You are on page 1of 2

PROFIBUS BC3100, BC3150

Configuration and
programming interface

Fieldbus connection
Fieldbus connection

Address selector

Address selector

Address selector
Configuration and Address selector
programming interface
Bus Terminal

446
BC3100, BC3150 | PROFIBUS Bus Terminal Controllers
The Bus Terminal Controllers BC3150 supports up to 255 Bus also be loaded via the fieldbus.
BC3100 and BC3150 are Bus Terminals via the K-bus exten- The inputs and outputs of the
Couplers with integrated PLC sion. Both PROFIBUS controllers connected Bus Terminals are
functionality and have a fieldbus offer automatic baud rate detec- assigned in the default setting
interface for PROFIBUS. They are tion up to 12 Mbaud and two of the PLC. Each Bus Terminal
intelligent slaves and can be address selection switches for can be configured in such a way
used as distributed intelligence address assignment. that it exchanges data directly
in the PROFIBUS system. In the The Bus Terminal Control- through the fieldbus with the
BC3100 Bus Terminal Controller, ler is programmed using the higher-level automation device.
one unit consists of the control- TwinCAT programming system Similarly, pre-processed data
ler, between 1 and 64 terminals, according to IEC 61131-3. can be exchanged between the
and a bus end terminal. The configuration/program- Bus Terminal Controller and the
The “Compact” BC3150 Bus ming interface of the BC31xx is higher-level controller via the
Terminal Controller is housed in used to load the PLC program. fieldbus.
a cost-optimised and compact If the software PLC TwinCAT
housing. Unlike the BC3100, the is in use, the PLC program can

Ordering information Description


BC3100 PROFIBUS Bus Terminal Controller for up to 64 Bus Terminals, 12 Mbaud
BC3150 PROFIBUS “Compact“ Bus Terminal Controller for up to 64 Bus Terminals (255 with K-bus extension), 12 Mbaud
BX3100 PROFIBUS Bus Terminal Controller for up to 64 Bus Terminals (255 with K-bus extension), 12 Mbaud 448
BK3xx0, LC3100 PROFIBUS Bus Coupler 400
CX8031 PROFIBUS Embedded PC 263

BECKHOFF New Automation Technology We reserve the right to make technical changes.
BC3100, BC3150 PROFIBUS

Controller for distributed signal processing


The programming system In addition, TwinCAT offers
TwinCAT for the BC3100 and extensive debug functionalities
BC3150 operates, independently (breakpoint, single step, moni-
of the manufacturer, in accor- toring, …), which facilitate
dance with IEC 61131-3. The commissioning. It is also pos-
PLC programs can be written in sible to perform adjustment and
five different programming lan- measurement of the cycle time.
guages (IL, FBD, LD, SFC, ST).

Bus Terminal
PLC data PROFIBUS | BC3100 BC3150
Programming TwinCAT (via programming interface or fieldbus)
Program memory 32/96 kbytes 48 kbytes
447
Data memory 32/64 kbytes 32 kbytes
Remanent data 512 bytes 2 kbytes
Run-time system 1 PLC task
PLC cycle time approx. 3 ms for 1,000 instructions (without I/O cycle, K-bus)
Programming languages IEC 61131-3 (IL, LD, FBD, SFC, ST)
Online change no yes

Technical data BC3100 BC3150


Number of Bus Terminals 64 64 (255 with K-bus extension)
Max. number of bytes fieldbus 128 byte input and 128 byte output
Max. number of bytes 512 byte input and 512 byte output
process image
Digital peripheral signals 512 inputs/outputs 2,040 inputs/outputs
Analog peripheral signals 128 inputs/outputs
Configuration possibility via KS2000 or fieldbus
Data transfer rates automatic detection up to 12 Mbaud
Bus interface 1 x D-sub socket, 9-pin
Power supply 24 V DC (-15 %/+20 %)
Input current 70 mA + (total K-bus current)/4, 500 mA max. 320 mA max.
Starting current 2.5 x continuous current
Supply current K-bus 1,750 mA 1,000 mA
Power contacts 24 V DC max./10 A max.
Electrical isolation 500 Vrms (power contact/supply voltage)
Weight typ. 170 g typ. 100 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Further information www.beckhoff.com/BC3100

Accessories
KS2000 configuration software for extended parameterisation 1064
TwinCAT PLC programming system conforms to IEC 61131-3 1146
Cordsets cordsets and connectors 632
FC310x PC Fieldbus Cards with PCI interface 1044

We reserve the right to make technical changes. BECKHOFF New Automation Technology