Enertronic Modular 3 Phase

Uninterruptible Power System (UPS)

Up to 60kVA of Secure
AC Power

Benning has applied over 70 years of accumulated knowledge and


experience in high reliability power electronics to come up with another world
class solution.
Introducing Enertronic Modular, high power density modular true three
phase inverter system for your mission critical telecom, datacenter, and other critical
AC power applications.
Traditional UPS systems operate as stand-alone systems without any
redundancy. System component faults can cause downtime of mission
critical loads with very costly consequences.
The Enertronic Modular UPS systems are based on parallel operating
hot-plug power modules. Each module represents a complete double
conversion UPS system with three phase 120/208VAC input and three
phase 120/208VAC output and integrated static by-pass. Maximum
availability is achieved by combining the parallel operating modules
with n+1 redundant design.
In comparison with a traditional fixed capacity UPS system with higher
initial upfront costs the advanced ENERTRONIC modular concept allows
the user to scale the installed output capacity in 10kVA steps and to
adapt the UPS system capacity to changing power requirements.
The cost of ownership is be reduced by eliminating yearly UPS service contract
due to the hot-plug modular nature of the system design. The system design
enables the UPS modules to be replaced in the event of a failure by simply unplugging the offending
module and replacing it with a new module by sliding a new module into the empty shelf. There is no
need for special tools or equipment. The module auto programs itself eliminating complicated setup
procedures.
To further enhance system availability, the module topology has been introduced whereby each inverter
module has its own Static Bypass Switch (SBS), eliminating the one large transfer switch of past
generations which can be a source of system failure. Secure data bus communications between modules
provides for a coordinated transfer to back-up AC in the unlikely event of system failure or overload.
Redundancy is determined dynamically, based on measurement of actual present load. A transfer to
back-up will take place when the system determines that its capacity has been exceeded either due to a
non-redundant module failure or due to excess load being added on the output.

Key Features
Hot swap 10kVA modules each with built-in SBS for the ultimate in scalability
N+1 redundancy ensures maximum availability
Employs DSP Technology for outstanding dynamic step load response and maintenance
of high quality, low distortion sine wave output into non-linear loads
Integrated Manual Bypass Switch
Front Door-mounted Graphical Display of Operating Mode & System Parameters
Remote Monitoring via Network (HTML/SNMP)

Enertronic Modular (R2_12) Benning Power Electronics 2012


Specifications are subject to change without notice

Technical Specifications
Module

Enertronic Modular 3 Phase Inverter


UPS Module Rating

10kVA / 9kW at 0.9 power factor inductive

Maximum System Capacity

60kVA / 54kW at 0.9 power factor inductive

Maximum Modules Per Cabinet

AC Output Volts

120 / 208 VAC 3 phase, 4 wire, Y connected

AC Output Amps

27.8A per phase at full load

AC Output

AC Output Frequency
Load Power Factor Range

60Hz +/- .01% on internal crystal


0.7 lagging (inductive) to 0.8 leading (capacitive), standard UPS de-rating

Output Regulation

Static: +/- 1%; Dynamic: +/-5% max with 100% step


load change, settling time: <10 ms

Efficiency

Up to 93%

Crest Factor Accommodated

<= 3

Distortion
Overload Capability

<2% THD into a linear load, <5% THD into a non-linear load
150% for 1 min; 125% for 10ms; 200% for 3s then Transfer to Bypass

Battery
Input

Number of Battery Cells


Max Battery Charging
Float Voltage
Ripple

AC
Input

AC Input Voltage
AC Input Current (w/Battery Charging)
Power Factor
THD

SYSTEM

Static Bypass Switch (SBS)


SBS Priority
Transfer Time
SBS Overload Capability

MECHANICAL

8A per Module (2kW per Module)


2.232.3V/Cell (216VDC - 288VDC per String)
<=1%
120 / 208 VAC 3 phase, 4 wire, Y connected
31A
0.99 (0.97 at 25% load)
<4%
120/208VAC, 3 Phase SCR bridge built into each module
Inverter Priority Only; Offline mode not possible
SBS is make-before-break; 2ms typical
500% for 100ms, 150% for 10min

Indicators

13 Programmable LEDs on front door display panel

Metering

Phase voltages, currents, kW, kVA, kVAR

Network Access

SNMP and TCP/IP (Server Shutdown with RCCMD Software)

Module Weight & Dimensions

99lbs. (45kg); 19.9 x 17.7 x 8.75 (5RU) (505 x 450 x 222 mm)

Cabinet Weight & Dimensions (each)

528lbs. (240kg); 24 W x 31.5 D x 84 H (600 x 800 x 2134 mm)

Module Mounting
Heat Output

Hot-plug into pre-wired mounting shelf


<30,000 BTUs / hour / 60kVA cabinet, full load @ 54VDC input

Operating Temperature Range

0-40C, up to 50C with output derating

Operating Humidity Range

0-95% relative humidity, non-condensing

Elevation

Fully rated to 2000M, de-rated thereafter

Output Protection

DESIGN

2 x 54 to 2 x 72

System AC Output Breaker

Safety

EN 60950, UL 1778, cUL 60950

Design

Transformerless Modular Online UPS

EMI Emissions

EN 62040-2 classification C3, FCC Class A

EMI Immunity

EN 61000-4-4, EN 61000-4-5

Electrostatic Discharge Immunity

Benning Power Electronics, Inc.


1220 Presidential Dr., Richardson, TX 75081
E-Mail: sales@benning.us
www.benning.us
Enertronic Modular (R2_12) Benning Power Electronics 2012
Specifications are subject to change without notice

EN 61000-4-2, (level: 4kV contact, 8kV air discharge)