You are on page 1of 70

Medium Voltage Distribution

Ringmaster
Ring Main Unit

Catalogue
2009

A new path for achieving your electrical installations


A comprehensive offer
The Ringmaster range is part of a comprehensive offer of products that are perfectly
coordinated to meet all medium and low voltage electrical distribution requirements.
All of these products have been designed to work together: electrical, mechanical
and communication compatibility.
The electrical installation is thus both optimised and has improved performance:
@ better service continuity,
@ increased personnel and equipment safety,
@ guaranteed upgradeability,
@ efficient monitoring and control.
You therefore have all the advantages at hand in terms of know-how and creativity
for achieving optimised, safe, upgradeable and compliant installations.

Tools for facilitating the design and installation


With Schneider Electric, you have a complete range of tools to help you get to know and
install the products whilst complying with current standards and good working practices.
These tools, technical sheets and guides, design software, training courses, etc are
regularly updated.

Schneider Electric is associating itself with


your know-how and your creativity to produce
optimised, safe, upgradeable and compliant
installations
For a real partnership with you
A universal solution doesnt exist because each electrical installation is specific.
The variety of combinations on offer allows you to truly customise the technical solutions.
You are able to express your creativity and put your know-how to best advantage
when designing, manufacturing and exploiting an electrical installation.

Ringmaster range

General contents

Presentation

Applications
Switchgear description
VIP protection relays
Network remote control
Ringmaster selection guide

2
3
5
6
8

Section 1

Ring main units

10 - 25

Circuit breaker, metering and switches

26 - 65

Remote control

66 - 68

Section 2
Installation drawings

70 - 80

Schematic diagrams

81 - 112

Section 3
Accessories

Section 4
Schneider Electric, an overview and order form

AMTED399086EN.indd

69

113
114 - 119

121
122 - 128

Ringmaster range
Presentation

Applications

Ringmaster is the ideal choice for all your MV applications.


From simple transformer protection, or sectionalising with remote
control, to multi-panel metered consumer switchboards,
the Ringmaster range from Schneider Electric offers a solution.
Quality engineering for extreme climates enables Ringmaster
to provide flexibility for any location.
Covering a wide range of options with an indoor and outdoor IP54
design and ratings up to 13.8 kV, 630 A and 21 kA, Ringmaster
has proved successful in markets around the world.

Product advantages
Simple, clear operation combined with compact size,
high functionality and reliability extends the applications
of the Ringmaster range.
Safety to personnel
Fully certified internal arc design.
Indoor/outdoor design
No need for expensive switchrooms.
Self powered protection
Not reliant on costly battery chargers.
Compact
Reduced dimensions, gives reduced civil costs.
Virtually maintenance free
Low lifetime costs.
Modular design
Quick, simple & easy to install.
Proven design
Assured consistent quality.
ISO 9001 quality certification.
PE40438

Environmental
Manufactured to ISO 14001 environmental standards.

AMTED399086EN.indd

Switchgear description

Ringmaster range
Presentation

A variety of different panel types are available for each unit within
the range, together with a number of optional accessories enabling
Ringmaster to satisfy the most complex system specification.

PE57064

PE57061

A multitude of configurations

Transformer mounted,
non-extensible ring main unit,
incorporated in a packaged
substation.

PE57065

PE57062

Free standing,
non-extensible,
cable connected
ring main unit.

Transformer mounted,
extensible ring main unit,
incorporated in a packaged
substation.

PE57066

PE57063

Free standing,
extensible cable
connected ring main unit

Free standing,
non-extensible
circuit breaker.

AMTED399086EN.indd

Cable connected
extensible switchboard.

Ringmaster range
Presentation

Switchgear description

PE57067

General characteristics
b Gas pressure indicator as standard
b Anti-reflex operating handle with facilities
for electrical operation
b Interlocked MV cable test access (no need to remove
cable terminations or use loose earthing devices)
b Integral self-powered protection with TFL,
adjustable curve & relay options
b IP54 enclosure
b Simple to follow mimic providing user-friendly operation
b Earth screened cast-resin gas module
b Range of dry type metering units
b Mechanical tripped on-fault indication
b Resin encapsulated busbars in air bus chamber
for extensible version
b Direct coupling to transformers or cable connection.

Standard and quality assurance


Manufactured to BS EN ISO 9001.
Ringmaster meets the following standards and has obtained
approval from the UK Electricity Association: IEC 56, IEC 60265,
IEC 62271-200, BS EN 60265 and EATS 41-26.

AMTED399086EN.indd

Ringmaster range
Presentation

VIP protection relays


Self-powered reliability

PE57160

VIP 300 - the leading protection relay providing a wide range of


selectivity and quality of supply
The VIP 300 is a three phase overcurrent and earth fault protection device, providing
protection for networks and equipment. Being an integral part of the highly successful
Ringmaster range, its main function is to detect phase and earth faults within the
network and to trip the circuit breaker.

PE57159

VIP 300
b Pick-up current ranges: RN2c, RE2c, CN2, CE2
Overcurrent: 20A-200A.
Earth fault: 2A-160A.
CE6 and RN6c Overcurrent: 80A-800A.
Earth fault: 8A to 640A.
Hardened electronics Certified EMC performance to IEC
60255 and EN 50061, EN50082.
b Separate overcurrent and earth fault trip indication.
b Flashing LEDs indicate when the relay is operating under
fault conditions.

Flexibility
The relay provides for a wide range of protection settings for most applications.
The IDMT characteristics employed for both the overcurrent and earth fault elements
can be easily adjusted to provide discrimination with upstream MV and downstream
LV protective devices. Fast power-up of the VIP 300 also provides immediate
protection and can detect faults instructing the CB to trip in less than 40ms.
Reliability
The relay has a self monitoring device and diagnostic routine that constantly checks
the operation of the relay automatically.
Self-powered reliability
The VIP 300 protection relay is a self powered microprocessor based device which
requires no external DC power source or batteries, making it the ideal solution for
location in remote areas where auxiliary supplies are not readily available.
Ease of use
VIP 300 has improved operation and control with the relay settings being clearly
displayed on the front panel. Manual reset flags show separate tripped on fault for
either phase or earth fault conditions.

VIP 35
provides protection against phase-to-phase faults
and earth faults.

Testing
The VAP 6 hand held test unit, is available to provide a simple check of the integrity
of the relay and can also be used to perform trip tests on the circuit breaker.
The circuit breaker trip inhibit facility allows the relay to be tested without tripping
the circuit breaker. Secondary injection can be carried out using conventional test
equipment.

PE56826

The VIP 30 and VIP 35 are self-powered devices, requiring no external DC power
source or batteries. They are designed for use in distribution networks providing
protection for transformers.

VAP 6

AMTED399086EN.indd

Network remote control

Ringmaster range
Presentation

T200E telecontrol

Ringmaster and T200E


Control your Ringmaster from a remote position
The Schneider Electric Easergy T200E telecontrol cabinet, which
links the Ringmaster to a control centres automation system,
allows you to manage a secondary distribution network from
a remote point. Network faults can be identified and isolated
and the network reconfigured in seconds without manual
intervention, which substantially improves the quality of supply.
The small and compact Easergy T200E can be easily mounted
directly onto the Ringmaster, saving installation costs and valuable
floor space.

PE57071

PE57069

Telecontrol equipment can be added any time after installation.


This makes Ringmaster RMUs even more cost-effective to install,
since a control system can be bought separately if needed at a later
date. Other RTUs can also be integrated if required.

Internal view
of Easergy T200E

Ringmaster C with Easergy T200E

AMTED399086EN.indd

Network remote control

Ringmaster range
Presentation

Easergy L500

Continuity of service guaranteed by an overall


telecontrol offer
Schneider Electric offers you a complete solution, including:

DE40901EN

PE56312

b the Easergy T200 E telecontrol interface,


b MT switchgear that is adapted for telecontrol.
HV/MV

RN2C

RN2C

RN2C

MV ring
Communication network

Network control centre


L500 network monitoring screen

RN2C

RN2C

RN2C

PE57073EN

Easergy L500, a low cost solution


to immediately improve your SAIDI *
* SAIDI: system average interruption duration index

Easergy L500 is a SCADA providing all the functions needed to operate


the MV network in real time
b Pre-configured with Easergy range products:
v MV/LV substations equipped with T200 E or Flair 200C
v overhead line equipped with Flite 116/G200
b Broad range of transmission supports: Radio, GSM, GPRS, PSTN, LL, FO.
Advantages
b Simple implementation:
v one to two weeks only for 20 MV/LV substations
v configuration, training and handling within a few days
b Short return on investment
b Simple and fast evolutions by operations managers
b Service quality and operations rapidly improved.

AMTED399086EN.indd

Ringmaster selection guide

PE57072

Ringmaster range
Presentation

RN2c

RE2c

RN6c

MU2

CN2

SN6

CE2

CE6

SE6

200 A
non extensible
ring main unit

200 A
extensible
ring main unit

630 A
non extensible
ring main unit

200 A
feeder
metering unit

200 A
non extensible
circuit breaker

630 A
non extensible
switch

200 A
extensible
circuit breaker

630 A
extensible
circuit breaker

630 A
extensible
switch

Key to product references


Ringmaster is available as standard panel types, allowing easy
selection and specification. The product references are made up as
follows:
R
C
S
N
E
MU

Ring main unit


Circuit breaker
Switch
Non-Extensible

2
6
16
21

200 A
600 A
16 kA
21 kA

Extensible
Metering unit

Example: CN2-T1/16 = circuit breaker, non extensible, 200 A, 16 kA fault rating.

The Ringmaster catalogue allows easy selection and specification,


based on a broad range of worldwide applications.
Included in this publication is:
b panel type specifications
b details of optional accessories
b schematic diagrams
b Installation drawings.

Accessories
Accessories for the Ringmaster range are supplied either fitted or
loose, where stated enabling simple panel configuration on site.
Details of accessories are contained within the panel type pages.

General arrangement drawings


General arrangement drawings are given for each panel type.
This allows you to quickly size up switchrooms and calculate
external connections at the pre-order stage.

Need more information?


If your requirements are not listed, please contact your local
Schneider Electric representative, or contact us on:
Tel:
+44(0) 113 290 3500
Email: MVswitchgearGB@schneider.co.uk

Electronic catalogue requests


Electronic copies of this selection guide are available free of charge
upon request. For this, and other MV literature, please email your
full contact details to Email:
MVswitchgearGB@schneider.co.uk
8

AMTED399086EN.indd

Ringmaster range
Section 1

Contents

Ring main units


Non-extensible ring main unit 200A
RN2c-T1, RN2c-T2, RN2c-T3, RN2c-T4, RN2c-T5
Non-extensible ring main unit 630A
RN6c-T1
Extensible ring main unit 200A
RE2c-T1, RE2c-T2, RE2c-T3, RE2c-T4

10 -17
18
19 - 25

Circuit breaker, metering and switches


Non-extensible circuit breaker - 200A
CN2-T1, CN2-T6

26 - 29

Non-extensible Switch 630A


SN6-S1, SN6-S2

30 - 33

Non-extensible metering unit - 200A


MU2-M1, MU2-M2, MU2-M3

34 - 38

Extensible circuit breaker - 200A


CE2-T2, CE2-T7, CE2-T*, CE2-T12, CE2-T**,
CE2-T13, CE2-T15, CE2-T16

39 - 49

Extensible circuit breaker - 630A


CE6-T4, CE6-T*, CE6-T8, CE6-T**

50 - 55

Extensible switch - 630A


SE6-S1, SE6-S2, SE6-E1

56 - 60

Extensible bus section - 630A


SE6-B1, CE6-B3, CE6-B5

61 - 65

Remote control
Telecontrol unit
Easergy T200-E01M, Easergy T200-E04M

AMTED399086EN.indd

66 - 68

Ringmaster range
Section 1

Ring main units non-extensible


Specification

RN2c-T1
TFL

RN2c-T2
VIP 300

RN2c-T3
VIP 30

RN2c-T4
VIP 35

RN2c-T5
Glass TFL

RN6c-T1
VIP 300

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b

b
b

b
b

b
b

b
b

b
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
b
O
b
O
b

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

Environment
Indoor / outdoor
IP54
Transformer mounted
Freestanding

Ratings
Busbars 630A
Circuit breaker normal rated current 200A
Circuit breaker normal rated current 630A
Switch normal rated current 630A
12kV 16kA 3 seconds 75kV BIL
13.8kV 21kA 3 seconds 95kV BIL
Ring switch cable earth switch 16kA 3 seconds
Ring switch cable earth switch 21kA 3 seconds
Circuit breaker earth switch 3.15kA

Mechanism
Independent manual
Provision for motorised mechanism LH ring switch
Provision for motorised mechanism RH ring switch
Provision for motorised mechanism circuit breaker

Protection & control - circuit breaker


CTs dual ratio - 100/50/5A class X
CTs ratio - 200/1A class X
CTs ratio - 500/200/1A class X
CTs ratio - 800/400/1A class X
Overcurrent & earth fault CT operated trip coils - TFL
Overcurrent & earth fault CT operated trip coils - glass TFL
Overcurrent relay - VIP 30
Overcurrent & earth fault relay - VIP 35
IDMT overcurrent & earth fault relay - VIP 300
Multi voltage shunt trip coil (see accessories page 11)

b
b
b

b
b

b
b
b
b
O

b
O

b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
O

b
O

b
O

b
O

b
O

b
b

b
b
O

b
b
O

b
b
O

b
b
O

b
b
O

b
b
O

RN2c-T1/16
RN2c-T1/21
RMINST-06
Page 77
RMINST-05
Page 116
RMSCH-01
Page 85

RN2c-T2/16
RN2c-T2/21
RMINST-06
Page 77
RMINST-05
Page 116

RN2c-T3/16
RN2c-T3/21
RMINST-06
Page 77
RMINST-05
Page 116

RN2c-T4/16
RN2c-T4/21
RMINST-06
Page 77
RMINST-05
Page 116

RN2c-T5/16
RN2c-T5/21
RMINST-06
Page 77
RMINST-05
Page 116
RMSCH-01
Page 85

RN6c-T1/16
RN6c-T1/21
RMINST-06
Page 77
RMINST-05
Page 116

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Neon indication 3.3 - 13.8kV
Gas pressure indicator (-25C to +55C)
RSW aux contacts 1NO & 1NC

Test facility
Integral ring cable test facility
Integral circuit breaker test facility

Standard features
Operating handle

Cable (see available cable kit accessories)


Bottom entry up 1 x 3C 300mm2
Bottom entry up 3 x 1C 630mm2
Top entry cables (indoor only)

Order codes
12kV, 16kA, 75kV BIL, 0.35bG
13.8kV, 21kA, 95kV BIL, 0.8bG
General arrangement drawing - transformer mounted
General arrangement drawing - freestanding
Schematic diagram - TFL
Schematic diagram - VIP 30

RMSCH-02
Page 87

Schematic diagram - VIP 35


Schematic diagram - VIP 300

RMSCH-15
Page 88
RMSCH-03
Page 86

RMSCH-42
Page 89

Key: b Standard feature O Optional feature

10

AMTED399086EN.indd

Ringmaster range
Section 1

Ring main units non-extensible


Accessories

RN2c-T1
TFL

RN2c-T2
VIP 300

RN2c-T3
VIP 30

RN2c-T4
VIP 35

RN2c-T5 RN6c-T1
Glass TFL VIP 300

Kit no.

v
v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

v
v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

v
v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

v
v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

v
v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

RMR-A/F47
RMR-F325
RMR-A316
RMR-A319
RMR-A322
RMR-A320
RMR-A10
RMR-A11
RMR-A105
RMR-A12
RMR-A13
RMR-A106
RMR-A120
RMR-A321
RMR-A525
RMR-A314
RMR-A370
RMR-A315
RMR-F303
RMR-F302
RMR-F523
RMR-F522
RMR-A317
RMR-A318

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

RMR-A/F323
RMR-A20
RMR-A343
RMR-A344
RMR-A22
RMR-A342
RMR-A17
RMR-A350
RMR-A201

b
v

b
v

b
v

b
v

RMR-F345
RMR-F328

RMR-F363

RMR-F329

RMR-F364

v
v
v

v
v
v

v
v
v

b
v
v

RMR-F543
RMR-F507
RMR-F365

v
v
v
v
v
v
O
O
v
v

v
v
v
v
v
v
O
O
v
v

v
v
v
v
v
v
O
O
v
v

v
v
v
v
v
v
O
O
v
v

RMR-F581
RMR-F582
RMR-F341
RMR-F348
RMR-F340
RMR-F347
RMR-A374
RMR-A202
RMR-F339
RMR-F368

Cable kits
Circuit breaker cable box
Circuit breaker cable box with integral cable test facility
Gland plate 1 x 3C
Gland plate 3 x 1C
Small gland plate 1 x 3c
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Small brass wiping gland 1 x 3c
Tubular gland 1 x 3C
Tubular gland 3 x 1C
Small tubular gland
CES5 gland
CES5 gland plate 1 x 3C
CES5 gland adaptor
6 x ECON cable termination kit
3 x STD ECON end cap
3 x ECON cable termination kit
Top entry cables RH cable box (indoor only)
Top entry cables LH cable box (indoor only)
Rsw extension box for 2 x 3C cables (left hand)
Rsw extension box for 2 x 3C (right hand)
Angled gland plate 1 x 3C
Split gland plate 1 x 3C

b
O
O
O
O

Installation items
Transformer mounting kit
Extension trunking (to clear transformer radiators)
Set of padlocks - 11 no
Anti-vandal fixings, including tool
Foundation bolts (not required for transformer mounting)
Multicore pilot glands
Time limit fuses (set of 2 - specify rating as table page 115)
RN2c to MU2 installation kit
Ariel mounting bracket

Operational items
b
b
Operating handle
v
v
LH ring switch control auxiliary sw for motorised
mechanism provision
v
v
LH ring switch termination block for motorised
mechanism provision (not Easergy)
v
v
RH ring switch control auxiliary sw for motorised
mechanism provision
v
v
RH ring switch termination block for motorised
mechanism provision (not Easergy)
v
v
Provision for motorised mechanism circuit breaker
v
v
Motorised mechanism - specify voltage
v
v
CB Termination block for motorised
mechanism provision (not Easergy)
v
v
Shunt trip coil (20-250V DC, 110-250V AC) TLF
v
v
Shunt trip coil (20-250V DC, 110-250V AC) VIP
v
v
Ring switch cable neon indication (11-13.8kV)
v
v
Ring switch cable neon indication (3.3-7.2kV)
v
v
Circuit breaker cable neon indication (11-13.8kV)
v
v
Circuit breaker cable neon indication (3.3-7.2kV)
O
O
Phase indication device
O
O
VAP 6 test unit for VIP 300/30/35
v
v
Emergency trip push button
v
v
Gas pressure switch for remote indication only
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

AMTED399086EN.indd

11

Ringmaster range
Section 1

Ring main units non-extensible


Accessories

RN2c-T1
TFL

RN2c-T2
VIP 300

RN2c-T3
VIP 30

RN2c-T4
VIP 35

RN2c-T5 RN6c-T1
Glass TFL VIP 300

Kit no.

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

RMR-F337
RMR-F338
RMR-F335
RMR-F336

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

RMR-F310
RMR-A304
RMR-A305
RMR-A308
RMR-A309
RMR-A422
RMR-A277
RMR-A278
RMR-A279
RMR-A57

Mechanical interlocks
Circuit breaker - key free, EARTH ON
Circuit breaker - key free, MAIN OFF
Switch - key free, SWITCH OFF LH
Switch - key free, SWITCH OFF RH
N. B. specify lock symbol at time of ordering ( 3 digits max) not
available with motor mechanisms

Earth fault passage indication (choose provision kit


and an EFPI required if not using Easergy T200E)
O
Phase & earth fault provision for Easergy T200E
O
EFPI provision kit, inside cable box
O
EFPI provision kit, CT outside cable box
O
EFPI provision kit, inside cable box, top entry
O
EFPI provision kit, outside cable box, top entry
O
Bowden RR EFPI and CT
O
Bowden STD EFPI type NB
O
Bowden LV reset EFPI type NB1
O
Bowden LV reset & alarm type NB2
O
Fundamentals ER FIND EFPI and CT
N. B. above CTs are ring type for split core - please consult
Schneider Electric
Key: v Factory fitted accessory O Loose accessory, assembled on site

12

AMTED399086EN.indd

Ringmaster range
Section 1

Non-extensible ring main unit


200 A

DE60181

DE60180

RN2c-T1
Transformer protection up to 1.6MVA at 11kV
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links
Protection CTs - 100/50/5A class X
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-01
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RN2c-T1/16
RN2c-T1/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

13

Ringmaster range
Section 1

Non-extensible ring main unit


200 A

DE60185

DE60180

RN2c-T2
Transformer protection up to 3.5MVA at 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CTs - 200/1A class X
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-03
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RN2c-T2/16
RN2c-T2/21

14

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Non-extensible ring main unit


200 A

DE60182

DE60180

RN2c-T3
MV transformer protection
Protection & control - CB
Self powered overcurrent relay, VIP 30.
Protection CTs - 500/200/1A class X
b Setting range: 500/1A
v Overcurrent: 20-200A
b Setting range: 200/1A
v Overcurrent: 8-80A
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-02
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable box (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RN2c-T3/16
RN2c-T3/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

15

Ringmaster range
Section 1

Non-extensible ring main unit


200 A

DE60183

DE60180

RN2c-T4
MV transformer protection
Protection & control - CB
Self powered overcurrent and earth fault relay, VIP 35.
Protection CTs - 500/200/1A class X
CH30 core balance CT
b Setting range: 500/1A
v Overcurrent: 20-200A
v Earth fault: 25-300A
b Setting range: 200/1A
v Overcurrent: 8-80A
v Earth fault: 10-120A
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-15
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RN2c-T4/16
RN2c-T4/21

16

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Non-extensible ring main unit


200 A

DE60184

DE60180

RN2c-T5
Transformer protection up to 1.6MVA at 11kV
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links (glass fuse link)
Protection CTs - 100/50/5A class X
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-01
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee off cable box
Order information
Code
RN2c-T5/16
RN2c-T5/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

17

Ringmaster range
Section 1

Non-extensible ring main unit


200 A

DE60186

DE60180

RN6c-T1
Network sectionalising up to 12MVA 11kV
Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CTs - 800/400/1A class X
b Setting range: 800/1A ratio
v Overcurrent: 80-800A
v Earth fault: 8-640A
b Setting range: 400/1A
v Overcurrent: 40-400A
v Earth fault: 4-320A
Documents
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-42
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/630A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Circuit breaker earth switch 16/21kA
Ring cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch and circuit breaker with plug
interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch and circuit breaker test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 11
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes (indoor only)
Freestanding
Order information
Code
RN6c-T1/16
RN6c-T1/21

18

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible ring main units


Specification

RE2c-T1
TFL

RE2c-T2
VIP 300

RE2c-T3
VIP 30

RE2c-T4
VIP 35

b
b
b
b
O

b
b
b
b
O

b
b
b
b
O

b
b
b
b
O

b
b

b
b

b
b

b
b

b
b
O
b
O
b
O

b
b
O
b
O
b
O

b
b
O
b
O
b
O

b
b
O
b
O
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

Environment
Indoor / outdoor
IP54
Transformer mounted
Freestanding
Extensible (RHS)

Ratings
Busbars 630A
Circuit breaker normal rated current 200A
Circuit breaker normal rated current 630A
Switch normal rated current 630A
12kV 16kA 3 seconds 75kV BIL
13.8kV 21kA 3 seconds 95kV BIL
Ring switch cable earth switch 16kA 3 seconds
Ring switch cable earth switch 21kA 3 seconds
Circuit breaker earth switch 3.15kA
Extensible rmu busbar chamber 630A

Mechanism
Independent manual
Provision for motorised mechanism LH ring switch
Provision for motorised mechanism RH ring switch
Provision for motorised mechanism circuit breaker

Protection & control - circuit breaker


CTs dual ratio - 100/50/5A class X
CTs ratio - 200/1A class X
CTs ratio - 500/200/1A class X
CTs ratio - 800/400/1A class X
Overcurrent & earth fault CT operated trip coils - TFL
Overcurrent & earth fault CT operated trip coils - glass TFL
Overcurrent relay - VIP 30
Overcurrent & earth fault relay - VIP 35
IDMT overcurrent & earth fault relay - VIP 300
Multi voltage shunt trip coil (see accessories)

b
b

b
b
b
O

b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O

b
b
O

b
b
O

b
b
O

12kV, 16kA, 75kV BIL, 0.35bG

RE2c-T1/16

RE2c-T2/16

RE2c-T3/16

RE2c-T4/16

13.8kV, 21kA, 95kV BIL, 0.8bG


General arrangement drawing - freestanding
Schematic diagram - TFL
Schematic diagram - VIP 30
Schematic diagram - VIP 35
Schematic diagram - VIP 300
Key: b Standard feature O Optional feature

RE2c-T1/21
RMINST-22, Page 75
RMSCH-01, Page 85

RE2c-T2/21
RMINST-22, Page 75

RE2c-T3/21
RMINST-22, Page 75

RE2c-T4/21
RMINST-22, Page 75

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Neon indication 3.3 - 13.8kV
Gas pressure indicator (-25C to +55C)
RSW aux contacts 1NO & 1NC

Test facility
Integral ring cable test facility

Standard features
Operating handle

Cable (see available cable kit accessories)


Bottom entry up 1 x 3C 300mm2
Bottom entry up 3 x 1C 630mm2
Top entry cables* (indoor only) (left hand side only)

Order codes

AMTED399086EN.indd

RMSCH-02, Page 87
RMSCH-15, Page 88
RMSCH-03, Page 86

19

Ringmaster range
Section 1

Extensible ring main units


Accessories

RE2c-T1
TFL

RE2c-T2
VIP 300

RE2c-T3
VIP 30

RE2c-T4
VIP 35

Kit no.

v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
O
O

RMR-A/F47
RMR-A316
RMR-A319
RMR-A322
RMR-A320
RMR-A10
RMR-A10
RMR-A105
RMR-A12
RMR-A13
RMR-A106
RMR-A120
RMR-A321
RMR-A525
RMR-A314
RMR-A370
RMR-A315
RMR-A371
RMR-F302
RMR-A317
RMR-A318

v
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
v
O
O

RMR-A/F323
RMR-A20
RMR-A343
RMR-A344
RMR-A22
RMR-A342
RMR-A17
RMR-A350
RMR-F369
RMR-A201

b
v

b
v

RMR-F345
RMR-F328

RMR-F363

RMR-F329

RMR-F364

v
v
v
v
v
v
v
v
v
v
v

v
v
v
v
v
v
v
v
v
v
v

RMR-F543
RMR-F507
RMR-F581
RMR-F582
RMR-F341
RMR-F348
RMR-F340
RMR-F347
RMR-A202
RMR-F339
RMR-F368

Cable kits
Extensible ring main units
Gland plate 1 x 3C
Gland plate 3 x 1C
Small gland plate 1 x 3C
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Small brass wiping gland 1 x 3C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
Small tubular gland 1 x 3C
CES5 gland
CES5 gland plate 1 x 3C
CES5 gland plate adaptor
6 x ECON cable termination kit
3 x STD ECON end cap
3 x ECON cable termination kit
3 x ECON end cap capacitors
Top entry cables LH cable box (indoor only)
Angled gland plate 1 x 3C
Split gland plate 1 x 3C

Installation items
Transformer mounting kit
Extension trunking (to clear radiators)
Set of padlocks - 11 no
Anti-vandal fixings, including tool
Foundation bolts (not required for transformer mounting)
Multicore pilot glands
Time limit fuses (set of 2 - specify rating as table page 115)
RE2c to MU2 installation kit
Extensible busbar chamber 630A
Ariel mounting bracket

Operational items
b
b
Operating handle
v
v
LH ring switch control auxiliary sw for motorised mechanism
provision
v
v
LH ring switch termination block for motorised mechanism
provision (not Easergy)
v
v
RH ring switch control auxiliary sw for motorised mechanism
provision
v
v
RH ring switch termination block for motorised mechanism
provision (not Easergy)
v
v
Provision for motorised mechanism circuit breaker
v
v
Motorised mechanism - specify voltage
v
v
Shunt trip coil (20-250V DC, 110-250V AC) TLF
v
v
Shunt trip coil (20-250V DC, 110-250V AC) VIP
v
v
Ring switch cable neon indication (11-13.8kV)
v
v
Ring switch cable neon indication (3.3-7.2kV)
v
v
Circuit breaker neon indication (11-13.8kV)
v
v
Circuit breaker neon indication (3.3-7.2kV)
v
v
VAP 6 test unit for VIP 300/30/35
v
v
Emergency trip push button
v
v
Gas pressure switch for remote indication only
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

20

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible ring main units


Accessories

RE2c-T1
TFL

RE2c-T2
VIP 300

RE2c-T3
VIP 30

RE2c-T4
VIP 35

Kit no.

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

RMR-F337
RMR-F338
RMR-F335
RMR-F336

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

RMR-F310
RMR-A304
RMR-A305
RMR-A308
RMR-A309
RMR-A422
RMR-A277
RMR-A278
RMR-A279
RMR-A57

Mechanical interlocks
Circuit breaker - key free, earth on
Circuit breaker - key free, main off
Switch - key free, switch off LH
Switch - key free, switch off RH
N. B. specify lock symbol at time of ordering (3 digits max) not
available with motor mechanisms

Earth fault passage indication (choose provision kit


and an EFPI required if not using Easergy T200E)
O
Phase & earth fault provision for Easergy T200E
O
EFPI provision kit, inside cable box
O
EFPI provision kit, CT outside cable box
O
EFPI provision kit, inside cable box, top entry
O
EFPI provision kit, outside cable box, top entry
O
Bowden RR EFPI and CT
O
Bowden STD EFPI type NB
O
Bowden LV reset EFPI type NB1
O
Bowden LV reset & alarm type NB
O
Fundamentals ER FIND EFPI and CT
N. B. above CTs are ring type for split core - please consult
Schneider Electric
Key: v Factory fitted accessory O Loose accessory, assembled on site

AMTED399086EN.indd

21

DE60187

DE60211

Ringmaster range
Section 1

Extensible ring main unit 200 A


RE2c-T1

Multiple transformer feeders or network switching points


Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links.
Protection CTs - 100/50/5A class X
Transformer ratings
See table - page 119
Documents
Freestanding installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-01
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 20
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Integral circuit breaker test facility
Inverted cable boxes LH, CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RE2c-T1/16
RE2c-T1/21

22

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

DE60188

DE60211

Ringmaster range
Section 1

Extensible ring main unit 200 A


RE2c-T2

Multiple transformer feeders or network switching points


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS 142.
Protection CTs - 200/1A class X
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A
Transformer ratings
See table - page 119
Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-03
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 20
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable box LH CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RE2c-T2/16
RE2c-T2/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

23

DE60189

DE60211

Ringmaster range
Section 1

Extensible ring main unit 200 A


RE2c-T3

MV transformer protection
Protection & control - CB
Self powered overcurrent relay, VIP 30.
Protection CTs - 500/200/1A class X
b Setting range: 500/1A
v Overcurrent: 20-200A
b Setting range: 200/1A
v Overcurrent: 8-80A
Transformer ratings
See table - page 119
Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-02
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table, page 20
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil 20V DC - 250V AC
Neon indication
Inverted cable boxes LH, CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RE2c-T3/16
RE2c-T3/21

24

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

DE60190

DE60211

Ringmaster range
Section 1

Extensible ring main unit 200 A


RE2c-T4

MV transformer protection
Protection & control - CB
Protection & control - CB
Self powered overcurrent and earth fault relay, VIP 35.
Protection CTs - 500/200/1A class with CH30 core balance CT
b Setting range: 500/1A
v Overcurrent: 20-200A
v Earth fault 25-300A
b Setting range: 200/1A
v Overcurrent: 8-80A
v Earth fault 10-120A
Transformer ratings
See table - page 119
Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-15
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A/200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21kA 3s
Transformer earth switch, 3.15kA 3s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
Earth position selected 1NO
Earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300mm2
Bottom entry up to 3 x 1C 630mm2
Accessories - see table page 20
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil
Neon indication
Inverted cable boxes LH, CB (indoor only)
Transformer mounting
Freestanding tee-off cable box
Order information
Code
RE2c-T4/16
RE2c-T4/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

25

Ringmaster range
Section 1

Non-extensible circuit breakers


200 A
Specification
CN2-T1

CN2-T6

b
b

b
b

b
b
O
b
O
b

b
b
O
b
O
b

Environment
Indoor / outdoor
IP54

Ratings
Normal rated current 200A
12kV 16kA 3 seconds 75kV BIL
13.8kV 21kA 3 seconds 95kV BIL
Cable earth switch 16kA 3 seconds
Cable earth switch 21kA 3 seconds
Transformer earth switch 3.15kA 3 seconds

Mechanism
Independent manual

Protection & control - circuit breaker


CTs dual ratio - 100/50/5A class X
CTs ratio - 200/1A class X
Overcurrent & earth fault CT operated trip coils
Time fuse Link
IDMT overcurrent & earth fault relay - VIP 300
20V-250shunt trip coil
Circuit breaker auxiliary switch 1NO 2NC

b
b
b
O
b
b
b

b
b

b
b
O
b
b

b
b
O
b
b

b
b

b
b

b
b

b
b

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Neon indication (6.6 - 13.8kV)
Auxiliary switch contacts 1NO 2NC
Gas pressure indicator

Test facility
Integral cable test facility

Standard features
Operating handle
Transformer earth switch 3.15kA 3 seconds

Cable (see available cable kit accessories)


Bottom entry up 300mm2 1 x 3c
Bottom entry up 630mm2 3 x 1c
Key: b Standard feature O Optional feature

26

AMTED399086EN.indd

Ringmaster range
Section 1

Non-extensible circuit breakers


200 A
Accessories
CN2-T1

CN2-T6

Kit no.

v
O
O
O
O
O
O
O
O
O

v
O
O
O
O
O
O
O
O
O

RMR-F47
RMR-A48
RMR-A49
RMR-A50 Blank
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132

O
O
O
O

O
O
O
O
O

RMR-A18/6
RMR-A19
RMR-A22
RMR-A16
RMR-A17

b
v
O
O
O

b
v
O
O

RMR-A23
RMR-F108
RMR-A24
RMR-A81
RMR-A202

v
v
v

v
v
v

RMR-F85
RMR-F86
RMR-F110

Cable kits
Tee-off cable box
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C

Installation items
Set of padlocks - 6 no
Anti-vandal fixings, including tool
Foundation bolts (not required for transformer mounting)
Multicore pilot glands
Time limit fuses (set of 2 - specify rating as table page 115)

Operational items
Operating handle
Neon indication (6.6-13.8kV)
Neon lamp test unit (including lamp)
Neon lamp
VAP 6 test unit for VIP 300

Mechanical interlocks
Key free, earth on
Key free, unit off
Transformer earth switch, key free, earth on
N. B. specify lock symbol at time of ordering (3 digits max) not
available with motor mechanisms

Order codes
12kV, 16kA, 75kV BIL, 0.35bG
CN2-T1/16
13.8kV, 21kA, 95kV BIL, 0.8bG
CN2-T1/21
General arrangement drawing - transformer mounted
RMINST-04 Page 76
General arrangement drawing - freestanding
RMINST-09 Page 117
Schematic diagram
RMSCH-26 Page 106
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

AMTED399086EN.indd

CN2-T6/16
CN2-T6/21
RMINST-04 Page 76
RMINST-09 Page 117
RMSCH-11 Page 96

27

Ringmaster range
Section 1

Non-extensible circuit breaker


200 A
CN2-T1

DE60250

Transformer protection up to 3.5MVA


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CTs - 200/1A class X
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2A-160A
Shunt trip coil, 20V DC-250V AC
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: RMSCH-26
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Tee-off earth switch, 3.15kA 3s
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 2 NC
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Tee-off cable box
Glands and plates
Interlocks
See page 27 for details
Order information
Code
CN2-T1/16
CN2-T1/21

28

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Non-extensible circuit breaker


200 A
CN2-T6

DE60192

Transformer protection up to 1.5MVA


Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links.
Protection CTs - 100/50/5A class X
Shunt trip coil, 20V DC-250V AC
Transformer ratings
See table - page 119
Documents
Transformer mounted installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: RMSCH-11
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Transformer earth switch, 3.15kA 3s
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 2 NC
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Tee-off cable box
Glands and plates
Interlocks
See page 27 for details
Order information
Code
CN2-T6/16
CN2-T6/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

29

Ringmaster range
Section 1

Non-extensible switch 630 A


Specification

SN6-S1

SN6-S2

b
b

b
b

b
b
b
b

b
b
b
b

b
b
O

b
b
O

b
b
O
b
O
O

b
b

b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Normal rated current 630A
13.8kV 21kA 3 seconds 95kV BIL
Cable earth switch 21kA 3 seconds
Transformer earth switch 3.15kA 3 seconds

Mechanism
Independent manual
Provision for actuator 24V DC
Actuator 24V DC

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Neon indication (6.6 - 13.8kV)
Auxiliary switch contacts 1NO 2NC
Phase and earth fault detection CTs for Easergy 200E
Provision for EFPI

Test facility
Integral cable test facility

Standard features
Operating handle
Transformer earth switch 3.15kA 3 seconds

Cable (see available cable kit accessories)


Bottom entry up 300mm2 1 x 3c
Bottom entry up 630mm2 3 x 1c
Key: b Standard feature O Optional feature

30

AMTED399086EN.indd

Ringmaster range
Section 1

Non-extensible switch 630 A


Accessories

SN6-S1

SN6-S2

Kit no.

v
O
O
O
O
O
O
O
O
O

v
O
O
O
O
O
O
O
O
O

RMR-F47
RMR-A48
RMR-A49
RMR-A50
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132

O
O
O
O

O
O
O
O

RMR-A18/6
RMR-A19
RMR-A22
RMR-A16

b
v

b
v

O
O

O
O
v

RMR-A23
RMR-F108
RMR-A24
RMR-A81
RMR-F67

RMR-F85
RMR-F86
RMR-F110

Cable kits
Tee-off cable box
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C

Installation items
Set of padlocks - 6 no
Anti-vandal fixings, including tool
Foundation bolts (not required for transformer mounting)
Multicore pilot glands

Operational items
Operating handle
Neon indication (6.6-13.8kV)
Neon lamp test unit (including lamp)
Neon lamp
Actuator 24V DC

Mechanical interlocks
Key free, earth on
Key free, unit off
Transformer earth switch, key free, earth on
N. B. specify lock symbol at time of ordering (3 digits max) not
available with motor mechanisms

v
v
v

Order codes
13.8kV, 21kA, 95kVBIL, 0.8bG
SN6-S1/21
General arrangement drawing - transformer mounted
RMINST-04 Page 76
General arrangement drawing - freestanding
RMINST-09 Page 117
Schematic diagram
N/A
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

AMTED399086EN.indd

SN6-S2/21
RMINST-04 Page 76
RMINST-09 Page 117
RMSCH-28 Page 107

31

Ringmaster range
Section 1

Non-extensible switch 630 A


SN6-S1

DE60193

Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 95kV
Operating mechanism
Independent manual
Standard features
Transformer earth switch, 3.15kA 3s
Cable earth switch, 21kA 3s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Tee-off cable box
Neon indication
Glands and plates
Interlocks
See page 31 for details
Order information
Code
SN6-S1/21

32

Rating
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Non-extensible switch 630 A


SN6-S2

DE60194

Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: RMSCH-28
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 95kV
Operating mechanism
Independent manual
Provision for actuator, 24V DC
Standard features
Transformer earth switch, 3.15kA 3s
Cable earth switch, 21kA 3s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Auxiliary contacts 1NO 2NC
Earth selected auxiliary contact 1NO
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Tee-off cable box
Actuator, 24V DC
Neon indication
Glands and plates
See page 31 for details
Order information
Code
SN6-S2/21

AMTED399086EN.indd

Rating
21kA, 13.8kV, 95kV BIL

33

Ringmaster range
Section 1

Non-extensible metering unit


200 A
Specification
MU2-M1

MU2-M2

MU2-M3

b
b

b
b

b
b

b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Normal rated current 200A
12kV 16kA 1 second 75kV BIL

Metering*
CTs -50/25/5A 0.5s 7.5VA
CTs -100/50/5A 0.5s 10VA
CTs -200/100/5A 0.5s 10VA
VTs -11kV/110V 0.5 50VA
*CTs - 2 phases (R & B), VTs phase to phase. 6.6kV VTs are
available - contact Schneider Electric

b
b
b

b
b

O
O

O
O

O
O

Cable (see available cable kit accessories)


Bottom entry up 300mm2 1 x 3c
Bottom entry up 630mm2 3 x 1c
Key: b Standard feature O Optional feature

34

AMTED399086EN.indd

Ringmaster range
Section 1

Non-extensible metering unit


200 A
Accessories
MU2-M1

MU2-M2

MU2-M3

Kit no.

Cable kits
Tee-off cable box
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMU)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

RMR-F47
RMR-A48
RMR-A49
RMR-A51 Blank
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132

O
O
O
O
O

O
O
O
O
O

O
O
O
O
O

RMR-A18/6
RMR-A22
RMR-A16
RMR-A350
RMR-A90

MU2-M2/16
RMINST-07/08
Page 78 - 79
RMSCH-14 Page 97

MU2-M3/16
RMINST-07/08
Page 78 - 79
RMSCH-14 Page 97

Installation items
Set of padlocks - XX no
Foundation bolts (not required for transformer mounting)
Multicore pilot glands
RMU - MU2 installation kit
Freestanding installation kit

Order codes
12kV, 16kA, 75kV BIL, 0.35bG
General arrangement drawing - transformer mounted

MU2-M1/16
RMINST-07/08
Page 78 - 79
Schematic diagram
RMSCH-14 Page 97
Key: v Factory fitted accessory O Loose accessory, assembled on site

AMTED399086EN.indd

35

Ringmaster range
Section 1

Non-extensible metering unit


200 A
MU2-M1

DE60210

Non-extensible metering unit


Protection & control - CB
N/A
Metering transformers
b Metering CTs R & B phases
v 50/25/5A
v 7.5VA class 0.5s
b Metering VT ph - ph
v 11kV/110V 50VA
v class 0.5
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16kA 1s
Normal current rating 200A
Normal rated voltage 12kV
Normal rated BIL 75kV
Standard features
Direct coupling between RMU and transformer (optional freestanding cable
connection)
Cable connection
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Cable box
Glands and plates
Installation kits
See page 35 for details
Order information
Code
MU2-M1/16

36

Rating
16kA, 12kV, 75kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Non-extensible metering unit


200 A
MU2-M2

DE60210

Non-extensible metering unit


Protection & control - CB
N/A
Metering transformers
b Metering CTs R & B phases
v 100/50/5A
v 10VA class 0.5s
b Metering VT ph - ph
v 11kV/110V 50VA
v class 0.5
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16kA 1s
Normal current rating 200A
Normal rated voltage 12kV
Normal rated BIL 75kV
Standard features
Direct coupling between RMU and transformer (optional freestanding cable
connection)
Cable connection
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Cable box
Glands and plates
Installation kits
See page 35 for details
Order information
Code
MU2-M2/16

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL

37

Ringmaster range
Section 1

Non-extensible metering unit


200 A
MU2-M3

DE60210

Non-extensible metering unit


Protection & control - CB
N/A
Metering transformers
b Metering CTs R & B phases
v 200/100/5A
v 10VA class 0.5s
b Metering VT ph - ph
v 11kV/110V 50VA
v class 0.5
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16kA 1s
Normal current rating 200A
Normal rated voltage 12kV
Normal rated BIL 75kV
Standard features
Direct coupling between RMU and transformer
(optional freestanding cable connection)
Cable connection
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Cable box
Glands and plates
Installation kits
See page 35 for details
Order information
Code
MU2-M3/16

38

Rating
16kA, 12kV, 75kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible circuit breakers


200 A
Specification
CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2T2
T3
T7
T11 T12 T13 T14 T15 T16 T19 T20 T21

Environment
Indoor / outdoor
IP54

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

b
b

b
b

b
b

b
b

O
b

O
b

O
b

O
b

b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b

Ratings
Busbars 630A
Circuit breaker normal rated current 200A
12kV 16kA 3 seconds 75kV BIL
13.8kV 21kA 3 seconds 95kV BIL
Cable earth switch 16kA 3 seconds
Cable earth switch 21kA 3 seconds

Mechanism
Independent manual
Provision for actuator 24V DC
Actuator 24V DC
Operating handle

Protection system
CTs dual ratio - 500/200/1A class x
Overcurrent relay - VIP 30
CTs dual ratio - 100/50/5A class X
CT ratio - 200/1A class X
Overcurrent & earth fault CT operated trip coils
Overcurrent & earth fault relay VIP 35
Time fuse link
IDMT overcurrent & earth fault relay - VIP 300
20V-250shunt trip coil
Auxiliary switch 1NO 2NC

b
b

b
b
b
b
b

b
b
b

O
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b

b
b

Metering
b

CTs -200/100/5A 0.5s 10VA


VTs -13.8kV/110V 0.5 10VA 13.8/110V/110V 0.5 50VA 3P 20VA
VTs -11kV/110V 0.5 50VA
VTs -6.6kV/110V 0.5 50VA
VTs phase - phase, CTs R & B
VTs phase - earth, CTs RYB

b
b
b

b
b

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Cable neon indication (6.6 - 13.8kV)
Auxiliary switch contacts 1NO 2NC
Earth selected auxiliary contacts 1NO

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

O
b

O
b

O
b

O
b

O
b
b

O
b
b

O
b
b

O
b

O
b

O
b

O
b

O
b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

Test facility
Integral cable test facility

Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Top entry cables
Key: b Standard feature O Optional feature

AMTED399086EN.indd

39

Extensible circuit breakers


200 A

Ringmaster range
Section 1

Accessories
CE2T2

CE2T3

CE2T7

CE2T11

CE2T12

CE2T13

CE2T14

CE2T15

CE2T16

CE2T19

CE2T20

CE2T21

Kit no.

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

RMR-A48
RMR-A49
RMR-A50
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132
RMR-F93

RMR-F94

O
O
O
b

O
O
b

O
O
b

O
O
O
b

O
O
O
b

O
O
O
b

RMR-A14
RMR-A78
RMR-A15
RMR-A18/6
RMR-A22

Cable kits
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C
Top entry cables standard
panels
Top entry cables MU6 only

Installation items
3 phase busbars 630A
O
3 phase busbars 630A
Busbar end kit
O
Set of padlocks - 6 no
O
Foundation bolts (not required b
for transformer mounting)
Multicore pilot glands
O
Time limit fuses (set of 2 - specify
rating as table page 115)

O
O
O
O
b

O
O
b

O
O
O
b

O
O
b

O
O
O
b

O
O

RMR-A16
RMR-A17

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

RMR-A23
RMR-F108

RMR-A24

O
O

O
O

O
O

O
O
v
v

O
O
v
v

O
O
v
v

O
O

O
O

O
O

O
O

RMR-A81
RMR-A202
RMR-F67
RMR-F391

v
v

v
v

RMR-F85
RMR-F86

Operational items
Operating handle
Cable neon indication
(6.6 - 13.8kV)
Neon lamp test unit
(including lamp)
Neon lamp
VAP 6 test unit for VIP 300
Actuator 24V DC
Polarity conversion kit**

Mechanical interlocks
v
v
v
v
Key free, EARTH ON
v
v
v
v
Key free, MAIN OFF
N. B. specify lock symbol at time
of ordering (3 digits max)
not available with motor
mechanisms
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
**Only required when unit is used with RE2c ring main units and automation.

40

AMTED399086EN.indd

Extensible circuit breakers


200 A

Ringmaster range
Section 1

Accessories
CE2T2

CE2T3

CE2T7

CE2T11

CE2T12

CE2T13

CE2T14

CE2T15

CE2T16

CE2T19

CE2T20

CE2T21

Kit no.

RMR-F30

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

RMR-A277
RMR-A278
RMR-A279

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

RMR-A56
RMR-A57

RMR-A80

CE2T2/16
CE2T2/21

CE2T3/16
CE2T3/21

CE2T7/16
CE2T7/21

CE2T11/16
CE2T11/21

CE2T12/16
CE2T12/21

CE2T13/16
CE2T13/21

CE2T14/16
CE2T14/21

CE2T15/16
CE2T15/21

CE2T16/16
CE2T16/21

N/A

CE2T20/16
N/A

N/A

Earth fault passage


indication (choose
provision kit and an EFPI
required if not using
Easergy 200E)
EFPI provision kit, inside
cable box
Bowden STD EFPI type NB
Bowden LV reset EFPI type NB1
Bowden LV reset & alarm
type NB2
Bowden RR EFPI and CT
Fundamentals ER FIND
EFPI and CT

Ancillary items
Tool box

Order code
12kV, 16kA, 75kV BIL, 0.35bG
13.8kV, 21kA, 95kV BIL, 0.8bG

CE2T19/21

CE2T21/21

General arrangement drawing

RMINST-03 RMINST-02 RMINST-03 RMINST-02 RMINST-03 RMINST-02 RMINST-02 RMINST-03 RMINST-03 RMINST-02 RMINST-02 RMINST-02
Page 74
Page 73
Page 74
Page 73
Page 74
Page 73
Page 73
Page 74
Page 74
Page 73
Page 73
Page 73

Schematic drawing

RMSCH-07 RMSCH-09 RMSCH-06 RMSCH-09 RMSCH-19 RMSCH-20 RMSCH-20 RMSCH-07 RMSCH-07 RMSCH-35 RMSCH-35 RMSCH-36
Page 92
Page 94
Page 91
Page 94
Page 100
Page 101
Page 101
Page 92
Page 92
Page 109
Page 109
Page 110

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
**Only required when unit is used with RE2c ring main units and automation.

AMTED399086EN.indd

41

Ringmaster range
Section 1

Extensible circuit breaker 200 A


CE2-T2

DE60251

Feeder protection up to 3.5MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-07
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order information
Code
CE2-T2/16
CE2-T2/21

42

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible circuit breaker 200 A


CE2-T7

DE60196

Transformer protection up to 1.5MVA at 11kV


Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision
for time fuse links.
Protection CTs - 100/50/5A class X
Shunt trip coil, 20V DC-250V AC
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-06
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order information
Code
CE2-T7/16
CE2-T7/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

43

Ringmaster range
Section 1

Extensible circuit breaker 200 A


CE2-T*

DE60252

Feeder protection up to 3.5MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A

(Select VT rating and switchgear rating from table below).

Metering transformers
b Metering CTs R & B phases
v 200/100/5A
v 10VA class 0.5s
b Metering VT
v see below
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Anti-reflex operating handle
Standard features
Cable earth switch, 16/21kA 3s
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order code
16kA, 12kV, 75kV BIL
CE2-T3/16
CE2-T11/16
N/A
21kA, 13.8kV, 95kV BIL
CE2-T3/21
CE2-T11/21
CE2-T19/21
b
b
Metering VT information:
Phase to phase
b
Phase to earth
b
6.6kV/110V
b
11kV/110V*
b
13.8kV/110V
General arrangement drawing RMINST-02
RMINST-02
RMINST-02
Page 73
Page 73
Page 73
Schematic diagram
RMSCH-09
RMSCH-09
RMSCH-35
Page 94
Page 94
Page 109
*Please consult Schneider Electric when ordering units with 95kV BIL voltage
Tel: +44(0)113 290 3500

44

CE2-T20/16
N/A

b
b
RMINST-02
Page 73
RMSCH-35
Page 109

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible circuit breaker 200 A


CE2-T12

DE60253

Feeder protection up to 3.5MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-19
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contact1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Actuator, 24V DC
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order information
Code
CE2-T12/16
CE2-T12/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

45

Ringmaster range
Section 1

Extensible circuit breaker 200 A


CE2-T**

DE60254

Feeder protection up to 3.5MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A

(Select VT rating and switchgear rating from table below).

Metering transformers
b Metering CTs
v 200/100/5A
v 10VA class 0.5s
b Metering VT
v see below
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Actuator, 24V DC
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order code
16kA, 12kV, 75kV BIL
CE2-T14/16
N/A
21kA, 13.8kV, 95kV BIL
CE2-T14/21
CE2-T21/21
Metering VT information:
b
Phase to phase
b
Phase to earth
b
6.6kV/110V
11kV/110V*
b
13.8kV/110V
General arrangement drawing RMINST-02
RMINST-02
Page 73
Page 73
Schematic diagram
RMSCH-20
RMSCH-36
Page 101
Page 110
*Please consult Schneider Electric when ordering units with 95kV BIL voltage
Tel: +44(0)113 290 3500

46

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible circuit breaker 200 A


CE2-T13

DE60254

Feeder protection up to 3.5MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 20-200A
v Earth fault: 2-160A
Metering transformers
b Metering CTs
v 200/100/5A
v 10VA class 0.5s
b Metering VT ph - ph
v 11kV/110V 50VA
v class 0.5
Documents
Installation drawing ref: RMINST-02
Schematic drawing ref: RMSCH-20
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order information
Code
CE2-T13/16
CE2-T13/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

47

Ringmaster range
Section 1

Extensible circuit breaker 200 A


CE2-T15

DE60251

Feeder protection up to 2.5MVA at 11kV


Protection & control - CB
Self powered overcurrent relay, VIP 30.
Protection CTs - 500/200/1A class X
b Setting range: 500/1A
v Overcurrent: 20-200A
b Setting range: 200/1A
v Overcurrent: 8-80A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-12
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order information
Code
CE2-T15/16
CE2-T15/21

48

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible circuit breaker 200 A


CE2-T16

DE60255

Feeder protection up to 2.5MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 35.
Protection CTs - 500/200/1A class X
CH30 core balance CT
b Setting range: 500/1A
v Overcurrent: 20-200A
v Earth fault: 25-300A
b Setting range: 200/1A
v Overcurrent: 8-80A
v Earth fault: 10-120A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-13
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 200A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 40 for details
Order information
Code
CE2-T16/16
CE2-T16/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

49

Ringmaster range
Section 1

Extensible circuit breakers


630 A
Specification
CE6T4

CE6T5

CE6T6

CE6T8

CE6T9

CE6T10

CE6T22

CE6T23

CE6T24

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

b
b

b
b

b
b

b
b

O
b

O
b

O
b

O
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Busbars 630A
Circuit breaker normal rated current 630A
12kV 16kA 3 seconds 75kV BIL
13.8kV 21kA 3 seconds 95kV BIL
Cable earth switch 16kA 3 seconds
Cable earth switch 21kA 3 seconds

Mechanism
Independent manual
Provision for actuator 24V DC
Actuator 24V DC
Operating handle

Protection system
CT ratio - 800/1A class X
IDMT overcurrent & earth fault relay - VIP 300
20V-250V shunt trip coil
Auxiliary switch 1NO 2NC

b
b

Metering
CTs - 400/200/5A 0.5s 10VA
VTs - 13.8kV/110V/110V/ 0.5 50VA 3P 20VA
VTs - 11V/110V 0.5 50VA
VTs - 6.6kV/110V 0.5 50VA
VTs - phase - phase, CTs R & B
VTs phase - earth, CTs RYB

b
b

b
b
b

b
b
b
b

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Cable neon indication (6.6 - 13.8kV)
Auxiliary switch contacts 1NO 2NC
Indication CT 600/5A 5VA CLS 1 Yph
Ammeter 0-600A
Earth selected auxiliary contacts 1NO
Gas pressure indicator

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

O
b
b
b

O
b
b
b

O
b
b
b

O
b
b
b

O
b
b
b
b
b

O
b
b
b

O
b
b
b
b
b

O
b
b
b

O
b
b
b
b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

Test facility
Integral cable test facility

Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Top entry cables
Key: b Standard feature O Optional feature

50

AMTED399086EN.indd

Extensible circuit breakers


630 A

Ringmaster range
Section 1

Accessories
CE6-T4

CE6-T5

CE6-T6

CE6-T8

CE6-T9

CE6-T10 CE6-T22 CE6-T23 CE6-T24 Kit no.

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

RMR-A48
RMR-A49
RMR-A50
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132
RMR-F93
RMR-F94

O
O
b

O
O
O
b

O
O
O
O
b

O
O
b

O
O
O
b

O
O
O
b

O
O
O
b

O
O
O
b

O
O
O
b

RMR-A14
RMR-A78
RMR-A15
RMR-A18/6
RMR-A22

RMR-A16

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

O
O
O

O
O
O

O
O

O
O
O
v
v

O
O
O
v
v

O
O
O
v
v

O
O
O

O
O
O
v
v

O
O
O

RMR-A23
RMR-A108
RMR-A24
RMR-A81
RMR-A202
RMR-F67
RMR-F391

v
Key free, EARTH ON
v
Key free, MAIN OFF
N. B. specify lock symbol at time of ordering
( 3 digits max) not available with motor
mechanisms

v
v

v
v

v
v

RMR-F85
RMR-F86

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

RMR-F30
RMR-A277
RMR-A278
RMR-A279
RMR-A56
RMR-A57

RMR-A80

CE6T4/16
CE6T4/21

CE6T5/16
CE6T5/21

CE6T6/16
CE6T6/21

CE6T8/16
CE6T8/21

CE6T9/16
CE6T9/21

CE6T10/16
CE6T10/21

N/A

N/A

CE6T22/21

CE6T12321

CE6T24/16
N/A

RMINST-03
Page 74
RMSCH-08
Page 93

RMINST-02
Page 73
RMSCH-10
Page 95

RMINST-02
Page 73
RMSCH-10
Page 95

RMINST-03
Page 74
RMSCH-23
Page 104

RMINST-02
Page 73
RMSCH-24
Page 105

RMINST-02
Page 73
RMSCH-24
Page 105

RMINST-02
Page 73
RMSCH-37
Page 111

RMINST-02
Page 73
RMSCH-38
Page 112

Cable kits
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C
Top entry cables standard panels
Top entry cables MU6 only

Installation items
3 phase busbars 630A
3 phase busbars 630A
Busbar end kit
Set of padlocks - 6 no
Foundation bolts (not required for
transformer mounting)
Multicore pilot glands

Operational items
Operating handle
Cable neon indication (6.6 - 13.8kV)
Neon lamp test unit (including lamp)
Neon lamp
VAP 6 test unit for VIP 300
Actuator 24V DC
Polarity conversion kit**

Mechanical interlocks
v
v

Earth fault passage indication


(choose provision kit and an EFPI
required if not using Easergy T200E)
EFPI provision kit, inside cable box
Bowden STD EFPI type NB
Bowden LV reset EFPI type NB1
Bowden LV reset & alarm type NB2
Bowden RR EFPI and CT
Fundamentals ER FIND EFPI and CT

Ancillary items
Tool box

Order code
12kV, 16kA, 75kV BIL, 0.35bG
13.8kV, 21kA, 95kV BIL, 0.8bG
General arrangement drawing
Schematic drawing

RMINST-02
Page 73
RMSCH-37
Page 111

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
**Only required when unit is used with RE2c ring main units and automation.

AMTED399086EN.indd

51

Ringmaster range
Section 1

Extensible circuit breaker 630 A


CE6-T4

DE60256

Feeder protection up to 12MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-08
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600A
Indication CT Y ph - 600/5A class 1.0, 5VA
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 51 for details
Order information
Code
CE6-T4/16
CE6-T4/21

52

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible circuit breaker 630 A


CE6-T*

DE60197

Feeder protection up to 12MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A

(Select VT rating and switchgear rating from table below).

Metering transformers
b Metering CTs
v 400/200/5A
v 10VA class 0.5s
b Metering VT
v see below
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600A
Indication CT Y ph - 600/5A class 1.0, 5VA
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Actuator, 24V DC
Neon indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 51 for details
Order code
16kA, 12kV, 75kV BIL
CE6-T5/16
CE6-T6/16
N/A
21kA, 13.8kV, 95kV BIL
CE6-T5/21
CE6-T6/21
CE6-T22/21
b
b
Metering VT information:
Phase to phase
b
Phase to earth
b
6.6kV/110V
b
11kV/110V*
b
13.8kV/110V
General arrangement drawing RMINST-02
RMINST-02
RMINST-02
Page 73
Page 73
Page 73
Schematic diagram
RMSCH-10
RMSCH-10
RMSCH-37
Page 95
Page 95
Page 111
*Please consult Schneider Electric when ordering units with 95kV BIL voltage
Tel: +44(0)113 290 3500

AMTED399086EN.indd

CE6-T24/16
N/A

b
b
RMINST-02
Page 73
RMSCH-37
Page 111

53

Ringmaster range
Section 1

Extensible circuit breaker 630 A


CE6-T8

DE60257

Feeder protection up to 12MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-23
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contact1NO
Ammeter 0-600A
Indication CT Y ph - 600/5A class 1.0, 5VA
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Actuator, 24V DC
Neon indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 51 for details
Order information
Code
CE6-T8/16
CE6-T8/21

54

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible circuit breaker 630 A


CE6-T**

DE60199

Feeder protection up to 12MVA at 11kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A

(Select VT rating and switchgear rating from table below).

Metering transformers
b Metering CTs
v 400/200/5A
v 10VA class 0.5s
b Metering VT
v see below
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A
Normal rated voltage 12/13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contacts
Ammeter 0-600A
Indication CT Y ph- 600/5A class 1.0, 5VA
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 51 for details
Order code
16kA, 12kV, 75kV BIL
CE6-T9/16
CE6-T10/16
N/A
21kA, 13.8kV, 95kV BIL
CE6-T9/21
CE6-T10/21
CE6-T23/21
b
b
Metering VT information:
Phase to phase
b
Phase to earth
b
6.6kV/110V
b
11kV/110V*
b
13.8kV/110V
General arrangement drawing RMINST-02
RMINST-02
RMINST-02
Page 73
Page 73
Page 73
Schematic diagram
RMSCH-24
RMSCH-24
RMSCH-38
Page 105
Page 105
Page 112
*Please consult Schneider Electric when ordering units with 95kV BIL voltage
Tel: +44(0)113 290 3500

AMTED399086EN.indd

55

Ringmaster range
Section 1

Extensible switches 630 A


Specification

SE6-S1

SE6-S2

SE6-E1

b
b

b
b

b
b

b
b
b
b

b
b
b
b

b
b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Busbars 630A
Switch normal rated current 630A
13.8kV 21kA 3 seconds 95kV BIL
Cable earth switch 21kA 3 seconds

Mechanism
Independent manual
Provision for actuator 24V DC
Actuator 24V DC
Operating handle

O
b

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Cable neon indication (6.6-13.8kV)
Busbar neon indication (6.6-13.8kV)
Auxiliary switch contacts1NO 1 NC
Phase and earth fault detection CTs for Easergy T200E
EFPI provision only CT inside box
Gas pressure indicator

b
b
v
v

b
b
v
v
v

O
b

O
O
b

b
b

Test facility
Integral cable test facility

Integral test facility


b

RH/LH busbar earthing

Cable (see available cable kit accessories)


b
Bottom entry up to 300mm2 1 x 3c
b
Bottom entry up to 630mm2 3 x 1c
Top entry cables
O
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

56

b
b
O

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible switches 630 A


Accessories

SE6-S1

SE6-S2

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O
v

O
O
O
b

O
O
O
b

SE6-E1

Kit no.

Cable kits
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C
Top entry cables

RMR-A48
RMR-A49
RMR-A50
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132
RMR-F93

Installation items
3 phase busbars 630A
Set of padlocks - 6 no
Busbar end kit (1 end kit required per switchboard)
Foundation bolts (not required for transformer mounting)
Multicore pilot glands

v
O
O
b

RMR-A14
RMR-A18/6
RMR-A15
RMR-A22
RMR-A16

RMR-A23
RMR-F108
RMR-F92
RMR-A24
RMR-A81
RMR-F67
RMR-F391

RMR-F85
RMR-F86

Operational items
Operating handle
Cable neon indication (6.6-13.8kV)
Cable and busbar neon indication (6.6-13.8kV)
Neon lamp test unit (including lamp)
Neon lamp
Actuator 24V DC
Polarity conversion kit*

b
v
v

b
v
v

O
O

O
O
v
v

Mechanical interlocks
Key free, earth ON
Key free, main OFF
N. B. specify lock symbol at time of ordering ( 3 digits max) not
available with motor mechanisms

v
v

Indication
EFPI provision kit, inside cable box
Bowden STD EFPI NB
Bowden LV reset EFPI type NB1
Bowden LV reset & alarm type NB2
Bowden RR EFPI and CT
Fundamentals ER FIND EFPI and CT

O
O
O
O
O
O

O
O
O
O
O
O

RMR-F30
RMR-A277
RMR-A278
RMR-A279
RMR-A56
RMR-A57

Ancillary items
Tool box

RMR-A80

Order code
13.8kV, 21kA, 95kV BIL, 0.8bG
General arrangement drawing

SE6-S2/21
RMINST-03
Page 74
Schematic drawing
RMSCH-29
Page 108
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
**Only required when unit is used with RE2c ring main units and automation.

AMTED399086EN.indd

SE6-S1/21
RMINST-03
Page 74
N/A

SE6-E1/21
RMINST-03
Page 74
N/A

57

Ringmaster range
Section 1

Extensible switch 630 A


SE6-S1

DE60201

Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 21kA 3s
Anti-reflex operating handles
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Neon indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 57 for details
Order information
Code
SE6-S1/21

58

Rating
21kA, 13.8kV, 95 kVBIL

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible switch 630 A


SE6-S2

DE60202

Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-29
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 95kV
Operating mechanism
Independent manual
Provision for actuator, 24V DC
Standard features
Cable earth switch, 21kA 3s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact 1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300mm2 1 x 3c
Bottom entry up to 630mm2 3 x 1c
Accessories
Actuator, 24V DC
Neon indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 57 for details
Order information
Code
SE6-S2/21

AMTED399086EN.indd

Rating
21kA, 13.8kV, 95kV BIL

59

Ringmaster range
Section 1

Extensible switch 630 A


SE6-E1

DE60203

Busbar earthing switch


Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 95kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 21kA 3s
Anti-reflex operating handle
Indication
Mechanical earth/main indicator
Gas pressure indicator
Test facility
N/A
Cable
N/A
Accessories
Interlocks
Busbar kit
See page 57 for details
Order information
Code
SE6-E1/21

60

Rating
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible bus-section 630 A


Specification

SE6-B1

CE6-B3

CE6-B5

b
b

b
b

b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Busbars 630A
Circuit breaker normal rated current 630A
Switch normal rated current 630A
12kV 16kA 3 seconds 75kV BIL
13.8kV 21kA 3 seconds 95kV BIL
RH busbar earth switch 16kA 3 seconds
RH busbar earth switch 21kA 3 seconds

b
b

O
b

O
b

b
b

O
b

b
b
b
b

b
b
b
b

b
b
b

b
b
b

b
b

b
b

b
b
b

O
b
b
b
b

O
b
b
b
b

Mechanism
Independent manual
Provision for actuator 24V DC
Actuator 24V DC
Operating handle

Protection system
CT ratio - 800/1A class X
IDMT overcurrent & earth fault relay - VIP 300
20- 250 V shunt trip coil
Auxiliary switch1NO 2 NC

Metering
CTs - 400/200/5A 0.5s 10VA
VTs - 11kA/110V 0.5 50VA
VTs phase - phase, CTs R & B

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Earth selected auxiliary contact1NO
RH busbar neon indication
Auxiliary switch contacts1NO 2NC
Indication CT 600/5A 5VA CLS 1 Y phase
Ammeter 0-600A
Gas pressure indicator

Integral test facility


RH busbar earthing
LH busbar earthing ( using SE6-E1)
Key: b Standard feature O Optional feature

AMTED399086EN.indd

61

Ringmaster range
Section 1

Extensible bus-section 630 A


Accessories

SE6-B1

CE6-B3

CE6-B5

v
v

v
v

v
v

O
O
b

O
O
b

O
O
b

b
v

b
v

b
v

O
O

O
O
O

v
v

v
v

Kit no.

Installation items
3 phase busbars 630A
3 phase busbars 630A (Joggle metering)
3 phase busbars 630A double width (metering)
Set of padlocks - XX no
Busbar end kit (1 end kit required per switchboard)
Foundation bolts (not required for transformer mounting)
Multicore pilot glands

RMR-A14
RMR-A79
RMR-A78
RMR-A18/6
RMR-A15
RMR-A22
RMR-A16

Operational items
Operating handle
LH and RH busbar neon indication
Neon lamp test unit (including lamp)
Neon lamp
VAP6 test unit for VIP 300
Actuator 24V DC
Polarity conversion kit*

O
O
v
v

RMR-A23
RMR-F92
RMR-A24
RMR-A81
RMR-A202
RMR-F67
RMR-F391

Mechanical interlocks
Key free, earth ON
Key free, main OFF
N. B. specify lock symbol at time of ordering ( 3 digits max) not
available with motor mechanisms

RMR-F85
RMR-F86

Ancillary items
Tool box

RMR-A80

Order code
12kV, 16kA, 75kV BIL, 0.35bG
13.8kV, 21kA, 95kV BIL, 0.8bG
General arrangement drawing

CE6-B3/16
CE6-B3/21
RMINST-01
Page 72
Schematic drawing
RMSCH-21
Page 102
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
**Only required when unit is used with RE2c ring main units and automation.

62

N/A
SE6-B1/21
RMINST-01
Page 72
N/A

CE6-B5/16
CE6-B5/21
RMINST-01
Page 72
RMSCH-22
Page 103

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible bus-section 630 A


SE6-B1

DE60204

Bus-section disconnector
Protection & control
Non-automatic
Documents
Installation drawing ref: RMINST-01
Schematic drawing ref: N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 95kV
Operating mechanism
Independent manual
Standard features
RH busbar earth switch, 21kA 3s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral RH busbar test facility
Cable
N/A
Accessories
Neon indication
Interlocks
Busbars
See page 62 for details
Order information
Code
SE6-B1/21

AMTED399086EN.indd

Rating
21kA, 13.8kV, 95kV BIL

63

Ringmaster range
Section 1

Extensible bus-section 630 A


CE6-B3

DE60258

Bus-section circuit breaker


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A
Metering transformers
b Metering CTs
v 400/200/5A
v 10VA class 0.5s
b Metering VT ph-ph
v 11kV/110V 50VA
v class 0.5
Documents
Installation drawing ref: RMINST-01
Schematic drawing ref: RMSCH-21
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Standard features
RH busbar earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600A
Indication CT Y ph- 600/5A class 1.0 5VA
Gas pressure indicator
Test facility
Integral RH busbar test facility
Cable
N/A
Accessories
Neon indication
Interlocks
Busbars
See page 62 for details
Order information
Code
CE6-B3/16
CE6-B3/21

64

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

AMTED399086EN.indd

Ringmaster range
Section 1

Extensible bus-section 630 A


CE6-B5

DE60259

Bus-section circuit breaker


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1A class X
Shunt trip coil, 20V DC-250V AC
b Setting range:
v Overcurrent: 80-800A
v Earth fault: 8-640A
Metering transformers
b Metering CTs
v 400/200/5A
v 10VA class 0.5s
b Metering VT ph-ph
v 11kV/110V 50VA
v class 0.5
Documents
Installation drawing ref: RMINST-01
Schematic drawing ref: RMSCH-22
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630A
Short time withstand 16/21kA 3s
Normal current rating 630A
Normal rated voltage 13.8kV
Normal rated BIL 75/95kV
Operating mechanism
Independent manual
Provision for actuator, 24V DC
Standard features
RH busbar earth switch, 16/21kA 3s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contacts1NO
Ammeter 0-600A
Indication CT Y ph- 600/5A class 1.0 5VA
Gas pressure indicator
Test facility
Integral RH busbar test facility
Cable
N/A
Accessories
Actuator, 24V DC
Neon indication
Interlocks
Busbars
See page 62 for details
Order information
Code
CE6-B5/16
CE6-B5/21

AMTED399086EN.indd

Rating
16kA, 12kV, 75kV BIL
21kA, 13.8kV, 95kV BIL

65

Ringmaster range
Section 1

Telecontrol units
Easergy T200E - Specification

Easergy T200 EO1


single function

Easergy T200 EO2


2 functions

Easergy T200 EO4


4 functions

b
b

b
b

b
b

b
b

b
b

b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b

b
b
b

b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b

b
b
b

b
b
b

b
b
b
b

b
b
b
b

b
b
b
b

b
b
b
b
b
b
b

b
b
b
b
b
b
b

b
b
b
b
b
b
b

b
b
b
b
b
b
b
b

b
b
b
b
b
b
b
b

b
b
b
b
b
b
b
b

Environment
Indoor / outdoor
IP54

Communication
RS232C using Westinghouse WISP+ protocol or
RS232/RS485 - Modbus protocol

Standard features
Freestanding/wall mounted/ switchgear mounted
Removable radio bracket ( no radio supplied)

Inputs to cabinet
Switch open - per switch
Switch closed - per switch
Earth selector earth/mains - per switch
1 spare - per switch

Control output to switchgear


To switch
- Open switch
- Close switch
- Reset external FPI

Output to SCADA
- Switch open
- Switch closed
- Earth selector earth/main
- Fault passage indication - phase and/or earth fault
From cabinet
- Local/remote failure
- Mains/equipment failure
- Battery and charger alarms

Local control
Push button open/close switch
Local/remote selector
Reset/test integral FPI
Power restart

Local indication
Mains present
Battery fault
Internal supplies on
Switch status - open/closed
FPI operated
Local/remote mode selected
Equipment fault (watchdog)

Battery and charger


Power supply 230V AC
Telecomms equipment - 12V DC
Control unit - 12V DC
Power supply 230V AC
Switchgear 24V AC
3 x 7AH sealed lead acid
20 degrees C, 3 hours after loss of supply
5 c/o switch operations
Key: b Standard feature O Optional feature

66

AMTED399086EN.indd

Ringmaster range
Section 1

Telecontrol units
Easergy T200-E01M

DE60191

Telecontrol unit - single switch control


Local indication
Mains failure, battery fault, internal supplies on,
Switch status - open/closed, FPI operated, local/remote mode selected, equipment
fault (Watchdog)
Inputs to cabinet
Switch open
Switch closed
*Earth selector earth/mains
3 spare
Control outputs to switchgear
b To switch
v Open switch
v Close switch
v Reset FPI
Local control
Push button open/close switch
Local/remote selector
Reset/test integral FPI
Optional features
b Integral phase and earth fault passage indicator
b 3 phase RMS current measurement
b Wall mounted/freestanding
Documents
Installation drawing ref: RMINST-11
Schematic drawing ref: RMSCH-17
Environment
Indoor/outdoor
IP54
Communication
RS232C using Westinghouse WISP+ protocol or RS232/RS485 - Modbus protocol
Standard features
Switchgear mounted removable radio bracket ( no radio/modem supplied)
Outputs to SCADA
b Switch open
b Switch closed
b Earth selector earth/main
b Fault passage indication - phase and/or earth fault
b From cabinet
v Local/remote mode
v Mains/equipment failure
v other configurable alarms
Batteries and charger
Telecomms equipment - 12V DC
Control unit - 12V DC
Switchgear - 24V DC
3 x 7Ah sealed lead acid
Power supply
230V AC +/- 15% 50Hz
Autonomy
20C 5 hours after loss of supply
5 C/O switch operations
Deep discharge protection
Order information
T200-EO1M

AMTED399086EN.indd

67

Ringmaster range
Section 1

Telecontrol units
Easergy T200-E04M

DE60195

Telecontrol unit - up to 4 switch control


Local indication
Mains failure, battery fault, internal supplies on,
Switch status - open/closed, FPI operated, local/remote mode selected, equipment
fault (Watchdog)
Inputs to cabinet
Switch open
Switch closed
*Earth selector earth/mains
3 spare
Control outputs to switchgear
b To switch
v Open switch
v Close switch
v Reset FPI
Local control
Push button open/close switch
Local/remote selector
Reset/test integral FPI
Optional features
b Integral phase and earth fault passage indicator
b 3 phase RMS current measurement
b Wall mounted/freestanding
Documents
Installation drawing ref: RMINST-11
Schematic drawing ref: RMSCH-17
Environment
Indoor/outdoor
IP54
Dimensions
480 x 370 x 280mm
Communication
RS232C using Westinghouse WISP+ protocol or
RS232/RS485 - Modbus protocol
Standard features
Switchgear mounted removable radio bracket ( no radio/modem supplied)
Outputs to SCADA
b Switch open
b Switch closed
b Earth selector earth/main
b Fault passage indication - phase and/or earth fault
b From cabinet
v Local/remote mode
v Mains/equipment failure
v other configurable alarms
Batteries and charger
Telecomms equipment - 12V DC
Control unit - 12V DC
Switchgear - 24V DC
3 x 7Ah sealed lead acid
Power supply
230V AC +/- 15% 50Hz
Autonomy
20C 5 hours after loss of supply
5 C/O switch operations
Deep discharge protection
Order information
T200-EO4M

68

AMTED399086EN.indd

You might also like