You are on page 1of 144

LOYTEC

Products
Product Catalog 2013/2014

Dear valued customer,


the building automation and building management market has evolved into a rather
exciting market, continuously demanding innovations from the manufacturers. Ever more
complex tasks have to be fulfilled in ever less time. Efficient work flows and automatisms
of integration have to be improved and adapted to the market. On the technological side,
IP communication has changed and shaped the world. Today, everybody is somehow
connected and linked to the cloud. Smart buildings also are being connected, and their
numbers are growing every day. As a result requirements regarding network security
escalate. What was considered secure yesterday, is condemned today, first of all, Java.
IP communication naturally determines communication in the building itself. The
everyday life of a Smart Building is characterized by various protocols, which all meet in
the IP network. Whether the standardized protocols BACnet/IP, LonMark IP-852, KNXnet/IP,
or the industry standards Modbus TCP and OPC all of them encounter each other in the
IP network, but actually, without seeing each other.
Without cross-communication between the different systems and without the integration
of devices, which communicate in the field via various building protocols, you simply cant
get a well-performing building, that achieves best comfort and energy efficiency through
the synergies of the systems, and on top, pleases the involved parties regarding operation
and maintenance.
This is exactly where LOYTEC comes into play. Multilingualism is woven into our product
solutions and IP communication down to the field level. IP network security is continually
improved and adapted to the changing scenarios of threats. Utilization of open protocols
not only is natural to LOYTEC, it is a requirement. We persistently improve work flows and
permanently invent new methods and automatisms so that working with our products is
trouble free.
Driven by this spirit, LOYTEC has created a highly innovative range of products, starting
with a building management system which completely covers control of HVAC, lighting,
sun blinds, and energy data acquisition.
In this catalog I proudly present to you our exhibition of achievements. Convince yourself
of the innovations and the consistency of our product solutions. Let yourself be inspired
by our technological advantages and gain new ideas to better fulfill the needs of your
clients.

Hans-Jrg Schweinzer, CEO


LOYTEC electronics GmbH

www.loytec.com

Content

LOYTEC Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LOYTEC Competence Partner Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Integrated Building Management System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
LWEB900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
LWEB8xx Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Graphical User Interface
LWEB-800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
LWEB-802. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Dream Report
LWEB-830. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
L-ROC Room Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
LROC-100, LROC-150. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
L-INX Automation Servers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
LINX150, LINX151 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
LINX120, LINX121 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
LINX220, LINX221. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
LINX110, LINX111. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
LINX210, LINX211 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
LINX100, LINX101. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
LINX200, LINX201. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
L-IOB I/O Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
LIOBFT I/O Controller
LIOB180/181/182/183/184. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
LIOBIP852 I/O Controller
LIOB480/481/482/483/484. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
LIOBBIP I/O Controller
LIOB580/581/582/583/584. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
L-IOB I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
LIOBConnect I/O Module
LIOB100/101/102/103. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
LIOBFT I/O Module
LIOB150/151/152/153/154. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
LIOBIP852 I/O Module
LIOB450/451/452/453/454 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
LIOBBIP I/O Module
LIOB550/551/552/553/554 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Gateways. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
L-GATE Gateway
LGATE-950/951. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
LGATE-900. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
L-Proxy CEA-709 Multiport Gateway
LP-33E100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
KNX TP1 Interface
LKNX-300. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

buildings under control

Content
M-Bus Level Converter
L-MBUS20, L-MBUS80 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
L-POW Power Supply
LPOW-2415A, LPOW-2415B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
L-VIS Touch Panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
LVIS-100-RE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
LVIS-3E100/3E112/3E115. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
LVIS-ME200/ME212/ME215. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
L-DALI Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
LDALI-3E101/3E102/3E104. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
LDALI-ME204. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
LDALI-3101-U/LDALI-E101-U. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
LDALI-E201-U. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
L-DALI Power Supply
LDALI-PWR-2-U, LDALI-PWR-4-U. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
L-IP CEA-709/IP-852 Routers
LIP-3ECTB, LIP-1ECTB, LIP-33ECTB, LIP-3333ECTB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
LIP-33ECRB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
L-IP BACnet/IP Router
LIP-ME201. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
L-Switch CEA-709 Router
LS-33CB, LS-13CB, LS-11CB, LS-13300CB, LS-33300CB, LS-13333CB, LS-11333CB . . . . . . . . . . . . . . . . . . . . . . 110
NIC-Network Interface
NIC709-IP3E100, NIC709-IP1E100, NIC852, NIC709USB100, NIC709-PCI100, NIC852-SW. . . . . . . . . . . . . . 111
L-Term Network Terminator
LT-03, LT-13, LT-33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
LT-04, LT-B4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
OPC Bridge Software
LOPC-BR800. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
LPA-CEA-709 Protocol Analyzer
LPA-SW, LPA-IP-SW, LPA-SW, LPA-SET-USB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Certificates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Dimensions of the devices (in mm und [inch]). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Technology Reference List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135

www.loytec.com

Programmable

OPC

M-Bus

Modbus

DALI

KNX

BACnet

LON

LOYTEC Product Overview

User Interface
iPad

LOYTEC
www.loytec.com

L-VIS
L-WEB

L-IOB

L-DALI

L-ROC
L-INX
L-IOB
L-KNX

L-INX
L-IOB
L-MBUS

L-INX
L-IOB
L-MBUS

L-GATE
L-INX
L-DALI
L-Proxy

L-IP
L-Switch
NIC

I/O Controller
+~ -~

ETHERNET

DO2 DO3 DO4 DO5 COM

24 VAC/DC

Made in Austria

6A

LOYTEC
www.loytec.com

6A

6A

DO6 COM DO7 DO8 COM DO9

6A

TRIAC

LIOB-580

TRIAC

status

status

L-IOB

I/O Controller
UNIVERSAL IN

DIGITAL IN

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

0-10V OUT

DI1 GND DI2 AO1 GND AO2

Lighting Control
DA1+ DA1DALI 1

POWER

DA2+ DA2DALI 2

DA3+ DA3DALI 3

Input
N
L

DA4+ DA4DALI 4

27

28

85-240VAC
50/60 Hz

29

DA4

L-DALI

30

32

DA3

PROG CHANNEL

Power Supply

LOYTEC
www.loytec.com

ON
OFF
AUTO

33

34

DA2

DALI4
ACT

L-DALI BACnet DALI controller

35

DA1

DALI3
ACT

DALI2
ACT

DALI1
ACT

LINK

CN/IP

ACT

IP ACT

MSTP Ethernet
+ - 100Base-T

LDALI-PWR4-U

13

14

power

serial

CONFIG

DALI Multi-Master

Made in Austria

OUTPUT
DALI 4x 116mA

status

12-35 VDC INPUT or


12-24 VAC, 3W

LDALI-ME204

- +
~ ~

LOYTEC
www.loytec.com

15

DC
AC

24 25 26

Made in EU

Room Automation
Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

LROC-100

USB

MICROSD

FT

LIOB-FT

EXT1

DO1 DO1 DO2 DO2

EXT2

16A

ACT

DO3 DO3 DO4 DO4 DO5 DO5

16A

LOYTEC
www.loytec.com

L-ROC

LINK

16A

16A

1
FT

LIOB-FT

EXT1

EXT2

LKNX-300

status

L-IOB

L-KNX

I/O Module

KNX Interface

0-10V OUT
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

Made in Austria

LOYTEC
www.loytec.com

status

Room Controller

PLC OPC

Ethernet 1 Ethernet 2

Made in Austria

16A

LIOB-103

EXT
GND B

AO1 GND AO2 AO3 GND AO4 AO5 GND AO6

KNX

PROG.

- +

Energy Management, Metering


Input
L
N

GAS

85-265VAC
50/60 Hz

24VDC/15W
GND +

MODBUS

DI1 GND DI2 DI3 GND DI4 DI5 GND DI6

EXT

Made in Austria

Ethernet 1 Ethernet 2

2
LIOB-FT

3
MODBUS

L-MBUS

DI7 GND DI8 DI9 GND DI10 DI11 GND DI12


DIGITAL IN
status

DIGITAL IN

LOYTEC
www.loytec.com

L-INX

LIOB-101

status

24 VAC/DC

I/O Module

4
EXT

UNIVERSAL IN

MBUS Interface
Made in Austria

LOYTEC
www.loytec.com

L-IOB

Automation Server

1
MSTP

L-MBUS20
RS-232

Port 2

LIOB-FT

ACT

MICROSD MS/TP

USB
LINK

PLC OPC

-~

LINX-221

SHORT
POWER

LOYTEC
www.loytec.com

+~

Ethernet
1 2

Made in Austria

TXD

status

L-POW

Power Supply

GND

Made in Austria

LOYTEC
www.loytec.com

RXD

LPOW-2415B

kWh

DIGITAL IN

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

DI16 GND DI15 DI14 GND DI13

Port 1 (TTL) Port 1

POWER

Port 2

MBUS

HVAC Control
77

Pa
P

21.6 C

19.5 C

0.0 %

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

USB

MICROSD

FT

LIOB-FT

77
T

19.4 C

20.4 C

6A

6A

6A

6A

+~ -~

Made in Austria

24 VAC/DC

status

6A

FT

DO1 DO1 DO2 DO2


16A

Made in Austria

LOYTEC
www.loytec.com

status

DO3 DO3 DO4 DO4 DO5 DO5

16A

16A

LIOB-153

6A

status

16A

status

L-IOB

L-IOB

I/O Module

I/O Module

0-10V OUT

0-10V OUT
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

AO1 GND AO2 AO3 GND AO4 AO5 GND AO6

AO1 GND AO2 AO3 GND AO4 AO5 GND AO6

22.3 C

0.0 %

Gateways
MICROSD

FT

MS/TP

-~ +~ 24VAC/DC

USB 1
USB 2

Ethernet 1 Ethernet 2

EXT

Universal Gateway

1
PWR

MODBUS

L-GATE

ACT

FT
B

2
A

MS/TP
GND

3
-

MODBUS

GND

EXT

GND B

LKNX-300

Made in Austria

L-KNX

KNX Interface
EXT
GND B

PROG.
A

LZIBI-800

L-MBUS

Made in Austria

LOYTEC
www.loytec.com

LOYTEC
www.loytec.com

KNX

- +

L-ZIBI

ZigBee Interface
EXT
GND B

MBUS Interface
Made in Austria

LOYTEC
www.loytec.com
24 VAC/DC

L-MBUS20
Port 2

RS-232

USB
LINK

BBMD OPC

LGATE-950

-~

LOYTEC
www.loytec.com

SHORT
POWER

Ethernet
1 2

Made in Austria

TXD

6A

LIOB-102

4
EXT

GND

3
MODBUS

+~

22.3 C

2
LIOB-FT

RXD

6A

LOYTEC
www.loytec.com

Automation Server

1
FT

STATUS

ANTENNA
A

Port 1 (TTL) Port 1

POWER

Port 2

MBUS

Network Infrastructure
L-IP
LIP-3333ECTB

Pa

DO1 COM DO2 DO3 COM DO4 DO5 COM DO6 DO7 COM DO8

EXT

L-INX

LINK

PLC OPC

Ethernet 1 Ethernet 2

77

MODBUS

6A

LINX-150

ACT

83

CEA 709/IP router


Made in EU

ACT

ACT

ACT

ACT

4 3 2 1
FT
4

FT

FT

B A
6

B A
8

B A

10 11 12

CNIP

LINK
ACT
SERVER

serial

B A

power

status

12-35 VDC INPUT or


12-24 VAC, 40-70 Hz

FT
13 14 15

100Base-T

LOYTEC
www.loytec.com

- +
~ ~

24 25 26

DC
AC

buildings under control

Functions
LOYTEC offers a wide range of products for various applications in building automation.
Those application-centric products often combine an entire set of different functions on
one single device (L-INX Automation Servers, IP-capable L-IOB I/O Modules and Controllers, L-ROC Room Controllers, L-GATE Gateways, L-VIS Touch Panels). This enables a given
product to be used for different tasks. For example, the L-GATE as a typical gateway also has
the ability to host a graphical user interface to dynamically visualize a site or record historic
data in trend logs. L-INX Automation Servers are primarily programmable controllers but
can also be used as gateways depending on the available protocols.
We have high quality standards in research, development, and production of our products.
In order to offer the same high standards to our customers, the programmable controllers
may only be purchased by trained staff of companies that are enrolled in the LOYTEC Competence Partner Program.
For all functions, LOYTEC ensures common workflows for configuration and operation. The
workflow for configuration of certain functions is the same, regardless which device is used.
This applies for integration in different communication network technologies, creating schedules, alarm conditions, trend logs, and
even for the design of graphical projects. For an efficient workflow the user can depending on the network technology create
single data points or entire device templates via a network scan or file import. The use of a single configuration tool for a range of
product models such as the L-INX Automation Servers, L-IOB I/O Modules, L-IOB I/O Controllers, and L-GATE Gateways, reduces the
learning curve notably when working with LOYTEC products.
The combination of different functions on a single device and the common workflows for configuration and operation offer a maximum of flexibility when selecting LOYTEC products for various application requirements. On the following pages we give an overview
on the offered functions. For more detailed information on the presented functions please refer to the respective product manuals,
which are available for download on our web site. The functions are represented by symbols, which are referred to by the respective
product descriptions later in the catalog.

AST-Functions
The acronym AST stands for the combination of alarming (alarm management), scheduling, and trending (historic data recording)
functions, which are available as automation functions on LOYTEC devices (L-INX Automation Servers, IP-capable L-IOB I/O Controllers, L-ROC Room Controllers, L-GATE Gateways, L-VIS Touch Panels). The AST functions can therefore be distributed into the field and
are available exactly where they are needed in a building automation system. AST functions can be seamlessly integrated with the
L-WEB building management software. Also graphical user interfaces like LWEB-800/802, the building management system LWEB-900
and the L-VIS Touch Panels provide access to the distributed AST functions.

Alarming (Alarm Management)


On a LOYTEC device it is possible to define alarm conditions for each data point. This can be done independently of the underlying communication technology (CEA-709, BACnet, DALI, M-Bus, Modbus, KNX, ) or the underlying, physical data point of a L-IOB I/O Module.
Alarms generated by these alarm conditions are reported to a generic alarm server, which is also independent of the network technology.
The alarm server collects alarm records and is the interface for remote access to those local alarms. Alarm records contain information on
the alarm source data point, the alarm value, an alarm message, alarm type (off-normal, limit, fault), alarm priority, and alarm state (alarm
active, acknowledged, inactive). The alarm message of the record can be user-defined and extended by variable placeholders.
LOYTEC devices with the BACnet interface support BACnet alarms with intrinsic reporting. BACnet alarm servers are mapped to BACnet
notification class (NC) objects. Alarm conditions can be defined for analog input, output, and value objects (AI, AO, AV), for binary input,
output, and value objects (BI, BO, BV) and for multi-state input, output, and value objects (MSI, MSO, MSV). More than this, alarm records
from generic alarm servers can be reported to BACnet alarm servers and can be exposed to notification class objects. This allows the reporting of alarm conditions from other communication technologies to BACnet. Using client mappings, LOYTEC devices can also access remote
BACnet notification class objects, for instance to receive alarms from third-party devices.
LOYTEC devices for LonMark Systems (CEA-709) support the transmission of alarms via the LonMark node objects nvoAlarm (SNVT_alarm)
and nvoAlarm_2 (SNVT_alarm_2). This allows other devices that support the LonMark alarm notifier profile to receive alarms sent by LOYTEC devices. The acknowledgement of alarms in the LonMark alarm server is defined in the LonMark specification and works with the
RQ_CLEAR_ALARM mechanism. Alarms from generic alarm servers can be reported to the LonMark alarm server (mapped to the LonMark
node object). This way alarm conditions of data points from other network technologies can be reported to a LonMark System.

www.loytec.com

Functions
Alarms of the different alarm servers can be displayed in LWEB-900, LWEB-800/802, L-VIS Touch Panels or in the devices integrated Web
interface using the built-in Web server.
The alarming feature also includes the recording of alarm transitions in an alarm log on the LOYTEC device. The alarm log works as a ring
buffer and its size can be configured. The alarm log can be viewed on the Web interface of the LOYTEC device and be exported to a CSV file.
The alarm log can also be transmitted as a CSV file e-mail attachment or be downloaded from the device via FTP access.

Scheduling
Scheduling refers to changing the value of data points on a timely basis using a time schedule. The schedule contains a weekly schedule
and exception days (e.g. holidays) and date periods (e.g. vacation time). The scheduling feature works locally on LOYTEC devices and can
be enabled depending on an enable data point.
All LOYTEC devices supporting the scheduling function feature a built-in battery buffered Real Time Clock (RTC). Schedules can change the
state of a binary data point or the value of an analog data point. This occurs independently of the underlying communication technology
(CEA-709, BACnet, DALI, M-Bus, Modbus, KNX, ) or the underlying, physical data point of a L-IOB I/O Module.
LOYTEC devices with a BACnet interface use the standardized BACnet schedule and calendar object to map the schedule. A separate
BACnet schedule object is created for each schedule. BACnet calendar objects are used for defining exception days. The BACnet schedule
object allows scheduling of a single value at a time (multistate, analog, or binary). More than one scheduled value or different data types
at a time are not possible. Using the client mapping function, it is possible to access remote BACnet scheduler objects. This allows reading
and modifying schedules of third-party devices.
LOYTEC devices for LonMark Systems (CEA-709) support CEA-709 schedulers and CEA-709 calendars via standard LonMark objects. For
CEA-709 schedules, more than one data point can be configured, possibly of different data type, for which a set of different values can be
scheduled at a time.
Schedules are executed autonomously on LOYTEC devices. The schedules and scheduled values can be viewed and configured in
LWEB-900, LWEB-800/802, L-VIS Touch Panels, or on the devices Web interface using the built-in Web server. The distributed schedules on
LOYTEC devices can be managed by the LWEB-900 Building Management System. LWEB-900 allows grouping schedules, building a hierarchical structure, configuring schedules efficiently, and generating backups. L-VIS Touch Panels also allow access to distributed schedules in
LOYTEC devices via the L-VIS schedule controls.

Trending (Historic Data Logging)


Generic trend logs are technology-independent and allow the recording of historic data values over time. The recording of data point
values occurs at fixed intervals, on a defined change-of-value, or is triggered by a trigger data point. Recording intervals can be aligned to
the wall-time. For example, different trend logs with 15 minutes intervals can record synchronously aligned to the top of the hour. For each
data point, a change-of-value condition can be defined on the LOYTEC device. Trends operate independently of the underlying communication technology (CEA-709, BACnet, DALI, M-Bus, Modbus, KNX, ) or the underlying, physical data point of a L-IOB I/O Module. Trend
logs can record local and remote data points of other, distributed devices. The capacity of a trend log and the storage mode (linear or ring
buffer) can be configured. Devices that support SD card and have a USB port also allow the storage of trend log data on external memory.
The time of backing up trend logs can be triggered by the user on the LCD display or by defined, automatic trigger conditions.
LOYTEC devices with a BACnet interface can also use BACnet trend log objects for historic data recording. These objects can be accessed
over the BACnet network and expose trend data to other BACnet devices and operator workstations (OWS). Each BACnet trend log object
can record data for a single data point only. The recorded data point is limited to the BACnet technology, either to a local BACnet object or
to a remote BACnet object (configured by a client mapping).
LOYTEC devices for LonMark Systems (CEA-709) use generic trend logs. There exists no LonMark functionality that allows transparent LonMark access to trend log data.
Trend log data of the different trend log objects can be displayed by LWEB-900, LWEB-800/802 and L-VIS. Trend data can be viewed either
in a table view or in a trend graph. In addition, the LWEB-900 or LWEB-900 server allows long-term storage of the historic trend data. For
doing so, the recorded data is periodically read out from the device and stored in a database. If no permanent IP connection should exist
between the L-WEB server and the respective LOYTEC devices, the devices can be configured to send trend data automatically as an e-mail
attachment to the L-WEB server. Trend data can also be exported as a CSV file (via FTP access), or stored to SD card or USB memory, if the
device supports it.

buildings under control

Functions
Communication
E-mail Notification
The integrated e-mail client allows for the transmission of messages based on a timely basis or triggered by events. Message texts can be
multi-line and consist of static text and variable placeholders, which are evaluated at the time of transmission and insert values into the
text. Further more, alarm logs and trend logs can be automatically transmitted as e-mail attachments in CSV file format.
The number of transmitted e-mails can be limited. Using a trigger data point, the e-mail transmission can be invoked on a timely basis or
event-based. In case an e-mail could not be delivered, retransmissions are tried every 30 minutes up to 24 times.

Ethernet (Ethernet Switch)


Ethernet summarizes a variety of networking technologies, software (protocols) and hardware (cable, hubs, interface cards, etc.) for wired,
local area networks (LANs). Originally published in 1983 as the IEEE 802.3 standard, Ethernet has evolved to todays most used LAN technology. As a packet-switched network, Ethernet belongs to the layers 1 and 2 of the ISO/OSI layer model and defines addressing and media
access. Ethernet is a common basis for networking protocols such as TCP/IP and UDP/IP and is able to multiplex several application protocols at the same time (e.g. HTTP, FTP, IP-852, BACnet/IP, KNXnet/IP).
LOYTEC devices with an Ethernet interface use 100Base-T (Fast Ethernet) at 100 Mbit/s and an RJ45 jack.
LOYTEC devices with two Ethernet ports connect these ports over an internal Ethernet switch. This allows for building a line topology,
which reduces costs for the network installation. Dual Ethernet ported devices allow the setup of a redundant Ethernet installation (ring
topology and a fully redundant Ethernet topology), which increases reliability. The redundant Ethernet topology is enabled by the Rapid
Spanning Tree Protocol (RSTP), which is supported by most managed switches.

LPOW-2415A

Made in Austria

status

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

LOYTEC
www.loytec.com

LINX-151

USB

Input
N
L

85-265VAC
50/60 Hz

Output
24VDC/15W

MICROSD

FT

FUSE 6A

EXT

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

status

LIOB-100

LIOB-FT

MODBUS

DI1 GND DI2 DI3 GND DI4 DI5 GND DI6


Made in Austria

DIGITAL IN

LOYTEC
www.loytec.com

status

UNIVERSAL IN
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

DIGITAL IN

L-IOB

UNIVERSAL IN
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

+ GND
24 VDC/100mA
OUTPUT

L-IOB

I/O Module

0-10V OUT

DI1 GND DI2 AO1 GND AO2

Made in Austria

LIOB-A2

LOYTEC
www.loytec.com

status

I/O Module

4
EXT

+ GND
24 VDC
INPUT

DI7 GND DI8 DI9 GND DI10 DI11 GND DI12


DIGITAL IN
status

LIOB-101

L-IOB

Automation Server

1
FT

Made in Austria

6A

LOYTEC
www.loytec.com

L-INX

ACT
PLC OPC

Ethernet 1 Ethernet 2

MODBUS

LIOB-FT

LINK

L-POW

Power Supply

Adapter 2

DIGITAL IN

LIOB-CONNECT IN/OUT

DI16 GND DI15 DI14 GND DI13

SEL GND A

B TERM

LOYTEC
www.loytec.com

Ethernet Switch

Fast Ethernet 100Base-T

ETHERNET
Made in Austria

+~ -~

24 VAC/DC

LOYTEC
www.loytec.com

DO2 DO3 DO4 DO5 COM


6A

6A

6A

DO6 COM DO7 DO8 COM DO9

6A

TRIAC

LIOB-450

ETHERNET

TRIAC

status

Made in Austria

+~ -~

DO2 DO3 DO4 DO5 COM

24 VAC/DC

6A

LOYTEC
www.loytec.com

status

6A

6A

DO6 COM DO7 DO8 COM DO9

6A

TRIAC

LIOB-450

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

Building LAN

DIGITAL IN

TRIAC

status

L-IOB

status

L-IOB

I/O Module
UNIVERSAL IN

I/O Module

0-10V OUT

UNIVERSAL IN

DI1 GND DI2 AO1 GND AO2

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

DIGITAL IN

0-10V OUT

DI1 GND DI2 AO1 GND AO2

Ethernet Switch
ETHERNET
Made in Austria

+~ -~

24 VAC/DC

LOYTEC
www.loytec.com

DO2 DO3 DO4 DO5 COM


6A

6A

6A

DO6 COM DO7 DO8 COM DO9

6A

TRIAC

LIOB-450

TRIAC

status

ETHERNET
Made in Austria

status

+~ -~

24 VAC/DC

LOYTEC
www.loytec.com

DO2 DO3 DO4 DO5 COM


6A

6A

6A

DO6 COM DO7 DO8 COM DO9

6A

LIOB-450

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

DIGITAL IN

0-10V OUT

DI1 GND DI2 AO1 GND AO2

TRIAC

TRIAC

status

status

L-IOB

L-IOB

I/O Module

I/O Module
UNIVERSAL IN

UNIVERSAL IN
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

DIGITAL IN

0-10V OUT

DI1 GND DI2 AO1 GND AO2

Max. distance between devices 100m (328ft)


Max. 20 devices in the Ethernet Ring

RSTP (Rapid Spanning Tree Protocol)

Network Security
Integral part of the LOYTEC hardware is a configurable firewall, which can be enabled and configured over the built-in Web server or over
OPC XML-DA. The built-in Web server is accessed via the secure HTTPS protocol. A pre-installed certificate allows a quick setup and can
later be replaced by a locally generated certificate or by a certificate issued by a certification authority. Data communication is encrypted
by TLS encryption methods and the use of secure certificates prevents man-in-the-middle attacks.

www.loytec.com

Functions
BACnet
BACnet (Building Automation and Control networks) is a standardized communication protocol for building automation (ISO 16484: Building automation and control systems Part 5: Data communication protocol). It was developed at the end of the 1980ies by the American
Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). Communication in the network is modeled on BACnet objects,
which are exposed as server objects by a BACnet device. Other BACnet devices connect as clients to those BACnet server objects. The network integration is accomplished by vendor-specific configuration tools.
LOYTEC devices with a BACnet interface expose data via BACnet server objects (binary, analog, multi-state) and communicate through
client mappings. Change-of-value (COV) events can trigger the transmission of values. The AST functions are available for BACnet scheduler, calendar, trend log, and notification class objects. Devices are connected to the BACnet network over BACnet MS/TP (twisted pair
based on RS-485) or BACnet/IP (100Base-T Ethernet). BACnet objects are created in the LOYTEC Configurator tool using EDE import, online
network scan, or manual creation.
As a default, BACnet objects use the ASCII character encoding on the device. This applies to the properties object name, object description,
active/inactive text, state text, etc. Most third-party tools are compatible with this setting. To support international character sets, LOYTEC
devices can be switched to use the encodings ISO-8895-1 (good for most Western Europe) or UCS-2 (good for Unicode character sets used
in Japan).
All LOYTEC products with the BACnet/IP interface can act as a BACnet time master. It is possible to use the BACnet services TimeSynchronization and UTCTimeSynchronization in order to send out time synchronization events. This happens after a power-on reset of the device,
when the system time is changed, or periodically. The system time on IP-based LOYTEC devices can be synchronized via NTP (Network
Time Protocol), which allows the LOYTEC device as a BACnet time master to synchronize all registered BACnet devices in the network to
the NTP time.
LOYTEC BACnet routers and BACnet devices with an integrated router can also function as a BACnet MS/TP slave proxy. A slave proxy
answers BACnet Who-Is broadcast requests sent to slave devices on the MS/TP bus on behalf of them with appropriate I-Am packets. This
covers the shortcoming of BACnet slave devices, which by definition cannot initiate communication by themselves. Using this feature, it
is possible to find MS/TP slave devices in a BACnet network scan, which would not be possible without the slave proxy. LOYTEC BACnet
routers, BACnet devices with an integrated router and L-GATE Gateways also have a built-in BACnet broadcast management device (BBMD)
for managing BACnet/IP Internetworks that span across IP routers. BACnet models without the router function can register as a foreign
device (FD) with other BBMDs.
BACnet devices with the BACnet MS/TP interface provide an additional remote MS/TP protocol analyzer. BACnet MS/TP packets are captured and can either be transmitted online to a Wireshark analyzer (sniffer program for analyzing network protocols available free of
charge) or stored offline as a capture file on the device. This file can be downloaded over the Web interface and opened later in Wireshark.
Other BACnet details such as the BACnet standardized device profile, the supported BIBBs (BACnet Interoperability Building Blocks) and
the object properties are specified in the respective PICS (Protocol Implementation Conformance Statement) document. Apart from this,
most LOYTEC devices are BTL-certified products that support the BACnet Building Controller (B-BC) profile (see also the related product
descriptions). The PICS, the BTL certificate, and the product manuals are available for download on www.loytec.com.

CEA-709
By the end of the 1990s, LON (Local Area Network) was standardized by the Consumer Electronics Association (CEA) under the title Control
Network Protocol as CEA-709. Today the CEA-709 protocol is a recognized international communication standard ISO/IEC-14908. LOYTEC
is highly experienced in the CEA-709 technology. LOYTEC developed its own technology to make devices talk on CEA-709 networks.
LOYTEC technology includes chip sets and also the fully featured ORION Protocol stack which executes the CEA-709 protocol on powerful 32-bit micro controllers. All LOYTEC devices supporting CEA-709 connectivity make use of this powerful technology. Communication
Objects (Network Variables) and functional profiles, standardized by LonMark International (www.LonMark.org), describe the communication interface of a LonMark device. Configuration properties (CPs) allow downloading and modification of device parameters. Network
integration is accomplished by a network management tool, which is independent of the hardware manufacturer (e.g. NL220 or LonMaker)
and is used for device installation and creation of bindings between network variables, which are stored in a database. This allows for a
clear separation between the application and the communication relations in the network. Configuration tools specific to LonMark nodes
integrate as plug-ins into the network management tool and allow for fast and simple device configuration.
LOYTEC devices can be used in LonMark Systems with standard network variable types (SNVT) or user-defined network variable types
(UNVT). The NVs can be created as static or dynamic network variables. Additionally, network variables of other LonMark nodes can be
brought in via external NVs, which are polled in a cyclical manner and written explicitly, without allocating and binding static or dynamic
NVs on the LOYTEC device. LOYTEC devices also offer direct access to configuration properties of other LonMark nodes (using LonMark
file transfer or read memory access methods). Both, standard configuration property types (SCPTs) and user-defined configuration property types (UCPTs) are supported. Network variables are created in the Configurator tool (plug in) by importing from a XIF file, scanning
an LNS database, scanning a network online, or by manual creation. The AST functions alarming (alarm management) and scheduling
are supported by using the respective LonMark profiles. Historic trend data can be logged by generic trend logs, which are technologyindependent. The device communicates on the LonMark System via a TP/FT-10 channel (twisted pair) or via IP-852 (Ethernet). A sub-group
of the LOYTEC devices is also LonMark certified (see product details).

buildings under control

Functions
DALI
DALI (Digital Addressable Lighting Interface) is a protocol for lighting control and standardized in Annex E of IEC 60929 and in the IEC
62386 standard. DALI is used as a lighting control sub-system for dimming and switching ballasts with a DALI interface. The ballasts can be
controlled and queried independently via DALI short addresses. Also DALI groups can be freely assigned for controlling lighting scenes.
The bi-directional communication allows also DALI ballasts to report operational parameters and errors. Although DALI buttons and DALI
multi-sensors are not covered by the DALI standard, they are interoperable depending on the manufacturer. The DALI standard specifies
the testing of emergency lighting systems with a DALI interface. In a DALI system, the DALI master controls and queries the DALI devices
in a master/slave manner. The multi-master capability allows also for multiple DALI masters on the channel.
LOYTEC devices with a DALI interface can be integrated in a DALI network as DALI masters with a constant light controller (CLC) function.
The configuration is done via the built-in Web interface or for some models via the Configurator tool. AST functions for alarming (alarm
management), scheduling, and trending (historical data recording) are also supported. As a DALI master, the devices can be installed
autonomously. For the integration in building automation systems, the LOYTEC DALI master is equipped with either a BACnet interface or
an interface to LonMark Systems.
More details on the communication behavior in the DALI network can be found in the respective product manuals, which are available for
download on www.loytec.com.

KNX
KNX is a communication protocol for building automation, which has been standardized as an international standard ISO/IEC 14543-3
Home Electronic Systems. KNX is used in the field of home automation and commercial building automation as well. In a KNX network,
sensors and actuators are assigned to a set of communication objects. A communication object represents a value of a given type, for
instance a temperature, a switch state or a setpoint. The communication objects communicate via group addresses. Sensors transmit a
message containing the current value to all actuators, which are member of the same group. In order to make devices of different manufacturers interoperable, the communication objects use a pre-defined set of standardized data point types (DPTs). Network integration in
a KNX system is accomplished by a vendor-independent installation tool based on a database (ETS - Engineering Tool Software).
LOYTEC devices are integrated into the KNX system by exporting the database of communication objects from the Engineering Tool Software (ETS4). ETS projects are imported by the LOYTEC Configurator tool. After the import of the KNX project, an overview of all available
KNX data points is displayed. The desired data points for use can be chosen from this list. Later changes to the ETS project can be tracked
and synchronized the same way. Once KNX data points have been integrated, they can be used for AST functions. The alarming (alarm
management) is based on generic alarm servers. On LOYTEC devices for LonMark Systems, KNX data points can be scheduled by LonMark
scheduler objects. On BACnet devices, KNX data points can be scheduled by BACnet scheduler objects. Historic trend data of KNX data
points can be logged by generic trend logs. The device communicates to the KNX system on KNX TP1 (twisted pair using an external KNX
coupler) and on KNXnet/IP (Ethernet).
More details on the communication behavior in KNX systems can be found in the respective product manuals, which are available for
download on www.loytec.com.

M-Bus
The M-Bus (Meter-Bus) is an established European standard (EN 13757-2, EN 13757-3) for remote meter reading. The M-Bus is a serial bus
and employs a master/slave architecture. The M-Bus master can request data from several slaves (meters) on the network. The data transfer
from master to slave is a voltage-modulated signal. The transfer from slave to master is a current-modulated signal. M-Bus devices can be
bus-powered. The maximum number of nodes, which can be powered on the bus, depends on the M-Bus transceiver.
LOYTEC devices with M-Bus support are M-Bus master and require an external transceiver for the integration of M-Bus meters. M-Bus data
points can be created from an online network scan or offline by using M-Bus device templates, which have been previously created. The
assignment of primary addresses to the M-Bus devices can be done in the Configurator tool. AST functions for alarming (alarm management), scheduling, and trending (historic data recording) also apply to M-Bus data points. Especially the historic data logging and cyclic
polling of values is optimized for M-Bus meters.
More details on the integration of M-Bus devices can be found in the respective product manuals, which are available for download on
www.loytec.com.

10

www.loytec.com

Functions
Modbus (TCP, RTU)
Modbus is an open protocol and a de-facto standard in the industry, which is based on a master/slave architecture. It was originally
designed at the end of the 1970s for exchanging data between PLCs. Today, Modbus is still a widely used interface for integrating field
devices into a system. Modbus devices communicate over a serial interface or over TCP/IP. Modbus TCP specifies communication over
TCP/IP and is part of the standard IEC 61158. Modbus devices use registers for data exchange, which are characterized by register type,
address, and length. In addition, data type and byte order need to be specified in order to interpret Modbus data. The configuration is done
by vendor-specific tools.
LOYTEC devices with a Modbus interface provide two communication methods: Modbus TCP (Ethernet TCP/IP) and Modbus RTU (Remote
Terminal Unit, based on RS-485). A Modbus interface can be operated either as a master or as a slave. The supported register types are:
Read Discrete Inputs (2), Read Coils (1), Write Coils (5), Read Input Registers (4), Read Holding Registers (3), Write Holding Registers (6). For
third-party integration, the vendors datasheet needs to be consulted in order to manually create a configuration. The Modbus technology
does not offer a method for scanning this information online, as it is known from other technologies. For Modbus devices that are online,
the manual configuration can however be tested via an online test function. By looking at the extracted values, the respective data points
can then be configured accordingly. Modbus device templates can be created, which allows the re-use of Modbus configurations and
reduces errors in configuration. AST functions for alarming (alarm management), scheduling, and trending (historic data recording) also
apply to Modbus data points.
More details on the communication behavior in a Modbus network can be found in the respective product manuals, which are available
for download on www.loytec.com.

OPC
OPC is a de-facto standard for interoperable communication in the automation industry, which is also often used for data exchange
between management level and automation level in building automation. OPC is a set of different specifications and versions, which can
be implemented independently of each other.
LOYTEC devices that support OPC have a built-in OPC server following the OPC XML-DA specification. When integrating the different
communication technologies (CEA-709, BACnet, DALI, M-Bus, Modbus, KNX, ), OPC tags are automatically created without additional
engineering effort and exposed via a Web services. The OPC server provides data access via Web services according to XML-DA, which are
available over the same TCP port as the built-in Web server. The OPC server exposes simple data points and complex AST functions as
OPC tags for alarming (alarm management), scheduling, and trending (historic data recording). Since the OPC XML-DA standard does not
specify corresponding tags for these functions, the OPC XML-DA server uses groups of OPC tags for exposing AST functions. Because
Web services are built for being routed across the Internet, the built-in OPC XML-DA server uses basic authentication for protection against
unauthorized write access. Authentication requires the operator user and the respective password.
The L-WEB System uses OPC XML-DA communication (Web services) for data exchange with LOYTEC devices. This allows for a hassle-free
communication in the Intranet or Internet across firewalls and NAT routers. Also third-party applications such as SCADA systems can communicate as OPC XML-DA clients over the Intranet or Internet and access the built-in OPC server in a simple and secure way. The embedded
OPC servers do not require extra PC hardware and can be distributed in the IP network. For those SCADA packages, which do not support
OPC XML-DA, a bridge software can be installed, which connects XML-DA to the COM-based protocol (OPC DA as of 2.0.5).
More details on OPC communication can be found in the respective product manuals, which are available on download from
www.loytec.com.

CEA-709 Router Function

CEA-709

The CEA-709 router function allows the transparent connection of two LonMark channels in a LonMark System. One of the channels can be
a LonMark IP-852 (Ethernet/IP) channel. LOYTEC devices featuring IP-852 routing have a built-in IP-852 configuration server to configure
and manage all IP-852 members on the channel.

BACnet Router Function

BACnet

The BACnet router function allows the transparent connection of one BACnet/IP channel and one BACnet MS/TP channel. In addition,
the router function implements a BACnet Broadcast Management Device (BBMD) and features Foreign Device support. For MS/TP slave
devices it acts as a slave proxy.

buildings under control

11

Functions
Remote Access
LOYTEC devices offer remote access functions, which differ slightly depending on the device model. All device settings can be modified, data point values can be queried, and configuration parameters can be modified. Apart from this, backup and restore of the device
configuration is available. The same applies to parameters. Access to AST functions for alarming (alarm management), scheduling, and
trending (historic data recording) is also supported, including reading out alarm logs and trend logs from the device via file transfer. The
devices offer various analysis functions and statistical data for troubleshooting the used communication protocols. Programmable LOYTEC
devices also provide online test functions for developing application programs.

Remote Network Interface (RNI)

RNI

The Remote Network Interface (RNI) function is available, if the LOYTEC device is configured to operate on the TP/FT-10 channel. In
this mode, the LOYTEC device appears as a LOYTEC network interface and thus enables remote access to the TP/FT-10 channel over an
Ethernet/IP connection. In this mode, the network interface can be used together with LNS-based tools such as NL220 or LonMaker or a
direct LOYTEC network interface. Furthermore, the RNI offers the remote LPA(LOYTEC Protocol Analyzer) feature for remote troubleshooting.

Gateway
The gateway functions allow data exchange between all available communication technologies. This is accomplished by using connections which connect data points of different technologies with each other. Both 1-to-n and m-to-1 connections are supported.
Connections can contain simple or complex calculations. Different engineering units of connected data points are automatically
converted. Repeating or complex connections can be created by using templates, which help using pre-defined gateway building
blocks. Connections are distinguished into local and global connections. Connections can be created manually or automatically using
the Smart Auto-Connect feature of the Configurator tool. Especially the automated creation of connections reduces the engineering
effort and helps preventing configuration errors.
The Smart Auto-Connect feature works on a selection of source data points and creates target data points and the respective connections. In principle, Smart Auto-Connect can work with all available communication technologies as sources. However, only select
technologies can be used as targets. Depending on the availability on the device model, data points can be created for the following
technologies: CEA-709 (static NVs), BACnet (server objects), Modbus (slave registers) and user registers. A remarkable feature in this
context is the automatic mapping of network variables to BACnet objects according to CEN/TS 15231:2005.

Local Connection
A local connection is used for connecting data points of different networking technologies, which are integrated on a single LOYTEC
device.

Global Connection
Global connections provide similar functions like local connections, but can span across an IP network between two or more LOYTEC
devices. A global connection creates a data cloud with a system-wide name. Data points which are added to a global connection can send
values into the cloud or receive values from the cloud. This is entirely independent from the installation location or the original communication technology.

12

www.loytec.com

Functions
L-IOB I/O Module
L-IOB I/O Modules extend the L-INX Automation Servers, IP-capable L-IOB I/O Controllers, and L-ROC Room Controllers by adding
physical inputs and outputs. There exist different L-IOB I/O Modules depending on I/O configurations and communication interfaces.
L-IOB I/O Modules with LIOB-Connect can be directly connected in a daisy-chain. Those L-INX Automation Servers and L-ROC Room
Controllers that support this feature, automatically detect which I/O modules are connected and map the corresponding data points.
All L-INX and L-ROC models provide an additional way for connecting and integrating L-IOB I/O Modules via LIOB-FT (twisted pair) and
L-IOB IP (Ethernet). L-IOB IP I/O Controllers are limited to the use of one additional L-IOB IP I/O Module.

LIOB

LIOB-Connect

CONNECT

The LIOB-Connect port of a L-INX or L-ROC device allows connecting LIOB-10X Modules and provides a power and communication path
without additional cabling. Regardless of the L-IOB type, up to 24 L-IOB I/O Modules are supported. This makes up to 24 LIOB-10x devices
possible in a daisy chain. The first four LIOB-10x can be connected directly. Starting with the fourth LIOB-10x, the LIOB-Connect chain
needs to be divided into two (or more) segments using L-IOB A2 adapters.
Parameterization of the I/O modules is done by the Configurator software or over the Web interface of the L-INX or L-ROC device. All parameter data is stored on the L-INX Automation Server or the L-ROC Room Controller and can be downloaded to the L-IOB Modules again if
needed. When replacing a L-IOB Module, it is detected and integrated again automatically.

LIOB
FT

LIOB-FT

The LIOB-FT port allows operation of remote LIOB-15x Modules. These are connected by twisted-pair cabling of up to 500m length in free
topology or more than 500m in bus topology. The maximum number of supported LIOB-15x Modules depends on the L-INX Automation
Server model, the L-IOB IP I/O Controller model, or the L-ROC Room Controller model.
Parameterization of the I/O Modules is done by the Configurator software or over the Web interface of the L-INX, L-IOB IP or L-ROC device.
All parameter data are stored on the L-INX Automation Server, the L-IOB IP I/O Controller or the L-ROC Room Controller and can be downloaded down to the L-IOB Modules again when needed. When replacing a L-IOB Module this is detected and integrated again automatically.

LIOB
IP

LIOB-IP

The LIOB-IP port allows operation of remote LIOB-45x Modules. These are connected over Ethernet/IP (100Base-T). The maximum number
of supported LIOB-45x Modules depends on the L-INX Automation Server model, the L-IOB IP I/O Controller model, or the L-ROC Room
Controller model. Communication across NAT routers is not supported.
Parameterization of the I/O Modules is done by the Configurator software or over the Web interface of the L-INX, L-IOB IP or L-ROC device.
All parameter data is stored on the L-INX Automation Server, the L-IOB IP I/O Controller or the L-ROC Room Controller and can be downloaded down to the L-IOB Modules again if needed. When replacing a L-IOB Module this is detected and iintegrated again automatically.

Programming Functions

&

IEC 61131- L-LOGICAD

The development of an application program is done in the graphical programming environment L-LOGICAD (IEC 61131-3 standard), which
offers programming languages using function blocks (FBs) or structured text (ST). It is possible to mix programming languages within the
same project. The IEC 61131-3 programming software allows an online test of the application over the Ethernet/IP network or the TP/FT-10
channel (depending on the hardware). IEC 61131-3 applications can be modified without interrupting execution. L-LOGICAD offers a variety of tools for diagnosis and debugging, commissioning, and additional service function blocks (e.g.,force update). Errors can be detected
early when developing the function plan in the integrated, graphical offline simulation. Oscilloscope and logic analyzer functions allow
a timely display of the respective values. Apart from this, watch pages can be added for visualization and modification of run-time values.
L-LOGICAD can access all data points and parameters on the device and process them in the logic program. The program operates independently of the underlying communication technology or the underlying L-IOB I/O Module..

buildings under control

13

Functions
IEC 61499 - L-Studio
The application project is created with the graphical programming system L-STUDIO (IEC 61499 standard), which allows programming
using function blocks (FBs). In L-STUDIO, the programming environment comprises the entire project, where each controller in the IP network is treated as a computing resource with data points. L-STUDIO deploys the application to the networked controllers and creates the
connections between them automatically. Event-oriented execution of the program allows for fast reaction times. As a novel approach to
automation we name this Cloud Control. An arbitrary set of functions can be mapped to a cloud of controllers. The strictly object oriented
programming method allows for efficient reuse of previously implemented functions. A variety of debugging and watch functions allows
for building-wide troubleshooting during run-time.

Mathematical Functions

y=f(x)

Mathematic objects with user-defined formulas can execute mathematical functions on data points. A mathematic object uses a number
of data points as input variables (v1, v2, , vn) and calculates a result according to the formula. The result is written as an output to a
number of data points. The calculation is executed each time one of the input data points changes its value. A result is calculated only if all
inputs have a valid value (i.e., none of them has the invalid value status).

Device Management

Backup / Restore
Depending on the device model, there exist several possibilities to backup and restore a device configuration. In principle, all LOYTEC
devices with a built-in Web server offer the backup and restore function on the Web interface. Also the Configurator tools provide this function for their respective device models. When using the L-WEB System, backups of device configuration can be created on a timely basis
(e.g. once a day) and restored easily when needed. Devices with SD card support and USB port allow a device backup onto external storage. The backup and restore function is operated locally on the LCD display. In all cases, the LOYTEC device is restored with all data points,
dynamic NVs and bindings, BACnet server objects and client mappings, etc. The device appears again as commissioned and online and is
fully functional in the network. In case an LNS-based tool is used, the LNS device needs to be replaced, which can be done at a later time.

L-DALI

Device Manager

LOYTEC

www.loytec.com

OC
L-R

LINX100
1

The Device Manager is a component of the L-WEB Server. It stores and manages configuration files of LOYTEC devices. For programmable
devices, the Device Manager also covers the application program. The backup feature ensures the frequent backup of all relevant device
configuration files over the Intranet or Internet. System-wide backups can be automatically created based on a time schedule. In case of a
device swap, the most current backup is readily available on the network and can be used to restore the configuration on the replacement
device. Depending on the hardware, the restore operation for the device configuration can be easily triggered from the LOYTEC device.
Otherwise it can be managed in the L-WEB System even from remote.
For efficient maintenance, the Device Manager lists all LOYTEC devices available in the system in a device overview. In this view it displays
the operational device state including the firmware version. A firmware upgrade can be performed for single devices as well as for groups
of devices.

14

www.loytec.com

Functions
Visualization / Operate and Monitor

Local Manual Operation


The LOYTEC device is equipped with a graphical LCD display (128x64) and a jog-dial, which can be used for monitoring, testing, and configuration. The backlight is automatically turned off after 30 minutes of jog-dial inactivity. Access to the display can be protected by a PIN
code. The display can show the current device configuration and allows its modification. All basic settings (IP address, BACnet ID, ) can
be made on the LCD display.
Apart from configuration, L-INX Automation Servers and L-GATE Gateways with a graphical LCD display allow operating trend data backup
to external storage (SD card or USB stick) and backup/restore of the entire device configuration. Also the state of the integrated data points
can be displayed and modified. Remote access to the LCD display over an Ethernet/IP connection is made possible by the VNC protocol.
The LOYTEC device exposes the display content over the integrated VNC server for remote display.
In L-IOB I/O Modules and Controllers, the graphical LCD displays allow apart from modifying the configuration access to physical I/O
data points and parameters. The data point state is displayed as a value and engineering unit, as a status text, or showing dynamic symbols.
Inputs and outputs can be switched to manual mode on the display and thus be decoupled from the physical input or the output value
from the logic application. Manual mode is shown per I/O on the display.

VNC

VNC

The VNC (Virtual Network Computing) service offers password-protected remote access to the LOYTEC device. VNC employs a client/server
model. The VNC server is a built-in component of the LOYTEC device. A great variety of freely available or commercial VNC clients is available on the market for different platforms. Which functions and views are exposed over VNC depends on the device.

Web Server for Device Configuration


The Web interface on LOYTEC devices with a built-in Web server provides an alternative to the Configurator tool for the maintenance
personnel. It can be used to configure the device settings and communication settings. It also provides extensive statistical information
on the used communication protocols for analysis and troubleshooting. Backup and restore can also be operated on the Web interface.
LOYTEC devices with an Ethernet/IP interface display data point values and states on the Web interface coming from different communication networks or registers. The display contains a data point list and a tree view. The data point list shows the data point name, direction,
type and the current value. Output data points can also be modified on the Web interface.
On LOYTEC devices with L-WEB support, all available graphical user interfaces are listed on the Web interface and can be started with a
mouse click.
LOYTEC devices with AST functions offer access to those functions over the Web interface.
An alarm summary page displays all currently active alarms of alarm data points, which can also be acknowledged, if configured so. The
Web interface also provides access to an historical alarm log, which lists alarms and acknowledgements. If an inactive, acknowledged
alarm disappears from the alarm summary page, the last transition is stored in the alarm log. The content of the historic alarm log can be
exported to a CSV file on the Web interface.
The Web interface provides a scheduler page, which allows modification of schedules and calendar entries for exception days during runtime. For existing local schedulers, the Web interface supports the re-configuration of the scheduled data points. The changes become
effective immediately and dont require a reboot of the device. For adding or removing data points to or from a scheduler, no reboot is
necessary, either.
The trend log configuration page on the Web interface allows the re-configuration of existing trend logs during run-time. This also includes
the assignment of new data points. The changes become effective immediately and dont require a reboot of the device. The trended data
can be exported into a CSV file over the Web interface.

buildings under control

15

LOYTEC Competence Partner


LOYTEC Comptence Partner Program
LOYTEC is a provider of innovative product solutions for designing networked building automation systems and interconnection of connected real estate. With our integrated products we
offer the foundation to build highly efficient automation solutions.
With the introduction of the LINX-120, LINX-150 and LINX-220 Automation Stations, LOYTEC
introduced the Competence Partner Program. The Competence Partner Program is the basis
for the successful use of L-INX Automation Servers and the entire LOYTEC product portfolio
in building automation.
We set high standards for ourselves regarding quality in research, development, and manufacturing of our products. As a Competence Partner you make a point of doing a professional planning and completion of automation solutions to the satisfaction of your
customers. With the Competence Partner Program we ensure that you get the necessary
knowledge of LOYTEC products and implementation concepts through sustainable training programs.
A true partnership is the foundation for our joint success in the market.
Therefore LOYTEC offers:
A balanced partnership while utilizing and marketing LOYTEC product solutions
Adjusted training programs for products and implementation concepts
Technical support for LOYTEC products and applications
Access to the freely programmable L-INX Automation Servers and L-IOB I/O Controllers
Access to L-WEB Building Management Software
Access to available graphics and application libraries
Priority information on new products and solutions
LOYTEC Competence Partner LOGO for use in your marketing activities
Your company data on our website with link to your website
You offer:
An established market access in building automation business
Pro-active marketing of LOYTEC product solutions
Pro-active feedback on LOYTEC products and market places
A dedicated and technically well-trained team
Regular attendance of LOYTEC trainings or trainings at a LOYTEC Competence Center
Always at least two staff members in the team trained by LOYTEC or the LOYTEC Competence Center
Preparation and publication of completed projects including a listing of utilized LOYTEC products and
providing of project information for use by LOYTEC
Link to LOYTEC website on your website
If you are interested in becoming LOYTEC Competence Partner, please contact sales@loytec.com

16

www.loytec.com

LOYTEC

COMPETENCE PARTNER

L-WEB Building Management

buildings under control

17

LOYTEC

LWEB900

COMPETENCE PARTNER

Gateways

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

Integrated Building Management System

The integrated building management software LWEB-900 provides a user interface to manage and operate a LOYTEC building management system. LWEB-900 is a highly flexible and scalable solution which accompanies you from installation and
configuration of LOYTEC devices (L-INX Automation Servers, L-IOB I/O Modules and Controllers with IP connectivity, L-ROC
Room Controllers, L-GATE Gateways, L-VIS Touch Panels), all the way to daily operation of the facilities. Thus, a common user
interface for the building automation system is available at all phases of the project.
LWEB-900 uses a client-server architecture consisting of the LWEB-900 Server and one or multiple LWEB-900 Clients. The
LWEB-900 Server manages and stores system and operating parameters, historic data, access rights, and device configurations in an SQL data base. It exchanges real time data with distributed autonomous LOYTEC devices via web services independently of the underlying field bus technology (CEA-709, BACnet, DALI, M-Bus, Modbus, KNX, etc.).
The LWEB-900 Client is the user interface of the building management system. The client can be installed on the same PC as
the server or on a remote PC. The use of web services to communicate between clients and server ensures that remote access
is easily possible across firewalls and NAT routers. In this way, Intranet and Internet can be used to build distributed building
automation systems. In addition, differences between the various field bus technologies are compensated and the user is
presented with a consolidated view of the separate communication systems.
To check the status of the buildings technical equipment, there is no need to install the LWEB-900 Client. If you have an IP
connection to the LWEB-900 Server, you can use a standard web browser to operate and monitor the building automation
system. It makes no difference, whether a smart phone, tablet, or PC is used.

LWEB-900 Client

iPad

L-VIS

Touch Panels

LWEB-900 Clients

LWEB-900 Server
NW

NE

SW

L-DALI

Lighting Control

LOYTEC
www.loytec.com

Ethernet
1 2

LGATE-951

USB

MICROSD RS-485

ACT

Routers, NIC

FT

EXT1

EXT2

L-GATE

LINK

1
RS-485

2
FT

EXT1

EXT2

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

Universal Gateway

BBMD OPC

Ethernet 1 Ethernet 2

CEA-709
BACnet
M-Bus
Modbus
KNX

LINX-120

USB

MICROSD

FT

LIOB-FT

MODBUS

FUSE 6A

EXT

ACT

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

LIOB-FT

MODBUS

Pa
P

21.6 C

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

status

LIOB-100

UI4

UI5

UI6 UI7

UI8

DI2 AO1

AO2

UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

19.5 C

UI6 UI7

UI8

DIGITAL IN
DI1

AO2

0.0 %

83

77
T

77

Pa

22.3 C

19.4 C

20.4 C

22.3 C

Software
Tools

0.0 %

18

+~ -~

24 VAC/DC

DO2 DO3 DO4 DO5 COM


6A

6A

6A

www.loytec.com

DO6 COM DO7 DO8 COM DO9

6A

TRIAC

LIOB-480

TRIAC

status

status

L-IOB

I/O Controller
UNIVERSAL IN

0-10V OUT

DI2 AO1

ETHERNET
Made in Austria

L-IOB

I/O Module

0-10V OUT

DIGITAL IN
DI1

LOYTEC
www.loytec.com

status

L-IOB

UNIVERSAL IN
UI2 UI3

Made in Austria

6A

LOYTEC
www.loytec.com

status

I/O Module

4
EXT
UI1

77

FUSE 6A

status

LIOB-100

Automation Server

1
FT

Made in Austria

6A

LOYTEC
www.loytec.com

L-INX

LINK

PLC OPC

Ethernet 1 Ethernet 2

Ethernet

Made in Austria

SE

LWEB-802 Client

Intranet
Internet
VPN

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

UI7 GND UI8

DIGITAL IN

0-10V OUT

DI1 GND DI2 AO1 GND AO2

L-WEB

LWEB900

Building Management

Integrated Building Management System

L-ROC

Room Automation

L-INX

Automation Servers

L-IOB

I/O Controllers/Modules

Visualize and Operate


iPad

Gateways
L-VIS

Touch Panels

In LWEB-900, all areas of a building are visualized and operated using installation schematics. Each schematic can consist of a large number of dynamic
display elements which reflect the current status of the facilities in real time.
These display elements also include complex elements like alarms, trend logs
and schedules. The configuration software to design the graphical representation of the installation is built directly into LWEB-900. Basic functions and
attractive pages can be created in no time without any know-how in HTML,
Java, etc. Dynamic information is shown in the form of numeric values, text,
changing icons, bar graphs, trend logs, alarm and event lists, or schedule controls. Pixel graphics in all common file formats (GIF, JPG, BMP, TIF, PNG) as well
as vector graphics (SVG) are supported.
The LWEB-900 Client adapts to the needs of the user. Dynamic schematics
can be displayed in a separate window or they can be arranged in a perspective together with an alarm view, navigation view, and data point watch view.

L-DALI
Routers, NIC

With LWEB-900, alarms from different sources can be visualized and managed in a uniform manner. It makes no difference whether an alarm is generated by a L-INX Automation Server to report that a V-belt is torn, a DALI light
controller to report that the emergency light test fails, or by an L-GATE device
to report an alarm from a 3rd party system. In LWEB-900, these alarms are
presented in a common way which enables the user to maintain an overview.
The user can acknowledge or disable alarms. When an alarm occurs, one or
multiple receivers can be notified via e-mail. If the alarm is not acknowledged
within a configurable amount of time, an alternative action can be triggered.

Lighting Control

Alarming

Software
Tools

buildings under control

19

LWEB900
Scheduling
LWEB-900 offers the unique possibility of organizing schedules executed
on different devices in a hierarchical way and configuring them efficiently.
The user interface is designed for non-technical users and is similar to calendar functions of common office applications. Schedulers are organized in
a tree structure. Entries on the highest hierarchical level have an impact on
all schedulers. Entries on a lower hierarchical level affect only the schedulers below that level. Local changes on the device are identified and can either be accepted or rejected. After the schedule hierarchy has been defined,
LWEB-900 calculates the resulting configurations and downloads them to the
corresponding devices. The schedules are executed decentralized in the devices to increase reliability of the system.

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

Integrated Building Management System

L-INX

Trending

Gateways

L-IOB

I/O Controllers/Modules

LOYTEC devices can record the value of data points over time. However, the
memory available on a device is limited. LWEB-900 overcomes this restriction by reading out the trend data from the devices periodically and storing
everything in the database. A user can also create ad-hoc trend logs directly
in LWEB-900. This is the fastest way to create a trend log. One simply selects
a data point and activates trending using the context menu. LWEB-900 periodically polls the data point value from the device and stores the value in the
database. If the LWEB-900 Server cannot access the LOYTEC device directly
via IP, an alternative communication method is available: the device can automatically e-mail trend data to the server. Trend logs can be viewed either as
tables or as charts. Especially for trend charts, a large number of customization options are available. In addition, LWEB-900 allows exporting trend data
as CSV files.
Event Log

L-VIS

Touch Panels

All events are logged by LWEB-900 in the database. Events include alarms,
alarm acknowledgements, log-in and log-out of users, change of operational
parameter, change of device configuration, system messages, etc. The event
log view offers a large variety of filters to efficiently analyze all activities in
LWEB-900.
Parameter View

L-DALI

Lighting Control

The parameter view allows configuring operational parameters, which are


distributed over multiple devices, efficiently. For example, parameters for
room temperature control, light control, or sunblind control can be organized in different parameter views. Each parameter view is a matrix where
each cell represents a parameter. Parameters can be organized freely in the
matrix depending on space layout and function. In this way, it is possible to
e.g. adjust the running periods of sun blinds across many rooms with a few
mouse clicks and write the new values reliably into the corresponding automation devices.
Global Connections

Software
Tools

Routers, NIC

With LWEB-900 it is easy to connect data points of different LOYTEC devices


via Ethernet/IP. For this purpose, a global connection can simply be created
and drag&drop can be used to add input and output data points. It makes no
difference whether the data points represent physical I/Os of L-IOB devices
or data from field bus systems (CEA-709, BACnet, DALI, M-Bus, Modbus, KNX,
etc.). LWEB-900 configures all devices which are part of the global connection
accordingly. After the connection has been configured, the devices exchange
data directly over the IP Network (without LWEB-900).

20

www.loytec.com

Device Configuration

L-IOB

I/O Controllers/Modules

LWEB-900 uses access control lists to define which operations a user can perform on a certain object (e.g. folder, data point, graphical view, parameter
view, trend chart). To speed up the access right configuration, access control
lists can be inherited from parent to child objects.

L-INX

LWEB-900 provides a separate work environment for each user. A user has
to log on to the system and is presented with a perspective tailored to his
individual requirements. A perspective defines which windows are open and
how they are arranged. In this way, a user can define separate perspectives
which are optimized for different tasks and quickly switch between them.

Automation Servers

Multiuser System

L-ROC

LWEB-900 gives a clear overview of the status of all devices and provides detailed information for each device (e.g. device type, name, IP address, firmware version, configuration file, program file, etc.). A firmware update can be
performed for individual devices or groups of devices.

Room Automation

LWEB-900 manages and configures all LOYTEC devices based on a central


database. The required device configuration software can be opened directly
in LWEB-900 and the configuration files are stored in the data base. A backup
feature ensures a regular backup of all relevant device configurations. If a defective device needs to be replaced, the configuration can be easily restored.
Depending on the device hardware, the restore operation can either be triggered from the LCD UI of the device or from the LWEB-900 Client.

L-WEB

LWEB900

Building Management

Integrated Building Management System

Licensing

L-VIS

Touch Panels

LOYTEC L-IP Router and L-IOB Modules connected to L-INX Automation Servers, L-ROC Room Controllers or L-IOB I/O Controllers via L-IOB plugnplay do
not consume a device license.

Gateways

The licensing is based on the number of devices connected to an LWEB-900


Server. The base license includes 10 LOYTEC device licenses. To extend the
number of devices, add-on licenses for 10 devices are available. An add-on
license for an unlimited number of devices is available as well. For customers
who know right from the beginning that they need a license for an unlimited
number of devices, such license is offered as well. The maximum number of
devices that can be integrated on an LWEB-900 Server depends on the PC
and the database ressources provided.

A fully featured LWEB-900 demo license with 30 days runtime is provided as


well, including 10 device licenses.
L-DALI
Routers, NIC

Together with LOYTEC devices, LWEB-900 is a seamless and comprehensive


solution for building automation. Instead of separate tools and project files
for different devices, LWEB-900 provides a common user interface for configuring and operating the complete system. The consistent use of web services
for data communication allows controlling LWEB-900 from remote, no matter
whether there are firewalls and NAT routers or not. In this way, end users and
service technicians can monitor, operate, and configure the buildings technical equipment from remote using standard IP technology.

Lighting Control

Conclusion

Software
Tools

buildings under control

21

L-WEB

Building Management

Integrated Building Management System

LWEB900
Features
Manages users and access rights

Saves complete device configurations, trend and alarm logs,


calendar and timer parameters, and parameter settings

Room Automation

SQL data base server with access to external links

L-ROC

Fast and system-wide access to real time data


Displays customized graphic pages with dynamic content
Presentation of trend data in the form of charts or tables
Hierarchical organization of calendar and scheduler parameters
across multiple devices

Automation Servers

Informative alarm lists, and time- and event-based forwarding


via e-mail to several recipients

L-INX

Structured representation and efficient adaptation of system


and operating parameters

Automatic, periodic device backup and easy recovery of the


device configuration for a device replacement
Automatic updates (Internet connection required)
Detects devices with outdated firmware
Download of the latest firmware for a defined group of devices
Uses Web services for communication (OPC XML-DA,
SOAP/XML)
Easy communication across firewalls and NAT routers on the
Intranet and Internet

L-IOB

I/O Controllers/Modules

Configuration software for LOYTEC hardware can be directly


started within the LWEB900 user interface.

For use with

LINX Automation Server, L-ROC Room Controller, L-GATE Gateway, L-DALI Controller,
L-VIS Touch Panel, LIOB I/O Controller, L-IP Router

Operating system

Windows7, Windows Vista, Windows XP, Windows Server 2008

Order number

Product description

LWEB900

Building Management Software for 10 LOYTEC devices (L-IP Router and L-IOB I/O Modules connected as extension to the L-INX Automation Servers, L-ROC Room Controllers and L-IOB I/O Controllers do not consume a
device license)

LWEB900-ADD-10

Add-on license for 10 additional LOYTEC devices

LWEB900-ADD-MAX

Add-on license for an unlimited number of LOYTEC devices

LWEB900-MAX

Building Management Software for an unlimited number of LOYTEC devices

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

Specifications

22

www.loytec.com

L-DALI

Lighting Control

Routers, NIC

Pictures speak louder than words. According to this principle LWEB-830


produces significant pictures in the form of reports. Energy consumption
reports from trend and event logs stored on the LWEB-900 Server can be
automatically created at regular intervals in PDF format, published on a Web
server or sent by e-mail to any user.

L-VIS

LWEB-830 Dream Report

Touch Panels

LWEB-802 can show customized graphic pages with dynamic content directly in a standard Web browser. LWEB-802 pages are based on HTML5 and
JavaScript that can be shown in todays Web browsers without the need to
install any additional software or browser plug-ins. LWEB-802 is tested to
work with PCs (MS and MAC), Tablet PCs and Smart Phones running Android
or iOS. The page creation process and also the feature set is like LWEB-800.

Gateways

LWEB-802 Operate and Monitor in a Web Browser

L-IOB

Customized graphic pages with dynamic content can be shown with


LWEB-800 on Windows PCs. Graphic pages are created with no requirement
for knowledge of any Web-based language within the L-VIS Configuration
Tool. Animation of the graphic elements is done via changes of values on
assigned data points. Data points used on graphical pages can come from
one or more IP enabled L-INX Automation Servers, L-Gate Gateways, L-VIS
Touch Panels, L-IOB I/O Controllers or L-ROC Room Controllers. Trend logs are
directly viewed from data on the device. If an LWEB-900 Server is available
the LWEB-800 application automatically merges the trend log data available
on the device with the long-term data stored in the LWEB-900 SQL database
when viewing a trend.

I/O Controllers/Modules

LWEB-800 Operate and Monitor on MS Windows PCs

L-INX

L-WEB components communicate with each other and with distributed


automation devices in the field via IP channels using the Web service OPC
XML-DA. The LOYTEC automation devices featuring Ethernet/IP connectivity
such as L-INX, L-ROC, L-IOB I/O Controllers, L-DALI and L-VIS support access
through OPC XML-DA. These devices do also support alarming, scheduling
and trending (AST functions) functionality.

Automation Servers

IP Communication via Web Services

L-ROC

Each user has different requirements for the systems in building automation. The range goes from a user who wants to operate his room from the PC
desktop (room automation) to the operator who is responsible for the maintenance of the mechanical systems (building automation). Or, the facility
manager who needs the energy consumption prepared in easily understandable reports. The L-WEB System provides a solution specific to each user.

Room Automation

Users in Focus

L-WEB

L-WEB is a powerful system for running distributed systems in building automation. Maximum flexibility and scalability is achieved through a combination of several software components that together form the L-WEB System.
Individual software components for specific tasks are available in the L-WEB
System to different users. Multiple users can simultaneously use the system
functions on different PCs.

Building Management

LWEB8xx Product Overview

Software
Tools

buildings under control

23

LWEB800
LWEB-800 is a graphical user interface to visualize dynamic pages showing plant
details or a virtual room operator panel on a Microsoft Windows PC.
Dynamic Graphical Pages
The graphical pages consist of multiple dynamic graphical controls that show
the current plant status in real time. It is also possible to access decentralized
schedules, alarm servers or trends. The graphical projects are designed with the
L-VIS/L-WEB configuration tool free of charge. Without any know-how in HTML
or Java, user specific graphical pages can be created. Dynamic information
is shown through value or text controls, changing symbols, bar charts, trend
views, alarm and event lists, or schedule controls. The L-VIS/L-WEB configuration
tool allows for using most of the pixel graphic formats (GIF, JPG, BMP, TIF, PNG) or
vector graphics (SVG). The graphical projects may be stored on a LOYTEC device
connected to the building network, on a file server, or on a 3rd party Web server.

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

Graphical User Interface

Integration in local PCs with adjustable dwell time for occupancy detection is
also available.

Data Point Communication through Web Services

L-IOB

I/O Controllers/Modules

LWEB-800 talks to the LOYTEC devices by using Web services. Utilizing Web
services allows for smooth communication across firewalls and NAT routers. It
enables to use the Intranet or the Internet to build up a distributed building
automation system.

Fast Navigation

Touch Panels

Gateways

When executing the graphical project, LWEB-800 loads the complete content
and stores it on a PC. When changes in the graphical project are made reloading
the project simply updates the version on the PC. During normal operation, the
data communication between LWEB-800 and the LOYTEC devices is limited to
data point updates. The result is a fast navigation between the pages even when
the connection is slow.

L-DALI

Lighting Control

L-VIS

LWEB-800 Client

Intranet
Internet
VPN

Routers, NIC

Ethernet

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

LGATE-951

USB

MICROSD RS-485

FT

EXT1

EXT2

L-GATE

LINK
ACT

1
RS-485

2
FT

EXT1

EXT2

LOYTEC
www.loytec.com

CEA-709
BACnet
M-Bus
Modbus
KNX

Software
Tools

Ethernet
1 2

Made in Austria

Universal Gateway

BBMD OPC

Ethernet 1 Ethernet 2

LINX-120

USB

MICROSD

FT

LIOB-FT

MODBUS

FUSE 6A

EXT

ACT

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

LIOB-FT

MODBUS

Pa
P

21.6 C

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

status

LIOB-100

UI4

UI5

UI6 UI7

UI8

L-IOB

I/O Module

0-10V OUT

DIGITAL IN
DI1

DI2 AO1

AO2

UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

19.5 C

UI6 UI7

UI8

DIGITAL IN
DI1

0-10V OUT

DI2 AO1

AO2

0.0 %

83

77
T

77

Pa

22.3 C

19.4 C

20.4 C

22.3 C

0.0 %

24

ETHERNET
Made in Austria

+~ -~

24 VAC/DC

LOYTEC
www.loytec.com

status

L-IOB

UNIVERSAL IN
UI2 UI3

Made in Austria

6A

LOYTEC
www.loytec.com

status

I/O Module

4
EXT
UI1

77

FUSE 6A

status

LIOB-100

Automation Server

1
FT

Made in Austria

6A

LOYTEC
www.loytec.com

L-INX

LINK

PLC OPC

Ethernet 1 Ethernet 2

www.loytec.com

DO2 DO3 DO4 DO5 COM


6A

6A

6A

DO6 COM DO7 DO8 COM DO9

6A

TRIAC

LIOB-480

TRIAC

status

status

L-IOB

I/O Controller
UNIVERSAL IN
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

DIGITAL IN

0-10V OUT

DI1 GND DI2 AO1 GND AO2

Virtual Room Operator Panel on PC

L-ROC

Room Automation

LWEB-800 can be used as a state of the art alternative to physically mounted


room operator panels. LWEB-800 pages can be viewed in Design Mode which
allows showing the graphical pages without frames and transparent background.
LWEB-800 virtual room operator panels can be stored on the LOYTEC devices and
operated within the MS Windows PC environment. There is practically no limit
for the designer regarding the size, colors, and utilization of graphical elements.
Even high availability of the system can be achieved by storing the virtual operator panels distributed on devices in the network.

L-WEB

LWEB800

Building Management

Graphical User Interface

Protected Kiosk Mode

Gateways

LOYTEC devices can host multiple LWEB-800 projects. Each of these projects can
have any resolution to display them perfectly on a PC monitor. Multiple Windows
PCs can access LOYTEC devices at the same time. Widgets or dashboards can be
created and placed on the PC desktop. Virtual room units can be designed appealingly in terms of style and usability to give access to room functions.

L-IOB

Display Diversity

I/O Controllers/Modules

LWEB-800 can show data points located on multiple distributed devices in one
page. This functionality is particularly important when utilized in energy monitoring applications where meter values are provided by distributed LOYTEC devices.

L-INX

Show Data Points from Multiple Devices in One Page

Automation Servers

In Kiosk Mode, users can only operate the LWEB-800 application on the PC.
When in Kiosk Mode, the user has no access to the PCs desktop or any other
software running on the PC.

Features

Automatic updates (Internet connection required)

Allows access to automation functions such as alarming,


scheduling, and trending

Uses Web services


communication

(OPC

XML-DA,

SOAP/XML)

Presentation of trend data in the form of charts or tables

Easy communication across firewalls and NAT routers

L-VIS

User-specific page layout, optional frameless with transparent


background

Design of graphical projects with the L-VIS Configuration


software

Touch Panels

Displays customized graphic pages with dynamic content

for

L-DALI

Lighting Control

Display of alarms in alarm lists


Allows links between distributed LWEB800 projects for a
continuous operation

Specifications
L-INX Automation Server, L-ROC Room Controller, LGATE-950 and LGATE-951 Gateway,
L-VIS Touch Panel, LIOB I/O Controller

Operating system

Windows7, Windows Vista, Windows XP, Windows Server 2003/2008 R2, Windows Mobile for
Pocket PC

Configuration tools

L-INX/L-GATE Configurator and L-VIS/L-WEB Configurator

Product description

LWEB800

Graphical user interface, distributed visualization on Windows PC, free download

buildings under control

Software
Tools

Order number

Routers, NIC

For use with

25

LWEB802
LWEB-802 is a platform independent graphical user interface to visualize dynamic pages showing plant details or a virtual room operator panel in a standard Web browser. By utilizing HTML5 and Java Script, the pages can be shown
in a standard Web browser without the need to install Java or browser plugins. LWEB-802 pages can also be shown on Smart Phones or Tablet PCs running
Android OS or iOS. No apps are required or need to be maintained.

L-ROC

Room Automation

L-WEB

Building Management

Graphical User Interface

Dynamic Graphical Pages

I/O Controllers/Modules

L-INX

Automation Servers

The graphical pages may consist of multiple dynamic graphical controls that
show the current plant status in real time. It is also possible to access decentral
schedules, alarm servers or trends. The graphical projects are designed with the
L-VIS/L-WEB configuration tool free of charge. Without any know-how in HTML
or Java, user specific graphical pages can be created. Dynamic information
is shown through value or text controls, changing symbols, bar charts, trend
views, alarm and event lists, or schedule controls. The L-VIS/L-WEB configuration
tool allows for using most of the pixel graphic formats (GIF, JPG, BMP, TIF, PNG)
or vector graphics (SVG). The

graphical projects may be stored on a LOYTEC device connected to the building network, on a file server, or on a 3rd party Web
server.

L-IOB

Data Point Communication through Web Services


LWEB-802 talks to LOYTEC devices using Web services. Utilizing Web services
allows for smooth communication across firewalls and NAT routers. It enables
to use the Intranet or the Internet to build up a distributed building automation
system.

Gateways

Fast Navigation
When opening the project, the complete content is loaded into the Web browser. Navigating through the pages is done without loading any more content.
The communication between LWEB-802 and LOYTEC devices is reduced to just
data point updates. The result is extremely fast navigation between graphical
pages even when the connection is slow.
iPad

Room Operation through Web Browser

L-VIS

Touch Panels

Specifically for room automation applications, LWEB-802 can be used as a state


of the art alternative to room operator panels. Virtual room operator panels can
be stored on the LOYTEC devices and operated within a standard Web browser.
There is practically no limit for the designer regarding the size, colors, and utilization of graphical elements. A high availability of the system can be achieved
by storing the virtual operator panels distributed on devices in the network.

Lighting Control

Show Data Points from Multiple Devices in One Page

Software
Tools

Routers, NIC

L-DALI

LWEB-802 can show data points located on multiple distributed devices in one
page. This functionality is particularly important when utilized in energy monitoring applications, where meter values are provided by distributed LOYTEC
devices.

26

www.loytec.com

L-WEB

LWEB-802

Building Management

Graphical User Interface

iPad

NW

L-ROC

Room Automation

NE

E
SE

SW

LWEB-802 Client

Automation Servers

Intranet
Internet
VPN

Ethernet
1
2

Made in Austria

LOYTEC
www.loytec.com

LGATE-951

USB

MICROSD RS-485

FT

EXT1

EXT2

L-GATE

LINK
ACT

1
RS-485

2
FT

EXT1

EXT2

Ethernet
1
2

Made in Austria

LOYTEC
www.loytec.com

Universal Gateway

BBMD OPC

Ethernet 1 Ethernet 2

L-INX

Ethernet

USB

MICROSD

FT

LIOB-FT

MODBUS

FUSE 6A

EXT

ACT

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

LIOB-FT

MODBUS

21.6 C

UI4

UI5

UI6 UI7

DI1

0.0

DI2 AO1

AO2

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

DO2 DO3 DO4 DO5 COM


6A

6A

6A

AO2

DO6 COM DO7 DO8 COM DO9

6A

TRIAC

LIOB-480

TRIAC

status

status

L-IOB

I/O Controller
UNIVERSAL IN

0-10V OUT

DI2 AO1

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

UI7 GND UI8

DIGITAL IN

0-10V OUT

DI1 GND DI2 AO1 GND AO2

77
T

Pa

UI2 UI3

83

77

+~ -~

24 VAC/DC

LOYTEC
www.loytec.com

L-IOB

UNIVERSAL IN
UI1

19.5 C

ETHERNET
Made in Austria

status

I/O Module

0-10V OUT

DIGITAL IN

UI8

Made in Austria

status

LIOB-100

L-IOB

UNIVERSAL IN
UI2 UI3

L-IOB

Pa

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9
6A

LOYTEC
www.loytec.com

status

I/O Module

4
EXT
UI1

77

FUSE 6A

status

LIOB-100

Automation Server

1
FT

Made in Austria

6A

LOYTEC
www.loytec.com

L-INX

LINK

PLC OPC

Ethernet 1 Ethernet 2

I/O Controllers/Modules

CEA-709
BACnet
M-Bus
Modbus
KNX

LINX-120

22.3 C

19.4 C

0.0

20.4 C

22.3 C

Gateways

Features

Presentation of trend data in the form of charts or tables


Display of alarms in alarm lists
Allows links between distributed LWEB802 projects for a
continuous operation

Automatic updates (Internet connection required)


Uses Web services
communication

(OPC

XML-DA,

SOAP/XML)

for

L-VIS

Allows access to automation functions such as alarming,


scheduling, and trending

Design of graphical projects with the L-VIS Configuration


software

Touch Panels

Displays customized graphic pages in the web browser

Easy communication across firewalls and NAT routers

L-DALI

Lighting Control

Specifications
L-INX Automation Server, L-ROC Room Controller, LGATE-950 and LGATE-951 Gateway,
L-VIS Touch Panel, LIOB I/O Controller

Web browser

Chrome, Internet Explorer 9, Firefox, Android Browser, iOS Browser

Configuration tools

L-INX/L-GATE Configurator and L-VIS/L-WEB Configurator

Order number

Product description

LWEB802

Graphical user interface via web browser, platform independent, compatible to Android and iOS, free download

Routers, NIC

For use with

Software
Tools

buildings under control

27

LWEB830
LWEB-830 Dream Report is a reporting software used for evaluation and treatment of long-term trend and event logs that are held by one or multiple existing
LWEB-900 Servers.
Report templates can be easily created or modified by the user. No programming
skills are required. Information can be linked in any order by mathematical operations. Data can be presented in numerical series, tables, or graphically (trend, bar
and pie graphs). The inclusion of illustrations or graphics helps to make the reports
meaningful. Reports can be generated at any time on user request or automatically
based on defined dates or periods (daily, weekly, monthly, etc.).

L-ROC

Room Automation

L-WEB

Building Management

Dream Report

L-INX

Automation Servers

Reports designed with LWEB-830 Dream Report are made available as PDF via a
Web portal, sent by e-mail automatically, stored on a server, or simply printed out.
The access to the reports can be restricted to authorized users.

Licensing

I/O Controllers/Modules

Various licenses are available, which differ in the number of processed data points.

L-IOB

Web Portal

E-Mail

File Server

Printer

4. Report Generation and Distribution

Gateways

3. Report Design
2. Data Extraction and Analysis

LWEB-830
Dream Report
1. Data and Alarm Collection

L-VIS

Touch Panels

LWEB-900 Server

Features
Generate meaningful reports
Easy design of report templates

Lighting Control

Report output as PDF file or print

L-DALI

Forwarding via e-mail


Placing on Web portal or stored on file server
Assignment of access rights

Software
Tools

Routers, NIC

Specifications

28

Pre-condition

LWEB900 Building Management Software

Operating system

Windows7, Windows Vista, Windows XP, Windows Server 2003/2008 R2

Order number

Configuration

LWEB-830-DR250

Reporting software for processing real-time data from LWEB900 for 250 data points

LWEB-830-DR2000

Reporting software for processing real-time data from LWEB900 for 2000 data points

LWEB-830-DR10000

Reporting software for processing real-time data from LWEB900 for 10000 data points

LWEB-830-DR50000

Reporting software for processing real-time data from LWEB900 for 50000 data points

www.loytec.com

L-ROC Room Automation

buildings under control

29

LROC-100, LROC-150

LOYTEC

COMPETENCE PARTNER

BACnet
CEA709
KNX

Modbus
M-Bus

The L-ROC Room Controller provides the basis for a revolutionary room automation system based on IP, which seamlessly integrates with native BACnet/IP networks and LonMark Systems at the controller level. Together with the L-STUDIO
software, flexible room solutions can be created with little effort and changed on
demand. Integral parts of the L-ROC System are a Web based room operation via
an LWEB800/802 dashboard and the automatic generation of graphics for the
L-VIS Touch Panel for local operation. For CEA709 room control units, CEA709
multi-sensors and other CEA709 devices can be connected via the LonMark
TP/FT-10 channel on the L-ROC Controller. Local inputs and outputs are provided
via L-IOB I/O Modules. KNX S-mode devices can be connected through KNX TP1 by
using the optional LKNX-300 module.

L-ROC

Room Automation

L-WEB

Building Management

L-ROC Room Controller

Automation Servers

Flexible Room Concept for Room Automation

L-INX

A room segment is the base unit of configuration in the L-ROC System. The L-ROC
Room Controller provides a set of functions for every window axis including:
lighting control including constant light controller

I/O Controllers/Modules

sun blind control with angle adjustment


LIOB

L-IOB

CONNECT

LIOB
FT

LIOB
IP

temperature control for heating, cooling, and ventilation


occupancy detection
window monitoring

Gateways

VNC

y=f(x)

Each LROC-100 Room Controller can handle up to 16 room segments. Building


dependent various room segement types need to be created. Based on the various
room segment types, larger buildings can be modeled in a hierarchical manner.
Areas are built by an area manager by combining multiple room controllers. A floor
manager manages multiple areas in one floor. Depending on the architecture, the
building can be split up into areas and floors as needed.
Area/Floor Managers are responsible for handling functions needed for corridor,
staircase, and bathroom lighting, or even ventilation. Floor managers facilitate the
data communication between the floors and handle floor relevant functions.

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Rooms can now be created arbitrarily in any size by moving, building, or removing
partition walls. The resulting logical connections between the L-ROC Room Controllers will be built automatically. All graphical user interfaces and network connections are automatically generated and adapted respectively.

30

www.loytec.com

AST for Every Room Segment

L-IOB

Connection to Higher-Level Systems

I/O Controllers/Modules

L-ROC controllers provide graphical user interfaces for room operation directly
and without additional Web server via an IP connection to the user. Graphic projects are distributed among the L-ROC Room Controllers and can be accessed by
LWEB-800/802 from any PC workstation, smart phone, or tablet PC running Android
or iOS.

L-INX

Integrated L-WEB Room Operation

Automation Servers

LROC Room Controllers are interconnected in a 100Base-T Ethernet network.


Each L-ROC device is equipped with two Ethernet ports including a built-in Ethernet switch. This allows daisy chaining of up to 20 LOYTEC devices featuring dual
Ethernet in an Ethernet ring. The Ethernet ring is connected with each end to an
Ethernet switch supporting RSTP (Rapid Spanning Tree Protocol). This ensures reliable communication and system availability as well as reduced wiring efforts at the
same time.

L-ROC

Room Communication through redundant IP Network

Room Automation

LROC-100 provides a set of functions for Alarming, Scheduling, and Trending


(AST) for every room segment. Each room segment can be operated entirely independent. The AST functions are fully available to higher-level systems through
BACnet/IP and Web services (L-WEB System). Distributed schedulers can be efficiently managed and changed with LWEB-900.

L-WEB

LROC-100, LROC-150

Building Management

L-ROC Room Controller

Higher-level systems can seamlessly integrate L-ROC Room Controllers via


BACnet/IP, LonMark IP-852, or Web services (OPC XML-DA).
Gateways

All these protocols are simultaneously available. It is possible to integrate the L-ROC
Room Controller in a BACnet Operator Workstation and at the same time LROC
will communicate with other CEA709 devices on the IP-852 channel. Moreover, a
higher-level SCADA or ERP System (Facility Management) gets information directly
from the L-ROC Room Controller by using Web services based on OPC XML-DA.

Full L-WEB Support


L-VIS

Touch Panels

The L-WEB System uses Web services to communicate with the L-ROC System. All
device and operating parameters of every single L-ROC Room Controller are automatically synchronized with the LWEB-900 SQL database by the LWEB-900 client or
the LWEB900 Master Device Manager. The parameters are available to all L-WEB
client applications.

I/O Integration via PlugnPlay


L-DALI

Lighting Control

The LROC Room Controllers can automatically integrate physical I/O by using
L-IOB I/O Modules. Up to 24 L-IOB I/O Modules can be connected through LIOBConnect, LIOB-FT or LIOB-IP. All I/O can be used by the L-ROC application. Moreover
the L-IOB I/Os can be controlled by a standard Web browser via the Web interface of
L-ROC. All configuration of the L-IOB Modules are stored on the L-ROC and loaded
on demand into the L-IOB I/O Modules. Exchanging I/O modules is done without
any configuration effort requiring only two quick configuration steps.

Routers, NIC
Software
Tools

buildings under control

31

LROC-100, LROC-150
L-STUDIO
L-STUDIO is the worlds first IEC61499 based room automation system. Any room
function can be realized with L-STUDIO in a distributed system of L-ROC devices.
This new approach in automation is called Cloud Control.

L-ROC

Room Automation

L-WEB

Building Management

L-ROC Room Controller

Automation Servers

In a cloud of L-ROC devices, arbitrary functions can be mapped automatically.


The object-oriented design method allows the efficient reuse of previously implemented functions. In the graphical development environment of L-STUDIO, the
room segment objects can be built with little effort. Additionally, common areas
can be created and interconnected as floors. The result is complete building control
configuration. Then the entire building application is automatically distributed to
the L-ROC Controllers and each individual configuration is loaded into the devices.

L-IOB

I/O Controllers/Modules

L-INX

Adjustments or new functions can be added to the room segment objects after
initial configuration. These new functions can be applied individually or to all
room segment objects very easily. Comprehensive debugging and watch functions allow for complete building troubleshooting of plant operation. An extensive
library of functions is provided for heating, ventilation, cooling, lighting, sun blind
control, and security. With the integrated graphical configuration tool, graphics for
L-VIS Touch Panels or L-WEB applications can be created.

L-STUDIO
LROC3
LROC

Gateways

>>AxisBusIn

>>AxisBusOut

LROC4
LROC
>>AxisBusIn

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

USB

LROC-150

MICROSD

FT

LIOB-FT

MODBUS

EXT

L-ROC

LINK
ACT

L-ROC
Proxy

Room Controller

PLC OPC

1
FT

Made in Austria

Ethernet 1 Ethernet 2

LOYTEC
www.loytec.com

LIOB-FT

MODBUS

4
EXT

Ethernet
1 2

LROC-150

USB

MICROSD

FT

LIOB-FT

MODBUS

EXT

L-ROC

LINK
ACT

Room Controller

PLC OPC

1
FT

LIOB-FT

MODBUS

4
EXT

Tenant 1

ETHERNET/IP

Ethernet 1 Ethernet 2

L-VIS

Touch Panels

>>AxisBusOut

Tenant 2
01.03.2010 10:35:47

L-WEB
Office PC

5000 lux

15.3C

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

LROC-150

USB

MICROSD

FT

ACT

L-DALI

Lighting Control

L-ROC

Ethernet 1 Ethernet 2

LIOB-FT

MODBUS

EXT

L-ROC

LINK

Room Controller

PLC OPC

L-VIS

10.0 m/s

Rain

1
FT

LIOB-FT

MODBUS

4
EXT

L-WEB
Office PC

15%

65500 lux

Area/Floor/Building
Manager

BACnet, CEA-709, KNX, Modbus, OPC XML-DA, M-Bus, DALI

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

L-ROC

LROC-100

USB

MICROSD

FT

LIOB-FT

EXT1

FUSE 6A

EXT2

ACT

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

EXT1

EXT2

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

status

LIOB-100

status

L-IOB

UI1

UI2 UI3

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

L-IOB

I/O Module

0-10V OUT

DI2 AO1

AO2

Made in Austria

6A

LOYTEC
www.loytec.com

status

I/O Module
UNIVERSAL IN

UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

0-10V OUT

DI2 AO1

Segment
Manager

Ethernet
1 2

Made in Austria

L-ROC

AO2

LOYTEC
www.loytec.com

LROC-100

USB

MICROSD

FT

LIOB-FT

EXT1

FUSE 6A

EXT2

ACT

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

LIOB-FT

EXT1

EXT2

FUSE 6A

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

status

LOYTEC
www.loytec.com

status

LIOB-100

status

L-IOB

L-IOB

I/O Module
UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

I/O Module

0-10V OUT

DI2 AO1

AO2

Made in Austria

6A

status

LIOB-100

Room Controller

1
FT

Made in Austria

6A

LOYTEC
www.loytec.com

L-ROC

LINK

PLC OPC

Ethernet 1 Ethernet 2

UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

0-10V OUT

DI2 AO1

Routers, NIC

2
LIOB-FT

FUSE 6A

status

LIOB-100

Room Controller

1
FT

Made in Austria

6A

LOYTEC
www.loytec.com

L-ROC

LINK

PLC OPC

Ethernet 1 Ethernet 2

Software
Tools

5000 lux

32

www.loytec.com

AO2

Segment
Manager

L-WEB

LROC-100, LROC-150

Building Management

L-ROC Room Controller

Features
Room controller for up to 16 room segments

Connection to KNXnet/IP directly, KNX TP1 via LKNX-300 Interface

L-ROC

Built-in OPC XML-DA server

Networking via redundant IP network

Integrated 100Base-T Ethernet switch

Programmable with L-STUDIO


Integrated AST functions for each room segment
Integrated LWEB-800/802 room control

Room Automation

Flexible built-in management for room segments

Integrated Web server for the device configuration and for


monitoring of data points
128x64 graphic display with backlight

Integrates smoothly in the LWEB-900 System

CEA-709 integration via LonMark IP-852 (Ethernet/IP) channel


Remote Network Interface (RNI) to access the LonMark TP/FT-10
channel

Remote manual operation via VNC client


Extension to physical inputs and outputs with LIOB I/O Modules
(LIOBConnect, LIOBFT, or LIOBIP852)
Configurable via Ethernet/IP or USB

L-INX

Connection of any CEA-709 device via TP/FT-10 channel

Manual operation using the jog dial with LCD display


Automation Servers

BACnet/IP compliant with B-BC (BACnet Building Controller)


functionality

I/O Controllers/Modules

L-IOB

General Specifications
Dimensions (mm)

159x100x75 (LxWxH), DIM005

Power supply

24VDC / 24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Specifications
2xEthernet (100Base-T)
Web-Services (OPC XMLDA),
BACnet/IP,
LonMark IP-852,
LIOB-IP,
KNXnet/IP,
Modbus TCP,
HTTP, FTP
1xTP/FT-10 (LonMark System)
1xLIOBConnect
1xLIOBFT
1xModbus RTU
1xM-Bus (needs LMBUS-20 or LMBUS-80) or
1xKNX TP1 (needs LKNX-300)
2xUSB-A, 1xUSB-B (PC)

LIOB I/O Modules

Up to 24 LIOB I/O Modules in any combination of type LIOBConnect, LIOBFT, and LIOBIP852

Program cycle time

Event-triggered

Programming, tools

LSTUDIO

L-DALI

2xEthernet (100Base-T)
Web-Services (OPC XMLDA),
BACnet/IP,
LIOB-IP,
LonMark IP-852,
KNXnet/IP,
HTTP, FTP
1xTP/FT-10 (LonMark System)
1xLIOBConnect
1xLIOBFT
1xKNX TP1 (needs LKNX-300)
2xUSB-A, 1xUSB-B (PC)

Lighting Control

Interfaces

L-VIS

LROC-150

Touch Panels

LROC-100

Gateways

Type

Resource limits
Trend logs

512 ~ 60 MB

Network Variables (NVs)

2000

E-mail templates

100

Alias NVs

2000

Math objects

100

External NVs (polling)

1000

BACnet server objects

1000

Adress table entries

1000 (non-ECS mode: 15)

BACnet client mappings

1000

LonMark Calendar

1 (25 calendar templates)

BACnet calendar objects

25

LonMark Scheduler

100

BACnet scheduler objects

100

LonMark Alarm Server

BACnet notification classes

32

Alarm logs

10

BACnet trend log objects

512

Number of L-WEB clients

32 (simultaneously)

KNX TP1 data points

1000

KNXnet/IP data points

1000

Connections (Local/Global) 2000 / 250

buildings under control

Software
Tools

10000

Routers, NIC

OPC XMLDA data points

33

L-WEB

Building Management

L-ROC Room Controller

LROC-100, LROC-150
LROC-100

2 x Ethernet / IP
Web
Interface

L-ROC

Room Automation

SWITCH

IP-852

LIOB
IP

BACnet/IP

Alarming
Scheduling
Trending

KNXnet/IP

E-Mail

LIOB
FT

Sum
LROC

>>AxisBusIn

LROC3

IEC 61499
Control

Incr
LROC2

>=

-1

LROC
>>AxisBusIn

Counter

>>AxisBusOut
max

>DINT

L-IOB

I/O Controllers/Modules

Gateways
L-VIS

Touch Panels

L-DALI

Lighting Control

Modbus
TCP

-1
>>AxisBusOut

TP/FT-10

SR

SEL

LROC4

<=

>INT

LROC

>>AxisBusIn
S1
Q1 >>AxisBusOut

>>AxisBusIn

Graphics
Graphics
Graphics

Web
Interface

Alarming
Scheduling
Trending

KNXnet/IP

E-Mail

OPC XML-DA
Server

LIOB

Data Point Abstraction Layer

LROC
>>AxisBusOut

CONNECT

y=f(x)

LIOB
FT

LROC1

Modbus
RTU

M-Bus
KNX TP1

V1.2.4

Sum
LROC

>>AxisBusIn

LROC3

IEC 61499
Control

Incr
LROC2

>=

-1

LROC
>>AxisBusIn

Counter

>>AxisBusOut
max

>DINT

-1
>>AxisBusOut

SR

LROC4

<=

>INT

LROC

>>AxisBusIn
S1
Q1 >>AxisBusOut
SEL

>>AxisBusIn

LROC
>>AxisBusOut

EXT

Order number

Product description

LROC-100

Room Controller with LIOBConnect for room segment management

LROC-150

Room Controller with LIOBConnect for aisle, floor, building or campus management

LROC-START-100

Starter kit: LROC-100, LIOB100, LSTUDIO

LSTUDIO

LROC programming and configuration software

LIOBA2

LIOB Adapter 2 to split the line of LIOB-Connect modules on the DIN rail for space and power considerations

LIOB100

LIOBConnect I/O Module: 8UI, 2DI, 2AO, 9DO (4xTriac plus 5xRelay 6A)

LIOB101

LIOBConnect I/O Module: 8UI, 16DI

LIOB102

LIOBConnect I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB103

LIOBConnect I/O Module: 6 UI, 6 AO, 5 DO (Relay 16A)

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB151

LIOBFT I/O Module: 8UI, 12DI

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB153

LIOBFT I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB154

LIOBFT I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB450

LIOBIP852 I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB451

LIOBIP852 I/O Module: 8UI, 12DI

LIOB452

LIOBIP852 I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB453

LIOBIP852 I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB454

LIOBIP852 I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB550

LIOBBIP I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB551

LIOBBIP I/O Module: 8UI, 12DI

LIOB552

LIOBBIP I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB553

LIOBBIP I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB554

LIOBBIP I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LMBUS20

M-Bus level converter for 20 M-Bus devices

LMBUS80

M-Bus level converter for 80 M-Bus devices

LKNX-300

KNX interface to connect KNXTP1 devices

Software
Tools

34

BACnet/IP

RNI

EXT1

Routers, NIC

LIOB
IP

CONNECT

LROC1

KNX TP1

IP-852

LIOB
y=f(x)

L-INX

Automation Servers

TP/FT-10

2 x Ethernet / IP
SWITCH

OPC XML-DA
Server

Data Point Abstraction Layer


RNI

LROC-150

Graphics
Graphics
Graphics

www.loytec.com

V1.2.3

L-INX Automation Servers

buildings under control

35

LINX150, LINX151

LOYTEC

COMPETENCE PARTNER

Modbus
M-Bus

The L-INX Automation Servers LINX-150 and LINX-151 are powerful, programmable automation stations. They can host user specific graphical pages and can
integrate physical I/O through L-IOB I/O Modules via LIOB-Connect, LIOB-FT, or
LIOB-IP. Local operation and override is provided by the built-in jog dial and the
backlit display (128x64 pixels). Device and data point information is shown on the
display by symbols and in text format.

L-IOB

LIOB

LIOB
FT

Gateways

I/O Controllers/Modules

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

BACnet
CEA709
KNX

L-INX Automation Server

VNC

RNI

CONNECT

y=f(x)

&
CEA-709

Touch Panels

LIOB
IP

BACnet

The powerful Automation Servers provide connectivity functions to concurrently


integrate CEA-709 (LonMark-Systems), BACnet, KNX, Modbus, and M-Bus subsystems. LonMark Systems can be integrated via IP-852 (Ethernet/IP) or TP/FT-10.
BACnet integration is supported through BACnet/IP (Ethernet/IP) or BACnet MS/
TP (RS-485). LINX150 Automation Servers feature an integrated Remote Network Interface (RNI) to access the TP/FT-10 channel on the device via Ethernet/IP.
LINX- 151 Automation Servers feature two built-in routers, one IP-852 router and
one BACnet/IP to MS/TP router including BBMD as well as Slave-Proxy functionality providing the complete feature set of the corresponding L-IP devices. Both
LINX150 and LINX151 implement the BACnet Building Controller (B-BC) profile
and are BTL tested and WSPcert certified. In addition, the L-INX Automation Servers provide connectivity to KNXnet/IP and Modbus TCP via Ethernet/IP and to
Modbus RTU via RS-485. M-Bus and KNX TP1 device integration needs optional
interface modules.
The gateway functionality allows data communication between all communication technologies available on the device. Different technology data points are
mapped through Local Connections on the device. The mapping of different technology data points on distributed devices is supported by Global Connections.
L-INX Automation Servers also support Smart Auto-Connect - the automatic
generation of connections to substantially reduce engineering efforts and cost.
All technology data points are automatically created as OPC XML-DA data points.
Each L-INX Automation Server is equipped with two Ethernet ports including a
built-in Ethernet switch. This allows daisy chaining of up to 20 LOYTEC devices
featuring dual Ethernet in an Ethernet ring. The Ethernet ring is connected with
each end to an Ethernet switch supporting RSTP (Rapid Spanning Tree Protocol).
This ensures reliable communication and system availability with reduced wiring
efforts.

L-VIS

The L-INX devices provide fully featured AST functionality and integrate perfectly into the L-WEB System.

Lighting Control

Features
Visualization of customized graphical pages through LWEB900
(Building Management), LWEB800 (Monitoring and Control), or
LWEB802 (Web Browser)
Built-in OPC XML-DA server
Access to network statistics
Compliant with ANSI/ASHRAE1352008 and ISO164845 standard
Supports BACnet MS/TP or BACnet/IP
BACnet Client Function (Write Property, Read Property, COV
Subscription)
BACnet Client Configuration with configuration tool (scan and
EDE import)
B-BC (BACnet Building Controller) functionality, BTL certified

Software
Tools

Routers, NIC

L-DALI

IEC61131-3 programmable with L-LOGICAD


Physical inputs and outputs with L-IOB I/O Modules (LIOBConnect, LIOBFT, and LIOBIP852)
128x64 graphic display with backlight
Local and remote access to information about device status and
data points
Manual operation using the jog dial or VNC client
Memory expansion with microSD card
Alarming, Scheduling, and Trending (AST)
Event-driven e-mail notification
Math objects to execute mathematical operations on data
points
Stores customized graphical pages

36

www.loytec.com

LINX-151

L-INX

Automation Servers

LINX-150

L-ROC

Integrated IP852 to TP/FT10 Router (LINX151 only)


KNXnet/IP, connection to KNX TP1 through LKNX-300 Interface
M-Bus Master according to EN13757-3, connection via optional
MBus Converter (e.g. LMBUS80)
Gateway functions including Smart Auto-Connect
Modbus TCP and Modbus RTU (Master or Slave)
Integrated web server for the device configuration and for
monitoring of data points
Configurable via Ethernet/IP, USB, or TP/FT10

Room Automation

Compliant with CEA709, CEA852 and ISO/IEC14908 Standard


(LonMark System)
Supports TP/FT-10 or IP-852 (Ethernet/IP)
Support of dynamically created or static NVs
Support of user-defined NVs (UNVTs) and Configuration Properties (SCPTs, UCPTs)
Remote Network Interface (RNI) with 2 MNI devices (LINX150
only)
Integrated BACnet/IP to BACnet MS/TP Router including BBMD
as well as Slave-Proxy functionality (LINX151 only)

L-WEB

LINX150, LINX151

Building Management

L-INX Automation Server

L-IOB

I/O Controllers/Modules

Gateways
L-VIS

Touch Panels

Modbus
TCP

Alarming
Scheduling
Trending

KNXnet/IP

E-Mail

TP/FT-10

CONNECT

y=f(x)

LIOB
FT

IP-852

>INT

BACnet
MS/TP

Modbus
RTU

M-Bus
KNX TP1

Sum

>DINT

max
Incr

IEC 61131-3
Program
>=

S1
Q1
SR
R

TP/FT-10

SEL

<=

-1

EXT

Counter

-1

LIOB
IP

BACnet/IP

LIOB
FT

Modbus
TCP

Alarming
Scheduling
Trending

KNXnet/IP

E-Mail

OPC XML-DA
Server

Routers, NIC

LIOB

Data Point Abstraction Layer


RNI

OPC XML-DA
Server

ROUTER

BACnet/IP

Graphics
Graphics
Graphics

Web
Interface

SWITCH

ROUTER

LIOB
IP

2 x Ethernet / IP

L-DALI

Web
Interface

SWITCH

IP-852

Graphics
Graphics
Graphics

Lighting Control

2 x Ethernet / IP

LIOB

Data Point Abstraction Layer

CONNECT

y=f(x)

>INT

BACnet
MS/TP

V1.2.2

Modbus
RTU

M-Bus
KNX TP1

Sum

>DINT

max
Incr

IEC 61131-3
Program
>=

S1
Q1
SR
R

SEL

<=

-1

EXT

Counter

-1

V1.2.2

Software
Tools

buildings under control

37

LINX150, LINX151
Specifications
Dimensions (mm)

159x100x75 (LxWxH), DIM005

Power supply

24 VDC / 24 VAC 10%, typ. 2.5W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

2xEthernet (100Base-T)
OPC XMLDA
BACnet/IP**
LIOBIP
KNXnet/IP
LonMark IP-852*
Modbus TCP (Master or Slave)
HTTP, FTP, SSH, HTTPS, Firewall
1x LIOBFT*

1xLIOBConnect
1xTP/FT-10* (LonMark System)
1xBACnet MS/TP**
1xModbus RTU (Master or Slave)
1xM-Bus, Master EN13757-3 (needs LMBUS20 or
LMBUS80) or
1xKNX TP1 (needs LKNX-300)
2xUSB-A, 1xUSB-B (PC)

*LonMark IP-852 or TP/FT-10


(LINX150 only)

** BACnet IP or BACnet MS/TP


(LINX150 only)

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

L-INX Automation Server

LIOB I/O Modules

Up to 24 LIOB I/O Modules in any combination of type LIOBConnect, LIOBFT, and LIOBIP852

Remote Network Interface

1 RNI with 2 MNI devices (LINX150 only)

BACnet/IP Router

1 (LINX151 only)

CEA709 Router

1 (LINX151 only)

Program cycle time

Down to 10ms

Programming, Tools

LLOGICAD software (IEC611313), LINX/L-GATE Configurator

OPC XMLDA data points

10000

LonMark Calendar

1 (25 calendar templates)

BACnet objects

1000 (analog, binary, multi-state)

LonMark Scheduler

100

BACnet client mappings

1000

LonMark Alarm Server

BACnet calendar objects

25

E-mail templates

100

BACnet scheduler objects

100 (64 data points per object)

Math objects

100

BACnet notification classes

32

Alarm logs

10

Trend logs (BACnet or generically)

512 (4 000000 logs, 60MB)

M-Bus data points

1000

Total trended data points

512

Modbus data points

2000

CEA709 network variables (NVs)

2000

KNX TP1 data points

1000

CEA709 Alias NVs

2000

KNXnet/IP data points

1000

CEA709 External NVs (polling)

1000

Connections (Local / Global)

2000 / 250

CEA709 address table entries

1000 (non-ECS mode: 15)

Number of L-WEB clients

32 (simultaneously)

L-IOB I/O Modules

24

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

Resource limits

38

www.loytec.com

L-WEB

LINX150, LINX151

Building Management

L-INX Automation Server

L-ROC

Room Automation

L-INX

Automation Servers

IEC 61131-3 programming tool, single license, includes USB dongle

LIOBA2

LIOB Adapter 2 to split the line of LIOBConnect modules on the DINrail for space and power considerations

LIOB100

LIOBConnect I/O Module: 8UI, 2DI, 2AO, 9DO (4xTriac 1A, 5xRelay 6A)

LIOB101

LIOBConnect I/O Module: 8UI, 16DI

LIOB102

LIOBConnect I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB103

LIOBConnect I/O Module: 6 UI, 6 AO, 5 DO (Relay 16A)

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB151

LIOBFT I/O Module: 8UI, 12DI

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB153

LIOBFT I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB154

LIOBFT I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB450

LIOBIP852 I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB451

LIOBIP852 I/O Module: 8UI, 12DI

LIOB452

LIOBIP852 I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB453

LIOBIP852 I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB454

LIOBIP852 I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB550

LIOBBIP I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB551

LIOBBIP I/O Module: 8UI, 12DI

LIOB552

LIOBBIP I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB553

LIOBBIP I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB554

LIOBBIP I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LOPC-BR800

OPC Bridge (PC software) to connect OPC DA clients (COM/DCOM) with LINX Automation Servers

LMBUS20

M-Bus level converter for 20 M-Bus devices

LMBUS80

M-Bus level converter for 80 M-Bus devices

LKNX-300

KNX interface to connect KNXTP1 devices

Routers, NIC

L-LOGICAD

L-DALI

Starter kit: LINX150, LIOB100, LIOB102, and LLOGICAD software license

Lighting Control

BACnet & CEA709 Automation Server with LIOBConnect and built-in BACnet/IP & IP-852 Router

LINXSTART-150

L-VIS

LINX151

Touch Panels

BACnet & CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

Gateways

LINX150

L-IOB

Product description
I/O Controllers/Modules

Order number

Software
Tools

buildings under control

39

LOYTEC

LINX120, LINX121

COMPETENCE PARTNER

Modbus
M-Bus

The L-INX Automation Servers LINX-120 and LINX-121 are powerful, programmable automation stations. They can host user specific graphical pages and can
integrate physical I/O through L-IOB I/O Modules via LIOB-Connect, LIOB-FT, or
LIOB-IP. Local operation and override is provided by the built-in jog dial and the
backlit display (128x64 pixels). Device and data point information is shown on
the display by symbols and in text format.

L-ROC

Room Automation

L-WEB

Building Management

BACnet
CEA709
KNX

L-INX Automation Server

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

The powerful Automation Servers provide connectivity functions to concurrently


integrate CEA-709 (LonMark-Systems), KNX, Modbus, and M-Bus subsystems.
LonMark Systems can be integrated via IP-852 (Ethernet/IP) or TP/FT-10. LINX120
Automation Servers feature an integrated Remote Network Interface (RNI) to
access the TP/FT-10 channel on the device via Ethernet/IP. LINX-121 Automation
Servers provide a built-in IP-852 router providing the complete feature set of the
corresponding L-IP devices. In addition, the L-INX Automation Servers provide
connectivity to KNXnet/IP and Modbus TCP via Ethernet/IP and to Modbus RTU
via RS-485. M-Bus and KNX TP1 device integration needs optional interface modules.

LIOB
CONNECT

LIOB
FT

LIOB
IP

Gateways

&

VNC

RNI

y=f(x)
CEA-709

The gateway functionality allows data communication between all communication technologies available on the device. Different technology data points are
mapped through Local Connections on the device. The mapping of different
technology data points on distributed devices is supported by Global Connections. L-INX Automation Servers also support Smart Auto-Connect the automatic generation of connections to substantially reduce engineering efforts and
cost. All technology data points are automatically created as OPC XML-DA data
points.
Each L-INX Automation Server is equipped with two Ethernet ports including a
built-in Ethernet switch. This allows daisy chaining of up to 20 LOYTEC devices
featuring dual Ethernet in an Ethernet ring. The Ethernet ring is connected with
each end to an Ethernet switch supporting RSTP (Rapid Spanning Tree Protocol).
This ensures reliable communication and system availability with reduced wiring
efforts.

L-VIS

Touch Panels

The L-INX devices provide fully featured AST functionality and integrate perfectly into the L-WEB System.

Features
IEC61131-3 programmable with L-LOGICAD

L-DALI

Lighting Control

Physical inputs and outputs with L-IOB I/O Modules (LIOBConnect, LIOBFT, and LIOBIP852)

Supports TP/FT-10 or IP-852 (Ethernet/IP)

128x64 graphic display with backlight

Support of dynamically created or static NVs

Local and remote access to information about device status


and data points

Support of user-defined NVs (UNVTs) and Configuration Properties (SCPTs, UCPTs)

Manual operation using the jog dial or VNC client

Remote Network Interface (RNI) with 2 MNI devices (LINX120


only)

Memory expansion with microSD card

Integrated IP852 to TP/FT10 Router (LINX121 only)

Alarming, Scheduling, and Trending (AST)

KNXnet/IP, connection to KNX TP1 through LKNX-300 Interface

Event-driven e-mail notification

Routers, NIC

Compliant with CEA709, CEA852 and ISO/IEC14908 Standard


(LonMark System)

Math objects to execute mathematical operations on data


points

M-Bus Master according to EN13757-3, connection via optional


MBus Converter (e.g. LMBUS80)

Stores customized graphical pages

Modbus TCP and Modbus RTU (Master or Slave)

Visualization of customized graphical pages through LWEB900


(building Management), LWEB800 (Monitoring and Control),
or LWEB802 (Web Browser)

Gateway functions including Smart Auto-Connect


Integrated Web server for the device configuration and for
monitoring of data points

Built-in OPC XML-DA server

Configurable via Ethernet/IP, USB, or TP/FT10

Software
Tools

Access to network statistics

40

www.loytec.com

IP-852

LIOB
IP

Modbus
TCP

Alarming
Scheduling
Trending

KNXnet/IP

E-Mail

y=f(x)

LIOB
FT

>INT

Modbus
RTU

M-Bus
KNX TP1

Sum

>DINT

max
Incr

IEC 61131-3
Program

Counter

>=

-1

S1
Q1
SR
R

TP/FT-10

SEL

<=

-1

EXT

LIOB
IP

Modbus
TCP

Alarming
Scheduling
Trending

KNXnet/IP

E-Mail

OPC XML-DA
Server

LIOB

Data Point Abstraction Layer

CONNECT

L-INX

TP/FT-10

CONNECT

IP-852

Graphics
Graphics
Graphics

Web
Interface

Automation Servers

RNI

OPC XML-DA
Server

LIOB

Data Point Abstraction Layer

2 x Ethernet / IP
SWITCH

ROUTER

Web
Interface

SWITCH

LINX-121

Graphics
Graphics
Graphics

L-ROC

2 x Ethernet / IP

Room Automation

LINX-120

y=f(x)

LIOB
FT

>INT

Modbus
RTU

M-Bus
KNX TP1

Sum

>DINT

max
Incr

IEC 61131-3
Program

Counter

>=

-1

S1
Q1
SR
R

SEL

<=

-1

EXT

V1.2.2

L-WEB

LINX120, LINX121

Building Management

L-INX Automation Server

V1.2.2

L-IOB

I/O Controllers/Modules

Specifications
159x100x75 (LxWxH), DIM005

Power supply

24 VDC / 24 VAC 10%, typ. 2.5W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

2xEthernet (100Base-T)
OPC XMLDA
LIOBIP
KNXnet/IP
LonMark IP-852*
Modbus TCP (Master or Slave)
HTTP, FTP, SSH, HTTPS, Firewall
1xTP/FT-10 *(LonMark System)

Gateways

Dimensions (mm)

L-VIS

Touch Panels

1xLIOBConnect
1xLIOBFT
1xModbus RTU (Master or Slave)
1xM-Bus, Master EN13757-3 (needs LMBUS20 or
LMBUS80) or
1xKNX TP1 (needs LKNX-300)
2xUSB-A, 1xUSB-B (PC)

*LonMark IP-852 or TP/FT-10 (LINX120 only)


Up to 24 LIOB I/O Modules in any combination of type LIOBConnect, LIOBFT, and LIOBIP852

Remote Network Interface

1 RNI with 2 MNI devices (LINX120 only)

CEA709 Router

1 (LINX121 only)

Program cycle time

Down to 10ms

Programming, Tools

LLOGICAD software (IEC611313), LINX/L-GATE Configurator

L-DALI

Lighting Control

LIOB I/O Modules

Resource limits
E-mail templates

100

Network variables (NVs)

2000

Math objects

100

Alias NVs

2000

Alarm logs

10

External NVs (polling)

1000

M-Bus data points

1000

Address table entries

1000 (non-ECS mode: 15)

Modbus data points

2000

LonMark Calendar

1 (25 calendar templates)

KNX TP1 data points

1000

LonMark Scheduler

100

KNXnet/IP data points

1000

LonMark Alarm Server

Connections (Local / Global)

2000 / 250

Trend logs

512 (4 000000 logs, 60MB)

Number of L-WEB clients

32 (simultaneously)

Total trended data points

512

L-IOB I/O Modules

24

buildings under control

Software
Tools

10000

Routers, NIC

OPC XMLDA data points

41

LINX120, LINX121

Order number

Product description

LINX120

CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

LINX121

CEA709 Automation Server with LIOBConnect and built-in IP-852 Router

LINXSTART-120

Starter kit: LINX120, LIOB100, LIOB102, and LLOGICAD software license

L-LOGICAD

IEC 61131-3 programming tool, single license, includes USB dongle

LIOBA2

LIOB Adapter 2 to split the line of LIOBConnect modules on the DINrail for space and power considerations

LIOB100

LIOBConnect I/O Module: 8UI, 2DI, 2AO, 9DO (4xTriac plus 5xRelay 6A)

LIOB101

LIOBConnect I/O Module: 8UI, 16DI

LIOB102

LIOBConnect I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB103

LIOBConnect I/O Module: 6 UI, 6 AO, 5 DO (Relay 16A)

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB151

LIOBFT I/O Module: 8UI, 12DI

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB153

LIOBFT I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB154

LIOBFT I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB450

LIOBIP852 I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB451

LIOBIP852 I/O Module: 8UI, 12DI

LIOB452

LIOBIP852 I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB453

LIOBIP852 I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB454

LIOBIP852 I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LOPC-BR800

OPC Bridge (PC software) to connect OPC DA clients (COM/DCOM) with LINX Automation Servers

LMBUS20

M-Bus level converter for 20 M-Bus devices

LMBUS80

M-Bus level converter for 80 M-Bus devices

LKNX-300

KNX interface to connect KNXTP1 devices

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

L-INX Automation Server

42

www.loytec.com

L-INX Automation Server

LOYTEC

LINX220, LINX221

COMPETENCE PARTNER

y=f(x)

BACnet

The L-INX devices provide fully featured


AST functionality and integrate perfectly into the L-WEB System.

L-VIS

Touch Panels

Features
IEC61131-3 programmable with L-LOGICAD

Local and remote access to information about device status


and data points
Manual operation using the jog dial or VNC client
Memory expansion with microSD card

BACnet Client Function (Write Property, Read Property, COV


Subscription)
BACnet Client Configuration with configuration tool (scan and
EDE import)
B-BC (BACnet Building Controller) functionality, BTL certified
Integrated BACnet/IP to BACnet MS/TP Router including BBMD
as well as Slave-Proxy functionality (LINX221 only)

Alarming, Scheduling, and Trending (AST)


Math objects to execute mathematical operations on data
points
Stores customized graphical pages
Visualization of customized graphical pages through LWEB900
(Building Management), LWEB800 (Monitoring and Control),
or LWEB802 (Web Browser)

KNXnet/IP, connection to KNX TP1 through LKNX-300 Interface


M-Bus Master according to EN13757-3, connection via optional
MBus Converter (e.g. LMBUS80)
Modbus TCP and Modbus RTU (Master or Slave)

Routers, NIC

Event-driven e-mail notification

Gateway functions including Smart Auto-Connect


Integrated Web server for the device configuration and for
monitoring of data points
Configurable via Ethernet/IP, or USB

buildings under control

Software
Tools

Access to network statistics

Supports BACnet MS/TP or BACnet/IP

L-DALI

128x64 graphic display with backlight

Compliant with ANSI/ASHRAE1352008 and ISO164845 standard


Lighting Control

Physical inputs and outputs with L-IOB I/O Modules (LIOBConnect, LIOBFT, and LIOBIP852)

Built-in OPC XML-DA server

Gateways

VNC

Each L-INX Automation Server is equipped with two Ethernet ports including a
built-in Ethernet switch. This allows daisy chaining of up to 20 LINX devices in an
Ethernet ring. The Ethernet ring is connected with each end to an Ethernet switch
supporting RSTP (Rapid Spanning Tree Protocol). This ensures reliable communication and system availability with reduced wiring efforts.

L-IOB

&

LIOB
IP

I/O Controllers/Modules

LIOB
FT

L-INX

CONNECT

Automation Servers

LIOB

The gateway functionality allows data communication between all communication technologies available on the device. Different technology data points are
mapped through Local Connections on the device. The mapping of different
technology data points on distributed devices is supported by Global Connections. L-INX Automation Servers also support Smart Auto-Connect the automatic generation of connections to substantially reduce engineering efforts and
cost. All technology data points are automatically created as OPC XML-DA data
points.

L-ROC

The powerful Automation Servers provide connectivity functions to concurrently


integrate BACnet, KNX, Modbus, and M-Bus subsystems. BACnet integration is
supported through BACnet/IP (Ethernet/IP) or BACnet MS/TP (RS-485). LINX221
Automation Servers feature a built-in BACnet/IP to MS/TP router including BBMD
as well as Slave-Proxy functionality providing the complete feature set of the
corresponding L-IP device. Both LINX220 and LINX221 implement the BACnet
Building Controller (B-BC) profile and are BTL tested and WSPcert certified. In
addition, the L-INX Automation Servers provide connectivity to KNXnet/IP and
Modbus TCP via Ethernet/IP and to Modbus RTU via RS-485. M-Bus and KNX TP1
device integration needs optional interface modules.

Room Automation

The L-INX Automation Servers LINX-220 and LINX-221 are powerful, programmable automation stations. They can host user specific graphical pages and can
integrate physical I/O through L-IOB I/O Modules via LIOB-Connect, LIOB-FT, or
LIOB-IP. Local operation and override is provided by the built-in jog dial and the
backlit display (128x64 pixels). Device and data point information is shown on the
display by symbols and in text format.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709
KNX

43

LINX220, LINX221

Room Automation

LINX-220

2 x Ethernet / IP
Web
Interface

L-ROC

SWITCH

BACnet/IP

LIOB
IP

Modbus
TCP

Alarming
Scheduling
Trending

KNXnet/IP

LINX-221

Graphics
Graphics
Graphics

E-Mail

OPC XML-DA
Server

LIOB

Data Point Abstraction Layer

CONNECT

Automation Servers

y=f(x)

L-INX

BACnet
MS/TP

LIOB
FT

M-Bus
KNX TP1

Sum

>DINT

max
Incr

IEC 61131-3
Program
>=

-1

L-IOB

BACnet
MS/TP

Counter

S1
Q1
SR
R

SEL

<=

-1

EXT

I/O Controllers/Modules

BACnet/IP

>INT

Modbus
RTU

2 x Ethernet / IP

LIOB
IP

Modbus
TCP

Graphics
Graphics
Graphics

Web
Interface

SWITCH

Alarming
Scheduling
Trending

KNXnet/IP

E-Mail

OPC XML-DA
Server

LIOB

Data Point Abstraction Layer

ROUTER

L-WEB

Building Management

L-INX Automation Server

CONNECT

y=f(x)

LIOB
FT

>INT

Modbus
RTU

M-Bus
KNX TP1

Sum

>DINT

max
Incr

IEC 61131-3
Program

Counter

>=

-1

S1
Q1
SR
R

SEL

<=

-1

EXT

V1.2.2

V1.2.2

Specifications
159x100x75 (LxWxH), DIM005

Power supply

24VDC / 24VAC 10%, typ. 2.5W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

2xEthernet (100Base-T)
OPC XMLDA
BACnet/IP*
LIOBIP
KNXnet/IP
Modbus TCP (Master or Slave),
HTTP, FTP, SSH, HTTPS, Firewall

LIOB I/O Modules

Up to 24 LIOB I/O Modules in any combination of type LIOBConnect, LIOBFT, and LIOBIP852

BACnet/IP Router

1 (LINX221 only)

Program cycle time

Down to 10ms

Programming, Tools

LLOGICAD software (IEC611313), LINX/L-GATE Configurator

Gateways

Dimensions (mm)

1xLIOBConnect
1xLIOBFT
1xBACnet MS/TP*
1xModbus RTU (Master or Slave)
1xM-Bus (Master EN13757-3) or
1xKNX TP1 (needs LKNX-300)
2xUSB-A, 1xUSB-B (PC)

L-VIS

Touch Panels

* BACnet IP or BACnet MS/TP (LINX220 only)

OPC XMLDA data points

10 000

Math objects

100

BACnet objects

1 000 (analog, binary, multi-state)

Alarm logs

10

BACnet client mappings

1 000

M-Bus data points

1000

BACnet calendar objects

25

Modbus data points

2000

BACnet scheduler objects

100 (64 data points per object)

KNX TP1 data points

1000

BACnet notification classes

32

KNXnet/IP data points

1000

Trend logs (BACnet or generically)

512 (4 000 000 logs, 60 MB)

Connections (Local / Global)

2000 / 250

Total trended data points

512

Number of L-WEB clients

32 (simultaneously)

E-mail templates

100

L-IOB I/O Modules

24

Software
Tools

Routers, NIC

L-DALI

Lighting Control

Resource limits

44

www.loytec.com

L-WEB

LINX220, LINX221

Building Management

L-INX Automation Server

L-ROC

Room Automation

L-INX

Automation Servers

IEC 61131-3 programming tool, single license, includes USB dongle

LIOBA2

LIOB Adapter 2 to split the line of LIOBConnect modules on the DINrail for space and power considerations

LIOB100

LIOBConnect I/O Module: 8UI, 2DI, 2AO, 9DO (4xTriac plus 5xRelay 6A)

LIOB101

LIOBConnect I/O Module: 8UI, 16DI

LIOB102

LIOBConnect I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB103

LIOBConnect I/O Module: 6 UI, 6 AO, 5 DO (Relay 16A)

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB151

LIOBFT I/O Module: 8UI, 12DI

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB153

LIOBFT I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB154

LIOBFT I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB550

LIOBBIP I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB551

LIOBBIP I/O Module: 8UI, 12DI

LIOB552

LIOBBIP I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB553

LIOBBIP I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB554

LIOBBIP I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LOPC-BR800

OPC Bridge (PC software) to connect OPC DA clients (COM/DCOM) with LINX Automation Servers

LMBUS20

M-Bus level converter for 20 M-Bus devices

LMBUS80

M-Bus level converter for 80 M-Bus devices

LKNX-300

KNX interface to connect KNXTP1 devices

Routers, NIC

L-LOGICAD

L-DALI

Starter kit: LINX220, LIOB100, LIOB102, and LLOGICAD software license

Lighting Control

LINXSTART-220

L-VIS

BACnet Automation Server with LIOBConnect, B-BC, and built-in BACnet/IP to MS/TP Router

Touch Panels

BACnet Automation Server with LIOBConnect, B-BC

LINX221

Gateways

LINX220

L-IOB

Product description

I/O Controllers/Modules

Order number

Software
Tools

buildings under control

45

LOYTEC

LINX110, LINX111

COMPETENCE PARTNER

Modbus
M-Bus

The L-INX Automation Servers LINX-110 and LINX-111 are programmable automation stations. They can host user specific graphical pages and can integrate physical I/O through L-IOB I/O Modules via LIOB-FT or LIOB-IP.

Room Automation

L-WEB

Building Management

BACnet
CEA709
KNX

L-INX Automation Server

L-INX

Automation Servers

L-ROC

The Automation Servers provide connectivity functions to concurrently integrate


CEA-709 (LonMark-Systems), Modbus, and M-Bus subsystems. LonMark Systems
can be integrated via IP-852 (Ethernet/IP) or TP/FT-10. LINX110 Automation Servers feature an integrated Remote Network Interface (RNI) to access the TP/FT-10
channel on the device via Ethernet/IP. LINX-111 Automation Servers feature a
built-in IP-852 router providing the complete feature set of the corresponding L-IP
devices. In addition, the L-INX Automation Servers provide connectivity to Modbus TCP via Ethernet/IP and to Modbus RTU via RS-485. M-Bus device integration
needs an optional interface module.

I/O Controllers/Modules

LIOB
FT

LIOB
IP

The gateway functionality allows data communication between all communication technologies available on the device. Different technology data points are
mapped through Local Connections on the device. The mapping of different technology data points on distributed devices is supported by Global Connections.
L-INX Automation Servers also support Smart Auto-Connect - the automatic
generation of connections to substantially reduce engineering efforts and cost.
All technology data points are automatically created as OPC XML-DA data points.

CEA-709

L-IOB

The L-INX devices provide fully featured AST functionality and integrate perfectly
into the L-WEB System.
&

Gateways

RNI

y=f(x)

LINX-110
L-VIS

Touch Panels

Ethernet / IP

IP-852

LIOB
IP

Web
Interface

Alarming
Scheduling
Trending

Modbus
TCP

LINX-111

Graphics
Graphics
Graphics

E-Mail

Ethernet / IP

OPC XML-DA
Server

y=f(x)

L-DALI

Lighting Control

RNI

TP/FT-10

LIOB
FT

>INT

Modbus
RTU

Sum

M-Bus

>DINT

max
Incr

IEC 61131-3
Program

Counter

>=

-1

S1
Q1
SR
R

TP/FT-10

SEL

<=

-1

Software
Tools

Routers, NIC

V1.2.2

46

LIOB
IP

www.loytec.com

Alarming
Scheduling
Trending

Modbus
TCP

E-Mail

OPC XML-DA
Server

Data Point Abstraction Layer

ROUTER

Data Point Abstraction Layer

IP-852

Graphics
Graphics
Graphics

Web
Interface

y=f(x)

LIOB
FT

>INT

Modbus
RTU

Sum

M-Bus

>DINT

max
Incr

IEC 61131-3
Program

Counter

>=

-1

S1
Q1
SR
R

SEL

<=

-1

V1.2.2

L-WEB

LINX110, LINX111

Building Management

L-INX Automation Server

Features
Support of dynamically created or static NVs

Alarming, Scheduling, and Trending (AST)


Event-driven e-mail notification
Math objects to execute mathematical operations on data
points

Built-in OPC XML-DA server

Integrated IP852 to TP/FT10 Router (LINX111 only)


M-Bus Master according to EN13757-3, connection via optional
MBus Converter (e.g. LMBUS80)

L-INX

Visualization of customized graphical pages through LWEB900


(Building Management), LWEB800 (Monitoring and Control), or
LWEB802 (Web Browser)

Remote Network Interface (RNI) with 2 MNI devices (LINX110


only)

Modbus TCP and Modbus RTU (Master or Slave)


Gateway functions including Smart Auto-Connect
Integrated Web server for the device configuration and for
monitoring of data points

Access to network statistics

Configurable via Ethernet/IP or TP/FT10

L-IOB

I/O Controllers/Modules

Compliant with CEA709, CEA852 and ISO/IEC14908 Standard


(LonMark System)

Automation Servers

Stores customized graphical pages

Support of user-defined NVs (UNVTs) and Configuration Properties (SCPTs, UCPTs)

L-ROC

Supports TP/FT-10 or IP-852 (Ethernet/IP)

Extension to physical inputs and outputs with LIOB I/O Modules


(LIOBFT or LIOBIP852)

Room Automation

IEC61131-3 programmable with L-LOGICAD

Specifications
Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
OPC XMLDA
LIOBIP
LonMark IP-852*
Modbus TCP (Master or Slave)
HTTP, FTP
1xTP/FT-10* (LonMark System) along with terminal LIOBFT
1xLIOBFT
1xModbus RTU (Master or Slave)
1xM-Bus (Master EN13757-3)
1xEIA-232 (RS-232)

L-VIS

Touch Panels

107x100x60 (LxWxH), DIM009

Gateways

Dimensions (mm)

*LonMark IP-852 or TP/FT-10 (LINX110 only)


Up to 8 LIOB I/O Modules in any combination of type LIOBFT and LIOBIP852

Remote Network Interface

1 RNI with 2 MNI devices (LINX110 only)

CEA709 Router

1 (LINX111 only)

Program cycle time

Down to 10ms

Programming, Tools

LLOGICAD software (IEC611313), LINX/L-GATE Configurator

L-DALI

Lighting Control

LIOB I/O Modules

Resource limits
Total trended data points

256

Network variables (NVs)

1000

E-mail templates

100

Alias NVs

1000

Math objects

100

External NVs (polling)

1000

Alarm logs

10

Address table entries

1000 (non-ECS mode: 15)

M-Bus data points

1000

LonMark Calendar

1 (25 calendar templates)

Modbus data points

2000

LonMark Scheduler

100

Connections (Local / Global)

1000 / 250

LonMark Alarm Server

Number of L-WEB clients

15 (simultaneously)

Trend logs

100 (390 000 logs, 6 MB)

L-IOB I/O Modules

8 (LIOB-FT or LIOBIP852)

buildings under control

Software
Tools

500

Routers, NIC

OPC XMLDA data points

47

LINX110, LINX111
Order number

Product description

LINX110

CEA709 Automation Server, IEC 61131-3 programmable, built-in Remote Network Interface (RNI)

LINX111

CEA709 Automation Server, IEC 61131-3 programmable, built-in IP-852 Router

LINXSTART-LC2

Starter kit: LINX100, LINX110, and LLOGICAD license

L-LOGICAD

IEC 61131-3 programming tool, single license, includes USB dongle

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB151

LIOBFT I/O Module: 8UI, 12DI

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB153

LIOBFT I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB154

LIOBFT I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB450

LIOBIP852 I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB451

LIOBIP852 I/O Module: 8UI, 12DI

LIOB452

LIOBIP852 I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB453

LIOBIP852 I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB454

LIOBIP852 I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LOPC-BR800

OPC Bridge (PC software) to connect OPC DA clients (COM/DCOM) with LINX Automation Servers

LMBUS20

M-Bus level converter for 20 M-Bus devices

LMBUS80

M-Bus level converter for 80 M-Bus devices

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

L-INX Automation Server

48

www.loytec.com

L-INX Automation Server

LOYTEC

LINX210, LINX211

COMPETENCE PARTNER

BACnet

&

y=f(x)

Ethernet / IP

Modbus
TCP

LIOB
IP

Alarming
Scheduling
Trending

LINX-211

Graphics
Graphics
Graphics

Web
User Interface

E-Mail

Ethernet / IP

OPC XML-DA
Server

Modbus
RTU

LIOB
FT

>DINT

max
Incr

ROUTER

IEC 61131-3
Program

BACnet
MS/TP

Counter

>=

S1
Q1
SR
R

SEL

-1

<=

-1

Alarming
Scheduling
Trending

E-Mail

OPC XML-DA
Server

Data Point Abstraction Layer


y=f(x)

>INT
Sum

M-Bus

LIOB
IP

L-VIS

y=f(x)

BACnet
MS/TP

Modbus
TCP

Graphics
Graphics
Graphics

Web
Interface

Touch Panels

Data Point Abstraction Layer

BACnet/IP

Gateways

LINX-210

BACnet/IP

L-IOB

The L-INX devices provide fully featured AST functionality and integrate perfectly
into the L-WEB System.

I/O Controllers/Modules

LIOB
IP

L-INX

LIOB
FT

The gateway functionality allows data communication between all communication technologies available on the device. Different technology data points are
mapped through Local Connections on the device. The mapping of different technology data points on distributed devices is supported by Global Connections.
L-INX Automation Servers also support Smart Auto-Connect - the automatic
generation of connections to substantially reduce engineering efforts and cost.
All technology data points are automatically created as OPC XML-DA data points.

Automation Servers

Both LINX210 and LINX211 implement the BACnet Building Controller (B-BC)
profile and are BTL tested and WSPcert certified. In addition, the L-INX Automation
Servers provide connectivity to Modbus TCP via Ethernet/IP and to Modbus RTU
via RS-485. M-Bus device integration needs an optional interface module.

L-ROC

The Automation Servers provide connectivity functions to concurrently integrate


BACnet, Modbus, and M-Bus subsystems. BACnet integration is supported through
BACnet/IP (Ethernet/IP) or BACnet MS/TP (RS-485). LINX211 Automation Servers
feature a built-in BACnet/IP to MS/TP router including BBMD as well as Slave-Proxy
functionality providing the complete feature set of the corresponding L-IP device.

Room Automation

The L-INX Automation Servers LINX-210 and LINX-211 are programmable automation stations. They can host user specific graphical pages and can integrate physical I/O through L-IOB I/O Modules via LIOB-FT or LIOB-IP.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709

KNX

Modbus
RTU

LIOB
FT

>INT
Sum

M-Bus

>DINT

max
Incr

IEC 61131-3
Program
>=

S1
Q1
SR
R

SEL

<=

-1

V1.2.2

L-DALI

Lighting Control

V1.2.2

Counter

-1

Features
Built-in OPC XML-DA server

Extension to physical inputs and outputs with LIOB I/O Modules


(LIOBFT or LIOBIP852)

Access to network statistics


Compliant with ANSI/ASHRAE1352008 and ISO164845 standard

Event-driven e-mail notification

Supports BACnet MS/TP or BACnet/IP

Math objects to execute mathematical operations on data


points

BACnet Client Function (Write Property, Read Property, COV


Subscription)

Stores customized graphical pages

BACnet Client Configuration with configuration tool (scan and


EDE import)

Visualization of customized graphical pages through LWEB900


(Building Management), LWEB800 (Monitoring and Control), or
LWEB802 (Web Browser)

B-BC (BACnet Building Controller) functionality, BTL certified

buildings under control

49

Software
Tools

Alarming, Scheduling, and Trending (AST)

Routers, NIC

IEC61131-3 programmable with L-LOGICAD

LINX210, LINX211
Integrated BACnet/IP to BACnet MS/TP Router including BBMD
as well as Slave-Proxy functionality (LINX211 only)
M-Bus Master according to EN13757-3, connection via optional
MBus Converter (e.g. LMBUS80)

L-ROC

Room Automation

L-WEB

Building Management

BACnet
CEA709

KNX

L-INX Automation Server

Modbus TCP and Modbus RTU (Master or Slave)

Modbus
M-Bus

Gateway functions including Smart Auto-Connect


Integrated Web server for the device configuration and for
monitoring of data points
Configurable via Ethernet/IP

Dimensions (mm)

107x100x60 (LxWxH), DIM009

Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
OPC XMLDA
BACnet/IP*
LIOBIP
Modbus TCP (Master or Slave)
HTTP, FTP
1xBACnet MS/TP*
1xLIOBFT
1xModbus RTU (Master or Slave)
1xM-Bus (Master EN13757-3)
1xEIA-232 (RS-232)
* BACnet IP or BACnet MS/TP (LINX210 only)

LIOB I/O Modules

Up to 8 LIOB I/O Modules in any combination of type LIOBFT and LIOBIP852

BACnet/IP Router

1 (LINX211 only)

Program cycle time

Down to 10ms

Programming, Tools

LLOGICAD software (IEC611313), LINX/L-GATE Configurator

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

Specifications

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

Resource limits

50

OPC XMLDA data points

500

E-mail templates

100

BACnet objects

750 (analog, binary, multi-state)

Math objects

100

BACnet client mappings

750

Alarm logs

10

BACnet calendar objects

25

M-Bus data points

1000

BACnet scheduler objects

100 (64 data points per object)

Number of L-WEB clients

15 (simultaneously)

BACnet notification classes

32

Modbus data points

2000

Trend logs (BACnet or generically)

100 (390000 logs, 6MB)

Connections (Local / Global)

1000 / 250

Total trended data points

256

L-IOB I/O Modules

8 (LIOB-FT or LIOBIP852)

Order number

Product description

LINX210

BACnet Automation Server, B-BC, IEC 61131-3 programmable

LINX211

BACnet Automation Server, B-BC, IEC 61131-3 programmable, built-in BACnet/IP to MS/TP Router

LINXSTART-BC2

Starter kit: LINX200, LINX210, and LLOGICAD software license

L-LOGICAD

IEC 61131-3 programming tool, single license, includes USB dongle

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB151

LIOBFT I/O Module: 8UI, 12DI

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB153

LIOBFT I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB154

LIOBFT I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB550

LIOBBIP I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB551

LIOBBIP I/O Module: 8UI, 12DI

LIOB552

LIOBBIP I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB553

LIOBBIP I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB554

LIOBBIP I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LOPC-BR800

OPC Bridge (PC software) to connect OPC DA clients (COM/DCOM) with LINX Automation Servers

LMBUS20

M-Bus level converter for 20 M-Bus devices

LMBUS80

M-Bus level converter for 80 M-Bus devices

www.loytec.com

L-INX Automation Server

LINX100, LINX101

y=f(x)

Ethernet / IP

IP-852

LIOB
IP

Modbus
TCP

Web
Interface

Alarming
Scheduling
Trending

LINX-101

Graphics
Graphics
Graphics

E-Mail

Ethernet / IP

OPC XML-DA
Server

TP/FT-10

LIOB
FT

Modbus
RTU

M-Bus

TP/FT-10

E-Mail

OPC XML-DA
Server

Data Point Abstraction Layer

ROUTER

y=f(x)

Alarming
Scheduling
Trending

Modbus
TCP

L-VIS

RNI

LIOB
IP

Graphics
Graphics
Graphics

Touch Panels

Data Point Abstraction Layer

IP-852

Web
Interface

Gateways

LINX-100

y=f(x)

LIOB
FT

Modbus
RTU

M-Bus

L-DALI

Lighting Control

V1.2.2

V1.2.2

Features
System visualization via LWEB800/802

L-IOB

RNI

I/O Controllers/Modules

The L-INX devices provide fully featured AST functionality and integrate perfectly
into the L-WEB System.

CEA-709

L-INX

LIOB
IP

Automation Servers

LIOB
FT

The gateway functionality allows data communication between all communication technologies available on the device. Different technology data points are
mapped through Local Connections on the device. The mapping of different technology data points on distributed devices is supported by Global Connections.
L-INX Automation Servers also support Smart Auto-Connect - the automatic
generation of connections to substantially reduce engineering efforts and cost.
All technology data points are automatically created as OPC XML-DA data points
as well.

L-ROC

The powerful Automation Servers provide connectivity functions to concurrently


integrate CEA-709 (LonMark-Systems), Modbus, and M-Bus subsystems. LonMark
Systems can be integrated via IP-852 (Ethernet/IP) or TP/FT-10. LINX100 Automation Servers feature an integrated Remote Network Interface (RNI) to access the
TP/FT-10 channel on the device via Ethernet/IP. LINX-101 Automation Servers feature a built-in IP-852 router providing the complete feature set of the corresponding L-IP devices. In addition, the L-INX Automation Servers provide connectivity to
Modbus TCP via Ethernet/IP and to Modbus RTU via RS-485. M-Bus device integration needs an optional interface module.

Room Automation

The L-INX Automation Servers LINX100 and LINX-101 can host user specific graphical pages and can integrate physical I/O through L-IOB I/O Modules via LIOB-FT or
LIOB-IP.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709
KNX

tion Properties (SCPTs, UCPTs)

Stores customized graphical pages

Built-in OPC XMLDA server

Integrated IP852 to TP/FT10 Router (LINX101 only)


M-Bus Master according to EN13757-3, connection via optional
MBus Converter (e.g. LMBUS80)

Alarming, Scheduling, and Trending (AST)

Routers, NIC

Extension to physical inputs and outputs with LIOB I/O Modules


(LIOBFT or LIOBIP852)

CEA709 Remote Network Interface (RNI) with 2 MNI devices


(LINX100 only)

Modbus TCP and Modbus RTU (Master or Slave)

Event-driven e-mail notification


Compliant with CEA709, CEA852, and ISO/IEC14908 standard
(LonMark System)

Integrated Web server for the device configuration and for


monitoring of data points
Access to network statistics

Support of dynamically created or static NVs


Support of CEA709 user-defined NVs (UNVTs) and Configura-

Configurable via Ethernet, EIA-232, or TP/FT-10

buildings under control

51

Software
Tools

Supports TP/FT-10 or IP-852 (Ethernet/IP)

Gateway functions including Smart Auto-Connect

LINX100, LINX101
Specifications
Dimensions (mm)

107x100x60 (LxWxH), DIM009

Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
OPC XMLDA
LIOBIP
LonMark IP-852*
Modbus TCP (Master or Slave)
HTTP, FTP
1xTP/FT-10* (LonMark System)
1xModbus RTU (Master or Slave)
1xM-Bus (Master EN13757-3)
1xEIA-232 (RS-232)
1xLIOBFT

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

L-INX Automation Server

L-IOB

I/O Controllers/Modules

*LonMark IP-852 or TP/FT-10 (LINX100 only)


LIOB I/O Modules

Up to 8 LIOB I/O Modules in any combination of type LIOBFT and LIOBIP852

Remote Network Interface

1 RNI with 2 MNI devices (LINX100 only)

CEA709 Router

1 (LINX101 only)

Tools

LINX/L-GATE Configurator

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

Resource limits

52

OPC XMLDA data points

2000

Total trended data points

256

Network variables (NVs)

1000

E-mail templates

100

Alias NVs

1000

Math objects

100

External NVs (polling)

1000

Alarm logs

10

Address table entries

512 (non-ECS mode: 15)

M-Bus data points

1000

LonMark Calendar

1 (25 calendar templates)

Modbus data points

2000

LonMark Scheduler

100

Connections (Local / Global)

2000 / 250

LonMark Alarm Server

Number of L-WEB clients

15 (simultaneously)

Trend logs

100 (390 000 logs, 6 MB)

L-IOB I/O Modules

8 (LIOB-FT or LIOBIP852)

Order number

Product description

LINX100

CEA709 Automation Server, built-in Remote Network Interface (RNI)

LINX101

CEA709 Automation Server, built-in IP-852 Router

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB151

LIOBFT I/O Module: 8UI, 12DI

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB153

LIOBFT I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB154

LIOBFT I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB450

LIOBIP852 I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB451

LIOBIP852 I/O Module: 8UI, 12DI

LIOB452

LIOBIP852 I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB453

LIOBIP852 I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB454

LIOBIP852 I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LOPC-BR800

OPC Bridge (PC software) to connect OPC DA clients (COM/DCOM) with LINX Automation Servers

LMBUS20

M-Bus level converter for 20 M-Bus devices

LMBUS80

M-Bus level converter for 80 M-Bus devices

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

www.loytec.com

L-INX Automation Server

LINX200, LINX201

BACnet

Ethernet / IP

LIOB
IP

Alarming
Scheduling
Trending

E-Mail

Ethernet / IP

OPC XML-DA
Server

y=f(x)

LIOB
FT

BACnet
MS/TP

M-Bus

Alarming
Scheduling
Trending

E-Mail

OPC XML-DA
Server

Data Point Abstraction Layer


y=f(x)

Modbus
RTU

LIOB
FT

M-Bus

V1.2.2

L-DALI

Modbus
RTU

LIOB
IP

Graphics
Graphics
Graphics

Lighting Control

BACnet
MS/TP

Modbus
TCP

ROUTER

Data Point Abstraction Layer

BACnet/IP

Web
Interface

L-VIS

Modbus
TCP

Web
Interface

Touch Panels

BACnet/IP

LINX-201

Graphics
Graphics
Graphics

Gateways

LINX-200

L-IOB

The L-INX devices provide fully featured AST functionality and integrate perfectly
into the L-WEB System.

I/O Controllers/Modules

LIOB
IP

L-INX

LIOB
FT

The gateway functionality allows data communication between all communication


technologies available on the device. Different technology data points are mapped
through Local Connections on the device. The mapping of different technology
data points on distributed devices is supported by Global Connections. L-INX Automation Servers also support Smart Auto-Connect - the automatic generation of
connections to substantially reduce engineering efforts and cost. All technology
data points are automatically created as OPC XML-DA data points.

Automation Servers

Both LINX200 and LINX201 implement the BACnet Building Controller (B-BC) profile and are BTL tested and WSPcert certified. In addition, the L-INX Automation
Servers provide connectivity to Modbus TCP via Ethernet/IP and to Modbus RTU
via RS-485. M-Bus device integration needs an optional interface module.

L-ROC

The Automation Servers provide connectivity functions to concurrently integrate


BACnet, Modbus, and M-Bus subsystems. BACnet integration is supported through
BACnet/IP (Ethernet/IP) or BACnet MS/TP (RS-485). LINX201 Automation Servers
feature a built-in BACnet/IP to MS/TP router including BBMD as well as Slave-Proxy
functionality providing the complete feature set of the corresponding L-IP device.

Room Automation

The L-INX Automation Servers LINX-200 and LINX-201 can host user specific graphical pages and can integrate physical I/O through L-IOB I/O Modules via LIOB-FT or
LIOB-IP.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709

KNX

V1.2.2

Features
Supports BACnet MS/TP or BACnet/IP

Stores customized graphical pages

BACnet Client Function (Write Property, Read Property, COV


Subscription)

Extension to physical inputs and outputs with LIOB I/O Modules


(LIOBFT or LIOBIP852)
Built-in OPC XMLDA server

BACnet Client Configuration with configuration tool (scan and


EDE import)

Routers, NIC

System visualization via LWEB800/802

B-BC (BACnet Building Controller) functionality, BTL certified

Alarming, Scheduling, and Trending (AST)

Integrated BACnet/IP to BACnet MS/TP Router including BBMD


as well as Slave-Proxy functionality (LINX201 only)

Event-driven e-mail notification


Compliant with ANSI/ASHRAE1352008 and ISO164845 standard

M-Bus Master according to EN13757-3, connection via optional


MBus Converter (e.g. LMBUS80)
Modbus TCP and Modbus RTU (Master or Slave)

buildings under control

53

Software
Tools

Built-in OPC XML-DA server

LINX200, LINX201

Room Automation

L-WEB

Building Management

L-INX Automation Server

Gateway functions including Smart Auto-Connect

Access to network statistics

Math objects to execute mathematical operations on data


points

Configurable via Ethernet/IP

L-ROC

Integrated Web server for the device configuration and for


monitoring of data points

Dimensions (mm)

107x100x60 (LxWxH), DIM009

Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
OPC XMLDA
LIOBIP
BACnet/IP*
Modbus TCP (Master or Slave)
HTTP, FTP
1xBACnet MS/TP*
1xModbus RTU (Master or Slave)
1xM-Bus (Master EN13757-3)
1xEIA-232 (RS-232)
1xLIOBFT

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

Specifications

* BACnet IP or BACnet MS/TP (LINX200 only)


LIOB I/O Modules

Up to 8 LIOB I/O Modules in any combination of type LIOBFT and LIOBIP852

BACnet/IP Router

1 (LINX201 only)

Tools

LINX/L-GATE Configurator

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

Resource limits

54

OPC XMLDA data points

2000

E-mail templates

100

BACnet objects

750 (analog, binary, multi-state)

Math objects

100

BACnet client mappings

750

Alarm logs

10

BACnet calendar objects

25

M-Bus data points

1000

BACnet scheduler objects

100 (64 data points per object)

Modbus data points

2000

BACnet notification classes

32

Connections (Local / Global)

1000 / 250

Trend logs (BACnet or generically)

100 (390000 logs, 6MB)

Number of L-WEB clients

15 (simultaneously)

Total trended data points

256

L-IOB I/O Modules

8 (LIOB-FT or LIOBIP852)

Order number

Product description

LINX200

BACnet Automation Server, B-BC

LINX201

BACnet Automation Server, B-BC, built-in BACnet/IP to MS/TP Router

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB151

LIOBFT I/O Module: 8UI, 12DI

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB153

LIOBFT I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB154

LIOBFT I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LIOB550

LIOBBIP I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

LIOB551

LIOBBIP I/O Module: 8UI, 12DI

LIOB552

LIOBBIP I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB553

LIOBBIP I/O Module: 6 UI, 6 AO, 5 DO (4xRelay 16A, 1xRelay 6A)

LIOB554

LIOBBIP I/O Module: 7 UI, 4 AO, 7 DO, 1 Pressure Sensor

LOPC-BR800

OPC Bridge (PC software) to connect OPC DA clients (COM/DCOM) with LINX Automation Servers

LMBUS20

M-Bus level converter for 20 M-Bus devices

LMBUS80

M-Bus level converter for 80 M-Bus devices

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

www.loytec.com

L-IOB I/O Controllers & Modules

buildings under control

55

L-WEB

Building Management

L-ROC

Room Automation

LIOB I/O Controllers


The L-IOB I/O Controller family of products consists of programmable controllers featuring various I/O configurations. Based
on LOYTECs 32-bit L-CORE platform, the L-IOB I/O Controllers provide first class performance and a wide area of applications.

Programmable
The built-in PLC functionality makes the L-IOB I/O Controllers a good fit for various control applications in building automation. Like the L-INX Automation Servers, the L-IOB I/O Controllers are programmed with L-LOGICAD in 61131-3. The same
application libraries and application programs can be used on both platforms.
The LIOB-BIP I/O Controllers adhere to the BACnet Building Controller Profile (B-BC) and communicate over Ethernet/IP in the
BACnet/IP network. The I/O data points can either be exposed through BACnet server objects or be actively fetched by the
L-IOB I/O Controllers from a BACnet server via BACnet client maps.

LonMark Models
The LIOB-FT I/O Controllers and LIOB-IP852 I/O Controllers communicate in the LonMark sytem via network variables over
TP/FT-10 or Ethernet/IP-852 respectively. They come with a freely configurable network variable interface and offer up to 256
address table entries.
LIOB I/O Controllers

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

BACnet/IP Models

LIOB I/O Controllers

IEC 61131-3 programmable

LonMark TP/FT-10
LIOB180

LonMark IP-852
LIOB480

Gateways

8 UI
2 DI
2 AO
8 DO

L-VIS

Touch Panels

L-DALI

LIOB581

LIOB482

8 UI
12 DI

LIOB582
6 UI
6 AO
8 DO

6 UI
6 AO
8 DO
Lighting Control

8 UI
2 DI
2 AO
8 DO

8 UI
12 DI

LIOB182

LIOB183

LIOB483

6 UI
6 AO
8 DO

LIOB583
6 UI
6 AO
5 DO

6 UI
6 AO
5 DO

Routers, NIC

LIOB580

LIOB481

8 UI
12 DI

LIOB184

LIOB484

6 UI
6 AO
5 DO

LIOB584
7 UI
4 AO
7 DO
1 Pressure
Sensor

Software
Tools

56

BACnet/IP

8 UI
2 DI
2 AO
8 DO

LIOB181

7 UI
4 AO
7 DO
1 Pressure
Sensor

IEC 61131-3 programmable

www.loytec.com

7 UI
4 AO
7 DO
1 Pressure
Sensor

LIOBFT I/O Controller


LOYTEC

LIOB180/181/182/183/184

COMPETENCE PARTNER

LIOB-18x I/O Controllers are compact, programmable automation stations for LonMark Systems with physical inputs and outputs.

L-ROC

LIOB-18x I/O Controllers communicate via twisted pair over a TP/FT-10 channel in
the LonMark System. LIOB-18x I/O Controllers offer extended features such as local
alarming (SNVT_alarm and SNVT_alarm_2) and local scheduling.

Room Automation

LonMark TP/FT-10 Channel

L-WEB

Modbus
Modbus
M-Bus
M-Bus

Building Management

BACnet
BACnet
CEA709

CEA709
KNX KNX

Local Operation and Override

L-INX

Automation Servers

All L-IOB I/O Controllers are equipped with an LCD display (128x64) with backlight
and jog dial for manual local operation and override. Device and data point information is displayed in text form and via graphical symbols.

I/O Controllers/Modules

&

L-IOB

IP-852
LonMark TP/FT-10

Gateways

Intranet
Internet
IP-852

IP-852

L-VIS

Touch Panels

Features

IEC61131-3 programmable with L-LOGICAD

Up to 256 address table entries (ECS mode)

128x64 graphic display with backlight

LNS plugin for the device configuration in the LonMark System

Local access to information about device status and data points


in clear text and symbols

Math objects to execute mathematical operations on data


points

Manual operation using the jog dial

LonMark Alarming with nvoAlarm


nvoAlarm_2 (SNVT_alarm_2)

SNVT-based interface for integration on the LonMark TP/FT-10


channel

(SNVT_alarm)

and

Local Scheduling (no real-time clock, system time is set via


SNVT_time_stamp)

Routers, NIC

Complient with CEA709 and ISO/IEC


14908-2 standard
(LonMark System)

L-DALI

NV interface can be freely defined

Lighting Control

Automation station with physical input and outputs

Software
Tools

buildings under control

57

LIOB180/181/182/183/184
General Specifications
Dimensions (mm)

107x100x75 (LxWxH), DIM015, DIM016, DIM017

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Power supply

24VDC / 24VAC 10%

Programming

LLOGICAD software (IEC 61131-3)

Program cycle time

Down to 10ms

Interface

1xLIOBFT or LonMark TP/FT-10

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

LIOBFT I/O Controller

Gateways

L-IOB

I/O Controllers/Modules

Resource limits
Network variables (NVs)

200

Alias NVs

200

Address table entries

256 (non-ECS mode: 15)

LonMark Calendar

1 (25 calendar templates)

LonMark Scheduler

10

LonMark Alarm Server

Connections (Local / Global)

200 / 0

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Specifications LIOBFT I/O Controller (LIOB18x)

58

Types

LIOB180

LIOB181

LIOB182

Power consumption

1.7W
2.6W (all Relay
on)

1.7W

1.7W
1.7W
1.7 W
2.7W (all Relay on) 2.5W (all Relay on) 2.6 W (all Relay
on)

Universal Input (UI)

Digital Input (DI)

12

Analog Output (AO)

Digital Output (DO)

8 (4xRelay,
4xTriac)

8 (8xRelay)

5 (4xRelay 16A,
1xRelay 6A)

7 (5xRelay,
2xTriac)

Digital Output specification

Relay: 6A
Triac: 1A @
24230VAC

Relay: 6A

Relay: 16A and


6A

Relay: 6A
Triac: 1A @
24230VAC

Differential Pressure Sensor

0500Pa

LIOB183

Order number

Product description

LIOB180

LIOBFT I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

LIOB181

LIOBFT I/O Controller: 8UI, 12DI

LIOB182

LIOBFT I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

LIOB183

LIOBFT I/O Controller: 6 UI, 6AO, 5DO (2xTriac, 4xRelay 16A)

LIOB184

LIOBFT I/O Controller: 7 UI, 6AO, 5DO (5xRelay 16A, 1xRelay 6A), 1 Pressure Sensor

L-LOGICAD

IEC 61131-3 programming tool, single license, includes USB dongle

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

L-TEMP2

External temperature sensor (NTC10K) for use with LIOB Universal Inputs

www.loytec.com

LIOB184

LIOBIP852 I/O Controller


LOYTEC

LIOB480/481/482/483/484

COMPETENCE PARTNER

LIOB
IP
&

VNC

y=f(x)

LIOB-IP

Gateways

IP-852
Intranet
Internet
IP-852
LIOB-IP

L-IOB

All L-IOB I/O Controllers are equipped with an LCD display (128x64) with backlight
and jog dial for manual local operation and override. Device and data point information is displayed in text form and via graphical symbols.

I/O Controllers/Modules

Local Operation and Override

L-INX

Technology data points are automatically exposed as OPC tags via the integrated
OPC server (XML-DA). The L-IOB I/O Controllers further allow data exchange over
global connections (network-wide data exchange), offer AST functions like alarming, scheduling, and trending, store custom graphic pages for visualization in
LWEB-800/802, and can be seamlessly integrated in the LWEB-900 Building Management System.

Automation Servers

The LIOB-48x I/O Controller is equipped with two Ethernet ports including a builtin Ethernet switch. This allows daisy chaining of up to 20 LOYTEC devices featuring
dual Ethernet in an Ethernet ring. The Ethernet ring is connected with each end to
an Ethernet switch supporting RSTP (Rapid Spanning Tree Protocol). This ensures
reliable communication and system availability with reduced wiring efforts.*

L-ROC

LonMark IP-852 Channel over Ethernet

Room Automation

LIOB-48x I/O Controllers are IP-enabled, compact, programmable automation stations for LonMark Systems with physical inputs and outputs and integrated graphical visualization.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709
KNX

IP-852

IP-852

L-VIS

Touch Panels
Lighting Control

L-DALI

* Available Q4/2013
Features
Automation station with physical input and outputs
IEC61131-3 programmable with L-LOGICAD

Module (LIOBIP852)
Complient with CEA852 and ISO/IEC
14908-4 standard
(LonMark System)

Ethernet/IP interface
128x64 graphic display with backlight
Local access to information about device status and data points
in clear text and symbols

NV interface can be freely defined


Up to 259 address table entries (ECS mode)

Stores customized graphical pages

LNS plugin for the device configuration in the LonMark System

Visualization of customized graphical pages through LWEB900


(building management), or LWEB800/802

Alarming, Scheduling, and Trending (AST)

Integrated Web server for the device configuration and for


monitoring of data points

Math objects to execute mathematical operations on data


points

Extension to physical inputs and outputs with one LIOB I/O

Built-in OPC XML-DA server

Routers, NIC

SNVT-based interface for integration on the LonMark IP-852


channel

Manual operation using the jog dial

Event-driven e-mail notification

59

Software
Tools

buildings under control

LIOB480/481/482/483/484
General Specifications
Dimensions (mm)

107x100x75 (LxWxH), DIM018, DIM019, DIM020, DIM021, DIM022

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Power supply

24VDC / 24VAC 10%

Programming

LLOGICAD software (IEC 61131-3)

Program cycle time

Down to 10ms

L-IOB I/O Module

Up to 1 L-IOB I/O Module of type LIOBIP852

Interface

2xEthernet (100Base-T)
- OPC XMLDA
- LonMark IP-852
- LIOB-IP

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

LIOBIP852 I/O Controller

Gateways

L-IOB

I/O Controllers/Modules

Resource limits
OPC XMLDA data points

200

Total trended data points

100

Network variables (NVs)

200

E-mail templates

20

Alias NVs

200

Math objects

20

Address table entries

256 (non-ECS mode: 15)

Alarm logs

LonMark Calendar

1 (25 calendar templates)

Connections (Local / Global)

200 / 100

LonMark Scheduler

10

Number of L-WEB clients

LonMark Alarm Server

L-IOB I/O Module

1 (LIOB-IP852)

Trend logs

50 (390 000 logs, 6 MB)

Types

LIOB480

LIOB481

LIOB482

LIOB483

LIOB484

Power consumption

1.7W
2.6W
(all Relay on)

1.7W

1.7W
2.7W
(all Relay on)

1.7W
2.5W
(all Relay on)

1.7 W
2.6 W
(all Relay on)

Universal Input (UI)

Digital Input (DI)

12

Analog Output (AO)

Digital Output (DO)

8 (4xRelay,
4xTriac)

8 (8xRelay)

5 (4xRelay 16A,
1xRelay 6A)

7 (5xRelay,
2xTriac)

Digital Output specification

Relay: 6A
Triac: 1A @
24230VAC

Relay: 6A

Relay: 16A and


6A

Relay: 6A
Triac: 1A @
24230VAC

Differential Pressure Sensor

0500Pa

Order number

Product description

LIOB480

LIOBIP852 I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

LIOB481

LIOBIP852 I/O Controller: 8UI, 12DI

LIOB482

LIOBIP852 I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

LIOB483

LIOBIP852 I/O Controller: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

LIOB484

LIOBIP852 I/O Controller: 7UI, 6AO, 5DO (5xRelay 16A, 1xRelay 6A), 1 Pressure Sensor

L-LOGICAD

IEC 61131-3 programming tool, single license, includes USB dongle

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

L-TEMP2

External temperature sensor (NTC10K) for use with LIOB Universal Inputs

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Specifications LIOBIP852 I/O Controller (LIOB48x)

60

www.loytec.com

LIOBBIP I/O Controller


LOYTEC

LIOB580/581/582/583/584

COMPETENCE PARTNER

y=f(x)

L-IOB

&

VNC

All L-IOB I/O Controllers are equipped with an LCD display (128x64) with backlight
and jog dial for manual local operation and override. Device and data point information is displayed in text form and via graphical symbols.

I/O Controllers/Modules

Local Operation and Override

LIOB
IP

L-INX

Technology data points are automatically exposed as OPC tags via the integrated
OPC server (XML-DA). The L-IOB I/O Controllers further allow data exchange over
global connections (network-wide data exchange), offer AST functions like alarming, scheduling, and trending, store custom graphic pages for visualization in
LWEB-800/802, and can be seamlessly integrated in the LWEB-900 Building Management System.

Automation Servers

The LIOB-58x I/O Controller is equipped with two Ethernet ports including a builtin Ethernet switch. This allows daisy chaining of up to 20 LOYTEC devices featuring
dual Ethernet in an Ethernet ring. The Ethernet ring is connected with each end to
an Ethernet switch supporting RSTP (Rapid Spanning Tree Protocol). This ensures
reliable communication and system availability with reduced wiring efforts.*

L-ROC

BACnet/IP over Ethernet

Room Automation

LIOB-58x I/O Controllers are IP-enabled, compact, programmable automation


stations for BACnet/IP networks with physical inputs and outputs and integrated
graphical visualization.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709
KNX

LIOB-IP

Gateways

Object

BACnet/IP

Object

BACnet/IP

Intranet
BACnet/IP
LIOB-IP

BACnet/IP
Object

L-VIS

Touch Panels

Object

L-DALI

Lighting Control

* Available Q4/2013
Features
Automation station with physical input and outputs
IEC61131-3 programmable with L-LOGICAD

Extension to physical inputs and outputs with one LIOB I/O


Module (LIOBBIP)
Compliant with ANSI/ASHRAE1352008 and ISO164845 standard

Ethernet/IP interface

BACnet objects for integration on BACnet/IP channels

128x64 graphic display with backlight


Local access to information about device status and data points
in clear text and symbols
Stores customized graphical pages
Visualization of customized graphical pages through LWEB900
(building management), or LWEB800/802

Alarming, Scheduling, and Trending (AST)


Event-driven e-mail notification
Math objects to execute mathematical operations on data
points
Built-in OPC XML-DA server

buildings under control

Software
Tools

Integrated Web server for the device configuration and for


monitoring of data points

BACnet Client Mappings for integration on BACnet/IP channels

Routers, NIC

Manual operation using the jog dial

61

LIOB580/581/582/583/584
General Specifications
Dimensions (mm)

107x100x75 (LxWxH), DIM018, DIM019, DIM020, DIM021, DIM022

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Power supply

24VDC / 24VAC 10%

Programming

LLOGICAD software (IEC 61131-3)

Program cycle time

Down to 10ms

L-IOB I/O Module

Up to 1 L-IOB I/O Module of type LIOBBIP

Interface

2xEthernet (100Base-T)
- OPC XMLDA
- BACnet/IP
- LIOB-IP

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

LIOBBIP I/O Controller

Gateways

L-IOB

I/O Controllers/Modules

Resource limits
OPC XMLDA data points

200

Total trended data points

100

BACnet objects

200 (analog, binary, multi-state)

E-mail templates

20

BACnet client mappings

200

Math objects

20

BACnet calendar objects

25

Alarm logs

BACnet scheduler objects

10

Connections (Local / Global)

200 / 100

BACnet notification classes

32

Number of L-WEB clients

Trend logs (BACnet or generically)

50 (390000 logs, 6MB)

L-IOB I/O Module

1 (LIOB-BIP)

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Specifications LIOBBIP I/O Controller (LIOB58x)

62

Types

LIOB580

LIOB581

LIOB582

Power consumption

1.7W
2.6W (all Relay on)

1.7W

1.7W
1.7W
1.7W
2.7W (all Relay on) 2.5W (all Relay on) 2.6W (all Relay
on)

Universal Input (UI)

Digital Input (DI)

12

Analog Output (AO)

Digital Output (DO)

8 (4xRelay,
4xTriac)

8 (8xRelay)

5 (4xRelay 16A,
1xRelay 6A)

7 (5xRelay,
2xTriac)

Digital Output specification

Relay: 6A
Triac: 1A @
24230VAC

Relay: 6A

Relay: 16A and


6A

Relay: 6A
Triac: 1A @
24230VAC

Differential Pressure Sensor

0500Pa

LIOB583

Order number

Product description

LIOB580

LIOBBIP I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

LIOB581

LIOBBIP I/O Controller: 8UI, 12DI

LIOB582

LIOBBIP I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

LIOB583

LIOBBIP I/O Controller: 6 UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

LIOB584

LIOBBIP I/O Controller: 7 UI, 6AO, 5DO (5xRelay 16A, 1xRelay 6A), 1 Pressure Sensor

L-LOGICAD

IEC 61131-3 programming tool, single license, includes USB dongle

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

L-TEMP2

External temperature sensor (NTC10K) for use with LIOB Universal Inputs

www.loytec.com

LIOB584

L-ROC

The LIOB-BIP I/O Modules adhere to the BACnet Building Controller Profile (B-BC) and communicate over Ethernet/IP in the
BACnet/IP network. The I/O data points can either be exposed through BACnet server objects or be actively fetched by the
L-IOB I/O Modules from a BACnet server via BACnet client maps.

Room Automation

BACnet/IP Models

L-WEB

The L-IOB I/O Module family of products consists of intelligent input/output devices featuring various I/O configurations.
Based on LOYTECs 32-bit L-CORE platform, the L-IOB I/O Modules provide first class performance and a wide area of applications.

Building Management

LIOB I/O Modules

LonMark Models

LIOB-Connect

LonMark TP/FT-10

LIOB100

LonMark IP-852
LIOB450

8 UI
2 DI
2 AO
8 DO

LIOB101

8 UI
2 DI
2 AO
8 DO

LIOB451

LIOB551
8 UI
12 DI

8 UI
12 DI

8 UI
12 DI

L-VIS

Touch Panels

8 UI
16 DI

LIOB550
8 UI
2 DI
2 AO
8 DO

LIOB151

BACnet/IP

Gateways

8 UI
2 DI
2 AO
9 DO

LIOB150

L-IOB

LIOB I/O Modules

I/O Controllers/Modules

The L-IOB I/O Modules can be used as I/O extensions for L-INX Automation Servers, L-ROC Room Controllers, and LIOB48x/58x I/O Controllers. The connection is done via gold-plated contacts on the side (LIOB-Connect), twisted pair (LIOB-FT),
or Ethernet/IP (LIOB-IP852 or LIOB-BIP), depending on the L-IOB model.

L-INX

Plug-and-play installation

Automation Servers

The LIOB-FT I/O Modules and LIOB-IP852 I/O Modules are LonMark certified I/O nodes which communicate in the LonMark
sytem via network variables over TP/FT-10 or Ethernet/IP-852 respectively.

LIOB102

LIOB452
6 UI
6 AO
8 DO

6 UI
6 AO
8 DO

LIOB453
6 UI
6 AO
5 DO

6 UI
6 AO
5 DO

LIOBA2

LIOB154
7 UI
4 AO
7 DO
1 Pressure
Sensor

LIOB553
6 UI
6 AO
5 DO

LIOB454

Routers, NIC

6 UI
6 AO
5 DO

LIOB153

6 UI
6 AO
8 DO

L-DALI

LIOB103

LIOB552

Lighting Control

6 UI
6 AO
8 DO

LIOB152

LIOB554
7 UI
4 AO
7 DO
1 Pressure
Sensor

7 UI
4 AO
7 DO
1 Pressure
Sensor

Software
Tools

buildings under control

63

LIOB100/101/102/103

LOYTEC

COMPETENCE PARTNER

LIOB-10x I/O Modules extend L-INX Automation Servers and L-ROC Room Controllers with physical inputs and outputs. Several LIOB-10x models with different I/O
configurations are available.

Room Automation

L-WEB

Building Management

BACnet
Modbus
CEA709 M-Bus
KNX

LIOBConnect I/O Module

L-ROC

LIOB-Connect
The LIOB-10x Modules have gold-plated connectors (LIOB-Connect) to string multiple devices together and connect them to the L-INX or L-ROC. The L-INX or L-ROC
automatically recognizes the LIOB-10x I/O Modules and provides the resulting
data points.

L-INX

Automation Servers

Local Operation and Override


LIOB

All L-IOB I/O Modules are equipped with an LCD display (128x64) with backlight
and jog dial for manual local operation. Device and data point information is displayed in text form and via graphical symbols.

L-IOB

I/O Controllers/Modules

CONNECT

LPOW-2415A

Made in Austria

status

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

LOYTEC
www.loytec.com

LINX-120

USB

L-POW

MODBUS

Output
24VDC/15W

FUSE 6A

EXT

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

status

LIOB-100

LIOB-FT

MODBUS

Made in Austria

LIOB-A2

L-IOB

L-IOB

I/O Module

4
EXT

UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

+ GND
24 VDC/200mA
OUTPUT

LOYTEC
www.loytec.com

status

Automation Server

1
FT

Ethernet 1 Ethernet 2

+ GND
24 VDC
INPUT

Made in Austria

6A

LOYTEC
www.loytec.com

L-INX

Adapter 2

0-10V OUT

DI2 AO1

LIOB-CONNECT IN/OUT

AO2

Gateways

85-265VAC
50/60 Hz

LIOB-FT

ACT

Power Supply
Input
N
L

FT

MICROSD

LINK

PLC OPC

SEL GND A

B TERM

LPOW-2415A

Made in Austria

status

LOYTEC
www.loytec.com

L-POW

Touch Panels

L-VIS
L-DALI

Lighting Control

85-265VAC
50/60 Hz

Made in Austria

LIOB-A2

+ GND
24 VDC/200mA
OUTPUT

FUSE 6A

Output
24VDC/15W

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

B TERM

UI2 UI3

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

I/O module with physical inputs and outputs


Connected to the L-INX Automation Server or L-ROC Room Controller via LIOBConnect
Manual operation using the jog dial

Routers, NIC

L-IOB

128x64 graphic display with backlight


Local access to information about device status and data points in clear text and symbols
Automatic integration into device configurations with L-INX and L-ROC

Software
Tools

Easy device replacement without any additional software at the L-INX and L-ROC

www.loytec.com

I/O Module

0-10V OUT

DI2 AO1

AO2

UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

+ GND
24 VDC
INPUT

Made in Austria

LIOB-A2

+ GND
24 VDC/200mA
OUTPUT

LOYTEC
www.loytec.com

status

I/O Module
UNIVERSAL IN
UI1

Features

64

LIOB-100

L-IOB

Adapter 2

Made in Austria

status

LOYTEC
www.loytec.com

status

L-IOB

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9
6A

status

LIOB-100

LIOB-CONNECT IN/OUT
SEL GND A

FUSE 6A

Made in Austria

6A

LOYTEC
www.loytec.com

LOYTEC
www.loytec.com

Power Supply
Input
N
L

+ GND
24 VDC
INPUT

0-10V OUT

DI2 AO1

AO2

L-IOB

Adapter 2
LIOB-CONNECT IN/OUT
SEL GND A

B TERM

L-WEB

LIOB100/101/102/103

Building Management

LIOBConnect I/O Module

L-ROC

Room Automation

L-INX

Automation Servers

L-IOB

I/O Controllers/Modules

General Specifications
Dimensions (mm)

107x100x75 (LxWxH), DIM011, DIM012, DIM013, DIM014

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Power supply

24VDC / 24VAC 10% via LINX, LROC, or LPOW, or with LIOBConnect, or via connecting of an
external power supply to the upper left terminal

Interfaces

1xLIOBConnect

Gateways

Specifications LIOBConnect
LIOB101

LIOB102

LIOB103

Power consumption

1.7W
2.6W (all Relay on)

1.7W

1.7W
2.7W (all Relay on)

1.7W
2.5W (all Relay on)

Universal Input (UI)

Digital Input (DI)

16

Analog Output (AO)

Digital Output (DO)

9 (5xRelay, 4xTriac)

8 (8xRelay)

5 (5xRelay)

Digital Output specification

Relay: 6A
Triac: 1A @ 24-230VAC

Relay: 6A

Relay: 16A

LIOB100

LIOBConnect I/O Module: 8UI, 2DI, 2AO, 9DO (4xTriac, 5xRelay 6A)

LIOB101

LIOBConnect I/O Module: 8UI, 16DI

LIOB102

LIOBConnect I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB103

LIOBConnect I/O Module: 6UI, 6AO, 5DO (Relay 16A)

LIOBA2

LIOB Adapter 2 to split the line of LIOBConnect modules on the DINrail for space and power considerations

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

L-TEMP2

External temperature sensor (NTC10K) for use with LIOB Universal Inputs

buildings under control

Software
Tools

Product description

Routers, NIC

Order number

L-DALI

LIOB100

Lighting Control

Types

L-VIS

Attachable (max. 4 modules) or connected with a 4-wire cable, max. 50m


Touch Panels

Installation

65

LIOB150/151/152/153/154

Modbus
M-Bus

The LIOB-15x Modules are LonMark certified and communicate over TP/FT-10 in
the LonMark System. They provide up to 512 address table entries (ECS mode)
which eliminates all binding restrictions.

Room Automation

L-WEB

Building Management

BACnet
CEA709
KNX

LIOBFT I/O Module

L-ROC

LIOB-FT Mode
The LIOB-15x Modules can be switched to LIOB-FT mode using manual local operation. In LIOB-FT mode, the LIOB-15x Modules extend L-INX Automation Servers
and L-ROC Room Controllers with physical inputs and outputs via plug-and-play.

Automation Servers

Local Operation and Override


L-INX

All L-IOB I/O Modules are equipped with an LCD display (128x64) with backlight
and jog dial for manual local operation. Device and data point information is displayed in text form and via graphical symbols.

L-IOB

I/O Controllers/Modules

LIOB
FT

Gateways

LonMark TP/FT-10

IP-852
Intranet
Internet
IP-852

L-DALI

Lighting Control

L-VIS

Touch Panels

IP-852

Features
I/O module with physical inputs and outputs

Routers, NIC

SNVT-based interface for integration on the LonMark TP/FT-10


channel
LonMark-certified

Connected to the L-INX Automation Server or L-ROC Room Controller via LIOBFT
Automatic integration into device configurations with L-INX
and L-ROC
Easy device replacement without any additional software at the
L-INX and L-ROC

Manual operation using the jog dial


128x64 graphic display with backlight
Local access to information about device status and data points
in clear text and symbols

LNS plugin for the device configuration in the LonMark System

Software
Tools

Compliant with CEA709 and ISO/IEC


14908-2 standard
(LonMark System)

66

www.loytec.com

L-WEB

LIOB150/151/152/153/154

Building Management

LIOBFT I/O Module

General Specifications
Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Power supply

24VDC / 24VAC 10% via LINX, LROC, or LPOW, or with LIOBConnect, or via connecting of an
external power supply to the upper left terminal

Interface

1xLIOBFT or LonMark TP/FT-10

L-ROC

107x100x75 (LxWxH), DIM015, DIM016, DIM017

Room Automation

Dimensions (mm)

Automation Servers

LIOB151

LIOB152

LIOB153

LIOB154

Power consumption

1.7W
2.6W (all Relay
on)

1.7W

1.7W
2.7W (all Relay
on)

1.7W
2.5W (all Relay
on)

1.7 W
2.6 W (all Relay
on)

Universal Input (UI)

Digital Input (DI)

12

Analog Output (AO)

Digital Output (DO)

8 (4xRelay,
4xTriac)

8 (8xRelay)

5 (4xRelay 16A,
1xRelay 6A)

7 (5xRelay, 2xTriac)

Digital Output specification

Relay: 6A
Triac: 1A @
24230VAC

Relay: 6A

Relay: 16A and


6A

Relay: 6A
Triac: 1A @ 24
230VAC

Differential Pressure Sensor

L-IOB

LIOB150

I/O Controllers/Modules

Types

L-INX

Specifications LIOBFT I/O Module (LIOB15x)

0500Pa

Gateways

Resource limits
Network variables (NVs)

Fixed static NV interface

Address table entries

512 (Non-ECS mode: 15)

L-VIS

Touch Panels

Product description

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

LIOB151

LIOBFT I/O Module: 8UI, 12DI

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB153

LIOBFT I/O Module: 6 UI, 6AO, 5DO (2xTriac, 4xRelay 16A)


LIOBFT I/O Module: 7 UI, 6AO, 5DO (5xRelay 16A, 1xRelay 6A), 1 Pressure Sensor
LIOB Adapter 2 to split the line of LIOBConnect modules on the DINrail for space and power considerations

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

L-TEMP2

External temperature sensor (NTC10K) for use with LIOB Universal Inputs

L-DALI

LIOB154
LIOBA2

Lighting Control

Order number

Routers, NIC
Software
Tools

buildings under control

67

LIOB450/451/452/453/454

Modbus
M-Bus

The LIOB-45x Modules are LonMark certified and communicate over Ethernet/IP-852
in the LonMark System. They provide up to 512 address table entries (ECS mode)
which eliminates all binding restrictions.

Room Automation

L-WEB

Building Management

BACnet
CEA709
KNX

LIOBIP852 I/O Module

L-ROC

LonMark IP-852 Channel over Ethernet

Automation Servers

The LIOB-45x I/O Module is equipped with two Ethernet ports including a built-in
Ethernet switch. This allows daisy chaining of up to 20 LOYTEC devices featuring
dual Ethernet in an Ethernet ring. The Ethernet ring is connected with each end to
an Ethernet switch supporting RSTP (Rapid Spanning Tree Protocol). This ensures
reliable communication and system availability with reduced wiring efforts.*

L-INX

The LIOB-45x Modules are equipped with a Web interface to query the device status. The local display can be accessed via VNC.

I/O Controllers/Modules

LIOB-IP Mode

L-IOB

LIOB
IP

Local Operation and Override


All L-IOB I/O Modules are equipped with an LCD display (128x64) with backlight
and jog dial for manual local operation. Device and data point information is displayed in text form and via graphical symbols.

Gateways

VNC

y=f(x)

The LIOB-45x Modules can be switched to LIOB-IP mode using manual local operation. In LIOB-IP mode, the LIOB-45x Modules extend L-INX Automation Servers,
LIOB-IP852 I/O Controllers, and L-ROC Room Controllers with physical inputs and
outputs via plug-and-play.

L-VIS

Touch Panels

Intranet
Internet
LIOB-IP

Lighting Control

L-INX I/O integration


through LIOB-IP via PlugnPlay
L-DALI

* Available Q4/2013
Features
I/O module with physical inputs and outputs

in clear text and symbols

Ethernet/IP network interface

Routers, NIC

SNVT-based interface for integration on the LonMark IP-852


channel
LonMark certified

Connected to the L-INX Automation Server, L-ROC Room Controller and LIOBIP852 I/O Controller via LIOBIP
Automatic integration into device configurations with L-INX,
L-ROC, and LIOBIP852 I/O Controller
Easy device replacement without any additional software at the
L-INX, L-ROC, and LIOBIP852 I/O Controller

Up to 512 address table entries (ECS mode)


Manual operation using the jog dial

Integrated Web server for the device configuration

128x64 graphic display with backlight

LNS plugin for the device configuration in the LonMark System

Software
Tools

Local access to information about device status and data points

68

www.loytec.com

L-ROC

Room Automation

Intranet
Internet
IP-852

L-WEB

LIOB450/451/452/453/454

Building Management

LIOBIP852 I/O Module

LIOB-IP

L-INX

Automation Servers

IP-852

In LonMark mode LIOB-IP852


devices communicate through NVs

PlugnPlay I/O integration


through LIOB-IP

107x100x75 (LxWxH), DIM018, DIM019, DIM020, DIM021, DIM022

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Power supply

24VDC / 24VAC 10% via LINX, LROC, or LPOW, or with LIOBConnect, or via connecting of an
external power supply to the upper left terminal

Interface

2xEthernet (100Base-T)
- LIOB-IP
- LonMark IP-852

L-IOB

Dimensions (mm)

I/O Controllers/Modules

General Specifications

LIOB451

LIOB452

LIOB453

LIOB454

Power consumption

1.7W
2.6W (all Relay
on)

1.7W

1.7W
2.7W
(all Relay on)

1.7W
2.5W
(all Relay on)

1.7 W
2.6 W
(all Relay on)

Universal Input (UI)

Digital Input (DI)

12

Analog Output (AO)

Digital Output (DO)

8 (4xRelay,
4xTriac)

8 (8xRelay)

5 (4xRelay 16A,
1xRelay 6A)

7 (5xRelay,
2xTriac)

Digital Output specification

Relay: 6A
Triac: 1A @
24230VAC

Relay: 6A

Relay: 16A and 6A Relay: 6A


Triac: 1A @
24230VAC

Differential Pressure Sensor

0500Pa

L-DALI

Lighting Control

L-VIS

LIOB450

Touch Panels

Types

Gateways

Specifications LIOBIP852 I/O Module (LIOB45x)

Resource limits
Network variables (NVs)

Fixed static NV interface

Address table entries

512 (Non-ECS mode: 15)

LIOB450

LIOBIP852 I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

LIOB451

LIOBIP852 I/O Module: 8UI, 12DI

LIOB452

LIOBIP852 I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB453

LIOBIP852 I/O Module: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

LIOB454

LIOBIP852 I/O Module: 7UI, 6AO, 5DO (5xRelay 16A, 1xRelay 6A), 1Pressure Sensor

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

L-TEMP2

External temperature sensor (NTC10K) for use with LIOB Universal Inputs

buildings under control

Software
Tools

Product description

Routers, NIC

Order number

69

LIOB550/551/552/553/554

The LIOB-55x Modules communicate over Ethernet/IP in the BACnet/IP network.


They adhere to the BACnet Building Controller Profile (B-BC) and either expose
their I/O data points through BACnet server objects or actively fetch them from a
BACnet server via BACnet client maps.

L-ROC

Room Automation

L-WEB

Building Management

BACnet
Modbus
CEA709 M-Bus
KNX

LIOBBIP I/O Module

According to the B-BC profile, the LIOB-55x Modules support BACnet alarming,
scheduling, and trending.

BACnet/IP over Ethernet

L-INX

Automation Servers

The LIOB-55x I/O Modules is equipped with two Ethernet ports including a built-in
Ethernet switch. This allows daisy chaining of up to 20 LOYTEC devices featuring
dual Ethernet in an Ethernet ring. The Ethernet ring is connected with each end to
an Ethernet switch supporting RSTP (Rapid Spanning Tree Protocol). This ensures
reliable communication and system availability with reduced wiring efforts.*

I/O Controllers/Modules

The LIOB-55x Modules are equipped with a Web interface to query the device status and display or change each data point of the module. In addition to the BACnet
object interface, the I/O data points are exposed by the OPC XML-DA server of the
modules. The local display can be accessed via VNC.

L-IOB

LIOB
IP

VNC
y=f(x)

LIOB-IP Mode
The LIOB-55x Modules can be switched to LIOB-IP mode using manual local operation. In LIOB-IP mode, the LIOB-55x Modules extend L-INX Automation Servers,
LIOB-BIP I/O Controllers, and L-ROC Room Controllers with physical inputs and
outputs via plug-and-play.

Local Operation and Override

Gateways

All L-IOB I/O Modules are equipped with an LCD display (128x64) with backlight
and jog dial for manual local operation. Device and data point information is displayed in text form and via graphical symbols.

L-VIS

Touch Panels

Intranet
LIOB-IP

L-DALI

Lighting Control

L-INX I/O integration


through LIOB-IP via PlugnPlay
* Available Q4/2013
Features
I/O module with physical inputs and outputs

Compliant with ANSI/ASHRAE1352008 and ISO164845 standard

Routers, NIC

Ethernet/IP network interface


BACnet objects for integration on BACnet/IP channels
BACnet Client Mappings to access to BACnet/IP objects
Fulfills the BACnet Building Controller Profile (BBC)
Manual operation using the jog dial
128x64 graphic display with backlight

Software
Tools

Local access to information about device status and data points


in clear text and symbols

Supports BACnet Alarming, Scheduling, and Trending


Connected to the L-INX Automation Server, L-ROC Room Controller and LIOBBIP I/O Controller via LIOBIP
Automatic integration into device configurations with L-INX,
L-ROC, and LIOBBIP I/O Controller
Easy device replacement without any additional software at the
L-INX, L-ROC, and LIOBBIP I/O Controller
Built-in OPC XMLDA server

Integrated web server for the device configuration and for


monitoring of data points

70

www.loytec.com

L-ROC

Room Automation

Intranet
BACnet/IP
LIOB-IP

L-WEB

LIOB550/551/552/553/554

Building Management

LIOBBIP I/O Module

BACnet/IP
Object

LIOB-IP

Automation Servers

Object

L-INX

LIOB-BIP devices communicate


through BACnet/IP

PlugnPlay I/O integration


through LIOB-IP

107x100x75 (LxWxH), DIM018, DIM019, DIM020, DIM021, DIM022

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Power supply

24VDC / 24VAC 10% via LINX, LROC, or LPOW, or with LIOBConnect, or via connecting of an
external power supply to the upper left terminal

Interface

2xEthernet (100Base-T)
- OPC XMLDA
- LIOB-IP
- BACnet/IP

L-IOB

Dimensions (mm)

I/O Controllers/Modules

General Specifications

Gateways

Specifications LIOBBIP I/O Module (LIOB55x)


LIOB553

LIOB554

Power consumption

1.7W
2.6W (all Relay
on)

1.7W

1.7W
2.7W (all Relay
on)

1.7W
2.5W (all Relay
on)

1.7 W
2.6 W (all Relay on)

Universal Input (UI)

Digital Input (DI)

12

Analog Output (AO)

Digital Output (DO)

8 (4xRelay,
4xTriac)

8 (8xRelay)

5 (4xRelay 16A,
1xRelay 6A)

7 (5xRelay,
2xTriac)

Digital Output specification

Relay: 6A
Triac: 1A @
24230VAC

Relay: 6A

Relay: 16A and


6A

Relay: 6A
Triac: 1A @
24230VAC

Differential Pressure Sensor

0500Pa

L-DALI

LIOB552

Lighting Control

LIOB551

L-VIS

LIOB550

Touch Panels

Types

Resource limits
100

BACnet notification classes

16

BACnet objects

1 per I/O

Trend logs (BACnet or generically)

10 (130000 Logdaten, 2MB)

BACnet client mappings

20

Total trended data points

10

BACnet calendar objects

10

Connections (Local )

200

BACnet scheduler objects

Product description

LIOB550

LIOBBIP I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

LIOB551

LIOBBIP I/O Module: 8UI, 12DI

LIOB552

LIOBBIP I/O Module: 6UI, 6AO, 8DO (Relay 6A)

LIOB553

LIOBBIP I/O Module: 6 UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

LIOB554

LIOBBIP I/O Module: 7 UI, 6AO, 5DO (5xRelay 16A, 1xRelay 6A), 1 Pressure Sensor

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

L-TEMP2

External temperature sensor (NTC10K) for use with LIOB Universal Inputs

buildings under control

Software
Tools

Order number

Routers, NIC

OPC XMLDA data points

71

L-WEB

Building Management

L-ROC

Room Automation

LIOB I/O Modules and Controllers


Input and Output Specification
UI Universal Input
UIs are universal inputs for four different input types. Configuration is made via the L-IOB Configuration Software. They correspond to class 1 with 1 % accuracy, have an input voltage range of 0 to 10V, and can withstand up to 30 V. The ADC resolution
is 16 bits. Galvanically isolated sensors resp. switches must be connected. Universal inputs can be configured as:

Binary Input (Digital Input)


L-INX

Automation Servers

L-IOB

I/O Controllers/Modules

Gateways

Sampling rate

Voltage metering 0-10V

Input impedance
Sampling rate
Resolution
Current loop 4-20mA
Input impedance
Sampling rate
Resistance Measurement
Input impedance
Sampling rate

10ms
>20k
1s
0.1V
249
1s
10k
1s

Resistance can be measured in the range of 1k to 100k. For popular temperature sensors (e.g. Pt1000, NTC10K, NTC1K8,
Ni1000) fixed internal translation tables are provided. For all other temperature sensors translation tables can be defined in
the configuration tool and used on the device.

DI Digital Input, Counter Input (S0-Pulse)


DIs are fast binary inputs, which can also be used as counter inputs (S0). They follow the S0 specification for electric meters
and have a sampling rate of 10 ms. They change state at a load of 195 between the DI terminal and GND. Galvanically isolated sensors resp. switches must be connected.
Input voltage range of 0 bis 10V.
Sampling rate
S0 Counter input

10ms
rising edge triggered

L-VIS

Touch Panels

AO Analog Output
AOs are analog outputs with a signal range of 0 to 10V (12V), a resolution of 10 bits, and a maximum output current of 10 mA
(short circuit protected).
Signal range
Output current
Load impedance

0 10V, supports up to 12V


10mA max (short circuit protected)
4.7k minimum for linear output characteristic

L-DALI

Lighting Control

DO Digital Output
Relay and Triac outputs are supported.

Relay Output
Capacity

6A, 250VAC resp. 30VDC


16A, 250VAC resp. 30VDC

Routers, NIC

TRIAC Output
Capacity 1A, 24 bis 230VAC

Pressure Sensor
Differential Pressure Sensor with high/low connectors:

0500 Pa (0-2.0 W.C.)

Software
Tools

72

www.loytec.com

Gateways

buildings under control

73

L-GATE, L-INX, L-DALI, L-Proxy


L-GATE Gateways are conceived as universal gateways to map and connect data
points from different communication technologies. This mapping and connecting is summarized with the term Connections. The configuration tool can create
such connections either manually or automatically by using Smart Auto-Connect.
Local and Global Connections are distinguished. Local Connections allow connections between data points from different communication technologies located on
the very same device. A Global Connection provides similar functions like a Local
Connection, but can span across an IP network between two or more LOYTEC devices. A Global Connection establishes a data cloud defining a system wide name.
Data points that are members of this data cloud get their input values automatically updated or can send their output values for the other cloud members to update
their data point values.

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

Gateways

L-IOB

I/O Controllers/Modules

The L-INX Automation Servers support the same gateway functionalities as described for the L-GATE products. Specifically the LINX-100/101 and LINX-200/201
Automation Servers can be used as very cost effective gateway solutions. The LINX100/101 supports connectivity to LonMark-Systems, Modbus, M-Bus, and OPC
XML-DA. The LINX-200/201 supports connectivity to BACnet, Modbus, M-Bus, and
OPC XML-DA. In addition, the L-INX Automation Servers can integrate physical I/O
through L-IOB I/O Modules. These I/O data points can also be utilized in the gateway connections.
The L-INX Automation Servers and L-GATE Gateways are configured with the very
same configuration tool. Therefore the work flows are identical.

Gateways

LOYTECs L-INX and L-GATE product offering provides a wide spectrum of gateway
solutions for our customers to benefit from the variety and flexibility when picking
the most suitable model.

L-VIS

Touch Panels

Features

LGATE-950 LGATE-951 LGATE-900 LP-33E100

LON IP-852 - TP/FT-10

BACnet/IP - MS/TP

X*

X*

KNXnet/IP - KNX TP1

X*

X*

Modbus TCP - Modbus RTU

X*

X*

M-Bus

X*

X*

OPC XMLDA server

Ethernet switch

LINX100

LINX101

Lighting Control

Support of LIOBFT

L-DALI

Support of LIOBIP
L-WEB Visualization

LINX201

IP Router
Remote Network Interface

LINX200

* See block diagram page 76

A detailed description of the LINX100/101 and LINX200/201can be found in the


catalog section L-INX Automation Servers.
Routers, NIC

Also the L-DALI Lighting Controllers offer gateway functionality to integrate DALI
lighting control systems into LonMark Systems or BACnet networks. For further details, please see the catalog section L-DALI Lighting Control.

Software
Tools

The L-Proxy CEA-709 multi-port gateway (LP-33E100) is designed to connect separate LonMark systems. Up to five networks can be integrated via 2 TP/FT-10 and
3 IP-852 interfaces. A detailed description of the LP-33E100 can be found in the
catalog section Gateways.

74

www.loytec.com

L-GATE Gateways

LGATE-950/951

L-IOB
Gateways

Each LGATE-950/951 is equipped with two Ethernet ports including a built-in Ethernet switch.

I/O Controllers/Modules

y=f(x)

L-INX

RNI

Automation Servers

VNC

The gateway functionality allows data communication between all communication technologies available on the device. Different technology data points are
mapped through Local Connections on the device. The mapping of different technology data points on distributed devices is supported by Global Connections.
The universal gateways LGATE-950/951 also support Smart Auto-Connect - the
automatic generation of connections to substantially reduce engineering efforts
and cost. Optionally, mathematical objects can be applied within a connection to
calculate the data point output values depending on the formula used. All technology data points are automatically created as OPC XML-DA data.

L-ROC

The powerful universal gateways provide connectivity functions to concurrently


integrate CEA-709 (LonMark-Systems), BACnet, KNX, Modbus, and M-Bus subsystems. LonMark Systems can be integrated via IP-852 (Ethernet/IP) or TP/FT-10.
BACnet integration is supported through BACnet/IP (Ethernet/IP) or BACnet MS/
TP (RS-485). LGATE-950/951 features an integrated Remote Network Interface
(RNI) to access the TP/FT-10 channel on the device via Ethernet/IP. Both LGATE950 and LGATE-951 implement the BACnet Building Controller (B-BC) profile, can
be configured to be a BBMD and are BTL tested and WSPcert certified. In addition,
the universal gateways provide connectivity to KNXnet/IP and Modbus TCP via
Ethernet/IP and to Modbus RTU via RS-485. M-Bus and KNX TP1 device integration
needs optional interface modules.

Room Automation

The L-GATE Gateways LGATE-950 and LGATE-951 are powerful universal gateways
that can host user specific graphical pages to be used with LWEB-800/802. They
can simultaneously integrate and map data points from multiple open protocols.
Local operation and override is provided by the built-in jog dial and the backlit
display (128x64 pixels). Device and data point information is provided by the Web
interface and shown on the display by symbols and in text format.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709
KNX

The L-GATE devices provide fully featured AST functionality and integrate perfectly into the L-WEB System.

Compliant with ANSI/ASHRAE1352008 and ISO164845 standard


B-BC (BACnet Building Controller) functionality

BACnet Client Function (Write Property, Read Property, COV


Subscription)
BACnet Client Configuration with configuration tool (scan and
EDE import)

Automatic mapping of network variables to BACnet objects in


accordance with CEN/TS15231:2005
Alarming, Scheduling, and Trending (AST)
Event-driven e-mail notification
Stores customized graphical pages
Visualization of customized graphical pages through LWEB900
(building management) and LWEB800/WEB802
Built-in OPC XML-DA server

Supports TP/FT-10 or IP-852 (Ethernet/IP)

Access to network statistics

Support of dynamically created or static NVs

Integrated Web server for the device configuration and for


monitoring of data points

Support of CEA709 user-defined NVs (UNVTs) and Configuration Properties (SCPTs, UCPTs)
Remote Network Interface (RNI) with 2 MNI devices
Support of KNX/IP directly, KNX TP1 via LKNX-300 Interface

Modbus TCP and Modbus RTU (Master or Slave)

Local and remote access to information about device status and


data points
128x64 graphic display with backlight

Software
Tools

M-Bus Master according to EN13757-3, connection via optional


MBus Converter (e.g. LMBUS80)

Manual operation using the jog dial or VNC client

Routers, NIC

Compliant with CEA709, CEA852 and ISO/IEC14908 Standard


(LonMark System)

Math objects to execute mathematical operations on data


points

L-DALI

Supports BACnet MS/TP or BACnet/IP

Automatic creation of Local Connections


(Smart Auto-Connect)

Lighting Control

Supports BBMD (BACnet Broadcast Management Device)

L-VIS

Universal gateway

Touch Panels

Features

Memory expansion with microSD card


Configurable via Ethernet/IP, USB, or TP/FT10

buildings under control

75

L-WEB

Building Management

L-GATE Gateways

LGATE-950/951
LGATE-950

2 x Ethernet / IP

L-ROC

Room Automation

Web
Interface

IP-852

Modbus
TCP

BACnet/IP

KNXnet/IP

SWITCH

Alarming
Scheduling
Trending

LGATE-951

Graphics
Graphics
Graphics

E-Mail

2 x Ethernet / IP
Web
Interface

OPC XML-DA
Server

IP-852

Modbus
TCP

BACnet/IP

Data Point Abstraction Layer

Automation Servers

RNI

L-INX

TP/FT-10

Modbus
RTU

Alarming
Scheduling
Trending

E-Mail

RNI

M-Bus
KNX TP1

EXT

KNXnet/IP

OPC XML-DA
Server

Data Point Abstraction Layer


y=f(x)

BACnet
MS/TP

Graphics
Graphics
Graphics

SWITCH

y=f(x)

TP/FT-10

BACnet
MS/TP

Modbus
RTU

M-Bus
KNX TP1

RS-485

V1.2.2

M-Bus
KNX TP1

EXT1

EXT2

V1.2.2

Dimensions (mm)

159x100x75 (LxWxH), DIM005

Power supply

24VDC / 24VAC 10%, typ. 2.5W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

2xEthernet (100Base-T)
OPC XMLDA
LonMark IP-852**
BACnet/IP***
KNXnet/IP
Modbus TCP (Master or Slave),
HTTP, FTP, SSH, HTTPS, Firewall
2xUSB-A, 1xUSB-B (PC)

Gateways

L-IOB

I/O Controllers/Modules

Specifications

1xTP/FT-10** (LonMark System)


1xBACnet MS/TP*** (LGATE-950 only)
1xModbus RTU (Master or Slave) (LGATE-950 only)
1xBACnet MS/TP or Modubus RTU (LGATE-951 only)
1xEXT (LGATE-950 only)//2xEXT* (LGATE-951 only)
EXT port extension alternatively for:
M-Bus, Master EN13757-3 (needs LMBUS20/80)
KNX TP1 (needs LKNX-300)

* Only one LKNX-300 and one L-MBUS-20/80 per LGATE-951, only one interface per EXT port
** LonMark IP-852 or TP/FT-10 (no router)
*** BACnet/IP or BACnet MS/TP (no router)
Tools

LINX/L-GATE Configurator

Remote Network Interface

1 RNI with 2 MNI devices

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Resource limits

76

OPC XMLDA data points

5000

LonMark Calendar

1 (25 calendar templates)

BACnet objects

1000 (analog, binary, multi-state)

LonMark Scheduler

100

BACnet client mappings

1000

LonMark Alarm Server

BACnet calendar objects

25

E-mail templates

100

BACnet scheduler objects

100 (64 data points per object)

Math objects

100

BACnet notification classes

32

Alarm logs

10

Trend logs (BACnet or generically)

512 (4 000000 logs, 60MB)

M-Bus data points

1000

Total trended data points

512

Modbus data points

2000

CEA709 network variables (NVs)

2000

KNX TP1 data points

1000

CEA709 Alias NVs

2000

KNXnet/IP data points

1000

CEA709 External NVs (polling)

1000

Connections (Local / Global)

2000 / 250

CEA709 address table entries

1000 (non-ECS mode: 15)

Number of L-WEB clients

32 (simultaneously)

Order number

Product description

LGATE-950

Universal Gateway

LGATE-951

Universal Gateway

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LOPC-BR800

OPC Bridge (PC software) to connect OPC DA clients (COM/DCOM) with LINX Automation Servers

LMBUS20

M-Bus level converter for 20 M-Bus devices

LMBUS80

M-Bus level converter for 80 M-Bus devices

LKNX-300

KNX interface to connect KNXTP1 devices

www.loytec.com

L-GATE Gateways

LGATE-900
The LGATE-900 Gateway is a powerful gateway to interconnect data points from
LonMark Systems (CEA-709) with BACnet data points.

Gateways

LVIS-ME215

LVIS-3E115
LOYTEC
www.loytec.com

LOYTEC
www.loytec.com

Internet / Intranet
Router / Firewall

LIP-ME201

L-IP

LIP-33ECTB

L-IP

21
Ethernet, IP-852

Ethernet, BACnet/IP

L-INX
1

L-GATE

L-INX
1234

L-IOB

LINX-120

L-INX
21

BACnet MS/TP

L-INX
1234

L-IOB

TP/FT-10

BACnet
MS/TP

TP/FT-10

TP/FT-10

L-DALI

Lighting Control

BACnet
MS/TP

LINX-100

L-VIS

LINX-220

Touch Panels

LGATE-900
LINX-200

L-IOB

CEA-709

I/O Controllers/Modules

BACnet

L-INX

y=f(x)

Automation Servers

The L-GATE devices provide fully featured AST functionality and integrate perfectly into the L-WEB System.

L-ROC

The gateway functionality is realized through connections that connect Network


Variables or even configuration properties from the LonMark System to BACnet
server objects or client maps on the BACnet side. Data points hosted on the L-GATE
are mapped through Local Connections on the device. The mapping of data points
on distributed devices is supported by Global Connections. The L-GATE also supports Smart Auto-Connect - the automatic generation of connections to substantially reduce engineering efforts and cost. Optionally, mathematical objects can be
applied within a connection to calculate the data point output values depending
on the formula used. All technology data points are automatically created as OPC
XML-DA data points.

Room Automation

LonMark Systems can be integrated via IP-852 (Ethernet/IP) or TP/FT-10. BACnet


integration is supported through BACnet/IP (Ethernet/IP) or BACnet MS/TP (RS485). The LGATE-900 implements the BACnet Building Controller (B-BC) profile and
is BTL tested and WSPcert certified.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709
KNX

Features
Interconnection of BACnet with LonMark Systems

(LonMark System)
Supports TP/FT-10 or IP-852 (Ethernet/IP)

Compliant with ANSI/ASHRAE135-2008 and ISO16484-5 standard

Support of user-defined NVs (UNVTs) and Configuration Properties (SCPTs, UCPTs)

B-BC (BACnet Building Controller) functionality, BTL certified

Support of dynamically created and static NVs

Math objects to execute mathematical operations on data


points

Supports BACnet MS/TP or BACnet/IP

Alarming, Scheduling, and Trending (AST)

BACnet Client Function (Write Property, Read Property, COV


Subscription)

Event-driven e-mail notification

BACnet Client Configuration with configuration tool (scan and


EDE import)

Integrated Web server for the device configuration and for


monitoring of data points

Compliant with CEA709, CEA852 and ISO/IEC14908 Standard

Built-in OPC XML-DA server

Configurable via Ethernet/IP or TP/FT10

buildings under control

77

Software
Tools

Supports BBMD (BACnet Broadcast Management Device)

Routers, NIC

Automatic mapping of network variables to BACnet objects in


accordance with CEN/TS15231:2005

L-WEB

Building Management

L-GATE Gateways

LGATE-900
LGATE-900

L-ROC

Room Automation

Ethernet / IP

IP-852

BACnet/IP

Alarming
Scheduling
Trending

Web
Interface

E-Mail

OPC XML-DA
Server

Automation Servers

Data Point Abstraction Layer

L-INX

y=f(x)

TP/FT-10

BACnet
MS/TP

I/O Controllers/Modules

V1.2.2

Gateways

L-IOB

Specifications
Dimensions (mm)

107x100x60 (LxWxH), DIM009

Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
LonMark IP-852**, BACnet/IP*, HTTP, FTP
1xTP/FT-10** (LonMark System)
1xBACnet MS/TP*
* BACnet IP or BACnet MS/TP
**LonMark IP-852 or TP/FT-10

Tools

LINX/L-GATE Configurator

CEA709 Network variables NVs

1000

BACnet objects

750 (analog, binary, multi-state)

CEA709 Alias NVs

1000

BACnet client mappings

750

CEA709 External NVs (polling)

1000

BACnet calendar objects

25

CEA709 address table entries

512 (non-ECS mode: 15)

BACnet scheduler objects

100 (64 data points per object)

CEA709 LonMark Calendar

1 (25 calendar templates)

BACnet notification classes

32

CEA709 LonMark Scheduler

100

Trend logs (BACnet or generically)

100 (130000 logs, 2MB)

CEA709 LonMark Alarm Server

Total trended data points

256

E-mail templates

100

Math objects

100

OPC-Tags

500

Alarm logs

10

Connections (Local / Global)

1000 / 250

Order number

Product description

LGATE-900

CEA709 / BACnet Gateway

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Resource limits

78

www.loytec.com

L-Proxy CEA-709 Multiport Gateway

LP-33E100

LONMARK IP-852

TP/FT-10

L-IP
1
DOMAIN 2

TP/FT-10

L-IOB

L-Proxy can be connected to an Ethernet/IP channel (LonMark IP-852) and to


TP/FT-10 channels. Static and dynamic NVs form the interface. In addition to
SNVTs, User Defined NVs (UNVTs) and Configuration Properties (SCPTs, UCPTs) are
supported.

I/O Controllers/Modules

DOMAIN 1

Network Communication

L-INX

TP/FT-10

Automation Servers

DOMAIN 0

L-ROC

L-Proxy
21

L-Proxy is the perfect solution for data exchange between independent LonMark
Systems. Whether different phases of construction, different systems, or expanded
networks with multiple LNS databases - L-Proxy connects. L-Proxy allows to share
common data (e.g. from a weather station) across network boundaries.

Room Automation

The L-Proxy Multiport Gateway exchanges data packets across domain boundaries in LonMark Systems. Network variables or configuration properties are used to
transfer data. L-Proxy represents up to five independent network nodes (one on
each TP/FT-10 channel and up to three on the IP-852 channel). Every L-Proxy node
can be configured in different domains and therefore in different LNS databases.
Individually created input and output network variables or configuration properties on every L-Proxy node are connected internally between the L-Proxy nodes
with a configuration tool supplied with the unit.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709
KNX

L-IP
1
DOMAIN 3

TP/FT-10

Gateways

L-IP
1
DOMAIN 4

TP/FT-10

Features

Supports TP/FT-10 or IP-852 (CEA-852 Ethernet)

Support of user defined NVs (UNVTs) and configuration properties (SCPTs, UCPTs)

Data exchange via network variables accross multiple domains


Extends the address tables of Neuron Chip based nodes

Represents up to five independent network nodes


Configuration tool usable with and without LNS

L-DALI

Lighting Control

Specifications
107x100x60 (LxWxH), DIM009

Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
LonMark IP-852, HTTP, FTP
2xTP/FT-10 (LonMark System)

Tools

L-Proxy Configurator

Routers, NIC

Dimensions (mm)

Resource limits
Network variables NVs

512 per L-Proxy node

External NVs (polling)

512 per L-Proxy node

Alias NVs

512 per L-Proxy node

Address table entries

512 (non-ECS mode: 15) per L-Proxy


node

Configuration

LP-33E100

CEA-709 Multiport Gateway

buildings under control

Software
Tools

Order number

L-VIS

Support of dynamically created network variables or static network variables

Touch Panels

Compliant with CEA-709, CEA-852, and ISO/IEC14908-1 standard (LonMark System)

79

LKNX-300

The KNX-Interface LKNX-300 allows the LINX12x/15x/22x Automation Servers,


the LROC-100/150 Room Controllers, and the LGATE-95x Universal Gateways to
interface to KNX devices connected to a KNX TP1 (EIB) Bus. The LKNX-300 Interface
needs to be connected to the EXT-Port on the L-INX/L-ROC/L-GATE devices.

L-ROC

Room Automation

L-WEB

Building Management

BACnet
Modbus
CEA709 M-Bus
KNX

KNX TP1 Interface

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

For the KNX integration LOYTECs L-INX/L-ROC/L-GATE devices use an ETS4 project.
The project data is exported as XML from the ETS4 and then imported the LOYTEC
L-INX/L-GATE Configurator. Thus, up to 1000 data points from the KNX network
can be used by the L-INX/L-ROC/L-GATE devices on each port supporting KNXnet/
IP or KNX TP1.

Gateways

Features
KNX TP1 Interface for LINX12x/15x/22x, LROC-100/150 and LGATE-95x
Access to a maximum of 1000 KNX data points via KNX TP1 (L-INX/L-ROC/L-GATE)
Configurable through ETS4 software via XML import

L-VIS

Touch Panels

Connected to the L-INX Automation Server, L-ROC Room Controller or LGATE-95x Gateway via port EXT

Routers, NIC

L-DALI

Lighting Control

Specifications
Dimensions (mm)

55x100x60 (LxWxH), DIM025

Power supply

Via the KNX TP1 bus

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Installation

Attachable or connected with a 3-wire cable, max. 1m

Interfaces

1xEXT
1xKNX TP1
LIOB-Connect is looped through the device

Baud rate

9600baud

Tools

LINX/L-GATE Configurator

For use with

LINX-12x, LINX-15x, LINX-22x, LROC-100, LROC-150, LGATE-950, LGATE-951

Resource limits
Number of KNX TP1 data points

1000

Product description

LKNX-300

KNX interface to connect KNXTP1 devices

Software
Tools

Order number

80

www.loytec.com

M-Bus Level Converter

L-MBUS20, L-MBUS80

The RS-232 port is used for connecting to the CEA709 Automation Servers
LINX100, LINX-101, LINX-110, and LINX-111 or BACnet Automation Servers
LINX200, LINX201, LINX-210, and LINX-211. The interface is galvanically isolated.

L-ROC

RS-232 Connection

Room Automation

The L-MBUS level converters are used to connect an M-Bus network to a L-INX
Automation Server. Up to 20 or 80 M-Bus devices can be connected via L-MBUS20
and L-MBUS80.

L-WEB

Modbus
M-Bus

Building Management

BACnet
CEA709
KNX

TTL Connection
L-INX

Automation Servers

The TTL port is used to connect to the LINX-120/121, LINX-220/221 Automation


Servers, and also to the LROC-150 Room Controller. The interface is galvanically
isolated.

L-IOB

I/O Controllers/Modules

POWER

L-MBUS

MBUS Interface
Made in Austria

Port 2

- +
~ ~

15 16 17

RS-232

Port 2

TXD

L-MBUS20
GND

12-35 VDC INPUT or


12-24 VAC, 40-70 Hz

LOYTEC
www.loytec.com
24 VAC/DC

RXD

LOYTEC
www.loytec.com

LINX-100

status

-~

serial
RS-232

Port 2

100Base-T

Port 1 (TTL) Port 1

power

SHORT
POWER

L-MBUS20

CS/RNI

TXD

FT
B A
5

MadeMade
in Austria
in EC

LOYTEC
www.loytec.com

ACT

GND

-~

+~

B A
1

SHORT
POWER

2 1

RS-485

MBUS Interface
Automation
Server
LINK

CNIP

ACT

RXD

OPC

24 VAC/DC

+~

L-MBUS
L-INX

DC
AC

MBUS

POWER

Port 1 (TTL) Port 1

Port 2

kWh

MBUS

Gateways

M-Bus

D-SUB 9
Modem Conversion Cable, F/F

GAS
L-VIS

Touch Panels

General Specifications
Dimensions (mm)

107x100x60 (LxWxH), DIM024

Power supply

24VDC / 24VAC 10%

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)
Lighting Control

L-MBUS20

L-MBUS80

Power consumption

9.6W

14.4W

Baud rate

300 to 9600baud

300 to 9600baud

Interfaces

1xTTL or 1xEIA-232 (RS-232), galvanically isolated


1xM-Bus

1xTTL or 1xEIA-232 (RS-232), galvanically isolated


1xM-Bus

For use with

L-INX Automation Server, LROC-150, LGATE-950, LGATE-951

Routers, NIC

Types

L-DALI

Specifications

Resource limits
M-Bus meter

Up to 20

Up to 80

Product description

L-MBUS20

M-Bus level converter for 20 M-Bus devices

L-MBUS80

M-Bus level converter for 80 M-Bus devices

buildings under control

Software
Tools

Order number

81

LPOW-2415A/LPOW-2415B
LPOW-2415A

LPOW-2415A is used to supply power to LOYTEC devices with the LOYTEC


LIOBConnect side outlet such as the L-INX Automation Servers LINX120, LINX121,
LINX150, LINX151, LINX220, and LINX-221 and the Room Controllers LROC-100
and LROC150. Even L-IOB I/O Modules and Controllers can be powered by the
LPOW-2415A.

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

BACnet Modbus
CEA709
M-Bus
KNX

L-POW Power Supply

L-INX

LPOW-2415A

Made in Austria

status

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

LOYTEC
www.loytec.com

LINX-120

L-POW

USB

I/O Controllers/Modules

85-240VAC
50/60 Hz

Output
24VDC/15W

LIOB-FT

FUSE 6A

EXT

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

1
FT

LIOB-FT

MODBUS

FUSE 6A

Made in Austria

6A

LIOB-100

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

status

LOYTEC
www.loytec.com

status

LIOB-100

status

L-IOB

L-IOB

I/O Module

4
EXT

UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

I/O Module

0-10V OUT

DI2 AO1

AO2

Made in Austria

6A

status

LOYTEC
www.loytec.com

Automation Server

PLC OPC

Ethernet 1 Ethernet 2

MODBUS

L-INX

ACT

Power Supply
Input
N
L

FT

MICROSD

LINK

UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

UI6 UI7

UI8

DIGITAL IN
DI1

0-10V OUT

DI2 AO1

AO2

L-IOB

LPOW-2415B
The power supply LPOW-2415B provides 24VDC via a plug-in screw terminal. It is
used to supply power to LOYTEC devices with a separate power terminal of 24VDC.

LPOW-2415B

Made in Austria

status

LOYTEC
www.loytec.com

L-IP
ACT

Gateways

L-POW

85-240VAC
50/60 Hz

24VDC/15W
GND +

Made in EC

2 1

Power Supply
Input
N
L

CEA-709/IP Router
CNIP

ACT

FT
1

B A
2

FT
B A
5

LINK
ACT
SERVER

serial

LOYTEC
www.loytec.com

100Base-T

LIP-33ECTB

power

status

12-35 VDC INPUT or


12-24 VAC, 40-70 Hz

- +
~ ~

DC
AC

15 16 17

Energy -Efficient
L-VIS

Touch Panels

The LPOW-2415 are highly efficient switching power supplies. Their efficiency is
approximately 80%. The input voltage range of 85240VAC (5060 Hz) allows
worldwide use.

L-DALI

Lighting Control

Specifications LPOW-2415A
Dimensions (mm)

55x100x60 (LxWxH), DIM028

To be used for

LIOB-Connect devices for power supply with 24VDC, max. 15W (625mA)

Input voltage

85-240 VAC 50-60Hz

Supply voltage

24VDC 15W via LIOBConnect

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

For use with

LINX-12x/15x/22x, LROC-100/150, LGATE-950/951, LIOB I/O Modules and Controllers

Software
Tools

Routers, NIC

Specifications LPOW-2415B

82

Dimensions (mm)

55x100x60 (LxWxH), DIM029

To be used for

Devices for power supply with 24VDC and max. 15W (625mA)

Input voltage

85-240 VAC 50-60Hz

Supply voltage

24VDC 15W with plugable screw terminal

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

For use with

LOYTEC devices except of LIOBConnect I/O Modules

Order number

Product description

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

www.loytec.com

L-VIS Touch Panels

buildings under control

83

LVIS-100-RE

Modbus
M-Bus

The LVIS-100-RE Room Edition is the perfect solution for room operation of CEA709based room control systems (LonMark Systems) via touch panel. All control functions are processed by the room control system and operated via the L-VIS Room
Edition. The LVIS-100-RE contains a predefined, static network variable interface,
which cannot be changed.

L-ROC

Room Automation

L-WEB

Building Management

BACnet
CEA709
KNX

L-VIS Touch Panels

Predefined Graphical Pages for Room Operation

L-INX

Automation Servers

Predefined graphical pages are supplied for the Room Edition of the L-VIS Touch
Panel to allow a quick implementation of room control functions. The pages include
functions for up to two lighting circuits, two sunblinds, and HVAC operation for the
room. Display of weather data provided by an available weather station in the LonMark System is also possible. Additional pages are created to display local trend
logs of the sun blinds and room temperatures.
The L-VIS Room Edition provides schedulers which can be parameterized via the
CEA709 network or the display of the touch panel.

I/O Controllers/Modules

The graphic project hosted by the L-VIS Room Edition may be edited with the L-VIS
configuration tool, depending on the requirements.

L-IOB

VNC

RNI

y=f(x)

Page Configuration with a Software Tool


As soon as the L-VIS Room Edition is turned on, the graphic project supplied with
the unit can be adjusted via the display of the touch panel according to the room
conditions. The adjustments happen without the use of a software tool.

Static Network Interface

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

LVIS-100-RE provides a static NV interface for easy integration into a LonMark System. The Room Edition L-VIS is compatible with a variety of existing room controllers from different manufacturers. If more flexibility is required by the application,
we recommend to use the LVIS-3E100 Touch Panel.

Features

Software
Tools

Routers, NIC

TFT touch display (320x240) with dimmable backlight

84

Anodized aluminium front frame

Compliant with CEA709, CEA852 und ISO/IEC14908 standard


(LonMark System)

Flush-mounting in combination with the mounting frame LVISFRAME1

Fixed NV interface for an easy handling


Remote Network Interface (RNI) with 2MNI devices

External temperature sensor LTEMP1 (optional) and input for


external light switch

Integrated Web server for the device configuration and for


monitoring of data points

Finished graphical pages for room control

Built-in OPC XMLDA server and client

Graphical pages may be configured with the L-VIS Configuration Tool

Integrated VNC server


Supports TP/FT-10 or IP-852 (Ethernet/IP)

www.loytec.com

L-WEB

LVIS-100-RE

Building Management

L-VIS Touch Panels

LVIS-100-RE
Ethernet / IP

L-ROC

Alarming
Scheduling
Trending

Room Automation

OPC XML-DA
Client

IP-852

Graphics

OPC XML-DA
Server

E-Mail

Data Point Abstraction Layer

5.7

Touch

Backlight

VISUALIZATION

Digital
Input 0

Digital
Input 1

DIGIN0

L-TEMP1
Sensors

L-INX

TP/FT-10

Automation Servers

y=f(x)

RNI

Web
User Interface

DIGIN1

V1.2

I/O Controllers/Modules

Specifications
LVIS-100-RE

Dimensions (mm)

210x164x63 (LxWxH), DIM001

Dimensions cut-out (mm)

180x150x57 (LxWxH)

Display resolution

320x240, 256 colors

Interfaces

1xEthernet (100Base-T)
LonMark IP-852*, HTTP, FTP, SMTP, NTP, VNC
1xTP/FT-10*
2xDigital Input
1xDigital interface for up to 4 L-TEMP1 sensors

Gateways

5.7" (14.5mm)

Type

L-IOB

Screen size

* LonMark IP-852 or TP/FT-10


Power supply

20-35VDC / 24VAC 10%, typ. 3W, backlight on: 8 W

Operating conditions

+10C bis 40C, 10-90% RH @ 50C, non condensing

Degree of protection

Front: IP54 / back: IP10

Tools

LVIS/LWEB Configurator

L-VIS

1 RNI with 2 MNI devices


Touch Panels

CEA709 Remote Network Interface (RNI)

Resource limits
Fixed static NV interface

Alias NVs

512

Address table entries

15 (non-ECS mode)

LonMark Calendar

1 (25 calendar templates)

LonMark Scheduler

10

LonMark Alarm Server

Email templates

100

Math objects

100

Alarm logs

10

Routers, NIC

Network variables (NVs)

L-DALI

16

Lighting Control

VNC-Clients

Product description

LVIS-100-RE

CEA709 Touch Panel Room Edition with 5.7" display (LonMark System)

LVIS-FRAME1

Mounting frame for 5.7" Touch Panels

LTEMP1

External temperature sensor

buildings under control

Software
Tools

Order number

85

LVIS-3E100/3E112/3E115

Modbus
M-Bus

L-VIS Touch Panels for LonMark Systems are ideally suited for visualization and
operation of various applications in building automation. L-VIS Touch Panels visualize building systems, can be used as room operator panels, for use in hospital
operation or isolation rooms, conference and reception areas. The fully customizeable user screens can show dynamic pages that are easy to navigate. L-VIS Touch
Panels make use of an extremely low power embedded controller platform and
operating system. This makes L-VIS resistant against problems when re-booting
after power outage and also resistant against any viruses.

L-ROC

Room Automation

L-WEB

Building Management

BACnet
CEA709
KNX

L-VIS Touch Panels

L-INX

Automation Servers

L-VIS impresses with its timeless design, harmonic integration into modern and historical architecture, and with its extremely user friendly concept. The shallow installation depth and low thermal power loss allow mounting in almost any location.

Three Different Sizes


L-VIS Touch Panels are available in three different sizes:

L-IOB

I/O Controllers/Modules

LVIS-3E100

5.7

Touch Display

320 x 240

256 colors

LVIS-3E112 12.1

Touch Display

800 x 600

65536 colors

LVIS-3E115 15

Touch Display

1024 x 768

65536 colors

Dynamic Graphical Pages

Gateways

The graphical pages may consist of multiple dynamic graphical controls that show
the current plant status in real time. It is also possible to access decentralized
schedules, alarm servers or trends. The graphical projects are designed with the
L-VIS/L-WEB configuration tool free of charge. Without any know-how in HTML or
Java, user specific graphical pages can be created. Dynamic information is shown
through value or text controls, changing symbols, bar charts, trend views, alarm
and event lists, or schedule controls. The L-VIS/L-WEB configuration tool allows for
using most of the pixel graphic formats (GIF, JPG, BMP, TIF, PNG) or vector graphics
(SVG).

Playback of Audio Files and Streams

L-VIS

Touch Panels

The L-VIS Touch Panel supports the playback of stereo MP3, WAV and MP3 streaming (for example webradio). The playback will be started or stopped by the respective action object. The action object is linked to one of the available audio files or to
the URL of an MP3 stream. When accessing a playback via LWEB-800 or LWEB-802,
it will be executed locally on the client.
VNC

L-DALI

Lighting Control

y=f(x)

RNI

Automatic Page Generation


Pages including data point names and values, alarm views, schedules or trends can
be created automatically by the L-VIS/L-WEB configuration tool. This significantly
reduces engineering time and cost.

Connectivity and Data Points


The L-VIS Touch Panels support connectivity to LonMark IP-852 (Ethernet/IP) or
TP/FT-10 channels. The integrated remote network interface (Ethernet/IP) provides
remote access to the device TP/FT-10 channel for configuration, service and maintenance purposes.

Software
Tools

Routers, NIC

Mathematical objects can calculate arbitrarily any kind of formula including any
data point available on the device. The resulting data point value can then be either
shown on the page or provided via an output Network Variable. Network Variables
are automatically mapped to OPC XML-DA data points that can be accessed via
Web services.

86

www.loytec.com

The L-VIS devices provide fully featured AST functionality and integrate perfectly
into the L-WEB System.

L-ROC

Room Automation

The LVIS-3E112/3E115 devices are equipped with two Ethernet ports including a
built-in Ethernet switch. This allows daisy chaining of up to 20 LOYTEC devices featuring dual Ethernet in an Ethernet ring.The Ethernet ring is connected with each
end to an Ethernet switch supporting RSTP (Rapid Spanning Tree Protocol). This
ensures reliable communication and system availability and reduced wiring efforts.

L-WEB

LVIS-3E100/3E112/3E115

Building Management

L-VIS Touch Panels

LVIS-3E100 comes with one Ethernet port.

L-INX

Automation Servers

Features
Event-driven e-mail notification

Flush-mounting in combination with the mounting frame


Stores customized graphical pages

Math objects to execute mathematical operations on data


points

Visualization of customized graphical pages through built-in


touch panel, LWEB900 (building management), and LWEB800/
LWEB-802

Compliant with CEA709, CEA852 and ISO/IEC14908 Standard


(LonMark System)
Supports TP/FT-10 or IP-852 (Ethernet/IP)

Device configuration and graphical page creation with the


L-VIS/L-WEB configuration tool free of charge

Support of dynamically created network variables or static network variables

Supports all popular graphic file formats such as BMP, ICO, JPEG,
TIFF, PNG, MNG, GIF

Support of user-defined NVs (UNVTs) and Configuration Properties (SCPTs, UCPTs)

Support of SVG vector graphics

Remote Network Interface (RNI) with 2 MNI devices

Supports Alpha Blending

Integrated Web server for the device configuration and for


monitoring of data points

Supports popular font types such as TrueType, Type-1, BDF, PCF,


and OTF

Access to network statistics

Built-in OPC XML-DA server

Playback of audio files and streams

L-VIS

Configurable via Ethernet/IP or TP/FT10

Touch Panels

Supports Unicode text


Built-in OPC XML-DA client

LVIS-3E100
Ethernet / IP

Graphics

OPC XML-DA
Server

E-Mail

IP-852

Audio

Data Point Abstraction Layer


y=f(x)

Touch

VISUALIZATION

Backlight

Digital
Input 0

Digital
Input 1

DIGIN0

OPC XML-DA
Client

Alarming
Scheduling
Trending

Graphics

OPC XML-DA
Server

E-Mail

L-TEMP1
Sensors

DIGIN1

y=f(x)

RNI

TP/FT-10

12.1/15 Touch
VISUALIZATION

V1.2.2

Backlight

Digital
Input 0

Digital
Input 1

DIGIN0

Routers, NIC

5.7

Web
Interface

SWITCH

Data Point Abstraction Layer

RNI

TP/FT-10

2 x Ethernet / IP

L-DALI

Alarming
Scheduling
Trending

LVIS-3E112
LVIS-3E115

Lighting Control

OPC XML-DA
Client

IP-852

Web
Interface

Gateways

Anodized aluminium front frame

L-IOB

Alarming, Scheduling, and Trending (AST)

I/O Controllers/Modules

High resolution TFT touch display with dimmable backlight

L-TEMP1
Sensors

DIGIN1

V1.2.2

Software
Tools

buildings under control

87

LVIS-3E100/3E112/3E115
Specifications
Type

LVIS-3E100

LVIS-3E112

LVIS-3E115

Screen size

5.7" (14.5mm)

12.1" (30.7mm)

15" (38.1mm)

Dimensions (mm)

210x164x63 (LxWxH),
DIM001

329x268.3x65 (LxWxH),
DIM002

394x318x65 (LxWxH), DIM003

Dimensions cut-out (mm)

180x150x57 (LxWxH)

300x250x61 (LxWxH)

355x295x61 (LxWxH)

Display resolution

320x240, 256 colors

800x600, 65536 colors

1024x768, 65536 colors

Interfaces

1xEthernet (100Base-T)
LonMark IP-852, HTTP, FTP,
SMTP, NTP, VNC
1xTP/FT-10
2xDigital Input
1xDigital interface for up to 4
L-TEMP1 sensors

2xEthernet (100Base-T), Switch


LonMark IP-852, HTTP, FTP,
HTTPS, SMTP, NTP, VNC
1xTP/FT-10
2xDigital Input
1xDigital interface for up to 4
L-TEMP1 sensors
1xEIA-485 (RS-485)
2xUSB-A, 1xUSB-B (PC)
speaker, audio output

2xEthernet (100Base-T), Switch


LonMark IP-852, HTTP, FTP,
HTTPS, SMTP, NTP, VNC
1xTP/FT-10
2xDigital Input
1xDigital interface for up to 4 LTEMP1 sensors
1xEIA-485 (RS-485)
2xUSB-A, 1xUSB-B (PC)
speaker, audio output

CEA-709 Remote Network


Interface

1 RNI with 2 MNI devices

1 RNI with 2 MNI devices

1 RNI with 2 MNI devices

Power supply

20-35VDC / 24VAC 10%


typ. 3W, backlight on: 8 W

24VDC 10% or 85-240 VAC


2W, backlight on: 13W

24VDC 10% or 85-240 VAC


2W, backlight on: 16W

Operating conditions

+10C bis 40C, 10-90% RH @ 50C, non condensing

Degree of protection

Front: IP54 / back: IP10

Tools

L-VIS/L-WEB Configurator

Gateways

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

L-VIS Touch Panels

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Resource limits

88

OPC XML-DA data points

2000

10000

10000

VNC-Clients

16

16

16

Network variables (NVs)

1000

1000

1000

Alias NVs

1000

1000

1000

Address table entries

524 (Non-ECS mode: 15)

524 (Non-ECS mode: 15)

524 (Non-ECS mode: 15)

LonMark Calendar

1 (25 calendar templates)

1 (25 calendar templates)

1 (25 calendar templates)

LonMark Scheduler

100

100

100

LonMark Alarm Server

Email templates

100

100

100

Math objects

100

100

100

Alarm logs

20

100

100

Trend logs

100 (390000 Logs, 6 MB)

512 (4000000 logs, 60 MB)

512 (4000000 logs, 60 MB)

Total trended data points

256

512

512

Connections (Local/Global)

1000/250

2000/250

2000/250

Number of L-WEB clients

15 (simultaneously)

32 (simultaneously)

32 (simultaneously)

Order number

Product description

LVIS-3E100

CEA-709 Touch Panel with 5.7" display (LonMark System)

LVIS-3E112

CEA-709 Touch Panel with 12.1" display (LonMark System)

LVIS-3E115

CEA-709 Touch Panel with 15" display (LonMark System)

LVIS-FRAME1

Mounting frame for 5.7" Touch Panels

LVIS-FRAME12

Mounting frame for 12.1" Touch Panels

LVIS-FRAME15

Mounting frame for 15" Touch Panels

L-TEMP1

External temperature sensor

www.loytec.com

LVIS-ME200/ME212/ME215

Touch Display

320 x 240

256 colors

LVIS-ME212 12.1

Touch Display

800 x 600

65536 colors

LVIS-ME215 15

Touch Display

1024 x 768

65536 colors

L-IOB

5.7

I/O Controllers/Modules

LVIS-ME200

L-INX

L-VIS Touch Panels are available in three different sizes:

Automation Servers

Three Different Sizes

L-ROC

L-VIS impresses with its timeless design, harmonic integration into modern and
historical architecture, and with its extremely user friendly concept. The shallow
installation depth and low thermal power loss allow mounting in almost any location.

Room Automation

L-VIS Touch Panels for BACnet networks are ideally suited for visualization and
operation of various applications in building automation. L-VIS Touch Panels visualize building systems, can be used as room operator panels, for use in hospital
operation or isolation rooms, conference and reception areas. The fully customizeable user screens can show dynamic pages that are easy to navigate. L-VIS Touch
Panels make use of an extremely low power embedded controller platform utilizing an embedded operating system. This makes LVIS resistant against problems
when re-booting after power outage and also resistant against any viruses.

L-WEB

L-VIS Touch Panels

Building Management

BACnet
Modbus
CEA709 M-Bus
KNX

Dynamic Graphical Pages

Gateways

The graphical pages may consist of multiple dynamic graphical controls that show
the current plant status in real time. It is also possible to access decentralized
schedules, alarm servers or trends. The graphical projects are designed with the
L-VIS/L-WEB configuration tool free of charge. Without any know-how in HTML or
Java, user specific graphical pages can be created. Dynamic information is shown
through value or text controls, changing symbols, bar charts, trend views, alarm
and event lists, or schedule controls. The L-VIS/L-WEB configuration tool allows for
using most of the pixel graphic formats (GIF, JPG, BMP, TIF, PNG) or vector graphics
(SVG).

Playback of Audio Files and Streams


L-VIS

y=f(x)

BACnet

Touch Panels

VNC

The L-VIS Touch Panel supports the playback of stereo MP3, WAV and MP3 streaming (for example webradio). The playback will be started or stopped by the respective action object. The action object is linked to one of the available audio files
or to the URL of an MP3 stream. When accessing a playback via L-WEB, it will be
executed locally on the client.

Automatic Page Generation

The L-VIS Touch Panels support connectivity to BACnet/IP and BACnet MS/TP and
implement the BACnet Building Controller (B-BC) profile. They include a fully featured built-in BACnet/IP to MS/TP router with BBMD and slave proxy functionality.

Routers, NIC

Mathematical objects can calculate arbitrarily any kind of formula including any
data point available on the device. The resulting data point value can then be either
shown on the page or provided via a BACnet object. All BACnet server objects are
automatically mapped to OPC XML-DA data points that can be accessed via Web
services.

L-DALI

Connectivity and Data Points

Lighting Control

Pages including data point names and values, alarm views, schedules or trends can
be created automatically by the L-VIS/L-WEB configuration tool. This significantly
reduces engineering time and cost.

Software
Tools

buildings under control

89

LVIS-ME200/ME212/ME215
The L-VIS devices provide fully featured AST functionality and integrate perfectly
into the L-WEB System.
The LVIS-ME212/ME215 devices are equipped with two Ethernet ports including
a built-in Ethernet switch. This allows daisy chaining of up to 20 LOYTEC devices
featuring dual Ethernet in an Ethernet ring. The Ethernet ring is connected with
each end to an Ethernet switch supporting RSTP (Rapid Spanning Tree Protocol).
This ensures reliable communication and system availability with reduced wiring
efforts.

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

L-VIS Touch Panels

L-VIS

Touch Panels

Gateways

L-IOB

I/O Controllers/Modules

Features
High resolution TFT touch display with dimmable backlight

Alarming, Scheduling, and Trending (AST)

Anodized aluminium front frame

Event-driven e-mail notification

Flush-mounting in combination with the mounting frame


Stores customized graphical pages

Math objects to execute mathematical operations on data


points

Visualization of customized graphical pages through builtin Touch Panel, LWEB900 (building management) und
LWEB800/802

Compliant with ANSI/ASHRAE1352008 and ISO164845 standard


Supports BACnet MS/TP or BACnet/IP

Device configuration and graphical page creation with the


L-VIS/L-WEB configuration tool free of charge

BACnet Client Function (Write Property, Read Property, COV


Subscription)

Supports all popular graphic file formats such as BMP, ICO, JPEG,
TIFF, PNG, MNG, GIF

BACnet Client Configuration with configuration tool (scan and


EDE import)

Support of SVG vector graphics

B-BC (BACnet Building Controller)

Supports Alpha Blending

Integrated BACnet/IP to BACnet MS/TP Router

Supports popular font types such as TrueType, Type-1, BDF, PCF,


and OTF

Integrated Web server for the device configuration and for


monitoring of data points

Supports Unicode text

Access to network statistics

Built-in OPC XML-DA server

Configurable via Ethernet/IP

Built-in OPC XML-DA client

Playback of audio files and streams

LVIS-ME212
LVIS-ME215

Ethernet / IP

OPC XML-DA
Client

BACnet
MS/TP

Alarming
Scheduling
Trending

OPC XML-DA
Server

E-Mail

Data Point Abstraction Layer

ROUTER

Routers, NIC

BACnet/IP

Graphics

Web
Interface

y=f(x)

5.7

Touch

VISUALIZATION

Backlight

Digital
Input 0

Digital
Input 1

BACnet
MS/TP

L-TEMP1
Sensors

DIGIN1

V1.2.2

Software
Tools

DIGIN0

BACnet/IP

90

Audio

www.loytec.com

2 x Ethernet / IP
Web
Interface

SWITCH

OPC XML-DA
Client

Alarming
Scheduling
Trending

Graphics

OPC XML-DA
Server

E-Mail

Data Point Abstraction Layer

ROUTER

L-DALI

Lighting Control

LVIS-ME200

y=f(x)

12.1/15 Touch
VISUALIZATION

Backlight

Digital
Input 0

Digital
Input 1

DIGIN0

L-TEMP1
Sensors

DIGIN1

V1.2.2

L-WEB

LVIS-ME200/ME212/ME215

Building Management

L-VIS Touch Panels

Specifications
12.1" (30.7mm)

15" (38.1mm)

Dimensions (mm)

210x164x63 (LxWxH),
DIM001

329x268.3x65 (LxWxH),
DIM002

394x318x65 (LxWxH),
DIM003

Dimensions cut-out (mm)

180x150x57 (LxWxH)

300x250x61 (LxWxH)

355x295x61 (LxWxH)

Display resolution

320x240, 256 colors

800x600, 65536 colors

1024x768, 65536 colors

Interfaces

1xEthernet (100Base-T)
BACnet/IP, HTTP, FTP,
SMTP, NTP, VNC
1xBACnet MS/TP
2xDigital Input
1xDigital interface for up to 4
L-TEMP1 sensors

2xEthernet (100Base-T), Switch


BACnet/IP, HTTP, FTP,
HTTPS, SMTP, NTP, VNC
1xBACnet MS/TP
2xDigital Input
1xDigital interface for up to 4
L-TEMP1 sensors
1xEIA-485 (RS-485)
2xUSB-A, 1xUSB-B (PC)
speaker, audio output

2xEthernet (100Base-T), Switch


BACnet/IP, HTTP, FTP,
HTTPS, SMTP, NTP, VNC
1xBACnet MS/TP
2xDigital Input
1xDigital interface for up to 4
L-TEMP1 sensors
1xEIA-485 (RS-485)
2xUSB-A, 1xUSB-B (PC)
speaker, audio output

Power supply

20-35VDC / 24 VAC 10%


typ. 3W, backlight on: 8 W

24VDC 10% or 85-240 VAC


2W, backlight on: 13W

24VDC 10% or 85-240 VAC


2W, backlight on: 16W

Operating conditions

+10C to 40C, 10-90% RH @ 50C, non condensing

Degree of protection

Front: IP54 / back: IP10

Tools

LVIS/LWEB Configurator

L-IOB

5.7" (14.5mm)

I/O Controllers/Modules

Screen size

L-INX

LVIS-ME215

Automation Servers

LVIS-ME212

L-ROC

LVIS-ME200

Room Automation

Type

Resource limits
VNC-Clients

16

16

16

BACnet server objects

512

512

512

BACnet calendar objects

25

25

25

BACnet scheduler objects

100 (64 data points per object)

100 (64 data points per object)

100 (64 data points per object)

BACnet notification classes

32

32

32

Email templates

100

100

100

Math objects

100

100

100

Alarm logs

10

10

10

Trend logs

100 (390 000 Logs, 6 MB)

512 (4 000 000 logs, 60 MB)

512 (4 000 000 logs, 60 MB)

Total trended data points

256

512

512

Connections (Local/Global)

1000/250

2000/250

2000/250

Number of L-WEB clients

15 (simultaneously)

32 (simultaneously)

32 (simultaneously)

L-DALI

Lighting Control

10000

L-VIS

10000

Touch Panels

2000

Gateways

OPC XML-DA data points

Product description

LVIS-ME200

BACnet Touch Panel with 5.7" display

LVIS-ME212

BACnet Touch Panel with 12.1" display

LVIS-ME215

BACnet Touch Panel with 15" display

LVIS-FRAME1

Mounting frame for 5.7" Touch Panels

LVIS-FRAME12

Mounting frame for 12.1" Touch Panels

LVIS-FRAME15

Mounting frame for 15" Touch Panels

LTEMP1

External temperature sensor

Routers, NIC

Order number

Software
Tools

buildings under control

91

L-WEB

Building Management

L-VIS Touch Panels

L-INX

Automation Servers

L-ROC

Room Automation

L-VIS Touch Panels are not only perfectly suitable for local operation, they also offer various remote access options that
can be used simultaneously if required:

VNC: The graphical user interface can be accessed via the built-in VNC server by a commercial or freely available
VNC-Client.

LWEB-800: The graphical user interface allows remote access to the graphical projects on the L-VIS Touch Panel from
a Microsoft Windows PC. Communication is done by using Web services - smoothly across firewalls and NAT routers.

LWEB-802: The platform-independent graphical user interface enables remote access to the graphical projects on
the L-VIS Touch Panel by a standard Web browser. The use of HTML5 and JavaScript allows applying Smart Phones
and Tablet PCs also.

LWEB-900: L-VIS Touch Panels integrate perfectly into the L-WEB System.

Various remote access options, alarming, scheduling, trending and e-mails sent on a timely basis or triggered by events
offer amazing flexibility and versatility.

I/O Controllers/Modules

Depending on the interface, L-VIS Touch Panels behave compliant to LonMark Systems or BACnet networks.

Gateways

L-IOB

Furthermore, the L-VIS Touch Panel can be used as an OPC XML DA client to LOYTEC devices (OPC XML-DA server) in the
Ethernet/IP network. If connected to a LOYTEC device, this way information from KNX, Modbus and M-bus networks can
be integrated and visualized additionally to information from LonMark Systems or BACnet networks.

LWEB-900

LWEB-800 Client

VNC

NW

Touch Panels

iPad

NE

L-VIS

E
SE

SW

LWEB-802 Client

Intranet
Internet
VPN

L-DALI

Lighting Control

L-VIS

Ethernet

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

LGATE-951

USB

MICROSD RS-485

FT

EXT1

EXT2

L-GATE

LINK
ACT

Universal Gateway

BBMD OPC

1
Ethernet 1 Ethernet 2

RS-485

2
FT

EXT1

EXT2

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

LINX-120

MICROSD

FT

LIOB-FT

MODBUS

FUSE 6A

EXT

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

LIOB-FT

MODBUS

Pa
P

21.6 C

UI4

UI5

UI6 UI7

UI8

DI2 AO1

L-IOB

UNIVERSAL IN
UI1

UI2 UI3

UI4

UI5

UI6 UI7

0.0 %

77

77

Pa

22.3 C

19.4 C

0.0 %

Software
Tools

AO2

19.5 C

www.loytec.com

status

I/O Module

0-10V OUT

DIGITAL IN
DI1

20.4 C

22.3 C

Made in Austria

status

LIOB-100

L-IOB

UNIVERSAL IN
UI2 UI3

83

92

COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9
6A

LOYTEC
www.loytec.com

status

I/O Module

4
EXT
UI1

77

FUSE 6A

status

LIOB-100

Automation Server

1
FT

Made in Austria

6A

LOYTEC
www.loytec.com

L-INX

ACT

CEA-709
BACnet
M-Bus
Modbus
KNX

Routers, NIC

USB
LINK

PLC OPC

Ethernet 1 Ethernet 2

UI8

DIGITAL IN
DI1

0-10V OUT

DI2 AO1

AO2

L-DALI Lighting Control

buildings under control

93

LDALI-3E101/3E102/3E104

BACnet
DALI
CEA709

L-DALI Controllers are multifunctional devices combining constant light control,


sunblind control, and gateway functions between LonMark and DALI (Digital Addressable Lighting Interface) systems. With alarming, scheduling, trending, and
e-mail notification (AST) the L-DALI Controller is a perfect solution for DALI lighting systems and for a smooth DALI integration into LonMark Systems.

L-ROC

Room Automation

L-WEB

Building Management

L-DALI Controller

Constant Light Control with built-in Sunblind Control

L-INX

Automation Servers

The integrated Constant Light Controller (LonMark Functional Profile #3050) handles DALI devices and CEA709 nodes in the same way. Optionally, the integrated
Sunblind Controller (LonMark Functional Profile #6111) can interact with the Constant Light Controller to assure maximum comfort and energy efficiency. Sunblind
actuators are also integrated as CEA709 nodes.

L-IOB

I/O Controllers/Modules

An effective sun and anti-glare protection can be reached through active slat control and slat adjustment according to the sun position. Energy efficiency is ensured
by linking room occupancy with light control and sun protection. If a room is unoccupied, the L-DALI Controller opens or closes the sunblinds depending on the
thermal requirements. This allows for instance to use the heat of the sun for heating
in winter while in summer, the heat from the sun is reduced by the closed blinds to
reduce the cooling load.
In addition to the constant light and sunblind control, any mathematical calculation and function or logical operation (boolean algebra) can be created on the device and process all available data points.

Device Configuration via Tool or Web Interface


Gateways

The device configuration, commissioning, and parameterization of the connected


DALI devices can be made via the built-in Web interface. Alternatively the configuration can be done via the comfortable configuration tool that can also be started
as LNS plug-in.

Advanced DALI Functions

Touch Panels

L-DALI supports selected DALI multisensors. A list of currently supported devices


can be found on www.loytec.com.
L-VIS

Auto Burn-In for Fluorescent Lamps


Fluorescent lamps must be operated about 100 hours with 100% brightness
before they may be dimmed. This burn-in process is monitored by L-DALI for
each lamp. After 100 hours burn-in time, the lamps constant light control is
enabled.

Lighting Control

Automatic Test of Emergency Lighting Systems

L-DALI

In emergency lighting systems, L-DALI can be used for testing the system. The
results can be logged.

Provision of Important Operational Parameters


For maximum transparency in the lighting system, L-DALI can record the operating hours of each lamp and also the projected energy consumption.

DALI Device Replacemant made Easy

Routers, NIC

Defective DALI ballasts can easily be replaced directly through buttons on the
LDALI controller or via the Web interface. No software tool is necessary.

Smooth DALI integration in LonMark Systems

Software
Tools

The L-DALI Controller maps information from the DALI network to Network Variables (NVs) used to control DALI ballasts or to display operating states. L-DALI represents a DALI-Master in the DALI network which can interact with selected DALI
multi-sensors in Multi-Master mode.

94

www.loytec.com

Network Interface

L-DALI Controller for LonMark Systems can be connected either to an Ethernet/IP


channel (LonMark IP-852) or a TP/FT-10 channel. The provided static NV interface
includes the following profiles:

Automation Servers

Lamp Actuator #3040


Light Sensor #1010
Occupancy Sensor #1060
Constant Light Controller #3050
Sunblind Controller #6111

L-INX

L-ROC

LonMark Interface

Room Automation

The L-DALI lineup for LonMark Systems features 1, 2, or 4 independent DALI channels. Up to 64 DALI-based luminaries per DALI channel can be controlled individually or via 16 groups. All luminaries are monitored for lamp or ballast defect.

L-WEB

LDALI-3E101/3E102/3E104

Building Management

L-DALI Controller

L-IOB

DALI Power Supply

I/O Controllers/Modules

The device configuration is done either with the L-DALI Configuration Tool (used
as stand-alone tool or as LNS plug-in) or via the integrated Web server. All data
points are available in a tree structure on the integrated Web server to be displayed or set using a standard Web browser.
An external DALI power supply is needed to power up the DALI network. Power
supplies are available for single channel or up to four channel DALI networks.

Gateways
L-VIS

Touch Panels

Features

Supports up to 64 DALI devices and 16 DALI groups per DALI


channel

Integrated DALI Protocol Analyzer

Built-in Web server for the device configuration


Test and assignment of the DALI devices via the Web interface
Replacement of DALI devices without additional software tools

Integrated Constant Light Controller


Integrated Sunblind Control

Network connection either with TP/FT-10 or IP-852 (CEA-852


Ethernet)
Alarming, Scheduling, and Trending (AST) locally or embedded in L-WEB (building management)
Event-driven e-mail notification
Supports Global Connections

Supports lamp burn-in mode

Routers, NIC

Supports up to 16 DALI sensors, tested products are listed in the


compatibility list on www.loytec.com or in the user manual

Compliant with CEA-709, CEA-852 and ISO/IEC14908-1 standard (LonMark System)

L-DALI

Supports periodic testing of DALI emergency lights

Lighting Control

DALI integration to LonMark Systems

Software
Tools

buildings under control

95

LDALI-3E101/3E102/3E104
DALI 4

Room Automation

L-WEB

Building Management

L-DALI Controller

L-ROC

DALI 3

DALI 2

L-INX

Automation Servers

DALI 1

LPOW-2415B

Made in Austria

POWER

status

DA1+ DA1DALI 1

DA2+ DA2DALI 2

DA3+ DA3DALI 3

DA4+ DA4DALI 4

27

28

29

DA4

I/O Controllers/Modules

L-POW

Power Supply

L-IOB

Input
N
L

85-240VAC
50/60 Hz

L-DALI

Power Supply

LOYTEC
www.loytec.com

24VDC/15W
GND +

Input
N
L

85-240VAC
50/60 Hz

PROG CHANNEL

30

DA3

LOYTEC
www.loytec.com
ON
OFF
AUTO

DALI4
ACT

32

33

34

DA2
DALI3
ACT

35

DA1
DALI2
ACT

L-DALI CEA-709 DALI controller


Made in Austria

FT

DALI Multi-Master

B A

LDALI-PWR4-U

13

85 - 240 VAC

via TP/FT-10
or IP-852

IP ACT

Made in Austria

OUTPUT
DALI 4x 116mA

LINK

CN/IP

ACT

DALI1
ACT

14

15

CONFIG

serial

Ethernet

LDALI-3E104

100Base-T

TP/FT-10

LOYTEC
www.loytec.com

power

status

12-35 VDC INPUT or


12-24 VAC, 3W

- +
~ ~

DC
AC

24 25 26

IP-852

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

Specifications
Dimensions (mm)

159x100x60 (LxWxH), DIM006

Power supply

12-35VDC / 12-24VAC 10%, typ. 2W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
LonMark IP-852*, HTTP, FTP, OPC XMLDA
1xTP/FT-10* (LonMark System)
*LonMark IP-852 or TP/FT-10

Types

LDALI-3E101

LDALI-3E102

LDALI-3E104

DALI channels

LonMark Profile

Lamp Actuator #3040,


Light Sensor #1010,
Occupancy Sensor #1060,
Constant Light Controller #3050
Sunblind Controller #6111

Tools

LDALI Configuration Tool, configuration via Web interface with browser

Software
Tools

Routers, NIC

Resource limits

96

DALI devices per DALI channel

64

Address table entries

512 (non-ECS mode: 15)

DALI groups per DALI channel

16

LonMark calendar

1* (10* templates)

DALI sensors per DALI channel

16

LonMark scheduler

16*

Scene control

16 groups per DALI channel

LonMark alarm server

1*

Broadcast scene

1 per DALI channel

Trend logs

25* (max. 2 MB)

Maths objects

100

Data points in trend log

64*

Alarm logs

10

E-mail templates

100

Global connections

250

* per DALI channel

Order number

Product description

LDALI-3E101

CEA709/DALI Controller, AST, Sunblind Controller, 1 DALI channel

LDALI-3E102

CEA709/DALI Controller, AST, Sunblind Controller, 2 DALI channels

LDALI-3E104

CEA709/DALI Controller, AST, Sunblind Controller, 4 DALI channels

LDALI-PWR2-U

DALI power supply unit for 2 DALI channels

LDALI-PWR4-U

DALI power supply unit for 4 DALI channels

www.loytec.com

LDALI-ME204

L-INX

The device configuration, commissioning, and parameterization of the DALI


devices connected can be made via the built-in Web interface.

Automation Servers

Device Configuration via Tool or Web Interface

L-ROC

The integrated Constant Light Controller works with DALI and BACnet devices.
In addition to the constant light control, the L-DALI provides for any mathematical calculation or logical operation (boolean algebra) on data points
available on the device.

Room Automation

L-DALI Controllers are multifunctional devices combining constant light


control, sunblind control and gateway functions between BACnet and DALI
(Digital Addressable Lighting Interface) systems. With alarming, scheduling,
trending and e-mail notification (AST) the L-DALI Controller is a perfect solution for DALI lighting systems and for a smooth DALI integration into BACnet
networks.

L-WEB

L-DALI Controller

Building Management

BACnet
DALI
CEA709

Advanced DALI Functions

Auto Burn-In for Fluorescent Lamps


Fluorescent lamps must be operated about 100 hours with 100% brightness before they may be dimmed. This burn-in process is monitored by
L-DALI for each lamp. After 100 hours burn-in time, the lamps constant
light control is enabled.
Automatic Test of Emergency Lighting Systems
In emergency lighting systems, L-DALI can be used for testing the system. The results can be logged.

Provision of Important Operational Parameters

L-VIS

Touch Panels

For maximum transparency in the lighting system, L-DALI can record the
operating hours of each lamp and also the projected energy consumption.

Gateways

L-IOB

I/O Controllers/Modules

L-DALI supports selected DALI multisensors. A list of currently supported


devices can be found on www.loytec.com.

DALI Device Replacemant made Easy


Defective DALI ballasts can easily be replaced directly through buttons
on the LDALI controller or via the Web interface. No software tool is necessary.

Smooth DALI integration into BACnet Networks


L-DALI

L-DALI Controllers can communicate in the BACnet network on the BACnet/IP


channel or on the BACnet MS/TP channel.

Lighting Control

The L-DALI Controller maps information from the DALI network to BACnet
objects that are used to control DALI ballasts or to display operating states.
L-DALI represents a DALI-Master in the DALI network which can interact with
selected DALI multi-sensors in Multi-Master mode.

Following BACnet server objects are supported:


Multi-State Output objects for scene control of DALI groups and channels

Analog Input objects providing feedback from DALI ballast, groups, and
channels

Analog Input objects providing status information from DALI groups and
channels

Accumulator objects providing estimated energy usage of DALI groups


and channels

buildings under control

97

Software
Tools

Analog Output objects to control DALI ballasts, groups, and channels

Routers, NIC

LDALI-ME204

L-ROC

Room Automation

L-WEB

Building Management

L-DALI Controller

Analog Input object providing lux level information from supported DALI sensors

Binary Input objects providing occupancy information from supported DALI


sensors

Loop objects providing constant light controller functionality

Network Interface

L-INX

Automation Servers

LDALI-ME204 features 4 independent DALI channels. Up to 64 DALI-based luminaries per DALI channel can be controlled individually or via 16 groups. All luminaries are monitored for lamp or ballast defect.
All data points are available on the web server in a tree structure and can be displayed and set via a standard web browser.

DALI Power Supply

L-IOB

I/O Controllers/Modules

An external DALI power supply is needed to power up the DALI network. Power
supplies are available for single channel or up to four channel DALI networks.

Gateways

DALI 4

DALI 3

DALI 2

L-VIS

Touch Panels

DALI 1

LPOW-2415B

Made in Austria

status

POWER

DA1+ DA1DALI 1

DA2+ DA2DALI 2

DA3+ DA3DALI 3

DA4+ DA4DALI 4

27

28

DA4

29

Lighting Control

L-POW

Power Supply
85-240VAC
50/60 Hz

24VDC/15W
GND +

Power Supply

LOYTEC
www.loytec.com
Input
N
L

85-240VAC
50/60 Hz

OUTPUT
DALI 4x 116mA

32

ON
OFF
AUTO

33

DA2

DALI4
ACT

DALI3
ACT

34

35

DA1
DALI2
ACT

DALI1
ACT

L-DALI
ACT

CN/IP

BACnet DALI controller


Made in Austria

LINK
IP ACT
CONFIG

DALI

MSTP Ethernet
+ - 100Base-T

Made in Austria

LDALI-PWR4-U

13

14

15

serial

LDALI-ME204

LOYTEC
www.loytec.com

power

status

12-35 VDC INPUT or


12-24 VAC, 3W

- +
~ ~

DC
AC

24 25 26

L-DALI

Input
N
L

L-DALI

PROG CHANNEL

30

DA3

LOYTEC
www.loytec.com

85 - 240 VAC

BACnet MS/TP

BACnet/IP

Routers, NIC

Features
DALI integration to BACnet networks

Supports lamp burn-in mode

Supports up to 64 DALI devices and 16 DALI groups per DALI


channel

Compliant with ANSI/ASHRAE1352008 and ISO164845 standard

Built-in Web server for the device configuration

Supports BACnet MS/TP or BACnet/IP

Test and assignment of the DALI devices on the Web interface

Alarming, Scheduling, and Trending (AST) locally or embedded in L-WEB (building management)

Replacement of DALI devices without additional software tools

Software
Tools

Integrated Constant Light Controller


Integrated DALI Protocol Analyzer

Supports up to 16 DALI sensors, tested products are listed in


the compatibility list on www.loytec.com or in the user manual

Supports periodic testing of DALI emergency lights

98

www.loytec.com

L-WEB

LDALI-ME204

Building Management

L-DALI Controller

L-ROC

Room Automation

Licht

Automation Servers

Jalousien

LOYTEC

Heizung
100
90

Auto

80
70

Manuell

60
50

Szene 1

40
30

Szene 2

L-INX

20
10

Aus

28

29

DA4

30

32

DA3

PROG CHANNEL

ON
OFF
AUTO

33

DA2

DALI4
ACT

DALI3
ACT

34

35

DA1
DALI2
ACT

L-DALI

DALI1
ACT

ACT

CN/IP

BACnet DALI controller


Made in Austria

LINK
IP ACT

serial

CONFIG

DALI

I/O Controllers/Modules

27

13

14

15

LDALI-ME204

LOYTEC
www.loytec.com

status

12-35 VDC INPUT or


12-24 VAC, 3W

- +
~ ~

DC
AC

L-IOB

MSTP Ethernet
+ - 100Base-T

power

24 25 26

Gateways

Specifications
159x100x60 (LxWxH), DIM006

Power supply

12-35VDC / 12-24VAC 10%, typ. 2W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
BACnet/IP*, HTTP, FTP
1xBACnet MS/TP*

L-VIS

Touch Panels

Dimensions (mm)

* BACnet IP or BACnet MS/TP


DALI channels

Tools

Configuration via Web interface with browser


64

BACnet client mappings

1000

DALI groups per DALI channel

16

BACnet scheduler objects

64

DALI sensors per DALI channel

16

BACnet calendar objects

Scene control

16 groups per DALI channel

BACnet notification classes

16

Trend logs

64 (max. 2 MB)

Data points in trend log

64

Product description

LDALI-ME204

BACnet/DALI Controller, 4 DALI channels

LDALI-PWR2-U

DALI power supply unit for 2 DALI channels

LDALI-PWR4-U

DALI power supply unit for 4 DALI channels

Routers, NIC

Order number

L-DALI

DALI devices per DALI channel

Lighting Control

Resource limits

Software
Tools

buildings under control

99

LDALI-3101-U/LDALI-E101-U

L-ROC

Built-In DALI Power Supply

L-INX

Automation Servers

The compact L-DALI Controller comes with a built-in DALI power supply. It can supply one DALI channel with up to 230mA. Thanks to the switching power supply of
the L-DALI, the device can handle input voltages from 85 - 240VAC 50/60Hz.

LonMark TP/FT10 or Ethernet/IP-852 Connection

L-IOB

I/O Controllers/Modules

LDALI-E101-U is equipped with two Ethernet ports including a built-in Ethernet


switch.* It also provides data exchange through Global Connections and supports
comprehensive AST functionality (alarming, scheduling, and trending) with
email notification. Full L-WEB integration is supported as well.
LDALI-3101-U features connectivity in LonMark Systems through TP/FT-10. It implements extended features like local alarming and scheduling. The system time can
be synchronized by the real time keeper object (SNVT_time_stamp).

VNC

Local Operation and Override

Gateways

Both LDALI-3101-U and LDALI-E101-U come with a built-in backlit Display (128x64)
and a jog-dial for local operation and override. Device and data point information
is displayed in text form and via graphical symbols. Using the local operation, DALI
devices can be integrated or replaced without the need of any software tool.

Constant Light Control with Built-in Sunblind Control

L-VIS

Touch Panels

DALI

The integrated Constant Light Controller LonMark Functional Profile #3050) handles DALI devices and CEA-709 nodes in the same way. Optionally, the integrated
Sunblind Controller (LonMark Functional Profile #6111) can interact with the Constant Light Controller to assure maximum comfort and energy efficiency. Sunblind
actuators are also integrated as CEA-709 nodes.

L-DALI

Lighting Control

An effective sun and anti-glare protection can be reached through active slat control and slat adjustment according to the sun position. Energy efficiency is ensured
by linking room occupancy with light control and sun protection. If a room is unoccupied, the L-DALI Controller opens or closes the sunblinds depending on the thermal requirements. This allows for instance to use the heat of the sun for heating in
winter while in summer, the heat from the sun is reduced by the closed blinds to
reduce the cooling load.

230mA DA+ DA-

ETHERNET

status

status

CEA-709 DALI Controller


L

INPUT

85-240VAC 50/60 Hz

Routers, NIC

In addition to the constant light and sunblind control, any mathematical calculation and function or logical operation (boolean algebra) can be created on the
device and process all available data points.

DALI Multi-Master

LOYTEC
LDALI-E101-U
www.loytec.com

L-DALI

Software
Tools

BACnet
DALI
CEA709

The compact LDALI Controllers LDALI-3101-U and LDALI-E101-U are multifunctional devices combining constant light control, sunblind control, and gateway
functions between LonMark and DALI (Digital Addressable Lighting Interface)
systems. With alarming, scheduling, trending, and e-mail notification (AST) the
L-DALI Controller is a perfect solution for DALI lighting systems and for a smooth
DALI integration into LonMark Systems.

Room Automation

L-WEB

Building Management

L-DALI Controller

Made in Austria

Device Configuration via Tool or Web Interface


The device configuration, commissioning, and parameterization of the DALI
devices connected can be made via the built-in Web interface. Alternatively, the
configuration can be done via the comfortable configuration tool that can be also
started as an LNS plug-in.

Advanced DALI Functions


L-DALI supports selected DALI multisensors. A list of currently supported devices
can be found on www.loytec.com.

* Available 4/2013

100

Fluorescent lamps must be operated about 100 hours with 100% brightness before
they may be dimmed. This burn-in process is monitored by L-DALI for each lamp.
After 100 hours burn-in time, the lamps constant light control is enabled.
In emergency lighting systems, L-DALI can be used for testing the system. The
results can be logged.

www.loytec.com

For maximum transparency in the lighting system, L-DALI can record the operating
hours of each lamp and also the projected energy consumption.

L-ROC

The L-DALI Controller maps information from the DALI network to Network Variables (NVs) used to control DALI ballasts or to display operating states. L-DALI represents a DALI-Master in the DALI network which can interact with selected DALI
multi-sensors in Multi-Master mode.

Room Automation

Smooth DALI integration in LonMark Systems

L-WEB

LDALI-3101-U/LDALI-E101-U

Building Management

L-DALI Controller

Features

Integrated detachable DALI bus power supply (16 VDC, 230mA)

Integrated Constant Light Controller

Manual operation using the jog dial

Integrated Sunblind Control

Local access to information about device status and data points


in clear text and symbols

Compliant with CEA-709, CEA-852, and ISO/IEC14908-1 standard

128x64 graphic display with backlight

Network connection either with TP/FT-10 or IP-852 (CEA-852


Ethernet)

Built-in Web server for the device configuration (LDALI-E101-U


only)

Integrated DALI Protocol Analyzer

Test and assignment of the DALI devices on the Web interface


(LDALI-E101-U only) or via the graphic display and jog dial

Alarming, Scheduling, and Trending (AST) locally or embedded in L-WEB (building management) (LDALI-E101-U only)

Replacement of DALI devices without additional software tools

Event-driven e-mail notification (LDALI-E101-U only)

Gateways

Supports lamp burn-in mode

L-IOB

Supports up to 16 DALI sensors, tested products are listed in


the compatibility list on www.loytec.com or in the user manual

I/O Controllers/Modules

Supports up to 64 DALI devices and 16 DALI groups per DALI


channel

L-INX

Supports periodic testing of DALI emergency lights

Automation Servers

DALI integration to LonMark Systems

Specifications
107x100x60 (LxWxH), DIM032, DIM033

Power supply

85-240 VAC, 50/60 Hz, current limited start up

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Types

LDALI-3101-U

LDALI-E101-U

DALI channels

Interfaces

1xTP/FT-10 (LonMark System)


1x 16VDC, 230mA (DALIPower Supply, detachable)

2xEthernet (100Base-T)
LonMark IP-852, HTTP, FTP
1x DALI (with integrated DALI
bus power supply 230mA,
detachable)

Profile

LonMark Functional Profiles


Lamp Actuator #3040,
Light Sensor #1010,
Occupancy Sensor #1060,
Constant Light Controller #3050,
Sunblind Controller #6111

LonMark Functional Profiles


Lamp Actuator #3040,
Light Sensor #1010,
Occupancy Sensor #1060,
Constant Light Controller
#3050,
Sunblind Controller #6111

Tools

LDALI Configuration Tool, configuration via Web interface with browser

L-VIS

Touch Panels

Dimensions (mm)

L-DALI

Lighting Control

Resource limits
64

Adress table entries

512 (non-ECS mode: 15)

DALI groups

16

Trend logs

25 ( 2 MB)

DALI sensors

16

Data point in trend log

64

Scene control

16 groups

LonMark calendar

1 (10 templates)

Broadcast scene

LonMark scheduler

16

Alarm Logs

10

LonMark alarm server

Global Connections

250

Product description

LDALI-3101-U

CEA709/DALI Controller for TP/FT-10 (LonMark System), 1DALI channel, integrated DALI power supply

LDALI-E101-U

CEA709/DALI Controller for IP-852 (Ethernet), 1DALI channel, integrated DALI power supply

buildings under control

Software
Tools

Order number

Routers, NIC

DALI devices

101

LDALI-E201-U

The compact LDALI Controller LDALI-E201-U is a multifunctional device combining constant light control and gateway functions between BACnet and DALI (Digital Addressable Lighting Interface) systems. With alarming, scheduling, trending,
and e-mail notification (AST) the L-DALI Controller is a perfect solution for DALI
lighting systems and for a smooth DALI integration into BACnet networks.

L-ROC

Room Automation

L-WEB

Building Management

BACnet
DALI
CEA709

L-DALI Controller

Built-In DALI Power Supply

Automation Servers

The compact L-DALI Controller comes with a built-in DALI power supply. It can supply one DALI channel with up to 230mA. Thanks to the switching power supply of
the L-DALI, the device can handle input voltages from 85 - 240VAC 50/60Hz.

L-INX

BACnet/IP Connectivity

I/O Controllers/Modules

LDALI-E201-U is equipped with two Ethernet ports including a built-in Ethernet


switch.* LDALI-E201-U features connectivity in BACnet networks via BACnet/IP. It
also provides data exchange through Global Connections and supports comprehensive AST functionality (alarming, scheduling, and trending) as well as email
notification. Full L-WEB integration is supported as well.

L-IOB

Local Operation and Override


LDALI-E201-U comes with a built-in backlit Display (128x64) and a jog-dial for local
operation and override. Device and data point information is displayed in text form
and via graphical symbols. Using the local operation, DALI devices can be integrated or replaced without the need of any software tool.

VNC

Gateways

Constant Light Control

DALI

The integrated Constant Light Controller works with DALI and with BACnet devices.
In addition to the constant light control, the L-DALI allows for any mathematical
calculation or logical operation (boolean algebra) on data points available on the
device.

Device Configuration via Web Interface

L-VIS

Touch Panels

The device configuration, commissioning, and parameterization of the DALI devices


connected can be made via the built-in Web interface.

Advanced DALI Functions

Lighting Control

L-DALI supports selected DALI multisensors. A list of currently supported devices


can be found on www.loytec.com.

230mA DA+ DA-

ETHERNET

DALI Multi-Master

L-DALI

LOYTEC
LDALI-E201-U
www.loytec.com

status

status

L-DALI

BACnet DALI Controller


N

Fluorescent lamps must be operated about 100 hours with 100% brightness before
they may be dimmed. This burn-in process is monitored by L-DALI for each lamp.
After 100 hours burn-in time, the lamps constant light control is enabled.

INPUT

85-240VAC 50/60 Hz

Made in Austria

In emergency lighting systems, L-DALI can be used for testing the system. The
results can be logged.
For maximum transparency in the lighting system, L-DALI can record the operating
hours of each lamp and also the projected energy consumption.

DALI - BACnet Integration


Routers, NIC

BACnet/IP

Ethernet/IP

LDALI maps information from the DALI network to BACnet objects that can access
data points on DALI ballasts for control, monitoring, or configuration purposes.
L-DALI operates as DALI master on the DALI network but can also interwork with
selected DALI Multi Sensors in multi master mode.

Software
Tools

Following BACnet server objects are supported:

102

Analog Output objects to control DALI ballasts, groups, and channels

Multi-State Output objects for scene control of DALI groups and channels

Analog Input objects providing feedback from DALI ballast, groups, and
channels

www.loytec.com

Accumulator objects providing estimated energy usage of DALI groups and


channels

Analog Input object providing lux level information from supported DALI
sensors

Binary Input objects providing occupancy information from supported DALI


sensors

Loop objects providing constant light controller functionality

L-INX

Automation Servers

L-ROC

Analog Input objects providing status information from DALI groups and
channels
Room Automation

L-WEB

LDALI-E201-U

Building Management

L-DALI Controller

Features

Supports up to 64 DALI devices and 16 DALI groups per DALI


channel

Supports periodic testing of DALI emergency lights

Integrated detachable DALI bus power supply (16 VDC, 230mA)

Supports up to 16 DALI sensors, tested products are listed in


the compatibility list on www.loytec.com or in the user manual

Manual operation using the jog dial

Integrated Constant Light Controller

Local access to information about device status and data points


in clear text and symbols

Integrated DALI Protocol Analyzer


Compliant with ANSI/ASHRAE135-2008 and ISO16484-5 standard

Built-in Web server for the device configuration

Supports BACnet MS/TP or BACnet/IP

Test and assignment of the DALI devices on the Web interface


or via the graphic display and jog dial

Alarming, Scheduling, and Trending (AST) locally or embedded in L-WEB (building management)

Replacement of DALI devices without additional software tools

Event-driven e-mail notification

107x100x60 (LxWxH), DIM033

Power supply

85-240 VAC, 50/60 Hz, current limited start up

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Types

LDALI-E201-U

DALI channels

Interfaces

2 xEthernet (100Base-T)
BACnet/IP, HTTP, FTP
1x DALI (with integrated DALI bus power supply 230mA,
detachable)

Profile

Tools

LDALI Configuration Tool, configuration via Web interface with browser

L-VIS

Dimensions (mm)

Touch Panels

Specifications

Gateways

128x64 graphic display with backlight

L-IOB

Supports lamp burn-in mode

I/O Controllers/Modules

DALI integration to BACnet networks

L-DALI

Lighting Control

Resource limits
64

BACnet client mappings

1000

DALI groups

16

BACnet scheduler objects

16

DALI sensors

16

BACnet calendar objects

Scene control

16 groups

BACnet notification classes

Alarm logs

10

Trend logs

16 ( 2 MB)

Data points in trend log

64

Product description

LDALI-E201-U

BACnet/DALI Controller for BACnet/IP, 1DALI channel, integrated DALI power supply

buildings under control

Software
Tools

Order number

Routers, NIC

DALI devices

103

LDALI-PWR2-U / LDALI-PWR4-U

The DALI power supplies LDALI-PWR2-U and LDALI-PWR4-U are used to power two
or four DALI channels. Per channel, the power supplies provide up to 116mA to
power devices connected to the DALI channel.

Room Automation

L-WEB

Building Management

BACnet
DALI
CEA709

L-DALI Power Supply

L-ROC

When the DALI devices connected to the channel consume more than the 116mA,
two DALI outputs of the power supplies can be used in parallel. Hence the maximum current provided this way is limited to 232mA.

Installation
Automation Servers

The DALI channel is treated to be non-SELV (Safety Extra Low Voltage).


L-INX

The maximum cable lenght of a DALI channel is limited to 300Meters, when using
a minimum wire cross-section of 1.5mm (AWG15) .

Wide Range Supply Voltage


The power supplies accept a wide range of supply voltage from 85-240VAC
50/60Hz. They also feature a starting-current limitation.

I/O Controllers/Modules

DALI Power Outputs

L-IOB

The DALI power outputs provide 16V (11V - 20.5V) and 116mA. The power outputs are isolated from mains by basic isolation.

Gateways

The power outputs are short circuit proof and shut down if thermally overloaded.

LPOW-2415B

Made in Austria

status

POWER

DA1+ DA1DALI 1

DA2+ DA2DALI 2

DA3+ DA3DALI 3

DA4+ DA4DALI 4

27

28

DA4

29

L-POW

Power Supply
85-265VAC
50/60 Hz

24VDC/15W
GND +

Input
N
L

85-240VAC
50/60 Hz

OUTPUT
DALI 4x 116mA

ON
OFF
AUTO

DALI4
ACT

32

33

DA2
DALI3
ACT

34

35

DA1
DALI2
ACT

DALI1
ACT

L-DALI CEA-709 DALI controller


Made in Austria

LINK

IP ACT

FT

DALI Multi-Master

B A

Made in Austria

LDALI-PWR4-U

CN/IP

ACT

13

14

15

CONFIG

serial

Ethernet

LDALI-3E104

100Base-T

LOYTEC
www.loytec.com

power

status

12-35 VDC INPUT or


12-24 VAC, 3W

- +
~ ~

DC
AC

24 25 26

Specifications
Dimensions (mm)

107x100x60 (LxBxH), DIM030

Power supply

85-240VAC, 50/60 Hz, current limited start up

Operating conditions

0C bis 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

LDALI-PWR2-U: 2x16VDC (11V bis 20,5V), each 116mA, short-circuit-proof, basic isolation (not SELV) to
the power line
LDALI-PWR4-U: 4x16VDC (11V bis 20,5V), each 116mA, short-circuit-proof, basic isolation (not SELV) to
the power line

Order number

Configuration

LDALI-PWR2-U

DALI Power Supply for 2 DALI channels

LDALI-PWR4-U

DALI Power Supply for 4 DALI channels

Software
Tools

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Input
N
L

L-DALI

Power Supply

LOYTEC
www.loytec.com

PROG CHANNEL

30

DA3

LOYTEC
www.loytec.com

104

www.loytec.com

Routers, NIC

buildings under control

105

The L-IP Router connects twisted pair channels (TP/FT-10 or TP/XF-1250) with the
Ethernet/IP channel (IP-852) in LonMark Systems. L-IP routes CEA709 packets
through an IP based network such as a LAN (Ethernet), an Intranet, or even the
Internet. The L-IP connects to the IP network via a 100Base-T Ethernet port.

L-ROC

Room Automation

L-WEB

Building Management

BACnet
DALI
CEA709

LIP-3ECTB, LIP-1ECTB,
LIP-33ECTP, LIP-3333ECTB

In order to provide optimal router configurations, the L-IP is available in four


different versions providing either 4 x TP/FT-10, 2 x TP/FT-10, 1 x TP/FT10, or 1 x
TP/XF-1250. Every L-IP supports the operating modes Smart Switch Mode and
Configured Router Mode.

L-INX

Automation Servers

Beside the router functionality, the L-IP Routers provide outstanding capabilities
for network diagnostic and analysis. They allow the LPA (LOYTEC Protocol Analyzer,
see page 117) transparent access to the twisted pair channels on the device via
Ethernet/IP. This feature can be used in a local Intranet or via the Internet.

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

L-IOB

I/O Controllers/Modules

The integrated CEA-852 Configuration Server can manage up to 100 IP-852


devices. The configuration is done through the built-in Web interface.

Routers, NIC

Features
Routes packets between TP/FT-10 or TP/XF-1250 channels and
Ethernet/IP (IP-852)

Easy installation, Auto-NAT, roaming, DHCP

Compliant with CEA-709, CEA-852, and ISO/IEC14908-1 standard (LonMark System)

Integrated Web server for the device and IP-852 configuration

Software
Tools

Supports Configured Router mode, Smart Switch mode, and


Repeater mode

Remote LPA support with LPA-IP


Built-in enhanced communication test for IP-852
Network diagnostic LEDs

Built-in CEA-852 configuration server for up to 100 members


Support for operation behind NAT-Routers and firewalls

106

www.loytec.com

L-WEB

Building Management

LIP-3ECTB, LIP-1ECTB,
LIP-33ECTP, LIP-3333ECTB
Specifications
0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Types

LIP-3ECTB

Dimensions (mm)

107x100x60 (LxWxH), DIM009

Interfaces

1xEthernet (100Base-T), LonMark IP-852, HTTP, FTP


1xTP/FT-10

1xTP/XF-1250

LIP-33ECTB

LIP-3333ECTB
159x100x60 (LxWxH), DIM007

2xTP/FT-10

4xTP/FT-10

Configuration via web browser or console (EIA-232)

Automation Servers

Tools

LIP-1ECTB

Resource limits

L-INX

Configuration Server

L-ROC

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

Room Automation

Power supply

CEA852 configuration server for up to 100 members on the IP-852 channel

LIP-1ECTB

CEA-709/IP-852 Router, 1xTP/XF-1250, 1xEthernet-Port (IP-852)

LIP-33ECTB

CEA-709/IP-852 Router, 2xTP/FT-10, 1xEthernet-Port (IP-852)

LIP-3333ECTB

CEA-709/IP-852 Router, 4xTP/FT-10, 1xEthernet-Port (IP-852)

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LT-03

Network terminator, 1xTP/FT-10 or TP/LPT-10 (bus or free topology), 1xNetwork Access Connector RJ45

LT-13

Network terminator, 1xTP/FT-10 or TP/LPT-10 (bus or free topology), 1xTP/XF-1250

LT-33

Network terminator, 2xTP/FT-10 or TP/LPT-10 (bus or free topology)

Gateways

CEA-709/IP-852 Router, 1xTP/FT-10, 1xEthernet-Port (IP-852)

L-IOB

Configuration

LIP-3ECTB

I/O Controllers/Modules

Order number

L-VIS

Touch Panels

L-DALI

Lighting Control

Routers, NIC
Software
Tools

buildings under control

107

LIP-33ECRB

The L-IP Router Redundant connects twisted pair channels (TP/FT-10 or TP/XF-1250)
with the Ethernet/IP-852 channel in LonMark Systems and allows building a redundant network infrastructure. An integrated algorithm detects and heals a broken
cable on the TP/FT-10 channel and helps to find the point of failure immediately.
In addition, the L-IP Redundant monitors the nodes on the TP/FT-10 channel and
creates an alarm in case of a failure. For this reason, L-IP Router Redundant can only
be used as a Configured Router.

L-ROC

Room Automation

L-WEB

Building Management

BACnet
DALI
CEA709

CEA-709/IP-852 Router

Automation Servers

Full redundancy on both the IP channel and the CEA709 channel including device
redundancy can be achieved using two devices in parallel (Twin Mode).
L-INX

L-IP
21

Routers, NIC

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

L-IOB

I/O Controllers/Modules

L-IP
21

Alarms report a broken network cable, node failures, or high communication loads.
The L-IP Router Redundant supports alarming according to the LonMark profile
definition. Similarly, alarm conditions are provided via network variables. Alarm
messages are displayed immediately via the built-in Web interface and the LNS
plug-in. Alarm conditions can be forwarded via e-mail in combination with a L-INX
Automation Server, an L-VIS Touch Panel, or an L-GATE Gateway, to inform about a
node failure or a broken network cable.

TP/FT-10

Features
Routes packets between a TP/FT-10 channel and Ethernet/IP
(IP-852)

Notification via SNVTs and LonMark alarming via Node Object

Compliant with CEA-709, CEA-852, and ISO/IEC14908-1 standard (LonMark System)

Supports Configured Router Mode only

Detection of broken cable (TP/FT10 channel)


Full redundancy with two L-IP Redundant devices in Twin Mode
(IP channel and TP/FT-10 channel)

Monitors network health (bandwidth utilization, error rate, etc.)


Built-in CEA-852 configuration server for up to 100 members
Support for operation behind NAT-Routers and firewalls
Easy installation, Auto-NAT, roaming, DHCP

Device redundancy by mutual monitoring of L-IP Redundant


devices in Twin mode

Remote LPA support with LPA-IP

Communication on the TP/FT-10 channel is guaranteed in case


of a single cable break

Built-in enhanced communication test for IP-852

Nodes on the TP/FT-10 channel can be monitored

Integrated Web server for the device and IP-852 configuration


Network diagnostic LEDs

Specifications
Dimensions (mm)

107x100x60 (LxWxH), DIM009

Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
LonMark IP-852, HTTP, FTP
2xTP/FT-10

Tools

L-IP Redundant Configurator

Resource limits
Configuration Server

Software
Tools

The integrated CEA-852 Configuration Server can manage up to 100 IP-852


devices. The configuration is done through the built-in Web interface.

Internet / Intranet
Router / Firewall

CEA852 configuration server for up to 100 members on the IP channel

Order number

Configuration

LIP-33ECRB

CEA-709 IP-Router for redundant mode, 2xTP/FT-10, 1xEthernet-Port (IP-852)

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LT-03

Network terminator, 1xTP/FT-10 or TP/LPT-10 (bus or free topology), 1xNetwork Access Connector RJ45

LT-33

Network terminator, 2xTP/FT-10 or TP/LPT-10 (bus or free topology)

108

www.loytec.com

LIP-ME201

L-INX

Automation Servers

L-IOB

I/O Controllers/Modules

The complete device configuration of the LIP-ME201 is done via the built-in Web
server.

L-ROC

The LIP-ME201 can act as BACnet Time Master and as BACnet MS/TP Slave Proxy.
Extended features like the optional write protection of the BDT, a BACnet/IP Access Control List (ACL), and a simple communications test for BBMD help to locate
issues on the network. The LIP-ME201 also features remote MS/TP data packet
capturing. BACnet MS/TP data packets are captured by the device and can be
analyzed using Wireshark (free Protocol Analyzer, www.wireshark.org). Wireshark
can either connect to the LIP-ME201 online or the capture file is loaded from the
L-IPs Web server and analyzed offline in Wireshark.

Room Automation

The LIP-ME201 BACnet/IP Router connects a BACnet MS/TP channel to a BACnet/IP


network. It routes BACnet packets back and forth through an IP based network,
such as a LAN (Ethernet), an Intranet, or even the Internet. The LIP-ME201 is compliant with the standards ASHRAE 135-2008 and ISO16484-5. LIP-ME201 can be
configured to act as a BACnet Broadcast Management Device (BBMD). The LIP also
provides Foreign Device support.

L-WEB

BACnet/IP Router

Building Management

BACnet
DALI
CEA709

Gateways

Configuration via built-in Web server or serial port

Compliant with ANSI/ASHRAE1352008 and ISO164845 standard

Access to network statistics via Web browser

BBMD (BACnet Broadcast Management Device)

BACnet MS/TP diagnostic via Web interface

Foreign device support

L-VIS

Routes packets between BACnet MS/TP and BACnet/IP

Touch Panels

Features

BACnet MS/TP diagnostic LED

Lighting Control

MS/TP remote data packet capture (Wireshark)

Slave Proxy for up to 32 MS/TP slave devices

L-DALI

Ethernet link and activity LED

Specifications
107x100x60 (LxWxH), DIM009

Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xEthernet (100Base-T)
BACnet/IP, HTTP, FTP
1xBACnet MS/TP

Tools

Configuration via Web browser or console (EIA-232)

Configuration

LIP-ME201

BACnet/IP Router, 1xBACnet MS/TP (EIA-485), 1xEthernet-Port (BACnet/IP)

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LT-04

Network terminator, 1xEIA-485 (bus topology), 1xNetwork Access Connector RJ45

LT-B4

Network terminator, 1xEIA-485 (bus topology) with biasing circuit (failsafe biasing)

buildings under control

Software
Tools

Order number

Routers, NIC

Dimensions (mm)

109

The L-SwitchXP is the solution for interconnecting multiple twisted pair channels
(TP/FT-10 or TP/XF-1250 channels) in LonMark Systems. It provides up to five ports
and routes packets between these ports. The L-SwitchXP router delivers first class
performance and flexibility in use. In order to provide the optimal router configuration, the L-SwitchXP comes with 2 to 5 ports and two operating modes Smart
Switch Mode and Configured Router Mode.

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

L-ROC

Room Automation

L-WEB

Building Management

BACnet
DALI
CEA709

LS-33CB, LS-13CB, LS-11CB, LS-13300CB,


LS33300CB, LS-13333CB, LS-11333CB

Features
Physical separation and logical connection of up to five CEA709
network segments
Compliant with CEA-709 and ISO/IEC14908-1 (LonMark
System)

Gateways

Can be used as configured router, learning switch, or as


repeater*
Plug and Play installation *

Supports up to four domains *


Learning of the topology with forwarding decision based on
subnet/node and group addresses *
Short propagation delay between ports
Network diagnostic LEDs
CEA-709 status and activity LED
Shapes for LonMaker Network Management Tool available

Forwards packets of up to 256 bytes length

L-VIS

Touch Panels

* Smart Switch mode enabled

General Specifications
Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating
conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Software
Tools

Routers, NIC

L-DALI

Lighting Control

Specifications
Types

LS-33CB

LS-13CB

LS-11CB

LS-33300CB

Dimensions (mm)

107x100x60 (LxWxH), DIM010

Interfaces

2xTP/FT-10 1xTP/XF-1250 2xTP/XF-1250 3xTP/FT-10


1xTP/FT-10

Tools

Configuration via console (EIA-232)

LS-13300CB

LS-13333CB

LS-11333CB

159x100x60 (LxWxH), DIM008


1xTP/XF-1250
2xTP/FT-10

1xTP/XF-1250 2xTP/XF-1250
4xTP/FT-10
3xTP/FT-10

Order number

Configuration

LS-33CB

CEA-709 Router, 2xTP/FT-10

LS-13CB

CEA-709 Router, 1xTP/XF-1250, 1xTP/FT-10

LS-11CB

CEA-709 Router, 2xTP/XF-1250

LS-33300CB

CEA-709 Router, 3xTP/FT-10

LS-13300CB

CEA-709 Router, 1xTP/XF-1250, 2xTP/FT-10

LS-13333CB

CEA-709 Router, 1xTP/XF-1250, 4xTP/FT-10

LS-11333CB

CEA-709 Router, 2xTP/XF-1250, 3xTP/FT-10

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LT-03

Network terminator, 1xTP/FT-10 or TP/LPT-10 (bus or free topology), 1xNetwork Access Connector RJ45

LT-33

Network terminator, 2xTP/FT-10 or TP/LPT-10 (bus or free topology)

LT-13

Network terminator, 1xTP/FT-10 or TP/LPT-10 (bus or free topology), 1xTP/XF-1250

110

www.loytec.com

L-ROC

The multiplexed network interface (MNI) support allows starting multiple LNS or
MIP applications to run in parallel with an LPA on a single network interface.

Room Automation

LOYTEC NICs are the most universal network interfaces for CEA709 and IP-852
(Ethernet/IP) channels. Based on LOYTEC Core Technologies, they offer high packet
update rates and short response times. All NICs are fully compatible with products
like NL220, ALEX, LonMaker, and other LNS 3.x and LNS TE applications. The
NICs are also compatible with NodeUtil32, NLUtil, OPC servers, and high performance ORION applications.

L-WEB

NIC709-IP3E100, NIC709-IP1E100, NIC852,


NIC709USB100, NIC709-PCI100, NIC852-SW

Building Management

BACnet
DALI
CEA709

L-INX

Automation Servers

NIC709-IP1E100

EIA709/IP Interface
Made in Austria

CONNECT

LINK
ACT

serial

TP-1250

LOYTEC
www.loytec.com

B A

LOYTEC
www.loytec.com

100Base-T

DC
AC

N/A

Printer Port

USB
Port

NIC-IP
NIC709-IP1E100

TP-1250
TP-2500

RS-485

FT-10
LPT-10

www.loytec.com

- +
~ ~

15 16 17

IP-852

NIC-USB ?

LOYTEC network interface

2
1

A B
USB

status

12-35 VDC INPUT or


12-24 VAC, 40-70 Hz

A B A B

CONFIG

power

ACT

EIA709/IP Interface
Made in Austria

CONNECT

LINK
ACT

serial

LOYTEC
www.loytec.com

TP-1250
4

B A
5

100Base-T

LOYTEC
www.loytec.com

power

status

12-35 VDC INPUT or


12-24 VAC, 40-70 Hz

- +
~ ~

Intranet
Internet
VPN

Intranet
Internet
VPN

Intranet
Internet
VPN

DC
AC

15 16 17

Ethernet

Ethernet

Gateways

Made in Austria

CEA-709

PCI Bus

L-IOB

ACT

I/O Controllers/Modules

NIC-IP

Ethernet

USB Port

NIC709-IP

NIC852

L-VIS

NIC709-USB

Touch Panels

NIC709-PCI

NIC852-SW

Features

Available for USB, PCI bus, and Ethernet port

Compatible with high performance ORION applications (ORION


API)

Create up to eight network nodes with a single network interface (MNI devices)

Compatible with BMS e.g. Honeywell EBI, TAC VISTA, etc.


Compatible with LNS applications in high performance VNI
mode e.g. NL220, NLFacilities, NLOPC-VNI, ALEX, LonMaker,
etc.

NIC-852 is fully compatible with L-IP and i.LON 600 Internet


routers
Use legacy MIP applications together with the IP-852 (Ethernet)
channel
Runs on Windows XP, Windows Server 2003, Windows Vista,
Windows7, Windows Server2008
Runs on Linux 2.6 (NIC709-PCI100)

Routers, NIC

Use the LPA, LSD Tool, your ORION applications, MIP applications, and LNS (VNI) applications on a single network interface
at the same time

L-DALI

Compatible with MIP applications (LDV interface) e.g. NodeUtil32, NLUtil, NLOPC-MIP, Honeywell CARE 5/7, etc.

Lighting Control

Network interface for TP/FT-10, TP/XF-1250, RS485, and


Ethernet/IP (IP-852) channels

Software
Tools

buildings under control

111

L-WEB

Building Management

L-ROC

Room Automation

NIC709-IP3E100, NIC709-IP1E100, NIC852,


NIC709USB100, NIC709-PCI100, NIC852-SW
Specifications NIC709-IP3E100, NIC709-IP1E100
Dimensions (mm)

107x100x60 (LxWxH), DIM009

Power supply

12-35VDC / 12-24VAC 10%, typ. 3W

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Types

NIC709-IP3E100

Interfaces

1xEthernet (100Base-T)

NIC709-IP1E100

L-INX

Automation Servers

1xTP/FT-10

1xTP/XF-1250

Tools

LOYTEC Network Interface NIC Software

Operating system

Windows7, Windows Vista, Windows XP, Windows Server 2003/2008 R2

Resource limits
MNI devices

8 (multiplexed network interfaces)

Gateways

L-IOB

I/O Controllers/Modules

Specifications NIC709-PCI100, NIC709-USB100


Types

NIC709-PCI100

NIC709-USB100

Dimensions (mm)

PCI card 145x120x20 (LxWxH)

120x70x23 (LxWxH)

Power supply

Via PC, internal PCI bus (3.3V or 5.0V)

Via USB, max. 130mA

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Interfaces

1xTP/FT-10
1xTP/XF-1250
1xEIA-485 (RS-485)

Tools

LOYTEC Network Interface NIC software

Operating system

Windows7, Windows Vista, Windows XP, Windows Server 2003/2008 R2


Linux 2.6

Resource limits

L-VIS

Touch Panels

MNI devices

8 (multiplexed network interfaces)

Specifications NIC852
Power supply

Via USB, max. 50mA

Interfaces

1xUSB PC connector

Tools

LOYTEC Network Interface NIC software

Operating system

Windows7, Windows Vista, Windows XP, Windows Server 2003/2008 R2

MNI devices

8 (multiplexed network interfaces)

Order number

Configuration

NIC852

Floating license via USB hardlock key, uses Ethernet port of PC to connect to LonMark IP-852 channel

NIC852-SW

Software license for one PC, uses Ethernet port of PC to connect to LonMark IP-852 channel

NIC709-PCI100

PCI card (3.3V/5.0V) for a PC, supports LonMark TP/FT-10, TP/XF-1250, and TP/RS-485 channels

NIC709-USB100

USB interface, connects to the USB port of a PC, supports LonMark TP/FT-10, TP/XF-1250, and TP/RS-485 channels

NIC709-IP3E100

Remote network interface (RNI), PC connection via Ethernet, supports a LonMark TP/FT-10 channel

NIC709-IP1E100

Remote network interface (RNI), PC connection via Ethernet, supports a LonMark TP/XF-1250 channel

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

LT-03

Network terminator, 1xTP/FT-10 or TP/LPT-10 (bus or free topology), 1xNetwork Access Connector RJ45

LT-33

Network terminator, 2xTP/FT-10 or TP/LPT-10 (bus or free topology)

LT-13

Network terminator, 1xTP/FT-10 or TP/LPT-10 (bus or free topology), 1xTP/XF-1250

Software
Tools

Routers, NIC

L-DALI

Lighting Control

Resource limits

112

www.loytec.com

LT-03, LT-13, LT-33

LOYTEC offers several network terminators in DIN rail housing for the LonMark
TP/FT-10 and TP/XF-1250 channels.

L-INX

Automation Servers

L-Term LT-13 combines a terminator for a TP/FT-10 or TP/LPT-10 channel in bus or


free topology with a terminator for a TP/XF-1250 channel. LT-13 is the perfect solution to be used together with the LS-13CB, LS-13300CB, or the LS-13333CB L-Switch.

L-ROC

L-Term LT-33 offers two standard network terminators for TP/FT-10 or TP/LPT10
channels in bus and free topology. LT-33 is the perfect solution for LOYTEC network
infrastructure products (e.g. L-IP, L-Switch, L-Proxy etc.).

Room Automation

L-Term LT-03 offers one standard network terminator for a TP/FT-10 or TP/LPT-10
channel supporting bus and free topology. In addition, LT-03 comes with a network
access connector (RJ45) for a simple and reliable connection to the CEA709 network e.g. for maintenance or analyzing the network locally.

L-WEB

L-Term Network Terminator

Building Management

BACnet
DALI
CEA709

L-IOB

I/O Controllers/Modules

Gateways
L-VIS

Touch Panels

L-DALI

Lighting Control

General Specifications
Dimensions (mm)

27x88.5x59 (LxWxH), DIM027

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Configuration

LT-03

1xTP/FT-10 or TP/LPT-10 (bus or free topology)


1xNetwork Access Connector RJ45

LT-13

1xTP/FT-10 or TP/LPT-10 (bus or free topology)


1xTP/XF-1250

LT-33

2xTP/FT-10 or TP/LPT-10 (bus or free topology)

Routers, NIC

Order number

Software
Tools

buildings under control

113

LT-04, LT-B4

DALI
Modbus

LOYTEC offers network terminators for EIA-485 channels such as BACnet MS/TP,
Modbus or TP/RS485 (CEA-709) in DIN rail housings.
L-Term LT-04 is a terminator for EIA-485 channels. In addition, LT-04 comes with a
network access connector (RJ45) for a simple and reliable connection to the network e.g. for maintenance or analyzing the network locally.

L-ROC

Room Automation

L-WEB

Building Management

BACnet
CEA709

L-Term Network Terminator

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

The LT-B4 is a bus terminator for an EIA-485 channel with biasing circuit (failsafe
biasing). This biasing circuit draws the level of the bus during standby mode (idle)
to a safe value (logic 1). The LT-B4 needs a power supply of 24 VAC or 24 VDC.

General Specifications
Dimensions (mm)

27x88.5x59 (LxWxH), DIM027

Operating conditions

0C to 50C, 1090% RH @ 50C, non condensing, degree of protection: IP40, IP20 (terminals)

Termination impedance (Z)

120

Specifications
LT-04

LT-B4

Power supply

24 VDC or 24 VAC 10%

Order number

Configuration

LT-04

1xEIA-485 (bus topology)


1xNetwork Access Connector RJ45

LT-B4

1xEIA-485 (bus topology) with biasing circuit (failsafe biasing)

Software
Tools

Routers, NIC

Types

114

www.loytec.com

Software Tools

buildings under control

115

LOPC-BR800
The LOPC-BR800 Bridge Software allows OPC DA client applications based on
Microsofts COM/DCOM technology to access multiple distributed L-INX Automation Servers and L-ROC Room Controllers via OPC XML-DA. LOPC-BR800 represents
every single L-INX Automation Server or L-ROC Room Controller as an independent
OPC DA (COM/DCOM) server. The Bridge Software runs on the same PC as the OPC
client application of a higher-level system such as a SCADA system of a third-party
supplier.

L-ROC

Room Automation

L-WEB

Building Management

OPC Bridge Software

L-INX

Automation Servers

SCADA
LOPC-BR800
OPC DA Client (COM/DCOM)
OPC DA Client

I/O Controllers/Modules

SCADA

OPC DA Server

OPC DA Server

OPC XML-DA Client

OPC XML-DA Client

OPC XML-DA
SERVER

OPC XML-DA
SERVER

Gateways

L-IOB

OPC Bridge
LOPC-BR800

L-INX
1234

L-IOB

L-ROC
1234

L-VIS

Touch Panels

BACnet/IP, LONMARK IP-852, OPC XML-DA


LWEB-801 Server
Internet / Intranet
Router / Firewall

L-INX
21

L-ROC
1234

L-IOB

L-DALI

Lighting Control

L-INX
21

Routers, NIC

Specifications
For use with

L-INX, L-ROC, L-GATE, L-VIS, L-IOB I/O Controllers

Operating system

Windows7, Windows Vista, Windows XP, Windows Server 2003/2008 R2

OPC DA Version (COM/DCOM)

Compatible from OPC DA 2.05

Resource limits
Maximum number of LOYTEC devices supported per LOPC-BR800

Software
Tools

L-IOB

Order number

Product description

LOPC-BR800

OPC Bridge software to connect OPC DA Clients (COM/DCOM) to OPC XMLDA servers

116

www.loytec.com

L-INX
21

L-INX
L-IOB

I/O Controllers/Modules

The intuitive and easy-to-use LPA-SW software runs on all LOYTEC NIC709 interfaces. The LPA-IP-SW runs on the NIC-852 network interfaces. Each LPA-SW or
LPA-IP-SW license must be registered for one LOYTEC NIC.

Automation Servers

With a single mouse-click, the built-in report function creates reports (text files)
showing the health condition of the investigated channel and gives hints and
tips on how to solve problems on this channel.

L-ROC

The long time recording capability helps to find even intermittent faults on the
network. When the system is configured by an LNS based tool, the LPA software
can browse the database in order to display the node and network variable
names. Together with all LOYTEC devices featuring a Remote Network Interface
(RNI), the LPA-IP software can record packets even from remote twisted-pair
channels.

Room Automation

The LOYTEC Protocol Analyzer (LPA) for LonMark Systems captures all data
packets on CEA709 or IP-852 networks and displays all recorded packets on
a PC screen. The LPA software provides a comprehensive set of functions and
methods to view, filter, and analyze data packets down to bit level.

L-WEB

LPA-SW, LPA-IP-SW, LPA-SW, LPA-SET-USB

Building Management

LPA-CEA-709 Protocol Analyzer

Features
Trend Logging for bandwidth utilization and packet errors

Packet interpretation down to bit-level

LNS database interpretation

High resolution packet time-stamping

Interpretation of SNVTs, network management, and diagnostic


messages

Advanced, context specific packet filter and converter manipulation

Displays SNVTs in ISO and Imperial US system

Advanced Transaction Identification

Remote LPA function (needs LPA-IP) with L-IP, NIC709-IP, LVIS3E100, LVIS-3E112, LVIS3E115, LINX-100, LINX-110, LINX-120,
LINX-150, LROC-100, LROC-150

L-VIS

Long-term packet recording capability and error tracking in


packets with protocol errors
Touch Panels

Conversion of network addresses and variables into symbolic


names
Integrated Node Statistics for all detected domains, subnets,
nodes, and groups

Gateways

Online CEA709.1 packet monitoring in LonMark Systems

Extensive packet statistics (short packets, CRC errors, packets/s,


etc.)

Lighting Control

Statistic report function including hints and tips for solving network problems

L-DALI

Statistic report plug-in interface for localization or customization of the statistic report

Specifications
NIC709-PCI100, NIC709-USB100, NIC709-IP3E100, NIC709-IP1E100

LPA-IP-SW for use with

NIC852, NIC852-SW

Operating system

Windows7, Windows Vista, Windows XP, Windows Server 2003/2008 R2

Routers, NIC

LPA-SW for use with

Order number Product description


Set contains:
Network Interface NIC709-USB100 and NIC852
Protocol Analyzer Software LPA-IP-SW for CEA-852 Networks, registered to NIC852
Protocol Analyzer Software LPA-SW for CEA709 Networks, registered to NIC709-USB100

LPA-IP

IP-852 Channel Protocol Analyzer bundle contains:


Network Interface NIC852
Protocol Analyzer Software LPA-IP-SW for CEA-852 Networks, registered to NIC852

LPA-SW

Protocol Analyzer Software for CEA709 networks, NIC709 not included, must be ordered separately

LPA-IP-SW

Protocol Analyzer Software for IP-852, supports remote LPA, NIC852 not included, must be ordered separately

buildings under control

Software
Tools

LPA-SET-USB

117

WSPCert Certificates

Room Automation

L-WEB

Building Management

Zertifikate

L-IOB

I/O Controllers/Modules

L-INX

Automation Servers

L-ROC

The complete family of the BACnet enabled L-INX Automation Servers and
L-GATE Gateways are BTL tested according to the standard ISO 16484-5:2010 and
WSPCert certified as BACnet Building Controllers (B-BC).

L-DALI

Lighting Control

L-VIS

Touch Panels

Gateways

The LIP-ME201 BACnet/IP to BACnet MS/TP Router is BTL tested according to the
standard ISO 16484-5:2010 and WSPcert certified as BACnet Application Specific
Controller (B-ASC).

CERTIFICATE
Management system as per
EN ISO 9001:2008

Routers, NIC

In accordance with TV AUSTRIA CERT procedures, it is hereby certified that

LOYTEC electronics GmbH


Blumengasse 35
A-1170 Wien

EN ISO 9001:2008
We realize that the quality of our products substantially influences the overall
performance of our customers systems. Therefore we are committed to deliver
high quality as defined by ISO9001:2008. Our quality goals and their realization
are documented in our quality management handbook and in process documents.

applies a management system in line with the above standard for the
following scope

Software
Tools

development, production and distribution


of electronic devices and components
Certificate Registration No. 20 100 32000455

Valid until 2013-06-11


Initial certification 2004-03-24

Certification Body
at TV AUSTRIA CERT GMBH

Vienna, 2010-06-10

This certification was conducted in accordance with TV AUSTRIA CERT auditing and certification
procedures and is subject to regular surveillance audits.
TV AUSTRIA CERT GMBH Krugerstrae 16 A-1015 Wien www.tuv.at

118

www.loytec.com

Device Dimensions

buildings under control

119

Dimensions of the devices (in mm and [inch])


DIM001

LVIS-100-RE
LVIS-3E100
LVIS-ME200

176 [6.929]

88.5 [3.484]
38
118 [4.646]

47.5

[1.870]

210 [8.268]
SCALE 1 : 3
10 0
20

DIM002

[1.496]

148 [5.827]
57 [2.244]

164 [6.457]

LOYTEC
www.loytec.com

5.7

40

60

80

100 mm

LVIS-3E112
LVIS-ME212
[.984]

27

[1.063]

25

[63]

1600

[9.803]

249

246 [9.685]
329 [12.928]

20

120

SCALE 1 : 5
0 20 40 60 80 100 mm

www.loytec.com

[10.563]

LOYTEC
www.loytec.com

12.1

[7.295]

61 [2.402]

268.3

185.3

[.157]

30 [1.181]
90 [3.543]
299 [11.772]

Dimensions of the devices (in mm and [inch])


DIM003

LVIS-3E115
LVIS-ME215

[.984]

27

[1.063]

25

[.157]

30 [1.181]
90 [3.543]
353 [13.898]

61 [2.402]

LOYTEC
www.loytec.com
[12.520]

228.25

[63]

318

[11.563]

293.7

1600

[8.986]

15

304.4

[11.984]

394 [15.512]

20

LTEMP1

25

[.984]

LTEMP2

35.5 [1.398]

71 [2.795]

6 [.236]
60

[2.362]

DIM004

SCALE 1 : 5
0 20 40 60 80 100 mm

[.157]

71 [2.795]

10

SCALE 1 : 2
0
20

buildings under control

40

60

80

100 mm

121

LROC-100

LGATE951

LINX151

LROC-150

LINX120

LINX220

LINX121

LINX221

15

LINX150

Ethernet
1 2

Made in Austria

LOYTEC
www.loytec.com

USB

89 [3.504]
100 [3.937]

13

60 [2.362]

LGATE950

MICROSD

LINK
ACT
OPC

[.512]

DIM005

[.591]

Dimensions of the devices (in mm and [inch])

Ethernet 1 Ethernet 2

159 [6.260]
164 [6.457]

DIM006

LDALI3E101

LDALIME204

LDALI3E102

13
28

DA4

PROG CHANNEL

29

30

32

DA3

ON
OFF
AUTO

33

DA2

DALI4
ACT

DALI3
ACT

34

35

DA1
DALI2
ACT

DALI1
ACT

L-DALI
CN/IP

ACT

Made in Austria

LINK
IP ACT

power

serial

CONFIG

DALI

12-35 VDC INPUT or


12-24 VAC, 3W

Ethernet
13

14

15

100Base-T

status

89 [3.504]
100 [3.937]

27

[.512]

60 [2.362]

LDALI3E104

LOYTEC
www.loytec.com

- +
~ ~

DC
AC

24 25 26

159 [6.260]
164 [6.457]

10

122

www.loytec.com

SCALE 1 : 2
0
20

40

60

80

100 mm

Dimensions of the devices (in mm and [inch])


LIP-3333ECTB

13
EIA709/IP router

LIP-3333ECTB

Made in Austria

ACT

ACT

ACT

ACT

4 3 2 1
FT
4

FT

B A
5

FT

B A
8

B A

10 11 12

CNIP

LINK
ACT

serial

SERVER

B A

status

12-35 VDC INPUT or


12-24 VAC, 3W

FT
13 14 15

power

89 [3.504]
100 [3.937]

L-IP

[.512]

60 [2.362]

DIM007

LOYTEC
www.loytec.com

100Base-T

- +
~ ~

DC
AC

24 25 26

159 [6.260]
164 [6.457]

LS11333CB

LS33300CB

LS13300CB

13

L-SwitchXP
ACT

ACT

ACT

EIA709 multiport-router
Made in Austria

ACT

ACT

5 4 3 2 1
B A
1

B A
5

B A
8

B A

10 11 12

serial

power

status

[.512]

60 [2.362]

LS13333CB

89 [3.504]
100 [3.937]

DIM008

12-35 VDC INPUT or


12-24 VAC, 3W

LOYTEC
www.loytec.com

B A

13 14 15

- +
~ ~

DC
AC

24 25 26

159 [6.260]
164 [6.457]

10

SCALE 1 : 2
0
20

buildings under control

40

60

80

100 mm

123

Dimensions of the devices (in mm and [inch])


LINX211

NIC709-IP3E100

LINX100

LIP1ECTB

LINX101

LIP33ECRB

LINX110

LIP33ECTB

LINX111

LIP3ECTB

LINX200

LIPME201

LINX201

LP33E100

LINX210

NIC709-IP1E100

13
Made in Austria

ACT

LINK

ACT

ACT

2 1

serial

LOYTEC
www.loytec.com
1

100Base-T

power

status

[.512]

60

[2.362]

LGATE900

89 [3.504]
100 [3.937]

DIM009

12-35 VDC INPUT or


12-24 VAC, 40-70 Hz

- +
~ ~

DC
AC

15 16 17

107 [4.213]
112 [4.409]

DIM010

LS-11CB
LS-13CB

13
ACT

EIA709 router
Made in Austria

ACT

2 1

serial

LOYTEC
www.loytec.com
1

B A
2

89 [3.504]
100 [3.937]

L-SwitchXP
3

B A
5

power

[.512]

60

[2.362]

LS-33CB

status

12-35 VDC INPUT or


12-24 VAC, 40-70 Hz

- +
~ ~

DC
AC

15 16 17

107 [4.213]
112 [4.409]
10

124

www.loytec.com

SCALE 1 : 2
0
20

40

60

80

100 mm

Dimensions of the devices (in mm and [inch])


LIOB100

13
COM DO1 DO2 DO3 DO4 DO5 DO6 COM DO7 DO8 COM DO9

Made in Austria

6A

status

LOYTEC
www.loytec.com

LIOB-100

status

L-IOB

89 [3.504]
100 [3.937]

FUSE 6A

[.512]

60

[2.362]

15

[.591]

DIM011

I/O Module
UNIVERSAL IN
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

DIGITAL IN

0-10V OUT

DI1 GND DI2 AO1 GND AO2

107 [4.213]
112 [4.409]

13
DI1 GND DI2 DI3 GND DI4 DI5 GND DI6
Made in Austria

DIGITAL IN

LOYTEC
www.loytec.com

DI7 GND DI8 DI9 GND DI10 DI11 GND DI12


DIGITAL IN
status

LIOB-101

status

L-IOB

[.512]

60

[2.362]

15

[.591]

LIOB101

89 [3.504]
100 [3.937]

DIM012

I/O Module
UNIVERSAL IN
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

DIGITAL IN
DI16 GND DI15 DI14 GND DI13

107 [4.213]
112 [4.409]
10

SCALE 1 : 2
0
20

buildings under control

40

60

80

100 mm

125

Dimensions of the devices (in mm and [inch])


LIOB102

13
6A

6A

6A

6A

6A

6A

6A

LIOB-102

6A

Made in Austria

status

status

L-IOB

89 [3.504]
100 [3.937]

DO1 COM DO2 DO3 COM DO4 DO5 COM DO6 DO7 COM DO8

LOYTEC
www.loytec.com

[.512]

60

[2.362]

15

[.591]

DIM013

I/O Module
0-10V OUT
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

AO1 GND AO2 AO3 GND AO4 AO5 GND AO6

107 [4.213]
112 [4.409]

LIOB103

13
16A

DO3 DO3 DO4 DO4 DO5 DO5

16A

16A

16A

LIOB-103

16A

Made in Austria

status

status

L-IOB

89 [3.504]
100 [3.937]

DO1 DO1 DO2 DO2

LOYTEC
www.loytec.com

[.512]

60

[2.362]

15

[.591]

DIM014

I/O Module
0-10V OUT
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

AO1 GND AO2 AO3 GND AO4 AO5 GND AO6

107 [4.213]
112 [4.409]
10

126

www.loytec.com

SCALE 1 : 2
0
20

40

60

80

100 mm

LIOB151

LIOB181

LIOB152

LIOB182

15

LIOB180

[2.362]

LIOB150

13
A

FT

Made in Austria

LOYTEC
www.loytec.com

status

L-IOB

89 [3.504]
100 [3.937]

+~ -~

24 VAC/DC

[.512]

60

DIM015

[.591]

Dimensions of the devices (in mm and [inch])

107 [4.213]
112 [4.409]

[.591]

LIOB153

13
DO1 DO1 DO2 DO2
16A

16A

DO3 DO3 DO4 DO4 DO5 DO5


16A

LOYTEC
www.loytec.com

16A

status

6A

status

L-IOB

[.512]

60

[2.362]

15

LIOB183

89 [3.504]
100 [3.937]

DIM016

0-10V OUT
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

AO1 GND AO2 AO3 GND AO4 AO5 GND AO6

107 [4.213]
112 [4.409]
10

SCALE 1 : 2
0
20

buildings under control

40

60

80

100 mm

127

Dimensions of the devices (in mm and [inch])


LIOB154
[.591]

DIM017

13
+~ -~

24 VAC/DC

FT

[3.701]

DO1 DO2 DO3 DO4 DO5 COM


6A

6A

6A

6A

DO6 COM DO7

6A

LOYTEC
www.loytec.com

LIOB-154

LOW
HIGH

TRIAC

Made in Austria

PRESSURE

status

status

L-IOB
UNIVERSAL IN

89 [3.504]
100 [3.937]

28

[1.102]

94

[.512]

60

[2.362]

15

LIOB184

0-10V OUT

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8 AO1 GND AO2 AO3 GND AO4

107 [4.213]
112 [4.409]

LIOB450

LIOB580
[.591]

DIM018

15

LIOB480

13
+~ -~

24 VAC/DC

DO2 DO3 DO4 DO5 COM


6A

6A

6A

DO6 COM DO7 DO8 COM DO9

6A

TRIAC

LOYTEC
www.loytec.com

TRIAC

status

status

L-IOB
UNIVERSAL IN
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8

DIGITAL IN

89 [3.504]
100 [3.937]

ETHERNET
Made in Austria

[.512]

60

[2.362]

LIOB550

0-10V OUT

DI1 GND DI2 AO1 GND AO2

107 [4.213]
112 [4.409]
10

128

www.loytec.com

SCALE 1 : 2
0
20

40

60

80

100 mm

Dimensions of the devices (in mm and [inch])


LIOB451

LIOB581
[.591]

DIM019

15

LIOB481

13
+~ -~

24 VAC/DC

DI5 GND DI6 DI7 GND DI8


DIGITAL IN

DI9 GND DI10 DI11 GND DI12


DIGITAL IN

LOYTEC
www.loytec.com

status

L-IOB
UNIVERSAL IN

89 [3.504]
100 [3.937]

ETHERNET
Made in Austria

[.512]

60

[2.362]

LIOB551

DIGITAL IN

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8 DI16 GND DI15 DI14 GND DI13

107 [4.213]
112 [4.409]

LIOB582
[.591]

LIOB452

15

LIOB482

13
ETHERNET
Made in Austria

+~ -~

24 VAC/DC

DO1 COM DO2 DO3 COM DO4


6A

6A

6A

6A

DO5 COM DO6 DO7 COM DO8


6A

LOYTEC
www.loytec.com

6A

6A

6A

status

L-IOB

[.512]

60

[2.362]

LIOB552

89 [3.504]
100 [3.937]

DIM020

0-10V OUT
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

AO1 GND AO2 AO3 GND AO4 AO5 GND AO6

107 [4.213]
112 [4.409]
10

SCALE 1 : 2
0
20

buildings under control

40

60

80

100 mm

129

Dimensions of the devices (in mm and [inch])


LIOB453

LIOB583
[.591]

DIM021

15

LIOB483

13
+~ -~

DO1 DO1 DO2 DO2

24 VAC/DC

16A

DO3 DO3 DO4 DO4 DO5 DO5

16A

16A

LOYTEC
www.loytec.com

16A

status

6A

status

L-IOB

89 [3.504]
100 [3.937]

ETHERNET
Made in Austria

[.512]

60

[2.362]

LIOB553

0-10V OUT
UI1 GND UI2 UI3 GND UI4 UI5 GND UI6

AO1 GND AO2 AO3 GND AO4 AO5 GND AO6

107 [4.213]
112 [4.409]

LIOB454

LIOB584
[.591]

DIM022

15

LIOB484

13
ETHERNET
Made in Austria

+~ -~

24 VAC/DC

[3.701]

DO1 DO2 DO3 DO4 DO5 COM


6A

6A

6A

6A

DO6 COM DO7

6A

LOW
HIGH

TRIAC

LOYTEC
www.loytec.com

status

PRESSURE

status

L-IOB
UNIVERSAL IN

89 [3.504]
100 [3.937]

28

[1.102]

94

[.512]

60

[2.362]

LIOB554

0-10V OUT

UI1 GND UI2 UI3 GND UI4 UI5 GND UI6 UI7 GND UI8 AO1 GND AO2 AO3 GND AO4

107 [4.213]
112 [4.409]
10

130

www.loytec.com

SCALE 1 : 2
0
20

40

60

80

100 mm

Dimensions of the devices (in mm and [inch])


LIOBA2

13
Made in Austria

LIOB-A2

89 [3.504]
100 [3.937]

+ GND
24 VDC
INPUT

[.512]

60 [2.362]

DIM023

+ GND
24 VDC/100mA
OUTPUT

LOYTEC
www.loytec.com

L-IOB

Adapter 2
LIOB-CONNECT IN/OUT
SEL GND A

B TERM

55 [2.165]
60 [2.362]

L-MBUS20

13
MBUS Interface
Made in Austria

POWER

Port 2

Port 1 (TTL) Port 1

RS-232

Port 2

TXD

RXD

L-MBUS
GND

-~

24 VAC/DC

SHORT
POWER

LOYTEC
www.loytec.com

89 [3.504]
100 [3.937]

L-MBUS

[.512]

60

[2.362]

L-MBUS80

+~

DIM024

MBUS

107 [4.213]
112 [4.409]

10

SCALE 1 : 2
0
20

buildings under control

40

60

80

100 mm

131

Dimensions of the devices (in mm and [inch])


LKNX-300

13
Made in Austria

LOYTEC
www.loytec.com

L-KNX

KNX Interface
EXT
GND B

89 [3.504]
100 [3.937]

LKNX-300

[.512]

60 [2.362]

DIM025

KNX

PROG.

- +

55 [2.165]
60 [2.362]

DIM027

LT-03

LT-33

LT-04

LT-B4

13

[.512]

59

[2.323]

LT-13

27

L-Term LT-03
Bus Terminator

LOYTEC
www.loytec.com
TP/FT-10
COM FREE BUS

BUS FREE COM

GND 24 V NC

TP/XF-1250
LOYTEC
www.loytec.com

TP/FT-10
LOYTEC
www.loytec.com

LOYTEC
www.loytec.com

L-Term

L-Term

L-Term LT-B4

Bus Terminator
TP/FT-10

Bus Terminator
TP/FT-10

510

88.5

BUS FREE COM


8

[3.484]

[1.063]

COM FREE BUS

COM FREE BUS

L-Term LT-04
Bus Terminator

LOYTEC
www.loytec.com

RS-485
+

NC

LT-13

10

132

NC

+5V
1

www.loytec.com

GND

LT-33

SCALE 1 : 2
0
20

40

Bus Terminator
+5V

RS-485
120

510 GND

60

NC

80

100 mm

Dimensions of the devices (in mm and [inch])


DIM029

LPOW-2415B

L-POW

Power Supply
Input
N
L

85-265VAC
50/60 Hz

status

LOYTEC
www.loytec.com

L-POW

Power Supply

Output
24VDC/15W

Input
N
L

55 [2.165]
60 [2.362]

85-265VAC
50/60 Hz

24VDC/15W
GND +

55 [2.165]
60 [2.362]

LDALI-PWR2-U

13
POWER

DA1+ DA1DALI 1

DA2+ DA2DALI 2

85-240VAC
50/60 Hz

DA4+ DA4DALI 4

L-DALI

Power Supply

LOYTEC
www.loytec.com
Input
N
L

DA3+ DA3DALI 3

[.512]

60

[2.362]

LDALI-PWR4-U

89 [3.504]
100 [3.937]

DIM030

Made in Austria

[.512]

13
LPOW-2415B

89 [3.504]
100 [3.937]

LOYTEC
www.loytec.com

[.512]

13
status

89 [3.504]
100 [3.937]

Made in Austria

LPOW-2415A

60 [2.362]

LPOW-2415A
60 [2.362]

DIM028

OUTPUT
DALI 4x 116mA

Made in Austria

LDALI-PWR4-U

107 [4.213]
112 [4.409]

10

buildings under control

SCALE 1 : 2
0
20

40

60

80

100 mm

133

Dimensions of the devices (in mm and [inch])


LDALI-3101-U

13
FT

230mA DA+ DA-

DALI Multi-Master
status

status

L-DALI

89 [3.504]
100 [3.937]

LOYTEC
LDALI-3101-U
www.loytec.com

[.512]

60

[2.362]

15

[.591]

DIM032

CEA-709 DALI Controller


N

INPUT

85-240VAC 50/60 Hz

Made in Austria

107 [4.213]
112 [4.409]

LDALI-E101-U
[.591]

DIM033

13
DALI Multi-Master

LOYTEC
www.loytec.com

status

status

L-DALI
N

INPUT

85-240VAC 50/60 Hz

89 [3.504]
100 [3.937]

230mA DA+ DA-

ETHERNET

[.512]

60

[2.362]

15

LDALI-E201-U

Made in Austria

107 [4.213]
112 [4.409]
10

134

www.loytec.com

SCALE 1SCALE
:2
1 :2
0 10
0 20
20 40

40 60

60 80

80 100 mm100 mm

Technology Reference List


CEA709, ISO/IEC14908-1 LonMark System
Order number

Product description

LROC-100

Room Controller with LIOBConnect for room segment management

Page
30

LROC-150

Room Controller with LIOBConnect for aisle, floor, building or campus management

30

LROC-START-100

Starter kit: LROC-100, LIOB100, LSTUDIO

30

LINX150

BACnet & CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

36

LINX151

BACnet & CEA709 Automation Server with LIOBConnect and built-in BACnet/IP & IP-852 Router

36

LINXSTART-150

Starter kit: LINX150, LIOB100, LIOB102, and LLOGICAD software license

36

LINX120

CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

40

LINX121

CEA709 Automation Server with LIOBConnect and built-in IP-852 Router

40

LINXSTART-120

Starter kit: LINX120, LIOB100, LIOB102, and LLOGICAD license

40

LINX110

CEA709 Automation Server, IEC 61131-3 programmable, built-in Remote Network Interface (RNI)

46

LINX111

CEA709 Automation Server, IEC 61131-3 programmable, built-in IP-852 Router

46

LINXSTART-LC2

Starter kit: LINX100, LINX110, and LLOGICAD license

46

LINX100

CEA709 Automation Server, built-in Remote Network Interface (RNI)

51

LINX101

CEA709 Automation Server, built-in IP-852 Router

51

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

66

LIOB151

LIOBFT I/O Module: 8UI, 12DI

66

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

66

LIOB153

LIOBFT I/O Module: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

66

LIOB154

LIOBFT I/O Module: 7UI, 4AO, 7DO, 1Pressure Sensor

66

LIOB180

LIOBFT I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

57

LIOB181

LIOBFT I/O Controller: 8UI, 12DI

57

LIOB182

LIOBFT I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

57

LIOB183

LIOBFT I/O Controller: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

57

LIOB184

LIOBFT I/O Controller: 7UI, 4AO, 7DO, 1 Pressure Sensor

57

LIOB450

LIOBIP852 I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

68

LIOB451

LIOBIP852 I/O Module: 8UI, 12DI

68

LIOB452

LIOBIP852 I/O Module: 6UI, 6AO, 8DO (Relay 6A)

68

LIOB453

LIOBIP852 I/O Module: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

68

LIOB454

LIOBIP852 I/O Module: 7UI, 4AO, 7DO, 1Pressure Sensor

68

LIOB480

LIOBIP852 I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

59

LIOB481

LIOBIP852 I/O Controller: 8UI, 12DI

59

LIOB482

LIOBIP852 I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

59

LIOB483

LIOBIP852 I/O Controller: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

59

LIOB484

LIOBIP852 I/O Controller: 7UI, 4AO, 7DO, 1Pressure Sensor

59

LGATE-950

Universal Gateway

75

LGATE-951

Universal Gateway

75

LGATE-900

CEA709/BACnet Gateway

77

LVIS-100-RE

CEA709 Touch Panel Room Edition with 5.7" display (LonMark System)

84

LVIS-3E100

CEA709 Touch Panel with 5.7" display (LonMark System)

86

LVIS-3E112

CEA709 Touch Panel with 12.1" display (LonMark System)

86

LVIS-3E115

CEA709 Touch Panel with 15" display (LonMark System)

86

buildings under control

135

Technology Reference List


CEA709, ISO/IEC14908-1 LonMark System
Order number Product description

Page

LDALI-3E101

CEA709/DALI Controller, AST, Sunblind Controller, 1 DALI channel

94

LDALI-3E102

CEA709/DALI Controller, AST, Sunblind Controller, 2 DALI channels

94

LDALI-3E104

CEA709/DALI Controller, AST, Sunblind Controller, 4 DALI channels

94

LDALI-3101-U

CEA709/DALI Controller for TP/FT-10 (LonMark System), 1DALI channel, integrated DALI power supply

100

LDALI-E101-U

CEA709/DALI Controller for IP-852 (Ethernet), 1DALI channel, integrated DALI power supply

100

LP-33E100

LProxy CEA709 Multiport Gateway

<?>

LIP-3ECTB

CEA709/IP-852 Router, 1xTP/FT-10, 1xEthernet-Port (IP-852)

106

LIP-1ECTB

CEA709/IP-852 Router, 1xTP/XF-1250, 1xEthernet-Port (IP-852)

106

LIP-33ECTB

CEA709/IP-852 Router, 2xTP/FT-10, 1xEthernet-Port (IP-852)

106

LIP-3333ECTB

CEA709/IP-852 Router, 4xTP/FT-10, 1xEthernet-Port (IP-852)

106

LIP-33ECRB

CEA709/IP-852 Router for redundant mode, 2xTP/FT-10, 1xEthernet-Port (IP-852)

108

LS-33CB

LSwitch CEA709 Router, 2xTP/FT-10

110

LS-13CB

LSwitch CEA709 Router, 1xTP/XF-1250, 1xTP/FT-10

110

LS-11CB

LSwitch CEA709 Router, 2xTP/XF-1250

110

LS-33300CB

LSwitch CEA709 Router, 3xTP/FT-10

110

LS-13300CB

LSwitch CEA709 Router, 1xTP/XF-1250, 2xTP/FT-10

110

LS-13333CB

LSwitch CEA709 Router, 1xTP/XF-1250, 4xTP/FT-10

110

LS-11333CB

LSwitch CEA709 Router, 2xTP/XF-1250, 3xTP/FT-10

110

NIC852

Floating license via USB hardlock key, uses Ethernet port of PC to connect to LonMark IP-852 channel

111

NIC852-SW

Software license for one PC, uses Ethernet port of PC to connect to LonMark IP-852 channel

111

NIC709-PCI100

PCI card (3.3V/5.0V) for a PC, supports LonMark TP/FT-10, TP/XF-1250, and TP/RS-485 channels

111

NIC709-USB100

USB interface, connects to the USB port of a PC, supports LonMark TP/FT-10, TP/XF-1250,
TP/RS-485 channels

111

NIC709-IP3E100

Remote network interface (RNI), PC connection via Ethernet, supports a LonMark TP/FT-10 channel

111

NIC709-IP1E100

Remote network interface (RNI), PC connection via Ethernet, supports a LonMark TP/XF-1250 channel

111

LT-03

Network terminator, 1xTP/FT-10 or TP/LPT-10 (bus- or free topology), 1xNetwork Access Connector RJ45

113

LT-13

Network terminator, 1xTP/FT-10 or TP/LPT-10 (bus- or free topology), 1xTP/XF-1250

113

LT-33

Network terminator, 2xTP/FT-10 or TP/LPT-10 (bus- or free topology)

113

LT-04

Network terminator, 1xEIA-485 (bus topology), 1xNetwork Access Connector RJ45

114

LT-B4

Network terminator, 1xEIA-485 (bus topology) with biasing circuit (failsafe biasing)

114

LPA-SET-USB

Set contains:
Network Interface NIC709-USB100 and NIC852
Protocol Analyzer Software LPA-IP-SW for CEA-852 Networks, registered to NIC852
Protocol Analyzer Software LPA-SW for CEA709 Networks, registered to NIC709-USB100

117

LPA-IP

IP-852 Channel Protocol Analyzer bundle contains:


Network Interface NIC852
Protocol Analyzer Software LPA-IP-SW for CEA-852 Networks, registered to NIC852

117

LPA-SW

Protocol Analyzer Software, supports all NIC709 network interfaces

117

LPA-IP-SW

Protocol Analyzer Software for IP-852 channels, supports Remote LPA functionality

117

136

www.loytec.com

Technology Reference List


BACnet ISO 16484-5
Order number

Product description

Page

LROC-100

Room Controller with LIOBConnect for room segment management

30

LROC-150

Room Controller with LIOBConnect for aisle, floor, building or campus management

30

LROC-START-100

Starter kit: LROC-100, LIOB100, LSTUDIO

30

LINX150

BACnet & CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

36

LINX151

BACnet & CEA709 Automation Server with LIOBConnect and built-in BACnet/IP & IP-852 Router

36

LINXSTART-150

Starter kit: LINX150, LIOB100, LIOB102, and LLOGICAD software license

36

LINX220

BACnet Automation Server with LIOBConnect, B-BC

43

LINX221

BACnet Automation Server with LIOBConnect, B-BC, and built-in BACnet/IP to MS/TP Router

43

LINXSTART-220

Starter kit: LINX220, LIOB100, LIOB102, and LLOGICAD software license

43

LINX210

BACnet Automation Server, B-BC, IEC 61131-3 programmable

49

LINX211

BACnet Automation Server, B-BC, IEC 61131-3 programmable, built-in BACnet/IP to MS/TP Router

49

LINXSTART-BC2

Starter kit: LINX200, LINX210, and LLOGICAD software license

49

LINX200

BACnet Automation Server, B-BC

53

LINX201

BACnet Automation Server, B-BC, built-in BACnet/IP to MS/TP Router

53

LIOB550

LIOBBIP I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

70

LIOB551

LIOBBIP I/O Module: 8UI, 12DI

70

LIOB552

LIOBBIP I/O Module: 6UI, 6AO, 8DO (Relay 6A)

70

LIOB553

LIOBBIP I/O Module: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

70

LIOB554

LIOBBIP I/O Module: 7UI, 4AO, 7DO, 1Pressure Sensor

70

LIOB580

LIOBBIP I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

61

LIOB581

LIOBBIP I/O Controller: 8UI, 12DI

61

LIOB582

LIOBBIP I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

61

LIOB583

LIOBBIP I/O Controller: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

61

LIOB584

LIOBBIP I/O Controller: 7UI, 4AO, 7DO, 1Pressure Sensor

61

LGATE-950

Universal Gateway

75

LGATE-951

Universal Gateway

75

LGATE-900

CEA709/BACnet Gateway

77

LVIS-ME200

BACnet Touch Panel with 5.7" display, B-BC

90

LVIS-ME212

BACnet Touch Panel with 12.1" display, B-BC

90

LVIS-ME215

BACnet Touch Panel with 15" display, B-BC

90

LDALI-ME204

BACnet/DALI Controller, 4 DALI channels

97

LDALI-E201-U

BACnet DALI Controller fr BACnet/IP with integrated DALI-Power supply

102

LIP-ME201

BACnet/IP Router, 1xBACnet MS/TP (EIA-485), 1xEthernet-Port (BACnet/IP)

109

LT-04

Network terminator, BACnet MS/TP, 1xEIA-485 (bus topology), 1xNetwork Access Connector RJ45

114

LT-B4

Network terminator, BACnet MS/TP, 1xEIA-485 (bus topology) with biasing circuit (failsafe biasing)

114

buildings under control

137

Technology Reference List


L-IOB I/O Modules, Controllers and Accessories
Order number Product description

Page

LIOBA2

LIOB Adapter 2 to split the line of LIOBConnect modules on the DINrail for space and power considerations

64

LIOB100

LIOBConnect I/O Module: 8UI, 2DI, 2AO, 9DO (5xRelay 6A)

64

LIOB101

LIOBConnect I/O Module: 8UI, 16DI

64

LIOB102

LIOBConnect I/O Module: 6UI, 6AO, 8DO (Relay 6A)

64

LIOB103

LIOBConnect I/O Module: 6UI, 6AO, 5DO (Relay 16A)

64

LIOB150

LIOBFT I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac 1A, 4xRelay 6A)

66

LIOB151

LIOBFT I/O Module: 8UI, 12DI

66

LIOB152

LIOBFT I/O Module: 6UI, 6AO, 8DO (Relay 6A)

66

LIOB153

LIOBFT I/O Module: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

66

LIOB154

LIOBFT I/O Module: 7UI, 4AO, 7DO, 1Pressure Sensor

66

LIOB180

LIOBFT I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

57

LIOB181

LIOBFT I/O Controller: 8UI, 12DI

57

LIOB182

LIOBFT I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

57

LIOB183

LIOBFT I/O Controller: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

57

LIOB184

LIOBFT I/O Controller: 7UI, 4AO, 7DO, 1 Pressure Sensor

57

LIOB450

LIOBIP852 I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

68

LIOB451

LIOBIP852 I/O Module: 8UI, 12DI

68

LIOB452

LIOBIP852 I/O Module: 6UI, 6AO, 8DO (Relay 6A)

68

LIOB453

LIOBIP852 I/O Module: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

68

LIOB454

LIOBIP852 I/O Module: 7UI, 4AO, 7DO, 1Pressure Sensor

68

LIOB480

LIOBIP852 I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

59

LIOB481

LIOBIP852 I/O Controller: 8UI, 12DI

59

LIOB482

LIOBIP852 I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

59

LIOB483

LIOBIP852 I/O Controller: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

59

LIOB484

LIOBIP852 I/O Controller: 7UI, 4AO, 7DO, 1Pressure Sensor

59

LIOB550

LIOBBIP I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

70

LIOB551

LIOBBIP I/O Module: 8UI, 12DI

70

LIOB552

LIOBBIP I/O Module: 6UI, 6AO, 8DO (Relay 6A)

70

LIOB553

LIOBBIP I/O Module: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

70

LIOB554

LIOBBIP I/O Module: 7UI, 4AO, 7DO, 1Pressure Sensor

70

LIOB580

LIOBBIP I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

61

LIOB581

LIOBBIP I/O Controller: 8UI, 12DI

61

LIOB582

LIOBBIP I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

61

LIOB583

LIOBBIP I/O Controller: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

61

LIOB584

LIOBBIP I/O Controller: 7UI, 4AO, 7DO, 1Pressure Sensor

61

LPOW-2415A

LIOBConnect power supply unit, 24VDC, 15W

82

LPOW-2415B

Power supply unit with power connector 24VDC, 15W

82

LTEMP2

External temperature sensor (NTC10K) for use with LIOB Universal Inputs

57

138

www.loytec.com

Technology Reference List


Modbus RTU and TCP
Order number Product description

Page

LROC-150

Room Controller with LIOBConnect for aisle, floor, building or campus management

30

LINX150

BACnet & CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

36

LINX151

BACnet & CEA709 Automation Server with LIOBConnect and built-in BACnet/IP & IP-852 Router

36

LINXSTART-150

Starter kit: LINX150, LIOB100, LIOB102, and LLOGICAD software license

36

LINX120

CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

40

LINX121

CEA709 Automation Server with LIOBConnect and built-in IP-852 Router

40

LINXSTART-120

Starter kit: LINX120, LIOB100, LIOB102, and LLOGICAD software license

40

LINX220

BACnet Automation Server with LIOBConnect, B-BC

43

LINX221

BACnet Automation Server with LIOBConnect, B-BC, and built-in BACnet/IP to MS/TP Router

43

LINXSTART-220

Starter kit: LINX220, LIOB100, LIOB102, and LLOGICAD software license

43

LINX110

CEA709 Automation Server, IEC 61131-3 programmable, built-in Remote Network Interface (RNI)

46

LINX111

CEA709 Automation Server, IEC 61131-3 programmable, built-in IP-852 Router

46

LINXSTART-LC2

Starter kit: LINX100, LINX110, and LLOGICAD license

46

LINX210

BACnet Automation Server, B-BC, IEC 61131-3 programmable

49

LINX211

BACnet Automation Server, B-BC, IEC 61131-3 programmable, built-in BACnet/IP to MS/TP Router

49

LINXSTART-BC2

Starter kit: LINX200, LINX210, and LLOGICAD software license

49

LINX100

CEA709 Automation Server, with Remote Network Interface (RNI)

51

LINX101

CEA709 Automation Server, built-in IP-852 Router

51

LINX200

BACnet Automation Server, B-BC

53

LINX201

BACnet Automation Server, B-BC, built-in BACnet/IP to MS/TP Router

53

LGATE-950

Universal Gateway

75

LGATE-951

Universal Gateway

75

LT-04

Network terminator, BACnet MS/TP, 1xEIA-485 (bus topology), 1xNetwork Access Connector RJ45

114

LT-B4

Network terminator, BACnet MS/TP, 1xEIA-485 (bus topology) with biasing circuit (failsafe biasing)

114

buildings under control

139

Technology Reference List


MBus EN13757
Order number Product description

Page

LROC-150

Room Controller with LIOBConnect for aisle, floor, building or campus management

30

LINX150

BACnet & CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

36

LINX151

BACnet & CEA709 Automation Server with LIOBConnect and built-in BACnet/IP & IP-852 Router

36

LINXSTART-150

Starter kit: LINX150, LIOB100, LIOB102, and LLOGICAD software license

36

LINX120

CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

40

LINX121

CEA709 Automation Server with LIOBConnect and built-in IP-852 Router

40

LINXSTART-120

Starter kit: LINX120, LIOB100, LIOB102, and LLOGICAD software license

40

LINX220

BACnet Automation Server with LIOBConnect, B-BC

43

LINX221

BACnet Automation Server with LIOBConnect, B-BC, and built-in BACnet/IP to MS/TP Router

43

LINXSTART-220

Starter kit: LINX220, LIOB100, LIOB102, and LLOGICAD software license

43

LINX110

CEA709 Automation Server, IEC 61131-3 programmable, built-in Remote Network Interface (RNI)

46

LINX111

CEA709 Automation Server, IEC 61131-3 programmable, built-in IP-852 Router

46

LINXSTART-LC2

Starter kit: LINX100, LINX110, and LLOGICAD license

46

LINX210

BACnet Automation Server, B-BC, IEC 61131-3 programmable

49

LINX211

BACnet Automation Server, B-BC, IEC 61131-3 programmable, built-in BACnet/IP to MS/TP Router

49

LINXSTART-BC2

Starter kit: LINX200, LINX210, and LLOGICAD software license

49

LINX100

CEA709 Automation Server, built-in Remote Network Interface (RNI)

51

LINX101

CEA709 Automation Server, built-in IP-852 Router

51

LINX200

BACnet Automation Server, B-BC

53

LINX201

BACnet Automation Server, B-BC built-in BACnet/IP to MS/TP Router

53

LGATE-950

Universal Gateway

75

LGATE-951

Universal Gateway

75

L-MBUS20

M-Bus level converter for 20M-Bus devices

81

L-MBUS80

M-Bus level converter for 80M-Bus devices

81

L-CABLE1

Connection cable between LINXx0x Automation Server and L-MBUSx0 M-Bus-Converter

81

DALI IEC62386
Order number Product description

Page

LDALI-3E101

CEA709/DALI Controller, AST, Sunblind Controller, 1 DALI channel

94

LDALI-3E102

CEA709/DALI Controller, AST, Sunblind Controller, 2 DALI channels

94

LDALI-3E104

CEA709/DALI Controller, AST, Sunblind Controller, 4 DALI channels

94

LDALI-ME204

BACnet/DALI Controller, 4 DALI channels

97

LDALI-PWR2-U

DALI power supply unit for 2 DALI channels

104

LDALI-PWR4-U

DALI power supply unit for 4 DALI channels

104

LDALI-3101-U

CEA709/DALI Controller for TP/FT-10 (LonMark System), 1DALI channel, integrated DALI power supply

100

LDALI-E101-U

CEA709/DALI Controller for IP-852 (Ethernet), 1DALI channel, integrated DALI power supply

100

LDALI-E201-U

BACnet/DALI Controller for BACnet/IP, 1DALI channel, integrated DALI power supply

102

140

www.loytec.com

Technology Reference List


OPC
Order number Product description

Page

LROC-100

Room Controller with LIOBConnect for room segment management

30

LROC-150

Room Controller with LIOBConnect for aisle, floor, building or campus management

30

LINX150

BACnet & CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

36

LINX151

BACnet & CEA709 Automation Server with LIOBConnect and built-in BACnet/IP & IP-852 Router

36

LINXSTART-150

Starter kit: LINX150, LIOB100, LIOB102, and LLOGICAD software license

36

LINX120

CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

40

LINX121

CEA709 Automation Server with LIOBConnect and built-in IP-852 Router

40

LINXSTART-120

Starter kit: LINX120, LIOB100, LIOB102, and LLOGICAD software license

40

LINX220

BACnet Automation Server with LIOBConnect, B-BC

43

LINX221

BACnet Automation Server with LIOBConnect, B-BC, and built-in BACnet/IP to MS/TP Router

43

LINXSTART-220

Starter kit: LINX220, LIOB100, LIOB102, and LLOGICAD software license

43

LINX110

CEA709 Automation Server, IEC 61131-3 programmable, built-in Remote Network Interface (RNI)

46

LINX111

CEA709 Automation Server, IEC 61131-3 programmable, built-in IP-852 Router

46

LINXSTART-LC2

Starter kit: LINX100, LINX110, and LLOGICAD license

46

LINX210

BACnet Automation Server, B-BC, IEC 61131-3 programmable

49

LINX211

BACnet Automation Server, B-BC, IEC 61131-3 programmable, built-in BACnet/IP to MS/TP Router

49

LINXSTART-BC2

Starter kit: LINX200, LINX210, and LLOGICAD software license

49

LINX100

CEA709 Automation Server, with Remote Network Interface (RNI)

51

LINX101

CEA709 Automation Server, built-in IP-852 Router

51

LINX200

BACnet Automation Server, B-BC

53

LINX201

BACnet Automation Server, B-BC, built-in BACnet/IP to MS/TP Router

53

LIOB480

LIOBIP852 I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

59

LIOB481

LIOBIP852 I/O Controller: 8UI, 12DI

59

LIOB482

LIOBIP852 I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

59

LIOB483

LIOBIP852 I/O Controller: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

59

LIOB484

LIOBIP852 I/O Controller: 7UI, 4AO, 7DO, 1Pressure Sensor

59

LIOB550

LIOBBIP I/O Module: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

70

LIOB551

LIOBBIP I/O Module: 8UI, 12DI

70

LIOB552

LIOBBIP I/O Module: 6UI, 6AO, 8DO (Relay 6A)

70

LIOB553

LIOBBIP I/O Module: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

70

LIOB554

LIOBBIP I/O Module: 7UI, 4AO, 7DO, 1Pressure Sensor

70

LIOB580

LIOBBIP I/O Controller: 8UI, 2DI, 2AO, 8DO (4xTriac, 4xRelay 6A)

61

LIOB581

LIOBBIP I/O Controller: 8UI, 12DI

61

LIOB582

LIOBBIP I/O Controller: 6UI, 6AO, 8DO (Relay 6A)

61

LIOB583

LIOBBIP I/O Controller: 6UI, 6AO, 5DO (4xRelay 16A, 1xRelay 6A)

61

LIOB584

LIOBBIP I/O Controller: 7UI, 4AO, 7DO, 1Pressure Sensor

61

LGATE-950

Universal Gateway

75

LGATE-951

Universal Gateway

75

LGATE-900

CEA709/BACnet Gateway

77

LVIS-3E100

CEA709 Touch Panel with 5.7" display (LonMark System)

86

LVIS-3E112

CEA709 Touch Panel with 12.1" display (LonMark System)

86

LVIS-3E115

CEA709 Touch Panel with 15" display (LonMark System)

86

LVIS-ME200

BACnet Touch Panel with 5.7" display, B-BC

90

LVIS-ME212

BACnet Touch Panel with 12.1" display, B-BC

90

LVIS-ME215

BACnet Touch Panel with 15" display, B-BC

90

buildings under control

141

Technology Reference List


KNX EN50090
Order number Product description

Page

LROC-100

Room Controller with LIOBConnect for room segment management

30

LROC-150

Room Controller with LIOBConnect for aisle, floor, building or campus management

30

LROC-START-100 Starter kit: LROC-100, LIOB100, LSTUDIO

30

LINX150

BACnet & CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

36

LINX151

BACnet & CEA709 Automation Server with LIOBConnect and built-in BACnet/IP & IP-852 Router

36

LINXSTART-150

Starter kit: LINX150, LIOB100, LIOB102, and LLOGICAD software license

36

LINX120

CEA709 Automation Server with LIOBConnect and built-in Remote Network Interface (RNI)

40

LINX121

CEA709 Automation Server with LIOBConnect and built-in IP-852 Router

40

LINXSTART-120

Starter kit: LINX120, LIOB100, LIOB102, and LLOGICAD software license

40

LINX220

BACnet Automation Server with LIOBConnect, B-BC

43

LINX221

BACnet Automation Server with LIOBConnect, B-BC, and built-in BACnet/IP to MS/TP Router

43

LINXSTART-220

Starter kit: LINX220, LIOB100, LIOB102, and LLOGICAD software license

43

LGATE-950

Universal Gateway

75

LGATE-951

Universal Gateway

75

LKNX-300

KNX interface to connect KNXTP1 devices

80

142

www.loytec.com

AST, LC3020, L-Chip, L-Core, L-DALI, L-GATE, L-INX, L-IOB, LIOB-Connect, LIOB-FT, L-IP, L-KNX, L-MBUS, L-OPC, LPA, L-POW, L-Proxy, L-ROC, L-STUDIO, L-Switch,
L-Term, L-VIS, L-WEB, ORION Stack, Smart Auto-Connect, buildings under control are trademarks of LOYTEC electronics GmbH.
Echelon, LON, LONWORKS, LNS, LonMaker, and Neuron are trademarks of Echelon Corporation registered in the United States and other countries.
LonMark and the LonMark Logo are registered trademarks owned by LonMark International. BACnet is a registered trade mark of the American Society of
Heating, Refrigerating and Air Conditioning Engineers, Inc. (ASHRAE).
KNX Association cvba is the owner of the worldwide standard for Home and Building Control: KNX and also the owner of the KNX trademark logo
worldwide.
Other trademarks and trade names used in this document refer either to the entities claiming the markets and names, or to their products. LOYTEC
disclaims proprietary interest in the markets and names of others.
Statements in this report that relate to future results and events are based on the companys current expectations. Actual results in future periods may
differ materially from those currently expected or desired because of a number of risks and uncertainties.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without the prior written permission of LOYTEC. Product specifications, availability, and design are subject to
change without prior notice.

Document No. 04007409

buildings under control

IMPRINT
Owner: LOYTEC electronics GmbH
Place of Manufacture: Wien
Typesetting and printing errors reserved

143

buildings under control

OUR MISSION
LOYTEC researches, develops and manufactures products and solutions to open up
new ways and opportunities for the modern building automation business.
Utilizing innovative technologies and open communication protocols in trendsetting
products, LOYTEC creates the basis for efficient system integration, highest energy
efficiency during operation and protection of investments taken by investors.

CONTACT
LOYTEC electronics GmbH
Blumengasse 35
1170 Vienna
Austria
www.loytec.com
info@loytec.com
phone: +43 (1) 4020805-0
fax: +43 (1) 4020805-99

LOYTEC Americas, Inc.


N27W23957 Paul Road
Suite 103
Pewaukee, WI 53072
USA
www.loytec-americas.com
info@loytec-americas.com
phone: +1 (262) 278-4370
fax: +1 (262) 408-5238

You might also like