WATER INDUSTRY

MECHANICAL AND ELECTRICAL


SPECIFICATION 3.02(A)
PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN
WIMES 3.02(A)
ISSUE 1
JULY 2008

Copyright 2008, ESR Technology. All rights reserved. No part of this document may be reproduced in any
form electronic or mechanical, including photocopying, recording or any other information storage and
retrieval system without permission in writing from the Pump Centre.

The Pump Centre is a Centre of Excellence within ESR Technology,


one of the UKs leading engineering, safety and risk consultancies. ESR
Technology provides independent technical expertise to help its
customers ensure asset integrity, improve machine reliability, manage
safety and risk and transfer best practice.

WATER INDUSTRY
MECHANICAL AND ELECTRICAL
SPECIFICATION 3.02(A)

PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Prepared by:
Roger Marlow

Pump Centre

With technical support and co-operation from the WIMES Electrical Working Group
consisting of:
J Hughes
P Davison
J Summers
T Strong
T Nicol
S Ellis
R Lennox
M Jones
A Bailey/D Watkins
K Waud
C Lomax
C Mildren
R Rennie

Anglian Water
Northern Ireland Water
Dwr Cymru
Northumbrian Water
Scottish Water
Severn Trent Water
South West Water
Southern Water
Thames Water
Three Valleys Water
United Utilities
Wessex Water
Yorkshire Water

Please Note
This Specification will be reviewed periodically to take account of feedback from
Water Companies/Suppliers. If changes to the document are necessary, it will be
re-issued.
Acknowledgments
The Authors of this Specification are grateful to Profibus International for their
guidance and assistance in the preparation of this document.

WIMES 3.02 (A) PROFIBUS & OPTICAL FIBRE NETWORK DESIGN

Page 1

CONTENTS
1.0 SCOPE

2.0 PROFIBUS DP NETWORKS


2.1 General
2.2 Network Design
2.2.1 General
2.2.2 Topology
2.2.3 Termination
2.2.4 Spur Lines
2.2.5 Cable Length Considerations (Based on a Design Baud Rate of 1.5 Mbit/s)
2.3 Component Selection
2.4 Network Installation
2.5 Earthing and Equipotential Bonding

2
2
2
2
2
4
5
5
5
5
5

3.0 PROFIBUS PA NETWORKS


3.1 General
3.2 Network Design
3.2.1 General
3.2.2 Topology
3.2.3 Termination
3.2.4 Spur Lines
3.2.5 Cable Length Considerations
3.2.6 Intrinsically Safe Considerations - Profibus PA in Hazardous Areas
3.3 Component Selection
3.4 Network Installation
3.5 Earthing and Equipotential Bonding

5
6
6
6
6
7
7
8
8
8
8
8

4.0 OPTICAL FIBRE NETWORKS


4.1 General
4.2 Network Design
4.3 Component Selection
4.4 Network Installation

8
8
9
9
9

5.0 DESIGN VERIFICATION AND NETWORK TESTING

APPENDIX A - SPECIFICATIONS AND STANDARDS REFERENCED

10

APPENDIX B GUIDANCE NOTES

11

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Page 2

1.0 SCOPE
This Specification defines the requirements for the design of Profibus DP, Profibus PA
and optical fibre networks in the Water Industry.
The installation of Profibus DP, Profibus PA and optical fibre networks is covered by
Section 9.4 of WIMES 3.02.
2.0 PROFIBUS DP NETWORKS
Profibus DP (decentralised periphery) is one of the well proven, widely accepted Profibus
family of fieldbus communications protocols. It utilises EIA RS 485 as its transmission
technology; which is a two wire data transmission technology using screened twisted pair
cable.
2.1 General
1. The design of the network shall comply with the latest editions (current at the time of
Tender) of all relevant International, Harmonised European and British Standards,
including:
a) IEC 61158-2 - Industrial communication networks - Fieldbus specifications
Part 2: Physical layer specification and service definition; and
b) BS EN 50174-1: 2001 - Information technology. Cabling installation.
Specification and quality assurance.
Refer to Appendix A for a list of the Regulations, Standards and Specifications
referenced in this Specification.
2.2 Network Design
2.2.1 General
1. The network shall be designed for a baud rate of 1.5 Mbits/s.
2.2.2 Topology
2.2.2.1 General
1. The network shall comprise a number of segments.
2. Each segment shall comprise a number of devices (or nodes) and shall be configured
as a linear bus with the network cable daisy chaining from device to device.

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Page 3

3. The specification of the EIA RS 485 data transmission system dictates that a
maximum number 32 devices (masters and slaves) may be incorporated within a
given segment. In practice, however, the number of devices incorporated within a
given segment shall be limited to 25 to allow for:
a) Spare segment capacity i.e. the incorporation of additional devices;
b) Network expansion (necessitating the use of repeaters (refer to Section 2.2.2.2,
below)); and
c) The connection of diagnostic/programming equipment to the segment.
4. To facilitate network analysis and troubleshooting, each segment shall incorporate at
least one connector with a piggyback socket, to enable monitoring and programming
equipment to be connected to the network without causing network disruption. The
piggyback socket shall only be attached to a device which can supply the required
operating current to the monitoring and programming equipment. Piggyback sockets
shall not be used for adding further devices to the network, as this would introduce a
spur line.
2.2.2.2 Use of Repeaters/OLMs
1. If there is a requirement to incorporate more than 25 devices within the network, the
network may be extended (thus increasing the number of segments) by the use of
repeaters or optical link modules (OLMs) as shown in Figure 1, below:

Figure 1 Use of Repeaters and Optical Link Modules to Produce a Complex


Network Structure

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Page 4

2. Repeaters/OLMs may also be incorporated into the network when:


a) There is a need to electrically isolate sections of the network; and/or
b) A segment exceeds the maximum permissible cable length for a baud rate of
1.5 Mbit/s.
3. Repeaters/OLMs shall be powered at all times.
4. It should be noted that repeaters/OLMs do count towards the 25 device limit for a
given segment.
5. A maximum of 4 repeaters/OLMs shall be used between any master and slave device,
unless the repeater/OLM manufacturers specifications state otherwise.
6. Repeaters shall be connected to the network so that the piggyback socket can be
used to examine the signals on the outgoing segment. This normally means that
the DP 1 repeater connection will be used for the outgoing segment and the DP2
connection will be used for the incoming segment.
2.2.3 Termination
1. To avoid reflections from the ends of the cables, the network shall be effectively
terminated.
2. Network termination shall be provided by separate active terminators. The advantage
of using separate active terminators, as opposed to termination resistors within
connectors, is that any device can be removed/replaced without disturbing the
network.
3. Active terminators shall be installed at the beginning and the end of each segment, as
shown in Figure 2 below:

AT

Slave

Slave

Master

Slave

Slave

AT

Slave

Slave

Slave

No additional terminations

Slave

Slave

AT Active Terminator
R - Repeater

Figure 2 Use of Separate Active Terminators


Note If the master is located at the beginning of a segment, it shall usually
incorporate the active terminator.

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Page 5

4. Active terminators shall be powered at all times (refer to Guidance Notes).


5. Active terminators do not count towards the 25 device limit for a given segment.
6. To avoid additional reflections, termination resistors within connectors or devices shall
always be disabled. This shall normally be done after all network testing and
commissioning activities have been completed.
2.2.4 Spur Lines
1. As far as reasonably possible, spur lines shall be avoided within the network because
they can cause reflections. If spur lines cannot be avoided, the total length of all spur
lines within an individual network segment shall not exceed 6.7 m (based on a design
baud rate of 1.5 Mbit/s). Within this figure of 6.7 m, suitable allowance shall be made
for the lengths of any internal spurs which may exist within devices (e.g. actuators
etc.) and also for any test equipment which may be connected to the network.
2.2.5 Cable Length Considerations (Based on a Design Baud Rate of 1.5 Mbit/s)
1. The maximum length of an individual network segment shall be 200 m.
2. To avoid reflections, there shall be a minimum cable length of 1 m between any two
devices.
2.3 Component Selection
Refer to Section 9.4.2.2 of WIMES 3.02.
2.4 Network Installation
Refer to Section 9.4.2.3 of WIMES 3.02.
2.5 Earthing and Equipotential Bonding
Refer to Section 9.4.2.4 of WIMES 3.02.
3.0 PROFIBUS PA NETWORKS
Profibus PA (Process Automation) is one of the well proven, widely accepted Profibus
family of fieldbus communications protocols.
Profibus PA networks utilise MBP (Manchester-encoded, Bus Powered) transmission
technology, which is a 2-wire technology combining the functions of data transmission and
power supply in a single network cable.

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Page 6

3.1 General
1. The design of the network shall comply with the latest editions (current at the time of
Tender) of all relevant International, Harmonised European and British Standards,
including:
a) IEC 61158-2 - Industrial communication networks - Fieldbus specifications
Part 2: Physical layer specification and service definition; and
b) BS EN 50174-1: 2001 - Information technology. Cabling installation.
Specification and quality assurance.
Refer to Appendix A for a list of the Regulations, Standards and Specifications
referenced in this Specification.
3.2 Network Design
3.2.1 General
1. The network is designed to operate at a baud rate of 31.25 Kbits/s.
3.2.2 Topology
1. A typical Profibus PA segment is shown in Figure 3 below:

Figure 3 Profibus PA Topology


2. As shown in Figure 3, each segment shall be configured in a trunk and spur topology,
with each device (or slave) being connected to the trunk cable via a spur cable and
T-connector/junction box.

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Page 7

3. The specification of the MBP transmission technology dictates that a maximum


number of 32 devices may be incorporated within a given segment. In practice,
however, the number of devices shall generally be limited to 20 to allow a maximum
spur length of 30 m between the trunk cable and a given device (refer also to
Section 3.2.4).
4. As shown in Figure 3, each segment shall be connected to the Profibus DP network
via a link/interface module and one or more DP/PA couplers, which will allow the DP
network to run at high speed, independently of the PA network baud rate. A single
DP/PA coupler shall be used for simple networks, whereas a link/interface module and
multiple DP/PA couplers shall be used for more complex networks. A number of
DP/PA couplers may be connected to each link/interface module (refer to
Guidance Notes).
5. The link/interface module provides power for the PA network and shall therefore be
powered at all times.
3.2.3 Termination
1. To avoid reflections from the ends of the cable, each segment shall be terminated at
both ends of the segment and nowhere else with a suitable terminator which shall
comprise a capacitor and resistor in series connected between the cable cores.
2. As shown in Figure 3, terminators shall be installed at the ends of the trunk cable only
(i.e. not at the ends of any spur cables). Most DP/PA couplers incorporate a built in
terminator which, by default, will ensure that a terminator is present at one end of the
trunk cable. The other terminator shall then be installed in the last or furthest device,
or preferably in the last junction box.
3.

Terminators shall not be powered.

3.2.4 Spur Lines


1. The recommended length of each individual spur cable shall comply with the following
table:
Number of Spur Lines

25 to 32
19 to 24
15 to 18
13 to 14
1 to 12

Maximum Spur Length


(non-intrinsically safe
installation)
1m
30 m
60 m
90 m
120 m

Maximum Spur Length


(intrinsically safe
installation)
30 m

Note - It is not normally practical to incorporate more than 12 devices in an IS network,


due to the limitations imposed on the power supply.

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Page 8

3.2.5 Cable Length Considerations


1. The maximum length of an individual network segment (including all branches and
spur cables) shall not exceed 1900 m, however, the particular characteristics of the
segment power supply and/or requirements for intrinsic safety may reduce this
significantly.
3.2.6 Intrinsically Safe Considerations - Profibus PA in Hazardous Areas
1. PA segments shall be designed to be intrinsically safe by ensuring that all devices are
certified for intrinsic safety and that the cable and terminations also meet the
requirements of intrinsic safety.
2. The Fieldbus Intrinsically Safe Concept (FISCO) (as detailed in BS EN 60079-27)
shall be used in system design (refer to Guidance Notes).
3.3 Component Selection
Refer to Section 9.4.3.2 of WIMES 3.02.
3.4 Network Installation
Refer to Section 9.4.3.3 of WIMES 3.02.
3.5 Earthing and Equipotential Bonding
Refer to Section 9.4.3.4 of WIMES 3.02.
4.0 OPTICAL FIBRE NETWORKS
4.1 General
1. The design of the network shall comply with the latest editions (current at the time of
Tender) of all relevant International, Harmonised European and British Standards,
including:
a) BS EN 50174-1:2001 - Information technology. Cabling installation. Specification
and quality assurance.
Refer to Appendix A for a list of the Regulations, Standards and Specifications
referenced in this Specification.

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Page 9

4.2 Network Design


1. The usual approach in designing an optical fibre network shall be as follows:
a) Determination of the transmission path length;
b) Selection of the most appropriate type of optical fibre cable according to the
required transmission path length;
c) Selection of suitable devices for the chosen optical fibre cable; and
d) Selection of suitable connectors for the chosen devices.
2. Plastic Optical Fibres or PCF/HCS (Plastic Clad silica Fibre)/Hard Clad silica Fibre)
optical fibres may be used at the same optical interface. Multimode and single mode
optical fibres require their own interface design.
4.3 Component Selection
Refer to Section 9.4.4.1 of WIMES 3.02.
4.4 Network Installation
Refer to Section 9.4.4.2 of WIMES 3.02.
5.0 DESIGN VERIFICATION AND NETWORK TESTING
Refer to Section 9.4.5 of WIMES 3.02.

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS AND OPTICAL FIBRE NETWORK DESIGN

Page 10

APPENDIX A - SPECIFICATIONS AND STANDARDS REFERENCED


Standards
IEC Series
IEC 61158-2 - Industrial communication networks - Fieldbus specifications Part 2:
Physical layer specification and service definition;
BS EN Series
BS EN 50174-1: 2001 - Information technology. Cabling installation. Specification and
quality assurance;
BS EN 60079-27 - Electrical apparatus for explosive gas atmospheres. Fieldbus
intrinsically safe concept (FISCO) and fieldbus non-incendive concept (FNICO).
Specifications
WIMES
WIMES 3.02 Low Voltage Electrical Installations.

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS & OPTICAL FIBRE NETWORK DESIGN

Page 11

APPENDIX B GUIDANCE NOTES


Clause 2.2.3.4
Active terminators should be used to provide segment termination instead of the
termination resistors provided in the connectors/devices.
Active terminators are
standalone Profibus DP components and require a 24 V DC power supply.
Clause 3.2.2.4
The DP/PA link acts as a slave on the DP network and a master on the PA network,
decoupling all data communication on the network. This means that DP and PA networks
can be combined without influencing the processing performance of the DP network.
The DP/PA link enables the addressing capacity of the network to be considerably
increased due to the fact that a large number of field devices can be connected to a
DP/PA link, but the link only reserves one DP address.
Ex and non-Ex rated PA segments can be connected to the DP network by connecting Ex
and non-Ex versions of the DP/PA coupler into the link/interface module. Ex couplers
incorporate protection barriers to limit the current and voltage supplied to an IS segment.
Connection of the link/interface module to the DP network is via a single 9-pin Sub-D
connector (the DP interfaces of the DP/PA couplers are redundant).
Clause 3.2.6.2
Significant care should be taken when designing segments if PROFIBUS PA is to be used
in hazardous areas. The FISCO (Fieldbus Intrinsically Safe Concept) model can make
planning, installing and expanding PROFIBUS networks in hazardous areas significantly
easier. The model is based on the concept that a network segment can be considered
intrinsically safe (with no separate intrinsic safety calculation required) if the voltage,
current, power, inductance and capacitance values of the relevant components (cable,
segment couplers, bus terminators) are within the boundaries of prescribed FISCO limits
and all field devices are FISCO certified.
FISCO power supplies limit the available output power to a given segment, however, in
addition, the voltage is limited which allows greater current to be delivered to the segment,
hence more devices can be used.
The FISCO model enforces the following restrictions:

Each segment has only one source of power;


Each field device consumes a constant basic current of at least 10 mA;
The field devices act as passive current sinks; even when a station is transmitting, no
power is fed into the bus;
Device internal capacitance and inductance is limited to < 5 nF and 10 H;
The total cable length limited to 1000 m (including spurs); and
Individual spur lines are limited to a maximum length of 30 m.

ISSUE 1

JULY 2008

WIMES 3.02(A) PROFIBUS & OPTICAL FIBRE NETWORK DESIGN

Page 12

Components and instrumentation by various manufacturers can be operated on the same


segment provided that all of them meet the requirements described. Intrinsic safety is
considered proven if all stations on an electrical circuit have been certified in accordance
with FISCO as defined in IEC/BS EN 60079-27.
Intrinsically safe DP/PA couplers incorporate barriers that provide current and voltage
limiting (a typical coupler for EEx ia gas group IIC might provide 110 mA at 13 V which
would limit the number of devices to 7 or 8 per segment (compared to 32 devices for a
non-hazardous application).

ISSUE 1

JULY 2008

For further information on the Water Industry Mechanical and Electrical Specifications please
contact:
The Pump Centre
ESR Technology plc
Whittle House
Birchwood Park
Warrington
Cheshire
WA3 6FW
Telephone:
Facsimile:
Email:
WWW:

+44 (0) 1925 843457


+44 (0) 1925 843500
roger.marlow@esrtechnology.com
www.pumpcentre.com/wimes.htm

You might also like