Professional Documents
Culture Documents
OVERCURRENT
PROTECTION
Overcurrent Protection
Discrimination by time
An appropriate time interval is given to ensure that the breaker nearest to
the fault opens first.
L
1.45
1.05
0.65
0.25
Discrimination By Currents
The fault current varies with the position of the fault.
0.24 0hms
X
11 kV
250MVA
X
H F2
11 10 3
3 (Z S + Z L )
11
=
250
= 0.485 ohms
ZL = 0.24 ohms
Hence
I=
11 10 3
3 (0.725)
= 8800 A
Discrimination By Currents
Relay setting of 8800 amp at J would protect the whole of the cable
section between J and H.
However, the disadvantage :
1.
Discrimination By
Both Time And Current
The relay operation time is inversely proportional
to the fault current level.
The actual characteristic is a function of both time
and current settings.
E
Xi
Xi
0.36 PU
0.29 PU
7.5 PU
Xi
1.98 PU
Xi
200 A
150 A
0.53
17.5
132 kV
11 kV
3.3 kV
Time(second)
F2
A
B
1.0
0.6
0.5
Current (amp)
the
interaction
of
two
These two fluxes are obtained by dividing the flux into two
components.
12 sin
but
Hence:
T = K I2
IDMT relay
Kutub
tertuduh
Sentuh
bukan
terteduh
Sentuh
bergerak
Sentuh
tetap
Cakera
Gelung
T
1
IC
E1
I1
Geganti IDMT
Juga dipanggil geganti masa songsang
Mengesan arus dan menjanakan isyarat belantik
setelah dilengahkan:
Perlengahan pendek untuk arus kerosakan besar
Perlengahan panjang untuk arus kerosakan kecil
Perlengan tidak terhingga semasa beban
Motor Arohan
2
T
Sentuh
bergerak
Gelung
Sentuh bukan
terteduh
Sentuh tetap
Cakera
2
T
Sentuh
bergerak
Gelung
Sentuh bukan
terteduh
Sentuh tetap
Cakera
T
1
1 arohkan voltan E1
2 arohkan voltan E2
E1
I1
E1 dan E2
I2
E2
Daya Kilas
T
1 2 Sin
1
2
Paksi Menegak
Masa kendalian (saat)
arus berubah
laju berubah
masa bertindak (menutup sesentuh) berubah
Pada gegelung disediakan tap (sadap)
Time-Current Characteristics
It was shown that:
T = K I2
torque
The larger current will produce the larger torque and, therefore, the
faster operating time to trip.
The majority of overcurrent relays have a characteristic which has
been standardized by BS 142.
The plug setting multiplier (PSM), becomes the horizontal axis of this
relay characteristic while the vertical axis, is the operating time in
seconds.
The higher the fault current, the shorter the operating time. The
operating time then tends to be constant for high fault currents (the
definite minimum time).
IDMT Characteristic
Relay Adjustments
The time taken to close the contacts depends on the
speed of rotation of the disc (depends on the
current).
The time can, therefore, be varied by interchanging
either the tap of the coil, or the separation of the
contacts.
Therefore, there are two parameters for setting this
relay : the current plug setting (PS) and the time
setting multiple (TSM).
moved
Overshoot
When the driving torque is removed, the relay disc
continues to rotate.
The time of rotation after the relay is de-energised is
called the overshoot time.
Recommended Discrimination
Time
Normally, 0.5 seconds is taken as the discrimination
time.
With faster modern circuit breakers and lower relay
overshoot time, 0.4 seconds is reasonable.
Under the best possible conditions, 0.35 seconds
can be used.
In some instances, a variable time value are used.
These are normally:
(a) A fixed time of 0.25 seconds.
(b) A variable time
Recommended Discrimination
Time
Hence, the total time interval t' is given by
t' = 0.25 t + 0.25
Where
t' = time interval
t = nominal operating time of the relay nearer to
the fault.
Relay Characteristics
Figure 2.5 shows that relay timecurrent characteristics can be
divided into four classes:
1. Definite time relays
2. Very inverse time relays
3. Extremely inverse time relays
4. Inverse definite minimum
time relays (IDMT)
Figure 2.5
K
2
(I - 1)
Determination Of
IDMT relay Settings
Two methods:
Graphical (template) method
Mathematical analysis.
CT x PS/100 A
PSM
FC/RSI
RCOT
f (PSM)
ROT
RCOT x TSM S
RjOT
RnOT + DT
S
S
400/5
400/5
200/5
100/5
Relay
Max
Fault
CT
Ratio
Plug
Setting
Max.
Load
Current
7850
400/5
150?
420
4500
400/5
125?
300
2690
200/5
100?
130
1395
100/5
100?
50
TSM = 1.0
= RnOT + DT
= 0.13 + 0.5
= 0.63 seconds
Therefore :
TSM =
ROT
RCOT
= 0.63/3.6
= 0.175
PS=100%
PS=100%
PS=125%
PS=150%
R (1,6)
R (5,6)
4
3
b) mines
c) petrochemical plant
Directional
relays
commonly applied to
systems.
are
ring
Graphical Method
Y
Moving the template vertically alters the time multiplier setting (TSM)
and horizontally the current setting (PS).
150/5
150/5
100/5
Exercise 1
An IDMT overcurrent relay has a current setting of 150% and
has a time multiplier setting of 0.5. The relay is connected in the
circuit through a C.T. having ratio 500:5 amps. Calculate the
time of operation of the relay if the circuit carries a fault current
of 6000 A. Use the standard relay characteristic in your
calculation with relay rating of 5 amp.
Solution
RSI = CT x PS/100
= 500 x 150/100
= 750
PSM = 6000/750 = 8
RCOT = 3.15 seconds
ROT = 3.15 x 0.5 = 1.575 seconds
Exercie 2
It is given that fault current level at 33 kV
side is 2,700 A, CT ratio at 33 kV side is
200 : 1 and 132 kV side is 100 : 1. It both
relays R1 and R2 are set for 100% plug
setting, determine the operation time for
both relays when time grading margin of
0.6 second is given and TSM for relay R1 is
0.15. Calculate also TSM for R2.
132kV
33kV
100/1
R2
Solution :
At R1
At R2
132/33kV
200/1
IF = 2700A
R1
Computer Method
BS 142 gives the equation as.
t=
0.14
xTSM
0.02
I
1
Study the single-line diagram of the system and identify the system components
Model each individual systems component
Convert all these impedances to a per unit system on a common MVA base.
Form the appropriate sequence networks.
Simplify of the network using star-delta and delta-star transformations etc.
On the basis of the type of faults to be analysed, connect the sequence networks for
analysis.
Calculate the sequence component currents.
Transform the sequence components currents to phase currents.
Convert the per unit currents to actual currents in amperes.
Repeat (iv) to (ix) for baseload condition.
Ph/F
E/F
51
51
64
(a)
51
64
E/F
(b)
Ph/F
51
51
(c)
64
E/F
are
provided
Operate for close up faults very quickly but should not operate even
for maximum fault currents at the remote end of the feeder.
Fuses
Simple
Can be very fast
Limit fault energy
Require Coordination
FIUS
Fuse Element
Element of Fuse
Normal operation
Overload current
Cut off
Figure 2.26
Fuse Classification
Fuses are classified into three categories :
1. High-voltage fuses
For protection of devices 1000V AC and above
2. Low-voltage fuses
For protection of devices up to 1000V AC and 1500V DC
3. Miniature and sub-miniature fuses
For protection of electrical and electronics apparatus up to 250 V
Fuses Operation
I2t value is unique
Peak asymmetrical
current
Prospective
current
Cut-off current
Zero current
Pre-arcing time
b
c
Arcing
time
1000000
Total I2t
Pre-arcing I2t
100000
I2 t
10000
80A
1000
100A
125A
160A
Time / Characteristic
A family of time/characteristic
curves for a standard fuse is
shown in Figure.
Penyelarasan Fius
400A
200A
250A
160A
Largest
fuse
100A
(a) Kaedah 2 ke 1
100A fuse
operated
Largest
fuse
100A
(b) Kaedah I2 t
160A fuse
not melted
125A fuse
arcing
100A
125A
160A
Figure 2.29
20 kW
LIGHTING
30 kW
HEATING
Figure 2.30
30 kW
MOTOR
1000
383A
452A
100
10
6s
Time
(s)
1
0.1
0.01
100
80A
100A
125A
160A
1000
Current (A)
Figure
10000
32 A
50 A
100 A
100A
fuse
operate
d
30 kW
160A
fuse
not
melted
125A
fuse
arcing
100
A
125
A
30 kW
160
A
Figure 2.32
Summary
The fuse must be adequately rated to supply normal current
to the circuit.
The rating must take into account any normal healthy
overload conditions, e.g. the starting of motors or the
switching of capacitors.
An allowance must be made if an overload occurs
frequently.
There must be an adequate margin if discrimination between
fuses is required.
The fuse must protect any equipment which is not rated at
the full short-circuit rating of the power system, e.g.
contactors, cables, switches, etc.
Coordination
Between Relay And Fuse
The relay characteristic best suited for this coordination with
fuses is normally that of the extremely inverse relay which
follows a similar characteristic.
Primary current setting of the relay should be approximately
three times the current rating of the fuse and that the grading
margin for proper coordination,
when expressed as a fixed quantity, should be less than
0.4s
when expressed as a variable quantity, should have a
minimum value of:
t = 0.4t +0.15,
where t = nominal operating time of fuse
Voltage operated
Current Operated
Thank You
Latihan 3
3.1
Suatu penyuap jejarian 11 kV seperti ditunjukkan dalam
Rajah 3.1 mempunyai tiga titik sadap dan dibekalkan oleh suatu
pengubah mengalirkan arus 5000 amp bila dilitar pintas di antara
fasa ke fasa. Galangan setiap penyuap adalah seperti di dalam rajah
dan pemutus litar dibelantikkan oleh geganti IDMT yang
mempunyai ciri-ciri seperti yang disediakan. Kira arus kerosakan
fasa ke fasa di setiap tempat dan cadangkan pengesetan geganti yang
sesuai serta nyatakan juga asas pilihan awak tersebut. Pengesetan
palam gandaan adalah diperolehi di antara 50% hingga 200%
dengan langkah 25%