You are on page 1of 7

International Journal of Advances in Engineering & Technology, Sept., 2014.

IJAET
ISSN: 22311963

INCREASING THE EFFICIENCY OF BOILER OPERATION BY


CONTROLLING DRUM LEVEL WITH BFP SCOOP OPERATION
IN THREE ELEMENT MODE
1

Aditya Sindhu, 2Aashish Bhaskar and 3Avdesh Bhardawaj


1

Department of EEE, MAIT, Rohini, Delhi, India


Senior consultant, Indiabulls Power Ltd, Amravati, Maharashtra, India
3
Department of Applied Sciences, ITM University, Sector 23 (A), Gurgaon, Haryana, India
2

ABSTRACT
In order to meet out the steam requirement, to safeguard the boiler water tubes and to safe guard the turbine
blades the boiler drum water level control plays an important role in thermal power station. The main objective
of the boilerturbine system control is to meet the load demand of electric power while maintaining the pressure
and water level in the drum within tolerances This paper demonstrates the increase in efficiency and energy
savings by using the three element mode method of drum level control and compares it to the the traditional DP
mode .Traditionally in most power stations , the DP mode of operation is used because it is believed it provides
more robust control of the throttle valve , however throttling losses do occur .This is primarily because it is a
linear system of control . The linear system of control causes more losses and hence greater power consumption.
Three element mode reduces these throttling losses by measuring the steam level , steam rate flow as well as the
water level simultaneously , thereby resulting in a lesser loss of pressure and hence lesser demand . Pressure drop
across the throttle valve can be optimized more efficiently using this method of control and the observations and
results regarding this have been discussed .The results found were very encouraging and the method can be
applied widely to all sub critical boiler systems across the power industry .

KEYWORDS- boiler, three element, FRS, control valve.

I.

INTRODUCTION

The control system for a boilerturbine unit usually needs to meet the requirement of the amount of
water in the steam drum must be maintained at a desired level to prevent overheating of the drum or
flooding of steam lines. This is critical for the safe and economic operation of a power plant. Scoop
controller PID maintains speed of Hydraulic coupled Pump operated by constant speed motor. For Drum
Level Control, Operator gives Set point for Drum Level Value. To achieve this set point value of Drum
Level, 3 or 1 - element controller will maintain the Feed Station Control Valve position. The main
purpose of scoop control is that this will reduce the throttling loss occurring due to high fluctuating DP
across control valve. The Valve operates in better controllability position. The drum level must be
controlled to the limits specified by the boiler manufacturer. If the drum level does not stay within these
limits, there may be water carryover. If the level exceeds the limits, boiler water carryover into the
super-heater or the turbine may cause damage resulting in extensive maintenance costs or outages of
either the turbine or the boiler. If the level is low, overheating of the water wall tubes may cause tube
ruptures and serious accidents, resulting in expensive repairs, downtime, and injury or death to
personnel. A rupture or a crack most commonly occurs where the tubes connect to the drum. Providing
tight water level control in a drum is mainly accomplished by utilizing one of three types of drum level
control: single-element, two-element, or three - element. The term 'single-element' is derived from
single variable: drum level influence on the feed-water valve position. While single - element drum

1402

Vol. 7, Issue 4, pp. 1402-1408

International Journal of Advances in Engineering & Technology, Sept., 2014.


IJAET
ISSN: 22311963
level control is acceptable for steady boiler load conditions; as load changes become more frequent,
more unpredictable, or severe; this type of level control cannot respond quickly enough to compensate.
The term 'three-element' is derived from three variables: steam flow, feed water flow and drum level
influence on the feed-water valve position. Wide Fast Combination of batch and continuous type
operations such that plant steam load characteristics often varies continuously and unpredictably. The
drum level must be controlled to the limits specified by the boiler manufacturer. If the drum level does
not stay within these limits, there may be water carryover. Poor level control also has an effect on drum
pressure control. Feed water going into the drum is not as hot as the water in the drum. Adding feed
water too fast will result in a cooling effect in the boiler drum reducing drum pressure and causing boiler
level shrinkage. This paper has been categorized into 4 main parts first one (background) introduces
the problem and existing method theoretically. Observations were duly noted here. The next part,
Technical and Financial Analysis introduces the solution both theoretically as well as
diagrammatically. The third part, Impact of implementation gives us the observations in tabulated form
and shows us the final derived values. This is then followed by Results

II.

BACKGROUND

2.1 Drum Level Measurement

Fig. 1. Boiler drum level management

The FIG-1 is an example of the arrangement of a differential drum level measuring transmitter. The
differential transmitter output signal increases as the differential pressure decreases. The differential
pressure range will vary between 10 and30 inches, depending on the size of the boiler drum, with a zero
suppression of several inches. On the high pressure side of the measuring device, the effective pressure
equals boiler drum pressure plus the weight of a water column at ambient temperature having a length
equal to the distance between the two drum pressure connections. On the low pressure side, the effective
pressure equals boiler drum pressure, plus the weight of a column of saturated steam having a length
from the upper drum pressure connection to the water level, and the weight of a column of water at
saturation temperature having a length from the water level to the lower drum pressure connection.

2.2 Existing Control System


Drum Level Control is implemented in the PID controller. Changeover between single element and
three element causes the drum level variation. Feed-water is controlled through Feed water regulating
control valve by two constant speed motor driven pumps. The Drum level compensation includes steam
temperature and drum pressure. Boiler drum level control is done by BFP scoop & feed water regulating
station (FRS) control valve in two ways, namely:
1. DP mode
2. Three element mode,

1403

Vol. 7, Issue 4, pp. 1402-1408

International Journal of Advances in Engineering & Technology, Sept., 2014.


IJAET
ISSN: 22311963
In DP mode BFP scoop maintains the DP across the FRS as per set point & control valve regulate feed
water flow as per three element errors to maintain drum level as per set point. Whereas in three element
mode, scoop maintain the drum level as per three element error keeping FRS control valve wide open.

2.3 Observation
In most of units having MD BFP only, drum level control is accomplished through DP mode because
it is believed that has robust control. But it results in appreciable energy loss due to throttling of FRS
valve. DP set point for scoop is observed between the range of 7- 10 kg/cm2; hence same is the pressure
drop across FRS valve. Reason of high DP is set point to increase differential pressure to improve the
control. Disadvantage of DP mode is increased pressure loss & Energy loss.

III.

TECHNICAL & FINANCIAL ANALYSIS

Energy Saving potential in throttled FRS valve is given below which clearly indicates pump power loss
can be optimized by minimizing pressure drop across the valve.
Energy Saving Potential = Pressure drop across the valve x Pump Power
------------------------------------------------------Total Pressure Rise across the Pump
DP optimization in DP mode gives no substantial energy saving due controlling action of FRS valve.
Further pressure drop reduction is only possible in three element mode scoop operation where FRS
valve is kept fully open.
Pump losses % = Pump power (100- efficiency)
------------------------------------Generated Load
In 275 MW capacity unit having overall efficiency of 40 % and for pump power= 7 MW, DP =7.5
kg/cm2, Total pr. Developed by pump = 180 kg/cm2, Energy saving potential & Calculated pump loss
is given below which are unusually high figure.
Energy saving potential =29 %
Calculated pump loss = 1.834 % of Boiler Heat I/P
As flow control by throttling in case of high power pump like BFP is inefficient, flow control by speed
regulation by means of BFP scoop is adopted.
Effect on System Curve with Throttling

HEAD
Fig 2 System Curve

In the above system, pump system curve get shifted to lower efficiency region as throttling increases.
Point A is the best efficiency point (BEP) where valve is full open at the pumps best efficiency point
(BEP). But, in actual operation, amount of flow in valve full open condition is not necessary hence we

1404

Vol. 7, Issue 4, pp. 1402-1408

International Journal of Advances in Engineering & Technology, Sept., 2014.


IJAET
ISSN: 22311963
throttle the valve. To point B to get desired flow. The reduction in flow rate has to be effected by a
throttle valve. In other words, we are introducing an artificial resistance in the system. Due to this
additional resistance, the frictional part of the system curve increases and thus the new system curve
will shift to the left -this is shown as the red curve. So the pump has to overcome additional pressure in
order to deliver the reduced flow. Now, the new system curve will intersect the pump curve at point B.
At point B, pump head is increased the red double arrow line shows the additional pressure drop due to
throttling. You may note that the best efficiency point has shifted from 82% to 77% efficiency. So what
we want is to actually operate at point C which is on the original system curve for the same required
flow. The head required at this point is reduced. What we now need is a new pump which will operate
with its best efficiency point at C. But there are other simpler options rather than replacing the pump.
The speed of the pump can be reduced or the existing impeller can be trimmed. The blue pump curve
represents either of these options. It is not feasible to replace pump or trimming of impeller so the best
solution is to reduce the speed. Hence flow control by speed control method is more efficient. DP control
mode & three element mode schematic is given below:
1.) Scoop operation in DP mode

Fig 3 DP mode scoop operation

2.) Scoop operation in three element mode

Fig 4 Three element mode scoop operation

DP mode is suitable in case of emergency & fluctuating load condition whereas three element mode is
suitable in steady load condition. A basic flow chart of the existing DP as well as 3 element have been
explained:

1405

Vol. 7, Issue 4, pp. 1402-1408

International Journal of Advances in Engineering & Technology, Sept., 2014.


IJAET
ISSN: 22311963
DP MODE :

Fig 5 DP mode control flowchart

THREE ELEMENT MODE :

Fig 6 Three element mode control flowchart

1406

Vol. 7, Issue 4, pp. 1402-1408

International Journal of Advances in Engineering & Technology, Sept., 2014.


IJAET
ISSN: 22311963

Fig 7 Digitalized control and monitoring of boiler drum as seen from main control room

IV.

IMPACT OF IMPLEMENTATION

BFP scoop operation was successfully tested in three element mode for each BFP. Pressure drop across
FRS valve is observed to be3.5 kg/cm2 in valve full open condition.
Ampere saving achievement is given below:
S.NO.

BFP UNIT

1
2
3
4

BFP - 1A
BFP - 1B
BFP - 2A
BFP - 2B

Table 1 Observations and savings per BFP unit


AMP. Gain/Hr
KW saving/Hr
GHG reduction KG/Hr
12
2.6
4.5
14.3

95
26
39
136

80
21
36
120

BFP hydraulic couplings response time and subsequent change in drum level shows that drum level
control directly through BFP scoop operation in three element mode variation is quite feasible especially
under steady operating condition

V.

RESULTS AND DISCUSSIONS

As evident from the observations above made, there is a considerable decrease in pressure drop which
was measured in full valve open condition, in the three element mode of operation. This lesser pressure
drop results in lesser demand for the BFP to work continuously at full load, thereby generating an
enormous potential for saving energy and increasing efficiency of the whole boiler operation system.
Thus, it was seen that a slight loss in control can correspond too much greater efficiency and overall a
better system of operation.

VI.

FUTURE WORK

Although the three element mode was successively tested and results were encouraging, there is always
a slight disadvantage to this method as compared to DP mode that is more degree of robust control
over the throttle valve. Thus, more future research is needed in the context of how to increase the

1407

Vol. 7, Issue 4, pp. 1402-1408

International Journal of Advances in Engineering & Technology, Sept., 2014.


IJAET
ISSN: 22311963
robustness of controlling the throttle valve as effectively as the DP mode and yet retain the same benefits
of the three element mode of operation.

VII.

CONCLUSION

A marked improvement in energy conservation and increase in overall efficiency of the system was
observed when the drum level was controlled by the three element mode, wherein the throttle valve was
fully opened as compared to the DP mode.

ACKNOWLEDGEMENTS
We are highly grateful to INDIABULLS POWER Pvt Ltd , Amravati unit for letting us use the boiler
control unit as well as the various boiler equipments in their Amravati Power Plant for our research
purposes .

REFERENCES
[1] INDIABULLS POWER Pvt Ltd , Amravati unit.
[2] Operation and maintenance manual, dong fang electric corporation ltd. Released on 2012.
[3] Invensys I/A Series hardware product specifications for controller, dong fang electric corporation ltd. Released
on 2012.
[4] M. Iacob, G.-D. Andreescu, Drum-boiler control system employing shrink and swell effect remission in
thermal power plants, Proc. 2011 3rd International Congress on Ultra Modern Telecommunications and Control
Systems and workshops (ICUMT), Budapest, Hungary, ISSN: 2157-0221, ISBN: 978-1-4577-0682-0, pp. 1-8,
Oct. 2011. IEEE
[5] M. Iacob, G.-D. Andreescu, N. Muntean, SCADA system for a central heating and power plant, (in book
chapter 8: Process Control and Automation Applications), in Instrument Engineers' Handbook Vol. 3: Process
Software andDigital Networks, 4th Edition, Eds.: B.G. Liptak, H. Eren, CRC Press, USA, ISBN: 9781439817766, pp. 930-939, Aug 2011
[6] Drum level control systems in process industries (Application Guide ) , ABB Power . Published 2014
[7] A guide to boiler drum level equipment control concepts by The Clark-Reliance Corporation ,16633Foltz
Industrial Parkway , Ohio ,USA.

[8] Xu Lian University of Nebraska-Lincoln , Optimized control strategies for a typical water loop heat pump
system , 2012
[9] Steam pressure reduction : opportunities and issues , US department of energy .

AUTHOR BIOGRAPHIES
Aditya Sindhu is a B.Tech Third year student, currently pursuing electrical and electronics
engineering from Maharaja Agrasen Institute of Technology (MAIT), under GGSIP University,
New Delhi. He has been an academic topper throughout and published a paper in an
international journal in the field of instrumentation. His research and technical interest areas
include power, transmission , instrumentation and control .
Aashish Bhaskar is working as a senior technical consultant at Indiabulls Power Ltd , a pioneer
in the name of power industry today . He is an electrical engineer and has done his B.Tech from
IIT Delhi. He has an experience of more than 5 years in the power sector and has led many teams
and project site divisions. He is singly handedly responsible for saving a lot of companys
investment by ingenious cost cutting methods. His research areas include energy conservation
and machines
Avdesh Bhardawaj is an accomplished academician, author, researcher and consultant. He has
done B.Sc, M.Sc and M.Phil from premiere universities in India. He has extensive teaching
experience in reputed colleges and universities. He is also working towards completion of his
PhD from IIT Delhi. He has published a large number of research papers in International and
National Journals and conferences. His research interests include EIA, mathematical modeling,
energy conservation and pollution remediation.

1408

Vol. 7, Issue 4, pp. 1402-1408

You might also like