Appendix II
Comparison of Compressive
Strength of Concrete Blocks
Prepared by PPAF & Available in
Market
Compressive Strength test results for Concrete Blocks and Results of PPAF
Concrete Mix Design
PPAF Test Results for Hollow Blocks (Compressive Strength at 10 days)
Bagh
Sample Location
Shahid Block Factory, Hardigail
near dispensary, Bagh
Jamil Block Factory, Hardigail,
Bagh
Friends Enterprise near Rafiqabad,
Bagh
Ittehad Block Factory, Nagmanpura,
near Pulmera, Bagh
Ahmadabad Block Factory near
Nagmanpura Petrol Pump Bagh
Amjad Gardezi Block Factory, near
bypass road, Hadabody, Bagh
Rawalakot
Sample Location
Farhan Block Factory, near PPAF
office, Rawalakot
Rafique Block Factory, Darak, near
Eidgah, Rawalakot
Al-Hassan
Methal
Merra,
Rawalakot
Sharif Block Factory, Darak near
Eidgah, Rawalakot
Hasrat Block Factory, near NADRA
office, Rawalakot
Mansehra
Sample Location
Kaghan road, Mansehra
Block
#
1
2
3
4
5
6
7
8
9
10
11
12
Block
#
1
2
3
4
5
6
7
8
9
10
Block
#
1
2
Size
16x 5 7/8 x 8
16x 5 7/8 x 8
15 1/4x5 7/8x8
15 1/4x5 7/8x8
15 1/4x5 7/8x8
15 1/4x5 7/8x8
15 1/4x5 7/8x8
15 1/4x5 7/8x8
14 7/8 x 5 7/8x 8
14 7/8 x 5 7/8x 8
15 3/4 x 6 x 7 3/4
15 3/4 x 6 x 7 3/4
Size
15 3/8 x 5 7/8 x 8
15 3/8 x 5 7/8 x 8
15 1/4 x5 3/4 x7 1/2
15 1/4 x5 3/4 x7 1/2
15 x 5 7/8 x 7 3/4
15 x 5 7/8 x 7 3/4
15 x 6 x 8
15 x 6 x 8
15 1/8 x 5 7/8 x 8
15 1/8 x 5 7/8 x 8
Size
16x 6 x 8
16x 6 x 8
Weight
Kg
17.36
15.48
16.18
16.00
15.42
15.16
16.84
16.16
14.59
14.42
16.08
17.14
10
days
Psi
712
396
365
318
696
435
399
290
440
337
369
448
Weight
Kg
17.34
15.88
14.40
14.70
14.22
14.33
13.90
14.04
15.02
15.04
10
days
Psi
652
422
583
563
718
619
346
493
417
441
Weight
Kg
15.00
15.80
10
days
Psi
214
471
Avg
10
days
Psi
Estd.
28
days
Psi
554
739
342
455
566
754
345
459
389
518
409
545
Avg
10
days
Psi
Estd.
28
days
Psi
537
716
573
764
669
891
420
559
429
572
Avg
10
days
Psi
Estd.
28
days
Psi
343
457
Note: None of the blocks tested have the specified strength1. Average varies from a low of 253 Psi to 669
Psi.
(28 days ASTM C 90: 1700 Psi net area unit compressive strength, average of three units to be not less
than 1900 Psi; if based on gross area then 1000 Psi.)
Sample Location
Chinar Road Mansehra
Ghandian Road Mansehra
Badara Chowl
Block
#
1
2
3
4
5
6
Size
16x 6 x 8
16x 6 x 8
12 x 5.5 x 5.5
12 x 5.5 x 5.5
12 x 5.5 x 5.5
12 x 5.5 x 5.5
Weight
Kg
20.8
21.1
11.98
12.21
14.32
14.32
10
days
Psi
565
671
269
269
250
255
Avg
10
days
Psi
Estd.
28
days
Psi
618
824
269
359
253
337
Compressive strength test results for PPAF concrete mix designs for solid blocks
(Compressive Strength at 10 days)
Avg Estd.
28
10
10
Block
Weight days days days
Psi
Psi
Mix (cement: sand: aggregate)
#
Size
Kg
Psi
1:2:4
1
12 x 8 x 6
15.00 2421
2
12 x 8 x 6
15.80 2236 2,329 3,105
1:3:6
1
12 x 8 x 6
22.40 1545
2
12 x 8 x 6
22.26 2154 1,850 2,466
1:4:8
1
12 x 8 x 6
15.00 1614
2
12 x 8 x 6
15.80 1591 1,603 2,137
1:6 (cement:river bed material)
1
12 x 8 x 6
15.00 2793
2
12 x 8 x 6
15.80 3065 2,929 3,905
1:8 (cement:river bed material)
1
12 x 8 x 6
15.00 2282
2
12 x 8 x 6
15.80 2282 2,282 3,043
1:10 (cement:river bed material)
1
12 x 8 x 6
15.00 1451
2
12 x 8 x 6
15.80 1358 1,405 1,873
1:3:6 with hole
1
12 x 8 x 6
15.00 1350
2
12 x 8 x 6
15.80 1427 1,389 1,851
1:3:6 half block
1
12 x 8 x 6
15.00 1521
2
12 x 8 x 6
15.80 1890 1,706 2,274
Note: Trials show that 1:3:6 and 1:4:8 both provide adequate strength (28 days ASTM C 90:
1700 Psi net area unit compressive strength, average of three units to be not less than 1900
Psi; if based on gross area then 1000 Psi.). Even 1:8 blocks using river bed material gave
satisfactory results. The key is to have proper mix design, water : cement ratio and adequate curing.
Appendix III
Calculation of Seismic Forces
Developed in Masonry Wall
V=
CvI
W
RT
Seismic Band
at Roof
Where
3ft
Seismic Band
at Lintel
4ft
3/4
3ft
Eq. 30-5
governs
a) Seismic Forces when earthquake is applied in the weaker direction of the wall
Base shear V is distributed statistically and following are the value at different level:
5.37 k
Lintel Level:
4.30 k
Sill Level:
2.63 k
Seismic Force
Direction
Roof Level:
Roof Level:
2.68 k
Lintel Level:
2.15 k
Sill Level:
1.32 k
b) Seismic Forces when earthquake is applied in the weaker direction of the wall
Wall resisting
Seismic
Forces
Seismic
Force
In this case, the calculated base shear is applied uniformly on the wall face.
For solid block wall; the earthquake pressure is approximated as:
Base shear, V=12.3kips
Pressure on the wall = 12.3/(15x10) x 1000/4
= 20.5 Psf
V=
CvI
W
RT
Seismic Band
at Roof
Where
3ft
Seismic Band
at Lintel
4ft
3/4
3ft
Eq. 30-5
governs
a) Seismic Forces when earthquake is applied in the weaker direction of the wall
Base shear V is distributed statistically and following are the value at different level:
4.22 k
Lintel Level:
2.70 k
Sill Level:
1.65 k
Seismic Force
Direction
Roof Level:
2.11 k
Lintel Level:
1.35 k
Sill Level:
0.83 k
b) Seismic Forces When Earthquake is Applied in the Weaker Direction of the Wall
Wall resisting
Seismic
Forces
Seismic
Force
In this case, the calculated base shear is applied uniformly on the wall face.
For solid block wall; the earthquake pressure is approximated as:
Base shear, V=8.58kips
Pressure on the wall = 8.58/(15x10) x 1000/4
= 14.3 Psf
Appendix IV
Stresses Developed in
Block Wall
Appendix V
Calculation of Soil Bearing
Capacity
Average Stress
60
60.0 x 6 x 30 x 144
30 x 30 x 2.24 x 1000
psi
0.771 Tons/sft
Average Stress
90
90 x 6 x 30 x 144
30 x 30 x 2.24 x 1000
psi
1.157 Tons/sft
30 "
30 "