Professional Documents
Culture Documents
Table of Contents
Table of Contents
Chapter 5 Grounding Regulations............................................................................................... 5-1
5.1 About This Chapter ............................................................................................................ 5-1
5.2 Introduction to Grounding .................................................................................................. 5-1
5.2.1 Related Concepts of Grounding.............................................................................. 5-1
5.2.2 Types and Methods of Grounding........................................................................... 5-2
5.3 M900/M1800 BSC System Grounding .............................................................................. 5-6
5.3.1 Grounding of Assembled Cabinets ......................................................................... 5-7
5.3.2 Grounding of BSC Equipment................................................................................. 5-7
5.3.3 Connection Between BSC and Transmission Equipment..................................... 5-10
5.3.4 Grounding Resistance........................................................................................... 5-10
5.4 Reconstruction of Network Equipment Grounding .......................................................... 5-10
5.5 Grounding Processing ..................................................................................................... 5-12
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
Introduction to Grounding
Grounding
Earth
It means the grounding device, consisting of metal cases and cables of electronic
equipment. It is connected to the earth through grounding cables and grounding
poles (bars).
Ensure safety.
Huawei Technologies Proprietary
5-1
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
According to the electric application rules, you must earth the metal case of
electronic equipment to avoid danger caused by insulation failure or electric
leakage.
z
Suppress interference.
The connection of the system ground of electronic equipment to the earth can
provide a stable reference potential for the signal loop. The connection of the
shielding layer to the earth can suppress the interference of the varying electric
field.
These grounding subsystems are also called three types of grounding busbars. Each
grounding subsystem has many types of grounding modes, as described later.
I. Protection Grounding
There are two grounding modes for the protection grounding of electric equipment:
z
Zero-line protection
It mostly applies to the three-phase four-line power distribution system. Normally
it works with the protection circuit. When a phase line contacts the case, there is a
large short circuit current flowing back to the power supply through protection
grounding. The protection circuit reacts to this and then cuts off the power.
Protection ground
It normally applies to single-phase electric equipment or electronic equipment of
small capacity.
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
Electronic
circuitry
Electronic
circuitry
Electronic
circuitry
If the float grounding system has a large resistance to the ground and a small
distribution capacitance to the ground, the interference current caused by the
external common mode interference is small. Generally, this mode applies to a
small control system or low speed device.
z
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
potential difference exists between the system ground and the earth, you can
select
this
mode.
The
capacitance
must
have
better
high-frequency
C2
Shielding
A
C1
EN
C1
C3
UN
C2
In Figure 5-2, A is the noise source. Its noise voltage is UN and capacitance C3. B is the
inducted signal line. Its capacitance to the ground is C1 and that to A is C2. EN is the
noise induction potential. It can be expressed in the following formula:
E N=
C2
UN
C1 + C 2
The shorter the distance between A and B is, the larger C2 and EN are. Nevertheless, if
the shielding layer of the signal line B is grounded, the induced noise potential is always
zero. Otherwise, the signal line can still be affected by partial induction potential due to
the distribution capacitance existing between the shielding layer and the signal line.
In addition, the grounding of the shielding layer can suppress the signal line from
radiating noise to the outside, as shown in Figure 5-2. If the shielding layer of the noise
source A is grounded, its noise voltage to the earth is zero. Thus it cannot generate
induction voltage to B.
The shielding layer made of non-magnetic conductive materials, such as copper and
aluminum, can only suppress static induction noise. To prevent magnetic induction
noise, you must use materials with strong magnetic conductivity, such as iron, for the
shielding layer.
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
For either system grounding or shielding layer grounding, one-point grounding mode is
often used, that is, use a grounding pole. This is because grounding resistance exists.
When the current flows to the earth, potential of the grounding pole and the earth
around it increases, causing the potential change of the equipment ground. Therefore,
potential difference always exists between two separate grounding points far away
from each other, as shown in Figure 5-3.
U1
U2
Signal line
O1
G1
O2
IN
G2
UN
Figure 5-3 Potential difference between two grounding points
The system grounds of two units U1 and U2 are connected to the earth at a nearby place
respectively. Potential difference UN exists at the grounding points G1 and G2, thus
generating interference current IN. Because of the effect of various factors, a great
change takes place to the potential around the grounding pole.
For example, the voltage can be up to between 1 kV and 2 kV when there is a lightning
strike. Therefore, the system has a large interference current instantly, thus affecting
the normal operation of the system.
In addition, the system ground or the shielding ground forms a closed loop with the
grounding cable and the earth. Interference current can be generated in the loop under
the effect of magnetic induction. Therefore, one-point grounding mode often applies to
the actual magnetic environment.
For high-frequency signal or interference, the shielding layer also uses the two-end
grounding or multi-point grounding mode. This is because even a short grounding
cable has great impedance and the voltage decreases at a high-frequency. Due to the
effect of distribution capacitance, it is indeed difficult to use one-point grounding.
Therefore, the two-end grounding or multi-point grounding mode is often used to
reduce grounding impedance and eliminate distribution capacitance.
For example, when the length of the cable is 1/4 that of the signal wave, the signal
generates standing wave on its shielding layer to form a noise transmission antenna. In
this case, you must use the two-end grounding mode to suppress the noise
transmission. Furthermore, the shielding layer of some sensitive high-frequency input
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
cables must also use the two-end grounding mode to reduce the area of the grounding
loop.
The small-capacity BSC must use the radiation one-point grounding mode, as shown in
Figure 5-4. That is to connect all parts to the grounding pole through grounding cables.
Thus interference due to common impedance and closed loop of grounding can be
avoided.
U1
U3
U2
When the system has many grounding cables, you can use the trunk grounding mode.
That is to use a conductor with an enough cross-sectional area as the grounding
busbar and connect it directly to the grounding pole. Then you can connect all parts to
the busbar nearby, as shown in Figure 5-5.
U1
U3
U2
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
The lightning protection and grounding design must take into consideration the
personal and equipment safety, and normal operation of communications
equipment.
The lightning protection and grounding design must also comply with relevant
specifications.
If there is difficulty in implementing some items of this regulation, you must detail
the reasons in the design documents, and propose solutions for approval.
The grounding cable, as thick and short as possible, must use copper conducting
wires to minimize high-frequency impedance.
The grounding terminal must be secured with bolts to ensure good contact.
To reduce mutual interference, the grounding cables and signal cables cannot be
parallel or wound together.
The BSC system must use joint grounding. The grounding cables of the cabinets
in the same module must be securely jointed to form an equipotential body.
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
During installation, connect the racks in the same row using bolts and washers.
z
Cabinet grounding
From each cabinet one GND wire and one PGND wire must be led out and
connected respectively to the GND and the PGND copper bars of the DC
distribution cabinet or power distribution box.
The GND copper bar of the DC distribution cabinet or power distribution box must
be connected to the GND terminal of the DC distribution panel through the black
plastic insulated copper core GND busbar. The PGND copper bar must be
connected to the PGND terminal of the equipment room through yellow and green
plastic insulated copper core PGND busbar.
The grounding cable of the cabinet must be no less than 25 mm2 in cross-sectional
area. The cross-sectional area of the grounding busbar must be calculated based
on engineering design. The cross-sectional area of the grounding busbar of the
DC distribution cabinet must be no less than 240 mm2 and that of the power
distribution box must be no less than 90 mm2.
Figure 5-6 shows the grounding of the assembled cabinet.
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
......
PGND
GND
......
-48V2
-48V1
-48V2
(2)
PGND
GND
-48V2
-48V1
PGND
-48V1
GND
-48V2
-48V1
(1)
......
GND
(4)
PGND
(4)
(4)
......
(3)
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
disconnected from the AC neutral line and then connected to the grounding cable from
the BSC GND.
Back up data.
2)
Cut off the power supply to the power supply unit in each frame in regular
sequence.
3)
Turn off the air breakers on the upper front of the rack one by one.
4)
Turn off the power switch of the cabinet through the power distribution cabinet or
power distribution box.
5)
Remove the nut from the PGND connector post and push the lug at one end of the
0.19m GND feeder into the PGND connector post.
6)
Remove the nut from the GND connector post and connect the lug at the other end
of the 0.19m GND feeder to the GND connector post. Meanwhile, connect the lug
on one end of another connecting 1.4m GND feeder to this post and connect the
other end to the GND connector post of the neighboring cabinet.
7)
Installation Manual
M900/M1800 Base Station Controller
8)
Installation Preparations
Chapter 5 Grounding Regulations
After all cable connections are complete, measure with a multimeter to see if there
is any short circuit between the 48 V terminal and the GND before power-on
again.
9)
Turn on the power switch in the power distribution cabinet or power distribution
box.
10) Turn on the air breakers on the upper front of the rack one by one.
11) Power on the power supply units in all frames in sequence.
12) Observe if every frame works normally.
Proceed with the reconstruction of the next rack.
Flat washer
Nut
Spring washer
Back-to-back installation
Flat washer
Nut
Spring washer
Bending 45 or 90 degrees
Figure 5-8 Installation of connectors (2)
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
Flat washer
Nut
Spring washer
Cross installation
Figure 5-9 Installation of connectors (3)
Contact resistance among the connecting cables, grounding post, and soil
Soil type
The soil type has the greatest impact on grounding resistance. For areas in poor
soil conditions, you can use some chemical agents such as acrylamide resistance
reduction agent around the grounding bar to meet the grounding requirements of
the BSC.
Temperature
When the temperature is below 0C, the grounding resistance may change much.
For the BSC installed in a cold area, you must mount grounding bars deep in the
earth and use chemical agents.
Humidity of soil
The connecting cables from the grounding bars to the grounding bolts on the BSC
equipment must use copper core cables with the cross-sectional area no less than 50
mm2 and the distance between them as short as possible. When the distance is over 50
m, you must use the copper core cables with a larger diameter.
Installation Manual
M900/M1800 Base Station Controller
Installation Preparations
Chapter 5 Grounding Regulations
You must tin both ends of the connecting cable or soak them in tin. Then clean the
coating material, varnish, and paint around the fixing point to ensure good contact
between the two metal surfaces.
All grounding parts must have anticorrosion protection. You must tighten the grounding
bolts mechanically to ensure a low resistance connection.