You are on page 1of 142

Release Date: Nov. 2009 / Manual Revision: 1.

00

Load Break Switch Control ETR300S


Users Manual

ENTEC

ENTEC
ELECTRIC & ELECTRONIC CO., LTD

Copyright 2009 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved.

Forerunner Distribution & Automation

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

CONTENT

1. Product Introduction ..................................................................................................... 6


1.1. Introduction ......................................................................................................................... 6
1.2. Characteristic summary ....................................................................................................... 7

2. Technical Specification ................................................................................................. 10


2.1. Input and Output ................................................................................................................ 10
2.2. Environment Test ............................................................................................................... 12
2.3. Metering Accuracy ............................................................................................................ 13
2.4. Monitoring ......................................................................................................................... 14
2.5. Event Recorder .................................................................................................................. 18
2.6. Maintenance ...................................................................................................................... 21
2.7. Communication ................................................................................................................. 21

3. Dimension and structure ................................................................................................. 22


4. External Input/Output Connector ................................................................................... 23
4.1. Current Input(Connector type:STLZ960-10) .................................................................... 24
4.2. Voltage Input(Connector type:STLZ960-6P,8P) ............................................................... 24
4.3. Digital Output(DO) ........................................................................................................... 25
4.4. Digital Input(DI) ................................................................................................................ 25
4.5. Power supply input& Modem power supply output .......................................................... 26
4.6. Remote Communication Port(modem connection) ........................................................... 26
4.7. 485 Communication Port ................................................................................................... 27
4.8. Ethernet Port(RJ45) ........................................................................................................... 27

5. User Interface Panel .................................................................................................... 28


5.1. Construction ...................................................................................................................... 29
5.2. Operation Manual (LCD instruction) ................................................................................ 36
5.3. LCD Menu Use.................................................................................................................. 43

6. Global Setting ............................................................................................................... 47


6.1. System ............................................................................................................................... 47
6.2. Communication ................................................................................................................. 54
6.3. Event Recorder .................................................................................................................. 69

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.4. Monitoring ......................................................................................................................... 70


6.5. PLC.................................................................................................................................... 81
6.6. Other setting items............................................................................................................. 86

7. Group Setting ................................................................................................................ 89


7.1. Fault pickup element ......................................................................................................... 90
7.2. Inrush Current Restraint Function ..................................................................................... 95
7.3. Directional Detection Function ......................................................................................... 98
7.4. SECTION ........................................................................................................................ 102
7.5. Phase angle synch detect ................................................................................................. 106
7.6. Line cut / Phase lost detect .............................................................................................. 106
7.7. Overcurrent detect element.............................................................................................. 107

8. EVENT ........................................................................................................................ 109


8.1. Operation Event............................................................................................................... 109
8.2. Fault Event ...................................................................................................................... 110
8.3. Fault Cycle - Summary.................................................................................................... 112
8.4. System Events ................................................................................................................. 113
8.5. Set Change Event ............................................................................................................ 114
8.6. Aver. Load/Min ................................................................................................................ 115
8.7. Peak. Load/Hour.............................................................................................................. 115
8.8. Peak. Load/Day ............................................................................................................... 116
8.9. Diagnostic Event ............................................................................................................. 117
8.10. PQM .............................................................................................................................. 120
8.11. Clear Saved Data ........................................................................................................... 121

9. Maintenance ................................................................................................................ 122


9.1. Count ............................................................................................................................... 122
9.2. Interrupt Time .................................................................................................................. 129
9.3. Contact Wear ................................................................................................................... 130
9.4. Data Reset........................................................................................................................ 130
9.5. CCU Information ............................................................................................................. 131

10. Time ........................................................................................................................... 132


11. Status .......................................................................................................................... 133
11.1. Switch ............................................................................................................................ 133
11.2. Input Ports ..................................................................................................................... 135
11.3. Output Ports ................................................................................................................... 135

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

12. Metering .................................................................................................................... 136


12.1. Current ........................................................................................................................... 136
12.2. Voltage ........................................................................................................................... 137
12.3. Frequency ...................................................................................................................... 138
12.4. Power ............................................................................................................................. 138
12.5. Energy............................................................................................................................ 139
12.6. Demand Current ............................................................................................................ 139
12.7. Unbalance ...................................................................................................................... 140
12.8. Harmonics ..................................................................................................................... 140
12.9. True R.M.S .................................................................................................................... 141
12.10. TD Monitoring............................................................................................................. 141
12.11. CCU Reference ............................................................................................................ 141

13. PLC function ............................................................................................................ 142

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

1. Product Introduction
1.1. Introduction
ETR300-S01 is embedded in Distribution Automation 25.8kV SF6 gas insulated load break
switch(Pole mount) control box.

It receives measurement information(3 phases current &

voltages) and status information from Switch, and meters current and voltage, detecs FI, Line cut,
Live line/Dead line, Unbalance, and send those information to SCADA(Master station).
As well as, controlling a swich by receiving Control Signal from SCADA, provides Distribution
Automation and minimize a fault area.
ETR300-S01 monitors not only electric quality of dirstirbution line but also, provides Section
operation in case of fault occurring and minimize its fault area.
All events occurring in the distribution line, are saved and provides fault analysis. With using
DNP3.0 Protocol, provides monitored status to SCADA for switch operation. Not only DNP3.0
Protocol, other communication protocols can beprovided by users request.
Switch operation is available by operation buttion on front panel. Fault detect Enable/Diable,
Fault

detect

Enable/Disable,

SECTION

function

Enable/Disable,

operation

selection

Local/Remote, Operation lock Lock/Unlock, ALTERNATE SETTING Enable/Disable, SEF


function Enable/Disable, SEC/TIE LOCKOUT Enable/Disable can be set.
INTERFACE SOFTWARE is very much convenient to have the maintenance of Set change and
Operation records in PC. It also has Zoom In/Out feature to analize Fault wave and Digital
operation signal with real time so that it provides much more uniq functions for the users.

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

1.2. Characteristic summary


MONITORING

Phase fault detect(Permenant , Instantaneous)

Earth fault detect(Permenant, Instantaneous)

SEF fault detect(Permenant, Instantaneous)

Inrush current restraint (Phase/Earth/SEF)

Directional (Phase/Earth/ SEF)

SECTION operation function

Unbalance detect

Line cut/phase loss detect element

Live line detect

Operation counter limit

Switch contact wear monitoring

Battery auto load test

Power Quality Monitoring


-

Interrupt

Sag

Swell

Harmonics

Current Unbalance

Voltage Unbalance

Under Voltage

Over Voltage

Under Frequency

Over Current

DC Analog Input Monitoring

Zero Sequence voltage(V0) detect

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

EVENT RECORDER

Switch Operation Record Last 256 events

Fault Event Record Last 256 events

Fault Waves(20 cycles 8EA) record Last 8 events

System Event Record Last 2048 events

Set Change Event Last 100 events

Average Load Event Record Last 1024 events

Max. Load per hour Event Record Last 1024 events

Max Load per day Event Record Last 1024 events

Diagnostic Event Record Last 512 events

PQM Monitoring Event Record Last 100 events

METERING

Phase Current and Phase Angle, Fault Current and Angle, SEF Current and Angle

Voltage and Angle between phases, Forward/Revserse/Zero Sequence and Angle

Frequency magnitude and changing rate per second

Real Power/Apparent Power/Reactive Power per phase

Power Factor per phase

Forward/Reverse Phase Energy

Demand

Source/Load side Voltage and Current Unbalance

Voltage and Current Harmonic rate

Phase True R.M.S voltage and current

DC Analog Input value

ETR300 Inside Temperature

MAINTENANCE

Number of Restart

Number of Diagnostic detec

Number of Switch fault occurred

Number of Instantaneous current fluctuation and its number per phase

Number of PQM occurred and accumulated time

Switch contact wear

COMMUNICATIONS

Side Panel PORT1 RS232 Serial port : DNP 3.0, Modbus and IEC60870-5-101 Protocol

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Side Panel PORT2 RS485 Serial port : DNP 3.0, Modbus and IEC60870-5-101 Protocol

Side Panel PORT3 RJ45 port : DNP 3.0 IEC60870-5-104 Protocol

Side Panel PORTF RS232 Serial port : ETR300-R Interface Software

USER INTERFACE

Fault Indicator

Manual battery load test: Battery voltage and chaged voltage

Dual function keypad

204 character display (LCD or VFD: Vacuum Fluorescent Display)

43 LED indicator Fault Indicator, Sequence Status, Battery status and so on

Fron Panel RS232 Port

Help Message

Security(Password)

AUXILIARY OUTPUTS

16 number of PLC Progoram available

AUXILIARY INPUTS

16 number of PLC Program available

Other

Fault Injection test available

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

2. Technical Specification
2.1. Input and Output
System

3 phases- 3 wires or 3 phases 4 wires, Max.38kW, Max 800A

Frequency

50/60 Hz System and ABC/ACB phase rotation

Control voltage input

AC Power supply input 110V/220Vac or other voltage(+10%,-15%)

Rated battery voltage : 24Vdc

User DC Poer Output Option

DC Power supply voltage : 12, 15, 24Vdc

Continuous DC Power supply : 30W

DC Power for 10 second: 70W

Voltage Transformer Input (VT) Standard

V11, V12, V13, V21, V22, V23 and V10

Input voltage range : Phase-Neutral continuous < 6V

Load burden : 0.002VA(4V)

Voltage Transformer Input (VT) Option

V11, V12, V13, V21, V22, V23 and V10

Input voltage range : Phase-Neutral continuous < 300V

Load burden : 0.6VA(300V), 0.2VA(220V), 0.05VA(120V), 0.02VA(67V)

Current Transformer (CT)

IA,IB,IC and IG, SEF, ZCT

IA,IB,IC,IG input current range


Nominal: AC 0.6Arms
Continuous: 2A
25A for 1 sec

10

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Load burden : 0.38VA(1A)

SEF input current range


Rated current : 0.05A
Continuous current : 0.16A
0.6A for 1sec
Load burden : 0.0375VA(0.05A)

ZCT input current range Option


Rated current : 1.5mA
Continuous ????????????????? mA
200mA for 1sec
Load burden : 0.0005VA(1.5mA)

Control Input Option

Control Input 8 channel

Rated voltage and operation range


250Vdc(-15%,+20%)
125Vdc(-15%,+20%)
48Vdc(-15%,+20%)
24Vdc(-15%,+20%)
12Vdc(-10%,+30%)

Operation current: at rated voltage, < 5mA

Control Output Contact Option

Control Input 8 channel

Open 5 channel

Close 5 channel
Alarm 1 channel

Auto surge protection Varistor 300Vac / 350Vdc

Operation and release time: at +20(+68) , < 5ms

Max operation power supply


Table 2-1. Max. Operation power supply
(L/R=7ms)
(cos=0.4)

125Vdc
48Vdc
24Vdc
250Vac
125Vac

0.1A
0.8A
3A
3A
5A

ENHANCED TECHNOLOGY

11

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

2.2. Environment Test


Dielectric Strength

CT Input, VT Input, Control Power Input, Fiber-optic insulation Input and Relay output
AC 60, 2/1 minute

Impulse Voltage

IEEE C62.45 (1992) , 6(1.250), 3(820) of Relay System for Radio


Electromagnetic Interference Transceiver.

Surge Withstand Capability

Protection relay and Relay system protection purpsoe IEEE C37.90.1 - 1989 IEEE SWC test
(3 Vibration1 to 1.5, 5 fast saturation 1.250)

IEEE C37.90.2 - 1987 IEEE Test, Test use standard, relay system for Radio Electromagnetic
Interface that comes from Transceiver, 10 V/m(150 and 450, 5 W transmitter 10)

Vibration Test

IEC 255-21-1-1988 Electric Relay, Part 21: Metering relay and protection device vibration,
impact, crash and earthquake test, Section One - Vibration tests (sinusoidal), Class 2

IEC 255-21-1-1988 Electrical relays, Part 21 : Vibration, shock, bump, and seismic tests on
measuring relays and protection equipment, Section One - Vibration tests (sinusoidal), Class 2

Control Operating Temperature

Operation range : -25+70(-13+158)

LCD : -20+70(-4+158) Standard

VFD(Vacuum Fluorescent Display-Vacuum florecense zero sequence output device) : 40+85(-40+185) optoin

12

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

2.3. Metering Accuracy


Measurement values for metering and protection are based on Input voltage and current which are
eliminated Harmonic.

Voltage metering

Rated voltage : AC voltage 4 V

Each phase voltage : 0.2 %(Rated voltage 80 120 %), 0.5

Zero sequence voltage(Vo) : 0.2 %(Rated voltage 80 120%), 0.5

3V1, 3V0, 3V2 : 0.6 %(Rated voltage 80 120%), 1

Current metering

Rated current : AC 0.6 Arms

IA, IB, IC, IG : 0.5 mA 0.1 % of reading(0.03~1.5 A), 0.5

IN : 0.005 mA + 0.5 % of reading(0.5~16.0 mA), 1

3I1, 3I0, 3I2 : 0.01 A 3 % of reading(0.003~1.5A ), 1

Power metering

Power : 1.2 %(at rated voltage>80 %, at rated current>0.03)

Rea Power : 0.7 % PF=1, 1% PF>0.87(at rated voltage>80%, at rated current>0.03)

Reactive Power : 0.7 % PF=0, 1% PF<0.5(at rated voltage>80%, at rated current>0.03)

Harmonic metering : 5%

ENHANCED TECHNOLOGY

13

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

2.4. Monitoring
Fault detect function
Phase fault pickup level ................................................. OFF, 50 ~ 630A (step: 5A)
Earth fault pickup level ................................................. OFF, 25 ~ 315A (step: 5A)
SEF pickup level ........................................................... OFF, 0.1 ~ 10.0A (step: 0.1A)
Dropout.......................................................................... Pickup level 96 ~ 98%
Instantaneous FI detect time .......................................... 1 ~ 180sec (step: 1sec)
Instantaneous FI detect time .......................................... 1 ~ 180sec (step: 1sec)

Phase Directional detect function


Pole voltage ................................................................... normal voltage V1
Directional detect .......................................................... Disable, Enable
Max. Torque angle ......................................................... 0 ~ 345 (step: 15 )
Min. Operation voltage.................................................. 0, 10 ~ 80% (step: 1% )
Phase angle accuracy ..................................................... 2
Internal operation delay ................................................. 1.5cycle

Ground/SEF Directional detect function


Pole voltage ................................................................... Zero sequence voltage Vo
Source side VTs must be Wye connection.
Directional detec ........................................................... Disable, Enable
Max. Torque Angle ........................................................ 0 ~ 345 (step: 15 )
Min. Operation voltage.................................................. 0, 10 ~ 80% (step: 1% )
Phase angle accuracy ..................................................... 2
Internal operation delay ................................................. 1.5cycle

Phase/Ground/SEF Cold Load Pickup Blocking function


Pickup level ................................................................... 1 ~ 20 MTC (step: 1 MTC)
Pickup current restore time ........................................... 0.0 ~ 180.0sec (step: 0.1sec)
CLPU reset time ........................................................... 0.01 ~ 60.00sec (step: 0.01sec)
Pickup level accuracy .................................................... 5%
Timing accuracy ............................................................ 5% or 20msec

14

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

SECTION function
Function ......................................................................... Disable, Enable
Auto closing .................................................................. Disable, Enable
Section type ................................................................... V-T, O-T
Close direction............................................................... Always, Source, Load
Open delay time............................................................. 0.1 ~ 25.5sec (step: 0.1sec)
Close waiting time ......................................................... 1 ~ 255sec (step: 1sec)
Close delay time ............................................................ 1 ~ 255sec (step: 1sec)
Lockout time.................................................................. 1 ~ 255sec (step: 1sec)
Source side lockout time ............................................... 1 ~ 255sec (step: 1sec)
Source side reset time .................................................... 1 ~ 255sec (step: 1sec)
Block Time .................................................................... 1 ~ 255sec (step: 1sec)
Operation Time .............................................................. 1 ~ 4 time (step: 1 time)

Phase Unbalance
Angle difference ............................................................ OFF, 5 ~ 80 (step: 5)
Detect delay time ........................................................... 0.0 ~ 180.0sec (step: 0.1sec)

Phase Open/Lost
On Level ........................................................................ phase voltaeg 70 ~ 85% (step: 5%)
Off Level ....................................................................... phase voltage 30 ~ 75% (step: 5%)
Detect delay time ........................................................... 0.0 ~ 180.0sec (step: 0.1sec)

Live line/Dead line detect(Communication)


Live line detect value .................................................... 0.10 ~ 0.90pu (step: 0.01pu)
Deect delay time ............................................................ 0.5sec fixed

Operation counter
Alarm function .............................................................. Off, On
Reset counter ................................................................ 0 ~ 65535 (step: 1)
Alarm counter ................................................................ 0 ~ 20000 (step: 1)

Battery auto load test


Test cycle ....................................................................... 1 ~ 72 hour (step: 1hour)

ENHANCED TECHNOLOGY

15

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Power Quality Monitoring - PQM


PQM function ............................................................... Disable, Enable
Sag pickup level ............................................................ 0(OFF), 0.50 ~ 0.99pu (step: 0.01pu)
Sag delay time ............................................................... 0.5 ~ 10.0cycle (step: 0.5cycle)
Swell pickup level ......................................................... 0(OFF), 1.01 ~ 1.50pu (step: 0.01pu)
Swell delay time ............................................................ 0.5 ~ 10.0cycle (step: 0.5cycle)
Interruption .................................................................... 0(OFF), 0.10 ~ 0.49pu (step: 0.01pu)
Interruption .................................................................... 0.5 ~ 10.0cycle (step: 0.5cycle)
Voltage harmonic pickup level ...................................... 0(OFF), 0.5 ~ 100.0% (step: 0.1%)
Current harmonic pickup level ...................................... 0(OFF), 0.5 ~ 100.0% (step: 0.1%)
Harmonic delay time ..................................................... 0.2 ~ 60.0sec (step: 0.1sec)
Voltage unbalance pickup level ..................................... 0(OFF), 1 ~ 100% (step: 1%)
Voltaeg unbalance delay time ........................................ 0.1 ~ 60.0sec (step: 0.1sec)
Current unbalance pickup level ..................................... 0(OFF), 1 ~ 100% (step: 1%)
Current unbalance delay time ........................................ 0.1 ~ 60.0sec (step: 0.1sec)
Low voltage pickuip level ............................................. 0(OFF), 0.30 ~ 0.95pu (step: 0.01pu)
Low voltage delay time ................................................. 0.0 ~ 180.0sec (step: 0.1sec)
Over voltage picup level................................................ 0(OFF), 1.05 ~ 1.50pu (step: 0.01pu)
Over voltage delay time ................................................ 0.0 ~ 180.0sec (step: 0.1sec)
Low frequency pickup level .......................................... 0(OFF), 46.00 ~ 59.98Hz (step: 0.01Hz)
Low frequency delay time ............................................. 0.03 ~ 10.00sec (step: 0.01sec)
Phase overcurrent pickup level...................................... 0(OFF), 50 ~ 630A (step: 5A)
Phase overcurrent delay time ........................................ 0.0 ~ 180.0sec (step: 0.1sec)
Ground overcurrent pickup level ................................... 0(OFF), 25 ~ 315A (step: 5A)
Ground overcurrent delay time...................................... 0.0 ~ 180.0sec (step: 0.1sec)
Current unbalance/THD detect Min. value ................... 0 ~ 630A (step: 1A)

Switch Contact wear


Contact wear detect ....................................................... Off, On
Pickup wear ................................................................... 0.0 ~ 50.0% (step: 0.1%)
Rated system ................................................................. 15, 27, 38
Rated interruption capacity() ..................................... 5.0 ~ 50.0 (step: 0.1)
Number of Max. interruption ........................................ 1 ~ 999 (step: 1)
Phase A contact wear ..................................................... 0.0 ~ 100.0 % (step: 0.1%)
Phase B contact wear..................................................... 0.0 ~ 100.0 % (step: 0.1%)
Phase C contact wear..................................................... 0.0 ~ 100.0 % (step: 0.1%)

16

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

TD Monitoring
TD1 rating ..................................................................... 20, 200
TD1 ratio ............................................................... ....... 1 ~ 3000 (step: 1)
TD1 offset.............................................................. ....... -10000 ~ +10000 (step: 1)
TD1-1 type ............................................................ ....... Under or Over
TD1-1 pickup value .............................................. ....... 0(OFF), 0.1 ~ 35.0V (step: 0.1V)
TD1-1 delay time................................................... ....... 0.01 ~ 600.00sec (step: 0.01sec)
TD1-2 type ............................................................ ....... Under or Over
TD1-2 pickup value .............................................. ....... 0(OFF), 0.1 ~ 35.0V (step: 0.1V)
TD1-2 delay time................................................... ....... 0.01 ~ 600.00sec (step: 0.01sec)
. NOTE : There are 4 more channels (TD2 ~ TD5) the same as above.

Zero Sequence Voltage(V0) detect


Pickup level detect..................................................... ... 0(OFF), 0.05 ~ 1.20pu (step: 0.01pu)
Detect dela time ......................................................... ... 0.1 ~ 6000.0sec (step: 0.1sec)

ENHANCED TECHNOLOGY

17

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

2.5. Event Recorder


Operation event recording device

Trigger source
Switch CLOSE
Switch OPEN
Earth Close(ECLOSE)
Earth Open(EOPEN)

Storage capacity : Total 256 events

Fault event recording device

Trigger source
Taget A, B, C, N phases, SEF
Fault detect : Instantaneous fault, Permenant fault
Detect direction : Forward, Reverse direction
Fault Sequence

Data channel
Current 4, Voltage 3, Frequency, Logic input status 32, Output relay 16channel, Input
16channel

Storage capacity : Total 256 events

Fault wave capture

Trigger source
Fault wave capture point
Fault current

Sampling ratio : 128x20, 64x40, 32x80, 16x160

Storage capacity: 8 fault waves of 20 cycle (20cycles 8EA).

System Event Recording device

Trigger source
52A contact
Input/Output status change
Front panel control
AC power supply
External control

18

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

External input status


System alarm
Sleep mode

Trigger time : each 1/4 cycle

Trigger type : Pickup and Dropout

Storage capacity : Last 2048 events

Set Change Event Recording device

Trigger source
Global setting change
Primary group setting change
Alternate group setting change

Storage capacity : Total 100events

Load Profile
1) Average Load/ Minute

Trigger source
Demand current(A, B, C, G)
Demand real power(A, B, C, 3)
Demand reactive power (A, B, C, 3)
Trigger time : 1, 2, 3, 4, 5, 6, 10, 12, 15, 20 or 30 min.

Storage capacity : Total 1024events (Storage Capacity : Total 1024 Events)

2) Peak Load/ Hour

Trigger source
Demand current(A, B, C, G)
Demand real power(A, B, C, 3)
Demand reactive power(A, B, C, 3)
Trigger time : Every 1 hour

Storage capacity : Total 1024 events, 42 days

3) Peak Load/ Day

Trigger source
Demand current(A, B, C, G)
Demand real power(A, B, C, 3)
Demand reactive power(A, B, C, 3)
Trigger time : Daily

ENHANCED TECHNOLOGY

19

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Storage capacity : Total 1024 events, 1024days

DIAGNOSTIC EVENT RECORDER

Trigger source
DSP failure
ADC failure
RTC failure
Memory failure
Flash-Rom failure
Circuit voltage failure
Globlal setting failure
Primary setting failure
Alternate setting failure
Event failure
Count failure
DO failure
Close failure
Open failure

Trigger time : evey 1/4 cycle

Trigger type : Pickup and Dropout

Storage capacity : Last 512 events

PQM event recording device (PQM EVENT RECORDER)

Trigger source
PQM pickup element

20

Storage capacity : Total 100events

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

2.6. Maintenance
COUNTER

Number of System restart : 0 ~ 65534

Number of maintenance : 0 ~ 65534

Number of Operation : 0 ~ 65534

Numer of fault: 0 ~ 65534

Number of Instantaneous current change detect : 0 ~ 65534

Number of PQM detect: 0 ~ 65534

Switch contact wear

Phase A wear: 0.0 ~ 100.0%

Phase B wear: 0.0 ~ 100.0%

Phase C wear: 0.0 ~ 100.0%

2.7. Communication
Table 2-2. Communication
RS232, 1200-19200bps, None, Odd or Even Parity, 7 or 8 Data bits, 1or 2
Side panel Port1

Stop bit
DNP 3.0, Modbus and IEC60870-5-101 protocol
RS485/422, 1200-19200bps, None, Odd or Even Parity, 7 or 8 Data bits,

Side panel Port2

1 or 2 Stop bit
DNP 3.0, Modbus and IEC60870-5-101 Protocol

Side panel Port3


Front panel PortF

RJ-45, 10BASE-T/100BASE-T
DNP 3.0, Modbus and IEC60870-5-104 Protocol
RS232, 1200-57600bps, No Parity, 8 Data Bits, 1 Stop bit
ETR300 interface software

ENHANCED TECHNOLOGY

21

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

22

K04
K03
K02

POWER IN

K01

V0

V23

CN1

950

J01 J02 J03 J04

V22
V21

3
CN2
4

V12

INPUTS
CN3

V11

OUT206

OUT205

950

H01 H02 H03 H04 H05 H06

Ise
IN

OUTPUTS

E10
E07

IN104

CN4

4
1

8
3
CN5

2
1

4
3

CN6
4
3
CN7

1:+12V
2:DC01
3,4:GND

1:DC02
3:DC03
2,4:COM

I03
I02

TRIP & CLOSE

I01

E02

IN102
IN101

IN103

+
+

ENHANCED TECHNOLOGY

5559
1

Figure 3-1. Dimension and Structure

1,3:DC(+)
2,4:DC(-)

5559

PORT F

4,8:COM

5559

MONITORS

OPEN

3,7:OUT204

CLOSE

E01

L4

N.C

L3

OUT104

TAG

OUT103

HOT LINE

LOCKED

1,5:N/C
2,6:OUT202

CONTROL

OUT102

L2

OUT101

L1 MANUAL LOCK

ENABLED

2,5:+12V

5559

950-08

AUX1

950-10

VC / VT
REMOTE

4:IN205

VB / VS

LOCKOUT

A01 A02 A03 A04 A05 A06 A07 A08 A09 A10 B01 B02 B03 B04 B05 B06 B07 B08

RESET

E08

ABC / RST LIVE


VA / VR

ENABLED

E09

C Phase Unbalance

SECTION

1:IN204

GPS

B Phase Unbalance

E06

ENABLED

E05

SEF

A Phase Unbalance

E04

GROUND
ENABLED

5559

3,6:GND

E03

ALTERNATE
SETTINGS

1:IN203
2:IN202
3:IN201
4:+12V

RCV

SEF
PROTECTION
ENABLED

F02
Antenna

C FAULT
GROUND

5559

F03

Antenna

PORT RF

F01

RESET

RX

B FAULT
FI
TEST

TX

LAMP TEST
BATT'
CHECK

1,3:P
2,4:N

TIE CYCLE

F04

F05

SEC CYCLE
ENT

A FAULT

+BAT

V13

F06

G01

ESC

SEC/TIE LOCKOUT

-BAT

5559

POWER SUPPLY

G02

UP

DOWN

AC 24V

G07
G05
PORT2

3
2

950

FUN

AC 24V

485+ 485- SG

1TX
1RX

2TX
2RX

BATTERY
REVERSE POWER

G08

PORT3

CHARGER

G06

AC SUPPLY

G04

RX / TX

G03

DIAG/ERROR

PORT1

RUN

1:DCD 2:RXD 3:TXD 4:DTR


5:GND 6:DSR 7:RTS 8:CTS
9:N/C

10M/100M

ETR300 -S02

Control & Communication Unit

RJ45
XPORT

LINK

3. Dimension and structure

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

4. External Input/Output Connector


ETR300 provides terminals(connector) to connect control and modem, the termainal arrangement
is as belows;

A01 A02 A03 A04 A05 A06 A07 A08 A09 A10 B01 B02 B03 B04 B05 B06 B07 B08

10M/100M

2TX
2RX

LINK

TX
950-10

RJ45
XPORT

950

950-08

RX
RCV

OUT104

OUT103

N.C

E02

E01

IN101

IN102

IN103

IN104

E03

I01

F01

E10

F02

F03

1TX
1RX

V11

Ise

V12

G01

V21

G03

G04

G06

G07

V23

G08

V0

POWER SUPPLY

K02

K03

K04

AC 24V

5559

K01

AC 24V

-BAT

J01 J02 J03 J04

950

1,3:P

2,4:N

1:IN203
2:IN202
3:IN201
4:+12V

POWER IN

CN1
3

5559

3,6:GND

2,5:+12V

1:IN204

G05

V22

CN2
4

4:IN205

OUT206

G02

V13

5559

1,5:N/C

2,6:OUT202

3,7:OUT204

F06

INPUTS

950

OUT205

F05

PORT3

PORT1

+BAT

H01 H02 H03 H04 H05 H06

1:DCD 2:RXD 3:TXD 4:DTR


5:GND 6:DSR 7:RTS 8:CTS
9:N/C

PORT2

F04

CN3

5559

4,8:COM

1,3:DC(+)

2,4:DC(-)

E09

PORT RF

OUTPUTS

5559

1:+12V
2:DC01
3,4:GND

E08

IN

Antenna

GPS

CN4
3

5559

1:DC02
3:DC03
2,4:COM

E07

I03

CN5
3

5559

E06

TRIP & CLOSE


CN6

E05

I02

MONITORS
CN7
4

E04

Antenna

485+ 485- SG

OUT102

OUT101

Figure 4-1. External Input/Output connector

Table 4-1.Cable size for connecter


Item

Size( )

Length( )

Connecter name

Current

1.25(50/0.18)

300

AkZ 960-10P

Power supply

"

"

AkZ 960-4P

Digital Input

0.75(12/0.18)

"

Molex 5557-6P,4P

Digital Output

"

"

AkZ 950-6P

Voltage

"

"

AkZ 960-6P,8P

ENHANCED TECHNOLOGY

Remark

23

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

4.1. Current Input(Connector type:STLZ960-10)


Current connecters terminal no. 1 starts with phase A and follows by B, C, N, SEF phase turn.
ETR300 current terminal provides all phase name.

E02

E01

E03

I01

E04

E05

I02

E06

E07

I03

E08

E09

IN

E10

Ise

Table 4-2. Current connecter pin


IO1

IO2

IO3

IN

Ise

SEF

phase phase phase phase


Figure 4-2. Current connector

4.2. Voltage Input(Connector type:STLZ960-6P,8P)


Voltage connector has source side 3 phases(A,B,C) and load side 3 phases(R,S,T) as belows;
Table 4-3. Voltage connecter Pin
E01

E02

I01

E03

E04

I02

E05

E06

I03

E07

E08

IN

E09

E10

V12

V13

Phase

Phase

Phase

V21

V22

V23

V0

Zero

Phase

Phase

Ise

Figure 4-3. Voltage connector

24

V11

ENHANCED TECHNOLOGY

Phase Sequence

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

4.3. Digital Output(DO)


Digital Output has total 8 output relays. Digital Output connecter delivers the control single from
the controller and its construction is as belows.
H01 H02 H03 H04 H05 H06

Table 4-4. Digital Output Connecter Pin


Pin

950

Number
OUT205

Pin

Signal

Number

Close

Open

OUT206

Figure 4-4. Digital Output Connector

4.4. Digital Input(DI)


Digital Input receives 16 status signals through insulated electric contacts. This is how increasing
DI part surge withstand capability and provide more insulation to Main module where signali is
connected but weak to surge voltage. Digital Input connector is the part where receiving status
signal from control part and its structure is as belows.

CN3

CN2
4

Table 4-5. Digital Input Connecter Pin


Connecter

1:IN203
2:IN202
3:IN201
4:+12V

1:IN204

4:IN205

2,5:+12V

3,6:GND

CN2

CN3

Pin
Number

Signal Connecter

01

Open

02
03

Close
Lock

01
04

Spare

Number
04

CN2

Door
Open

Pin

CN3

04
04
02,05
02,05

Figure 4-5. Digital Input Connector

ENHANCED TECHNOLOGY

25

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

4.5. Power supply input& Modem power supply output


Power supply connecter has ETR300 operation power supply terminal and modem power supply
terminal. Each connecter provides its name and pin number 1 is for +24V input and pin number 2
is Grond input.

P : DC 24V +Terminal
N : DC 24V GND
N

Figure 4-6. Power Supply Connecter

4.6. Remote Communication Port(modem connection)


Modem communication port is D-SUB 9 pin male type and all pins are connected except the
number 9 pin (Ring Indicator)

Table 4-6. Remote Communication Port Pin


Pin No.
9

5 4

7 6

DTR : Data Terminal ready

RxD : Received Data

TxD : Transmitted Data

DTR : Data Terminal Ready

GND : Ground

DSR : Data Set Ready

RTS : Request To Send

CTS : Clear To Send

2 1

Figure 4-7. Remote Communication Port

26

Signal Info

RI

: Ring Indicator

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

4.7. 485 Communication Port


485 Communication Port has 3 pins and its construction is as follows.

3
2T

Table 4-7. 485Communication Port Pin

2R

Pin No.
485+
485-

485+ 485- SG

SG

Figure 4-8. 485Commnication Port

4.8. Ethernet Port(RJ45)


Ethernet Port (RJ-45) has 8 pins and its constructions is as follows.

Table 4-8. EthernetPort Pin

BPS

LINK
Pin No.
1

RJ45
XPORT

Figure 4-9. Ethernet Port

10Base-T Signal
100Base-TX Signal
White/Green
Transmit+
Wire Color

Green

Transmit-

White/Orange

Receive+

Blue

Unused

White/Blue

Unused

Orange

Receive-

White/Brown

Unused

Brown

Unused

ENHANCED TECHNOLOGY

27

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5. User Interface Panel


User Interface Panel uses LCD(20 4) and keypad to select functions and monitors switch status,
and also with LEDs, selected functions status and switch operation status can be checked.
User Interface Panel provides following functions;

Switch control

Control status check

System status check

Metering value check

Saved records check in ETR300

Set check and change in ETR300

ETR300 -S02

Control & Communication Unit

RUN
DIAG/ERROR
RX / TX
AC SUPPLY
CHARGER
BATTERY
REVERSE POWER

FUN
UP
ESC

SEC CYCLE
DOWN

ENT
TIE CYCLE
SEC/TIE LOCKOUT
A FAULT
LAMP TEST
B FAULT

BATT'
CHECK

FI

RESET

C FAULT

TEST

GROUND
SEF
PROTECTION

ALTERNATE

ENABLED

SETTINGS

GROUND

SEF

ENABLED

ENABLED

A Phase Unbalance
B Phase Unbalance
C Phase Unbalance
ABC / RST LIVE
VA / VR

SECTION
ENABLED

RESET
VB / VS

LOCKOUT

VC / VT
REMOTE

AUX1
L1

ENABLED

L2
CONTROL

AUX2

L3

LOCKED
L4

CLOSE

OPEN
PORT F

Figure 5-1. User Interface Panel

28

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.1. Construction
Panel consists of following 12 parts ;

Operation section

Local control section

Menu control section

Other control section

Fault indication section

Line status indication section

Section status section

System diagnostic section

Battery status section

PCL status section

Other status section

Spare ports section

5.1.1. Operation Section


OPEN
Press [OPEN] button to send Trip signal to Switch.
CLOSE
Press [CLOSE] button to send Close signal to Switch.
ETR300 has close time delay and the close operation can be conducted after a set time. Set time
range is from 0.00 ~ 600.00 sec.
POSITION LED
Switch staus is indicated. Position LED is operated based on 52a contact.

Figure 5-2. Operation Selection

ENHANCED TECHNOLOGY

29

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.1.2. Local Control Section


Control panel shows all the status of function. If a function is enabled, LED is ON, and when
disabled, LED is OFF. Button changes Enable to Disable vice versa.

PROTECTION

ALTERNATE

ENABLED

SETTINGS

GROUND

SEF

ENABLED

ENABLED

SECTION

RESET

ENABLED

LOCKOUT

AUX1

REMOTE
ENABLED

AUX2

CONTROL
LOCKED

Figure 5-3. Local Control Section


Protection(Enable/Disable)
When Enable(LED ON), phase fault detecting is enabled and when Disable(LED OFF), phase
fault detecting is disabled.
NOTE : When Protection is enabled, all protection of ETR300 is on operation, however,
Ground fault and SEF(Sensitive Earth Fault) function shall be set individually on font panel.
Ground (Enable/Disable)
When LED is on, ground fault detecting is enabled and when LED is off, ground fault detecting is
disabled. It is only available when Protection is enabled. Although Ground LED is on, protection
is disabled, ground fault detection is not conducted.

SECTION(Enable/Disable)
When LED is ON, SECTION is enabled, and when LED is OFF, SECTION is disabled.

30

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Operation select(Local/Remote)
When LED is ON, Remote and Local operation are all available. When LED is OFF, only Local
operation is available.
Operation Lock(Lock/Unlock)
When it is Unlock, local and remote operations are all available. When it is Lock, local and
remote operations are not available.
NOTE : Even if operation lock status, Open, Lamp test, Battery load test and Menu
controlare all available.
ALTERNATE SETTINGS(Select)
When ALTERNATE SETTINGS LED is ON, Group setting becomes Alternate setting and the
Alternate setting is activated. When the LED is OFF,Group setting becomes Primary setting and
the primary setting is activated.
SEF(Enable/Disable)
When LED is ON, SEF is enabled. When LED is OFF, SEF is disabled. Although SEF is
enabled,Protoection is not enabled, SEF is not activated.
SEC/TIE LOCKOUT(Unlock)
SEC/TIE LOCKOUT is dismissed.
AUX(1/2)
Aux. function button.

ENHANCED TECHNOLOGY

31

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.1.3. Menu Control Section


204 LCD is used to check setting, metering and
events, details informations are refer to 5. Operation
manual(How to use LCD).

204 character LCD

4 operation button(Increase, Decrease, Function


selection)

FUN
UP
ESC

DOWN

ENT

Figure 5-4. Menu Control Section

5.1.4. Other Control Section


LAMP TEST
BATT'
CHECK

FI

RESET

TEST

Figure 5-5. Other Control Section


Lamp Test Button

Normal : Press the button to check all Lamps.

FI occurred : It resets FI Target by pressing the button.

Battery
It takes 5 seconds to check battery and charging circuit. When pressing the button and if AC
power supply is provided, charging circuit is disconnected and connects a load resister to battery
and check the charging circuit.

FI Test
When pressing FI Test button, trip test begins beased on set value.

32

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.1.5. Fault Indication Section


In case of Permenant or Instantaneous fault, corresponding LED

A FAULT

is ON. LED lamp can be off by manually from local by pressing


FI Reset button or from remote by sending a signal. Otherwise,

B FAULT
C FAULT

LED lamp will be on although H.V. line becomes normal.

GROUND
SEF

Figure 5-6. Fault Indication


Section

5.1.6. H.V. line status indication section


Phase Unbalance lamp

A Phase Unbalance

Phase A,B,C Unbalance are indicated.

B Phase Unbalance

Under condition that source side and load side are all live line
and switch is open status, check angles, if it meets then, it is OK,

C Phase Unbalance
ABC / RST LIVE

otherwise, it is unbalanced.
Although it is unbalanced, control is still available. Operater
shall decide an operation.

VA / VR
VB / VS
VC / VT

Live line lamp

Figure 5-7. Disconnect/Open

Source side and load side live line status are indicated.

phase Lamp

More than one phase voltage is higher than an Off Level of


Disconnect line/Open phase, it is Live line. And all 3 phases are
less than that, it is Dead line. Operater shall decide an operation.
Phase Open/Loss lamp
Source and load side Phase A, B, C Open/Loss phase are
indicated. In case that 1 or 2 phases voltage is less than Off
Level

of

Disconnect/Open

phase, it is determined

as

Disconnet/Open phase. LED will be Off when the voltages are


higher than On Level.

ENHANCED TECHNOLOGY

33

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.1.7. System Diagnostic Section


ETR300-R Diagnostic is displayed. RUN Lamp(green) indicates that ETR300 has passed the
internal diagnostic test and does not have any problem.

RX/TX Lamp(Red) indicates the

communication state of ETR300

RUN : It indicates the operation status. In normal


operation, it flicker periodically. In system problem

RUN

case , it is lighting or turned off.

DIAG/ERROR

DIAG/ERROR : Turn on with abnormality of Self


Diagnostic.

RX / TX

RX : Turn on when transmit data

TX : Turn on when transmit data

Figure 5-8.System Diagnostic Lamp

5.1.8. Section Status Section


Indicates present staus of set section function process.

SEC Sequence: Indicates Section operation status.

TIE Sequence: Indicates Tie sequence operation status.

SEC/TIE Sequence End : Indicates sequence Lockout

TIE CYCLE

status.

SEC/TIE LOCKOUT

SEC CYCLE

Figure 5-9. Section Status Lamp

5.1.9. Battery Status Section


The system power status of ETR300 is displayed. When ETR300 is supplying external power, AC
SUPPLY Lamp is on. CHARGER lamp shows the charging status of ETR300 and the BATTERY
lamp shows the battery status of ETR300.

AC SUPPLY : Indicates the external AC power supply


status.

CHARGER : Turn on, when the charger status is

AC SUPPLY
CHARGER

normal.

BATTERY : Turn on, when the battery status is

BATTERY

normal.
Figure 5-10. Battery Status
Lamp

34

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.1.10. User LED Section


LED can be indicated according to the user setting.
L1

LED logic can be set in ETR300 interface software

L2
L3
L4

Figure 5-11. User Lamp

5.1.11. Other Status Section


REVER POWER

REVERSE POWER

In reverse current case, the REVER POWER lamp becomes


On.

Figure 5-12. Rever Power lamp

5.1.12. Port F Section


This connection port is for the communication with administration program. It obtains setting
change, control and others events.

TYPE : RS232C(male)

Pin 2 : RXD

Pin 3 : TXD

Pin 5 : GND

Pin 1,4,6,7,8,9 : N/G

Location : Front panel

PORT F

Figure 5-13. Port F

ENHANCED TECHNOLOGY

35

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.2. Operation Manual (LCD instruction)


5.2.1. LCD Screen
20 4 character LCD which has back-light support, is used for a user to operate conveniently and
to check operation status clearly.

5.2.2. Control button


LCD Control button is composed of four basic keys(increase, decrease, function/cancel, ENT).
Following table is explanation of the keys.
Table 5-1.Control Button
Button

Explanation

Move to menu selection mode from display mode and move to prior menu from
sub-menu. When press the button in Main Menu it is changed into display
ESC
mode. When this key is operated after changed the value, all changed value are
FUNC/CANCEL reverted to original setting value.
FUN

ENT

ENT

UP

INCREASE

DOWN

DECREASE

36

It is used for menu selection or setting change. In menu selection screen this
button is used for menu selection function. In setting change status moves to
menu mode by pressing this button (it operates in toggle method in menu
selection.setting change)
It is used to move the menu into above side or to increase the setting point. As
all menu has circulated function, from the top menu moves into the lowest
menu. In setting change case, after highest setting value comes the lowest
setting value. A level is increased by pressing the button and it is increased
quickly by pressing the button over 2 seconds.
It is used to move the menu or to decrease the changed value.
This button has circulated function for menu change/setting change as
[increase] button. A level is decreased by pressing the button and it is decreased
quickly by pressing the button over 2 seconds.

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.2.3. Menu structure tree

Screen structure consists Initial Logo and Main menu.

Initial screen and all menu are round robin algorithm.

Menu screen is composed of setting and event management menu.

[ ]

[ ]

[MAIN MENU]

[BI-CCU(S) FOR DAS]


SECTION
: DISABLE
S/W STATUS :
OPEN
[ RESET ]

>1.GLOBAL SETTING

>2.GROUP SETTING

>3.EVENT

>4.MAINTENANCE

>5.TIME

A:00000
00.0/00.0
B:00000
00.0/00.0
C:00000
00.0/00.0
N:00000[00.000-0000]

>6.STATUS

>7.METERING

Figure 5-14. Initial Logo and Main Menu

ENHANCED TECHNOLOGY

37

SWITCH CONTROL ETR300-S01

[MAIN MENU]

http://www.entecene.co.kr

>1.GLOBAL SETTING

>1.SYSTEM

>1.POWER LINE
2.CURRNET SENSING
3.VOLTAGE SENSING

>2.COMMUNICATION

>1.PROTOCOL SETUP

>3.EVENT RECORDER

>2.PORT SETUP

>4.MONITORING

>1.PHASE DIFF

>1.DNP1
2.DNP2
3.IEC870-5-101
4.IEC870-5-104
5.MODBUS
>1.PORT1(232)
2.PORT2(485)
3.PORT3(ETHERNET)
4.PORTF(232)

>2.OPERATION COUNT

>3.CONTACT WEAR
>4.BATTERY TEST

>5.PQM
>6.TD MONITOR

>1.PQM FUNCTION
2.INTERRUPT
3.SAG
4.SWELL
5.HARMONICS
6.CURR UNBALANCE
7.VOLT UNBALANCE
8.UNDER VOLTAGE
9.OVER VOLTAGE
10.UNDER FREQUENCY

>7.V0 DETECT

>5.PLC

>1.COMMON

>2.DI/DO

>6.OTHERS

>*.SAVE SETTING

>2.GROUP SETTING

>1.PICKUP CURRENT

>2.INRUSH RESTRAINT

>2.ALTERNATE

>3.DIRECTION

>4.F.I SETTING TIME

>3.EVENT

>5.F.I RESET

>6.SECTION
>7.DELTA I

>8.OVER CURRENT

>*.SAVE SETTING

>4.MAINTENANCE

>1.COUNT

>2.INTERRUT TIME

>3.CONTACT WEAR

>4.DATA RESET

>5.CCU INFO
>5.TIME
>6.F.I TEST

>6.STATUS

>7.METERING

>1.SWITCH
2.INPUT PORTS
3.OUTPUT PORTS

>1.CCU
2.OPERATION
3.FAULT
4.DELTA I
5.PQM
>1.CCU COUNT
2.OPERATION COUNT
3.FAULT COUNT
4.DELTA I COUNT
5.PQM COUNT
6.COUNT ALL
7.INTERRUT TIME
8.CONTACT WEAR
9.ENERGY
10.ABOVE ALL

>1.CURRENT
2.VOLTAGE
3.FREQUENCY
4.POWER
5.ENERGY
6.DEMAND
7.UNBALANCE
8.HARMONICS
9.TRUE R.M.S
10.TD
11.CCU SEF

Figure 5-15. Menu Tree Structure

38

>1.INPUT DEBOUNCE
2.OUTPUT PULSE TIME

>1.FACTORY DEBUG

>1.PRIMARY

>1.OPERATION
2.FAULT
3.FAULT CYCLE
4.SYSTEM
5.SET CHANGE
6.AVER.LOAD/MIN
7.PEAK.LOAD/HOUR
8.PEAK.LOAD/DAY
9.DIGNOSTIC
10.PQM
11.CLEAR SAVED DATA

>1.LOGIC TIMER
2.PULSE TIMER
3.PULSE COUNTER

ENHANCED TECHNOLOGY

>1.PHASE
2.GROUND
3.SEF

SWITCH CONTROL ETR300-S01

[MAIN MENU]

>1.GLOBAL SETTING

http://www.entecene.co.kr

>1.SYSTEM

>2.COMMUNICATION

>1.POWER LINE
2.CURRENT SENSING
3.VOLTAGE SENSING
4.CB OPENING TIME
>1.PROTOCOL SETUP

>2.PORT SETUP

>1.PORT1(232)
2.PORT2(485)
3.PORT3(ETHERNET)
4.PORTF(232)

>3.EVENT RECORDER

>3.DIALUP MODEM

>1.DIAL1
2.DIAL2

>4.MONITORING

>1.SYNCHROCHECK
2.OPERATION COUNT
3.CONTACT WEAR
4.BATTERY TEST

>5.PQM

>5.LOOP CONTROL

>6.PLC

>7.OTHERS

>*.SAVE SETTING

>2.GROUP SETTING

>1.SELECT SETBANK

>2.PRIMARY

>3.ALTERNATE

>4.EDITBANK

>6.TD MONITOR
7.V0 DETECT

>1.LOGIC TIMER
2.PULSE TIMER
3.PULSE COUNTER

>2.DI/DO

>1.INPUT DEBOUNCE
2.OUTPUT PULSE TIME

>1.TIME DISPTYPE
2.PANEL SLEEP TIME
3.FACTORY DEBUG
>1.OPERATION
2.INTERVALS
3.PICKUP CURRENT
4.PHASE FAST
5.PHASE DELAY
6.GROUND FAST
7.GROUND DELAY
8.SEF ELEMENT
9.NEG SEQ FAST
10.NEG SEQ DELAY
11.H/C TRIP-PHA
12.H/C TRIP-GND
13.H/C TRIP-NEG
14.H/C LOCKUOT-PHA
15.H/C LOCKUOT-GND
16.H/C LOCKUOT-NEG
17.COLD LOAD PICKUP
>18.DIRECTION

>19.VOLTAGE

>20.FREQUENCY
>1.OPERATION
2.FAULT
3.FAULT CYCLE
4.SYSTEM
5.SET CHANGE
6.AVER.LOAD/MIN
7.PEAK.LOAD/HOUR
8.PEAK.LOAD/DAY
9.DIGNOSTIC
10.PQM
11.PD

>12.CLEAR SAVED DATA

>4.MAINTENANCE

>1.COUNT

>2.INTERRUT TIME

>3.CONTACT WEAR

>4.DATA RESET
>5.TIME
>5.CCU INFO

>6.STATUS

>7.METERING

>1.RECLOSER
2.INPUT PORTS
3.OUTPUT PORTS
>1.CURRENT
2.VOLTAGE
3.FREQUENCY
4.POWER
5.ENERGY
6.DEMAND
7.UNBALANCE
8.HARMONICS
9.TRUE R.M.S
10.PD
11.TD
12.CCU SEF

>1.PQM FUNCTION
2.INTERRUPT
3.SAG
4.SWELL
5.HARMONICS
6.CURR UNBALANCE
7.VOLT UNBALANCE
8.UNDER VOLTAGE
9.OVER VOLTAGE
10.UNDER FREQUENCY

>1.COMMON

>5.AUTO SGRP CHANGE

>3.EVENT

>1.DNP3
2.IEC870-5-101
3.IEC870-5-104
4.MODBUS

>21.OTHER ELEMENT

>22.USER CURVE

>1.PHASE
2.GROUND
3.SEF
4.NEG SEQ
>1.UNDER VOLTAGE 1
2.UNDER VOLTAGE 2
3.OVER VOLTAGE 1
4.OVER VOLTAGE 2
>1.UNDER FREQUENCY
2.OVER FREQUENCY
>1.USER
2.USER
3.USER
4.USER

CURVE
CURVE
CURVE
CURVE

1
2
3
4

>23.LIVE LOAD BLOCK


*.SAVE SETTING
>1.OPERATION
2.FAULT
3.SYSTEM
4.SET CHANGE
5.LOAD PROFILE
6.DIGNOSTIC
7.PQM
8.PD
9.ABOVE ALL
>1.CCU
2.OPERATION
3.FAULT
4.DELTA I
5.PQM
6.PD
>1.CCU COUNT
2.OPERATION COUNT
3.FAULT COUNT
4.DELTA I COUNT
5.PQM COUNT
6.PD COUNT
7.COUNT ALL
8.INTERRUT TIME
9.CONTACT WEAR
10.ENERGY
11.ABOVE ALL

ENHANCED TECHNOLOGY

39

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.2.4. GLOBAL Setting


SYSTEM
Set items related to system elements. Consists of POWER LINE, CURRENT SENSING,
VOLTAGE SENSING and CB OPENING TIME.

COMMUNICATION
Set the items related to the communication elements. Consists of PROTOCOL SETUP and PROT
SETUP.

EVENT RECORDER
Set the items related to the event recorder elements.

MONITORING
Set the items related to metering and maintenance. Consist of OPERATION COUNT, CONTACT
WEAR, BATTERY TEST, PQM, TD MONITOR and V0 DETECTION.

PLC
Set the items related to PLC (Progamable Logic Control) elementsConsist of COMMON and
DI/DO.

OTHERS
Set the items related to the others elements.

SAVE SETTING
Save all changed setting value.

40

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.2.5. GROUP Setting


This menu is divided into Primary Group and Alternate Group for the convenience of the user and
according to the ON/OFF of ALTERNATE SETTINGS lamp of ETR300 panel the applied
group is selected.

(1) Select Set-group


It is composed of Primary group and Alternate group.

PRIMARY group : When ALTERNATE SETTINGS lamp is OFF, the set point of
Primary group is applied in the line operating element.

ALTERNATE group : When ALTERNATE SETTINGS lamp is ON, the set point of
Alternate group is applied in the line operation element.

ALTERNATE
SETTINGS

[GROUP SETTING]
>1.PRIMARY
2.ALTERNATE

Ficture 5-16. PRIMARY group and ALTERNATE group


By using [ALTERNATE SETTINGS] button, can change the applied group of current protective
unit.

(2) Primary Setting


This menu set the items related to the line operating elements.

(3) Alternate Setting


This menu set items related to the line operating elements. Setting items are same with
PRIMARY SETTING.

ENHANCED TECHNOLOGY

41

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.2.6. Event
This menu displays the event information of ETR300. For more details refer the 8. Event

5.2.7. Maintenance
This menu displays the maintenance information of ETR300.

COUNTER : Indicates counter information related to the system.

INTERRUT TIME : Displays the occurring accumulated time if interruption.

CONTACT WEAR : Display the connect life of the switch.

DATA RESET : Reset the datas related to Maintenance.

CCU INFO : Display the current information of ETR300

For more details refer the 10. Maintenance .

5.2.8. Time
Check and set the current time.

5.2.9. Status
Display the current status and input output port status of the switch.

5.2.10. Metering
This menu displays the metering value. For more details, refer to 12. METERING .

42

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.3. LCD Menu Use


5.3.1. INITING screen
The main information of ETR300 is displayed in the initial screen, for the easy access and
understanding of the user.

To move to other initial screen, press [] [] button.

Press [FUN] button in initial screen to move to Main menu.

INITNG LOGO
[BI-CCU(S) FOR DAS]
SECTION
: DISABLE
S/W STATUS :
OPEN
[ RESET ]
[BI-CCU(S) FOR DAS]
SECTION
:

S/W STATUS :

Start-up screen1
SENTION: Indicate the section function status (DISABLE/ENABLE).
S/W STATUS: Indicate the switch status (OPEN/CLOSE).
SENTION Indicate the operation status
- RESET
- RUNNING
- LOCKOUT

NOTE :
When WARING SYSTEM ERROR is displayed,means that the control
section is in bad status. Finisht the operation immediately and contact to the
manufacturer.

A:00000
00.0/00.0
B:00000
00.0/00.0
C:00000
00.0/00.0
N:00000[00.000-0000]
A:
B:
C:
N: [

/
/
/
-

Starut-up screen2
Indicate the current of each phase(A,B,C,N).[A].
Indicate the voltage of each phase(A,B,C,R,S,T). [kV].
Indicate SEF current[A].
Indicate the zero phase voltage[V].

ENHANCED TECHNOLOGY

43

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.3.2. Main Menu


In the initial menu, press [FUN] button, it is moved into Main menu. If press [FUN] button in
main menu, it is moved to the initial menu. Main menu has sub-menu as below.
MAIN MENU
[MAIN MENU]
>1.GLOBAL SETTING
2.GROUP SETTING
3.EVENT
4.MAINTENANCE
5.TIME
6.STATUS
7.METERING

Main Menu is composed of 7 submenus.


Select the submenu by using [] [] key.
Move to the submenu by pressing [ENT] key.

As the above explanation, you can move or select the submenu..

5.3.3. View Example


Move to MAIN MENU / STATUS / INPUT PORTS to see the external input port status.
The following screen is displayed.
MAIN MENU/ STATUS/ INPUT PORTS
[INPUT PORT]
IN 101 :LO/DEASSERT
IN 102 :LO/DEASSERT
IN 103 :LO/DEASSERT
IN 104 :LO/DEASSERT
IN 105 :LO/DEASSERT
IN 106 :LO/DEASSERT
IN 107 :LO/DEASSERT
IN 108 :LO/DEASSERT
IN 201 : HI/ASSERT
IN 202 : HI/ASSERT
IN 203 : HI/ASSERT
IN 204 : HI/ASSERT
IN 205 : HI/ASSERT
IN 206 : HI/ASSERT
IN 207 : HI/ASSERT
IN 208 : HI/ASSERT

44

LO/DEASSERT : Shows External Input is de-asserted,


HI/ASSERT

: Shows External Input is asserted.

4 lines are displayed in the LCD screen.


See next line by using [] [] key .

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.3.4. Setting Example


Change of Phase Pickup Current of line operating element of Primary setting.
1) Move toMAIN MENU/ GROUP SETTING/ PRIMARY/ PICKUP CURRENT / PHASE.
The following screen is displayed.
MAIN MENU/ GROUP SETTING/ PRIMARY/ PICKUP CURRENT / PHASE
[PICKUP CURRENT]
>Phase:
400
Ground:
70
S.E.F:
OFF

Range

OFF, 50 ~ 630A

Default 300

Step

5A

Set the Phase Pickup Current.

2) In the above screen, locate the cursor on Phase by using choose [] [] key and then press
the [ENT] key to change the set point.
3) Change in new setting point by using [] [] key.
By pressing [ENT] key, you can see the changed phase setting point.
NOTE : Be sure to save all changed set point in the menu *. Setting Save.

ENHANCED TECHNOLOGY

45

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

5.3.5. Setting Save


Follow the following step to save all changed set point.
Move to MAIN MENU/ GROUP SETTING/ PRIMARY / SAVE SETTING and follow the
following step. (Global Setting menu and Group Setting or Alternate menu have the
*.Setting Save menu).
MAIN MENU / PRIMARY SETTING / SAVE SETTING

To save the changed setting value, press [ENT] button in screen . If


SETTING CHANGED
PRESS <ENT> TO SAVE

the change has succeed screen is appeared.


If, there is nothing changed and select *. SAVE SETTING, the

* NOTHING CHANGED *

[SAVE SETTING]

screen is displayed.
NOTE :
Changed set value is applied if the changed set value is saved.
If changed set value saving is cancelled, previous value is
remained.

* SUCCESS *

46

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6. Global Setting
Locate the cursor on 1.GLOBAL SETTING in the main menu, and move to this menu by
pressing [ENT]. GLOBAL SETTING menu has the following submenu.

[GLOBAL SETTING]
>1.SYSTEM
2.COMMUNICATION
3.EVENT RECODER
4.MONITERING
5.PLC
6.OTHERS
*.SAVE SETTING

NOTE : The changed setting point works after being saved.


When cancel the save, setting point maintain the previous value.

6.1. System
Locate the cursor on 1.SYSETM in GLOBAL SETTING menu and move to this menu by
pressing [ENT] button. In this menu, various elements related to the system can be set. It has the
following submenu.

[SYSTEM]
>1.POWER LINE
2.CURRENT SENSING
3.VOLTAGE SENSING

NOTE : Do not change the setting elements of SYSTEM , as they are set according to the
characteristics of recloser.

ENHANCED TECHNOLOGY

47

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.1.1. Power Line


Locate the cursor on 1.POWER LINE in SYSTEM menu, move to this menu by pressing [ENT]
button. In this menu, enter the Line information of the device installation location.
GLOBAL SETTING / SYSTEM / POWER LINE / Frequency
[POWER LINE]
>Frequency:
50
Phase Rotation: ABC
[50/60Hz]

Range

50, 60

Default 50

Step

Select the nominal power system frequency. This value is used as a


default to set the optimal digital sampling rate.

GLOBAL SETTING / SYSTEM / POWER LINE / Phase Rotation


[POWER LINE]
Frequency:
60
>Phase Rotation: ABC
[ABC/ACB]

Range

ABC, ACB

Default ABC

Step

Select the phase rotation of the power system.

GLOBAL SETTING / SYSTEM / POWER LINE / Nominal Volt


[POWER LINE]
>Nominal Volt: 11500
[1000~30000:10V]

Range

1000 ~ 30000V

Default 11500

Step

10V

Set the rated voltage of the power system

6.1.2. Current Sensing


Locate the cursor on 2.CURRENT SENSING in SYSTEM menu, move to this menu by pressing
[ENT] button.
Enter the exact CT rate for the accurate metering and monitoring.
Enter the CT rate after changing the second side in 1 Amp.
GLOBAL SETTING / SYSTEM / CURRENT SENSING / CT-Ratio
[CURRENT SENSING]
>CT-Ratio:
1000
CT-Polarity:
FOR
[1~2000:1]

Range

1 ~ 2000

Default 1000

Step

Enter the CT rate.

GLOBAL SETTING / SYSTEM / CURRENT SENSING / CT-Polarity

48

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

[CURRENT SENSING]
CCT-Ratio:
1000
>CT-Polarity:
FOR
[FOR/REV]

Range

http://www.entecene.co.kr

Forward, Reverse

Default Forward

Step

Enter the CT polarity.

GLOBAL SETTING / SYSTEM / CURRENT SENSING / ZCT-Ratio


[CURRENT SENSING]
>ZCT-Ratio:
133.3
ZCT-Polarity:
FOR
0(OFF),0~1000.0:0.1

Range

0(OFF), 0.1 ~ 1000.0

Default 133.3

Step

0.1

Enter the ZCT rate..

GLOBAL SETTING / SYSTEM / CURRENT SENSING / CT-Polarity


[CURRENT SENSING]
CZCT-Ratio:
1.0
>ZCT-Polarity:
FOR
[FOR/REV]

Range

Forward, Reverse

Default Forward

Step

Enter the ZCT pole direction

ENHANCED TECHNOLOGY

49

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.1.3. Voltage Sensing


Locate the cursor on 3.VOLTAGE SENSING in the SYSTEM menu, move to this menu by
pressing the [ENT] button.
ETR300 has 2 Voltage Connectors. Voltage connectors are receiving Source side and Load side
line voltages. To measure received voltages, set Voltage connectors Connect Type, 2nd Nominal
Voltage and VT Ratio.
According to the installed line VT, ETR300 performs the voltage metering, power calculation and
direction control of over current, and the line VT can be used to perform the Phase Sync Fail.
GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 1V Connect Type
[VOLTAGE SENSING]
>1V CON-Type:
WYE
Reference Phase: A
[NONE/WYE/DELTY]

Range

NONE, WYE, DELTA

Default WYE

Step

st

Select 1V(1 voltage connector).


NONE : VT uninstalled. Select NONE if Voltage Sensing item is
not used.
WYE : If Voltage Connect type of 1V is Y type, select WYE.
DELTA : If Voltage Connect type of 1V is -type, select DELTA.

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / Reference Phase


[POWER LINE]
>1V CON-Type:
WYE
>Reference Phase: A
[A/B/C]

Range

A, B, C

Default A

Step

Enter base voltage of Voltage connector.


. NOTE ) The connect phase of main bushing changes according to
the Base Voltage of Voltage connector and phase
rotation of power system(MAIN MENU(COM)/
GLOBAL SETTING/ SYSTEM/ POWER LINE/
Phase Rotation). Table 6-1. Refer to the phase
selection according to the base voltage and phase
rotation.

50

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Table 6-1. Phase selection according to the base voltage and phase rotation.
Setting
Terminal

Base
Voltage
Phase
Rotation

REF A

REF B

REF C

ABC

ACB

ABC

ACB

ABC

ACB

Device A Bushing

Device B Bushing

Device C Bushing

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 1V 2nd(V)


[VOLTAGE SENSING]
>1V 2nd(V):
4.0
>1V Ratio:
3300.0
[2.0~350.0:0.1V]

Range

2.0 ~ 350.0V

Default 4.0

Step

0.1V

Enter the second rated voltage(V) of 1V(1st Voltage connector).


This setting is the second rated voltage that entered in the relay about
line rated voltage.

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 1V Ratio


[VOLTAGE SENSING]
>1V 2nd(V):
4.0
>1V Ratio:
3300.0
[10.0~6500.0:0.1]

Range

10.0 ~ 6500.0

Default 3300.0

Step

0.1

Enter the VT rated rate of 1V(1st Voltage connector).

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 2V Connect Type


[VOLTAGE SENSING]
>2V CON-Type:
WYE
2V 2nd(V):
4.0
[NONE/WYE/DELTY]

Range

NONE, WYE, DELTA

Default WYE

Step

Select the voltage type of system that input to 2V(2nd Voltage


Connector) .
NONE : VT non installed. Select NON if Voltage Sensing item is
not used.
WYE : If Voltage Connect Type of 2V is Y-Type, Select WYE.
DELTA : If Voltage Connect Type of 2V is -Type, Select DELTA.

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 2V 2nd(V)

ENHANCED TECHNOLOGY

51

SWITCH CONTROL ETR300-S01

[VOLTAGE SENSING]
>2V 2nd(V):
4.0
>2V Ratio:
3300.0
[2.0~350.0:0.1V]

Range

http://www.entecene.co.kr

2.0 ~ 350.0V

Default 4.0

Step

0.1V

Enter the second rated voltage(V) of 2V(2nd Voltage Connector).


This setting is the second rated voltage that entered in the relay about
line rated voltage.

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 2V Ratio


[VOLTAGE SENSING]
>2V 2nd(V):
4.0
>2V Ratio:
3300.0
[10.0~6500.0:0.1]

Range

10.0 ~ 6500.0

Default 3300.0

Step

0.1

Enter the VT Rated Rate of 2V(2nd Voltage Connector).

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / Source Side


[VOLTAGE SENSING]
>2V Ratio:
3300.0
>Source Side:
1V
[1V/2V]

Range

1V, 2V

Default 1V

Step

Select the Source side of System.


According to the selected value the indication of MAIN MENU/
METERING/ VOLTAGE change. In the VOLTAGE screen, indicate
ABC in the Source Side, and RST in the Load Side.

52

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Setting Examples
In case of Y-type connection use, set VT2nd[V] for 4V initial value, and if the primary phasephase voltage is 15 -, VT ratio is calculated as below.
Voltage- = Voltage-N

nd

Voltage-N = VT 2 [V] VT Ratio


8.66-N = 15 - / 3
8.66-N = 4[V] 2165
According to the above formula, VT rate is calculated in 2165.
With the same VT2nd[V] and VT ratio, if the primary phase-phase voltage(Voltage-) is 11kV,
the primary phase voltage is 6.35-N (=11

3 ), VT secondary input voltage is

3V(=6.35-N /2165)
In case that -type connection is used, if VT2nd[V] is 4V and the primary phase to phase to phase
is 15 -, VT ratio is 3750(15 - /4V = 3750).
Table 6-2. VT Rated Rate
Wye connection

Line-Line

Delta connection

Votage

VT 2nd (v)

VT Ratio

VT 2nd (v)

VT Ratio

15

2165

100

150

27

3897.1

100

270

38

5484.8

100

380

ENHANCED TECHNOLOGY

53

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.2. Communication
Locate the cursor on 2. COMMUNICATION in GLOBAL SETTING, move to this menu by
pressing [ENT] button. In this menu, all elements related to the communication can be set and has
the following submenu.

[COMMUNICATION]
>1.PROTOCOL SETUP
2.PORT SETUP

6.2.1. Protocol Setup


Locate the cursor on 1. PROTOCOL SETUP in COMMUNICATION menu, move to this menu
by pressing [ENT] button. In this menu, set the communication protocol that is supported ETR300.
This menu has the following submenu.

[PROTOCOL SETUP]
>1.DNP3

ETR300 supports DNP3, IEC60870-5-101, IEC60870-5-104 and MODBOUS according to the


communication conditions of the user. Each supported protocol can be set.

6.2.1.1. DNP3.0 Protocol Setup


ETR300 can DNP3.0 communicate by using the communication port1, port2, port3 or port4. For
more information refer the DNP3.0 Protocol Technical Manual.
DNP3.0 protocol setting menu is as following.

54

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

(1) DNP3
To setting DNP3 Protocol move to MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/
PROTOCOL SETUP/ DNP3.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Function
[DNP3]
>Function:
COM Port:
[OFF/ON]

Range
ON
PORT1

ON, OFF

Default ON

Step

Toselect DNP3, set ON.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ COM Port


[DNP3]
>COM Port:
PORT1
D/L Confirm:
SOME
[PORT1/PORT2/PORT3]

Range

PORT1, PORT2, PORT3

Default PORT1

Step

Select DNP3 communication port.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L Confirm


[DNP3]
>D/L Confirm:
D/L FrameDly:
[NO/YES/SOME]

Range
SOME
100

NO, YES, SOMETIME

Default SOMETIME

Step

Choose whether Data Link Confirm is used or not.


NO : Data Link Confirm is not used.
YES : Data Link Confirm is used
SOMETIME : Use Data Link Confirm in case of multi frame.
When set the use of Data Link Confirm, check the setting status of
host and set same with the host. If the setting status is different with
the host can be occur an communication error because of Data Link
Reset.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L FrameDly


[DNP3]
>D/L Confirm:
>D/L FrameDly:
[10~5000:10ms]

Range
SOME
100

10 ~ 5000msec

Default 100

Step

10msec

Set Data Link frame Delay time.


If the D/L Confirm setting is OFF, means the transmission distance
between Frame when occurs multi frame.

ENHANCED TECHNOLOGY

55

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L Retries


[DNP3]
>D/L Retries:
D/L Timeout:
[0~2:1]

Range
0
10

0, 1, 2

Default 0

Step

Set the retry number of Data Link.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L Timeout


[DNP3]
>D/L Timeout:
A/L Retries:
[1~255:1s]

Range
10
0

1 ~ 255 sec

Default 10

Step

1 sec

Set the waiting time of Data Link Frame transmission to the Data Link
Confirm (ACK) receiveing of the master side. ETR300 resends the
Data Link Frame, when the Data Link Confirm has not received
during the setting time and it is possible to retry the Data Link.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ A/L Retries


[DNP3]
>A/L Retries:
A/L Timeout:
[0~2:1]

Range
0
15

0, 1, 2

Default 0

Step

Set the retry number of Application Link Layer.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ A/L Timeout


[DNP3]
>A/L Timeout:
15
Fault I Report: YES
[1~255:1s]

Range

1 ~ 255 sec

Default 15

Step

1 sec

In case that request Confirm during the data transmission from Slave
Application to Master Application, set the maximum time of A/L
Confirm(ACK) receiving from Mast Application to Slave Application.

56

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Fault I Report


[DNP3]
>A/L Timeout:
15
>Fault I Report: YES
[NO/YES/1SHOT]

Range

NO, YES, 1SHOT

Default YES

Step

NO : Do not send the all Fault Current Sequence to Event.


YES : Send all Fault Current Sequence to Event.
1SHOT : Send the first Sequence Fault Current of Fualt Sequence
to Event.
NOTE :
The Fault Current occurrence time of each Sequence is when
becomes no voltage after experience the Fault Current.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Fault I Reset


[DNP3]
>Fault I Report: YES
>Fault I Resec:
NO
[NO/YES]

Range

NO, YES

Default NO

Step

Set the Fault Current Initialization.


NO : Final Fault Current Value is maintained till the next fault
occurrence even the fault detection information is reseted.
YES : Fault Current Value is initialized in 0 at the time that
current detect information is canceld.
NOTE :
Fault Current is handled in RMS maximum value of each
Sequence Fault Current Waveform.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Master Addr


[DNP3]
>Master Addr: 65534
DNP Address:
0
[0~65534:1]

Range

0 ~ 65534

Default 65534

Step

Enter the DNP address of Master station. ETR300 refer this address
when send Unsol message.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ DNP Address


[DNP3]
>DNP Address:
SBO Time:
[0~65534:1]

Range
0
15

0 ~ 65534

Default 0

Step

Enter the address of Slave(ETR300).


GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ SBO Time

ENHANCED TECHNOLOGY

57

SWITCH CONTROL ETR300-S01

[DNP3]
>SBO Time:
Debounce Time:
[1~255:1s]

Range
15
20

http://www.entecene.co.kr

1 ~ 255 sec

Default 15

Step

1 sec

Set the time interval between Select Function and Operate Function.
It is time that maintain the Select order after receiving it, if there is not
an operation order during setting value the select order is canceled.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Debounce Time


[DNP3]
>SBO Time:
>Debounce Time:
[10~100:20ms]

Range
15
20

10 ~ 100 msec

Default 20

Step

5 msec

Set the connection debounce time


But, the debounce time of door open information it is fixed in 1
second.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Aver. Load Calc T


[DNP3]
>Aver.Load Calc T:15
>Daily Max I: ENABLE
1~6/10/12/15/20/30m

Range

1/2/3/4/5/6/10/12/15/20/30 min

Default 15

Step

Set the time interval for the calculation of average load current.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Daily Max I


[DNP3]
>Aver.Load Calc T:15
>Daily Max I: ENABLE
[DISABLE/ENABLE]

Range

DISABLE, ENABLE

Default ENABLE

Step

Select the [DISABLE/ENABLE] of Daily Maximum Load Current


transmission.
DISABLE : Do not process Daily Maximum Load Current Event..
ENABLE : Process Daily Maximum Load Current.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Init Unsol


[DNP3]
>Daily Max I: ENABLE
>Init Unsol: ENABLE
[DISABLE/ENABLE]

Range

DISABLE, ENABLE

Default ENABLE

Step

Select [DISABLE/ENABLE] of Initial Unsolicited Response Use


when Power Up.
Enable : When Power Up, transmit the Initial Unsolicited
Response Message.
Disable : When Power Up, do not transmit Initial Unsolicited
Response Message.

58

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Class 1


[DNP3]
>Class 1:
ENABLE
Class 2:
ENABLE
[DISABLE/ENABLE]

DISABLE, ENABLE

Range

Default ENABLE

Step

Select [ENABLE/DESABLE] of Unsolicied Response transmission to


the master station when occurs an Event in Class 1.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Class 2


[DNP3]
>Class 1:
ENABLE
>Class 2:
ENABLE
[DISABLE/ENABLE]

DISABLE, ENABLE

Range

Default ENABLE

Step

Select [ENABLE/DESABLE] of Unsolicied Response transmission to


the master station when occurs an Event in Class 2.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Class 3


[DNP3]
>Class 2:
ENABLE
>Class 3:
ENABLE
[DISABLE/ENABLE]

DISABLE, ENABLE

Range

Default ENABLE

Step

Select [ENABLE/DESABLE] of Unsolicied Response transmission to


the master station when occurs an Event in Class 3.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Unsol Time


[DNP3]
>Class 3:
ENABLE
>Unsol Time:
5
[0~60:1s]

0 ~ 60 sec

Range

Default 5

Step

1 sec

Set the delay time of Unsolicited mode event transmission to the


master station. It is transmitted if new event does not happen during
this time.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ VOC Leve1(%)


[DNP3]
>VOC Level(%):
OFF
>VOC Min:
100
[0(OFF),1~50:1%]

Range

0(OFF), 1 ~ 50 %

Default OFF

Step

1%

Set the detect level of VOC(Value Of Change) Event1.


When set in OFF, does not occur Event information.
Display the analog input regulation in percentage, in case that the
regulation is higher than the setting point it is reported by
communication.

ENHANCED TECHNOLOGY

59

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ VOC Min


[DNP3]
VOC Level(%):
>VOC Min:
[0~630:1A]

Range
OFF
100

0 ~ 630 A

Default 100

Step

1A

Set VOC level to detect VOC Event.


In case that analog input value is under minimum value, does not
transmit communication to the superior.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ VOC Select


[DNP3]
>VOC Min:
>VOC Select:
[RMS/AVER]

Range
100
AVER

RMS, AVER

Default AVER

Step

Select current used for the VOC decision.


RMS : Apply virtual value current to VOC detection.
AVER : Apply average current to VOC detection.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ TCP/IP Port


[DNP3]
>TCP/IP Port:
IP Addr1:
[1~65535:1]

Range
0
0

0 ~ 65535

Default 0

Step

Set TCP/IP port of ETR300.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ IP Addr1~4


>IP
IP
IP
>IP

[DNP3]
Addr1:
Addr2:
Addr3:
Addr4:

Range
0
0
0
0

0 ~ 255

Default 0

Step

Select the master station IP address for DNP3.0 communication.


IP Address : 192.xxx.xxx.xxx

IP Addr1,2,3,4 means ,,,.


For example, in case that the IP address is 255.255.255.255, set as
the following.
Master IP Oct1 : 255
Master IP Oct2 : 255
Master IP Oct3 : 255
Master IP Oct4 : 255

60

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.2.2. Port Setup


Locate the cursor on 2. PORT SETUP in COMMUNICATION menu, move to this menu by
pressing [ENT] button. In this menu, set the communication port and related elements of ETR300.
It has the following submenu.

[PORT SETUP]
>1.PORT1(232)
2.PORT2(485)
3.PORT3(ETHERNET)
4.PORTF(232)

6.2.2.1. PORT1(232) Setup


Set elements related to PORT1 which is located in the side panel of ETR300.
Move

to

MAIN

MENU/

GLOBAL

SETTING/

COMMUNICATION/

PORT

SETUP/PORT1(232) to set Port 1.


GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Baud Rate
[PROT1(232)]
>Baud Rate:
1200
Parity Bit:
NONE
[1200 ~ 19200 bps]

Range

1200, 2400, 4800, 9600, 19200 bps

Default 1200

Step

Select the baud rate of PORT1.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Parity Bit


[PROT1(232)]
Baud Rate:
1200
>Parity Bit:
NONE
[NONE/ODD/EVEN]

Range

NONE, ODD, EVEN

Default NONE

Step

Select the use of Parity Bit and its type.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Data Bit


[PROT1(232)]
Parity Bit:
NONE
>Data Bit:
8
[7~8:1]

Range

7, 8

Default 8

Step

Select the Data bit number which will be used for the communication.

ENHANCED TECHNOLOGY

61

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Stop Bit


[PROT1(232)]
Data Bit:
>Stop Bit:
[1~2:1]

Range
8
1

1, 2

Default 1

Step

Slect the Stop bit number which will be used for the communication.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Modem Sel


[PROT1(232)]
>Modem Sel:
4W
>CTS Usage:
ON
[2W/4W/D1/D2/NONE]

Range

2W, 4W, D1, D2, NONE

Default 4W

Step

Select a modem for communication.


2W : 2 wire private line is used and continuously Carrier is monitored
to control data flow by DCD(Data Carrier Detect).
4W : 4 wire private line is used and RTS(Request To Send) and
CTS(clear to Send) signal are used to control data flow.
D1 : Dial-Up1 modem is used.
D2 : Dial-Up2 modem is used.
NONE : Not used.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ CTS Usage


[PROT1(232)]
>Modem Sel:
>CTS Usage:
[OFF/ON]

Range
4W
ON

ON, OFF

Default ON

Step

Set the [OFF/ON] of CTS signal usage.


ON : Transfer the transmission data after checking that the CTS
signal is Assert.
OFF : Transfer the transmission data regardless of the CTS sign.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ DCD Usage


[PROT1(232)]
>DCD Usage:
OFF
>RTS Usage:
AUTO
[OFF/ON]

Range

ON, OFF

Default ON

Step

Set the [OFF/ON] of DCD signal usage.


ON : Transfer the transmission data checking that the DCD signal
is Deassert.
OFF : Transfor the transmission data regardless of the DCD signal.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ RTS Usage

62

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

[PROT1(232)]
>DCD Usage:
OFF
>RTS Usage:
AUTO
[OFF/ON/AUTO]

Range

http://www.entecene.co.kr

OFF, ON, AUTO

Default AUTO

Step

ON : RTS sign of ETR is always ON(Assert).


OFF : RTS sign of ETR300 is always OFF(Deassert).
AUTO : When request a data transmission to modem the RTS sign
of ETR300 is ON and when finish the transmission the RTS sign of
ETR300 is OFF.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ CTS CheckOut


[PROT1(232)]
>CTS CheckOut:
2
>DCD CheckOut: 5000
[1~255:1s]

Range

1 ~ 255 sec

Default 2

Step

1 sec

Set a waiting time that waits Modems confirmation on RTS signal


which informs that ETR300 is ready to transfer a data. If there is no
CTS response within a set time, RTU confirms CTS Fail and does not
transfer the data.
It is available if CTS Usage setting is ON.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ DCD CheckOut


[PROT1(232)]
>CTS CheckOut:
2
>DCD CheckOut: 5000
[10~30000:5ms]

Range

10 ~ 30000 msec

Default 5000

Step

5 msec

Set a delay time of DCD signal check which determine modem status
before sending RTS signal in 2 wire communication type. After a set
time, if DCD signal is ON, ETR300 does not transfer the data and
treat it as DCD Fail. It is available if DCD Usage setting is ON.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ RTS OffDelay


[PROT1(232)]
DCD CheckOut: 5000
>RTS Off Dly:
50
[10~500:5ms]

Range

10 ~ 500 msec

Default 50

Step

5 msec

RTS Off Delay Time set the delay time of RTS sign that becom Off
after the data transmission.
It is time delay to prevent the liss if last data after sending the data.
Commonly, RTS Off Delay Time is set in 1 or 2 Byte transmission
occur time.

ENHANCED TECHNOLOGY

63

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.2.2.2. PORT2(485) Setup


Set items related to the PORT2 located in the side panel of ETR300.
To set PORT2 move to MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT
SETUP/PORT2(485).
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Baud Rate
[PROT2(485)]
>Baud Rate:
1200
Parity Bit:
NONE
[1200 ~ 19200 bps]

Range

1200, 2400, 4800, 9600, 19200 bps

Default 1200

Step

Select the Baud Rate of PORT2 .

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Parity Bit


[PROT2(485)]
Baud Rate:
1200
>Parity Bit:
NONE
[NONE/ODD/EVEN]

Range

NONE, ODD, EVEN

Default NONE

Step

Select the use of Parity Bit and its type.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Data Bit


[PROT2(485)]
Parity Bit:
NONE
>Data Bit:
8
[7~8:1]

Range

7, 8

Default 8

Step

Select the Data Bit number used for the communication..

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Stop Bit


[PROT2(485)]
Data Bit:
>Stop Bit:
[1~2:1]

Range
8
1

1, 2

Default 1

Step

Select the Stop Bit number used for the communication.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Line Type


[PROT2(485)]
>Line Type:
RS422
CA Delay:
1.00
[RS422/RS485]

Range

RS422, RS485

Default RS422

Step

Select the Line Type used for the communication..


GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ CA Delay
[PROT2(485)]
>Line Type:
RS422
>CA Delay:
1.00
[0.00~240.00:0.01]

Range

0.00 ~ 240.00

Default 1.00

Step

0.01 sec

Set the Delay type of the answer data transmission after data receipt.

64

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.2.2.3. PORT3(EHTERNET) Setup


Set items related to the PORT3 located in the side panel of ETR300
To set PORT3 move to MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT
SETUP/PORT3(ETHERNET).
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ PORT3/ IP Addr Oct1 ~ 4
[PORT3(ETHERNET)]
>IP Addr Oct1:
0
IP Addr Oct2:
0
IP Addr Oct3:
0
IP Addr Oct4:
0

Range

0 ~ 255

Default 0

Step

Select IP address of ETR300.


IP Address : 192.xxx.xxx.xxx

IP Addr1,2,3,4 means ,,,.


For example, in case that the IP address is 255.255.255.255, set as
the following.
IP Addr Oct1 : 255
IP Addr Oct2 : 255
IP Addr Oct3 : 255
IP Addr Oct4 : 255
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ PORT3/ Gateway Oct1 ~ 4
[PORT3(ETHERNET)]
>Gateway Oct1:
0
Gateway Oct2:
0
Gateway Oct3:
0
Gateway Oct4:
0

Range

0 ~ 255

Default 0

Step

Select Gateway adress.


Gateway Address : 192.xxx.xxx.xxx

Gateway Addr1,2,3,4 means ,,,.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ PORT3/ SubnetMask Oct1 ~ 4


[PORT3(ETHERNET)]
>SubnetMask Oct1: 0
SubnetMask Oct2: 0
SubnetMask Oct3: 0
SubnetMask Oct4: 0

Range

0 ~ 255

Default 0

Step

Select Subnet Mask address of ETR300.


Subnet Mask Address : 192.xxx.xxx.xxx

Subnet Mask Addr1,2,3,4 means ,,,.

ENHANCED TECHNOLOGY

65

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.2.2.4. PORTF(232) Setup


Set items related to the PORTF located in the front panel of ETR300
To set the PORTF move to MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT
SETUP/PORTF(232) .
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Wireless
[PORTF(232)]
>Wireless:
DISABLE
Slave Addr:
1
[DISABLE/ENABLE]

Range

DISABLE, ENABLE

Default DISABLE

Step

Select the use[DISABLE/ENABLE] of Wireless communication.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Slave Addr


[DNP3]
>Slave Addr:
>Master Addr:
[0~65534:1]

Range
1
65534

0 ~ 65534

Default 1

Step

Enter Slave(ETR300) adress.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Master Addr


[DNP3]
>Slave Addr:
>Master Addr:
[0~65534:1]

Range
1
65534

0 ~ 65534

Default 1

Step

Enter Master station adress.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Baud Rate


[PROTF(232)]
>Baud Rate:
1200
Modem Sel:
4W
[1200 ~ 57600 bps]

Range

1200, 2400, 4800, 9600, 19200, 38400, 57600 bps

Default 1200

Step

Select Baud Rate of PORTF.


GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Modem Sel
[PROTF(232)]
>Modem Sel:
4W
>CTS Usage:
ON
[2W/4W/D1/D2/NONE]

Range

2W, 4W, D1, D2, NONE

Default 4W

Step

Select a modem for communication.


2W : 2 wire private line is used and continuously Carrier is monitored
to control a data flow by DCD(Data Carrier Detect) signal.
4W : 4 wire private line is used and RTS(Request To Send) and
CTS(Clear To Send) signal is used to control a data flow.

66

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

D1 : Dial-Up1 modem is used.


D2 : Dial-Up2 modem is used.
NONE : Not used.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ CTS Usage
[PROTF(232)]
>Modem Sel:
>CTS Usage:
[OFF/ON]

ON, OFF

Range
4W
ON

Default ON

Step

Set the use [OFF/ON] of CTS sign.


ON : Transmit the sending data after check that the CTS sign is
Assert.
OFF : Transmit the sending data regardless of CTS sign.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ DCD Usage


[PROTF(232)]
>DCD Usage:
OFF
>RTS Usage:
AUTO
[OFF/ON]

Range

ON, OFF

Default ON

Step

Set the use [OFF/ON] of DCD sign.


ON : Transmit the sending data after check that the DCD sign is
Desassert.
OFF : Transmit the sending data regardless of DCD sign.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ RTS Usage


[PROTF(232)]
>DCD Usage:
OFF
>RTS Usage:
AUTO
[OFF/ON/AUTO]

Range

OFF, ON, AUTO

Default AUTO

Step

ON : RTS sign of ETR300-R is always ON(Assert).


OFF : RTS sign of ETR300-R is always OFF(Deassert).
AUTO : When request a data transmission to modem the RTS sign
of ETR300 is ON and when finish the transmission the RTS sign of
ETR300 is OFF.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ CTS CheckOut

ENHANCED TECHNOLOGY

67

SWITCH CONTROL ETR300-S01

[PROTF(232)]
>CTS CheckOut:
2
>DCD CheckOut: 5000
[1~255:1s]

http://www.entecene.co.kr

1 ~ 255 sec

Range

Default 2

Step

1 sec

Set a waiting time that waits for a modem response on RTS signal
which informs ETR300 is ready to transfer a data. If no response
within a set time, RTU treats CTS Fail and does not transfer a data.
It is available if CTS Usage setting is ON.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ DCD CheckOut


[PROTF(232)]
>CTS CheckOut:
2
>DCD CheckOut: 5000
[10~30000:5ms]

10 ~ 30000 msec

Range

Default 5000

Step

5 msec

Set a delay time of DCD signal to check modem status before transfer
a RTS signal in 2 wire communication type. If DCD signal is ON after
set time, ETR300 does not transfer a data and treats DCD Fail.
It is available if DCD Usage setting is ON.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ RTS OffDelay


[PROTF(232)]
DCD CheckOut: 5000
>RTS OffDelay:
50
[10~500:5ms]

10 ~ 500 msec

Range

Default 50

Step

5 msec

RTS Off Delay Time is a time delay after transfer a data till RTS
signal Off. It is a time delay to prevent a last data loss during a data
transfer.
Generally, RTS Off Delay Time is set for 1 or 2 Byte.

68

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.3. Event Recorder


Locate the cursor on 3. EVENT RECORDER in GLOBAL SETTING, press [ENT] button to
move to this menu. In this menu, items related to the wave record are set.
GLOBAL SETTING / EVENT RECORDER / Wave Capture
[EVENT RECORDER]
>Wave Capture:
OFF
>Wave S/R:
64
[OFF/ON]

Range

ON, OFF

Default ON

Step

Step

Set whether to use Wave capture.

GLOBAL SETTING / EVENT RECORDER / Wave S/R


[EVENT RECORDER]
>Wave Capture:
OFF
>Wave S/R:
64
[16/32/64/128]

Range

16, 32, 64, 128 sample

Default 64 sample

If record the wave, select the wave sampling capture.


The recorded wave cycle number is 20cycle per 128 sampling and it is
changeable according to the sampling number.

GLOBAL SETTING / EVENT RECORDER / Wave Pre-Cycle


[EVENT RECORDER]
>Wave Pre-Cycle:
5
>Wave Post-Cycle: 5
[1~5:1cycel]

Range

1 ~ 5 cycle

Default 5

Step

1 cycle

Pre-cycle is to record(capture) a number of wave cycle before fault


pickup occurring.

GLOBAL SETTING / EVENT RECORDER / Wave Post-Cycle


[EVENT RECORDER]
>Wave Pre-Cycle:
5
>Wave Post-Cycle: 5
[1~5:1cycel]

Range

1 ~ 5 cycle

Default 5

Step

1 cycle

Post-cycle is to record(capture) a number of wave cycle after Trip.

GLOBAL SETTING / EVENT RECORDER / Wave Head-Cycle


[EVENT RECORDER]
>Wave Post-Cycle: 5
>Wave Head-Cycle: 5
[1~10:1cycel]

Range

1 ~ 10 cycle

Default 5

Step

1 cycle

Head-Cycle is to record(capture) a number of wave cycle before Trip.

ENHANCED TECHNOLOGY

69

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.4. Monitoring
Locate the cursor on 4. MONITORING in GLOBAL SETTING, push [ENT] button and move
to this menu.
[MONITERING]
>1.OPERATION COUNT
2.CONTACT WEAR
3.BATTERY TEST
4.PQM
5.TD MONITOR
6.V0 DETEC

6.4.1. Operation Count


Locate the cursor on 1. OPERATION COUNT in MONITORING menu, press [ENT] button
and move to this men. In this menu, set the elements related to Operation Count Monitering of
switch.
GLOBAL SETTING / MONITORING / OPERATION COUNT / Function
[OPERATION COUNT]
>Function:
ON
Limit:
10000
[OFF/ON]

Range

OFF, ON

Default ON

Step

Set whether to use Operation Caunt Monitering

GLOBAL SETTING / MONITORING / OPERATION COUNT / Limit


[OPERATION COUNT]
>Function:
OFF
>Limit:
10000
[1~20000:1]

Range

1 ~ 20000

Default 10000

Step

Ring the Alarm when Switch operation count (MAINENANCE/


COUNT/ OPERATION) reach the setting value.

GLOBAL SETTING / MONITORING / OPERATION COUNT / Count set


[TRIP COUNTER]
Limit:
10000
>Count set:
0
[0~65535:1]

Range

0 ~ 65535

Default 0

Step

Use to set the same the Operation Count with the main device.
Set value is available after Operation Counter is reset. You can reset
the counter in MAINENANCE/ DATA RESET / OPERATION
COUNT or COUNT ALL

70

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.4.2. Contact Wear


Place the curser on 3. CONTACT WEAR in MONITORING menu, press [ENT] button to move
into this menu. Switch contact wear and monitoring elements are set in this menu.
GLOBAL SETTING / MONITORING / CONTACT WEAR / Function
[CONTACT WEAR]
>Function:
OFF
Pickup(%):
20.0
[OFF/ON]

Range

OFF, ON

Default OFF

Step

Select whether to use Switch contact wear monitoring.

GLOBAL SETTING / MONITORING / CONTACT WEAR / Pickup(%)


[CONTACT WEAR]
>Function:
OFF
>Pickup(%):
20.0
[0.0~50.0:0.1%]

Range

0.0 ~ 50.0 %

Default 20.0
Set

pickup

Step
value

to

alarm when

0.1 %
switch

contact

wear

(MAINENANCE/ CONTACT WEAR) reaches set value.


GLOBAL SETTING / MONITORING / CONTACT WEAR / Rated Volt(kV)
[CONTACT WEAR]
Pickup(%):
20.0
>Rated Volt(kV): 38
[15/27/38kV]

Range

15, 27, 38

Default 27

Step

Set Rated Voltage of System.

GLOBAL SETTING / MONITORING / CONTACT WEAR / Interrupt(kA)


[CONTACT WEAR]
Rated Volt(kV): 15
>Interrupt(kA): 12.5
[5.0~50.0:0.1kA]

Range

5.0 ~ 50.0 kA

Default 12.5

Step

0.1 kA

Set the maximum rated interrupt.

GLOBAL SETTING / MONITORING / CONTACT WEAR / No. Max I


[CONTACT WEAR]
Interrupt(kA): 12.5
>No. Max I:
100
[1~999:1]

Range

1 ~ 999

Default 100

Step

Enter the capacity of rated Interrupter.

GLOBAL SETTING / MONITORING / CONTACT WEAR / A Wear Set


[CONTACT WEAR]
>A Wear Set: 100.00
>B Wear Set: 100.00
[0.00~100.00:0.01%]

Range

0.00 ~ 100.00 %

ENHANCED TECHNOLOGY

71

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Default 100.00

Step

0.01%

It is to set Switch phase A contact wear value in ETR300. Set value is


available after Contact Wear Rset. Contact wear reset refers to
MAINENANCE/ DATA RESET / CONTACT WEAR.
GLOBAL SETTING / MONITORING / CONTACT WEAR / B Wear Set
[CONTACT WEAR]
>A Wear Set: 100.00
>B Wear Set: 100.00
[0.00~100.00:0.01%]

Range

0.00 ~ 100.00 %

Default 100.00

Step

0.01%

It is to set Switch phase B contact wear value in ETR300. Set value is


available after Contact Wear Rset. Contact wear reset refers to
MAINENANCE/ DATA RESET / CONTACT WEAR.

GLOBAL SETTING / MONITORING / CONTACT WEAR / C Wear Set


[CONTACT WEAR]
>B Wear Set: 100.00
>C Wear Set: 100.00
[0.00~100.00:0.01%]

Range

0.00 ~ 100.00 %

Default 100.00

Step

0.01%

It is to set Switch phase C contact wear value in ETR300. Set value is


available after Contact Wear Rset. Contact wear reset refers to
MAINENANCE/ DATA RESET / CONTACT WEAR.

6.4.3. Battery Test


Locate the cursor on 3. BATTERY TEST in MONITORING menu, press [ENT] button and
move to this menu.
GLOBAL SETTING / MONITORING / BATTERY TEST / Period
[BATTERY TEST]
>Period:
24

Range

1 ~ 720 hour

Default 24

Step

[1~720:1hour]

Set the Battery Test Hour Period.

72

ENHANCED TECHNOLOGY

1 hour

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.4.4. PQM
Locate the cursor on 4. PQM in MONITERING menu, press [ENT] button and move to this
menu. In this menu, set the elements of PQM and has the following submenu.

[PQM]
>1.PQM FUNCTION
2.INTERRUPT
3.SAG
4.SWELL
5.HARMONICS
6.CURR UNBALANCE
7.VOLT UNBALANCE
8.UNDER VOLTAGE
9.OVER VOLTAGE
10.UNDER FREQUENCY
11.UBI/THD MIN.I

6.4.4.1. PQM Function


Locate the cursor on 1. PQM FUNCTION in PQM Menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / PQM FUNCTION / Function
[PQM FUNCTION]
>Function:
DISABLE

Range

DISABLE, ENABLE

Default DISABLE

Step

[DISABLE/ENABLE]

Select [DISABLE/ENABLE] of PQ.

6.4.4.2. Interrupt
Locate the cursor on PQM 2. INTERRUPT in the menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / INTERRUPT / Level
[INTERRUPT]
>Level:
0.10
>Time:
2.0
[0(OFF),0.10~0.49pu]

Range

0(OFF), 0.10 ~ 0.49 pu

Default 0.10

Step

0.01 pu

Set the Interrupt Detect Level of PQ.


Detect Level shall be set in multiple of rated voltage of source side
user.

ENHANCED TECHNOLOGY

73

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GLOBAL SETTING / MONITORING / PQM / INTERRUPT / Time


[INTERRUPT]
>Level:
0.10
>Time:
2.0
[0.5~10.0:0.5cycle]

Range

0.5 ~ 10.0 cycle

Default 2.0

Step

0.5 cycle

Set Interrupt Detect Time.

6.4.4.3. Sag
Locate the cursor on 3. SAG in PQM menu, press [ENT] key and move to this menu.
GLOBAL SETTING / MONITORING / PQM / SAG / Level
[SAG]
>Level:
0.80
>Time:
2.0
[0(OFF),0.50~0.99pu]

Range

0(OFF), 0.50 ~ 0.99 pu

Default 0.80

Step

0.01 pu

Set the Voltage Sag Detect Level of PQ.


Detect Level shall be set in multiple of rated voltage of source side
user.

GLOBAL SETTING / MONITORING / PQM / SAG / Time


[SAG]
>Level:
0.80
>Time:
2.0
[0.5~10.0:0.5cycle]

Range

0.5 ~ 10.0 cycle

Default 2.0

Step

0.5 cycle

Set Voltage Sag Detect Time.

6.4.4.4. Swell
Locate the cursor on 4. SWELL in PQM menu, press [ENT] button and move to this menu.
GLOBAL SETTING / MONITORING / PQM / SWELL / Level
[SWELL]
>Level:
1.20
>Time:
2.0
[0(OFF),1.01~1.50pu]

Range

0(OFF), 1.01 ~ 1.50 pu

Default 1.20

Step

0.01 pu

Set the Voltage Swell Detect Level of PQ.


Detect Level shall be set in multiple of rated voltage of source side
user..

GLOBAL SETTING / MONITORING / PQM / SWELL / Time


[SWELL]
>Level:
1.20
>Time:
2.0
[0.5~10.0:0.5cycle]

74

Range

0.5 ~ 10.0 cycle

Default 2.0

Step

ENHANCED TECHNOLOGY

0.5 cycle

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Set Voltage Swell Detect Time.

6.4.4.5. Harmonics
Locate the cursor on 5. HARMONICS in PQM menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / HARMONICS / VTHD Pickup
[HARMONICS]
>VTHD Pickup:
OFF
>VTHD Delay:
1.0
[OFF,0.5~100.0:0.01]

Range

0(OFF), 0.5 ~ 100.0 %

Default OFF

Step

0.1%

Set a detect level of voltage harmonic distortion.

GLOBAL SETTING / MONITORING / PQM / HARMONICS / VTHD Delay


[HARMONICS]
>VTHD Pickup:
OFF
>VTHD Delay:
1.0
[0.2~60.0:0.1s]

Range

0.2 ~ 60.0 sec

Default 1.0

Step

0.1 sec

Set a detect time to detect voltage harmonic distortion.

GLOBAL SETTING / MONITORING / PQM / HARMONICS / ITHD Pickup


[HARMONICS]
>ITHD Pickup:
OFF
>ITHD Delay:
1.0
[OFF,0.5~100.0:0.01]

Range

0(OFF), 0.5 ~ 100.0 %

Default OFF

Step

0.1%

Set a detect level of current harmonic distortion.

GLOBAL SETTING / MONITORING / PQM / HARMONICS / ITHD Delay


[HARMONICS]
>ITHD Pickup:
OFF
>ITHD Delay:
1.0
[0.2~60.0:0.1s]

Range

0.2 ~ 60.0 sec

Default 1.0

Step

0.1 sec

Set a detect time to detect current harmonic distortion.

6.4.4.6. Current Unbalance


Locate the cursor on 6. CURR UNBALANCE in PQM menu, press [ENT] button and move to
this menu.
GLOBAL SETTING / MONITORING / PQM / CURR UNBALANCE / Level
[CURR UNBALANCE]
>Level:
30
>Time:
1.0
[0(OFF),1~100:1%]

Range

0(OFF), 1 ~ 100 %

Default 30

Step

ENHANCED TECHNOLOGY

1%

75

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Set a detect level of Current Unbalance for Power Quality.


GLOBAL SETTING / MONITORING / PQM / CURR UNBALANCE / Time
[CURR UNBALANCE]
>Level:
30
>Time:
1.0
[0.1~60.0:0.1s]

Range

0.1 ~ 60.0 sec

Default 1.0

Step

0.1 sec

Set a detect time of current unbalance.

6.4.4.7. Voltage Unbalance


Locate the cursor on 7. VOLT UNBALANCE in PQM menu, press [ENT] button and move to
this menu.
GLOBAL SETTING / MONITORING / PQM / VOLT UNBALANCE / Level
[VOLT UNBALANCE]
>Level:
30
>Time:
1.0
[0(OFF),1~100:1%]

Range

0(OFF), 1 ~ 100 %

Default 30

Step

1%

Set Voltage Unbalance Detect Level of PQ.

GLOBAL SETTING / MONITORING / PQM / VOLT UNBALANCE / Time


[VOLT UNBALANCE]
>Level:
30
>Time:
1.0
[0.1~60.0:0.1s]

Range

0.1 ~ 60.0 sec

Default 1.0

Step

0.1 sec

Set Voltage Unbalance Detect Time.

6.4.4.8. Under Voltage


Place the curser on 8. UNDER VOLTAGE in PQM menu, press [ENT] button to move into this
menu.
GLOBAL SETTING / MONITORING / PQM / UNDER VOLTAGE / Level
[UNDER VOLTAGE]
>Level:
0.80
>Time:
60.0
[0(OFF),0.30~0.95pu]

Range

0(OFF), 0.30 ~ 0.95 pu

Default 0.80

Step

0.01 pu

Set Under Voltage Detect Level of PQ.


Detect Level shall be set in multiple of rated voltage of source side
user..

GLOBAL SETTING / MONITORING / PQM / UNDER VOLTAGE / Time


[UNDER VOLTAGE]
>Level:
0.80
>Time:
60.0
[0.0~180.0:0.1s]

76

Range

0.0 ~ 180.0 sec

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Default 60.0

Step

0.1 sec

Set Under Voltage Detect Time.

6.4.4.9. Over Voltage


Locate the cursor on 9. OVER VOLTAGE in PQM menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / OVER VOLTAGE / Level
[OVER VOLTAGE]
>Level:
1.20
>Time:
60.0
[0(OFF),1.05~1.50pu]

Range

0(OFF), 1.05 ~ 1.50 pu

Default 1.20

Step

0.01 pu

Set Over Voltage Detect Level of PQ.


Detect Level shall be set in multiple of rated voltage of source side
user.

GLOBAL SETTING / MONITORING / PQM / OVER VOLTAGE / Time


[OVER VOLTAGE]
>Level:
1.20
>Time:
60.0
[0.0~180.0:0.1s]

Range

0.0 ~ 180.0 sec

Default 60.0

Step

0.1 sec

Set Over Voltage Detect Time.

6.4.4.10. Under Frequency


Locate the cursor on 10. UNDER FREQUENCY in PQM menu, press [ENT] button and move
to this menu.
GLOBAL SETTING / MONITORING / PQM / UNDER FREQUENCY / Level
[UNDER FREQUENCY]
>Level:
59.50
>Time:
0.10
0(OFF),46.00~59.98Hz

Range

0(OFF), 46.00 ~ 59.98 Hz

Default 59.50

Step

0.01 Hz

Set Under Frequency Detect Level of PQ..

GLOBAL SETTING / MONITORING / PQM / UNDER FREQUENCY / Time


[UNDER FREQUENCY]
>Level:
59.50
>Time:
0.10
[0.03~10.00:0.01s]

Range

0.03 ~ 10.00 sec

Default 0.10

Step

0.01 sec

Set Under Frequency Detect Time.

ENHANCED TECHNOLOGY

77

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.4.4.11. Current Unbalance/THD Detect Limit


Locate the cursor on 11. UBI/THD MIN. in PQM menu, select [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / UBI/THD MIN. / Min. I
[UBI/THD MIN.I]
>Min. I:
60

Range

0 ~ 630 A

Default 60

Step

1A

[0~630:1A]

Set in minimum current to detect the Current Unbalance and THD.

6.4.5. TD MONITOR
Locate the cursor on 5. TD Monitor in MONITERING menu, press [ENT] button and move to
this menu.
. In this menu, set operation elements of transducer which can be used for the moditoring of DC
analog input.

It has 5 channels of transducer, each transducer has 2 pickup setting values to detects the
signal size of input, monitoring in 2 levels the input sinal which is over than pickup setting
value and give the alarm.

The no. 1 and 2 transducer can detect the battery and charger status by receiving the battery
voltage and charge section voltage in input signal and sending to the controller.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1 Rate


[TD MONITOR]
>TD1 Rate:
>TD1 Ratio:
[20/200]

Range
20
1

20, 200

Default 20

Step

Enter TD1 monitoring rate.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1 Ratio


[TD MONITOR]
>TD1 Rate:
>TD1 Ratio:
[1~3000:1]

Range
20
1

1 ~ 3000

Default 1

Step

Enter TD1 ratio.

78

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GLOBAL SETTING / MONITORING / TD MONITOR / TD1 Offset


[TD MONITOR]
>TD1 Ratio:
1
>TD1 Offset:
+0
[-10000 ~ +10000:1]

Range

-10000 ~ +10000

Default 0

Step

Enter TD1 off set.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-1 Type


[TD MONITOR]
>TD1-1 Type:
UNDER
>TD1-1 PU:
OFF
[UNDER/OVER]

Range

UNDER, OVER

Default UNDER

Step

Set the 1st monitoring type of TD1.


UNDER is set to give the alarm when input value is reduced under
pickup setting value, OVER is to give the alarm when input value is
increased over pickup setting value.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-1 PU(V)


[TD MONITOR]
>TD1-1 PU(V):
OFF
>TD1-1 Delay:
2.00
[OFF,1.0~35.0:0.1V]

Range

0(OFF), 1.0 ~ 35.0 V

Default OFF

Step

0.1V

Set the 1st Pickup value of TD1.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-1 Delay


[TD MONITOR]
>TD1-1 PU(V):
OFF
>TD1-1 Delay:
2.00
[0.01~600.00:0.01s]

Range

0.01 ~ 600.00 sec

Default 2.00

Step

0.01 sec

Set the 1st Delay time of TD1.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-2 Type


[TD MONITOR]
>TD1-2 Type:
UNDER
>TD1-2 PU(V):
OFF
[UNDER/OVER]

Range

UNDER, OVER

Default UNDER

Step

Set the 2nd monitoring type of TD1

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-2 PU


Range

0(OFF), 1.0 ~ 35.0 V

Default OFF

Step

ENHANCED TECHNOLOGY

0.1V

79

SWITCH CONTROL ETR300-S01

[TD MONITOR]
>TD1-2 PU(V):
OFF
>TD1-2 Delay:
2.00
[OFF,1.0~35.0:0.1V]

http://www.entecene.co.kr

Set the 2nd Pickup value of TD1.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-2 Delay


[TD MONITOR]
>TD1-2 PU:
OFF
>TD1-2 Delay:
2.00
[0.01~600.00:0.01s]

Range

0.01 ~ 600.00 sec

Default 2.00

Step

0.01 sec

Set the 2nd Delay time of TD1.

. NOTE : TD2 ~ TD5 have the same setting items with TD1.

6.4.6. V0 Detect
Locate the cursor on 6. V0 DETECT in MONITERING menu, press [ENT] button and move to
this menu. In this menu, set the Zero Voltage detection.
GLOBAL SETTING / MONITORING / PQM / V0 DETECT / Detect Level
[V0 DETECT]
>Detect Level:
OFF
>Detect Time:
1.0
[0(OFF),0.05~1.20pu]

Range

0(OFF), 0.05 ~ 1.20 pu

Default OFF

Step

0.01 pu

Set V0 Detect Level.

GLOBAL SETTING / MONITORING / V0 DETECT / Detect Time


[V0 DETECT]
>Detect Level:
OFF
>Detect Time:
1.0
[0.1~6000.0:0.1s]

Range

0.1 ~ 6000.0 sec

Default 1.0

Step

Set V0 Detect Time.

80

ENHANCED TECHNOLOGY

0.1 sec

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.5. PLC
Locate the cursor on 5. PLC in GLOBAL SETTING menu, press[ENT] button and move to this
menu.
[PLC]
>1.COMMON
2.DI/DO

6.5.1. COMMON
Locate the cursor on 1. COMMON in PLC menu, press [ENT] button amd move to this menu.
[OMMON]
>1.LOGIC TIMER
2.PULSE TIMER
3.PULSE COUNTER

6.5.1.1. Logic Timer


Locate the cursor on 1. LOGIC TIMER in COMMON menu, press [ENT] button amd move to
this menu.

There are 16 logictimer inside the PLC.

When occurs input A in logictimer, output B becomes 1 after time X and when input A
disappears output B becomes 0 after time Y. Refer to Ficture 5-1. Logic Timer symbol.

X is Pick up time and Y is Dropout time.

In PLC, enter A in user logic TMI.

In PLC, B is output in TMO.

TM
X
Y
0s/0s

Ficture 6-1. Logic Timer Symbol

ENHANCED TECHNOLOGY

81

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GLOBAL SETTING / PLC / COMMON / LOGIC TIMER / TM1-PU


[LOGIC TIMER]
>TM1-PU:
0.01
TM1-DO:
0.01
[0.01~600.00:0.01s]

0.01 ~ 600.00 sec

Range

Default 0.01

Step

0.01 sec

Set Pickup Time of logic timer 1.

GLOBAL SETTING / PLC / COMMON / LOGIC TIMER / TM1-DO


[LOGIC TIMER]
>TM1-PU:
0.01
>TM1-DO:
0.01
[0.01~600.00:0.01s]

0.01 ~ 600.00 sec

Range

Default 0.01

Step

0.01 sec

Set Dropout Time of logic timer 1.

. NOTE : The setting of TM2 ~ TM16 are same with TM1.

6.5.1.2. Pulse Timer


Locate the cursor on 2. PULSE TIMER in COMMON menu, press [ENT] button and move to
this menu.

There are 16 pulse timer inside the PLC

When input A becomes 1 in pulse timer, output B becomes 1 and it output during Y time.
Refer to Figure 5-2. Pulse Timer symbol.

In PLC, enter A in user logic PTMI.

In PLC, B is output in PTMO.

PTM
A

Y
0s
Ficture 6-2. Pulse Timer Symbol

GLOBAL SETTING / PLC / COMMON / PULSE TIMER / PTM1


[PULSE TIMER]
>PTM1 :
0.01
PTM2 :
0.01
[0.01~600.00:0.01s]

Range

0.01 ~ 600.00 sec

Default 0.01

Step

Set output time of Pulse Timer 1.

. NOTE : Setting of TM2 ~ PTM16 is same with PTM1.

82

ENHANCED TECHNOLOGY

0.01 sec

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.5.1.3.Pulse Counter
Locate the cursor on 3. PULSE COUNTER in COMMON menu, press [ENT] button and move
to this menu.

There are 16 Pulse Counter in PLC.

When input B is 0 and input A becomes 1 it increases once and output C becomes 1 when it is
over setting number X. When input B becomes 1 output C becomes 0 and the increased count
becomes 0. Refer to Figure 5-3. Pulse Counter symbol

In PLC, enter A in user logic PCI.

In PLC, enter B in user logic PCR.

In PLC, C is output in PCO.

PC
X
Q
R

A
B

0
Ficture 6-3. Pulse Counter Symbol
GLOBAL SETTING / PLC / COMMON / PULSE COUNTER / PC1
[PULSE TIMER]
>PC1 :
1000
PC2 :
1000
[1~60000:1]

Range

1 ~ 60000

Default 1000

Step

Set the utput value(X) of Pulse Counter(PC1).

. NOTE : The setting item of PC2 ~ PC16 is same with PC1.

ENHANCED TECHNOLOGY

83

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.5.2. DI/DO
Locate the cursor on 2. DI/DO in PLC menu, press [ENT] button and move to this menu.

[DI/DO]
>1.INPUT DEBOUNCE
2.OUTPUT PULSE TIME

6.5.2.1. Input Debounce Timer


Locate the cursor on 1. INPUT DEBOUNCE in DI/DO menu, press [ENT] button and move to
this menu.

Input Debounce Timer is provided individually in Control Input.

Input Debounce Timer st the time to eliminate the Chattering of INPUT signal.

When input A becomes 1 in Input Debounce Timer output B becomes 1 after X time and
when input A disappears output B becomes 0 after X time. Refer to Figure 5-4. Input
Debounce Timer symbol.

In PLC, A is IN01~IN of Control Input and B is output in IN.

IN
X

0s
Ficture 6-4. Input Debounce Timer Symbol
GLOBAL SETTING / PLC / DI/DO / INPUT DEBOUNCE / IN101
[INPUT DEBOUNCE]
>IN101 :
0.020
IN102 :
0.020
0.005~10.000:0.001s

Range

0.005 ~ 10.000 sec

Default 0.020

Step

0.001 sec

Set Input Debounce time of IN101.

. NOTE : Setting items of IN102 ~ IN108 and IN201 ~ IN208 are same with IN101.

84

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.5.2.2. Output Pulse Timer


Locate the cursor on 2. OUTPUT PULSE TIME in DI/DO menu, press [ENT] button and move
to this menu.

Output Pulse Timer is provided individually in Control Output.

When input B is 0 in Output Pulse Timer, output C becomes 1 according to the input A. When
input A becomes 1output C becomes 1 during Y time. But if set the Y time in 0, they react at
the same time according to input A. When A is 1 C becomes 1 and when A is 0 C becomes 0, it
is Buffer. Refer toFigure 5-5. Output Pulse Timer symbol .

In PLC, enter A in user logic OUT.

In PLC, enter B in user logic BKOUT.

In PLC, C is output in OUT and this output runs RELAY.

OUT
A
B

R
0s

Ficture 6-5. Output Pulse Timer Symbol


GLOBAL SETTING / PLC / DI/DO / OUTPUT PULSE TIME / OUT101
[OUTPUT PULSE TIME]
>OUT101 :
0.01
OUT102 :
0.01
0(BUFF),0.01~100.00s

Range

0(BUFF), 0.01 ~ 100.00 sec

Default 0.01

Step

0.01 sec

Set Output Pulse Time of OUT101.

. NOTE : The setting item of OUT102 ~ OUT 108 and OUT201 ~ OUT208 are same with OUT101.

ENHANCED TECHNOLOGY

85

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.6. Other setting items


Locate the cursor on 7. OTHERS in GLOBAL SETTING menu, press [ENT] button and move
to this menu.
[OTHERS]
>1.F.I TEST
2.FACTORY DEBUG

6.6.1. F.I TEST


ETR 300 has F.I Test in LCD menu to test the fault detect element and normal operation of fault
count. F.I Test function are same as the following.

(1) Basic Operation of F.I Test

Select which phase among A,B,C,N will be produced F.I (plural selection is possible)

After starting FI Test, produces F.I regardless of Pickup Current of Group Setting Menu.

For F.I Test, Sequence is set in the range of 1~3.

F.I Test is Disable when all A,B,C,N phase are OFF or Sequence is 0.

Produce 1000A Fault current for 10 cycle as the setting number. Eacg Sequence interval is 2
second.

After 2 seconds of FI test, temporary fault is generated.

When do the FI test, fault indication lamp of the front panel is lighted and send related
information to the main device without saving as internal event or increasing fault count.

Fault Current Transmission send the faul current to Event according to Fault I Report setting.
At this time, phase that has not done the FI test indicates present load current value.

After the test, fault indication (front panel lamo and BI point) is maintained until FI Reset.

When do the FI test in the status that fault indication is remained, cancel the prior fault
indication and shows FI information

(2) FI Setting Value Storage


Selected phase for F.I Test Target and Setting Value for F.I Test Sequence are saved at the started
time of F.I Test.

(3) Setting Basic Value


F.I Test initial value is sames as the following.

86

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

Targer : A,B,C,N all ON

Sequence : 3

http://www.entecene.co.kr

(4) End of F.I Test


When F.I test starts, consider as F.I test mode the simulated fault current (1000A) permission,
F.I logic performance as much as the sequence setting and LED lighting after F.I set. End the test
mode after finishing these process.
FI Test Start
1000A
(10cycle)

Case: Sequence
Setting 1

2sec

Temporary
Fault Detect
Fault Detected

FI Test Start
1000A
(10cycle)

1000A
(10cycle)

Case: Sequence
Setting 2
2sec
Fault Detect

2sec
Fault Detect

Temporary
Fault Detected

FI Test Start
1000A
(10cycle)

1000A
(10cycle)

1000A
(10cycle)

Case: Sequence
Setting 3
2sec
Fault Detect

2sec

Fault Detect

2sec

Temporary
Fault Detect Fault Detected

Ficture 6-6. F.I Test according to Sequence Setting


Locate the cursor on 1. F.I TEST in OTHERS menu, press [ENT] button and move to this menu.
In this menu, set the FI occur phase for the F.I mock test,and Sequence number.
[F.I TEST]
>1.F.I TEST TARGET
2.F.I TEST SEQ.
3.F.I TEST START

ENHANCED TECHNOLOGY

87

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

6.6.1.1. F.I TEST TARGET


Locate the cursor on 1. F.I TEST TARGET in F.I TEST menu, press [ENT] button and move to
this menu. In this menu, set the target phasefor the occurance of F.I.
GLOBAL SETTING / OTHERS / F.I TEST / F.I TEST TARGET / IA TEST
[F.I TEST TARGET]
>IA TEST:
ON
>IB TEST:
ON
[OFF/ON]

Range

OFF, ON

Default ON

Step

When select ON, F.I occurs in A phase.

. NOTE : Setting of IB TEST, IC TEST and IN TEST ar same with IA TEST.

6.6.1.2.F.I TEST SEQUENCE


Locate the cursor on 2. F.I TEST SEQ. in F.I TEST menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / OTHERS / F.I TEST / F.I TEST SEQUENCE / SEQ. COUNT
[F.I TEST SEQUENCE]
>SEQ. COUNT:
3
>
[DISABLE,1~3:1]

Range

DISABLE, 1 ~ 3

Default 3

Step

Set F.I Sequence.

6.6.1.3.F.I TEST START


Locate the cursor on 3. F.I TEST START in F.I TEST menu, press [ENT] button and move to
this menu.
GLOBAL SETTING / OTHERS / F.I TEST / F.I TEST SEQUENCE / F.I TEST START
Press [ENT] button if wants to Start the F.I test.
*F.I TEST START*
PRESS <ENT> TO START

6.6.2. Factory Debug


This menu is for Manufacturers maintenance purpose.

88

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

7. Group Setting
Locate the cursor on 2.GROUP SETTING in main menu, press [ENT] button and move to this
menu. In this menu, set line operating items.

[GROUP SETTING]
>1.PRIMARY
2.ALTERNATE

Ficture 7-1. PRIMARY and ALTERNATE group


GROUP SETTING menu is divided in PRIMARY group and ALTERNATE group for the
convenience of user and it is applied according to the ON/OFF of ALTERNATE SETTINGS
Lamp. When ALTERNATE SETTINGS Lamp is OFF, PRIMARY group setting is applied
and when ALTERNATE SETTINGS Lamp is ON, ALTERNATE group setting is applied.
The submenu of PRIMARY group and ALTERNATE group are same, as the following.

[PRIMARY SETTING]
>1.PICKUP CURRENT
2.COLD LOAD PICKUP
3.DIRECTION
4.F.I SETTING TIME
5.F.I RESET
6.SECTION
7.PHASE DIFF
8.ON/OFF LEVEL
9.OVER CURRNET
*.SAVE SETTING

NOTE : Changed setting value are available only when they are saved.
Setting value can be saved by Setting value save massage indicated when depart to *.
Setting Save menu or topmenu.

ENHANCED TECHNOLOGY

89

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

7.1. Fault pickup element


When occurs a fault in line, ETR300 detects and indicates the fault of each phase (A, B, C, N,
SEF). The fault type are permanent and temporary.

(1) Permanent FI Detect


It is used for the permanent FI detection of distribution line and it operates according to following
condition.

Voltage

Pickup Level
Current

Temporary
FI SETTING TIME

Permanent
FI SETTING TIME
CLEAR
Temporary FI

Permanent FI
FI SET

AUTO
RESET

Permanent Fault

Ficture 7-2. Permanent FI Detection(1)


Occurrence Condition
FI information is set when becomes dead line status after fault current over the minim. pickup
current flowed in Hot line status, and set the fault type in FI if dead line status is maintained
during setting time (permanent FI Set Time, 1sec~180sec possible to change, Default: 20 second).
But, when returns to Hot line status by reclosing before the permanent FI Set Time, FI Set Time is
initialized and returned to the first permanent FI occurrence condition.
Cancel Condition
If normal current is detected in hot line status after the permanent FI, permanent FI is cancelled

90

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

automatically at the time that passed the permanent FI Set Time. Before the automatic FI cancel, it
can be cancelled by Fault Indicator Reset button or remote FI reset control. But, Reset order is not
working before the end of fault judgement after fault detection.
A,N

A,N

B,N

B,N

Pickup Level
Normal Current

Permanent Fault
Detect Time
0.6s

2s

FI(A, N)
Fault Current(A,B,C,N,SEF)

15s

FI(B)

Fault Permanent

Ficture 7-3. Permanent Fault Detection PickupOperation(2)

Fault is experienced in normal stats and FI is occurred in no voltage status ( time :


additional occurrence phase update

Fault Current Size is maximum RMS from the fault detection to no voltage and Event time is
no-voltage detect time.
Fault Current Event is occurred at the first fault(When Fault 'I' Report Evnet setting is

1Shot)

Additional FI is not set when fault has been detected in the same phaset during Sequence
operation(t). When detects fault of other phase during Sequence, FI is set. ()

After finishing Sequence (Permanent Fault Judge time), Permanent Fault Set is sent to main
device()

Permanent FI set and FI set is cancelled after FI Reset order or Temporary FI judge
time after normal line reset.

ENHANCED TECHNOLOGY

91

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

(2) Temporary FI Detection


It is used for Temporary fault monitoring of distribution line and operates based on the following
condition.

Voltage

Pickup Level
Current

Temporary
FI SETTING TIME

Permanant
FI SETTING TIME
CLEAR
Temporary FI
FI SET
Permanant FI

Temporary Fault

Ficture 7-4. Temporary Fault Detect Operation(1)


Set Condition
Temporary Fault set FI information when becomes dead line status after flowed fault current over
minimum pickup current. Temporary FI is set when pass the setting time (Temporary FI Set Time,
1sec~180sec possible to change, Default:2sec) after reset to nomal current from hot line status by
reclosing in source side.
Cancel Condition
FI and Fault Type(Temporary) are cleared only in FI Reset case. If FI is set again before the reset
status, delete prior FI and indicates the latest FI. Handle the existing FI Clear time at first than
new FI Set time

92

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

A,N

Temporary Fault
Detect Time

B,N

Pickup Level
Normal Current

0.6s

Fault Temporary

2s

FI(B)
FI(A, N)
Fault Current(A,B,C,N,SEF)
Ficture 7-5. Temporary Fault Detect Operation( (2)

Fault is experienced in normal stats and FI is occurred in no voltage status ( time :


additional occurrence phase update

Fault Current Size is maximum RMS from the fault detection to no voltage and Event time is
no-voltage detect time.
Fault Current Event is occurred at the first fault(When Fault 'I' Report Evnet setting is

1Shot)

Additional FI is not set when fault has detected in the same phase during Sequence operation.
When detects fault of other phase during Sequence, FI is set()

After normal line reset, send :Temporary Fault Set information to main device when pass
Temporary FI judge time) ()

When order FI Reset", Temporary FI Set and FISet information is cancelled.

Fault Detect element setting items are same as following.

7.1.1. Pickup Current Setting


Move to GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT menu to set
Pickup Current.

GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT / Phase


[PICKUP CURRENT]
>Phase:
400
Ground:
70
[OFF,50~630:5A]

Range

0(OFF), 50 ~ 630A

Default 400

Step

ENHANCED TECHNOLOGY

5A

93

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Set Pickup Current of phase.


GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT / Ground
[PICKUP CURRENT]
>Phase:
400
>Ground:
70
[OFF,25~315:5A]

Range

0(OFF), 25 ~ 315A

Default 70

Step

5A

Set Pickup Current of ground.

GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT / SEF


[PICKUP CURRENT]
>Ground:
70
>SEF:
0.2
[OFF,0.1~10.0:0.1A]

Range

0(OFF), 0.1 ~ 10.0A

Default 0.2

Step

0.1A

Set Pickup Current of SEF.

7.1.2. F.I Detect Time Setting


Move to GROUP SETTING / PRIMARY or ALTERNATE / F.I SETTING TIME menu to set
F.I Detect Time Setting.
GROUP SETTING / PRIMARY or ALTERNATE / F.I SETTING TIME / Permanent
[F.I SETTING TIME]
>Permanent :
20
>Temporary :
2
[1~180:1s]

Range

1 ~ 180sec

Default 20

Step

1sec

It is Delay time for Permanent Fault Detection.

GROUP SETTING / PRIMARY or ALTERNATE / F.I SETTING TIME / Temporary


[F.I SETTING TIME]
>Permanent :
20
>Temporary :
2
[1~180:1s]

Range

1 ~ 180sec

Default 20

Step

1sec

It is Delay time for Temporary Fault Detection.

94

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

7.2. Inrush Current Restraint Function


ETR300 has restraint function to prevent the malfunction by inrush current, occurred by switch
closing by reclosing and local and remote after fault occurance. Inrush current restraint function
can be corrected in phase, ground and SEF.
Inrush current restraint function is applied when both Source side and Load side becomes hot
status from dead status or when close the switch. When transient current is over CLPU Pickup
level as Inrush current 1, fault pickup element operates normally instead of inrush current restraint
function. If it is under CLPU Pickup level as Inrushc current 2, restraint during RMT time and
operates the normal fault pickup element. But, if it is under Pickup current as Inrush current 3,
inrush current restraint function is cancelled after Reset time.

Current
Outage time

Restore Minimum Time

Inrush current 1
Trip

CLPU
Pickup Level

Inrush current 2
Trip

Overcurrent
Pickup Level

Inrush current 3
Time

Ficture 7-6. Cold Load Pickup Characteristic

ENHANCED TECHNOLOGY

95

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Move to GROUP SETTING / PRIMARY or ALTERNATE / Cold Load Pickup menu to set
Inrush Current Restraint Function.
GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / PHA(xCT)
[ COLD LOAD PICKUP ]
>PHA(xMTC):
4
>GND(xMTC):
4
[1~20: 1xMTC]

Range

1 ~ 20 xMTC

Default 4

Step

1 xMTC

It is Phase Inrush Current Retraint multiple, this setting point is


multiple of Pickup Current(Phase)

GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / GND(xCT)


[ COLD LOAD PICKUP ]
>PHA(xMTC):
4
>GND(xMTC):
4
[1~20: 1xMTC]

Range

1 ~ 20 xMTC

Default 4

Step

1 xMTC

It is Ground Inrush Current Retraint multiple, this setting point is


multiple of Pickup Current(Ground)

GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / SEF(xCT)


[ COLD LOAD PICKUP ]
>GND(xMTC):
4
>SEF(xMTC):
4
[1~20: 1xMTC]

Range

1 ~ 20 xMTC

Default 4

Step

1 xMTC

It is SEF Inrush Current Retraint multiple, this setting point is multiple


of Pickup Current(SEF)

GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / RMT Time-PHA


[ COLD LOAD PICKUP ]
>RMT Time-PHA:
0.2
>RMT Time-GND:
0.2
[0.0~180.0:0.1s]

Range

0.0 ~ 180.0 sec

Default 0.2

Step

0.1 sec

Set Reset time of Pickup Current (Phase).


When passes the setting time the inrush current restraint algorithm is
cancelled and operates normal phase fault pickup element, when
source side and load side becomes hot status from dead status or after
switch closing. (Pickup level resets tofault pickup current in Cold load
pickup level.)

. NOTE : The setting item of RMT Time-GND and RMT Time-SEF are same with RMT TimePHA setting.

96

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

ENHANCED TECHNOLOGY

97

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

7.3. Directional Detection Function


When detect fault, ETR300 distinguish fault current direction and indicates the fault direction in
fault events. Directional Detection setting is composed of Phase, Ground, and SEF elements.

7.3.1. Phase Directional Detection


The direction distinction of phase fault current use normal voltage (V1) and normal current(I1) of
symmetry, and operation are as following.

Distinguish in Forward if I1 pahse about V1 is within 90 according M.T.A basis and if not
in Reverse.

When fault is occurred in Voltage Metering nearby V1 value can be lost. In this case, use the
saved V1 and performs the directional detection

To operates in direction, V1 detected in fault status shall be bigger than min. polarizing
voltage. If V1 is smaller than this setting value does not detect direction, even the fault current
is over the minimum pickup current

Polarizing Referance
Voltage:

V1

ro
Ze
rq
To
ue
L in
e

Typical Fault Angle


M.T.A= 60 Lag
I1
in e
eL
u
rq
To
m
u
xi m
Ma

D
OR
RW
FO

E
RS
VE
RE

Ficture 7-7. Phase directional detection element characteristic

98

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Move to GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE menu to


set Phase Directional Detection Element.
GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / Function
[PHASE]
>Function:
DISABLE
>M.T.A:
60
[DISABLE/ENABLE]

Range

DISABLE, ENABLE

Default DISABLE

Step

Set [DISABLE/ENABLE] of Directional Detection, when occurs


phase fault.

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / M.T.A


[PHASE]
>M.T.A:
>M.P.V:
[0~345:1deg]

Range
60
30

0 ~ 345

Default 60

Step

15

Set Maximum Torque Angle of normal current (I1) about normal


voltage (V1), when occurs phase fault.

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / M.P.V


[PHASE]
M.T.A:
>M.P.V:
[NONE,10~80:1%]

Range
300
30

0(NONE), 10~80 %

Default 30

Step

1%

Set Minimum Polarizing Voltage about normal voltage(V1) to


distinguish the direction.
If is under normal voltage(V1), it does not distinguish the direction.

ENHANCED TECHNOLOGY

99

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

7.3.2. Ground and SEF Directional Detection


Directional Detection of Ground and SEF fault current use Zero Seq. Voltage(V0) and Zero Seq.
Current(I0).
Polarizing Referance
Voltage:

-V0

r
Ze

Typical Fault Angle


M.T.A= 45 Lag
In

Li

r
To

ne

o
Li

To
r

qu

qu
M

ax

im

um

ne

R
FO
R
O
W
D

R
ER
EV
SE

V0

Ficture 7-8. Ground and SEF Directional Detection element characteristic

IF phase angle of I0 about V0 is within 90 based on Max. Torque Angle is Forword, if not
is Reverse.

To operates in direction, V0 detected in fault status shall be biggenr than min. polarizing
voltage. If V0 is smaller than each element setting does not detect direction, even fault current
and SEF are over min. pickup current setting value.

Move to GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / GROUND menu


to set Groud Directional Detection Element.
GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / Function
[PHASE]
>Function:
DISABLE
>M.T.A:
60
[DISABLE/ENABLE]

Range

DISABLE, ENABLE

Default DISABLE

Step

Set [DISABLE/ENABLE] of directional detection, when occurs a


ground fault.

100

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / GROUND / M.T.A


[GROUND]
>M.T.A:
>M.P.V:
[0~345:15deg]

Range
60
30

0 ~ 345

Default 60

Step

15

Set Maximum Torque Angle of zero current (I0) about zero


voltage(V0).

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / GROUND / M.P.V


[GROUND]
M.T.A:
>M.P.V:
[NONE,10~80:1%]

Range
60
30

0(NONE), 10 ~ 80%

Default 30

Step

1%

Set Minimum Polarizing Voltage about zero voltage (V0) to


distinguish the direction.
If is zero voltage (V0), it does not distinguish the direction.

. NOTE : Move to GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / SEF


to set SEF Directional Detection element, and the SEF directional setting items are
same with phase direction setting item.

ENHANCED TECHNOLOGY

101

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

7.4. SECTION
Locate the cursor on 6. SECTION in PRIMARY or ALTERNATE menu, push [ENT] button
and move to this menu. Submenu is same as following.

[SECTION]
1.FUNCTION
2.TIME
3.OPERATION COUNT

7.4.1. SECTION FUNCTION


Locate the cursor on 1. FUNCTION in SECTION menu, push [ENT] button and move to this
menu. Submenu is same as following. In this menu, set the use of Section Function and Section
Type.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Function


[SECTION FUNCTION]
>Function: DISABLE
>Auto Close:DISABLE
[DISABLE/ENABLE]

Range

DISABLE, ENABLE

Default DISABLE

Step

Set [DISABLE/ENABLE] of Section Function.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Auto Close


[SECTION FUNCTION]
>Function:
DISABLE
>Auto Close: DISABLE
[DISABLE/ENABLE]

Range

DISABLE, ENABLE

Default DISABLE

Step

DISABLE : Auto opening is possible but auto closing is restraint.


ENABLE : Auto closing is possible by section reclosing function.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Section Type


[SECTION FUNCTION]
>Section Type:
V-T
>Close Dir:
ALWAYS
[V-T/O-T]

Range

V-T, O-T

Default V-T

Step

V-T : Operates in V-T mode(Section).


O-T : Operates in O-T mode(Tie).

102

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Close Direction


[SECTION FUNCTION]
>Section Type:
V-T
>Close Dir:
ALWAYS
[ALWAYS/SOURCE/LOAD]

Range

ALWAYS, SOURCE, LOAD

Default ALWAYS

Step

Set the voltage side applided in section function closing. Switch


operates by judging the voltage of selected side.
ALWAYS : Close by judging source side or load side voltage.
SOURCE : Close by judging source side voltage.
LOAD : Close by judging load side voltage.

7.4.2. SECTION TIME


Locate the cursor on 2. TIME in SECTION menu, select [ENT] button and move to this menu.
In this menu, set time elements related to section function.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Open Delay
[SECTION TIME]
>Open Delay:
3.0
>Close Wait:
17
[0.1~25.5:0.1s]

Range

0.1 ~ 25.5 sec

Default 3.0

Step

0.1 sec

Set Open Delay time. It is delay time to order an opening, when


detects fault in V-T mode and became no-voltage.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Close Wait


[SECTION TIME]
>Open Delay:
3.0
>Close Wait:
17
[1~255:1s]

Range

1 ~ 255 sec

Default 17

Step

1 sec

Set Close Wait Time.


After opening by section on V-T mode, if it does not became hot
during Closing wait time Lockout.
But, it is only available when Autp Close setting is ENABLE status. In
other words, if Auto Close Setting is DISABLE status, it Lockout at
the sime time of opening by section function.

ENHANCED TECHNOLOGY

103

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Close Delay


[SECTION TIME]
>Close Delay:
>Lockout:
[1~255:1s]

1 ~ 255 sec

Range
2
1

Default 2

Step

1 sec

Set Close Delay Time.


It is delay time to order closing when becomes hot status before
Lockout after the opening by section in V-T mode.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Lockout


[SECTION TIME]
>Close Delay:
>Lockout:
[1~255:1s]

1 ~ 255 sec

Range
2
1

Default 1

Step

1 sec

Close by section in V-T mode, If there isnt a fault during Lockout


time Lockout in close status. If becomes no voltage by experience a
fault within Lockout time, Lockout the close after close delay.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Source Lockout


[SECTION TIME]
>Source Lock:
>Source Reset:
[1~255:1s]

1 ~ 255 sec

Range
4
4

Default 4

Step

1 sec

Set Lockout Time of Source Side.


In normal condition(Live line), if Dead voltage is detected and it goes
in O-T(Outage Time) and within this O-T time, Live line comes back,
then, Source Lock time is applied and during this srouce locktime, if
Live line keeps last, it goes back to Home, however, During Source
Lock Time, if Deadline comes back again, automatically it does
Lockout

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Source Lockout


[SECTION TIME]
>Source Lock:
>Source Reset:
[1~255:1s]

Range
4
4

1 ~ 255 sec

Default 4

Step

1 sec

Set Reset Time of Source Side.


In O-T mode, under automatic Lockout condition, if Live line is
detected, Source reset time is started and if the live line keeps last
until Source reset time, Lock is released.

104

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Resetraint


[SECTION TIME]
>Source Reset:
4
>Resetraint:
60
[1~255:1s]

Range

1 ~ 255 sec

Default 60

Step

1 sec

In O-T mode, close after pass the Open Delay Time + Restraint Time
+ Close Time if becomes Dead line in Hot line status .

7.4.3. OPERATION COUNT


Locate the cursor on 3. OPERATION COUNT in SECTION menu, press [ENT] button and
move to this menu. This menu set the use of section function and section type.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / OPERATION COUNT / Count
[OPERATION COUNT]
>Count:
2
>
[1~4:1]

Range

1~4

Default 2

Step

Set operation count of section function.

ENHANCED TECHNOLOGY

105

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

7.5. Phase angle unbalance


Locate the cursor on 7. PHASE DIFF in PRIMARY or ALTERNATE menu, press [ENT] button
and move into this menu. In this menu, set phase angle difference elements.
Compare the phase of source side and phase of load side, in hot line status and open condition. It
is Phase angle inconsistency of is over set angle and normal if is under the set angle. But, phase
angle difference is not detected when source side or load side circuit is dead line.
GROUP SETTING / PRIMARY or ALTERNATE / PHASE DIFF / Level
[PHASE DIFF]
>Level:
30
Time :
4.0
[0(OFF),5~80:5deg]

Range

0(OFF), 5 ~ 80

Default 30

Step

Set phase angle difference.

GROUP SETTING / PRIMARY or ALTERNATE / PHASE DIFF / Time


[PHASE DIFF]
>Level:
30
>Time :
4.0
[0.0~180.0:0.1s]

Range

0.0 ~ 180.0sec

Default 4.0

Step

0.1sec

Set delay time of phase angle difference element.

7.6. Phase open/loss


Locate the cursor on 8. ON/OFF LEVELin PRIMARY or ALTERNATE menu, press [ENT]
button and move into this menu. In this menu, set phase open/loss elements.
If 1 or more than 2 phase among 3phase are over the Off Level of phase voltage, is phase
open/loss. If all 3 phase are Over On Level, they are normal voltage and phase open/loss detect is
cancelled. If all 3 phase are under Off Level, does not indicate phase open/loss as they are
normal(dead line)
GROUP SETTING / PRIMARY or ALTERNATE / ON/OFF LEVEL / On Level
[ON/OFF LEVEL]
>On Level:
80
>Off Level:
50
[70~85:5deg]

Range

70 ~ 85%

Default 80

Step

Set normal voltage Level.

106

ENHANCED TECHNOLOGY

5%

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GROUP SETTING / PRIMARY or ALTERNATE / ON/OFF LEVEL / Off Level


[ON/OFF LEVEL]
>On Level:
80
>Off Level:
50
[30~75:5deg]

Range

30 ~ 75%

Default 50

Step

5%

Set phase open/loss Level.

GROUP SETTING / PRIMARY or ALTERNATE / ON/OFF LEVEL / Time


[ON/OFF LEVEL]
>Off Level:
50
>Time :
4.0
[0.1~180.0:0.1s]

Range

0.1 ~ 180.0sec

Default 4.0

Step

0.1sec

Set delay time of line phase open/loss element.

7.7. Overcurrent detect element


Locate the cursor 10. OVER CURRENTin PRIMARY or ALTERNATE menu, press [ENT]
button and move into this menu. In this menu, set overcurrent detect element.
Overcurrent detect element is managed as PQ monitoring function item.
GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / PHA-Pickup
[OVER CURRENT]
>PHA-Pickup:
400
>PHA-Time:
2.0
[0(OFF),50~630:5A]

Range

0(OFF), 50 ~ 630A

Default 400

Step

5A

Set pickup level of over current for phase.

GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / PHA-Time


[OVER CURRENT]
>PHA-Pickup:
400
>PHA-Time:
2.0
[0.0~180.0:0.1s]

Range

0.0 ~ 180.0 sec

Default 2.0

Step

0.1sec

Set detection time of over current for phase.

GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / GND-Pickup


[OVER CURRENT]
>GND-Pickup:
100
>GND-Time:
2.0
[0(OFF),25~315:5A]

Range

0(OFF), 25 ~ 315A

Default 100

Step

5A

Set pickup level of over current for ground.

ENHANCED TECHNOLOGY

107

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / GND-Time


[OVER CURRENT]
>GND-Pickup:
100
>GND-Time:
2.0
[0.0~180.0:0.1s]

Range

0.0 ~ 180.0 sec

Default 2.0

Step

Set detection time of over current for ground.

108

ENHANCED TECHNOLOGY

0.1sec

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

8. EVENT
Place the cursorn on
Place the curser on 3.EVENT, press [ENT] button to move into this menu.
ETR300-R records all events during the operation, occurred events are recorded separately such as
operation event, fault event, system event, set change event, load event and diagnostic event. All
events are recorded in order(FIFO). In this menu, all events can be checked and deleted.
This menu has sub-menu as below. Press [ENT] to move into sub-menu.
.

[EVENT]
>1.OPERATION
2.FAULT
3.FAULT CYCLE
4.SYSTEM
5.SET CHANGE
6.AVER.LOAD/MIN
7.PEAK.LOAD/HOUR
8.PEAK.LOAD/DAY
9.DIGNOSTIC
10.PQM
11.CLEAR SAVED DATA

8.1. Operation Event


Operation event records max. 256 events. When Recloser operates(OPEN/CLOSE), operation
status and control signal(LOCAL/REMOTE) is recorded in operation event.
Move to MAIN MENU / EVENT / OPERATION to confirm operation events.

[001/256]
CONTROL :

CLOSE
REMOTE

2007/10/01 00:00:03

[002/256]
CONTROL :

OPEN
REMOTE

2007/10/01 00:00:02

[003/256]
CONTROL :

CLOSE
REMOTE

2007/10/01 00:00:01

[][] are used to check event. [001/256] is the latest event record.

Trigger Source

ENHANCED TECHNOLOGY

109

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

STATUS
- CLOSE
- OPEN
- EARTH CLOSE (ECLOSE)
- EARTH OPEN (EOPEN)

CONTROL
- MANUAL: Switch mechanical manual operation.
- LOCAL: Operation at local
- REMOTE: Remote operation.

Trigger Time
Monitor changes of Trigger source status in every 5 msec.

Trigger Capacity
Save maximum 256 events.

8.2. Fault Event


Fault event records maximum 256 events. Fault event records fault detection time, fault current
sixe of each phase, fault direction and fault events of each phase can be checked.
Move to MAIN MENU / EVENT / FAULT to confirm fault events.

[001/256] 1 EV
Target : A B C

2008/10/01 00:03:01
ENT

[001/256] 1 EV
A:00440FR B:00440FR
C:00446FR N:00006
SEF:00000mA

[002/256] 2 EV
Target : A B C

2008/10/01 00:02:00
ENT

[002/256] 1 EV
A:00440FF B:00440FF
C:00446FF N:00006
SEF:00000mA

[003/256] TO
Target : A B C

2008/10/01 00:01:00
ENT

[003/256] TO
A:00440T B:00440T
C:00446T N:00006
SEF:00000mA

[][] buttons are used to check fault events. Press [ENT] button in fault event screen to check
fault current value. And press [ENT] again to return to fault event screen. [001/256] is the latest
event record.

110

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Fault Event Information(EV)


Information before deciding the Fault type(permanent, temporary) is recorded.
SEQUENCE Sequence is recoded from one [FAULT].
TARGET Record Fault detection phase and Fault Direction.
001/256 Shows the latest event in order and records 100 events.
FAULT Max fault current is displayed on fault occurring. Fault Detection phase and Fault
CURRENT Current Direction are indicated.
- F: Fault Detection
- FF: Forward Fault Detection
- FR: Reverse Fault Detection

Total Information(TO)
Fault type (PermanentFault/Temporary Fault) and time, maximum current are recorded.
TARGET Record Fault detect phase and Fault type( P: Permanent fault, T: Temporary fault)
001/256 Shows the latest event in order and max.256 events are recorded.
FAULT Shows maximum current value when occurs fault and indicates fault detection
CURRENT fault type.

Trigger Source

Taget Element
- A: A phase
- B: B phase
- C: C phase
- N: N phase
- S: SEF

Fault Detect Element


- T: Temporary fault (TEMPORARY)
- P: Permanent fault (PERMANENT)

Detect direction
- F: FORWARD
- R: REVERSE

Fault Current[A]: A phase, B phase, C phase, N phase, SEF

ENHANCED TECHNOLOGY

111

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Trigger Time
Moniters changes of Trigger source status in every 1/4 cycle.

Trigger Capacity
Save maximum 256 events.

8.3. Fault Cycle - Summary


Fault wave is recorded up to 8 fault waves. Fault wave information is displayed on LCD.
Captured waveform can be checked in interface software.
Move to MAIN MENU / EVENT / FAULT CYCLE to confirm fault cycle summary.

[001/ 8]
PU
A: 00000
B: 00000
C: 00000
N: 00000
2008/10/01 03:00:00

[002/ 8]
PU
A: 00000
B: 00000
C: 00000
N: 00000
2008/10/01 02:00:00

[003/ 8]
PU
A: 00000
B: 00000
C: 00000
N: 00000
2008/10/01 01:00:00

[][] is used to check the fault event. [001/008] is the latest event record.

Trigger Source

Fault wave captured time.


- PU: Pick up time.
- TR: Trip time.
- PU&TR: Picku up & Trip time

Fault current [A]: A phase, B phase, C phase, N phase

Trigger Time
Moniters changes of Trigger source status in every 1/4 cycle.

Trigger Capacity
Maximum 8 events are recorded. (20cycles 8EA).

112

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

8.4. System Events


System events records maximum 2048 events.
Move to MAIN MENU / EVENT / SYSTEM to confirm system events.
[001/2048]
CPULINK
STATUS : HI/ASSERT

[002/2048]
CPULINK
STATUS : HI/ASSERT

[003/2048]
CPULINK
STATUS : HI/ASSERT

2008/10/01 00:00:03

2008/10/01 00:00:02

2008/10/01 00:00:01

[][] button is used to check the records. [001/2048] is the latest event record.

Trigger Source

52A Contact

Front panel control

AC supply

External control

Fail operation

External input/output status

System alarm

Sleep Mode

GAS STATUS

. NOTE : Refer to Appendix C.LOGIC BIT Attributes & Description for mored details
about trigger source.

Trigger Time
Monitors changes of Trigger source status in every 1/4 cycle.

Trigger type
Record when Pickup(HI/ASSERT) or Dropout(LO/DEASSERT).

Storage Capacity
Save maximum 2048 events.

ENHANCED TECHNOLOGY

113

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

8.5. Set Change Event


Set Change Event records maximum 100 events.
Move to MAIN MENU / EVENT / SET CHANGE to confirm set change events.

[001/100]
TARGET :

LOCAL
GLOBAL

[002/100]
TARGET :

2008/10/01 00:00:03

LOCAL
GLOBAL

2008/10/01 00:00:02

[001/100]
TARGET :

LOCAL
GLOBAL

2008/10/01 00:00:01

[][] button is used to check the records. [001/100] is the latest event record.

Trigger Source

Changed set menu


- GLOBAL SETTING
- PRIMARY SETTING
- ALTERNATE SETTING

Change method
- LOCAL: Set change at local
- REMOTE: Set change in remote
- PROGRAM: Set change by Interface software
. NOTE : Refer to Appendix C.LOGIC BIT Attributes & Description for more details
about trigger source

Trigger Time
Monitoring change of Trigger source status in every 5msec.

Storage Capacity
Saves maximum 100 events.

114

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

8.6. Aver. Load/Min


Records Average load value every 15 minutes. As records maximum 1024 values, about 10 days
events can be recorded.
Move to MAIN MENU / EVENT / AVER. LOAD/MIN to confirm aver. load/min events.

[0001/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 00:00:45

[0002/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 00:00:30

ENT

P3:
PA:
PB:
PC:

00000/
00000/
00000/
00000/

00000
00000
00000
00000

[0003/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 00:00:15
ENT

ENT

P3:
PA:
PB:
PC:

00000/
00000/
00000/
00000/

00000
00000
00000
00000

P3:
PA:
PB:
PC:

00000/
00000/
00000/
00000/

00000
00000
00000
00000

[][] button is used to check the events. To check real active power and reactive power, press
[ENT] button. To return back to previous screen, press [ENT] again. [0001/1024] is the latest
event record.

Trigger Source

Measured current [A]: A phase, B phase, C phase, N phase

Measured active power [kW]: 3 phases, A phase, B phase, C phase

Measured reactive power [kVar]: 3phases, A phase, B phase, C phase

Trigger Time
Monitors changes of Trigger source status in every 15min.

Storage Capacity
Saves maximum 1024 events.

8.7. Peak. Load/Hour


Records Peak load event.As records maximum 1024 events, about 43 days events can be recorded.

ENHANCED TECHNOLOGY

115

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Move to MAIN MENU / EVENT / PEAK. LOAD/HOUR to confirm peak. load/hour events.

[0001/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 03:00:00

[0002/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 02:00:00

ENT

P3:
PA:
PB:
PC:

00000/
00000/
00000/
00000/

00000
00000
00000
00000

[0003/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 01:00:00

ENT

P3:
PA:
PB:
PC:

00000/
00000/
00000/
00000/

00000
00000
00000
00000

ENT

P3:
PA:
PB:
PC:

00000/
00000/
00000/
00000/

00000
00000
00000
00000

[][] button is used to check the events. To check real active power and reactive power, press
[ENT] button in Current display screen. To return back to current display screen, press [ENT]
again. [0001/1024] is the latest event record.

Trigger Source

Measured current [A]: A phase, B phase, C phase, N phase

Measured active power [kW]: 3 phases, A phase, B phase, C phase

Measured reactive power [kVar]: 3phases, A phase, B phase, C phase

Trigger Time
Monitors changes of Trigger source status in every 1hour..

Storage Capacity
Saves maximum 1024 events.

8.8. Peak. Load/Day


Records Peak Load/Day events.As saves maximum 1024 events, about 1024 days event can be
recorded.
Move to MAIN MENU / EVENT / PEAK. LOAD/DAY to confirm peak. load/day events.

116

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

[0001/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/03 00:00:00

http://www.entecene.co.kr

[0002/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/02 00:00:00

ENT

P3:
PA:
PB:
PC:

00000/
00000/
00000/
00000/

00000
00000
00000
00000

[0003/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 00:00:00

ENT

P3:
PA:
PB:
PC:

00000/
00000/
00000/
00000/

ENT

00000
00000
00000
00000

P3:
PA:
PB:
PC:

00000/
00000/
00000/
00000/

00000
00000
00000
00000

[][] button is used to check the events. To check real active power and reactive power, press
[ENT] button in Current display screen. To return back to current display screen, press [ENT]
again. [0001/1024] is the latest event record.

Trigger Source

Measured current [A]: A phase, B phase, C phase, N phase

Measured active power [kW]: 3 phases, A phase, B phase, C phase

Measured reactive power [kVar]: 3phases, A phase, B phase, C phase

Trigger Time
Monitors changes of Trigger source status in every 1 day.

Storage Capacity
Saves maximum 1024 events.

8.9. Diagnostic Event


Diagnostic event records and shows maximum 512 events.
Move to MAIN MENU / EVENT / DIGNOSTIC to confirm Diagnostic Event.
[001/512]
SELFTOK
STATUS : HI/ASSERT

[002/512]
SELFTOK
STATUS : HI/ASSERT

[003/512]
SELFTOK
STATUS : HI/ASSERT

2008/10/01 00:00:03

2008/10/01 00:00:02

2008/10/01 00:00:01

ENHANCED TECHNOLOGY

117

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

[][] button is used to check the events. [001/512] is the latest event record.

Trigger Source

DSP Failure

ADC Failure

RTC Failure

Memory Failure

Flash-Rom Failure

Circuit Voltage Failure

Globlal Setting Failure

Primary Setting Failure

Alternate Setting Failure

Event Failure

Count Failure

DO Failure

Closing Failure

Opening Failure
. NOTE : Refer to Appendix C.LOGIC BIT Attributes & Description for more details
about trigger source.

Trigger Time
Monitors status of Trigger source in every 5msec.

Trigger type
Records Dignostic event Pickup(HI/ASSERT) or Dropout(LO/DEASSERT).

Storage Capacity
Saves maximum 512 events.
When occurs Self Diagnosis Fault, handle as following
Table 8-1.Treatment method of Self Diagnosis Failure

118

No.

Diagnosis item

Treatment Period

Treatment Method

DSP

within 200msec

Change to FI Detect Restrain

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

ADC

1/4 cycle

Change to FI Detect Restrain

RTC

1hour, when booting

Change the date to Jan. 1st, 1970

Memory

Restart

Flash-Rom

Circuit Voltage

Global Setting

Primary Setting

Alternate Setting

10

Event

1hour, when booting


When Read and WriteFlashRom , when booting
1/4 cycle
When change setting, when
booting
When change setting, when
booting
When change setting, when
booting
When save and read event

Change to FI Detect Restrain


Change to Global setting value
Default value
Change to Primary Setting value
Default value
Change to Alternate Setting value
Default value
Event initialization

11

Count

When write and read count

Counter initialization

12

DO Signal

50msec

Block the output power

13

Close/Opem

When Closing and Openning

Need to check in local

Restart

ENHANCED TECHNOLOGY

119

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

8.10. PQM
Power Quality Management (PQM) detect event records 100 events.
Move to MAIN MENU / EVENT / PQM to confirm PQM events.
[001/100]
SWL&TEMP
TARGET :
1WAY A
DATA: 1670V 337 Cyc
2008/10/01 10:00:03

[002/100]
OVS
TARGET :
1WAY A
DATA:
1668V
2008/10/01 09:00:00

[003/100]
UBI
TARGET :
1WAY
DATA:
102%
2008/10/01 08:10:20

[][] button is used to check the event. [001/100] is the latest event record.

Trigger Source

PQM detect element.


- Sag(SAG): Instantaneous(INST), Momentary(MOME), Temporary(TEMP),
Long Time(LONG)
- Swell(SWL): Instantaneous(INST), Momentary(MOME), Temporary(TEMP),
Long Time(LONG)
- Interruption(INT): Momentary(MOME), Temporary(TEMP), Sustained(LONG)
- Source side Unbalance Voltage(UBV)
- Load side Unbalance Voltage (UBL)
- Current Unbalance(UBI)
- Source side Over voltage (OVS)
- Load side Over voltage (OVL)
- Over Current
- Voltage Harmonic distortion (VTH)
- Current Harmonic distortion (ITH)

PQM element detected phase: Aphase, Bphase, Cphase

PQM element related measured value

PQM detect time(cycle)

Trigger Time
Monitors status of Trigger source in every 5msec.

120

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

Storage Capacity
Saves maximum 100 events.

8.11. Clear Saved Data


Move to EVENT / CLEAR SAVED DATA to clear saved data.
EVENT / CLEAR SAVED DATA
[CLEAR SAVED DATA]
>1.OPERATION
2.FAULT
3.SYSTEM
4.SET CHANGE
5.LOAD PROFILE
6.DIGNOSTIC
7.PQM
8.ABOVE ALL

Clear Saved Data


Select an item to delete and press[ENT] button.
If deleting is completed, EVENT CLEAR SUCCESS
message is displayed.

8. ABOVE ALL
[EVENT CLEAR]

1 ~ 7 items are all deleted.

EVENT CLEAR SUCCESS

ENHANCED TECHNOLOGY

121

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

9. Maintenance
Place the curser on 4. MAINTENANCE in Main menu, press [ENT] button to move into this
menu. This menu displays Maintenance information.
This menu has sub-menu as below and by pressing [ENT] button, move into sub-menu.

[MAINTENANCE]
>1.COUNT
2.INTERRUT TIME
3.CONTACT WEAR
4.DATA RESET
5.CCU INFO

9.1. Count
This menu displays counter information and has submenus as following.

[COUNT]
>1.CCU
2.OPERATION
3.FAULT
4.PQM

9.1.1. CCU Count


Move to MAINTENANCE / COUNT / CCU to confirm CCU (ETR 300)count.
MAINTENANCE / COUNT / CCU
[CCU]
RESTART
:
DIAGNOSTIC :

30
0

Restart Count
ETR300-R restart number is displayed.

Diagnostic Count
ETR300-R Diagnostic Count is displayed.

122

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

9.1.2. Operation Count


Move to MAINTENANCE / COUNT / OPERATION to confirm operation count.
MAINTENANCE / COUNT / OPERATION
Displays operation counter of switch.

[OPERATION]
COUNT :

9.1.3. Fault Count


Move to MAINTENANCE / COUNT / FAULT to confirm fault count.
MAINTENANCE / COUNT / FAULT
TOT:
A :
C :

[FAULT]
0 SEF:
0 B :
0 N :

1/3
0
0
0

Number of fault is displayed. This COUNT menu consists in 3


pages. Use [][] button to move into sub-menu.

FAULT(1/3)
Total number of fault detection and fault detection number per phase
[FAULT-P]
TOT:
0 SEF:
A :
0 B :
C :
0 N :

2/3
0
0
0

ard displayed.

FAULT(2/3)
Total number of PERMANENT fault and number of fault per phase
TOT:
A :
C :

[FAULT-T]
0
0 B :
0 N :

3/3
0
0

are displayed.

FAULT(3/3)
Total number of TEMPORARY fault and number of fault per phase
are displayed.

9.1.4. PQM Count


This menu displays PQM count information and has the following submenu.

ENHANCED TECHNOLOGY

123

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

[PQM COUNT]
>1.INTERRUT
2.SAG
3.SWELL
4.HARMONICS
5.CURR UNBALANCE
6.VOLT UNBALANCE
7.UNDER VOLTAGE
8.OVER VOLTAGE
9.OVER CURRENT
10.UNDER FREQUNCY

9.1.4.1. INTERRUPT
Move to MAINTENANCE / PQM / INTERRUPT to confirm interrupt count.
MAINTENANCE / COUNT / PQM / INTERRUPT
[INTERRUPT] 1/2
TOTAL:
0
A :
0 B :
0
C :
0

Number of Interruption is displayed. This COUNT menu consists in 2


pages and use [][] button to move into each pages.

INTERRUPT(1/2)
Total number of Interruption and number of interruption per phase are
[INTERRUPT] 2/2
MOMENTARY :
0
TEMPORARY :
0
SUSTAINED :
0

displayed.

INTERRUPT(2/2)
Number of fault per type is displayed on Interruption.

124

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

9.1.4.2. Sag
Move to MAINTENANCE / COUNT / PQM / SAG to confirm sag count.
MAINTENANCE / COUNT / PQM / SAG

A :
C :

[SAG]
TOTAL:
0 B :
0

1/2
0
0

Number of Sag is displayed. This COUNT menu consists 2 pages and


use [][] buttons to move into sub-menu.

SAG(1/2)
Total number of Sag occurred and number of Sag per phase are
INS:
TMP:

[SAG]
2/2
0 MOM:
0
0 LON:
0

displayed.

SAG(2/2)
Number of Sag per type is displayed.

9.1.4.3.Swell
Move to MAINTENANCE / COUNT / PQM / SWELL to confirm swell count.
MAINTENANCE / COUNT / PQM / SWELL

A :
C :

[SWELL]
TOTAL:
0 B :
0

1/2
0
0

Number of Swell occurred is displayed. This COUNT menu consists


of 2 pages and use [][] button to move into sub-menu.

SWELL(1/2)
Total number of Swell and number of Swell per phase are displayed.
INS:
TMP:

[SWELL]
0 MOM:
0 LON:

2/2
0
0

SWELL(2/2)
Number of Swell per type is displayed.

ENHANCED TECHNOLOGY

125

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

9.1.4.4. Harmonics
Move to MAINTENANCE / COUNT / PQM / HARMONIC to confirm sag count.
MAINTENANCE / COUNT / PQM / SWELL

A :
C :

[VTHD]
TOTAL:
0 B :
0

1/2
0
0

Number of Harmonic distortion is displayed. The COUNT menu


consists 2 pages and use [][] buttons to move into sub-menu.

VTHD(1/2)
Total number of Voltage Harmonic distortion and number of voltage
A :
C :

[ITHD]
TOTAL:
0 B :
0

2/2
0
0

harmonic distortion per phase are displayed.

ITHD(2/2)
Total number of current harmonic distortion and number of current
harmonic distortion per phase are displayed.

9.1.4.5. Current Unbalance


Move to MAINTENANCE / COUNT / PQM / CURRENT UNBALANCE to confirm current
unbalance count.
MAINTENANCE / COUNT / PQM / CURRENT UNBALANCE
[CURRENT UNBALANCE]
COUNT :

126

Number of Current Unbalance occurred is displayed.

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

9.1.4.6. Voltage Unbalance


Move to MAINTENANCE / COUNT / PQM / VOLTAGE UNBALANCE to confirm voltage
unbalance count.
MAINTENANCE / COUNT / PQM / VOLTAGE UNBALANCE
[VOLTAGE UNBALANCE]
SOURCE SIDE :
0
LOAD SIDE
:
0

Number of voltage unbalance occurred is displayed.

SOURSE SIDE
Number of voltage unbalance at source side is displayed.

LOAD SIDE
Number of voltage unbalance at load side is displayed.

9.1.4.7. Under Voltage


Move to MAINTENANCE / COUNT / PQM / UNDER VOLTAGE to confirm under voltage
count.
MAINTENANCE / COUNT / PQM / UNDER VOLTAGE
[VS-UNDER VOLT] 1/2
TOTAL:
0
A :
0 B :
0
C :
0

Number of under-voltage is displayed. This COUNT menu consists 2


pages and use [][] button to move into sub-menu.

VS-UNDER VOLT(1/2)
[LS-UNDER VOLT] 2/2
TOTAL:
0
A :
0 B :
0
C :
0

Total number of undervoltage at source side and number of


undervoltage per phase are displayed.

LS-UNDER VOLT (2/2)


Total number of undervoltage at load side and number of
undervoltage at load side per phase are displayed.

ENHANCED TECHNOLOGY

127

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

9.1.4.8. Over Voltage


Move to MAINTENANCE / COUNT / PQM / OVER VOLTAGE to confirm over voltage
count.
MAINTENANCE / COUNT / PQM / OVER VOLTAGE
[VS-OVER VOLT] 1/2
TOTAL:
0
A :
0 B :
0
C :
0

Number of over-voltage is displayed. This COUNT menu consists 2


pages and use [][] button to move into sub-menu.
.

VS-OVER VOLT(1/2)
[LS-OVER VOLT] 2/2
TOTAL:
0
A :
0 B :
0
C :
0

Total number of overvoltage at source side and number of


undervoltage per phase are displayed.

LS-OVER VOLT (2/2)


Total number of overvoltage at load side and number of overvoltage
at load side per phase are displayed.

9.1.4.9.Under Frequency
Move to MAINTENANCE / COUNT / PQM / Under Frequency to confirm under frequency
count.
MAINTENANCE / COUNT / PQM / UNDER FRQUENCY
[UNDER FREQUENCY]
COUNT :

128

Number of underfrequency is displayed.

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

9.2. Interrupt Time


Move to MAINTENANCE / INTERRUPT TIME to confirm interrupt time.
MAINTENANCE / INTERRUPT TIME
[INTERRUP TIME] 1/2
TOTAL:
0
A :
0 B :
0
C :
0 N :
0

Accumulated interrupt time is displayed. This COUNT menu consists


2 pages and use [][] button to move into sub-menu.

INTERRUPT TIME(1/2)
Total accumulated time and accumulated time per phase are
[INTERRUP
MOMENTARY
TEMPORARY
SUSTAINED

TIME] 2/2
:
0
:
0
:
0

displayed. Time unit is Cycle.

INTERRUPT TIME(2/2)
Accumulated time per interrupt type is displayed, time unit is cycle.

ENHANCED TECHNOLOGY

129

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

9.3. Contact Wear


Move to MAINTENANCE / CONTACT WEAR to confirm contact wear.
MAINTENANCE / CONTACT WEAR
[CONTACT WEAR-%]
A : 100.00
B : 100.00
C : 100.00

Displays switch contact wear in percentage.

9.4. Data Reset


Move to MAINTENANCE / DATA RESET. This menu resets COUNT and Maintenance data.
MAINTENACE / DATA RESET
[DATA RESET]
>1.CCU COUNT
2.OPERATION COUNT
3.FAULT COUNT
4.DELTA I COUNT
5.PQM COUNT
6.COUNT ALL
7.INTERRUPT COUNT
8.CONTACT WEAR
9.ENERGY
10.ABOVE ALL
[EVENT CLEAR]
EVENT CLEAR SUCCESS

Saved data reset


Select an item to delete and press[ENT] button.
If deleting is completed, EVENT CLEAR SUCCESS
message is displayed.

. NOTE :
1) OPERATION COUNT is reset by a set value in MAIN MENU/
GLOBLA SETTING/ MONITERING/ OPERATION COUNT.
2) CONTACT WEAR is reset by a set value in MAIN MENU/
GLOBLA SETTING/ MONITERING/ CONTACT WEAR.
3) Except OPERATION COUNT and CONTACT WEAR, all data
is reset for 0.

10. ABOVE ALL


1 ~ 9 item data are all reset.

130

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

9.5. CCU Information


Move to MAINTENANCE / CCU INFO to confirm ccu information.
MAINTENANCE / CCU INFO
TYPE:ETR300S-11D-4024-11D-1FF-DMN

Present CCU(ETR300-S) information is displayed.

61-0101-0000-KR-1000

ENT

Prog Opt:ox70310156
MPU Ver: 1.0
DSP Ver: 1.0
CPU Ver: 1.0

ENHANCED TECHNOLOGY

131

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

10. Time
Place the curser on 5.TIME in Main menu, press [ENT] button to move in this menu.
TIME
[CURRENT TIME]
2006/11/05 21:02:38
PRESS <ENT>

TO SET

Set present date and time.


1) Press [ENT] button to select and change a setting.
2) To change a number, use [][] button and to move next item,

[SETTING TIME]
2006/11/05 21:02:38
USE [UP/DOWN/ENTER]
PRESS <FUNC> : ABORT

press [ENT] button.


3) To save all changed setting, press [ENT].

[SAVE TIME]
2006/11/06 15;01:50
PRESS <ENT> TO SAVE

132

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

11. Status
Place the curser on 6. STATUS in Main menu, press [ENT] button to move in this menu. This
menu has sub-menu as below. Press [ENT] to move into sub-menu.

[STATUS]
>1.SWITCH
2.INPUT PORTS
3.OUTPUT PORTS

11.1. Switch
You can confirm in MAIN MENU / STATUS / RECLOSER
STATUS/ SWITCH
[SWITCH]
>SWITCH
:TROUBLE
PANEL LOCK : UNLOCK
CONTROL
: LOCAL
SECTION
:DISABLE
PHA-PROTECT:DISABLE
GND-PROTECT:DISABLE
LOCKOUT
:LOCKOUT
POWER
:
OFF
BATTERY
: NORMAL
BATCHRGER : NORMAL
DOOR
: CLOSE
CCU ADDRESS:
0
MASTER ADDR: 65534
HANDLE LOCK:LOCKOUT
GAS
: NORMAL

Present switch and ETR300 status are displayed.


Use [] [] button to check all items.

SWITCH
Displays main device status.
OPEN, CLOSE, TROUBLE(Device Trouble status)

PANEL LOCK
Displays panel lock status.

LOCK, UNLOCK

CONTROL
Operation control select is displayed.

REMOTE, LOCAL, TROUBLE(Device Trouble Status)

SECTION
Display whether to use section function.

DISABLE, ENABLE

PHA-PROTECT
Phase protection function status is displayed.

DISABLE, ENABLE

GND-PROTECT

ENHANCED TECHNOLOGY

133

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

STATUS/ SWITCH
Ground protection function status is displayed.
DISABLE, ENABLE

LOCKOUT
Section operation status is displayed.

RESET, RUNNING, LOCKOUT

POWER
External power supply status is displayed.
ON, OFF

BATTERY
Battery status is displayed.
NORMAL, FAIL

BAT CHARGER
Battery charger status is displayed.
NORMAL, FAIL

DOOR
Door status is displayed.
OPEN, CLOSE

CCU ADDRESS
DNP set address of ETR300 is displayed.(0~65535)

MASTER ADDR
DNP Host Address (0~65534:65535 is used for Broadcast)

GAS
Circuit breaker gas pressure status is displayed.
NORMAL, LOW

134

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

11.2. Input Ports


You can confirm in MAIN MENU / STATUS / INPUT PORTS
STATUS/ INPUT PORTS
IN
IN
IN
IN
IN

IN

[INPUT PORTS]
101 :LO/DEASSERT
102 :LO/DEASSERT
103 :LO/DEASSERT
104 :LO/DEASSERT
105 :LO/DEASSERT

Displays 16 input terminal(IN101 ~ IN108 and IN208 ~ IN208) status

208 :

[] [] button is used to check all input terminal status.

HI/ASSERT

Depending on input signal, HI/ASSERT or LO/DEASSERTis


displayed.

11.3. Output Ports


You can confirm in MAIN MENU / STATUS / OUTPUT PORTS
STATUS/ OUTPUT PORTS
[OUTPUT PORTS]
OUT 101:LO/DEASSERT
OUT 102:LO/DEASSERT
OUT 103:LO/DEASSERT
OUT 104:LO/DEASSERT
OUT 105:LO/DEASSERT

OUT 208: HI/ASSERT

Displays 16 output terminal(OUT101 ~ OUT108 and OUT208 ~


OUT208) status.
Depending on output signal, HI/ASSERT or LO/DEASSERTis
displayed.
[] [] button is used to check all input terminal status.

ENHANCED TECHNOLOGY

135

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

12. Metering
Place the curser on 7. MERING in Main menu, press [ENT] button to move in this menu. This
menu displays present measured value and has sub-menu as following. Press [ENT] to move into
sub-menu.

[METERING]
>1.CURRENT
2.VOLTAGE
3.FREQUENCY
4.POWER
5.ENERGY
6.DEMAND
7.UNBALANCE
8.HARMONICS
9.TRUE R.M.S
10.TD
11.CCU SEF

12.1. Current
ETR300 metering and indicates the following current items.

IA : Displays the measured phase A RMS current and phase (A, deg)

IB : Displays the measured phase B RMS current and phase (A, deg)

IC : Displays the measured phase C RMS current and phase (A, deg)

IN : Displays the measured ground RMS current and phase (A, deg)

SEF: Displays the measured sensitive earth RMS current and phase (A, deg)

You can confirm in MAIN MENU / METERING / CURRENT


MAIN MENU / METERING / CURRENT
IA:
IB:
IC:
IN:
SEF:

136

[CURRENT]
0 A 000.0
0 A 000.0
0 A 000.0
0 A 000.0
0mA 000.0

Current per phase and angle per phase are displayed.


Use [] [] keys to move to next value.

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

12.2. Voltage
ETR300 metering and indicates the following voltage items.

VS-PN: Voltage per phase and angle per phase at source side, are displayed(, deg).

VS-PP: Phase to phase voltage and angle at source side, are displayed(, deg).

VS-SEQ: Forward/Reverse/Zero sequence voltage and angle at source side, are displayed(,
deg).

VL-PN: Voltage per phase and angle per phase at load side, are displayed (, deg).

VL-PP: Phase to phase voltage and angle at load side, are displayed (, deg).

VL-SEQ: Forward/Reverse/Zero sequence voltage and angle at load side, are displayed (,
deg).

You can confirm in MAIN MENU / METERING / VOLTAGE


MAIN MENU / METERING / VOLTAGE
[VS-PN]
A : 00.00 kV 000.0
B : 00.00 kV 000.0
C : 00.00 kV 000.0

[VS-PP]
AB: 00.00 kV 000.0
BC: 00.00 kV 000.0
CA: 00.00 kV 000.0

[VS-SEQ]
V1: 00.00 kV 000.0
V2: 00.00 kV 000.0
V0: 00.00 kV 000.0

[VL-SEQ]
V1: 00.00 kV 000.0
V2: 00.00 kV 000.0
V3: 00.00 kV 000.0

[VL-PP]
RS: 00.00 kV 000.0
ST: 00.00 kV 000.0
TR: 00.00 kV 000.0

[VL-PN]
R : 00.00 kV 000.0
S : 00.00 kV 000.0
T : 00.00 kV 000.0

[GPT]
VN: 00.00 kV 000.0

Voltage and angle per phase are displayed. Use [][] button to check it.

ENHANCED TECHNOLOGY

137

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

12.3. Frequency
ETR300 metering and indicates the following frequency items.
;

Hz: Present frequency is displayed.

You can confirm in MAIN NEMU / METERING / FREQUENCY


MAIN MENU / METERING / FREQUENCY
[FREQUENCY]
0.00 Hz

Frequency measured value is displayed.

12.4. Power
ETR300 metering and indicates the following power items.

POWER-KW/KVAR/KVA: Per phase, active power/apparent power/reactive power are


displayed.

POWER FACTOR: Power factor per phase is displayed.

You can confirm in MAIN NEMU / METERING / POWER


MAIN MENU / METERING / POWER
[POWER- KW/KVAR/KVA]
A : 0000 0000 0000
B : 0000 0000 0000
C : 0000 0000 0000

Per phase, power and power factor are displayed.


Use [][] button to check the power metering information.

[POWER FACTOR]
A : 000
B : 000
C : 000

138

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

12.5. Energy
ETR300 metering and indicates the following energy items.

FORWARD KWh/KVARh: Energy per phase in forward is displayed.

REVERSE KWh/KVARh: Energy per phase in reverse is displayed.

You can confirm in MAIN NEMU / METERING / ENERGY


MAIN MENU / METERING / ENERGY
[FORWARD- KWh/KVARh]
A : 000000 000000
B : 000000 000000
C : 000000 000000

Energy is displayed. Use [][] button to check the energy


metering information.

[REVERSE- KWh/KVARh]
A : 000000 000000
B : 000000 000000
C : 000000 000000

12.6. Demand Current


You can confirm in MAIN MENU / METERING / DEMAND
MAIN MENU / METERING / DEMAND
[DEMAND
A: 0000 A
C: 0000 A
SEF

CURRENT]
B: 0000 A
N: 0000 A
:00.000 A

Load current per phase are displayed.

ENHANCED TECHNOLOGY

139

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

12.7. Unbalance
ETR300 metering and indicates the following unbalance items.

SOURCE-VOLT: Voltage unbalance at source side is displayed.

LOAD-VOLT: Voltage unbalance at load side is displayed.

CURRENT: Current unbalance is displayed.

You can confirm in MAIN MENU / METERING / UNBALANCE


MAIN MENU / METERING / UNBALANCE
[UNBALANCE- %]
SOURCE-VOLT:
0.00
LOAD-VOLT:
0.00
CURRENT:
0.00

Unbalance of metering value is displayed.

12.8. Harmonics
You can confirm in MAIN MENU / METERING / HARMONICS
MAIN MENU / METERING / HARMONICS
[%V-Harm.
THD : 0.0
02H : 0.0
03H : 0.0

A/B/C]
0.0 0.0
0.0 0.0
0.0 0.0

[%I-Harm. 31H]
A : 0.0 B : 0.0
C : 0.0 N : 0.0

[%V-Harm.
04H : 0.0
05H : 0.0
06H : 0.0

A/B/C]
0.0 0.0
0.0 0.0
0.0 0.0

[%V-Harm. A/B/C]
31H : 0.0 0.0 0.0

[%I-Harm. 02H]
A : 0.0 B : 0.0
C : 0.0 N : 0.0

[%I-Harm. THD]
A : 0.0 B : 0.0
C : 0.0 N : 0.0

Voltage and current harmonic rate are displayed. Use [][] button to check harmonic rate
information.

140

ENHANCED TECHNOLOGY

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

12.9. True R.M.S


You can confirm in MAIN NEMU / METERING / TRUE R.M.S
MAIN MENU / METERING / TRUE R.M.S
[VOLTAGE-TURE R.M.S]
A :
000 V
B :
000 V
C :
000 V

TRUE R.M.S voltage and current per phase are displayed. Use
[][] button to check TURE R.M.S. information .

[ CURRENT- TURE R.M.S]


A : 0.0A
B: 0.0 A
C : 0.0A
N : 0.0 A

12.10. TD Monitoring
You can confirm in MAIN MENU / METERING / TD MONITORING
MAIN MENU / METERING / TD MONITORING
[TD
TD1:
TD3:
TD5:

MONITERRING]
00.0 TD2: 00.0
00.0 TD4: 00.0
00.0

TD input value is displayed.

12.11. CCU Reference


You can confirm in MAIN MENU / METERING / CCU REF
MAIN MENU / METERING / CCU REF
[CCU Rer]
+5V: 4.9 -5V:-4.8
Temp: 37

ETR300 reference values are displayed.

ENHANCED TECHNOLOGY

141

SWITCH CONTROL ETR300-S01

http://www.entecene.co.kr

13. PLC function


ETR300 has changeable PLC for user. PLC has Timer, Counter and Event to control input and
output. Circuit can be optimized to omit unnecessary timer and aux. relay. During ETR300
running, in case the circuit needs to be changed, PLC can be used to meet users need. PLC is
programmed in ETR300 Interface Software.

Ficture 13-1. PLC Edit Screen

142

ENHANCED TECHNOLOGY

You might also like