You are on page 1of 49

2009 System x and BladeCenter

Technical Conference
July 27 July 31, 2009 Chicago, Illinois

Powering Your
IBM BladeCenter Chassis
xEE02
William Champion
IBM System x ATS

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

A dynamic infrastructure is required to address todays needs


and lay the foundation for the future.
There are seven interrelated initiatives that
clients can evaluate and consider on their
journey towards building a dynamic
infrastructure.
The Energy Efficiency initiative aims to
address energy, environment, and
sustainability challenges and opportunities
across business and IT infrastructure.

If we can understand the basics of how and


where power and energy are used
throughout the IT and infrastructure, we can
identify areas of inefficiency, risk, and
overhead.
Understanding that the successful
implementation of a well designed energy
efficiency strategy has farther reaching
effects on the business than the efficiency
gains themselves starts us on this journey.

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

Agenda
Terms & Conventions
BladeCenter H Power
BladeCenter S Power
BladeCenter E Power
Links
3

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

Terms & Conventions


PM = Power Module = PS = Power Supply
Blue Indicates Power Domain One
Brown/Burgundy Indicates Power Domain Two
PDU = Power Distribution Unit
UPS = Uninterruptable Power Supply
4

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter H
BladeCenter H

2
CD

HS21

3
CD

LS21

LS41

9
CD

JS22

HS21

LS41

8
CD

CD

CD

QS21

10

11

CD

HS21

12

13

LS41

10

11

14
CD

CD

JS22

LS41

12

CD

13

QS21

14

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter H Power Domains


Devicesa

PM 1
(Std)

PM 2
(Std)

Blades 1-7

Yes

Yes

Blades 8-14
I/O modules 1 & 2 (SM 1-2)b

Yes

Yes

I/O modules 3 & 4 (SM 1&2/BM 3&4)

Yes

Yes

I/O modules 5 & 6 (BM 1 & 2)


I/O modules 7 & 8 (HSSM 1 & 3)

Yes

I/O modules 9 & 10 (HSSM 2 & 4)


Management modulesb

PM 3
(Opt)

PM 4
(Opt)

Yes

Yes

Yes

Yes

Yes

Yes

Yes
Yes

Yes

Yes

Yes
Yes

Yes

a.

SM = switch module; BM = bridge module; HSSM = high speed switch module.

b.

The two management modules and I/O modules 1 and 2 are powered by any power module.

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter H Power Modules


PM 1 and 2 Come Standard

Front of BC H Chassis
PM 1
PM 3

PM 3 and 4 Optional

2900 Watts PMs 16A at 208V AC


For Redundant Power

BladeCenter H

10

11

12

13

14

10

11

12

13

14

Connect PMs 1 & 4 And One


Blower To One AC Source

Connect PMs 2 & 3 And One


Blower To Another AC Source

PM 2

PM 4

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter H Power Modules


PM Has 3-fan Pack
Each Fan Pack Is Used To Cool The
Power Supply In PM And Provide
Cooling To I/O Modules 7 - 10
PMs 1 & 3 Provide Cooling To I/O
Modules 7 & 8
PMs 2 & 4 Provide Cooling To I/O
Modules 9 & 10

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter H Power Cords


Right Rear Double 30A Power Cord
PM 1 And Blower 2 Share One L6-30
Connector
PM 4 Uses The Other L6-30 Connector
Left Rear Double 30A Power Cord
PM 2 And Blower 1 Share One L6-30
Connector

PM 3 Uses The Other L6-30 Connector

4.3m 208V Double 30A NEMA L6-30P


P/N: 25R5783 FC: 6270

Right Rear Triple 16A Power Cord


PM 1 & 4 And Blower 2 Each Have
Dedicated IEC 320-C20 Connector
Left Rear Triple 16A Power Cord
PM 2 & 3 And Blower 1 Each Have
Dedicated IEC 320-C20 Connector

2.8m 200-240V Triple 16A IEC 320-C20


P/N: 25R5785 FC: 6226

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter H 2 x 60A Single Phase


37A Total Max

37A Total Max


Rear of BC H Chassis
7

16A PM2

PS

PS

1
8

OK

Link

M3
P
16A
r1
e
ow
l
B
5A

TX/RX

IP

MM 1

MM 2

16A PM 1
16A
5 A PM 4
Bl
ow
er
2

10

60A
Single Phase
Rack PDU
(48A Derated)

10

60A
Single Phase
Rack PDU
(48A Derated)

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter H 2 x 60A 3 Phase

Rear of BC H Chassis
7
PS

27.7A

27.7A

16A PM2
PM 3
A
16
r1
e
ow
Bl
5A

PS

1
8

OK

Link

TX/RX

IP

27.7A

MM 1

MM 2

1 6 A PM 1
16A
5A PM 4
Bl
ow
er
2

27.7A

27.7A

27.7A
9

10

60A
3 Phase
Rack PDU
27.7A / Phase

11

60A
3 Phase
Rack PDU
27.7A / Phase

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

2 BCH 4 x 60A 1Phase


Rear of BC H Chassis
7

16A PM2

PS

PS

1
8

OK

Link

3
PM
r1
e
w
lo

TX/RX

16A

5A

IP

MM 1

MM 2

16A PM 1
16A
5 A PM 4
Bl
ow
er
2

10

60A
Single Phase
Rack PDU
(48A Derated)

60A
Single Phase
Rack PDU
(48A Derated)

Rear of BC H Chassis
7

16A PM2

PS

PS

1
8

OK

Link

3
PM
A
6
1
1
er
w
o
Bl
5A

TX/RX

IP

MM 1

MM 2

16A PM 1
16A
5 A PM 4
Bl
ow
er
2

10

60A
Single Phase
Rack PDU
(48A Derated)
12

60A
Single Phase
Rack PDU
(48A Derated)
2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

2 BCH 2 x 60A 3Phase & 2 x 30A 1Phase


16A

Rear of BC H Chassis

PM 2

PM
16A

7
PS

30A
Single Phase
Rack PDU
(24A Derated)

PS

30A
Single Phase
Rack PDU
(24A Derated)

1
8

OK

Link

TX/RX

5A

IP

MM 1

MM 2

Bl
ow
e

r2

16

PM

5A

PM

16

er
w
o
Bl

27.7A

16A
27.7A

27.7A

27.7A

10

PM

2
5A Blo
wer 1
16A PM3

7
PS

PS

1
8

OK

Link

TX/RX

M1
P
16A
wer 2
o
l
B
A
5
1 6 A PM 4

27.7A

27.7A

IP

60A
3 Phase
Rack PDU
27.7A / Phase

MM 1

MM 2

60A
3 Phase
Rack PDU
27.7A / Phase

10

13

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

3 BCH 4 x 60A 3Phase


Rear of BC H Chassis
7
PS

PS

1
8

OK

Link

TX/RX

2
PM
16A
3
PM
A
6
1

IP

MM 1

MM 2

27.7A

5A

er
ow
Bl

27.7A

lo
w
er

5A

16 A
1 6 PM 1
A
PM
4

27.7A

27.7A

10

27.7A

27.7A

1 6A

PM 2

7
PS

60A
3 Phase
Rack PDU
27.7A / Phase

M1
6A P

PS

60A
3 Phase
Rack PDU
27.7A / Phase

1
8

OK

Link

TX/RX

5A

IP

MM 1

MM 2

Bl
ow
e

r2

16
A

PM

5A

PM

16

er
ow
l
B

27.7A

16A
27.7A

27.7A

27.7A

10

PM

2
5A Blo
wer 1
16A PM3

7
PS

PS

1
8

OK

Link

TX/RX

1
PM
A
16
wer 2
5A Blo
16A PM 4

27.7A

27.7A

IP

60A
3 Phase
Rack PDU
27.7A / Phase

MM 1

MM 2

60A
3 Phase
Rack PDU
27.7A / Phase

10

14

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

4 BCH 6 x 60A 3Phase


Rear of BC H Chassis
27.7A

27.7A

16A PM2
PM3
16 A
1
er
low
B
5A

7
PS

PS

1
8

OK

Link

TX/RX

IP

MM 1

MM 2

16A PM 1
16 A
5A PM 4
Bl
ow
er
2

27.7A

27.7A

27.7A

27.7A
9

60A
3 Phase
Rack PDU
27.7A / Phase

60A
3 Phase
Rack PDU
27.7A / Phase

10

7
PS

PS

1
8

OK

Link

TX/RX

2
PM
1 6A
3
PM
A
16

IP

MM 1

MM 2

27.7A

5A

er
ow
Bl

lo
w
er

5A

27.7A

16A
1 6 PM 1
A
PM
4

27.7A

27.7A

10

27.7A

27.7A

16A

PM
16A

PM 2

7
PS

60A
3 Phase
Rack PDU
27.7A / Phase

PS

60A
3 Phase
Rack PDU
27.7A / Phase

1
8

OK

Link

TX/RX

5A

IP

MM 1

MM 2

Bl
ow
e
A

r2

16
A

PM

5A

PM

16

er
ow
Bl

27.7A

16A
27.7A

27.7A

27.7A

10

PM

2
5A Blo
wer 1
16A PM3

7
PS

PS

1
8

OK

Link

TX/RX

1
PM
16A
wer 2
5A Blo
16A PM 4

27.7A

27.7A

IP

60A
3 Phase
Rack PDU
27.7A / Phase

MM 1

MM 2

60A
3 Phase
Rack PDU
27.7A / Phase

10

15

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

4 BCH 4 x 60A 3Phase & 2 x 60A 1Phase


Rear of BC H Chassis
7
PS

16A PM2

PS

1
8

OK

Link

16A
5A

PM 3

er
ow
Bl

TX/RX

1
IP

MM 1

MM 2

16A PM 1
16 A
PM
5A
4
Bl
ow
er
2

10

60A
Single Phase
Rack PDU
(48A Derated)

60A
Single Phase
Rack PDU
(48A Derated)

7
PS

PS

1
8

OK

Link

TX/RX

2
PM
16 A
3
PM
A
16

IP

MM 1

MM 2

27.7A

5A

er
ow
Bl

lo
w
er

5A

27.7A

16A
1 6 PM 1
A
PM
4

27.7A

27.7A

10

27.7A

27.7A

16A

PM
16A

PM 2

7
PS

60A
3 Phase
Rack PDU
27.7A / Phase

PS

60A
3 Phase
Rack PDU
27.7A / Phase

1
8

OK

Link

TX/RX

5A

IP

MM 1

MM 2

Bl
ow
e
A

r2

16
A

PM

5A

PM

16

er
ow
Bl

27.7A

1 6A
27.7A

27.7A

27.7A

10

PM

2
5A Blo
wer 1
16A PM3

7
PS

PS

1
8

OK

Link

TX/RX

1
PM
16A
wer 2
5A Blo
16A PM 4

27.7A

27.7A

IP

60A
3 Phase
Rack PDU
27.7A / Phase

MM 1

MM 2

60A
3 Phase
Rack PDU
27.7A / Phase

10

16

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

5 BCH 8 x 60A 1Phase


Rear of BC H Chassis

5 BCH Chassis Will Require


Minimum of 45U of Rack Space

7
PS

16A PM2

1
8

OK

Link

16A PM 1

TX/RX

16 A

48A

5A

PM

e
ow
Bl

16 A

IP

MM 1

MM 2

5A

r1

PM

Bl
ow
er

48A
2

10

16A PM2

APC Makes Two 48U Racks

7
PS

PS

16A PM 1

1
8

OK

Link

TX/RX

NetShelter SX 48U 600mm


P/N AR3107

PS

PM3
16A wer 1
o
l
AB

IP

MM 1

MM 2

5A B
16Alower 2
PM
4

47A

47A
9

10

1 6 A PM
2
5A Blower 1

NetShelter SX 48U 750mm

7
PS

PS

1
8

1
1 6 A PM
5A Blower 2

OK

Link

16A P

M3

TX/RX

P/N AR3157

16 A P

M4

IP

48A

MM 1

MM 2

48A

16A P

10

M
16A P

M2

Use APC PDUs In APC Racks Since


8 IBM PDUs Will Not Mount Cleanly

PS

16A PM3
er 1
low
5A B

42A

16A P

PS

1
8

OK

Link

TX/RX

IP

MM 1

MM 2

16A PM 4
5A B
low
er 2

10

16 A P

M2

M1

42A

5A Blower 1
3
16A PM

PS

PS

1
8

OK

Link

TX/RX

5A Blower 2
1 6 A PM
4

IP

60A
Single Phase
Rack PDU
(48A Derated)

17

10

MM 1

MM 2

60A
Single Phase
Rack PDU
(48A Derated)

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BCH 1 x 60A 1Phase


Rear of BC H Chassis
7
PS

PS

1
8

OK

Link

TX/RX

10

MM 1

MM 2

9.5A PM 4

5A Blower 2
9.5A PM 1

9.5A PM 3
5A Blower 1

9.5A PM 2

IP

24A Total Max


5000 Watts

24A Total Max


5000 Watts

60A
Single Phase
Rack PDU
(48A Derated)

BC H Maximum Amp Load In Fail-Over 24A


with One Power Feed
Non-Redundant Single Power Feed

Room PDU

18

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

An Option For 2 x 30A Circuits on BCH


Equipment can wired based on actual power
consumption levels instead of label ratings
Customer has to perform a continuous 30 day power
measurement study as per National Electric Code
(NEC) in the US
This procedure is spelled out in detail in the NEC
section 220.87 Determining Existing Loads

19

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

Excerpt - NEC Sec. 220.87 Determining Existing Loads


The calculation of a feeder or service load for existing installations shall be permitted
to use actual maximum demand to determine the existing load under all of the
following conditions:

20

1.

The maximum demand data is available for a 1-year period.


Exception: If the maximum demand data for a 1-year period is not available, the
calculated load shall be permitted to be based on the maximum demand
(measure of average power demand over a 15-minute period) continuously
recorded over a minimum 30-day period using a recording ammeter or
power meter connected to the highest loaded phase of the feeder or
service, based on the initial loading at the start of the recording. The
recording shall reflect the maximum demand of the feeder or service by
being taken when the building or space is occupied and shall include by
measurement or calculation the larger of the heating or cooling equipment
load, and other loads that may be periodic in nature due to seasonal or
similar conditions.

2.

The maximum demand at 125 percent plus the new load does not exceed the
ampacity of the conductor.

3.

The feeder has overcurrent protection in accordance with 240.4, and the service
has overload protections in accordance with 230.90.

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

The Net of It
Item 1 we use the "30-day" exception process detailed on the
pervious slide
Item 2 is the standard "derating" applied to branch circuits.
IBMs System x PDUs and products meet the requirement
detailed in item 3

The customer needs to work with their electrician and local


authority of jurisdiction (i.e. local electrical inspector in most
cases) to insure wiring was done properly and legally
If the configuration changes after it is certified, it will have to
be tested again with this process and recertified
Note: Derating, in the context to above reference, is the limiting of load to 80% of capacity. For
example, if a circuit has a 30 amp capacity the 80% derated load capacity is 24 amps.
21

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BCH 2 x IBM 10KVA UPS


Rear of BC H Chassis
7
PS

PS

1
8

OK

Link

TX/RX

Output Pwr

C
O
M

Reset

N
C

+ G
N
1 NN O
2 DO
V

N
C

10

MM 1

MM 2

N
O

C
O
M

Reset

N
C

+ G
N
1 NN O
2 DO
V

Probe

C
O
M

N
C

10/100Base-T

C
O
M

10/100

AP9619 Network Management Card EM

AP9619 Network Management Card EM

TVSS
GND

TVSS
GND

www.apcc.com

Rear of 10KVA UPS


8000 Watts

22

Zone
1

10/100Base-T

C
O
M

10/100
www.apcc.com

37A Total Max


7700 Watts

16A PM 4

Output Pwr

Probe

C
O
M

5A Blower 2
16A PM 1

16A PM 2

Zone
1

N
O

16A PM 3
5A Blower 1

IP

37A Total Max


7700 Watts

Rear of 10KVA UPS


8000 Watts

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BCH 1 x IBM 10KVA UPS With PDU


PDUs 7700 Watts or Greater
39Y8940

Rear of BC H Chassis

39Y8923

7
PS

PS

1
8

OK

Link

71763NX

TX/RX

10

MM 1

MM 2

Output Pwr

C
O
M

Reset

N
C

+ G
N
1 NN O
2 DO
V

39Y8948, 71762MX,
71762NX

Zone
1

N
O

71763MX

16A PM 4

5A Blower 2
16A PM 1

16A PM 3
5A Blower 1

16A PM 2

IP

Probe

C
O
M

N
C

With Line Cords 40K9615

10/100Base-T

C
O
M

10/100
www.apcc.com

37A Total Max


7700 Watts
TVSS
GND

7700 Watts
Minimum
Capacity PDU

AP9619 Network Management Card EM

Rear of 10KVA UPS


8000 Watts

23

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter S
BladeCenter S
SM1
1

MT

SM2

CD

CD

HS21

HS21

HS21

HS21

HS21

HS21

300GB

CD

300GB

CD

300GB

CD

300GB

300GB

300GB

CD

I/O 3

300GB

300GB

300GB

300GB

300GB

300GB

SM1

24

I/O 4

MT

SM2

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter S Power Modules


PM 1 and 2 Come Standard
PM 3 and 4 Optional

All PMs In One Power Domain


PMs are 950 Watts at 120V / 11.2A AC
PMs are 1450 Watts at 208V / 8A AC

Rear of BladeCenter S
PM 3
PM 1
3

I/O 1

I/O 3

MM

OK

AC DC

AC DC

PMs Auto Sense 120V or 208V AC power

Link

TX/RX

All PMs Must Be Feed With Same


Voltage Levels In Same Chassis
Standard PMs 2 IEC 320 C19 - C20
Power Cords, & 4 Country Specific Cords

Optional PMs Comes With 2 Additional


IEC 320 C19 - C20 Power Cords

25

2
AC DC

AC DC

PM 4

I/O 2

I/O 4

PASS
THRU

PM 2

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter S Power Modules


Rear of BladeCenter S
3

I/O 1

I/O 3

MM

OK

AC DC

AC DC

Link

TX/RX

2
AC DC

AC DC

I/O 2

I/O 4

PASS
THRU

Standard Power Supplies Can Power:


2 x Blade Servers
SM1 With Disks
I/O Bays 1 & 3

With Optional Power Supplies 3 & 4


Can Power:
6 x Blade Servers
Note: Chassis has Non-Redundant
2 x SMs With Disks
Power When Using 120V
4 x I/O Bays
Use Power Configurator and Planning Guide to determine specific blade and configuration power usage and
power supply requirements.
26

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BCS 2 x 30A/208V 1Phase


16A Total Max

Rear of BladeCenter S
3

I/O 1

I/O 3

MM

16A Total Max

OK

AC DC

AC DC

Link

TX/RX

8A

8A
AC DC

AC DC

8A
8A
4

30A / 208V
Single Phase
Rack PDU
(24A Derated)

27

I/O 2

I/O 4

PASS
THRU

30A / 208V
Single Phase
Rack PDU
(24A Derated)

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

3 BCS 4 x 30A/208V 1Phase


Rear of BladeCenter S
3

I/O 1

I/O 3

MM

OK

AC DC

AC DC

Link

TX/RX

8A

2
AC DC

AC DC

8A
4

I/O 2

I/O 4

I/O 1

I/O 3

PASS
THRU

MM

8A
8A

OK

AC DC

8A
30A / 208V
Single Phase
Rack PDU
(24A Derated)

AC DC

Link

TX/RX

2
AC DC

AC DC

8A

I/O 2

I/O 4

I/O 1

I/O 3

PASS
THRU

MM

8 A 30A / 208V
Single Phase
Rack PDU
(24A Derated)
8A

OK

AC DC

AC DC

8A

8A

Link

TX/RX

2
AC DC

AC DC

8A
30A / 208V
Single Phase
Rack PDU
(24A Derated)
28

I/O 2

I/O 4

PASS
THRU

8 A 30A / 208V
Single Phase
Rack PDU
(24A Derated)
2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BCS 4 x 20A/110V 1Phase


Rear of BladeCenter S
3

I/O 1

I/O 3

MM

OK

AC DC

L5-20R
Outlet

AC DC

11.2A

11.2A

L5-20R
Outlet

AC DC

AC DC

L5-20R
Outlet

11.2A

L5-20R
Outlet

Link

TX/RX

11.2A
4

I/O 2

I/O 4

PASS
THRU

NEMA L5-20R - 120V / 20A


Is Dreated To 16A

29

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BCS 110V 1Phase PDUs


22.4A Total Max

Rear of BladeCenter S
3

I/O 1

I/O 3

MM

22.4A Total Max

OK

AC DC

AC DC

Link

TX/RX

11.2 A

11.2 A
AC DC

AC DC

11.2 A
11.2 A
4

30A / 110V
Single Phase
Rack PDU
(24A Derated)

I/O 2

I/O 4

PASS
THRU

30A / 110V
Single Phase
Rack PDU
(24A Derated)

The IBM Front-End PDU (P/N: 39Y8938) is 110V / 30A PDU that can
be using in this configuration. It comes with a NEMA L5-30 line cord.
30

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter S UPS Solution

16A Total Max

Rear of BladeCenter S
3

I/O 1

I/O 3

MM

16A Total Max


Requires Special IEC320
C14 to C19 Line Cord

OK

AC DC

AC DC

Link

TX/RX

8A

8A
Uplink

POWER

STATUS

RESET

1 2

4
100 10

COM

ConnectUPS-X Web/SNMP/xHub Card

8A
8A
4

I/O 2

I/O 4

PASS
THRU

ON

OFF

ON

1
2

AC DC

OFF

ON

OFF

AC DC

Rear of 3KVA UPS


2700 Watts (208V)

30A / 208V
Single Phase
Rack PDU
(24A Derated)

Note: Only Valid At 200-240V

31

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter E
BladeCenter

32

CD

CD

CD

HS21

LS21

LS41

LS41

CD

CD

CD

CD

CD

JS22

QS21

HS21

HS21

LS41

10

11

LS41

12

CD

CD

JS22

QS21

13

14

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter E Power Domains


Devices
Blades 1-6

PM 1
(Std)

PM 2
(Std)

Yes

Yes

Blades 7-14

33

I/O modules 1 & 2

Yes

Yes

I/O modules 3 & 4

Yes

Yes

Blowers

Yes

Yes

Management modules

Yes

Yes

PM 3
(Opt)

PM 4
(Opt)

Yes

Yes

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BladeCenter E Power Modules


PM 1 and 2 Come Standard
PM 3 and 4 Optional

2000 Watts PMs 12A at 208V AC


2320 Watts PMs 13.8A at 208V AC

Rear of BladeCenter E
PM 3
PM 1
OK

AC

AC

DC

DC

For Redundant Power Connect One


PM From Each Power Domain To
Each AC Source
Standard 2 IEC 320 C19 - C20
Power Cords
Optional PMs Comes With 2
Additional IEC 320 C19 - C20 Power
Cords

34

Link

TX/RX

IP

AC

AC

DC

DC

PM 4

PM 2

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

IBM BladeCenter E Chassis Refresh in 1Q09


Enhanced BladeCenter E chassis 3 new models (branded as BladeCenter E)
8677-3SX: 2000-watt PS & new DVD Multi-burner SATA drive, USB 2.0, midplane
upgrade
8677-4SX: 2320-watt PS & new DVD Multi-burner SATA drive, USB 2.0, midplane
upgrade
8677-CTO: choice of PS, upgraded midplane, choice of optical drive.
Note: Optical drive choice is an opt-in option
New Power supply option
46M0508: 2x2320W power supply upgrade option
AMM module with 48G or later firmware required
2320W PS May Require PDU Upgrade
30A PDU sufficient for 2000W PS (business as usual)
60A PDU advised for 2320W PS
No changes to power cords
Current Blowers Support All Models
35

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

2000W P/S With 2 x 30A Single Phase PDUs

24A Total Max

Rear of BC E Chassis
2000W P/S

24A Total Max


OK

AC

AC

DC

DC

12 A
12 A

30A
Single Phase
Rack PDU
(24A Derated)

36

Link

TX/RX

IP

AC

AC

DC

DC

12 A

12 A
30A
Single Phase
Rack PDU
(24A Derated)

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

2320W P/S With 2 x 30A Single Phase PDUs

27.6A Total Max

Rear of BC E Chassis
2320W P/S

27.6A Total Max


OK

AC

AC

DC

DC

13.8 A
13.8 A

30A
Single Phase
Rack PDU
(24A Derated)

37

Link

TX/RX

IP

AC

AC

DC

DC

13.8 A

13.8 A
30A
Single Phase
Rack PDU
(24A Derated)

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

2320W P/S With 4 x 30A Single Phase PDUs


Rear of BC E Chassis
2320W P/S
OK

AC

AC

DC

DC

13.8 A
13.8 A

30A
Single Phase
Rack PDU
(24A Derated)
38

Link

TX/RX

IP

AC

AC

DC

DC

13.8 A
13.8 A

30A
Single Phase
Rack PDU
(24A Derated)
2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

2320W P/S With 2 x 60A Single Phase PDUs

27.6A Total Max

Rear of BC E Chassis
2320W P/S

27.6A Total Max


OK

AC

AC

DC

DC

13.8 A
13.8 A

60A
Single Phase
Rack PDU
(48A Derated)

39

Link

TX/RX

IP

AC

AC

DC

DC

13.8 A

13.8 A
60A
Single Phase
Rack PDU
(48A Derated)

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

2320W P/S With 2 x 60A 3 Phase PDUs


Rear of BC E Chassis
2320W P/S
27.7A

27.7A
OK

27.7A

AC
DC

13.8A

27.7A

60A
3 Phase
Rack PDU
27.7A / Phase

40

AC
DC

13.8A

Link

TX/RX

IP

AC

AC

DC

DC

13.8A

27.7A

1 3 .8 A

27.7A

60A
3 Phase
Rack PDU
27.7A / Phase

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

2 x BCE With 2320W P/S Option 1

Rear of BC E Chassis
2320W P/S
OK

27.7A

AC

AC

DC

DC

Link

TX/RX

13.8A

13.8A

13.8A

IP

AC

AC

DC

DC

27.7A

13.8A

27.7A

27.7A

27.7A

27.7A
OK

60A
3 Phase
Rack PDU
27.7A / Phase

41

AC

AC

DC

DC

13.8A
13.8A

Link

TX/RX

IP

AC

AC

DC

DC

13.8A
13.8A

60A
3 Phase
Rack PDU
27.7A / Phase

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

2 x BCE With 2320W P/S Option 2


Rear of BC E Chassis
2320W P/S
OK

AC

AC

DC

DC

Link

TX/RX

13.8 A
13.8 A

13.8 A

IP

AC

AC

DC

DC

13.8 A

OK

AC

AC

DC

DC

13.8 A
13.8 A

60A
Single Phase
Rack PDU
(48A Derated)
42

Link

TX/RX

IP

AC

AC

DC

DC

13.8 A

13.8 A
60A
Single Phase
Rack PDU
(48A Derated)
2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

3 x BCE With 2320W P/S


Rear of BC E Chassis
2320W P/S
OK

AC

AC

DC

DC

Link

TX/RX

13.8A

13.8A

27.7A

13.8A

IP

AC

AC

DC

DC

13.8A

27.7A

OK

AC

AC

DC

DC

Link

TX/RX

13.8A

13.8A

IP

27.7A

27.7A

13.8A

AC

AC

DC

DC

13.8A

27.7A

60A
3 Phase
Rack PDU
27.7A / Phase

27.7A

OK

AC
DC

13.8A
13.8A

43

AC
DC

Link

TX/RX

IP

AC

AC

DC

DC

13.8A

60A
3 Phase
Rack PDU
27.7A / Phase

13.8A

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BCE 1 x IBM 7.5KVA UPS With PDU


27.6A Total Max

Rear of BC E Chassis
2320W P/S

27.6A Total Max


OK

AC

AC

DC

DC

13.8 A
13.8 A

IP

AC

AC

DC

DC

13.8 A

13.8 A
Output Pwr

Zone
1

N
O

C
O
M

Reset

N
C

+ G
N
1 NN O
2 DO
V

Probe

C
O
M

N
C

10/100Base-T

C
O
M

10/100
www.apcc.com

AP9619 Network Management Card EM

TVSS
GND

60A
Single Phase
Rack PDU
(48A Derated)

Link

TX/RX

Rear of 7.5KVA UPS


6000 Watts
44

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

BCE 2 x IBM 3KVA UPS With PDU

27.6A Total Max

Rear of BC E Chassis
2320W P/S

27.6A Total Max


OK

AC

AC

DC

DC

Link

TX/RX

RESET

1 2

4
COM

ConnectUPS-X Web/SNMP/xHub Card

13.8 A

Uplink

POWER

STATUS

RESET

1 2

4
100 10

COM

ConnectUPS-X Web/SNMP/xHub Card

13.8 A

ON

OFF

ON

1
2

OFF

45

AC
DC

ON

60A
Single Phase
Rack PDU
(48A Derated)

AC
DC

13.8 A

OFF

13.8 A

IP

ON

STATUS

OFF

POWER

ON

OFF

ON

OFF

Uplink

100 10

2 x Rear of 3KVA UPS


2700 Watts

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

Links
IBM System x PDU Guide - North America
http://www-03.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101526

Power Configurator Tool


http://www-03.ibm.com/systems/bladecenter/resources/powerconfig/
BladeCenter S Planning Guide
http://www947.ibm.com/systems/support/supportsite.wss/docdisplay?lndocid=MIG
R-5073632&brandind=5000020

46

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

IBM Systems
Lab Services and Training
is composed of experts who develop and deploy
solutions across IBMs systems family offerings. From
in-depth product expertise, to training, to platform-specific
hardware and software solutions, were here for you!

Sample System x and BladeCenter


Services and Training
Accelerator! Assessment Services for Modular & Storage
Accelerator! Services for Altiris Deployment on System x
Accelerator! Services for IBM BladeCenter Open Fabric Manager
Accelerator! Services for IBM RapidFlash! for BladeCenter
Deep Computing Collaboration Services
Accelerator! IBM Systems Director Services
IBM BladeCenter Fundamentals - Course
IBM System x and Fiber Channel Storage - Course
System x and BladeCenter certifications
Private and customized courses
"No Travel Training" options (instructor-led online, e-learning,
onsite training, etc.)
Money saving IBM Education Packs
Technical Conferences

Contact Us
stgls@us.ibm.com or visit

ibm.com/systems/services/labservices

47

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

Trademarks
The following are trademarks of the International Business Machines Corporation in the United States, other countries, or both.
Not all common law marks used by IBM are listed on this page. Failure of a mark to appear does not mean that IBM does not use the mark nor does it mean that the product is not
actively marketed or is not significant within its relevant market.
Those trademarks followed by are registered trademarks of IBM in the United States; all others are trademarks or common law marks of IBM in the United States.

For a complete list of IBM Trademarks, see www.ibm.com/legal/copytrade.shtml:


*, AS/400, e business(logo), DBE, ESCO, eServer, FICON, IBM, IBM (logo), iSeries, MVS, OS/390, pSeries, RS/6000, S/30, VM/ESA, VSE/ESA,
WebSphere, xSeries, z/OS, zSeries, z/VM, System i, System i5, System p, System p5, System x, System z, System z9, BladeCenter

The following are trademarks or registered trademarks of other companies.


Adobe, the Adobe logo, PostScript, and the PostScript logo are either registered trademarks or trademarks of Adobe Systems Incorporated in the United States, and/or other countries.
Cell Broadband Engine is a trademark of Sony Computer Entertainment, Inc. in the United States, other countries, or both and is used under license therefrom.
Java and all Java-based trademarks are trademarks of Sun Microsystems, Inc. in the United States, other countries, or both.
Microsoft, Windows, Windows NT, and the Windows logo are trademarks of Microsoft Corporation in the United States, other countries, or both.
Intel, Intel logo, Intel Inside, Intel Inside logo, Intel Centrino, Intel Centrino logo, Celeron, Intel Xeon, Intel SpeedStep, Itanium, and Pentium are trademarks or registered trademarks of Intel
Corporation or its subsidiaries in the United States and other countries.
UNIX is a registered trademark of The Open Group in the United States and other countries.
Linux is a registered trademark of Linus Torvalds in the United States, other countries, or both.
ITIL is a registered trademark, and a registered community trademark of the Office of Government Commerce, and is registered in the U.S. Patent and Trademark Office.
IT Infrastructure Library is a registered trademark of the Central Computer and Telecommunications Agency, which is now part of the Office of Government Commerce.
* All other products may be trademarks or registered trademarks of their respective companies.
Notes:
Performance is in Internal Throughput Rate (ITR) ratio based on measurements and projections using standard IBM benchmarks in a controlled environment. The actual throughput that any user will
experience will vary depending upon considerations such as the amount of multiprogramming in the user's job stream, the I/O configuration, the storage configuration, and the workload processed.
Therefore, no assurance can be given that an individual user will achieve throughput improvements equivalent to the performance ratios stated here.
IBM hardware products are manufactured from new parts, or new and serviceable used parts. Regardless, our warranty terms apply.
All customer examples cited or described in this presentation are presented as illustrations of the manner in which some customers have used IBM products and the results they may have achieved. Actual
environmental costs and performance characteristics will vary depending on individual customer configurations and conditions.
This publication was produced in the United States. IBM may not offer the products, services or features discussed in this document in other countries, and the information may be subject to change without
notice. Consult your local IBM business contact for information on the product or services available in your area.
All statements regarding IBM's future direction and intent are subject to change or withdrawal without notice, and represent goals and objectives only.
Information about non-IBM products is obtained from the manufacturers of those products or their published announcements. IBM has not tested those products and cannot confirm the performance,
compatibility, or any other claims related to non-IBM products. Questions on the capabilities of non-IBM products should be addressed to the suppliers of those products.
Prices subject to change without notice. Contact your IBM representative or Business Partner for the most current pricing in your geography.

48

2009 IBM Corporation

IBM System x and BladeCenter Technical Conference - Chicago

49