DK Cable Junction Boxes

DK Cable Junction Boxes


- 1.5 up to 240 mm
- Degree of protection IP 54-67
- Cable Junction Boxes are VDE tested in accordance with IEC 60670-22

Assembling
videos

15

DK Cable Junction Boxes


Content

Criteria for selecting


Box walls

18 - 19
20

With FIXCONNECT plug-in technology for copper conductors


from 1.5 up to 16 mm2
IP 65/IP 55
cable entry via metric knockouts

22

With or without terminals


from 1.5 up to 240 mm2
IP 65/IP 55
cable entry via metric knockouts
- with terminals for copper conductors
- without terminals

24 - 29
30 - 31

Box walls without knockouts


from 1.5 up to 50 mm2
IP 65
box walls without knockouts, can be drilled individually for customized requirements
- without terminals
- without terminals, for electrical equipment up to 63 A
- Accessories

33 - 34
35 - 36
37 - 39

Cable entry via elastic membranes and integrated M20 thread


up to 4 mm2
IP 55
- without terminals
- with terminals for copper conductors

41
41

Cable entry via cable, cable trunking and conduits


from 1.5 up to 4 mm2
IP 54
- with terminals for copper conductors
- without terminals, Accessories

43
44

Cable entry via elastic membranes


from 1.5 up to 4 mm2
IP 55
- with terminals for copper conductors, grey RAL 7035
- without terminals, grey RAL 7035
- with terminals for copper conductors, white RAL 9016
- without terminals, white RAL 9016, Accessories

46
47
48
49

Cable entry via elastic membranes from the rear and by box walls and lid
from 1.5 up to 2.5 mm2
IP 55
for the clip-on attachment
- with terminals for copper conductors, grey RAL 7035
- without terminals, grey RAL 7035
- with terminals for copper conductors, white RAL 9016
- without terminals, white RAL 9016

51
51
52
52

For aluminium- (Alu) and copper (Cu) conductors


from 1.5 up to 240 mm2
IP 65/55
cable entry via metric knockouts
- with terminal blocks for aluminium- (Alu) and copper (Cu) conductors

54 - 60

"Weatherproof" - for outdoor installation - harsh environment and/or outdoor


from 1.5 up to 50 mm2
IP 66
cable/conduit entry via metric knockouts
- with / without terminals, colours grey RAL 7032, black RAL 9011
box walls without knockouts
- without terminals, colours grey RAL 7032, black RAL 901
16

62 - 69
71 - 74

DK Cable Junction Boxes


Content

"Weatherproof" - for outdoor installation - harsh environment and/or outdoor


from 1.5 up to 50 mm2
IP 66 / IP 65 with UL/CSA approval, (Nema 4X)
box walls without knockouts, can be drilled individually
- without terminals

76 - 77

"Waterproof" - for outdoor installation - harsh environment and/or outdoor


from 1,5 up to 10 mm2
cable entry via metric knockouts
- for encapsulating, colours grey RAL 7032, black RAL 9011 NEW

80 - 84

For offshore / heavy duty applications


from 1.5 up to 35 mm2
IP 66 / IP 67
cable entry via metric knockouts
- with / without terminals
box walls without knockouts
- without terminals
Tested for intrinsic fire resistance
from 0.5 up to 16 mm2
IP 65 / IP 66
- material: duroplast, cable entry via included grommets, IP 65
- material: sheet steel, powder-coated, cable entry via mounted grommets, IP 66

86 - 90
91 - 92

94 - 95, 101
96 - 100, 101

For special applications


from 1.5 up to 25 mm2
IP 55 / IP 65
cable entry via metric knockouts
- for security lighting circuits, with red lid
- for equipotential bonding conductors

103
104

With main line branch terminals


from 25 up to 35 mm2
IP 55 / IP 65
cable/conduit entry via metric knockouts
- with terminal blocks for copper conductors 25 mm and 35 mm

106 - 107

With terminal blocks for aluminium- (Alu) and copper conductors (Cu)
from 1.5 up to 4 mm2
IP 65
cable/conduit entry via metric knockouts
- Terminal boxes with terminal blocks

109 - 111

Accessories

113 - 121

Technical Details

123 - 134

Additional information and planning tools (e.g. CAD parts libraries)


can be found on the Internet at www.hensel-electric.in

17

DK Cable Junction Boxes


Criteria for Selecting

Applications

Functions
Branching and
connecting of
copper conductors

Branching and
connecting of
aluminium and
copper conductors

In rooms with dry climate


In damp and wet environments
Protected outdoors (refer to technical details)
On flameable parts of buildings
In buildings with mainly inflammable materials
In areas with a high risk of fire

Pages 22-52

Pages 54-60

Cable trunking installation

Pages 43-44

Intrinsic fire resistance

Pages 94-101

"Waterproof" for encapsulating

Pages 80-84

Weatherproof, for outdoor installation (harsh


environment and/or outdoor)
Improved behaviour in cases of fire
ame-resistant and halogen-free

Pages 62-74

Offshore applications

Pages 86-92

Security lighting circuits

Page 103

Equipotential bonding

Page 104

PA
UL Approval

Page 76-77

DNV Approval
Germanisch Lloyd
Russian Maritime Register of Shipping

Pages 62-92

18

DK Cable Junction Boxes


Criteria for Selecting

Connecting solid
conductors and
stranded conductors

Combining multiple control wires


to one control
cable

2 circuits
in one box

Main line branch


terminals

Without terminals

Box walls
without
knockouts

Page 54-55
Pages 109-111

Pages 109-111

Pages 43-44
DP 9220,
DP 9221,
DP 9222

Page 106-107

Pages 30-36,
Page 41 DN 2000,
DN 2030,
Page 44, 47
Page 48 DE 9321,
Page 49,
Page 51 DE 9220,
Page 52 DE 9221,
Pages 64-65, 68-69,
71-74, 76-77, 89-92
Page 103 D 9220,
D 9240

Pages 33-36
all Boxes,
Pages 71-74, 76-77
Page 91-92

Pages 43-44
DP 9220,
DP 9221,
DP 9222

Page 44

Pages 64-65
Pages 68-69
Pages 71-74

Pages 71-74

Pages 89-92

Page 91-92

Page 76-77

Pages 64-65, 68-69


Pages 71-74, 89-92

Pages 71-74, 89-92

19

DK Cable junction boxes


Box Walls

Assignment of box walls:


The assignment of box walls is effected via wall symbols that are
assigned to each product. The individual figures

give an indication,

4
5 Wand 5
6

All box walls are listed in the


fold-out of the coverpages.

which wall is concerned.

Wall 1

Wall 14

Wall 22

1 x M 20

3 x M 25/32

1 x Elastic
membranes

Wall 2

Wall 15

1 x M 20/25

2 x M 25/32
1 x M 40/50

Wand 3
2 x M 20

Wall 23
2 x Elastic
membranes

Wall 16
3 x M 32/40

Wall 24

2 x M 20/25

Wall 17

3 x Elastic
membranes

Wall 5

4 x M 25/32
1 x M 40/50

Wall 4

1 x M 20/25
1 x M 25/32
Wall 18

Wall 25

4 x M 25
3 x M 40/50

1 x Removablesystem

Wall 19

Wall 26

8 x M 32
4 x M 40/50

2 x Removablesystem

2 x M 32/40

Wall 20

Wall 27

Wall 9

3 x Removablesystem

2 x M 40

2 x M 20
10 x M 25
1 x M 32/40

Wall 10

Wall 21

2 x M 20/25
1 x M 25/32

1 x M 20
4 x M 25
1 x M 32/40
3 x M 40/50

Wall 6
2 x M 25/32
Wall 7
2 x M 32
Wall 8

Wall 28

Wall 11
2 x M 20/25
1 x M 32/40

4 x Removablesystem

Wall 29
1 x M 63
Wall 30

Wall 12

2 x M 50

1 x M 20/25
1 x M 25/32
1 x M 40/50

Wall 31

Wall 13
1 x M 20/25
2 x M 40/50

20

4 x up to 16 mm
1 x up to 35 mm

DK Cable Junction Boxes


with Terminals in Plug-in Technology
Cable Entry via Metric Knockouts

Plenty

of space for the wiring:


Wiring facilities both below the DIN rails
and between the terminals.

Different

Conductors

Stainless

Labelling

Burning

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

conductor types - rigid (r) and


flexible (f) without treatment of conductors - can be connected in one terminal.

system for circuit description


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

can be directly
connected and disconnected with
installed terminal.

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

21

DK Cable Junction Boxes


with Terminals in Plug-in Technology
Cable Entry via Metric Knockouts
KC 9045

10
6 Wall 5
10

1.5-4 mm, Cu 3~
FIXCONNECT

plug-in terminal technology


per pole 4 x 1 x 1,5-4 mm sol/f, terminal technology,
see annex DK Cable junction boxes
included cable entry: 4 ESM 25, sealing range 9-17 mm
for normal environment and protected outdoor

139

rated insulation voltage


current carrying capacity

70

119

5-pole

AC/DC 690 V
32 A

KC 9255

16
8 Wall 8
11

2.5-10 mm, Cu 3~
FIXCONNECT

plug-in terminal technology


per pole 4 x 1 x 2.5-10 mm r/f
included cable entry: 3 ESM 32, sealing range 9-23 mm
for normal environment and protected outdoor

200

98

rated insulation voltage


current carrying capacity

160

5-pole

AC/DC 690 V
50 A

KC 9355

13
15 Wall 15
13

2.5-16 mm, Cu 3~
FIXCONNECT

plug-in terminal technology


per pole 4 x 1 x 2.5-16 mm r/f
included cable entry: 3 ESM 40, sealing range 17-30 mm
for normal environment and protected outdoor

260

rated insulation voltage


current carrying capacity

22

AC/DC 690 V
76 A

210

5-pole

117

DK Cable Junction Boxes


Cable Entry via Metric Knockouts

Variable

terminal mounting
positions (5 positions) and
new terminal technology

Stainless

Hensel

Included

Labelling

Burning

accessories as listed:
grommets ESM = IP 55

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

system for circuit description


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

cable junction boxes can in


general also be used in poor
environmental conditions by using
IP 65 cable glands AKM/ASM.

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C / 960 C,
flame-retardant, self-extinguishing

23

DK Cable Junction Boxes


Cable Entry via Metric Knockouts

D 9025

3
3 Wall 3
1

1.5-2.5 mm, Cu 3~
with

rated insulation voltage


tightening torque for terminal

88

AC/DC 690 V
1,2 Nm

D 9125

3
3 Wall 3
1

1.5-2.5 mm, Cu 3~
with

88

AC/DC 690 V
1,2 Nm

D 9145
1.5-4 mm, Cu 3~

3
3 Wall 3
1

with

98

rated insulation voltage


tightening torque for terminal

61

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
included cable entry: 4 ESM 20, sealing range 6-13 mm
for normal environment and protected outdoor
5-pole

AC/DC 690 V
1,2 Nm

D 9045
with

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
included cable entry: 4 ESM 25, sealing range 9-17 mm
for normal environment and protected outdoor
rated insulation voltage
tightening torque for terminal

AC/DC 690 V
1,2 Nm

98

1.5-4 mm, Cu 3~

4
4 Wall 4
2

5-pole

24

53

88

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
included cable entry: 4 ESM 20, sealing range 6-13 mm
with external fixing
for normal environment and protected outdoor
5-pole

rated insulation voltage


tightening torque for terminal

53

88

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
included cable entry: 4 ESM 20, sealing range 6-13 mm
for normal environment and protected outdoor
5-pole

61

DK Cable Junction Boxes


Cable Entry via Metric Knockouts

K 9065

10
6 Wall 5
10

2.5-6 mm, Cu 3~
with

terminals
per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,
2 x 10 mm sol
included cable entry: 3 ESM 32, sealing range 9-23 mm
for normal environment and protected outdoor

139

rated insulation voltage


tightening torque for terminal

AC/DC 690 V
1,5 Nm

K 9105

14
6 Wall 6
10

4-10 mm, Cu 3~
with

terminals
per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,
4 x 10 mm sol, 2 x 16 mm s
included cable entry: 3 ESM 32, sealing range 9-23 mm
for normal environment and protected outdoor

167

82

125

5-pole

rated insulation voltage


current carrying capacity
tightening torque for terminal

70

119

5-pole

AC/DC 690 V
63 A
2,0 Nm

K 9255

16
8 Wall 8
11

10-25 mm, Cu 3~
with

terminals
per pole 6 x 10 mm sol, 4 x 16 mm s, 4 x 25 mm s,
2 x 35 mm s
included cable entry: 3 ESM 40, sealing range 17-30 mm
for normal environment and protected outdoor

200

98

rated insulation voltage


current carrying capacity
tightening torque for terminal

160

5-pole

AC/DC 690 V
102 A
3,0 Nm

K 9502

12
17 Wall 17
12

10-35 mm, Cu 3~
with

terminals
per pole 4 x 10 mm sol, 4 x 16 mm s, 4 x 25 mm s,
2 x 35 mm s
included cable entry: 3 ESM 40, sealing range 17-30 mm
for normal environment and protected outdoor

210

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

310

5-pole

AC/DC 690 V
102 A
3,0 Nm

25

DK Cable Junction Boxes


Cable Entry via Metric Knockouts

K 9355

15
13 Wall 13
15

16-35 mm, Cu 3~
with

terminals
per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,
2 x 50 mm s
included cable entry: 3 ESM 40, sealing range 17-30 mm
for normal environment and protected outdoor

210

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

260

5-pole

AC/DC 690 V
125 A
12,0 Nm

K 9504

12
17 Wall 17
12

16-50 mm, Cu 3~
with

terminals
per polel 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,
4 x 50 mm s
cable entry via knockouts,
order AKM/ASM separately (refer to index cable entry systems)
for normal environment and protected outdoor

210

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

310

4-pole

AC/DC 690 V
150 A
12,0 Nm

K 9505

12
17 Wall 17
12

16-50 mm, Cu 3~
with

terminals
per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,
4 x 50 mm s
cable entry via knockouts,
order AKM/ASM separately (refer to index cable entry systems)
for normal environment and protected outdoor

210

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

310

5-pole

AC/DC 690 V
150 A
12,0 Nm

K 7055

20
21 Wall 21
20

16-50 mm, Cu 3~
with

terminals
per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,
4 x 50 mm s
sealable
Order cable glands, flanges and other accessories separately as
required
for normal environment and protected outdoor

300

rated insulation voltage


current carrying capacity
tightening torque for terminal

26

AC/DC 690 V
150 A
12,0 Nm

450

5-pole

170

DK Cable Junction Boxes


Cable Entry via Metric Knockouts

K 7004

20
21 Wall 21
20

16-70 mm, Cu 3~
with

terminals
per pole 4 x 16-70 mm s
sealable
Order cable glands, flanges and other accessories separately as
required
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

450

4-pole

AC/DC 690 V
216 A
10,0 Nm

K 7005

20
21 Wall 21
20

16-70 mm, Cu 3~
with

terminals
per polel 4 x 16-70 mm s
sealable
Order cable glands, flanges and other accessories separately as
required
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

450

5-pole

AC/DC 690 V
216 A
10,0 Nm

K 1204

20
21 Wall 21
20

16-150 mm, Cu/Alu 3~


with

terminals
per pole 2 x 16-150 mm, 4 x 16-70 mm,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

450

4-pole

AC/DC 690 V
250 A
20,0 Nm

27

DK Cable Junction Boxes


Cable Entry via Metric Knockouts

K 1205

20
21 Wall 21
20

16-150 mm, Cu/Alu 3~


with

terminals
per pole 2 x 16-150 mm, 4 x 16-70 mm,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

450

5-pole

AC/DC 690 V
250 A
20,0 Nm

K 2404

20
19 Wall 19
18

25-240 mm, Cu/Alu 3~


with

terminals
per pole 2 x 25-185/240 mm, 4 x 25-120 mm,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

rated insulation voltage


current carrying capacity
tightening torque for terminal

28

AC/DC 690 V
400 A
40,0 Nm

600

4-pole

170

DK Cable Junction Boxes


Cable Entry via Metric Knockouts

K 2405

20
19 Wall 19
18

25-240 mm, Cu/Alu 3~


with

terminals
per pole 2 x 25-185/240 mm, 4 x 25-120 mm,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

600

5-pole

AC/DC 690 V
400 A
40,0 Nm

29

DK Cable Junction Boxes


Cable Entry via Metric Knockouts

D 9020

3
3 Wall 3
1

without

terminals
cable entry: 4 ESM 20, sealing range 6-13 mm
for normal environment and protected outdoor

88

D 9120

3
3 Wall 3
1

without

terminals
external fixing
included cable entry: 4 ESM 20, sealing range 6-13 mm
for normal environment and protected outdoor

88

53

88

with

D 9140

3
3 Wall 3
1

without

98

terminals
cable entry: 4 ESM 20, sealing range 6-13 mm
for normal environment and protected outdoor

58

98

included

D 9040

4
4 Wall 4
2

without

98

terminals
cable entry: 4 ESM 25, sealing range 9-17 mm
for normal environment and protected outdoor

K 9060

10
6 Wall 5
10

without

terminals
cable entry: 3 ESM 32, sealing range 9-23 mm
for normal environment and protected outdoor

139

K 9100

14
6 Wall 6
10

without

167
125

terminals
cable entry: 3 ESM 32, sealing range 9-23 mm
for normal environment and protected outdoor

70

119

included

included

61

98

included

30

53

88

included

82

DK Cable Junction Boxes


Cable Entry via Metric Knockouts

K 9250

16
8 Wall 8
11

without

terminals
cable entry: 3 ESM 40, sealing range 17-30 mm
for normal environment and protected outdoor

200

98

160

included

K 9350
terminals
cable entry: 3 ESM 40, sealing range 17-30 mm
for normal environment and protected outdoor

13
15 Wall 15
13

without

260

117

210

included

K 9500
terminals
entry via knockouts, order AKM/ASM separately
(refer to index cable entry systems)
for normal environment and protected outdoor

12
17 Wall 17
12

without

210

117

310

cable

31

DK Cable Junction Boxes


Box Walls without Knockouts

Cable entries can be drilled


individually.

Burning

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

32

Labelling

system for circuit description


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

Stainless

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

DK Cable Junction Boxes


Box Walls without Knockouts

D 8020
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
for normal environment and protected outdoor
wall thickness of the bottom part

88

53

88

53

88

box

2,3 mm

D 8120
without

terminals
external fixing
box walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
for normal environment and protected outdoor
wall thickness of the bottom part

88

with

2,3 mm

D 8040
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
for normal environment and protected outdoor

98

wall thickness of the bottom part

58

98

box

2,3 mm

K 8060
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 32
for normal environment and protected outdoor

139

wall thickness of the bottom part

70

119

box

2,6 mm

K 8100
without

wall thickness of the bottom part

167

82

125

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 32
for normal environment and protected outdoor
box

2,8 mm

33

DK Cable Junction Boxes


Box Walls without Knockouts

K 8250
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 40
for normal environment and protected outdoor

200

98

wall thickness of the bottom part

160

box

3 mm

K 8350
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 50
for normal environment and protected outdoor

260

117

wall thickness of the bottom part

210

box

3 mm

K 8500
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 50
for normal environment and protected outdoor

210

wall thickness of the bottom part

34

3 mm

310

box

117

DK Cable Junction Boxes


Box Walls without Knockouts

K 0100
transparent lid
fasteners for tool operation
box walls without knockouts
please order DIN rails or mounting plates additionally
for normal environment and protected outdoor
lid

rated current
wall thickness of the bottom part

300

170

300

170

300

170

300

170

150

with

for electrical devices up to 63 A


3,5 mm

K 0200
with

transparent lid
fasteners for tool operation
box walls without knockouts
please order DIN rails or mounting plates additionally
for normal environment and protected outdoor
rated current
wall thickness of the bottom part

300

lid

for electrical devices up to 63 A


3,5 mm

K 0300
with

transparent lid
fasteners for tool operation
box walls without knockouts
please order DIN rails or mounting plates additionally
for normal environment and protected outdoor
rated current
wall thickness of the bottom part

450

lid

for electrical devices up to 63 A


3,5 mm

K 0400
with

transparent lid
fasteners for tool operation
box walls without knockouts
please order DIN rails or mounting plates additionally
for normal environment and protected outdoor
rated current
wall thickness of the bottom part

600

lid

for electrical devices up to 63 A


3,5 mm

35

DK Cable Junction Boxes


Box Walls without Knockouts

K 0101
opaque lid
fasteners for tool operation
box walls without knockouts
please order DIN rails or mounting plates additionally
for normal environment and protected outdoor
lid

rated current
wall thickness of the bottom part

300

170

300

170

300

170

300

170

150

with

for electrical devices up to 63 A


3,5 mm

K 0201
with

opaque lid
fasteners for tool operation
box walls without knockouts
please order DIN rails or mounting plates additionally
for normal environment and protected outdoor
rated current
wall thickness of the bottom part

300

lid

for electrical devices up to 63 A


3,5 mm

K 0301
with

opaque lid
fasteners for tool operation
box walls without knockouts
please order DIN rails or mounting plates additionally
for normal environment and protected outdoor
rated current
wall thickness of the bottom part

450

lid

for electrical devices up to 63 A


3,5 mm

K 0401
with

opaque lid
fasteners for tool operation
box walls without knockouts
please order DIN rails or mounting plates additionally
for normal environment and protected outdoor
rated current
wall thickness of the bottom part

36

for electrical devices up to 63 A


3,5 mm

600

lid

DK Cable Junction Boxes


Empty Boxes
Accessories for Cable Junction Boxes K0x0x
Mi TS 15
DIN rail
length 134 mm
in

accordance with DIN EN 60 715


Mi Empty box size 1
for equipment or terminals with clip-on mounting
with fixing screws

15

134
35

for

Mi TS 30
DIN rail
length 284 mm
in

accordance with DIN EN 60 715


Mi empty box sizes 1 to 8
for equipment or terminals with clip-on mounting
with fixing screws

15

284
35

for

Mi TS 45
DIN rail
length 434 mm
in

accordance with DIN EN 60 715


Mi empty box size 3
for equipment or terminals with clip-on mounting
with fixing screws

15

434
35

for

Mi TS 60
DIN rail
length 584 mm
in

15

584
35

accordance with DIN EN 60 715


Mi empty box sizes 4 and 8
for equipment or terminals with clip-on mounting
with fixing screws
for

Mi MP 1
Mounting plate
W 259 x H 115 mm
material

259
115

thickness 4 mm
Mi-Empty boxes sizes 1, 2, 3, 4
with fixing screws
for

Mi MP 2
Mounting plate
W 265 x H 265 mm
material

265
265

thickness 4 mm
Mi-Empty boxes sizes 2 to 8
with fixing screws
for

37

DK Cable Junction Boxes


Empty Boxes
Accessories for Cable Junction Boxes K0x0x
Mi MP 3
Mounting plate
W 265 x H 415 mm
material

thickness 4 mm
Mi-Empty boxes sizes 3, 4
with fixing screws

265

415

for

Mi MP 4
Mounting plate
W 265 x H 565 mm
material

thickness 4 mm
Mi-Empty boxes sizes 4, 8
with fixing screws

265

565

for

Mi PL 2
Sealing cap
2

sealing caps for converting the lid fasteners

Mi SR 4
Conversion set
for manual operation on tool operation
4

fastening covers

Mi SN 4
Conversion set
for converting lid fasteners from tool to
manual operation
4

38

manual actuators

DK Cable Junction Boxes


Empty Boxes
Accessories for Cable Junction Boxes K0x0x
Mi DV 01
Locking device insertion
only

in connection with Mi PL 2, Mi SR 4 or Mi SN 4

Mi ZS 11
Lid lock
with locking device I
Is

being used instead of fasteners for hand or tool operation in


order to prevent unauthorised opening of the lids
consisting of: cylinder lock, keys, locking device insertion, dust
cover

Mi ZS 12
Lid lock
with locking device II
Is

being used instead of fasteners for hand or tool operation in


order to prevent unauthorised opening of the lids
consisting of: cylinder lock, keys, locking device insertion, dust
cover

Mi DR 04
Lid fastener for tool operation
triangle 8 mm
is

used instead of fasteners for hand- or tool operation, in order to


make unauthorized opening of lids more difficult
4 locking devices with triangle 8 mm and key

DS 1
Triangular key 8 mm

Mi AL 40
4 stainless steel external brackets
for

external fixing of enclosures

39

DK Cable Junction Boxes


Cable Entry via Elastic Membranes and Integrated M 20 Thread

IP

55 with cable entry via


elastic membranes.

Burning

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

40

IP

65 with ADM 20 cable gland without


locknut. The gland is secured by an
integrated M 20 thread.

Captive

cover screws with


quick-release lock.

DK Cable Junction boxes


Cable Entry via Elastic Membranes and Integrated M 20 Thread

DN 2035
1.5-2.5 mm, Cu 3~

3
3 Wall 3
3

with

85

rated insulation voltage


tightening torque for terminal

51

85

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
cable entry via elastic membranes and integrated M 20 thread
8 elastic membranes, closed, sealing range 3-12 mm
included cable entry: 3 ADM 20, sealing range 6,5-13,5 mm
for normal environment and protected outdoor
5-pole

AC/DC 690 V
1,2 Nm

DN 2005
1.5-2.5 mm, Cu 3~

3
3 Wall 3
3

with

85

rated insulation voltage


tightening torque for terminal

51

85

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
cable entry via elastic membranes and integrated M 20 thread
8 elastic membranes, closed, sealing range 3-12 mm
for normal environment and protected outdoor
5-pole

AC/DC 690 V
1,2 Nm

DN 2030

3
3 Wall 3
3

without

85

51

85

terminals
entry via elastic membranes and integrated M 20 thread
8 elastic membranes, closed, sealing range 3-12 mm
included cable entry: 3 ADM 20, sealing range 6,5-13,5 mm
cable

DN 2000

3
3 Wall 3
3

without

85

51

85

terminals
entry via elastic membranes and integrated M 20 thread
8 elastic membranes, closed, sealing range 3-12 mm
for normal environment and protected outdoor
cable

ADM 20
ISO thread M 20 x 1.5
sealing

range 6,5-13,5 mm
strain relief
for indoor - normal environment and (or) protected outdoor installation
ambient temperature - 25 to + 35 C
glow wire test IEC 60 695-2-11: 750 C
with

tightening torque

2,0 Nm

41

DK Cable Junction Boxes


Cable Entry via Knockouts
for Cable Trunking and Conduit Installation

Simply

cut out cable trunking wall


to the required width.

The

cables can be inserted from the


front! No threading of cables neccessary!
Supplied accessory grommets
DPS 02 = IP 54

Stainless

The

Labelling

Burning

clean installation solution for cable


trunking!
Removable trunking adapters
for connection of cable trunkings
to junction boxes.
42

system for circuit description


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

DK Cable Junction Boxes


Cable Entry via Knockouts
for Cable Trunking and Conduit Installation
DP 9025

26
26 Wall 26
25

1.5-2.5 mm, Cu 3~
with

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
for cable trunking and conduit installation
included cable entry: 4 DPS 02, sealing range 10-13,5 mm
for normal environment and protected outdoor

88

rated insulation voltage


tightening torque for terminal

AC/DC 690 V
1,2 Nm

DP 9221

28
27 Wall 27
27

1.5-2.5 mm, Cu 3~
with

139

AC/DC 690 V
1,2 Nm

DP 9222

28
27 Wall 27
27

1.5-2.5 mm, Cu 3~
with

139

AC/DC 690 V
1,2 Nm

DPC 9225

28
27 Wall 27
27

1.5-2.5 mm, Cu 3~
FIXCONNECT

139

50

119

plug-in terminal technology


per pole 4 x 1 x 1.5-2.5 mm sol/f, terminal technology,
see annex DK Cable junction boxes
for cable trunking and conduit installation
included cable entry: 4 DPS 02, sealing range 10-13,5 mm
for normal environment and protected outdoor
5-pole

rated insulation voltage


current carrying capacity

50

119

2 terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
for cable trunking and conduit installation
included cable entry: 7 DPS 02, sealing range 10-13,5 mm
for normal environment and protected outdoor
5-pole

rated insulation voltage


tightening torque for terminal

50

119

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
for cable trunking and conduit installation
included cable entry: 7 DPS 02, sealing range 10-13,5 mm
for normal environment and protected outdoor
5-pole

rated insulation voltage


tightening torque for terminal

50

88

5-pole

AC/DC 690 V
32 A

43

DK Cable Junction Boxes


Cable Entry via Knockouts
for Cable Trunking and Conduit Installation
DP 9020

26
26 Wall 26
25

without

terminals
cable trunking and conduit installation
included cable entry: 4 DPS 02, sealing range 10-13,5 mm
for normal environment and protected outdoor

88

DP 9220

139
119

terminals
cable trunking and conduit installation
included cable entry: 7 DPS 02, sealing range 10-13,5 mm
for normal environment and protected outdoor

28
27 Wall 27
27

without
for

DPS 02
Removable grommet
degree

of protection: IP 54 sealing range 10-13.5 mm


retrofitting
for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225
for

ERA 20
Removable conduit adapter
degree

of protection: IP 54 sealing range 10-13.5 mm


wiring conduits M 20
for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225
for

EKA 20
Removable trunking adapter
degree

of protection: IP 54 sealing range 10-13.5 mm


mini trunking up to 20 x 20 mm
for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221, DP 9222, DP 9026, DPC 9225
for

44

50

88

for

50

DK Cable Junction Boxes


Cable Entry via Elastic Membranes

No

punching tool required - insert the


conductor and its done
Degree of protection IP 55

Grommet

Box

Stainless

wall with 3 cable entries

supplied for sealing membranes in case of modifications.

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

Labelling

system for circuit description


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

Burning

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

45

DK Cable Junction Boxes


Cable Entry via Elastic Membranes

DE 9325

24
23 Wall 23
24

1.5-2.5 mm, Cu 3~
with

rated insulation voltage


tightening torque for terminal

88

AC/DC 690 V
1,2 Nm

DE 9345

24
23 Wall 23
24

1.5-4 mm, Cu 3~
with

98

AC/DC 690 V
1,2 Nm

DE 9335

24
23 Wall 23
24

1.5-4 mm, Cu 3~
terminals

46

AC/DC 500 V
32 A
0,8 Nm
6 mm

88
88

with wire protection


per pole 4 x 1.5 mm sol/s/f, 4 x 2.5 mm sol/s/f,
2 x 4 mm sol/s/f
10 elastic membranes, closed cable entries,
sealing range 6.5-16 mm
with cable retention (2 pc.) for cable tie up to 6.5 mm width
for normal environment and protected outdoor
5-pole

rated insulation voltage


rated current
tightening torque for terminal
Dismantling length

52

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
10 elastic membranes, closed cable entries,
sealing range 6.5-18 mm
for normal environment and protected outdoor
5-pole

rated insulation voltage


tightening torque for terminal

47

88

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
10 elastic membranes, closed cable entries,
sealing range 6.5-16 mm
for normal environment and protected outdoor
5-pole

47

DK Cable Junction Boxes


Cable Entry via Elastic Membranes

DE 9320
without
10

88

DE 9340

98

DE 9330

88

DE 9350

98

52

98

terminals
elastic membranes, closed cable entries,
sealing range 6.5-18 mm
with cable retention (2 pc.) for cable tie up to 6.5 mm width
for normal environment and protected outdoor

24
23 Wall 23
24

without
10

47

88

terminals
elastic membranes, closed cable entries,
sealing range 6.5-16 mm
with cable retention (2 pc.) for cable tie up to 6.5 mm width
for normal environment and protected outdoor

24
23 Wall 23
24

without
10

52

98

terminals
elastic membranes, closed cable entries,
sealing range 6.5-18 mm
for normal environment and protected outdoor

24
23 Wall 23
24

without
10

47

88

terminals
elastic membranes, closed cable entries,
sealing range 6.5-16 mm
for normal environment and protected outdoor

24
23 Wall 23
24

47

DK Cable Junction Boxes


Cable Entry via Elastic Membranes

DE 9326

24
23 Wall 23
24

1.5-2.5 mm, Cu 3~
with

rated insulation voltage


tightening torque for terminal

88

AC/DC 690 V
1,2 Nm

DE 9346

24
23 Wall 23
24

1.5-4 mm, Cu 3~
with

98

AC/DC 690 V
1,2 Nm

DE 9336

24
23 Wall 23
24

1.5-2.5 mm, Cu 3~
terminals

88

AC/DC 500 V
32 A
0,8 Nm
11 mm

DE 9321

48

88
88

terminals
elastic membranes, closed cable entries,
sealing range 6.5-16 mm
for normal environment and protected outdoor

24
23 Wall 23
24

without
10

47

88

with wire protection


per pole 4 x 1.5 mm sol/s/f, 4 x 2.5 mm sol/s/f,
2 x 4 mm sol/s/f
10 elastic membranes, closed cable entries,
sealing range 6.5-16 mm
with cable retention (2 pc.) for cable tie up to 6.5 mm width
for normal environment and protected outdoor
5-pole

rated insulation voltage


rated current
tightening torque for terminal
Dismantling length

52

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
10 elastic membranes, closed cable entries,
sealing range 6.5-18 mm
for normal environment and protected outdoor
5-pole

rated insulation voltage


tightening torque for terminal

47

88

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
10 elastic membranes, closed cable entries,
sealing range 6.5-16 mm
for normal environment and protected outdoor
5-pole

47

DK Cable Junction Boxes


Cable Entry via Elastic Membranes

DE 9341
without
10

98

DE 9331

88

DE 9351

98

52

98

terminals
elastic membranes, closed cable entries,
sealing range 6.5-18 mm
with cable retention (2 pc.) for cable tie up to 6.5 mm width
for normal environment and protected outdoor

24
23 Wall 23
24

without
10

47

88

terminals
elastic membranes, closed cable entries,
sealing range 6.5-16 mm
with cable retention (2 pc.) for cable tie up to 6.5 mm width
for normal environment and protected outdoor

24
23 Wall 23
24

without
10

52

98

terminals
elastic membranes, closed cable entries,
sealing range 6.5-18 mm
for normal environment and protected outdoor

24
23 Wall 23
24

KHR 01
Cable retention
for cable diameter 6,5 - 14 mm
set

with 10 x 6 cable rentention rings


pieces for cable diameter 6,5 - 10 mm
30 pieces for cable diameter 10 - 14 mm
30

KHR 02
Cable retention
for cable diameter 10 - 16 mm
set

with 10 x 6 cable rentention rings


pieces for cable diameter 10 - 14 mm
30 pieces for cable diameter 13 - 16 mm
30

DK ZE 10
Cable retention
set

with 10 pieces
fixing in the bottom part of DK-cable junction boxes
cable retention with cable clip up to 6.5 mm
for

49

DK Cable Junction Boxes


Cable Entry via Elastic Membranes
in Bottom and Box Walls

Cable

entry from the rear via elastic


membranes in the bottom

Lid

Flexible

Burning

elastic membranes no cable glands required.


Push through and tight!

50

for clip-on attachment.


Reducing cover xing time

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

Cable

entry via elastic membranes


in box walls

DK Cable Junction Boxes


Cable Entry via Elastic Membranes
in Bottom and Box Walls
DE 9225

23
24 Wall 24
23

1.5-2.5 mm, Cu 3~
with

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
box walls with 10 elastic membranes, closed, sealing range
3-14 mm, bottom with 2 elastic membranes, closed
lid with clip-on attachment
for normal environment and protected outdoor
rated insulation voltage
tightening torque for terminal

53

76
76

5-pole

AC/DC 690 V
1,2 Nm

DE 9220

23
24 Wall 24
23

without

terminals
walls with 10 elastic membranes, closed, sealing range
3-14 mm, bottom with 2 elastic membranes, closed
lid with clip-on attachment
with cable retention (2 pc.) for cable tie up to 6.5 mm width
for normal environment and protected outdoor

53

76
76

box

DK ZE 10
Cable retention
set

with 10 pieces
fixing in the bottom part of DK-cable junction boxes
cable retention with cable clip up to 6.5 mm
for

KHR 01
Cable retention
for cable diameter 6,5 - 14 mm
set

with 10 x 6 cable rentention rings


pieces for cable diameter 6,5 - 10 mm
30 pieces for cable diameter 10 - 14 mm
30

KHR 02
Cable retention
for cable diameter 10 - 16 mm
set

with 10 x 6 cable rentention rings


pieces for cable diameter 10 - 14 mm
30 pieces for cable diameter 13 - 16 mm
30

DE MB 10
Assembly bracket
external

10

70
55
18
6

brackets 10 units
thermoplastics
for quick installation of cable junction boxes DE 922. and DN 20..
material:

10

51

DK Cable Junction Boxes


Cable Entry via Elastic Membranes
in Bottom and Box Walls
DE 9226

23
24 Wall 24
23

1.5-2.5 mm, Cu 3~
with

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
box walls with 10 elastic membranes, closed, sealing range
3-14 mm, bottom with 2 elastic membranes, closed
lid with clip-on attachment
for normal environment and protected outdoor
rated insulation voltage
tightening torque for terminal

53

76
76

5-pole

AC/DC 690 V
1,2 Nm

DE 9221

23
24 Wall 24
23

without

terminals
walls with 10 elastic membranes, closed, sealing range
3-14 mm, bottom with 2 elastic membranes, closed
lid with clip-on attachment
with cable retention (2 pc.) for cable tie up to 6.5 mm width
for normal environment and protected outdoor

53

76
76

box

DK ZE 10
Cable retention
set

with 10 pieces
fixing in the bottom part of DK-cable junction boxes
cable retention with cable clip up to 6.5 mm
for

KHR 01
Cable retention
for cable diameter 6,5 - 14 mm
set

with 10 x 6 cable rentention rings


pieces for cable diameter 6,5 - 10 mm
30 pieces for cable diameter 10 - 14 mm
30

KHR 02
Cable retention
for cable diameter 10 - 16 mm
set

with 10 x 6 cable rentention rings


pieces for cable diameter 10 - 14 mm
30 pieces for cable diameter 13 - 16 mm
30

DE MB 10
Assembly bracket
external

52

10

70
55
18
6

brackets 10 units
thermoplastics
for quick installation of cable junction boxes DE 922. and DN 20..
material:

10

DK Cable Junction Boxes


with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts

Degree

of protection up to IP 65. In the


case of twisted cables, cable glands
are required in principle to achieve the
degree of protection IP 54.

Stainless

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

Separate

clamping units for


aluminium and copper conductors

Labelling

system for circuit description.


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

Burning

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

53

DK Cable Junction Boxes


with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
D 9041
1.5-2.5 mm, Cu/Alu 3~

4
4 Wall 4
2

with

98

terminals
per polel 4 x 1.5 mm sol/f, 4 x 2.5 mm sol/f, conductors
are inserted into the screw-type terminal, terminal technology,
see annex DK Cable junction boxes
included cable entry: 4 ESM 25, sealing range 9-17 mm
In the case of twisted cables, cable glands are required in
principle to achieve the degree of protection IP 54.
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor
rated insulation voltage
current carrying capacity
tightening torque for terminal

AC/DC 250 V
20 A
0,5 Nm

K 9061

10
6 Wall 5
10

1.5-4 mm, Cu/Alu 3~


with

54

AC/DC 400 V
20 A
0,6 Nm

139
119

terminals
per pole 4 x 1.5 mm sol/f, 4 x 2.5 mm sol/f, 4 x 4 mm
sol/f, conductors are inserted into the screw-type terminal,
terminal technology, see annex DK Cable junction boxes
included cable entry: 3 ESM 32, sealing range 9-23 mm
In the case of twisted cables, cable glands are required in
principle to achieve the degree of protection IP 54.
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor
5-pole

rated insulation voltage


current carrying capacity
tightening torque for terminal

61

98

5-pole

70

DK Cable Junction Boxes


with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 9351

13
15 Wall 15
13

6-16 mm, Cu/Alu 3~


with

terminals
per polel 4 x 6 mm sol/f, 4 x 10 mm sol/f, 4 x 16 mm
sol/s/f, conductors are inserted into the screw-type terminal,
terminal technology, see annex DK Cable junction boxes
included cable entry: 3 ESM 40, sealing range 17-30 mm
In the case of twisted cables, cable glands are required in
principle to achieve the degree of protection IP 54.
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

260

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

210

5-pole

AC/DC 690 V
76 A
3,0 Nm

KF 9251

16
8 Wall 8
11

1.5-50 mm, Cu/Alu 3~


with

connecting terminal
per pole 2 x 1 x 1.5-50 mm, conductors are inserted into
the screw-type terminal, terminal technology,
see annex DK Cable junction boxes
included cable entry: 2 EDK 40, sealing range 11-30 mm
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

200

98

rated insulation voltage


current carrying capacity
tightening torque for terminal

160

5-pole

AC/DC 690 V
160 A
1.5 Nm 1.5-2.5 mm
5.0 Nm 4-10 mm
12,0 Nm 16-50 mm

55

DK Cable Junction Boxes


with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
KF 9501

12
17 Wall 17
12

1.5-50 mm, Cu/Alu 3~


with

connecting terminal
per pole 2 x 1 x 1.5-50 mm, conductors are inserted into
the screw-type terminal, terminal technology,
see annex DK Cable junction boxes
included cable entry: 2 EDK 40, sealing range 11-30 mm
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

210

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

310

5-pole

AC/DC 690 V
160 A
1.5 Nm 1.5-2.5 mm
5.0 Nm 4-10 mm
12,0 Nm 16-50 mm

K 7051

20
21 Wall 21
20

2.5-50 mm, Cu/Alu 3~


with

terminals
per pole 4 x 2.5-50 mm, conductors are inserted into the
screw-type terminal, terminal technology,
see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

rated insulation voltage


current carrying capacity
tightening torque for terminal

56

AC/DC 750 V
Cu, 150 A
Alu, 120 A
10,0 Nm

450

5-pole

170

DK Cable Junction Boxes


with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 7042

20
21 Wall 21
20

10-95 mm Cu/Alu 3~
with

terminals
per pole 2 x 10-95 mm, conductors can be inserted from
the front into the clamping unit, terminal technology,
see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

450

4-pole

AC/DC 690 V
160 A
20,0 Nm

K 7052

20
21 Wall 21
20

10-95 mm Cu/Alu 3~
with

terminals
per pole 2 x 10-95 mm, conductors can be inserted from
the front into the clamping unit, terminal technology,
see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

450

5-pole

AC/DC 690 V
160 A
20,0 Nm

57

DK Cable Junction Boxes


with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 9951

20
21 Wall 21
20

6-95 mm, Cu/Alu 3~


with

terminals
per pole 4 x 6-95 mm, conductors are inserted into the
screw-type terminal, terminal technology,
see annex DK Cable junction boxes
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

450

5-pole

AC/DC 690 V
490 A
12.0 Nm 6-25 mm
22.0 Nm 35-95 mm

K 1204

20
21 Wall 21
20

16-150 mm, Cu/Alu 3~


with

terminals
per pole 2 x 16-150 mm, 4 x 16-70 mm, conductors can
be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

rated insulation voltage


current carrying capacity
tightening torque for terminal

58

AC/DC 690 V
250 A
20,0 Nm

450

4-pole

170

DK Cable Junction Boxes


with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 1205

20
21 Wall 21
20

16-150 mm, Cu/Alu 3~


with

terminals
per pole 2 x 16-150 mm, 4 x 16-70 mm,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

450

5-pole

AC/DC 690 V
250 A
20,0 Nm

K 2404

20
19 Wall 19
18

25-240 mm, Cu/Alu 3~


with

terminals
per pole 2 x 25-185/240 mm, 4 x 25-120 mm,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

600

4-pole

AC/DC 690 V
400 A
40,0 Nm

59

DK Cable Junction Boxes


with Terminals for Aluminium and Copper Conductors
Cable Entry via Metric Knockouts
K 2405

20
19 Wall 19
18

25-240 mm, Cu/Alu 3~


with

terminals
per pole 2 x 25-185/240 mm, 4 x 25-120 mm,
conductors can be inserted from the front into the clamping unit,
terminal technology, see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

170

rated insulation voltage


current carrying capacity
tightening torque for terminal

600

5-pole

AC/DC 690 V
400 A
40,0 Nm

K 2401

20
19 Wall 19
18

35-240 mm, Cu/Alu 3~


with

terminals
per pole 4 x 35-240 mm, conductors are inserted into the
screw-type terminal, terminal technology,
see annex DK Cable junction boxes
sealable
Order cable glands, flanges and other accessories separately as
required
Reference to the preparation of aluminum conductors:
1. Clean the bared conductor end carefully by scraping off the
oxide film, for example with a knife, (Please do not use rasps,
emery paper or brushes!).
2. Immediately after removing the oxide film the conductor end
is to rub in with acid and alkali free fat for example vaseline,
and immediately to be connected in the terminal.
3. The prementioned processing steps are to be repeated, if the
conductor was disconnected and connected again.
4. Due to the disposition to flowing of aluminum the terminals are
to be re-tightened before start-up and after the first 200
operation hours.
for normal environment and protected outdoor

300

rated insulation voltage


current carrying capacity
tightening torque for terminal

60

AC/DC 690 V
850 A
26.0 Nm 35-120 mm
55.0 Nm 150-240 mm

600

5-pole

170

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Cable Entry via Metric Knockouts

Degree

of protection IP 66
retardant, self-extinguishing,
made of high-grade material:
PC-GFS, glass-bre reinforced
thermoplastics, impact proof

Flame

Stainless

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

KF-Cable

junction boxes comply with


regulatory restrictions for buildings with
requirements regarding the structural fire
protection!
halogen-free, silicone-free:
low toxicity, low fume development

Degree

of protection IP 66 using cable


glands ASS.. (colour black) or cable
glands ASM.. (colour grey), available as
an accessory.

Burning

behaviour:
Glow-wire test 960C
according to IEC 60 695-2-11,
UL Subject 94: V-0
ame-retardant, self-extinguishing
61

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 9025

3
3 Wall 3
1

1.5-2.5 mm, Cu 3~
with

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

88

rated insulation voltage


tightening torque for terminal

AC/DC 690 V
1,2 Nm

KF 9045
1.5-4 mm, Cu 3~

4
4 Wall 4
2

with

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"
rated insulation voltage
tightening torque for terminal

AC/DC 690 V
1,2 Nm

KF 9065

10
6 Wall 5
10

2.5-6 mm, Cu 3~
with

terminals
per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,
2 x 10 mm sol
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

139

AC/DC 690 V
1,5 Nm

KF 9105

14
6 Wall 6
10

4-10 mm, Cu 3~
with

AC/DC 690 V
63 A
2,0 Nm

167
125

terminals
per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,
4 x 10 mm sol, 2 x 16 mm s
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"
5-pole

rated insulation voltage


current carrying capacity
tightening torque for terminal

70

119

5-pole

rated insulation voltage


tightening torque for terminal

61

98

5-pole

62

53

88

5-pole

82

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 9255

16
8 Wall 8
11

10-25 mm, Cu 3~
with

terminals
per pole 6 x 10 mm sol, 4 x 16 mm s, 4 x 25 mm s,
2 x 35 mm s
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

200

98

rated insulation voltage


current carrying capacity
tightening torque for terminal

160

5-pole

AC/DC 690 V
102 A
3,0 Nm

KF 9355

15
13 Wall 13
15

16-35 mm, Cu 3~
with

terminals
per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,
2 x 50 mm s
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

210

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

260

5-pole

AC/DC 690 V
125 A
12,0 Nm

KF 9505

12
17 Wall 17
12

16-50 mm, Cu 3~
with

terminals
per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,
4 x 50 mm s
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

210

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

310

5-pole

AC/DC 690 V
150 A
12,0 Nm

63

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 9020

3
3 Wall 3
1

without

terminals
entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

88

KF 9040

4
4 Wall 4
2

without

98

terminals
entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

KF 9060

10
6 Wall 5
10

without

terminals
entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

139

70

119

cable

KF 9100

14
6 Wall 6
10

without

terminals
entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

167

82

125

cable

KF 9250
terminals
entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

61

98

cable

16
8 Wall 8
11

without

200
160

cable

64

53

88

cable

98

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 9350
terminals
entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

13
15 Wall 15
13

without

260

117

210

cable

KF 9500
terminals
entry via knockouts, order ASM separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

12
17 Wall 17
12

without

210

117

310

cable

65

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 5025

3
3 Wall 3
1

1.5-2.5 mm, Cu 3~
with

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

88

rated insulation voltage


tightening torque for terminal

AC/DC 690 V
1,2 Nm

KF 5045
1.5-4 mm, Cu 3~

4
4 Wall 4
2

with

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"
rated insulation voltage
tightening torque for terminal

AC/DC 690 V
1,2 Nm

KF 5065

10
6 Wall 5
10

2.5-6 mm, Cu 3~
with

terminals
per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,
2 x 10 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

139

AC/DC 690 V
1,5 Nm

KF 5105

14
6 Wall 6
10

4-10 mm, Cu 3~
with

AC/DC 690 V
63 A
2,0 Nm

167
125

terminals
per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,
4 x 10 mm sol, 2 x 16 mm s
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"
5-pole

rated insulation voltage


current carrying capacity
tightening torque for terminal

70

119

5-pole

rated insulation voltage


tightening torque for terminal

61

98

5-pole

66

53

88

5-pole

82

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 5255

16
8 Wall 8
11

10-25 mm, Cu 3~
with

terminals
per pole 6 x 10 mm sol, 4 x 16 mm s, 4 x 25 mm s,
2 x 35 mm s
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

200

98

rated insulation voltage


current carrying capacity
tightening torque for terminal

160

5-pole

AC/DC 690 V
102 A
3,0 Nm

KF 5355

15
13 Wall 13
15

16-35 mm, Cu 3~
with

terminals
per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,
2 x 50 mm s
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

210

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

260

5-pole

AC/DC 690 V
125 A
12,0 Nm

KF 5505

12
17 Wall 17
12

16-50 mm, Cu 3~
with

terminals
per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,
4 x 50 mm s
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

210

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

310

5-pole

AC/DC 690 V
150 A
12,0 Nm

67

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 5020

3
3 Wall 3
1

without

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

88

KF 5040

4
4 Wall 4
2

without

98

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

KF 5060

10
6 Wall 5
10

without

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

139

70

119

cable

KF 5100

14
6 Wall 6
10

without

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

167

82

125

cable

KF 5250
terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

61

98

cable

16
8 Wall 8
11

without

200
160

cable

68

53

88

cable

98

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Cable Entry via Metric Knockouts
KF 5350
terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

13
15 Wall 15
13

without

260

117

210

cable

KF 5500
terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Outdoor - harsh environment and (or) outdoor"

12
17 Wall 17
12

without

210

117

310

cable

69

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Box Walls without Knockouts

Cable

entries can be drilled individually

Labelling

system for circuit description.


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

Burning

behaviour:
Glow-wire test 960 C
according to IEC 60 695-2-11,
UL Subject 94: V-0
ame-retardant, self-extinguishing

70

Stainless

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Box Walls without Knockouts
KF 8020
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
"Outdoor - harsh environment and (or) outdoor"

88

wall thickness of the bottom part

53

88

box

2,3 mm

KF 8040
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
"Outdoor - harsh environment and (or) outdoor"

98

wall thickness of the bottom part

58

98

box

2,3 mm

KF 8060
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 32
"Outdoor - harsh environment and (or) outdoor"

139

wall thickness of the bottom part

70

119

box

2,6 mm

KF 8100
without

wall thickness of the bottom part

167

82

125

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 32
"Outdoor - harsh environment and (or) outdoor"
box

2,8 mm

71

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Box Walls without Knockouts
KF 8250
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 40
"Outdoor - harsh environment and (or) outdoor"

200

98

wall thickness of the bottom part

160

box

3 mm

KF 8350
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 50
"Outdoor - harsh environment and (or) outdoor"

260

117

wall thickness of the bottom part

210

box

3 mm

KF 8500
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 50
"Outdoor - harsh environment and (or) outdoor"

210

wall thickness of the bottom part

72

3 mm

310

box

117

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Box Walls without Knockouts
KF 4020
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
"Outdoor - harsh environment and (or) outdoor"

88

wall thickness of the bottom part

53

88

box

2,3 mm

KF 4040
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
"Outdoor - harsh environment and (or) outdoor"

98

wall thickness of the bottom part

58

98

box

2,3 mm

KF 4060
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 32
"Outdoor - harsh environment and (or) outdoor"

139

wall thickness of the bottom part

70

119

box

2,6 mm

KF 4100
without

wall thickness of the bottom part

167

82

125

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 32
"Outdoor - harsh environment and (or) outdoor"
box

2,8 mm

73

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Box Walls without Knockouts
KF 4250
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 40
"Outdoor - harsh environment and (or) outdoor"

200

98

wall thickness of the bottom part

160

box

3 mm

KF 4350
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 50
"Outdoor - harsh environment and (or) outdoor"

260

117

wall thickness of the bottom part

210

box

3 mm

KF 4500
without

terminals
walls without knockouts
wall surface can be drilled individually for cable entry max. M 50
"Outdoor - harsh environment and (or) outdoor"

210

wall thickness of the bottom part

74

3 mm

310

box

117

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Approved for United States and Canada (UL/CSA)
Box Walls without Knockouts

Cable

junction boxes with external


brackets made of stainless steel.

Approved

for United States


and Canada

Cable

entries can be drilled


individually.

Stainless

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

Labelling

system for circuit description.


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

Burning

behaviour:
Glow-wire test 960 C
according to IEC 60 695-2-11,
UL Subject 94: V-0
ame-retardant, self-extinguishing
75

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Approved for United States and Canada (UL/CSA)
Box Walls without Knockouts
KF 7020
without

terminals
UL/CSA approval
box walls without knockouts
wall surface can be drilled individually for cable entry M 20,
NPT 3/8" and NPT 1/2"

88

wall thickness of the bottom part


external brackets

53

88

with

2,3 mm
2

KF 7040
without

terminals
UL/CSA approval
box walls without knockouts
wall surface can be drilled individually for cable entry M 20,
NPT 3/8" and NPT 1/2"

98

wall thickness of the bottom part


external brackets

58

98

with

2,3 mm
2

KF 7060
without

terminals
UL/CSA approval
box walls without knockouts
wall surface can be drilled individually for cable entry M 20/25/32,
NPT 3/8", NPT 1/2" and NPT 3/4"

139

wall thickness of the bottom part


external brackets

70

119

with

2,6 mm
2

KF 7100
without

wall thickness of the bottom part


external brackets

76

2,8 mm
2

167
125

terminals
UL/CSA approval
box walls without knockouts
wall surface can be drilled individually for cable entry M 20/25/32,
NPT 3/8", NPT 1/2", NPT 3/4" and 1"
with

82

DK Cable Junction Boxes


Weatherproof, for Outdoor Installation
Approved for United States and Canada (UL/CSA)
Box Walls without Knockouts
KF 7250
without

terminals
UL/CSA approval
box walls without knockouts
wall surface can be drilled individually for cable entry M 20/25/32,
NPT 3/8", NPT 1/2", NPT 3/4" and 1"

200

98

wall thickness of the bottom part


external brackets

160

with

3 mm
4

77

DK Cable Junction Boxes


Waterproof, for Encapsulating

The ingress of water and formation of


condensation are completely prevented.
The sealing compound can be easily removed
for subsequent installations or inspections.

Cable

junction boxes for encapsulating

Scope

of application:
Ground level installations

78

In

case of re-installation or testing the


sealing compound can be removed
easily

Stainless

Scope

Scope

of application:
Pump shafts

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

of application:
Flood areas close to rivers or
unprotected outdoor installations which
are in close proximity to the ground

DK Cable Junction Boxes


Waterproof, for Encapsulating

Permanent waterproof
connection Cable junction boxes
for encapsulating
in accordance with
DIN VDE V 0606-22-100

Time and time again, electricians


come across installation environments whereby the ingress
of water into an enclosure must
be safely excluded. Even enclosures which have a high degree
of protection cannot guarantee
this. The IP degree of protection
allows the ingress of non-harmful
quantities of water in the interior
of an enclosure.

The ingress of water and


formation of condensation
are completely prevented.
The sealing compound
can be easily removed for
subsequent installations or
inspections.

Scope

Under extreme environmental


conditions, for example, the accumulation of condensation may
result in damage to the electrical
installation or devices or cause
these to malfunction.
Ventilation measures will often
suffice to prevent harmful condensation from forming.
In many cases, however, ventilation is not possible, e.g. because
the cable junction boxes are installed close to rivers and water
could enter through the vent holes.

of application:
Installations which are in close proximity
to the ground or underground

Scope

Which applications require


waterproof connections?
Pump shafts
Ground-level installation ducts
in outdoor areas
Flood areas close to rivers
Unprotected outdoor installations which are in close
proximity to the ground
Why is the IP degree of protection alone not sufficient?
All degrees of protection allowed Water ingress
The accumulation of condensation cannot always be
prevented
Ventilation measures cannot
be applied in all environments
The waterproof connection
Sealing the cable junction boxes
with a fast setting, permanently
elastic sealing compound completely the ingress of water and the

of application:
Flood areas close to rivers

excludes forming of condensation.


The sealing compound features
outstanding
insulation properties. As the compound is transparent, it is
possible for visual inspections of
the installation to be carried out
at any time. The durable elastic
material is self-sealing, therefore it
is also easy for the electrical connections to be tested after they
have been sealed.
The sealing compound can be
easily removed for repairs, subsequent installations or changes to
installations.
Another benet: the sealed cable
junction boxes also offer reliable
protection against shock and vibration. The sealing compound
does not, however, provide strain
relief as it only adheres to material
and does not stick together. Suitable cable entries must also be
used here, e.g. Hensel ASM.

Scope

of application:
Ground level installations or underground

79

DK Cable Junction Boxes


Waterproof, for Encapsulating

KF WP 3025

3
3 Wall 3
1

1.5-2.5 mm, Cu 3~
with

Degree of protection

rated insulation voltage


tightening torque for terminal

88

For totally encapsulated cable


junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
AC/DC 690 V
1,2 Nm

KF WP 3045
with

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
cable junction box for encapsulating
for ground installation without live loads or in risk of condensation
formation and ingress of liquids
installation permanently under water up to a depth of 1 meter
possible
with sealing compound and sealing plug
in case of re-installation or testing the sealing compound can be
removed easily
Check the expiry date of the sealing compound!
enclosure volume 350 ml
Degree of protection

rated insulation voltage


tightening torque for terminal

For totally encapsulated cable


junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
AC/DC 690 V
1,2 Nm

98

1.5-4 mm, Cu 3~

4
4 Wall 4
2

5-pole

80

53

88

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
cable junction box for encapsulating
for ground installation without live loads or in risk of condensation
formation and ingress of liquids
installation permanently under water up to a depth of 1 meter
possible
with sealing compound and sealing plug
in case of re-installation or testing the sealing compound can be
removed easily
Check the expiry date of the sealing compound!
enclosure volume 250 ml
5-pole

61

DK Cable Junction Boxes


Waterproof, for Encapsulating

KF WP 3065

10
6 Wall 5
10

2.5-6 mm, Cu 3~
with

terminals
per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,
2 x 10 mm sol
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
cable junction box for encapsulating
for ground installation without live loads or in risk of condensation
formation and ingress of liquids
installation permanently under water up to a depth of 1 meter
possible
with sealing compound and sealing plug
in case of re-installation or testing the sealing compound can be
removed easily
Check the expiry date of the sealing compound!
enclosure volume 750 ml

139

Degree of protection

rated insulation voltage


tightening torque for terminal

For totally encapsulated cable


junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
AC/DC 690 V
1,5 Nm

KF WP 3105

14
6 Wall 6
10

4-10 mm, Cu 3~
with

rated insulation voltage


current carrying capacity
tightening torque for terminal

167

82

125

terminals
per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,
4 x 10 mm sol, 2 x 16 mm s
cable entry via knockouts, order ASM separately
(refer to index cable entry systems)
cable junction box for encapsulating
for ground installation without live loads or in risk of condensation
formation and ingress of liquids
installation permanently under water up to a depth of 1 meter
possible
with sealing compound and sealing plug
in case of re-installation or testing the sealing compound can be
removed easily
Check the expiry date of the sealing compound!
enclosure volume 1200 ml
5-pole

Degree of protection

70

119

5-pole

For totally encapsulated cable


junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
AC/DC 690 V
63 A
2,0 Nm

81

DK Cable Junction Boxes


Waterproof, for Encapsulating

KF WP 2025

3
3 Wall 3
1

1.5-2.5 mm, Cu 3~
with

Degree of protection

rated insulation voltage


tightening torque for terminal

88

For totally encapsulated cable


junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
AC/DC 690 V
1,2 Nm

KF WP 2045
with

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
cable junction box for encapsulating
for ground installation without live loads or in risk of condensation
formation and ingress of liquids
installation permanently under water up to a depth of 1 meter
possible
with sealing compound and sealing plug
in case of re-installation or testing the sealing compound can be
removed easily
Check the expiry date of the sealing compound!
enclosure volume 350 ml
Degree of protection

rated insulation voltage


tightening torque for terminal

For totally encapsulated cable


junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
AC/DC 690 V
1,2 Nm

98

1.5-4 mm, Cu 3~

4
4 Wall 4
2

5-pole

82

53

88

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
cable junction box for encapsulating
for ground installation without live loads or in risk of condensation
formation and ingress of liquids
installation permanently under water up to a depth of 1 meter
possible
with sealing compound and sealing plug
in case of re-installation or testing the sealing compound can be
removed easily
Check the expiry date of the sealing compound!
enclosure volume 250 ml
5-pole

61

DK Cable Junction Boxes


Waterproof, for Encapsulating

KF WP 2065

10
6 Wall 5
10

2.5-6 mm, Cu 3~
with

terminals
per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,
2 x 10 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
cable junction box for encapsulating
for ground installation without live loads or in risk of condensation
formation and ingress of liquids
installation permanently under water up to a depth of 1 meter
possible
with sealing compound and sealing plug
in case of re-installation or testing the sealing compound can be
removed easily
Check the expiry date of the sealing compound!
enclosure volume 750 ml

139

Degree of protection

rated insulation voltage


tightening torque for terminal

For totally encapsulated cable


junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
AC/DC 690 V
1,5 Nm

KF WP 2105

14
6 Wall 6
10

4-10 mm, Cu 3~
with

rated insulation voltage


current carrying capacity
tightening torque for terminal

167

82

125

terminals
per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,
4 x 10 mm sol, 2 x 16 mm s
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
cable junction box for encapsulating
for ground installation without live loads or in risk of condensation
formation and ingress of liquids
installation permanently under water up to a depth of 1 meter
possible
with sealing compound and sealing plug
in case of re-installation or testing the sealing compound can be
removed easily
Check the expiry date of the sealing compound!
enclosure volume 1200 ml
5-pole

Degree of protection

70

119

5-pole

For totally encapsulated cable


junction boxes the degree
of protection of enclosures
according to DIN EN 60529 is
not applicable.
AC/DC 690 V
63 A
2,0 Nm

83

DK Cable Junction Boxes


Waterproof, for Encapsulating

GH 0250
Set sealing compound, 250 ml
as

spares
compound for refilling KF WP x025 after changes or repairs
Check the expiry date of the sealing compound!
sealing

GH 0350
Set sealing compound, 350 ml
as

spares
compound for refilling KF WP x045 after changes or repairs
Check the expiry date of the sealing compound!
sealing

GH 0750
Set sealing compound, 750 ml
as

spares
compound for refilling KF WP x065 after changes or repairs
Check the expiry date of the sealing compound!
sealing

GH 1200
set sealing compound, 1200 ml
as

spares
compound for refilling KF WP x105 after changes or repairs
Check the expiry date of the sealing compound!
sealing

84

DK Cable Junction Boxes


for Offshore Applications
Cable Entry via Metric Knockouts

Degree

of protection: IP 66 / IP 67
temporary submersion
up to 1 meter, max. 15 minutes
with cable glands ASS.. available as an
accessory

Cable

Stainless

Saltwater-proof

Material:

UV-resistant

- halogen free
- impact resistant
- low toxicity
Burning behaviour: UL Subject 94 = 5V

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

entries can be drilled individually

Labelling

system for circuit description.


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

85

DK Cable Junction Boxes


for Offshore Applications
Cable Entry via Metric Knockouts
KD 5025

3
3 Wall 3
1

1.5-2.5 mm, Cu 3~
with

rated insulation voltage


tightening torque for terminal

88

AC/DC 690 V
1,2 Nm

KD 5125

3
3 Wall 3
1

1.5-2.5 mm, Cu 3~
with external fixing
with

88

AC/DC 690 V
1,2 Nm

KD 5045
with

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V
rated insulation voltage
tightening torque for terminal

AC/DC 690 V
1,2 Nm

98

1.5-4 mm, Cu 3~

4
4 Wall 4
2

5-pole

86

53

88

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V
5-pole

rated insulation voltage


tightening torque for terminal

53

88

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V
5-pole

61

DK Cable Junction Boxes


for Offshore Applications
Cable Entry via Metric Knockouts
KD 5065

10
6 Wall 5
10

2.5-6 mm, Cu 3~
with

terminals
per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,
2 x 10 mm sol
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

139

rated insulation voltage


tightening torque for terminal

AC/DC 690 V
1,5 Nm

KD 5105

14
6 Wall 6
10

4-10 mm, Cu 3~
with

terminals
per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,
4 x 10 mm sol, 2 x 16 mm s
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

167

82

125

5-pole

rated insulation voltage


current carrying capacity
tightening torque for terminal

70

119

5-pole

AC/DC 690 V
63 A
2,0 Nm

KD 5255

16
8 Wall 8
11

10-25 mm, Cu 3~
with

terminals
per pole 6 x 10 mm sol, 4 x 16 mm s, 4 x 25 mm s,
2 x 35 mm s
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

200

98

rated insulation voltage


current carrying capacity
tightening torque for terminal

160

5-pole

AC/DC 690 V
102 A
3,0 Nm

87

DK Cable Junction Boxes


for Offshore Applications
Cable Entry via Metric Knockouts
KD 5355

15
13 Wall 13
15

16-35 mm, Cu 3~
with

terminals
per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s,
2 x 50 mm s
cable entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

210

rated insulation voltage


current carrying capacity
tightening torque for terminal

88

AC/DC 690 V
125 A
12,0 Nm

260

5-pole

117

DK Cable Junction Boxes


for Offshore Applications
Cable Entry via Metric Knockouts
KD 5020

3
3 Wall 3
1

without

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

88

53

88

cable

KD 5120

3
3 Wall 3
1

with external fixing


without

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

88

53

88

cable

KD 5040

4
4 Wall 4
2

without

98

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

KD 5060

139

70

119

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

10
6 Wall 5
10

without
cable

61

98

cable

89

DK Cable Junction Boxes


for Offshore Applications
Cable Entry via Metric Knockouts
KD 5100

14
6 Wall 6
10

without

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

167

82

125

cable

KD 5250

16
8 Wall 8
11

without

terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

200

98

160

cable

KD 5350
terminals
entry via knockouts, order ASS separately
(refer to index cable entry systems)
"Offshore applications"
saltwater-proof
acid-resistant lid screws made of stainless steel
burning behaviour 960 C; UL Subject 94: 5 V

13
15 Wall 15
13

without

260

90

210

cable

117

DK Cable Junction Boxes


for Offshore Applications
Box Walls without Knockouts
KD 4020
without

terminals
applications"
acid-resistant lid screws made of stainless steel
box walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
burning behaviour 960 C; UL Subject 94: 5 V
wall thickness of the bottom part

88

53

88

53

88

"Offshore

2,3 mm

KD 4120
with external fixing
without

terminals
applications"
acid-resistant lid screws made of stainless steel
box walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
burning behaviour 960 C; UL Subject 94: 5 V
wall thickness of the bottom part

88

"Offshore

2,3 mm

KD 4040
without

terminals
applications"
acid-resistant lid screws made of stainless steel
box walls without knockouts
wall surface can be drilled individually for cable entry max. M 20
burning behaviour 960 C; UL Subject 94: 5 V

98

wall thickness of the bottom part

58

98

"Offshore

2,3 mm

KD 4060
without

wall thickness of the bottom part

139

70

119

terminals
applications"
acid-resistant lid screws made of stainless steel
box walls without knockouts
wall surface can be drilled individually for cable entry max. M 32
burning behaviour 960 C; UL Subject 94: 5 V
"Offshore

2,6 mm

91

DK Cable Junction Boxes


for Offshore Applications
Box Walls without Knockouts
KD 4100
without

terminals
applications"
acid-resistant lid screws made of stainless steel
box walls without knockouts
wall surface can be drilled individually for cable entry max. M 32
burning behaviour 960 C; UL Subject 94: 5 V

167

wall thickness of the bottom part

82

125

"Offshore

2,8 mm

KD 4250
without

terminals
applications"
acid-resistant lid screws made of stainless steel
box walls without knockouts
wall surface can be drilled individually for cable entry max. M 40
burning behaviour 960 C; UL Subject 94: 5 V

200

98

wall thickness of the bottom part

160

"Offshore

3 mm

KD 4350
without

terminals
applications"
acid-resistant lid screws made of stainless steel
box walls without knockouts
wall surface can be drilled individually for cable entry max. M 50
burning behaviour 960 C; UL Subject 94: 5 V

260

wall thickness of the bottom part

92

3 mm

210

"Offshore

117

DK Cable Junction Boxes


Tested for Intrinsic Fire Resistance,
with Included Grommets

Cable junction boxes IP 65 / IP 66


according to IEC 60670-22.,
tested for intrinsic fire resistance.

Material: Insulating material /


Duroplast

Material: Sheet steel,


powder-coated

FK Cable junction boxes comply


with these requirements when
used together with type-approved cables as well as suitable
cable clamps or mounting
devices.

Degree

Special characteristics:
of protection: IP 65
Impact strength:
IK 06 (1 Joule)
Mounting via internal fixing
with approved universal anchors (included)
Halogen-free
Protection against electric
shock: insulated

Special characteristics:
Degree of protection: IP 66
Impact strength:
IK 10 (20 Joule)
Mounting via external
brackets for use with fixings
approved by the building
authorities
Halogen-free
Protection against electric
shock: earthed
No additional fire load, no
toxic or corrosive emissions
Protection against direct
contact also maintained due
to the box

Cable

junction boxes tested


for intrinsic fire resistance
Intrinsic fire resistance according to DIN 4102 part 12
(German standard) together
with function-retaining cables
of 0.5-16 mm
Cover with 4 captive screws
Pastel orange RAL 2003

93

DK Cable Junction Boxes


Tested for Intrinsic Fire Resistance,
with Included Grommets
FK 7045
7 Wall 7

Cable junction box 0.8 mm / 0.5-1.5 mm, Cu


Connection box 0,8 mm / 0,5-4 mm, Cu
5-pole

per pole 4 x 0.8 mm / 0.5 mm sol, 4 x 1.5 mm sol,


2 x 2.5 mm sol, 2 x 4 mm sol
connecting terminal made from ceramic with resistance to high
temperatures
included cable entry 4 EDKF 32, sealing range 8-23 mm
Intrinsic fire resistance in accordance with DIN 4102 part 12 in
combination with function-retaining cables
Tested with the cable manufacturers Dtwyler, Eupen, Studer, Prysmian
and Nexans for the intrinsic fire resistance E30 and E90, see test
certificate no.: P-MPA-E-08-021, valid till July 27, 2014,
download available from www.hensel-electric.de
The enclosed screw anchors can be used for concrete C20/25,
limestone blocks KSV 12, building bricks MZ 12 and clinker bricks KS 12.
for normal environment and protected outdoor
rated insulation voltage
current carrying capacity

AC/DC 400 V
32 A

FK 7105

7
9 Wall 9
7

Cable junction box 1.5-4 mm, Cu


Connection box 1.5-10 mm, Cu
5-pole

94

AC/DC 400 V
40 A

168
143

per pole 4 x 1.5 mm sol, 4 x 2.5 mm sol, 4 x 4 mm sol,


2 x 6 mm sol, 2 x 10 mm sol
connecting terminal made from ceramic with resistance to high
temperatures
included cable entry 4 EDKF 40, sealing range 11-30 mm
Intrinsic fire resistance in accordance with DIN 4102 part 12 in
combination with function-retaining cables
Tested with the cable manufacturers Dtwyler, Eupen, Studer,
Prysmian and Nexans for the intrinsic fire resistance E30 and E90,
see test certificate no.: P-MPA-E-08-021, valid till July 27, 2014,
download available from www.hensel-electric.de
The enclosed screw anchors can be used for concrete C20/25,
limestone blocks KSV 12, building bricks MZ 12 and clinker bricks
KS 12.
for normal environment and protected outdoor
rated insulation voltage
current carrying capacity

59

122

122

71

DK Cable Junction Boxes


Tested for Intrinsic Fire Resistance,
with Included Grommets
FK 7165

9
9 Wall 9
9

Cable junction box 1.5-6 mm, Cu


Connection box 1.5-16 mm, Cu
5-pole

rated insulation voltage


current carrying capacity

242

85

168

per pole 4 x 1.5 mm sol, 4 x 2.5 mm sol, 4 x 4 mm sol,


4 x 6 mm sol, 2 x 10 mm sol, 2 x 16 mm r
(remove cable protection)
connecting terminal made from ceramic with resistance to high
temperatures
included cable entry 4 EDKF 40, sealing range 11-30 mm
Intrinsic fire resistance in accordance with DIN 4102 part 12 in
combination with function-retaining cables
Tested with the cable manufacturers Dtwyler, Eupen, Studer,
Prysmian and Nexans for the intrinsic fire resistance E30 and E90,
see test certificate no.: P-MPA-E-08-021, valid till July 27, 2014,
download available from www.hensel-electric.de
The enclosed screw anchors can be used for concrete C20/25,
limestone blocks KSV 12, building bricks MZ 12 and
clinker bricks KS 12.
for normal environment and protected outdoor
AC/DC 400 V
63 A

95

DK Cable Junction Boxes


Tested for Intrinsic Fire Resistance
Cable Entry via Mounted Grommets
FK 9025

7
Wall

Cable junction box 0.8 mm / 0.5-1.5 mm, Cu


Connection box 0,8 mm / 0,5-4 mm, Cu
5-pole

rated insulation voltage


current carrying capacity

AC/DC 400 V
32 A

FK 9105

7
Wall

Cable junction box 1.5-4 mm, Cu


Connection box 1.5-10 mm, Cu

5-pole

96

AC/DC 400 V
40 A

8,2

170
150

200
160

per pole 4 x 1.5 mm sol, 4 x 2.5 mm sol, 4 x 4 mm sol,


2 x 6 mm sol, 2 x 10 mm sol
connecting terminal made from ceramic with resistance to high
temperatures
mounted grommets 4 EDKF 32,
sealing range: 8-23 mm, closed
Intrinsic fire resistance in accordance with DIN 4102 part 12 in
combination with function-retaining cables
Tested with cable manufacturers Dtwyler, Eupen, Nexans,
Studer, Pirelli and Lynenwerk for the intrinsic fire resistance E30
and E90, see test certificate no.: P-MPA-E-02-032, valid till March
20, 2018, download available from www.hensel-electric.de
mounted using exterior wall fixings
(for dowels refer to technical data)
for normal environment and protected outdoor
rated insulation voltage
current carrying capacity

89

150
110

170
150

8,2

per pole 4 x 0.8 mm / 0.5 mm sol, 4 x 1.5 mm sol,


2 x 2.5 mm sol, 2 x 4 mm sol
connecting terminal made from ceramic with resistance to high
temperatures
mounted grommets 4 EDKF 32,
sealing range: 8-23 mm, closed
Intrinsic fire resistance in accordance with DIN 4102 part 12 in
combination with function-retaining cables
Tested with cable manufacturers Dtwyler, Eupen, Nexans,
Studer, Pirelli and Lynenwerk for the intrinsic fire resistance E30 and
E90, see test certificate no.: P-MPA-E-02-032, valid till March 20, 2018,
download available from www.hensel-electric.de
mounted using exterior wall fixings
(for dowels refer to technical data)
for normal environment and protected outdoor

89

DK Cable Junction Boxes


Tested for Intrinsic Fire Resistance
Cable Entry via Mounted Grommets
FK 9255

9
Wall

Cable junction box 1.5-6 mm, Cu


Connection box 1.5-16 mm, Cu

5-pole

rated insulation voltage


current carrying capacity

AC/DC 400 V
63 A

FK 6505

29
30 Wall 30
29

Cable junction box E90 16-35 mm, Cu, "r"


Connection box E90 16-50 mm, Cu, "r"
5-pole

per pole 6 x 16 mm, 4 x 25 mm, 4 x 35 mm, 2 x 50 mm


terminal made from ceramic with resistance to high
temperatures
Intrinsic fire resistance in accordance with DIN 4102 part 12 in
combination with function-retaining cables
Tested with the cable manufacturers Dtwyler and Eupen for the
intrinsic fire resistance E90, see test certificate no.: P-1011 DMT DO,
download available at www.hensel-electric.de > Type - Documents
mounted using exterior wall fixings, keyhole (6.5 mm dowel refer to
technical data)
for normal environment and protected outdoor

280
262

connecting

rated insulation voltage


current carrying capacity
Material

89

8,2

220
200

200
160

per pole 4 x 1.5 mm sol, 4 x 2.5 mm sol, 4 x 4 mm sol,


4 x 6 mm sol, 2 x 10 mm sol, 2 x 16 mm r (remove cable protection)
connecting terminal made from ceramic with resistance to high
temperatures
mounted grommets 4 EDKF 40,
sealing range 11-30 mm, closed
Intrinsic fire resistance in accordance with DIN 4102 part 12 in
combination with function-retaining cables
Tested with cable manufacturers Dtwyler, Eupen, Nexans, Studer,
Pirelli and Lynenwerk for the intrinsic fire resistance E30 and E90,
see test certificate no.: P-MPA-E-02-032, valid till March 20, 2018,
download available from www.hensel-electric.de
mounted using exterior wall fixings
(for dowels refer to technical data)
for normal environment and protected outdoor

138

534
513

Ui = 690 V a.c./d.c.
150 A
External brackets for wall
fixing: Stainless steel 1.4462,
resistance class IV
Enclosure including lid and outer
screws: Stainless steel 1.4571,
resistance class III

97

DK Cable Junction Boxes


Tested for Intrinsic Fire Resistance
Cable Entry via Mounted Grommets
FK 9259

9
Wall

Cable junction box 1.5-10 mm, Cu

cable

junction box with fused outgoing unit


01 neozed fuse base
5-pole terminal with 2 connecting terminals, 2 junction terminals
and 2 PE terminals, each 1.5-10 mm sol
terminal block made from ceramic with resistance to high
temperatures
mounted grommets 4 EDKF 40,
sealing range 11-30 mm, closed
intrinsic fire resistance E 30 in accordance with DIN 4102 part 12
The use of this equipment requires the approval from the planning
and building control office for individual cases
Tested with cable manufacturers Dtwyler and Nexans for the
intrinsic fire resistance E30,
see test certificate no.: P-MPA-E-02-032, valid till March 20, 2018,
download available from www.hensel-electric.de
mounted using exterior wall fixings
(for dowels refer to technical data)
for normal environment and protected outdoor

220
200

rated insulation voltage


current carrying capacity

200
160

AC 400 V
40 A

FK 9259, with fused outgoing circuit


Can be used in emergency lighting in installations that
cover a large area (e.g. tunnels).
The use of a fused branch circuit makes it possible to
supply a group of emergency luminaires with one supply
lead.
If one or several emergency luminaires are damaged
during a re, the back-up fuse is tripped and ensures
that the power supply of the common supply lead is
maintained.
The use of this equipment requires approval from
the planning department and building control
office for individual cases.

98

8,2

L1
L2
L3
N
PE
PE
Note
selectivity of
protective
system

Load
Emergency
luminaire

F1
(D 01)

89

DK Cable junction boxes


Communication Box
Tested for Intrinsic Fire Resistance
FK 5000

31
31 Wall 31
31

Communication junction box E30


for the installation of connecting device
for telecommunications
without

terminals
mounting brackets for the installation of connecting device
for telecommunications
Intrinsic fire resistance in accordance with DIN 4102 part 12 in
combination with function-retaining cables
cable entry via integrated elastic membranes
cable entries on 4 sides 1 x up to 35 mm, 4 x up to 16 mm
each
The enclosed screw anchors can be used for concrete C20/25,
limestone blocks KSV 12, building bricks MZ 12 and clinker bricks
KS 12.
The use of this equipment requires the approval from the planning
and building control office for individual cases

285
255

rated insulation voltage

155

255

with

10

{Un = 100 V a.c.}

FK 5110
Connecting device for telecommunications
screwless for 10 pairs
LSA

connection technology, solder and screwless, no insulation removal is required


installation on mounting brackets in FK 5000
suitable for a solid conductor with diameter of 0.4 up to 0.8 mm or for two identical solid
conductors with diameters of 0.4 up to 0.65 mm
outer diameter of insulation 0.7 up to 1.6 mm
with fixing screws
for

rated insulation voltage

{Un = 100 V a.c.}

FK 5120
Connecting device for telecommunications
screwless for 20 pairs
LSA

connection technology, solder and screwless, no insulation removal is required


installation on mounting brackets in FK 5000
suitable for a solid conductor with diameter of 0.4 up to 0.8 mm or for two identical solid
conductors with diameters of 0.4 up to 0.65 mm
outer diameter of insulation 0.7 up to 1.6 mm
with fixing screws
for

rated insulation voltage

{Un = 100 V a.c.}

99

DK Cable junction boxes


Communication Box
Tested for Intrinsic Fire Resistance
FK 5210
Connecting device for telecommunications
screw-type connection for 10 pairs
screw/screw

connection technology
installation on mounting brackets in FK 5000
suitable for a solid conductor with diameter of 0.4 up to 0.8 mm or for two identical solid
conductors with diameters of 0.4 up to 0.65 mm
with fixing screws
with labelling strips
for

rated insulation voltage

{Un = 100 V a.c.}

FK 5220
Connecting device for telecommunications
screw-type connection for 20 pairs
screw/screw

connection technology
installation on mounting brackets in FK 5000
suitable for a solid conductor with diameter of 0.4 up to 0.8 mm or for two identical solid
conductors with diameters of 0.4 up to 0.65 mm
with fixing screws
with labelling strips
for

rated insulation voltage

100

{Un = 100 V a.c.}

DK Cable Junction Boxes


Tested for Intrinsic Fire Resistance
Cable Entry
EDKF 32
Grommets
for knockouts M 32
sealing

range: 8-23 mm
32.5 mm
wall thickness 1.5-3.5 mm
for indoor - normal environment and (or) protected outdoor installation
ambient temperature - 25 to + 35 C
glow wire test IEC 60 695-2-11: 750 C
bore-hole:

EDKF 40
Grommets
for knockouts M 40
sealing

range: 11-30 mm
40.5 mm
wall thickness 1.5-3.5 mm
for indoor - normal environment and (or) protected outdoor installation
ambient temperature - 25 to + 35 C
glow wire test IEC 60 695-2-11: 750 C
bore-hole:

101

DK Cable Junction Boxes


for Safety Lighting Circuits
Cable Entry via Metric Knockouts

Cable

junction boxes for security lighting


circuits with red lid.

Terminal

cables.

102

box for equipotential bonding

Degree

of protection IP 65
using cable glands ASM.. available as an
accessory

Stainless

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

Labelling

system for circuit description.


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

Burning

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

DK Cable Junction Boxes


for Safety Lighting Circuits
Cable Entry via Metric Knockouts
D 9225

3
3 Wall 3
1

1.5-2.5 mm, Cu 3~
with

rated insulation voltage


tightening torque for terminal

88

53

88

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol
included cable entry: 4 ESM 20, sealing range 6-13 mm
for security lighting circuits
with red lid RAL 3000
for normal environment and protected outdoor
5-pole

AC/DC 690 V
1,2 Nm

D 9220

3
3 Wall 3
1

without

88

53

88

terminals
security lighting circuits
with red lid RAL 3000
included cable entry: 4 ESM 20, sealing range 6-13 mm
for normal environment and protected outdoor
for

D 9245
1.5-4 mm, Cu 3~

4
4 Wall 4
2

with

98

rated insulation voltage


tightening torque for terminal

61

98

terminals
per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
included cable entry: 4 ESM 25, sealing range 9-17 mm
for security lighting circuits
with red lid RAL 3000
for normal environment and protected outdoor
5-pole

AC/DC 690 V
1,2 Nm

D 9240

4
4 Wall 4
2

without

98

61

98

terminals
security lighting circuits
with red lid RAL 3000
included cable entry: 4 ESM 25, sealing range 9-17 mm
for normal environment and protected outdoor
for

103

DK Cable Junction Boxes


for Equipotential Bonding Conductors
Cable Entry via Removable Grommets
DP 9026

26
26 Wall 26
25

4-25 mm / 4-10 mm, Cu


with

104

88
88

terminals
1 x 4-25 mm, 5 x 4-10 mm (16 mm sol)
for equipotential bonding cables
included cable entry: 4 DPS 02, sealing range 10-13,5 mm
for normal environment and protected outdoor
1-pole

50

DK Cable Junction Boxes


with Main Line Branch Terminals for Copper Conductors, Sealable
Cable Entry via Metric Knockouts

Degree

of protection IP 65
using cable glands ASM.. available as an
accessory

DK

cable junction boxes with main


branch terminals for copper conductors
are equipped with sealable lids.

Labelling

system for circuit description.


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

Stainless

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

Burning

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

105

DK Cable Junction Boxes


with Main Line Branch Terminals for Copper Conductors, Sealable
Cable Entry via Metric Knockouts
K 9259

16
8 Wall 8
11

6-25 mm, Cu
with

main line branch terminals for copper conductors


per pole terminals for incoming cables:
10-25 mm r, 6-16 mm f, with end ferrule, terminals for outgoing
cables: 6-16 mm r, 4-10 mm with end ferrule
with sealing facility
included cable entry: 3 ESM 40, sealing range 17-30 mm
for normal environment and protected outdoor

200

98

rated insulation voltage


current carrying capacity
tightening torque for terminal

160

4-pole

AC 400 V
80 A
3.0 Nm terminals for incoming
cables
terminals for outgoing cables
3.0 Nm

K 9258

16
8 Wall 8
11

6-25 mm, Cu
with

main line branch terminals for copper conductors


per pole terminals for incoming cables
10-25 mm r, 6-16 mm f, with end ferrule, terminals for outgoing
cables 6-16 mm r, 4-10 mm f with end ferrule
with sealing facility
included cable entry: 3 ESM 40, sealing range 17-30 mm
for normal environment and protected outdoor

200

98

rated insulation voltage


current carrying capacity
tightening torque for terminal

160

5-pole,

AC 400 V
80 A
3.0 Nm terminals for incoming
cables
terminals for outgoing cables
3.0 Nm

K 9508

17
12 Wall 12
17

6-25 mm, Cu
with

main line branch terminals for copper conductors


per pole terminals for incoming cables:
10-25 mm r, 6-16 mm f, with end ferrule, terminals for outgoing
cables: 6-16 mm r, 4-10 mm with end ferrule
with sealing facility
cable entry via knockouts, order AKM/ASM separately
(refer to index cable entry systems)
for normal environment and protected outdoor

310

rated insulation voltage


current carrying capacity
tightening torque for terminal

106

AC 400 V
80 A
3.0 Nm terminals for incoming
cables
terminals for outgoing cables
3.0 Nm

210

4-pole

117

DK Cable Junction Boxes


with Main Line Branch Terminals for Copper Conductors, Sealable
Cable Entry via Metric Knockouts
K 9503

17
12 Wall 12
17

6-25 mm, Cu
with

main line branch terminals for copper conductors


per pole terminals for incoming cables
10-25 mm r, 6-16 mm f, with end ferrule, terminals for outgoing
cables 6-16 mm r, 4-10 mm f with end ferrule
with sealing facility
cable entry via knockouts, order AKM/ASM separately
(refer to index cable entry systems)
for normal environment and protected outdoor

310

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

210

5-pole,

AC 400 V
80 A
3.0 Nm terminals for incoming
cables
terminals for outgoing cables
3.0 Nm

K 9509

17
12 Wall 12
17

6-35 mm, Cu
with

main line branch terminals for copper conductors


per pole terminals for incoming cables:
16-35 mm r, 10-25 mm f, with end ferrule, terminals for
outgoing cables: 10-25 mm r, 6-16 mm f with end ferrule
with sealing facility
cable entry via knockouts, order AKM/ASM separately
(refer to index cable entry systems)
for normal environment and protected outdoor

310

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

210

4-pole

AC 400 V
100 A
4.0 Nm incoming terminals
terminals for outgoing cables
3.0 Nm

K 9507

17
12 Wall 12
17

6-35 mm, Cu
with

main line branch terminals for copper conductors


per pole incoming terminals 16-35 mm r, 10-25 mm f,
with end ferrule, outgoing cables 10-25 mm r, 6-16 mm f with
end ferrule
with sealing facility
cable entry via knockouts, order AKM/ASM separately
(refer to index cable entry systems)
for normal environment and protected outdoor

310

117

rated insulation voltage


current carrying capacity
tightening torque for terminal

210

5-pole

AC 400 V
100 A
4.0 Nm incoming terminals
terminals for outgoing cables
3.0 Nm

107

DK Cable Junction Boxes


with Terminal Blocks for Aluminium- and Copper Conductors
Cable Entry via Metric Knockouts

Other terminal sets available on


request.

Stainless

steel cover screws with quick


fastening metric thread.
Reducing cover xing time.

DK

cable junction boxes with main


branch terminals for copper conductors
are equipped with sealable lids.

108

Labelling

system for circuit description.


template on the Internet at
www.hensel-electric.de - in the
Downloads area.

Label

Burning

behaviour:
Glow wire test according
to IEC 60 695-2-11: 750 C,
flame-retardant, self-extinguishing

Included

accessories as listed:
grommets ESM = IP 55

DK Cable Junction Boxes


with Terminal Blocks for Aluminium- and Copper Conductors
Cable Entry via Metric Knockouts
RD 9123

3
3 Wall 3
1

1.5-2.5 mm
3

rated insulation voltage


current carrying capacity
tightening torque for terminal

88

AC/DC 500 V
24 A
0,4 Nm

RD 9125

3
3 Wall 3
1

1.5-2.5 mm
5

88

AC/DC 500 V
24 A
0,4 Nm

RD 9127

3
3 Wall 3
1

1.5-2.5 mm
7

88

53

88

terminal blocks WKM 2.5/15


terminal 2 x 0,5-2,5 mm f, 2 x 0,5-4 mm sol or
2 x 1,5-2,5 mm s,
see Technical details for more information about terminal
assignment
terminal blocks, by Wieland
for aluminium and copper conductors
terminal marking, neutral
cable/conduit entry via metric knockouts order ESM/AKM
separately (refer to index LES)
with external fixing
for normal environment and protected outdoor
per

rated insulation voltage


current carrying capacity
tightening torque for terminal

53

88

terminal blocks WKM 2.5/15


terminal 2 x 0,5-2,5 mm f, 2 x 0,5-4 mm sol or
2 x 1,5-2,5 mm s,
see Technical details for more information about terminal
assignment
terminal blocks, by Wieland
for aluminium and copper conductors
terminal marking, neutral
cable/conduit entry via metric knockouts order ESM/AKM
separately (refer to index LES)
with external fixing
for normal environment and protected outdoor
per

rated insulation voltage


current carrying capacity
tightening torque for terminal

53

88

terminal blocks WKM 2.5/15


terminal 2 x 0,5-2,5 mm f, 2 x 0,5-4 mm sol or
2 x 1,5-2,5 mm s,
see Technical details for more information about terminal
assignment
terminal blocks, by Wieland
for aluminium and copper conductors
terminal marking, neutral
cable/conduit entry via metric knockouts order ESM/AKM
separately (refer to index LES)
with external fixing
for normal environment and protected outdoor
per

AC/DC 500 V
24 A
0,4 Nm

109

DK Cable Junction Boxes


with Terminal Blocks for Aluminium- and Copper Conductors
Cable Entry via Metric Knockouts
RD 9045
1.5-4 mm

4
4 Wall 4
2

98

terminal blocks WKM 4/15


terminal 2 x 0,5-4 mm f, 2 x 0,5-6 mm sol or 2 x 1,5-4 mm s,
see Technical details DK cable junction boxes for more information
about terminal assignment
terminal blocks, by Wieland
for aluminium and copper conductors
terminal marking, neutral
cable/conduit entry via metric knockouts order ESM/AKM
separately (refer to index LES)
for normal environment and protected outdoor
rated insulation voltage
current carrying capacity
tightening torque for terminal

AC/DC 500 V
28 A
0,5 Nm

RD 9041
1.5-4 mm

4
4 Wall 4
2

10

98

terminal blocks WKM 4/15


terminal 2 x 0,5-4 mm f, 2 x 0,5-6 mm sol or 2 x 1,5-4 mm s,
see Technical details DK cable junction boxes for more information
about terminal assignment
terminal blocks, by Wieland
for aluminium and copper conductors
terminal marking, neutral
cable/conduit entry via metric knockouts order ESM/AKM
separately (refer to index LES)
for normal environment and protected outdoor
rated insulation voltage
current carrying capacity
tightening torque for terminal

AC/DC 500 V
28 A
0,5 Nm

RK 9062

10
6 Wall 5
10

1.5-4 mm
12

AC/DC 690 V
41 A
0,5 Nm

139
119

terminal blocks WK 4/U


terminal 2 x 0,5-4 mm f, 2 x 0,5-6 mm sol or 2 x 1,5-4 mm s,
see Technical details DK cable junction boxes for more information
about terminal assignment
terminal blocks, by Wieland
for aluminium and copper conductors
terminal marking, neutral
cable/conduit entry via metric knockouts order ESM/AKM
separately (refer to index LES)
for normal environment and protected outdoor
per

rated insulation voltage


current carrying capacity
tightening torque for terminal

61

98

per

110

61

98

per

70

DK Cable Junction Boxes


with Terminal Blocks for Aluminium- and Copper Conductors
Cable Entry via Metric Knockouts
RK 9064

10
6 Wall 5
10

1.5-4 mm
14

terminal blocks WK 4/U


terminal 2 x 0,5-4 mm f, 2 x 0,5-6 mm sol or 2 x 1,5-4 mm s,
see Technical details DK cable junction boxes for more information
about terminal assignment
terminal blocks, by Wieland
for aluminium and copper conductors
terminal marking, neutral
cable/conduit entry via metric knockouts order ESM/AKM
separately (refer to index LES)
for normal environment and protected outdoor

139

rated insulation voltage


current carrying capacity
tightening torque for terminal

AC/DC 690 V
41 A
0,5 Nm

RK 9109

14
6 Wall 6
10

1.5-4 mm
19

167

AC/DC 690 V
41 A
0,5 Nm

RK 9104

14
6 Wall 6
10

1.5-4 mm
24

167

82

125

terminal blocks WK 4/U


terminal 2 x 0,5-4 mm f, 2 x 0,5-6 mm sol or 2 x 1,5-4 mm s,
see Technical details DK cable junction boxes for more information
about terminal assignment
terminal blocks, by Wieland
for aluminium and copper conductors
terminal marking, neutral
cable/conduit entry via metric knockouts order ESM/AKM
separately (refer to index LES)
for normal environment and protected outdoor
per

rated insulation voltage


current carrying capacity
tightening torque for terminal

82

125

terminal blocks WK 4/U


terminal 2 x 0,5-4 mm f, 2 x 0,5-6 mm sol or 2 x 1,5-4 mm s,
see Technical details DK cable junction boxes for more information
about terminal assignment
terminal blocks, by Wieland
for aluminium and copper conductors
terminal marking, neutral
cable/conduit entry via metric knockouts order ESM/AKM
separately (refer to index LES)
for normal environment and protected outdoor
per

rated insulation voltage


current carrying capacity
tightening torque for terminal

70

119

per

AC/DC 690 V
41 A
0,5 Nm

111

DK Cable Junction Boxes


Accessories

DIN rails

112

113

Cable retention

114

Terminal sets

115 - 117

Accessories

118

Facility for sealing

119

Accessories for cable junction boxes 70 mm

120 - 121

DK Cable Junction Boxes


Accessories

TSD 02
DIN rail
for

cable junction boxes D x020, D x120, KF x020, KD x020


and empty box KF PV 0100
max. installation depth 32 mm, top hat profile 15 mm
for the installation of terminal blocks
with fixing screws

15

57

5
4,2

2,5 12 8

TSD 04
DIN rail
for

cable junction boxes D x040, KF x040, KD x040 and


empty box KF PV 0200
max. installation depth: 40 mm, top hat profile 15 mm
for the installation of terminal blocks
with fixing screws

15

82

5
4,2

7 12 8

TSK 06
DIN rail
for

cable junction boxes K x060, KF x060, KF x060


and empty box KF PV 0300
max. installation depth: 44,5 mm, top hat profile 35 mm
for the installation of terminal blocks
with fixing screws

105
35

54
33,5

5,5

7,5
4,5

TSK 10
DIN rail
for

cable junction boxes K x100, KF x100, KD x100


and empty box KF PV 0400
max. installation depth: 56,5 mm, top hat profile 35 mm
for the installation of terminal blocks
with fixing screws

35

7,5

TSK 25
DIN rail
for

cable junction boxes K x250, KF x250, K x350, KF x350,


KD x250, KD x350 and empty boxes KF PV 0500, KF PV 0600
max. installation depth: 71,5 mm, top hat profile 35 mm
for the installation of terminal blocks
with fixing screws

35

7,5

TSK 35
DIN rail
for

213

7,5

96

35

cable junction boxes K x350, KF x350, KD x350,


and empty box KF PV 0600
max. installation depth: 80,5 mm, top hat profile 35 mm
for the installation of terminal blocks
with fixing screws

4,5

TSK 50
DIN rail
for

7,5

35

cable junction boxes K x500, KF x500 and empty box KF PV 0700


installation depth: 80,5 mm, top hat profile 35 mm
for the installation of terminal blocks
with fixing screws
max.

113

DK Cable Junction Boxes


Accessories

KHR 01
Cable retention
for cable diameter 6,5 - 14 mm
set

with 10 x 6 cable rentention rings


pieces for cable diameter 6,5 - 10 mm
30 pieces for cable diameter 10 - 14 mm
30

KHR 02
Cable retention
for cable diameter 10 - 16 mm
set

with 10 x 6 cable rentention rings


pieces for cable diameter 10 - 14 mm
30 pieces for cable diameter 13 - 16 mm
30

114

DK Cable Junction Boxes


Accessories

DKL 04
Rated connecting capacity: 1,5-6 mm, Cu
for

insertion in cable junction boxes


per pole 6 x 1.5 mm sol, 4 x 2.5 mm sol, 3 x 4 mm sol,
2 x 6 mm sol
for cable junction boxes D 8020, D 8120, D 8040, D 9020, D 9120,
D 9040, D 9220, DP 9020, DP 9220, DE 9320, DE 9321, DE 9340,
DE 9341, KF 4020, KF 4040, KF 5020, KF 5040, KF 8020, KF 8040,
KF 9020, KF 9040, KD 5020, KD 5040, KD 4020, KD 4040
complete with fixing elements
5-pole

rated insulation voltage


Dismantling length
tightening torque for terminal

AC/DC 690 V
11 mm
1,2 Nm

KKL 06
Rated connecting capacity: 2,5-10 mm, Cu
for

insertion in cable junction boxes


per pole 4 x 2.5 mm sol, 4 x 4 mm sol, 3 x 6 mm sol,
2 x 10 mm sol
for cable junction boxes K 8060, K 9060, KF 4060, KF 5060, KF 8060,
KF 9060, KD 5060, KD 4060
complete with fixing elements
5-pole

rated insulation voltage


Dismantling length
tightening torque for terminal

AC/DC 690 V
11 mm
1,5 Nm

KLS 10
Rated connecting capacity: 2,5-16 mm, Cu
for

insertion in cable junction boxes


carrying capacity: 63 A
5-pole per pole 6 x 2.5 mm sol, 4 x 4 mm sol, 4 x 6 mm sol,
4 x 10 mm sol, 2 x 16 mm s
for cable junction boxes K 8100, K 9100, KF 4100, KF 5100, KF 8100,
KF 9100, KD 5100, KD 4100
complete with fixing elements
current

rated insulation voltage


Dismantling length
tightening torque for terminal

AC/DC 690 V
11 mm
2,0 Nm

KLS 25
rated connecting capacity: 6-35 mm, Cu
for

insertion in cable junction boxes


carrying capacity: 102 A
5-pole per pole 6 x 6 mm sol, 6 x 10 mm sol/ f*, 4 x 16 mm s/
f*, 4 x 25 mm s/ f*, 2 x 35 mm s/ f* f* = with gas-tight end ferrule
for cable junction boxes K 8250, K 8500, K 9250, K 9500, KF
4250, KF 5250, KF 5500, KF 8250, KF 8500, KF 9250, KF 9500,
KD 4250, KD 5250
complete with fixing elements
current

rated insulation voltage


Dismantling length
tightening torque for terminal

AC/DC 690 V
16 mm
3,0 Nm

115

DK Cable Junction Boxes


Accessories

KLS 50
Rated connecting capacity: 16-50 mm, Cu
for

insertion in cable junction boxes


carrying capacity: 150 A
4-pole per polel 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s, 4 x 50 mm s
for cable junction boxes K 9350, K 9500, K 8350, K 8500, KF 9350, KF 9500,
KF 8350, KF 8500, KF 5350, KF 5500, KF 4350, KF 4500, KD 5350,
KD 4350
complete with fixing elements
current

rated insulation voltage


Dismantling length
tightening torque for terminal

AC/DC 690 V
20 mm
12,0 Nm

KLS 51
Rated connecting capacity: 16-50 mm, Cu
for

insertion in cable junction boxes


carrying capacity: 150 A
5-pole per pole 6 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s, 4 x 50 mm s
for cable junction boxes K 9350, K 9500, K 8350, K 8500, KF 9350,
KF 9500, KF 8350, KF 8500, KF 5350, KF 5500, KF 4350, KF 4500,
KD 5350, KD 4350
complete with fixing elements
current

rated insulation voltage


Dismantling length
tightening torque for terminal

AC/DC 690 V
20 mm
12,0 Nm

KLS 54
Rated connecting capacity: 16-70 mm, Cu
for

insertion in cable junction boxes


carrying capacity: 216 A
4-pole per pole 4 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s, 4 x 50 mm s,
4 x 70 mm s
for cable junction boxes K 8500, K 9500, KF 4500, KF 5500, KF 8500,
KF 9500
complete with fixing elements
current

rated insulation voltage


Dismantling length
tightening torque for terminal

AC/DC 690 V
16 mm
10,0 Nm

KLS 55
Rated connecting capacity: 16-70 mm, Cu
for

insertion in cable junction boxes


carrying capacity: 216 A
5-pole per pole 4 x 16 mm s, 4 x 25 mm s, 4 x 35 mm s, 4 x 50 mm s,
4 x 70 mm s
complete with fixing elements
current

rated insulation voltage


Dismantling length
tightening torque for terminal

116

AC/DC 690 V
16 mm
10,0 Nm

DK Cable Junction Boxes


Accessories

FC L 45
Rated connecting capacity: 1,5-4 mm, Cu
FIXCONNECT

terminal set consisting of 5 terminals and 2 DIN rails


insertion in cable junction boxes
current carrying capacity: 32 A
5-pole per pole 4 x 1 x 1.5-4 mm r/f
for cable junction boxes K 8060, K 9060, KF 4060, KF 5060, KF 8060, KF 9060, KD 5060,
KD 4060, K 8100, K 9100, KF 4100, KF 5100, KF 8100, KF 9100, KD 5100, KD 4100
complete with fixing elements
for

rated insulation voltage


Dismantling length

AC/DC 690 V
17 mm

FC L 04
FIXCONNECT plug-in terminal 1.5-4 mm, Cu
as

a connecting terminal
installation on DIN rails, 15 mm top hat profile
current carrying capacity: 32 A
1-pole 4 x 1.5-4 mm r/f
for

rated insulation voltage


Dismantling length

AC/DC 690 V
17 mm

117

DK Cable Junction Boxes


Accessories

DK AL 2
External brackets 2 pieces
for

external wall fixing of cable junction boxes type D, K, KF, KD


and empty box KF PV
slot for wall mounting for screws up to 4.5 mm diameter
Material: stainless steel V2A

DE MB 10
Assembly bracket
external

DPS 02
Removable grommet
degree

of protection: IP 54 sealing range 10-13.5 mm


retrofitting
for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221,
DP 9222, DP 9026, DPC 9225
for

EKA 20
Removable trunking adapter
degree

of protection: IP 54 sealing range 10-13.5 mm


mini trunking up to 20 x 20 mm
for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221,
DP 9222, DP 9026, DPC 9225
for

ERA 20
Removable conduit adapter
degree

of protection: IP 54 sealing range 10-13.5 mm


wiring conduits M 20
for cable junction boxes DP 9020, DP 9220, DP 9025, DP 9221,
DP 9222, DP 9026, DPC 9225
for

DK BS 5
Labelling system for circuit description
set

with 5 pieces
cable junction boxes from 2.5 to 50 mm and KF PV boxes...,
can be inserted into cover fixing ducts.
for attaching of labelling strips or marking with felt tip pen
inscribable surface of 45 x 30 mm
label template on the Internet at www.hensel-electric.de download area
cannot be used in cable junction boxes 2.5 to 4 mm and
KF PV 01 / KF PV 02 boxes with sealing facility
for

118

10

70
55
18
6

brackets 10 units
thermoplastics
for quick installation of cable junction boxes DE 922. and DN 20..
material:

10

DK Cable Junction Boxes


Accessories

PLS 06
Facility for sealing
for

cable junction boxes 2.5 mm: D 9x2x, D 8x2x, DE 9x2x, DP 9x2x, DPC 9225, KF 9x2x,
KF 8x2x, KF 7x2x, KF 4x2x, KF 5x2x, RD 9x2x, KD x020
for cable junction boxes 4 mm: D 9x4x, D 8x4x, DE 9x4x, KF 9x4x, KF 8x4x, KF 7x4x, KF 4x4x,
KF 5x4x, RD 9x4x, KD x040
for cable junction boxes 6 mm: K 9x6x, K 8x6x, KF 9x6x, KF 8x6x, KF 7x6x, KF 4x6x, KF 5x6x,
RD 9x6x, KD x060, KC 9045
for boxes PV 01xx, KF PV 02xx, KF PV 03xx,
The following cable junction boxes and main line junction boxes are fitted with sealable covers as
standard: K 7004, K 7005, K 7042, K 7052, K 1204, K 1205, K 2404, K 2405, K 9259, K 9508,
K 9509.

PLS 50
Facility for sealing
for

cable junction boxes 10 mm: K 91xx, K 81xx, KF 91xx, KF 81xx, KF 71xx, KF 410x, KF 51xx,
KD x100
for cable junction boxes 25 mm: K 925x, K 825x, KF, 925x, KF 825x, KF 725x, KF 425x,
KF 525x, RK 91xx, KD x250, KC 9255
for cable junction boxes 35/50 mm: K 93xx, K 95xx, K 83xx, K 85xx, KF 93xx, KF 95xx, KF 83xx,
KF 85xx, KF 53xx, KF 55xx, KF 45xx, KD x350, KC 9355
for boxes KF PV 04xx, KF PV 05xx, KF PV 06xx, KF PV 07xx,
The following cable junction boxes and main line junction boxes are fitted with sealable covers as
standard: K 7004, K 7005, K 7042, K 7052, K 1204, K 1205, K 2404, K 2405, K 9259, K 9508,
K 9509.

119

DK Cable Junction Boxes


Accessories for Cable Junction Boxes from 70 mm onwards

Mi AL 40
4 stainless steel external brackets
for

external fixing of enclosures

Mi FM 40
Flange
knockouts: 2 x M 25/32, 5 x M 32/40
box
with

wall 300 mm
fixing wedges and seal

300
25

Mi FM 50
Flange
knockouts: 2 x M 20, 4 x M 32/40/50
box
with

wall 300 mm
fixing wedges and seal

300
25

Mi FM 60
Flange
knockouts: 3 x M 40/50/63
box
with

wall 300 mm
fixing wedges and seal

300
25

Mi FM 63
Flange with cable arrangement space
knockouts: 3 x M 40/50/63
box
with

wall 300 mm
fixing wedges and seal

300
80

Mi FP 70
Flange
sealing range: 1 x 30-72 mm
with

wall 300 mm
fixing wedges and seal

300
25

100

box

Mi FP 72
Flange
sealing range: 2 x each 30-72 mm
with

wall 300 mm
fixing wedges and seal

300
116
25

120

100

box

DK Cable Junction Boxes


Accessories for Cable Junction Boxes from 70 mm onwards

Mi FP 82
Cable insert
sealing range: 2 x each 30-72 mm
box

300
100
45

135

wall 300 mm
for cable insertion from the front
degree of protection IP 54 only with additional strain and pressure
relief (e.g. Mi ZE 62)
divisible

Mi ZE 62
Cable strain relief
for 2 cables with max. 60 mm external diameter
with
to

fixing rail 284 mm long


be used only in connection with cable insertion Mi FP 82

Mi SA 2
Dust protection cover
for
for

box sizes 1 to 4
2 lid fittings

121

DK Cable Junction Boxes


Technical Details

122

Dimensions in mm

123 - 124

Dimensions in mm of box walls without knockouts

125 - 126

Terminals

127 - 129

Operating and ambient conditions

130 - 132

Standards and regulations

133

FK cable junction boxes tested


for instrinsic re ressistance

134

DK Cable Junction Boxes


Technical Details
Dimensions in mm
53

46

66

88

4,2

37

27

K 8100
K 9100
KF 4100
KF 5100
KF 7100
KF 8100
KF 9100
KD 4100
KD 5100

167
141
133
108
77
54,4

82
64

4,2

88
59
36

125
99
84
66
61
40

D 8020
D 9020
D 9220
KF 4020
KF 5020
KF 7020
KF 8020
KF 9020
KD 5020
KD 4020

38
44

95
88
59
40

57

4,2
46

66

34

88

27
38

D 9040
KF 5040
KF 9040
KD 5040

K 8250
K 9250
KF 4250
KF 5250
KF 7250
KF 8250
KF 9250
KD 4250
KD 5250

200
173
165
140
96
77

98
79

4,2

53
37

29,6

160
133
116
100
90
77

D 8120
D 9120
KD 4120
KD 5120

98
61

46

76

98

4,2

45

54

K 9350
KF 4350
KF 9350
KF 8350
KF 5350
KD 4350
KD 5350

67
260
240
190
138
96
77

36

117
88

4,2

69
36

69

58

36

53

90
77

126
96

98

210

D 8040
KF 4040
KF 7040
KF 8040
KD 4040

177
140

46

43

37,5

70
52

165
148

77

37,5

117
88

210
180
160
148
140
83,4

4,2

139
114
107
80
77
54

95

63

310
280
274
248
240

4,2

33

K 8500
K 9500
KF 4500
KF 5500
KF 8500
KF 9500

119
94
83
60
57
34

K 8060
K 9060
KF 4060
KF 5060
KF 7060
KF 8060
KF 9060
KD 4060
KD 5060

46

76

98

4,2

42

63
77
43
55

= usable installation space


with mounted cable glands
123

DK Cable Junction Boxes


Technical Details
Dimensions in mm
DE 9320
DE 9321

88
59
36

K 7055
K 7004
K 7005
K 7042
K 7052
K 9951
K 1204
K 1205

88
76

4,2

47
33

300
272
238

170
146

450
422
388

32
98
69
36

52
37

98
79

4,2

DE 9340
DE 9341

25
275 x 425

37
88
59
36
14

300
272
238

K 2401
K 2404
K 2405

50
33

170
146

41,8

39,4

88
66

4,2

DP 9020

113

35

600
572
538

139
117
107
80
54,5
46

50
33

119
97
83
60
54,5
34

4,2

DP 9220

35

DN 2000/
DN 2030

85
70
65
55

113

51

36

85
70
65
55

DE 9220/
DE 9221

25
275 x 575

53
38
5,2

76
63
49

76
71

28

= usable installation space


when cable glands are attached
124

DK Cable Junction Boxes


Technical Details
Dimensions in mm of Box Walls Without Knockouts

30

K 8250
KF 8250
KF 4250
KF 7250
KD 4250

111,5

53

119

27
27

27

119

30

30

30

27

73

51

D 8020
KF 8020
KF 4020
KF 7020
KD 4020

73

D 8120

51

51

27

51

73

27

70

76

45

69

41

32

41

45

D 8040
KF 8040
KF 4040
KF 7040
KD 4040

45

73

69

45

27

27

76

K 8350
KF 8350
KF 4350
KD 4350

111,5

61

30
30

30

30

53

61

36,5

61

36,5

36,5

36,5

61

76

70

76

32

22

70

101

61

60

101

K 8500
KF 8500
KF 4500

32

32

K 8060
KF 8060
KF 4060
KF 7060
KD 4060

46

115

86

86

115

46

41

108

61

41

61
61

41

41

108

K 8100
KF 8100
KF 4100
KF 7100
KD 4100

101

70

101

86

86

42,5

135

42,5
42,5

42,5

135

= usable installation area


in box walls
125

DK Cable Junction Boxes


Technical Details
Dimensions in mm of Box Walls Without Knockouts
K 0100
K 0101

170
146
7

150
122
92

300
272
238

113

25
275 x 125

K 0200
K 0201

300
272
238

300
272
238

170
146

113

25
275 x 275

K 0300
K 0301

300
272
238

450
422
388

170
146

25
275 x 425

K 0400
K 0401

113

300
272
238

600
572
538

170
146

25
275 x 575

113

= usable installation space

126

DK Cable Junction Boxes


Technical Details
Terminals
Connecting terminals for copper conductors (Cu)
Hint: The connection of different types of conductors and/or different cross-sections at one clamping unit is not permitted.
f1 = exible with end ferrule
Type of terminal

DKL 04

KKL 06

KLS 10

Rated
connecting
capacity
mm2 and
types of
conductors

Conductors to be
connected
per pole

Tightening
torque

Current
carrying
capacity

Rated
cross
section of
terminal

D 9025, D 9125, D 9225,


1
D 9245, D 9045, DP 9025
DP 9221, DP 9222
DE 9325, DE 9326
DE 9345, DE 9346
KD 5025, KD 5045
KF 5025, KF 5045
KF 9025, KF 9045,
DN 2035, KF WP 2025,
KF WP 2045, KF WP 3025
KF WP 3045

6 sol
4 sol
2.5 sol
1.5 sol

1-2
1-3
1-4
1-6

1.2 Nm

6 mm2

K 9065,
KD 5065
KF 5065, KF 9065
KF WP 3065

10 sol
6 sol
4 sol
2.5 sol

1-2
1-3
1-4
1-4

1.5 Nm

10 mm2

K 9105, K 8105
KD 5105
KF 5105, KF 9105
KF WP 2105,
KF WP 3105

16 s
10 sol
6 sol
4 sol
2.5 sol, f1

1-2
1-4
1-4
1-4
2-6

2 Nm

63 A

16 mm2

K 9255, K 8255, K 9502


KD 5255
KF 5255, KF 9255

35 s, f1
25 s, f1
16 s, f1
10 sol, f1
6 sol

1-2
1-4
1-4
1-6
1-6

3 Nm

102 A

35 mm2

K 9504

50 s
35 s
25 s
16 s

1-4
1-4
1-4
1-6

12 Nm

150 A

50 mm2

K 7055, K 9355, K 9505,


KF 9355, KF 9505,
KF 5355, KF 5505,
KD 5355, KD 4355

50 s
35 s
25 s
16 s

1-4
1-4
1-4
1-6

12 Nm

150 A

50 mm2

K 7004

70 s
50 s
35 s
25 s
16 s

1-4
1-4
1-4
1-4
1-4

10 Nm

216 A

70 mm2

K 7005

70 s
50 s
35 s
25 s
16 s

1-4
1-4
1-4
1-4
1-4

10 Nm

216 A

70 mm2

K 9259
K 9508

incoming 2
outgoing 4

25 r
16 r

1-2
1-4

3 Nm

80 A

25 mm2

K 9509
K 9508

incoming 2
outgoing 4

35 r
35 r

1-2
1-4

4 Nm
3 Nm

100 A

35 mm2

Fixed in cable junction


boxes

Clamping
units
per pole

KLS 25

KLS 50

KLS 51

4 x KLS 54

5 x KLS 55

terminal for equipotential bonding:


DP 9026 for 1 continued conductor 4-25 mm2 and 5 conductors 4-10 mm2 (16 mm2 sol)
127

DK Cable Junction Boxes


Technical Details
Terminals
Terminal blocks for copper- (Cu) and aluminium conductors (Alu)
Current
carrying
capacity

Terminal
design/
nominal
cross-section
of terminal

International
approvals of
terminal blocks

USA/

Tightening
torque

Canada/CSA

Cross-sections and
types of conductors
f = exible wire
f1 = exible wire with
end ferrule
sol = solid wire
s = stranded wire
r = rigid (solid and
stranded)

SF/SETI

Conductors
to be
connected per
pole

NL/KEMA

corresponding
crosssection
mm

DK/Demko

Clamping
units
per
pole

N/Nemko

Type

CH/SEV

Fixed in
cable junction boxes

Manufacturer Wieland:
RD 9123, RD 9125,
RD 9127

WKM
2.5/15

RD 9045, RD 9041

WKM
4/15

2,5
1,5

f/f1
sol
s

= 0,5-2,5
= 0,5-4
= 1.5-2.5

0.4 Nm 24 A

4
2.5
1.5

f/f1
sol
s

= 0.5-4
= 0.5-6
= 1.5-4

0.5 Nm 32 A

4
2.5
1.5

f/f1
sol
s

= 0.5-4
= 0.5-6
= 1.5-4

0.5 Nm 41 A

rated voltage
AC/DC 500 V

rated voltage
AC/DC 500 V

RK 9062, RK 9064
RK 9109, RK 9104

WK 4/U
rated voltage
AC/DC 800 V

Manufacturer Weidmller:
D 9041

2.5
1.5

f/f1 sol = 0.5-2.5


s
= 1.5-2.5

0.5 Nm 20 A

4
2.5
1.5

f/sol
s
f1

= 0.5-4
= 1.5-4
= 0.5-2.5

0.6 Nm 20 A

WDU 16 N 4

16
10
6

f1/sol = 1.5-16
f/s
= 1.5-25

3.0 Nm 76 A

2.5-50

10.0 Nm Cu
150 A

AKZ 2.5
rated voltage
AC/DC 250 V

K 9061

AKZ 4
rated voltage
AC/DC 400 V

K 9351

rated voltage
AC/DC 400 V

K 7051

= 2.5-50

Alu
120 A
KF 9251
KF 9501

1.5-50

= 1.5-50

1.5 Nm
to
12 Nm

Cu/Alu
150 A

K 9951

6-95

= 6-95

12 Nm
to
22 Nm

Cu/Alu
490 A

K 2401

35-240 4

= 35-240

26 Nm
to
55 Nm

Cu/Alu
850 A

128

DK Cable Junction Boxes


Technical Details
Terminals
Terminals
K 7042 / K 7052

K 1204 / K 1205

K 240
04 / K 2405

95 mm2

150 mm2

240 mm2

Current carrying capacity

160 A

250 A

400 A

Tightening torque

20 Nm

20 Nm

40 Nm
4

Rated connecting capacity

Clamping units per pole

10-50

16-50

16-50

25-50

25-50

16-95

16-150

16-70

25-240

25-120

Conductor cross section Cu/Alu1) sol (sector)

50-95

50-150

50-70

50-185

50-120

Conductor cross section Cu s (sector)

35-95

35-150

35-70

35-240

35-120

35-70

50-120

35-50

95-185

50-95

Conductor cross section Cu/Alu1) sol (round)


Conductor cross section Cu/Alu1) s (round),
f (flexible)

Conductor cross section Alu1) s (round),


f (flexible)

1) Prior to connection, aluminium conductors must be prepared according to the


e relevant technical
recommendations. The connections must be checked at regular intervals and maintained after
6 months at the latest.
FIXCONNECT technology
Type

Clamping units
per pole

Rated connecting capacity


per types of conductors
r (rigid)

DPC 9225
KC 9045
KC 9255
KC 9355

Current carrying
capacity

f (flexible)

1.5 - 4 mm2

1.5 - 4 mm2

32 A

1.5 - 4 mm2

32 A

4
4

1.5 - 4 mm

2.5 - 10 mm

2.5 - 16 mm

57 A

76 A

2.5 - 10 mm

2.5 - 16 mm

129

DK Cable Junction Boxes


Technical Details
Operating and Ambient Conditions
Removable
grommets

Boxes with terminals


D ..., DP ...,
DPC ..., DE ...,
KC ..., K ...,
RD ..., RK ...

K 7055
K 7004/5
K 9951
K 1204/5
K 2404/5
K 2401
Mi FM ..

EKA 20,
ERA 20,
DPS 02

Boxes with terminals


KF ...

Application area

Suitable for indoor installation


(normal environment and/or protected outdoor)

Resistant to occasional
cleaning procedures

Resistant to occasional cleaning procedures (direct jet)


max. with high-pressure cleaner without additives
water pressure: max. 100 bar, water temperature: max. 80 C, distance 0.15 m
in accordance with the requirements IP 69K
box and cable entries at least IP 65

KD ...

Suitable for outdoor installation


(harsh environment and/or outdoor)

Ambient temperature
- Average value over 24 hours
- Maximum value
- Minimum value

+ 35 C
+ 40 C
25 C

+ 35 C
+ 40 C
25 C

+ 35 C
+ 40 C
25 C

+ 55 C
+ 70 C
25 C

+ 55 C
+ 70 C
25 C

Relative humidity
- short-time

50% at 40 C
100% at 25 C

50% at 40 C
100% at 25 C

50% at 40 C
100% at 25 C

50% at 40 C
100% at 25 C

Fire protection
in the event of internal faults

Demands placed on electrical devices from standards and laws:


Minimum requirements
- Glow wire test in accordance with IEC 60 695-2-11:
- 650 C for boxes and cable glands
- 850 C for conducting components

Fire protection
in the event of specic risks or
hazards

Demands
placed on electrical installations and devices in areas and facilities subject to re risk,
e.g. DIN VDE 0100 Part 482 (German standard), ofcial regulations, VdS directives
Minimum requirements
- Glow wire test in accordance with IEC 60 695-2-11:
- 850 C for boxes and cable glands
- 850 C for cavity wall installation
- use of re resistant cables

Burning behaviour
- Glow wire test
IEC 60 695-2-11
- UL Subject 94

750 C
V-2
ame-retardant
self-extinguishing

960 C
V-2
ame-retardant
self-extinguishing

750 C

ame-retardant
self-extinguishing

960 C
V-0
ame-retardant
self-extinguishing

960 C
5V
ame-retardant
self-extinguishing

Degree of protection
against mechanical load

IK07 (2 Joule)

IK08 (5 Joule)

IK08 (5 Joule)

IK08 (5 Joule)

Toxic behaviour

halogen-free
silicone-free

halogen-free
silicone-free

halogen-free
silicone-free

halogen-free
silicone-free

halogen-free
silicone-free

Halogen-free in accordance with IEC 754-2 Common test methods for cables Determination of the amount of halogen acid gas.
For material properties see technical data.

130

DK Cable Junction Boxes


Technical Details
Operating and Ambient Conditions
Empty boxes

Removable
grommets

D ..., DP ..., DE ...,


K 9..., K 8...

EKA 20, ERA 20,


DPS 02

Empty boxes
KF ...

Empty boxes
KD ...

Application area

Suitable for indoor installation


(normal environment and/or protected outdoor)

Suitable for outdoor installation


(harsh environment and/or outdoor)

Resistant to occasional
cleaning procedures

Resistant to occasional cleaning procedures (direct jet)


max. with high-pressure cleaner without additives
water pressure: max. 100 bar, water temperature: max. 80 C, distance 0.15 m
in accordance with the requirements IP 69K
box and cable entries at least IP 65

Ambient temperature
- Average value over 24 hours
- Maximum value
- Minimum value

+ 40 C
25 C

Fire protection
in the event of internal faults

Demands
placed on electrical devices from standards and laws

+ 35 C
+ 60 C
25 C

+ 55 C
+ 70 C
25 C

+ 55 C
+ 70 C
25 C

Minimum requirements
- Glow wire test in accordance with IEC 60 695-2-11:
- 650 C for boxes and cable glands
- 850 C for conducting components
Fire protection
in the event of specic risks or
hazards

Demands placed on electrical installations and devices in areas and facilities subject to re risk,
e.g. DIN VDE 0100 Part 482 (German standard), ofcial regulations, VdS directives:
Minimum requirements
- Glow wire test in accordance with IEC 60 695-2-11:
- 850 C for boxes and cable glands
- 850 C for cavity wall installation
- use of re resistant cables

Burning behaviour
- Glow wire test
IEC 60 695-2-11
- UL Subject 94

750 C
V-2
ame-retardant
self-extinguishing

750 C

ame-retardant
self-extinguishing

960 C
V-0
ame-retardant
self-extinguishing

960 C
5V
ame-retardant
self-extinguishing

Degree of protection
against mechanical load

IK07 (2 Joule)

IK08 (5 Joule)

IK08 (5 Joule)

Toxic behaviour

halogen-free
silicone-free

halogen-free
silicone-free

halogen-free
silicone-free

halogen-free
silicone-free

Halogen-free in accordance with IEC 754-2 Common test methods for cables Determination of the amount of halogen acid gas.
For material properties see technical data.

131

DK Cable Junction Boxes


Technical Details
Operating and Ambient Conditions
Boxes with terminals
KF WP ....
Application area

Suitable for outdoor installation (harsh environment and/or outdoor).


For application in ambient conditions with formation of condensation and ingress of water as well as for
installation in the ground without trafc loads in accordance with DIN VDE V 0606-22-100.

Resistant to occasional
cleaning procedures

Resistant to cleaning procedures (direct jet)


max. with high-pressure cleaner without additives, water temperature: max. 80 C

Ambient temperature
- Average value over 24 hours
- Maximum value
- Minimum value

+ 55 C
+ 70 C
25 C

Relative humidity

100%

Burning behaviour
- Glow wire test
IEC 60 695-2-11
- UL Subject 94

960 C
V-0
ame-retardant
self-extinguishing

Degree of protection
against mechanical load

IK08 (5 Joule)

Toxic behaviour

halogen-free
silicone-free

132

DK Cable Junction Boxes


Technical Details
Standards
Hensel cable junction boxes and cable entry systems comply with the following standards and requirements:
1. Cable junction boxes
- IEC 60 670 - 22
Particular requirements for connecting boxes and enclosures
Part 22: Particular requirements for connecting boxes
- IEC 60 998
Connecting devices for low voltage circuits for household and similar purposes
Part 2-1: Particular requirements for connecting devices as separate entities with screw-type terminals
Part 2-2: Particular requirements for connecting devices as separate entities with screwless-type terminals
- IEC 60 999
EN 60 999
Connecting devices
Safety requirements for screw-type and screwless-type clamping units for electrical copper conductors
- DIN VDE V 0606-22-100 (German standard)
Enclosures for encapsulation with connection terminals (GVV)
2. Cable junction boxes with terminal blocks
- IEC 60 670-22
Particular requirements for connecting boxes and enclosures
- EN 60 947 -7-1
Low-voltage switchgear and controlgear,
Part 7: Auxiliary equipment;
Section 1 - Terminal blocks for copper conductors
3. Conduit entries (ERA 20)
- EN 60 423
Conduits for electrical pursposes - Outside diameters of conduits for electrical installations and threads for conduits and ttings
4. Degrees of protection
- IEC 60 529
DIN VDE 0470 Part 1 (German standard)
Degree of protection by enclosure (IP Code)
5. Halogen-free
- EN 50 267
examination of cables and insulated wires
halogen-free materials

133

DK Cable Junction Boxes


Technical Details
Cable Junction Boxes Tested for Intrinsic Fire Resistance
Safety circuits must remain operational for a
sufcient period in accordance with the national
regulations governing re protection requirements
for cable installations during exposure to re.

FK Cable junction boxes comply with these


requirements when used together with typeapproved cables as well as suitable cable
clamps or mounting devices.
Cable junction boxes tested for intrinsic re
restistance.

This ensures that electrotechnical equipment such


as luminaires, lifts, smoke outlets, alarm systems
etc. are supplied with power for 30 or 90 minutes
and thereby enable people to leave the building
and assist rescue teams in carrying out their work.
Junction box with connected cables
after testing.

Degree of protection IP 65, IP 66


Box made from sheet steel with powder coating
or duroplastic, pastel orange RAL 2003
No additional re load, no toxic or corrosive
emissions

When planning and implementing these cable


installations, the current specimen regulation for
re protection requirements in these installations
must be observed.

Intrinsic re resistance according to DIN 4102


part 12 (German standard) in connection with
function-retaining cables of 0.5-16 mm2
Protection against direct contact also maintained
due to the box
Captive cover with 4 screw fixings

Box fixing with plugs:


Anchor (building materials)

Fischer type ...


FIS V..

Limestone blocks KS 12
Test temperature curve in
accordance with DIN 4102

FNA..

Hilti type ...


FBS..

FBN..

FHY..

HUS..

Building bricks Mz 12

Airbricks HLz 12

Limestone air blocks KSL 12

HSA..

x
x
x
x

Prestressed concrete slabs

Porous concrete slabs => 3.3

Porous concrete blocks => 4

Concrete => B25 / =< B55

x
x

Please observe the current approvals and notes from the manufacturer of the plugs.

Standards and regulations:


IEC 60 998 -1
EN 60 998 Part 1
IEC 60 998 -2 -1
EN 60 998 Part 2-1

IEC 60 670-22

EN 60 947 -7 -1

IEC 60 529
DIN VDE 0470 Part 1 (German standard)

EN 50 262
DIN 4102 Part 12 (German standard)

Ambient conditions in working operation:


Type

FK 7xx5

Application area

Suitable for indoor installation (normal environment and/or protected outdoor)

Ambient temperature
- Average value over 24 hours
- Maximum value
- Minimum value

+ 35 C
+ 40 C
25 C

+ 35 C
+ 40 C
25 C

+ 35 C
+ 40 C
5 C

Relative humidity
- short-time

50 % at 40 C
100 % at 25 C

50 % at 40 C
100 % at 25 C

50 % at 40 C
100 % at 25 C

Material

Duroplast
halogen-free

sheet steel, powder-coated


halogen-free

Degree of protection
against mechanical load

IK06 (1 Joule)

IK10 (20 Joule)

134

HIT-HY..

FK 9xx5

FK 9259