You are on page 1of 59

CM e2 1 0 0 Qu i c k M an u al

CM e2100

En g l i sh
Version 3.0

Get the com plete m anual online at w w w .elvaco.com


CM e2100 Quick M anual English v3.0

Page | 1

Co nt ent s
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Page | 2

DOCUM ENT NOTES............................................................................ 3


INTRODUCTION .................................................................................. 6
MOUNTING ....................................................................................... 10
CONFIGURE FOR E-MAIL REPORTS ................................................. 14
CONFIGURE FOR FTP REPORTS ....................................................... 17
CONFIGURE FOR HTTP REPORTS .................................................... 19
CONFIGURE FOR TRANSPARENT M-BUS ........................................ 21
RESET TO FACTORY DEFAULT......................................................... 23
CHANGING CONFIGURATION .......................................................... 24
LED INDICATIONS............................................................................. 33
TROUBLESHOOTING ........................................................................ 35
REPORT TEM PLATES ........................................................................ 42
COMM AND LISTING ......................................................................... 45
TECHNICAL SPECIFICATIONS .......................................................... 48
SAFETY AND ENVIRONM ENT .......................................................... 55
ACCESSORIES AND SIMILAR PRODUCTS ....................................... 58
Support: +46 300 434300 ? support@elvaco.com

D o c u m en t no t es

All information in this manual, including product data, diagrams, charts,


etc. represents information on products at the time of publication, and is
subject to change by Elvaco AB w ithout notice. It is recommended that
customers contact Elvaco AB to find out the latest available documentation.
Elvaco AB assumes no responsibility for technical inaccuracies,
typographical errors or any damage, liability, or other losses by use of
this product.

2011, Elvaco AB. All rights reserved. No part of the contents of this m anual m ay be
transm itted or reproduced in any form by any m eans w ithout the w ritten perm ission
of Elvaco AB. Printed in Sw eden.

CM e2100 Quick M anual English v3.0

Page | 3

This manual provides information needed to get started w ith the


CMe2100 product.
CMe2100 version appliance: >= 1.2.0
For a complete description of the CMe2100 product, dow nload the full
manual from Elvaco AB w eb site, w w w .el v ac o.c om .

Page | 4

Support: +46 300 434300 ? support@elvaco.com

1 .1

Co n t act i n f o rm at i o n

El v ac o A B Headquar t er

El v ac o A B Tec hni c al Suppor t

Teknikgatan 18
434 37 Kungsbacka
SWEDEN

Phone: +46 300 434300


E-Mail: support@elvaco.com
Online: w w w .elvaco.com

Phone: +46 300 30250


Fax: +46 300 18440
E-Mail: info@elvaco.com

CM e2100 Quick M anual English v3.0

Page | 5

In t r o d u c t i o n

The CMe2100 is a stand-alone, DIN-mounted GSM/GPRS equipm ent


w ith M -Bus master, intended to read and store values from any m eter
supporting the M -Bus protocol.
The CMe2100 is available in the follow ing variants:
CMe2100

Page | 6

GPRS M-Bus terminal with M -Bus 2-wire interface and


E-Mail support

Support: +46 300 434300 ? support@elvaco.com

2 .1

K ey f eat ur es

Read and store meter data from ABB electricity meters w ith
IR interface or any slaves supporting the M -Bus standard protocol
Connect up to 8 M -Bus slaves, extendable using CMeX Series
Send a variety of meter data reports using E-Mail, FTP, HTTP and SM S
Transparent M -Bus using TCP and GSM data
Configurable using SMS ,Telnet and HTTP
Remotely upgradable application and firmw are
Manufacturer specific report templates
The CMe2100 fits into almost any kind of meter collecting system, i.e.
remote reading for M -Bus compatible electricity meters, w ater meters,
gas meters, temperature meters, heat meters etc.

CM e2100 Quick M anual English v3.0

Page | 7

2 .2

Ov er vi ew

1.
2.
3.
4.
5.
Page | 8

Serial number
Button
M-Bus connector
Antenna SM A connector
M-Bus IR interface

Support: +46 300 434300 ? support@elvaco.com

6.
7.
8.
9.
10.
11.
12.
CM e2100 Quick M anual English v3.0

GSM LED (Yellow)


Error LED (Red)
Status LED (Green)
SIM card holder
Service interface
Power supply N
Power supply L
Page | 9

M o u n t i ng

The CMe2100 should be mounted on a DIN-rail. The metallic clip on the


bottom is used to mount and demount the unit from the DIN-rail. For
safety reasons, a DIN-rail enclosure must cover the terminals.

3 .1

SIM c ar d

Install the GSM SIM card into the SIM card holder (9). Remember the
phone number for later use.

IMPORTANT
The SIM card shall not have any PIN code activated
The SIM card must have GPRS internet access activated for full
functionality
If a prepaid SIM card is used, ensure that enough credits are available
Page | 10

Support: +46 300 434300 ? support@elvaco.com

3 .2

A n t en n a

The antenna should be connected to the SMA connector (4). Depending


on signal strength and environment, a different antenna w ith extension
cable can be used. Torque should be finger tight.

IMPORTANT
Do not mount the antenna close to any metallic objects
Do not mount the antenna close to the M -Bus 2-w ire bus
Do not mount the antenna inside a metallic cabinet

3 .3

M -Bu s 2 -w ir e b u s

M-Bus is a multi-drop 2-w ire bus w ith no polarity. A cable of either


shielded (typically 4 x 0.8 m m diam./0.5 m m 2) telephone type or
standard mains type (1.5 mm 2) should be used. Connect the w iring to
the connector (3). Do not exceed the maximum cable length of 1000 m .
CM e2100 Quick M anual English v3.0

Page | 11

IMPORTANT
The internal M -Bus interface can handle up to 8 slaves. Overloading
the bus causes communication problems w ith the connected slaves.
All connected slaves must have unique M -Bus secondary addresses.

3 .4

IR i nt erf ac e w i t h A BB el ect ri c it y m et er s or
CM eX Seri es m o d u l es

When the IR interface w ill be used beside an ABB electricity meter or


CMeX module, the IR shield (5) should be removed. The CM e2100
should be mounted on the left side of the ABB electricity m eter or CMeX
module. There shall be no space betw een the CMe2100 and the ABB
electricity meter or CM eX module. (Do not remove the shield if not used
beside an ABB electricity meter or CM eX module.)

Page | 12

Support: +46 300 434300 ? support@elvaco.com

3 .5

Po w er su p p l y

The m ain supply should be connected to the pow er supply screw


terminals (11) and (12). Main supply voltage should be in the range of
100-240 VAC, 50/60 Hz. The CM e2100 w ill be running factory default
settings w hen first pow ered up.
An emergency circuit breaker should be used in order to ensure safe
separation of the CMe2100 product from the main pow er supply.
The next chapters cover the configuration of the CMe2100 product. If any
problem occurs during configuration, please refer to the
Troubleshooting section on page 33.

CM e2100 Quick M anual English v3.0

Page | 13

Co n f i g u r e f o r E-M ai l r ep o r t s

This section describes how to enable the CMe2100 product to send


E-Mail reports of connected slaves to one or more E-Mail recipients. The
CMe2100 product w ill store hourly values of connected slaves, send
value reports every day at 00:00 and send an E-Mail installation report
on completion.

4 .1

Set E-M ai l r eci p i ent s

SMS to CMe2100 product: qset email <recipients>


Example: qset email name@domain.com,name2@domain.com
The CMe2100 product w ill acknowledge with an SMS receipt.

Page | 14

Support: +46 300 434300 ? support@elvaco.com

4 .2

Sear c h an d i n st all M -Bu s sl av es

The CMe2100 product w ill search and install M -Bus slaves using primary
and secondary addressing on 2400 baud and synchronize time w ith an
internet time server.
SMS to CMe2100 product: install <slaves> <profile> <mode>

Par am et er d esc r ip t io n :
<slaves> - Num ber of slaves to find. Not m andatory
<profile> - Configuration profile nam e. Not m andatory
<mode>- Use w ord keep to keep existing slaves and clean to
rem ove all slaves before searching for new .

CM e2100 Quick M anual English v3.0

Page | 15

Ex am pl es:
Install and search for 2 meters and use profile myprofile:

install 2 myprofile
Install and search for 2 m eters:
install 2
Clean all existing m eters and install and search for 2 m eters:
install 2 clean
Keep all existing m eters and install and search for 2 n ew m eters:
install 2 keep
Install and search for unknow n num ber of m eters:
install
The CMe2100 product is now configured and w ill by default send E-Mail
value reports of connected slaves every day at 00:00.
Page | 16

Support: +46 300 434300 ? support@elvaco.com

Co n f i g u r e f o r FTP r ep o r t s

This section describes how to enable the CMe2100 product to send FTP
reports of connected slaves to an FTP server. The CMe2100 product w ill
store hourly values of connected slaves, send value reports every day at
00:00 and send an E-Mail installation report on completion (if E-Mail is
configured, see page 14).

5 .1

Set FTP ser v er

SMS to CMe2100 product: qset ftp <server> <port> <user>

<password> <remotedir>
Example: qset ftp ftp.domain.com 21 user pass datafolder
The CMe2100 product w ill acknowledge with an SMS receipt.

CM e2100 Quick M anual English v3.0

Page | 17

5 .2

Sear c h an d i n st all M -Bu s sl av es

First perform steps as described on page 15.


FTP reports must be manually activated.
Ex am pl es:
Activate to send FTP reports every day using report template 2104:

sch report2 1day 2104


Activate to send FTP reports every hour using report template 2104:

sch report2 1hour 2104


Activate to send FTP reports every month using report template 2105:

sch report2 1month 2105

Page | 18

Support: +46 300 434300 ? support@elvaco.com

Co n f i g u r e f o r HTTP r ep o r t s

This section describes how to enable the CMe2100 product to send


HTTP POST reports of connected slaves to a w eb server. The CMe2100
product w ill store hourly values of connected slaves, send value reports
every day at 00:00 and send an E-Mail installation report on completion
(if E-Mail is configured, see page 14).

6 .1

Set HTTP ser v er

SMS to CMe2100 product: qset http <url> <user> <password>

<authentication mode>
Example: qset http http://www.domain.com user pass basic
The CMe2100 product w ill acknowledge with an SMS receipt.

CM e2100 Quick M anual English v3.0

Page | 19

6 .2

Sear c h an d i n st all M -Bu s sl av es

First perform steps as described on page 15.


HTTP reports must be manually activated.
Ex am pl es:
Activate to send HTTP reports every day using report template 3104:

sch report3 1day 3104


Activate to send HTTP reports every hour using report tem plate 3104:

sch report3 1hour 3104


Activate to send HTTP reports every month using report template 3105:

sch report3 1month 3105

Page | 20

Support: +46 300 434300 ? support@elvaco.com

Co n f i g u r e f o r t r an sp ar en t M -Bu s

This section describes how to enable transparent M -Bus over TCP or


dial-up GSM data.

7 .1

Co n f i g u r e f o r t r an sp ar ent M -Bu s o v er
GSM d at a

SMS to CMe2100 product: qset csd on tmbus <baud>


Example: qset csd on tmbus 300
The CMe2100 product w ill acknowledge with an SMS receipt.
Available baud rates are 300 and 2400. The calling party should use 8
data bits, even parity and 1 stop bit (8E1).
CM e2100 Quick M anual English v3.0

Page | 21

7 .2

Co n f i g u r e f o r t r an sp ar ent M -Bu s o v er TCP


o n b au d 3 0 0

SMS to CMe2100 product: qset tmbus1 on

Or to turn off transparent server:


SMS to CMe2100 product: qset tmbus1 off
The CMe2100 product w ill acknowledge with an SMS receipt. The product
w ill listen for incoming connections on TCP port 300.

7 .3

Co n f i g u r e f o r t r an sp ar ent M -Bu s o v er TCP


o n b au d 2 4 0 0

SMS to CMe2100 product: qset tmbus2 on


The CMe2100 product w ill acknowledge with an SMS receipt. The product
w ill listen for incoming connections on TCP port 2400.
Page | 22

Support: +46 300 434300 ? support@elvaco.com

Reset t o f ac t o r y d ef au l t

In order to reset the CM e2100 product configuration to factory default,


press and hold the button on pow er-up until the green and red LED
lights flashes fast. Then release the button and the CMe2100 product w ill
reset to factory default configuration and restart.
The CMe2100 product can also be reset to factory default using SMS.
SMS to CMe2100 product: factoryreset
Example: factoryreset
The CMe2100 product w ill acknowledge with an SMS receipt.

CM e2100 Quick M anual English v3.0

Page | 23

Ch ang i n g c on f i g u r at i o n

9 .1

M an u all y set net w or k p ar am et er s

How to manually set netw ork configuration if the Auto APN is not
available or a specific netw ork setting is needed, i.e. static public IP APN:
SMS to CMe2100 product: qset net <apn> <user> <password>
Example: qset net online.telia.se guest guest
The CMe2100 product w ill acknowledge with an SMS receipt.
SMS to revert to Auto APN: qset net
Reverting to Auto APN also reverts to Auto SMTP.

Page | 24

Support: +46 300 434300 ? support@elvaco.com

9 .2

M an u all y set SM TP ser v er

How to manually set SMTP server if the Auto SMTP is not available or a
specific SMTP server setting is needed:
SMS to CMe2100 product: qset email <recipients> <smtp

server> <smtp port> <user> <password>


Example: qset email name@domain.com

smtpserver.domain.com 25 user password


The CMe2100 product w ill acknowledge with an SMS receipt.
SMS to revert to Auto SMTP: qset email
Reverting to Auto SMTP also reverts to Auto APN.

CM e2100 Quick M anual English v3.0

Page | 25

9 .3

Ch an g e sl av e l o g i nt er v al

How to change the interval for the CMe2100 product to read and store
values of installed slaves:
SMS to CMe2100 product: sch storevalue <interval>
Example: sch storevalue 10min
The CMe2100 product w ill acknowledge with an SMS receipt.
Available intervals: 1m in, 5min, 10min, 15m in, 20min, 30min, 1hour,
12hour, 1day, 1w eek, 1month

Page | 26

Support: +46 300 434300 ? support@elvaco.com

9 .4

Ch an g e M -Bu s sear c h m o d e an d b au d r at e

How to change the M -Bus search configuration:


SMS to CMe2100 product: qset mbus <searchmode>

<searchbaud>
Example: qset mbus primary,secondary 300,2400
The CMe2100 product w ill acknowledge with an SMS receipt.
Available searchmode: prim ary,secondary
Available searchbaud: 300, 600, 1200, 2400, 4800, 9600

CM e2100 Quick M anual English v3.0

Page | 27

9 .5

Ch an g e r ep o rt sc h ed ul e o r t em pl at e

How to change the interval and template for a report configuration:


SMS to CMe2100 product: sch report1 <interval> [template]

Or to turn off report schedule:


SMS to CMe2100 product: sch report1 off
Example: sch report1 10min 1104
The CMe2100 product w ill acknowledge with an SMS receipt.
Available intervals: 1m in, 5min, 10min, 15m in, 20min, 30min, 1hour,
12hour, 1day, 1w eek, 1month
Available templates: See page 42. Leaving out the template parameter,
w ill keep current template setting.
Changing report interval doesnt change slave log interval, see page 26.
Page | 28

Support: +46 300 434300 ? support@elvaco.com

9 .6

Get p r o d u c t st at u s i n f or m at i o n

How to get a variety of information on the CM e2100 product:


SMS to CMe2100 product: status <request>
Example: status net
The CMe2100 product w ill respond w ith an SM S of common status
information.
Available requests: common, prepaid, net, module, ver

CM e2100 Quick M anual English v3.0

Page | 29

9 .7

Ch an g e t im e U TC o f f set

How to set the local time offset from UTC:


SMS to CMe2100 product: set common.time.utcoffset=<offset>
Example: set common.time.utcoffset=2
The CMe2100 product w ill acknowledge with an SMS receipt.
Offset range: -11 to 11
CMe2100 currently does not support daylight savings.

Page | 30

Support: +46 300 434300 ? support@elvaco.com

9 .8

Req u est a sp eci f ic r ep or t

How to manually request a report w ithout scheduling the report:


SMS to CMe2100 product: report <interval> <template>
or
SMS to CMe2100 product: report <template>
Example: report 1004
The CMe2100 product will send report 1004 (System log) to configured
E-Mail recipients.
Available intervals: 1m in, 5min, 10min, 15m in, 20min, 30min, 1hour,
12hour, 1day, 1w eek, 1month
Available templates: See page 42.

CM e2100 Quick M anual English v3.0

Page | 31

9 .9

Ch an g e p assw o r d

How to change passw ord for security level 1 to enable passw ord
security for all communication w ith the CMe2100 product:
SMS to CMe2100 product:

set common.security.password1=<password>
Example: set common.security.password1=1234
The CMe2100 product w ill acknowledge with an SMS receipt.
Default passw ord is blank. Default passw ord for security level 2 is 22 22
and for security level 3 is 3 333 . When passw ord for security level 1 is
set, all SM S m essages must start w ith <passw ord> and new line.

Page | 32

Support: +46 300 434300 ? support@elvaco.com

1 0 LED i n d i c at i o n s
The CMe2100 product is equipped w ith three LEDs. The red LED
indicates error, the green LED show currents operation and the yellow
LED indicates GSM/GPRS modem activity. See follow ing pages for LED
indication explanations. Green and Red operation LEDs:
Off/Restart

Green LED (Off)


Red LED (Off)

Pow er On

Green LED (On)


Red LED (On)

Normal operation

Green LED (Short dip)


Red LED (Off)

CM e2100 Quick M anual English v3.0

Page | 33

Green and Red operation LEDs continued:


M-Bus short-circuit

Green LED (Short dip)


Red LED (On)

No SIM installed

Green LED (Short dip)


Red LED (50/50)

No GSM netw ork

Green LED (Short dip)


Red LED (Short flash)

Page | 34

Support: +46 300 434300 ? support@elvaco.com

11

Tr o u b l esho o t i n g

1 1 .1 A ll LED s ar e p erm an en t l y of f
There is a problem w ith the supply voltage. Please verify 100-240 VAC. If
the problem persists, the product may be m alfunctioning. Please contact
Elvaco support.

1 1 .2 Red LED is p er m an ent l y o n


This indicates an error on the M -Bus 2-w ire bus.
Please verify no short-circuit of the M -Bus bus. The voltage of the bus
should be betw een 24 VDC and 30 VDC.

CM e2100 Quick M anual English v3.0

Page | 35

1 1 .3 Red LED is f l ashi n g 5 0/5 0


This indicates a SIM card error. Please verify:
SIM card has no PIN code activated
SIM card is activated
SIM card contact areas are clean
LED Indication

Green LED(Short dip)

No SIM installed

Red LED(50/50)

Page | 36

Support: +46 300 434300 ? support@elvaco.com

1 1 .4 Red LED is f l ashi n g sh or t


No GSM network coverage/unable to attach to GSM network. Please verify:
Antenna installation
o Installation w ith bad netw ork coverage sometimes requires an
external antenna. Do not mount antenna inside metallic cabinets
SIM card activated
SIM card contact areas are clean
LED Indication

Green LED(Short dip)

No GSM netw ork

Red LED(short flash)

CM e2100 Quick M anual English v3.0

Page | 37

11.5 The product does not respond t o SM S


request s
This error may depend on many things. Please verify:

Product is pow ered up


LEDs are show ing normal operation and netw ork coverage
Security access codes may be used; verify correct access code
If a prepaid SIM card is used, balance may be zero

If the problem persists, try resetting the product to factory defaults, see
page 23.

Page | 38

Support: +46 300 434300 ? support@elvaco.com

1 1 .6 In st al l c o m m an d d o es n o t f i n d an y m et ers
Please verify your M -Bus slave configuration:

Voltage over M -Bus slave should be betw een 24 VDC and 30 VDC
All M -Bus slaves must have unique secondary addresses
M-Bus slave baud rates
o Default search baud is 2400, please see command qset m bu s,
page 27, how to change the searched baud rates

CM e2100 Quick M anual English v3.0

Page | 39

1 1 .7 St at u s r ep o rt i n d i c at es n o A PN
This may be due to Auto APN detection has no information about your
netw ork provider. Please contact your netw ork provider for the follow ing
internet access information:

APN
Optional APN username
Optional APN passw ord
Set network parameters manually using command qset net , see page 24.

Page | 40

Support: +46 300 434300 ? support@elvaco.com

1 1 .8 E-M ai l r ep o rt i n g i s c o n f i g u r ed b u t n o
E-M ai l s ar e sen t
This may be due to the follow ing reasons:

No or w rong SMTP server is auto detected. Please verify comm and


st at us, see page 29. If the SMTP server is not set, please set the
SMTP server manually using command qset em ai l , see page 25.
No valid recipients set. Set recipients w ith command qset em ai l ,
see page 25.
Report is not correctly activated, please configure E-Mail reports w ith
command sc h , see page 28.
If you still have problems getting your CMe2100 running, please contact
Elvaco support, see page 5.
CM e2100 Quick M anual English v3.0

Page | 41

12

Rep o r t t em p l at es

Get the complete report template documentation on Elvaco w eb site.


Report Id Description
SMS Reports
1
Installation report
E-Mail Reports
1001
Installation report (HTM L)
1002
Installation report (PLAIN)
1003
System report (HTM L)
1004
System log report (HTM L)
1005
Event report (HTM L)
1006
Log report (HTML, machine friendly in CSV attached file of EMail)
1007
Monitor event report (HTM L)
1101
Value report (HTM L, human readable in body of E-M ail)
Page | 42

Support: +46 300 434300 ? support@elvaco.com

1102
1103
1104
1105
1106
1107
1108

Value report (HTM L, machine friendly in body of E-Mail)


Value report (HTM L, machine friendly in CSV attached files of E-M ail)
Value report (HTML, hum an readable in CSV attached files of E-M ail)
Value report (HTM L, machine friendly in CSV attached files of E-M ail

+ extra colum n header indicator)


Value report (HTM L, machine friendly with zip extension (not zipped)
attached files of E-Mail + extra colum n header indicator)
Value report with energy consum ption (HTM L, m achine friendly in
CSV attached files of E-M ail)
Value report (HTM L, machine friendly in CSV attached file of E-M ail +
extra colum n header indicator)

FTP Reports
2101
Value report
2102
Value report
2103
Value report
2104
Value report
2105
Value report

(hum an readable in a single CSV files)


(machine friendly CSV files)
(machine friendly CSV files)
(hum an readable CSV files)
(hum an readable CSV files + extra colum n header

indicator)
CM e2100 Quick M anual English v3.0

Page | 43

2108

Value report (machine friendly in CSV file + extra column header


indicator)

HTTP Reports
3101
Value report
3102
Value report
3103
Value report
3104
Value report
3105
Value report

(hum an readable in a single CSV POST)


(machine friendly CSV POSTs)
(machine friendly CSV POSTs)
(hum an readable CSV POSTs)
(hum an readable CSV POSTs + extra colum n header

indicator)

3108

Value report (machine friendly CSV POST + extra colum n header


indicator)

Page | 44

Support: +46 300 434300 ? support@elvaco.com

13

Co m m an d l i st i n g

Get the complete command description documentation from Elvaco w eb


site.
Command name
command1
command2
command3
command4
command5
device
factoryreset
fwupdate
get
install
login

Description
User definable command 1.
User definable command 2.
User definable command 3.
User definable command 4.
User definable command 5.
Send M-Bus command directly to slave
Restore all settings to factory default
Update product firmware
Get a configuration key
Search for installed slaves
Login in console or SMS mode

CM e2100 Quick M anual English v3.0

Page | 45

maintenance
monitor1
monitor2
monitor3
monitor4
monitor5
qset
reboot
report
report1
report2
report3
report4
report5
set
sch
Page | 46

Maintenance task
User definable monitor 1.
User definable monitor 2.
User definable monitor 3.
User definable monitor 4.
User definable monitor 5.
Quick set configuration
Reboot product
User definable report.
User definable report 1
User definable report 2
User definable report 3
User definable report 4
User definable report 5
Set a configuration key
Schedules a command
Support: +46 300 434300 ? support@elvaco.com

status
storevalue
sysreport
logreport
sync
timesync

Get status information from the product


Read and store value of installed slaves
Sends system report
Sends system log report
Synchronize configuration with synchronize server
Synchronize time with internet timeserver

CM e2100 Quick M anual English v3.0

Page | 47

14

Tec h n i c al sp ec i f i c at i o n s

1 4 .1 Ch ar act eri st i c s
Mechanics
Casing material
Protection class
Dimensions
Weight
Connection MBus
Electrical
Nominal voltage
Power supply
Voltage range
Page | 48

Value

Unit

Com ments

Polyamide
IP20
100x65x36
120
Pin terminal

mm
g
-

Solid wire 0.6-0.8 mm

100-240
Screw
terminal
-10 to +10

VAC
%

Cable 0-2.5 mm 2, 0.5 Nm


tightening torque
Of nominal voltage

Support: +46 300 434300 ? support@elvaco.com

Frequency
Power
consum ption
(Max)
Power
consum ption
(Nom)
Installation
category
GSM/GPRS
GPRS Class
Band
Environmental
Operating
temperature
range
Storage

50/60
<2.5

Hz
W

<1

CAT IV

Up to 12
850/900/
1800/1900

MHz

-20 to +55

-40 to +85

CM e2100 Quick M anual English v3.0

Page | 49

temperature
range
Operating
humidity max.
Pollution
Operating
altitude
Usage
User interface
Green LED
Red LED
Yellow LED
Push button
M-Bus
M-Bus standard
Page | 50

80

%RH

Degree 2
0-2000

Meters

Indoor use
only
Power
Error
GSM status
Factory
reset
EN 13757

Tem peratures up to 31C,


decreasing linearly to
50%RH at 40C

can be extended with IP67


enclosure for outdoor use

Full M-Bus decoder


Support: +46 300 434300 ? support@elvaco.com

implemented
M-Bus baud rate
Transparent
M-Bus
Maximum
connected MBus slaves
Maximum cable
length
IR Interface
Pass Through
Com patibility

300, 2400
Listening
server on
TCP and
GSM data
8

Bit/s
-

1000

Yes
No
All standard
M-Bus
meters, all
ABB meters
with IR

CM e2100 Quick M anual English v3.0

Can be extended using


CMeX10 Series

Page | 51

interface,
CMeX
Series
products
General
Data storage

~1.4

MByte

Real time clock


Backup

12

Real time clock


Accuracy
Script Engine

<2

s/day

Firmware update

Using
GSM/GPRS/

Page | 52

Data storage for meter


data and custom report
configuration
Num ber of hours real
time clock resumes
running without power
Intelligent script engine
for active content
generation

Support: +46 300 434300 ? support@elvaco.com

Software update
Integration
Transparent MBus static IP
Transparent MBus
E-mail
FTP
HTTP

HTTP
Using
GSM/GPRS/
HTTP

TCP
GSM
CSD/raw MBus data
SMTP
Standard
FTP client
Standard
HTTP and
HTTPS
client, POST

CM e2100 Quick M anual English v3.0

Page | 53

& GET
Configuration

Approvals
EMC
Safety

Page | 54

SMS, HTTP,
FTP, GSM
CSD, Telnet

EN 61000-62, EN 610006-3
EN 61010-1,
CAT IV

Support: +46 300 434300 ? support@elvaco.com

15

Saf et y an d en v i r o n m en t

The follow ing safety precautions must be observed during all phases of
the operation, usage, service or repair of any CMe2100 product. Users of
the product are advised to convey the follow ing safety information to
users and operating personnel and to incorporate these guidelines into
all manuals supplied w ith the product. Failure to comply w ith these
precautions violates safety standards of design, manufacture and
intended use of the product. Elvaco AB assumes no liability for
customers failure to comply w ith these precautions.
When in a hospital or other health care facility, observe the restrictions
on the use of mobiles. Sw itch the product off, if instructed to do so by
the guidelines posted in sensitive areas. Medical equipment m ay be
sensitive to RF energy.

CM e2100 Quick M anual English v3.0

Page | 55

The operation of cardiac pacemakers, other implanted medical


equipment and hearing aids can be affected by interference from cellular
terminals or mobiles placed close to the product. If in doubt about
potential danger, contact the physician or the m anufacturer of the
product to verify that the equipment is properly shielded. Pacemaker
patients are advised to keep the product aw ay from the pacemaker,
w hile it is on.
Sw itch off the product before boarding an aircraft. Make sure it cannot
be sw itched on inadvertently. The operation of w ireless appliances in an
aircraft is forbidden to prevent interference w ith communication
systems. Failure to observe these instructions may lead to the suspension
or denial of cellular services to the offender, legal action, or both.
Do not operate the product in the presence of flammable gases or
fumes. Sw itch off the product w hen you are near petrol stations, fuel
depots, chemical plants or w here blasting operations are in progress.
Page | 56

Support: +46 300 434300 ? support@elvaco.com

Operation of any electrical equipment in potentially explosive


atmospheres can constitute a safety hazard.
Your product receives and transmits radio frequency energy w hile
sw itched on. Remember that interference can occur if it is used close to
TV sets, radios, computers or inadequately shielded equipment. Follow
any special regulations and alw ays sw itch off the product w herever
forbidden, or w hen you suspect that it may cause interference or
danger.

IMPORTANT!
CMe2100 operates using radio signals and cellular netw orks. Because of
this, connection cannot be guaranteed at all times under all conditions.
Therefore, you should never rely solely upon any w ireless product for
essential communications, for example emergency information.

CM e2100 Quick M anual English v3.0

Page | 57

16

A c c esso r i es and si m i l ar p r o d u c t s

Elvaco provides a complete product range to meet various demands.


A c c essor i es:
Product
External
Antenna
CMeX10
CMeX20
CMeX30
CMeX40
CMa10

Page | 58

Description
External antenna to increase GSM signal strength
M-Bus master Connect up to 32 M -Bus slaves
M-Bus activator Enable standard M -Bus
comm unication to ABB electricity meters with IR
interface
M-Bus D/A m odule Steer 0 to 10 V or 0 to 20 mA
output
M-Bus I/O module Input/output to peripheral devices
M-Bus temperature and humidity sensor for indoor use
with display
Support: +46 300 434300 ? support@elvaco.com

CMa11
CMa20
M-Bus Splitter

M-Bus temperature and humidity sensor for indoor use


without display
M-Bus temperature and humidity sensor for outdoor
use
Share one to four M -Bus meter between two M -Bus
masters

Si m i l ar pr oduc t s:
Product
CMi2110
CMi2120
CMi2130
CMe3000

Description
GPRS M-Bus com munication module integrated in
Landis+Gyr UH50 meter and 8 M -Bus slaves
GPRS M-Bus com munication module integrated in
Landis+Gyr E350 meter and 8 M-Bus slaves
GPRS M-Bus com munication module integrated in Itron
ECHO II / CF meters and 8 M-Bus slaves
TCP/IP M-Bus com munication module for ABB
electricity meters with IR interface and 8 M -Bus slaves

CM e2100 Quick M anual English v3.0

Page | 59