-02

Dispositif de renclenchement automatique


Relais de renclenchement automatique

Device for auto-reclosing


Auto-reclose relay

EN 60617-7:1996

41

No.

Symbole

Symbol

Chapter VI: Proximity and touch-sensitive devices


Section 19 Sensors and detectors

Lgende

Description

07-19-01

Capteur sensible une proximit

Proximity sensor

07-19-02

Dispositif sensible une proximit, symbole fonctionnel


Le mode daction peut tre indiqu.

Proximity sensing device, block symbol


The method of operating may be indicated.

07-19-03

EXEMPLE:

EXAMPLE:

Dtecteur capacitif de proximit fonctionnant lapproche


dun matriau solide

Capacitive proximity detector operating on the approach


of solid material

Capteur sensible leffleurement

Touch sensor

07-19-04

EN 60617-7:1996

42

Chapitre VI: Dispositifs sensibles une proximit ou


leffleurement
Section 19 Capteurs et dtecteurs

BSI 10-1998

BSI 10-1998

Section 20 Dispositifs contacts


No.

Symbole

Symbol

Section 20 Switches
Lgende

Description

07-20-01

Dispositif sensible leffleurement avec contact


fermeture

Touch sensitive switch, make contact

07-20-02

Dispositif sensible une proximit avec contact


fermeture

Proximity switch, make contact

07-20-03

Dispositif sensible une proximit, command


lapproche dun aimant avec contact fermeture

Proximity switch, operated on the approach of a magnet,


make contact

07-20-04

Dispositif sensible une proximit, command


lapproche de fer avec contact ouverture

Proximity switch, operated on the approach of iron, break


contact

EN 60617-7:1996

43

No.

Symbole

Symbol

Chapter VII: Protective devices


Section 21 Fuses and fuse-switches
Lgende

Description

07-21-01

Fusible, symbole gnral

Fuse, general symbol

07-21-02

Fusible dont lextrmit restant sous tension aprs


fonctionnement est indique par un trait renforc

Fuse with the side, that remains live after blowing,


indicated by a thick line

07-21-03

Fusible percuteur ( liaison mcanique)

Fuse with mechanical linkage (striker fuse)

07-21-04

Fusible percuteur avec contact de signalisation point


commun

Fuse with alarm contact, three terminals

07-21-05

Fusible percuteur avec circuit de signalisation distinct

Fuse with separate alarm circuit

EN 60617-7:1996

44

Chapitre VII: Dispositifs de protection


Section 21 Fusibles et interrupteurs fusibles

BSI 10-1998

BSI 10-1998

No.

Symbole

Symbol

Lgende

Description

07-21-06

Interrupteur triphas ouverture automatique par lun


quelconque des fusibles percuteur

Three-pole switch with automatic release by any one of


the strike fuses

07-21-07

Fusible interrupteur

Fuse-switch

07-21-08

Fusible sectionneur

Fuse-disconnector (fuse isolator)

07-21-09

Fusible interrupteur-sectionneur

Fuse switch-disconnector (on-load isolating fuse switch)

EN 60617-7:1996

45

No.

Symbole

Symbol

Section 22 Spark gaps and arresters


Lgende

Description

07-22-01

clateur

Spark gap

07-22-02

clateur double

Double spark gap

07-22-03

Parafoudre

Surge diverter
Lightning arrester

07-22-04

Tube gaz limiteur de tension

Protective gas discharge tube

07-22-05

Tube gaz limiteur de tension, symtrique

Symmetric protective gas discharge tube

Section 23 Extincteurs

Section 23 Fire-extinguishers

Transfr lannexe A.3.

Transferred to 3 of annex A

EN 60617-7:1996

46

Section 22 clateurs et parafoudres

BSI 10-1998

BSI 10-1998

Chapitre VIII: Symboles divers


Section 24 Bobines dallumage et indicateurs
drapeau

Chapter VIII: Miscellaneous symbols


Section 24 Igniters and flag-indicators
Transferred to annex A4

Transfr a lannexe A4

Section 25 Interrupteurs statiques


No.
07-25-01

Symbole

Symbol

Section 25 Static switches


Lgende

Interrupteur semiconducteur (statique), symbole


gnral
1. Le petit cercle reprsentant larticulation
(voir CEI 617-7, Chapitre I, rgle 1.2) ne doit pas tre
ajout a ce symbole.
2. Des symboles distincitifs, appropris peuvent tre
ajouts pour prciser la fonction de linterrupteur
semiconducteur, conformment aux sections 2 5.

Description
Static switch, general symbol
1. The small circle representing the hinge point
(see chapter I, general rule 1.2) shall not be added to this
symbol.
2. Appropriate qualifying symbols may be added to denote
the function of the static switch, according to
sections 2 to 5.

07-25-02

Contacteur semiconducteur (statique)

Static (semicondutor) contactor

07-25-03

Interrupteur semiconducteur, (statique) passage du


courant dans un seul sens

Static switch, passing current in one direction only

EN 60617-7:1996

47

No.
07-26-01

Symbole

Symbol

Section 26 Static switching devices


Lgende

Relais statique, symbole gnral reprsent avec un


interrupteur semiconducteur, contact fermeture

Description
Static relay, general symbol, shown with semiconductor
make contact

Un symbole distinctif peut tre ajout pour prciser le type A qualifying symbol to denote the type of actuating
de llment de commande.
element may be added.

07-26-02

07-26-03

07-26-04

EXEMPLE:

EXAMPLE:

Relais statique command par diode


lectro-luminescente et reprsent avec un contact
fermeture semiconducteur

Static relay with light emitting diode as actuator shown


with make contact semiconductor

EXEMPLE:

EXAMPLE:

Relais thermique de surcharge triphase avec deux


interrupteurs semiconducteur, lun contact
douverture, lautre contact fermeture; lactionneur
ncessite une source dalimentation auxiliaire spare.

Three-pole thermal overload relay with two semiconductor


contacts one semiconductor make contact and one
semiconductor break contact; the actuator needs a
separate auxiliary power supply.

EXEMPLE:

EXAMPLE:

Dispositif de commande semiconducteur avec contact


fermeture semiconducteur

Semiconductor operating device with semiconductor make


contact

EN 60617-7:1996

48

Section 26 Dispositifs statiques de connexion

BSI 10-1998

BSI 10-1998

Section 27 Coupleurs et relais statiques, symboles


fonctionnels
No.
07-27-01

07-27-02

Symbole

Symbol

Section 27 Coupling devices and static relays,


block symbols

Lgende

Description

Coupleur sparation lectrique

Coupling device with electrical separation

1. Lastrisque (*) doit tre remplac par le symbole du


moyen de couplage ou tre omis.

1. The asterisk (*) shall either be replaced by the symbol


for the coupling medium or be omitted.

2. X et Y doivent tre remplacs par les indications


correspondant aux grandeurs concernes ou tre omis.

2. X and Y shall either be replaced by the appropriate


indications for the quantities concerned or be omitted.

3. La double barre peut tre remplace par deux


diagonales.

3. The double solidus may be replaced by a double


diagonal.

EXEMPLE:

EXAMPLE:

Coupleur optique avec sparation lectrique

Optical coupling device with electrical separation

EN 60617-7:1996

49

Annex A (informative) Older symbols

Cette annexe contient une slection de symboles normaliss dans la CEI 617-7 (1983)
qui sont maintenant supprims. Ces symboles figurent ici seulement afin de faciliter la
comprhension des schmas anciens.

This annex contains symbols standardized in IEC 617-7 (1983), which are now deleted.
They are shown here for information purposes only to facilitate the comprehension of
older diagrams.

(Dans cette annexe, les numros de la publication de 1983 sont mis entre parenthses.)

(In this annex the numbering from 1983-edition is quoted in parentheses.)

A1 Contacts agissant sous leffet dune variation


de vitesse, commutateurs mercure et de
nivellement
No.
07-A1-01

Symbole

Symbol

A1 Speed change sensitive contacts, mercury and


levelling switches

Lgende

Description

Interrupteur inertie (actionn par une brusque


dclration)

Inertia switch (operated by sudden deceleration)

Commutateur mercure, trois bornes


Commutateur de nivellement, trois bornes

Mercury switch, three terminals


Levelling switch, three terminals

Commutateur mercure, quatre bornes


Commutateur de nivellement, quatre bornes

Mercury switch, four terminals


Levelling switch, four terminals

(07-10-01)
07-A1-02

(07-10-02)
07-A1-03

(07-10-03)

EN 60617-7:1996

50

Annexe A (informative) Anciens symboles

BSI 10-1998

BSI 10-1998

A2 Dmarreurs de moteurs
No.

Symbole

Symbol

07-A2-01

A2 Block symbols for motor starters


Lgende

Description

Dmarreur avec mise larrt automatique

Starter with automatic release

(07-14-04)

A3 Extincteurs
No.
07-A3-01

Symbole

Symbol

A3 Fire-extinguishers
Lgende

Description

Extincteur une seule commande avec un connecteur

Fire-extinguisher: single head with connector

Extincteur deux commandes avec deux connecteurs

Fire-extinguisher: double head with connectors

(07-23-01)
07-A3-02

(07-23-02)

EN 60617-7:1996

51

No.
07-A4-01

Symbole

Symbol

A4 Igniters and flag-indicators

Lgende

Description

Bobine dallumage haute nergie

Ignition unit, high energy

Allumeur rsistance

Squib igniter

Bougie dallumage

Igniter plug (typical)

Indicateur drapeau command par une bobine

Coil-operated flag indicator

(07-24-01)
07-A4-02

(07-24-02)
07-A4-03

(07-24-03)
07-A4-04

(07-24-04)

EN 60617-7:1996

52

A4 Bobines dallumage et indicateurs drapeau

BSI 10-1998

BSI 10-1998

07-12-02
07-21-05
07-21-04
07-07-05
07-15-12
07-22-03
07-05-06
07-18-02
07-14-07
07-06-03
07-06-01
07-06-02
07-01-07
07-01-05
07-02-04
07-02-03
07-04-04
07-04-03
07-06-03
07-05-03
07-05-04
07-02-09
07-11-09
07-18-01
07-11-02
07-11-03
07-19-03
07-02-04
07-02-05
07-02-06
07-13-05
07-01-02
07-12-01
07-13-02
07-02-09
07-02-08
07-05-06
07-01-07

Contact, automatic tripping function


Contact, break
Contact, break, delayed, device activated
Contact, break, delayed, device de-activated
Contact, break, which is early to open
Contact, break, which is late to open
Contact, break, with automatic return
Contact, change-over break before make
Contact, change-over make before break
Contact, change-over, with off-position in the centre
Contact, circuit breaker function
Contact, contactor function
Contact, disconnector function
Contact, isolating-switch function
Contact, isolator function
Contact, main break, of a contactor
Contact, mainmake, of a contactor
Contact, make
Contact, make, delayed both, device activated and
de-activated
Contact, make, delayed, device activated
Contact, make, delayed, device de-activated
Contact, make, which is early to close
Contact, make, which is late to close
Contact, make, with automatic return
Contact, make, without automatic return
Contact, non-automatic return function
Contact, passing make, closing momentarily during
operation
Contact, passing make, closing momentarily during
operation and release
Contact, passing make, closing momentarily during
release
Contact, position switch function,
Contact, positive operation of a switch
Contact, spring return function
Contact, stay put function
Contact, stay put, make
Contact, switch-disconnector function
Contact, two-way
Contactor

07-01-05
07-02-03
07-05-03
07-05-04
07-04-04
07-04-03
07-06-03
07-02-04
07-02-06
07-02-05
07-01-02
07-01-01
07-01-03
07-01-04
07-01-03
07-13-04
07-13-02
07-02-01
07-05-05
07-05-01
07-05-02
07-04-01
07-04-02
07-06-01
07-06-02
07-01-08
07-03-01
07-03-03
07-03-02
07-01-06
07-01-09
07-01-07
07-01-08
07-06-02
07-01-04
07-06-04
07-13-02

EN 60617-7:1996

53

Annex B (informative)
English alphabetic index
18-position rotary wafer switch
Alarm circuit, separate, fuse
Alarm contact-fuse, three terminals
Alarm, for example, single push-button switch
Alternating current relay, relay coil
Arrester, lightning
Assembly of contacts with delayed operation, contact
Auto-reclose relay
Auto-transformer, motor starter (block symbol)
Automatic return, break contact
Automatic return, make contact
Automatic return, make contact without it
Automatic return-function, contact
Automatic tripping function, contact
Break before make, change over contact
Break contact
Break contact which is early to open
Break contact which is late to open
Break contact with automatic return
Break contact, delayed, device activated
Break contact, delayed, device de-activated
Breaks, two by contact
Bridging, six-position, single pole switch
Buchholz protective device (gas relay)
Button-operated switch, operated by pushing and by
turning
Button-operated switch, operated either by pushing or by
turning
Capacitive proximity detector operating on the approach
of solid material
Change-over break before make contact
Change-over contact with off-position in the centre
Change-over make before break contact
Circuit breaker
Circuit breaker function, contact
Complex switch, general symbol
Contact opened in the unoperated position)
Contact with two breaks
Contact with two makes
Contact, assembly of contacts with delayed operation
Contact, automatic return function

07-13-04
07-01-01
07-13-03
07-27-01
07-27-02
07-11-12
07-16-09
07-16-08
07-05-05
07-05-03
07-05-04
07-05-01
07-05-02
07-05-06
07-17-04
07-18-02
07-16-01
07-13-00
07-16-05
07-22-04
07-13-06
07-13-10
07-13-07
07-17-11
07-22-02
07-04-01
07-04-04
07-16-07
07-15-22
07-07-06
07-07-06

BSI 10-1998

07-16-02
07-09-04
07-11-07
07-01-02
07-01-07
07-01-05
07-01-01
07-01-03
07-01-04

Function, isolator, disconnector


Function, non-automatic return
Function, position switch
Function, positive operation of a switch
Function, positive switch operation
Function, spring return
Function, stay put
Function, switch-disconnector (isolating-switch)
Function, tripping, automatic
Fuse isolator
Fuse switch-disconnector
Fuse with alarm contact, three terminals
Fuse with mechanical linkage
Fuse with separate alarm circuit
Fuse, general symbol
Fuse-disconnector
Fuse-switch
Fuses, three-pole switch with automatic release by any
one of the striker fuses
Gap, spark
Gas discharge tube with thermal element
Gas discharge tube, protective
Gas relay
High speed relay (fast-operating and fast-releasing),
relay coil
Inverse time-lag characteristic
Iron-approaching-operated proximity switch, brake
contact
Isolating-switch function, contact
Isolator
Isolator function, contact
Isolator, manually operated disconnector
Isolator, two-way
Latched relay, mechanically, relay coil
Late to close make contact
Late to open break contact
Lever-operated switch
Light emitting diode as actuator, static relay
Lightning arrester
Limit switch with positive opening operation of the
break contact
Limit switch, break contact
Limit switch, make contact

07-01-03
07-01-08
07-01-06
07-01-09
07-02-01
07-01-07
07-01-08
07-01-04
07-01-05
07-21-08
07-21-09
07-21-04
07-21-03
07-21-05
07-21-01
07-21-08
07-21-07
07-21-06
07-22-01
07-09-04
07-22-04
07-18-01
07-15-10
07-16-11
07-21-02
07-01-04
07-13-06
07-01-03
07-13-10
07-13-07
07-15-14
07-04-02
07-04-03
07-11-01
07-26-02
07-22-03
07-08-04
07-08-02
07-08-01

EN 60617-7:1996

54

Contactor closed in the unoperated position


Contactor function
Contactor with automatic tripping
Coupling device with electrical separation
Coupling device, optical, with electrical separation
Cumulative parallel switching, multipole switch,
single-pole multi-position
Current between neutrals of two polyphase systems
Current in the neutral conductor
Delayed both, device activated and de-activated, make
contact
Delayed break contact, device activated
Delayed break contact, device de-activated
Delayed make contact, device activated
Delayed make contact, device de-activated
Delayed operation, assembly of contacts, contact
Delayed overcurrent, example, measuring relais
Device for auto-reclosing
Device related to a measuring relay
Device, switch, power switching
Differential current
Discharge of gas, protective, tube
Disconnector (isolator)
Disconnector (isolator), manually operated
Disconnector (isolator), two-way
Divided-conductor detection relay, example, measuring
relay
Double spark gap
Early to close make contact
Early to open break contact
Earth fault current
Electronic relay, operating device
Emergency stop switch
Emergency stop switch, mushroom-head (activated by)
Failure to frame, voltage (frame potential in
case of fault)
Fluorescent lamp, starter
Four-position switch with four independent circuits
Function circuit breaker
Function, automatic return
Function, automatic tripping
Function, contactor
Function, disconnector (isolator)
Function, isolating-switch, switch-disconnector

BSI 10-1998

07-08-03
07-17-13
07-20-03
07-02-06
07-02-01
07-04-01
07-04-02
07-06-01
07-06-02
07-05-05
07-05-00
07-05-02
07-03-01
07-03-03
07-03-02
07-06-02
07-02-08
07-07-01
07-16-01
07-21-03
07-08-03
07-03-03
07-03-01
07-03-02
07-14-01
07-13-13
07-11-04
07-11-05
07-11-11
07-11-13
07-07-06
07-17-01

Non-automatic return function


Off-position in the centre, change-over contact
On-load isolating fuse switch
On-load isolating switch, switch-disconnector, power
switching device
One pole of a six-position multi-pole switch
Operating device of a thermal relay
Operating device of an electronic relay
Operating device with two separate windings, attached
representation
Operating device with two separate windings, detached
representation
Operating device, general symbol
Optical coupling device with electrical separation
Overcurrent relay with two measuring elements
Overcurrent relay with two output
Overcurrent relay, delayed
Overpower for reactive power, measuring relay
Percentage differential current
Phase failure detection, measuring relay
Polarized relay with neutral position, self restoring,
operating for either direction of current in the
winding
Polarized relay with two stable positions
Polarized relay, relay coil
Polarized relay, self restoring, operating for only one
direction of current in the winding
Position diagram, example, multipole switch
Position switch function, contact
Position switch with positive opening operation of the
break contact
Position switch, break contact
Position switch, make contact
Position switch, mechanically operated in both
directions with two separate circuits
Positive opening operation of the break contact, limit
switch
Positive operation by single push button switch
Positive operation, switch
Power at phase angle
Power switching device, circuit breaker
Power switching device, contactor
Power switching device, contactor with automatic
tripping

07-01-08
07-02-05
07-21-09
07-13-08
07-11-13
07-15-21
07-15-22
07-15-03
07-15-05
07-15-01
07-27-02
07-17-05
07-17-14
07-17-04
07-17-06
07-16-06
07-17-12
07-15-17
07-15-18
07-15-15
07-15-16
07-11-06
07-01-06
07-08-04
07-08-02
07-08-01
07-08-03
07-08-04
07-07-05
07-01-09
07-16-10
07-13-05
07-13-02
07-13-03

EN 60617-7:1996

55

Limit switch, mechanically operated in both directions


with two separate circuits
Locked rotor detection relay, example,
measuring relay
Magnet-approaching-operated proximity switch,
make contact
Make before break, contact, change-over
Make contact
Make contact which is early to close
Make contact which is late to close
Make contact with automatic return
Make contact without automatic return
Make contact, delayed both, device activated and
de-activated
Make contact, delayed, device activated
Make contact, delayed, device de-activated
Make contact, passing, closing momentarily during
operation
Make contact, passing, closing momentarily during
operation and release
Make contact, passing, closing momentarily during
release
Make contact, stay put
Makes, two by contact
Manually operated switch, general symbol
Measuring relay
Mechanical linkage-fuse
Mechanically operated limit switch, both directions with
two seperate circuits
Momentarily closing during operation and release contact,
passing make
Momentarily closing during operation contact, passing
make
Momentarily closing during release contact,
passing make
Motor starter, general symbol
Motor with a spring storage operating a three-pole
mechanical switching device
Multi-position switch
Multi-position switch (small number of positions)
Multi-position switch, bridging
Multipole switch, one of a six-position multipole-switch
Mushroom-head, emergency stop switch (activated by)
No voltage, example, measuring relay

07-13-06
07-13-10
07-13-07
07-13-07
07-13-00
07-13-14
07-13-09
07-13-08
07-13-12
07-13-13
07-13-11
07-22-04
07-22-05
07-19-03
07-19-02
07-19-01
07-20-02
07-20-03
07-20-04
07-07-03
07-07-02
07-07-05
07-07-05
07-07-02
07-14-08
07-14-03

BSI 10-1998

07-15-10
07-15-14
07-15-13
07-15-15
07-15-11
07-15-19
07-15-09
07-15-08
07-15-07

Relay coil of an alternating current relay


Relay coil, general symbol
Relay, measuring
Relay, measuring, current with maximum and
minimum settings
Relay, measuring, delayed overcurrent
Relay, measuring, divided-conductor detection relay
Relay, measuring, locked-rotor detection
Relay, measuring, no voltage
Relay, measuring, overcurrent with two measuring
elements
Relay, measuring, overcurrent with two output
Relay, measuring, overpower for reactive power:
Relay, measuring, phase-failure detection
Relay, measuring, relay detecting short-circuits between
windings.
Relay, measuring, reverse current
Relay, measuring, under-impedance
Relay, measuring, underpower
Relay, measuring, undervoltage
Relay, static, general symbol
Relay, static, with light emitting diode as actuator
Relay, three-pole thermal overload
Remanent relay, relay coil
Residual voltage
Resonant relay, mechanically, relay coil
Reverse current
Reverse current, measuring relay
Reversing the rotation of a motor by direct-on-line
motor starter (block symbol) with contactor
Rotary drum switch, six position
Rotary wafer switch, 18-position
Self-operating thermal switch, break contact
Self-operating thermal switch, for example: bimetal
Semiconductor operating device with semiconductor
make contact
Semiconductor, contactor, static switch
Sensor, proximity
Sensor, touch
Separate windings, two, on operating device, attached
representation
Separate windings, two, on operating device, detached
representation
Separation, electrical, coupling device

07-15-12
07-15-01
07-16-01
07-17-08
07-17-04
07-17-11
07-17-13
07-17-01
07-17-05
07-17-14
07-17-06
07-17-12
07-17-10
07-17-02
07-17-09
07-17-03
07-17-07
07-26-01
07-26-02
07-26-03
07-15-19
07-16-03
07-15-13
07-16-04
07-17-02
07-14-05
07-12-03
07-12-02
07-09-03
07-09-03
07-26-04
07-25-00
07-19-01
07-19-04
07-15-03
07-15-05
07-27-01

EN 60617-7:1996

56

Power switching device, disconnector (isolator)


Power switching device, disconnector (isolator),
manually operated
Power switching device, disconnector (isolator), two-way
Power switching device, isolator, two-way
Power switching device, switch
Power switching device, switch with positive opening
operation
Power switching device, switch-disconnector
Power switching device, switch-disconnector (on-load
isolating switch)
Power switching device, three-pole mechanical, operated
by motor or manually with trip-free mechanism
Power switching device, three-pole mechanical, operated
by motor with a spring storage
Power switching device, trip-free mechanism
Protective gas discharge tube
Protective gas discharge tube, symmetric
Proximity detector, capacitive, operating on the approach
of solid material
Proximity sensing device, block symbol
Proximity sensor
Proximity switch, make contact
Proximity switch, operated on the approach of a magnet,
make contact
Proximity switch, operated on the approach of iron,
break contact.
Pull-switch
Push-button switch
Push-button switch with positive operation
Push-button switch, for example: alarm
Push-button switch, single pole
Regulator with thyristors, motor starter (block symbol)
Regulator, motor starter (block symbol)
Relay coil of a high speed relay (fast-operating and
fast-releasing)
Relay coil of a mechanically latched relay
Relay coil of a mechanically resonant relay
Relay coil of a polarized relay
Relay coil of a relay unaffected by alternating current
Relay coil of a remanent relay
Relay coil of a slow-operating and slow-releasing relay
Relay coil of a slow-operating relay
Relay coil of a slow-releasing relay

BSI 10-1998

07-17-10
07-11-12
07-11-10
07-11-09
07-11-08
07-12-03
07-15-08
07-15-07
07-22-01
07-01-07
07-15-18
07-14-06
07-09-04
07-14-05
07-14-01
07-14-02
07-14-03
07-14-08
07-14-06
07-14-07
07-25-02
07-26-02
07-26-01
07-25-01
07-26-00
07-01-08
07-06-02
07-14-02
07-07-06
07-21-03
07-22-03
07-13-01
07-12-02
07-12-01
07-12-03
07-09-04
07-08-02
07-08-01
07-08-03

Switch, limit, with positive opening operation of the


break contact
Switch, manually operated, general symbol
Switch, multipole, button-operated, operated by
pushing and by turning
Switch, multipole, button-operated, operated either by
pushing or by turning
Switch, multipole, example with position diagram
Switch, multipole, four-position, with four independent
circuits
Switch, multipole, lever-operated
Switch, multipole, multi-position
Switch, multipole, multi-position (small number of
positions)
Switch, multipole, multi-position, bridging
Switch, multipole, one pole of a six-position multi-pole
switch
Switch, multipole, single-pole multi-position for
cumulative parallel switching
Switch, position, break contact
Switch, position, make contact
Switch, position, mechanically operated in both
directions with two separate circuits
Switch, position, with positive opening operation
of the break contact
Switch, positive operation
Switch, proximity, make contact
Switch, proximity, operated on the approach of
a magnet, make contact
Switch, proximity, operated on the approach of iron,
break contact
Switch, self-operating, thermal, break contact
Switch, self-operating, thermal, for example: bimetal
Switch, single pole, manually operated, general symbol
Switch, single pole, pull-switch
Switch, single pole, push-button
Switch, single, emergency stop
Switch, single, mushroom-head, emergency stop
(activated by)
Switch, single, push-button, for example: alarm
Switch, single, push-button with positive operation
Switch, single, turn-switch
Switch, single-pole, four-position
Switch, single-pole, multi-position, bridging

07-08-04
07-07-01
07-11-02
07-11-03
07-11-06
07-11-07
07-11-01
07-11-04
07-11-05
07-11-11
07-11-13
07-11-12
07-08-02
07-08-01
07-08-03
07-08-04
07-01-09
07-20-02
07-20-03
07-20-04
07-09-03
07-09-03
07-07-01
07-07-03
07-07-02
07-07-06
07-07-06
07-07-05
07-07-05
07-07-04
07-11-08
07-11-10

EN 60617-7:1996

57

Short-circuits between windings detected by relay,


example, measuring relais
Single-pole multi-position switch for cumulative
parallel switching
Single-pole multi-position switch, bridging
Single-pole six-position switch, bridging
Single-pole, four-position switch
Six-position rotary drum switch
Slow-operating relay, relay coil
Slow-releasing relay, relay coil
Spark gap
Spring return function, contact
Stable positions, two, polarized relay
Star-delta motor starter (block symbol)
Starter for fluorescent lamp
Starter, motor (block symbol), direct-on-line, with
contactor for reversing the rotation of a motor
Starter, motor (block symbol), general symbol
Starter, motor (block symbol), operating in steps
Starter, motor (block symbol), regulator
Starter, motor (block symbol), regulator
with thyristors
Starter, motor (block symbol), star-delta
Starter, motor (block symbol), with auto-transformer
Static (semiconductor) contactor
Static relay with light emitting diode as actuator
Static relay, general symbol
Static switch, general symbol
Static switch, passing current in one direction only
Stay put function, contact
Stay put make contact
Steps-operating motor starter (block symbol)
Stop switch for case of emergency
Striker fuse
Surge diverter
Switch
Switch, complex, 18-position rotary wafer
Switch, complex, general symbol
Switch, complex, six-position, rotary drum
Switch, gas discharge tube with thermal element
Switch, limit, break contact
Switch, limit, make contact
Switch, limit, mechanically operated in both directions
with two separate circuits

07-11-09
07-25-02
07-25-01
07-25-03
07-09-02
07-09-01
07-20-01
07-13-14
07-13-09
07-13-08
07-13-05
07-13-02
07-13-04
07-13-03
07-13-06
07-13-10
07-13-07
07-13-07
07-13-14
07-13-09
07-13-08
07-13-13
07-13-11
07-09-02
07-09-00
07-26-03
07-15-21
07-09-03
07-13-12
07-13-13

BSI 10-1998

07-21-06
07-26-03
07-14-08
07-20-01

Touch sensor
Trip-free mechanism
Tube, gas discharge, with thermal element
Tube, protective gas discharge
Tube, protective gas discharge, symmetric
Turn-switch
Two way isolator
Two-way contact
Under-impedance, example, measuring relay
Underpower, example, measuring relais
Undervoltage, example, measuring relay
Voltage failure to frame(frame potential in case of fault)
Wafer switch, 18-position, rotary
Windings, short-circuits between windings detected by
relay, measuring relais

07-19-04
07-13-11
07-09-04
07-22-04
07-22-05
07-07-04
07-13-07
07-06-04
07-17-09
07-17-03
07-17-07
07-16-02
07-12-02
07-17-10

EN 60617-7:1996

58

Switch, single-pole, six-position, bridging


Switch, static, (semiconductor) contactor
Switch, static, general symbol
Switch, static, passing current in one direction only
Switch, temperature sensitive, break contact
Switch, temperature sensitive, make contact
Switch, touch sensitive, make contact
Switch, with positive opening operation
Switch-disconnector
Switch-disconnector (on-load isolating switch)
Switchgear and controlgear, circuit breaker
Switchgear and controlgear, contactor
Switchgear and controlgear, contactor
Switchgear and controlgear, contactor with
automatic tripping
Switchgear and controlgear, disconnector (isolator)
Switchgear and controlgear, disconnector (isolator),
manually operated
Switchgear and controlgear, disconnector (isolator),
two-way
Switchgear and controlgear, isolator, two-way
Switchgear and controlgear, switch with positive
opening operation
Switchgear and controlgear, switch-disconnector
Switchgear and controlgear, switch-disconnector
(on-load isolating switch)
Switchgear and controlgear, three-pole mechanical
switching device operated by motor with a spring
storage
Switchgear and controlgear, trip-free mechanism
Temperature sensitive switch, break contact
Temperature sensitive switch, make contact
Thermal overload, three pole, relay
Thermal relay, operating device
Thermal switch, self-operating, break contact
Three-pole mechanical switching device operated by
motor or manually with trip-free mechanism
Three-pole mechanical switching device operated by
motor with a spring storage
Three-pole switch with automatic release by any one of
the striker fuses
Three-pole thermal overload relay
Thyristor-regulator, motor starter (block symbol)
Touch sensitive switch, make contact

blank

BSI
389 Chiswick High Road
London
W4 4AL

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

BSI British Standards Institution


BSI is the independent national body responsible for preparing British Standards. It
presents the UK view on standards in Europe and at the international level. It is
incorporated by Royal Charter.
Revisions
British Standards are updated by amendment or revision. Users of British Standards
should make sure that they possess the latest amendments or editions.
It is the constant aim of BSI to improve the quality of our products and services. We
would be grateful if anyone finding an inaccuracy or ambiguity while using this
British Standard would inform the Secretary of the technical committee responsible,
the identity of which can be found on the inside front cover. Tel: 020 8996 9000.
Fax: 020 8996 7400.
BSI offers members an individual updating service called PLUS which ensures that
subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.
In response to orders for international standards, it is BSI policy to supply the BSI
implementation of those that have been published as British Standards, unless
otherwise requested.
Information on standards
BSI provides a wide range of information on national, European and international
standards through its Library and its Technical Help to Exporters Service. Various
BSI electronic information services are also available which give details on all its
products and services. Contact the Information Centre. Tel: 020 8996 7111.
Fax: 020 8996 7048.
Subscribing members of BSI are kept up to date with standards developments and
receive substantial discounts on the purchase price of standards. For details of
these and other benefits contact Membership Administration. Tel: 020 8996 7002.
Fax: 020 8996 7001.
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the UK, of
the publications of the international standardization bodies. Except as permitted
under the Copyright, Designs and Patents Act 1988 no extract may be reproduced,
stored in a retrieval system or transmitted in any form or by any means electronic,
photocopying, recording or otherwise without prior written permission from BSI.
This does not preclude the free use, in the course of implementing the standard, of
necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.
If permission is granted, the terms may include royalty payments or a licensing
agreement. Details and advice can be obtained from the Copyright Manager.
Tel: 020 8996 7070.