Professional Documents
Culture Documents
To understand how PID controllers are used, it is important to first understand some
basic control system principles. The image below illustrates the 2 basic types of control
system.
The open loop system can clearly be seen to have no feedback, therefore if the load
changes on the motor, the motor speed will change. The control unit cannot command
the driver to increase or decrease the power to the motor, as it has no knowledge of the
speed change induced in the motor, by the change in load.
The closed loop system however has feedback from the motor. So if the motors
speed were to decrease due to an increase in load, the control unit could command the
driver to increase the power to the motor, keeping a constant speed. Common direct
current motor control is achieved via PWM, and simply increasing or decreasing the duty
cycle will increase or decrease the motor speed.
2.
3.
4.
5.
Let us classify the controllers. There are mainly two types of controllers and they are
written below:
Continuous Controllers: The main feature of continuous controllers is that the
controlled variable (also known as the manipulated variable) can have any value within
the range of controllers output. Now in the continuous controllers theory, there are
three basic modes on which the whole control action takes place and these modes are
written below. We will use the combination of these modes in order to have a desired
and accurate output.
1.
Proportional controllers.
2.
Integral controllers.
3.
Derivative controllers.
5.
Proportional Controllers
We cannot use types of controllers at anywhere, with each type controller, there are
certain conditions that must be fulfilled. With proportional controllers there are two
conditions and these are written below:
1.
Deviation should not be large, it means there should be less deviation between the input
and output.
2.
Proportional controller helps in reducing the steady state error, thus makes the system
more stable.
2.
Slow response of the over damped system can be made faster with the help of these
controllers.
2.
Integral Controllers
As the name suggests in integral controllers the output (also called the actuating
signal) is directly proportional to the integral of the error signal. Now let us analyze
integral controller mathematically. As we know in an integral controller output is directly
proportional to the integration of the error signal, writing this mathematically we have,
Where Ki is integral constant also known as controller gain. Integral controller is also known as
reset controller.
Derivative Controllers
We never use derivative controllers alone. It should be used in combinations with
other modes of controllers because of its few disadvantages which are written below:
1.
2.
It produces saturation effects and also amplifies the noise signals produced in the
system.
Now, as the name suggests in a derivative controller the output (also called the
actuating signal) is directly proportional to the derivative of the error signal. Now let us
analyze derivative controller mathematically. As we know in a derivative controller output
is directly proportional to the derivative of the error signal, writing this mathematically we
have,
Where Kd is proportional constant also known as controller gain. Derivative controller is also
known as rate controller.
Sometimes, the control element has only two position either it is fully closed or fully
open. This control element does not operate at any intermediate position, i.e. partly
open or partly closed position. The control system made for controlling such elements,
is known as on off control theory. In this control system, when process variable
changes and crosses certain preset level, the output valve of the system is suddenly
fully opened and gives 100% output.
Generally in on off control system, the output causes change in process variable. Hence
due to effect of output, the process variable again starts changing but in reverse
direction. During this change, when process variable crosses certain predetermined
level, the output valve of the system is immediately closed and output is suddenly
reduced to 0%.
As there is no output, the process variable again starts changing in its normal direction.
When it crosses the preset level, the output valve of the system is again fully open to
give 100% output. This cycle of closing and opening of output valve continues till the
said on-off control system is in operation.
A very common example of on-off control theory is fan controlling scheme of
transformer cooling system.
When transformer runs with such a load, the temperature of the electrical power
transformer rises beyond the preset value at which the cooling fans start rotating with
their full capacity.
As the cooling fans run, the forced air (output of the cooling system) decreases the
temperature of the transformer.
When the temperature (process variable) comes down below a preset value, the control
switch of fans trip and fans stop supplying forced air to the transformer. After that, as
there is no cooling effect of fans, the temperature of the transformer again starts rising
due to load.
Again when during rising, the temperature crosses the preset value, the fans again start
rotating to cool down the transformer.
Theoretically, we assume that there is no lag in the control equipment. That means,
there is no time day for on and off operation of control equipment. With this assumption
if we draw series of operations of an ideal on off control system, we will get the graph
given below.
But in practical on off control, there is always a non zero time delay for closing and
opening action of controller elements.
This time delay is known as dead time. Because of this time delay the actual response
curve differs from the above shown ideal response curve.
Let us try to draw actual response curve of an on off control system.
Say at time T O the temperature of the transformer starts rising. The measuring
instrument of the temperature does not response instantly, as it requires some time
delay for heating up and expansion of mercury in temperature sensor bulb say from
instant T1 the pointer of the temperature indicator starts rising. This rising is exponential
in nature. Let us at point A, the controller system starts actuating for switching on
cooling fans and finally after period of T2 the fans starts delivering force air with its full
Sensitivity: The parameters of control system are always changing with change in
surrounding conditions, internal disturbance or any other parameters. This change can
be expressed in terms of sensitivity. Any control system should be insensitive to such
parameters but sensitive to input signals only.
Noise: An undesired input signal is known as noise. A good control system should be
able to reduce the noise effect for better performance.
Stability: It is an important characteristic of control system. For the bounded input
signal, the output must be bounded and if input is zero then output must be zero then
such a control system is said to be stable system.
There are two main types of control system. They are as follow
1.
2.
Manual control system. Fig 1 shows the block diagram of open loop control system in
which process output is totally independent of controller action.
Electric Hand Drier Hot air (output) comes out as long as you keep your hand under
the machine, irrespective of how much your hand is dried.
2.
Automatic Washing Machine This machine runs according to the pre-set time
irrespective of washing is completed or not.
3.
Bread Toaster This machine runs as per adjusted time irrespective of toasting is
completed or not.
4.
Automatic Tea/Coffee Maker These machines also function for pre adjusted time
only.
5.
Timer Based Clothes Drier This machine dries wet clothes for pre adjusted time, it
does not matter how much the clothes are dried.
6.
Light Switch lamps glow whenever light switch is on irrespective of light is required or
not.
7.
2.
Economical.
3.
Easy to maintain.
4.
Generally stable.
5.
2.
3.
2.
3.
Water Level Controller Input water is controlled by water level of the reservoir.
4.
5.
6.
Closed loop control systems are more accurate even in the presence of
non-linearity.
2.
3.
4.
Facilitates automation.
5.
6.
2.
3.
4.
5.
6.
Stability is the major problem and more care is needed to design a stable
closed loop system.
It is stable one.
Easy to construct.
Complicated construction.
It is an economical.
It is costly.
It is inaccurate.
It is accurate.
Less maintenance.
More maintenance.
It is unreliable.
It is reliable.
10
When feedback signal is positive then system called positive feedback system. For
positive feedback system, the error signal is the addition of reference input signal and
feedback signal. When feedback signal is negative then system is called negative
feedback system. For negative feedback system, the error signal is given by difference
of reference input signal and feedback signal.
Effect Of Feedback
Refer figure beside, which represents feedback system where
R = Input signal
E = Error signal
G = forward path gain
H = Feedback
C = Output signal
B = Feedback signal
1.
2.
3.
Improvement in sensitivity.
4.
5.
At point B, the controller system starts actuating for switching off the cooling fans and
finally after a period of T3 the fans stop delivering force air. Then the temperature of the
transformer again starts rising in same exponential manner.
N.B.: Here during this operation we have assumed that, loading condition of
theelectrical power transformer, ambient temperature and all other conditions of
surrounding are fixed and constant.
Non-linear Systems
We can simply define non linear control system as all those system which do not
follow the principle of homogeneity. In practical life all the systems are non-linear
system.
clear from the curve given below that in the beginning there is a linear relationship
between winding mmf and the air gap flux but after this, saturation has come which
shows the non linear behavior of the curve or characteristics of the non linear control
system.
can convert various sources of continuous input signal like sinusoidal type signal input
source, square type of signal input source etc into discrete form using the switch.
Now there are various advantages of discrete or digital system over the analog system
and these advantages are written below:
1.
Digital systems can handle non linear control systems more effectively than the analog
type of systems.
2.
3.
Digital system has higher rate of accuracy and can perform various complex
computations easily as compared to analog systems.
4.
Reliability of digital system is more as compared to analog system. They also have small
and compact size.
5.
Digital system works on the logical operations which increases their accuracy many
times.
6.
Losses in case of discrete systems are less as compared to analog systems in general.
1.
Mechanical system.
2.
Electrical system.
3.
Electronic system.
4.
Thermal system.
5.
Hydraulic system.
6.
Before I describe these systems in detail let us know, what is the meaning of modeling
of the system? Mathematical modelling of control system is the process of drawing
the block diagram for these types of systems in order to determine the performance and
the transfer functions. Now let us describe mechanical and electrical type of systems in
detail. We will derive analogies between mechanical and electrical system only which
are most important in understanding the theory of control system.
2.
3.
2.
3.
2.
3.
2.
Now let us consider the linear displacement mechanical system which is shown below-
We have already marked various variables in the diagram itself. We have x is the
displacement as shown in the diagram. From the Newtons second law of motion, we
can write force as-
On substituting the values of F1, F2 and F3 in the above equation and taking the Laplace
transform we have the transfer function as,
1.
2.
3.
And also we have three parameters which are active and passive elements
1.
2.
3.
Now we are in condition to derive analogy between electrical and mechanical types of
systems. There are two types of analogies and they are written below:
Force Voltage Analogy : In order to understand this type of analogy, let us consider a
circuit which consists of series combination of resistor, inductor and capacitor.
A voltage V is connected in series with these elements as shown in the circuit diagram.
Now from the circuit diagram and with the help of KVL equation we write the expression
for voltage in terms of charge, resistance, capacitor and inductor as,
Now comparing the above with that we have derived for the mechanical system we find that-
1.
2.
3.
4.
5.
A voltage E is connected in parallel with these elements as shown in the circuit diagram.
Now from the circuit diagram and with the help of KCL equation we write the expression
for current in terms of flux, resistance, capacitor and inductor as,
Now comparing the above with that we have derived for the mechanical system we find that,
1.
2.
3.
4.
5.
On substituting the values of T1, T2 and T3 in the above equation and taking the Laplace
transform we have the transfer function as,
When we study the analysis of the transient state and steady state response of
control system it is very essential to know a few basic terms and these are described
below.
Standard Input Signals : These are also known as test input signals. The input signal
is very complex in nature, it is complex because it may be a combination of various
other signals. Thus it is very difficult to analyze characteristic performance of any
system by applying these signals. So we use test signals or standard input signals
which are very easy to deal with. We can easily analyze the characteristic performance
of any system more easily as compared to non standard input signals. Now there are
various types of standard input signals and they are written below:
Unit Impulse Signal : In the time domain it is represented by (t). The Laplace
transformation of unit impulse function is 1 and the corresponding waveform associated
with the unit impulse function is shown below.
Unit Step Signal : In the time domain it is represented by u (t). The Laplace
transformation of unit step function is 1/s and the corresponding waveform associated
with the unit step function is shown below.
Unit Ramp signal : In the time domain it is represented by r (t). The Laplace
transformation of unit ramp function is 1/s2 and the corresponding waveform associated
with the unit ramp function is shown below.
Sinusoidal Type Signal : In the time domain it is represented by sin (t).The Laplace
transformation of sinusoidal type of the function is / (s2 + 2) and the corresponding waveform
associated with the sinusoidal type of the function is shown below.
Cosine Type of Signal : In the time domain it is represented by cos (t). The Laplace
transformation of the cosine type of the function is / (s2 + 2) and the corresponding waveform
Now are in a position to describe the two types of responses which are a function of
time.
Now the transient state response of control system gives a clear description of how the
system functions during transient state and steady state response of control
systemgives a clear description of how the system functions during steady state.
Therefore the time analysis of both states is very essential. We will separately analyze
both the types of responses. Let us first analyze the transient response. In order to
analyze the transient response, we have some time specifications and they are written
as follows:
Delay Time : This time is represented by td. The time required by the response to reach
fifty percent of the final value for the first time, this time is known as delay time. Delay
time is clearly shown in the time response specification curve.
Rise Time : This time is represented by tr. We define rise time in two cases:
1.
In case of under damped systems where the value of is less than one, in this case rise
time is defined as the time required by the response to reach from zero value to hundred
percent value of final value.
2.
In case of over damped systems where the value of is greater than one, in this case
rise time is defined as the time required by the response to reach from ten percent value to
ninety percent value of final value.
Peak Time : This time is represented by tp. The time required by the response to reach
the peak value for the first time, this time is known as peak time. Peak time is clearly
shown in the time response specification curve.
Settling Time : This time is represented by ts. The time required by the response to
reach and within the specified range of about (two percent to five percent) of its final
value for the first time, this time is known as settling time. Settling time is clearly shown
in the time response specification curve.
Maximum Overshoot : It is expressed (in general) in percentage of the steady state
value and it is defined as the maximum positive deviation of the response from its
desired value. Here desired value is steady state value.
Steady State Error : It can be defined as the difference between the actual output and
the desired output as time tends to infinity.
From this block diagram we can find overall transfer function which is linear in nature.
The transfer function of the first order system is 1/((sT+1)). We are going to analyze the
steady state and transient response of control system for the following standard signal.
1.
Unit impulse.
2.
Unit step.
3.
Unit ramp.
Unit impulse response : We have Laplace transform of the unit impulse is 1. Now let
us give this standard input to a first order system, we have
Now taking the inverse Laplace transform of the above equation, we have
It is clear that the steady state response of control system depends only on the time constant
Unit step response : We have Laplace transform of the unit impulse is 1/s. Now let us
give this standard input to first order system, we have
With the help of partial fraction, taking the inverse Laplace transform of the above equation, we
have
It is clear that the time response depends only on the time constant T. In this case the steady
state error is zero by putting the limit t is tending to zero.
Unit ramp response : We have Laplace transform of the unit impulse is 1/s 2. Now let us
give this standard input to first order system, we have
With the help of partial fraction, taking the inverse Laplace transform of the above equation we
have
On plotting the exponential function of time we have T by putting the limit t is tending to zero.
From this block diagram we can find overall transfer function which is nonlinear in
nature. The transfer function of the second order system is ( 2) / ( s ( s + 2 )). We are
going to analyze the transient state response of control system for the following
standard signal.
Unit impulse response : We have Laplace transform of the unit impulse is 1. Now let
us give this standard input to second order system, we have
Unit step response : We have Laplace transform of the unit impulse is 1/s. Now let us
give this standard input to first order system, we have
With the help of partial fraction, taking the inverse Laplace transform of the above equation we
have
Now we will see the effect of different values of on the response. We have three types of
systems on the basis of different values of .
1.
Under damped system : A system is said to be under damped system when the value
of is less than one. In this case roots are complex in nature and the real parts are always
negative. System is asymptotically stable. Rise time is lesser than the other system with the
presence of finite overshoot.
2.
Critically damped system : A system is said to be critically damped system when the
value of is one. In this case roots are real in nature and the real parts are always repetitive in
nature. System is asymptotically stable. Rise time is less in this system and there is no presence
of finite overshoot.
3.
Over damped system : A system is said to be over damped system when the value of
is greater than one. In this case roots are real and distinct in nature and the real parts are
always negative. System is asymptotically stable. Rise time is greater than the other system and
there is no presence of finite overshoot.
4.
Sustained Oscillations : A system is said to be sustain damped system when the value
of zeta is zero. No damping occurs in this case.
Now let us derive the expressions for rise time, peak time, maximum overshoot, settling
time and steady state error with a unit step input for second order system.
Rise time : In order to derive the expression for the rise time we have to equate the
expression for c(t) = 1. From the above we have
Peak Time : On differentiating the expression of c(t) we can obtain the expression for peak time.
dc(t)/ dt = 0 we have expression for peak time,
Maximum overshoot : Now it is clear from the figure that the maximum overshoot will occur at
peak time tp hence on putting the valye of peak time we will get maximum overshoot as
Steady state error : The steady state error is diffrerence between the actual output and the
desired output hence at time tending to infinity the steady state error is zero.
For any control system there exists a reference input termed as excitation or cause
which operates through a transfer operation termed as transfer function and produces
an effect resulting in controlled output or response. Thus the cause and effect
relationship between the output and input is related to each other through a transfer
function.
It is not necessary that the output will be of same category as that of the input. For
example in case of an electrical motor, the input is an electrical quantity and output is
a mechanical one. In control system all mathematical functions are converted to their
corresponding Laplace transforms. So the transfer function is expressed as a ratio of
Laplace transform of input function to Laplace transform of output function.
While doing Laplace transform, while determining transfer function we assume all initial
conditions to be zero.
The transfer function of a control system is defined as the ration of the Laplace
transform of the output variable to Laplace transform of the input variable
assuming all initial conditions to be zero.
Procedure for determining the transfer function of a control system are as follows :
1. We form the equations for the system
2. Now we take Laplace transform of the system equations, assuming initial conditions
as zero.
3. Specify system output and input
4. Lastly we take the ratio of the Laplace transform of the output and the Laplace
transform of the input which is the required transfer function
Methods of obtaining a Transfer function: There are major two ways of obtaining a
transfer function for the control system .The ways are
Block diagram method : It is not convenient to derive a complete transfer function for a
complex control system. Therefore the transfer function of each element of a control
system is represented by a block diagram. Block diagram reduction techniques are
applied to obtain the desired transfer function.
Signal Flow graphs : The modified form of a block diagram is a signal flow graph.
Block diagram gives a pictorial representation of a control system . Signal flow graph
further shortens the representation of a control system.
The transfer function of a system is completely specified in terms of its poles and zeroes
and the gain factor. Let us know about the poles and zeroes of a transfer function in
brief.
Putting the numerator of equation (ii) equal to zero we get the value of zero of the
transfer function. For this T.F is equal to zero.
There are two types of transfer functions :i) Open loop transfer function( O.L.T.F) : Transfer function of the system without
feedback path or loop.
ii) Closed loop transfer function (C.L.T.F) : Transfer function of the system with feedback
path or loop.
The root locus technique in control system was first introduced in the year 1948 by
Evans. Any physical system is represented by a transfer function in the form of
We can find poles and zeros from G(s). The location of poles and zeros are crucial
keeping view stability, relative stability, transient response and error analysis. When the
system put to service stray inductance and capacitance get into the system, thus
changes the location of poles and zeros. In root locus technique in control
system we will evaluate the position of the roots, their locus of movement and
associated information. These information will be used to comment upon the system
performance.
Now before I introduce what is a root locus technique, it is very essential here to discuss
a few of the advantages of this technique over other stability criteria. Some of the
advantages of root locus technique are written below.
2.
With the help of root locus we can easily predict the performance of the whole system.
3.
Now there are various terms related to root locus technique that we will use frequently in
this article.
1.
2.
Break away Points : Suppose two root loci which start from pole and moves in opposite
direction collide with each other such that after collision they start moving in different directions
in the symmetrical way. Or the break away points at which multiple roots of the characteristic
equation 1 + G(s)H(s)= 0 occur. The value of K is maximum at the points where the branches of
root loci break away. Break away points may be real, imaginary or complex.
3.
Break in Point : Condition of break in to be there on the plot is written below : Root
locus must be present between two adjacent zeros on the real axis.
4.
Centre of Gravity : It is also known centroid and is defined as the point on the plot from
where all the asymptotes start. Mathematically, it is calculated by the difference of summation of
poles and zeros in the transfer function when divided by the difference of total number of poles
and total number of zeros. Centre of gravity is always real & it is denoted by A.
Asymptotes of Root Loci : Asymptote originates from the centre of gravity or centroid
and goes to infinity at definite some angle. Asymptotes provide direction to the root locus when
they depart break away points.
6.
Angle of Asymptotes : Asymptotes makes some angle with the real axis and this angle
can be calculated from the given formula,
Where p = 0, 1, 2 . (N-M-1)
N is the total number of poles
M is the total number of zeros.
7.
8.
Intersection of Root Locus with the Imaginary Axis : In order to find out the point of
intersection root locus with imaginary axis, we have to use Routh Hurwitz criterion. First, we find
the auxiliary equation then the corresponding value of K will give the value of the point of
intersection.
9.
Gain Margin : We define gain margin as a by which the design value of the gain factor
can be multiplied before the system becomes unstable. Mathematically it is given by the formula
10.
Phase Margin : Phase margin can be calculated from the given formula:
11.
Symmetry of Root Locus : Root locus is symmetric about the x axis or the real axis.
How to determine the value of K at any point on the root loci ? Now there are two ways
of determining the value of K, each way is described below.
1.
Magnitude Criteria : At any points on the root locus we can apply magnitude criteria as,
Using this formula we can calculate the value of K at any desired point.
2.
Using Root Locus Plot : The value of K at any s on the root locus is given by
This is also known as root locus technique in control system and is used for determining
the stability of the given system. Now in order to determine the stability of the system
using the root locus technique we find the range of values of K for which the complete
performance of the system will be satisfactory and the operation is stable.
Now there are some results that one should remember in order to plot the root locus.
These results are written below:
1.
Region where root locus exists : After plotting all the poles and zeros on the plane, we
can easily find out the region of existence of the root locus by using one simple rule which is
written below,
Only that segment will be considered in making root locus if the total number of poles
and zeros at the right hand side of the segment is odd.
2.
How to calculate the number of separate root loci ? : A number of separate root loci
are equal to the total number of roots if number of roots are greater than the number of poles
otherwise number of separate root loci is equal to the total number of poles if number of roots
are greater than the number of zeros.
1.
Find out all the roots and poles from the open loop transfer function and then plot them
on the complex plane.
2.
All the root loci starts from the poles where k = 0 and terminates at the zeros where K
tends to infinity. The number of branches terminating at infinity equals to the difference between
the number of poles & number of zeros of G(s)H(s).
3.
Find the region of existence of the root loci from the method described above after
finding the values of M and N.
4.
5.
Plot the asymptotes and centroid point on the complex plane for the root loci by
calculating the slope of the asymptotes.
6.
Now calculate angle of departure and the intersection of root loci with imaginary axis.
7.
Now determine the value of K by using any one method that I have described above.
By following above procedure you can easily draw the root locus plot for any open loop
transfer function.
8.
9.
10.
You can easily comment on the stability of the system by using Routh array.
Bode plots were first introduced by H.W. Bode, when he was working at Bell labs in the
United States. Now before I describe what are this plots it is very essential here to
discuss a few advantages over other stability criteria. Some of the advantages of this
plot are written below:
It is based on the asymptotic approximation, which provides a simple method to plot the
logarithmic magnitude curve.
2.
The multiplication of various magnitude appears in the transfer function can be treated
as an addition, while division can be treated as subtraction as we are using a logarithmic scale.
3.
With the help of this plot only we can directly comment on the stability of the system
without doing any calculations.
4.
Bode plots provides relative stability in terms of gain margin and phase margin.
5.
Now there are various terms related to this plot that we will use frequently in this article.
1.
Gain Margin: Greater will the gain margin greater will be the stability of the system. It
refers to the amount of gain, which can be increased or decreased without making the system
unstable. It is usually expressed in dB.
2.
Phase Margin: Greater will the phase margin greater will be the stability of the system.
It refers to the phase which can be increased or decreased without making the system unstable.
It is usually expressed in phase.
3.
Gain Cross Over Frequency: It refers to the frequency at which magnitude curve cuts
the zero dB axis in the bode plot.
4.
Phase Cross Over Frequency: It refers to the frequency at which phase curve cuts the
negative times the 180 degree axis in this plot.
5.
Corner Frequency: The frequency at which the two asymptotes cuts or meet each other
is known as break frequency or corner frequency.
6.
Resonant Frequency: The value of frequency at which the modulus of G (j) has a
peak value is known as resonant frequency.
7.
Factors: Every loop transfer function (i.e. G(s) H(s)) product of various factors like
constant term K, Integral factors (j), first order factors ( 1 + jT)( n) where n is an integer,
second order or quadratic factors.
8.
Slope: There is a slope corresponding to each factor and slope for each factor is
expressed in the dB per decade.
9.
Angle: There is an angle corresponding to each factor and angle for each factor is
expressed in the degrees.
Bode Plot
These are also known as logarithmic plot (because we draw these plots on semi-log
papers) and are used for determining the relative stabilities of the given system. Now in
order to determine the stability of the system using bode plot we draw two curves, one is
for magnitude called magnitude curve another for phase called Bode phase plot.
Now there are some results that one should remember in order to plot the Bode curve.
These results are written below:
Constant term K: This factor has a slope of zero dB per decade. There is no
corner frequency corresponding to this constant term. The phase angle associated
with this constant term is also zero.
Integral factor 1/(j)n: This factor has a slope of -20 n (where n is any
integer)dB per decade. There is no corner frequency corresponding to this integral
factor. The phase angle associated with this integral factor is -90 n here n is also
an integer.
First order factor 1/ (1+jT): This factor has a slope of -20 dB per decade.
The corner frequency corresponding to this factor is 1/T radian per second. The
phase angle associated with this first factor is -tan - 1(T).
First order factor (1+jT): This factor has a slope of 20 dB per decade. The
corner frequency corresponding to this factor is 1/T radian per second. The phase
angle associated with this first factor is tan - 1(T) .
Second order or quadratic factor : [{1/(1+(2/)} (j) + {(1/2)}
(j)2)]: This factor has a slope of -40 dB per decade. The corner frequency
corresponding to this factor is n radian per second. The phase angle associated
with this first factor is tan-1{ (2 / n) / (1-( / n)2)} .
Keeping all these points in mind we are able to draw the plot for any kind of system.
Now let us discuss the procedure of making a bode plot:
1.
2.
3.
Now we are required one semi-log graph chooses a frequency range such that the plot
should start with the frequency which is lower than the lowest corner frequency. Mark angular
frequencies on the x-axis, mark slopes on the left hand side of the y-axis by marking a zero
slope in the middle and on the right hand side mark phase angle by taking -180 degrees in the
middle.
4.
Calculate the gain factor and the type or order of the system.
5.
Constant term K.
2.
3.
4.
5.
(c) Now sketch the line with the help of corresponding slope of the given factor. Change
the slope at every corner frequency by adding the slope of the next factor. You will get
magnitude plot.
(d) Calculate the gain margin.
For drawing the Bode phase plot :
1.
2.
Substitute various values to above function in order to find out the phase at different
points and plot a curve. You will get a phase curve.
3.
For Stable System : Both the margins should be positive. Or phase margin should be
greater than the gain margin.
2.
For Marginal Stable System : Both the margins should be zero. Or phase margin
should be equal to the gain margin.
3.
For Unstable System : If any of them is negative. Or phase margin should be less than
the gain margin.