You are on page 1of 11

EMERGENCY LIGHTING DESIGN GUIDE

THE FIRE PRECAUTIONS (WORKPLACE) REGULATIONS 1997

The main reason for installing an emergency lighting system is to


enable the building to meet fire safety legislation in a way that is
visually acceptable and meets the users needs for ease of
operation and maintenance. Consequently it is important to
establish all the relevant legal requirements for emergency lighting
and fire alarm systems before commencing the design these should
ideally be agreed between the system designer, user, fire authority,
building control officer and system installer.

This directive controls the way that the building will be used and
the equipment and systems needed to safeguard the occupants.
The legal requirement is that - Emergency routes and exits
requiring illumination must be provided with emergency lighting of
adequate intensity in case the lighting fails. The law is explained
and the rules for compliance are given in a joint Home Office and
Health & Safety Executive document - FIRE SAFETY - An employers
guide. Main points from the guide are:

The main legislative requirements are:

The employer has legal responsibility for compliance

THE BUILDING REGULATIONS 2000

Although the legislation uses and modifies the Fire Precautions


Act 1971, it now covers all premises where people are
employed

These regulations detail the design and construction characteristics


of a building. Approved Document B details the fire safety
requirements for new buildings and the major refurbishment of
existing premises. Table 9 of this document shows the locations that
must be provided with emergency lighting. It now defines that in
addition to escape routes, all open areas larger than 60m2 must
be illuminated in the event of the failure of the normal lighting
supply. It also clarifies that emergency lighting is needed for all
parts of schools that either do not have natural light or are used
outside normal school hours. The regulations require that systems
comply with BS 5266-1, the code of practice for emergency
lighting.

Any site with five or more employees must keep a formal record
of Fire Risk Assessment. This should evaluate the site and detail
the measures taken to ensure the safety of the premises
If the premises already have a fire certificate to the latest
standards the employer still needs to provide a risk assessment,
but it is unlikely that they will need any additional equipment.
If however the fire certificate was issued prior to 1999, when
BS 5266-1 was revised, the risk assessment needs to check
whether improvements are needed to meet the latest standard

Step 1

Identify fire hazards - such as sources of ignition, fuel or work processes

Step 2

Identify the location of people at risk in the case of fire

Step 3

Evaluate the risks to check whether existing fire safety measures are adequate, including:
- Control of ignition and fuel sources
- Fire detection and warning
- Means of escape and the provision of emergency lighting
- Means of fighting fire
- Maintenance and testing of fire precautions
- Fire safety training of employees

Step 4

Carry out any improvements needed

Step 5

Record findings and action taken

Step 6

Keep the assessment under review - revise provisions if the situation changes

441

Technical - Emergency Lighting Design Guide

LEGAL REQUIREMENTS

EMERGENCY LIGHTING DESIGN GUIDE


THE FIRE PRECAUTIONS (WORKPLACE) REGULATIONS 1997 (contd)

EMERGENCY LIGHTING - SYSTEM DESIGN

From this directive there are a number of points that are of major
importance to emergency lighting system design.

This section provides guidance on system design to meet BS 5266


Parts 1 and 7: 1999 and so achieve compliance with legislation

The evaluation of areas with a fire risk assists when deciding


which areas need protection, e.g. a school chemical
laboratory may be smaller than 60m2 but still need emergency
lighting, as combustible materials and sources of ignition would
be present
The assessment of the location of employees and any visitors to
the site assist in determining the most appropriate escape routes
The guidance to the directive gives detailed requirements for the
suitability of escape routes and calls for the installation of
emergency lighting to be in accordance with BS 5266-1

442

It recommends that advice on the installation should be given


by a competent person who specialises in emergency lighting
systems
Continued maintenance and testing must be correctly carried
out, to comply with the directive
The equipment used must be capable of being demonstrated
as of adequate quality. Compliance with the appropriate
British Standard, or other approved third party scheme,
gives evidence of this. The standard for luminaires is
BS EN 60598-2-22. ICEL 1001 registration endorses the
spacing data of these luminaires. The standard for central
battery systems is BS EN 50171
Note: When the premises are being assessed for risk,
shortcomings in other areas of fire protection can be compensated
for by improved levels of emergency lighting and fire alarms.
Compliance with BS5266-1:1999 is deemed to comply with
these requirements.

Technical - Emergency Lighting Design Guide

THE HEALTH AND SAFETY (SAFETY SIGNS AND SIGNALS)


REGULATIONS 1996
This regulation requires the adequate provision of signs protected
by emergency lighting. It details that signs should be located at all
final exits and also on the escape routes at any location where the
route may be in doubt.

OTHER REQUIREMENTS
In addition to fire safety legislation, some workplaces require a
licence from the Local Authority, including theatres and cinemas,
sport stadiums and premises for public entertainment, music,
dancing, gambling and the sale of alcohol. Other premises must
be registered with the Local Authority and be inspected by the Fire
Authority, including nursing homes, children's homes, residential
care homes and independent schools. Both licensed and registered
premises have to pass a fire inspection to confirm that they have
systems complying with BS 5266-1 for the emergency lighting and
BS 5839 for fire equipment. Records of a system are now essential
to maintain the validity of approvals and licences.

DESIGN OBJECTIVE
BS 5266, when referring to the provision of Escape Lighting in
section 4.2, requires that when the supply to all or part of the
normal lighting in occupied premises fails, escape lighting is
required to fulfil the following function:
(a) To indicate clearly and unambiguously the escape routes.
(b) To provide illumination along such routes to allow safe
movement towards and through the exits provided.
(c) To ensure that fire alarm call points and fire fighting equipment
provided along escape routes can be readily located.
(d) To permit operations concerned with safety measures.
BS 5266-1 recommends that discussions should be held prior
to commencing the design, to establish the areas to be covered,
the method of operation, the testing regime and the most suitable
type of system. These discussions should include the owner or
occupier of the premises, the system designer, the installer,
the supplier of the equipment and the fire authority.
Note: BS5266 will be revised during 2004 following the
publication of EN50172. For up to date information visit our
website at www.cooper-ls.com. Alternatively visit the British
Standards Institute website, at www.bsi-global.com

STAGE 1
LOCATE LUMINAIRES AT MANDATORY POINTS OF EMPHASIS
Initial design is conducted by situating luminaires to reveal specific hazards and highlight safety equipment and signs, in addition to
providing illumination to assist safe travel along the escape route. This should be performed regardless of whether it is an emergency
escape route or an open (anti-panic) area. Only when this is accomplished should the type of luminaire or its light output be considered.
BS5266 Pt 7: 1999 requires that the luminaires sited at points of emphasis must comply with BS EN 60 598-2-22.
Specific locations where a luminaire must be provided are:

At each exit door

All safety exit signs

Outside and near each final exit

Near stairs so that each tread receives direct


light

At each change of direction

Near each first aid post

Near any other change of floor level

At each intersection of corridors

Near each piece of fire fighting equipment and


call point

Note - the term near means within 2 metres measured horizontally

Technical - Emergency Lighting Design Guide

443

EMERGENCY LIGHTING DESIGN GUIDE


STAGE 2
ENSURE THAT EXIT SIGNS ARE OF CORRECT FORMAT AND SIZE
Section 4.1 of BS5266 Pt 7 states that Signs which are provided at all exits intended to be used in an emergency and along escape routes
shall be illuminated to indicate unambiguously the route of escape to a point of safety. Where direct sight of an emergency exit is not
possible, an illuminated directional sign (or series of signs) shall be provided to assist progression towards the emergency exit.

Sign formats should not be mixed


- BS2560: 1975
Old-style signs now obsolete. Should have been replaced by
December 1998
- BS 5499 Pt 1
Signs are still acceptable, if they are already in the building
- European Signs Directive Format
This came into force on 1st April 1996, under The Signs
Directive

444

EXIT
EXIT

If there is any doubt as to the most appropriate format of sign,


guidance should be obtained from the local Fire Authority.

Maximum viewing distances


For all format of safety signs the maximum viewing distances and luminance conditions are given in BS 5266 pt7/EN 1838 Signs can be
either internally illuminated, such as exit boxes or edge lit emergency luminaires with a screened sign that have a controlled illuminance,
or painted signs with an external emergency light illuminating them. Maximum viewing distances are:
Internally illuminated signs - 200 x the panel height

Technical - Emergency Lighting Design Guide

Externally illuminated signs - 100 x the panel height

<200 x h

<100 x h

Illumination requirements
The sign must conform to the colours of ISO 3864, which defines that exit and first aid signs must be white with green as the contrast
colour. The ratio of luminance of the white colour to the green colour must be between 5:1 and 15:1. The minimum luminance of any
10mm patch area on the sign must be greater than 2cd/m2 and the ratio of maximum to minimum luminance shall be less than 10:1 for
either colour
min luminance = 2cd/m2
ratio of luminance shall be
less than 10:1 for either colour

contrast of the colours must be


between 5:1 and 15:1

Note: Internally illuminated exit signs are pre-tested to ensure they meet these requirements, provided that they comply with EN 60598-2-22.
If the sign is designed to be externally illuminated, considerable care must be taken by the system designer to see that these conditions are met.
Even though an emergency luminaire must be sited within 2 metres from the sign (see stage 1) calculations should still be made to check that
the sign is adequately illuminated.

STAGE 3
LOCATE LUMINAIRES AT THE FOLLOWING ESSENTIAL AREAS IN THE BUILDINGS
Locate luminaires at the following essential areas in the buildings.
These locations are not part of the escape route but because of their risk they require protection by emergency lighting.

a) Lift cars - although only in exceptional


circumstances will they be part of the
escape route, do present a problem
in that the public may be trapped in
them in the event of a supply failure.

c) Escalators - to enable users to get off


them safely.

e) Covered car parks - the normal


pedestrian routes should be provided
with non-maintained luminaires of at
least 1 hour duration.

445

d) Motor generator, control or plant


rooms - require battery supplied
emergency lighting to assist any
maintenance or operating personnel
in the event of failure.

Technical - Emergency Lighting Design Guide

b) Toilets - all toilets for the disabled and


facilities exceeding 8m2 floor area or
without borrowed lights.

EMERGENCY LIGHTING DESIGN GUIDE


STAGE 4
ESCAPE ROUTE LIGHTING
When the points of emphasis have been covered, it is essential to provide any additional luminaires to ensure that minimum illuminance levels
are met to enable the routes to be used safely. In addition, every compartment on the escape route must have at least two luminaires,
to provide some light in the event of luminaire failure.
Light Level Requirements
BS 5266 Pt 7: 1999 (EN1838) calls for a minimum of 1 lux
anywhere on the centre line of the escape route for normal
risks. A uniformity ratio of 40:1 maximum to minimum must not
be exceeded. This illuminance must be provided must be
provided for the full duration and life of the system. 50% of the
illuminance must be available within 5 seconds and the full
value within 60 seconds of supply failure.

446

Note: The UK has an A deviation which continues to allow a


0.2 lux minimum value for routes that will be permanently
unobstructed. It should be noted that this puts a heavy burden on
the user to ensure routes are kept clear even in an emergency.
For this reason it is recommended that the 1 lux level should
always be used.
Photometric Design
Emergency Escape Routes
The use of spacing tables or a suitable computer program
provides the information to determine whether luminaires
are needed in addition to those for the points of emphasis
(see data section), to provide the minimum required level of
illumination on the escape routes. To ensure that the design
will meet the required levels at all times the data is de-rated,
as required by the standard, to cover the following factors:
i. Reduction in light as the battery voltage reduces during
discharge.
ii. Aging of lamps in maintained circuits
iii. The effects of dirt (Spacing tables use a figure of 80%).

PHOTOMETRIC DATA
Britelite

Escape route 2m wide


1 lux min

Luminaire Mounting
type
height (m)

Open (anti-panic) area


0.5 lux min

Lux level
directly
under

0.5L

0.5L

0.5L

0.5L

Self-contained
NM

2.5

3.28

3.9

11.3

4.0

2.0

4.0

1.28

2.1

9.6

5.6

1.2

3.3

14.8

7.2

1.9

6.0

0.57

1.6

4.0

12.4

12.0

7.4

6.0

0.8

1.9

2.5

2.75

3.3

10.7

5.2

1.8

3.7

11.7

5.8

1.8

4.0

1.07

1.5

8.0

5.0

0.7

3.5

14.2

7.0

1.7

6.0

0.48

11m

22m

ceiling 2.5m

Locate luminaires at mandatory


Points of emphasis

11m

11m

11m

Add additional luminaire to


achieve 1 lux minimum
ceiling 2.5m

Technical - Emergency Lighting Design Guide

Example - luminaire spacing along escape route

STAGE 5
OPEN (ANTI-PANIC) CORE AREAS
Areas larger than 60m2, open areas with an escape route passing through them, or hazards identified by the building risk assessment all
require emergency lighting. The current standard is easy to design for and to verify, promoting systems that provide good uniformity rather than
ones that use a few large output luminaires.
Light Level Requirements
BS5266 Pt 7/EN1838 - 4.3 calls for 0.5 lux minimum of
the empty core area, which excludes a border of 0.5m of the
perimeter of the area. Spacing tables or a suitable computer
program provide simple and accurate data that can easily be
used. The spacing tables for 0.5 lux are de-rated on the same
basis as those for escape routes. They can also be used as a
guide for initial selection of the location of luminaires when
using a computer program

If using standard mains luminaires fitted with an emergency


conversion kit, typical data is shown on pages 456-459.
The data details the polar distribution for common types of
luminaires, from which a suitable match should be selected.
The factors considered should be the shape of the polar curve
and the scale, which is shown by the nadir intensity.
Alternatively, a computer program can be used and the light
outputs of the appropriate kit can be used with the actual
distribution data of the luminaire chosen.

447

Spacing data
Specific data is available for self-contained dedicated
emergency luminaires. This can be found on each of the
individual product entries in this catalogue and repeated in
the section after this design guide.

Luminaire spacing in open (anti-panic) core areas

0.5L

0.5L

0.5L

0.5 metre border


(core area excludes a border
of 0.5m of the perimeter of the area)
Minimum points - at which 0.5 lux is obtained

Technical - Emergency Lighting Design Guide

0.5L

EMERGENCY LIGHTING DESIGN GUIDE


STAGE 6

STAGE 7

HIGH RISK TASK AREA LIGHTING

CONTROL

Areas of high physical risk, or the control rooms of dangerous plant


and production lines, need emergency lighting to enable them to
be shut down safely. BS5266 Part 1: 1999 defines that
emergency lighting should provide 10% of the normal lighting level
at the hazard, with a minimum of 15 Lux. (In practice this minimum
is unlikely ever to be a problem, as it would only be valid if the
risk area had a normal illumination level less than 150 lux).

Non-maintained luminaires must be activated by failure of supply


to the normal lighting. They must therefore be connected an
unswitched live taken from the local normal lighting final circuit.

DESIGN PROCEDURES

448

Reaching the light levels needed would normally be achieved by


using a conversion of the normal luminaire, or by using a tungsten
projector unit. If conversion units are selected, a direct ratio can be
obtained by the Ballast Lumen Factor (BLF). i.e. to achieve 10% of
normal use either:
- Emergency units with a BLF of 10% are needed for each fitting
in the area
- Emergency units with a BLF of 20% are needed for every other
fitting
- Emergency units with a BLF of 100% are needed for one in 10
fittings
Care is needed to ensure that a reasonably uniform distribution is
achieved by whatever combination of luminaire and conversion kit
used. If tungsten projector units are selected, a co-efficient of
utilisation calculation has to be performed for the required value.

Once the design has been completed it becomes apparent that


the performance of the luminaire depends as much on the light
distribution as it does the light output available. Consequently it
becomes essential that luminaire types specified for a particular
design do not get changed without a re-appraisal of the
photometric design.

L
N

Normal lighting

Emergency lighting

Technical - Emergency Lighting Design Guide

TESTING AND LOG BOOK


The Fire Precautions (Workplace) Regulations 1997 require that
appropriate testing is performed to maintain compliance of the
system. The system should include adequate facilities for testing
and recording the system condition. These need to be appropriate
for the specific site and should be considered as part of the system
design. Discussions with the user or system designer should
identify:
- The calibre and reliability of staff available to do the testing
- The level of difficulty in performing the test
- If discharge tests need to be done outside normal working
hours, or phased so only alternate luminaires are tested in
buildings that are permanently occupied
The testing requirements in the code of practice are:
Function test
All emergency luminaires should be tested be breaking the
supply to them and checking that they operate satisfactorily.
The supply must then be restored and the charging indicators
must be seen to be operating correctly. This test must be
performed at least once per month and the results logged
Discharge test
The luminaires must be tested for their full rated duration period
and checked for satisfactory operation. The supply must then be
restored and the charging indicators rechecked. This test must
be performed at least annually and the results logged
Note: BS 5266-1: 1999 allows a one hour test to be performed
as an alternative every six months for the first 3 years of the
system, but the guidance document to the Fire Precaution
Regulations calls for the annual test at all stages of equipment life.

STAGE 7 (contd)
MANUAL TESTING

AUTOMATIC TEST SYSTEMS

If manual testing is utilised, the following points should be


considered:
- Is a single switch to be used? Unless the whole building is to
be switched off, a separate switch should be used for each
final circuit. As the feed to non-maintained circuits must be
taken from the switch this will probably mean that the building
will have to be walked around twice, once to check the
luminaires and once to check that they are recharging
- Are luminaires to be individually switched? In practice, only a
single walk around the building will be needed. However, the
test switches could spoil the dcor of the building and they must
be of a type that is tamper proof.
After the tests, the performance of the luminaires must be logged.

If the costs of an engineer time and the disruption caused by


manual testing are excessive, automatic systems should be
considered. Different formats are available to match particular site
requirements. Cooper Lighting and Security offer two alternative
testing systems:

BS5266 Pt 1: 1999 and the European Standard both require


written declarations of compliance to be available on site for
inspection. These consist of:
1. Installation quality.
IEE regulations must have been conformed with and nonmaintained fittings fed from the final circuit of the normal
lighting in each, as required in BS 5266
2. Photometric performance.
Evidence of compliance with light levels has to be supplied by
the system designer. Photometric tests for Cooper Lighting and
Security luminaires are performed at BSI and spacing data is
registered by the ICEL scheme. Therefore copies of the spacing
data in this catalogue provide the verification required.
3. Declaration of a satisfactory test of operation.
A log of all system tests and results must be maintained. System
log books, with commissioning forms, testing forms and
instructions are available from Cooper Lighting and Security.

MAINTENANCE
Finally, to ensure that the system remains at full operational status,
essential servicing should be defined. This normally would be
performed as part of the testing routine, but in the case of
consumable items such as replacement lamps, spares should be
provided for immediate use.

EasiCheck Panel

449

Intellem Programmer

Intellem
Designed for use with self-contained emergency luminaires,
Intellem is a stand alone self-test system for small to medium
sized installations. Intellem is available in two options. In the
basic format, Self Check, the testing module self calibrates and
carries out testing at predetermined intervals. Faults are
precisely reported by an audible alarm and the flashing
sequence of the LED indicator. The enhanced Intellem Infra-Red
option adds the benefits of flexible test set up, luminaire status
interrogation and initiation of manual tests, all via a hand held
programmer. Both options also continuously monitor the
emergency luminaires, reporting faults as soon as they occur.

Technical - Emergency Lighting Design Guide

COMMISSIONING CERTIFICATE

EasiCheck
Particularly suited to medium to large sized installations,
EasiCheck is a versatile addressable emergency lighting
system that uses a central control panel to perform automatic
test schedules, initiate manual tests and download event logs
and test reports. It is available for use with both self-contained
luminaires and central power systems. EasiCheck continuously
monitors the emergency circuit, reporting faults as soon as they
occur. Up to 63 panels can be networked together, ensuring
EasiCheck can be utilised in the largest of projects of up to
15,750 emergency luminaires. It also has advanced software
options for PC monitoring and control.

EMERGENCY LIGHTING DESIGN GUIDE


EXAMPLE OF SYSTEM DESIGN

i
a,b,c,f&k
m
x
x
Acid bath

4
Plant room

Workshop (iv)

450

c&h

h&f

x
d

x
Office (iii)
x

Technical - Emergency Lighting Design Guide

Office (i)

Office (ii)

Lift

b&e

e&h

e&h

2
Toilet
Escalator

Lobby
a,b & c
i

EXAMPLE OF SYSTEM DESIGN

WIRING INSTALLATION

Stage 1
Locate luminaires at points of emphasis on escape route
a At each exit door
b To illuminate exit and safety signs
c Near call points (some covered by a.)
d Near each staircase
e Change of direction (covered by b.)
f Near fire fighting equipment (covered by a.)
g Change of floor level
h Near intersection of escape routes
i Outside final exits
k Near first aid points

The wiring of emergency luminaires should generally be in


accordance with normal wiring practice (I.E.E. Wiring
Regulations), statutory requirements applicable to the type
of building, local by-laws and regulations. The supply for self
contained luminaires should be taken from the unswitched local
light source

Stage 3
Other areas, which require emergency lighting but are not on the
escape route area.
1 Lift car
2 Toilet (above 8m2 floor area)
3 Escalators
4 Plant room
Stage 4
Check minimum illuminance levels on the escape routes.
After selecting a suitable luminaire, e.g. Britelite, consulting the
spacing table shows the number of fittings needed to provide a
minimum of 1 lux on the centre line of the escape routes.

The supply to self-contained luminaires should be such as to


prevent unauthorised disconnection, but should incorporate suitable
means for simulating a mains failure for test purposes. The source
of supply should be from the same local fuse as the normal
lighting, so that in the event of a fuse failure causing the normal
lighting to be extinguished, the emergency lighting is brought into
operation in the same locality.

Non - maintained installation


mains lighting fuse
L
N

to mains lighting
tamper proof
test switch

Stage 5
Anti-panic open areas (x) apply to any areas over 60m2 floor
area, or that have an escape route passing through them.
(i) Office over 60m2
- 3 x Britelite
(ii) Office under 60m2
- no requirement
(iii) Under 60m2, but part of escape route from office (ii)
- 2 x Britelite fittings, either as compartment of escape route or
an open anti-panic area
(iv) Workshop 4m high
- 3 x Britelite + 1 x DQX - 5 cell conversion unit for high risk
(m) or 4 x DQX - 5 cell conversion units (Use of conversion
units is dependent on suitable mains luminaires being used).
Stage 6
High risk lighting requirement for an acid bath (m) is included in
the design for stage 5. If a conversion of a mains luminaire is not
suitable, a high power tungsten projector, such as Beamlite could
be used instead.

451

to additional
emergency luminaires

N
L

non-maintained emergency
luminaire

Maintained or sustained installation


mains lighting fuse
L
N

to mains lighting
tamper proof
test switch

to additional
emergency luminaires

N
L1
L2
maintained lighting
control switch

Wiring details

maintained
emergency luminaire

Technical - Emergency Lighting Design Guide

Stage 2
Exit sign location is covered by Stage 1, but it is important to
check that maximum viewing distances are not exceeded and that
if the normal lighting is dimmed, e.g. in cinemas, the exit signs
must be permanently illuminated while the building is occupied
(maintained lighting).

Cabling used when installing self-contained emergency luminaires


should be of a similar type to that used for the normal mains light.
In the event of a fire, if the cabling used for the emergency
luminaires has greater protection, there may be a chance of the
normal lighting failing and the emergency lighting remaining in
the normal mode (i.e. inoperative). Hence it is recommended that
self-contained emergency luminaires are wired in PVC insulated
cable.

You might also like