The NEC calls for use of Ground Fault Protection (GFP) type for circuit breakers for services
over 1000A, does this include buildings or just equipment?
Posted on June 13, 2011 by E&S Grounding Solutions Engineering Team

Hi Nazhan,
Thank you for your question regarding Ground Fault Protection (GFP), it is our pleasure to assist you.
The National Electrical Code (NEC) requires Ground Fault Protection for equipment in Articles 215.10, 230.95,
240.13 and 517.17. Ground Fault Protection Circuit Breakers use special sensors to detect low-magnitude
ground faults. These low-magnitude faults are sensed by the breaker and current flow is stopped. Highmagnitude faults are stopped by traditional over current protection mechanisms. NEC Article 230.95 does indeed
require that all service disconnects over 1,000-amps must have Ground Fault Protection in addition to regular
overcurrent protection systems. There are a few exceptions to this rule, but first let me explain what Ground Fault
Protection is NOT.
Ground Fault Protection:
Does NOT protect people from shock hazards
Does NOT protect people and equipment from ground faults like a GFCI system (Ground Fault Circuit
Interrupter)
Does NOT provide protection from 3-phase, phase-phase, or phase-neutral faults
Does NOT provide protection from high-magnitude ground faults
Ground Fault Protection systems are very sophisticated devices, often with many variable settings to Dial-In the
specific requirements needed for your site. Also, the reliability of the GFP systems depends on many factors
beyond the proper settings on the device. Improper wiring of the system, including accidental neutral return paths
can easily negate the effectiveness of a Ground Fault Protection device. These devices must also have regular
maintenance including annual calibration.
As mentioned earlier, there are some exceptions to the Ground Fault Protection rule. Specifically, Ground Fault
Protection is NOT required for the following:
1. Any system with a disconnect less than 1000 amps

http://www.esgroundingsolutions.com/blog/309/the-nec-calls-for-use-of-ground-fault-pro... 23/05/2012

The NEC calls for use of Ground Fault Protection (GFP) type for circuit breakers for se... Pgina 2 de 2

2. Any 208Y/120 Volt, 3-phase, 4-wire (wye) system


3. Any single-phase system
4. Systems over 600-volts (high or medium voltage systems)
5. Any delta system (grounded or ungrounded)
6. Service with six disconnects or less (NEC 230.71) where each disconnect is less than 1,000 amps. A 4,000A
service could be split into 5 800A switches
7. Resistance or impedance grounded systems
8. Fire Pumps
9. Any system with Ground Fault Protection (except for Health Care Facilities. See NEC 517.17)
10. Continuous industrial process where a non-orderly shutdown would increase hazards
We hope you find this information useful. If you should have any further questions, please do not hesitate to ask.
Best regards,
The Engineering Team at E&A Grounding Solutions
Photo Credit: E&S Grounding Solutions
Share this article with your friends:

This entry was posted in Electrical Grounding, Electrical Standards. Bookmark the permalink.

ES Grounding Solutions | Electrical Grounding Questions and Answers Blog


Bad Behavior has blocked 4 access attempts in the last 7 days.

http://www.esgroundingsolutions.com/blog/309/the-nec-calls-for-use-of-ground-fault-pro... 23/05/2012

You might also like