Engineer Data

DAIKIN DDW Air Handling Units


Horizontal Unit
Model:
Air Flow:

Vertical Unit
Model:
Air Flow:

DDW020H-DDW450H
2000m3/h-45000m3/h

DDW040V-DDW450V
4000m3/h-45000m3/h

ED-DDW-201401A

Double Skin Air Handling Unit DDW


Literature No.: ED-DDW-201401A
Supersedes: ED-DDW-201310A

Contents
Nomenclature....................................................................................................................... 2
Features................................................................................................................................ 3
Specifications....................................................................................................................... 4
Fan Discharge Type............................................................................................................ 16
Special Notes...................................................................................................................... 17
Wiring Diagrams................................................................................................................. 17
Installation........................................................................................................................... 18
Servicing And Maintenance .............................................................................................. 20
Common Failures............................................................................................................... 22

Note: Installation and maintenance are to be performed only by qualified personnel who are
familiar with local codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning: Moving machinery and electrical power hazard may cause severe personal injury or
death. Disconnect and lock off power before servicing equipment.

DDW

Double Skin Air Handling Unit

Nomenclature
D D W 080 H R 08 -4 L- F F B E
Export
Design ID
Discharge Type
F - Horizontal Discharge Type
T - Top Discharge Type
Power Supply:
F - 380-415V/3N~/50Hz
R - 380V/3N~/60Hz
P - 208-230V/3N~/60Hz
Q - 460V/3N~/60Hz
Pipe Connection:
R - Left Hand
L - Right Hand
(Facing Air Discharge)
Coil Rows:
4 - 4 Rows
6 - 6 Rows
External Total Pressure
08 - 80 Pa; 15 - 150Pa
22 - 220Pa; 30 - 300Pa
Air Conditioning
R - Return Air
F - Fresh Air
Structure Type
H - Horizontal
V - Vertical
Air Flow
080 - 8000m3/h
DDW - Double-Skin AHU

Double Skin Air Handling Unit DDW

Features
General Information
DAIKIN DDW air handling units are designed to meet the needs of the terminal air conditioning market. DDW
units are full featured handlers that are applicable for the central air-conditioning systems installed in hotels,
supermarkets, hospitals and office buildings.

Casing
DDW Casing units is of double-skin panels and assembled with self supporting modular panel elements with an
integrated base frame made of galvanized steel. assembled 25mm polyurethane foam offer ideal heat/sound
insulation.

Filter
Washable nylon primary air filter, removable and easy installation. Bag filter is optional.

Coil Selection
All the computing results and the products built on these results have passed strict test. This ensures their safe,
reliable and effcient operation.

Certrifugal Fan
High efficient and quiet titled multi-blade double-intake fans.

Motor
V-belt driving,Class F,IP55 provide different amounts of air low and ETP to meet different needs.

Mixing Section Option


Optional mixing section with low leak dampers are available for applications where both return and fresh air are
delivered directly to the unit.

DDW

Double Skin Air Handling Unit

Specifications
DDW-H (Horizontal)
Model

DDW020H

DDW030H

DDW040H

DDW050H

DDW060H

DDW080H

Nominal Air Flow (m3/h)

2000

3000

4000

5000

6000

8000

80

80

80

II

150

150

150

150

150

150

III

220

220

220

220

220

220

IV

--

300

300

300

Nominal
cooling
capacity
(kW)

4 Rows (Return air)

12

17

24

30

37

49

4 Rows (Fresh air)

28

41

56

66

80

111

6 Rows (Return air)

15

23

32

38

46

61

6 Rows (Fresh air)

34

52

67

86

103

136

Nominal
heating
capacity
(kW)

4 Rows (Return air)

19

29

40

49

60

81

4 Rows (Fresh air)

32

48

65

80

97

130

6 Rows (Return air)


6 Rows (Fresh air)

23
37

35
56

47
75

59
93

71
112

94
149

External
total
pressure
(Pa)

Coil

Fan

Motor

Filter
Casing
Unit weight
(kg)
Unit
dimension
Packing
dimension

Type

Corrugated aluminum fin mechanically bonded with copper tube

FPI

12

Working pressure (MPa)


Entering/Leaving
water pipe
Condensing water pipe

1.6
R1-1/2

R1-1/2

R2

R2

R2

R2

R1-1/4

Copper pipie diameter (mm)

12.7

Type/Material

High Efficient Centrifugal Multi-blades Fan/Galavnize Steel

Drive type

V-belt

Fan disdcharge orientation

Lower horizontal discharge/Top discharge

Power source

380-415V/3N~/50Hz; 380V/3N~/60Hz; 208-230V/3N~/60Hz; 460V/3N~/60Hz

Motor type

3-Phase Asynchronous Motor,Class F, no less than IP54


I

0.37(0.37)

0.55(0.55)

0.55(0.75)

II

0.37(0.55)

0.55(0.75)

0.75(1.1)

1.1(1.1)

1.1(1.5)

1.5(2.2)

III
IV

0.55(0.55)
-

0.75(0.75)
-

6 Rows

153

174

Height (mm)

600

650

765

765

839

839

Width (mm)

900

1050

1080

1250

1320

1680

Length (mm)

960

1000

1100

1060

1150

1150

Motor output power


(kW)
Type/Material
Thickness (mm)
Type
4 Rows

1.1(1.1)
1.1(1.5)
1.5(1.5)
2.2(2.2)
1.5(1.5)
1.5(2.2)
2.2(2.2)
Plate/Nylon
21
25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel
143
168
185
210
230
269
197

217

242

294

Height (mm)

800

850

965

965

1039

1039

Width (mm)

1150

1300

1330

1500

1570

1930

Length (mm)

1170

1210

1310

1270

1360

1360

NOTES:
1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.
2) STANDARD RETURN AIR COOLING CONDITIONS: 27C DB/19.5C WB;

STANDARD FRESH AIR COOLING CONDITIONS: 34C DB/28C WB;

STANDARD RETURN AIR HEATING CONDITION: 21C DB; STANDARD FRESH AIR HEATING CONDITION: 0C WB STANDARD
COOLING WATER ENTERING/LEAVING CONDITIONS: 7C FOR ENTERING WATER; 12C FOR LEAVING WATER;

STANDARD HEATING WATER ENTERING/LEAVING CONDITIONS: 60C FOR ENTERING WATER; 50C FOR LEAVING WATER;
3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW
SELECTION SOFTWARE.
4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.

Double Skin Air Handling Unit DDW

DDW-H (Horizontal)
Model
Nominal Air Flow (m /h)

DDW100H

DDW120H

DDW150H

DDW180H

DDW200H

DDW250H
25000

10000

12000

15000

18000

20000

II

150

150

150

150

150

150

III

220

220

220

220

220

220

IV

300

300

300

300

300

300

Nominal
cooling
capacity
(kW)

4 Rows (Return air)

62

73

95

108

121

152

4 Rows (Fresh air)

139

166

194

233

266

333

6 Rows (Return air)

76

91

118

144

151

190

6 Rows (Fresh air)

170

204

263

316

346

430

Nominal
heating
capacity
(kW)

4 Rows (Return air)

101

120

152

182

200

250

4 Rows (Fresh air)

159

193

242

291

325

404

6 Rows (Return air)


6 Rows (Fresh air)

118
186

141
223

179
283

213
335

237
373

297
467

External
total

pressure
(Pa)

Coil

Fan

Type

Corrugated aluminum fin mechanically bonded with copper tube

FPI

12

Working pressure (MPa)

1.6

Entering/Leaving
water pipe
Condensing water pipe

R2

R2-1/2

R3

12.7

Type/Material

High Efficient Centrifugal Multi-blades Fan/Galavnize Steel

Drive type

V-belt

Fan disdcharge orientation

Lower horizontal discharge/Top discharge

Power source

380-415V/3N~/50Hz; 380V/3N~/60Hz; 208-230V/3N~/60Hz; 460V/3N~/60Hz

Motor output power


(kW)
Type/Material
Thickness (mm)

Casing

Type

Unit weight
(kg)

4 Rows

Packing
dimension

R2-1/2

Copper pipie diameter (mm)

Filter

Unit
dimension

R2-1/2

R1-1/4

Motor type
Motor

R2

6 Rows

3-Phase Asynchronous Motor,Class F, no less than IP54


I

II

2.2(2.2)

2.2(3.0)

3.0(4.0)

4.0(4.0)

4.0(4.0)

5.5(5.5)

III
IV

2.2(2.2)
2.2(3.0)

3.0(3.0)
3.0(3.0)

4.0(4.0)
4.0(5.5)
4.0(5.5)
5.5(7.5)
4.0(4.0)
5.5(5.5)
5.5(5.5)
7.5(7.5)
Plate/Nylon
21
25mm Double skin,outer plate material is color coated steel,inner plate material is
EG steel
330
341
391
464
499
552
352

370

432

517

555

617

Height (mm)

970

1085

1215

1275

1275

1465

Width (mm)

1690

1690

1940

2120

2300

2400

Length (mm)

1170

1170

1170

1310

1310

1310

Height (mm)

1170

1285

1415

1475

1475

1665

Width (mm)

1940

1940

2190

2370

2550

2650

Length (mm)

1380

1380

1380

1520

1520

1520

NOTES:
1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.
2) STANDARD RETURN AIR COOLING CONDITIONS: 27C DB/19.5C WB;

STANDARD FRESH AIR COOLING CONDITIONS: 34C DB/28C WB;

STANDARD RETURN AIR HEATING CONDITION: 21C DB; STANDARD FRESH AIR HEATING CONDITION: 0C WB STANDARD
COOLING WATER ENTERING/LEAVING CONDITIONS: 7C FOR ENTERING WATER; 12C FOR LEAVING WATER;

STANDARD HEATING WATER ENTERING/LEAVING CONDITIONS: 60C FOR ENTERING WATER; 50C FOR LEAVING WATER;
3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW
SELECTION SOFTWARE.
4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.

DDW

Double Skin Air Handling Unit

DDW-H (Horizontal)
Model
Nominal Air Flow (m3/h)
External total
pressure (Pa)

Nominal cooling
capacity (kW)

Nominal heating
capacity (kW)

Coil

Fan

DDW300H
30000

DDW350H
35000

DDW400H
40000

DDW450H
45000

300

300

300

300

II

400

400

400

400

III

500

500

500

500

IV

600

600

600

600

4 Rows (Return air)

178

205

238

266

4 Rows (Fresh air)

390

448

520

577

6 Rows (Return air)

222

256

296

329

6 Rows (Fresh air)

490

556

639

703

4 Rows (Return air)

295

337

391

437

4 Rows (Fresh air)

472

534

604

670

6 Rows (Return air)


6 Rows (Fresh air)

371
544

398
629

450
719

500
802

Type
FPI

Corrugated aluminum fin mechanically bonded with copper tube


12

Working pressure (MPa)

1.6

Entering/Leaving
water pipe
Condensing water pipe
Copper pipie diameter
(mm)
Type/Material
Drive type
Fan disdcharge
orientation
Power source

R3

R2-1/2

Motor output
power (kW)

R2-1/2

R1-1/4
12.7
High Efficient Centrifugal Multi-blades Fan/Galavnize Steel
V-belt
Horizontal discharge /Top discharge
380-4~5V/3N~/50Hz; 380V/3N~/60Hz; 208-230V/3N~/60Hz; 460V/3N~/60Hz

Motor type
Motor

R2-1/2

3-Phase Asynchronous Motor,Class F,IP55


I

7.5(11)

11(11)

11(15)

15(15)

II

11(11)

11(15)

15(15)

15(18.5)

III

11(11)

15(15)

15(15)

18.5(18.5)

IV

15(15)

15(15)
18.5(18.5)
18.5(18.5)
G3 Plate Prefilter/Nylon
46
25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel

Casing

Type/Material
Thickness (mm)
Type
Height (mm)

1549

1709

1869

2029

Unit dimension

Length (mm)

1646

1646

1806

1806

Width (mm)
Height (mm)
Width (mm)
Length (mm)

2766
1566
1846
2966

2766
1726
1846
2966

2926
1886
2006
3126

2926
2046
2006
3126

Filter

Packing
dimension

NOTES:
1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.
2) STANDARD RETURN AIR COOLING CONDITIONS: 27C DB/19.5C WB;

STANDARD FRESH AIR COOLING CONDITIONS: 34C DB/28C WB;

STANDARD RETURN AIR HEATING CONDITION: 21C DB; STANDARD FRESH AIR HEATING CONDITION: 0C WB STANDARD
COOLING WATER ENTERING/LEAVING CONDITIONS: 7C FOR ENTERING WATER; 12C FOR LEAVING WATER;

STANDARD HEATING WATER ENTERING/LEAVING CONDITIONS: 60C FOR ENTERING WATER; 50C FOR LEAVING WATER;
3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW
SELECTION SOFTWARE.
4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.

Double Skin Air Handling Unit DDW

DDW-V (Vertical)
Model
Nominal Air Flow (m3/h)
External
total
pressure
(Pa)
Nominal
cooling
capacity
(kW)
Nominal
heating
capacity
(kW)

DDW040V
4000

Fan

Filter

DDW080V
8000

DDW100V
10000

DDW120V
12000

DDW150V
15000

150

150

150

150

150

150

150

III

220

220

220

220

220

220

220

IV

300

300

300

300

300

300

300

29
69
39

36
78
54

49
106
61

62
135
76

72

90

164

194

6 Rows (Return air)

23
54
31

94

118

6 Rows (Fresh air)

69

85

102

132

164

202

259

4 Rows (Return air)

39

49

59

80

100

120

152

4 Rows (Fresh air)

64

80

96

128

161

193

241

6 Rows (Return air)


6 Rows (Fresh air)

47
75

59
93

71
112

95
149

119
187

141
223

176
279

R2

R2-1/2

4 Rows (Return air)


4 Rows (Fresh air)

Corrugated aluminum fin mechanically bonded with copper tube

FPI

12

Working pressure (MPa)

1.6

Entering/Leaving
water pipe
Condensing water pipe

R2

R2

R2

R2

R2

R1-1/4

Copper pipie diameter (mm)

12.7

Type/Material

High Efficient Centrifugal Multi-blades Fan/Galavnize Steel

Drive type

V-belt

Fan disdcharge orientation

Top discharge

Power source

380-415V/3N~/50Hz; 380V/3N~/60Hz; 208-230V/3N~/60Hz; 460V/3N~/60Hz

Motor type
Motor

DDW060V
6000

II

Type

Coil

DDW050V
5000

Motor output power


(kW)

I
II

0.75(1.1)

1.1(1.1)

III
IV

1.1(1.1)
1.1(1.5)

1.1(1.5)
1.5(1.5)

3-Phase Asynchronous Motor,Class F,IP55


1.5(1.5)
1.5(2.2)
2.2(2.2)
1.5(2.2)
2.2(2.2)

Type/Material

2.2(2.2)
2.2(2.2)
Plate/Nylon

2.2(2.2)
2.2(3.0)

2.2(3.0)

3.0(4.0)

3.0(3.0)
3.0(3.0)

4.0(4.0)
4.0(5.0)

Thickness (mm)

21

Casing

Type

25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel

Unit weight
(kg)

4 Rows

197

223

244

272

343

367

433

6 Rows

206

235

257

303

365

397

475

Unit
dimension
Packing
dimension

Height (mm)

1346

1403

1460

1673

1933

2010

1746

Length (mm)

980

1140

1210

1320

1390

1530

2090

Width (mm)

650

650

650

810

900

900

900

Height (mm)

1533

1590

1647

1860

2120

2197

1933

Width (mm)

860

860

860

1020

1110

1110

1110

Length (mm)

1160

1320

1390

1500

1570

1710

2270

NOTES:
1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.
2) STANDARD RETURN AIR COOLING CONDITIONS: 27C DB/19.5C WB;

STANDARD FRESH AIR COOLING CONDITIONS: 34C DB/28C WB;

STANDARD RETURN AIR HEATING CONDITION: 21C DB; STANDARD FRESH AIR HEATING CONDITION: 0C WB STANDARD
COOLING WATER ENTERING/LEAVING CONDITIONS: 7C FOR ENTERING WATER; 12C FOR LEAVING WATER;

STANDARD HEATING WATER ENTERING/LEAVING CONDITIONS: 60C FOR ENTERING WATER; 50C FOR LEAVING WATER;
3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW
SELECTION SOFTWARE.
4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.

DDW

Double Skin Air Handling Unit

DDW-V (Vertical)
Model

DDW180V

DDW200V

DDW250V

DDW300V

DDW350V

DDW400V

DDW450V

Nominal Air Flow (m3/h)

18000

20000

25000

30000

35000

40000

45000

300

300

300

300

II

150

150

150

400

400

400

400

III

220

220

220

500

500

500

500

300
109
239

300
121
266

300
154
342

600
178
390

600
205
448

600
238
520

600
266
577
329

External
total
pressure
(Pa)
Nominal
cooling
capacity
(kW)
Nominal
heating
capacity
(kW)

IV
4 Rows (Return air)
4 Rows (Fresh air)
6 Rows (Return air)

135

152

193

222

256

296

6 Rows (Fresh air)

313

347

427

490

556

639

703

4 Rows (Return air)

183

200

250

295

337

391

437

4 Rows (Fresh air)

292

325

393

472

534

604

670

6 Rows (Return air)


6 Rows (Fresh air)

214
336

237
373

297
469

371
544

398
629

450
719

500
802

Type

Coil

Fan

Corrugated aluminum fin mechanically bonded with copper tube

FPI

12

Working pressure (MPa)


Entering/Leaving
water pipe
Condensing water pipe

1.6
R2-1/2

R2-1/2

R3

Filter
Casing
Unit weight
(kg)
Unit
dimension
Packing
dimension

R2-1/2

R2-1/2

Copper pipie diameter (mm)

12.7

Type/Material

High Efficient Centrifugal Multi-blades Fan/Galavnize Steel

Drive type

V-belt

R2-1/2

Fan disdcharge orientation

Top discharge

Power source

380-415V/3N~/50Hz; 380V/3N~/60Hz; 208-230V/3N~/60Hz; 460V/3N~/60Hz

Motor type
Motor

R3
R1-1/4

Motor output power


(kW)
Type/Material
Thickness (mm)
Type
4 Rows

3-Phase Asynchronous Motor,Class F,IP55


I

7.5(11)

11(11)

11(15)

15(15)

II

4.0(4.0)

4.0(4.0)

5.5(5.5)

11(11)

11(15)

15(15)

15(18.5)

III
IV

4.0(5.5)
5.5(5.5)

4.0(5.5)
5.5(7.5)
11(11)
15(15)
15(15)
18.5(18.5)
5.5(5.5)
15(15)
15(15)
18.5(18.5)
18.5(18.5)
7.5(7.5)
Plate/Nylon
G3 Plate Prefilter/Nylon
46
21
25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel
485

538

608

6 Rows

536

595

673

Height (mm)

1978

2048

2108

2715

2875

3195

3355

Length (mm)

2240

2320

2670

1006

1006

1166

1166
2926

Width (mm)

900

900

900

2766

2766

2926

Height (mm)

2165

2235

2295

2732

2892

3212

3372

Width (mm)

1110

1110

1110

1206

1206

1366

1366

Length (mm)

2420

2500

2850

2966

2966

3126

3126

NOTES:
1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.
2) STANDARD RETURN AIR COOLING CONDITIONS: 27C DB/19.5C WB;

STANDARD FRESH AIR COOLING CONDITIONS: 34C DB/28C WB;

STANDARD RETURN AIR HEATING CONDITION: 21C DB; STANDARD FRESH AIR HEATING CONDITION: 0C WB STANDARD
COOLING WATER ENTERING/LEAVING CONDITIONS: 7C FOR ENTERING WATER; 12C FOR LEAVING WATER;

STANDARD HEATING WATER ENTERING/LEAVING CONDITIONS: 60C FOR ENTERING WATER; 50C FOR LEAVING WATER;
3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW
SELECTION SOFTWARE.
4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.

Double Skin Air Handling Unit DDW

External static presure check list


DDW-H
Unit model

DDW020H DDW030H DDW040H DDW050H DDW060H DDW080H DDW100H DDW120H DDW150H DDW180H DDW200H

Nominal air flow (m3/h)

ETP (Pa)

ESP (Pa)

2000

3000

4000

5000

6000

8000

10000

12000

15000

18000

20000

80

80

80

II

150

150

150

150

150

150

150

150

150

150

150

III

220

220

220

220

220

220

220

220

220

220

220

IV

300

300

300

300

300

300

300

300

50

34

39

II

120

104

109

86

104

68

99

77

35

61

85

III

190

174

179

156

174

138

169

147

105

131

155

IV

236

254

218

249

227

185

211

235

DDW-V
Unit model

DDW040V

DDW050V

DDW060V

DDW080V

DDW100V

DDW120V

DDW150V

DDW180V

DDW200V

Norminal air flow (m3/h)

4000

5000

6000

8000

10000

12000

15000

18000

20000

II

150

150

150

150

150

150

150

150

150

III

220

220

220

220

220

220

220

220

220

IV

300

300

300

300

300

300

300

300

300

II

69

86

58

68

85

56

78

61

85

III

139

156

128

138

155

126

148

131

155

IV

219

236

208

218

235

206

228

211

235

ETP (Pa)

ESP (Pa)

DDW-H/V
Unit model
Norminal air flow (m3/h)

ETP (Pa)

ESP (Pa)

DDW250H DDW300H DDW350H DDW400H DDW450H DDW250V DDW300V DDW350V DDW400V DDW450V
25000

30000

35000

40000

45000

25000

30000

35000

40000

45000

300

300

300

300

300

300

300

300

II

150

400

400

400

400

150

400

400

400

400

III

220

500

500

500

500

220

500

500

500

500

IV

300

600

600

600

600

300

600

600

600

600

201

165

188

159

201

165

188

159

II

48

301

265

288

259

48

301

265

288

259

III

118

401

365

388

359

118

401

365

388

359

IV

198

501

465

488

459

198

501

465

488

459

NOTES:
THE DATA IS FOR STANDARD UNIT.ESP VALUE IS BASED ON ETP VALUE.FOR EXAMPLE,THE ESP VALUE IS 50PA WHEN ETP IS 80PA
FOR DDW020H UNIT.

DDW

Double Skin Air Handling Unit

DDW-H (Horizontal)

Hanging holes 4- 15

Manual air vent


Chilled leaving water pipe D
Chilled entering
water pipe D
Condensation water
drain pipe C

DDW-H Horizontal Discharge

Hanging holes 4- 15

Chilled leaving
water pipe D

Chilled entering
water pipe D
Condensation
water drain pipe C

DDW-H Top Discharge

Unit: mm

Dimension

Width

Length Height

Return air

Supply air
B

Chilled
Connection pipe
Condensation
entering
dimension
water drain pipe
water pipe

Hanging holes

MODEL

DDW020H

900

960

600

810

460

298

262 1080 1020 910 150 201 191 85

158 276

R 1-1/2

R 1-1/4

DDW030H

1050

1000

650

960

510

331

289 1230 1170 950 150 207 280 85

158 339

R 1-1/2

R 1-1/4

DDW040H

1080

1100

765

990

590

395

341 1260 1200 1050 150 177 234 85

164 454

R2

R 1-1/4

DDW050H

1250

1060

765

1160

625

395

341 1430 1370 1010 150 216 317 85

164 454

R2

R 1-1/4

DDW060H
DDW080H

1320
1680

1150
1150

839
839

1230
1590

660
660

471
471

404 1500 1440 1100 150 243 324 85


404 1860 1800 1100 150 243 529 85

164 518
164 518

R2
R2

R 1-1/4
R 1-1/4

10

Double Skin Air Handling Unit DDW

DDW-H (Horizontal)

L
N

28.5

Hanging holes 4- 15

40

W
M
K

Manual air vent


Chilled leaving water pipe D

90

50
P

95

Chilled entering water pipe D


Condensation water drain pipe C

DDW-H Horizontal Discharge

L
N

28.5

Hanging holes 4- 15
W
M
K

Chilled leaving water pipe D


S

R
H

40

90

50
P

95

Chilled entering water pipe D


Condensation water drain pipe C

DDW-H Top Discharge

Unit: mm

Dimension

Width

Length Height Return air Supply air


F

Chilled Condensation
Connection pipe entering
water drain
water
dimension
pipe
pipe

Hanging holes

MODEL

DDW100H

1690

1170

970

1600 790

373

404

1870

1810

1120

150

194 102 85

164

645

R2

R 1-1/4

DDW120H

1690

1170

1085

1600 910

373

404

1870

1810

1120

150

194 102 85

164

772

R2

R 1-1/4

DDW150H

1940

1170

1215

1850 1040 373

404

2120

2060

1120

150

194 237 85

172

883

R 2-1/2

R 1-1/4

DDW180H

2120

1310

1275

2030 1100 430

478

2300

2240

1260

150

295 197 85

172

946

R 2-1/2

R 1-1/4

DDW200H
DDW250H

2300
2400

1310
1310

1275
1465

2210 1100 557


2310 1290 557

478
478

2480
2580

2420
2520

1260
1260

165
165

295 135 85
295 107 85

172
178

946 R 2-1/2
1124
R3

R 1-1/4
R 1-1/4

11

DDW

Double Skin Air Handling Unit

DDW-H (Horizontal)

40

A
Manual air vent

90

Chilled leaving water pipe D


Chilled entering
water pipe D

Chilled leaving
water pipe D

Chilled entering
water pipe D

DDW-H Horizontal Discharge

80

125

Condensation water drain pipe C

W
B

Manual air vent

40

90

Chilled entering
water pipe D

Chilled entering
water pipe D
Chilled leaving
water pipe D

Condensation water drain pipe C

80

125

Chilled entering
water pipe D

DDW-H Top Discharge

Unit: mm

Dimension

Width

Length Height Return air


F

Supply
air
A

Connection
pipe
dimension

Hanging holes
S

Condensation
water drain pipe

MODEL

DDW300H

2766

1646

1549

2670 1390 569 569

273

450

352 200

98

R3

R 1-1/4

DDW350H

2766

1646

1709

2670 1550 569 569

284

450

352 203

98

R 2-1/2

R 1-1/4

DDW400H

2926

1806

1869

2830 1710 638 638

266

500

352 213

98

R 2-1/2

R 1-1/4

DDW450H

2926

1806

2029

2830 1870 638 638

266

500

352 213

98

R 2-1/2

R 1-1/4

12

Chilled
entering
water pipe

Double Skin Air Handling Unit DDW

DDW-V (Vertical)

40

Manual air vent

Chilled leaving
water pipe D

Condensation
water drain pipe C

N
L

90

50

Chilled entering
water pipe D

M
W

DDW-V Top Discharge

Unit: mm

Dimension

Width

MODEL
DDW040V
DDW050V
DDW060V
DDW080V
DDW100V
DDW120V

W
980
1140
1210
1320
1390
1530

Length Height
L
650
650
650
810
900
900

H
1346
1403
1460
1673
1933
2010

Return air

Supply air

F
890
1050
1120
1230
1300
1440

A
331
395
395
471
557
557

G
655
687
740
842
1014
1070

B
289
341
341
404
478
478

Connection pipe
dimension

Hanging holes
M
960
1120
1190
1300
1370
1510

N
630
630
630
790
880
880

13

S
71
84
84
98
98
102

E
444
480
480
517
574
639

P
85
85
85
85
85
85

Q
164
164
164
164
164
164

R
518
518
581
708
835
899

Chilled
Condensation
entering
water drain
water
pipe
pipe
D
C
R2
R 1-1/4
R2
R 1-1/4
R2
R 1-1/4
R2
R 1-1/4
R2
R 1-1/4
R2
R 1-1/4

DDW

Double Skin Air Handling Unit

DDW-V (Vertical)
F

20

40

Chilled leaving
water pipe D

Chilled entering water pipe D

50

Condensation water drain pipe C

90

DDW-V Top Discharge

Unit: mm

Dimension

Width

Length

Height

MODEL
DDW150V
DDW180V
DDW200V
DDW250V

W
2090
2240
2320
2670

L
900
900
900
900

H
1746
1978
2048
2108

Return air
F
2000
2150
2230
2580

G
923
1035
1109
1155

Supply air
A
471
430
557
557

B
404
478
478
478

Chilled
Condensation
Connection pipe entering
water drain
dimension
water
pipe
pipe

Hanging holes
M
2070
2220
2300
2650

14

N
880
880
880
880

S
144
100
98
100

E
167
440
156
156

P
85
85
85
85

Q
172
172
172
178

R
756
883
946
997

D
R 2-1/2
R 2-1/2
R 2-1/2
R3

C
R 1-1/4
R 1-1/4
R 1-1/4
R 1-1/4

Double Skin Air Handling Unit DDW

DDW-V (Vertical)

40

20

Chilled leaving
water pipe D

Chilled entering
water pipe D

Chilled leaving
water pipe D

80

Chilled entering
water pipe D

Condensation
water drain pipe C

90

DDW-V Top Discharge

Unit: mm

Dimension Width

Length Height

Return air

Supply air

Hanging holes

Connection
Chilled
Condensation
pipe
entering water water drain
dimension
pipe
pipe
P
D
C

MODEL

DDW300V

2766

1006

2715

2670

1390

569

569

284

450

305

98

R3

R 1-1/4

DDW350V

2766

1006

2875

2670

1550

569

569

273

450

305

98

R 2-1/2

R 1-1/4

DDW400V

2926

1166

3195

2830

1710

638

638

276

500

357

98

R 2-1/2

R 1-1/4

DDW450V

2926

1166

3355

2830

1870

638

638

267

500

357

98

R 2-1/2

R 1-1/4

15

DDW

Double Skin Air Handling Unit

Fan Discharge Type


Horizontal Air Discharge For DDW-H
Horizontal Type

Top Air Discharge For DDW-H


Horizontal Type

Horizontal air discharge of DDW-H fans

Top air discharge for DDW-H fans

Top Air Discharge For DDW-V Vertical


Type

Top air discharge of DDW-V fans

16

Double Skin Air Handling Unit DDW

Special Notes
Facing air discharge, if the chilled water inlet/outlet is on your left, the unit is L connection. Otherwise,

the unit is R connection.


For vertical type unit,refer to the below chart to judge the connection.
Please provide unit model, quantity and operating condition when purchasing. Please contact us if any
other specifications required.

Left connection

Left connection

Entering air

Entering air

Leaving air

Right connection

Right connection

Figure 2

Figure 1

Wiring Diagrams
Motor power input < 11kW

Motor power input 11kW

U1

M
~

V1

W1 U2

V2

M
~

NOTE:
TO CONNECT ELECTRIC CONTROL DEVICES, PLEASE USE OVER-CURRENT, SHORT CIRCUIT AND OVERHEAT
PROTECTORS.

17

W2

DDW

Double Skin Air Handling Unit

Installation
Installing DDW
Important Notice
Installation and maintenance are to be performed only by technicians who are familiar with local rules and
regulations, and experienced with this type of equipment.
Make sure that the rated voltage of the power supply conforms to the voltage stated on the unit nameplate.
Cut off all power supplies before mounting or maintaining the unit.
Electric connections must conform to local laws and regulations.
The voltage should fluctuate within the range of 10% of the rated voltage.
The unit must be well earthed to prevent insulation failures.
All the wires must be securely connected.
The design of water pipes and ducts must conform to the Specifications of Heating, Ventilation and Air
Conditioning (GBJ19-87).
DDW Mounting Location
Make sure it is convenient to connect wires and pipes in the selected mounting location. The minimum space
reserved around DDW horizontal units is shown in Figure 1; DDW vertical units are shown in Figure 2.
Unit: mm
50
0

50
0

50

00
10

10
00

Figure 1

Figure 2

18

0
50

Double Skin Air Handling Unit DDW

Suspending Installation
During the installation, please handle the unit or packing case with care, to avoid damage to any part. Before
leaving the factory, the unit or its packing case already has forklift handling holes or hoisting holes. During the
hoisting, the lifting poles should be strong enough to bear the unit weight. Please handle the DDW unit as shown
in Figure 3.

Figure 3

Storage
When a unit is placed protect it from dirt, rain, snow and even animals. Be sure not to damage the protective film
on its surface.

Base Setup
Adjust the base levelness
The base, if not put on a level surface, may result in water leakage or break the dynamic balance of the fan due to
poor drainage of condensing water or cause the bearing to fail or vibrate.
The base height should match the U-shaped pipe blend. The drain pipe should be connected with the Ushaped
water seal, as shown in Figure 4.
Need suitable water seal when installing in order to condensation water drain smoothly.

Drain pipe

P = Negative pressure value (Pa) inside the unit


H P/10+20(mm)

NOT MORE THAN 1/2H


Drain bend

Figure 4
19

DDW

Double Skin Air Handling Unit

Servicing And Maintenance


Notices
Responsibilities And Obligations
This product comes to you with the DAIKIN service warranty. Only DAIKIN technicians or experienced technicians
authorized by DAIKIN are allowed to install, test or maintain these products.

Using The Unit


After installing the piping system, please first wash the pipes. To do so, be sure to shut off the valve connected to
the unit, to prevent unwanted things in the pipes from entering the coils or blocking the loop.
After the installation, please check there is anything unwanted inside the fan. Turn the blades by hand. If no
unusual noise is heard, turn on the fan, to see if it is running properly.
Before turning on the water flow, please open the exhaust valve to let the air out of the pipe till water flows out from
the pipe.
When the unit stops running, fill the coil with water or otherwise keep the pipe from erosion.
When the environment temperature falls below 0C in the winter, drain the pipe to prevent it from freezing.
Clean the coils at regular intervals, to remove the dust from the coils. Clean the scale inside the coils every 2 or 3
years. If possible, use soft water to supply hot/cold water to the coils.
Check the unit filter for dust regularly; if possible, please use a pressure difference detector. Once the resistance
reaches the limit, wash or replace the filter media in time.
After the unit runs for a week, please readjust the V-belt. Afterwards, check the belt every three months.

Servicing And Maintenance


A sound maintenance schedule helps reduce operational failures.
A dirty filter may worsen the performance and air flow of the unit. Thus, replace or wash the filter in time. Be sure
to check the filter every month to see if it is clean enough.
Wash the coils with compressed air or water. Brush the coil surface gently with a soft brush or use a vacuum
cleaner to clean the dust.
Do the following on a regular basis:
Clean up the fans every 6 months, to keep them in good balance.
Check and clean the water coils. Check the drain pipe in case dust or unwanted things block the pipes.
Check if the bearing comes loose. If so, fix the fastening screw tightly to the bearing.
Clean the dirt in the coils at regular intervals.
Check that the side front of the fan V-belt is flush with the side front of the motor V-belt, to make sure the pulleys
are placed on a flat plane. Usually, check using the four-point method (see Figure 5).
Use V-belts of the same brand and model. Never mix old V-belts with new ones. Make sure that the V-belts
match the pulley grooves.
Use a tensiometer to check the V-belts, and tighten them properly (see Figure 6).

20

Double Skin Air Handling Unit DDW

Check and adjust the levelness of the V-belt using the four-point method, as shown in Figure 5.
Ruler
A

Figure 5

Check the tightness of the V-belt, as shown in Figure 6.


C
sp ente
ac r to
ing c
e

nte

The belt tension indicator acts on the


midpoint of center-to-center spacing

Torture 16mm
every meter

Figure 6

21

DDW

Double Skin Air Handling Unit

Common Failures
DDW
Common
Failures

Locations

1. Blower

Possible Causes

Solutions

Blower out off center

Contact the seller

Loose bearings due to large gap

Contact the seller

Blower is loose

Contact the seller

Loose connection between bearings

Contact the seller

Blower is damaged

Contact the seller

The fan fastening screw is loose

Fasten the screw

There are unwanted things inside fans.

Remove unwanted things

Belt pulley is not fastened on the axis.


Fasten the V-shaped belt
V-shaped belt is loose. Adjust after it runs for 48 hours for the
Adjust the V-shaped belt
first time.
V-shaped belt is too tight
Adjust the V-shaped belt
2. Drive

The V-shaped belt model is not right


V belts are of different length

Replace the V-shaped belt


Replace V-shaped belts with those of the
same length

The V-shaped belt pulley of the fan does not align with that of
Align the belt pulleys
the motor
V-shaped belt is damaged
Replace the V-shaped belt

3. Bearing

Abnormal
sound
4. Fan house

The screw fixing the motor to the motor base is loose

Fasten the screw

Bearing failure

Replace bearings

Lack of lubricant oil

Add lubricant oil

The bearing housing is loose

Fasten the bearing housing

The bearing is not mounted flush

Re-mount the bearing

There are unwanted things inside bearings

Remove unwanted things

Bearings are damaged

Replace bearings

Bearings are rusty

De-rust or replace bearings

There are unwanted things inside houses

Remove the unwanted things

House is loose

Contact the seller

Air intake house is damaged

Contact the seller

Incoming line is loose

Fasten the incoming line

5. Electric appliances Motor gives AC hum

6. Axis

7. Air speed is too high

Contact the seller.

Phase lack

Supply 3-phase power

Bent or distorted

Replace axis

Balance weight is loose

Fasten the balance weight

Axis is loose

Fasten axis

Duct is too small

Re-design the duct


Change the V-shaped belt pulley to reduce
Static pressure has not reached the set static pressure value
the fan speed
The duct is too small
Re-design the duct

8. Periodical vibration System is unstable

Adjust the system

Duct vibrates as the fan pulsates

Adjust the fan speed

9. Noise caused by hispeed wind passing Duct leaks


the aperture & holes

Seal it with glue

Duct turns too sharply

Re-design the duct

Duct expands sharply


10. When blocked,
the high-speed air Duct shrinks sharply
rattles or howls
Air speed is too high inside the duct

Re-design the duct


Re-design the duct
Re-design the duct

Damping connector is too tight

Re-adjust the damping connector

22

Double Skin Air Handling Unit DDW

Common
failures

Locations

Possible causes

Solutions

Blower is mounted incorrectly

Contact the seller

Fan rotates in the opposite direction

Regulate the power phase sequence

Actual resistance in the duct exceeds set resistance.

Re-design the system

Duct is poorly sealed

Seal with glue

Fireproof valve is shut off

Shut on the fireproof valve

3. Filter

Too dirty or even blocked

Clean or replace filter

The fan is 4. Coil


functioning
but the air 5. Blocked air supply
supply is
insufficient 6. Fan air inlet is
blocked

Too dirty or even blocked

Clean coil

1. Fan

2. Duct system

The air inlet and the air outlet are not properly isolated. Thus,
Add air deflector
the air runs directly to the air inlet through the separator
Elbow at the return air inlet and fan outlet are too close to the
Move the fan
unit wallboard
The fan outlet is blocked

Remove the obstructions

A length of straight tube is mounted at the fan outlet during


7. No collimator tube at fan testing. Without straight tube, the fan performance might
the fan outlet
be worsened. Thus, the fan may run faster to offset the
resistance. (Check the fan speed)
8. Therere unwanted The fan outlet is blocked
things inside fan
There is an elbow at the fan outlet
system

The fan is
functioning 1. System
but the air
supply is
too large
2. Duct

Mount collimator tube


Remove the obstructions
Re-design duct

Improper duct size

Remove the obstructions

The access door is open

Close the access door

The system is not well balanced and the actual resistance is


lower than the set resistance

Re-design the system

No air valve or air valve blade

Mount wind valve or wind valve blower

Filter falls off

Re-mount the filter

Return duct leaks

Seal it with glue

23

Warning

Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in
a particular country. Prior to purchase, please therefore confirm with your local authorized importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable
for use, in the region where the product will be used. This statement does not purport to exclude,
restrict or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the Users Manual carefully before using this product. The Users Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

The air conditioners manufactured


by Daikin Industries have received
ISO 9001 series certification for
quality assurance.

The airconditioning factories of


Daikin Industries have received
environmental management system
standard ISO 14001 certification.

Certificate Number. 9601019

Certificate Number. EMS80362

Cautions on product corrosion


1. The units should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the
unit close to the sea shore, contact your local distributor.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
All rights reserved
Printed with soy ink.


Literature No.: ED-DDW-201401A
Supersedes: ED-DDW-201310A

You might also like