You are on page 1of 42

CLIENT

CONSULTANT
CONTRACTOR
PROJECT:
PACKAGEII:
DOCUMENTNAME:
REV

DOCUMENTNO.

SUMMARYSHEET
Thetotalplantisdividedintothefollowingmajorareasandthesoilresistivityconsideredforcalculation(basedonsoilreport)areasfollows
1

SS1SUBSTATION

70.53

m 14 TRANSFERHOUSE(TH2A)

151.39

SS2SUBSTATION

25.050

m 15 PARKINGSTATION(PS1)

151.39

SS3SUBSTATION

25.050

m 16 PARKINGSTATION(PS2)

35.100

m
m

TRANSFERHOUSE(TH1)

72.640

m 17 TRANSFERHOUSE(TH3)

35.100

SILOBUILDING

151.390

m 18 TRANSFERHOUSE(TH4)

44.840

TAILDRIVEHOUSE

151.390

m 19 TRANSFERHOUSE(TH5)

41.940

TRANSFERHOUSE(TH2)

151.390

m 20 TRANSFERHOUSE(TH6)

128.940

PUMPHOUSE1

205.510

m 21 PUMPHOUSE2

228.680

ATHTP1

128.380

m 22 ATHTP2

70.150

10

ATHTP3

25.050

m 23 ATHTP4

26.040

11

ATHTP5

49.870

m 24 ATHTP6

37.530

12

ATHTP7

51.150

m 25 ATHTP8

35.100

13

ATSECONDARYCRUSHER

441.550

m 26 ATTRANDFERSTATION

49.890

Theearthgridvaluesofeachareasiscalculatedseperatelyandalltheseareasareinterconnectedthroughearthflat.Thecombinedearthresistanceforthetotallayoutasper
projectspecificationsshallbelessthan1
CalculationofoverallEarthresistanceofthetotalplant
10
1.0

EarthResistancearoundElectricalSubstationBuildingSS1
R1

0.81

10.0
ReferAnnexureI

EarthResistancearoundElectricalSubstationBuildingSS2
R10

0.29

ReferAnnexureX

2.0 EarthResistancearoundElectricalSubstationBuildingSS3&Earth
11.0
ResistancearoundPumphouseBuilding2
ReferAnnexureII
R2 =
0.82

EarthResistancearoundTransferHouseTH1

3.0 EarthResistancearoundsilobuilding

EarthResistancearoundTraveldrivehouse

R3

12.0
9.61

ReferAnnexureIII

4.0 EarthResistancearoundTransferHouseTH2
R4

9.61

13.0
ReferAnnexureIV

5.0 EarthResistancearoundparkingstationPS1
R5

9.61

14.0
.
ReferAnnexureV

6.0 EarthResistancearoundTransferHouseTH3
R6

2.23

15.0
ReferAnnexureVI

7.0 EarthResistancearoundTransferHouseTH5
R7

2.66

16.0
ReferAnnexureVII

8.0 EarthResistancearoundPumphouse1
R8
9.0

17.0
10.44

ReferAnnexureVIII

R11

R12

4.61

9.61

ReferAnnexureXI

ReferAnnexureXII

EarthResistancearoundTransferHouseTH2A
R13

9.61

ReferAnnexureXIII

EarthResistancearoundparkingstationPS2
R14

4.46

ReferAnnexureXIV

EarthResistancearoundTransferHouseTH4
R15

2.85

ReferAnnexureXV

EarthResistancearoundTransferHouseTH6
R16

8.19

ReferAnnexureXVI

EarthResistanceNearTransferStation
R17

6.33

ReferAnnexureXVII

EarthResistanceofdownhillconveyorDHC723atNearHTP2(TR64)
R9A

0.80

ReferAnnexureIX

10.0 EarthResistanceofdownhillconveyorDHC723atNearHTP6(TR107)
R9B

DOC.NO.-EL00007,REV-02

0.75

ReferAnnexureIXA

1 OF 42

SUMMARY

Note:TheOverallPlantEarthGridresistancevaluewillbereducedwhenallTailEndTH's&SSgridwillbeinterconnected.
1
R

1
R1

1
R

1
0.81

1
R
1
R
1
R

1
R3

1
R4

1
R5

1
R8

1
R11

1
R12

1
R13

1
9.61

1
9.61

1
9.61

1
10.44

1
4.61

1
9.61

1
9.61

0.81 +
0.81 x

9.61
9.61

9.61
9.61

+
x

9.61
9.61

10.44
10.44

+
x

4.61
4.61

9.61
9.61

+
x

9.61
9.61

10.43
7.83

19.22
92.38

15.05
48.14

19.22
92.38

0.21

0.31

0.21

1.33

1
R

2.06

1
2.06

0.485

Note:RefertheEarthingPit&StripSchemeforoverallplant.

Finallywecalculateas

RT

Ohms EarthResistanceofoverallplantTailendside

0.49

Note:TheOverallPlantEarthGridresistancevaluewillbereducedwhenallHeadEndTH's&SSgridwillbeinterconnected.
1
R

1
R2

1
R6

1
R7

1
R10

1
R14

1
R15

1
R16

1
R17

1
R

1
0.82

1
2.23

1
2.66

1
0.29

1
4.46

1
2.85

1
8.19

1
6.33

0.82 +
0.82 x

2.23
2.23

2.66
2.66

+
x

0.29
0.29

4.46
4.46

+
x

2.85
2.85

8.19
8.19

+
x

6.33
6.33

1
R

1
R

3.05
1.83

2.95
0.77

7.30
12.69

14.52
51.86

3.83

0.58

0.28

1
R

1.67

1
R

6.36

1
6.36

0.157

Finallywecalculateas

Note:RefertheEarthingPit&StripSchemeforoverallplant.

RT

0.16

Ohms EarthResistanceofoverallplantHeadendside

NOTE:
1 Thecalculatedearthpitqty.areminimumtobeprovidedatsite.Howeveraspersitecondition,theoverallresistanceisnotachivedlessthan1
withaboveearthpitqtythanadditionalpitsshallbeprovidedtomeettheoverallgridresistancelessthan1 .
2 Earthflatrunningthroughcabletraywillbeconsiderasinterconnectionbetweentwogridswherevergroundprofileisnothillyarea.

DOC.NO.-EL00007,REV-02

2 OF 42

SUMMARY

CALCULATION OF MAIN GRID CONDUCTOR & EARTHING STRIP

REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage MV Voltage

11

kV

25

kA

sec

sec

0.415

kV

50

kA

sec

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
1.02
flow through the protective device for HV System (see IEC 60909-0);

If

1.03 The operating time of the protective device for automatic disconnection in s;

ts

1.04 Fault clearing time

tsc

1.05 System nominal voltage LV Voltage

Vs

1.06

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device for LV System (see IEC 60909-0);

If

1.07 Fault clearing time

tsc

Pipe

Steel

QC

3.8 x 10-3

202

2.00 Earthing Conductor Data


2.01 Earth Electrode Material (Rod or Pipe)
2.02 Volumetric heat capacity of conductor material

J/0C mm3

(J/oC mm3) at 20 oC
2.03 Reciprocal Of temp.Cofficient of resistivity at O 0C

for the conductor (2020C as IEC 60364-5-54)

20

138x10-6

2.05 Initial temperature of conductor (40 0C)

45

2.06 Final temperature of conductor (200 0C)

500

2.04 Electrical resistivity of conductor material at 200C

-mm

3.00 CALCULATION FOR SIZING OF EARTH CONDUCTOR BASED ON 11KV SYSTEM

Minimum Cross sectional area required = A


As per IEEE - 80 ,the minimum cross sectional area of the earthing conductor to withstand the
Short circuit current is given by
A
If

= Is the cross-sectional area, in mm2;


=

is the value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);

t = is the operating time of the protective device for automatic disconnection in s;


k

= is the factor dependent on the material of the protective conductor, the insulation and is the factor dependent on the material of the protective conductor, the
insulation and

(If t)
k

The factor of K is determine from the formula (Annex A - IEC - 60364-5-54)


0

Qc( + 20 C)

ln

20

1+

f - i

+ i

Qc( + 20C)

20

The value of

80

80

for steel as per ,Table A.54.1 of IEC 60364-5-54

ln

1+

500
202

45
45

80

1.045

81.76

Therefore ,the area of conductor for the maximum fault level of 40A and consider the fault clearing
time is < 0.5 sec.the conductor area is

25000
A

81.76
Considering 15% corrosion allowance of the strip will be

306

Sq.mm

Hence the calculated minimum diameter of the GI rod

351.63

Sq.mm

Hence the calculated minimum width & Thickness of the Earthing strip

D/4

Earthing Conductor(strip) width

Earthing Conductor(strip) Thickness

40
X
10

mm
mm

Ax4

306 x
3.142
20

However as per TS 75x10mm strip shall be used for main earthing


grid.

mm

Considering 15% corrosion allowance the diameter of the MS rod will be 32mm will be sufficient
However we will select a standard size of 100mm MS rod for the main earth mat below ground as per contract specifications.

D =

DOC.NO.-EL00007,REV-02

100 mm

6 OF 42

MAIN CONDUCTOR SIZING

TRANSFER STATION GROUNDING CALCULATION

ANNEXURE-XVII
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00

SYSTEM DATA
Vs

1.01 System nominal voltage

=
=

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which
1.02
can flow through the protective device (see IEC 60909-0);

If

1.03 The operating time of the protective device for automatic disconnection in s;

ts

415

50

kA

sec

tsc

LxB

1.06 Area of earth grid around Substation

41.25

1.07 Resistivity of the soil

49.89

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

2600.0

cm

2 02 Depth
2.02
D th off b
burial
i l off conductor
d t (St
(Strip)
i )

80

cm

7.50

cm

1.04
0 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

2.00

sec
x

5.5
m

-m

Buried earth conductor (strip)

2.03 Width (Incase of strip) of the conductor (Strip)


2.04

1
7.5

Earth conductor (Rod or Pipe)


Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


Th resistance
The
i t
off earth
th grid
id can be
b calculated
l l t d by
b using
i
the
th formula
f
l
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 49.89)
(2 x 3.142 x 2600)

Rg =

0.305354

Rg =

3.06

ln

(2xL
L )
(x t)
ln

(2 x 6760000)
(80 x 7.5)

10.023

The resistance of the earth Conductor (Strip)

Rg =

DOC.NO.-EL00007,REV-02

3.06

ohms

41 OF 42

TRANSFER STATION

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 49.89)
(2 x 3.142 x 300)

Re =

2.646404

Re =

12.67

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

12.67

ohms

The overall earth resistance of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

12.67

1
-----R2

1
12.67

1
Rn
1

---------------------

12.67

1
Rn

Finally we calculate as
Add no. of pits

the Combined value of

n pits

R18 =

R1- Total Resistance of Earth Electrodes(pits)

(Re)

6.33

R2 - Total Earth Resistance of the buried Conductor

(Rg)

3.06

6.33

Ohms

Refer Annexure-VI
1
R
1
R

1
R1

1
6.33

1
R2
+

1
3.06

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

R18A

R1

R2

R1

R2

6.33
6.33

x
+

3.06
3.06

19.39
9.40

2.06

Ohms

42 OF 42

TRANSFER STATION

4.00 CALCULATION FOR SIZING OF EARTH CONDUCTOR BASED ON LV SYSTEM

Minimum Cross sectional area required = A


As per IEEE - 80 ,the minimum cross sectional area of the earthing conductor to withstand the
Short circuit current is given by
A
If

= Is the cross-sectional area, in mm2;


=

is the value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can flow through the protective device (see IEC 60909-0);

t = is the operating time of the protective device for automatic disconnection in s;


k

= is the factor dependent on the material of the protective conductor, the insulation and is the factor dependent on the material of the protective conductor, the
insulation and

(If t)
k

The factor of K is determine from the formula (Annex A - IEC - 60364-5-54)

Qc( + 200C)
20

ln

1+

f - i

+ i

Qc( + 20C)

20

The value of

80

80

for steel as per ,Table A.54.1 of IEC 60364-5-54

ln

1+

500
202

45
45

80

1.045

81.76

Therefore ,the area of conductor for the maximum fault level of 40A and consider the fault clearing
time is < 0.5 sec.the conductor area is

50000
A

81.76
Considering 15% corrosion allowance of the strip will be

612

Sq.mm

Hence the calculated minimum diameter of the MS Rod

703.26

Sq.mm

Hence the calculated minimum width & Thickness of the Earthing strip

D/4

Earthing Conductor(strip) width

Earthing Conductor(strip) Thickness

70
X
10

mm
mm

Ax4

612 x
3.142
28

Hence ,1R x 75 x10Sqmm GI.strip shall be used for main


earthing grid as per NIT

mm

Considering 15% corrosion allowance the diameter of the GI pipe will be 32mm.
However we will select a standard size of 100mm GI pipe for the main earth mat below ground as per contract specifications

D =

100 mm

Conculation:5.00

from the above calculations,we concluded that the required size of main earthing conductor for LV system is higher than that of HV(11kv system)
Hence the size of earth conductor of main grid is selected based on LV system earthing calculation

6.00

The conductor selected for main earth is 1 Run of 75 x 10mm GI flat as per NIT.
The earthing Electrode selected for earth pit is 100mm dia & 3mtr.as per NIT

DOC.NO.-EL00007,REV-02

7 OF 42

MAIN CONDUCTOR SIZING

SS-1-ELECTRICAL SUBSTATION GROUNDING CALCULATION

ANNEXURE-I
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which
1.02
can flow through the protective device (see IEC 60909-0);

If

=
=

415

50

kA

1.03 The operating time of the protective device for automatic disconnection in s;

ts

1.04 Fault clearing time

tsc

LxB

1.06 Area of earth grid around Substation

551.8

1.07 Resistivity of the soil

70.53

1.08 Design Ambient temperature

Ta

45

1.05 Length and breadth of the earth grid around Substation

15.5

sec
sec
x

35.6
m

-m

2.00 Buried earth conductor (strip)


2.01 Length of burial of Earthing Strip

10220.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

G.I.Pipe

3.00 Earth conductor (Rod or Pipe)

Pipe

3.02 Length of earth electrode rod/pipe

Mtr

3.03 Diameter of earth electrode rod/pipe

100

mm

3.01 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 70.53)
(2 x 3.142 x 10220)

Rg =

0.109821

Rg =

1.40

ln

( 2 x L )
(x t)
ln

(2 x 104448400)
(80 x 7.5)

12.760

The resistance of the earth Conductor (Strip)

Rg =

DOC.NO.-EL00007,REV-02

1.40

ohms

8 OF 42

SS-1

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 70.53)
(2 x 3.142 x 300)

Re =

3.741248

Re =

17.91

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

17.91

ohms

The overall earth resistance of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

17.91

1
-----R2

1
17.91

1
Rn
1

---------------------

17.91

1
Rn

Finally we calculate as

22

Add no. of pits n

the Combined value of n pits

R1

0.81

Ohms

add all transformer body&neutral earth pit

R1- Total Resistance of Earth Electrodes(pits)

(Re)

0.81

R2 - Total Earth Resistance of the buried Conductor

(Rg)

1.40

Refer Annexure-I
1
R
1
R

1
R1

1
0.81

1
R2
+

1
1.40

Hence the combined resistance of grid + Earth pits


R

R1A =

DOC.NO.-EL00007,REV-02

R1

R2

R1

R2

0.81
0.81

x
+

1.40
1.40

1.14
2.22

0.51

Ohms

9 OF 42

SS-1

SS-2-ELECTRICAL SUBSTATION GROUNDING CALCULATION

ANNEXURE-X
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00

SYSTEM DATA
Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which
can flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;

If

=
=

ts

415

50

kA

sec

tsc

LxB

551.8

1.07 Resistivity of the soil

25.05

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

10220.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

G.I.Pipe

1.04 Fault clearing time


1.05 Length and breadth of the earth grid around Substation
1.06 Area of earth grid around Substation

2.00

2.04

1
15.5

sec
x

35.6

m2

-m

Buried earth conductor (strip)

Earth conductor (Rod or Pipe)


Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As p
per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 25.05)
(2 x 3.142 x 10220)

Rg =

0.039005

Rg =

0.50

ln

( 2 x L )
(x t)
ln

(2 x 104448400)
(80 x 7.5)

12.760

The resistance of the earth Conductor (Strip)

Rg =

DOC.NO.-EL00007,REV-02

0.50

ohms

10 OF 42

SS-2

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 25.05)
(2 x 3.142 x 300)

Re =

1.328771

Re =

6.36

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

6.36

ohms

The overall earth resistance of Electrodes:-

1
=
R

1
R1

+
1

1
=
R

6.36

1
-----R2

1
6.36

1
Rn
1

---------------------

6.36

Finally we calculate as
Add no. of pits

1
Rn

22

the Combined value of

n pits

R10 =

0.29

Ohms

add all transformer body&neutral earth pit


R1- Total Resistance of Earth Electrodes(pits)

(Re)

0.29

R2 - Total Earth Resistance of the buried Conductor

(Rg)

0.50

Refer Annexure-X
1
R
1
R

1
R1

1
0.29

1
R2
+

1
0.50

Hence the combined resistance of grid + Earth pits


R

R10A =

DOC.NO.-EL00007,REV-02

R1

R2

R1

R2

0.29
0.29

x
+

0.50
0.50

0.14
0.79

0.18

Ohms

11 OF 42

SS-2

SS-3-ELECTRICAL SUBSTATION GROUNDING CALCULATION

ANNEXURE-II
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00

SYSTEM DATA
Vs

1.01 System nominal voltage

=
=

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which
1.02
can flow through the protective device (see IEC 60909-0);

If

1.03 The operating time of the protective device for automatic disconnection in s;

ts

415

50

kA

sec

tsc

LxB

102.8625

1.07 Resistivity of the soil

25.05

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

4465.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

1.04 Fault clearing time


1.05 Length and breadth of the earth grid around Substation
1.06 Area of earth grid around Substation

2.00

2.04

1
6.5

sec
x

15.83 m
m2

-m

Buried earth conductor (strip)

Earth conductor (Rod or Pipe)


Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr

2.07 Diameter of earth electrode rod/pipe

100

mm

2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 25.05)
(2 x 3.142 x 4465)

Rg =

0.089279

Rg =

0.99

ln

( 2 x L )
(x t)
ln

(2 x 19936225)
(80 x 7.5)

11.104

The resistance of the earth Conductor (Strip)

Rg =

DOC.NO.-EL00007,REV-02

0.99

ohms

12 OF 42

SS-3

Resistance of earth Electrode (Steel Rod Or Pipe)

As per IS:3043 clause no.9.2.2


l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 25.05)
(2 x 3.142 x 300)

Re =

1.328771

Re =

6.36

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

6.36

ohms

The overall earth resistance of Electrodes:-

1
=
R

1
R1

+
1

1
=
R

1
-----R2

1
6.36

6.36

1
Rn
1

---------------------

6.36

1
Rn

Finally we calculate as
Add no. of pits

the Combined value of

n pits - (RA)

0.91

Ohms

Add Pump House-2 earth pit

RA- Total Resistance of Earth Electrodes(pits) of SS-3

(Re)

0.91

RB- Total Resistance of Earth Electrodes(pits) of Pump House-2

(Re)

8 30
8.30

1
R

1
R

1
R1

1
0.91

Refer Annexure-II

1
R2
+

1
8.30

Hence the combined resistance of grid + Earth pits


R

R2 =

DOC.NO.-EL00007,REV-02

R1

R2

R1

R2

0.91
0.91

x
+

8.30
8.30

7.54
9.21

0.82

Ohms

13 OF 42

SS-3

TRANSFER HOUSE (TH-1) GROUNDING CALCULATION

ANNEXURE-XI
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

=
=

ts

tsc

LxB

415

50

kA

sec

1
11

sec
x

1.06 Area of earth grid around Substation

88

1.07 Resistivity of the soil

72.64

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

3800.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

-m

2.00 Buried earth conductor (strip)

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg

( 100 x )
( 2 x x L)

ln

Rg =

(100 x 72.64)
(2 x 3.142 x 3800)

Rg =

0.304198

Rg =

3.28

( 2 x L )
(x t)
ln

(2 x 14440000)
(80 x 7.5)

10.782

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg =

3.28

ohms

14 OF 42

TH-1

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re

( 100 x )
( 2 x x l)

Re

(100 x 72.64)
(2 x 3.142 x 300)

Re

3.853172

Re

18.45

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

18.45

ohms

The Earth resistance with numbers of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

18.45

1
-----R2

1
18.45

1
Rn
1

---------------------

18.45

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R11 =

R1- Total Resistance of Earth Electrodes(pits)

(Re)

4.61

R2 - Total Earth Resistance of the buried Conductor

(Rg)

3.28

4.61

Ohms

Refer Annexure-XI
1
R
1
R

1
R1

1
4.61

1
R2
+

1
3.28

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

R11A =

R1

R2

R1

R2

4.61
4.61

x
+

3.28
3.28

15.13
7.89

4.61

Ohms

15 OF 42

TH-1

TRANSFER HOUSE (TH-2) GROUNDING CALCULATION

ANNEXURE-IV
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which
can flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;

If

=
=

ts

415

50

kA

sec

tsc

LxB

13.7

147.275

1.07 Resistivity of the soil

151.39

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

4890.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

1.04 Fault clearing time


1.05 Length and breadth of the earth grid around Substation
1.06 Area of earth grid around Substation

sec
x

10.75 m
m2

-m

2.00 Buried earth conductor (strip)

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 151.39)
(2 x 3.142 x 4890)

Rg =

0.492666

Rg =

5.56

ln

( 2 x L )
(x t)
ln

(2 x 23912100)
(80 x 7.5)

11.286

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg =

5.56

ohms

16 OF 42

TH-2

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 151.39)
(2 x 3.142 x 300)

Re =

8.030448

Re =

38.45

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

38.45

ohms

The Earth resistance with numbers of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

38.45

1
-----R2

1
38.45

1
Rn
1

---------------------

38.45

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R4

R1- Total Resistance of Earth Electrodes(pits)

(Re)

9.61

R2 - Total Earth Resistance of the buried Conductor

(Rg)

5.56

9.61

Ohms

Refer Annexure-IV
1
R
1
R

1
R1

1
9.61

1
R2
+

1
5.56

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

R4A =

R1

R2

R1

R2

9.61
9.61

x
+

5.56
5.56

53.44
15.17

3.52

Ohms

17 OF 42

TH-2

TRANSFER HOUSE (TH-2A) GROUNDING CALCULATION

ANNEXURE-XIII
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

415

50

kA

sec

ts

tsc

LxB

1
9

sec
x

7.5

1.06 Area of earth grid around Substation

67.5

1.07 Resistivity of the soil

151.39

1.09 Design Ambient temperature

Ta

45

-m

2.00 Buried earth conductor (strip)


2.01 Length of burial of Earthing Strip

3300.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 151.39)
(2 x 3.142 x 3300)

Rg =

0.730041

Rg =

7.67

ln

( 2 x L )
(x t)
ln

(2 x 10890000)
(80 x 7.5)

10.500

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg =

7.67

ohms

18 OF 42

TH-2A

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 151.39)
(2 x 3.142 x 300)

Re =

8.030448

Re =

38.45

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

38.45

ohms

The Earth resistance with numbers of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

38.45

1
-----R2

1
38.45

1
Rn
1

---------------------

38.45

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R13 =

R1- Total Resistance of Earth Electrodes(pits)

(Re)

9.61

R2 - Total Earth Resistance of the buried Conductor

(Rg)

7.67

9.61

Ohms

Refer Annexure-XIII
1
R
1
R

1
R1

1
9.61

1
R2
+

1
7.67

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

R13A =

R1

R2

R1

R2

9.61
9.61

x
+

7.67
7.67

73.67
17.28

4.26

Ohms

19 OF 42

TH-2A

SILO BUILDING GROUNDING CALCULATION

ANNEXURE-III
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

=
=

ts

tsc

LxB

415

50

kA

sec

1
11

sec
x

9.6

1.06 Area of earth grid around Substation

105.6

1.07 Resistivity of the soil

151.39

1.09 Design Ambient temperature

Ta

45

-m

2.00 Buried earth conductor (strip)


2.01 Length of burial of Earthing Strip

4120.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg

( 100 x )
( 2 x x L)

Rg

(100 x 151.39)
(2 x 3.142 x 4120)

Rg

0.584741

Rg

6.40

ln

( 2 x L )
(x t)
ln

(2 x 16974400)
(80 x 7.5)

10.943

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg

6.40

ohms

20 OF 42

SILO BUILDING

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re

( 100 x )
( 2 x x l)

Re

(100 x 151.39)
(2 x 3.142 x 300)

Re

8.030448

Re

38.45

ln

4x

l
d

ln

300
10

4.787

The resistance of the earth electrode

Re

38.45

ohms

The Earth resistance with numbers of Electrodes:-

1
R

1
R

1
R1

+
1

38.45

1
-----R2

1
Rn-1

1
38.45

1
Rn

---------------------

38.45

1
Rn

Finally we calculate as

Add no. of electrode per pits

the Combined value of n pits

R3

R1- Total Resistance of Earth Electrodes(pits)

(Re)

9.6

R2 - Total Earth Resistance of the buried Conductor

(Rg)

6.40

9.61

Ohms

Refer Annexure-III
1
R

=
1

1
R1

1
9.61

1
R2
+

1
6.40

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

R3A =

R1

R2

R1

R2

9.61
9.61

x
+

6.40
6.40

61.50
16.01

3.84

Ohms

21 OF 42

SILO BUILDING

TAIL DRIVE HOUSE GROUNDING CALCULATION

ANNEXURE-XII
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

=
=

ts

tsc

LxB

415

50

kA

sec

1
20.5

sec
x

16.5

1.06 Area of earth grid around Substation

338.25

1.07 Resistivity of the soil

151.39

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

7400.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.5

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

-m

2.00 Buried earth conductor (strip)

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg

( 100 x )
( 2 x x L)

ln

Rg =

(100 x 151.39)
(2 x 3.142 x 7400)

Rg =

0.325559

Rg =

3.94

( 2 x L )
(x t)
ln

(2 x 54760000)
(80 x 7.5)

12.115

The resistance of the earth Conductor (Strip)

Rg =

DOC.NO.-EL00007,REV-02

3.94

ohms

22 OF 42

TRAVEL DRIVE HOUSE

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re

( 100 x )
( 2 x x l)

Re

(100 x 151.39)
(2 x 3.142 x 300)

Re

8.030448

Re

38.45

ln

4x

l
d

ln

300
10

4.787

The resistance of the earth electrode

Re =

38.45

ohms

The overall earth resistance of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

38.45

1
-----R2

1
Rn-1

1
38.45

1
Rn

---------------------

38.45

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R12 =

R1- Total Resistance of Earth Electrodes(pits)

(Re)

9.61

R2 - Total Earth Resistance of the buried Conductor

(Rg)

3.94

9.61

Ohms

Refer Annexure-XII
1
R
1
R

1
R1

1
9.61

1
R2
+

1
3.94

Hence the combined resistance of grid + Earth pits


R

R12A =

DOC.NO.-EL00007,REV-02

R1

R2

R1

R2

9.61
9.61

x
+

3.94
3.94

37.91
13.56

2.80

Ohms

23 OF 42

TRAVEL DRIVE HOUSE

PARKING STATION-1 GROUNDING CALCULATION

ANNEXURE-V
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

=
=

ts

tsc

LxB

415

50

kA

sec

1
10

sec
x

12

1.06 Area of earth grid around Substation

120

1.07 Resistivity of the soil

151.39

1.09 Design Ambient temperature

Ta

45

-m

2.00 Buried earth conductor (strip)


2.01 Length of burial of Earthing Strip

4400.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg

( 100 x )
( 2 x x L)

Rg

(100 x 151.39)
(2 x 3.142 x 4400)

Rg

0.547531

Rg

6.06

ln

( 2 x L )
(x t)
ln

(2 x 19360000)
(80 x 7.5)

11.075

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg =

6.06

ohms

24 OF 42

PARKING STATION-1

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re

( 100 x )
( 2 x x l)

Re

(100 x 151.39)
(2 x 3.142 x 300)

Re

8.030448

Re

38.45

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re

38.45

ohms

The overall earth resistance of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

38.45

1
-----R2

1
38.45

1
Rn
1

---------------------

38.45

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R5

R1- Total Resistance of Earth Electrodes(pits)

(Re)

9.61

R2 - Total Earth Resistance of the buried Conductor

(Rg)

6.06

9.61

Ohms

Refer Annexure-V
1
R

=
1

1
R1

1
9.61

1
R2
+

1
6.06

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

R5A =

R1

R2

R1

R2

9.61
9.61

x
+

6.06
6.06

58.28
15.68

3.72

Ohms

25 OF 42

PARKING STATION-1

PARKING STATION-2 GROUNDING CALCULATION

ANNEXURE-XIV
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which
can flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

=
=

ts

tsc

LxB

415

50

kA

sec

1
10

sec
x

12

1.06 Area of earth grid around Substation

120

1.07 Resistivity of the soil

35.1

1.09 Design Ambient temperature

Ta

45

-m

2.00 Buried earth conductor (strip)


2.01 Length of burial of Earthing Strip

4400.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 35.1)
(2 x 3.142 x 4400)

Rg =

0.126946

Rg =

1.41

ln

( 2 x L )
(x t)
ln

(2 x 19360000)
(80 x 7.5)

11.075

The resistance of the earth Conductor (Strip)

Rg =

DOC.NO.-EL00007,REV-02

1.41

ohms

26 OF 42

PARKING STATION-2

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 35.1)
(2 x 3.142 x 300)

Re =

1.861871

Re =

8.91

ln

4x

l
d

ln

300
10

4.787

The resistance of the earth electrode

Re =

8.91

ohms

The overall earth resistance of Electrodes:-

1
=
R

1
R1

+
1

1
=
R

1
-----R2

1
8.91

8.91

1
Rn-1

1
Rn

---------------------

8.91

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R14

R1- Total Resistance of Earth Electrodes(pits)

(Re)

4.46

R2 - Total Earth Resistance of the buried Conductor

(Rg)

1.41

4.46

Ohms

Refer Annexure-XIV
1
R
1
R

1
R1

1
4.46

1
R2
+

1
1.41

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

R14A =

R1

R2

R1

R2

4.46
4.46

x
+

1.41
1.41

6.27
5.86

1.07

Ohms

27 OF 42

PARKING STATION-2

TRANSFER HOUSE (TH-3) GROUNDING CALCULATION

ANNEXURE-VI
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which
can flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

=
=

ts

tsc

LxB

415

50

kA

sec

1
10.265

sec
x

9.5

1.06 Area of earth grid around Substation

97.5175

1.07 Resistivity of the soil

35.1

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

3953.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

-m

2.00 Buried earth conductor (strip)

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 35.1)
(2 x 3.142 x 3953)

Rg =

0.141301

Rg =

1.53

ln

( 2 x L )
(x t)
ln

(2 x 15626209)
(80 x 7.5)

10.861

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg =

1.53

ohms

28 OF 42

TH-3

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 35.1)
(2 x 3.142 x 300)

Re =

1.861871

Re =

8.91

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

8.91

ohms

The overall earth resistance of Electrodes:-

1
=
R

1
R1

+
1

1
=
R

1
-----R2

1
8.91

8.91

1
Rn
1

---------------------

8.91

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R6

R1- Total Resistance of Earth Electrodes(pits)

(Re)

2.23

R2 - Total Earth Resistance of the buried Conductor

(Rg)

1.53

2.23

Ohms

Refer Annexure-VI
1
R
1
R

1
R1

1
2.23

1
R2
+

1
1.53

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

R6A =

R1

R2

R1

R2

2.23
2.23

x
+

1.53
1.53

3.42
3.76

0.91

Ohms

29 OF 42

TH-3

TRANSFER HOUSE (TH-5) GROUNDING CALCULATION

ANNEXURE-VII
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

=
=

415

50

kA

sec

ts

tsc

LxB

16.95

sec
x

12.5

1.06 Area of earth grid around Substation

211.875

1.07 Resistivity of the soil

41.94

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

5890.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

cm

2.07 Diameter of earth electrode rod/pipe

100

cm

-m

2.00 Buried earth conductor (strip)

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 41.94)
(2 x 3.142 x 5890)

Rg =

0.113312

Rg =

1.32

ln

( 2 x L )
(x t)
ln

(2 x 34692100)
(80 x 7.5)

11.658

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg =

1.32

ohms

30 OF 42

TH-5

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 41.94)
(2 x 3.142 x 300)

Re =

2.224698

Re =

10.65

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

10.65

ohms

The overall earth resistance of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

10.65

1
-----R2

1
10.65

1
Rn
1

---------------------

10.65

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R7

2.66

Ohms

Note:- Refer the Earthing Pit & Strip Scheme for overall plant.

R1- Total Resistance of Earth Electrodes(pits)

(Re)

2.66

R2 - Total
T t lE
Earth
th R
Resistance
i t
off the
th buried
b i d Conductor
C d t

(R )
(Rg)

1 32
1.32

Refer Annexure-VII
1
R
1
R

1
R1

1
2.66

1
R2
+

1
1.32

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

R7A =

R1

R2

R1

R2

2.66
2.66

x
+

1.32
1.32

3.52
3.98

0.88

Ohms

31 OF 42

TH-5

TRANSFER HOUSE (TH-6) GROUNDING CALCULATION

ANNEXURE-XVI
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

=
=

415

50

kA

sec

ts

tsc

LxB

10.85

sec
x

6.5

1.06 Area of earth grid around Substation

70.525

1.07 Resistivity of the soil

128.94

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

3470.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

-m

2.00 Buried earth conductor (strip)

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 128.94)
(2 x 3.142 x 3470)

Rg =

0.591319

Rg =

6.27

ln

( 2 x L )
(x t)
ln

(2 x 12040900)
(80 x 7.5)

10.600

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg =

6.27

ohms

32 OF 42

TH-6

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 128.94)
(2 x 3.142 x 300)

Re =

6.839593

Re =

32.74

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

32.74

ohms

The overall earth resistance of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

32.74

1
-----R2

1
32.74

1
Rn
1

---------------------

32.74

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R16 =

8.19

Ohms

Note:- Refer the Earthing Pit & Strip Scheme for overall plant.

R1- Total Resistance of Earth Electrodes(pits)

(Re)

8.19

R2 - Total
T t lE
Earth
th R
Resistance
i t
off the
th buried
b i d Conductor
C d t

(R )
(Rg)

6 27
6.27

Refer Annexure-XVI
1
R
1
R

1
R1

1
8.19

1
R2
+

1
6.27

Hence the combined resistance of grid + Earth pits


R
R

DOC.NO.-EL00007,REV-02

=
=

R16A =

R1

R2

R1

R2

8.19
8.19

x
+

6.27
6.27

51.31
14.45

3.55

Ohms

33 OF 42

TH-6

PUMP HOUSE-1 GROUNDING CALCULATION

ANNEXURE-VIII
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

=
=

ts

tsc

LxB

415

50

kA

sec

1
11

sec
x

6.5

1.06 Area of earth grid around Substation

71.5

1.07 Resistivity of the soil

205.51

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

3500.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

-m

2.00 Buried earth conductor (strip)

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 205.51)
(2 x 3.142 x 3500)

Rg =

0.934391

Rg =

9.92

ln

( 2 x L )
(x t)
ln

(2 x 12250000)
(80 x 7.5)

10.617

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg =

9.92

ohms

34 OF 42

PUMP HOUSE-1

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 205.51)
(2 x 3.142 x 300)

Re =

10.90123

Re =

52.19

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

52.19

ohms

The overall earth resistance of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

52.19

1
-----R2

1
52.19

1
Rn
1

---------------------

52.19

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits

R8

10.44

Ohms

Note:- Refer the Earthing Pit & Strip Scheme for overall plant.

R1- Total Resistance of Earth Electrodes(pits)

(Re)

R2 - Total
T t lE
Earth
th R
Resistance
i t
off the
th buried
b i d Conductor
C d t

(R )
(Rg)

10.44

Refer Annexure-VIII
1
R
1
R

1
R1

1
10.44

9 92
9.92

1
R2
+

1
9.92

Hence the combined resistance of grid + Earth pits


R
R

=
=

R8A =

DOC.NO.-EL00007,REV-02

R1

R2

R1

R2

10.44
10.44

x
+

9.92
9.92

103.55
20.36

5.09

Ohms

35 OF 42

PUMP HOUSE-1

PUMP HOUSE-2 GROUNDING CALCULATION

ANNEXURE-XVII
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00 SYSTEM DATA

Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which can
flow through the protective device (see IEC 60909-0);

1.03 The operating time of the protective device for automatic disconnection in s;
1.04 Fault clearing time
1.05 Length and breadth of the earth grid around Substation

If

415

50

kA

sec

ts

tsc

LxB

1
9

sec
x

7.5

1.06 Area of earth grid around Substation

67.5

1.07 Resistivity of the soil

228.68

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

3300.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

2.03 Width (Incase of strip) of the conductor (Strip)

7.50

cm

Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

-m

2.00 Buried earth conductor (strip)

2.04 Earth conductor (Rod or Pipe)


2.05 Earth Electrode Material (Rod or Pipe)

Resistance of Buried earth conductor (Strip)


The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 228.68)
(2 x 3.142 x 3300)

Rg =

1.102753

Rg =

11.58

ln

( 2 x L )
(x t)
ln

(2 x 10890000)
(80 x 7.5)

10.500

The resistance of the earth Conductor (Strip)

DOC.NO.-EL00007,REV-02

Rg =

11.58

ohms

36 OF 42

PUMP HOUSE-2

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 228.68)
(2 x 3.142 x 300)

Re =

12.13028

Re =

58.07

ln

4x

l
d

ln

1
Rn-1

300
10

4.787

The resistance of the earth electrode

Re =

58.07

ohms

The overall earth resistance of Electrodes:-

1
=
R
1
=
R

1
R1

+
1

58.07

1
-----R2

1
58.07

1
Rn
1

58.07

---------------------

1
Rn

Finally we calculate as

Add no. of pits n

the Combined value of n pits (RB)

R1- Total Resistance of Earth Electrodes(pits)

(Re)

R2 - Total Earth Resistance of the buried Conductor

(Rg)

8.30

8.30

Ohms

Refer Annexure-XVII
1
R
1
R

1
R1

1
8.30

11.58

1
R2
+

1
11.58

Hence the combined resistance of grid + Earth pits


R

DOC.NO.-EL00007,REV-02

RB

R1

R2

R1

R2

8.30
8.30

x
+

11.58
11.58

96.06
19.87

8.30

Ohms

37 OF 42

PUMP HOUSE-2

DHC AT NEAR AREA HTP-2 (TR-64) CALCULATION

ANNEXURE-IX
REFERENCE
IEC:60364-5-54
IS:3043

ENTER THE VALUE IN YELLOW COLOR BOXES ONLY

STEP-1 : BASIC DESIGN DATA


1.00

SYSTEM DATA
Vs

1.01 System nominal voltage


1.02

The value (r.m.s) in A of prospective fault current for a fault of negligible impedance, which
can flow through the protective device (see IEC 60909-0);

If

=
=

415

50

kA

1.03 The operating time of the protective device for automatic disconnection in s;

ts

sec

1.04 Fault clearing time

tsc

sec

LxB

800

1.07 Resistivity of the soil at DHC HTP-2

70.15

1.09 Design Ambient temperature

Ta

45

2.01 Length of burial of Earthing Strip

18000.0

cm

2.02 Depth of burial of conductor (Strip)

80

cm

7.50

cm

1.05 Length and breadth of the earth grid around Substation


1.06 Area of earth grid around Substation

2.00

10
m2

-m

Buried earth conductor (strip)

2.03 Width (Incase of strip) of the conductor (Strip)


2.04

80

Earth conductor (Rod or Pipe)


Pipe

G.I.Pipe

2.06 Length of earth electrode rod/pipe

Mtr.

2.07 Diameter of earth electrode rod/pipe

100

mm

2.05 Earth Electrode Material (Rod or Pipe)

R i t
Resistance
off Buried
B i d earth
th conductor
d t
(Strip)
(St i )
The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

L = Length of the Strip (in Cm)


= Depth of burial of the Earthing strip cm
t = Width(incase of Strip) or twice the diameter(fir Conductors) in cm.
= Resistivity of the soil in m
Rg = Resistance of the earth conductor

Rg =

( 100 x )
( 2 x x L)

Rg =

(100 x 70.15)
(2 x 3.142 x 18000)

Rg =

0.062018

Rg =

0.86

ln

The resistance of the earth Conductor (Strip)

Rg =

0.86

ohms

( 2 x L )
(x t)
ln

13.892

(2 x 324000000)
(80 x 7.5)

Resistance of earth Electrode (Steel Rod Or Pipe)


As per IS:3043 clause no.9.2.2
l

= Length of rod or Pipe (in Cm)

d = Diameter of rod or pipe in cm

= Resistivity of the soil in m


Re = Resistance of the earth Electrode
The resistance of earth electrode is given by

Re =

( 100 x )
( 2 x x l)

Re =

(100 x 70.15)
(2 x 3.142 x 300)

Re =

3.721091

Re =

17.81

4x

l
d

ln

1
Rn-1

ln

300
10

4.787

The resistance of the earth electrode

Re =

17.81

ohms

The overall earth resistance of Electrodes:-

1
=
R

1
R1

+
1

1
=
R

17.81

1
-----R2

1
17.81

1
Rn
1

---------------------

17.81

1
Rn

Finally we calculate as
Add no. of pits

20

the Combined value of

n pits

0.89

Ohms

Note:- Refer the Earthing Pit & Strip Scheme for overall plant.

R1 Total
R1T t lR
Resistance
i t
off Earth
E th Electrodes(pits)
El t d ( it )

R1

(R )
(Re)

0 89
0.89

R2 - Total Earth Resistance of the buried Conductor

R2

(Rg)

0.86

Refer Annexure-IX
1
R
1
R

1
R1

1
0.89

1
R2
+

1
0.86

Hence the combined resistance of grid + Earth pits


R

R3

R1

R2

R1

R2

0.89
0.89

x
+

0.86
0.86

0.77
1.75

0.44

Ohms

Resistance of earth conductor (Strip) riser & DHC gantry strip at HTP-3 to HTP-6
The resistance of earth grid can be calculated by using the formula
As per IS:3043 clause no.9.2.3

l = Length of the Strip (in m)

1950.0

A = Area of the earth conductor strip =

75

= Resistivity of the GI conductor in m

m
10

138 x 10-9

Rg = Resistance of the earth conductor

Rg =

Rg =
Rg =

(lx)
A
(1950 x 138 x 10-9)
-6
750
x 10
0.36

The resistance of the earth Conductor (Strip)

R4 =

0.359

ohms

750

Sqmm

R3- Total Resistance of Earth Electrodes(pits)+Grid Strip

R3 =

(Re)

0.44

R4 - Total Earth Resistance of the along the conveyor earth strip

R4 =

(Rg)

0.36

R3

R4

0.44

0.36

0.80

Hence the combined resistance of grid + Earth Strip

R9A =

0.80

Ohms

CLIENT
CONSULTANT
CONTRACTOR
PROJECT:
PACKAGEII:
DOCUMENTNAME:
DOCUMENTNO.

REV.

SIZINGOFPLANTEARTHINGCONDUCTOR
SR.NO.

DESCRIPTION

A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

MainGridandConnectivitytoPlantearthing
Substation1(SS1)
Substation2(SS2)
S b t ti 3 (SS 3)
Substation3(SS3)
TransferHouse(TH1)
TransferHouse(TH2)
TransferHouse(TH2A)
SiloBuilding
TaildriveHouse
TransferHouse(TH3)
TransferHouse(TH4)
TransferHouse(TH5)
Transfer House (TH6)
TransferHouse(TH
6)
Parkingstation(PS1)
Parkingstation(PS2)
Alongtheconv718gallarycableTray
Alongtheconv719gallarycableTray
Alongtheconv721gallarycableTray
Alongtheconv727gallarycableTray
Alongtheconv7271gallarycableTray
Alongtheconv7272gallarycableTray
Alongtheconv723gallarycableTray

B
1
2

Transformer
TransformerBodyEarthing
TransformerNeutralEarthing

C
1
2
D
1
1.1
1.2
1.3
1.4
1.5
1.6
1.8
19
1.9

SIZEOF
NO.OFEARTH EARTHING
CONNECTION CONDUCTOR
(SQMM)

NOOF
RUNPER
CONDUCTORTYPE REMARKS
CONNECT
ION

75x10mm
75x10mm
75 10
75x10mm
75x10mm
75x10mm
75x10mm
75x10mm
75x10mm
75x10mm
75x10mm
75x10mm
75 x 10 mm
75x10mm
75x10mm
75x10mm
50x6mm
50x6mm
50x6mm
50x6mm
50x6mm
50x6mm
50x6mm

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

GIFlat
GIFlat
GI Fl t
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GI Flat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat

2separate
2separate

65x10mm
65x10mm

1
1

GIFlat
GIFlat

HTEquipment
6.6kvHTpanelatSS1
11kvHTpanelatSS2

2separate
2separate

50x6mm
50x6mm

1
1

GIFlat
GIFlat

LTE i
LTEquipment
t
LTPower&ControlPanels
PMCCatSS1
PMCCatSS2
ACVENTMCCatSS1
ACVENTMCCatSS2
DFDSboardatPumpHouse1
DFDSboardatPumpHouse2
HydraulicSystemControlPanelsbodyearth
Lubrication System Control Panels body earth
LubricationSystemControlPanelsbodyearth

2separate
2separate
2separate
2separate
2separate
2separate
2separate
2 separate
2separate

60x10mm
60x10mm
60x10mm
60x10mm
60x10mm
60x10mm
25x6mm
25 x 6 mm
25x6mm

1
1
1
1
1
1
1
1

GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GI Flat
GIFlat

DOC.NO.-EL00007,REV-02

4 OF 42

PLANT CONCUCTOR

SR.NO.

SIZEOF
NO.OFEARTH EARTHING
CONNECTION CONDUCTOR
(SQMM)

DESCRIPTION

2
2.1
2.2
2.3
2.4
2.5
2.6
2.7

LTDistributionBoard
MainLightingDistributionBoard
WeldingDistributionBoard
AuxiliaryPowerDistributionBoard
LightingDistributionBoard
FieldPowerDistributionBoard
LocalPushButtonsBoard
UPS,UPSdistributionBoard
Battery Charger & DCDB
BatteryCharger&DCDB

3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9

Electricalitems
3PhaseWeldingsocketBodyearthing
Exaustfan
LightingFixture
CellingFan
Socket3Pin
LightingJB
StreetLightingpoleEarthing
g
gp
g
ControlJunctionBox
PowerJunctionBox

2separate
2separate
2separate
2separate
2separate
2separate
2separate
2 separate
2separate

50x6mm
50x6mm
50x6mm
25x6mm
25x6mm
25x6mm
25x6mm
25 x 6 mm
25x6mm

1
1
1
1
1
1
1
1

GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GIFlat
GI Flat
GIFlat

2separate

16Sqmm

StrandedGIwire

Samesizeasphaseconductor

2
2separate
2separate
p
2separate
2separate

E
1
2
3
4

LTMotors
LTMotorsupto2.2kw
LTMotors3.7kwto15kw
LTMotors15kwto45kw
LTMotorsabove45kw

2separate
2separate
2separate
2separate

F
1
2
3
4
5
6
7
8
9

FieldInstrument
Pullcordswitches
BeltSwaySwitches
ZerospeedSwitches
ChuteJamSwitches
BeltWeighSwitch
SlipSwitches
MonoralHoist
PJBforMotors
CJBforMotors
CJB for Motors

2separate
2separate
2separate
2separate
2separate
2separate
2separate
2separate
2separate
2 separate

DOC.NO.-EL00007,REV-02

NOOF
RUNPER
CONDUCTORTYPE REMARKS
CONNECT
ION

16Sq.mm
16Sq.mm
q
6Sq.mm
6Sq.mm

1
1
1
1

GIWire
GIWire
StrandedGIwire
StrandedGIwire

6Sq.mm
16Sq.mm
25x3mm
50x6mm

1
1
1
1

StrandedGIwire
StrandedGIwire
GIFlat
GIFlat

1
1
1
1
1
1
1
1
1

StrandedGIwire
StrandedGIwire
StrandedGIwire
StrandedGIwire
StrandedGIwire
StrandedGIwire
GIFlat
GIFlat
StrandedGIwire
Stranded GI wire

6Sq.mm
6Sq.mm
6Sq.mm
6Sq.mm
6Sq.mm
6Sq.mm
25x6mm
SameasMotor
6Sq.mm
6 Sq mm

5 OF 42

PLANT CONCUCTOR